All buildings interact with the ground for its ability to support their foundations. However, very few buildings interact with the ground for its ability to provide thermal energy storage. We have all experienced the moderate temperatures within a cave at depths of just a few metres. These temperatures are a function of average annual air temperature and are the result of the ground absorbing and storing solar energy. The use of this indirect and renewable solar energy can provide significant energy savings for heating and cooling systems.
A Ground Heat Exchanger (GHX) provides the ability to utilise the ground for thermal energy storage, essentially transforming the ground into a thermal battery. It enables us to extract heat from it in winter (heat source) and return that heat in summer (heat sink). It is a dynamic thermal battery that operates both simultaneously and over the annual heating / cooling cycle.
This presentation will provide an overview of how the ground is being utilised for its thermal energy storage capabilities around the world, with focus on a local installation at the Tumut Council owned Riverina Highlands Building, located in Tumut NSW. The installation has provided Council with energy savings on heating and cooling of 80 %, reduced peak energy loads by 40%, reduced maintenance costs and, importantly, provided significantly higher levels of occupant comfort. This has also increased the capacity and effectiveness of the concurrently installed solar PV array and will ensure that future solar energy storage will have greater impact.
Thermal Potential in the Built EnvironmentYale Carden
HVAC systems have traditionally used the local ambient air (heating and cooling) or fossil fuels (predominantly heating through combustion) as their heat source and heat sink. Thermal storage is still a relatively new application and typically requires large volumes of water or ice.
This paper explores the available thermal potential within the built environment and how the utilisation of this thermal potential can provide efficient heating, cooling and hot water as well as thermal storage. In some instances, this may be the local ambient air, less likely it will be fossil fuels.
More likely, it includes the thermal potential within the ground, water bodies and infrastructure such as subways, water, sewer, building foundations and other buildings as well as artificial thermal storage such as phase change materials.
The key is to identify the optimal thermal sources, sinks and storages for a given building at a given location and climate. Then, an integrated approach using optimised control strategies, including predictive capabilities, will enable a building to access these various thermal sources at the thermally optimal time to provide significant energy savings and enhanced operation.
Such an integrated approach also maximises the availability of on-site renewable power generation, further increasing energy savings, decreasing the typical cooling peak demand and increasing energy productivity.
Small Council, Big Vision, Bigger Savings - AIRAH Pre-loved Buildings 2014Yale Carden
Presentation showing the incredible energy savings potential of geoexchange / ground source heat pumps for heating and cooling commercial buildings. This presentation was delivered at the AIRAH Pre-loved Buildings Conference in Brisbane, Australia in October 2014.
Titled Small Council, Big Vision, Bigger Savings, it takes the audience on the journey of this project from initial concept through to completion. It discussed both the incredible energy and dollar savings while also addresses the importance of the project team and their importance in delivering what was a truly great project.
Geoexchange and Thermal Potential at GeoscienceYale Carden
Geoscience Australia was one of the original geoexchange
or GSHP systems in Australia. Now over 20 years old, the building recently hosted an information session on electrification of heating and cooling in the ACT. Speakers included ACT Government representative as well as this presentation on thermal potential and the role of renewable thermal energy in the removal of thermal gas from our buildings.
IGSHPA Presentation: Las Vegas, October 2013Yale Carden
Presentation in my role as Founding President of the Australasian Ground Source Heat Pump Association (AGSHPA). AGSHPA is our local chapter of the International Ground Source Heat Pump Association (IGSHPA). Awkward acronyms but we will work with what we have.
The focus of this presentation was to provide a snapshot of the geoexchange or ground source heat pump industry in Australia and New Zealand.
Using the Ground for Thermal Energy Storage: The Experience of the Riverina H...Yale Carden
All buildings interact with the ground for its ability to support their foundations. However, very few buildings interact with the ground for its ability to provide thermal energy storage. We have all experienced the moderate temperatures within a cave at depths of just a few metres. These temperatures are a function of average annual air temperature and are the result of the ground absorbing and storing solar energy. The use of this indirect and renewable solar energy can provide significant energy savings for heating and cooling systems.
A Ground Heat Exchanger (GHX) provides the ability to utilise the ground for thermal energy storage, essentially transforming the ground into a thermal battery. It enables us to extract heat from it in winter (heat source) and return that heat in summer (heat sink). It is a dynamic thermal battery that operates both simultaneously and over the annual heating / cooling cycle.
