Automatic Transfer Breaker
Automatic Transfer Switch
Air Circuit Breaker Type
Applied Standard & code/Features/Interlock condition of switch system
Appearance and Operation Method
Standard Rating
Installation Method
Protection equipment of Trip Relay
Trip Relay Curve
Special Functions of ATB
-CTTS(Closed Transition Transfer Switch)
-ATB Transfer & Retransfer Operation with Time Delay
-Operation Method for By-Pass system Built-in ATB
-Application of Interlocking
Control Circuit Diagram
Dimension of Appearance
Contents
"ATB (Automatic Transfer Breaker) "
of HANCESS Co., Ltd.
ATB has been developed with mechanical and
electrical interlocking system for stable electric power
supply to the critical demands, such as hospital,
communication & broadcasting center, computer room,
power plant, main facilities for factories & buildings
and others eliminating the problems of conventional
ATS.
The compact and light weight designed ATB with high speed
switching system and excellent breaking performance
detecting over current and ground fault current protects
the electric power system from the fault and abnormal
current.
HANCESS ATB Automatic Transfer Breaker AC 600V / Up to 6300A
4
[MainFeatures]
• Design in according to well-known International Standard and Code
• Electric Motor Charging System
• Both sources OFF position available, Neutral Position
• Draw-out type, economical fixed type, By-pass built-in type are available
• Combined Circuit Breaker as both sources trip device(Uninterrupted By-Pass system)
• Compact & Ligh weight design, high installation efficiency inside cubicle accordingly
• Digital OCR ( Over Current Protection Relay )
- Easy sense for load capacity, over current & earth fault current and ab-normal current
- Pre-alarm function
• AC/DC combined operating voltage
• Automatic switching time setting available employing the suitable controller
Features
Applied Standard & Code
Interlock Condition of Switch System
Open
Open
* Close
* Option at CTTS Function
Close Open
Open
* Close
Close
- IEC-60947-6-1
- EN-60947-6-1
- BS 4652 part 1
- VDE 0660
- ANS 1(27.13)
- KSC 8325
- JIS 160
- GB/T 14048.11
HANCESS ATB
5
[AppearanceandOperationMethod]
Appearance & Operation Method
Caution)
Incaseofmanualoperation,ifonesource
putinon,theATBmustbetrippedbefore
inputtheothersourcetoavoidtheelectrical
accident&clash.
Ex) A Source --> Transfer B Source
- A(On) --> A(Off) --> B(On)
B Source --> Transfer A Source
- B(On) --> B(Off) --> A(On)
Manual Operation Method
•Wheninputchargingcompletely,thechargingdisplayshows“CHARGE”
•TheInputandtheTripbuttonisnotworkingsimultaneouslybecauseof
mechanicalinterlocksystem.
•TheconditionofmaincontactofATB,CloseorOpen,isrepresentedon
StateDisplay.
•InordertokeeptherightpositionofHandles,thebothsourcesshouldbe
chargedcompletely.
Afterinputchargingspringusinghandle,ifinputbutton(On)push,
itthrowsin.Iftripbutton(Off)push,ittrips.
Motor charging operation
•Inputspringchargeautomaticallybyelectricmotor.Aftercharging,
chargingdisplayshows“CHRAGE”
•WhenInputbuttonpush(On)manually,itthrowsinshowing
“DISCHARGE”onChargingDisplayand“Close”onStateDisplay.
•Atthistime,Inputspringchargeautomaticallybyelectricmotor.
Aftercharging,chargingdisplayshows“CHRAGE”
•WhenTripbuttonpush(Off)manually,ittripsshowing“OPEN”onState
Display.
•Atthistime,thespringchargeautomaticallybyelectricmotor.
Aftercharging,chargingdisplayshows“CHRAGE”
•TheBothsourcesarenotworkingsimultaneouslybecauseofmechanical
interlocksystem.
•WhenbothsourcesOPENposition,thebothsourcesshouldbeshutted
off.
