A Review on Suppression of Secondary Arc
Current Trough Single-Phase Auto-Reclosing
1
Shalini Chandel, 2
A. K. Sharma
1,2
Electrical Engineering Department, Jabalpur Engineering College, Jabalpur, India
Abstract: When single-phase to ground fault occurs in high voltage transmission line, secondary arc current and
recovery voltage must be suppressed in order to ensure that single-phase auto-reclosing operates reliably and
successfully.
This work adopts the suppression measure of secondary arc current using shunt reactor with neutral small
reactor-which is applied widely in India, and then uses MATLAB Simulink software to simulate suppression effect
about different fault point locations toward an example of 735kv double-ended sources high-voltage transmission
line. According to the simulation results, suppression effects about different locations are distinct. Moreover, this
measure can suppress secondary arc current effectively, ensure success of single phase auto-reclosing operation
and finally achieve security and stability of power system
Keywords: Fault point location, neutral reactor, secondary arc current, single phase auto reclosing.
1. INTRODUCTION
Single-line-to-ground (S-L-G) transient arcing faults make up around 80% of faults on transmission lines [2]. In an effort
to maintain high power quality levels and to provide continuous service to their customers, the power companies use fault
locators and auto reclosure schemes. For the design of these fault mitigation techniques to be effective, it is important to
possess accurate knowledge of the levels of prospective fault current on the line and the characteristics and behavior of
electrical arcs.
The best way to gain the required understanding is to simulate fault conditions on model power systems using computer
software. In order to accurately simulate the transient processes that a power system may be subjected to under fault
conditions, it is important to realistically model the arcing fault so that all of its effects on the power system can be
assessed.
Fig.1: Equivalent circuit diagram of an S-L-G fault
ISSN 2350-1049
International Journal of Recent Research in Interdisciplinary Sciences (IJRRIS)
Vol. 3, Issue 2, pp: (11-16), Month: April 2016 - June 2016, Available at: www.paperpublications.org
Page | 12
Paper Publications
Auto Reclosing:
Auto reclosing is the practice of reenergizing a circuit shortly after a fault has occurred. It takes advantage of the fact that
on overhead lines, 80-90% of faults are transient in nature [4]. An auto reclosing relay will send a signal to a circuit
breaker to reclose, re-energizing the faulted circuit. Should the fault persist after this time, the protection will operate
again and re-trip the line, and usually the auto-reclose will be disabled and the fault assumed to be permanent. In some
schemes, particularly at distribution level, the auto-reclose relay will be calibrated to attempt to reclose a number of times,
known as multi-shot re-closure.
There are a number of parameters involved in configuring auto reclosing relays, of which the most important are dead
time, reclaim time and number of shots. Dead time is the time after the protection operates before the reclosing relay
attempts the first re-closure, and the reclaim time is the time from the first reclose signal until the relay is ready to respond
to further faults. The number of shots is how many reclose attempts are allowed before lock out, usually set at increasing
time intervals between shots.
This figure illustrates auto-reclose cycle for a circuit breaker fitted with single shot auto-reclose scheme.
Fig.2: Auto-reclose cycle for a circuit breaker with a single shot auto-reclose scheme
High Voltage Auto-Reclose:
In the high voltage circuits where the fault levels associated are extremely high, it is essential that the system dead time be
kept to a few cycles so that the generators do not drift apart. High speed protection such as pilot wire carrier or distance
must be used to obtain operating times of one or two cycles. It is therefore desired that the re closure be of the single shot
type. High speed re closure in high voltage circuits improves the stability to a considerable extent on single-circuit ties.
On double circuit ties subjected to single circuit faults the continuity through the healthy circuit prevents the generators
from drifting apart so fast and increase in the stability limit is thus moderate. Nevertheless, it is sometimes important.
However, when the faults occur simultaneously on both the circuits the stability limit increases again considerably.
The successful application of high speed auto-reclose to high voltage systems interlinking a number of sources depends
on the following factors.
(i) The maximum time available for opening and closing the circuit breakers at each end of the faulty line, without loss
of synchronism.
(ii) The time required to deionize the arc at the fault, so that it will not restrike when the breakers are reclosed.
(iii) The speed of operation on opening and closing of the circuit breakers.
(iv) The probability of transient faults, that will allow high speed reclosure of the faulty lines.
It will be seen that some of these conditions are conflicting, e.g., the faster the breakers are reclosed the greater the power
that can be transmitted without loss of synchronism, provided that the arc does not restrike. But here the likelihood of arc
restriking is greater. An unsuccessful reclosure is more detrimental to stability than no reclosure at all. For this reason the
time allowed to deionize the line must not be less than the critical time for which the arc hardly ever restrikes.
ISSN 2350-1049
International Journal of Recent Research in Interdisciplinary Sciences (IJRRIS)
Vol. 3, Issue 2, pp: (11-16), Month: April 2016 - June 2016, Available at: www.paperpublications.org
Page | 13
Paper Publications
The reduction of reclosing time obtained by high speed relaying is however preferred as it reduces the duration of arc.
Indeed, the increase in power limit due to reclosing is muchgreater with very rapid fault clearing than with slower fault
clearing. For best resultsthe circuit breakers at both ends of the faulty line must be opened simultaneously.
Any time during which one circuit breaker is open in advance of the other represents an effective reduction of the breaker
electrical dead time and may well jeopardize the chances of a successful reclosure. To determine the electrical dead time
for a circuit breaker used in a high speed auto-reclose scheme it is essential to know the time interval during which the
line must be kept de-energized in order to allow for the complete deionization of the arc and ensure that it will not restrike
when the line is reconnected to the system.
2. METHODS OF SECONDARY ARC EXTINCTION
1. Single-Pole Tripping and Reclosing:
Single-pole switching (SPS) is the method by which only the faulted phase is taken out of service. SPS does not come
without its challenges. From the point of view of a protection engineer, the complexity of the protection scheme is
increased. From the point of view of a systems operator, questions need to be addressed, such as: “How long can the
system tolerate a single-pole open condition (an unbalance on the system) before it affects generators and motors?”
SPS also leads to challenges on the power system, such as the extinction of the secondary arc resulting from the coupling
between the faulted phase and healthy phase conductors.
Single-pole switching is a practical means to improve stability and reliability in extra high voltage networks where most
circuit breakers have independent pole operation. Several methods are used to ensure secondary arc extinction. For short
lines, no special methods are needed. For long lines, the four-reactor scheme is most commonly used. High-speed
grounding switches may be used. A hybrid reclosing method used successfully by Bonneville Power Administration
(BPA) on many lines over many years employs single-pole tripping, but with three-pole tripping on the back swing
followed by rapid three-pole reclosure the three-pole tripping ensures secondary arc extinction .
Single-pole switching may necessitate positive sequence filtering in stability control input signals. For advanced stability
control, signal processing and pattern recognition techniques may be developed to detect secondary arc extinction.
Reclosing into a fault is avoided and single-pole reclosing success is improved.
High-speed reclosing or single-pole switching may not allow increased power transfers because deterministic reliability
criteria generally specify permanent faults. Nevertheless, fast reclosing provides „„defense-in-depth‟‟ for frequently
occurring single-phase temporary faults and false operation of protective relays. The probability of power failures because
of multiple line outages is greatly reduced.
2. Auto-Reclosing On EHV Transmission Lines:
The most important consideration in the application of auto-reclosing to EHV transmission lines is the maintenance of
system stability and synchronism. The problems involved are dependent on whether the transmission system is weak or
strong. With a weak system, loss of a transmission link may lead quickly to an excessive phase angle across the CB used
for re-closure, thus preventing a successful re-closure. In a relatively strong system, the rate of change of phase angle will
be slow, so that delayed auto-reclose can be successfully applied.
An illustration is the interconnector between two power systems as shown in Figure Under healthy conditions, the amount
of synchronizing power transmitted, P, crosses the power/angle curve OAB at point X, showing that the phase
displacement between the two systems is θo. Under fault conditions, the curve OCB is applicable, and the operating point
changes to Y. Assuming constant power input to both ends of the line, there is now an accelerating power XY. As a result,
the operating point moves to Z, with an increased phase displacement, θ1, between the two systems. At this point the
circuit breakers trip and break the connection.
The phase displacement continues to increase at a rate dependent on the inertia of the two power sources. To maintain
synchronism, the circuit breaker must be reclosed in a time short enough to prevent the phase angle exceeding θ2. This
angle is such that the area (2) stays greater than the area (1), which is the condition for maintenance of synchronism.
ISSN 2350-1049
International Journal of Recent Research in Interdisciplinary Sciences (IJRRIS)
Vol. 3, Issue 2, pp: (11-16), Month: April 2016 - June 2016, Available at: www.paperpublications.org
Page | 14
Paper Publications
This example, for a weak system, shows that the successful application of auto-reclosing in such a case needs high-speed
protection and circuit breakers, and a short dead time. On strong systems, synchronism is unlikely to be lost by the
tripping out of a single line. For such systems, an alternative policy of delayed auto-reclosing may be adopted. This
enables the power swings on the system resulting from the fault to decay before reclosure is attempted.
3. SECONDARY ARC EXTINCTION TIME
Based on the experience, some equations have been proposed in the past to estimate the arc extinction time. In the
estimation of secondary arc extinction time only the stable extinction is taken in to consideration, because the
instantaneous extinction could happen in less than 0.15 sec. According to the experiment the arc extinction time versus
secondary arc currents about 20A and above, and voltage about 20 to30 kv is calculated from the equation
Further more the dead time of reclosure must be 0.25 more than extinction time which results in
The exact value of arc extinction time depends on various factors and parameters of the system and could be batter
estimated through performing transient studies.
Fig.3: Secondary arc current transposed line with shunt compensation with fault location in 1km of line
Fig.4: Secondary arc current un-transposed line with shunt compensation with fault location in 1km of line
ISSN 2350-1049
International Journal of Recent Research in Interdisciplinary Sciences (IJRRIS)
Vol. 3, Issue 2, pp: (11-16), Month: April 2016 - June 2016, Available at: www.paperpublications.org
Page | 15
Paper Publications
Fig.5: Secondary arc current transposed line with shunt compensation with fault location in 100km of line
Fig.6: Secondary arc current un-transposed line with shunt compensation with fault location in 100km of line
4. CONCLUSION
The purpose of this paper is to illustrate some considerations in the design and implementation of single-pole-tripping
relaying schemes. Single line to ground faults are the least damaging to the power system and that an open pole condition
allows for the secondary arc to extinguish, while at the same time allowing power transfer. These conditions increase
power system stability. SPT relaying scheme are implemented with SPT breakers and require individual control of the trip
coils of each pole of the breakers. These breakers are more expensive than 3PT breakers at lower HV voltage levels, but
breakers at EHV levels because of their phase clearance requirements, already have the ability to trip individual phases.
Ones a faulted phase has been selected and the SPT relaying system opens the proper pole a pole open condition is created
in the power system. Ground directional units should be disabled during this condition and some considerations should be
evaluated in adjacent lines to prevent miss operation of ground directional units.
ISSN 2350-1049
International Journal of Recent Research in Interdisciplinary Sciences (IJRRIS)
Vol. 3, Issue 2, pp: (11-16), Month: April 2016 - June 2016, Available at: www.paperpublications.org
Page | 16
Paper Publications
REFERENCES
[1] IEEE Standard Common Format for Transient Data Exchange (COMTRADE) forPower Systems. IEEE Std C37.111-
1999. DOI: 10.1109/IEEESTD.1999.90571
[2] V. Terzija, N. Elkalashy, G. Preston, V. Stanojevic, G. Strbac. “Detection of ArcingFaults: Modelling, Simulation,
Testing and Algorithms Aspects”. IEEE Power Tech.Conference Lausanne 2007, pp 1147 – 1152. DOI:
10.1109/PCT.2007.4538477
[3] M. Kizilcay, T. Pniok. “Digital Simulation of Fault Arcs in Power Systems”. ETEPVol.1, No. 1, Jan/Feb 1991.
[4] V. Terzija, Z. Radojevic, M. Djuric. “A New Approach for Arcing Faults Detection andFault Distance Calculation in
Spectral Domain”. Transmission and DistributionConference Proceedings, 15-20 Sept. 1996. pp 573-578.
[5] Papoulis. „Probability, Random Variables and Stochastic Processes‟. 4th Ed.McGraw Hill. http://www.mhhe.com
/engcs /electrical/papoulis ISBN: 0073660116
[6] EMTP Simulation of the Secondary ArcExtinction at Overhead Transmission Linesunder Single Phase Automatic
Reclosing, 2005 IEEE St. Petersburg Power Tech Proceedings, June 27-30, 2005, Report №15.–ISBN 5-93208-034-0
[7] Research on Suppression of Secondary Arc Current under Different Fault Locations for 500kV Transmission Line ,
Cui Ruochen, Yin Zhongdong, Wang Miaomiao, Li Ke, 978-1-4244-4813-5/10/2010 IEEE
[8] Modelling of Secondary Arc Using EMTP-RV, Yun-Sik Oh․ Sung-Bum Kang․ Hun-ChulSeo․Chul-Hwan Kim, The
Transactions of the Korean Institute of Electrical Engineers Vol. 61, No. 7, pp. 937~943, 2012
[9] Secondary arc extinction in extra high voltage systems using grounding switches, Qais M. Alias, Wafaa F. Tobia,
Diyala Journal of Engineering Sciences, Vol. 07, No. 01, pp. 81-93, March 2014
[10]Analysis of Secondary Arc Extinction Effects according to the Application of Shunt Reactor and High Speed
Grounding Switches in Transmission Systems, Seung-Hyun Sohn, Gyu-Jung Cho , Journal of International Council
on Electrical Engineering Vol. 4, No. 4, pp.324~329, 2014

