SlideShare a Scribd company logo
Journal of ELECTRICAL ENGINEERING, VOL 68 (2017), NO1, 54–60
Loss of excitation of synchronous generator
Vladim´ır Kriˇstof,
∗
Mari´an Meˇster
∗∗
This paper presents results of study of loss-of-excitation phenomena simulations. Loss of excitation is a very common fault
in synchronous machine operating and can be caused by short circuit of the field winding, unexpected field breaker open or
loss-of-excitation relay mal-operation. According to the statistic [1], the generator failure due to loss-of-excitation accounts
for 69 % of all generator failures. There has been concern over possible incorrect operation of the relay when operating the
generator in the under-excited region, during stable transient swings and during major system disturbances. This article can
serve as inputs for system operators in preparation of operation area or protection relaying area.
K e y w o r d s: loss of excitation, excitation system, synchronous generator, stability
1 Introduction
The loss of synchronism (stability) of synchronous gen-
erator and the subsequent transition to asynchronous op-
eration is a very serious and unfavorable operating condi-
tion. It occurs if the machine is not able to transmit the
electrical power (Pe ) corresponding to supplied mechan-
ical power (Pm ). This could be caused by the following
reasons:
– loss of excitation of synchronous generator (significant
decrease of internal electromotive force),
– weakening of the transmission grid (eg line outages),
– increasing of the transmitted power (threat for static
stability),
– etc.
Asynchronous operation of synchronous generator is ana-
lyzed eg in [2]. This article deals with the loss of excitation
of synchronous generator.
2 Excitation systems of synchronous machines
The essential function of excitation system is to supply
direct current for the power of synchronous machine ex-
citation winding. Furthermore, it has several protection
and control functions. The excitation system consists of
two relatively independent components — excitation reg-
ulator (automatic voltage regulator) and the exciter it-
self [3]. The exciter power makes up generally 0.2–0.8 %
of the generator power. The exciter voltage generally does
not exceed 1 kV so that its winding does not need addi-
tional insulation [2].
Basically there are static and rotating exciters. In ro-
tating exciters, the excitation current is obtained from
direct current generators (eventually alternative current
generators equipped with rectifiers). Since direct current
sources do not provide the necessary power, they are con-
nected into cascade. This is however followed by increas-
ing of equivalent exciter time constant (and thus worsen-
ing of exciter dynamics).
Basic components of static excitation systems are
thyristor rectifiers, controlled with excitation regulator
by means of thyristor ignition impulse circuits. This can
be performed in two ways via the transformer, namely
either from an independent source (so called independent
excitation) or directly from the generator (so called de-
pendent excitation). The main benefit of static excitation
systems is the speed with which the excitation voltage re-
sponds to the change of regulator voltage.
The excitation systems of synchronous machines are
subject of following requirements:
– keep the generator in a condition when it is possible
by (long) lines to transmit the power close to the limit
line power (ie enable the generator operation in the
area of so called artificial stability [4]),
– ensure sufficient dynamic stability reserve and damp-
ing of generator power swings after failure,
– maintain stability during change of properties of elec-
tric lines or grid to which the generator is connected,
– easily and reliably measure the parameters according
to which regulation occurs,
– high operating reliability.
An integral part of the excitation system is apart from
the exciter itself also the excitation regulator. The pri-
mary task of the excitation regulator is to maintain the
required voltage on generator terminals. In addition, the
excitation regulator generally fulfills most of the following
supplementary functions [3, 5]:
– limiter of rotor and stator current: protects generator
before stator or rotor circuit overloading,
– under-excitation limit control: main aim is to prevent
machine de-excitation (under-excitation) to the degree
∗
Power System Management s.r.o., Ondavsk´a 5, 040 01 Koˇsice, Slovakia, kristof.vladimir@gmail.com
∗∗
Vchodoslovensk´a distribuˇcn´a,
a.s., Mlynsk´a 31, 040 01 Koˇsice, Slovakia, marian.mester@gmail.com
DOI: 10.1515/jee-2017-0007, Print (till 2015) ISSN 1335-3632, On-line ISSN 1339-309X c 2017 FEI STU
Journal of ELECTRICAL ENGINEERING 68 (2017), NO1 55
90°
Pe (pu)
d
180°
0.2
0.6
1.0
1.4
1.8
Mechanical
power Pm
UB = 100 %
80 %
60 %
40 %
0° d(0)
Fig. 1. Power – angle characteristic for individual values of excita-
tion voltage UB
Out of step protection
R
x
xd
xd/2’
x xd t/2 +’
Loss of excitation
protection
Fig. 2. Measured trajectory in the impedance plane during loss of
excitation
where threat of its static stability arises, stator wind-
ing terminals warm up, etc,
– power system stabilizer: dampens electromechanical
swings that originate as result of commutations in the
grid,
– secondary regulator of reactive power: maintains reac-
tive power on desired value.
From the above presented facts it is obvious that excita-
tion systems are important components of both the gen-
erator as well as the electricity grid. Therefore, it is de-
sirable that they provide the highest possible operating
reliability. The outages or failures in excitation systems
can have very unfavorable operating consequences.
3 Loss of excitation protection
Loss of excitation of synchronous generator can be
caused by several factors, such as power supply outage,
exciter damage or short circuit in the excitation winding.
Regardless of the reason the loss of excitation represents a
high risk with regard to synchronous generator damage.
In addition, outage of synchronous generator with high
unit power represents a significant risk for the stability
of electricity grid. During loss of excitation the current in
excitation winding decreases (exponentially). Proportion-
ally also the internal electromotive force and the electro-
magnetic relation between the stator and rotor decrease.
This is reflected in gradual decrease of reactive power on
generator terminals. When the under-excitation limit is
achieved, the loss of synchronism occurs (the relation be-
tween the stator and rotor is already very week at this
time). This whole process is similar to loss of static sta-
bility of synchronous machine. The development of loss
of synchronism after loss of excitation can simply be ex-
plained by power characteristics. For the electric power
supplied with generator to grid under stabilized condi-
tions the following applies
Pe =
EGES
X
sin δ (1)
where EG is internal voltage of generator, ES – grid
voltage, X – transmission reactance and δ is rotor angle
(angle between EG and ES ).
The intersection between the turbine mechanical power
(Pm ) and power curve (P − δ) defines the operating ro-
tor angle (sometimes so called load angle). Decreasing
internal voltage of generator results in decreased power
curve (Fig. 1). As the power curve decreases the rotor an-
gle increases and gets close to the limit operating point
(δcrit = 90◦
). At this point the electric power supplied
by generator reaches its maximum level (for respective
operating conditions). The following subsequent decrease
of the power curve as result of loss of excitation will
cause that generator will no longer be able to transmit
the electric power corresponding to the mechanical power
of turbine. The imbalance (excessive mechanical power of
turbine) will be reflected in the generator rotor speeding
up. Generator speeding up will be then reflected in the
decreasing turbine power (corresponding to turbine reg-
ulator statics). Under certain circumstances, when the
decrease of the excitation voltage is successfully stopped
by machine operator, the new balanced operating point
(with worse operating conditions) will be achieved. The
resulting generator rotations are determined by turbine
regulator statics and grid “toughness” (in synchronous
operation of extensive grid the rotations generally do
not change, whereas in island mode operation the fre-
quency/rotations deviation can reach up to 5 % before
the machine is disconnected from the grid).
The loss of excitation is a transient phenomenon of
medium speed with the time interface of several seconds
(3 to 8 seconds according to [6]). The loss of excitation
represents a threat mainly from the following reasons [7]:
– stator overloading as result of significant supply of re-
active power from the grid (0.4 to 1.9-multiple of Sn ),
– warming up of rotor winding influenced by induced
currents,
– extensive swings of active power, which are typical for
asynchronous operation.
The loss of excitation can have adverse effect not only
on the generator itself, but also on the whole grid and
adjacent generators — mainly if they are connected to
56 V. Kriˇstof , M. Meˇster: LOSS OF EXCITATION OF SYNCHRONOUS GENERATOR
High
load
R
x
xd
xd/2’
Low
load
1.0 pu
0
Zone 1
Zone 2
Impedance locus during
loss of excitation
R
x
xs
xd/2’
1.1 xd
0
Zone 1
Zone 2
Directional
element
R
x
xs
xd/2’
xd
0
Zone 1
Zone 2 R
x
5% xq
xq
0
Fig. 3. Impedance patterns of loss of excitation protection
G2 G3
G1
Z1 Z2
16.5 kV
230 kV
230 kV230 kV
18 kV 230 kV 230 kV
Z3
230 kV 13.8 kV
Fig. 4. 9-node test grid IEEE
common point with the generator that lost excitation (i.e.
generators in one power plant). As was presented above
in the text, if generator lost excitation it changes into
significant consumer of reactive power. If this generator
is not shut down, the adjacent generators start increasing
the production of reactive power up to the limit when
their limiters of rotor and stator currents act. The effect
of loss of excitation on adjacent generators is analyzed in
more details in [8].
If not even the grid can cope with increased supply of
reactive power, it can cause overloading and subsequent
the transmission lines outages in cascades. Significant de-
crease of voltage in individual nodes of the grid and the
resultant threat of voltage collapse could have another
adverse effect.
Operators of the transmission grids shall for reasons
of planning the operation, development or maintenance
of safe and reliable supplies of electric energy perform
extensive calculations. Calculations of dynamic stability
of grid after loss of excitation of important generators
within the grid should also be considered. Since dynamic
simulations are time consuming, use of so called screening
technique appears to be more suitable [6]. This technique
applies classic calculation of power system load flow with
the aim to determine critical machines, or nodes in the
grid based on so called grid screens where loss of excita-
tion of generator could have adverse effects. Following the
identification of critical nodes, simulations on dynamic
models for specific examples shall be performed for pur-
poses of detailed analysis, proposal of protection settings
during loss of excitation or other necessary safety mea-
sures.
4 Loss of excitation protection
Loss of excitation protection is the so called impedance
type of protection. Their first installations reach back to
50-ties of the last century. The impedance principle is
with good results used also nowadays, since it has high
ability to detect loss of excitation and at the same time
is very reliable. However, there is an area of generator
operation when this type of protection can function im-
properly. These are the cases when generator operated
in under excited condition, during stable transient power
swings in the grid and during significant system outages
with frequency drop [8].
Example of measured impedance on generator termi-
nals is shown on Fig. 2. It can be seen that the impedance
trajectory seen by the protection on machine terminals
crosses the characteristic of loss of excitation protection
and enters into it. This excites the impulse for protection
Journal of ELECTRICAL ENGINEERING 68 (2017), NO1 57
-0.8
-0.4
0
0.4
0.8
1.2
1 2 3 4 5 6 7 8 9 10
(pu)
Time (s)
NT
UG
QG
PG
Fig. 5. Courses of values of generator No. 2 during loss of excitation
-1.5
-1
-0.5
0
0.5
1
1.5
0 1 2 3 4 5 6 7 8 9 10
Time (s)
(pu) IB
UB
Fig. 6. Courses of values of generator No. 2 during loss of excitation
Im (Z)
Re (Z)
-0.2
-0.4
-0.8
-0.6
-0.2 0 0.4 0.8 1.2
Fig. 7. Impedance measured with protection during loss of excita-
tion
impulse component and as long as the impedance stays
in operation zone of protection for some specified period,
the protection issues command to shut down the syn-
chronous generator. This shut down command is issued
with time delay of 1 to 2 seconds in order to prevent un-
desirable protection operation during some swing effects
in the grid.
Typical operation characteristics of loss of excitation
protection are presented in Fig. 3. The characteristics
shown on Fig. 2a and b are defined by the IEEE stan-
dard [9]. The characteristic (b) has an extra directional
element built in in order to prevent undesirable opera-
tion of protection during some swing effects in the grid
or close faults (i.e. during short circuit on terminals of
block transformer). The characteristic (c) is taken over
from IEEE, it is modified and used in China [10]. Finally,
the characteristic (d) is an example of older type of pro-
tection D21 used also in our power system [2].
5 Simulation on dynamic model
The loss of excitation of synchronous generator and
the operation of protection during loss of excitation can
be demonstrated on the following example. For simula-
tion purposes the network simulator MODES (see [11])
was used. As the test grid the 9–node IEEE grid taken
from [12] was used.
In the reference article [10] similar simulations of the
loss of excitation were performed using different methods.
For simulation purposes the following two were used:
– short circuit in excitation winding (Ub = 0),
– disconnection of excitation winding (Ib = 0).
In MODES the loss of excitation according to first