Air Circuit Break Type Automatic Transfer Switch
Items ATB-06 ATB-32
630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300Rated Current (A)
AC 1000VInsulation Level (V)
AC 690VRated Voltage (V)
50/60HzFrequency (Hz)
3P/4PNumber of Poles
OCR Setting Steps
Endurance
Rated Breaking Current
(KA, Sym)[lcs]
Rated Input Current
(KA, peak)[1cm]
Rated Impulse Voltage [Uimp]
Max. Electricity Breaking time
[mSec]
Making Time
[mSec]
Time of Motor Charging
[Max. Sec]
Weight (kg, 3 pole)
Fixed Type
Drawable
Type
Fixed Type
Drawable
Type
Weight (kg, 4 pole)
Dimensions (4pole)
Mechanical
Electrical
AK58AK58AK56AK56AK56AK56
AK781AK781AK341AK341AK341AK341
VK8
0504
0806
10 sec
100 105 110 120 130 140 150 160 170 200 220
110 115 120 130 140 150 160 170 180 220 240
135 142 150 162 176 190 203 216 230 270 300
150 155 162 176 190 203 216 230 243 - -
019018017036055035054W
055H
095065005D
6
[StandardRating]
ATB-08 ATB-10 ATB-12 ATB-16 ATB-20 ATB-25 ATB-40 ATB-50 ATB-63
1.0 - 0.9 - 0.8 - 0.7 -0.6 (5steps)
10,000 times
3,000 times
HANCESS ATB Automatic Transfer Breaker AC 600V / Up to 6300A
Fixed Type (630-6300A)
Manual Change Type
OCR / GR
ATB
Electric Powered Charge Type
Shutter
Position S/W
Arc Barrier
Digital Type
LED Type
AUX S/W (5a+5a)
Keying Circuit
Keying Inter Lock
Key Lock
Special Function of ATB
UVT / Voltage Trip Condenser Trip
Drawable Type (630-4000A)1. Mounting
Method
2. Accessoried for
Drawable Type
3. Method of Input
Operation
4. Protection Tools
5. Electrical Trip Tools
6. Accessories
7. Front Panel Accessories
Air Circuit Break Type Automatic Transfer Switch
HANCESS ATB
7
ATB-06 ATB-32ATB-08 ATB-10 ATB-12 ATB-16 ATB-20 ATB-25 ATB-40 ATB-50 ATB-63
[Rating][Rating]
8
[InstallationMethod]
Drawable type ATB
Fixed type ATB
Circuitbreakerisfixedindistributingboard.
Maincircuitandcontrolcircuitareisolatedanddoorof
wiringroomcanbeclosed.
ATBisdrewfromdraw-outframecompletely.
Maincircuitisisolatedandcontrolcircuitiscontacted.
Testcanbeperformedbyclosingthedoorofwiringroom.
Maincircuitandcontrolcircuitarecontacted.
Theyareusedatnormalstate.
Itiscomposedofcircuitbreakeranddraw-outframe.onlydrawofcircuitbreakerispossible.Draw-out cradleisfixedatdistributingboard.
Inthistype,therearethreepositionssuchas'Connected','Test',and'Isolated'.Itispossibletoclosepaneldooratisolatedposition.
Draw-outPositionIsolatedPosition
ConnectedPosition TestPosition
HANCESS ATB Automatic Transfer Breaker AC 600V / Up to 6300A
HANCESS ATB
9
[ProtectionDeviceforTripRelay]
Appearance
Setting rated current (0.7-0.8-0.9-0.95-1.0) x In Max
(0.8-0.85-0.9-0.95-1.0) x In
If setting value is exceeded, ‘LTD’ ‘LED’ turns On.
15-30-60-120-240-480 sec
(2-3-4-6-8-10) x In
If setting value is exceeded, ‘STD’ ‘LED’ turns On.
0.05-0.1-0.2-0.3-0.4-0.5 sec
(4-6-8-10-13-16) x In
If setting value is exceeded, ‘STD’ ‘LED’ turns On.
(0.7-0.8-0.9-0.95-1.0) x lc.
If setting value is exceeded, ‘PTA’ ‘LED’ turns On.
15-30-60-120-240-480 sec
(0.1-0.2-0.3-0.4-0.5-0.6) x In
If max setting value is exceeded, ‘GFT’ ‘LED’ turns On.
0.1-0.3-0.8-1.5-3.0 sec
Setting long-time delay tripping current
Setting long-time delay tripping time
Setting short-time delay tripping time
Setting instantaneous-time delay tripping current
Setting pre-alarm current
Setting pre-alarm time
Setting ground fault current
Setting ground fault time
Setting short-time delay tripping current
LCD Display : pre fault alarm setting Value 90%, over current trip indication,
ground fault trip indication, phase balance [(Im-lav)/lav]*100lav=[la+lb+lc]/3, Im=maximum
Knob Name Mode Set-up Procedure
Air Circuit Break Type Automatic Transfer Switch
ATB 2007F
Rated Current of CT Primary Current (I ct)
Ground Fault Setting range (GFT)
Pre - Trip Alarm range (PAT)
Long - Time Delay Setting range (LTD)
Short - Time Delay Setting range (STD)
Instantaneous - Time Delay Setting range (INST)
10
[TripRelayCurve]
HANCESS ATB Automatic Transfer Breaker AC 600V / Up to 6300A
CTTS (Closed Transition Transfer Switch) of ATB
Specifications
HANCESS ATB
11
[SpecialFunctionofATB]
Generally,theCircuitBreakersshouldbedesignedandinstalledatthefrontandrearofATSinordertoprotecttheelectricequipment
fromfaultcurrent,suchasgroundfault,shortcircuitandsurge.
Whenfaultandabnormalcurrentoccurs,ATBmustdesignedandproducedinordertostandatleast20timesofratedcurrentand
3cyclesbeforetrip.
Fg1)whenswitchfromNorm.sourcetoEmergencysource,
attheClosedposition,transfertoemergencesource.
(TestorElectricpowertransferring)
Fg2)whenswitchfromEmergencysourcetoNorm.source,
attheClosedposition,transfertoNorm.source.