More Related Content

What's hot

Overvoltage phenomenon
Overvoltage phenomenonOvervoltage phenomenon
Overvoltage phenomenonSwaminathan P
 
REPORT- RADIAL FEEDER PROTECTION PANEL DEVELOPMENT
REPORT- RADIAL FEEDER PROTECTION PANEL DEVELOPMENTREPORT- RADIAL FEEDER PROTECTION PANEL DEVELOPMENT
REPORT- RADIAL FEEDER PROTECTION PANEL DEVELOPMENTHimanshu Paghdal
 
Introduction to Transient Disturbances of power system and its types
Introduction to Transient Disturbances of power system and its typesIntroduction to Transient Disturbances of power system and its types
Introduction to Transient Disturbances of power system and its typesshantanu Chutiya begger
 
Ferro-resonance due to interruption of magnetizing currents of a cable fed tr...
Ferro-resonance due to interruption of magnetizing currents of a cable fed tr...Ferro-resonance due to interruption of magnetizing currents of a cable fed tr...
Ferro-resonance due to interruption of magnetizing currents of a cable fed tr...Rathan Yadav
 
Power system transients (IV-EEE)
Power system transients (IV-EEE)Power system transients (IV-EEE)
Power system transients (IV-EEE)betasam
 
Hybrid circuit breaker
Hybrid circuit breakerHybrid circuit breaker
Hybrid circuit breakerVishal Bhimani
 
Feasibility Analysis of the Positioning of Superconducting Fault Current Limi...
Feasibility Analysis of the Positioning of Superconducting Fault Current Limi...Feasibility Analysis of the Positioning of Superconducting Fault Current Limi...
Feasibility Analysis of the Positioning of Superconducting Fault Current Limi...mkanth
 
FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTIONFEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTIONDr. Rohit Babu
 
Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...
Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...
Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...Gilberto Mejía
 
Transient Recovery Voltage(TRV) in Interruption of Small Inductive Currents b...
Transient Recovery Voltage(TRV) in Interruption of Small Inductive Currents b...Transient Recovery Voltage(TRV) in Interruption of Small Inductive Currents b...
Transient Recovery Voltage(TRV) in Interruption of Small Inductive Currents b...Ali Sepehri
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrushmichaeljmack
 
Reactors and its types
Reactors and its typesReactors and its types
Reactors and its typesSlides Hub
 
