Indonesian Journal of Electrical Engineering and Computer Science
Vol. 21, No. 1, January 2021, pp. 92~100
ISSN: 2502-4752, DOI: 10.11591/ijeecs.v21.i1.pp92-100  92
Journal homepage: http://ijeecs.iaescore.com
Supervision and control by SCADA of an automated fire system
Omar Chamorro-Atalaya, Dora Arce-Santillan, Teodoro Diaz-Leyva, Martin Diaz-Choque
Faculty of Engineering and Management, National Technological University of Lima Sur (UNTELS),
Villa El Salvador, Perú
Article Info ABSTRACT
Article history:
Received May 23, 2020
Revised Jul 28, 2020
Accepted Aug 8, 2020
The purpose of this article is to describe the development of a prototype of a
monitoring and control system for a fire-fighting system, implemented
through SCADA (supervisory control and data acquisition) for which the
OPC (OLE for process control) is known. Known KepServerEX6 (single
data source connectivity platform), with which the integration of the PLC
(programmable logic controller), the human-machine interface (HMI) and the
computer will be controlled, with the application of monitoring the operating
parameters of a fire fighting system. These parameters are the pressure and
flow of the electric pump, the values of the parameters are regularly
controlled automatically by means of a frequency variator, according to the
sprinkler actuation, the variator varies its operating frequency until achieving
the optimal pressure and flow values. The level of correlation between the
indicators to be monitored by the SCADA system is highly significant, equal
to 0.977, 0.983 and 0.997 respectively. In addition, the dispersion model of
the indicators monitored by the SCADA system will be determined, is the
quadratic, with a determination factor of 0.999.
Keywords:
Automated control
Open protocol communication
Programmable logic controller
Scada
Sprayer
Supervision
Variable frequency drive
This is an open access article under the CC BY-SA license.
Corresponding Author:
Omar Freddy Chamorro Atalaya
Av. Central y Av. Bolivar
Sector 3, Grupo 1A - 03, Villa El Salvador, Peru
Email: omar_chamorro1@hotmail.com
1. INTRODUCTION
Every organization where people work is exposed to the presence of risks, conditioned by the
environment in which its activities are carried out [1]. In case of not being controlled these risks can be
triggered by accidents and damage to property, which can be caused by natural effects or by acciodentes of
people as part of their routine activities [2]. From the field of research, development and innovation and
taking into account the evolution of technology, there are various electronic solutions that improve conditions
in terms of security and fire protection in companies [3]. The risk of fire and explosion are two of the most
important risks that must be controlled in the workplace. Electronic systems reduce response time to
emergencies [4].
In the industry there are vital systems and equipment to keep the company's production process
active, ensuring the availability and operation of all the emergency equipment present in the facilities [5]. To
guarantee operational continuity in vital critical process and industrial safety equipment, a system is required
to monitor the operating and operational parameters of the fire protection system [6]. A fire protection system
is essential in all types of industrial warehouses, companies or buildings to safeguard human lives and
minimize the economic losses caused by fire [7]. To determine the necessary prevention and protection
measures that help reduce the risk of fire in buildings, the degree of risk must be evaluated [8]. It is important
in this type of project to monitor and control the project from the beginning of the design to the operation and
maintenance of the system, [9] defining the quality control mechanisms, the operational tests and the
Indonesian J Elec Eng & Comp Sci ISSN: 2502-4752 
Supervision and control by SCADA of an automated fire system (Omar Chamorro-Atalaya)
93
procedures that must be carried out for its correct operation ensuring that its pressure and flow indicators are
adequate permanently [10]. In the case of underdeveloped countries that often do not have the economic
resources necessary to invest in high-tech fire systems, which are usually very expensive and their function is
only to protect, they make industries ignore this type of systems, the same that would harbor a high risk for
the life of the workers [11]. For this reason, technology motivates companies to apply methodologies to
control their processes [12].
The control and supervision in real time of a process is carried out through a control system called
SCADA [13] which has hardware and software components that allow to supervise and control the industrial
process [14]. This system monitors the process data for further processing and provides a communication
interface between the user and the machine [15]. Process supervision generally refers to decision-making
activities aimed at maintaining the functioning of the system [16]. The SCADA control system refers to
control, supervision and data acquisition that allows the management and control of any local or remote
system thanks to a graphical interface that communicates the user with the system [17]. A SCADA system is
an application or set of software applications specially designed to work on production control computers,
with access to the plant through digital communication with instruments and actuators, and a high-level
graphic interface for the operator (touch screens, mice or cursors, styluses, etc.) [18]. It has the benefits of
reducing engineering costs, time and risk through easy integration with all devices in the plant [19].
In order to integrate the SCADA system with the other components of the automated process, an
OPC is used, which allows interoperability for the safe and reliable exchange of information in the space of
industrial automation and in other industries [20]. It is used to ensure a continuous flow of information and
overcome communication problems between controller devices or applications from multiple providers [21].
Also, the human machine interface (HMI), are used to represent the reality of processes [22]. The OPC
standard is based on a series of specifications developed by industry vendors, end users and software
developers and managed by the OPC that serve to define the interface between clients and servers, real-time
data access, alarm monitoring and events, access to history among other applications [23]. OPC Servers are
bi-directional connectors that allow you to "read from" and "write to" a Data source [24]. The relationship
between the OPC Server and the OPC Client is of the master/slave type, which means that an OPC Server
will only transfer data from/to a Data Source if an OPC Client requests it [25].
In this sense, the purpose of this article is to describe the development of a monitoring and control
system implemented through SCADA, by using the OPC KepServerEX6, with which the integration of the
programmable logic controller, the human-machine interface (HMI) will be achieved. And the computer, in
order to monitor and control the parameters of a fire-fighting system, which is automated by means of a PLC;
these parameters to control are the pressure and flow of the pump, when the sprinklers are activated.
