UNIT 43
AIR SOURCE HEAT PUMPS
UNIT OBJECTIVES
After studying this unit, the reader should be able to
• Describe the operation of reverse-cycle refrigeration (heat pumps)
• Explain the function and operation of heat pump system components
• List heat sources commonly used in heat pump systems
• Discuss how heat pump efficiency is determined
• Explain the concepts of coefficient of performance and auxiliary heat
• Describe the control sequence of an air-to-air heat pump system
• Explain how heat pump efficiency can be increased
• Discuss preventive maintenance on a heat pump system
REVERSE-CYCLE REFRIGERATION
• Air-conditioning equipment can only pump
heat in one direction
• Heat pumps can pump heat two ways
• Heat pumps have a four-way reversing valve
• Four-way reversing valves control the
direction of flow of the heat-laden vapor
between the low- and high-pressure sides of
the system
Functions as the evaporator
in the heating mode
Functions as the condenser in
the heating mode
Functions as the condenser in
the cooling mode
Functions as the evaporator
in the cooling mode
HEAT SOURCES FOR WINTER
• Air conditioners pump heat from low temperature inside
the structure to a higher temperature outside the house
• There is heat in a substance until it is cooled to -460°F
• At 0°F outside air temperature, there is still 85% usable
heat in the air
• Heat pumps have the ability to absorb heat from the
structure in the summertime and discharge it to the outside
• Heat pumps are able to absorb heat from the outside air
and discharge it to the inside of the structure
THE FOUR-WAY VALVE
• Allows the heat pump to pump heat in two directions
• Diverts the discharge gas to either heat or cool the
conditioned space
• Refrigerant is directed from the compressor to the indoor
coil in the heating mode
• Refrigerant is directed from the compressor to the
outdoor unit in the cooling mode
• Controlled by the space temperature thermostat
• Pilot-operated valve
• Four piping connections on the valve
Hot gas from compressor
Suction gas to
compressor
Connected to
indoor coil
Connected to
outdoor coil
Moveable slide
inside valve
Direct-acting
reversing valve is
controlled directly
by a solenoid coil
Hot gas from compressor
Suction gas
to compressor
Connected to
indoor coil
Connected to
outdoor coil
Pilot-operated
reversing valve is
controlled by the
system pressures
System high
pressure pushes
the slide to the
right
COOLING
Hot gas from compressor
Suction gas
to compressor
Connected to
indoor coil
Connected to
outdoor coil
Pilot-operated
reversing valve is
controlled by the
system pressures
HEATING
TYPES OF HEAT PUMPS
• Air is not the only source from which a heat
pump ban absorb heat, but it is the most popular
• Other heat sources for heat pumps include water
and Earth
• A typical water-to-air heat pump uses 3 gallons
of water per minute in the heating cycle and 1.5
gallons of water per minute in the cooling mode
per ton of refrigeration
SOLAR-ASSISTED HEAT PUMPS
• These pumps capture heat from the sun
• The heat is then brought to usable levels for
heating homes
• Some systems are specially designed to
operate in conjunction with solar heat
THE AIR-TO-AIR HEAT PUMP
• Most popular type
• Basic sealed system components of a heat
pump are the same as an air conditioner, but
the terminology changes
• In a heat pump, the terms indoor coil and
outdoor coil are used
• The function of each coil changes as the
operating mode of the heat pump changes
THE AIR-TO-AIR HEAT PUMP
• Function of coils in the cooling mode
– Indoor coil absorbs heat by boiling refrigerant at low
temperature and pressure (evaporator)
– Outdoor coil rejects heat by condensing a high-
temperature and pressure vapor to a high-
temperature and pressure vapor (condenser)
– Refrigerant from the compressor is first pumped to
the outdoor coil
Hot gas from compressor
Suction gas to
compressor
Connected to
indoor coil
Connected to
outdoor coil
THE AIR-TO-AIR HEAT PUMP
• Function of coils in the heating mode
– Outdoor coil absorbs heat by boiling refrigerant at
low temperature and pressure (evaporator)
– Indoor coil rejects heat by condensing a high-
temperature and pressure vapor to a high-temperature
and pressure vapor (condenser)
– Hot gas from the compressor is first pumped to the
indoor coil
Hot gas from compressor
Suction gas to
compressor
Connected to
indoor coil
Connected to
outdoor coil
THE AIR-TO-AIR HEAT PUMP
• Mode of operation is determined by which
way the hot gas from the compressor is
flowing
• Mode of operation can be determined by
touching the gas line to the indoor coil
– In the cooling mode, the gas line will feel cool
– In the heating mode, the gas line will feel hot
REFRIGERANT LINE IDENTIFICATION
• The large diameter line is called the gas line because
only refrigerant vapor flows through it
• The gas line is a cold gas line in the summer and a hot
gas line in the winter
• The smaller diameter line is called the liquid line
because only liquid refrigerant travels through it
• During the cooling mode, the liquid travels to the
indoor coil
• During the heating mode, the liquid travels to the
outdoor coil
Indoor Unit Outdoor Unit
HEAT PUMP OPERATING IN THE HEATING MODE
Hot gas from
compressor
High pressure liquid
to metering device
and evaporator
Indoor Unit Outdoor Unit
HEAT PUMP OPERATING IN THE COOLING MODE
Cool suction gas to
compressor
High pressure liquid
to metering device
and evaporator
METERING DEVICES
• Specially designed for heat pump applications
• There must be a metering device at the outdoor
unit in the heating mode
• There must be a metering device at the indoor
coil in the cooling mode
THERMOSTATIC EXPANSION
VALVES (TEV, TXV)
• Maintains Desired superheat in the evaporator
• Check valves are piped parallel to the TXV to allow
refrigerant to bypass the control when needed
• Heating mode
– The refrigerant flows through the TXV at the outdoor coil
– The refrigerant bypasses the TXV at the indoor coil
• Cooling mode
– The refrigerant flows through the TXV at the indoor coil
– The refrigerant bypasses the TXV at the outdoor coil
THE CAPILLARY TUBE
• Commonly used on heat pumps
• Will allow refrigerant to flow in both directions
• Sometimes two capillary tubes are used with
check valves
• There must be a drier/strainer at the inlet of the
capillary tube to ensure that the tube does not
get clogged
Ball-type Check Valve
COMBINATIONS OF METERING
DEVICES
• Uses the capillary tube at the indoor coil
– Used in the cooling mode
– Load is relatively constant in the warmer months
• Uses a thermostatic expansion valve at the
outdoor coil
– Used in the heating mode
– Allows system to reach maximum efficiency quickly
ELECTRONIC EXPANSION
DEVICES
• Can meter refrigerant in both directions
• If indoor and outdoor coils are close together,
one device can be used
• The correct superheat will be maintained in both
heating and cooling modes
ORIFICE METERING DEVICES
• Used in conjunction with check valves
• One device is located at each coil
• The bore at the indoor coil is larger than the
bore at the outdoor coil
• Normally used with a bi-flow filter drier
LIQUID LINE ACCESSORIES
• Two standard filter driers can be used on
systems with check valves
– Only one drier will be in the refrigeration circuit
at a time
– They are installed with the arrows pointing in the
same direction as the check valves
• Bi-flow filter driers
– Two driers in one
– Designed for heat pump applications
Check valve
closed
Refrigerant from outdoor coil
Refrigerant to indoor coil
COOLING MODE
Check valve
closed
Refrigerant to outdoor coil
Refrigerant from indoor coil
HEATING MODE
APPLICATION OF THE AIR-TO-AIR HEAT PUMP
• Usually installed in milder climates (temperatures as low
as 10°)
• In the winter, the outdoor coil absorbs heat
• Difference between outdoor and evaporator temperature
is about 25°
• If outside temperature is 10°, the refrigerant boils at
approximately -15°
• The compressor and the system lose efficiency as the
evaporator temperature goes down
• The system loses capacity as the outside temperature
drops
AUXILIARY HEAT
• Required when the heat pump cannot provide
all the heat a structure needs
• The heat pump is the primary heat source
• Auxiliary heat could be electric, oil or gas
• Electric heat is the most common auxiliary heat
used
• As the outside temperature drops, the structure
requires more heat
BALANCE POINT
• Balance point occurs when the heat pump can
pump in exactly as much heat as the structure is
leaking out
• Above the balance point, the heat pump will cycle
on and off
