ACCC®
Conductor
Installation Training Service
Instructor: Saeful Hidayat
PT PLN UIT Jawa Bagian Tengah
Jepara, 04 Agustus 2020
Technoloy is Not Stagnant
ACSR
1910
2004
ACCC®
Copyright January 2020 CTC Global All Rights Reserved 2
Ukuran dan Testing Konduktor ACCC ®
Proses Pembuatan Core
Copyright January 2020 CTC Global All Rights Reserved 3
Ukuran dan Testing Konduktor ACCC ®
Proses Pembuatan Core
Copyright January 2020 CTC Global All Rights Reserved 4
Ukuran dan Testing Konduktor ACCC ®
Design Avoides “Keystoning”or Gaps
Copyright January 2020 CTC Global All Rights Reserved 5
Ukuran dan Testing Konduktor ACCC ®
Environmental Testing & Monitoring
2000
1800
ACSR
1600 ACSS
(mm
1400 ACCR
1200 ACCC
Sag
1000
Cable
800
600
400
200
0
0 20 40 60 80 100 120 140 160 180 200 220 240 260
Temperature (C)
ACCC
®
Lines being monitored by:
• National Grid (Niagara Falls, New York)
• EPRI HTLS Conductor Study Group (at APS)
• WAPA (Phoenix, AZ)
• PacifiCorp (Salt Lake City)
• State Grid China (Beijing and Shanghai)
• RTE / EDF France (Minerve and Renardieres)
*Characteristics being monitored:
• Ambient Temperature
• Tension, Sag, and clearance
• Conductor Temperature
• Electrical Current
• Wind Speed and Direction
• Solar Radiation
• Rainfall
• Ice buildup
• Splice Resistance
• Infrared Measurements
• Corona Observations
• Electric and Magnetic Fields
Copyright January 2020 CTC Global All Rights Reserved 6
Ukuran dan Testing Konduktor ACCC ®
Core Testing:
2.1.1 Tensile Testing
2.1.2 Flexural, Bending & Shear Tests
2.1.3 Sustained Load Tests
2.1.4 Tg Tests
2.1.5 CTE Measurements
2.1.6 Shear Testing
2.1.7 Impact and Crush Testing
2.1.8 Torsion Testing
2.1.9 Notched Degradation Testing
2.1.10 Moisture Resistance Testing
2.1.11 Long Term Thermal Testing
2.1.12 Sustained Load Thermal Testing
2.1.13 Cyclic Thermal Testing
2.1.14 Specific Heat Capacity Testing
2.1.15 High Temperature Short Duration
2.1.16 High Temperature Core Testing
2.1.17 Thermal Oxidation Testing
2.1.18 Brittle Fracture Testing
2.1.19 UV Testing
2.1.20 Salt Fog Exposure Tests
2.1.21 Creep Tests
2.1.22 Stress Strain Testing
2.1.24 Micrographic Analysis
2.1.25 Dye Penetrant Testing
2.1.26 High Temperature Shear Testing
2.1.27 Low Temperature Shear Testing
Mechanical Conductor Testing:
2.2.28 Stress Strain Testing
2.2.29 Creep Testing
2.2.30 Aeolian Vibration Testing
2.2.31 Galloping Tests
2.2.32 Self Damping Tests
2.2.33 Radial Impact and Crush Tests
2.2.34 Turning Angle Tests
2.2.35 Torsion Tests
2.2.36 High Temperature Sag Tests
2.2.37 High Temperature Sustained Load
2.2.38 High Temperature Cyclic Load Tests
2.2.39 Cyclic Ice Load Tests
2.2.40 Sheave Wheel Tests
2.2.41 Ultimate Strength Tests
2.2.42 Cyclic Thermo-Mechanical Testing
2.2.43 Combined Cyclic Load Testing
2.2.44 Conductor Comparison Testing
Systems & Hardware Testing:
2.4.55 Current Cycle Testing
2.4.56 Sustained Load Testing
2.4.57 Ultimate Assembly Strength Testing
2.4.58 Salt Fog Emersion Testing
2.4.60 Static Heat Tests
2.4.61 Suspension Clamp Testing
2.4.62 Thermo-Mechanical Testing
2.4.63 Cyclic Load Testing
Electrical Conductor Testing:
2.3.45 Resistivity Testing
2.3.46 Power Loss Comparison Testing
2.3.47 Ampacity
2.3.48 EMF Measurements
2.3.49 Impedance Comparison Testing
2.3.50 Corona Testing
2.3.51 Radio Noise Testing
2.3.52 Short Circuit Testing
2.3.53 Lightning Strike Testing
2.3.54 Ultra High Voltage AC & DC Testing
Field Testing:
2.5.64 Ambient Temperature
2.5.65 Tension, Sag, and Clearance
2.5.66 Conductor Temperature
2.5.67 Electric Current
2.5.68 Wind Speed and Direction
2.5.69 Solar Radiation
2.5.70 Rainfall
2.5.71 Ice Buildup
2.5.72 Splice Resistance
2.5.73 Infrared Measurements
2.5.74 Corona Observations
2.5.75 Electric and Magnetic Fields
2.5.76 Wind and Ice Load Measurements
2.5.77 Vibration Monitoring
Konduktor ACCC telah mengalami pengujian extensif
2.5.78 Typhoon Test
Copyright January 2020 CTC Global All Rights Reserved 7
Perbandingan ACSR dengan ACCC ®
ACSR Conductor
• Berumur > 100 tahun
• 95+% transmisi menggunakan
ACSR, murah dan memiliki
history yang panjang.
• Temperatur operasi (<95C) dan
memiliki sag yang besar bila di
operasikan pada suhu lebih tinggi
ACCC®
Conductor
• Teknologi ini dikembangkan dari
tahun 2001 sampai 2005
• Terpasang pada tahun 2006
• Hybrid composite core ringan dan
lebih kuat dibandingkan baja,
memungkinkan 28% aluminium
tanpa menambah berat konduktor
• Beroperasi max temperatur 175 o
C
dan memiliki sag rendah
Manfaat ACCC® Conductor :
• Peningkatan Kapasitas
• Kerugian jalur berkurang
• Biaya proyek rendah
• Meningkatkan kehandalan sistem
Copyright January 2020 CTC Global All Rights Reserved 8
Keuntungan Konduktor ACCC ®
Kekuatan Besar & Sag Rendah
Jarak span lebih panjang
Peningkatan kapasitas listrik
Kerugian jalur berkurang
Penurunan konsumsi bahan bakar & emisi
Keandalan terbukti pada lebih dari 275 lokasi
Copyright January 2020 CTC Global All Rights Reserved 9
Ukuran Konduktor ACCC ®
ACCC®
Conductor Diameter Core Diameter Weight Core Rated Strength Conductor Rated DC @ 20°C AC @ 25°CAC @ 75°C AC Ampacity
Strength
Size (kcmil) (mm²) (in) (mm) (in) (mm) (lb/kft) (kg/km) (lbf) (kN) (lbf) (kN) (ohm/km) (ohm/km) (ohm/km) 75°C 180°C
Helsinki 303 153.7 0.616 15.65 0.235 5.97 322 479 13,580 60.4 15,500 69.1 0.1861 0.19011 0.22766 479 802
Linnet 431 218.4 0.720 18.29 0.235 5.97 441 656 13,580 60.4 16,300 72.7 0.12801 0.13120 0.15774 599 1,007
Oriole 438 221.9 0.741 18.82 0.280 7.11 463 689 19,290 85.8 22,000 97.9 0.12609 0.12867 0.15489 609 1,024
Reykjavik 447 226.3 0.741 18.82 0.280 7.11 472 703 19,290 85.8 22,100 98.5 0.12630 0.12669 0.15171 615 1,039
Copenhagen 440 223.0 0.720 18.29 0.235 5.97 450 670 13,580 60.4 16,400 72.9 0.1279 0.13090 0.15675 601 1,013
Glasgow 473 239.8 0.769 19.53 0.305 7.75 504 750 22,880 101.8 25,900 115.3 0.11690 0.12197 0.14606 633 1,070
Casablanca 546 276.8 0.807 20.50 0.280 7.11 565 840 19,290 85.8 22,700 101.1 0.10130 0.10587 0.12677 688 1,166
Hawk 611 309.6 0.857 21.77 0.280 7.11 625 930 19,290 85.8 23,200 103.2 0.90300 0.09291 0.11161 745 1,264
Oslo 627 317.7 0.882 22.40 0.345 8.76 666 992 29,260 130.2 33,300 148.1 0.08820 0.09219 0.11041 755 1,284
Lisbon 629 318.7 0.857 21.78 0.280 7.11 643 957 19,290 85.8 23,300 103.7 0.0896 0.09199 0.11016 750 1,275
Dove 713 361.3 0.927 23.55 0.305 7.75 728 1083 22,880 101.8 27,500 122.3 0.07738 0.07986 0.09583 821 1,398
Amsterdam 733 371.4 0.927 23.55 0.305 7.75 748 1113 22,880 101.8 27,600 122.7 0.0769 0.07911 0.09474 826 1,408
Grosbeak 816 413.5 0.990 25.15 0.320 8.13 832 1238 25,190 112.1 30,400 135.2 0.06761 0.07005 0.08392 892 1,527
Brussels 839 425.3 0.990 25.14 0.320 8.13 857 1275 25,190 112.1 30,600 136.1 0.0673 0.06941 0.08312 897 1,534
Stockholm 913 462.7 1.039 26.40 0.345 8.76 944 1406 29,260 130.2 35,200 156.5 0.0612 0.06324 0.07573 952 1,632
Warsaw 1016 514.8 1.091 27.72 0.345 8.76 1034 1539 29,260 130.2 35,800 159.1 0.0556 0.05764 0.06902 1,010 1,736
Ampacity values based on altitude of sun at 90˚ deg, 25˚ deg C ambient temperature, 0.5 Solar Absorbtivity, 0.5 Emissivity, 2 ft/sec wind and 96 Watt/ft^2,
at corresponding surface temperatures. The information contained herein is offered in good faith and believed to be accurate. The final design of a shaped
wire compact conductor is contingent upon several factors, such as layer diameter, wire width, and wire thickness. The actual configuration of a given size
may vary between manufacturers. This may result in a slight variation. However, although the information is mathematically derived, normal dimensional
tolerances in actual cable construction may lead to differences between the indicated values.
Copyright January 2020 CTC Global All Rights Reserved 10
Ukuran Konduktor ACCC ®
(lanjutan)
ACCC®
Conductor Diameter Core Diameter Weight Core Rated Strength Conductor Rated DC @ 20°CAC @ 25°CAC @ 75°C AC Ampacity
Strength
Size (kcmil) (mm²) (in) (mm) (in) (mm) (lb/kft) (kg/km) (lbf) (kN) (lbf) (kN) (ohm/km) (ohm/km) (ohm/km) 75°C 180°C
Drake 1020 516.8 1.108 28.14 0.375 9.53 1047 1558 34,570 153.8 41,100 182.8 0.05409 0.05640 0.06749 1,025 1,765
Dublin 1043 528.5 1.108 28.15 0.375 9.53 1072 1595 34,570 153.8 41,300 183.5 0.05410 0.05608 0.06715 1,028 1,769
Hamburg 1092 553.3 1.127 28.62 0.345 8.76 1106 1646 29,260 130.2 36,300 161.3 0.05170 0.05375 0.06436 1,054 1,816
Milan 1134 574.6 1.146 29.10 0.345 8.76 1146 1705 29,260 130.2 36,500 162.5 0.04880 0.05186 0.06210 1,078 1,859
Rome 1183 599.4 1.177 29.89 0.375 9.53 1205 1793 34,570 153.8 42,200 187.5 0.04680 0.04981 0.05965 1,108 1,913
Cardinal 1222 619.2 1.196 30.38 0.345 8.76 1228 1828 29,260 130.2 37,100 165.0 0.04535 0.04793 0.05712 1,137 1,971
Vienna 1255 635.9 1.198 30.42 0.345 8.76 1259 1873 29,260 130.2 37,300 165.9 0.04410 0.04700 0.05627 1,146 1,981
Budapest 1332 674.9 1.240 31.50 0.375 9.53 1346 2003 34,570 153.8 43,100 191.8 0.04160 0.04447 0.05325 1,189 2,059
Prague 1377 697.7 1.251 31.77 0.345 8.76 1377 2050 29,260 130.2 38,100 169.4 0.04030 0.04326 0.05180 1,208 2,093
Munich 1461 740.3 1.293 32.85 0.375 9.53 1471 2189 34,570 153.8 44,000 195.5 0.03800 0.04094 0.04902 1,253 2,175
London 1512 766.1 1.315 33.40 0.385 9.78 1523 2266 36,440 162.1 46,100 205.2 0.03660 0.03954 0.04736 1,280 2,224
Bittern 1572 796.5 1.345 34.16 0.345 8.76 1555 2314 29,260 130.2 39,300 174.8 0.03517 0.03815 0.04511 1,320 2,315
Paris 1620 820.9 1.345 34.17 0.345 8.76 1603 2385 29,260 130.2 39,700 176.4 0.03420 0.03721 0.04456 1,328 2,310
Antwerp 1879 952.1 1.451 36.85 0.385 9.78 1867 2778 36,440 162.1 48,500 215.7 0.02950 0.03251 0.03893 1,449 2,532
Lapwing 1965 995.7 1.504 38.20 0.385 9.78 1961 2918 36,440 162.1 49,000 218.0 0.02836 0.03169 0.03720 1,497 2,655
Berlin 2004 1015.4 1.504 38.20 0.415 10.54 2000 2977 42,340 188.3 55,200 245.5 0.02760 0.03058 0.03661 1,509 2,642
Madrid 2020 1023.5 1.504 38.20 0.385 9.78 1999 2974 36,440 162.1 49,400 219.7 0.02740 0.03044 0.03645 1,512 2,647
Chukar 2242 1136.0 1.602 40.69 0.395 10.03 2226 3312 38,360 170.6 52,700 234.5 0.02486 0.02851 0.03323 1,610 2,882
Bluebird 2726 1381.5 1.762 44.75 0.415 10.54 2696 4012 42,340 188.3 59,800 266.0 0.02044 0.02461 0.02835 1,788 3,246
Ampacity values based on altitude of sun at 90˚ deg, 25˚ deg C ambient temperature, 0.5 Solar Absorbtivity, 0.5 Emissivity, 2 ft/sec wind and 96 Watt/ft^2,
at corresponding surface temperatures. The information contained herein is offered in good faith and believed to be accurate. The final design of a shaped
wire compact conductor is contingent upon several factors, such as layer diameter, wire width, and wire thickness. The actual configuration of a given size
may vary between manufacturers. This may result in a slight variation. However, although the information is mathematically derived, normal dimensional
tolerances in actual cable construction may lead to differences between the indicated values.
Copyright January 2020 CTC Global All Rights Reserved 11
CTC Global Corporation
ACCC®
Conductor Transportation, Handling,
Storage Training and Hardware Installation
Copyright January 2020 CTC Global All Rights Reserved 12
Penyimpanan Konduktor ACCC®
Hal – hal yang harus diperhatian dalam penyimpanan
Konduktor ACCC :
1. Simpan haspel (drum) sedemikian rupa sehingga haspel /
drum tidak tergenang air dan pastikan konduktor dalam
kondisi baik sampai proses penarikan/stringing dilaksanakan.
Copyright January 2020 CTC Global All Rights Reserved 13
Penyimpanan Konduktor ACCC®
2. Haspel (drum) konduktor ACCC dikirim dari
pabrikan di lengkap
pelindung pada konduktor dan sisi luar kayu di
ikat mengunakan plat.
Copyright January 2020 CTC Global All Rights Reserved 14
Penyimpanan Konduktor ACCC®
3. Tanda identifikasi atau informasi jangan
sampai hilang sampai konduktor digunakan.
Copyright January 2020 CTC Global All Rights Reserved 15
Pengiriman dan Penanganan Konduktor ACCC®
Konduktor ACCC harus dikontrol dengan baik
selama proses pemuatan, pembongkaran, dan
penarikan konduktor ACCC
1. Haspel (drum) konduktor harus diletakkan
secara vertikal, baik pada saat pengiriman
maupun pada saat sudah di site (lokasi).
Copyright January 2020 CTC Global All Rights Reserved 16
Pengiriman dan Penanganan Konduktor ACCC®
2. Peralatan yang tersedia untuk menangani
konduktor ACCC harus memiliki kapasitas yang sesuai
untuk menghindari kerusakan.
Copyright January 2020 CTC Global All Rights Reserved 17
Pengiriman dan Penanganan Konduktor ACCC®
3. Apabila menggunakan crane harus memakai sprader
bar (besi)/crane seling dengan panjang 2-3 meter.
Copyright January 2020 CTC Global All Rights Reserved 18
Pengiriman dan Penanganan Konduktor ACCC®
4. Mengangkut haspel memakai forklift harus melakukan
dari samping sehingga berat haspel tertumpu pada flange.
Copyright January 2020 CTC Global All Rights Reserved 19
Pengiriman dan Penanganan Konduktor ACCC®
5. Pastikan pada saat pembongkaran konduktor tidak dijatuhkan dari
truk/kontainer karena dapat menyebabkan konduktor cacat atau
rusak.
Copyright January 2020 CTC Global All Rights Reserved 20
Pengiriman dan Penanganan Konduktor ACCC®
✓
Jangan pernah
tekuk konduktor ACCC lebih
kecil dari diameter lengkung
minimum.
✓
Penting
untuk tidak
menekuk dengan tajam ACCC
Conductor. Meskipun composite
carbon & glass fiber pada core
ACCC mempunyai kekuatan
dan ketahanan tinggi, tetapi
keseluruhan konduktor
sama sekali tidak boleh
ditekuk secara tajam.
Copyright January 2020 CTC Global All Rights Reserved 21
Pedoman Penanganan Umum Konduktor ACCC®
ACCC Conductor tidak boleh
ditekuk dengan sudut yang
tajam, apalagi dengan
diameter lengkungan yang
kecil.
Gambarsebelah adalah contoh
dimana kemungkinan bisa
terjadi lengkungan yang
terlalu kecil. Harus hati-hati
dan waspada agar hal ini tidak
terjadi selama proses
stringing.
Copyright January 2020 CTC Global All Rights Reserved 22
Pedoman Penanganan Umum Konduktor ACCC®
Bila sudut konduktor pada tikungan besar
(lebih dari 20 derajat) gunakan roller yang
lebih besar atau gunakan tandem roller.
Bila sudut besar sekali, dapat digunakan
double tandem roller.
Copyright January 2020 CTC Global All Rights Reserved 23
Pedoman Penanganan Umum Konduktor ACCC®
✓
Jangan menekan konduktor kesatu sisi seperti
pada gambar ini. Konduktor harus bisa
meluncur bebas diatas montage roll.
✓
Jika konduktor diperlakukan seperti ini, maka
“birdcaging” (konduktor mekar seperti
kandang burung) bisa terjadi diarah tensioner,
atau konduktor bisa rusak.
Copyright January 2020 CTC Global All Rights Reserved 24
X
Pedoman Penanganan Umum Konduktor ACCC®
❖
Hindari menyeret
konduktor hingga
tergesek oleh tanah
atau material yang
tajam
❖
Hindari
menarik konduktor ke
tower tanpa
memberikan ikatan –
ikatan di belakang
came along
Copyright January 2020 CTC Global All Rights Reserved 25
Pedoman Penanganan Umum Konduktor ACCC®
• Sangat penting bahwa jalan atau rel
KA dilindungi oleh struktur sementara
sehingga konduktor tidak terkena
mobil atau peralatan bergerak
lainnya.
• Juga penting bahwa semua saluran
listrik TT, TM atau TR di lindungi
struktur.
• Jangan sampai konduktor bergesek
dengan ujung dari struktur.
Copyright January 2020 CTC Global All Rights Reserved 26
Pedoman Penanganan Umum Konduktor ACCC®
❑ Karena aluminium strand ACCC lunak, tindakan pencegahan tambahan perlu
dilakukan untuk menghindari kerusakan pada permukaan.
❑ Bila konduktor akan diturunkan, letakkan kertas atau material lain yang
bersih diatas tanah untuk menjaga agar konduktor tidak menyentuh tanah.
❑ Yakinkan bahwa tidak ada batu atau barang-barang lain yang dapat merusak
konduktor.
Copyright January 2020 CTC Global All Rights Reserved 27
Pedoman Penanganan Umum Konduktor ACCC®
✓ Tarikan maksimum stringing – aturan umum untuk Konduktor ACCC
✓ Tegangan waktu stringing dianjurkan tidak lebih dari 10% RTS
konduktor
✓ Berapa lama konduktor boleh ditinggal duduk pada roller sebelum
clamping?
✓ IEEE 524 merekomendasikan bahwa konduktor sudah di sagging
dan clamping dalam jangka waktu 24 – 48 jam setelah penarikan.
✓ IEEE 524 merekomendasikan bahwa maksimum waktu yang
diperbolehkan bagi konduktor untuk tetap duduk di roller (dari saat
penarikan sampai clamping) tidak lebih dari 72 jam.
✓ Bila konduktor akan di sagging pada hari yang sama, maka tambahkan
2% atau minus 9 derajat untuk mengatasi “creep” yang akan terjadi
dalam satu malam. Semua konduktor mempunyai creep, tapi Core
