HOSPITAL FACILTY PLANNING BASICS
Space Management, Engineering Services
& Facility Correction
Season.EV , seasonev@gmail.com , Mobile no.9745863521
The Location
• Plot with sufficient water source
• Two way access road till hospital from main road
• Area not less than double the floor area.
• Three Entrances – Main , Emergency and Service Entries
Season.EV , seasonev@gmail.com , Mobile no.9745863521
FLOOR AREA OF HOSPITAL
• Approx. 800 – 1000 Sq Ft per bed/ hospital
FLOOR AREA ALLOCATION
• OPD – 12%-18%
• Wards, Rooms , ICUs & OT s – 37%-45%
• Diagnostic & Therapeutic – 18%-22%
• Administration – 8%-12%
• Service Departments – 15%-20%
Season.EV , seasonev@gmail.com , Mobile no.9745863521
Bureau Of Indian Standards -
Recommendations
• IS 10905-1: Recommendations for basic requirements of general
hospital buildings, Part 1: Administrative and hospital services
department buildings
• IS 10905-2: Recommendations for basic requirements of general
hospital buildings, Part 2: Medical services department buildings
• IS 10905-3: Recommendations for Basic Requirements of General
Hospital Buildings, Part 3: Engineering Services Department Buildings
Season.EV , seasonev@gmail.com , Mobile no.9745863521
• IS 12433-1: Basic requirements for hospital planning, Part 1: upto 30
bedded hospitals
• IS 12433-2: Basic Requirements for Hospital Planning, Part 2: UP to
100 Bedded Hospital
• Indian Public Health Standards - Governnment of India
• http://www.nhm.gov.in/nhm/nrhm/guidelines/indian-public-health-
standards.html
Season.EV , seasonev@gmail.com , Mobile no.9745863521
• CORRIDORS
• Main corridor should allow for passage of two beds with persons on
sides ~2.5 meter width
• Segregation of clean and dirty corridors
• OPD
• For every bed three patients are seen in OPD ( Expected OPD =No.of
Beds x 3 )
• 60% of area should be for waiting & corridors
• Consultation room – 150 sq ft
Season.EV , seasonev@gmail.com , Mobile no.9745863521
ICU
• Bed strength – 30% of total beds in a Tertiary care center
• Bed strength – 20% of total beds in a Secondary care center
• Each bed approximate 150 – 200 sq ft
Operation Theatres – Minimum nos.
• One OT per 50 beds
• Approximate 400 Sq.Ft area.
• 10 Feet height
Season.EV , seasonev@gmail.com , Mobile no.9745863521
HOSPITAL ENGINEERING SERVICES
PLANNING BASICS
Season.EV , seasonev@gmail.com , Mobile no.9745863521
SCOPE OF ENGINEERING SERVICES
• Electrical
• HVAC
• Plumbing and Sanitary
• Medical Gas
• Lift
• STP & ETP
• Boiler
• Incinerator
• Fire protection and Fire fighting
• Pneumatic tube systems
Season.EV , seasonev@gmail.com , Mobile no.9745863521
SCOPE OF IT SERVICES
• NETWORKING – Computer systems
• NETWORKING – Medical Equipments
• TV
• CCTV
• Telephones
• ACCESS points
• Nurse Call Systems
• PACS
• Wi Fi
Season.EV , seasonev@gmail.com , Mobile no.9745863521
Electrical - Minimum Requirements
• HT Substation with adequate cross ventilation
• Full back up Generator with adequate cross ventilation
• UPS power for all IT related Equipments.
• UPS power for all Critical care Medical Equipments ( which are
recommended to use UPS power)
• Panel rooms in all floors.
• DBs for Power, Lighting , UPS separately.
• Emergency lights in corridors , all critical care areas & fire escape
route staircase.
Season.EV , seasonev@gmail.com , Mobile no.9745863521
Regulations
Indian Standards
Electrical Inspectorate & Electricity Board rules.
SP 30 (2011): National Electrical Code of India
International Standards
• Electrical services - Health Technical Memorandum 06-01: Electrical
services supply and distribution ( UK )
• National Electrical Code USA, NFPA 70® & NFPA 90®
Season.EV , seasonev@gmail.com , Mobile no.9745863521
HVAC - Minimum Requirements
• Chiller plant room
• Heat rejection - Cooling Tower / Air cooled condensers
• AHU rooms ,Space for CSUs /FCUs
• All Chillers, AHUs and Pumps preferred with VFD starters
• Dedicated shafts for
• Chilled water piping,
• Supply , Return ,Fresh Air & Extract ducting .
Season.EV , seasonev@gmail.com , Mobile no.9745863521
HVAC - Minimum Requirements
• 1 Tr of Refrigeration approximate for 150 Sq.Ft.
• 1 Air change per hour ( ACH) Fresh Air for comfort applications.
• Low velocity ducting design ( DW 144 European std. , SMACNA US std.
Ducting Standards)
• Low Velocity Chilled water Design ( CIBSE British Guidelines )
• ASHRAE Guidelines for Air-conditioning & ventilation.
• Room Indoor design conditions – ASHRAE , NABH guidelines
Season.EV , seasonev@gmail.com , Mobile no.9745863521
• Chilled water pipe pressure test – Minimum twice the running
pressure.
• Valve selections – Minimum PN 20.
• Control Valves – Pressure Independent type.
• Pumps
Season.EV , seasonev@gmail.com , Mobile no.9745863521
Medical Gas - Minimum Requirements
• Medical Gas Manifold – Medical Oxygen
• 100 beds and Above – Main Manifold Minimum 8 x 8 cylinders ,
Emergency 4 cylinders
• 200 beds and Above – Main Manifold Minimum 10 x 10 cylinders ,
Emergency 5 cylinders , Liquid Medical Oxygen Tanks with 5000 ltrs
capacity preferred.
• 500 beds and Above – Main Manifold Minimum 12 x 12 cylinders ,
Emergency 4 cylinders , Liquid Medical Oxygen Tanks with 10000 ltrs
capacity preferred.
Season.EV , seasonev@gmail.com , Mobile no.9745863521
Medical Gas - Minimum Requirements
• OT : Oxygen , Nitrous oxide, Carbon Di oxide ,Medical Air ( 4 Bar)
,Surgical Air ( 7 Bar) ,Vacuum , AGSS.
• ICUs : Oxygen , Medical Air ( 4 Bar) ,Vacuum.
• Rooms & wards : Oxygen , Vacuum.
• Medical Oxygen usage : ( Qty. to be specified by Doctor)
• Normal patients : 2 ltrs per Hour.
• Ventilator patients : Approx. 10 ltrs per Hour.(if 100 % )
Season.EV , seasonev@gmail.com , Mobile no.9745863521
Medical Gas - Minimum Requirements
• Liquid Medical Oxygen Plant – As per specs of PESO ( Petroleum &
Explosives Safety Organisation)
• Manifold room and Compressor Rooms - As per HTM 02-01
standards,ISO 7396 -1:2007
• Pressure Control Stations - As per HTM 02-01 standards , ISO 10524 -
2:2007
Season.EV , seasonev@gmail.com , Mobile no.9745863521
Medical Gas - Pressure @ Area Valve Control Unit
• O2 , N2O , Co2 , Medical Air -
Minimum pressure 45 PSI ( 3.16 Kg/ Cm3) & Maximum pressure 75 PSI
( 5.27 Kg/ Cm3)
Surgical Air - Minimum pressure 95 PSI ( 6.67 Kg/ Cm3) & Maximum
pressure 105 PSI ( 7.38 Kg/ Cm3)
Vacuum - Minimum suction pressure 12 mm / Hg & Maximum Suction
pressure 32 mm / Hg.
Season.EV , seasonev@gmail.com , Mobile no.9745863521
Plumbing & Sanitary - Minimum Requirements
• Minimum of two water sources
• Water storage capacity for two days(approximately 1000 ltrs per bed
* 2 days)
• Water tanks with stand by for each domestic, flush & fire tanks
• Disinfection of water tanks and supply lines