Neutral Grounding Resistors
Neutral Grounding ResistorsNeutral Grounding Resistors
Neutral Grounding ResistorsElifAksoy13
 
Analysis of the Performance of Active Type SFCL and FCL for Reduction Capabil...
Analysis of the Performance of Active Type SFCL and FCL for Reduction Capabil...Analysis of the Performance of Active Type SFCL and FCL for Reduction Capabil...
Analysis of the Performance of Active Type SFCL and FCL for Reduction Capabil...IJSRD
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear johny renoald
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDINGPROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDINGDr. Rohit Babu
 
Electromagnetic transients in power system
Electromagnetic transients in power systemElectromagnetic transients in power system
Electromagnetic transients in power systemMathankumar S
 
High voltage grounding methods
High voltage grounding methods High voltage grounding methods
High voltage grounding methods Adnan Khan
 

What's hot (20)

Overvoltage phenomenon
Overvoltage phenomenonOvervoltage phenomenon
Overvoltage phenomenon
 
REPORT- RADIAL FEEDER PROTECTION PANEL DEVELOPMENT
REPORT- RADIAL FEEDER PROTECTION PANEL DEVELOPMENTREPORT- RADIAL FEEDER PROTECTION PANEL DEVELOPMENT
REPORT- RADIAL FEEDER PROTECTION PANEL DEVELOPMENT
 
Introduction to Transient Disturbances of power system and its types
Introduction to Transient Disturbances of power system and its typesIntroduction to Transient Disturbances of power system and its types
Introduction to Transient Disturbances of power system and its types
 
circuit breakers
circuit breakerscircuit breakers
circuit breakers
 
Ferro-resonance due to interruption of magnetizing currents of a cable fed tr...
Ferro-resonance due to interruption of magnetizing currents of a cable fed tr...Ferro-resonance due to interruption of magnetizing currents of a cable fed tr...
Ferro-resonance due to interruption of magnetizing currents of a cable fed tr...
 
Power system transients (IV-EEE)
Power system transients (IV-EEE)Power system transients (IV-EEE)
Power system transients (IV-EEE)
 
Hybrid circuit breaker
Hybrid circuit breakerHybrid circuit breaker
Hybrid circuit breaker
 
Feasibility Analysis of the Positioning of Superconducting Fault Current Limi...
Feasibility Analysis of the Positioning of Superconducting Fault Current Limi...Feasibility Analysis of the Positioning of Superconducting Fault Current Limi...
Feasibility Analysis of the Positioning of Superconducting Fault Current Limi...
 
FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTIONFEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTION
 
Ssfcl
SsfclSsfcl
Ssfcl
 
Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...
Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...
Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...
 
Transient Recovery Voltage(TRV) in Interruption of Small Inductive Currents b...
Transient Recovery Voltage(TRV) in Interruption of Small Inductive Currents b...Transient Recovery Voltage(TRV) in Interruption of Small Inductive Currents b...
Transient Recovery Voltage(TRV) in Interruption of Small Inductive Currents b...
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
 
Reactors and its types
Reactors and its typesReactors and its types
Reactors and its types
 
Neutral Grounding Resistors
Neutral Grounding ResistorsNeutral Grounding Resistors
Neutral Grounding Resistors
 
Analysis of the Performance of Active Type SFCL and FCL for Reduction Capabil...
Analysis of the Performance of Active Type SFCL and FCL for Reduction Capabil...Analysis of the Performance of Active Type SFCL and FCL for Reduction Capabil...
Analysis of the Performance of Active Type SFCL and FCL for Reduction Capabil...
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDINGPROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING
 
Electromagnetic transients in power system
Electromagnetic transients in power systemElectromagnetic transients in power system
Electromagnetic transients in power system
 
High voltage grounding methods
High voltage grounding methods High voltage grounding methods
High voltage grounding methods
 

Viewers also liked

Factors Affecting the Adoption of Electronic Health Records by Nurse
Factors Affecting the Adoption of Electronic Health Records by NurseFactors Affecting the Adoption of Electronic Health Records by Nurse
Factors Affecting the Adoption of Electronic Health Records by Nursepaperpublications3
 
Barriers to Development and Progress of Entreprenurs: Case of Lesotho
Barriers to Development and Progress of Entreprenurs: Case of LesothoBarriers to Development and Progress of Entreprenurs: Case of Lesotho
Barriers to Development and Progress of Entreprenurs: Case of Lesothopaperpublications3
 
Family Attachment to Coffee Farms, a Case of Coffee Farming in Kisii County, ...
Family Attachment to Coffee Farms, a Case of Coffee Farming in Kisii County, ...Family Attachment to Coffee Farms, a Case of Coffee Farming in Kisii County, ...
Family Attachment to Coffee Farms, a Case of Coffee Farming in Kisii County, ...paperpublications3
 
PRELIMINARY STUDY ON NUTRIENT REMOVAL OF DAIRY WASTEWATER BY PILOT SCALE SUBS...
PRELIMINARY STUDY ON NUTRIENT REMOVAL OF DAIRY WASTEWATER BY PILOT SCALE SUBS...PRELIMINARY STUDY ON NUTRIENT REMOVAL OF DAIRY WASTEWATER BY PILOT SCALE SUBS...
PRELIMINARY STUDY ON NUTRIENT REMOVAL OF DAIRY WASTEWATER BY PILOT SCALE SUBS...paperpublications3
 
Invitro Study of Antibacterial Activity of Leaf and Root Extract of Rauvolfia...
Invitro Study of Antibacterial Activity of Leaf and Root Extract of Rauvolfia...Invitro Study of Antibacterial Activity of Leaf and Root Extract of Rauvolfia...
Invitro Study of Antibacterial Activity of Leaf and Root Extract of Rauvolfia...paperpublications3
 
Rainfall Trend Analysis of Mysore District in Karnataka
Rainfall Trend Analysis of Mysore District in KarnatakaRainfall Trend Analysis of Mysore District in Karnataka
Rainfall Trend Analysis of Mysore District in Karnatakapaperpublications3
 
Grievance Resolution Mechanism on Employee Productivity: Commercial Banks in ...
Grievance Resolution Mechanism on Employee Productivity: Commercial Banks in ...Grievance Resolution Mechanism on Employee Productivity: Commercial Banks in ...
Grievance Resolution Mechanism on Employee Productivity: Commercial Banks in ...paperpublications3
 
Monitoring and Controlling Of Electric Overhead Travelling Crane Using PLC an...
Monitoring and Controlling Of Electric Overhead Travelling Crane Using PLC an...Monitoring and Controlling Of Electric Overhead Travelling Crane Using PLC an...
Monitoring and Controlling Of Electric Overhead Travelling Crane Using PLC an...paperpublications3
 
Evolution Analysis of Structures And Landforms Of Thalisain Area, Garhwal Him...
Evolution Analysis of Structures And Landforms Of Thalisain Area, Garhwal Him...Evolution Analysis of Structures And Landforms Of Thalisain Area, Garhwal Him...
Evolution Analysis of Structures And Landforms Of Thalisain Area, Garhwal Him...paperpublications3
 
Study of Bio-Nano Composite of Poly-Lactic Acid for Food Packaging- A Review
Study of Bio-Nano Composite of Poly-Lactic Acid for Food Packaging- A ReviewStudy of Bio-Nano Composite of Poly-Lactic Acid for Food Packaging- A Review
Study of Bio-Nano Composite of Poly-Lactic Acid for Food Packaging- A Reviewpaperpublications3
 
Microalgae as Potential Feedstock for Biodiesel Production-A Review
Microalgae as Potential Feedstock for Biodiesel Production-A ReviewMicroalgae as Potential Feedstock for Biodiesel Production-A Review
Microalgae as Potential Feedstock for Biodiesel Production-A Reviewpaperpublications3
 
Internal Audit Independence and Share Performance of Firms Listed In the Nair...
Internal Audit Independence and Share Performance of Firms Listed In the Nair...Internal Audit Independence and Share Performance of Firms Listed In the Nair...
Internal Audit Independence and Share Performance of Firms Listed In the Nair...paperpublications3
 