(Composite Carbon) ACCC lebih kecil creep nya dibanding yang lain.
Copyright January 2020 CTC Global All Rights Reserved 28
Penanganan Konduktor ACCC®
Tirfor
Came Along
Copyright January 2020 CTC Global All Rights Reserved 29
Penanganan Konduktor ACCC®
Tirfor
Came Along
Copyright January 2020 CTC Global All Rights Reserved 30
Penanganan Konduktor ACCC®
Copyright January 2020 CTC Global All Rights Reserved 31
Penanganan Konduktor ACCC®
Tower 47D Tower 47C Tower 47B Tower 47A
Konduktor
ACCC
Copyright January 2020 CTC Global All Rights Reserved 32
Penanganan Konduktor ACCC®
Tirfor
Came
Along
Tower 47D Tower 47C Tower 47B Tower 47A
Konduktor
ACCC
Copyright January 2020 CTC Global All Rights Reserved 33
Penanganan Konduktor ACCC®
Copyright January 2020 CTC Global All Rights Reserved 34
Penanganan Konduktor ACCC®
Copyright January 2020 CTC Global All Rights Reserved 35
Penanganan Konduktor ACCC®
Splice
Nylon
Copyright January 2020 CTC Global All Rights Reserved 36
Penanganan Konduktor ACCC®
Copyright January 2020 CTC Global All Rights Reserved 37
Penanganan Konduktor ACCC®
Copyright January 2020 CTC Global All Rights Reserved 38
Penanganan Konduktor ACCC®
Konduktor batch 1 untuk proyek ini ternyata mempunyai GAP antara core
dengan lapisan dalam aluminium strand.
Copyright January 2020 CTC Global All Rights Reserved 39
Penanganan Konduktor ACCC®
Simulasi Konduktor ACCC menggunakan Deadend Clamps
Copyright January 2020 CTC Global All Rights Reserved 40
Penanganan Konduktor ACCC®
Bila baut – baut pada alat bantu untuk menarik konduktor dikencangkan
dengan berlebihan maka core bisa pecah karena tergencet dari 2 arah saja.
Copyright January 2020 CTC Global All Rights Reserved 41
Penanganan Konduktor ACCC®
Copyright January 2020 CTC Global All Rights Reserved 42
Penanganan Konduktor ACCC®
Copyright January 2020 CTC Global All Rights Reserved 43
Penanganan Konduktor ACCC®
Copyright January 2020 CTC Global All Rights Reserved 44
CTC Global Corporation
ACCC®
Conductor Tools and
Equipment Training
Copyright January 2020 CTC Global All Rights Reserved 45
Tensioner
Tensioner adalah peralatan yang digunakan untuk
menahan konduktor pada proses stringing /
penarikan konduktor untuk pemasangan baru atau
rekonduktoring.
Spesifikasi :
❑
Sistem Hydraulic
❑
Diameter Bull-wheel sesuai “Daftar Sheeve Size
ACCC”
❑
Diameter alur tidak boleh lebih kecil 0.55 x Diameter
konduktor ACCC
❑
Minimum bull-wheel memiliki 4 alur
❑
Alur Bull-wheel tidak berbentuk “V”
❑
Memiliki kekuatan minimum 4.5 ton
❑
Bull-wheel dilapisi dengan nylon atau urethane
❑
Bull-wheel double
❑
Memiliki sistem pengerak dan pengereman hydraulic
Copyright January 2020 CTC Global All Rights Reserved 46
Tensioner
Copyright January 2020 CTC Global All Rights Reserved 47
Drum Stand & Brake
Drum Stand adalah alat yang digunakan untuk menempatkan drum konduktor
agar bisa bergerak dengan stabil.
Spesifikasi :
❑
Memiliki kekuatan minimum 5 ton
❑
Terdapat disc brake atau hydraulic brake
Brake/ Rem adalah alat yang digunakan
Untuk menggatur putaran
drum Konduktor agar
selalu stabil.
Copyright January 2020 CTC Global All Rights Reserved 48
Drum Stand & Brake
Copyright January 2020 CTC Global All Rights Reserved 49
Payout Reel Brakes
Hydraulic ✓ Disc ✓
Copyright January 2020 CTC Global All Rights Reserved 50
Roller Grounding & Stick Grounding
Roller Grounding adalah alat yang digunakan untuk pengaman bila terjadi
induksi pada proses stringing / penarikan konduktor. Alat ini biasanya
dipasang di depan tensioner dan puller.
Spesifikasi :
❑
Bahan terbuat dari aluminium
❑
Roda yang digunakan harus halus
❑
Kabel grounding diameter 50 mm2
❑
Stick harus berbahan fiber glass
❑
Grounding rod harus cukup
Copyright January 2020 CTC Global All Rights Reserved 51
Roller / Pulley / Travelers
Roller adalah alat yang digunakan untuk tempat
bergeraknya konduktor , dipasang pada setiap tower.
Spesifikasi :
❑
Bahan terbuat dari polyurethane/nylon atau Aluminium
❑
Diameter (Ds) minimum sesuai “Daftar Sheeve Size
ACCC”
❑
Memiliki kedalaman alur 1.25 x diameter konduktor
ACCC
❑
Memiliki jari – jari alur minimum 0.55 x diameter konduktor
ACCC
❑
Bisa dalam konfigurasi double roller atau lebih
❑
Dapat juga dipasang secara tandem 2 atau lebih untuk
mengatasi sudut yang besar
Copyright January 2020 CTC Global All Rights Reserved 52
Working Diameter / Diameter Kerja
✓ X
Copyright January 2020 CTC Global All Rights Reserved 53
Sheeve Sizes ACCC ®
ACCC Core
Conductor
Sheave Size
Tensioner Bull-
Diameter Working
Wheel
mm inches International ASTM Diameter
Silvassa, Helsinki,
5.97 0.235 Copenhagen, Rovinj, Linnet, Oceanside. 511 mm (20.1”) 1000 mm (39.4")
Gdansk
7.11 0.280
Zadar, Reykjavik,
Oriole, Laredo, Hawk 610 mm (24")
Casablanca, Lisbon.
7.75 0.305
Jaipur, Glasgow,
Waco, Dove 650 mm (25.6")
Amsterdam, Cordoba
8.13 0.32 Brussels Grosbeak 710 mm (28") 1200 mm (48")
Oslo, Stockholm, Warsaw,
Irving, Lubbock,
Galveston, Plano,
8.76 0.345 Hamburg, Milan, Vienna, Corpus Christi, Cardinal,
Prague, Paris. El Paso, Bittern.
Leipzig, Dublin, Kolkata, Drake, Arlington, Fort 800 mm (31.5")
9.53 0.375 Rome, Budapest, worth, Beaumont
Mumbai, Munich. (Dhaka)
9.78 0.385 Londan, Antwerp, Madrid
San Antonio, Dallas,
Lapwing. 1500 mm (60")
10.03 0.395 Chukar, Chukar II.
Monte Carlo, 25mm,
Curlew, Houston, Falcon, 1000 mm (39")
10.54 0.415 Warwick, Bordeaux,
Bluebird.
Berlin, Athens
Copyright January 2020 CTC Global All Rights Reserved 54
Sheeve Sizes ACCC ®
X
✓
Copyright January 2020 CTC Global All Rights Reserved 55
Sheeve Sizes ACCC ®
Copyright January 2020 CTC Global All Rights Reserved 56
Tandem Sheeve ACCC ®
Copyright January 2020 CTC Global All Rights Reserved 57
Multiple Roller Arrays
Copyright January 2020 CTC Global All Rights Reserved 58
Camealong / Pulling Grip
Came along adalah peralatan yang digunakan
untuk memegang atau menahan konduktor.
Spesifikasi :
❑
Memiliki kekuatan 7.5 ton
❑
Memiliki panjang rahang 254 mm
❑
Liner tidak bergigi dan halus (Sesuaikan dengan
ukuran konduktor.
Copyright January 2020 CTC Global All Rights Reserved 59
Camealong / Pulling Grip
Pemeriksaan Kekuatan Camealong
Camealong rusak pada saat test 0.5 ton
• Yakinkan bahwa type dan configurasi grip akan mampu memegang konduktor
lebih kuat dari tegangan yang diperkirakan terjadi pada waktu melakukan sagging.
Lakukan test yang diperlukan.
Copyright January 2020 CTC Global All Rights Reserved 60
Pemasangan Bugs & Pulling Sock
Pemasangan Core Retainer / Bugs
Bugs / Core Retainer Bugs adalah alat
yang dipasang pada setiap ujung
konduktor ACCC pada setiap stringing
atau penarikan konduktor. Tujuan dari
pemasangan bugs adalah untuk
menahan core agar tidak slip terhadap
aluminium konduktor.
Spesifikasi :
❑
Desain dan supply dari CTC Global
Copyright January 2020 CTC Global All Rights Reserved 61
Pemasangan Bugs & Pulling Sock
Video Pemasangan Core Retainer / Bugs
Copyright January 2020 CTC Global All Rights Reserved 62
Pemasangan Bugs & Pulling Sock
Pemasangan Pulling Sock / Sustrum
Pulling sock adalah peralatan digunakan untuk sambungan sementara
pada saat proses stringing atau penarikan konduktor. Ukuran pulling sock
haru disesuaikan dengan konduktor yang akan di tarik.
Spesifikasi :
❑
Bahan terbuat dari sling baja
❑
Memiliki rating bervariasi sesuai kebutuhan
❑
Memiliki panjang minimum 1.5 meter
Copyright January 2020 CTC Global All Rights Reserved 63
Pemasangan Bugs & Pulling Sock
Pemasangan Pulling Sock / Sustrum
Copyright January 2020 CTC Global All Rights Reserved 64
Pemasangan Bugs & Pulling Sock
Pemasangan Pulling Sock / Sustrum
✓
Copyright January 2020 CTC Global All Rights Reserved 65
Swivel, Connector & Shackel
Swivel adalah peralatan dipasang antara sustrum dengan sling pada
proses stringing
atau penarikan konduktor untuk menghilangkan putaran yang terjadi.
Spesifikasi :
❑
Bahan terbuat dari baja
❑
Memiliki rating bervariasi sesuai kebutuhan
❑
Minimum Kapasitas 5 ton
Connector & Shackle adalah peralatan tambahan yang digunakan pada
proses stringing
atau penarikan konduktor.
Spesifikasi :
❑
Bahan terbuat dari besi
❑
Memiliki ukuran dan rating tertentu sesuai kebutuhan
❑
Minimum kapasitas 5 ton
Copyright January 2020 CTC Global All Rights Reserved 66
Swivel, Connector & Shackel
Swivel
Connector
Shackle
Copyright January 2020 CTC Global All Rights Reserved 67
Dynamometer & Saging Scope
Dynamometer digunakan pada saat sagging dilaksanakan untuk
memastikan bahwa tarikan yang akan diberikan telah sesuai dengan
ketentuan yang telah diatur. Dynamometer yang dipakai bisa
menggunakan jenis manual atau digital yang memiliki rating kapasitas yang
cukup minimum 5 ton. Dynamometer harus ditera sebelum dipergunakan.
Copyright January 2020 CTC Global All Rights Reserved 68
Dynamometer & Saging Scope
Sag scope digunakan untuk memastikan bahwa pada saat proses sagging
yang dilaksanakan telah sesuai dengan ketentuan yang telah disetujui. Sag
scope biasanya dipakai untuk melihat sagging (andongan) pada span
terpanjang pada section dimana akan dilaksanakan sagging.
Copyright January 2020 CTC Global All Rights Reserved 69
Bundled Conductors - Saging
Sag adjustment link
Copyright January 2020 CTC Global All Rights Reserved 70
Hydraulic Compression Tools & Dies
Mesin press adalah alat yang digunakan pada setiap pemasangan deadend
dan splice (joint) untuk menyatukan antara aluminium konduktor dengan
hardware deadend mapupun splice (joint).
Spesifikasi :
❑
Memiliki tekanan 700 bar atau 10.000 psi
❑
Kapasitas hydraulic head 60 ton (ACCC) atau 100 ton
100 Ton
60 Ton
Copyright January 2020 CTC Global All Rights Reserved 71
Spreader Bar & Tandem
Spreader Bar adalah alat yang digunakan pada setiap mengangkat haspel
/ drum agar
flange haspel tidak terdorong ke dalam
Spesifikasi :
❑
Terbuat dari besi
❑
Memiliki panjang 2 – 3 meter
❑
Mampu mengangkat beban 5 ton
Tandem adalah alat berbentuk segitiga yang digunakan untuk
menyatukan 2 buah roller menjadi tandem pada tower yang mempunyai
sudut vertikal / horizontal tajam.
Spesifikasi :
❑
Terbuat dari besi
❑
Memiliki panjang 2 – 3 meter
Copyright January 2020 CTC Global All Rights Reserved 72
Spreader Bar & Tandem
Spreader Bar Tandem Roller
Copyright January 2020 CTC Global All Rights Reserved 73
Tandem Roller
Copyright January 2020 CTC Global All Rights Reserved 74
Bundled Conductors — Stringing
Running Board
Gator
Head Board
4 Bundle Block
(with center sheave for pilot line)
Twin Bundle Block
(with center sheave for pilot line)
Copyright January 2020 CTC Global All Rights Reserved 75
Trolley / Line Car
Cable buggie / Line Car adalah alat yang digunakan pada saat akan
memasang spacer biasanya terbuat dari bahan aluminium / besi.
Spesifikasi :
❑
Terbuat dari aluminium / besi
❑
Roda yang terbuat dari nylon, aluminium atau neoprene
❑
Kapasitas sesuai dengan kebutuhan
Copyright January 2020 CTC Global All Rights Reserved 76
Tangga / Tower Ladder
Tawer ladder adalah alat bantu yang digunakan untuk memasang
deadend atau splice (joint) sehingga pekerja dapat bekerja secara
mudah, efektif, dan aman.
Copyright January 2020 CTC Global All Rights Reserved 77
Peralatan lain - lain
Kunci Inggris
• Cukup Besar untuk memutar steel eye
pada Deadend atau Coupling pada
Joint atau Bug dengan torsi yang
cukup
• Panjang yang dianjurkan minim 380
mm.
• Dibutuhkan dua unit
Cable Trimmer dan Gergaji Besi
• Cable trimmers harus tajam dan dalam
kondisi baik. Cable Trimmer dengan
kontrol kedalaman potong yang baik
sangat diperlukan. Bila pemotongan
terlalu dalam dapat melukai core.
• Gergaji besi mempunyai gigi yang halus.
Final cut ACCC konduktor dilakukan
dengan memakai gergaji gigi halus ini.
Copyright January 2020 CTC Global All Rights Reserved 78
CTC Global Corporation
ACCC®
Conductor Stringing &
Errection Training
Copyright January 2020 CTC Global All Rights Reserved 79
Metode Stringing
1. Metode Layout
Metode ini biasanya dilakukan dengan cara mengelar terlebih dahulu
konduktor / kabel diatas tanah, dengan menggunakan bantuan winch
atau dengan tenaga manusia. Metode ini sering disebut juga dengan
penarikan atau stringing manual.
Copyright January 2020 CTC Global All Rights Reserved 80
Metode Stringing
2. Metode Tension
Dengan Metode ini, konduktor diberikan gaya tarik supaya pada saat proses
penarikan (Stringing) konduktor tidak menyentuh tanah, rumah,
pohon, serta jaringan TM yang dapat penyebabkan permukaan konduktor
tergores atau luka. Peralatan yang digunakan Tensioner dan Puller sebagai alat
bantu untuk proses Penarikan (Stringing).
Copyright January 2020 CTC Global All Rights Reserved 81
Metode Stringing
Layout Proses Penarikan / Stringing
Copyright January 2020 CTC Global All Rights Reserved 82
Set Up Tensioner & Drum
Roller pertama Bullwheel Tensioner berjarak Jarak antara drum dan
sebesar sebanding 3:1 dengan tinggi roller tensioner 15 m – 23 m.
mungkin yang pertama.
mpak Atas Pastikan bahwa Drum, Tensioner, dan
Roller pertama dalam garis lurus.
Copyright January 2020 CTC Global All Rights Reserved 83
Set Up Tensioner & Drum
Alternatve # 1
Apa yang harus dilakukan apabila kondisi lahan tidak
memenuhi jarak ideal pada tensioner ???
❑
Perbesar roller sehingga sudut lengkung konduktor menjadi tidak tajam
Copyright January 2020 CTC Global All Rights Reserved 84
Set Up Tensioner & Drum
Alternatve # 2
❑
Pasang tandem roller
Copyright January 2020 CTC Global All Rights Reserved 85
Set Up Tensioner & Drum
Alternatve # 3
❑
Turunkan roller pertama ke body tower
Copyright January 2020 CTC Global All Rights Reserved 86
Set Up Tensioner & Drum
Alternatve # 4
15m
Front Feed
Tensioner(s)
Copyright January 2020 CTC Global All Rights Reserved 87
Set Up Tensioner & Drum
✓
Banyak tensioner yang digunakan mempunyai
sudut masuk ke bullwheel / capstan yang terlalu
tajam.
Copyright January 2020 CTC Global All Rights Reserved 88
Set Up Tensioner & Drum
Copyright January 2020 CTC Global All Rights Reserved 89
Set Up Tensioner & Drum
Angkur Pada Mesin dan Haspel (Drum)
Copyright January 2020 CTC Global All Rights Reserved 90
Set Up Tensioner & Drum
Akibat tidak diangkur Pada Mesin dan Haspel (Drum)
Copyright January 2020 CTC Global All Rights Reserved 91
Set Up Tensioner & Drum
Reel Arbor Hole and Let-off Equipment
• Pastikan bahwa reel stand yang
digunakan sesuai dengan haspel.
Ukuran Poros/mandrel harus sesuai
dengan lobang pada haspel.
• Gambar menunjukkan poros yang
digunakan terlalu kecil sehingga
haspel akan bergerak keatas kebawah
kian kemari. Ini menyebabkan kontrol
atas tegangan konduktor yang masuk
ke bulwheel /capstan tensioner
menjadi sulit.
Copyright January 2020 CTC Global All Rights Reserved 92
Set Up Tensioner & Drum
Brake Tension pada Drum Stand
✓
Penting untuk betul2 memperhatikan
“brake tension control” pada haspel
konduktor.
✓
Dianjurkan untuk menugaskan satu orang
untuk mengawasi dan mengatur
“brake tension”.
✓
Konduktor akan meluncur dengan lancar
tanpa sentakan2 bila “brake control” yang
tepat digunakan.
✓
Paling baik adalah bila pada drumstand ada
hydraulic motor yang bekerja secara
sinkron dengan tensioner.
Copyright January 2020 CTC Global All Rights Reserved 93
Dead End Assembly
Copyright January 2020 CTC Global All Rights Reserved 94
Peralatan Pemasangan Dead End
Copyright January 2020 CTC Global All Rights Reserved 95
Pemasangan Dead End ACCC®
Prosedure Pemasangan Deadend
Copyright January 2020 CTC Global All Rights Reserved 96
Pemasangan Dead End ACCC®
Pemasangan ACCC ®
Compression Deadend
• Pemotong Kabel standard dapat
digunakan untuk pemotongan
awal konduktor.
• Karena tidak ada steel core
didalam Konduktor ACCC, maka
konduktor akan terpotong dengan
lebih mudah dibanding ACSR.
Copyright January 2020 CTC Global All Rights Reserved 97
Pemasangan Dead End ACCC®
Final Cut Sebelum Pasang Deadend
• Gunakan gergaji tangan untuk
pemotongan final
• Gergaji memastikan ujung core simetris
untuk pemasangan dalam collet.
Copyright January 2020 CTC Global All Rights Reserved 98
Pemasangan Dead End ACCC®
Deadend Body dan Selongsong Dalam
• Setelah pemotongan dengan gergaji,
dorong ke konduktor - pertama inner
sleeve (selongsong dalam) dan
kemudian deadend body.
• Ujung yang tirus (tapered) dari
selongsong dalam dan ujung yang
berlawanan dengan jumper pad di
deadend body yang juga tirus
harus masuk lebih dahulu.
Copyright January 2020 CTC Global All Rights Reserved 99
Pemasangan Dead End ACCC®
Menandai Konduktor untuk Membuka Core
• Buat tanda pada konduktor dengan