method is simulated by intervention in the scenario. By
the command Par2 the exciter parameters change in
time. By this intervention Ub = 0 is forced to the ex-
citer set.
Second method (Ib = 0) can be simulated by forc-
ing Un = 0 to the exciter set and at the same time
by change of the generator parameter T d0′
→ 0. This
will cause a stepwise increase of excitation winding re-
sistance RBUD → ∞. This method is obvious from the
following PARK formulas that are used in network simu-
lator MODES to describe the complete generator model
(“PARK” model)
T ′
d0 ∗ E′◦
q = UB + (Xd − X′
d) ∗ Id − E′
q ,
T ′
q0 ∗ E′◦
d = −(Xq − X′
q) ∗ Iq − E′
d ,
T ′′
d0 ∗ E′′◦
q = E′
q + (X′
d − X′′
d ) ∗ Id − E′′
q ,
T ′′
q0 ∗ E′′◦
d = E′
d − (X′
q − X′′
q ) ∗ Iq − E′′
d ,
(2)
where E′
q , E′
d , E′′
q , E′′
d are phasors projections of elec-
tromotive forces into axis d and q, Id , Iq are stator
currents projections, UB is excitation voltage, T ′
d0 , T ′′
d0 ,
T ′′
q0 are time constants of synchronous machine in no load
condition, Xd , X′
d , X′′
d are synchronous, transient and
subtransient reactance in direct axis, Xq , X′
q are syn-
chronous and transient reactance in quadrature axis.
It is obvious that the first formula is the most decisive
for excitation modelling. The time constant T ′
d0 is deter-
mined by the ratio L/R. From this it is obvious that the
disconnection of excitation winding will simulate a con-
dition when T ′
d0 → 0 or RBUD → ∞. As base values the
nominal values of stator voltage, current and excitation
voltage in no load condition were selected. Under this
assumption the electromotive force behind synchronous
58 V. Kriˇstof , M. Meˇster: LOSS OF EXCITATION OF SYNCHRONOUS GENERATOR
Time (s)
UG
QG
PG
0.2
0.4
0.6
0.8
1
1.2
0 1 2 3 4 5 6 7 8 9 10
Fig. 8. Courses of values of generator No. 1 during loss of excitation
QG
PG
Time (s)
(pu)
-1
-0.5
0
0.5
1
1.5
1 2 3 4 5 6 7 8 9 10
NT
UG
Fig. 9. Courses of values of generator No. 2 during loss of excitation
(pu)
IB
UB
Time (s)
-0.2
0
0.2
0.4
0.6
0.8
1
1 2 3 4 5 6 7 8 9 10
Fig. 10. Courses of values of generator No. 2 during loss of excita-
tion
Im (Z)
Re (Z)
0.2
-0.2
-0.6
-1.0
-1.4
0.5 1 1.5-0.5 0
Fig. 11. Impedance measured with protection during loss of exci-
tation
(pu)
PG1
Time (s)-0.2
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
1 3 5 7 9 11 13 15
PG3
PG2
Fig. 12. Courses of active powers of generators
reactance Eq equals to excitation current Ib . It applies
the following
Eq = IB = E′
q − (Xd − X′
d) ∗ Id . (3)
Let’s assume that on generator No. 2 at the time of 1 s
there occurs the loss of excitation as result of short cir-
cuit in excitation winding. The courses of relevant values
are presented in Figs. 5 and 6, where PG stands for ac-
tive power of generator, QG is reactive power of genera-
tor, UG is voltage on generator terminals, NT is turbine
power, IBUD is excitation current and UBUD is excitation
voltage.
From the courses presented in Figs. 5 and 6 it is ob-
vious that after loss of excitation the machine starts to
take reactive power from the grid and at the time just
after the 4th
second the machine loses synchronism. This
is obvious from the saw-tooth courses of values (powers,
voltage) that are typical for asynchronous operation. The
impedance measured with protection in Fig. 7 responds
well with its quality to the impedance course in the ref-
erence article [10].
Figure 8 shows the courses of values of generator No. 1.
From the presented courses it is obvious that generator
No.1 responded to failure of generator No. 2 by increas-
ing the production of active power (influence of rotations
regulation) and also reactive power. However, since gen-
erator No. 2 was not disconnected from the grid it also
caused swings of remaining two machines operating in the
grid.
Figure 9 shows the courses of relevant values for gen-
erator No. 2 for the scenario when the excitation winding
was disconnected (ie the second method (Ib = 0)).
When comparing the courses of values during loss of
excitation it is obvious that the second method (i.e. dis-
Journal of ELECTRICAL ENGINEERING 68 (2017), NO1 59
connection of excitation winding) is less favorable and ex-
citation decreases faster and subsequently generator loses
synchronism. The following figure shows the patterns of
active powers of generators G1 to G3 for the case that
protection acts during loss of excitation at the time t=9
s. It is clear that the protection shuts down generator
G2 on time and this has significant importance from the
perspective of maintaining the stability of remaining gen-
erators operating in the grid.
6 Salient pole (hydrogenerator)
vs cylindrical (turbogenerator)
The publication [13] explains that the hydrogenerator
should be immediately shut down after loss of excitation.
The protection acts on signal, switch, de-excitation and
quick release of the turbine. However, the protection will
not shut down the turbogenerator immediately. It acts
on automatics during loss of excitation (ANSI 40). The
automatics acts on turbine regulator and decreases the
generator power. Since it is heated up it enables the op-
eration of generator in above synchronous rotations for
some time. This is how operators or excitation regula-
tor get time and can take an early action to eliminate the
cause (if it is possible) and thus prevent unnecessary shut
down of generator. If it is not possible to eliminate the
cause until the specified period, the automatics will shut
down the generator.
We will try to analyze this situation in more detail.
Hydroelectric generators are synchronous machines with
salient poles where xd = xq . The generally applicable
relation for calculation of electric active power supplied
by generator into the grid, specified also above in this
article, is simplified. Fully covered relation, described in
per units, can be expressed as (in accordance with [14])
pe =
ubuS
x
sin δ + u2
s
xd − xq
2xdxq
sin 2δ . (4)
This relation consists of two elements. First is the torque,
or power of synchronous machine that is proportional to
excitation voltage (first part of equation). Second is so
called reluctance power (second part) that is usually ne-
glected in calculations. However, if it is considered and
ub = 0, ie we assume the loss of excitation occurred, we
determine there is reluctance power on the machine shaft.
With detailed analysis of asynchronous and synchronous
machine in excited and non-excited condition we can con-
clude the following:
1) Asynchronous machine: has squirrel cage rotor
with regular arrangement. During operation with asyn-
chronous rotations neither swings nor power changes oc-
cur during constant load.
2) Synchronous machine in excited condition: by in-
creasing the power up to the stability limit only the in-
ternal machine angle (rotor angle) increases. Once this
limit is crossed synchronism loss and mechanical shocks
on the shaft and turbine occur. These shocks have slip
frequency.
3) Synchronous machine in non-excited condition: its
behavior is somewhere between the two previous exam-
ples. The machine continues to operate as asynchronous
machine, ie with slip. It has obviously zero synchronous
torque determined with the magnetic field of rotor. How-
ever, there still operates the already mentioned reluctance
torque that is proportional to the difference of longitudi-
nal and transverse reactance of the machine. During each
slip the swing (shock) originates, the intensity of which is
also dependent on the difference of longitudinal and trans-
verse reactance. This means that the average torque and
power on the shaft remain approximately equally big as
at the time before loss of excitation. The machine supplies
asynchronous power (similarly as asynchronous machine)
in the grid. The immediate power and torque of the ma-
chine swing around this median at each slip by the value
of reluctance power. If we consider the machine is turbo-
generator, ie machine with cylindrical rotor, that has a
very small difference between longitudinal and transverse
reactance, the immediate value of power and torque of
the machine will slightly swing. In case of hydroelectric
generator, ie machine with salient poles, the swing will
be apparent, since there is significant difference between
the machine reactances.
From this analysis it is obvious that the hydroelectric
generator shall be shut down as soon as possible after loss
of excitation. Turbogenerator can operate with approved
asynchronous operation for some time, as long as it is al-
lowed by the manufacturer. However, the question is why
to keep such machine in non-excited condition further in
operation. This depends on several factors:
– operating method of the whole grid,
– importance of machine that lost excitation protection,
– will the outage of this machine be a threat for the grid
stability?
– can the machine supplying lower power for some time
improve the grid stability?
Basically, there are two viewpoints with respect to this
issue. If the machine is shut down later, the grid stability
will face a smaller threat, yet there will be higher risk
of rotor overheating and machine damage. On the other
hand, if the machine is shut down earlier, it will be bet-
ter for the machine itself, yet with worse consequences
for the grid stability. Practically, not even turbogener-
ators are allowed to operate in asynchronous operation
for above stated reason in order not to cross the allowed
warming of rotor parts or damper (amortisseur) windings.
Generally, it is subject of agreement of the grid operator,
generator operator and generator manufacturer whether
such machine is disconnected from the grid immediately
or asynchronous operation is allowed for some time. Fi-
nally, this time information should be provided by the
manufacturer in type tests.
60 V. Kriˇstof , M. Meˇster: LOSS OF EXCITATION OF SYNCHRONOUS GENERATOR
7 Conclusion
Article deals with loss of excitation of synchronous ge-
nerator. It describes physical nature of this phenomenon,
protection devices against loss of excitation and also
shows possibility of using of network simulator MODES
for loss of excitation analysis.
The article emphasizes the need of this type of calcula-
tions in real operation of transmission systems because of
the loss of synchronism (stability) of synchronous genera-
tor and the subsequent transition to asynchronous opera-
tion is a very serious and unfavorable operating condition.
Loss of synchronism can damage faulted generator but
also can cause problems with stability (angle, voltage) in
power system. In last chapter article analyzes possibility
of operation when generator loses synchronism. There are
three type of machine operation analyzed. This analysis
shows that in case of turbogenerator further operation of
generator must be allowed by producer of machine and
also by operator of transmission system. In case of hydro-
generator further operation is not allowed in any case.
References
[1] Z. Shi, ”Investigation on Generator Loss of Excitation Protec-
tion in Generator Protection Coordination”, School of Electrical
Engineering Royal, Institute of Technology, Stockholm, Sweden
2010, http://www.diva-portal.org/smash/get/diva2:610188/
fulltext01.pdf.
[2] K. M´aslo and L. Haˇnka, ”Anal´yza asynchr´onn´ıho chodu gener-
atoru”, 5. mezin´arodn´ı konference CP&HS 2002, Zl´ın, 2002, (in
Czech).
[3] O. Hora, Regulaˇcn´ı a bud´ıc´ı syst´emy synchronn´ıch stroj˚u, SNTL,
Praha, 1985, (in Czech).
[4] F. Jan´ıˇcek, V. Chladn´y, A. Bel´aˇn and ˇZ. Eleschov´a, Digit´alne
ochrany v elektrizaˇcnej s´ustave. (Digital Protection in Power
System), Vydavatel’stvo STU, Bratislava, 2004, (in Slovak).
[5] K. M´aslo, ”The General Purpose Network Simulator MODES”,
Proc. of the 4th Int. Workshop on El. Power System Control
Centers, Rethymno, Greece, 1997.
[6] H. G. Darron, J. K. Koepfinger, J. R. Mather and P. A. Pusche
”The Influence of Generator Loss of Excitation on Bulk Power
System Reliability”, IEEE Trans Power Apparatus and Systems,
vol. 94, no. 5, 1473–1481, 1975.
[7] J. Tlust´y, J. Kyncl, L. Musil, J. ˇSpetlik, J. ˇSvec, P. Hamouz,
M. M¨uller and Z. M¨uller, Monitorov´an´ı, ˇr´ızen´ı a chr´anˇen´ı elek-
trizaˇcn´ıch soustav, ˇCesk´e vysok´e uˇcen´ı technick´e v Praze, Praha,
2011, (in Czech).
[8] J. Berdy, ”Loss of Excitation Protection for Modern Syn-
chronous Generator”, IEEE Trans Power Apparatus and Sys-
tems, vol. 94, no. 5, 1457–1463, 1975.
[9] IEEE Std.C37.102 - 2006: IEEE Guide for AC Generator pro-
tection. IEEE Power System Society 2006.
[10] Y. Siwang, W. Weijian, L. Ling, G. Ling and Q. Arui, ”Discus-
sion on Setting Calculation of Loss of Excitation Protection for
Large Turbogenerator”, International Conference on Electrical
Machines and Systems (ICEMS), Incheon, 2010.
[11] P. M. Anderson and A. A. Fouad, Power System Control and
Stability, 1977, Iowa State Press University.
[12] V. Chladn´y, Digit´alne ochrany v ES, Technick´a Univerzita
Koˇsice, 2007, (in Slovak).
[13] P. Dohn´alek, Ochrany pro pr˚umysl a energetiku, 1991, (in
Czech).
Received 18 November 2016
Vladim´ır Kriˇstof was born on July 1985 in Koˇsice, Slo-
vakia. He received the MSc and PhD in Power System Engi-
neering from Technical University in Koˇsice, Faculty of Elec-
trical Engineering and Informatics, Department of Electric
Power Engineering. He is currently Power system calculation
specialist in company Power System Management, Ltd. He
was a member of scientific teams on two scientific projects.
He is also author or co-author of 2 university books and more
than 20 scientific and technical papers. His work is focused
in the field of power system stability, short-circuit currents,
power quality and wide area monitoring system.
Mari´an Meˇster born in 1973, received the MSc and PhD
in Power Engineering from Technical University in Koˇsice.
Since 1998 he teaches at Technical University in Koˇsice, Fac-
ulty of Electrical Engineering and Informatics, Department
of Electric Power Engineering. He is currently Head of Dis-
tribution System Operation Section in distribution company
V´ychodoslovensk´a distribuˇcn´a, a.s. He is also author or co-
author of 5 books and more than 70 scientific and technical
papers. He is focused on research in the field of stability of
power system, short-circuit current and digital relays.