• Water Treatment Plant
• Pumping system with standby
• R.O Water for Dialysis and for sterlization
• Hot water system for rooms & kitchen
Season.EV , seasonev@gmail.com , Mobile no.9745863521
Sewage & Effluent Treatment.
• As per Central Pollution Control board – Each bed produces 450 ltrs of
Soiled water. ( in kerala our normal usage is 800 Ltrs to 1000 Ltrs)
• Minimum Size of STP/ETP = No.of Beds x 450 ltrs.
• Separate pipelines of Sewage , Laundry and Kitchen
• Separate treatments for Sewage , Laundry and Kitchen .
• STP output water preferred characteristics :
Sl No. Parameters Treated water KSPCB Standards
1 PH 6.5-7.5 5.5-9.0
2 BOD 3 days at 270c <15 mg/l 30 mg/l
3 COD, mg/l < 50 mg/l 250 mg/l
3 Suspended Solids <50 mg/l 100 mg/l
4 Oil & Grease <1mg/l 10 mg/l
Season.EV , seasonev@gmail.com , Mobile no.9745863521
LIFTS minimum nos. required
• Depends upon number of beds above groundfloor
• Up to 50 – one; Every 50 beds 1 No. Lift each.
• Lift Car Size – >2280X1600X2300 mm ; with door size >1300X2100
mm
• ARD for each Lift
• Machine room : With adequate Light , Ventilation and dust free
condition with suitable nos. of Rope holes, Ceiling Hooks. Dedicated
power supply with ELCB.
Season.EV , seasonev@gmail.com , Mobile no.9745863521
LIFTS minimum nos. required
• Lift Shaft size : Depth more than 700mm Lift Size.
• Lift Shaft size : Width more than 300 mm in each side than Lift size.
• Lift Shaft size : Entrance opening more than 200 mm than lift size.
• Lift Shafts to be with Lights in each floors ,Pit ladder and without
plumb.
• Pit depth depending upon Lift size ,speed and Manufacturer.
Season.EV , seasonev@gmail.com , Mobile no.9745863521
Engineering Services - Requirements
•Electrical Substation ,Panel room Space for Panels,DBs Shaft Cabling
•HVAC Chiller plant Space for AHUs & Panels
Shaft Cabling
Piping ( Chilled water in &
out , Drain pipes Ducting
•Plumbing and Sanitary Pump room ,Tanks
Accees point / Shaft doors / Ceiling
trap doors
Shaft Piping
•Medical Gas
Med.Gas Manifold room ,
Compressor room.
Accees point / Shaft doors / Ceiling
trap doors
Shaft Piping
•Lift Lift roooms , Lift pit. Lift rooms Shaft/ lift well Cabling
•Boiler Plant room Ceiling trap doors Shaft Piping
•Fire protection and Fire fighting Pump room ,Tanks
Accees point / Shaft doors / Ceiling
trap doors
Shaft Cabling Piping
•Pneumatic tube systems Plant room Accees points /Ceiling trap doors
Shaft Cabling Piping
•NETWORKING – Computer systems
Server room , Floor wise IT rooms. Ceiling trap doors
Shaft Cabling
•NETWORKING – Medical Equipments Shaft Cabling
•TV Shaft Cabling
•CCTV Shaft Cabling
•Telephones Shaft Cabling
•ACCESS points Shaft Cabling
•Nurse Call Systems Shaft Cabling
•PACS Shaft Cabling
•Wi Fi Shaft Cabling
Season.EV , seasonev@gmail.com , Mobile no.9745863521
FIRE MANAGEMENT SYSTEMS
• Fire fighting is the act of extinguishing fires to protect lives and to prevent
the destruction of property and of the environment
System consist of
• Fire Pump and Fire Tanks
• Fire Hydrant Systems
• Sprinklers
• Fire Extinguishers
• FM200/ Clean Agents (such as Novec systems…)
Season.EV , seasonev@gmail.com , Mobile no.9745863521
Exit Facilities:
In buildings or sections occupied by bed-ridden patients where the floor area is over
280 m2, facilities shall be
• provided to move patients in hospital beds to the other side of a smoke barrier
from any part of such building or
• section not directly served by approved horizontal exits or exits from the first
floor (floor 2) of a building to the outside.
Not less than two exits of one or more of the following types shall be provided for
every floor, including basement, of every building or section:
a) Doors leading directly outside the building;
b) Stairways;
c) Ramps;
d) Horizontal exits; and
e) Fire tower.
Season.EV , seasonev@gmail.com , Mobile no.9745863521
Exit Facilities
• All required exits that serve as egress from hospital or infirmary sections
shall be not less than 2 m in clear width
• All patient bedroom doors to permit transportation of patients on beds,
litters, or mattresses.
• Min. width of corridors to serve patients bedrooms shall be 2500 mm.
• UPS Lighting in fire stairs to be provided for use when the raw power
supply fails.
• That part of emergency lighting ( With UPS power ) is provided to ensure
that the escape route is illuminated at all times or at times the main
lighting is not available, either for the whole building or the escape routes.
Season.EV , seasonev@gmail.com , Mobile no.9745863521
Fire Exit Doors
• DOOR: The door with a fire resistance rating 2 hrs.
• SIGNAGES: Fire exit doors and way to the Fire exit doors
are marked in WHITE letters in GREEN background and
are either marked with self-luminous material or
illuminated with battery back up.
• SMOKE FREE: It is Fire/smoke free area through which
the personal in the building can be evacuated safely.
• PANIC BAR: The Fire exit doors have a panic bar hard
ware provided on the door.
• ACCESS CONTROL: Fire doors to have Fail safe access
control options
Season.EV , seasonev@gmail.com , Mobile no.9745863521
S.N o
Type of
building /
Occupancy
Type Of Installation Water Supply (in liters) Pump Capacity (inL/min)
Fire
Extinguis
her
Hose
Reel
Dry
Riser
Wet Riser Downcomer
yard
Hydrant
Automatic Sprinkler System
Manually Operated Eletric
Fire Alarm System
Automatic
Detection
& Fire
Alarm
System
Undergrou
nd Static
Water
Storage
Tank
Terrace Tank
pump near
underground
static water
storage tank
with min
pressure
3.5kg/cm2at
terrace level
At the
terrece
tank level
with min
pressure
2kg/cm2
1
Ground Plus
2 or more
storeys,with
bed
R R NR R NR NR R R R 50000 5000 NOTE 3 NR
2
Less than
15m in
height with
plot area
more than
1000m2
R R NR R NR R R R R 10000 10000 NOTE 3 NR
3
Above 15m
height but
not
exceeding
24m in hight
R R NR R NR R R R R 100000 20000 NOTE 4 NR
4
Above 15m
height but
not
exceeding
30m in hight
R R NR R NR R R R R 150000 20000 NOTE 5 NR
Note 3 One electric & one diesel pump of capacity 1620 ipm and one electric pump of capacity 180 Ipm
R = Requried / NR = Not RequriedNote 4 One electric & one diesel pump of capacity 2280 ipm and one electric pump of capacity 180 Ipm
Note 5 One electric & one diesel pump of capacity 2280 ipm and one electric pump of capacity 180 Ipm
Season.EV , seasonev@gmail.com , Mobile no.9745863521
Recommended to refer :
• National Building Code of India – Part 4 Fire & Life safety
• National Disaster Management Guidelines – Hospital Safety
• ( National disaster Management Authority, Govt.of India)
• Indian Standard Code of Practice for Fire Safety
• NABH & FIRE SAFETY
• NFPA standards
Season.EV , seasonev@gmail.com , Mobile no.9745863521