jarak sepanjang housing + 50 mm
dari ujung konduktor.
• Dua atau tiga lapis aluminium akan
dibuang mulai dari tanda sampai
ke ujung konduktor.
Copyright January 2020 CTC Global All Rights Reserved 100
Pemasangan Dead End ACCC®
Membuang Strand Aluminum dari Core
• Dua atau tiga lapis strand aluminium
dibuang sehingga core tampak.
• Sebelum memotong strand
aluminium, pastikan strands sudah
diikat memakai klem, kawat atau
tape. Gunakan Strand Cutter atau
gergaji untuk membuang dua atau
tiga lapis strand yang melilit core.
Catatan :
Core jangan tergores/terpotong alat
potong. Bila core tergores, kita harus mulai
lagi dari awal.
Copyright January 2020 CTC Global All Rights
Copyright January 2020 CTC Global All Rights Reserved
Reserved
101
Pemasangan Dead End ACCC®
Membuang Strand Aluminum dari Core
▪
Jangan sampai core tergores alat potong.
▪
Lapisan terbawah aluminium strand
dipotong hanya sebagian.
▪
Kawat aluminium dengan mudah akan
putus bila ditekuk bolak balik.
Copyright January 2020 CTC Global All Rights Reserved 102
Pemasangan Dead End ACCC®
Membersihkan Core
• Bersihkan/lap core dengan kain bersih.
• Perlahan-lahan gunakan amplas yang
tersedia dalam dead end kit untuk
menghilangkan kilap pada lapisan
luar core.
• Bersihkan kembali core
menggunakan lap bersih.
Copyright January 2020 CTC Global All Rights Reserved 103
Pemasangan Dead End ACCC®
Memasang Collet dan Collet Housing
• Selongsongkan collet housing pada
core. Ujung dengan lubang lebih
kecil masuk lebih dulu.
• Kemudian dorong collet (wedge)
dengan bagian yang kecil lebih
dulu ke housing.
• Ujung dari core harusnya muncul
dibelakang collet antara 1/8”
sampai maksimum 1/4”
(3 mm sampai 6 mm)
Copyright January 2020 CTC Global All Rights Reserved 104
Pemasangan Dead End ACCC®
Memasang Deadend Eye
• Masukkan ulir deadend eye
kedalam collet housing dan
putar dengan tangan untuk
mengencangkan.
• Stabilkan dan suport collet
housing pada saat eyebolt
dikencangkan.
• Pastikan untuk menjaga agar
collet housing dan konduktor
tetap dalam satu garis lurus
antara satu dengan lainnya.
Copyright January 2020 CTC Global All Rights Reserved 105
Pemasangan Dead End ACCC®
Memasang Deadend Eye
Minimum
16in (406 mm)
• Gunakan dua wrench (kunci
Inggris) besar untuk
mengencangkan eyebolt dengan
collet housing sampai paling
tidak torsinya 115 Newton
meters. Satu wrench memegang
eyebolt dan satunya pada collect
housing. Hati-hati agar core
tidak terputar pada waktu
pengencangan ini.
• Mengencangkan sambungan
ini akan mendudukkan collet
untuk memegang core.
• Catatan : Selalu putar deadend eye
saja dan tahan dengan wrench
pada housing.
Copyright January 2020 CTC Global All Rights Reserved 106
Pemasangan Dead End ACCC®
Kencangkan Deadend Sampai 85 Foot Pounds/115 Newton Meters
• Setelah eyebolt dikencangkan ke collet housing, akan ada kira-kira 76mm
(3”) core muncul diarah konduktor.
• Collet akan menyembul keluar dari housing nya kira-kira 6 mm (1/4”) yang
menunjukkan bahwa torsi yang benar telah diaplikasikan pada dead-end
dan collet housing.
Copyright January 2020 CTC Global All Rights Reserved 107
Pemasangan Dead End ACCC®
Membersihkan Konduktor
• Gunakan Sikat Kawat untuk membersihkan oksidasi pada
permukaan konduktor aluminium. Jangan gunakan sikat
tembaga untuk pekerjaan ini.
• Deadend harus selalu ditopang / dipegang supaya tidak
core tertekuk.
Copyright January 2020 CTC Global All Rights Reserved 108
Pemasangan Dead End ACCC®
Mengoleskan PROXALUHT A13 pada permukaan Konduktor
• Untuk menghindari masalah dengan oksidasi, inhibitors (disebut demikian
karena ia mencegah akses oksigen dan pertumbuhan lapisan oksidasi)
telah digunakan selama puluhan tahun.
Copyright January 2020 CTC Global All Rights Reserved 109
Pemasangan Dead End ACCC®
Mengoleskan PROXALUHT pada selongsong bagian dalam
• Sikat selongsong dalam untuk membersihkan oksidasi seperti halnya
pada konduktor.
• Sapukan High Temperature Proxaluht pada selongsong dalam dan
dorong selongsong ke dead end body sampai berhenti.
Copyright January 2020 CTC Global All Rights Reserved 110
Pemasangan Dead End ACCC®
Mengapa kita menaruh High Temperature Oxide Inhibitor
(Proxaluth) pada Konduktor dan Selongsong Dalam (Inner
Sleeve) ?
1. Mencegah Oksidasi
2. Membantu mencegah cairan masuk ke deadend dan
splice (sambungan/joint)
3. Membantu menjaga alat ini lebih dingin
Copyright January 2020 CTC Global All Rights Reserved 111
Pemasangan Dead End ACCC®
Memasang Deadend Body
▪
Posisi Ujung Dead End Body
Marking sebelum dipress yaitu tepat berada
pada tanda atau marking yang
sudah ada pada steel eye.
▪
Sebelum di press pastikan Pad
berada pada posisi yang benar.
• Untuk mengarahkan posisi Pad
pada posisi yang benar, hanya
diperbolehkan memutar Dead
End Body saja ( Bukan Steel
Eye ).
• Awal Press dimulai dari arah
konduktor ke arah steel Eye.
Copyright January 2020 CTC Global All Rights Reserved 112
Pemasangan Dead End ACCC®
Birdcaging
▪
Mengepres selongsong aluminium ke
arah konduktor akan menyebabkan strand
aluminium terdorong dan menimbulkan
“birdcaging”
▪
Aluminium akan terdorong sekitar 2,54
mm (satu per sepuluh inci) untuk setiap
kali pengepresan.
▪
CTC mengharuskan metode back press
untuk menghilangkan semua birdcaging
di konduktor.
Copyright January 2020 CTC Global All Rights Reserved 113
Pemasangan Dead End ACCC®
Pengepresan Deadend
▪
Oleskan sabun atau material lain yang
licin pada bagian luar deadend body
agar tidak melekat pada dies.
▪
Tahan dengan tangan ujung selongsong
dalam pada posisinya, kemudian lakukan
satu press mulai 6 mm dari garis tanda
yang paling dekat dengan konduktor.
▪
Putar Boompress 180 derajat setiap
dua press untuk menjaga deadend
tetap lurus.
Copyright January 2020 CTC Global All Rights Reserved 114
Pemasangan Dead End ACCC®
Pengepresan Deadend (Lanjutan)
▪
Teruskan press deadend body dari
arah konduktor ke arah tanda yang
ada di tengah deadend body.
▪
Overlap pengepresan sekitar 10-25 %
mulai dari arah konduktor ke deadend
eye.
Copyright January 2020 CTC Global All Rights Reserved 115
Pemasangan Dead End ACCC®
Deadend Body Pada Pressan Terakhir
▪
Selesai pengepresan pada deadend
body yang terdekat dengan
konduktor, geser press head ke posisi
berikut menuju ke deadend eye.
▪
Lakukan satu atau dua kali
pengepresan dan perhatikan bahwa
body deadend bergerak mendekati
steel eye.
▪
Terdapat Gap / Jarak antara body dead end
dengan steel eye 2 mm – 28 mm*.
▪
Beberapa Dead End type lain memiliki
design GAP yang berbeda.
*Setiap pabrikan hardware memiliki masing – masing prosedur installasi ( tergantung jenis Hardware dan teknis instalasinya )
Copyright January 2020 CTC Global All Rights Reserved 116
Video Dead End ACCC®
Copyright January 2020 CTC Global All Rights Reserved 117
Midspan Joint Assembly (Splice ACCC®
)
Splice Body
Splice Coupler
Copyright January 2020 CTC Global All Rights Reserved
Inner Sleeve
Collet Housing
Collet
118
Pemasangan Midspan Joint ACCC®
Copyright January 2020 CTC Global All Rights Reserved 119
Pemasangan Midspan Joint ACCC®
Persiapan Penyambungan
• Potong secara rata ujung kedua
konduktor yang akan disambung
menggunakan gergaji besi.
• Pada salah satu konduktor
selongsongkan selongsong dalam dan
selongsong luar. (Ujung yang tirus dari
selongsong dalam menghadap keluar
dari ujung konduktor yang dipotong).
• Pada konduktor yang satunya
selongsongkan juga selongsong
dalam satunya.
Copyright January 2020 CTC Global All Rights Reserved 120
Pemasangan Midspan Joint ACCC®
Instruksi Penyambungan – Teknik Back Pressing
▪
▪
Selongsongkan selongsong dalam pada konduktor sampai sejauh kira2
1 meter (gamb 1).
Kemudian selongsongkan selongsong luar pada sisi yang lebih jauh dari
tower (Side B) hingga ujung tabung sekitar 60 cm dari ujung konduktor
yang dipotong.
Copyright January 2020 CTC Global All Rights Reserved 121
Pemasangan Midspan Joint ACCC®
Instruksi Penyambungan (lanjutan)
• Pasang tape melilit aluminium strand pada jarak tertentu dari ujung konduktor
(Lihat Tabel A)
ACCC
Code
Name
Linnet
Hawk
Dove
Grosbeak
Drake
Cardinal
Bittern
Lapwing
Chukar
Bluebird
Outside
Dia.
(inches)
0.720
0.858
0.927
0.990
1.108
1.196
1.345
1.504
1.602
1.762
Table A
Side A
Exposed core
length (inches)
9.0 (228 mm)
9.0 (228 mm)
9.0 (228 mm)
9.0 (228 mm)
12.5 (317 mm)
12.5 (317 mm)
12.5 (317 mm)
12.5 (317 mm)
12.5 (317 mm)
12.5 (317 mm)
Side B
Exposed core
length (inches)
7.0 (177 mm)
7.0 (177 mm)
7.0 (177 mm)
7.0 (177 mm)
10.5 (266 mm)
10.5 (266 mm)
10.5 (266 mm)
10.5 (266 mm)
10.5 (266 mm)
10.5 (266 mm)
▪
Munculkan solid core dengan memotong aluminium strand pada tanda, satu lapis demi satu lapis
Copyright January 2020 CTC Global All Rights Reserved 122
Pemasangan Midspan Joint ACCC®
Instruksi Penyambungan (lanjutan)
• Lap permukaan core sampai bersih, bebas dari oli dan kotoran lain.
Kemudian gosok core perlahan memakai kertas amplas 220 mesh sampai
putih dan lap kembali core menggunakan kain bersih.
• Pasang collet housing (Lihat Fig.2)
▪
Pasang collet (Fig.2) pada core dengan ujung yang kecil kearah
housing, sampai core muncul sekitar 6 mm disisi besar collet (Lihat
Fig.3). Ulangi untuk sisi lainnya.
Copyright January 2020 CTC Global All Rights Reserved 123
Pemasangan Midspan Joint ACCC®
Instruksi Penyambungan (lanjutan)
▪
Pasang coupling di sisi A (terdekat dengan tower) dan collet retainer pada sisi B
(terjauh dari tower) dan kencang-kan pakai tangan. Kencangkan lebih lanjut
menggunakan kunci Inggris (diperlukan torsi 85 ftlbs atau 115 NM).
▪
Untuk Sisi A pastikan bahwa kira - kira 76 mm core dan ujung kecil collet tampak
setelah dikencangkan (Lihat Fig 4).
▪
Untuk sisi B pastikan bahwa kira - kira 26 mm core dan ujung kecil collet tampak
setelah dikencangkan (Lihat Fig 4)
▪
Taruh sedikit inhibitor pada ulir. Satukan kedua sisi dan kencangkan dengan tangan.
Kencangkan lebih lanjut memakai wrench (perlu torsi 115Nm)
Copyright January 2020 CTC Global All Rights Reserved 124
Pemasangan Midspan Joint ACCC®
Instrucksi Penyambungan (lanjutan)
▪
Tandai konduktor pada sisi A sepanjang Inner sleeve dari ujung aluminium strand
pakai tape atau spidol (Fig.5). Tanda ini adalah lokasi ujung
selongsong dalam.
• Catatan : Bila pakai tape, tape ini harus dibuang sebelum pengepresan.
▪
Sikat aluminium strand yang akan tertutup oleh selongsong luar dan sapukan
oxidation inhibitor pada bagian strand yang telah disikat.(Lihat Fig. 5)
Tandai pada konduktor
sepanjang inner sleeve
Copyright January 2020 CTC Global All Rights Reserved 125
Pemasangan Midspan Joint ACCC®
Instruksi Penyambungan (lanjutan)
▪
Kemudian pasang selongsong luar aluminium menutupi coupling assembly.
▪
Sisi A : Berikan oxidation inhibitor pada bagian luar selongsong dalam,dan
masukkan selongsong dalam ke selongsong luar sampai ke tanda di
konduktor. Pastikan selongsong dalam mencapai pembatas yang ada
didalam selongsong luar. Gerakkan selongsong luar bila perlu.
▪
Ketika selongsong luar sudah pada tempatnya, press selongsong dimulai dari sisi
A kearah dalam menggunakan dies yang benar dan overlap press 10-25% lebar
Dies sampai akhir zona press di Sisi A (Lihat Fig. 6)
mark conductor
Copyright January 2020 CTC Global All Rights Reserved 126
Pemasangan Midspan Joint ACCC®
Finished Splice
▪
Dengan memutar presshead 180 derajat setiap dua kali mengepres
dan menjaga agar semua level ketika mengepres, sambungan akan
lurus setelah selesai.
Catatan : Oleskan sabun atau material lain yang licin pada bagian
luar sambungan agar aluminium tidak menyangkut ke dies.
Copyright January 2020 CTC Global All Rights Reserved 127
Video Midspan Joint ACCC®
Copyright January 2020 CTC Global All Rights Reserved 128
Pemasangan Jumper ACCC®
✓
Jumper pad akandi
“back pressed” untuk menghilangkan
kemungkinan birdcaging.
✓
Gaya mekanis yang
bekerja padaJumper relatif
kecil sehingga tidak perlu ada upaya
khusus untruk memegang core.
✓
Dengan demikian
untukpemasangan Jumper,
aluminium strand tidak perlu
dikupas lebih dahulu.
Copyright January 2020 CTC Global All Rights Reserved 129
Pemasangan Jumper ACCC®
❑
Potong ujung konduktor memakai gergaji.
❑
Sikat permukaan konduktor.
❑
Masukkan dan tarik konduktor ke dan dari dalam pad
beberapa kali, kemudian buang kelebihan inhibitor
memakai kain bersih.
❑
Setelah membuang kelebihan inhibitor, masukkan
konduktor hingga ke ujung dari pad.
❑
Gunakan mesin press hydraulic kapasitas minimum 60
Ton untuk press jumper body. Pres mulai dari arah
konduktor menuju ke ujung pad. Overlap setiap pres.
❑
Bersihkan inhibitor yang berlebih.
Copyright January 2020 CTC Global All Rights Reserved 130
Pemasangan Jumper ACCC®
✓ Bila jumper fitting di pres seperti biasanya, akan terjadi birdcaging yang ekstrim dari
strand aluminium paling luar karena konduktor kurang panjang untuk bisa
menyerap atau menghilangkan birdcaging.
✓ Untuk mencegah hal ini terjadi, jumper pad fitting dipasang dengan cara “back
pressing”
Copyright January 2020 CTC Global All Rights Reserved 131
Toleransi Dead End & Midspan
Joint ACCC®
✓ Setiap kali dies alat pres menekan pada fitting, logam dipaksa bergerak dibagian
dalam dan luar dari fitting. Dalam proses ini, gesekan antara fitting dan die set
bisa menyebabkan bagian yang dipress melengkung. Adalah penting untuk
memberi pelumas pada dies dan menjaga fitting tetap lurus. Melumuri bagian luar
fitting dengan sabun akan sangat menolong.
✓ Sebagai aturan umum maka besar maksimum lengkungan pada deadend atau
jumper fitting adalah 1/2 diameter konduktor sedang pada splice
(sambungan) adalah 1 x diameter konduktor.
✓
Periksa kelurusan fitting.
✓
Lengkung terlalu
banyak bisamenyebabkan stres
internal pada logam dan kegagalan
mekanis fitting.
Copyright January 2020 CTC Global All Rights Reserved 132
Suspention Clamp & Damper
Melindungi terhadap tekukan, tekanan, gesekan, arc-over dan juga perbaikan. Dipakai
pada konduktor ACCC menolong menurunkan panas. Gunakan “parrot bill” armor rod
pada tegangan ekstra tinggi – 345 kV dan lebih tinggi. Karena konduktor ACCC dari
aluminium lunak, maka pada pemasangan suspension clamp, damper dan spacer
maka armor rod harus digunakan.
Copyright January 2020 CTC Global All Rights Reserved 133
Suspention Clamp & Damper
AGS/Thermolign/CGS, and Hibus Suspensions
▪
AGS (Armor Grip Suspension) atau
Thermolign Suspension direkomendasikan
untuk dipakai pada konduktor ACCC. Sistim
AGS pakai satu set armor rod sedang
Thermolign pakai dua set armorrod.
Thermolign mempunyai temperatur rating
maksimum yang lebih tinggi. Keduanya
mengurangi temperatur ke insulator secara
dramatis dan juga memberi perlindungan
tambahan terhadap sudut. Untuk sudut
yang lebih besar lagi, direkomendasikan
memakai double suspension system.
▪
Dimana tidak cukup ruang untuk memasang
armor rod seperti pada Jumper, gunakan CGS
(Cushion Grip Suspensions) yang menawarkan
suspension system bertemperatur tinggi tanpa
armor rod.
Copyright January 2020 CTC Global All Rights Reserved 134
Suspention Clamp & Damper
Double Suspension Clamps
▪
Bila struktur mengalami downpull
yang besar atau mempunyai peru-
bahan sudut lebih besar dari 30
derajat, double suspension clamp
arrangement bisa digunakan untuk
pengganti deadend..
Copyright January 2020 CTC Global All Rights Reserved 135
Suspention Clamp & Damper
Lifting ACCC
Copyright January 2020 CTC Global All Rights Reserved 136
Suspention Clamp & Damper
Vibration Damper
▪ Tanya pada FCI Burndy, PLP atau vendor yang telah disetujui tentang desain
damper yang sesuai beserta rekomendasi metode dan posisi pemasangannya
untuk konduktor ACCC.
Copyright January 2020 CTC Global All Rights Reserved 137
Suspention Clamp & Damper
T-Tap ACCC
Press
Direction
Copyright January 2020 CTC Global All Rights Reserved 138
Kesimpulan Instalasi Konduktor ACCC®
✓ Meskipun ada beberapa perbedaan
cara pemasangan antara konduktor
ACSR dengan ACCC, namun Yang sama
lebih banyak.
✓ Persiapan yang baik adalah hal penting
untuk menghindari kejutan yang tidak
menyenangkan pada waktu
pelaksanaan..
✓ Crew stringing akan cepat beradaptasi
dengan konduktor ACCC karena teknik
pemasangan tidak rumit dan mudah
dipelajari.
Copyright January 2020 CTC Global All Rights Reserved 139
thanks you for attending today’s
Saeful Hidayat
Email: saeful_hidayat@de-mandiri.com
HP : 0853 1015 5478
PT Dinamika Elektra Mandiri
Jl. Perjuangan, Rukan Graha Mas Blok B.
26 Kebon Jeruk, Jakarta Barat 11530
Copyright January 2020 CTC Global All Rights Reserved 140

