1) A three-phase system uses three coils arranged 120 degrees apart to induce current. This solves the problem of induction motors not being able to start on their own with a single-phase system.
2) The three-phase system can be represented by a wye or delta circuit connection. In a wye connection, the three phase currents sum to zero at the neutral point.
3) In a balanced three-phase system, the phase voltages and currents are equal in magnitude but 120 degrees out of phase. This results in the line voltages and currents being equal as well.
2. Flux density
B [T]
l
d
L
A
M
N
Generator for single phase
Current induces in the coil as the
coil moves in the magnetic field
Current produced at terminal
Note
Induction motor cannot start
by itself. This problem is
solved by introducing three
phase system
3. Instead of using one coil only , three coils are used arranged in one
axis with orientation of 120o each other. The coils are R-R1 , Y-Y1
and B-B1. The phases are measured in this sequence R-Y-B. I.e Y
lags R by 120o , B lags Y by 120o.
4. The three winding can be represented by the above circuit. In this
case we have six wires. The emf are represented by eR , eY, eB.
t
e
sin
Em
R
)
120
-
sin(
Em
Y
t
e
)
240
-
sin(
Em
B
t
e
Load
Finish
Finish
Finish
start
start
start
R
R1
Y
Y1
B
B1
L1
L2
L3
eR
eY
eB
5. The circuit can be simplified as follows, where R1 can be
connected to Y and Y1 can be connected to B. In this case
the circuit is reduced to 4 wires.
B
Y
R
1
RB e
e
e
e
)]
240
sin(
)
120
sin(
[sin
Em
t
t
t
120
sin
t
cos
120
cos
t
sin
t
[sin
m
E
]
240
sin
t
cos
240
cos
t
sin
]
t
866
.
0
t
sin
5
.
0
t
cos
866
.
0
t
sin
5
0
t
[sin
kos
.
Em
0
Since the total emf is zero, R and B1 can be connected together, thus
we arrive with delta connection system.
Finish
Finish
Finish
start
start
start
R
R1
Y
Y1
B
B1
eR+eY+eB
eR
eY
eB
6. R
R1
Y
Y1
B
B1
eB
eR
eY
Line
conductors
R
R1
Y
Y1
B
B1
PL
PM
PN
•Since the total emf is zero, R and B1 can be
connected together as in Fig.A , thus we arrive
with delta connection system as in Fig. C.
•The direction of the emf can be referred to the
emf waveform as in Fig. B where PL is +ve (R1-
R), PM is –ve (Y-Y1) and PN is –ve (B-B1).
Fig.A
Fig. B
Fig. C
7. •R1, Y1 and B1 are connected together.
•As the e.m.f generated are assumed in
positive direction , therefore the current
directions are also considered as flowing
in the positive direction.
•The current in the common wire (MN)
is equal to the sum of the generated
currents. i.e iR+iY+iB .
•This arrangement is called four –wire
star-connected system. The point N
refers to star point or neutral point.