More Related Content

What's hot

Power System Oscillations
Power System Oscillations Power System Oscillations
Power System Oscillations
Power System Operation
 
Vk
VkVk
INTRODUCTION TO POWER SYSTEM STABILITY BY Kundur Power Systems Solutions
INTRODUCTION TO POWER SYSTEM STABILITY BY Kundur Power Systems SolutionsINTRODUCTION TO POWER SYSTEM STABILITY BY Kundur Power Systems Solutions
INTRODUCTION TO POWER SYSTEM STABILITY BY Kundur Power Systems Solutions
Power System Operation
 
Dol starter by kantiakapil
Dol  starter by kantiakapilDol  starter by kantiakapil
Dol starter by kantiakapilKapil Kantia
 
Steady state stability analysis and enhancement of three machine nine bus pow...
Steady state stability analysis and enhancement of three machine nine bus pow...Steady state stability analysis and enhancement of three machine nine bus pow...
Steady state stability analysis and enhancement of three machine nine bus pow...
eSAT Journals
 
Static excitation-system
Static excitation-systemStatic excitation-system
Static excitation-system
Deepak Jha
 
POWER SYSTEM STABILIZER
POWER SYSTEM STABILIZERPOWER SYSTEM STABILIZER
POWER SYSTEM STABILIZER
Power System Operation
 
Power system stability
Power system stability Power system stability
Power system stability
MANGESHKULKARNI72
 
EXCITATION SYSTEMS
EXCITATION SYSTEMSEXCITATION SYSTEMS
EXCITATION SYSTEMS
Power System Operation
 
Voltage Stability analysis by using SVC With Fuzzy Logic Controller in Multi ...
Voltage Stability analysis by using SVC With Fuzzy Logic Controller in Multi ...Voltage Stability analysis by using SVC With Fuzzy Logic Controller in Multi ...
Voltage Stability analysis by using SVC With Fuzzy Logic Controller in Multi ...
paperpublications3
 
Electric drives
Electric drivesElectric drives
Electric drives
Samsu Deen
 
Loss of excitation
Loss of excitationLoss of excitation
Loss of excitation
NTPC
 
EXCITATION SYSTEMS by Dr. Kundur Power Systems
EXCITATION SYSTEMS by Dr. Kundur Power SystemsEXCITATION SYSTEMS by Dr. Kundur Power Systems
EXCITATION SYSTEMS by Dr. Kundur Power Systems
Power System Operation
 