• Below the balance point, the heat pump will run
continuously and second stage (auxiliary) heat
will be energized
COEFFICIENT OF PERFORMANCE
• One watt of usable heat is supplied for each
watt of energy purchased
– Using electric resistance heat
– This is called 100% efficient
– Coefficient of performance (COP) of 1:1
– The output is the same as the input
• Air-to-air heat pumps can have a COP of 3.5:1
– When 1 watt of electrical energy is used by the
compressor, it can furnish 3.5 watts of usable heat
(COP is 3.5:1)
COEFFICIENT OF PERFORMANCE
• High COP only occurs during higher outdoor winter
temperatures
• A heat pump’s COP falls as the outdoor temperature falls
• A typical air-to-air heat pump has a COP of 1.5:1 at 0°F
• Some manufacturers have controls to shut off the
compressor at temperatures of 0 to 10°F
• Water-to-air heat pumps might not need auxiliary heat
since the heat source (water) temperature is constant
• Water-to-air heat pumps have a COP rating as high as 4:1
SPLIT-SYSTEM AIR-TO-AIR
HEAT PUMPS
• Air-to-air systems can be split or package type
• Both heat pumps and straight cooling units look
identical
• Split systems require the installation of the gas
and liquid refrigerant lines to connect the indoor
and outdoor units
Functions as the evaporator
in the heating mode
Functions as the condenser in
the heating mode
Field installed
refrigerant lines
THE INDOOR UNIT
• The part of the system that circulates the air
within the structure
• It contains the fan and coil and often the electric
strip heaters
• The refrigerant coil must be located in the
airstream before the auxiliary heating coil
• The indoor unit may be a gas or oil fired furnace
• If gas or oil furnace is the indoor unit, the coil
must be located in the outlet airstream of the
furnace
• If a gas or oil furnace is used, the heat pump
will not operate when they are operating
• Heat pumps added to electric furnaces should
have the coil located after the heat strips
THE INDOOR UNIT
AIR TEMPERATURE OF THE
CONDITIONED AIR
• Air temperatures of a heat pump are not as hot
as with fossil-fuel equipment
• Maximum heat pump air supply temperatures
are around 100°F
• Most heat pumps require a minimum of 400
cfm per ton of refrigeration
• Supply air temperature will fall when outside
air temperatures drop
Supply duct
Return air from the
occupied space (75°F)
Air handler (condenser in winter)
Heated air
(100°F)
THE OUTDOOR UNIT INSTALLATION
• Much like a regular air-conditioning installation
• Must have good air circulation around it
• Prevailing winds affect performance
• In the wintertime, the outdoor coil will collect moisture
and the moisture will freeze on the coil
• Outdoor coil should be installed so it is raised above the
ground pad to allow defrost water to run to the ground
• A defrost system is provided to defrost the ice from the
outdoor coil
PACKAGE AIR-TO-AIR HEAT PUMPS
• Has all the sealed system and electrical
components in one housing
• Works much the same way as a packaged air-
conditioning unit
• Only one power supply required
• Supply and return ductwork must be field
installed
Package heat pump system
Supply and return ducts
are field installed
CONTROLS FOR AIR-TO-AIR HEAT PUMPS
• Controls are different than other heating/cooling
equipment
• In a heat pump, there are two heating systems and one
cooling system
• Auxiliary heating system must be operated as a system
by itself in case the heat pump fails
• Auxiliary heat is referred to as emergency heat when
used because of heat pump failure
• The space thermostat is the key to controlling the
system
• Normally, a two-stage heating and two-stage cooling
thermostat is used
CONTROLS FOR AIR-TO-AIR HEAT PUMPS
• Automatic changeover thermostat changes automatically
between heating and cooling modes
• Cooling cycle controls
– Thermostat contacts control the operation of the compressor,
outdoor fan motor, and reversing valve coil
– When the thermostat is satisfied, the compressor, outdoor fan
motor, and indoor fan motor are de-energized
– The reversing valve solenoid coil remains energized
Heat Cool
1ST
1ST
2ND
2ND
H(Y)
1(W)
O
C(Y)
FIRST STAGE COOLING (SIMPLIFIED)
Outdoor unit
4-way reversing valve
coil energized
R
O
Heat Cool
1ST
1ST
2ND
2ND
H(Y)
1(W)
O
C(Y)
SECOND STAGE COOLING (SIMPLIFIED)
Outdoor unit
4-way reversing valve
coil energized
R
O
Y
Compressor contactor
coil energized
CONTROLS FOR AIR-TO-AIR
HEAT PUMPS
• Space heating control
– Thermostat controls compressor, outdoor fan
motor, and indoor fan motor operation
– Excessively cold temperatures energize second-
stage heat
– Second-stage heat cycles on and off to assist
the heat pump
Heat Cool
1ST
1ST
2ND
2ND
H(Y)
1(W)
O
C(Y)
FIRST STAGE HEATING (SIMPLIFIED)
Outdoor unit
R
Y
Compressor contactor
coil energized
Heat Cool
1ST
1ST
2ND
2ND
H(Y)
1(W)
O
C(Y)
SECOND STAGE HEATING (SIMPLIFIED)
Outdoor unit
R
Y
Compressor contactor
coil energized
Heat Cool
1ST
1ST
2ND
2ND
H(Y)
1(W)
O
C(Y)
SECOND STAGE HEATING WITH OUTDOOR THERMOSTATS
(SIMPLIFIED)
Outdoor unit
R
Y
Compressor contactor
coil energized
Outdoor thermostats for electric heaters
CONTROLS FOR AIR-TO-AIR
HEAT PUMPS
• Balance point
– Point at which the heat pump can satisfy the load without
shutting down
– May be multiple balance points
• Electric heaters are energized at different temperatures
– Only the minimum number of heaters is energized at a time
– Conserves energy
– Auxiliary heat operation indicated by signal light on
thermostat
CONTROLS FOR AIR-TO-AIR HEAT PUMPS
• Emergency heat mode
– Used in the event of heat pump failure
– All heating elements are energized
– Signal light on thermostat
• Heat anticipators
– Found on heat pump thermostats and conventional
thermostats
– Most heat pump thermostats are equipped with two
EMERGENCY HEATING (SIMPLIFIED)
Heat
1ST
1ST
2ND
2ND
H(Y)
1(W)
O
C(Y)
R
Emergency heat relay
contacts
Cool
THE DEFROST CYCLE
• Defrosts ice from outside coil during winter operation
• Outdoor coil operates below freezing anytime the outside
air is below 45°F
• Outdoor coil operates 20° to 25°F below the outside air
temperature
• The need for defrost varies depending on outside air
temperatures and conditions
• The more moisture in the air, the more frost that forms on
the outdoor coil
• Defrost affects the efficiency of the systems
HEATING SEASONAL
PERFORMANCE FACTOR (HSPF)
• Seasonal performance for particular piece of equipment
• Breaks the country into six zones
• Used to calculate operation costs
• Considers average number and length of defrost cycles
per year
• Considers whether auxiliary heaters are energized during
defrost
• SEER and HSPF are results of federal energy policies
HEAT PUMP DEFROST
• Air-to-air heat pumps accomplish defrost by stopping
the outdoor fan and cycling unit into cooling mode
• During defrost, one stage of strip heat is turned on
• The system is cooling and heating at the same time
during defrost
• Demand defrost means defrosting only when needed
• Combinations of time, temperature, and pressure drop
across the outdoor coil are also used in some systems
to determine when defrost is needed
INITIATING THE DEFROST CYCLE
• Manufacturers design the systems to start defrost when
frost affects performance
• Some use time and temperature initiated defrost systems
• Both conditions must be met before defrost will be
activated
• Coil temperature sensing devices will close around
outdoor coil temperature of 25°
• Typically, the timer will run any time the compressor
runs
4-way reversing
valve coil
L1
L2
Timer motor
Defrost relay
Outdoor fanOutdoor coil thermostat
TIME AND TEMPERATURE INITIATED DEFROST
INITIATING THE DEFROST CYCLE
• Some systems will also include a pressure
switch along with the temperature and timer
function
• When ice forms on the coil, the pressure switch
closes
• Time, temperature, and pressure defrost systems
ensure that there is ice buildup on the outdoor
coil
4-way reversing
valve coil
L1 L2
Timer motor
Defrost relay
Outdoor fanOutdoor coil stat
TIME, TEMPERATURE AND PRESSURE INITIATED DEFROST
Pressure
TERMINATING THE DEFROST CYLE
• Stopping the defrost is as important as starting the
defrost
• Time, temperature, and pressure can all be used to
terminate the defrost cycle
• Temperature sensors used for the defrosting
function will open at 50°F
• 10 minutes is the normal maximum time allowed
for defrost cycle
4-way reversing
valve coil
L1
L2
Timer motor
Defrost relay
Outdoor fanOutdoor coil thermostat
TIME OR TEMPERATURE TERMINATED DEFROST
ELECTRONIC CONTROL OF
DEFROST
• Electronic timers and thermistors used to