Inadequacy of Safe Domestic Water Supply in Small Urban Centre’s in Kenya: A ...
Inadequacy of Safe Domestic Water Supply in Small Urban Centre’s in Kenya: A ...Inadequacy of Safe Domestic Water Supply in Small Urban Centre’s in Kenya: A ...
Inadequacy of Safe Domestic Water Supply in Small Urban Centre’s in Kenya: A ...paperpublications3
 
The Prevalence of Pseudomonas Aeruginosa on Recommended Glasses of Selected V...
The Prevalence of Pseudomonas Aeruginosa on Recommended Glasses of Selected V...The Prevalence of Pseudomonas Aeruginosa on Recommended Glasses of Selected V...
The Prevalence of Pseudomonas Aeruginosa on Recommended Glasses of Selected V...paperpublications3
 
DESIGN AND DEVELOPMENT OF SMES BASED DVR MODEL IN SIMULINK
DESIGN AND DEVELOPMENT OF SMES BASED DVR MODEL IN SIMULINKDESIGN AND DEVELOPMENT OF SMES BASED DVR MODEL IN SIMULINK
DESIGN AND DEVELOPMENT OF SMES BASED DVR MODEL IN SIMULINKpaperpublications3
 
Rainfall Trend Analysis of Hassan District in Karnataka
Rainfall Trend Analysis of Hassan District in KarnatakaRainfall Trend Analysis of Hassan District in Karnataka
Rainfall Trend Analysis of Hassan District in Karnatakapaperpublications3
 
Socioeconomic Status of Women in Lesotho
Socioeconomic Status of Women in LesothoSocioeconomic Status of Women in Lesotho
Socioeconomic Status of Women in Lesothopaperpublications3
 
Water Quality Assessment - Case Study PCMC Area
Water Quality Assessment - Case Study PCMC AreaWater Quality Assessment - Case Study PCMC Area
Water Quality Assessment - Case Study PCMC Areapaperpublications3
 
Evaluation of Protective Efficacy of Hydro Alcoholic Extract and Methanol Fra...
Evaluation of Protective Efficacy of Hydro Alcoholic Extract and Methanol Fra...Evaluation of Protective Efficacy of Hydro Alcoholic Extract and Methanol Fra...
Evaluation of Protective Efficacy of Hydro Alcoholic Extract and Methanol Fra...paperpublications3
 

Viewers also liked (20)

Factors Affecting the Adoption of Electronic Health Records by Nurse
Factors Affecting the Adoption of Electronic Health Records by NurseFactors Affecting the Adoption of Electronic Health Records by Nurse
Factors Affecting the Adoption of Electronic Health Records by Nurse
 
Barriers to Development and Progress of Entreprenurs: Case of Lesotho
Barriers to Development and Progress of Entreprenurs: Case of LesothoBarriers to Development and Progress of Entreprenurs: Case of Lesotho
Barriers to Development and Progress of Entreprenurs: Case of Lesotho
 
Family Attachment to Coffee Farms, a Case of Coffee Farming in Kisii County, ...
Family Attachment to Coffee Farms, a Case of Coffee Farming in Kisii County, ...Family Attachment to Coffee Farms, a Case of Coffee Farming in Kisii County, ...
Family Attachment to Coffee Farms, a Case of Coffee Farming in Kisii County, ...
 
PRELIMINARY STUDY ON NUTRIENT REMOVAL OF DAIRY WASTEWATER BY PILOT SCALE SUBS...
PRELIMINARY STUDY ON NUTRIENT REMOVAL OF DAIRY WASTEWATER BY PILOT SCALE SUBS...PRELIMINARY STUDY ON NUTRIENT REMOVAL OF DAIRY WASTEWATER BY PILOT SCALE SUBS...
PRELIMINARY STUDY ON NUTRIENT REMOVAL OF DAIRY WASTEWATER BY PILOT SCALE SUBS...
 
Invitro Study of Antibacterial Activity of Leaf and Root Extract of Rauvolfia...
Invitro Study of Antibacterial Activity of Leaf and Root Extract of Rauvolfia...Invitro Study of Antibacterial Activity of Leaf and Root Extract of Rauvolfia...
Invitro Study of Antibacterial Activity of Leaf and Root Extract of Rauvolfia...
 
Rainfall Trend Analysis of Mysore District in Karnataka
Rainfall Trend Analysis of Mysore District in KarnatakaRainfall Trend Analysis of Mysore District in Karnataka
Rainfall Trend Analysis of Mysore District in Karnataka
 
Grievance Resolution Mechanism on Employee Productivity: Commercial Banks in ...
Grievance Resolution Mechanism on Employee Productivity: Commercial Banks in ...Grievance Resolution Mechanism on Employee Productivity: Commercial Banks in ...
Grievance Resolution Mechanism on Employee Productivity: Commercial Banks in ...
 
Monitoring and Controlling Of Electric Overhead Travelling Crane Using PLC an...
Monitoring and Controlling Of Electric Overhead Travelling Crane Using PLC an...Monitoring and Controlling Of Electric Overhead Travelling Crane Using PLC an...
Monitoring and Controlling Of Electric Overhead Travelling Crane Using PLC an...
 
Evolution Analysis of Structures And Landforms Of Thalisain Area, Garhwal Him...
Evolution Analysis of Structures And Landforms Of Thalisain Area, Garhwal Him...Evolution Analysis of Structures And Landforms Of Thalisain Area, Garhwal Him...
Evolution Analysis of Structures And Landforms Of Thalisain Area, Garhwal Him...
 
Study of Bio-Nano Composite of Poly-Lactic Acid for Food Packaging- A Review
Study of Bio-Nano Composite of Poly-Lactic Acid for Food Packaging- A ReviewStudy of Bio-Nano Composite of Poly-Lactic Acid for Food Packaging- A Review
Study of Bio-Nano Composite of Poly-Lactic Acid for Food Packaging- A Review
 
Microalgae as Potential Feedstock for Biodiesel Production-A Review
Microalgae as Potential Feedstock for Biodiesel Production-A ReviewMicroalgae as Potential Feedstock for Biodiesel Production-A Review
Microalgae as Potential Feedstock for Biodiesel Production-A Review
 
PROBLEMS FACED IN AUTOMATION
PROBLEMS FACED IN AUTOMATIONPROBLEMS FACED IN AUTOMATION
PROBLEMS FACED IN AUTOMATION
 
Internal Audit Independence and Share Performance of Firms Listed In the Nair...
Internal Audit Independence and Share Performance of Firms Listed In the Nair...Internal Audit Independence and Share Performance of Firms Listed In the Nair...
Internal Audit Independence and Share Performance of Firms Listed In the Nair...
 
Inadequacy of Safe Domestic Water Supply in Small Urban Centre’s in Kenya: A ...
Inadequacy of Safe Domestic Water Supply in Small Urban Centre’s in Kenya: A ...Inadequacy of Safe Domestic Water Supply in Small Urban Centre’s in Kenya: A ...
Inadequacy of Safe Domestic Water Supply in Small Urban Centre’s in Kenya: A ...
 
The Prevalence of Pseudomonas Aeruginosa on Recommended Glasses of Selected V...
The Prevalence of Pseudomonas Aeruginosa on Recommended Glasses of Selected V...The Prevalence of Pseudomonas Aeruginosa on Recommended Glasses of Selected V...
The Prevalence of Pseudomonas Aeruginosa on Recommended Glasses of Selected V...
 