More Related Content

What's hot

Report on hospital design
Report on hospital designReport on hospital design
Report on hospital designBee Key Verma
 
Final hospital planning and layout ppt
Final hospital planning and layout pptFinal hospital planning and layout ppt
Final hospital planning and layout pptSandeep Singh
 
500 Bed Hospital
500 Bed Hospital500 Bed Hospital
500 Bed HospitalShayne Galo
 
Spatial organisation in Hospital Design
Spatial organisation in Hospital DesignSpatial organisation in Hospital Design
Spatial organisation in Hospital DesignTanisha Agarwal
 
Designing of OPD and day care services
Designing of OPD and day care servicesDesigning of OPD and day care services
Designing of OPD and day care servicesDrSiddharthSingh5
 
Design and Management of Opd
Design and Management of OpdDesign and Management of Opd
Design and Management of OpdDr. Divya Khandelwal
 
Hospital Design Guide: How to Get Started
Hospital Design Guide: How to Get StartedHospital Design Guide: How to Get Started
Hospital Design Guide: How to Get StartedHussain Varawalla
 
Inpatient dpt of Hospital (IPD)
Inpatient dpt of Hospital (IPD)Inpatient dpt of Hospital (IPD)
Inpatient dpt of Hospital (IPD)Vidya Neelesh
 
Hospital planning
Hospital planningHospital planning
Hospital planningawantika diwan
 
Hospital. engineering service
Hospital. engineering serviceHospital. engineering service
Hospital. engineering serviceNc Das
 
literature study for EMERGENCY DEPARTMENT in hospital
literature study for EMERGENCY DEPARTMENT in hospitalliterature study for EMERGENCY DEPARTMENT in hospital
literature study for EMERGENCY DEPARTMENT in hospitalBalaji Ar
 
CASE STUDY HOSPITAL.pptx
CASE STUDY HOSPITAL.pptxCASE STUDY HOSPITAL.pptx
CASE STUDY HOSPITAL.pptxAliAzharRajput
 
Hospital design
Hospital designHospital design
Hospital designdhobacyare
 
Planning for New Hospital
Planning for New HospitalPlanning for New Hospital
Planning for New HospitalNc Das
 
Hospital hvac design salah ramadan
Hospital hvac design  salah ramadanHospital hvac design  salah ramadan
Hospital hvac design salah ramadanEng Salah Ramadan
 
gynecology , neurology , nephrology
gynecology , neurology , nephrologygynecology , neurology , nephrology
gynecology , neurology , nephrologyShivani Nandgowle
 
HOSPITAL LAUNDRY DESIGN literature study - RM
HOSPITAL LAUNDRY DESIGN  literature study - RMHOSPITAL LAUNDRY DESIGN  literature study - RM
HOSPITAL LAUNDRY DESIGN literature study - RMRishadmufas1
 
Hospital Design Case Study
Hospital Design Case StudyHospital Design Case Study
Hospital Design Case StudyGargi Bhatele
 

What's hot (20)

Report on hospital design
Report on hospital designReport on hospital design
Report on hospital design
 
Final hospital planning and layout ppt
Final hospital planning and layout pptFinal hospital planning and layout ppt
Final hospital planning and layout ppt
 
500 Bed Hospital
500 Bed Hospital500 Bed Hospital
500 Bed Hospital
 
Spatial organisation in Hospital Design
Spatial organisation in Hospital DesignSpatial organisation in Hospital Design
Spatial organisation in Hospital Design
 
HOSPITAL PLANNING
HOSPITAL PLANNINGHOSPITAL PLANNING
HOSPITAL PLANNING
 
Designing of OPD and day care services
Designing of OPD and day care servicesDesigning of OPD and day care services
Designing of OPD and day care services
 
Design and Management of Opd
Design and Management of OpdDesign and Management of Opd
Design and Management of Opd
 