Fg3)whenswitchfromNorm.sourcetoEmergencysource,
attheOpenposition,transfertoEmergencesource.
(Norm.sourceOff)
No. of Phase & Wires
Rated voltage
Rated frequency
Rated current
Phase angle Difference at Switch
Frequency difference at switch
Voltage at switch
instantaneous after installation related time
Note
Afterinstallationandwiringconnectioncompletely,thebothsources’phaseordermustbeconfirmedandtheovercurrent
mustbeconsideredduetothephaseangledifferenceandvoltagedifferencewhichiscauseofovercurrent.
Single Phase, Single Phase three wires, 3Phase three-wires / four wires
110V / 220V / 380V / 440V / 480V
50Hz / 60Hz
630A - 6300A
Within 10 Phase Degree
within 0.2Hz
Voltage difference is within 5% with normal source
within 50mSec
Fg4)whenswitchfromEmergencysourcetoNorm.source,
attheClosedposition,transfertoNorm.source.
(TransferringtoNorm.sourcewithoutanyInterrupt)
Item Specifications
Air Circuit Break Type Automatic Transfer Switch
[ Note : If Permitted by the Utility Company ]
Operation Method for By-Pass System Built-in ATB
ATB Transfer & Retransfer Operation with Time Delay
12
[SpecialFunctionofATB]
LOADisaccessedtoASourceand
operatedbyATB.
InputByPassATBtothesame
powersource(ASource)ofATB.
(Itissafebecausemechanical
andelectricalinterlockisbuilt-in.)
1.TransferATBtooperationposition
(Sameasdrawmotion)
2.Whentransferfromtestpositionto
operationposition.
3.ATBandByPassATB shouldbe
interlocked
Normal operation
1)
2)
3)
A,BSourceMaincircuitisaccessed
andloadsideisisolated.
Thereforeelectricaloperation
testissafety.
Draw of ATB (Test position)
Undraw of ATB
DrawoutMainATB.
Allmaincircuitsareisolated.
Inspect DrewoutATBaftertransfer
ByPassATB.
Draw of ATB
(isolated, drawable position)
ATB check & Test
IncaseofATBtestoruninterruptedfacilities(Broadcastingstation,hospital,computerroom,powerplantandothers). ByPassIsolationswitchhasallcharacteristicsthat
ATBhastopreventpowerfailureofloadingsidethatisoccurredincaseoftestormaintenanceofgeneralATSaddoneByPassIsolationSwitchtoATSandoperateitasfollowing
figure.Itistheswitchthattestorrepaircanbeperformedwithoutdifficultiestoloadingside.
ATB
ATB
ATB
ATB
ATB
ATB
HANCESS ATB Automatic Transfer Breaker AC 600V / Up to 6300A
LOADisaccessedtoBSourceand
operatedbyATB.
By-pass Isolation Switch
function of ATB
Applications of Interlocking
HANCESS ATB
13
ATB 1 + ACB 1
ATB 2 SetACB 5 Set
Air Circuit Break Type Automatic Transfer Switch
ACB1 ACB2 ACB3
ACB 3 Set
ACB1 ACB2
ACB3
ACB4 ACB5
ACB
ACB 2 Set
ACB1 ACB2
ATB 1 Set
ATB
ATB ATB
ATB
14
[ControlCircuitDiagram]
HANCESS ATB Automatic Transfer Breaker AC 600V / Up to 6300A
01.PP,PN:OCRCONTROLSOURCEDC110V
02.M+,M-:MOTORSOURCEDC110V
03.APC1,APC2:“A”SIDECLOSING
04.APT,ANT:“A”SIDETRIP
05.BPC1,BPC2:“B”SIDECLOSING
06.BPT,BNT:“B”SIDETRIP
07.A11~A22:“A”SIDEAUXILIARYCONTACTOR
08.B11~B22:“B”SIDEAUXILIARYCONTACTOR
09.A/L:PRETRIPALARM
10.51:OVERCURRENTFAULT
11.51G:GROUNDOVERCURRENTFAULT
12.COM:UVRCOM
13.AUVR,BUVR:UNDERVOLTAGEFAULT
14.C1,C2:OCRTRIP
NOTE
DC 110V OCR CONTROL
A Side Closing Coil
B Side Closing Coil
A Side Trip Coil
B Side Trip Coil
ACC
BCC
ATC
BTC
Air Circuit Break Type Automatic Transfer Switch
Auto Transfer Breaker
"A"SOURCE
"A" OFF
MANU.