DESIGN AND DEVELOPMENT OF SMES BASED DVR MODEL IN SIMULINK
DESIGN AND DEVELOPMENT OF SMES BASED DVR MODEL IN SIMULINKDESIGN AND DEVELOPMENT OF SMES BASED DVR MODEL IN SIMULINK
DESIGN AND DEVELOPMENT OF SMES BASED DVR MODEL IN SIMULINK
 
Rainfall Trend Analysis of Hassan District in Karnataka
Rainfall Trend Analysis of Hassan District in KarnatakaRainfall Trend Analysis of Hassan District in Karnataka
Rainfall Trend Analysis of Hassan District in Karnataka
 
Socioeconomic Status of Women in Lesotho
Socioeconomic Status of Women in LesothoSocioeconomic Status of Women in Lesotho
Socioeconomic Status of Women in Lesotho
 
Water Quality Assessment - Case Study PCMC Area
Water Quality Assessment - Case Study PCMC AreaWater Quality Assessment - Case Study PCMC Area
Water Quality Assessment - Case Study PCMC Area
 
Evaluation of Protective Efficacy of Hydro Alcoholic Extract and Methanol Fra...
Evaluation of Protective Efficacy of Hydro Alcoholic Extract and Methanol Fra...Evaluation of Protective Efficacy of Hydro Alcoholic Extract and Methanol Fra...
Evaluation of Protective Efficacy of Hydro Alcoholic Extract and Methanol Fra...
 

Similar to A Review on Suppression of Secondary Arc Current Trough Single-Phase Auto-Reclosing

Power Swing Phenomena and Comparative Study of Its Detection on Transmission ...
Power Swing Phenomena and Comparative Study of Its Detection on Transmission ...Power Swing Phenomena and Comparative Study of Its Detection on Transmission ...
Power Swing Phenomena and Comparative Study of Its Detection on Transmission ...ijsrd.com
 
Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...
Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...
Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...IRJET Journal
 
Protection of 20industrial electronic.pdf
Protection of 20industrial electronic.pdfProtection of 20industrial electronic.pdf
Protection of 20industrial electronic.pdfwhmonkey
 
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdfAzizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdfSultanAlSaiari1
 
01-120917022737-phpapp02.pdf
01-120917022737-phpapp02.pdf01-120917022737-phpapp02.pdf
01-120917022737-phpapp02.pdfThien Phan Bản
 
Double Circuit Transmission Line Protection using Line Trap & Artificial Neur...
Double Circuit Transmission Line Protection using Line Trap & Artificial Neur...Double Circuit Transmission Line Protection using Line Trap & Artificial Neur...
Double Circuit Transmission Line Protection using Line Trap & Artificial Neur...IRJET Journal
 
Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...
Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...
Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...Niraj Solanki
 
IRJET- Study Over Current Relay (MCGG53) Response using Matlab Model
IRJET- Study Over Current Relay (MCGG53) Response using Matlab ModelIRJET- Study Over Current Relay (MCGG53) Response using Matlab Model
IRJET- Study Over Current Relay (MCGG53) Response using Matlab ModelIRJET Journal
 
Relay operation principles
Relay operation principlesRelay operation principles
Relay operation principlesAmmar Al Hakeim
 
Pq unit ii
Pq unit iiPq unit ii
Pq unit iivenki249
 
lecture1423723756.pdf
lecture1423723756.pdflecture1423723756.pdf
lecture1423723756.pdfssuser564db8
 
Short circuit current calculations
Short circuit current calculationsShort circuit current calculations
Short circuit current calculationsRonald Santos
 
Transient Stability Assessment of the Nigerian 330kV Network.
Transient Stability Assessment of the Nigerian 330kV Network.Transient Stability Assessment of the Nigerian 330kV Network.
Transient Stability Assessment of the Nigerian 330kV Network.CSCJournals
 

Similar to A Review on Suppression of Secondary Arc Current Trough Single-Phase Auto-Reclosing (20)

Class 16 load shedding
Class 16 load sheddingClass 16 load shedding
Class 16 load shedding
 
Power Swing Phenomena and Comparative Study of Its Detection on Transmission ...
Power Swing Phenomena and Comparative Study of Its Detection on Transmission ...Power Swing Phenomena and Comparative Study of Its Detection on Transmission ...
Power Swing Phenomena and Comparative Study of Its Detection on Transmission ...
 
Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...
Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...
Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...
 
Auto recloser
Auto recloserAuto recloser
Auto recloser
 
Protection of 20industrial electronic.pdf
Protection of 20industrial electronic.pdfProtection of 20industrial electronic.pdf
Protection of 20industrial electronic.pdf
 
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdfAzizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
Azizan_2020_IOP_Conf._Ser.__Mater._Sci._Eng._767_012004.pdf
 
01-120917022737-phpapp02.pdf
01-120917022737-phpapp02.pdf01-120917022737-phpapp02.pdf
01-120917022737-phpapp02.pdf
 
Pe3426652670
Pe3426652670Pe3426652670
Pe3426652670
 
What's short circuit level
What's short circuit levelWhat's short circuit level
What's short circuit level
 
Double Circuit Transmission Line Protection using Line Trap & Artificial Neur...
Double Circuit Transmission Line Protection using Line Trap & Artificial Neur...Double Circuit Transmission Line Protection using Line Trap & Artificial Neur...
Double Circuit Transmission Line Protection using Line Trap & Artificial Neur...
 
Fy3610821086
Fy3610821086Fy3610821086
Fy3610821086
 
D04522631
D04522631D04522631
D04522631
 
98X- didier2013.pdf
98X- didier2013.pdf98X- didier2013.pdf
98X- didier2013.pdf
 
Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...
Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...
Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...
 
IRJET- Study Over Current Relay (MCGG53) Response using Matlab Model
IRJET- Study Over Current Relay (MCGG53) Response using Matlab ModelIRJET- Study Over Current Relay (MCGG53) Response using Matlab Model
IRJET- Study Over Current Relay (MCGG53) Response using Matlab Model
 
Relay operation principles
Relay operation principlesRelay operation principles
Relay operation principles
 
Pq unit ii
Pq unit iiPq unit ii
Pq unit ii
 
lecture1423723756.pdf
lecture1423723756.pdflecture1423723756.pdf
lecture1423723756.pdf
 
Short circuit current calculations
Short circuit current calculationsShort circuit current calculations
Short circuit current calculations
 
Transient Stability Assessment of the Nigerian 330kV Network.
Transient Stability Assessment of the Nigerian 330kV Network.Transient Stability Assessment of the Nigerian 330kV Network.
Transient Stability Assessment of the Nigerian 330kV Network.
 

Recently uploaded

Heredity: Inheritance and Variation of Traits
Heredity: Inheritance and Variation of TraitsHeredity: Inheritance and Variation of Traits
Heredity: Inheritance and Variation of TraitsCharlene Llagas
 
Call Girls in Hauz Khas Delhi 💯Call Us 🔝9953322196🔝 💯Escort.
Call Girls in Hauz Khas Delhi 💯Call Us 🔝9953322196🔝 💯Escort.Call Girls in Hauz Khas Delhi 💯Call Us 🔝9953322196🔝 💯Escort.
Call Girls in Hauz Khas Delhi 💯Call Us 🔝9953322196🔝 💯Escort.aasikanpl
 
Solution chemistry, Moral and Normal solutions
Solution chemistry, Moral and Normal solutionsSolution chemistry, Moral and Normal solutions
Solution chemistry, Moral and Normal solutionsHajira Mahmood
 
Call Girls in Aiims Metro Delhi 💯Call Us 🔝9953322196🔝 💯Escort.
Call Girls in Aiims Metro Delhi 💯Call Us 🔝9953322196🔝 💯Escort.Call Girls in Aiims Metro Delhi 💯Call Us 🔝9953322196🔝 💯Escort.
Call Girls in Aiims Metro Delhi 💯Call Us 🔝9953322196🔝 💯Escort.aasikanpl
 
LIGHT-PHENOMENA-BY-CABUALDIONALDOPANOGANCADIENTE-CONDEZA (1).pptx
LIGHT-PHENOMENA-BY-CABUALDIONALDOPANOGANCADIENTE-CONDEZA (1).pptxLIGHT-PHENOMENA-BY-CABUALDIONALDOPANOGANCADIENTE-CONDEZA (1).pptx
LIGHT-PHENOMENA-BY-CABUALDIONALDOPANOGANCADIENTE-CONDEZA (1).pptxmalonesandreagweneth
 
Transposable elements in prokaryotes.ppt
Transposable elements in prokaryotes.pptTransposable elements in prokaryotes.ppt
Transposable elements in prokaryotes.pptArshadWarsi13
 