IPD Hospital
IPD Hospital IPD Hospital
IPD Hospital
 
Hospital Design Guide: How to Get Started
Hospital Design Guide: How to Get StartedHospital Design Guide: How to Get Started
Hospital Design Guide: How to Get Started
 
Inpatient dpt of Hospital (IPD)
Inpatient dpt of Hospital (IPD)Inpatient dpt of Hospital (IPD)
Inpatient dpt of Hospital (IPD)
 
Hospital planning
Hospital planningHospital planning
Hospital planning
 
Hospital. engineering service
Hospital. engineering serviceHospital. engineering service
Hospital. engineering service
 
literature study for EMERGENCY DEPARTMENT in hospital
literature study for EMERGENCY DEPARTMENT in hospitalliterature study for EMERGENCY DEPARTMENT in hospital
literature study for EMERGENCY DEPARTMENT in hospital
 
CASE STUDY HOSPITAL.pptx
CASE STUDY HOSPITAL.pptxCASE STUDY HOSPITAL.pptx
CASE STUDY HOSPITAL.pptx
 
Hospital design
Hospital designHospital design
Hospital design
 
Planning for New Hospital
Planning for New HospitalPlanning for New Hospital
Planning for New Hospital
 
Hospital hvac design salah ramadan
Hospital hvac design  salah ramadanHospital hvac design  salah ramadan
Hospital hvac design salah ramadan
 
gynecology , neurology , nephrology
gynecology , neurology , nephrologygynecology , neurology , nephrology
gynecology , neurology , nephrology
 
HOSPITAL LAUNDRY DESIGN literature study - RM
HOSPITAL LAUNDRY DESIGN  literature study - RMHOSPITAL LAUNDRY DESIGN  literature study - RM
HOSPITAL LAUNDRY DESIGN literature study - RM
 
Hospital Design Case Study
Hospital Design Case StudyHospital Design Case Study
Hospital Design Case Study
 

Similar to Hospital space &amp; engineering services planning basics by season

About engineering department and its installations
About engineering department and its installationsAbout engineering department and its installations
About engineering department and its installationsPolly Thomas
 
Calibration introduction
Calibration introductionCalibration introduction
Calibration introductionsigmatest21
 
Electromechanical systems in hospitals, 061205
Electromechanical systems in hospitals, 061205Electromechanical systems in hospitals, 061205
Electromechanical systems in hospitals, 061205Moustafa M Elsayed
 
Hospital engineering
Hospital engineeringHospital engineering
Hospital engineeringkarthik5500
 
A Trusted Steam Flow Meter Manufacturer and Supplier- Manas
A Trusted Steam Flow Meter Manufacturer and Supplier- ManasA Trusted Steam Flow Meter Manufacturer and Supplier- Manas
A Trusted Steam Flow Meter Manufacturer and Supplier- ManasManasMicrosystems
 
Pyrosales Catalogue - Total Sensor Solution Providers
Pyrosales Catalogue - Total Sensor Solution ProvidersPyrosales Catalogue - Total Sensor Solution Providers
Pyrosales Catalogue - Total Sensor Solution ProvidersPYROSALES
 
Energy conservation Opportunities - Offices
Energy conservation Opportunities - OfficesEnergy conservation Opportunities - Offices
Energy conservation Opportunities - Officesravindradatar
 
NZEUKWU CHIJIOKE JOHN cv {updated}
NZEUKWU CHIJIOKE JOHN cv {updated}NZEUKWU CHIJIOKE JOHN cv {updated}
NZEUKWU CHIJIOKE JOHN cv {updated}Chijioke Eluwa Nzeukwu
 
Automation in seasonal management practices
Automation in seasonal management practicesAutomation in seasonal management practices
Automation in seasonal management practicesVijay4356
 
How to hande greasy waste in industrial kitchens
How to hande greasy waste in industrial kitchensHow to hande greasy waste in industrial kitchens
How to hande greasy waste in industrial kitchensDillen Valerie
 
Capstone turbine corporation e-finity distributed generation
Capstone turbine corporation  e-finity distributed generation Capstone turbine corporation  e-finity distributed generation
Capstone turbine corporation e-finity distributed generation TNenergy
 
Resume Electrical -1
Resume Electrical -1Resume Electrical -1
Resume Electrical -1MAGESHWARAN MANI
 
Introduction to Heat Pump Systems: Installation, Maintenance, and Repair
Introduction to Heat Pump Systems: Installation, Maintenance, and RepairIntroduction to Heat Pump Systems: Installation, Maintenance, and Repair
Introduction to Heat Pump Systems: Installation, Maintenance, and RepairEconoair Heating & Cooling Inc.
 
Heatpulse 4100 s rapid thermal processor
Heatpulse 4100 s rapid thermal processorHeatpulse 4100 s rapid thermal processor
Heatpulse 4100 s rapid thermal processorEmily Tan
 
MadgeTech Wireless Data Loggers
MadgeTech Wireless Data LoggersMadgeTech Wireless Data Loggers
MadgeTech Wireless Data LoggersMadgeTech Inc
 

Similar to Hospital space &amp; engineering services planning basics by season (20)

About engineering department and its installations
About engineering department and its installationsAbout engineering department and its installations
About engineering department and its installations
 
Calibration introduction
Calibration introductionCalibration introduction
Calibration introduction
 
Electromechanical systems in hospitals, 061205
Electromechanical systems in hospitals, 061205Electromechanical systems in hospitals, 061205
Electromechanical systems in hospitals, 061205
 
Hospital engineering
Hospital engineeringHospital engineering
Hospital engineering
 
pH electrodes-pH sensors CPS41
pH electrodes-pH sensors CPS41pH electrodes-pH sensors CPS41
pH electrodes-pH sensors CPS41
 
Specifications gc
Specifications gcSpecifications gc
Specifications gc
 
A Trusted Steam Flow Meter Manufacturer and Supplier- Manas
A Trusted Steam Flow Meter Manufacturer and Supplier- ManasA Trusted Steam Flow Meter Manufacturer and Supplier- Manas
A Trusted Steam Flow Meter Manufacturer and Supplier- Manas
 
Specifications aas
Specifications aasSpecifications aas
Specifications aas
 
Pyrosales Catalogue - Total Sensor Solution Providers
Pyrosales Catalogue - Total Sensor Solution ProvidersPyrosales Catalogue - Total Sensor Solution Providers
Pyrosales Catalogue - Total Sensor Solution Providers
 