LCD-H3
AUTO "A" POWER
"A" ON
"A" TIMER
ON
CONTROLLER
"B" POWER"B" TIMER
"B" ON
ON
"B" OFF
"B"SOURCE
MANUAL
AUTO
15
(Unit:mm)
FixedType/630-4000A3P
Front View Side View Rear View
130 270
75
t
500
100
Fixed Hole
D
15 15
550
610
60
60
C
A B
15 15
Fixed
Hole
12
JKLM
E F G H
A
LOAD
B
Type A B C D E F
Type G H J K L M
ATB - 16
ATB - 20
ATB - 25
ATB - 32
ATB - 40
ATB - 16
ATB - 20
ATB - 25
ATB - 32
ATB - 40
16
[Dimension]
225
225
225
225
225
225
225
225
225
305
450
450
450
450
530
70
70
70
90
90
125
105
105
95
105
100
120
120
130
160
100
120
120
130
160
125
105
105
95
105
162.5
162.5
162.5
162.5
159.5
120
120
120
120
123.5
120
120
120
120
123.5
134.8
134.8
132.5
132.5
132.5
(630-1200 :12t / 1600-2000 :15t / 2500-3000 :20t / 3200-6300 :25t)
HANCESS ATB Automatic Transfer Breaker AC 600V / Up to 6300A
(Unit:mm)
(630-1200 :12t / 1600-2000 :15t / 2500-3000 :20t / 3200-6300 :25t)
FixedType/630-4000A4P
15 15
550
C
A B
15 15
Fixed
Hole
12
130 270
75
t
500
100
Fixed Hole
D
Type A B C D E F
Type G,H J K L M N
ATB - 16
ATB - 20
ATB - 25
ATB - 32
ATB - 40
ATB - 16
ATB - 20
ATB - 25
ATB - 32
ATB - 40
JKLM
E F G H N
N T S R
A
LOAD
B
Front View Side View Rear View
HANCESS ATB
17
225
225
225
225
304
225
305
305
325
385
450
530
530
550
689
70
70
70
70
90
75
85
80
80
104
100
120
120
130
160
100
120
120
130
160
162.5
162.5
162.5
159.5
159.5
120
120
120
120
123.5
134.8
134.8
132.5
132.5
132.8
120
120
120
120
123.5
75
85
85
85
104
Air Circuit Break Type Automatic Transfer Switch
FixedType/630-4000A3P
3P Rear View
JKLM
E F G GF F E
A
LOAD
B
4P Rear View
JKLM
E N G GF GF F E
A
LOAD
B
C
C
A B
1515
550
15 15
Fixed
Hole
12
Front View
130 270
75
t
500
100
Fixed Hole
D
Side View
5000A BUS BAR
23 23
35 35
35
6300A BUS BAR
15 15
30 30
30 30
30 30
70
Type G J K L M N
ATB - 50 3P
ATB - 63 3P
ATB - 50 4P
ATB - 63 4P
Type A B C D E F
ATB - 50 3P
ATB - 63 3P
ATB - 50 4P
ATB - 63 4P
18
[Dimension]
(Unit:mm)
(630-1200 :12t / 1600-2000 :15t / 2500-3000 :20t / 3200-6300 :25t)
30
40
30
40
162.5
159
162.5
159
123.5
123.5
123.5
123.5
123.5
123.5
123.5
123.5
132.5
132.5
132.5
132.5
150
-
150
150
315
465
387
545
315
525
387
625
630
990
774
1170
90
90
90
90
60
95
42
105
150
280
150
280
HANCESS ATB Automatic Transfer Breaker AC 600V / Up to 6300A
DrawableType/1600-4000A
HANCESS ATB
19
Bottom View
650 D
190120120
E
Side View
C
A B
610
610
60
60
Front View
<ATB-06~16> <ATB-20,25,32>
<ATB-40> <ATB-50>
30
30
20
20
55
120
35
20
150
25
20
80
Type
ATB - 06 ~ 16
ATB - 20
ATB - 25
ATB - 32
ATB - 40
A B C D E
A
B
650
4- 13
ATB
No. of Pole
3P
4P
3P
4P
3P
3P
4P
4P
Rated Current A B
Size
600 - 1600A 290 427
290 427
370 427
290 444
390 444
370
470 444
444
2000A
2500A
3200A
4000A
4000A
268
268
268
268
348
268
348
348
370
428
536
616
616
638
776
70
70
70
70
70
12 / 15
15
20
20
20
(Unit:mm)
Air Circuit Break Type Automatic Transfer Switch
(630-1200 :12t / 1600-2000 :15t / 2500-3000 :20t / 3200-6300 :25t)
Head Office
144, Achasan-ro, Seongdong-gu, Seoul, Korea
TEL : 82 - 2 - 462 - 3731 ~ 3
FAX : 82 - 2 - 463 - 8350
Plant
48, Daram-ro 57beon-gil, Docheock-Myeon, Gwangju-si,
Gyeonggi-Do, Korea
TEL : 82 - 31 - 762 - 7500
FAX : 82 - 31 - 764 - 0302
Agent
note) The specifications are subject to change without notice in order to improve the performance and quality.