This presentation will provide an overview of how the ground is being utilised for its thermal energy storage capabilities around the world, with focus on a local installation at the Tumut Council owned Riverina Highlands Building, located in Tumut NSW. The installation has provided Council with energy savings on heating and cooling of 80 %, reduced peak energy loads by 40%, reduced maintenance costs and, importantly, provided significantly higher levels of occupant comfort. This has also increased the capacity and effectiveness of the concurrently installed solar PV array and will ensure that future solar energy storage will have greater impact.
Thermal Potential in the Built EnvironmentYale Carden
HVAC systems have traditionally used the local ambient air (heating and cooling) or fossil fuels (predominantly heating through combustion) as their heat source and heat sink. Thermal storage is still a relatively new application and typically requires large volumes of water or ice.
This paper explores the available thermal potential within the built environment and how the utilisation of this thermal potential can provide efficient heating, cooling and hot water as well as thermal storage. In some instances, this may be the local ambient air, less likely it will be fossil fuels.
More likely, it includes the thermal potential within the ground, water bodies and infrastructure such as subways, water, sewer, building foundations and other buildings as well as artificial thermal storage such as phase change materials.
The key is to identify the optimal thermal sources, sinks and storages for a given building at a given location and climate. Then, an integrated approach using optimised control strategies, including predictive capabilities, will enable a building to access these various thermal sources at the thermally optimal time to provide significant energy savings and enhanced operation.
Such an integrated approach also maximises the availability of on-site renewable power generation, further increasing energy savings, decreasing the typical cooling peak demand and increasing energy productivity.
Small Council, Big Vision, Bigger Savings - AIRAH Pre-loved Buildings 2014Yale Carden
Presentation showing the incredible energy savings potential of geoexchange / ground source heat pumps for heating and cooling commercial buildings. This presentation was delivered at the AIRAH Pre-loved Buildings Conference in Brisbane, Australia in October 2014.
Titled Small Council, Big Vision, Bigger Savings, it takes the audience on the journey of this project from initial concept through to completion. It discussed both the incredible energy and dollar savings while also addresses the importance of the project team and their importance in delivering what was a truly great project.
Geoexchange and Thermal Potential at GeoscienceYale Carden
Geoscience Australia was one of the original geoexchange
or GSHP systems in Australia. Now over 20 years old, the building recently hosted an information session on electrification of heating and cooling in the ACT. Speakers included ACT Government representative as well as this presentation on thermal potential and the role of renewable thermal energy in the removal of thermal gas from our buildings.
IGSHPA Presentation: Las Vegas, October 2013Yale Carden
Presentation in my role as Founding President of the Australasian Ground Source Heat Pump Association (AGSHPA). AGSHPA is our local chapter of the International Ground Source Heat Pump Association (IGSHPA). Awkward acronyms but we will work with what we have.
The focus of this presentation was to provide a snapshot of the geoexchange or ground source heat pump industry in Australia and New Zealand.
Presentation to the UK Energy Storage conference (UKES), November 25th to 27th 2015 at the University of Birmingham, UK. Dr John Barton and Dr Murray Thomson
Regression model for calculating the base load energy using the utility bills.Divyesh Kumar
The research aims to determine if the electricity consumption for the ST. Dana building at University of Michigan, Ann Arbor, can be calculated by using the utility bills and heating degree days for three different academic term. ANCOVA analysis, using R statistics, from the available utility bills and the monthly Heating degree day for past 3 years, showed that there are significant interaction between the heating degree days and the Winter and Fall academic-terms. However, the analysis failed to identify any interaction between the heating degree days and the summer term. Dana building’s base-load electricity consumption was calculated using the regression model for the winter term.