Energy conservation Opportunities - Offices
Energy conservation Opportunities - OfficesEnergy conservation Opportunities - Offices
Energy conservation Opportunities - Offices
 
NZEUKWU CHIJIOKE JOHN cv {updated}
NZEUKWU CHIJIOKE JOHN cv {updated}NZEUKWU CHIJIOKE JOHN cv {updated}
NZEUKWU CHIJIOKE JOHN cv {updated}
 
Automation in seasonal management practices
Automation in seasonal management practicesAutomation in seasonal management practices
Automation in seasonal management practices
 
How to hande greasy waste in industrial kitchens
How to hande greasy waste in industrial kitchensHow to hande greasy waste in industrial kitchens
How to hande greasy waste in industrial kitchens
 
Capstone turbine corporation e-finity distributed generation
Capstone turbine corporation  e-finity distributed generation Capstone turbine corporation  e-finity distributed generation
Capstone turbine corporation e-finity distributed generation
 
Resume Electrical -1
Resume Electrical -1Resume Electrical -1
Resume Electrical -1
 
Introduction to Heat Pump Systems: Installation, Maintenance, and Repair
Introduction to Heat Pump Systems: Installation, Maintenance, and RepairIntroduction to Heat Pump Systems: Installation, Maintenance, and Repair
Introduction to Heat Pump Systems: Installation, Maintenance, and Repair
 
Heatpulse 4100 s rapid thermal processor
Heatpulse 4100 s rapid thermal processorHeatpulse 4100 s rapid thermal processor
Heatpulse 4100 s rapid thermal processor
 
Labsol Product Catalog
Labsol Product CatalogLabsol Product Catalog
Labsol Product Catalog
 
Qualification of high performance liquid chromatography
Qualification of high performance liquid chromatographyQualification of high performance liquid chromatography
Qualification of high performance liquid chromatography
 
MadgeTech Wireless Data Loggers
MadgeTech Wireless Data LoggersMadgeTech Wireless Data Loggers
MadgeTech Wireless Data Loggers
 

Recently uploaded

VIP Call Girl Sector 10 Noida Call Me: 9711199171
VIP Call Girl Sector 10 Noida Call Me: 9711199171VIP Call Girl Sector 10 Noida Call Me: 9711199171
VIP Call Girl Sector 10 Noida Call Me: 9711199171Call Girls Service Gurgaon
 
VIP Call Girls Noida Jhanvi 9711199171 Best VIP Call Girls Near Me
VIP Call Girls Noida Jhanvi 9711199171 Best VIP Call Girls Near MeVIP Call Girls Noida Jhanvi 9711199171 Best VIP Call Girls Near Me
VIP Call Girls Noida Jhanvi 9711199171 Best VIP Call Girls Near Memriyagarg453
 
Jalna Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Jalna Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetJalna Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Jalna Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetCall Girls Service
 
Call Girl In Zirakpur ❤️♀️@ 9988299661 Zirakpur Call Girls Near Me ❤️♀️@ Sexy...
Call Girl In Zirakpur ❤️♀️@ 9988299661 Zirakpur Call Girls Near Me ❤️♀️@ Sexy...Call Girl In Zirakpur ❤️♀️@ 9988299661 Zirakpur Call Girls Near Me ❤️♀️@ Sexy...
Call Girl In Zirakpur ❤️♀️@ 9988299661 Zirakpur Call Girls Near Me ❤️♀️@ Sexy...Sheetaleventcompany
 
ooty Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
ooty Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meetooty Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
ooty Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetCall Girls Service
 
Call Girls Patiala Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Patiala Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Patiala Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Patiala Just Call 9907093804 Top Class Call Girl Service AvailableDipal Arora
 
(Deeksha) 💓 9920725232 💓High Profile Call Girls Navi Mumbai You Can Get The S...
(Deeksha) 💓 9920725232 💓High Profile Call Girls Navi Mumbai You Can Get The S...(Deeksha) 💓 9920725232 💓High Profile Call Girls Navi Mumbai You Can Get The S...
(Deeksha) 💓 9920725232 💓High Profile Call Girls Navi Mumbai You Can Get The S...Ahmedabad Call Girls
 
bhubaneswar Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
bhubaneswar Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meetbhubaneswar Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
bhubaneswar Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetCall Girls Service
 
VIP Call Girls Noida Sia 9711199171 High Class Call Girl Near Me
VIP Call Girls Noida Sia 9711199171 High Class Call Girl Near MeVIP Call Girls Noida Sia 9711199171 High Class Call Girl Near Me
VIP Call Girls Noida Sia 9711199171 High Class Call Girl Near Memriyagarg453
 
Muzaffarpur Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Muzaffarpur Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetMuzaffarpur Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Muzaffarpur Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetCall Girls Service
 
Call Girl Raipur 📲 9999965857 whatsapp live cam sex service available
Call Girl Raipur 📲 9999965857 whatsapp live cam sex service availableCall Girl Raipur 📲 9999965857 whatsapp live cam sex service available
Call Girl Raipur 📲 9999965857 whatsapp live cam sex service availablegragmanisha42
 
VIP Call Girl Sector 32 Noida Just Book Me 9711199171
VIP Call Girl Sector 32 Noida Just Book Me 9711199171VIP Call Girl Sector 32 Noida Just Book Me 9711199171
VIP Call Girl Sector 32 Noida Just Book Me 9711199171Call Girls Service Gurgaon
 
Call Girls Thane Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Thane Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Thane Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Thane Just Call 9907093804 Top Class Call Girl Service AvailableDipal Arora
 
Chandigarh Call Girls 👙 7001035870 👙 Genuine WhatsApp Number for Real Meet
Chandigarh Call Girls 👙 7001035870 👙 Genuine WhatsApp Number for Real MeetChandigarh Call Girls 👙 7001035870 👙 Genuine WhatsApp Number for Real Meet
Chandigarh Call Girls 👙 7001035870 👙 Genuine WhatsApp Number for Real Meetpriyashah722354
 
Call Now ☎ 9999965857 !! Call Girls in Hauz Khas Escort Service Delhi N.C.R.
Call Now ☎ 9999965857 !! Call Girls in Hauz Khas Escort Service Delhi N.C.R.Call Now ☎ 9999965857 !! Call Girls in Hauz Khas Escort Service Delhi N.C.R.
Call Now ☎ 9999965857 !! Call Girls in Hauz Khas Escort Service Delhi N.C.R.ktanvi103
 
dhanbad Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
dhanbad Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meetdhanbad Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
dhanbad Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetCall Girls Service
 