control defrost
• More accurate control than non-electronic
methods
• Can incorporate time and temperature
features into a single unit
INDOOR FAN MOTOR CONTROL
• In a heat pump, the fan must be started at the
beginning of each mode of operation
• The indoor fan is started with the thermostat
• Fan switch terminal function is normally the G
terminal on the thermostat
• The indoor fan motor often operates during defrost
– Circulates air to prevent coil freezing
– Air is tempered to prevent cold air from being
introduced to the occupied space
AUXILIARY HEAT
• Usually accomplished with electric heat
• Required to assist the heat pump when it
cannot provide all the heat the structure needs
• Also used as emergency heat when the heat
pump needs service
• Heaters also energized during defrost
SERVICING THE AIR-TO-AIR HEAT PUMP
• Much like servicing a refrigeration system
• During the cooling mode, system is operating as a high-
temperature refrigeration system
• During the heating mode, system is operating as a low-
temperature refrigeration system
• Servicing of the system is divided into electrical and
mechanical
• The heat pump may run for days and not stop when
outdoor temperatures are below the balance point
TROUBLESHOOTING
MECHANICAL PROBLEMS
• Can be hard to identify in a heat pump,
particularly in winter operation
• Summer operation of a heat pump is similar
to an air-conditioning unit
• Mechanical problems are solved with gage
manifolds, wet-bulb and dry-bulb
thermometers, and air-measuring instruments
TROUBLESHOOTING THE
FOUR-WAY VALVE
• Common problems: stuck valve, defection coil
and internal leaks
• Check to see if coil is energized
• A warm coil indicates power is being supplied to
the coil
• Place a screwdriver on the surface of the coil to
sense magnetic field
• Check for voltage supplied to the coil
• Defective coils can be replaced without changing
the entire valve
TROUBLESHOOTING THE
FOUR-WAY VALVE
• Four-way valves leaking through can be confused with a
compressor that is not pumping to capacity
• Capacity of the system will not be normal in summer or
winter cycles
• Check the temperature of the low-side line, the suction
line from the evaporator, and the permanent suction line
between the four-way valve and the compressor
• In this check, the temperature difference should not be
more than about 3°F
Hot gas from compressor
Suction gas to
compressor
Connected to
indoor coil
Connected to
outdoor coil
50°F
60°F
Leaking reversing
valve in the cooling
mode
Hot gas from compressor
Suction gas to
compressor
Connected to
indoor coil
Connected to
outdoor coil
Leaking reversing
valve in the heating
mode
30°F
40°F
CHECKING THE CHARGE
• Most heat pumps have a critical refrigerant charge
• If systems are low on charge, technicians must
locate and repair leaks
• Caution should be taken when charging systems
with suction accumulators
• Suction accumulators store part of the charge in
the winter mode and will boil out later
CHECKING THE CHARGE
• Sweating suction-line accumulator
– When checking or charging a system, heat the
accumulator by running water over it to drive the
refrigerant out of it
– Often the accumulator will frost or sweat at a
particular level if liquid refrigerant is contained in it
SPECIAL APPLICATION FOR
HEAT PUMPS
• Use of oil or gas furnaces for auxiliary heat
• More efficient applications than auxiliary electric heat
• The heat pump coil must be installed downstream of the
oil or gas heat exchanger
• The air must flow through the furnace heat exchanger
before the heat pump coil
• The oil or gas furnace must not operate at the same time
that the heat pump is operating
HEAT PUMPS USING SCROLL
COMPRESSORS
• Ideally suited for heat pump application because
of its pumping characteristics
• Scrolls do not lose as much capacity as
reciprocating compressors
• Scroll compressor pressures are about the same
as reciprocating compressors
• Scroll compressors are discharge gas cooled,
• Scroll compressors have a check valve in the
discharge leaving the compressor to prevent
pressures from equalizing through the
compressor during the off cycle
• Scroll compressors normally do not require a
suction-line accumulator because they are not as
sensitive to liquid floodback
HEAT PUMPS USING SCROLL
COMPRESSORS
HEAT PUMP SYSTEMS WITH
VARIABLE-SPEED MOTORS
• Use of variable-speed motors for the compressor and
both fan motors is the method used to improve system
efficiency in heat pump systems
• Sized closer to the heating requirements of the structure
at full load and will run at part load and reduced power
in warmer months
• Less auxiliary heat is required for these systems
• Variable speed is accomplished with electronically
controlled motors
SUMMARY - 1
• Heat pumps can pump heat two ways to provide both
heating and cooling
• Four-way reversing valves control the direction of flow
of the heat-laden vapor between the low- and high-
pressure sides of the system
• In the cooling mode, the outdoor coil functions as the
condenser and the indoor coil functions as the evaporator
• In the heating mode, the outdoor coil functions as the
evaporator and the indoor coil functions as the condenser
SUMMARY - 2
• Metering devices are located at the inlet of both the indoor
and outdoor coils
• Check valves are used to bypass the metering device that
should not be in the active refrigerant circuit
• Bidirectional or bi-flow filter driers are two driers in a
single shell and are designed for heat pump applications
• In the heating mode, heat pumps lose efficiency as the
outside ambient temperature drops
• Auxiliary heat is required when the heat pump cannot
provide all the heat a structure needs
SUMMARY - 3
• Balance point occurs when the heat pump can pump in
exactly as much heat as the structure is leaking out
• Coefficient of performance is the ratio of usable heat (in
watts) produced from each watt of energy purchased
• In winter operation, the COP increases as the outside
ambient temperature increases
• Split heat pump systems require the installation of gas
and liquid lines to connect the indoor and outdoor units
• The indoor unit contains the fan and coil and often the
electric strip heaters
SUMMARY - 4
• Maximum air supply temperatures are around 100°F
• Outdoor coil should be installed so it is raised above the
ground pad to allow defrost water to run to the ground
• A defrost system is provided to defrost the ice from the
outdoor coil
• Package heat pump systems have all system and electrical
components in one housing
• There are two heating systems and one cooling system
• Auxiliary heating system must be operated as a system by
itself in case the heat pump fails
SUMMARY - 5
• Automatic changeover thermostat changes automatically
between heating and cooling modes
• Emergency heat mode is used in the event of heat pump
failure
• The need for defrost varies depending on outside air
temperatures and conditions
• The more moisture in the air, the more frost that forms
on the outdoor coil
• Defrost affects the efficiency of the systems
• Air-to-air heat pumps accomplish defrost by stopping the
outdoor fan and cycling unit into cooling mode
SUMMARY - 6
• Combinations of time, temperature, and pressure
drop across the outdoor coil are also used in some
systems to determine when defrost is needed and
when defrost is terminated
• Defrost can also be controlled electronically
• In a heat pump, the fan must be started at the
beginning of each mode of operation
• The indoor fan motor often operates during defrost
• During the cooling mode, system is operating as a
high-temperature refrigeration system
SUMMARY - 7
• During the heating mode, system is operating as a low-
temperature refrigeration system
• Common reversing valve problems include: stuck
valve, defection coil and internal leaks
• Temperature readings of the reversing valve
connections can be taken to evaluate the valve
• Most heat pumps are critically charged systems
• If the system operated correctly in at least one mode,
the refrigerant charge is correct
SUMMARY - 8
• Oil or gas furnaces can be used for auxiliary heat
• The heat pump coil must be installed downstream of the
oil or gas heat exchanger
• Scroll compressor is ideally suited for heat pump
applications because of its pumping characteristics
• Scroll compressors normally do not require a suction-line
accumulator because they are not as sensitive to liquid
floodback
• Use of variable-speed motors for the compressor and both
fan motors is the method used to improve system
efficiency in heat pump systems