More Related Content

What's hot

Modul pemeliharaan komponen engine
Modul pemeliharaan komponen engineModul pemeliharaan komponen engine
Modul pemeliharaan komponen engineAhmad Faozi
 
Thiết kế hộp phân phối vi sai có vi sai và khớp ma sát điều khiển điện tử
Thiết kế hộp phân phối vi sai có vi sai và khớp ma sát điều khiển điện tửThiết kế hộp phân phối vi sai có vi sai và khớp ma sát điều khiển điện tử
Thiết kế hộp phân phối vi sai có vi sai và khớp ma sát điều khiển điện tửLeovnuf
 
MEKANIKA TEKNIK - TEGANGAN
MEKANIKA TEKNIK - TEGANGANMEKANIKA TEKNIK - TEGANGAN
MEKANIKA TEKNIK - TEGANGANHettyk Sari
 
Aplikasi excel-2007-dalam-bidang-teknik-mesin
Aplikasi excel-2007-dalam-bidang-teknik-mesinAplikasi excel-2007-dalam-bidang-teknik-mesin
Aplikasi excel-2007-dalam-bidang-teknik-mesinRonny wisanggeni
 
259343480 transmisi-4-speed
259343480 transmisi-4-speed259343480 transmisi-4-speed
259343480 transmisi-4-speedwitospd
 
Laporan praktikum desmen 3
Laporan praktikum desmen 3Laporan praktikum desmen 3
Laporan praktikum desmen 3Dheny Dharmawan
 
ANALISIS DESAIN SISTEM GRID PENTANAHAN PLTU BERAU KALIMANTAN TIMUR 2 X 7 MW
ANALISIS DESAIN SISTEM GRID PENTANAHAN PLTU BERAU KALIMANTAN TIMUR 2 X 7 MWANALISIS DESAIN SISTEM GRID PENTANAHAN PLTU BERAU KALIMANTAN TIMUR 2 X 7 MW
ANALISIS DESAIN SISTEM GRID PENTANAHAN PLTU BERAU KALIMANTAN TIMUR 2 X 7 MWSyamsirAbduh2
 
Job Sheet Pembongkaran, pemeriksaan dan perakitan starter
Job Sheet Pembongkaran, pemeriksaan dan perakitan starterJob Sheet Pembongkaran, pemeriksaan dan perakitan starter
Job Sheet Pembongkaran, pemeriksaan dan perakitan starterCharis Muhammad
 
Pengukuran roda gigi bab5
Pengukuran roda gigi bab5Pengukuran roda gigi bab5
Pengukuran roda gigi bab5LAZY MAGICIAN
 
MACAM-MACAM SAMBUNGAN PADA KONSTRUKSI MESIN
MACAM-MACAM SAMBUNGAN PADA KONSTRUKSI MESINMACAM-MACAM SAMBUNGAN PADA KONSTRUKSI MESIN
MACAM-MACAM SAMBUNGAN PADA KONSTRUKSI MESINDwi Ratna
 
ANALISIS PENYEBAB GANGGUAN JARINGAN PADA DISTRIBUSI.pdf
ANALISIS PENYEBAB GANGGUAN JARINGAN PADA DISTRIBUSI.pdfANALISIS PENYEBAB GANGGUAN JARINGAN PADA DISTRIBUSI.pdf
ANALISIS PENYEBAB GANGGUAN JARINGAN PADA DISTRIBUSI.pdffadilahkurniati1
 
Thiết kế máy uốn ống.pdf
Thiết kế máy uốn ống.pdfThiết kế máy uốn ống.pdf
Thiết kế máy uốn ống.pdfMan_Ebook
 
Tugas1 cnc kelas a_presentasi_power point
Tugas1 cnc kelas a_presentasi_power pointTugas1 cnc kelas a_presentasi_power point
Tugas1 cnc kelas a_presentasi_power pointIlham Reyzer Firmansyah
 
Teknologi bengkel elektronika
Teknologi bengkel elektronikaTeknologi bengkel elektronika
Teknologi bengkel elektronikaEko Supriyadi
 
Tune-up Motor Bensin
Tune-up Motor BensinTune-up Motor Bensin
Tune-up Motor BensinAhmad Faozi
 
contoh-soal-motor-induksi-satu-phasa.
contoh-soal-motor-induksi-satu-phasa.contoh-soal-motor-induksi-satu-phasa.
contoh-soal-motor-induksi-satu-phasa.Kevin Adit
 

What's hot (20)

Modul pemeliharaan komponen engine
Modul pemeliharaan komponen engineModul pemeliharaan komponen engine
Modul pemeliharaan komponen engine
 
Thiết kế hộp phân phối vi sai có vi sai và khớp ma sát điều khiển điện tử
Thiết kế hộp phân phối vi sai có vi sai và khớp ma sát điều khiển điện tửThiết kế hộp phân phối vi sai có vi sai và khớp ma sát điều khiển điện tử
Thiết kế hộp phân phối vi sai có vi sai và khớp ma sát điều khiển điện tử
 
MEKANIKA TEKNIK - TEGANGAN
MEKANIKA TEKNIK - TEGANGANMEKANIKA TEKNIK - TEGANGAN
MEKANIKA TEKNIK - TEGANGAN
 
Aplikasi excel-2007-dalam-bidang-teknik-mesin
Aplikasi excel-2007-dalam-bidang-teknik-mesinAplikasi excel-2007-dalam-bidang-teknik-mesin
Aplikasi excel-2007-dalam-bidang-teknik-mesin
 
259343480 transmisi-4-speed
259343480 transmisi-4-speed259343480 transmisi-4-speed
259343480 transmisi-4-speed
 
Laporan praktikum desmen 3
Laporan praktikum desmen 3Laporan praktikum desmen 3
Laporan praktikum desmen 3
 
ANALISIS DESAIN SISTEM GRID PENTANAHAN PLTU BERAU KALIMANTAN TIMUR 2 X 7 MW
ANALISIS DESAIN SISTEM GRID PENTANAHAN PLTU BERAU KALIMANTAN TIMUR 2 X 7 MWANALISIS DESAIN SISTEM GRID PENTANAHAN PLTU BERAU KALIMANTAN TIMUR 2 X 7 MW
ANALISIS DESAIN SISTEM GRID PENTANAHAN PLTU BERAU KALIMANTAN TIMUR 2 X 7 MW
 
Job Sheet Pembongkaran, pemeriksaan dan perakitan starter
Job Sheet Pembongkaran, pemeriksaan dan perakitan starterJob Sheet Pembongkaran, pemeriksaan dan perakitan starter
Job Sheet Pembongkaran, pemeriksaan dan perakitan starter
 
Pengukuran roda gigi bab5
Pengukuran roda gigi bab5Pengukuran roda gigi bab5
Pengukuran roda gigi bab5
 
MACAM-MACAM SAMBUNGAN PADA KONSTRUKSI MESIN
MACAM-MACAM SAMBUNGAN PADA KONSTRUKSI MESINMACAM-MACAM SAMBUNGAN PADA KONSTRUKSI MESIN
MACAM-MACAM SAMBUNGAN PADA KONSTRUKSI MESIN
 
Rumus perhitungan roda gigi lurus
Rumus perhitungan roda gigi lurusRumus perhitungan roda gigi lurus
Rumus perhitungan roda gigi lurus
 
ANALISIS PENYEBAB GANGGUAN JARINGAN PADA DISTRIBUSI.pdf
ANALISIS PENYEBAB GANGGUAN JARINGAN PADA DISTRIBUSI.pdfANALISIS PENYEBAB GANGGUAN JARINGAN PADA DISTRIBUSI.pdf
ANALISIS PENYEBAB GANGGUAN JARINGAN PADA DISTRIBUSI.pdf
 
Generator dc
Generator dcGenerator dc
Generator dc
 
Lift 3 lantai plc
Lift 3 lantai plcLift 3 lantai plc
Lift 3 lantai plc
 
Thiết kế máy uốn ống.pdf
Thiết kế máy uốn ống.pdfThiết kế máy uốn ống.pdf
Thiết kế máy uốn ống.pdf
 
Tugas1 cnc kelas a_presentasi_power point
Tugas1 cnc kelas a_presentasi_power pointTugas1 cnc kelas a_presentasi_power point
Tugas1 cnc kelas a_presentasi_power point
 
Teknologi bengkel elektronika
Teknologi bengkel elektronikaTeknologi bengkel elektronika
Teknologi bengkel elektronika
 
Tune-up Motor Bensin
Tune-up Motor BensinTune-up Motor Bensin
Tune-up Motor Bensin
 
Sistem pelumasan
Sistem pelumasanSistem pelumasan
Sistem pelumasan
 
contoh-soal-motor-induksi-satu-phasa.
contoh-soal-motor-induksi-satu-phasa.contoh-soal-motor-induksi-satu-phasa.
contoh-soal-motor-induksi-satu-phasa.
 