WWW.HANCESS.COM
Transter & Bypass Status
Normal Source Emergency Source
Source
Available
Main MainByPass ByPass
LOAD
Lamp Test
Hanpro3000
ATBCTTS&ByPassControllerBasedonDSP
Vietnam Represented Office:
Hancess Vietnam - Quanpham Co.,ltd
285 Dien Bien Phu, Ward 07 -district 03,
Ho Chi Minh City - Vietnam
Tel: +84 39304952 - 39302400
Fax: +84 39304953
E-mail: info@quanpham.vn
Website: www.quanpham.vn

HANCESS ATB CATALOGUE

  • 1.
  • 2.
    Automatic Transfer Switch AirCircuit Breaker Type Applied Standard & code/Features/Interlock condition of switch system Appearance and Operation Method Standard Rating Installation Method Protection equipment of Trip Relay Trip Relay Curve Special Functions of ATB -CTTS(Closed Transition Transfer Switch) -ATB Transfer & Retransfer Operation with Time Delay -Operation Method for By-Pass system Built-in ATB -Application of Interlocking Control Circuit Diagram Dimension of Appearance Contents
  • 3.
    "ATB (Automatic TransferBreaker) " of HANCESS Co., Ltd. ATB has been developed with mechanical and electrical interlocking system for stable electric power supply to the critical demands, such as hospital, communication & broadcasting center, computer room, power plant, main facilities for factories & buildings and others eliminating the problems of conventional ATS. The compact and light weight designed ATB with high speed switching system and excellent breaking performance detecting over current and ground fault current protects the electric power system from the fault and abnormal current.
  • 4.
    HANCESS ATB AutomaticTransfer Breaker AC 600V / Up to 6300A 4 [MainFeatures] • Design in according to well-known International Standard and Code • Electric Motor Charging System • Both sources OFF position available, Neutral Position • Draw-out type, economical fixed type, By-pass built-in type are available • Combined Circuit Breaker as both sources trip device(Uninterrupted By-Pass system) • Compact & Ligh weight design, high installation efficiency inside cubicle accordingly • Digital OCR ( Over Current Protection Relay ) - Easy sense for load capacity, over current & earth fault current and ab-normal current - Pre-alarm function • AC/DC combined operating voltage • Automatic switching time setting available employing the suitable controller Features Applied Standard & Code Interlock Condition of Switch System Open Open * Close * Option at CTTS Function Close Open Open * Close Close - IEC-60947-6-1 - EN-60947-6-1 - BS 4652 part 1 - VDE 0660 - ANS 1(27.13) - KSC 8325 - JIS 160 - GB/T 14048.11
  • 5.
    HANCESS ATB 5 [AppearanceandOperationMethod] Appearance &Operation Method Caution) Incaseofmanualoperation,ifonesource putinon,theATBmustbetrippedbefore inputtheothersourcetoavoidtheelectrical accident&clash. Ex) A Source --> Transfer B Source - A(On) --> A(Off) --> B(On) B Source --> Transfer A Source - B(On) --> B(Off) --> A(On) Manual Operation Method •Wheninputchargingcompletely,thechargingdisplayshows“CHARGE” •TheInputandtheTripbuttonisnotworkingsimultaneouslybecauseof mechanicalinterlocksystem. •TheconditionofmaincontactofATB,CloseorOpen,isrepresentedon StateDisplay. •InordertokeeptherightpositionofHandles,thebothsourcesshouldbe chargedcompletely. Afterinputchargingspringusinghandle,ifinputbutton(On)push, itthrowsin.Iftripbutton(Off)push,ittrips. Motor charging operation •Inputspringchargeautomaticallybyelectricmotor.Aftercharging, chargingdisplayshows“CHRAGE” •WhenInputbuttonpush(On)manually,itthrowsinshowing “DISCHARGE”onChargingDisplayand“Close”onStateDisplay. •Atthistime,Inputspringchargeautomaticallybyelectricmotor. Aftercharging,chargingdisplayshows“CHRAGE” •WhenTripbuttonpush(Off)manually,ittripsshowing“OPEN”onState Display. •Atthistime,thespringchargeautomaticallybyelectricmotor. Aftercharging,chargingdisplayshows“CHRAGE” •TheBothsourcesarenotworkingsimultaneouslybecauseofmechanical interlocksystem. •WhenbothsourcesOPENposition,thebothsourcesshouldbeshutted off. Air Circuit Break Type Automatic Transfer Switch
  • 6.
    Items ATB-06 ATB-32 630800 1000 1250 1600 2000 2500 3200 4000 5000 6300Rated Current (A) AC 1000VInsulation Level (V) AC 690VRated Voltage (V) 50/60HzFrequency (Hz) 3P/4PNumber of Poles OCR Setting Steps Endurance Rated Breaking Current (KA, Sym)[lcs] Rated Input Current (KA, peak)[1cm] Rated Impulse Voltage [Uimp] Max. Electricity Breaking time [mSec] Making Time [mSec] Time of Motor Charging [Max. Sec] Weight (kg, 3 pole) Fixed Type Drawable Type Fixed Type Drawable Type Weight (kg, 4 pole) Dimensions (4pole) Mechanical Electrical AK58AK58AK56AK56AK56AK56 AK781AK781AK341AK341AK341AK341 VK8 0504 0806 10 sec 100 105 110 120 130 140 150 160 170 200 220 110 115 120 130 140 150 160 170 180 220 240 135 142 150 162 176 190 203 216 230 270 300 150 155 162 176 190 203 216 230 243 - - 019018017036055035054W 055H 095065005D 6 [StandardRating] ATB-08 ATB-10 ATB-12 ATB-16 ATB-20 ATB-25 ATB-40 ATB-50 ATB-63 1.0 - 0.9 - 0.8 - 0.7 -0.6 (5steps) 10,000 times 3,000 times HANCESS ATB Automatic Transfer Breaker AC 600V / Up to 6300A
  • 7.