More Related Content

What's hot

15679104 basic-civil-and-mechanical-engineering-unit-v
15679104 basic-civil-and-mechanical-engineering-unit-v15679104 basic-civil-and-mechanical-engineering-unit-v
15679104 basic-civil-and-mechanical-engineering-unit-v
Mahendiran Subramaniyan
 
Refrigeration Basics
Refrigeration BasicsRefrigeration Basics
Refrigeration Basics
Alvin Bene
 
Refrigeration and-air-conditioning-notes
Refrigeration and-air-conditioning-notesRefrigeration and-air-conditioning-notes
Refrigeration and-air-conditioning-notes
Olumide Daniel
 
Refrigeration And Air Conditioning
Refrigeration And Air ConditioningRefrigeration And Air Conditioning
Refrigeration And Air Conditioning
Saurabh Jain
 
Refrigeration and air conditioning (full note)
Refrigeration and air conditioning (full note)Refrigeration and air conditioning (full note)
Refrigeration and air conditioning (full note)
shone john
 
Refrigeration
RefrigerationRefrigeration
Refrigeration
stooty s
 

What's hot (20)

15679104 basic-civil-and-mechanical-engineering-unit-v
15679104 basic-civil-and-mechanical-engineering-unit-v15679104 basic-civil-and-mechanical-engineering-unit-v
15679104 basic-civil-and-mechanical-engineering-unit-v
 
Refrigeration
RefrigerationRefrigeration
Refrigeration
 
Refrigeration Basics
Refrigeration BasicsRefrigeration Basics
Refrigeration Basics
 
Hvac chilled water distribution schemes
Hvac chilled water distribution schemesHvac chilled water distribution schemes
Hvac chilled water distribution schemes
 
Water Chilled Airconditioning
Water Chilled AirconditioningWater Chilled Airconditioning
Water Chilled Airconditioning
 
Refrigeration system
Refrigeration systemRefrigeration system
Refrigeration system
 
Air conditioning
Air conditioningAir conditioning
Air conditioning
 
Air Conditioning and Security Installations
Air Conditioning and Security InstallationsAir Conditioning and Security Installations
Air Conditioning and Security Installations
 
Refrigeration and-air-conditioning-notes
Refrigeration and-air-conditioning-notesRefrigeration and-air-conditioning-notes
Refrigeration and-air-conditioning-notes
 
Chiller water systems
Chiller water systemsChiller water systems
Chiller water systems
 
Refrigeration
RefrigerationRefrigeration
Refrigeration
 
Refrigeration systems
Refrigeration systemsRefrigeration systems
Refrigeration systems
 
vapour compression refrigeration system
vapour compression refrigeration systemvapour compression refrigeration system
vapour compression refrigeration system
 
Refrigeration cycle
Refrigeration cycleRefrigeration cycle
Refrigeration cycle
 
Refrigeration
RefrigerationRefrigeration
Refrigeration
 
Refrigeration system
Refrigeration systemRefrigeration system
Refrigeration system
 
Refrigeration and air conditioning RAC
Refrigeration and air conditioning RACRefrigeration and air conditioning RAC
Refrigeration and air conditioning RAC
 
Refrigeration And Air Conditioning
Refrigeration And Air ConditioningRefrigeration And Air Conditioning
Refrigeration And Air Conditioning
 
Refrigeration and air conditioning (full note)
Refrigeration and air conditioning (full note)Refrigeration and air conditioning (full note)
Refrigeration and air conditioning (full note)
 
Refrigeration
RefrigerationRefrigeration
Refrigeration
 

Similar to CURSO DE AIRE ACONDICIONADO FRÍO CALOR

Module 1 heating - steam (wecompress.com)
Module 1   heating - steam (wecompress.com)Module 1   heating - steam (wecompress.com)
Module 1 heating - steam (wecompress.com)
DeepakSingh1807
 
Cem 350 hvac air side systems 10-2016
Cem 350 hvac air side systems 10-2016Cem 350 hvac air side systems 10-2016
Cem 350 hvac air side systems 10-2016
miresmaeil
 

Similar to CURSO DE AIRE ACONDICIONADO FRÍO CALOR (20)

Module 1 heating - steam (wecompress.com)
Module 1   heating - steam (wecompress.com)Module 1   heating - steam (wecompress.com)
Module 1 heating - steam (wecompress.com)
 
AC System Components.ppt
AC System Components.pptAC System Components.ppt
AC System Components.ppt
 
Condensers in refrigeration.ppt
Condensers in refrigeration.pptCondensers in refrigeration.ppt
Condensers in refrigeration.ppt
 
hvac systems basic components
hvac systems basic componentshvac systems basic components
hvac systems basic components
 
hvac-systems-components.ppt
hvac-systems-components.ppthvac-systems-components.ppt
hvac-systems-components.ppt
 
Hvac systems-components
Hvac systems-componentsHvac systems-components
Hvac systems-components
 
hvac-systems-components 2023.ppt
hvac-systems-components 2023.ppthvac-systems-components 2023.ppt
hvac-systems-components 2023.ppt
 
Heat Pumps.pptx
Heat Pumps.pptxHeat Pumps.pptx
Heat Pumps.pptx
 
Regrigeratio cycle
Regrigeratio cycleRegrigeratio cycle
Regrigeratio cycle
 
Unit 26
Unit 26Unit 26
Unit 26
 
Air Conditioning system and types
Air Conditioning system and typesAir Conditioning system and types
Air Conditioning system and types
 
Heat pumps
Heat pumpsHeat pumps
Heat pumps
 
Unit 03 esl
Unit 03 eslUnit 03 esl
Unit 03 esl
 
Architecture - Centralized Air Conditioning System
Architecture - Centralized Air Conditioning System Architecture - Centralized Air Conditioning System
Architecture - Centralized Air Conditioning System
 
S3 Lec 6 (Air Distribution) Note
S3 Lec 6 (Air Distribution) NoteS3 Lec 6 (Air Distribution) Note
S3 Lec 6 (Air Distribution) Note
 
Gbu air conditioning system (1)
Gbu air conditioning system (1)Gbu air conditioning system (1)
Gbu air conditioning system (1)
 