Starters of induction motor and protection equipment
Starters of induction motor and protection equipmentStarters of induction motor and protection equipment
Starters of induction motor and protection equipment
sateesh kumar
 
Transient enhancement technique
Transient enhancement techniqueTransient enhancement technique
Transient enhancement technique
Vipin Pandey
 
Urn009728
Urn009728Urn009728
Urn009728
Nikolay Djagarov
 
Power System Oscillations Behavior, Types, Causes,Role of the System Operator...
Power System Oscillations Behavior, Types, Causes,Role of the System Operator...Power System Oscillations Behavior, Types, Causes,Role of the System Operator...
Power System Oscillations Behavior, Types, Causes,Role of the System Operator...
Power System Operation
 
SMALL SIGNAL ROTOR ANGLE STABILITY
SMALL SIGNAL ROTOR ANGLE STABILITY SMALL SIGNAL ROTOR ANGLE STABILITY
SMALL SIGNAL ROTOR ANGLE STABILITY
Power System Operation
 

What's hot (20)

Power System Oscillations
Power System Oscillations Power System Oscillations
Power System Oscillations
 
Vk
VkVk
Vk
 
INTRODUCTION TO POWER SYSTEM STABILITY BY Kundur Power Systems Solutions
INTRODUCTION TO POWER SYSTEM STABILITY BY Kundur Power Systems SolutionsINTRODUCTION TO POWER SYSTEM STABILITY BY Kundur Power Systems Solutions
INTRODUCTION TO POWER SYSTEM STABILITY BY Kundur Power Systems Solutions
 
Dol starter by kantiakapil
Dol  starter by kantiakapilDol  starter by kantiakapil
Dol starter by kantiakapil
 
Steady state stability analysis and enhancement of three machine nine bus pow...
Steady state stability analysis and enhancement of three machine nine bus pow...Steady state stability analysis and enhancement of three machine nine bus pow...
Steady state stability analysis and enhancement of three machine nine bus pow...
 
Static excitation-system
Static excitation-systemStatic excitation-system
Static excitation-system
 
POWER SYSTEM STABILIZER
POWER SYSTEM STABILIZERPOWER SYSTEM STABILIZER
POWER SYSTEM STABILIZER
 
Power system stability
Power system stability Power system stability
Power system stability
 
EXCITATION SYSTEMS
EXCITATION SYSTEMSEXCITATION SYSTEMS
EXCITATION SYSTEMS
 
Voltage Stability analysis by using SVC With Fuzzy Logic Controller in Multi ...
Voltage Stability analysis by using SVC With Fuzzy Logic Controller in Multi ...Voltage Stability analysis by using SVC With Fuzzy Logic Controller in Multi ...
Voltage Stability analysis by using SVC With Fuzzy Logic Controller in Multi ...
 
Electric drives
Electric drivesElectric drives
Electric drives
 
Loss of excitation
Loss of excitationLoss of excitation
Loss of excitation
 
EXCITATION SYSTEMS by Dr. Kundur Power Systems
EXCITATION SYSTEMS by Dr. Kundur Power SystemsEXCITATION SYSTEMS by Dr. Kundur Power Systems
EXCITATION SYSTEMS by Dr. Kundur Power Systems
 
Hamza Kazmi (GTE)
Hamza Kazmi (GTE)Hamza Kazmi (GTE)
Hamza Kazmi (GTE)
 
Starters of induction motor and protection equipment
Starters of induction motor and protection equipmentStarters of induction motor and protection equipment
Starters of induction motor and protection equipment
 
Transient enhancement technique
Transient enhancement techniqueTransient enhancement technique
Transient enhancement technique
 
Urn009728
Urn009728Urn009728
Urn009728
 
Project PPT
Project PPTProject PPT
Project PPT
 
Power System Oscillations Behavior, Types, Causes,Role of the System Operator...
Power System Oscillations Behavior, Types, Causes,Role of the System Operator...Power System Oscillations Behavior, Types, Causes,Role of the System Operator...
Power System Oscillations Behavior, Types, Causes,Role of the System Operator...
 
SMALL SIGNAL ROTOR ANGLE STABILITY
SMALL SIGNAL ROTOR ANGLE STABILITY SMALL SIGNAL ROTOR ANGLE STABILITY
SMALL SIGNAL ROTOR ANGLE STABILITY
 

Similar to [1339309 x journal of electrical engineering] loss of excitation of synchronous generator

Power Swing Phenomena and its Detection and Prevention
Power Swing Phenomena and its Detection and PreventionPower Swing Phenomena and its Detection and Prevention
Power Swing Phenomena and its Detection and Prevention
Power System Operation
 
H11 BACKGROUND OF POWER EMERSON EDUARDO RODRIGUES.pdf
H11 BACKGROUND OF POWER EMERSON EDUARDO RODRIGUES.pdfH11 BACKGROUND OF POWER EMERSON EDUARDO RODRIGUES.pdf
H11 BACKGROUND OF POWER EMERSON EDUARDO RODRIGUES.pdf
EMERSON EDUARDO RODRIGUES
 
Generator protection
Generator protectionGenerator protection
Generator protection
SSVASAVA
 
Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of ExcitationPerformance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation
paperpublications3
 
New Microsoft Word Document
New Microsoft Word DocumentNew Microsoft Word Document
New Microsoft Word DocumentBarunava Sikdar
 
PLACEMENT OF POWER SYSTEM STABILIZER (PSS) IN NIGERIA 28-BUS POWER NETWORK FO...
PLACEMENT OF POWER SYSTEM STABILIZER (PSS) IN NIGERIA 28-BUS POWER NETWORK FO...PLACEMENT OF POWER SYSTEM STABILIZER (PSS) IN NIGERIA 28-BUS POWER NETWORK FO...
PLACEMENT OF POWER SYSTEM STABILIZER (PSS) IN NIGERIA 28-BUS POWER NETWORK FO...
IRJET Journal
 
29 9761 loss paper id 0029 (edit ari
29 9761 loss paper id 0029 (edit ari29 9761 loss paper id 0029 (edit ari
29 9761 loss paper id 0029 (edit ari
IAESIJEECS
 
Power System Analysis Unit - V
Power System Analysis Unit - VPower System Analysis Unit - V
Power System Analysis Unit - V
arunatshare
 
Rotor earth fault protection of electric generator
Rotor earth fault protection of electric generatorRotor earth fault protection of electric generator
Rotor earth fault protection of electric generator
CS V
 
Et33879883
Et33879883Et33879883
Et33879883
IJERA Editor
 
Et33879883
Et33879883Et33879883
Et33879883
IJERA Editor
 
Inspection of voltage sags and voltage swells incident in power quality probl...
Inspection of voltage sags and voltage swells incident in power quality probl...Inspection of voltage sags and voltage swells incident in power quality probl...
Inspection of voltage sags and voltage swells incident in power quality probl...
IRJET Journal
 
L58037783
L58037783L58037783
L58037783
IJERA Editor
 
DOC-20240122-WA001jhfjyfguyf1. (1) (1).pptx
DOC-20240122-WA001jhfjyfguyf1. (1) (1).pptxDOC-20240122-WA001jhfjyfguyf1. (1) (1).pptx
DOC-20240122-WA001jhfjyfguyf1. (1) (1).pptx
SahitiDarika
 
Rotor earth fault protection of electric generator
Rotor earth fault protection of electric generatorRotor earth fault protection of electric generator
Rotor earth fault protection of electric generator
mytechinfo
 
A Load Shedding Scheme Based On Frequency Response Model With Fast Voltage St...
A Load Shedding Scheme Based On Frequency Response Model With Fast Voltage St...A Load Shedding Scheme Based On Frequency Response Model With Fast Voltage St...
A Load Shedding Scheme Based On Frequency Response Model With Fast Voltage St...
IRJET Journal
 
Electrical machines lecture notes
Electrical machines lecture notesElectrical machines lecture notes
Electrical machines lecture notes
IYAKAREMYE Jean De Dieu
 
IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...
IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...
IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...
IRJET Journal
 

Similar to [1339309 x journal of electrical engineering] loss of excitation of synchronous generator (20)

Power Swing Phenomena and its Detection and Prevention
Power Swing Phenomena and its Detection and PreventionPower Swing Phenomena and its Detection and Prevention
Power Swing Phenomena and its Detection and Prevention
 
H11 BACKGROUND OF POWER EMERSON EDUARDO RODRIGUES.pdf
H11 BACKGROUND OF POWER EMERSON EDUARDO RODRIGUES.pdfH11 BACKGROUND OF POWER EMERSON EDUARDO RODRIGUES.pdf
H11 BACKGROUND OF POWER EMERSON EDUARDO RODRIGUES.pdf
 
40220140504006
4022014050400640220140504006
40220140504006
 
Generator protection
Generator protectionGenerator protection
Generator protection
 
Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of ExcitationPerformance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation
 
New Microsoft Word Document
New Microsoft Word DocumentNew Microsoft Word Document
New Microsoft Word Document
 
PLACEMENT OF POWER SYSTEM STABILIZER (PSS) IN NIGERIA 28-BUS POWER NETWORK FO...
PLACEMENT OF POWER SYSTEM STABILIZER (PSS) IN NIGERIA 28-BUS POWER NETWORK FO...PLACEMENT OF POWER SYSTEM STABILIZER (PSS) IN NIGERIA 28-BUS POWER NETWORK FO...
PLACEMENT OF POWER SYSTEM STABILIZER (PSS) IN NIGERIA 28-BUS POWER NETWORK FO...
 