Similar to ACCC INSTALASI

PIT39 HATHI persentasi teknologi pembangkit tenaga listrik
PIT39 HATHI persentasi  teknologi pembangkit tenaga listrikPIT39 HATHI persentasi  teknologi pembangkit tenaga listrik
PIT39 HATHI persentasi teknologi pembangkit tenaga listrikspoytv23
 
01_PPT Lawe Sikap rev04
01_PPT Lawe Sikap rev0401_PPT Lawe Sikap rev04
01_PPT Lawe Sikap rev04Putri Hidayati
 
perhitungan metode PCI (PAVEMENT CONDITION INDEX)
perhitungan metode PCI (PAVEMENT CONDITION INDEX)perhitungan metode PCI (PAVEMENT CONDITION INDEX)
perhitungan metode PCI (PAVEMENT CONDITION INDEX)eniwijayanti
 
Perencanaan jaringan nirkabel dan analisa tekno ekonominya
Perencanaan jaringan nirkabel dan analisa tekno ekonominyaPerencanaan jaringan nirkabel dan analisa tekno ekonominya
Perencanaan jaringan nirkabel dan analisa tekno ekonominyamohamad syahral
 
C3 e36de dd01
C3 e36de dd01C3 e36de dd01
C3 e36de dd01Teateen X
 
Analisis Drainase Green Lake Cipondoh.pdf
Analisis Drainase Green Lake Cipondoh.pdfAnalisis Drainase Green Lake Cipondoh.pdf
Analisis Drainase Green Lake Cipondoh.pdfedipurnomo68
 
PPT justifikasi Pendampingan.pptx
PPT justifikasi Pendampingan.pptxPPT justifikasi Pendampingan.pptx
PPT justifikasi Pendampingan.pptxHandityoPramadhana
 
Ppt tanjung emas semarang final
Ppt tanjung emas semarang finalPpt tanjung emas semarang final
Ppt tanjung emas semarang finalAldoni Harda
 
Tugas Kelompok Mata Kuliah Pembangunan dan Pemeliharaan Jalan Raya
Tugas Kelompok Mata Kuliah Pembangunan dan Pemeliharaan Jalan Raya Tugas Kelompok Mata Kuliah Pembangunan dan Pemeliharaan Jalan Raya
Tugas Kelompok Mata Kuliah Pembangunan dan Pemeliharaan Jalan Raya Reza Maha
 
Perencanaan Ulang Fondasi Abutmen Jembatan Bendo Menggunakan Fondasi.pptx
Perencanaan Ulang Fondasi Abutmen Jembatan Bendo Menggunakan Fondasi.pptxPerencanaan Ulang Fondasi Abutmen Jembatan Bendo Menggunakan Fondasi.pptx
Perencanaan Ulang Fondasi Abutmen Jembatan Bendo Menggunakan Fondasi.pptxryanmuamar
 
PPT UJI KEMAMPUAN DAYA TAMPUNG DRAINASE.pptx
PPT UJI KEMAMPUAN DAYA TAMPUNG DRAINASE.pptxPPT UJI KEMAMPUAN DAYA TAMPUNG DRAINASE.pptx
PPT UJI KEMAMPUAN DAYA TAMPUNG DRAINASE.pptxMuhammadKamil69
 
Analysis Vortex Generator
Analysis Vortex GeneratorAnalysis Vortex Generator
Analysis Vortex GeneratorRobbi Hamdika
 
Atap panggung inflatable energi surya fotovoltaik
Atap panggung inflatable energi surya fotovoltaikAtap panggung inflatable energi surya fotovoltaik
Atap panggung inflatable energi surya fotovoltaikHery budiyanto
 
MB 9.a.6. - PerhitPipa.ppt
MB 9.a.6. - PerhitPipa.pptMB 9.a.6. - PerhitPipa.ppt
MB 9.a.6. - PerhitPipa.pptRidhaSafrani
 
Desain Rekayasa II FIXED JACKET PLATFORM 70.000 BOPD by Muhammad Azka Bintang...
Desain Rekayasa II FIXED JACKET PLATFORM 70.000 BOPD by Muhammad Azka Bintang...Desain Rekayasa II FIXED JACKET PLATFORM 70.000 BOPD by Muhammad Azka Bintang...
Desain Rekayasa II FIXED JACKET PLATFORM 70.000 BOPD by Muhammad Azka Bintang...MuhammadAzkaBintangA
 
Materi-Bahan Presentasi_013362.pdf
Materi-Bahan Presentasi_013362.pdfMateri-Bahan Presentasi_013362.pdf
Materi-Bahan Presentasi_013362.pdfArif Matondang
 
Kalkulasi tegangan jatuh
Kalkulasi tegangan jatuhKalkulasi tegangan jatuh
Kalkulasi tegangan jatuhMuhammad Reza
 

Similar to ACCC INSTALASI (20)

PIT39 HATHI persentasi teknologi pembangkit tenaga listrik
PIT39 HATHI persentasi  teknologi pembangkit tenaga listrikPIT39 HATHI persentasi  teknologi pembangkit tenaga listrik
PIT39 HATHI persentasi teknologi pembangkit tenaga listrik
 
01_PPT Lawe Sikap rev04
01_PPT Lawe Sikap rev0401_PPT Lawe Sikap rev04
01_PPT Lawe Sikap rev04
 
perhitungan metode PCI (PAVEMENT CONDITION INDEX)
perhitungan metode PCI (PAVEMENT CONDITION INDEX)perhitungan metode PCI (PAVEMENT CONDITION INDEX)
perhitungan metode PCI (PAVEMENT CONDITION INDEX)
 
Perencanaan jaringan nirkabel dan analisa tekno ekonominya
Perencanaan jaringan nirkabel dan analisa tekno ekonominyaPerencanaan jaringan nirkabel dan analisa tekno ekonominya
Perencanaan jaringan nirkabel dan analisa tekno ekonominya
 
C3 e36de dd01
C3 e36de dd01C3 e36de dd01
C3 e36de dd01
 
Analisis Drainase Green Lake Cipondoh.pdf
Analisis Drainase Green Lake Cipondoh.pdfAnalisis Drainase Green Lake Cipondoh.pdf
Analisis Drainase Green Lake Cipondoh.pdf
 
Data Teknis Fluke 1630-2 FC
Data Teknis Fluke 1630-2 FCData Teknis Fluke 1630-2 FC
Data Teknis Fluke 1630-2 FC
 
PPT justifikasi Pendampingan.pptx
PPT justifikasi Pendampingan.pptxPPT justifikasi Pendampingan.pptx
PPT justifikasi Pendampingan.pptx
 
Ppt tanjung emas semarang final
Ppt tanjung emas semarang finalPpt tanjung emas semarang final
Ppt tanjung emas semarang final
 
Tugas Kelompok Mata Kuliah Pembangunan dan Pemeliharaan Jalan Raya
Tugas Kelompok Mata Kuliah Pembangunan dan Pemeliharaan Jalan Raya Tugas Kelompok Mata Kuliah Pembangunan dan Pemeliharaan Jalan Raya
Tugas Kelompok Mata Kuliah Pembangunan dan Pemeliharaan Jalan Raya
 
RAB PLTMH Sirin-Punti-dgn-ppn
RAB PLTMH  Sirin-Punti-dgn-ppnRAB PLTMH  Sirin-Punti-dgn-ppn
RAB PLTMH Sirin-Punti-dgn-ppn
 
Perencanaan Ulang Fondasi Abutmen Jembatan Bendo Menggunakan Fondasi.pptx
Perencanaan Ulang Fondasi Abutmen Jembatan Bendo Menggunakan Fondasi.pptxPerencanaan Ulang Fondasi Abutmen Jembatan Bendo Menggunakan Fondasi.pptx
Perencanaan Ulang Fondasi Abutmen Jembatan Bendo Menggunakan Fondasi.pptx
 
PPT UJI KEMAMPUAN DAYA TAMPUNG DRAINASE.pptx
PPT UJI KEMAMPUAN DAYA TAMPUNG DRAINASE.pptxPPT UJI KEMAMPUAN DAYA TAMPUNG DRAINASE.pptx
PPT UJI KEMAMPUAN DAYA TAMPUNG DRAINASE.pptx
 
Analysis Vortex Generator
Analysis Vortex GeneratorAnalysis Vortex Generator
Analysis Vortex Generator
 
Atap panggung inflatable energi surya fotovoltaik
Atap panggung inflatable energi surya fotovoltaikAtap panggung inflatable energi surya fotovoltaik
Atap panggung inflatable energi surya fotovoltaik
 
MB 9.a.6. - PerhitPipa.ppt
MB 9.a.6. - PerhitPipa.pptMB 9.a.6. - PerhitPipa.ppt
MB 9.a.6. - PerhitPipa.ppt
 
Desain Rekayasa II FIXED JACKET PLATFORM 70.000 BOPD by Muhammad Azka Bintang...
Desain Rekayasa II FIXED JACKET PLATFORM 70.000 BOPD by Muhammad Azka Bintang...Desain Rekayasa II FIXED JACKET PLATFORM 70.000 BOPD by Muhammad Azka Bintang...
Desain Rekayasa II FIXED JACKET PLATFORM 70.000 BOPD by Muhammad Azka Bintang...
 
Materi-Bahan Presentasi_013362.pdf
Materi-Bahan Presentasi_013362.pdfMateri-Bahan Presentasi_013362.pdf
Materi-Bahan Presentasi_013362.pdf
 
Tugas softskill
Tugas softskillTugas softskill
Tugas softskill
 
Kalkulasi tegangan jatuh
Kalkulasi tegangan jatuhKalkulasi tegangan jatuh
Kalkulasi tegangan jatuh
 

Recently uploaded

Strategi Pengembangan Agribisnis di Indonesia
Strategi Pengembangan Agribisnis di IndonesiaStrategi Pengembangan Agribisnis di Indonesia
Strategi Pengembangan Agribisnis di IndonesiaRenaYunita2
 
Slide Transformasi dan Load Data Menggunakan Talend Open Studio
Slide Transformasi dan Load Data Menggunakan Talend Open StudioSlide Transformasi dan Load Data Menggunakan Talend Open Studio
Slide Transformasi dan Load Data Menggunakan Talend Open Studiossuser52d6bf
 
Pembangkit Listrik Tenaga Nuklir Kelompok 1.pptx
Pembangkit Listrik Tenaga Nuklir Kelompok 1.pptxPembangkit Listrik Tenaga Nuklir Kelompok 1.pptx
Pembangkit Listrik Tenaga Nuklir Kelompok 1.pptxmuhammadrizky331164
 
05 Sistem Perencanaan Pembangunan Nasional.ppt
05 Sistem Perencanaan Pembangunan Nasional.ppt05 Sistem Perencanaan Pembangunan Nasional.ppt
05 Sistem Perencanaan Pembangunan Nasional.pptSonyGobang1
 
001. Ringkasan Lampiran Juknis DAK 2024_PAUD.pptx
001. Ringkasan Lampiran Juknis DAK 2024_PAUD.pptx001. Ringkasan Lampiran Juknis DAK 2024_PAUD.pptx
001. Ringkasan Lampiran Juknis DAK 2024_PAUD.pptxMuhararAhmad
 
2021 - 10 - 03 PAPARAN PENDAHULUAN LEGGER JALAN.pptx
2021 - 10 - 03 PAPARAN PENDAHULUAN LEGGER JALAN.pptx2021 - 10 - 03 PAPARAN PENDAHULUAN LEGGER JALAN.pptx
2021 - 10 - 03 PAPARAN PENDAHULUAN LEGGER JALAN.pptxAnnisaNurHasanah27
 

Recently uploaded (6)

Strategi Pengembangan Agribisnis di Indonesia
Strategi Pengembangan Agribisnis di IndonesiaStrategi Pengembangan Agribisnis di Indonesia
Strategi Pengembangan Agribisnis di Indonesia
 
Slide Transformasi dan Load Data Menggunakan Talend Open Studio
Slide Transformasi dan Load Data Menggunakan Talend Open StudioSlide Transformasi dan Load Data Menggunakan Talend Open Studio
Slide Transformasi dan Load Data Menggunakan Talend Open Studio
 
Pembangkit Listrik Tenaga Nuklir Kelompok 1.pptx
Pembangkit Listrik Tenaga Nuklir Kelompok 1.pptxPembangkit Listrik Tenaga Nuklir Kelompok 1.pptx
Pembangkit Listrik Tenaga Nuklir Kelompok 1.pptx
 
05 Sistem Perencanaan Pembangunan Nasional.ppt
05 Sistem Perencanaan Pembangunan Nasional.ppt05 Sistem Perencanaan Pembangunan Nasional.ppt
05 Sistem Perencanaan Pembangunan Nasional.ppt
 
001. Ringkasan Lampiran Juknis DAK 2024_PAUD.pptx
001. Ringkasan Lampiran Juknis DAK 2024_PAUD.pptx001. Ringkasan Lampiran Juknis DAK 2024_PAUD.pptx
001. Ringkasan Lampiran Juknis DAK 2024_PAUD.pptx
 
2021 - 10 - 03 PAPARAN PENDAHULUAN LEGGER JALAN.pptx
2021 - 10 - 03 PAPARAN PENDAHULUAN LEGGER JALAN.pptx2021 - 10 - 03 PAPARAN PENDAHULUAN LEGGER JALAN.pptx
2021 - 10 - 03 PAPARAN PENDAHULUAN LEGGER JALAN.pptx
 