Aqat
AqatAqat
Aqat
 
Complete hvac ppt by kk 354647.pptx 1234
Complete hvac ppt by kk 354647.pptx 1234Complete hvac ppt by kk 354647.pptx 1234
Complete hvac ppt by kk 354647.pptx 1234
 
Deep dive into_pc_cooling_2019
Deep dive into_pc_cooling_2019Deep dive into_pc_cooling_2019
Deep dive into_pc_cooling_2019
 
Cem 350 hvac air side systems 10-2016
Cem 350 hvac air side systems 10-2016Cem 350 hvac air side systems 10-2016
Cem 350 hvac air side systems 10-2016
 

More from Percy Alfredo Huanca Chambi

More from Percy Alfredo Huanca Chambi (13)

AIRE ACONDICIONADO calculo
AIRE ACONDICIONADO calculoAIRE ACONDICIONADO calculo
AIRE ACONDICIONADO calculo
 
REFRIGERACIÓN COMERCIAL
 REFRIGERACIÓN COMERCIAL REFRIGERACIÓN COMERCIAL
REFRIGERACIÓN COMERCIAL
 
AIRE ACONDICIONADO - DISEÑO
AIRE ACONDICIONADO  - DISEÑOAIRE ACONDICIONADO  - DISEÑO
AIRE ACONDICIONADO - DISEÑO
 
AIRE ACONDICIONADO INVERTER - VRV - RESUMEN MODELOS DAIKIN
AIRE ACONDICIONADO INVERTER  -  VRV  - RESUMEN MODELOS DAIKINAIRE ACONDICIONADO INVERTER  -  VRV  - RESUMEN MODELOS DAIKIN
AIRE ACONDICIONADO INVERTER - VRV - RESUMEN MODELOS DAIKIN
 
LIBRO REFRIGERACIÓN - BUENAS PRACTICAS
LIBRO REFRIGERACIÓN  - BUENAS PRACTICASLIBRO REFRIGERACIÓN  - BUENAS PRACTICAS
LIBRO REFRIGERACIÓN - BUENAS PRACTICAS
 
AIRE ACONDICIONADO Nuevas tecnologías
AIRE ACONDICIONADO  Nuevas tecnologías AIRE ACONDICIONADO  Nuevas tecnologías
AIRE ACONDICIONADO Nuevas tecnologías
 
AIRE ACONDICIONADO - SISTEMAS DE CLIMATIZACION.
AIRE ACONDICIONADO - SISTEMAS DE CLIMATIZACION.AIRE ACONDICIONADO - SISTEMAS DE CLIMATIZACION.
AIRE ACONDICIONADO - SISTEMAS DE CLIMATIZACION.
 
AIRE ACONDICIONADO - MANUAL VENTILACIÓN CALEFACCION
AIRE ACONDICIONADO - MANUAL VENTILACIÓN CALEFACCIONAIRE ACONDICIONADO - MANUAL VENTILACIÓN CALEFACCION
AIRE ACONDICIONADO - MANUAL VENTILACIÓN CALEFACCION
 
AIRE ACONDICIONADO - Climatización
AIRE ACONDICIONADO  -  Climatización AIRE ACONDICIONADO  -  Climatización
AIRE ACONDICIONADO - Climatización
 
Aire acondicionado - cálculo simplificado del equipo
Aire acondicionado - cálculo simplificado del equipo Aire acondicionado - cálculo simplificado del equipo
Aire acondicionado - cálculo simplificado del equipo
 
CURSO TALLER AIRE ACONDICIONADO SPLIT PARED Año 2018- 2019
CURSO TALLER AIRE ACONDICIONADO SPLIT PARED  Año 2018- 2019CURSO TALLER AIRE ACONDICIONADO SPLIT PARED  Año 2018- 2019
CURSO TALLER AIRE ACONDICIONADO SPLIT PARED Año 2018- 2019
 
Curso refrigeración comercial y domestica
Curso refrigeración comercial y domesticaCurso refrigeración comercial y domestica
Curso refrigeración comercial y domestica
 
Calderos ata
Calderos ataCalderos ata
Calderos ata
 

Recently uploaded

Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
jaanualu31
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Kandungan 087776558899
 
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
mphochane1998
 
Introduction to Robotics in Mechanical Engineering.pptx
Introduction to Robotics in Mechanical Engineering.pptxIntroduction to Robotics in Mechanical Engineering.pptx
Introduction to Robotics in Mechanical Engineering.pptx
hublikarsn
 

Recently uploaded (20)

School management system project Report.pdf
School management system project Report.pdfSchool management system project Report.pdf
School management system project Report.pdf
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
 
Memory Interfacing of 8086 with DMA 8257
Memory Interfacing of 8086 with DMA 8257Memory Interfacing of 8086 with DMA 8257
Memory Interfacing of 8086 with DMA 8257
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
 
Introduction to Artificial Intelligence ( AI)
Introduction to Artificial Intelligence ( AI)Introduction to Artificial Intelligence ( AI)
Introduction to Artificial Intelligence ( AI)
 
8th International Conference on Soft Computing, Mathematics and Control (SMC ...
8th International Conference on Soft Computing, Mathematics and Control (SMC ...8th International Conference on Soft Computing, Mathematics and Control (SMC ...
8th International Conference on Soft Computing, Mathematics and Control (SMC ...
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
Augmented Reality (AR) with Augin Software.pptx
Augmented Reality (AR) with Augin Software.pptxAugmented Reality (AR) with Augin Software.pptx
Augmented Reality (AR) with Augin Software.pptx
 
Convergence of Robotics and Gen AI offers excellent opportunities for Entrepr...
Convergence of Robotics and Gen AI offers excellent opportunities for Entrepr...Convergence of Robotics and Gen AI offers excellent opportunities for Entrepr...
Convergence of Robotics and Gen AI offers excellent opportunities for Entrepr...
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
 
Introduction to Geographic Information Systems
Introduction to Geographic Information SystemsIntroduction to Geographic Information Systems
Introduction to Geographic Information Systems
 
Introduction to Robotics in Mechanical Engineering.pptx
Introduction to Robotics in Mechanical Engineering.pptxIntroduction to Robotics in Mechanical Engineering.pptx
Introduction to Robotics in Mechanical Engineering.pptx
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdf
 
Linux Systems Programming: Inter Process Communication (IPC) using Pipes
Linux Systems Programming: Inter Process Communication (IPC) using PipesLinux Systems Programming: Inter Process Communication (IPC) using Pipes
Linux Systems Programming: Inter Process Communication (IPC) using Pipes
 
👉 Yavatmal Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top Class Call Girl S...
👉 Yavatmal Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top Class Call Girl S...👉 Yavatmal Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top Class Call Girl S...
👉 Yavatmal Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top Class Call Girl S...
 