R
R1
Y
Y1
B
B1
Generator Load
N
iR
iB
iY
1
iR+iY+iB
M
8. t
sin
i
m
R I
)
120
t
sin(
i
-
Im
Y
)
240
t
sin(
i
-
Im
B
The instantaneous current in loads L1 , L2 and L3 are
B
Y
R
N i
i
i
i
0
)]
240
t
sin(
)
120
t
sin(
t
[sin
m
I
R
R
1
Y Y
1
B
B1
Line
conductors
R
N
iR
iB
iY
iR
+iY
+iB
L3
L1
L2
B
Y
9. Three-wire star-connected system with
balanced load
For balanced loads, the fourth wire carries no current , so it can
be dispensed
R
R
1
Y Y
1
B
B1
N
L
L
L
a b c balanced
load
generator
coils
5A
10A
5A
0
8.66A
2.6A
9.7A
7.1A
8.66A
11. VR
VY
VB
-VY
-VB
-VR
VRY
VYB
VBR
)
( Y
R
Y
R
RY V
V
V
V
V
R
Y
B
N
VRY
VYB
IR
IB
IY
R
Y
B
N
V
VRY
VBR
VYB
IR
IB
IY
R
VY
VB
)
( B
Y
B
Y
YB V
V
V
V
V
)
( R
B
R
B
BR V
V
V
V
V
•VRY, VYB and VBR are called line voltage
•VR, VY and VB are called phase voltage
From Kirchoff voltage law we have
In phasor diagram
12. VR
VY
VB
-VY
-VB
-VR
VRY
VYB
VBR
For balanced load VR , VY and
VB are equaled but out of phase
VR = VP30;
VY = VP-90;
VB = VP150;
P
o
R
RY V
V
V 3
30
cos
2
therefore
VRY = VL30;
VYB = VL-90;
VBR = VL150;
P
o
Y
YB V
V
V 3
30
cos
2
P
o
B
BR V
V
V 3
30
cos
2
14. I3
R
Y
B
IB
IR
IY
I2
I1
•IR, IY and IB are called line current
•I1, I2 and I3 are called phase current
)
(
I
I
I 3
1
3
1
R I
I
)
(
I
I
I 1
2
1
2
Y I
I
)
(
I
I
I 2
3
2
3
B I
I
I2
I1
I3
-I3
-I2
-I1
IR
IY
IB
From Kirchoff current law we have
In phasor diagram
VL
VP
15. I2
I1
I3
-I3
-I2
-I1
IR
IY
IB
P
R I
I
I )
3
(
30
cos
2 1
P
Y I
I
I )
3
(
30
cos
2 2
P
B I
I
I 3
30
cos
2 3
Since the loads are balanced, the magnitude of currents are
equaled but 120o out of phase. i.e I1 =I2=I3 ,=IP Therefore:-
Thus IR=IY=IB = IL
Where IP is a phase current and IL is a line current
I1 = VP30;
I2 = VP-90;
I3 = VP150;
IR = IL30;
IY = IL-90;
IB = IL150;
17. Unbalanced load
In a three-phase four-wire system the line voltage is 400V
and non-inductive loads of 5 kW, 8 kW and 10 kW are
connected between the three conductors and the neutral.
Calculate: (a) the current in each phase
(b) the current in the neutral conductor.
18. V
V
V L
P 230
3
400
3
A
V
P
I
P
B
B 7
.
21
230
10
5 3
A
V
P
I
P
Y
Y 8
.
34
230
10
8 3
A
V
P
I
P
R
R 5
.
43
230
104
Voltage to neutral
Current in 8kW resistor
Current in 10kW resistor
Current in 5kW resistor
19. IR
IY
IB
IYH
IYV
IBH
IBV
A
.
I
I
I o
B
Y
H 3
.
11
7
.
21
8
.
34
866
0
30
cos
30
cos
A
I
I
I
I o
B
Y
R
V 0
.
13
)
7
.
21
8
.
34
(
5
.
0
5
.
43
60
cos
60
cos
INV
INH
IN
A
.
I
I
I NV
NH
N 2
.
17
0
.
13
3
11 2
2
2
2
Resolve the current components into horizontal and vertical
components.
21. 2
2
2
2
Y X
R
Z
2
2
60
20
2
2
1
Y
R
X
tan
20
60
tan 1
C
BR
3
X
V
I
90
)
10
30
50
2
/(
1
400
6
A
77
.
3
A
Z
V
I
Y
YB
32
.
6
60
20
400
2
2
2
o
90
In branch between YB , there are two components , R2 and X2
In the branch RB , only capacitor in
it , so the XC is -90 out of phase.
'
34
71
VRY
IR
I3
I2
VYB
VBR
I1
71o34'
90o
30o
-I3
30o
22. (b) 3
1
R I
I
I
2
3
3
1
2
1
2
cos
2 I
I
I
I
IR
3
.
56
77
.
3
30
cos
77
.
3
0
.
4
2
0
.
4
2
2
2
o
R
I
A
IR 5
.
7
1
2
Y I
I
I
2
1
2
1
2
2
2
cos
2 I
I
I
I
IY
5
.
105
0
.