    Fixed Type (630-6300A) ManualChange Type OCR / GR ATB Electric Powered Charge Type Shutter Position S/W Arc Barrier Digital Type LED Type AUX S/W (5a+5a) Keying Circuit Keying Inter Lock Key Lock Special Function of ATB UVT / Voltage Trip Condenser Trip Drawable Type (630-4000A)1. Mounting Method 2. Accessoried for Drawable Type 3. Method of Input Operation 4. Protection Tools 5. Electrical Trip Tools 6. Accessories 7. Front Panel Accessories Air Circuit Break Type Automatic Transfer Switch HANCESS ATB 7 ATB-06 ATB-32ATB-08 ATB-10 ATB-12 ATB-16 ATB-20 ATB-25 ATB-40 ATB-50 ATB-63
  • 8.
    [Rating][Rating] 8 [InstallationMethod] Drawable type ATB Fixedtype ATB Circuitbreakerisfixedindistributingboard. Maincircuitandcontrolcircuitareisolatedanddoorof wiringroomcanbeclosed. ATBisdrewfromdraw-outframecompletely. Maincircuitisisolatedandcontrolcircuitiscontacted. Testcanbeperformedbyclosingthedoorofwiringroom. Maincircuitandcontrolcircuitarecontacted. Theyareusedatnormalstate. Itiscomposedofcircuitbreakeranddraw-outframe.onlydrawofcircuitbreakerispossible.Draw-out cradleisfixedatdistributingboard. Inthistype,therearethreepositionssuchas'Connected','Test',and'Isolated'.Itispossibletoclosepaneldooratisolatedposition. Draw-outPositionIsolatedPosition ConnectedPosition TestPosition HANCESS ATB Automatic Transfer Breaker AC 600V / Up to 6300A
  • 9.
    HANCESS ATB 9 [ProtectionDeviceforTripRelay] Appearance Setting ratedcurrent (0.7-0.8-0.9-0.95-1.0) x In Max (0.8-0.85-0.9-0.95-1.0) x In If setting value is exceeded, ‘LTD’ ‘LED’ turns On. 15-30-60-120-240-480 sec (2-3-4-6-8-10) x In If setting value is exceeded, ‘STD’ ‘LED’ turns On. 0.05-0.1-0.2-0.3-0.4-0.5 sec (4-6-8-10-13-16) x In If setting value is exceeded, ‘STD’ ‘LED’ turns On. (0.7-0.8-0.9-0.95-1.0) x lc. If setting value is exceeded, ‘PTA’ ‘LED’ turns On. 15-30-60-120-240-480 sec (0.1-0.2-0.3-0.4-0.5-0.6) x In If max setting value is exceeded, ‘GFT’ ‘LED’ turns On. 0.1-0.3-0.8-1.5-3.0 sec Setting long-time delay tripping current Setting long-time delay tripping time Setting short-time delay tripping time Setting instantaneous-time delay tripping current Setting pre-alarm current Setting pre-alarm time Setting ground fault current Setting ground fault time Setting short-time delay tripping current LCD Display : pre fault alarm setting Value 90%, over current trip indication, ground fault trip indication, phase balance [(Im-lav)/lav]*100lav=[la+lb+lc]/3, Im=maximum Knob Name Mode Set-up Procedure Air Circuit Break Type Automatic Transfer Switch ATB 2007F
  • 10.
    Rated Current ofCT Primary Current (I ct) Ground Fault Setting range (GFT) Pre - Trip Alarm range (PAT) Long - Time Delay Setting range (LTD) Short - Time Delay Setting range (STD) Instantaneous - Time Delay Setting range (INST) 10 [TripRelayCurve] HANCESS ATB Automatic Transfer Breaker AC 600V / Up to 6300A
  • 11.