Online electricity billing project report..pdf
Online electricity billing project report..pdfOnline electricity billing project report..pdf
Online electricity billing project report..pdf
 

CURSO DE AIRE ACONDICIONADO FRÍO CALOR

  • 1. SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS
  • 2. UNIT OBJECTIVES After studying this unit, the reader should be able to • Describe the operation of reverse-cycle refrigeration (heat pumps) • Explain the function and operation of heat pump system components • List heat sources commonly used in heat pump systems • Discuss how heat pump efficiency is determined • Explain the concepts of coefficient of performance and auxiliary heat • Describe the control sequence of an air-to-air heat pump system • Explain how heat pump efficiency can be increased • Discuss preventive maintenance on a heat pump system
  • 3. REVERSE-CYCLE REFRIGERATION • Air-conditioning equipment can only pump heat in one direction • Heat pumps can pump heat two ways • Heat pumps have a four-way reversing valve • Four-way reversing valves control the direction of flow of the heat-laden vapor between the low- and high-pressure sides of the system
  • 4. Functions as the evaporator in the heating mode Functions as the condenser in the heating mode
  • 5. Functions as the condenser in the cooling mode Functions as the evaporator in the cooling mode
  • 6. HEAT SOURCES FOR WINTER • Air conditioners pump heat from low temperature inside the structure to a higher temperature outside the house • There is heat in a substance until it is cooled to -460°F • At 0°F outside air temperature, there is still 85% usable heat in the air • Heat pumps have the ability to absorb heat from the structure in the summertime and discharge it to the outside • Heat pumps are able to absorb heat from the outside air and discharge it to the inside of the structure
  • 7. THE FOUR-WAY VALVE • Allows the heat pump to pump heat in two directions • Diverts the discharge gas to either heat or cool the conditioned space • Refrigerant is directed from the compressor to the indoor coil in the heating mode • Refrigerant is directed from the compressor to the outdoor unit in the cooling mode • Controlled by the space temperature thermostat • Pilot-operated valve • Four piping connections on the valve
  • 8. Hot gas from compressor Suction gas to compressor Connected to indoor coil Connected to outdoor coil Moveable slide inside valve Direct-acting reversing valve is controlled directly by a solenoid coil
  • 9. Hot gas from compressor Suction gas to compressor Connected to indoor coil Connected to outdoor coil Pilot-operated reversing valve is controlled by the system pressures System high pressure pushes the slide to the right COOLING
  • 10. Hot gas from compressor Suction gas to compressor Connected to indoor coil Connected to outdoor coil Pilot-operated reversing valve is controlled by the system pressures HEATING
  • 11. TYPES OF HEAT PUMPS • Air is not the only source from which a heat pump ban absorb heat, but it is the most popular • Other heat sources for heat pumps include water and Earth • A typical water-to-air heat pump uses 3 gallons of water per minute in the heating cycle and 1.5 gallons of water per minute in the cooling mode per ton of refrigeration
  • 12. SOLAR-ASSISTED HEAT PUMPS • These pumps capture heat from the sun • The heat is then brought to usable levels for heating homes • Some systems are specially designed to operate in conjunction with solar heat
  • 13. THE AIR-TO-AIR HEAT PUMP • Most popular type • Basic sealed system components of a heat pump are the same as an air conditioner, but the terminology changes • In a heat pump, the terms indoor coil and outdoor coil are used • The function of each coil changes as the operating mode of the heat pump changes
  • 14. THE AIR-TO-AIR HEAT PUMP • Function of coils in the cooling mode – Indoor coil absorbs heat by boiling refrigerant at low temperature and pressure (evaporator) – Outdoor coil rejects heat by condensing a high- temperature and pressure vapor to a high- temperature and pressure vapor (condenser) – Refrigerant from the compressor is first pumped to the outdoor coil
  • 15. Hot gas from compressor Suction gas to compressor Connected to indoor coil Connected to outdoor coil
  • 16.
  • 17. THE AIR-TO-AIR HEAT PUMP • Function of coils in the heating mode – Outdoor coil absorbs heat by boiling refrigerant at low temperature and pressure (evaporator) – Indoor coil rejects heat by condensing a high- temperature and pressure vapor to a high-temperature and pressure vapor (condenser) – Hot gas from the compressor is first pumped to the indoor coil
  • 18. Hot gas from compressor Suction gas to compressor Connected to indoor coil Connected to outdoor coil
  • 19.
  • 20. THE AIR-TO-AIR HEAT PUMP • Mode of operation is determined by which way the hot gas from the compressor is flowing • Mode of operation can be determined by touching the gas line to the indoor coil – In the cooling mode, the gas line will feel cool – In the heating mode, the gas line will feel hot
  • 21. REFRIGERANT LINE IDENTIFICATION • The large diameter line is called the gas line because only refrigerant vapor flows through it • The gas line is a cold gas line in the summer and a hot gas line in the winter • The smaller diameter line is called the liquid line because only liquid refrigerant travels through it • During the cooling mode, the liquid travels to the indoor coil • During the heating mode, the liquid travels to the outdoor coil
  • 22. Indoor Unit Outdoor Unit HEAT PUMP OPERATING IN THE HEATING MODE Hot gas from compressor High pressure liquid to metering device and evaporator
  • 23. Indoor Unit Outdoor Unit HEAT PUMP OPERATING IN THE COOLING MODE Cool suction gas to compressor High pressure liquid to metering device and evaporator
  • 24. METERING DEVICES • Specially designed for heat pump applications • There must be a metering device at the outdoor unit in the heating mode • There must be a metering device at the indoor coil in the cooling mode
  • 25. THERMOSTATIC EXPANSION VALVES (TEV, TXV) • Maintains Desired superheat in the evaporator • Check valves are piped parallel to the TXV to allow refrigerant to bypass the control when needed • Heating mode – The refrigerant flows through the TXV at the outdoor coil – The refrigerant bypasses the TXV at the indoor coil • Cooling mode – The refrigerant flows through the TXV at the indoor coil – The refrigerant bypasses the TXV at the outdoor coil
  • 26.
  • 27.
  • 28. THE CAPILLARY TUBE • Commonly used on heat pumps • Will allow refrigerant to flow in both directions • Sometimes two capillary tubes are used with check valves • There must be a drier/strainer at the inlet of the capillary tube to ensure that the tube does not get clogged
  • 30. COMBINATIONS OF METERING DEVICES • Uses the capillary tube at the indoor coil – Used in the cooling mode – Load is relatively constant in the warmer months • Uses a thermostatic expansion valve at the outdoor coil – Used in the heating mode – Allows system to reach maximum efficiency quickly
  • 31. ELECTRONIC EXPANSION DEVICES • Can meter refrigerant in both directions • If indoor and outdoor coils are close together, one device can be used • The correct superheat will be maintained in both heating and cooling modes
  • 32. ORIFICE METERING DEVICES • Used in conjunction with check valves • One device is located at each coil • The bore at the indoor coil is larger than the bore at the outdoor coil • Normally used with a bi-flow filter drier
  • 33. LIQUID LINE ACCESSORIES • Two standard filter driers can be used on systems with check valves – Only one drier will be in the refrigeration circuit at a time – They are installed with the arrows pointing in the same direction as the check valves • Bi-flow filter driers – Two driers in one – Designed for heat pump applications
  • 34. Check valve closed Refrigerant from outdoor coil Refrigerant to indoor coil COOLING MODE
  • 35. Check valve closed Refrigerant to outdoor coil Refrigerant from indoor coil HEATING MODE
  • 36. APPLICATION OF THE AIR-TO-AIR HEAT PUMP • Usually installed in milder climates (temperatures as low as 10°) • In the winter, the outdoor coil absorbs heat • Difference between outdoor and evaporator temperature is about 25° • If outside temperature is 10°, the refrigerant boils at approximately -15° • The compressor and the system lose efficiency as the evaporator temperature goes down • The system loses capacity as the outside temperature drops
  • 37. AUXILIARY HEAT • Required when the heat pump cannot provide all the heat a structure needs • The heat pump is the primary heat source • Auxiliary heat could be electric, oil or gas • Electric heat is the most common auxiliary heat used • As the outside temperature drops, the structure requires more heat