Fraunhofer IBP comparative tests with ecofective system EE2Gabriele Sorg
Comparative measurements by the Fraunhofer Institute for Building Physics IBP confirm by 13 percent less gas consumption using the energy efficiency management system EE2 from Ecofective, more information www.ecofective.com
ON THE INTEGRATION OF ROTARY HEATER IN GAS FIRED POWER PLANTS WITH POST-COMBUSTION CARBON CAPTURE: A PRELIMINARY EVALUATION - presentation by Laura Herraiz of the University of Edinburgh at the UKCCSRC Natural Gas CCS Network Meeting at GHGT-12, Austin, Texas, October 2014
High efficiency technologies for process cooling: a significant contribution ...CAREL Industries S.p.A
Roberto Sandano, Business Unit Manager HVAC OEM illustrates at XVII European Conference in Milan CAREL's latest Technology in Refrigeration and Air Conditioning
Performance optimization assessment for a proper heat pump technology functio...Premier Publishers
This investigation represents a thermodynamic assessment of thermal performance optimization for a proper heat pump technology suitable for district hot water production at (60-65) °C. The clean energy sources integrated with environment friendly refrigerants were studied to optimize and validate the use of Cascade heat pump technology at various configurations. Three pure, R744, R600a and R134a, and one azeotropic mixture R410A refrigerants were circulated at different cycle arrangements. Two Cascade systems (Three Cycles), single Cascade system (Two Cycles), and compound Cascade system (Three Cycles) were proposed for the present assessment. The low temperature cycle operated at evaporator temperature of (-15 to -2) °C and the high temperature condenser was set at a temperature of (70) °C. The single Cascade heat pump circulating R410A/R134a and the two Cascade R410A/R717/R134a systems showed the best heating coefficient of performance (COP). The former refrigerant pair exhibited higher heating (COP) than that of the latter by (3.6-5) % calculated at (22.5) °C low temperature cycle intermediate temperature for the whole range of test conditions. The lowest (COP) was experienced by the two Cascade heat pump technology circulating R744/R717/R134a and R744/R717/R600a refrigerant pairs. The compound Cascade heat pump is definitely a promising option for low temperature heat source technology on the long term basis due to its low running cost for heating load generation. The heating (COP) showed a range of (2 to 2.7) at (70 %) compressor isentropic efficiency according to the system type, refrigerant pair and operating conditions considered in the present work. Any improvement for the compressor isentropic efficiency provides a valuable augmentation for the heating (COP) of the Cascade heat pump.
The Friends of NELHA presented a 3 part workshop called Energy Efficiency and Auditing Workshop in Hawaii. This slideshow presentation by Dr. Roderick Hinman is the first section which discusses what electricity is, how it is measured, and how you can measure the electrical loads of each appliance in your home to make decisions that can save on your home electric bill.
This paper describes an experimental study of using the waste heat from a Panasonic Under-
Ceiling split room air - conditioner had a rated capacity of 3.51 kW (12,000 Btu/h). An under – ceiling
split type air conditioning for heating domestic water in private homes. Energy recovery improved the
performance, and the recovered energy could replace electricity completely for heating domestic water
use. An extra charge of refrigerant in the air-conditioner could prevent its compressor from over heating
during energy recovery. The experimental conducted on varies capacity of the range from 22.5 litres to
120 litres storage tank. Results show the water temperature increased lies in the range of 50 OC to 65
OC. It was found that, when the initial water temperature in the 22.5 litres storage tank 27 OC, the water
temperature reached 65 OC in 105 minutes. For 120 litres water, temperature increased from 27 OC to 62
OC,5 in 240 minutes.
Presentation to the UK Energy Storage conference (UKES), November 25th to 27th 2015 at the University of Birmingham, UK. Dr John Barton and Dr Murray Thomson
Regression model for calculating the base load energy using the utility bills.Divyesh Kumar
The research aims to determine if the electricity consumption for the ST. Dana building at University of Michigan, Ann Arbor, can be calculated by using the utility bills and heating degree days for three different academic term. ANCOVA analysis, using R statistics, from the available utility bills and the monthly Heating degree day for past 3 years, showed that there are significant interaction between the heating degree days and the Winter and Fall academic-terms. However, the analysis failed to identify any interaction between the heating degree days and the summer term. Dana building’s base-load electricity consumption was calculated using the regression model for the winter term.