ACCC INSTALASI

  • 1. ACCC® Conductor Installation Training Service Instructor: Saeful Hidayat PT PLN UIT Jawa Bagian Tengah Jepara, 04 Agustus 2020
  • 2. Technoloy is Not Stagnant ACSR 1910 2004 ACCC® Copyright January 2020 CTC Global All Rights Reserved 2
  • 3. Ukuran dan Testing Konduktor ACCC ® Proses Pembuatan Core Copyright January 2020 CTC Global All Rights Reserved 3
  • 4. Ukuran dan Testing Konduktor ACCC ® Proses Pembuatan Core Copyright January 2020 CTC Global All Rights Reserved 4
  • 5. Ukuran dan Testing Konduktor ACCC ® Design Avoides “Keystoning”or Gaps Copyright January 2020 CTC Global All Rights Reserved 5
  • 6. Ukuran dan Testing Konduktor ACCC ® Environmental Testing & Monitoring 2000 1800 ACSR 1600 ACSS (mm 1400 ACCR 1200 ACCC Sag 1000 Cable 800 600 400 200 0 0 20 40 60 80 100 120 140 160 180 200 220 240 260 Temperature (C) ACCC ® Lines being monitored by: • National Grid (Niagara Falls, New York) • EPRI HTLS Conductor Study Group (at APS) • WAPA (Phoenix, AZ) • PacifiCorp (Salt Lake City) • State Grid China (Beijing and Shanghai) • RTE / EDF France (Minerve and Renardieres) *Characteristics being monitored: • Ambient Temperature • Tension, Sag, and clearance • Conductor Temperature • Electrical Current • Wind Speed and Direction • Solar Radiation • Rainfall • Ice buildup • Splice Resistance • Infrared Measurements • Corona Observations • Electric and Magnetic Fields Copyright January 2020 CTC Global All Rights Reserved 6
  • 7. Ukuran dan Testing Konduktor ACCC ® Core Testing: 2.1.1 Tensile Testing 2.1.2 Flexural, Bending & Shear Tests 2.1.3 Sustained Load Tests 2.1.4 Tg Tests 2.1.5 CTE Measurements 2.1.6 Shear Testing 2.1.7 Impact and Crush Testing 2.1.8 Torsion Testing 2.1.9 Notched Degradation Testing 2.1.10 Moisture Resistance Testing 2.1.11 Long Term Thermal Testing 2.1.12 Sustained Load Thermal Testing 2.1.13 Cyclic Thermal Testing 2.1.14 Specific Heat Capacity Testing 2.1.15 High Temperature Short Duration 2.1.16 High Temperature Core Testing 2.1.17 Thermal Oxidation Testing 2.1.18 Brittle Fracture Testing 2.1.19 UV Testing 2.1.20 Salt Fog Exposure Tests 2.1.21 Creep Tests 2.1.22 Stress Strain Testing 2.1.24 Micrographic Analysis 2.1.25 Dye Penetrant Testing 2.1.26 High Temperature Shear Testing 2.1.27 Low Temperature Shear Testing Mechanical Conductor Testing: 2.2.28 Stress Strain Testing 2.2.29 Creep Testing 2.2.30 Aeolian Vibration Testing 2.2.31 Galloping Tests 2.2.32 Self Damping Tests 2.2.33 Radial Impact and Crush Tests 2.2.34 Turning Angle Tests 2.2.35 Torsion Tests 2.2.36 High Temperature Sag Tests 2.2.37 High Temperature Sustained Load 2.2.38 High Temperature Cyclic Load Tests 2.2.39 Cyclic Ice Load Tests 2.2.40 Sheave Wheel Tests 2.2.41 Ultimate Strength Tests 2.2.42 Cyclic Thermo-Mechanical Testing 2.2.43 Combined Cyclic Load Testing 2.2.44 Conductor Comparison Testing Systems & Hardware Testing: 2.4.55 Current Cycle Testing 2.4.56 Sustained Load Testing 2.4.57 Ultimate Assembly Strength Testing 2.4.58 Salt Fog Emersion Testing 2.4.60 Static Heat Tests 2.4.61 Suspension Clamp Testing 2.4.62 Thermo-Mechanical Testing 2.4.63 Cyclic Load Testing Electrical Conductor Testing: 2.3.45 Resistivity Testing 2.3.46 Power Loss Comparison Testing 2.3.47 Ampacity 2.3.48 EMF Measurements 2.3.49 Impedance Comparison Testing 2.3.50 Corona Testing 2.3.51 Radio Noise Testing 2.3.52 Short Circuit Testing 2.3.53 Lightning Strike Testing 2.3.54 Ultra High Voltage AC & DC Testing Field Testing: 2.5.64 Ambient Temperature 2.5.65 Tension, Sag, and Clearance 2.5.66 Conductor Temperature 2.5.67 Electric Current 2.5.68 Wind Speed and Direction 2.5.69 Solar Radiation 2.5.70 Rainfall 2.5.71 Ice Buildup 2.5.72 Splice Resistance 2.5.73 Infrared Measurements 2.5.74 Corona Observations 2.5.75 Electric and Magnetic Fields 2.5.76 Wind and Ice Load Measurements 2.5.77 Vibration Monitoring Konduktor ACCC telah mengalami pengujian extensif 2.5.78 Typhoon Test Copyright January 2020 CTC Global All Rights Reserved 7
  • 8. Perbandingan ACSR dengan ACCC ® ACSR Conductor • Berumur > 100 tahun • 95+% transmisi menggunakan ACSR, murah dan memiliki history yang panjang. • Temperatur operasi (<95C) dan memiliki sag yang besar bila di operasikan pada suhu lebih tinggi ACCC® Conductor • Teknologi ini dikembangkan dari tahun 2001 sampai 2005 • Terpasang pada tahun 2006 • Hybrid composite core ringan dan lebih kuat dibandingkan baja, memungkinkan 28% aluminium tanpa menambah berat konduktor • Beroperasi max temperatur 175 o C dan memiliki sag rendah Manfaat ACCC® Conductor : • Peningkatan Kapasitas • Kerugian jalur berkurang • Biaya proyek rendah • Meningkatkan kehandalan sistem Copyright January 2020 CTC Global All Rights Reserved 8
  • 9. Keuntungan Konduktor ACCC ® Kekuatan Besar & Sag Rendah Jarak span lebih panjang Peningkatan kapasitas listrik Kerugian jalur berkurang Penurunan konsumsi bahan bakar & emisi Keandalan terbukti pada lebih dari 275 lokasi Copyright January 2020 CTC Global All Rights Reserved 9
  • 10. Ukuran Konduktor ACCC ® ACCC® Conductor Diameter Core Diameter Weight Core Rated Strength Conductor Rated DC @ 20°C AC @ 25°CAC @ 75°C AC Ampacity Strength Size (kcmil) (mm²) (in) (mm) (in) (mm) (lb/kft) (kg/km) (lbf) (kN) (lbf) (kN) (ohm/km) (ohm/km) (ohm/km) 75°C 180°C Helsinki 303 153.7 0.616 15.65 0.235 5.97 322 479 13,580 60.4 15,500 69.1 0.1861 0.19011 0.22766 479 802 Linnet 431 218.4 0.720 18.29 0.235 5.97 441 656 13,580 60.4 16,300 72.7 0.12801 0.13120 0.15774 599 1,007 Oriole 438 221.9 0.741 18.82 0.280 7.11 463 689 19,290 85.8 22,000 97.9 0.12609 0.12867 0.15489 609 1,024 Reykjavik 447 226.3 0.741 18.82 0.280 7.11 472 703 19,290 85.8 22,100 98.5 0.12630 0.12669 0.15171 615 1,039 Copenhagen 440 223.0 0.720 18.29 0.235 5.97 450 670 13,580 60.4 16,400 72.9 0.1279 0.13090 0.15675 601 1,013 Glasgow 473 239.8 0.769 19.53 0.305 7.75 504 750 22,880 101.8 25,900 115.3 0.11690 0.12197 0.14606 633 1,070 Casablanca 546 276.8 0.807 20.50 0.280 7.11 565 840 19,290 85.8 22,700 101.1 0.10130 0.10587 0.12677 688 1,166 Hawk 611 309.6 0.857 21.77 0.280 7.11 625 930 19,290 85.8 23,200 103.2 0.90300 0.09291 0.11161 745 1,264 Oslo 627 317.7 0.882 22.40 0.345 8.76 666 992 29,260 130.2 33,300 148.1 0.08820 0.09219 0.11041 755 1,284 Lisbon 629 318.7 0.857 21.78 0.280 7.11 643 957 19,290 85.8 23,300 103.7 0.0896 0.09199 0.11016 750 1,275 Dove 713 361.3 0.927 23.55 0.305 7.75 728 1083 22,880 101.8 27,500 122.3 0.07738 0.07986 0.09583 821 1,398 Amsterdam 733 371.4 0.927 23.55 0.305 7.75 748 1113 22,880 101.8 27,600 122.7 0.0769 0.07911 0.09474 826 1,408 Grosbeak 816 413.5 0.990 25.15 0.320 8.13 832 1238 25,190 112.1 30,400 135.2 0.06761 0.07005 0.08392 892 1,527 Brussels 839 425.3 0.990 25.14 0.320 8.13 857 1275 25,190 112.1 30,600 136.1 0.0673 0.06941 0.08312 897 1,534 Stockholm 913 462.7 1.039 26.40 0.345 8.76 944 1406 29,260 130.2 35,200 156.5 0.0612 0.06324 0.07573 952 1,632 Warsaw 1016 514.8 1.091 27.72 0.345 8.76 1034 1539 29,260 130.2 35,800 159.1 0.0556 0.05764 0.06902 1,010 1,736 Ampacity values based on altitude of sun at 90˚ deg, 25˚ deg C ambient temperature, 0.5 Solar Absorbtivity, 0.5 Emissivity, 2 ft/sec wind and 96 Watt/ft^2, at corresponding surface temperatures. The information contained herein is offered in good faith and believed to be accurate. The final design of a shaped wire compact conductor is contingent upon several factors, such as layer diameter, wire width, and wire thickness. The actual configuration of a given size may vary between manufacturers. This may result in a slight variation. However, although the information is mathematically derived, normal dimensional tolerances in actual cable construction may lead to differences between the indicated values. Copyright January 2020 CTC Global All Rights Reserved 10
  • 11. Ukuran Konduktor ACCC ® (lanjutan) ACCC® Conductor Diameter Core Diameter Weight Core Rated Strength Conductor Rated DC @ 20°CAC @ 25°CAC @ 75°C AC Ampacity Strength Size (kcmil) (mm²) (in) (mm) (in) (mm) (lb/kft) (kg/km) (lbf) (kN) (lbf) (kN) (ohm/km) (ohm/km) (ohm/km) 75°C 180°C Drake 1020 516.8 1.108 28.14 0.375 9.53 1047 1558 34,570 153.8 41,100 182.8 0.05409 0.05640 0.06749 1,025 1,765 Dublin 1043 528.5 1.108 28.15 0.375 9.53 1072 1595 34,570 153.8 41,300 183.5 0.05410 0.05608 0.06715 1,028 1,769 Hamburg 1092 553.3 1.127 28.62 0.345 8.76 1106 1646 29,260 130.2 36,300 161.3 0.05170 0.05375 0.06436 1,054 1,816 Milan 1134 574.6 1.146 29.10 0.345 8.76 1146 1705 29,260 130.2 36,500 162.5 0.04880 0.05186 0.06210 1,078 1,859 Rome 1183 599.4 1.177 29.89 0.375 9.53 1205 1793 34,570 153.8 42,200 187.5 0.04680 0.04981 0.05965 1,108 1,913 Cardinal 1222 619.2 1.196 30.38 0.345 8.76 1228 1828 29,260 130.2 37,100 165.0 0.04535 0.04793 0.05712 1,137 1,971 Vienna 1255 635.9 1.198 30.42 0.345 8.76 1259 1873 29,260 130.2 37,300 165.9 0.04410 0.04700 0.05627 1,146 1,981 Budapest 1332 674.9 1.240 31.50 0.375 9.53 1346 2003 34,570 153.8 43,100 191.8 0.04160 0.04447 0.05325 1,189 2,059 Prague 1377 697.7 1.251 31.77 0.345 8.76 1377 2050 29,260 130.2 38,100 169.4 0.04030 0.04326 0.05180 1,208 2,093 Munich 1461 740.3 1.293 32.85 0.375 9.53 1471 2189 34,570 153.8 44,000 195.5 0.03800 0.04094 0.04902 1,253 2,175 London 1512 766.1 1.315 33.40 0.385 9.78 1523 2266 36,440 162.1 46,100 205.2 0.03660 0.03954 0.04736 1,280 2,224 Bittern 1572 796.5 1.345 34.16 0.345 8.76 1555 2314 29,260 130.2 39,300 174.8 0.03517 0.03815 0.04511 1,320 2,315 Paris 1620 820.9 1.345 34.17 0.345 8.76 1603 2385 29,260 130.2 39,700 176.4 0.03420 0.03721 0.04456 1,328 2,310 Antwerp 1879 952.1 1.451 36.85 0.385 9.78 1867 2778 36,440 162.1 48,500 215.7 0.02950 0.03251 0.03893 1,449 2,532 Lapwing 1965 995.7 1.504 38.20 0.385 9.78 1961 2918 36,440 162.1 49,000 218.0 0.02836 0.03169 0.03720 1,497 2,655 Berlin 2004 1015.4 1.504 38.20 0.415 10.54 2000 2977 42,340 188.3 55,200 245.5 0.02760 0.03058 0.03661 1,509 2,642 Madrid 2020 1023.5 1.504 38.20 0.385 9.78 1999 2974 36,440 162.1 49,400 219.7 0.02740 0.03044 0.03645 1,512 2,647 Chukar 2242 1136.0 1.602 40.69 0.395 10.03 2226 3312 38,360 170.6 52,700 234.5 0.02486 0.02851 0.03323 1,610 2,882 Bluebird 2726 1381.5 1.762 44.75 0.415 10.54 2696 4012 42,340 188.3 59,800 266.0 0.02044 0.02461 0.02835 1,788 3,246 Ampacity values based on altitude of sun at 90˚ deg, 25˚ deg C ambient temperature, 0.5 Solar Absorbtivity, 0.5 Emissivity, 2 ft/sec wind and 96 Watt/ft^2, at corresponding surface temperatures. The information contained herein is offered in good faith and believed to be accurate. The final design of a shaped wire compact conductor is contingent upon several factors, such as layer diameter, wire width, and wire thickness. The actual configuration of a given size may vary between manufacturers. This may result in a slight variation. However, although the information is mathematically derived, normal dimensional tolerances in actual cable construction may lead to differences between the indicated values. Copyright January 2020 CTC Global All Rights Reserved 11
  • 12. CTC Global Corporation ACCC® Conductor Transportation, Handling, Storage Training and Hardware Installation Copyright January 2020 CTC Global All Rights Reserved 12
  • 13. Penyimpanan Konduktor ACCC® Hal – hal yang harus diperhatian dalam penyimpanan Konduktor ACCC : 1. Simpan haspel (drum) sedemikian rupa sehingga haspel / drum tidak tergenang air dan pastikan konduktor dalam kondisi baik sampai proses penarikan/stringing dilaksanakan. Copyright January 2020 CTC Global All Rights Reserved 13
  • 14. Penyimpanan Konduktor ACCC® 2. Haspel (drum) konduktor ACCC dikirim dari pabrikan di lengkap pelindung pada konduktor dan sisi luar kayu di ikat mengunakan plat. Copyright January 2020 CTC Global All Rights Reserved 14
  • 15. Penyimpanan Konduktor ACCC® 3. Tanda identifikasi atau informasi jangan sampai hilang sampai konduktor digunakan. Copyright January 2020 CTC Global All Rights Reserved 15
  • 16. Pengiriman dan Penanganan Konduktor ACCC® Konduktor ACCC harus dikontrol dengan baik selama proses pemuatan, pembongkaran, dan penarikan konduktor ACCC 1. Haspel (drum) konduktor harus diletakkan secara vertikal, baik pada saat pengiriman maupun pada saat sudah di site (lokasi). Copyright January 2020 CTC Global All Rights Reserved 16
  • 17. Pengiriman dan Penanganan Konduktor ACCC® 2. Peralatan yang tersedia untuk menangani konduktor ACCC harus memiliki kapasitas yang sesuai untuk menghindari kerusakan. Copyright January 2020 CTC Global All Rights Reserved 17
  • 18. Pengiriman dan Penanganan Konduktor ACCC® 3. Apabila menggunakan crane harus memakai sprader bar (besi)/crane seling dengan panjang 2-3 meter. Copyright January 2020 CTC Global All Rights Reserved 18
  • 19. Pengiriman dan Penanganan Konduktor ACCC® 4. Mengangkut haspel memakai forklift harus melakukan dari samping sehingga berat haspel tertumpu pada flange. Copyright January 2020 CTC Global All Rights Reserved 19
  • 20. Pengiriman dan Penanganan Konduktor ACCC® 5. Pastikan pada saat pembongkaran konduktor tidak dijatuhkan dari truk/kontainer karena dapat menyebabkan konduktor cacat atau rusak. Copyright January 2020 CTC Global All Rights Reserved 20
  • 21. Pengiriman dan Penanganan Konduktor ACCC® ✓ Jangan pernah tekuk konduktor ACCC lebih kecil dari diameter lengkung minimum. ✓ Penting untuk tidak menekuk dengan tajam ACCC Conductor. Meskipun composite carbon & glass fiber pada core ACCC mempunyai kekuatan dan ketahanan tinggi, tetapi keseluruhan konduktor sama sekali tidak boleh ditekuk secara tajam. Copyright January 2020 CTC Global All Rights Reserved 21
  • 22. Pedoman Penanganan Umum Konduktor ACCC® ACCC Conductor tidak boleh ditekuk dengan sudut yang tajam, apalagi dengan diameter lengkungan yang kecil. Gambarsebelah adalah contoh dimana kemungkinan bisa terjadi lengkungan yang terlalu kecil. Harus hati-hati dan waspada agar hal ini tidak terjadi selama proses stringing. Copyright January 2020 CTC Global All Rights Reserved 22
  • 23. Pedoman Penanganan Umum Konduktor ACCC® Bila sudut konduktor pada tikungan besar (lebih dari 20 derajat) gunakan roller yang lebih besar atau gunakan tandem roller. Bila sudut besar sekali, dapat digunakan double tandem roller. Copyright January 2020 CTC Global All Rights Reserved 23
  • 24. Pedoman Penanganan Umum Konduktor ACCC® ✓ Jangan menekan konduktor kesatu sisi seperti pada gambar ini. Konduktor harus bisa meluncur bebas diatas montage roll. ✓ Jika konduktor diperlakukan seperti ini, maka “birdcaging” (konduktor mekar seperti kandang burung) bisa terjadi diarah tensioner, atau konduktor bisa rusak. Copyright January 2020 CTC Global All Rights Reserved 24 X
  • 25. Pedoman Penanganan Umum Konduktor ACCC® ❖ Hindari menyeret konduktor hingga tergesek oleh tanah atau material yang tajam ❖ Hindari menarik konduktor ke tower tanpa memberikan ikatan – ikatan di belakang came along
  • 26. Copyright January 2020 CTC Global All Rights Reserved 25
  • 27. Pedoman Penanganan Umum Konduktor ACCC® • Sangat penting bahwa jalan atau rel KA dilindungi oleh struktur sementara sehingga konduktor tidak terkena mobil atau peralatan bergerak lainnya. • Juga penting bahwa semua saluran listrik TT, TM atau TR di lindungi struktur. • Jangan sampai konduktor bergesek dengan ujung dari struktur. Copyright January 2020 CTC Global All Rights Reserved 26
  • 28. Pedoman Penanganan Umum Konduktor ACCC® ❑ Karena aluminium strand ACCC lunak, tindakan pencegahan tambahan perlu dilakukan untuk menghindari kerusakan pada permukaan. ❑ Bila konduktor akan diturunkan, letakkan kertas atau material lain yang bersih diatas tanah untuk menjaga agar konduktor tidak menyentuh tanah. ❑ Yakinkan bahwa tidak ada batu atau barang-barang lain yang dapat merusak konduktor. Copyright January 2020 CTC Global All Rights Reserved 27
  • 29. Pedoman Penanganan Umum Konduktor ACCC® ✓ Tarikan maksimum stringing – aturan umum untuk Konduktor ACCC ✓ Tegangan waktu stringing dianjurkan tidak lebih dari 10% RTS konduktor ✓ Berapa lama konduktor boleh ditinggal duduk pada roller sebelum clamping? ✓ IEEE 524 merekomendasikan bahwa konduktor sudah di sagging dan clamping dalam jangka waktu 24 – 48 jam setelah penarikan. ✓ IEEE 524 merekomendasikan bahwa maksimum waktu yang diperbolehkan bagi konduktor untuk tetap duduk di roller (dari saat penarikan sampai clamping) tidak lebih dari 72 jam. ✓ Bila konduktor akan di sagging pada hari yang sama, maka tambahkan 2% atau minus 9 derajat untuk mengatasi “creep” yang akan terjadi dalam satu malam. Semua konduktor mempunyai creep, tapi Core (Composite Carbon) ACCC lebih kecil creep nya dibanding yang lain. Copyright January 2020 CTC Global All Rights Reserved 28
  • 30. Penanganan Konduktor ACCC® Tirfor Came Along Copyright January 2020 CTC Global All Rights Reserved 29