29 9761 loss paper id 0029 (edit ari
29 9761 loss paper id 0029 (edit ari29 9761 loss paper id 0029 (edit ari
29 9761 loss paper id 0029 (edit ari
 
Power System Analysis Unit - V
Power System Analysis Unit - VPower System Analysis Unit - V
Power System Analysis Unit - V
 
Rotor earth fault protection of electric generator
Rotor earth fault protection of electric generatorRotor earth fault protection of electric generator
Rotor earth fault protection of electric generator
 
Et33879883
Et33879883Et33879883
Et33879883
 
Et33879883
Et33879883Et33879883
Et33879883
 
Inspection of voltage sags and voltage swells incident in power quality probl...
Inspection of voltage sags and voltage swells incident in power quality probl...Inspection of voltage sags and voltage swells incident in power quality probl...
Inspection of voltage sags and voltage swells incident in power quality probl...
 
L58037783
L58037783L58037783
L58037783
 
40220140505010
4022014050501040220140505010
40220140505010
 
DOC-20240122-WA001jhfjyfguyf1. (1) (1).pptx
DOC-20240122-WA001jhfjyfguyf1. (1) (1).pptxDOC-20240122-WA001jhfjyfguyf1. (1) (1).pptx
DOC-20240122-WA001jhfjyfguyf1. (1) (1).pptx
 
Rotor earth fault protection of electric generator
Rotor earth fault protection of electric generatorRotor earth fault protection of electric generator
Rotor earth fault protection of electric generator
 
A Load Shedding Scheme Based On Frequency Response Model With Fast Voltage St...
A Load Shedding Scheme Based On Frequency Response Model With Fast Voltage St...A Load Shedding Scheme Based On Frequency Response Model With Fast Voltage St...
A Load Shedding Scheme Based On Frequency Response Model With Fast Voltage St...
 
Electrical machines lecture notes
Electrical machines lecture notesElectrical machines lecture notes
Electrical machines lecture notes
 
IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...
IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...
IRJET-Review on Power Quality Enhancement in weak Power Grids by Integration ...
 

Recently uploaded

Lateral Ventricles.pdf very easy good diagrams comprehensive
Lateral Ventricles.pdf very easy good diagrams comprehensiveLateral Ventricles.pdf very easy good diagrams comprehensive
Lateral Ventricles.pdf very easy good diagrams comprehensive
silvermistyshot
 
general properties of oerganologametal.ppt
general properties of oerganologametal.pptgeneral properties of oerganologametal.ppt
general properties of oerganologametal.ppt
IqrimaNabilatulhusni
 
(May 29th, 2024) Advancements in Intravital Microscopy- Insights for Preclini...
(May 29th, 2024) Advancements in Intravital Microscopy- Insights for Preclini...(May 29th, 2024) Advancements in Intravital Microscopy- Insights for Preclini...
(May 29th, 2024) Advancements in Intravital Microscopy- Insights for Preclini...
Scintica Instrumentation
 
Nutraceutical market, scope and growth: Herbal drug technology
Nutraceutical market, scope and growth: Herbal drug technologyNutraceutical market, scope and growth: Herbal drug technology
Nutraceutical market, scope and growth: Herbal drug technology
Lokesh Patil
 
erythropoiesis-I_mechanism& clinical significance.pptx
erythropoiesis-I_mechanism& clinical significance.pptxerythropoiesis-I_mechanism& clinical significance.pptx
erythropoiesis-I_mechanism& clinical significance.pptx
muralinath2
 
Leaf Initiation, Growth and Differentiation.pdf
Leaf Initiation, Growth and Differentiation.pdfLeaf Initiation, Growth and Differentiation.pdf
Leaf Initiation, Growth and Differentiation.pdf
RenuJangid3
 
GBSN - Biochemistry (Unit 5) Chemistry of Lipids
GBSN - Biochemistry (Unit 5) Chemistry of LipidsGBSN - Biochemistry (Unit 5) Chemistry of Lipids
GBSN - Biochemistry (Unit 5) Chemistry of Lipids
Areesha Ahmad
 
GBSN - Microbiology (Lab 4) Culture Media
GBSN - Microbiology (Lab 4) Culture MediaGBSN - Microbiology (Lab 4) Culture Media
GBSN - Microbiology (Lab 4) Culture Media
Areesha Ahmad
 
The ASGCT Annual Meeting was packed with exciting progress in the field advan...
The ASGCT Annual Meeting was packed with exciting progress in the field advan...The ASGCT Annual Meeting was packed with exciting progress in the field advan...
The ASGCT Annual Meeting was packed with exciting progress in the field advan...
Health Advances
 
Deep Behavioral Phenotyping in Systems Neuroscience for Functional Atlasing a...
Deep Behavioral Phenotyping in Systems Neuroscience for Functional Atlasing a...Deep Behavioral Phenotyping in Systems Neuroscience for Functional Atlasing a...
Deep Behavioral Phenotyping in Systems Neuroscience for Functional Atlasing a...
Ana Luísa Pinho
 
EY - Supply Chain Services 2018_template.pptx
EY - Supply Chain Services 2018_template.pptxEY - Supply Chain Services 2018_template.pptx
EY - Supply Chain Services 2018_template.pptx
AlguinaldoKong
 
extra-chromosomal-inheritance[1].pptx.pdfpdf
extra-chromosomal-inheritance[1].pptx.pdfpdfextra-chromosomal-inheritance[1].pptx.pdfpdf
extra-chromosomal-inheritance[1].pptx.pdfpdf
DiyaBiswas10
 
Observation of Io’s Resurfacing via Plume Deposition Using Ground-based Adapt...
Observation of Io’s Resurfacing via Plume Deposition Using Ground-based Adapt...Observation of Io’s Resurfacing via Plume Deposition Using Ground-based Adapt...
Observation of Io’s Resurfacing via Plume Deposition Using Ground-based Adapt...
Sérgio Sacani
 
NuGOweek 2024 Ghent - programme - final version
NuGOweek 2024 Ghent - programme - final versionNuGOweek 2024 Ghent - programme - final version
NuGOweek 2024 Ghent - programme - final version
pablovgd
 
Orion Air Quality Monitoring Systems - CWS
Orion Air Quality Monitoring Systems - CWSOrion Air Quality Monitoring Systems - CWS
Orion Air Quality Monitoring Systems - CWS
Columbia Weather Systems
 
RNA INTERFERENCE: UNRAVELING GENETIC SILENCING
RNA INTERFERENCE: UNRAVELING GENETIC SILENCINGRNA INTERFERENCE: UNRAVELING GENETIC SILENCING
RNA INTERFERENCE: UNRAVELING GENETIC SILENCING
AADYARAJPANDEY1
 
Body fluids_tonicity_dehydration_hypovolemia_hypervolemia.pptx
Body fluids_tonicity_dehydration_hypovolemia_hypervolemia.pptxBody fluids_tonicity_dehydration_hypovolemia_hypervolemia.pptx
Body fluids_tonicity_dehydration_hypovolemia_hypervolemia.pptx
muralinath2
 
Structures and textures of metamorphic rocks
Structures and textures of metamorphic rocksStructures and textures of metamorphic rocks
Structures and textures of metamorphic rocks
kumarmathi863
 
SCHIZOPHRENIA Disorder/ Brain Disorder.pdf
SCHIZOPHRENIA Disorder/ Brain Disorder.pdfSCHIZOPHRENIA Disorder/ Brain Disorder.pdf
SCHIZOPHRENIA Disorder/ Brain Disorder.pdf
SELF-EXPLANATORY
 
Nucleic Acid-its structural and functional complexity.
Nucleic Acid-its structural and functional complexity.Nucleic Acid-its structural and functional complexity.
Nucleic Acid-its structural and functional complexity.
Nistarini College, Purulia (W.B) India
 

Recently uploaded (20)

Lateral Ventricles.pdf very easy good diagrams comprehensive
Lateral Ventricles.pdf very easy good diagrams comprehensiveLateral Ventricles.pdf very easy good diagrams comprehensive
Lateral Ventricles.pdf very easy good diagrams comprehensive
 
general properties of oerganologametal.ppt
general properties of oerganologametal.pptgeneral properties of oerganologametal.ppt
general properties of oerganologametal.ppt
 
(May 29th, 2024) Advancements in Intravital Microscopy- Insights for Preclini...
(May 29th, 2024) Advancements in Intravital Microscopy- Insights for Preclini...(May 29th, 2024) Advancements in Intravital Microscopy- Insights for Preclini...
(May 29th, 2024) Advancements in Intravital Microscopy- Insights for Preclini...
 
Nutraceutical market, scope and growth: Herbal drug technology
Nutraceutical market, scope and growth: Herbal drug technologyNutraceutical market, scope and growth: Herbal drug technology
Nutraceutical market, scope and growth: Herbal drug technology
 
erythropoiesis-I_mechanism& clinical significance.pptx
erythropoiesis-I_mechanism& clinical significance.pptxerythropoiesis-I_mechanism& clinical significance.pptx
erythropoiesis-I_mechanism& clinical significance.pptx
 
Leaf Initiation, Growth and Differentiation.pdf
Leaf Initiation, Growth and Differentiation.pdfLeaf Initiation, Growth and Differentiation.pdf
Leaf Initiation, Growth and Differentiation.pdf
 
GBSN - Biochemistry (Unit 5) Chemistry of Lipids
GBSN - Biochemistry (Unit 5) Chemistry of LipidsGBSN - Biochemistry (Unit 5) Chemistry of Lipids
GBSN - Biochemistry (Unit 5) Chemistry of Lipids
 
GBSN - Microbiology (Lab 4) Culture Media
GBSN - Microbiology (Lab 4) Culture MediaGBSN - Microbiology (Lab 4) Culture Media
GBSN - Microbiology (Lab 4) Culture Media
 
The ASGCT Annual Meeting was packed with exciting progress in the field advan...
The ASGCT Annual Meeting was packed with exciting progress in the field advan...The ASGCT Annual Meeting was packed with exciting progress in the field advan...
The ASGCT Annual Meeting was packed with exciting progress in the field advan...
 