Fraunhofer IBP comparative tests with ecofective system EE2Gabriele Sorg
Comparative measurements by the Fraunhofer Institute for Building Physics IBP confirm by 13 percent less gas consumption using the energy efficiency management system EE2 from Ecofective, more information www.ecofective.com
ON THE INTEGRATION OF ROTARY HEATER IN GAS FIRED POWER PLANTS WITH POST-COMBUSTION CARBON CAPTURE: A PRELIMINARY EVALUATION - presentation by Laura Herraiz of the University of Edinburgh at the UKCCSRC Natural Gas CCS Network Meeting at GHGT-12, Austin, Texas, October 2014
High efficiency technologies for process cooling: a significant contribution ...CAREL Industries S.p.A
Roberto Sandano, Business Unit Manager HVAC OEM illustrates at XVII European Conference in Milan CAREL's latest Technology in Refrigeration and Air Conditioning
Performance optimization assessment for a proper heat pump technology functio...Premier Publishers
This investigation represents a thermodynamic assessment of thermal performance optimization for a proper heat pump technology suitable for district hot water production at (60-65) °C. The clean energy sources integrated with environment friendly refrigerants were studied to optimize and validate the use of Cascade heat pump technology at various configurations. Three pure, R744, R600a and R134a, and one azeotropic mixture R410A refrigerants were circulated at different cycle arrangements. Two Cascade systems (Three Cycles), single Cascade system (Two Cycles), and compound Cascade system (Three Cycles) were proposed for the present assessment. The low temperature cycle operated at evaporator temperature of (-15 to -2) °C and the high temperature condenser was set at a temperature of (70) °C. The single Cascade heat pump circulating R410A/R134a and the two Cascade R410A/R717/R134a systems showed the best heating coefficient of performance (COP). The former refrigerant pair exhibited higher heating (COP) than that of the latter by (3.6-5) % calculated at (22.5) °C low temperature cycle intermediate temperature for the whole range of test conditions. The lowest (COP) was experienced by the two Cascade heat pump technology circulating R744/R717/R134a and R744/R717/R600a refrigerant pairs. The compound Cascade heat pump is definitely a promising option for low temperature heat source technology on the long term basis due to its low running cost for heating load generation. The heating (COP) showed a range of (2 to 2.7) at (70 %) compressor isentropic efficiency according to the system type, refrigerant pair and operating conditions considered in the present work. Any improvement for the compressor isentropic efficiency provides a valuable augmentation for the heating (COP) of the Cascade heat pump.
The Friends of NELHA presented a 3 part workshop called Energy Efficiency and Auditing Workshop in Hawaii. This slideshow presentation by Dr. Roderick Hinman is the first section which discusses what electricity is, how it is measured, and how you can measure the electrical loads of each appliance in your home to make decisions that can save on your home electric bill.
This paper describes an experimental study of using the waste heat from a Panasonic Under-
Ceiling split room air - conditioner had a rated capacity of 3.51 kW (12,000 Btu/h). An under – ceiling
split type air conditioning for heating domestic water in private homes. Energy recovery improved the
performance, and the recovered energy could replace electricity completely for heating domestic water
use. An extra charge of refrigerant in the air-conditioner could prevent its compressor from over heating
during energy recovery. The experimental conducted on varies capacity of the range from 22.5 litres to
120 litres storage tank. Results show the water temperature increased lies in the range of 50 OC to 65
OC. It was found that, when the initial water temperature in the 22.5 litres storage tank 27 OC, the water
temperature reached 65 OC in 105 minutes. For 120 litres water, temperature increased from 27 OC to 62
OC,5 in 240 minutes.
ENERGY SAVINGS IN DOMESTIC REFRIGERATOR USING TWO THERMOELECTRIC MODULES& WAT...ijiert bestjournal
The study deals with hybrid refrigerator that combi nes thermoelectric (TER) and vapor compression refrigeration (VCR) and also entail exp erimental details of combined VCR & TER system. Objective is to configure hybrid refrig erator by introducing two Peltier modules (TER) in domestic refrigerator and to analyze compr essor cycles of conventional refrigerator with TER to increase energy efficiency of vapor com pression cycle. For this comparison of standalone VCR and Hybrid VCR+TER system is carried out. A Peltier module of size 4cm � 4cm � .4cm is introduced in the refrigerator cabinet & t he effect on energy efficiency in terms of trip time of compressor is recorded. The e ffect of Air cooled & Water cooled condenser with TER in different structures is also investigated. It is observed that by introducing thermoelectric effect,energy consumpti on of VCR is reduced by almost 10.92% annually,which accounts for 80 units per year. Thu s ultimately improving COP of the hybrid system with better control on temperature over the total run time.
Upgrading of Low Temperature Solar Heat with Cascade Vapor Compression and Ab...IJMER
International Journal of Modern Engineering Research (IJMER) is Peer reviewed, online Journal. It serves as an international archival forum of scholarly research related to engineering and science education.