4
'
34
11
cos
32
.
6
0
.
4
2
32
.
6
2
2
2
o
Y
I
A
IY 3
.
10
I1
-I1
I2
IY
120o
71o
34'
60o
= 71o 34’ -60o= 11o 34’
=30o
23. 2
2
2
3
2
3
2
cos
2 I
I
I
I
IB
5
.
18
77
.
3
'
26
138
cos
32
.
6
77
.
3
2
32
.
6
2
2
2
o
B
I
A
IB 3
.
4
= 180-30o-11o 34’ = 138o 34’
2
3
B I
I
I
-I2
I2
I3
I2
71o 34'
90o
30o
11o 34'
24. Power in three phase
Active power per phase = IPVP x power factor
Total active power= 3VPIP x power factor
cos
3 P
PI
V
P
If IL and VL are rms values for line current and line voltage
respectively. Then for delta () connection: VP = VL and IP
= IL/3. therefore:
cos
3 L
L I
V
P
For star connection () : VP = VL/3 and IP = IL. therefore:
cos
3 L
L I
V
P
25. A three-phase motor operating off a 400V system is developing
20kW at an efficiency of 0.87 p.u and a power factor of 0.82.
Calculate:
(a)The line current;
(b)The phase current if the windings are delta-connected.
(a) Since
watts
in
power
input
watts
in
power
output
Efficiency
f
p
V
I
watts
in
power
output
L
L .
3
82
.
0
400
3
1000
20
87
.
0
L
I
And line current =IL=40.0A
(b) For a delta-connected winding
A
current
line
current
Phase 1
.
23
3
0
.
40
3
26. Three identical coils, each having a resistance of 20 and
an inductance of 0.5 H connected in (a) star and (b) delta
to a three phase supply of 400 V; 50 Hz. Calculate the
current and the total power absorbed by both method of
connections.
20
RP
157
5
.
0
50
2
XP
2
2
P
P
P
P
P X
R
jX
R
Z
83
158
20
157
tan
157
20 1
2
2
First of all calculating the impedance of the coils
P
P
1
R
X
tan
where
1264
.
0
83
cos
cos
29. A balanced three phase load connected in star, each phase consists
of resistance of 100 paralleled with a capacitance of 31.8 F.
The load is connected to a three phase supply of 415 V; 50 Hz.
Calculate: (a) the line current;
(b) the power absorbed;
(c) total kVA;
(d) power factor .
415
V
240
3
415
3
V
V L
P
30. P
P
P
X
1
R
1
Y
C
j
1
XP
Admittance of the load
where
C
j
R
1
P
6
10
8
.
31
50
2
j
100
1
S
)
01
.
0
j
01
.
0
(
)
01
.
0
01
.
0
(
240 j
Y
V
I
I P
P
P
L
45
39
.
3
4
.
2
4
.
2
j
P
P
VA I
V
P
45
4
.
814
45
39
.
3
240
576
45
cos
4
.
814
PA
P
kW
728
.
1
576
3
PA
Line current
Volt-ampere per phase
Active power per phase
Total active power
31. kW
728
.
1
j
576
3
j
PR
Reactive power per phase 576
j
45
sin
4
.
814
j
PPR
Total reactive power
kVA
44
.
2
4
.
814
3
Total volt-ampere
(b)
(c)
(d)
Power Factor = cos = cos 45 = 0.707 (leading)
32. A three phase star-connected system having a phase voltage of
230V and loads consist of non reactive resistance of 4 , 5
and 6 respectively.
Calculate:(a) the current in each phase conductor
(b) the current in neutral conductor
and (c) total power absorbed.
A
5
.
57
4
230
I4
A
46
5
230
I5
A
3
.
38
6
230
I6
33. 57.5 A
46 A
38.3 A
X-component = 46 cos 30 + 38.3 cos 30 - 57.5 = 15.5 A
Y-component = 46 sin 30 - 38.3 sin 30 = 3.9 A
16A
3.9
15.5
I 2
2
N
Therefore
(b)
(c) kW
61
.
32
3
.
38
46
5
.
57
230
P