Deep Behavioral Phenotyping in Systems Neuroscience for Functional Atlasing a...
Deep Behavioral Phenotyping in Systems Neuroscience for Functional Atlasing a...Deep Behavioral Phenotyping in Systems Neuroscience for Functional Atlasing a...
Deep Behavioral Phenotyping in Systems Neuroscience for Functional Atlasing a...
 
EY - Supply Chain Services 2018_template.pptx
EY - Supply Chain Services 2018_template.pptxEY - Supply Chain Services 2018_template.pptx
EY - Supply Chain Services 2018_template.pptx
 
extra-chromosomal-inheritance[1].pptx.pdfpdf
extra-chromosomal-inheritance[1].pptx.pdfpdfextra-chromosomal-inheritance[1].pptx.pdfpdf
extra-chromosomal-inheritance[1].pptx.pdfpdf
 
Observation of Io’s Resurfacing via Plume Deposition Using Ground-based Adapt...
Observation of Io’s Resurfacing via Plume Deposition Using Ground-based Adapt...Observation of Io’s Resurfacing via Plume Deposition Using Ground-based Adapt...
Observation of Io’s Resurfacing via Plume Deposition Using Ground-based Adapt...
 
NuGOweek 2024 Ghent - programme - final version
NuGOweek 2024 Ghent - programme - final versionNuGOweek 2024 Ghent - programme - final version
NuGOweek 2024 Ghent - programme - final version
 
Orion Air Quality Monitoring Systems - CWS
Orion Air Quality Monitoring Systems - CWSOrion Air Quality Monitoring Systems - CWS
Orion Air Quality Monitoring Systems - CWS
 
RNA INTERFERENCE: UNRAVELING GENETIC SILENCING
RNA INTERFERENCE: UNRAVELING GENETIC SILENCINGRNA INTERFERENCE: UNRAVELING GENETIC SILENCING
RNA INTERFERENCE: UNRAVELING GENETIC SILENCING
 
Body fluids_tonicity_dehydration_hypovolemia_hypervolemia.pptx
Body fluids_tonicity_dehydration_hypovolemia_hypervolemia.pptxBody fluids_tonicity_dehydration_hypovolemia_hypervolemia.pptx
Body fluids_tonicity_dehydration_hypovolemia_hypervolemia.pptx
 
Structures and textures of metamorphic rocks
Structures and textures of metamorphic rocksStructures and textures of metamorphic rocks
Structures and textures of metamorphic rocks
 
SCHIZOPHRENIA Disorder/ Brain Disorder.pdf
SCHIZOPHRENIA Disorder/ Brain Disorder.pdfSCHIZOPHRENIA Disorder/ Brain Disorder.pdf
SCHIZOPHRENIA Disorder/ Brain Disorder.pdf
 
Nucleic Acid-its structural and functional complexity.
Nucleic Acid-its structural and functional complexity.Nucleic Acid-its structural and functional complexity.
Nucleic Acid-its structural and functional complexity.
 

[1339309 x journal of electrical engineering] loss of excitation of synchronous generator