International Journal of Modern Engineering Research (IJMER) covers all the fields of engineering and science: Electrical Engineering, Mechanical Engineering, Civil Engineering, Chemical Engineering, Computer Engineering, Agricultural Engineering, Aerospace Engineering, Thermodynamics, Structural Engineering, Control Engineering, Robotics, Mechatronics, Fluid Mechanics, Nanotechnology, Simulators, Web-based Learning, Remote Laboratories, Engineering Design Methods, Education Research, Students' Satisfaction and Motivation, Global Projects, and Assessment…. And many more.
International Journal of Engineering and Science Invention (IJESI) is an international journal intended for professionals and researchers in all fields of computer science and electronics. IJESI publishes research articles and reviews within the whole field Engineering Science and Technology, new teaching methods, assessment, validation and the impact of new technologies and it will continue to provide information on the latest trends and developments in this ever-expanding subject. The publications of papers are selected through double peer reviewed to ensure originality, relevance, and readability. The articles published in our journal can be accessed online.
International Journal of Engineering Research and Applications (IJERA) is an open access online peer reviewed international journal that publishes research and review articles in the fields of Computer Science, Neural Networks, Electrical Engineering, Software Engineering, Information Technology, Mechanical Engineering, Chemical Engineering, Plastic Engineering, Food Technology, Textile Engineering, Nano Technology & science, Power Electronics, Electronics & Communication Engineering, Computational mathematics, Image processing, Civil Engineering, Structural Engineering, Environmental Engineering, VLSI Testing & Low Power VLSI Design etc.
Load Shifting Assessment of Residential Heat Pump System in JapanIEREK Press
With the economic growth and increasing requirement of indoor thermal comfort, the load of building sector presents a greater variability. This paper aims at analyzing the energy consumption characteristics and influencing factors of the residential heat pump system. Firstly, we selected residential households as investigated objective in Kitakyushu, Japan, and compared the energy saving performances of heat supply systems between heat pump and natural gas boiler. The results were based on real measured residential load during winter period, and calculated the cost saving performance of residential heat pump system compared with traditional natural gas boiler. We also did a survey of residential occupation behavior for the 12 selected residential customers. The result indicated that there was low relationship between power consumption and occupation hours, and the number of family members had a significant impact on the power consumption. The results indicate that residential heat pump system presented promising energy saving and cost reduction potential.
Load Shifting Assessment of Residential Heat Pump System in JapanIEREK Press
With the economic growth and increasing requirement of indoor thermal comfort, the load of building sector presents a greater variability. This paper aims at analyzing the energy consumption characteristics and influencing factors of the residential heat pump system. Firstly, we selected residential households as investigated objective in Kitakyushu, Japan, and compared the energy saving performances of heat supply systems between heat pump and natural gas boiler. The results were based on real measured residential load during winter period, and calculated the cost saving performance of residential heat pump system compared with traditional natural gas boiler. We also did a survey of residential occupation behavior for the 12 selected residential customers. The result indicated that there was low relationship between power consumption and occupation hours, and the number of family members had a significant impact on the power consumption. The results indicate that residential heat pump system presented promising energy saving and cost reduction potential
EXPERIMENTAL AND THEORTICAL STUDY OF THE THERMAL PERFORMANCE OF HEAT PIPE HEA...IAEME Publication
Heat pipe heat exchanger (HPHE) considers one of the most useful devices for the recovery of waste heat energy. An Experimental study has been carried out on air to –air HPHE constructed of thermosyphon heat pipes with distilled water as the working fluid and a fill ratio of 75% from the evaporator length. Its model was composed of 4 rows, each row contains 12 copper tubes, each tube have ID= 9.5 mm, OD=10mm and length =950 mm and the rows of tubes were arranged in a staggered manner. Aluminum wavy plate fins of 0.1mm thickness were fixed among the tubes to increase the heat transfer area. Tests were conducted at various flow rates (air flow rate through evaporator and condenser sections) ranged between 0.12 and 0.37 kg/s and at different temperatures of air entering evaporator section (90, 100,110) ℃ to indicate discontinuity in the effectiveness when the flow rate ratio equal to one .
EXPERIMENTAL INVESTIGATION OF WASTE HEAT RECOVERY SYSTEM FOR DOMESTIC REFRIGE...IAEME Publication
The objective of this project was to determine the energy savings associated with improved utilization of waste heat from a domestic refrigerator. Domestic refrigerators maybe operate
continuously to maintain proper food storage condition. The continual operation of this equipment accounts more electrical energy consumption. Furthermore, a significant amount of waste heat is rejected by the condensers of refrigerator.