  • 38. BALANCE POINT • Balance point occurs when the heat pump can pump in exactly as much heat as the structure is leaking out • Above the balance point, the heat pump will cycle on and off • Below the balance point, the heat pump will run continuously and second stage (auxiliary) heat will be energized
  • 39. COEFFICIENT OF PERFORMANCE • One watt of usable heat is supplied for each watt of energy purchased – Using electric resistance heat – This is called 100% efficient – Coefficient of performance (COP) of 1:1 – The output is the same as the input • Air-to-air heat pumps can have a COP of 3.5:1 – When 1 watt of electrical energy is used by the compressor, it can furnish 3.5 watts of usable heat (COP is 3.5:1)
  • 40. COEFFICIENT OF PERFORMANCE • High COP only occurs during higher outdoor winter temperatures • A heat pump’s COP falls as the outdoor temperature falls • A typical air-to-air heat pump has a COP of 1.5:1 at 0°F • Some manufacturers have controls to shut off the compressor at temperatures of 0 to 10°F • Water-to-air heat pumps might not need auxiliary heat since the heat source (water) temperature is constant • Water-to-air heat pumps have a COP rating as high as 4:1
  • 41. SPLIT-SYSTEM AIR-TO-AIR HEAT PUMPS • Air-to-air systems can be split or package type • Both heat pumps and straight cooling units look identical • Split systems require the installation of the gas and liquid refrigerant lines to connect the indoor and outdoor units
  • 42. Functions as the evaporator in the heating mode Functions as the condenser in the heating mode Field installed refrigerant lines
  • 43. THE INDOOR UNIT • The part of the system that circulates the air within the structure • It contains the fan and coil and often the electric strip heaters • The refrigerant coil must be located in the airstream before the auxiliary heating coil • The indoor unit may be a gas or oil fired furnace
  • 44. • If gas or oil furnace is the indoor unit, the coil must be located in the outlet airstream of the furnace • If a gas or oil furnace is used, the heat pump will not operate when they are operating • Heat pumps added to electric furnaces should have the coil located after the heat strips THE INDOOR UNIT
  • 45. AIR TEMPERATURE OF THE CONDITIONED AIR • Air temperatures of a heat pump are not as hot as with fossil-fuel equipment • Maximum heat pump air supply temperatures are around 100°F • Most heat pumps require a minimum of 400 cfm per ton of refrigeration • Supply air temperature will fall when outside air temperatures drop
  • 46. Supply duct Return air from the occupied space (75°F) Air handler (condenser in winter) Heated air (100°F)
  • 47. THE OUTDOOR UNIT INSTALLATION • Much like a regular air-conditioning installation • Must have good air circulation around it • Prevailing winds affect performance • In the wintertime, the outdoor coil will collect moisture and the moisture will freeze on the coil • Outdoor coil should be installed so it is raised above the ground pad to allow defrost water to run to the ground • A defrost system is provided to defrost the ice from the outdoor coil
  • 48. PACKAGE AIR-TO-AIR HEAT PUMPS • Has all the sealed system and electrical components in one housing • Works much the same way as a packaged air- conditioning unit • Only one power supply required • Supply and return ductwork must be field installed
  • 49. Package heat pump system Supply and return ducts are field installed
  • 50. CONTROLS FOR AIR-TO-AIR HEAT PUMPS • Controls are different than other heating/cooling equipment • In a heat pump, there are two heating systems and one cooling system • Auxiliary heating system must be operated as a system by itself in case the heat pump fails • Auxiliary heat is referred to as emergency heat when used because of heat pump failure • The space thermostat is the key to controlling the system • Normally, a two-stage heating and two-stage cooling thermostat is used
  • 51. CONTROLS FOR AIR-TO-AIR HEAT PUMPS • Automatic changeover thermostat changes automatically between heating and cooling modes • Cooling cycle controls – Thermostat contacts control the operation of the compressor, outdoor fan motor, and reversing valve coil – When the thermostat is satisfied, the compressor, outdoor fan motor, and indoor fan motor are de-energized – The reversing valve solenoid coil remains energized
  • 52. Heat Cool 1ST 1ST 2ND 2ND H(Y) 1(W) O C(Y) FIRST STAGE COOLING (SIMPLIFIED) Outdoor unit 4-way reversing valve coil energized R O
  • 53. Heat Cool 1ST 1ST 2ND 2ND H(Y) 1(W) O C(Y) SECOND STAGE COOLING (SIMPLIFIED) Outdoor unit 4-way reversing valve coil energized R O Y Compressor contactor coil energized
  • 54. CONTROLS FOR AIR-TO-AIR HEAT PUMPS • Space heating control – Thermostat controls compressor, outdoor fan motor, and indoor fan motor operation – Excessively cold temperatures energize second- stage heat – Second-stage heat cycles on and off to assist the heat pump
  • 55. Heat Cool 1ST 1ST 2ND 2ND H(Y) 1(W) O C(Y) FIRST STAGE HEATING (SIMPLIFIED) Outdoor unit R Y Compressor contactor coil energized
  • 56. Heat Cool 1ST 1ST 2ND 2ND H(Y) 1(W) O C(Y) SECOND STAGE HEATING (SIMPLIFIED) Outdoor unit R Y Compressor contactor coil energized
  • 57. Heat Cool 1ST 1ST 2ND 2ND H(Y) 1(W) O C(Y) SECOND STAGE HEATING WITH OUTDOOR THERMOSTATS (SIMPLIFIED) Outdoor unit R Y Compressor contactor coil energized Outdoor thermostats for electric heaters
  • 58. CONTROLS FOR AIR-TO-AIR HEAT PUMPS • Balance point – Point at which the heat pump can satisfy the load without shutting down – May be multiple balance points • Electric heaters are energized at different temperatures – Only the minimum number of heaters is energized at a time – Conserves energy – Auxiliary heat operation indicated by signal light on thermostat
  • 59. CONTROLS FOR AIR-TO-AIR HEAT PUMPS • Emergency heat mode – Used in the event of heat pump failure – All heating elements are energized – Signal light on thermostat • Heat anticipators – Found on heat pump thermostats and conventional thermostats – Most heat pump thermostats are equipped with two
  • 61. THE DEFROST CYCLE • Defrosts ice from outside coil during winter operation • Outdoor coil operates below freezing anytime the outside air is below 45°F • Outdoor coil operates 20° to 25°F below the outside air temperature • The need for defrost varies depending on outside air temperatures and conditions • The more moisture in the air, the more frost that forms on the outdoor coil • Defrost affects the efficiency of the systems
  • 62. HEATING SEASONAL PERFORMANCE FACTOR (HSPF) • Seasonal performance for particular piece of equipment • Breaks the country into six zones • Used to calculate operation costs • Considers average number and length of defrost cycles per year • Considers whether auxiliary heaters are energized during defrost • SEER and HSPF are results of federal energy policies
  • 63. HEAT PUMP DEFROST • Air-to-air heat pumps accomplish defrost by stopping the outdoor fan and cycling unit into cooling mode • During defrost, one stage of strip heat is turned on • The system is cooling and heating at the same time during defrost • Demand defrost means defrosting only when needed • Combinations of time, temperature, and pressure drop across the outdoor coil are also used in some systems to determine when defrost is needed
  • 64. INITIATING THE DEFROST CYCLE • Manufacturers design the systems to start defrost when frost affects performance • Some use time and temperature initiated defrost systems • Both conditions must be met before defrost will be activated • Coil temperature sensing devices will close around outdoor coil temperature of 25° • Typically, the timer will run any time the compressor runs
  • 65. 4-way reversing valve coil L1 L2 Timer motor Defrost relay Outdoor fanOutdoor coil thermostat TIME AND TEMPERATURE INITIATED DEFROST
  • 66. INITIATING THE DEFROST CYCLE • Some systems will also include a pressure switch along with the temperature and timer function • When ice forms on the coil, the pressure switch closes • Time, temperature, and pressure defrost systems ensure that there is ice buildup on the outdoor coil
  • 67. 4-way reversing valve coil L1 L2 Timer motor Defrost relay Outdoor fanOutdoor coil stat TIME, TEMPERATURE AND PRESSURE INITIATED DEFROST Pressure
  • 68. TERMINATING THE DEFROST CYLE • Stopping the defrost is as important as starting the defrost • Time, temperature, and pressure can all be used to terminate the defrost cycle • Temperature sensors used for the defrosting function will open at 50°F • 10 minutes is the normal maximum time allowed for defrost cycle
  • 69. 4-way reversing valve coil L1 L2 Timer motor Defrost relay Outdoor fanOutdoor coil thermostat TIME OR TEMPERATURE TERMINATED DEFROST