  • 1. Journal of ELECTRICAL ENGINEERING, VOL 68 (2017), NO1, 54–60 Loss of excitation of synchronous generator Vladim´ır Kriˇstof, ∗ Mari´an Meˇster ∗∗ This paper presents results of study of loss-of-excitation phenomena simulations. Loss of excitation is a very common fault in synchronous machine operating and can be caused by short circuit of the field winding, unexpected field breaker open or loss-of-excitation relay mal-operation. According to the statistic [1], the generator failure due to loss-of-excitation accounts for 69 % of all generator failures. There has been concern over possible incorrect operation of the relay when operating the generator in the under-excited region, during stable transient swings and during major system disturbances. This article can serve as inputs for system operators in preparation of operation area or protection relaying area. K e y w o r d s: loss of excitation, excitation system, synchronous generator, stability 1 Introduction The loss of synchronism (stability) of synchronous gen- erator and the subsequent transition to asynchronous op- eration is a very serious and unfavorable operating condi- tion. It occurs if the machine is not able to transmit the electrical power (Pe ) corresponding to supplied mechan- ical power (Pm ). This could be caused by the following reasons: – loss of excitation of synchronous generator (significant decrease of internal electromotive force), – weakening of the transmission grid (eg line outages), – increasing of the transmitted power (threat for static stability), – etc. Asynchronous operation of synchronous generator is ana- lyzed eg in [2]. This article deals with the loss of excitation of synchronous generator. 2 Excitation systems of synchronous machines The essential function of excitation system is to supply direct current for the power of synchronous machine ex- citation winding. Furthermore, it has several protection and control functions. The excitation system consists of two relatively independent components — excitation reg- ulator (automatic voltage regulator) and the exciter it- self [3]. The exciter power makes up generally 0.2–0.8 % of the generator power. The exciter voltage generally does not exceed 1 kV so that its winding does not need addi- tional insulation [2]. Basically there are static and rotating exciters. In ro- tating exciters, the excitation current is obtained from direct current generators (eventually alternative current generators equipped with rectifiers). Since direct current sources do not provide the necessary power, they are con- nected into cascade. This is however followed by increas- ing of equivalent exciter time constant (and thus worsen- ing of exciter dynamics). Basic components of static excitation systems are thyristor rectifiers, controlled with excitation regulator by means of thyristor ignition impulse circuits. This can be performed in two ways via the transformer, namely either from an independent source (so called independent excitation) or directly from the generator (so called de- pendent excitation). The main benefit of static excitation systems is the speed with which the excitation voltage re- sponds to the change of regulator voltage. The excitation systems of synchronous machines are subject of following requirements: – keep the generator in a condition when it is possible by (long) lines to transmit the power close to the limit line power (ie enable the generator operation in the area of so called artificial stability [4]), – ensure sufficient dynamic stability reserve and damp- ing of generator power swings after failure, – maintain stability during change of properties of elec- tric lines or grid to which the generator is connected, – easily and reliably measure the parameters according to which regulation occurs, – high operating reliability. An integral part of the excitation system is apart from the exciter itself also the excitation regulator. The pri- mary task of the excitation regulator is to maintain the required voltage on generator terminals. In addition, the excitation regulator generally fulfills most of the following supplementary functions [3, 5]: – limiter of rotor and stator current: protects generator before stator or rotor circuit overloading, – under-excitation limit control: main aim is to prevent machine de-excitation (under-excitation) to the degree ∗ Power System Management s.r.o., Ondavsk´a 5, 040 01 Koˇsice, Slovakia, kristof.vladimir@gmail.com ∗∗ Vchodoslovensk´a distribuˇcn´a, a.s., Mlynsk´a 31, 040 01 Koˇsice, Slovakia, marian.mester@gmail.com DOI: 10.1515/jee-2017-0007, Print (till 2015) ISSN 1335-3632, On-line ISSN 1339-309X c 2017 FEI STU
  • 2. Journal of ELECTRICAL ENGINEERING 68 (2017), NO1 55 90° Pe (pu) d 180° 0.2 0.6 1.0 1.4 1.8 Mechanical power Pm UB = 100 % 80 % 60 % 40 % 0° d(0) Fig. 1. Power – angle characteristic for individual values of excita- tion voltage UB Out of step protection R x xd xd/2’ x xd t/2 +’ Loss of excitation protection Fig. 2. Measured trajectory in the impedance plane during loss of excitation where threat of its static stability arises, stator wind- ing terminals warm up, etc, – power system stabilizer: dampens electromechanical swings that originate as result of commutations in the grid, – secondary regulator of reactive power: maintains reac- tive power on desired value. From the above presented facts it is obvious that excita- tion systems are important components of both the gen- erator as well as the electricity grid. Therefore, it is de- sirable that they provide the highest possible operating reliability. The outages or failures in excitation systems can have very unfavorable operating consequences. 3 Loss of excitation protection Loss of excitation of synchronous generator can be caused by several factors, such as power supply outage, exciter damage or short circuit in the excitation winding. Regardless of the reason the loss of excitation represents a high risk with regard to synchronous generator damage. In addition, outage of synchronous generator with high unit power represents a significant risk for the stability of electricity grid. During loss of excitation the current in excitation winding decreases (exponentially). Proportion- ally also the internal electromotive force and the electro- magnetic relation between the stator and rotor decrease. This is reflected in gradual decrease of reactive power on generator terminals. When the under-excitation limit is achieved, the loss of synchronism occurs (the relation be- tween the stator and rotor is already very week at this time). This whole process is similar to loss of static sta- bility of synchronous machine. The development of loss of synchronism after loss of excitation can simply be ex- plained by power characteristics. For the electric power supplied with generator to grid under stabilized condi- tions the following applies Pe = EGES X sin δ (1) where EG is internal voltage of generator, ES – grid voltage, X – transmission reactance and δ is rotor angle (angle between EG and ES ). The intersection between the turbine mechanical power (Pm ) and power curve (P − δ) defines the operating ro- tor angle (sometimes so called load angle). Decreasing internal voltage of generator results in decreased power curve (Fig. 1). As the power curve decreases the rotor an- gle increases and gets close to the limit operating point (δcrit = 90◦ ). At this point the electric power supplied by generator reaches its maximum level (for respective operating conditions). The following subsequent decrease of the power curve as result of loss of excitation will cause that generator will no longer be able to transmit the electric power corresponding to the mechanical power of turbine. The imbalance (excessive mechanical power of turbine) will be reflected in the generator rotor speeding up. Generator speeding up will be then reflected in the decreasing turbine power (corresponding to turbine reg- ulator statics). Under certain circumstances, when the decrease of the excitation voltage is successfully stopped by machine operator, the new balanced operating point (with worse operating conditions) will be achieved. The resulting generator rotations are determined by turbine regulator statics and grid “toughness” (in synchronous operation of extensive grid the rotations generally do not change, whereas in island mode operation the fre- quency/rotations deviation can reach up to 5 % before the machine is disconnected from the grid). The loss of excitation is a transient phenomenon of medium speed with the time interface of several seconds (3 to 8 seconds according to [6]). The loss of excitation represents a threat mainly from the following reasons [7]: – stator overloading as result of significant supply of re- active power from the grid (0.4 to 1.9-multiple of Sn ), – warming up of rotor winding influenced by induced currents, – extensive swings of active power, which are typical for asynchronous operation. The loss of excitation can have adverse effect not only on the generator itself, but also on the whole grid and adjacent generators — mainly if they are connected to
  • 3. 56 V. Kriˇstof , M. Meˇster: LOSS OF EXCITATION OF SYNCHRONOUS GENERATOR High load R x xd xd/2’ Low load 1.0 pu 0 Zone 1 Zone 2 Impedance locus during loss of excitation R x xs xd/2’ 1.1 xd 0 Zone 1 Zone 2 Directional element R x xs xd/2’ xd 0 Zone 1 Zone 2 R x 5% xq xq 0 Fig. 3. Impedance patterns of loss of excitation protection G2 G3 G1 Z1 Z2 16.5 kV 230 kV 230 kV230 kV 18 kV 230 kV 230 kV Z3 230 kV 13.8 kV Fig. 4. 9-node test grid IEEE common point with the generator that lost excitation (i.e. generators in one power plant). As was presented above in the text, if generator lost excitation it changes into significant consumer of reactive power. If this generator is not shut down, the adjacent generators start increasing the production of reactive power up to the limit when their limiters of rotor and stator currents act. The effect of loss of excitation on adjacent generators is analyzed in more details in [8]. If not even the grid can cope with increased supply of reactive power, it can cause overloading and subsequent the transmission lines outages in cascades. Significant de- crease of voltage in individual nodes of the grid and the resultant threat of voltage collapse could have another adverse effect. Operators of the transmission grids shall for reasons of planning the operation, development or maintenance of safe and reliable supplies of electric energy perform extensive calculations. Calculations of dynamic stability of grid after loss of excitation of important generators within the grid should also be considered. Since dynamic simulations are time consuming, use of so called screening technique appears to be more suitable [6]. This technique applies classic calculation of power system load flow with the aim to determine critical machines, or nodes in the grid based on so called grid screens where loss of excita- tion of generator could have adverse effects. Following the identification of critical nodes, simulations on dynamic models for specific examples shall be performed for pur- poses of detailed analysis, proposal of protection settings during loss of excitation or other necessary safety mea- sures. 4 Loss of excitation protection Loss of excitation protection is the so called impedance type of protection. Their first installations reach back to 50-ties of the last century. The impedance principle is with good results used also nowadays, since it has high ability to detect loss of excitation and at the same time is very reliable. However, there is an area of generator operation when this type of protection can function im- properly. These are the cases when generator operated in under excited condition, during stable transient power swings in the grid and during significant system outages with frequency drop [8]. Example of measured impedance on generator termi- nals is shown on Fig. 2. It can be seen that the impedance trajectory seen by the protection on machine terminals crosses the characteristic of loss of excitation protection and enters into it. This excites the impulse for protection
  • 4. Journal of ELECTRICAL ENGINEERING 68 (2017), NO1 57 -0.8 -0.4 0 0.4 0.8 1.2 1 2 3 4 5 6 7 8 9 10 (pu) Time (s) NT UG QG PG Fig. 5. Courses of values of generator No. 2 during loss of excitation -1.5 -1 -0.5 0 0.5 1 1.5 0 1 2 3 4 5 6 7 8 9 10 Time (s) (pu) IB UB Fig. 6. Courses of values of generator No. 2 during loss of excitation Im (Z) Re (Z) -0.2 -0.4 -0.8 -0.6 -0.2 0 0.4 0.8 1.2 Fig. 7. Impedance measured with protection during loss of excita- tion impulse component and as long as the impedance stays in operation zone of protection for some specified period, the protection issues command to shut down the syn- chronous generator. This shut down command is issued with time delay of 1 to 2 seconds in order to prevent un- desirable protection operation during some swing effects in the grid. Typical operation characteristics of loss of excitation protection are presented in Fig. 3. The characteristics shown on Fig. 2a and b are defined by the IEEE stan- dard [9]. The characteristic (b) has an extra directional element built in in order to prevent undesirable opera- tion of protection during some swing effects in the grid or close faults (i.e. during short circuit on terminals of block transformer). The characteristic (c) is taken over from IEEE, it is modified and used in China [10]. Finally, the characteristic (d) is an example of older type of pro- tection D21 used also in our power system [2]. 5 Simulation on dynamic model The loss of excitation of synchronous generator and the operation of protection during loss of excitation can be demonstrated on the following example. For simula- tion purposes the network simulator MODES (see [11]) was used. As the test grid the 9–node IEEE grid taken from [12] was used. In the reference article [10] similar simulations of the loss of excitation were performed using different methods. For simulation purposes the following two were used: – short circuit in excitation winding (Ub = 0), – disconnection of excitation winding (Ib = 0). In MODES the loss of excitation according to first method is simulated by intervention in the scenario. By the command Par2 the exciter parameters change in time. By this intervention Ub = 0 is forced to the ex- citer set. Second method (Ib = 0) can be simulated by forc- ing Un = 0 to the exciter set and at the same time by change of the generator parameter T d0′ → 0. This will cause a stepwise increase of excitation winding re- sistance RBUD → ∞. This method is obvious from the following PARK formulas that are used in network simu- lator MODES to describe the complete generator model (“PARK” model) T ′ d0 ∗ E′◦ q = UB + (Xd − X′ d) ∗ Id − E′ q , T ′ q0 ∗ E′◦ d = −(Xq − X′ q) ∗ Iq − E′ d , T ′′ d0 ∗ E′′◦ q = E′ q + (X′ d − X′′ d ) ∗ Id − E′′ q , T ′′ q0 ∗ E′′◦ d = E′ d − (X′ q − X′′ q ) ∗ Iq − E′′ d , (2) where E′ q , E′ d , E′′ q , E′′ d are phasors projections of elec- tromotive forces into axis d and q, Id , Iq are stator currents projections, UB is excitation voltage, T ′ d0 , T ′′ d0 , T ′′ q0 are time constants of synchronous machine in no load condition, Xd , X′ d , X′′ d are synchronous, transient and subtransient reactance in direct axis, Xq , X′ q are syn- chronous and transient reactance in quadrature axis. It is obvious that the first formula is the most decisive for excitation modelling. The time constant T ′ d0 is deter- mined by the ratio L/R. From this it is obvious that the disconnection of excitation winding will simulate a con- dition when T ′ d0 → 0 or RBUD → ∞. As base values the nominal values of stator voltage, current and excitation voltage in no load condition were selected. Under this assumption the electromotive force behind synchronous