    CTTS (Closed TransitionTransfer Switch) of ATB Specifications HANCESS ATB 11 [SpecialFunctionofATB] Generally,theCircuitBreakersshouldbedesignedandinstalledatthefrontandrearofATSinordertoprotecttheelectricequipment fromfaultcurrent,suchasgroundfault,shortcircuitandsurge. Whenfaultandabnormalcurrentoccurs,ATBmustdesignedandproducedinordertostandatleast20timesofratedcurrentand 3cyclesbeforetrip. Fg1)whenswitchfromNorm.sourcetoEmergencysource, attheClosedposition,transfertoemergencesource. (TestorElectricpowertransferring) Fg2)whenswitchfromEmergencysourcetoNorm.source, attheClosedposition,transfertoNorm.source. Fg3)whenswitchfromNorm.sourcetoEmergencysource, attheOpenposition,transfertoEmergencesource. (Norm.sourceOff) No. of Phase & Wires Rated voltage Rated frequency Rated current Phase angle Difference at Switch Frequency difference at switch Voltage at switch instantaneous after installation related time Note Afterinstallationandwiringconnectioncompletely,thebothsources’phaseordermustbeconfirmedandtheovercurrent mustbeconsideredduetothephaseangledifferenceandvoltagedifferencewhichiscauseofovercurrent. Single Phase, Single Phase three wires, 3Phase three-wires / four wires 110V / 220V / 380V / 440V / 480V 50Hz / 60Hz 630A - 6300A Within 10 Phase Degree within 0.2Hz Voltage difference is within 5% with normal source within 50mSec Fg4)whenswitchfromEmergencysourcetoNorm.source, attheClosedposition,transfertoNorm.source. (TransferringtoNorm.sourcewithoutanyInterrupt) Item Specifications Air Circuit Break Type Automatic Transfer Switch [ Note : If Permitted by the Utility Company ]
  • 12.
    Operation Method forBy-Pass System Built-in ATB ATB Transfer & Retransfer Operation with Time Delay 12 [SpecialFunctionofATB] LOADisaccessedtoASourceand operatedbyATB. InputByPassATBtothesame powersource(ASource)ofATB. (Itissafebecausemechanical andelectricalinterlockisbuilt-in.) 1.TransferATBtooperationposition (Sameasdrawmotion) 2.Whentransferfromtestpositionto operationposition. 3.ATBandByPassATB shouldbe interlocked Normal operation 1) 2) 3) A,BSourceMaincircuitisaccessed andloadsideisisolated. Thereforeelectricaloperation testissafety. Draw of ATB (Test position) Undraw of ATB DrawoutMainATB. Allmaincircuitsareisolated. Inspect DrewoutATBaftertransfer ByPassATB. Draw of ATB (isolated, drawable position) ATB check & Test IncaseofATBtestoruninterruptedfacilities(Broadcastingstation,hospital,computerroom,powerplantandothers). ByPassIsolationswitchhasallcharacteristicsthat ATBhastopreventpowerfailureofloadingsidethatisoccurredincaseoftestormaintenanceofgeneralATSaddoneByPassIsolationSwitchtoATSandoperateitasfollowing figure.Itistheswitchthattestorrepaircanbeperformedwithoutdifficultiestoloadingside. ATB ATB ATB ATB ATB ATB HANCESS ATB Automatic Transfer Breaker AC 600V / Up to 6300A LOADisaccessedtoBSourceand operatedbyATB. By-pass Isolation Switch function of ATB
  • 13.
    Applications of Interlocking HANCESSATB 13 ATB 1 + ACB 1 ATB 2 SetACB 5 Set Air Circuit Break Type Automatic Transfer Switch ACB1 ACB2 ACB3 ACB 3 Set ACB1 ACB2 ACB3 ACB4 ACB5 ACB ACB 2 Set ACB1 ACB2 ATB 1 Set ATB ATB ATB ATB
  • 14.
    14 [ControlCircuitDiagram] HANCESS ATB AutomaticTransfer Breaker AC 600V / Up to 6300A 01.PP,PN:OCRCONTROLSOURCEDC110V 02.M+,M-:MOTORSOURCEDC110V 03.APC1,APC2:“A”SIDECLOSING 04.APT,ANT:“A”SIDETRIP 05.BPC1,BPC2:“B”SIDECLOSING 06.BPT,BNT:“B”SIDETRIP 07.A11~A22:“A”SIDEAUXILIARYCONTACTOR 08.B11~B22:“B”SIDEAUXILIARYCONTACTOR 09.A/L:PRETRIPALARM 10.51:OVERCURRENTFAULT 11.51G:GROUNDOVERCURRENTFAULT 12.COM:UVRCOM 13.AUVR,BUVR:UNDERVOLTAGEFAULT 14.C1,C2:OCRTRIP NOTE DC 110V OCR CONTROL A Side Closing Coil B Side Closing Coil A Side Trip Coil B Side Trip Coil ACC BCC ATC BTC
  • 15.
    Air Circuit BreakType Automatic Transfer Switch Auto Transfer Breaker "A"SOURCE "A" OFF MANU. LCD-H3 AUTO "A" POWER "A" ON "A" TIMER ON CONTROLLER "B" POWER"B" TIMER "B" ON ON "B" OFF "B"SOURCE MANUAL AUTO 15
  • 16.