In this communication, simulation studies of a borehole heat exchanger are worked out through computational
fluid dynamics (CFD) software. A two dimensional ( − ) realizable turbulent model with standard wall function is used to
evaluate the temperature variation along with depth of BHE, pitch optimization and to determine the effect of two
dimensionless parameters as ratio of pitch to borehole diameter and ratio of borehole to pipe diameter. The predicted results are
validated through experimental data; and statistical assessment shows a good agreement between simulated and experimental
results. The tube air temperature is proportional to depth in cooling mode and BHE can decrease the temperature of air by
13-14°C when ambient temperature observed by 41°C. The optimised pitch for 8 inch borehole and 2 inch diameter U-tube is
found to be 4 inch, however two U-tubes are recommended for enhanced performance. The effective borehole to tube diameter
ratio is estimated by 4. The BHE system can be used for heating and cooling of buildings it is a feasible solution for
sustainable development.
WASTE HEAT RECOVERY IN DOMESTIC REFRIGERATION SYSTEM IN THE APPLICATION OF WA...Journal For Research
Heat is the energy, so energy saving is one of the key matters for the protection of global environment. Heat also radiated from our domestic refrigerator. This waste heat from refrigerator will affect the environmental because as heat in the environment will increases it will cause global warming. So it is necessary that a significant effort should be made for conserving energy through waste heat recovery too. So An attempt has been made to utilize waste heat from condenser of refrigerator. This heat can be used for various of domestic and industrial purposes. In minimum constructional, maintenance and running cost, this system is very useful for domestic purpose. It is valuable alternative approach to increase overall efficiency and reuse the waste heat. The study has shown that such a system is technically feasible and economical. This system is a cabin that we are going to install over the head of the simple refrigerator, this cabin will be an arrangement of coils that will work as a heat exchanger for reuse of waste heat. These coils are hot coils of condenser of the refrigerator that will be modified and will put in the cabin. It can serve the purpose of cooking, geysers etc. Besides, the refrigerator may be used as conventional refrigerator. Further COP will also increase. Heat rejection may occur directly to the air in the case of a conventional household domestic refrigerator having air-cooled condenser. This system rejected less heat to the environment so it is safer in environmental aspects also.
Similar to An aquifer thermal storage system in a Belgian hospital: Long-term experimental evaluation of energy and cost savings (20)
Overview of the fundamental roles in Hydropower generation and the components involved in wider Electrical Engineering.
This paper presents the design and construction of hydroelectric dams from the hydrologist’s survey of the valley before construction, all aspects and involved disciplines, fluid dynamics, structural engineering, generation and mains frequency regulation to the very transmission of power through the network in the United Kingdom.
Author: Robbie Edward Sayers
Collaborators and co editors: Charlie Sims and Connor Healey.
(C) 2024 Robbie E. Sayers
Immunizing Image Classifiers Against Localized Adversary Attacksgerogepatton
This paper addresses the vulnerability of deep learning models, particularly convolutional neural networks
(CNN)s, to adversarial attacks and presents a proactive training technique designed to counter them. We
introduce a novel volumization algorithm, which transforms 2D images into 3D volumetric representations.
When combined with 3D convolution and deep curriculum learning optimization (CLO), itsignificantly improves
the immunity of models against localized universal attacks by up to 40%. We evaluate our proposed approach
using contemporary CNN architectures and the modified Canadian Institute for Advanced Research (CIFAR-10
and CIFAR-100) and ImageNet Large Scale Visual Recognition Challenge (ILSVRC12) datasets, showcasing
accuracy improvements over previous techniques. The results indicate that the combination of the volumetric
input and curriculum learning holds significant promise for mitigating adversarial attacks without necessitating
adversary training.
CW RADAR, FMCW RADAR, FMCW ALTIMETER, AND THEIR PARAMETERSveerababupersonal22
It consists of cw radar and fmcw radar ,range measurement,if amplifier and fmcw altimeterThe CW radar operates using continuous wave transmission, while the FMCW radar employs frequency-modulated continuous wave technology. Range measurement is a crucial aspect of radar systems, providing information about the distance to a target. The IF amplifier plays a key role in signal processing, amplifying intermediate frequency signals for further analysis. The FMCW altimeter utilizes frequency-modulated continuous wave technology to accurately measure altitude above a reference point.
