The document analyzes the performance of an 80-ton capacity air-cooled scroll chiller system using R-22 and R-407C refrigerants. Experimental results show the theoretical COP of R-22 is 4.166 but the actual COP is 2.227, while for R-407C the theoretical COP is 3.465 and actual COP is higher at 2.745. Based on these results, R-407C is concluded to be a viable alternative refrigerant to R-22 for air-cooled chilling systems and HVAC applications.