    (Unit:mm) FixedType/630-4000A3P Front View SideView Rear View 130 270 75 t 500 100 Fixed Hole D 15 15 550 610 60 60 C A B 15 15 Fixed Hole 12 JKLM E F G H A LOAD B Type A B C D E F Type G H J K L M ATB - 16 ATB - 20 ATB - 25 ATB - 32 ATB - 40 ATB - 16 ATB - 20 ATB - 25 ATB - 32 ATB - 40 16 [Dimension] 225 225 225 225 225 225 225 225 225 305 450 450 450 450 530 70 70 70 90 90 125 105 105 95 105 100 120 120 130 160 100 120 120 130 160 125 105 105 95 105 162.5 162.5 162.5 162.5 159.5 120 120 120 120 123.5 120 120 120 120 123.5 134.8 134.8 132.5 132.5 132.5 (630-1200 :12t / 1600-2000 :15t / 2500-3000 :20t / 3200-6300 :25t) HANCESS ATB Automatic Transfer Breaker AC 600V / Up to 6300A
  • 17.
    (Unit:mm) (630-1200 :12t /1600-2000 :15t / 2500-3000 :20t / 3200-6300 :25t) FixedType/630-4000A4P 15 15 550 C A B 15 15 Fixed Hole 12 130 270 75 t 500 100 Fixed Hole D Type A B C D E F Type G,H J K L M N ATB - 16 ATB - 20 ATB - 25 ATB - 32 ATB - 40 ATB - 16 ATB - 20 ATB - 25 ATB - 32 ATB - 40 JKLM E F G H N N T S R A LOAD B Front View Side View Rear View HANCESS ATB 17 225 225 225 225 304 225 305 305 325 385 450 530 530 550 689 70 70 70 70 90 75 85 80 80 104 100 120 120 130 160 100 120 120 130 160 162.5 162.5 162.5 159.5 159.5 120 120 120 120 123.5 134.8 134.8 132.5 132.5 132.8 120 120 120 120 123.5 75 85 85 85 104 Air Circuit Break Type Automatic Transfer Switch
  • 18.
    FixedType/630-4000A3P 3P Rear View JKLM EF G GF F E A LOAD B 4P Rear View JKLM E N G GF GF F E A LOAD B C C A B 1515 550 15 15 Fixed Hole 12 Front View 130 270 75 t 500 100 Fixed Hole D Side View 5000A BUS BAR 23 23 35 35 35 6300A BUS BAR 15 15 30 30 30 30 30 30 70 Type G J K L M N ATB - 50 3P ATB - 63 3P ATB - 50 4P ATB - 63 4P Type A B C D E F ATB - 50 3P ATB - 63 3P ATB - 50 4P ATB - 63 4P 18 [Dimension] (Unit:mm) (630-1200 :12t / 1600-2000 :15t / 2500-3000 :20t / 3200-6300 :25t) 30 40 30 40 162.5 159 162.5 159 123.5 123.5 123.5 123.5 123.5 123.5 123.5 123.5 132.5 132.5 132.5 132.5 150 - 150 150 315 465 387 545 315 525 387 625 630 990 774 1170 90 90 90 90 60 95 42 105 150 280 150 280 HANCESS ATB Automatic Transfer Breaker AC 600V / Up to 6300A
  • 19.
    DrawableType/1600-4000A HANCESS ATB 19 Bottom View 650D 190120120 E Side View C A B 610 610 60 60 Front View <ATB-06~16> <ATB-20,25,32> <ATB-40> <ATB-50> 30 30 20 20 55 120 35 20 150 25 20 80 Type ATB - 06 ~ 16 ATB - 20 ATB - 25 ATB - 32 ATB - 40 A B C D E A B 650 4- 13 ATB No. of Pole 3P 4P 3P 4P 3P 3P 4P 4P Rated Current A B Size 600 - 1600A 290 427 290 427 370 427 290 444 390 444 370 470 444 444 2000A 2500A 3200A 4000A 4000A 268 268 268 268 348 268 348 348 370 428 536 616 616 638 776 70 70 70 70 70 12 / 15 15 20 20 20 (Unit:mm) Air Circuit Break Type Automatic Transfer Switch (630-1200 :12t / 1600-2000 :15t / 2500-3000 :20t / 3200-6300 :25t)
  • 20.
    Head Office 144, Achasan-ro,Seongdong-gu, Seoul, Korea TEL : 82 - 2 - 462 - 3731 ~ 3 FAX : 82 - 2 - 463 - 8350 Plant 48, Daram-ro 57beon-gil, Docheock-Myeon, Gwangju-si, Gyeonggi-Do, Korea TEL : 82 - 31 - 762 - 7500 FAX : 82 - 31 - 764 - 0302 Agent note) The specifications are subject to change without notice in order to improve the performance and quality. WWW.HANCESS.COM Transter & Bypass Status Normal Source Emergency Source Source Available Main MainByPass ByPass LOAD Lamp Test Hanpro3000 ATBCTTS&ByPassControllerBasedonDSP Vietnam Represented Office: Hancess Vietnam - Quanpham Co.,ltd 285 Dien Bien Phu, Ward 07 -district 03, Ho Chi Minh City - Vietnam Tel: +84 39304952 - 39302400 Fax: +84 39304953 E-mail: info@quanpham.vn Website: www.quanpham.vn