Welcome to WIPAC Monthly the magazine brought to you by the LinkedIn Group Water Industry Process Automation & Control.
In this month's edition, along with this month's industry news to celebrate the 13 years since the group was created we have articles including
A case study of the used of Advanced Process Control at the Wastewater Treatment works at Lleida in Spain
A look back on an article on smart wastewater networks in order to see how the industry has measured up in the interim around the adoption of Digital Transformation in the Water Industry.
HEAP SORT ILLUSTRATED WITH HEAPIFY, BUILD HEAP FOR DYNAMIC ARRAYS.
Heap sort is a comparison-based sorting technique based on Binary Heap data structure. It is similar to the selection sort where we first find the minimum element and place the minimum element at the beginning. Repeat the same process for the remaining elements.
Forklift Classes Overview by Intella PartsIntella Parts
Discover the different forklift classes and their specific applications. Learn how to choose the right forklift for your needs to ensure safety, efficiency, and compliance in your operations.
For more technical information, visit our website https://intellaparts.com
Cosmetic shop management system project report.pdfKamal Acharya
Buying new cosmetic products is difficult. It can even be scary for those who have sensitive skin and are prone to skin trouble. The information needed to alleviate this problem is on the back of each product, but it's thought to interpret those ingredient lists unless you have a background in chemistry.
Instead of buying and hoping for the best, we can use data science to help us predict which products may be good fits for us. It includes various function programs to do the above mentioned tasks.
Data file handling has been effectively used in the program.
The automated cosmetic shop management system should deal with the automation of general workflow and administration process of the shop. The main processes of the system focus on customer's request where the system is able to search the most appropriate products and deliver it to the customers. It should help the employees to quickly identify the list of cosmetic product that have reached the minimum quantity and also keep a track of expired date for each cosmetic product. It should help the employees to find the rack number in which the product is placed.It is also Faster and more efficient way.
Cosmetic shop management system project report.pdf
An aquifer thermal storage system in a Belgian hospital: Long-term experimental evaluation of energy and cost savings
1. An aquifer thermal storage system
in a Belgian hospital: Long-term
experimental evaluation of energy
and cost savings
D. Vanhoudt, J. Desmedt, J. Van Bael, N. Robeyn, H. Hoes
Flemish Institute for Technological Research, Belgium.
Sayed Rasul
ID: 1015102008
Journal of Energy and Buildings
2. Objective
An aquifer thermal energy storage
system(ATES) was monitored in combination
with a heat pump for heating and cooling of
ventilation air in a Belgian hospital. The Study
analyzed the technical, economical and
ecological performance of the
ATES and heat pump system. Which allow
us to conclude on the operation and the
economy and ecological effect of the
system.
3. Introduction
Hospitals and health care buildings typically have
high energy demand for heating and cooling.
Conventional HVAC installations are energy
intensive and expensive. To reduce the energy use
and the emission of greenhouse gases by these
installations, energy efficient solutions operating at
the lowest cost is needed. In this case study an
integration of thermal energy storage for space
heating and cooling of buildings by using an aquifer
thermal energy storage (ATES) system was studied
over a three years period.
8. Monitoring System
Heat exchange by the groundwater circuit by
calculating the flow rate of the groundwater and
the inlet and outlet water temperatures.
Heat supplied by two heat pumps by calculating
the operating time of fixed flow pumps and the
inlet and outlet water temperatures of condensers
(evaporators).
Energy demand for heating and cooling of the
hospital is calculated by the AHU’s supply and
return temperatures and the corresponding flows.
Electricity consumption of the two heat pumps and
the groundwater pumps.
Ambient air temperature and relative humidity.
16. Conclusion
Energy balance shows that 81% of the total cooling energy
was mainly provided by the direct use for groundwater,while a
22% of the heating of the ventilation was provided by direct
use of groundwater.
The overall seasonal performance factor (SPF) for heating
was 5.9, while the cooling at an efficiency factor of 26.1.
The primary energy saving for the acclimatization of the
ventilation air reached 71% as compared to reference
installation composed of gas-fired boilers and cooling
machines.
CO2-emission reduction of 73% as compared to the
reference installation.
The overall economic analysis indicated a payback time of
8.4 years without subsidies and an annual cost reduction of
k€54 a year.