Russian Call Girls in Noida Pallavi 9711199171 High Class Call Girl Near Me
Russian Call Girls in Noida Pallavi 9711199171 High Class Call Girl Near MeRussian Call Girls in Noida Pallavi 9711199171 High Class Call Girl Near Me
Russian Call Girls in Noida Pallavi 9711199171 High Class Call Girl Near Memriyagarg453
 
Tirupati Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Tirupati Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetTirupati Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Tirupati Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetCall Girls Service
 
9316020077📞Goa Call Girls Numbers, Call Girls Whatsapp Numbers Goa
9316020077📞Goa  Call Girls  Numbers, Call Girls  Whatsapp Numbers Goa9316020077📞Goa  Call Girls  Numbers, Call Girls  Whatsapp Numbers Goa
9316020077📞Goa Call Girls Numbers, Call Girls Whatsapp Numbers Goarussian goa call girl and escorts service
 
Nanded Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Nanded Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetNanded Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Nanded Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetCall Girls Service
 

Recently uploaded (20)

VIP Call Girl Sector 10 Noida Call Me: 9711199171
VIP Call Girl Sector 10 Noida Call Me: 9711199171VIP Call Girl Sector 10 Noida Call Me: 9711199171
VIP Call Girl Sector 10 Noida Call Me: 9711199171
 
VIP Call Girls Noida Jhanvi 9711199171 Best VIP Call Girls Near Me
VIP Call Girls Noida Jhanvi 9711199171 Best VIP Call Girls Near MeVIP Call Girls Noida Jhanvi 9711199171 Best VIP Call Girls Near Me
VIP Call Girls Noida Jhanvi 9711199171 Best VIP Call Girls Near Me
 
Jalna Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Jalna Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetJalna Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Jalna Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
 
Call Girl In Zirakpur ❤️♀️@ 9988299661 Zirakpur Call Girls Near Me ❤️♀️@ Sexy...
Call Girl In Zirakpur ❤️♀️@ 9988299661 Zirakpur Call Girls Near Me ❤️♀️@ Sexy...Call Girl In Zirakpur ❤️♀️@ 9988299661 Zirakpur Call Girls Near Me ❤️♀️@ Sexy...
Call Girl In Zirakpur ❤️♀️@ 9988299661 Zirakpur Call Girls Near Me ❤️♀️@ Sexy...
 
ooty Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
ooty Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meetooty Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
ooty Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
 
Call Girls Patiala Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Patiala Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Patiala Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Patiala Just Call 9907093804 Top Class Call Girl Service Available
 
(Deeksha) 💓 9920725232 💓High Profile Call Girls Navi Mumbai You Can Get The S...
(Deeksha) 💓 9920725232 💓High Profile Call Girls Navi Mumbai You Can Get The S...(Deeksha) 💓 9920725232 💓High Profile Call Girls Navi Mumbai You Can Get The S...
(Deeksha) 💓 9920725232 💓High Profile Call Girls Navi Mumbai You Can Get The S...
 
bhubaneswar Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
bhubaneswar Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meetbhubaneswar Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
bhubaneswar Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
 
VIP Call Girls Noida Sia 9711199171 High Class Call Girl Near Me
VIP Call Girls Noida Sia 9711199171 High Class Call Girl Near MeVIP Call Girls Noida Sia 9711199171 High Class Call Girl Near Me
VIP Call Girls Noida Sia 9711199171 High Class Call Girl Near Me
 
Muzaffarpur Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Muzaffarpur Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetMuzaffarpur Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Muzaffarpur Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
 
Call Girl Raipur 📲 9999965857 whatsapp live cam sex service available
Call Girl Raipur 📲 9999965857 whatsapp live cam sex service availableCall Girl Raipur 📲 9999965857 whatsapp live cam sex service available
Call Girl Raipur 📲 9999965857 whatsapp live cam sex service available
 
VIP Call Girl Sector 32 Noida Just Book Me 9711199171
VIP Call Girl Sector 32 Noida Just Book Me 9711199171VIP Call Girl Sector 32 Noida Just Book Me 9711199171
VIP Call Girl Sector 32 Noida Just Book Me 9711199171
 
Call Girls Thane Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Thane Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Thane Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Thane Just Call 9907093804 Top Class Call Girl Service Available
 
Chandigarh Call Girls 👙 7001035870 👙 Genuine WhatsApp Number for Real Meet
Chandigarh Call Girls 👙 7001035870 👙 Genuine WhatsApp Number for Real MeetChandigarh Call Girls 👙 7001035870 👙 Genuine WhatsApp Number for Real Meet
Chandigarh Call Girls 👙 7001035870 👙 Genuine WhatsApp Number for Real Meet
 
Call Now ☎ 9999965857 !! Call Girls in Hauz Khas Escort Service Delhi N.C.R.
Call Now ☎ 9999965857 !! Call Girls in Hauz Khas Escort Service Delhi N.C.R.Call Now ☎ 9999965857 !! Call Girls in Hauz Khas Escort Service Delhi N.C.R.
Call Now ☎ 9999965857 !! Call Girls in Hauz Khas Escort Service Delhi N.C.R.
 
dhanbad Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
dhanbad Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meetdhanbad Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
dhanbad Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
 
Russian Call Girls in Noida Pallavi 9711199171 High Class Call Girl Near Me
Russian Call Girls in Noida Pallavi 9711199171 High Class Call Girl Near MeRussian Call Girls in Noida Pallavi 9711199171 High Class Call Girl Near Me
Russian Call Girls in Noida Pallavi 9711199171 High Class Call Girl Near Me
 
Tirupati Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Tirupati Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetTirupati Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Tirupati Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
 
9316020077📞Goa Call Girls Numbers, Call Girls Whatsapp Numbers Goa
9316020077📞Goa  Call Girls  Numbers, Call Girls  Whatsapp Numbers Goa9316020077📞Goa  Call Girls  Numbers, Call Girls  Whatsapp Numbers Goa
9316020077📞Goa Call Girls Numbers, Call Girls Whatsapp Numbers Goa
 
Nanded Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Nanded Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real MeetNanded Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
Nanded Call Girls 👙 6297143586 👙 Genuine WhatsApp Number for Real Meet
 