Speech, hearing, noise, intelligibility.pptx
Speech, hearing, noise, intelligibility.pptxSpeech, hearing, noise, intelligibility.pptx
Speech, hearing, noise, intelligibility.pptxpriyankatabhane
 
Call Girls in Munirka Delhi 💯Call Us 🔝8264348440🔝
Call Girls in Munirka Delhi 💯Call Us 🔝8264348440🔝Call Girls in Munirka Delhi 💯Call Us 🔝8264348440🔝
Call Girls in Munirka Delhi 💯Call Us 🔝8264348440🔝soniya singh
 
RESPIRATORY ADAPTATIONS TO HYPOXIA IN HUMNAS.pptx
RESPIRATORY ADAPTATIONS TO HYPOXIA IN HUMNAS.pptxRESPIRATORY ADAPTATIONS TO HYPOXIA IN HUMNAS.pptx
RESPIRATORY ADAPTATIONS TO HYPOXIA IN HUMNAS.pptxFarihaAbdulRasheed
 
Welcome to GFDL for Take Your Child To Work Day
Welcome to GFDL for Take Your Child To Work DayWelcome to GFDL for Take Your Child To Work Day
Welcome to GFDL for Take Your Child To Work DayZachary Labe
 
Recombinant DNA technology( Transgenic plant and animal)
Recombinant DNA technology( Transgenic plant and animal)Recombinant DNA technology( Transgenic plant and animal)
Recombinant DNA technology( Transgenic plant and animal)DHURKADEVIBASKAR
 
‏‏VIRUS - 123455555555555555555555555555555555555555
‏‏VIRUS -  123455555555555555555555555555555555555555‏‏VIRUS -  123455555555555555555555555555555555555555
‏‏VIRUS - 123455555555555555555555555555555555555555kikilily0909
 
Cytokinin, mechanism and its application.pptx
Cytokinin, mechanism and its application.pptxCytokinin, mechanism and its application.pptx
Cytokinin, mechanism and its application.pptxVarshiniMK
 
Forest laws, Indian forest laws, why they are important
Forest laws, Indian forest laws, why they are importantForest laws, Indian forest laws, why they are important
Forest laws, Indian forest laws, why they are importantadityabhardwaj282
 
Module 4: Mendelian Genetics and Punnett Square
Module 4:  Mendelian Genetics and Punnett SquareModule 4:  Mendelian Genetics and Punnett Square
Module 4: Mendelian Genetics and Punnett SquareIsiahStephanRadaza
 
Gas_Laws_powerpoint_notes.ppt for grade 10
Gas_Laws_powerpoint_notes.ppt for grade 10Gas_Laws_powerpoint_notes.ppt for grade 10
Gas_Laws_powerpoint_notes.ppt for grade 10ROLANARIBATO3
 
Call Girls In Nihal Vihar Delhi ❤️8860477959 Looking Escorts In 24/7 Delhi NCR
Call Girls In Nihal Vihar Delhi ❤️8860477959 Looking Escorts In 24/7 Delhi NCRCall Girls In Nihal Vihar Delhi ❤️8860477959 Looking Escorts In 24/7 Delhi NCR
Call Girls In Nihal Vihar Delhi ❤️8860477959 Looking Escorts In 24/7 Delhi NCRlizamodels9
 
Call Girls in Mayapuri Delhi 💯Call Us 🔝9953322196🔝 💯Escort.
Call Girls in Mayapuri Delhi 💯Call Us 🔝9953322196🔝 💯Escort.Call Girls in Mayapuri Delhi 💯Call Us 🔝9953322196🔝 💯Escort.
Call Girls in Mayapuri Delhi 💯Call Us 🔝9953322196🔝 💯Escort.aasikanpl
 
Best Call Girls In Sector 29 Gurgaon❤️8860477959 EscorTs Service In 24/7 Delh...
Best Call Girls In Sector 29 Gurgaon❤️8860477959 EscorTs Service In 24/7 Delh...Best Call Girls In Sector 29 Gurgaon❤️8860477959 EscorTs Service In 24/7 Delh...
Best Call Girls In Sector 29 Gurgaon❤️8860477959 EscorTs Service In 24/7 Delh...lizamodels9
 

Recently uploaded (20)

Heredity: Inheritance and Variation of Traits
Heredity: Inheritance and Variation of TraitsHeredity: Inheritance and Variation of Traits
Heredity: Inheritance and Variation of Traits
 
Call Girls in Hauz Khas Delhi 💯Call Us 🔝9953322196🔝 💯Escort.
Call Girls in Hauz Khas Delhi 💯Call Us 🔝9953322196🔝 💯Escort.Call Girls in Hauz Khas Delhi 💯Call Us 🔝9953322196🔝 💯Escort.
Call Girls in Hauz Khas Delhi 💯Call Us 🔝9953322196🔝 💯Escort.
 
Hot Sexy call girls in Moti Nagar,🔝 9953056974 🔝 escort Service
Hot Sexy call girls in  Moti Nagar,🔝 9953056974 🔝 escort ServiceHot Sexy call girls in  Moti Nagar,🔝 9953056974 🔝 escort Service
Hot Sexy call girls in Moti Nagar,🔝 9953056974 🔝 escort Service
 
Solution chemistry, Moral and Normal solutions
Solution chemistry, Moral and Normal solutionsSolution chemistry, Moral and Normal solutions
Solution chemistry, Moral and Normal solutions
 
Call Girls in Aiims Metro Delhi 💯Call Us 🔝9953322196🔝 💯Escort.
Call Girls in Aiims Metro Delhi 💯Call Us 🔝9953322196🔝 💯Escort.Call Girls in Aiims Metro Delhi 💯Call Us 🔝9953322196🔝 💯Escort.
Call Girls in Aiims Metro Delhi 💯Call Us 🔝9953322196🔝 💯Escort.
 
LIGHT-PHENOMENA-BY-CABUALDIONALDOPANOGANCADIENTE-CONDEZA (1).pptx
LIGHT-PHENOMENA-BY-CABUALDIONALDOPANOGANCADIENTE-CONDEZA (1).pptxLIGHT-PHENOMENA-BY-CABUALDIONALDOPANOGANCADIENTE-CONDEZA (1).pptx
LIGHT-PHENOMENA-BY-CABUALDIONALDOPANOGANCADIENTE-CONDEZA (1).pptx
 
Transposable elements in prokaryotes.ppt
Transposable elements in prokaryotes.pptTransposable elements in prokaryotes.ppt
Transposable elements in prokaryotes.ppt
 
Speech, hearing, noise, intelligibility.pptx
Speech, hearing, noise, intelligibility.pptxSpeech, hearing, noise, intelligibility.pptx
Speech, hearing, noise, intelligibility.pptx
 
Call Girls in Munirka Delhi 💯Call Us 🔝8264348440🔝
Call Girls in Munirka Delhi 💯Call Us 🔝8264348440🔝Call Girls in Munirka Delhi 💯Call Us 🔝8264348440🔝
Call Girls in Munirka Delhi 💯Call Us 🔝8264348440🔝
 
RESPIRATORY ADAPTATIONS TO HYPOXIA IN HUMNAS.pptx
RESPIRATORY ADAPTATIONS TO HYPOXIA IN HUMNAS.pptxRESPIRATORY ADAPTATIONS TO HYPOXIA IN HUMNAS.pptx
RESPIRATORY ADAPTATIONS TO HYPOXIA IN HUMNAS.pptx
 
Welcome to GFDL for Take Your Child To Work Day
Welcome to GFDL for Take Your Child To Work DayWelcome to GFDL for Take Your Child To Work Day
Welcome to GFDL for Take Your Child To Work Day
 
Recombinant DNA technology( Transgenic plant and animal)
Recombinant DNA technology( Transgenic plant and animal)Recombinant DNA technology( Transgenic plant and animal)
Recombinant DNA technology( Transgenic plant and animal)
 
‏‏VIRUS - 123455555555555555555555555555555555555555
‏‏VIRUS -  123455555555555555555555555555555555555555‏‏VIRUS -  123455555555555555555555555555555555555555
‏‏VIRUS - 123455555555555555555555555555555555555555
 