  • 31. Penanganan Konduktor ACCC® Tirfor Came Along Copyright January 2020 CTC Global All Rights Reserved 30
  • 32. Penanganan Konduktor ACCC® Copyright January 2020 CTC Global All Rights Reserved 31
  • 33. Penanganan Konduktor ACCC® Tower 47D Tower 47C Tower 47B Tower 47A Konduktor ACCC Copyright January 2020 CTC Global All Rights Reserved 32
  • 34. Penanganan Konduktor ACCC® Tirfor Came Along Tower 47D Tower 47C Tower 47B Tower 47A Konduktor ACCC Copyright January 2020 CTC Global All Rights Reserved 33
  • 35. Penanganan Konduktor ACCC® Copyright January 2020 CTC Global All Rights Reserved 34
  • 36. Penanganan Konduktor ACCC® Copyright January 2020 CTC Global All Rights Reserved 35
  • 37. Penanganan Konduktor ACCC® Splice Nylon Copyright January 2020 CTC Global All Rights Reserved 36
  • 38. Penanganan Konduktor ACCC® Copyright January 2020 CTC Global All Rights Reserved 37
  • 39. Penanganan Konduktor ACCC® Copyright January 2020 CTC Global All Rights Reserved 38
  • 40. Penanganan Konduktor ACCC® Konduktor batch 1 untuk proyek ini ternyata mempunyai GAP antara core dengan lapisan dalam aluminium strand. Copyright January 2020 CTC Global All Rights Reserved 39
  • 41. Penanganan Konduktor ACCC® Simulasi Konduktor ACCC menggunakan Deadend Clamps Copyright January 2020 CTC Global All Rights Reserved 40
  • 42. Penanganan Konduktor ACCC® Bila baut – baut pada alat bantu untuk menarik konduktor dikencangkan dengan berlebihan maka core bisa pecah karena tergencet dari 2 arah saja. Copyright January 2020 CTC Global All Rights Reserved 41
  • 43. Penanganan Konduktor ACCC® Copyright January 2020 CTC Global All Rights Reserved 42
  • 44. Penanganan Konduktor ACCC® Copyright January 2020 CTC Global All Rights Reserved 43
  • 45. Penanganan Konduktor ACCC® Copyright January 2020 CTC Global All Rights Reserved 44
  • 46. CTC Global Corporation ACCC® Conductor Tools and Equipment Training Copyright January 2020 CTC Global All Rights Reserved 45
  • 47. Tensioner Tensioner adalah peralatan yang digunakan untuk menahan konduktor pada proses stringing / penarikan konduktor untuk pemasangan baru atau rekonduktoring. Spesifikasi : ❑ Sistem Hydraulic ❑ Diameter Bull-wheel sesuai “Daftar Sheeve Size ACCC” ❑ Diameter alur tidak boleh lebih kecil 0.55 x Diameter konduktor ACCC ❑ Minimum bull-wheel memiliki 4 alur ❑ Alur Bull-wheel tidak berbentuk “V” ❑ Memiliki kekuatan minimum 4.5 ton ❑ Bull-wheel dilapisi dengan nylon atau urethane ❑ Bull-wheel double ❑ Memiliki sistem pengerak dan pengereman hydraulic
  • 48. Copyright January 2020 CTC Global All Rights Reserved 46
  • 49. Tensioner Copyright January 2020 CTC Global All Rights Reserved 47
  • 50. Drum Stand & Brake Drum Stand adalah alat yang digunakan untuk menempatkan drum konduktor agar bisa bergerak dengan stabil. Spesifikasi : ❑ Memiliki kekuatan minimum 5 ton ❑ Terdapat disc brake atau hydraulic brake Brake/ Rem adalah alat yang digunakan Untuk menggatur putaran drum Konduktor agar selalu stabil.
  • 51. Copyright January 2020 CTC Global All Rights Reserved 48
  • 52. Drum Stand & Brake Copyright January 2020 CTC Global All Rights Reserved 49
  • 53. Payout Reel Brakes Hydraulic ✓ Disc ✓ Copyright January 2020 CTC Global All Rights Reserved 50
  • 54. Roller Grounding & Stick Grounding Roller Grounding adalah alat yang digunakan untuk pengaman bila terjadi induksi pada proses stringing / penarikan konduktor. Alat ini biasanya dipasang di depan tensioner dan puller. Spesifikasi : ❑ Bahan terbuat dari aluminium ❑ Roda yang digunakan harus halus ❑ Kabel grounding diameter 50 mm2 ❑ Stick harus berbahan fiber glass ❑ Grounding rod harus cukup
  • 55. Copyright January 2020 CTC Global All Rights Reserved 51
  • 56. Roller / Pulley / Travelers Roller adalah alat yang digunakan untuk tempat bergeraknya konduktor , dipasang pada setiap tower. Spesifikasi : ❑ Bahan terbuat dari polyurethane/nylon atau Aluminium ❑ Diameter (Ds) minimum sesuai “Daftar Sheeve Size ACCC” ❑ Memiliki kedalaman alur 1.25 x diameter konduktor ACCC ❑ Memiliki jari – jari alur minimum 0.55 x diameter konduktor ACCC ❑ Bisa dalam konfigurasi double roller atau lebih ❑ Dapat juga dipasang secara tandem 2 atau lebih untuk mengatasi sudut yang besar
  • 57. Copyright January 2020 CTC Global All Rights Reserved 52
  • 58. Working Diameter / Diameter Kerja ✓ X Copyright January 2020 CTC Global All Rights Reserved 53
  • 59. Sheeve Sizes ACCC ® ACCC Core Conductor Sheave Size Tensioner Bull- Diameter Working Wheel mm inches International ASTM Diameter Silvassa, Helsinki, 5.97 0.235 Copenhagen, Rovinj, Linnet, Oceanside. 511 mm (20.1”) 1000 mm (39.4") Gdansk 7.11 0.280 Zadar, Reykjavik, Oriole, Laredo, Hawk 610 mm (24") Casablanca, Lisbon. 7.75 0.305 Jaipur, Glasgow, Waco, Dove 650 mm (25.6") Amsterdam, Cordoba 8.13 0.32 Brussels Grosbeak 710 mm (28") 1200 mm (48") Oslo, Stockholm, Warsaw, Irving, Lubbock, Galveston, Plano, 8.76 0.345 Hamburg, Milan, Vienna, Corpus Christi, Cardinal, Prague, Paris. El Paso, Bittern. Leipzig, Dublin, Kolkata, Drake, Arlington, Fort 800 mm (31.5") 9.53 0.375 Rome, Budapest, worth, Beaumont Mumbai, Munich. (Dhaka) 9.78 0.385 Londan, Antwerp, Madrid San Antonio, Dallas, Lapwing. 1500 mm (60") 10.03 0.395 Chukar, Chukar II. Monte Carlo, 25mm, Curlew, Houston, Falcon, 1000 mm (39") 10.54 0.415 Warwick, Bordeaux, Bluebird. Berlin, Athens Copyright January 2020 CTC Global All Rights Reserved 54
  • 60. Sheeve Sizes ACCC ® X ✓ Copyright January 2020 CTC Global All Rights Reserved 55
  • 61. Sheeve Sizes ACCC ® Copyright January 2020 CTC Global All Rights Reserved 56
  • 62. Tandem Sheeve ACCC ® Copyright January 2020 CTC Global All Rights Reserved 57
  • 63. Multiple Roller Arrays Copyright January 2020 CTC Global All Rights Reserved 58
  • 64. Camealong / Pulling Grip Came along adalah peralatan yang digunakan untuk memegang atau menahan konduktor. Spesifikasi : ❑ Memiliki kekuatan 7.5 ton ❑ Memiliki panjang rahang 254 mm ❑ Liner tidak bergigi dan halus (Sesuaikan dengan ukuran konduktor.
  • 65. Copyright January 2020 CTC Global All Rights Reserved 59
  • 66. Camealong / Pulling Grip Pemeriksaan Kekuatan Camealong Camealong rusak pada saat test 0.5 ton • Yakinkan bahwa type dan configurasi grip akan mampu memegang konduktor lebih kuat dari tegangan yang diperkirakan terjadi pada waktu melakukan sagging. Lakukan test yang diperlukan. Copyright January 2020 CTC Global All Rights Reserved 60
  • 67. Pemasangan Bugs & Pulling Sock Pemasangan Core Retainer / Bugs Bugs / Core Retainer Bugs adalah alat yang dipasang pada setiap ujung konduktor ACCC pada setiap stringing atau penarikan konduktor. Tujuan dari pemasangan bugs adalah untuk menahan core agar tidak slip terhadap aluminium konduktor. Spesifikasi : ❑ Desain dan supply dari CTC Global
  • 68. Copyright January 2020 CTC Global All Rights Reserved 61
  • 69. Pemasangan Bugs & Pulling Sock Video Pemasangan Core Retainer / Bugs Copyright January 2020 CTC Global All Rights Reserved 62
  • 70. Pemasangan Bugs & Pulling Sock Pemasangan Pulling Sock / Sustrum Pulling sock adalah peralatan digunakan untuk sambungan sementara pada saat proses stringing atau penarikan konduktor. Ukuran pulling sock haru disesuaikan dengan konduktor yang akan di tarik. Spesifikasi : ❑ Bahan terbuat dari sling baja ❑ Memiliki rating bervariasi sesuai kebutuhan ❑ Memiliki panjang minimum 1.5 meter
  • 71. Copyright January 2020 CTC Global All Rights Reserved 63
  • 72. Pemasangan Bugs & Pulling Sock Pemasangan Pulling Sock / Sustrum Copyright January 2020 CTC Global All Rights Reserved 64
  • 73. Pemasangan Bugs & Pulling Sock Pemasangan Pulling Sock / Sustrum ✓ Copyright January 2020 CTC Global All Rights Reserved 65
  • 74. Swivel, Connector & Shackel Swivel adalah peralatan dipasang antara sustrum dengan sling pada proses stringing atau penarikan konduktor untuk menghilangkan putaran yang terjadi. Spesifikasi : ❑ Bahan terbuat dari baja ❑ Memiliki rating bervariasi sesuai kebutuhan ❑ Minimum Kapasitas 5 ton Connector & Shackle adalah peralatan tambahan yang digunakan pada proses stringing atau penarikan konduktor. Spesifikasi : ❑ Bahan terbuat dari besi ❑ Memiliki ukuran dan rating tertentu sesuai kebutuhan ❑ Minimum kapasitas 5 ton
  • 75. Copyright January 2020 CTC Global All Rights Reserved 66
  • 76. Swivel, Connector & Shackel Swivel Connector Shackle Copyright January 2020 CTC Global All Rights Reserved 67
  • 77. Dynamometer & Saging Scope Dynamometer digunakan pada saat sagging dilaksanakan untuk memastikan bahwa tarikan yang akan diberikan telah sesuai dengan ketentuan yang telah diatur. Dynamometer yang dipakai bisa menggunakan jenis manual atau digital yang memiliki rating kapasitas yang cukup minimum 5 ton. Dynamometer harus ditera sebelum dipergunakan. Copyright January 2020 CTC Global All Rights Reserved 68
  • 78. Dynamometer & Saging Scope Sag scope digunakan untuk memastikan bahwa pada saat proses sagging yang dilaksanakan telah sesuai dengan ketentuan yang telah disetujui. Sag scope biasanya dipakai untuk melihat sagging (andongan) pada span terpanjang pada section dimana akan dilaksanakan sagging. Copyright January 2020 CTC Global All Rights Reserved 69
  • 79. Bundled Conductors - Saging Sag adjustment link Copyright January 2020 CTC Global All Rights Reserved 70
  • 80. Hydraulic Compression Tools & Dies Mesin press adalah alat yang digunakan pada setiap pemasangan deadend dan splice (joint) untuk menyatukan antara aluminium konduktor dengan hardware deadend mapupun splice (joint). Spesifikasi : ❑ Memiliki tekanan 700 bar atau 10.000 psi ❑ Kapasitas hydraulic head 60 ton (ACCC) atau 100 ton 100 Ton 60 Ton
  • 81. Copyright January 2020 CTC Global All Rights Reserved 71
  • 82. Spreader Bar & Tandem Spreader Bar adalah alat yang digunakan pada setiap mengangkat haspel / drum agar flange haspel tidak terdorong ke dalam Spesifikasi : ❑ Terbuat dari besi ❑ Memiliki panjang 2 – 3 meter ❑ Mampu mengangkat beban 5 ton Tandem adalah alat berbentuk segitiga yang digunakan untuk menyatukan 2 buah roller menjadi tandem pada tower yang mempunyai sudut vertikal / horizontal tajam. Spesifikasi : ❑ Terbuat dari besi ❑ Memiliki panjang 2 – 3 meter
  • 83. Copyright January 2020 CTC Global All Rights Reserved 72
  • 84. Spreader Bar & Tandem Spreader Bar Tandem Roller Copyright January 2020 CTC Global All Rights Reserved 73
  • 85. Tandem Roller Copyright January 2020 CTC Global All Rights Reserved 74
  • 86. Bundled Conductors — Stringing Running Board Gator Head Board 4 Bundle Block (with center sheave for pilot line) Twin Bundle Block (with center sheave for pilot line) Copyright January 2020 CTC Global All Rights Reserved 75
  • 87. Trolley / Line Car Cable buggie / Line Car adalah alat yang digunakan pada saat akan memasang spacer biasanya terbuat dari bahan aluminium / besi. Spesifikasi : ❑ Terbuat dari aluminium / besi ❑ Roda yang terbuat dari nylon, aluminium atau neoprene ❑ Kapasitas sesuai dengan kebutuhan
  • 88. Copyright January 2020 CTC Global All Rights Reserved 76
  • 89. Tangga / Tower Ladder Tawer ladder adalah alat bantu yang digunakan untuk memasang deadend atau splice (joint) sehingga pekerja dapat bekerja secara mudah, efektif, dan aman. Copyright January 2020 CTC Global All Rights Reserved 77
  • 90. Peralatan lain - lain Kunci Inggris • Cukup Besar untuk memutar steel eye pada Deadend atau Coupling pada Joint atau Bug dengan torsi yang cukup • Panjang yang dianjurkan minim 380 mm. • Dibutuhkan dua unit Cable Trimmer dan Gergaji Besi • Cable trimmers harus tajam dan dalam kondisi baik. Cable Trimmer dengan kontrol kedalaman potong yang baik sangat diperlukan. Bila pemotongan terlalu dalam dapat melukai core. • Gergaji besi mempunyai gigi yang halus. Final cut ACCC konduktor dilakukan dengan memakai gergaji gigi halus ini. Copyright January 2020 CTC Global All Rights Reserved 78
  • 91. CTC Global Corporation ACCC® Conductor Stringing & Errection Training Copyright January 2020 CTC Global All Rights Reserved 79
  • 92. Metode Stringing 1. Metode Layout Metode ini biasanya dilakukan dengan cara mengelar terlebih dahulu konduktor / kabel diatas tanah, dengan menggunakan bantuan winch atau dengan tenaga manusia. Metode ini sering disebut juga dengan penarikan atau stringing manual. Copyright January 2020 CTC Global All Rights Reserved 80
  • 93. Metode Stringing 2. Metode Tension Dengan Metode ini, konduktor diberikan gaya tarik supaya pada saat proses penarikan (Stringing) konduktor tidak menyentuh tanah, rumah, pohon, serta jaringan TM yang dapat penyebabkan permukaan konduktor tergores atau luka. Peralatan yang digunakan Tensioner dan Puller sebagai alat bantu untuk proses Penarikan (Stringing). Copyright January 2020 CTC Global All Rights Reserved 81
  • 94. Metode Stringing Layout Proses Penarikan / Stringing Copyright January 2020 CTC Global All Rights Reserved 82
  • 95. Set Up Tensioner & Drum Roller pertama Bullwheel Tensioner berjarak Jarak antara drum dan sebesar sebanding 3:1 dengan tinggi roller tensioner 15 m – 23 m. mungkin yang pertama. mpak Atas Pastikan bahwa Drum, Tensioner, dan Roller pertama dalam garis lurus. Copyright January 2020 CTC Global All Rights Reserved 83
  • 96. Set Up Tensioner & Drum Alternatve # 1 Apa yang harus dilakukan apabila kondisi lahan tidak memenuhi jarak ideal pada tensioner ??? ❑ Perbesar roller sehingga sudut lengkung konduktor menjadi tidak tajam
  • 97. Copyright January 2020 CTC Global All Rights Reserved 84
  • 98. Set Up Tensioner & Drum Alternatve # 2 ❑ Pasang tandem roller
  • 99. Copyright January 2020 CTC Global All Rights Reserved 85
  • 100. Set Up Tensioner & Drum Alternatve # 3 ❑ Turunkan roller pertama ke body tower Copyright January 2020 CTC Global All Rights Reserved 86
  • 101. Set Up Tensioner & Drum Alternatve # 4 15m Front Feed Tensioner(s) Copyright January 2020 CTC Global All Rights Reserved 87
  • 102. Set Up Tensioner & Drum ✓ Banyak tensioner yang digunakan mempunyai sudut masuk ke bullwheel / capstan yang terlalu tajam.
  • 103. Copyright January 2020 CTC Global All Rights Reserved 88
  • 104. Set Up Tensioner & Drum Copyright January 2020 CTC Global All Rights Reserved 89
  • 105. Set Up Tensioner & Drum Angkur Pada Mesin dan Haspel (Drum) Copyright January 2020 CTC Global All Rights Reserved 90
  • 106. Set Up Tensioner & Drum Akibat tidak diangkur Pada Mesin dan Haspel (Drum) Copyright January 2020 CTC Global All Rights Reserved 91
  • 107. Set Up Tensioner & Drum Reel Arbor Hole and Let-off Equipment • Pastikan bahwa reel stand yang digunakan sesuai dengan haspel. Ukuran Poros/mandrel harus sesuai dengan lobang pada haspel. • Gambar menunjukkan poros yang digunakan terlalu kecil sehingga haspel akan bergerak keatas kebawah kian kemari. Ini menyebabkan kontrol atas tegangan konduktor yang masuk ke bulwheel /capstan tensioner menjadi sulit. Copyright January 2020 CTC Global All Rights Reserved 92
  • 108. Set Up Tensioner & Drum Brake Tension pada Drum Stand ✓ Penting untuk betul2 memperhatikan “brake tension control” pada haspel konduktor. ✓ Dianjurkan untuk menugaskan satu orang untuk mengawasi dan mengatur “brake tension”. ✓ Konduktor akan meluncur dengan lancar tanpa sentakan2 bila “brake control” yang tepat digunakan. ✓ Paling baik adalah bila pada drumstand ada hydraulic motor yang bekerja secara sinkron dengan tensioner.
  • 109. Copyright January 2020 CTC Global All Rights Reserved 93
  • 110. Dead End Assembly Copyright January 2020 CTC Global All Rights Reserved 94
  • 111. Peralatan Pemasangan Dead End Copyright January 2020 CTC Global All Rights Reserved 95
  • 112. Pemasangan Dead End ACCC® Prosedure Pemasangan Deadend Copyright January 2020 CTC Global All Rights Reserved 96
  • 113. Pemasangan Dead End ACCC® Pemasangan ACCC ® Compression Deadend • Pemotong Kabel standard dapat digunakan untuk pemotongan awal konduktor. • Karena tidak ada steel core didalam Konduktor ACCC, maka konduktor akan terpotong dengan lebih mudah dibanding ACSR. Copyright January 2020 CTC Global All Rights Reserved 97
  • 114. Pemasangan Dead End ACCC® Final Cut Sebelum Pasang Deadend • Gunakan gergaji tangan untuk pemotongan final • Gergaji memastikan ujung core simetris untuk pemasangan dalam collet. Copyright January 2020 CTC Global All Rights Reserved 98
  • 115. Pemasangan Dead End ACCC® Deadend Body dan Selongsong Dalam • Setelah pemotongan dengan gergaji, dorong ke konduktor - pertama inner sleeve (selongsong dalam) dan kemudian deadend body. • Ujung yang tirus (tapered) dari selongsong dalam dan ujung yang berlawanan dengan jumper pad di deadend body yang juga tirus harus masuk lebih dahulu. Copyright January 2020 CTC Global All Rights Reserved 99