  • 70. ELECTRONIC CONTROL OF DEFROST • Electronic timers and thermistors used to control defrost • More accurate control than non-electronic methods • Can incorporate time and temperature features into a single unit
  • 71. INDOOR FAN MOTOR CONTROL • In a heat pump, the fan must be started at the beginning of each mode of operation • The indoor fan is started with the thermostat • Fan switch terminal function is normally the G terminal on the thermostat • The indoor fan motor often operates during defrost – Circulates air to prevent coil freezing – Air is tempered to prevent cold air from being introduced to the occupied space
  • 72. AUXILIARY HEAT • Usually accomplished with electric heat • Required to assist the heat pump when it cannot provide all the heat the structure needs • Also used as emergency heat when the heat pump needs service • Heaters also energized during defrost
  • 73. SERVICING THE AIR-TO-AIR HEAT PUMP • Much like servicing a refrigeration system • During the cooling mode, system is operating as a high- temperature refrigeration system • During the heating mode, system is operating as a low- temperature refrigeration system • Servicing of the system is divided into electrical and mechanical • The heat pump may run for days and not stop when outdoor temperatures are below the balance point
  • 74. TROUBLESHOOTING MECHANICAL PROBLEMS • Can be hard to identify in a heat pump, particularly in winter operation • Summer operation of a heat pump is similar to an air-conditioning unit • Mechanical problems are solved with gage manifolds, wet-bulb and dry-bulb thermometers, and air-measuring instruments
  • 75. TROUBLESHOOTING THE FOUR-WAY VALVE • Common problems: stuck valve, defection coil and internal leaks • Check to see if coil is energized • A warm coil indicates power is being supplied to the coil • Place a screwdriver on the surface of the coil to sense magnetic field • Check for voltage supplied to the coil • Defective coils can be replaced without changing the entire valve
  • 76. TROUBLESHOOTING THE FOUR-WAY VALVE • Four-way valves leaking through can be confused with a compressor that is not pumping to capacity • Capacity of the system will not be normal in summer or winter cycles • Check the temperature of the low-side line, the suction line from the evaporator, and the permanent suction line between the four-way valve and the compressor • In this check, the temperature difference should not be more than about 3°F
  • 77. Hot gas from compressor Suction gas to compressor Connected to indoor coil Connected to outdoor coil 50°F 60°F Leaking reversing valve in the cooling mode
  • 78. Hot gas from compressor Suction gas to compressor Connected to indoor coil Connected to outdoor coil Leaking reversing valve in the heating mode 30°F 40°F
  • 79. CHECKING THE CHARGE • Most heat pumps have a critical refrigerant charge • If systems are low on charge, technicians must locate and repair leaks • Caution should be taken when charging systems with suction accumulators • Suction accumulators store part of the charge in the winter mode and will boil out later
  • 80. CHECKING THE CHARGE • Sweating suction-line accumulator – When checking or charging a system, heat the accumulator by running water over it to drive the refrigerant out of it – Often the accumulator will frost or sweat at a particular level if liquid refrigerant is contained in it
  • 81. SPECIAL APPLICATION FOR HEAT PUMPS • Use of oil or gas furnaces for auxiliary heat • More efficient applications than auxiliary electric heat • The heat pump coil must be installed downstream of the oil or gas heat exchanger • The air must flow through the furnace heat exchanger before the heat pump coil • The oil or gas furnace must not operate at the same time that the heat pump is operating
  • 82. HEAT PUMPS USING SCROLL COMPRESSORS • Ideally suited for heat pump application because of its pumping characteristics • Scrolls do not lose as much capacity as reciprocating compressors • Scroll compressor pressures are about the same as reciprocating compressors • Scroll compressors are discharge gas cooled,
  • 83. • Scroll compressors have a check valve in the discharge leaving the compressor to prevent pressures from equalizing through the compressor during the off cycle • Scroll compressors normally do not require a suction-line accumulator because they are not as sensitive to liquid floodback HEAT PUMPS USING SCROLL COMPRESSORS
  • 84. HEAT PUMP SYSTEMS WITH VARIABLE-SPEED MOTORS • Use of variable-speed motors for the compressor and both fan motors is the method used to improve system efficiency in heat pump systems • Sized closer to the heating requirements of the structure at full load and will run at part load and reduced power in warmer months • Less auxiliary heat is required for these systems • Variable speed is accomplished with electronically controlled motors
  • 85. SUMMARY - 1 • Heat pumps can pump heat two ways to provide both heating and cooling • Four-way reversing valves control the direction of flow of the heat-laden vapor between the low- and high- pressure sides of the system • In the cooling mode, the outdoor coil functions as the condenser and the indoor coil functions as the evaporator • In the heating mode, the outdoor coil functions as the evaporator and the indoor coil functions as the condenser
  • 86. SUMMARY - 2 • Metering devices are located at the inlet of both the indoor and outdoor coils • Check valves are used to bypass the metering device that should not be in the active refrigerant circuit • Bidirectional or bi-flow filter driers are two driers in a single shell and are designed for heat pump applications • In the heating mode, heat pumps lose efficiency as the outside ambient temperature drops • Auxiliary heat is required when the heat pump cannot provide all the heat a structure needs
  • 87. SUMMARY - 3 • Balance point occurs when the heat pump can pump in exactly as much heat as the structure is leaking out • Coefficient of performance is the ratio of usable heat (in watts) produced from each watt of energy purchased • In winter operation, the COP increases as the outside ambient temperature increases • Split heat pump systems require the installation of gas and liquid lines to connect the indoor and outdoor units • The indoor unit contains the fan and coil and often the electric strip heaters
  • 88. SUMMARY - 4 • Maximum air supply temperatures are around 100°F • Outdoor coil should be installed so it is raised above the ground pad to allow defrost water to run to the ground • A defrost system is provided to defrost the ice from the outdoor coil • Package heat pump systems have all system and electrical components in one housing • There are two heating systems and one cooling system • Auxiliary heating system must be operated as a system by itself in case the heat pump fails
  • 89. SUMMARY - 5 • Automatic changeover thermostat changes automatically between heating and cooling modes • Emergency heat mode is used in the event of heat pump failure • The need for defrost varies depending on outside air temperatures and conditions • The more moisture in the air, the more frost that forms on the outdoor coil • Defrost affects the efficiency of the systems • Air-to-air heat pumps accomplish defrost by stopping the outdoor fan and cycling unit into cooling mode
  • 90. SUMMARY - 6 • Combinations of time, temperature, and pressure drop across the outdoor coil are also used in some systems to determine when defrost is needed and when defrost is terminated • Defrost can also be controlled electronically • In a heat pump, the fan must be started at the beginning of each mode of operation • The indoor fan motor often operates during defrost • During the cooling mode, system is operating as a high-temperature refrigeration system
  • 91. SUMMARY - 7 • During the heating mode, system is operating as a low- temperature refrigeration system • Common reversing valve problems include: stuck valve, defection coil and internal leaks • Temperature readings of the reversing valve connections can be taken to evaluate the valve • Most heat pumps are critically charged systems • If the system operated correctly in at least one mode, the refrigerant charge is correct
  • 92. SUMMARY - 8 • Oil or gas furnaces can be used for auxiliary heat • The heat pump coil must be installed downstream of the oil or gas heat exchanger • Scroll compressor is ideally suited for heat pump applications because of its pumping characteristics • Scroll compressors normally do not require a suction-line accumulator because they are not as sensitive to liquid floodback • Use of variable-speed motors for the compressor and both fan motors is the method used to improve system efficiency in heat pump systems