Cytokinin, mechanism and its application.pptx
Cytokinin, mechanism and its application.pptxCytokinin, mechanism and its application.pptx
Cytokinin, mechanism and its application.pptx
 
Forest laws, Indian forest laws, why they are important
Forest laws, Indian forest laws, why they are importantForest laws, Indian forest laws, why they are important
Forest laws, Indian forest laws, why they are important
 
Module 4: Mendelian Genetics and Punnett Square
Module 4:  Mendelian Genetics and Punnett SquareModule 4:  Mendelian Genetics and Punnett Square
Module 4: Mendelian Genetics and Punnett Square
 
Gas_Laws_powerpoint_notes.ppt for grade 10
Gas_Laws_powerpoint_notes.ppt for grade 10Gas_Laws_powerpoint_notes.ppt for grade 10
Gas_Laws_powerpoint_notes.ppt for grade 10
 
Call Girls In Nihal Vihar Delhi ❤️8860477959 Looking Escorts In 24/7 Delhi NCR
Call Girls In Nihal Vihar Delhi ❤️8860477959 Looking Escorts In 24/7 Delhi NCRCall Girls In Nihal Vihar Delhi ❤️8860477959 Looking Escorts In 24/7 Delhi NCR
Call Girls In Nihal Vihar Delhi ❤️8860477959 Looking Escorts In 24/7 Delhi NCR
 
Call Girls in Mayapuri Delhi 💯Call Us 🔝9953322196🔝 💯Escort.
Call Girls in Mayapuri Delhi 💯Call Us 🔝9953322196🔝 💯Escort.Call Girls in Mayapuri Delhi 💯Call Us 🔝9953322196🔝 💯Escort.
Call Girls in Mayapuri Delhi 💯Call Us 🔝9953322196🔝 💯Escort.
 
Best Call Girls In Sector 29 Gurgaon❤️8860477959 EscorTs Service In 24/7 Delh...
Best Call Girls In Sector 29 Gurgaon❤️8860477959 EscorTs Service In 24/7 Delh...Best Call Girls In Sector 29 Gurgaon❤️8860477959 EscorTs Service In 24/7 Delh...
Best Call Girls In Sector 29 Gurgaon❤️8860477959 EscorTs Service In 24/7 Delh...
 

A Review on Suppression of Secondary Arc Current Trough Single-Phase Auto-Reclosing