  • 116. Pemasangan Dead End ACCC® Menandai Konduktor untuk Membuka Core • Buat tanda pada konduktor dengan jarak sepanjang housing + 50 mm dari ujung konduktor. • Dua atau tiga lapis aluminium akan dibuang mulai dari tanda sampai ke ujung konduktor. Copyright January 2020 CTC Global All Rights Reserved 100
  • 117. Pemasangan Dead End ACCC® Membuang Strand Aluminum dari Core • Dua atau tiga lapis strand aluminium dibuang sehingga core tampak. • Sebelum memotong strand aluminium, pastikan strands sudah diikat memakai klem, kawat atau tape. Gunakan Strand Cutter atau gergaji untuk membuang dua atau tiga lapis strand yang melilit core. Catatan : Core jangan tergores/terpotong alat potong. Bila core tergores, kita harus mulai lagi dari awal. Copyright January 2020 CTC Global All Rights Copyright January 2020 CTC Global All Rights Reserved Reserved 101
  • 118. Pemasangan Dead End ACCC® Membuang Strand Aluminum dari Core ▪ Jangan sampai core tergores alat potong. ▪ Lapisan terbawah aluminium strand dipotong hanya sebagian. ▪ Kawat aluminium dengan mudah akan putus bila ditekuk bolak balik. Copyright January 2020 CTC Global All Rights Reserved 102
  • 119. Pemasangan Dead End ACCC® Membersihkan Core • Bersihkan/lap core dengan kain bersih. • Perlahan-lahan gunakan amplas yang tersedia dalam dead end kit untuk menghilangkan kilap pada lapisan luar core. • Bersihkan kembali core menggunakan lap bersih. Copyright January 2020 CTC Global All Rights Reserved 103
  • 120. Pemasangan Dead End ACCC® Memasang Collet dan Collet Housing • Selongsongkan collet housing pada core. Ujung dengan lubang lebih kecil masuk lebih dulu. • Kemudian dorong collet (wedge) dengan bagian yang kecil lebih dulu ke housing. • Ujung dari core harusnya muncul dibelakang collet antara 1/8” sampai maksimum 1/4” (3 mm sampai 6 mm) Copyright January 2020 CTC Global All Rights Reserved 104
  • 121. Pemasangan Dead End ACCC® Memasang Deadend Eye • Masukkan ulir deadend eye kedalam collet housing dan putar dengan tangan untuk mengencangkan. • Stabilkan dan suport collet housing pada saat eyebolt dikencangkan. • Pastikan untuk menjaga agar collet housing dan konduktor tetap dalam satu garis lurus antara satu dengan lainnya. Copyright January 2020 CTC Global All Rights Reserved 105
  • 122. Pemasangan Dead End ACCC® Memasang Deadend Eye Minimum 16in (406 mm) • Gunakan dua wrench (kunci Inggris) besar untuk mengencangkan eyebolt dengan collet housing sampai paling tidak torsinya 115 Newton meters. Satu wrench memegang eyebolt dan satunya pada collect housing. Hati-hati agar core tidak terputar pada waktu pengencangan ini. • Mengencangkan sambungan ini akan mendudukkan collet untuk memegang core. • Catatan : Selalu putar deadend eye saja dan tahan dengan wrench pada housing. Copyright January 2020 CTC Global All Rights Reserved 106
  • 123. Pemasangan Dead End ACCC® Kencangkan Deadend Sampai 85 Foot Pounds/115 Newton Meters • Setelah eyebolt dikencangkan ke collet housing, akan ada kira-kira 76mm (3”) core muncul diarah konduktor. • Collet akan menyembul keluar dari housing nya kira-kira 6 mm (1/4”) yang menunjukkan bahwa torsi yang benar telah diaplikasikan pada dead-end dan collet housing. Copyright January 2020 CTC Global All Rights Reserved 107
  • 124. Pemasangan Dead End ACCC® Membersihkan Konduktor • Gunakan Sikat Kawat untuk membersihkan oksidasi pada permukaan konduktor aluminium. Jangan gunakan sikat tembaga untuk pekerjaan ini. • Deadend harus selalu ditopang / dipegang supaya tidak core tertekuk. Copyright January 2020 CTC Global All Rights Reserved 108
  • 125. Pemasangan Dead End ACCC® Mengoleskan PROXALUHT A13 pada permukaan Konduktor • Untuk menghindari masalah dengan oksidasi, inhibitors (disebut demikian karena ia mencegah akses oksigen dan pertumbuhan lapisan oksidasi) telah digunakan selama puluhan tahun. Copyright January 2020 CTC Global All Rights Reserved 109
  • 126. Pemasangan Dead End ACCC® Mengoleskan PROXALUHT pada selongsong bagian dalam • Sikat selongsong dalam untuk membersihkan oksidasi seperti halnya pada konduktor. • Sapukan High Temperature Proxaluht pada selongsong dalam dan dorong selongsong ke dead end body sampai berhenti. Copyright January 2020 CTC Global All Rights Reserved 110
  • 127. Pemasangan Dead End ACCC® Mengapa kita menaruh High Temperature Oxide Inhibitor (Proxaluth) pada Konduktor dan Selongsong Dalam (Inner Sleeve) ? 1. Mencegah Oksidasi 2. Membantu mencegah cairan masuk ke deadend dan splice (sambungan/joint) 3. Membantu menjaga alat ini lebih dingin Copyright January 2020 CTC Global All Rights Reserved 111
  • 128. Pemasangan Dead End ACCC® Memasang Deadend Body ▪ Posisi Ujung Dead End Body Marking sebelum dipress yaitu tepat berada pada tanda atau marking yang sudah ada pada steel eye. ▪ Sebelum di press pastikan Pad berada pada posisi yang benar. • Untuk mengarahkan posisi Pad pada posisi yang benar, hanya diperbolehkan memutar Dead End Body saja ( Bukan Steel Eye ). • Awal Press dimulai dari arah konduktor ke arah steel Eye. Copyright January 2020 CTC Global All Rights Reserved 112
  • 129. Pemasangan Dead End ACCC® Birdcaging ▪ Mengepres selongsong aluminium ke arah konduktor akan menyebabkan strand aluminium terdorong dan menimbulkan “birdcaging” ▪ Aluminium akan terdorong sekitar 2,54 mm (satu per sepuluh inci) untuk setiap kali pengepresan. ▪ CTC mengharuskan metode back press untuk menghilangkan semua birdcaging di konduktor. Copyright January 2020 CTC Global All Rights Reserved 113
  • 130. Pemasangan Dead End ACCC® Pengepresan Deadend ▪ Oleskan sabun atau material lain yang licin pada bagian luar deadend body agar tidak melekat pada dies. ▪ Tahan dengan tangan ujung selongsong dalam pada posisinya, kemudian lakukan satu press mulai 6 mm dari garis tanda yang paling dekat dengan konduktor. ▪ Putar Boompress 180 derajat setiap dua press untuk menjaga deadend tetap lurus. Copyright January 2020 CTC Global All Rights Reserved 114
  • 131. Pemasangan Dead End ACCC® Pengepresan Deadend (Lanjutan) ▪ Teruskan press deadend body dari arah konduktor ke arah tanda yang ada di tengah deadend body. ▪ Overlap pengepresan sekitar 10-25 % mulai dari arah konduktor ke deadend eye. Copyright January 2020 CTC Global All Rights Reserved 115
  • 132. Pemasangan Dead End ACCC® Deadend Body Pada Pressan Terakhir ▪ Selesai pengepresan pada deadend body yang terdekat dengan konduktor, geser press head ke posisi berikut menuju ke deadend eye. ▪ Lakukan satu atau dua kali pengepresan dan perhatikan bahwa body deadend bergerak mendekati steel eye. ▪ Terdapat Gap / Jarak antara body dead end dengan steel eye 2 mm – 28 mm*. ▪ Beberapa Dead End type lain memiliki design GAP yang berbeda. *Setiap pabrikan hardware memiliki masing – masing prosedur installasi ( tergantung jenis Hardware dan teknis instalasinya ) Copyright January 2020 CTC Global All Rights Reserved 116
  • 133. Video Dead End ACCC® Copyright January 2020 CTC Global All Rights Reserved 117
  • 134. Midspan Joint Assembly (Splice ACCC® ) Splice Body Splice Coupler Copyright January 2020 CTC Global All Rights Reserved Inner Sleeve Collet Housing Collet 118
  • 135. Pemasangan Midspan Joint ACCC® Copyright January 2020 CTC Global All Rights Reserved 119
  • 136. Pemasangan Midspan Joint ACCC® Persiapan Penyambungan • Potong secara rata ujung kedua konduktor yang akan disambung menggunakan gergaji besi. • Pada salah satu konduktor selongsongkan selongsong dalam dan selongsong luar. (Ujung yang tirus dari selongsong dalam menghadap keluar dari ujung konduktor yang dipotong). • Pada konduktor yang satunya selongsongkan juga selongsong dalam satunya. Copyright January 2020 CTC Global All Rights Reserved 120
  • 137. Pemasangan Midspan Joint ACCC® Instruksi Penyambungan – Teknik Back Pressing ▪ ▪ Selongsongkan selongsong dalam pada konduktor sampai sejauh kira2 1 meter (gamb 1). Kemudian selongsongkan selongsong luar pada sisi yang lebih jauh dari tower (Side B) hingga ujung tabung sekitar 60 cm dari ujung konduktor yang dipotong. Copyright January 2020 CTC Global All Rights Reserved 121
  • 138. Pemasangan Midspan Joint ACCC® Instruksi Penyambungan (lanjutan) • Pasang tape melilit aluminium strand pada jarak tertentu dari ujung konduktor (Lihat Tabel A) ACCC Code Name Linnet Hawk Dove Grosbeak Drake Cardinal Bittern Lapwing Chukar Bluebird Outside Dia. (inches) 0.720 0.858 0.927 0.990 1.108 1.196 1.345 1.504 1.602 1.762 Table A Side A Exposed core length (inches) 9.0 (228 mm) 9.0 (228 mm) 9.0 (228 mm) 9.0 (228 mm) 12.5 (317 mm) 12.5 (317 mm) 12.5 (317 mm) 12.5 (317 mm) 12.5 (317 mm) 12.5 (317 mm) Side B Exposed core length (inches) 7.0 (177 mm) 7.0 (177 mm) 7.0 (177 mm) 7.0 (177 mm) 10.5 (266 mm) 10.5 (266 mm) 10.5 (266 mm) 10.5 (266 mm) 10.5 (266 mm) 10.5 (266 mm) ▪ Munculkan solid core dengan memotong aluminium strand pada tanda, satu lapis demi satu lapis Copyright January 2020 CTC Global All Rights Reserved 122
  • 139. Pemasangan Midspan Joint ACCC® Instruksi Penyambungan (lanjutan) • Lap permukaan core sampai bersih, bebas dari oli dan kotoran lain. Kemudian gosok core perlahan memakai kertas amplas 220 mesh sampai putih dan lap kembali core menggunakan kain bersih. • Pasang collet housing (Lihat Fig.2) ▪ Pasang collet (Fig.2) pada core dengan ujung yang kecil kearah housing, sampai core muncul sekitar 6 mm disisi besar collet (Lihat Fig.3). Ulangi untuk sisi lainnya. Copyright January 2020 CTC Global All Rights Reserved 123
  • 140. Pemasangan Midspan Joint ACCC® Instruksi Penyambungan (lanjutan) ▪ Pasang coupling di sisi A (terdekat dengan tower) dan collet retainer pada sisi B (terjauh dari tower) dan kencang-kan pakai tangan. Kencangkan lebih lanjut menggunakan kunci Inggris (diperlukan torsi 85 ftlbs atau 115 NM). ▪ Untuk Sisi A pastikan bahwa kira - kira 76 mm core dan ujung kecil collet tampak setelah dikencangkan (Lihat Fig 4). ▪ Untuk sisi B pastikan bahwa kira - kira 26 mm core dan ujung kecil collet tampak setelah dikencangkan (Lihat Fig 4) ▪ Taruh sedikit inhibitor pada ulir. Satukan kedua sisi dan kencangkan dengan tangan. Kencangkan lebih lanjut memakai wrench (perlu torsi 115Nm) Copyright January 2020 CTC Global All Rights Reserved 124
  • 141. Pemasangan Midspan Joint ACCC® Instrucksi Penyambungan (lanjutan) ▪ Tandai konduktor pada sisi A sepanjang Inner sleeve dari ujung aluminium strand pakai tape atau spidol (Fig.5). Tanda ini adalah lokasi ujung selongsong dalam. • Catatan : Bila pakai tape, tape ini harus dibuang sebelum pengepresan. ▪ Sikat aluminium strand yang akan tertutup oleh selongsong luar dan sapukan oxidation inhibitor pada bagian strand yang telah disikat.(Lihat Fig. 5) Tandai pada konduktor sepanjang inner sleeve Copyright January 2020 CTC Global All Rights Reserved 125
  • 142. Pemasangan Midspan Joint ACCC® Instruksi Penyambungan (lanjutan) ▪ Kemudian pasang selongsong luar aluminium menutupi coupling assembly. ▪ Sisi A : Berikan oxidation inhibitor pada bagian luar selongsong dalam,dan masukkan selongsong dalam ke selongsong luar sampai ke tanda di konduktor. Pastikan selongsong dalam mencapai pembatas yang ada didalam selongsong luar. Gerakkan selongsong luar bila perlu. ▪ Ketika selongsong luar sudah pada tempatnya, press selongsong dimulai dari sisi A kearah dalam menggunakan dies yang benar dan overlap press 10-25% lebar Dies sampai akhir zona press di Sisi A (Lihat Fig. 6) mark conductor Copyright January 2020 CTC Global All Rights Reserved 126
  • 143. Pemasangan Midspan Joint ACCC® Finished Splice ▪ Dengan memutar presshead 180 derajat setiap dua kali mengepres dan menjaga agar semua level ketika mengepres, sambungan akan lurus setelah selesai. Catatan : Oleskan sabun atau material lain yang licin pada bagian luar sambungan agar aluminium tidak menyangkut ke dies. Copyright January 2020 CTC Global All Rights Reserved 127
  • 144. Video Midspan Joint ACCC® Copyright January 2020 CTC Global All Rights Reserved 128
  • 145. Pemasangan Jumper ACCC® ✓ Jumper pad akandi “back pressed” untuk menghilangkan kemungkinan birdcaging. ✓ Gaya mekanis yang bekerja padaJumper relatif kecil sehingga tidak perlu ada upaya khusus untruk memegang core. ✓ Dengan demikian untukpemasangan Jumper, aluminium strand tidak perlu dikupas lebih dahulu. Copyright January 2020 CTC Global All Rights Reserved 129
  • 146. Pemasangan Jumper ACCC® ❑ Potong ujung konduktor memakai gergaji. ❑ Sikat permukaan konduktor. ❑ Masukkan dan tarik konduktor ke dan dari dalam pad beberapa kali, kemudian buang kelebihan inhibitor memakai kain bersih. ❑ Setelah membuang kelebihan inhibitor, masukkan konduktor hingga ke ujung dari pad. ❑ Gunakan mesin press hydraulic kapasitas minimum 60 Ton untuk press jumper body. Pres mulai dari arah konduktor menuju ke ujung pad. Overlap setiap pres. ❑ Bersihkan inhibitor yang berlebih.
  • 147. Copyright January 2020 CTC Global All Rights Reserved 130
  • 148. Pemasangan Jumper ACCC® ✓ Bila jumper fitting di pres seperti biasanya, akan terjadi birdcaging yang ekstrim dari strand aluminium paling luar karena konduktor kurang panjang untuk bisa menyerap atau menghilangkan birdcaging. ✓ Untuk mencegah hal ini terjadi, jumper pad fitting dipasang dengan cara “back pressing” Copyright January 2020 CTC Global All Rights Reserved 131
  • 149. Toleransi Dead End & Midspan Joint ACCC® ✓ Setiap kali dies alat pres menekan pada fitting, logam dipaksa bergerak dibagian dalam dan luar dari fitting. Dalam proses ini, gesekan antara fitting dan die set bisa menyebabkan bagian yang dipress melengkung. Adalah penting untuk memberi pelumas pada dies dan menjaga fitting tetap lurus. Melumuri bagian luar fitting dengan sabun akan sangat menolong. ✓ Sebagai aturan umum maka besar maksimum lengkungan pada deadend atau jumper fitting adalah 1/2 diameter konduktor sedang pada splice (sambungan) adalah 1 x diameter konduktor. ✓ Periksa kelurusan fitting. ✓ Lengkung terlalu banyak bisamenyebabkan stres internal pada logam dan kegagalan mekanis fitting. Copyright January 2020 CTC Global All Rights Reserved 132
  • 150. Suspention Clamp & Damper Melindungi terhadap tekukan, tekanan, gesekan, arc-over dan juga perbaikan. Dipakai pada konduktor ACCC menolong menurunkan panas. Gunakan “parrot bill” armor rod pada tegangan ekstra tinggi – 345 kV dan lebih tinggi. Karena konduktor ACCC dari aluminium lunak, maka pada pemasangan suspension clamp, damper dan spacer maka armor rod harus digunakan. Copyright January 2020 CTC Global All Rights Reserved 133
  • 151. Suspention Clamp & Damper AGS/Thermolign/CGS, and Hibus Suspensions ▪ AGS (Armor Grip Suspension) atau Thermolign Suspension direkomendasikan untuk dipakai pada konduktor ACCC. Sistim AGS pakai satu set armor rod sedang Thermolign pakai dua set armorrod. Thermolign mempunyai temperatur rating maksimum yang lebih tinggi. Keduanya mengurangi temperatur ke insulator secara dramatis dan juga memberi perlindungan tambahan terhadap sudut. Untuk sudut yang lebih besar lagi, direkomendasikan memakai double suspension system. ▪ Dimana tidak cukup ruang untuk memasang armor rod seperti pada Jumper, gunakan CGS (Cushion Grip Suspensions) yang menawarkan suspension system bertemperatur tinggi tanpa armor rod. Copyright January 2020 CTC Global All Rights Reserved 134
  • 152. Suspention Clamp & Damper Double Suspension Clamps ▪ Bila struktur mengalami downpull yang besar atau mempunyai peru- bahan sudut lebih besar dari 30 derajat, double suspension clamp arrangement bisa digunakan untuk pengganti deadend.. Copyright January 2020 CTC Global All Rights Reserved 135
  • 153. Suspention Clamp & Damper Lifting ACCC Copyright January 2020 CTC Global All Rights Reserved 136
  • 154. Suspention Clamp & Damper Vibration Damper ▪ Tanya pada FCI Burndy, PLP atau vendor yang telah disetujui tentang desain damper yang sesuai beserta rekomendasi metode dan posisi pemasangannya untuk konduktor ACCC. Copyright January 2020 CTC Global All Rights Reserved 137
  • 155. Suspention Clamp & Damper T-Tap ACCC Press Direction Copyright January 2020 CTC Global All Rights Reserved 138
  • 156. Kesimpulan Instalasi Konduktor ACCC® ✓ Meskipun ada beberapa perbedaan cara pemasangan antara konduktor ACSR dengan ACCC, namun Yang sama lebih banyak. ✓ Persiapan yang baik adalah hal penting untuk menghindari kejutan yang tidak menyenangkan pada waktu pelaksanaan.. ✓ Crew stringing akan cepat beradaptasi dengan konduktor ACCC karena teknik pemasangan tidak rumit dan mudah dipelajari. Copyright January 2020 CTC Global All Rights Reserved 139
  • 157. thanks you for attending today’s Saeful Hidayat Email: saeful_hidayat@de-mandiri.com HP : 0853 1015 5478 PT Dinamika Elektra Mandiri Jl. Perjuangan, Rukan Graha Mas Blok B. 26 Kebon Jeruk, Jakarta Barat 11530 Copyright January 2020 CTC Global All Rights Reserved 140