1. HP LP BYPASS SYSTEM
Presented by
A S GUPTA BE,MBA,BOE,EA,IPMA-D
Supdt(O)
2. HP & LP BYPASS SYSTEM
Purpose
Primarily meant to enable Boiler operation independent of
the turbine
Opening o HPBP & LPBP Valves ensures minimum steam
flow through superheater & reheater tubes during start-ups,
low load operation & sudden unloading of unit
Utilized or building up of steam parameters quickly before
starting of the turbine online
Avoiding the boiler trip on Reheat protection
No steam flow through Boiler steam tubes will lead to
starvation & thereby overheating and lead to premature
failure of tubes
4. HP & LP BYPASS SYSTEM
Provides the alternative path for boiler operation
HP Bypass dumps steam into CRH inlet of reheater
LP Bypass bypasses IPT & LPT and dumps steam into
condenser
The capacity of HPLP bypass is 60% of full load turbine
steam flow
Reduces chances of opening of Boiler safety valves at
raised steam pressures
5. REHEAT PROTECTION
RH protection (delay=10 sec) will act if
TURBINE HP V/V & HPBP CLOSED [ either turbine
HP stop v/v or HP CV in both HP line closed ] & [
both HP BP <2%] OR
TURBINE IP V/V & LP BP closed [ Either IP stop
v/v or IP CV v/v in both IP line closed ] & [ Either LP
BP stop v/v or LP BP C/V in both LP line is closed]
OR
Generator ckt bkr open & [both HP BP closed OR
both LP BP closed
6. HP BYPASS SYSTEM
Benefits
Boiler start-up without starving superheater & reheater
tubes, till the opening of turbine steam control valves
Raising the steam parameters (press& temp) quickly, to a
level acceptable for the starting of the turbine at an optimum
rate
Continued Boiler operation while tripping of turbine provided
boiler load <60%
Avoiding Reheat protection
Conservation of DM water, during start-up or Shut down (by
dumping steam into condenser instead of atmosphere)
Maintain sufficient steam pressure in the CRH line for
auxiliary steam supply purpose during low load condition
8. HP BYPASS SYSTEM
HP Bypass consists of:
Bypass Valves BP1 & BP2
Spray water pressure controller BD valve
Spray water temp. controller BPE1, BPE2 valves
2 nos Hydraulic Oil Supply units
MS press. ahead of HPT is maintained by proper
adjustment of BP valves
Steam temp in CRH line controlled by BPE valves
9. OIL SUPPLY UNIT
OSU provides Energy for operation of steam valves
Consists of Filters, Axial piston pump, Relief valve, NRV, Oil
Accumulator, Press reducing valve, Ball Cocks
Axial Pump maintains Contant oil press. in the accumulator
by automatic operation
Gas filled bladder to retain oil press in accumulator or fairly
long duration
A safety valve protects the system from excessive pressure
11. OIL SUPPLY UNIT INTERLOCKS
Pump Auto off Oil Press high >160ksc
Pump Auto on Oil Press Low <120ksc
Pump Auto off Oil Temp high >70 DegC
Pump Auto off Oil Level low <18 Lit
Alarm Oil Press too high >170ksc
Alarm Oil Press too Low <90ksc
13. HP BP PROTECTION
BP Valve Priority Close Conditions
Condenser Vacuum Low (<-0.6 ksc)
Bypass Downstream Temp very high (>380 degC)
Loss of Oil Pressure in Safety System Accumulator
<100 ksc (stage-1)
Under these conditions
Steam Press Controller Switches to Manual from
Auto
spray water valve will close
This protection will override the Fast opening signal
& open push button operation
14. HP BP PROTECTION
HP Bypass Fast Opening Conditions
Generator Circuit Breaker Opening & Boiler on
& no priority close
Turbine Trip & Boiler on & no priority close
Turbine Load Shedding Relay Operation
HP BP Pressure Controller Deviation > 8 ksc
Pressing the Fast Opening Button
15. HP BP PROTECTION
BP Valve Auto Blocking Conditions
Bypass valve priority close command
BP position transmitter failed
OSU-1 & 2 Oil Pressure <90 ksc
Main steam Pressure transmitter failed
16. HP BP INTERLOCKS
BPE Valve Conditions
Steam Bypass Valves BP1 or BP2<2 % Auto Close
Command to ensure positive shut off
Steam Bypass Valves BP1 or BP2<2 % Spray Water
Pressure Control Valve (BD Valve) close
Steam Bypass Valves BP1 or BP2>2 % Spray Water
System (BPE1, BPE2, BD Valve) will switch over to
Auto
17. HP BP INTERLOCKS
BPE Valve Auto Blocking Conditions
Bypass Downstream Temp very high (>380 degC)
BP auto command blocking
BPE valve position transmitter failed
BPE Temp transmitter deviation high
Therefore, it is necessary to make proper set
values for Spray Water Header Pressure &
HP BP downstream temperature before
operating the Steam Bypass Valves
18. LP BYPASS
Functions of LP Bypass System are:
Maintaining minimum Steam Flow through Re-heater
Maintaining desired Steam Pressure in the Re-heater
Providing an alternative path for dumping the steam (not
accepted by the IP & LP Turbines) into the condenser
LP BP System comprises of :
Steam Pressure Control Loop
Valve Position Control Loop
Automatic Control Interface (ACI)
Condenser Temperature Protection
Tracking Unit
29. LP BYPASS PROTECTIONS
Close LP Bypass under following conditions:
Condenser Vacuum Low (<-0.6 ksc)
Spray Water Pressure Low (<8 ksc)
Condenser Wall Temperature High ( > 90 DegC)
LPBP Down Steam Pressure High (>19 ksc)
Spray Water valve open command at Steam pressure before
bypass valve >6.8 ksc