  • 1. ISSN 2350-1049 International Journal of Recent Research in Interdisciplinary Sciences (IJRRIS) Vol. 3, Issue 2, pp: (11-16), Month: April 2016 - June 2016, Available at: www.paperpublications.org Page | 11 Paper Publications A Review on Suppression of Secondary Arc Current Trough Single-Phase Auto-Reclosing 1 Shalini Chandel, 2 A. K. Sharma 1,2 Electrical Engineering Department, Jabalpur Engineering College, Jabalpur, India Abstract: When single-phase to ground fault occurs in high voltage transmission line, secondary arc current and recovery voltage must be suppressed in order to ensure that single-phase auto-reclosing operates reliably and successfully. This work adopts the suppression measure of secondary arc current using shunt reactor with neutral small reactor-which is applied widely in India, and then uses MATLAB Simulink software to simulate suppression effect about different fault point locations toward an example of 735kv double-ended sources high-voltage transmission line. According to the simulation results, suppression effects about different locations are distinct. Moreover, this measure can suppress secondary arc current effectively, ensure success of single phase auto-reclosing operation and finally achieve security and stability of power system Keywords: Fault point location, neutral reactor, secondary arc current, single phase auto reclosing. 1. INTRODUCTION Single-line-to-ground (S-L-G) transient arcing faults make up around 80% of faults on transmission lines [2]. In an effort to maintain high power quality levels and to provide continuous service to their customers, the power companies use fault locators and auto reclosure schemes. For the design of these fault mitigation techniques to be effective, it is important to possess accurate knowledge of the levels of prospective fault current on the line and the characteristics and behavior of electrical arcs. The best way to gain the required understanding is to simulate fault conditions on model power systems using computer software. In order to accurately simulate the transient processes that a power system may be subjected to under fault conditions, it is important to realistically model the arcing fault so that all of its effects on the power system can be assessed. Fig.1: Equivalent circuit diagram of an S-L-G fault
  • 2. ISSN 2350-1049 International Journal of Recent Research in Interdisciplinary Sciences (IJRRIS) Vol. 3, Issue 2, pp: (11-16), Month: April 2016 - June 2016, Available at: www.paperpublications.org Page | 12 Paper Publications Auto Reclosing: Auto reclosing is the practice of reenergizing a circuit shortly after a fault has occurred. It takes advantage of the fact that on overhead lines, 80-90% of faults are transient in nature [4]. An auto reclosing relay will send a signal to a circuit breaker to reclose, re-energizing the faulted circuit. Should the fault persist after this time, the protection will operate again and re-trip the line, and usually the auto-reclose will be disabled and the fault assumed to be permanent. In some schemes, particularly at distribution level, the auto-reclose relay will be calibrated to attempt to reclose a number of times, known as multi-shot re-closure. There are a number of parameters involved in configuring auto reclosing relays, of which the most important are dead time, reclaim time and number of shots. Dead time is the time after the protection operates before the reclosing relay attempts the first re-closure, and the reclaim time is the time from the first reclose signal until the relay is ready to respond to further faults. The number of shots is how many reclose attempts are allowed before lock out, usually set at increasing time intervals between shots. This figure illustrates auto-reclose cycle for a circuit breaker fitted with single shot auto-reclose scheme. Fig.2: Auto-reclose cycle for a circuit breaker with a single shot auto-reclose scheme High Voltage Auto-Reclose: In the high voltage circuits where the fault levels associated are extremely high, it is essential that the system dead time be kept to a few cycles so that the generators do not drift apart. High speed protection such as pilot wire carrier or distance must be used to obtain operating times of one or two cycles. It is therefore desired that the re closure be of the single shot type. High speed re closure in high voltage circuits improves the stability to a considerable extent on single-circuit ties. On double circuit ties subjected to single circuit faults the continuity through the healthy circuit prevents the generators from drifting apart so fast and increase in the stability limit is thus moderate. Nevertheless, it is sometimes important. However, when the faults occur simultaneously on both the circuits the stability limit increases again considerably. The successful application of high speed auto-reclose to high voltage systems interlinking a number of sources depends on the following factors. (i) The maximum time available for opening and closing the circuit breakers at each end of the faulty line, without loss of synchronism. (ii) The time required to deionize the arc at the fault, so that it will not restrike when the breakers are reclosed. (iii) The speed of operation on opening and closing of the circuit breakers. (iv) The probability of transient faults, that will allow high speed reclosure of the faulty lines. It will be seen that some of these conditions are conflicting, e.g., the faster the breakers are reclosed the greater the power that can be transmitted without loss of synchronism, provided that the arc does not restrike. But here the likelihood of arc restriking is greater. An unsuccessful reclosure is more detrimental to stability than no reclosure at all. For this reason the time allowed to deionize the line must not be less than the critical time for which the arc hardly ever restrikes.
  • 3. ISSN 2350-1049 International Journal of Recent Research in Interdisciplinary Sciences (IJRRIS) Vol. 3, Issue 2, pp: (11-16), Month: April 2016 - June 2016, Available at: www.paperpublications.org Page | 13 Paper Publications The reduction of reclosing time obtained by high speed relaying is however preferred as it reduces the duration of arc. Indeed, the increase in power limit due to reclosing is muchgreater with very rapid fault clearing than with slower fault clearing. For best resultsthe circuit breakers at both ends of the faulty line must be opened simultaneously. Any time during which one circuit breaker is open in advance of the other represents an effective reduction of the breaker electrical dead time and may well jeopardize the chances of a successful reclosure. To determine the electrical dead time for a circuit breaker used in a high speed auto-reclose scheme it is essential to know the time interval during which the line must be kept de-energized in order to allow for the complete deionization of the arc and ensure that it will not restrike when the line is reconnected to the system. 2. METHODS OF SECONDARY ARC EXTINCTION 1. Single-Pole Tripping and Reclosing: Single-pole switching (SPS) is the method by which only the faulted phase is taken out of service. SPS does not come without its challenges. From the point of view of a protection engineer, the complexity of the protection scheme is increased. From the point of view of a systems operator, questions need to be addressed, such as: “How long can the system tolerate a single-pole open condition (an unbalance on the system) before it affects generators and motors?” SPS also leads to challenges on the power system, such as the extinction of the secondary arc resulting from the coupling between the faulted phase and healthy phase conductors. Single-pole switching is a practical means to improve stability and reliability in extra high voltage networks where most circuit breakers have independent pole operation. Several methods are used to ensure secondary arc extinction. For short lines, no special methods are needed. For long lines, the four-reactor scheme is most commonly used. High-speed grounding switches may be used. A hybrid reclosing method used successfully by Bonneville Power Administration (BPA) on many lines over many years employs single-pole tripping, but with three-pole tripping on the back swing followed by rapid three-pole reclosure the three-pole tripping ensures secondary arc extinction . Single-pole switching may necessitate positive sequence filtering in stability control input signals. For advanced stability control, signal processing and pattern recognition techniques may be developed to detect secondary arc extinction. Reclosing into a fault is avoided and single-pole reclosing success is improved. High-speed reclosing or single-pole switching may not allow increased power transfers because deterministic reliability criteria generally specify permanent faults. Nevertheless, fast reclosing provides „„defense-in-depth‟‟ for frequently occurring single-phase temporary faults and false operation of protective relays. The probability of power failures because of multiple line outages is greatly reduced. 2. Auto-Reclosing On EHV Transmission Lines: The most important consideration in the application of auto-reclosing to EHV transmission lines is the maintenance of system stability and synchronism. The problems involved are dependent on whether the transmission system is weak or strong. With a weak system, loss of a transmission link may lead quickly to an excessive phase angle across the CB used for re-closure, thus preventing a successful re-closure. In a relatively strong system, the rate of change of phase angle will be slow, so that delayed auto-reclose can be successfully applied. An illustration is the interconnector between two power systems as shown in Figure Under healthy conditions, the amount of synchronizing power transmitted, P, crosses the power/angle curve OAB at point X, showing that the phase displacement between the two systems is θo. Under fault conditions, the curve OCB is applicable, and the operating point changes to Y. Assuming constant power input to both ends of the line, there is now an accelerating power XY. As a result, the operating point moves to Z, with an increased phase displacement, θ1, between the two systems. At this point the circuit breakers trip and break the connection. The phase displacement continues to increase at a rate dependent on the inertia of the two power sources. To maintain synchronism, the circuit breaker must be reclosed in a time short enough to prevent the phase angle exceeding θ2. This angle is such that the area (2) stays greater than the area (1), which is the condition for maintenance of synchronism.
  • 4. ISSN 2350-1049 International Journal of Recent Research in Interdisciplinary Sciences (IJRRIS) Vol. 3, Issue 2, pp: (11-16), Month: April 2016 - June 2016, Available at: www.paperpublications.org Page | 14 Paper Publications This example, for a weak system, shows that the successful application of auto-reclosing in such a case needs high-speed protection and circuit breakers, and a short dead time. On strong systems, synchronism is unlikely to be lost by the tripping out of a single line. For such systems, an alternative policy of delayed auto-reclosing may be adopted. This enables the power swings on the system resulting from the fault to decay before reclosure is attempted. 3. SECONDARY ARC EXTINCTION TIME Based on the experience, some equations have been proposed in the past to estimate the arc extinction time. In the estimation of secondary arc extinction time only the stable extinction is taken in to consideration, because the instantaneous extinction could happen in less than 0.15 sec. According to the experiment the arc extinction time versus secondary arc currents about 20A and above, and voltage about 20 to30 kv is calculated from the equation Further more the dead time of reclosure must be 0.25 more than extinction time which results in The exact value of arc extinction time depends on various factors and parameters of the system and could be batter estimated through performing transient studies. Fig.3: Secondary arc current transposed line with shunt compensation with fault location in 1km of line Fig.4: Secondary arc current un-transposed line with shunt compensation with fault location in 1km of line
  • 5. ISSN 2350-1049 International Journal of Recent Research in Interdisciplinary Sciences (IJRRIS) Vol. 3, Issue 2, pp: (11-16), Month: April 2016 - June 2016, Available at: www.paperpublications.org Page | 15 Paper Publications Fig.5: Secondary arc current transposed line with shunt compensation with fault location in 100km of line Fig.6: Secondary arc current un-transposed line with shunt compensation with fault location in 100km of line 4. CONCLUSION The purpose of this paper is to illustrate some considerations in the design and implementation of single-pole-tripping relaying schemes. Single line to ground faults are the least damaging to the power system and that an open pole condition allows for the secondary arc to extinguish, while at the same time allowing power transfer. These conditions increase power system stability. SPT relaying scheme are implemented with SPT breakers and require individual control of the trip coils of each pole of the breakers. These breakers are more expensive than 3PT breakers at lower HV voltage levels, but breakers at EHV levels because of their phase clearance requirements, already have the ability to trip individual phases. Ones a faulted phase has been selected and the SPT relaying system opens the proper pole a pole open condition is created in the power system. Ground directional units should be disabled during this condition and some considerations should be evaluated in adjacent lines to prevent miss operation of ground directional units.
  • 6. ISSN 2350-1049 International Journal of Recent Research in Interdisciplinary Sciences (IJRRIS) Vol. 3, Issue 2, pp: (11-16), Month: April 2016 - June 2016, Available at: www.paperpublications.org Page | 16 Paper Publications REFERENCES [1] IEEE Standard Common Format for Transient Data Exchange (COMTRADE) forPower Systems. IEEE Std C37.111- 1999. DOI: 10.1109/IEEESTD.1999.90571 [2] V. Terzija, N. Elkalashy, G. Preston, V. Stanojevic, G. Strbac. “Detection of ArcingFaults: Modelling, Simulation, Testing and Algorithms Aspects”. IEEE Power Tech.Conference Lausanne 2007, pp 1147 – 1152. DOI: 10.1109/PCT.2007.4538477 [3] M. Kizilcay, T. Pniok. “Digital Simulation of Fault Arcs in Power Systems”. ETEPVol.1, No. 1, Jan/Feb 1991. [4] V. Terzija, Z. Radojevic, M. Djuric. “A New Approach for Arcing Faults Detection andFault Distance Calculation in Spectral Domain”. Transmission and DistributionConference Proceedings, 15-20 Sept. 1996. pp 573-578. [5] Papoulis. „Probability, Random Variables and Stochastic Processes‟. 4th Ed.McGraw Hill. http://www.mhhe.com /engcs /electrical/papoulis ISBN: 0073660116 [6] EMTP Simulation of the Secondary ArcExtinction at Overhead Transmission Linesunder Single Phase Automatic Reclosing, 2005 IEEE St. Petersburg Power Tech Proceedings, June 27-30, 2005, Report №15.–ISBN 5-93208-034-0 [7] Research on Suppression of Secondary Arc Current under Different Fault Locations for 500kV Transmission Line , Cui Ruochen, Yin Zhongdong, Wang Miaomiao, Li Ke, 978-1-4244-4813-5/10/2010 IEEE [8] Modelling of Secondary Arc Using EMTP-RV, Yun-Sik Oh․ Sung-Bum Kang․ Hun-ChulSeo․Chul-Hwan Kim, The Transactions of the Korean Institute of Electrical Engineers Vol. 61, No. 7, pp. 937~943, 2012 [9] Secondary arc extinction in extra high voltage systems using grounding switches, Qais M. Alias, Wafaa F. Tobia, Diyala Journal of Engineering Sciences, Vol. 07, No. 01, pp. 81-93, March 2014 [10]Analysis of Secondary Arc Extinction Effects according to the Application of Shunt Reactor and High Speed Grounding Switches in Transmission Systems, Seung-Hyun Sohn, Gyu-Jung Cho , Journal of International Council on Electrical Engineering Vol. 4, No. 4, pp.324~329, 2014