  • 5. 58 V. Kriˇstof , M. Meˇster: LOSS OF EXCITATION OF SYNCHRONOUS GENERATOR Time (s) UG QG PG 0.2 0.4 0.6 0.8 1 1.2 0 1 2 3 4 5 6 7 8 9 10 Fig. 8. Courses of values of generator No. 1 during loss of excitation QG PG Time (s) (pu) -1 -0.5 0 0.5 1 1.5 1 2 3 4 5 6 7 8 9 10 NT UG Fig. 9. Courses of values of generator No. 2 during loss of excitation (pu) IB UB Time (s) -0.2 0 0.2 0.4 0.6 0.8 1 1 2 3 4 5 6 7 8 9 10 Fig. 10. Courses of values of generator No. 2 during loss of excita- tion Im (Z) Re (Z) 0.2 -0.2 -0.6 -1.0 -1.4 0.5 1 1.5-0.5 0 Fig. 11. Impedance measured with protection during loss of exci- tation (pu) PG1 Time (s)-0.2 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 1 3 5 7 9 11 13 15 PG3 PG2 Fig. 12. Courses of active powers of generators reactance Eq equals to excitation current Ib . It applies the following Eq = IB = E′ q − (Xd − X′ d) ∗ Id . (3) Let’s assume that on generator No. 2 at the time of 1 s there occurs the loss of excitation as result of short cir- cuit in excitation winding. The courses of relevant values are presented in Figs. 5 and 6, where PG stands for ac- tive power of generator, QG is reactive power of genera- tor, UG is voltage on generator terminals, NT is turbine power, IBUD is excitation current and UBUD is excitation voltage. From the courses presented in Figs. 5 and 6 it is ob- vious that after loss of excitation the machine starts to take reactive power from the grid and at the time just after the 4th second the machine loses synchronism. This is obvious from the saw-tooth courses of values (powers, voltage) that are typical for asynchronous operation. The impedance measured with protection in Fig. 7 responds well with its quality to the impedance course in the ref- erence article [10]. Figure 8 shows the courses of values of generator No. 1. From the presented courses it is obvious that generator No.1 responded to failure of generator No. 2 by increas- ing the production of active power (influence of rotations regulation) and also reactive power. However, since gen- erator No. 2 was not disconnected from the grid it also caused swings of remaining two machines operating in the grid. Figure 9 shows the courses of relevant values for gen- erator No. 2 for the scenario when the excitation winding was disconnected (ie the second method (Ib = 0)). When comparing the courses of values during loss of excitation it is obvious that the second method (i.e. dis-
  • 6. Journal of ELECTRICAL ENGINEERING 68 (2017), NO1 59 connection of excitation winding) is less favorable and ex- citation decreases faster and subsequently generator loses synchronism. The following figure shows the patterns of active powers of generators G1 to G3 for the case that protection acts during loss of excitation at the time t=9 s. It is clear that the protection shuts down generator G2 on time and this has significant importance from the perspective of maintaining the stability of remaining gen- erators operating in the grid. 6 Salient pole (hydrogenerator) vs cylindrical (turbogenerator) The publication [13] explains that the hydrogenerator should be immediately shut down after loss of excitation. The protection acts on signal, switch, de-excitation and quick release of the turbine. However, the protection will not shut down the turbogenerator immediately. It acts on automatics during loss of excitation (ANSI 40). The automatics acts on turbine regulator and decreases the generator power. Since it is heated up it enables the op- eration of generator in above synchronous rotations for some time. This is how operators or excitation regula- tor get time and can take an early action to eliminate the cause (if it is possible) and thus prevent unnecessary shut down of generator. If it is not possible to eliminate the cause until the specified period, the automatics will shut down the generator. We will try to analyze this situation in more detail. Hydroelectric generators are synchronous machines with salient poles where xd = xq . The generally applicable relation for calculation of electric active power supplied by generator into the grid, specified also above in this article, is simplified. Fully covered relation, described in per units, can be expressed as (in accordance with [14]) pe = ubuS x sin δ + u2 s xd − xq 2xdxq sin 2δ . (4) This relation consists of two elements. First is the torque, or power of synchronous machine that is proportional to excitation voltage (first part of equation). Second is so called reluctance power (second part) that is usually ne- glected in calculations. However, if it is considered and ub = 0, ie we assume the loss of excitation occurred, we determine there is reluctance power on the machine shaft. With detailed analysis of asynchronous and synchronous machine in excited and non-excited condition we can con- clude the following: 1) Asynchronous machine: has squirrel cage rotor with regular arrangement. During operation with asyn- chronous rotations neither swings nor power changes oc- cur during constant load. 2) Synchronous machine in excited condition: by in- creasing the power up to the stability limit only the in- ternal machine angle (rotor angle) increases. Once this limit is crossed synchronism loss and mechanical shocks on the shaft and turbine occur. These shocks have slip frequency. 3) Synchronous machine in non-excited condition: its behavior is somewhere between the two previous exam- ples. The machine continues to operate as asynchronous machine, ie with slip. It has obviously zero synchronous torque determined with the magnetic field of rotor. How- ever, there still operates the already mentioned reluctance torque that is proportional to the difference of longitudi- nal and transverse reactance of the machine. During each slip the swing (shock) originates, the intensity of which is also dependent on the difference of longitudinal and trans- verse reactance. This means that the average torque and power on the shaft remain approximately equally big as at the time before loss of excitation. The machine supplies asynchronous power (similarly as asynchronous machine) in the grid. The immediate power and torque of the ma- chine swing around this median at each slip by the value of reluctance power. If we consider the machine is turbo- generator, ie machine with cylindrical rotor, that has a very small difference between longitudinal and transverse reactance, the immediate value of power and torque of the machine will slightly swing. In case of hydroelectric generator, ie machine with salient poles, the swing will be apparent, since there is significant difference between the machine reactances. From this analysis it is obvious that the hydroelectric generator shall be shut down as soon as possible after loss of excitation. Turbogenerator can operate with approved asynchronous operation for some time, as long as it is al- lowed by the manufacturer. However, the question is why to keep such machine in non-excited condition further in operation. This depends on several factors: – operating method of the whole grid, – importance of machine that lost excitation protection, – will the outage of this machine be a threat for the grid stability? – can the machine supplying lower power for some time improve the grid stability? Basically, there are two viewpoints with respect to this issue. If the machine is shut down later, the grid stability will face a smaller threat, yet there will be higher risk of rotor overheating and machine damage. On the other hand, if the machine is shut down earlier, it will be bet- ter for the machine itself, yet with worse consequences for the grid stability. Practically, not even turbogener- ators are allowed to operate in asynchronous operation for above stated reason in order not to cross the allowed warming of rotor parts or damper (amortisseur) windings. Generally, it is subject of agreement of the grid operator, generator operator and generator manufacturer whether such machine is disconnected from the grid immediately or asynchronous operation is allowed for some time. Fi- nally, this time information should be provided by the manufacturer in type tests.
  • 7. 60 V. Kriˇstof , M. Meˇster: LOSS OF EXCITATION OF SYNCHRONOUS GENERATOR 7 Conclusion Article deals with loss of excitation of synchronous ge- nerator. It describes physical nature of this phenomenon, protection devices against loss of excitation and also shows possibility of using of network simulator MODES for loss of excitation analysis. The article emphasizes the need of this type of calcula- tions in real operation of transmission systems because of the loss of synchronism (stability) of synchronous genera- tor and the subsequent transition to asynchronous opera- tion is a very serious and unfavorable operating condition. Loss of synchronism can damage faulted generator but also can cause problems with stability (angle, voltage) in power system. In last chapter article analyzes possibility of operation when generator loses synchronism. There are three type of machine operation analyzed. This analysis shows that in case of turbogenerator further operation of generator must be allowed by producer of machine and also by operator of transmission system. In case of hydro- generator further operation is not allowed in any case. References [1] Z. Shi, ”Investigation on Generator Loss of Excitation Protec- tion in Generator Protection Coordination”, School of Electrical Engineering Royal, Institute of Technology, Stockholm, Sweden 2010, http://www.diva-portal.org/smash/get/diva2:610188/ fulltext01.pdf. [2] K. M´aslo and L. Haˇnka, ”Anal´yza asynchr´onn´ıho chodu gener- atoru”, 5. mezin´arodn´ı konference CP&HS 2002, Zl´ın, 2002, (in Czech). [3] O. Hora, Regulaˇcn´ı a bud´ıc´ı syst´emy synchronn´ıch stroj˚u, SNTL, Praha, 1985, (in Czech). [4] F. Jan´ıˇcek, V. Chladn´y, A. Bel´aˇn and ˇZ. Eleschov´a, Digit´alne ochrany v elektrizaˇcnej s´ustave. (Digital Protection in Power System), Vydavatel’stvo STU, Bratislava, 2004, (in Slovak). [5] K. M´aslo, ”The General Purpose Network Simulator MODES”, Proc. of the 4th Int. Workshop on El. Power System Control Centers, Rethymno, Greece, 1997. [6] H. G. Darron, J. K. Koepfinger, J. R. Mather and P. A. Pusche ”The Influence of Generator Loss of Excitation on Bulk Power System Reliability”, IEEE Trans Power Apparatus and Systems, vol. 94, no. 5, 1473–1481, 1975. [7] J. Tlust´y, J. Kyncl, L. Musil, J. ˇSpetlik, J. ˇSvec, P. Hamouz, M. M¨uller and Z. M¨uller, Monitorov´an´ı, ˇr´ızen´ı a chr´anˇen´ı elek- trizaˇcn´ıch soustav, ˇCesk´e vysok´e uˇcen´ı technick´e v Praze, Praha, 2011, (in Czech). [8] J. Berdy, ”Loss of Excitation Protection for Modern Syn- chronous Generator”, IEEE Trans Power Apparatus and Sys- tems, vol. 94, no. 5, 1457–1463, 1975. [9] IEEE Std.C37.102 - 2006: IEEE Guide for AC Generator pro- tection. IEEE Power System Society 2006. [10] Y. Siwang, W. Weijian, L. Ling, G. Ling and Q. Arui, ”Discus- sion on Setting Calculation of Loss of Excitation Protection for Large Turbogenerator”, International Conference on Electrical Machines and Systems (ICEMS), Incheon, 2010. [11] P. M. Anderson and A. A. Fouad, Power System Control and Stability, 1977, Iowa State Press University. [12] V. Chladn´y, Digit´alne ochrany v ES, Technick´a Univerzita Koˇsice, 2007, (in Slovak). [13] P. Dohn´alek, Ochrany pro pr˚umysl a energetiku, 1991, (in Czech). Received 18 November 2016 Vladim´ır Kriˇstof was born on July 1985 in Koˇsice, Slo- vakia. He received the MSc and PhD in Power System Engi- neering from Technical University in Koˇsice, Faculty of Elec- trical Engineering and Informatics, Department of Electric Power Engineering. He is currently Power system calculation specialist in company Power System Management, Ltd. He was a member of scientific teams on two scientific projects. He is also author or co-author of 2 university books and more than 20 scientific and technical papers. His work is focused in the field of power system stability, short-circuit currents, power quality and wide area monitoring system. Mari´an Meˇster born in 1973, received the MSc and PhD in Power Engineering from Technical University in Koˇsice. Since 1998 he teaches at Technical University in Koˇsice, Fac- ulty of Electrical Engineering and Informatics, Department of Electric Power Engineering. He is currently Head of Dis- tribution System Operation Section in distribution company V´ychodoslovensk´a distribuˇcn´a, a.s. He is also author or co- author of 5 books and more than 70 scientific and technical papers. He is focused on research in the field of stability of power system, short-circuit current and digital relays.