Hospital space &amp; engineering services planning basics by season

  • 1. Season’s Greetings !! Somos Uno !! “ we are one “ Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 2. HOSPITAL FACILTY PLANNING BASICS Space Management, Engineering Services & Facility Correction Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 3. The Location • Plot with sufficient water source • Two way access road till hospital from main road • Area not less than double the floor area. • Three Entrances – Main , Emergency and Service Entries Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 4. FLOOR AREA OF HOSPITAL • Approx. 800 – 1000 Sq Ft per bed/ hospital FLOOR AREA ALLOCATION • OPD – 12%-18% • Wards, Rooms , ICUs & OT s – 37%-45% • Diagnostic & Therapeutic – 18%-22% • Administration – 8%-12% • Service Departments – 15%-20% Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 5. Bureau Of Indian Standards - Recommendations • IS 10905-1: Recommendations for basic requirements of general hospital buildings, Part 1: Administrative and hospital services department buildings • IS 10905-2: Recommendations for basic requirements of general hospital buildings, Part 2: Medical services department buildings • IS 10905-3: Recommendations for Basic Requirements of General Hospital Buildings, Part 3: Engineering Services Department Buildings Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 6. • IS 12433-1: Basic requirements for hospital planning, Part 1: upto 30 bedded hospitals • IS 12433-2: Basic Requirements for Hospital Planning, Part 2: UP to 100 Bedded Hospital • Indian Public Health Standards - Governnment of India • http://www.nhm.gov.in/nhm/nrhm/guidelines/indian-public-health- standards.html Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 7. • CORRIDORS • Main corridor should allow for passage of two beds with persons on sides ~2.5 meter width • Segregation of clean and dirty corridors • OPD • For every bed three patients are seen in OPD ( Expected OPD =No.of Beds x 3 ) • 60% of area should be for waiting & corridors • Consultation room – 150 sq ft Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 8. ICU • Bed strength – 30% of total beds in a Tertiary care center • Bed strength – 20% of total beds in a Secondary care center • Each bed approximate 150 – 200 sq ft Operation Theatres – Minimum nos. • One OT per 50 beds • Approximate 400 Sq.Ft area. • 10 Feet height Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 9. HOSPITAL ENGINEERING SERVICES PLANNING BASICS Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 10. SCOPE OF ENGINEERING SERVICES • Electrical • HVAC • Plumbing and Sanitary • Medical Gas • Lift • STP & ETP • Boiler • Incinerator • Fire protection and Fire fighting • Pneumatic tube systems Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 11. SCOPE OF IT SERVICES • NETWORKING – Computer systems • NETWORKING – Medical Equipments • TV • CCTV • Telephones • ACCESS points • Nurse Call Systems • PACS • Wi Fi Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 12. Electrical - Minimum Requirements • HT Substation with adequate cross ventilation • Full back up Generator with adequate cross ventilation • UPS power for all IT related Equipments. • UPS power for all Critical care Medical Equipments ( which are recommended to use UPS power) • Panel rooms in all floors. • DBs for Power, Lighting , UPS separately. • Emergency lights in corridors , all critical care areas & fire escape route staircase. Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 13. Regulations Indian Standards Electrical Inspectorate & Electricity Board rules. SP 30 (2011): National Electrical Code of India International Standards • Electrical services - Health Technical Memorandum 06-01: Electrical services supply and distribution ( UK ) • National Electrical Code USA, NFPA 70ÂŽ & NFPA 90ÂŽ Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 14. HVAC - Minimum Requirements • Chiller plant room • Heat rejection - Cooling Tower / Air cooled condensers • AHU rooms ,Space for CSUs /FCUs • All Chillers, AHUs and Pumps preferred with VFD starters • Dedicated shafts for • Chilled water piping, • Supply , Return ,Fresh Air & Extract ducting . Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 15. HVAC - Minimum Requirements • 1 Tr of Refrigeration approximate for 150 Sq.Ft. • 1 Air change per hour ( ACH) Fresh Air for comfort applications. • Low velocity ducting design ( DW 144 European std. , SMACNA US std. Ducting Standards) • Low Velocity Chilled water Design ( CIBSE British Guidelines ) • ASHRAE Guidelines for Air-conditioning & ventilation. • Room Indoor design conditions – ASHRAE , NABH guidelines Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 16. • Chilled water pipe pressure test – Minimum twice the running pressure. • Valve selections – Minimum PN 20. • Control Valves – Pressure Independent type. • Pumps Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 17. Medical Gas - Minimum Requirements • Medical Gas Manifold – Medical Oxygen • 100 beds and Above – Main Manifold Minimum 8 x 8 cylinders , Emergency 4 cylinders • 200 beds and Above – Main Manifold Minimum 10 x 10 cylinders , Emergency 5 cylinders , Liquid Medical Oxygen Tanks with 5000 ltrs capacity preferred. • 500 beds and Above – Main Manifold Minimum 12 x 12 cylinders , Emergency 4 cylinders , Liquid Medical Oxygen Tanks with 10000 ltrs capacity preferred. Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 18. Medical Gas - Minimum Requirements • OT : Oxygen , Nitrous oxide, Carbon Di oxide ,Medical Air ( 4 Bar) ,Surgical Air ( 7 Bar) ,Vacuum , AGSS. • ICUs : Oxygen , Medical Air ( 4 Bar) ,Vacuum. • Rooms & wards : Oxygen , Vacuum. • Medical Oxygen usage : ( Qty. to be specified by Doctor) • Normal patients : 2 ltrs per Hour. • Ventilator patients : Approx. 10 ltrs per Hour.(if 100 % ) Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 19. Medical Gas - Minimum Requirements • Liquid Medical Oxygen Plant – As per specs of PESO ( Petroleum & Explosives Safety Organisation) • Manifold room and Compressor Rooms - As per HTM 02-01 standards,ISO 7396 -1:2007 • Pressure Control Stations - As per HTM 02-01 standards , ISO 10524 - 2:2007 Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 20. Medical Gas - Pressure @ Area Valve Control Unit • O2 , N2O , Co2 , Medical Air - Minimum pressure 45 PSI ( 3.16 Kg/ Cm3) & Maximum pressure 75 PSI ( 5.27 Kg/ Cm3) Surgical Air - Minimum pressure 95 PSI ( 6.67 Kg/ Cm3) & Maximum pressure 105 PSI ( 7.38 Kg/ Cm3) Vacuum - Minimum suction pressure 12 mm / Hg & Maximum Suction pressure 32 mm / Hg. Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 21. Plumbing & Sanitary - Minimum Requirements • Minimum of two water sources • Water storage capacity for two days(approximately 1000 ltrs per bed * 2 days) • Water tanks with stand by for each domestic, flush & fire tanks • Disinfection of water tanks and supply lines • Water Treatment Plant • Pumping system with standby • R.O Water for Dialysis and for sterlization • Hot water system for rooms & kitchen Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 22. Sewage & Effluent Treatment. • As per Central Pollution Control board – Each bed produces 450 ltrs of Soiled water. ( in kerala our normal usage is 800 Ltrs to 1000 Ltrs) • Minimum Size of STP/ETP = No.of Beds x 450 ltrs. • Separate pipelines of Sewage , Laundry and Kitchen • Separate treatments for Sewage , Laundry and Kitchen . • STP output water preferred characteristics : Sl No. Parameters Treated water KSPCB Standards 1 PH 6.5-7.5 5.5-9.0 2 BOD 3 days at 270c <15 mg/l 30 mg/l 3 COD, mg/l < 50 mg/l 250 mg/l 3 Suspended Solids <50 mg/l 100 mg/l 4 Oil & Grease <1mg/l 10 mg/l Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 23. LIFTS minimum nos. required • Depends upon number of beds above groundfloor • Up to 50 – one; Every 50 beds 1 No. Lift each. • Lift Car Size – >2280X1600X2300 mm ; with door size >1300X2100 mm • ARD for each Lift • Machine room : With adequate Light , Ventilation and dust free condition with suitable nos. of Rope holes, Ceiling Hooks. Dedicated power supply with ELCB. Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 24. LIFTS minimum nos. required • Lift Shaft size : Depth more than 700mm Lift Size. • Lift Shaft size : Width more than 300 mm in each side than Lift size. • Lift Shaft size : Entrance opening more than 200 mm than lift size. • Lift Shafts to be with Lights in each floors ,Pit ladder and without plumb. • Pit depth depending upon Lift size ,speed and Manufacturer. Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 25. Engineering Services - Requirements •Electrical Substation ,Panel room Space for Panels,DBs Shaft Cabling •HVAC Chiller plant Space for AHUs & Panels Shaft Cabling Piping ( Chilled water in & out , Drain pipes Ducting •Plumbing and Sanitary Pump room ,Tanks Accees point / Shaft doors / Ceiling trap doors Shaft Piping •Medical Gas Med.Gas Manifold room , Compressor room. Accees point / Shaft doors / Ceiling trap doors Shaft Piping •Lift Lift roooms , Lift pit. Lift rooms Shaft/ lift well Cabling •Boiler Plant room Ceiling trap doors Shaft Piping •Fire protection and Fire fighting Pump room ,Tanks Accees point / Shaft doors / Ceiling trap doors Shaft Cabling Piping •Pneumatic tube systems Plant room Accees points /Ceiling trap doors Shaft Cabling Piping •NETWORKING – Computer systems Server room , Floor wise IT rooms. Ceiling trap doors Shaft Cabling •NETWORKING – Medical Equipments Shaft Cabling •TV Shaft Cabling •CCTV Shaft Cabling •Telephones Shaft Cabling •ACCESS points Shaft Cabling •Nurse Call Systems Shaft Cabling •PACS Shaft Cabling •Wi Fi Shaft Cabling Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 26. FIRE MANAGEMENT SYSTEMS • Fire fighting is the act of extinguishing fires to protect lives and to prevent the destruction of property and of the environment System consist of • Fire Pump and Fire Tanks • Fire Hydrant Systems • Sprinklers • Fire Extinguishers • FM200/ Clean Agents (such as Novec systems…) Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 27. Exit Facilities: In buildings or sections occupied by bed-ridden patients where the floor area is over 280 m2, facilities shall be • provided to move patients in hospital beds to the other side of a smoke barrier from any part of such building or • section not directly served by approved horizontal exits or exits from the first floor (floor 2) of a building to the outside. Not less than two exits of one or more of the following types shall be provided for every floor, including basement, of every building or section: a) Doors leading directly outside the building; b) Stairways; c) Ramps; d) Horizontal exits; and e) Fire tower. Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 28. Exit Facilities • All required exits that serve as egress from hospital or infirmary sections shall be not less than 2 m in clear width • All patient bedroom doors to permit transportation of patients on beds, litters, or mattresses. • Min. width of corridors to serve patients bedrooms shall be 2500 mm. • UPS Lighting in fire stairs to be provided for use when the raw power supply fails. • That part of emergency lighting ( With UPS power ) is provided to ensure that the escape route is illuminated at all times or at times the main lighting is not available, either for the whole building or the escape routes. Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 29. Fire Exit Doors • DOOR: The door with a fire resistance rating 2 hrs. • SIGNAGES: Fire exit doors and way to the Fire exit doors are marked in WHITE letters in GREEN background and are either marked with self-luminous material or illuminated with battery back up. • SMOKE FREE: It is Fire/smoke free area through which the personal in the building can be evacuated safely. • PANIC BAR: The Fire exit doors have a panic bar hard ware provided on the door. • ACCESS CONTROL: Fire doors to have Fail safe access control options Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 30. S.N o Type of building / Occupancy Type Of Installation Water Supply (in liters) Pump Capacity (inL/min) Fire Extinguis her Hose Reel Dry Riser Wet Riser Downcomer yard Hydrant Automatic Sprinkler System Manually Operated Eletric Fire Alarm System Automatic Detection & Fire Alarm System Undergrou nd Static Water Storage Tank Terrace Tank pump near underground static water storage tank with min pressure 3.5kg/cm2at terrace level At the terrece tank level with min pressure 2kg/cm2 1 Ground Plus 2 or more storeys,with bed R R NR R NR NR R R R 50000 5000 NOTE 3 NR 2 Less than 15m in height with plot area more than 1000m2 R R NR R NR R R R R 10000 10000 NOTE 3 NR 3 Above 15m height but not exceeding 24m in hight R R NR R NR R R R R 100000 20000 NOTE 4 NR 4 Above 15m height but not exceeding 30m in hight R R NR R NR R R R R 150000 20000 NOTE 5 NR Note 3 One electric & one diesel pump of capacity 1620 ipm and one electric pump of capacity 180 Ipm R = Requried / NR = Not RequriedNote 4 One electric & one diesel pump of capacity 2280 ipm and one electric pump of capacity 180 Ipm Note 5 One electric & one diesel pump of capacity 2280 ipm and one electric pump of capacity 180 Ipm Season.EV , seasonev@gmail.com , Mobile no.9745863521
  • 31. Recommended to refer : • National Building Code of India – Part 4 Fire & Life safety • National Disaster Management Guidelines – Hospital Safety • ( National disaster Management Authority, Govt.of India) • Indian Standard Code of Practice for Fire Safety • NABH & FIRE SAFETY • NFPA standards Season.EV , seasonev@gmail.com , Mobile no.9745863521