2. PROCEDURE
In order to control and supervise the operating parameters (pressure and flow) of the fire fighting
system, implemented for an industrial warehouse, initially as a prototype, the architecture outlining the
components is specified in Figure 1 of the industrial network.
Figure 1. Network architecture of the control and supervision system of the fire fighting system
Established the network architecture of the components that allow the supervision and control of the
operating parameters of the fire fighting system, the procedure for programming the programmable logic
controller and SCADA is shown Figure 2.
SQL
DB
OPC
SERVER
ORDENADOR
SCADA- HMI
TCP /IP
CONTROLLER
S7-1212C-2DP
PROFIBUS
DECENTRALIZED
PERIPHERY
 ISSN: 2502-4752
Indonesian J Elec Eng & Comp Sci, Vol. 21, No. 1, January 2021 : 92 - 100
94
Initially, a variable table is created in which analog (0-10 volts) digital inputs (Boolean type) and
digital outputs (Boolean type) are specified in the programmable logic controller register. Once the input and
output variables are specified, programming is carried out in the PLC so that synergy is established between
all the components that participate in the fire fighting system for monitoring and supervision. In Figure 2, the
first segment of the programming of the fire system automation is shown, in which a block (type SR) called
system (M0.0) is created in which a start button (start) is connected to the SET input and at the REST input, a
normally closed (NC) button is connected, which is denially called ina stop, and at the output of the SR (Set
Rest) block, a digital output Q0.3 is connected, indicating that the system is found on or off. One of the NA
(normally open) contacts of the system block (M0.0) is in series with all the segments of the program in order
to control them.
Figure 3 shows the programming the frequency variator who will regulate the operation speed of the
electric pump, which requires the use of 3 speeds (low, medium, high), which the PLC will control the
variator (simatic V20). Furthermore, sensor 1 (I0.2), sensor 2 (I0.3) and sensor 3 (I0.4) are in parallel and all
of them in series with the NC contacts (normally closed) of the average speeds (M0.3), high (M0.4) and with
the NO contact of the system (M0.0), which control the switching on and off of the low speed (M0.2) and the
hmi pump (M0.1).
Figure 4 shows the programming of the on and off of the lighting and outlet outputs. In the third
segment of this programming, the NO contacts of solenoid valves 1 (Q0.0), 2 (Q0.1) and 3 (Q0.2) are shown
in series with the NO contact of the system (M0.0), the which control the lighting output (Q0.4) and
outlet (Q0.5).
Figure 2. Ignition system programming
Figure 3. Programming the frequency inverter speeds
Indonesian J Elec Eng & Comp Sci ISSN: 2502-4752 
Supervision and control by SCADA of an automated fire system (Omar Chamorro-Atalaya)
95
In Figure 5, the alarm programming is carried out, in this function block, the warning alarms are
found, it is observed in segment 1 that sensor 1 (I0.2) is in series with the data blocks_1 of sensors 1 and 2
(DB1.DBX0.3), 1 and 3 (DB1.DBX0.4), 1 and 2 and 3 (DB1.DBX0.6), the same ones that allow the control
of the output of data block_1 Sensor 1 (DB1.DBX0.0). Sensor 2 (I0.3) is in series with data blocks_1 of
sensors 1 and 2 (DB1.DBX0.3), 2 and 3 (DB1.DBX0.5), 1 and 2 and 3 (DB1. DBX0.6), which control the
output of data block_1 of sensor 2 (DB1.DBX0.1). Sensor 3 (I0.4) is in series with data blocks_1 of sensors 1
and 3 (DB1.DBX0.4), 2 and 3 (DB1.DBX0.5), 1 and 2 and 3 (DB1. DBX0.6), which control the output of
data block_1 of sensor 3 (DB1.DBX0.2).
Figure 4. Programming the lighting on and off and outlets
Figure 5. Programming the alarm history function block
Also in relation to the previous figure, in the function block in which the warning alarms are located,
we see that in segment 2, sensor 1 (I0.2) and sensor 2 (I0.3) are in series with the data block_1 of sensors 1
and 2 and 3 (DB1.DBX0.6), which control the output of data block_1 of sensors 1 and 2 (DB1.DBX0.3).
Sensor 2 (I0.3) and sensor 3 (I0.4) are in series with data block_1 of sensors 1 and 2 and 3 (DB1.DBX0.6),
which control the output of data block_1 from sensors 2 and 3 (DB1.DBX0.5). Sensor 1 (I0.2) and sensor 3
(I0.4) are in series with data block_1 of sensors 1 and 2 and 3 (DB1.DBX0.6), which control the output of
data block_1 from sensors 1 and 3 (DB1.DBX0.4).
 ISSN: 2502-4752
Indonesian J Elec Eng & Comp Sci, Vol. 21, No. 1, January 2021 : 92 - 100
96
Regarding SCADA, an OPC (KEP SERVER EX6) will be used, which will integrate the PLC, hmi
and computer. For this, a table of variables that are related to the PLC and that are in the OPC will be created
in order to connect it with the Wonderware (INTOCH) to perform the SCADA. Figure 6 shows the
programming for managing alarms in the InTouch, associated with the variables defined in the
KepServerEX6.
Figure 6. Programming the alarms on the InTouch
3. RESEARCH METHOD
3.1. Research level
The research carried out is descriptive, since it initially seeks to describe the operating conditions of
an automated fire system using a programmable Logico controller, and for the purposes of monitoring and
controlling its operation, a Supervision and Control (SCADA) system will be used). Descriptive research is
what is used, as the name implies, to describe the reality of situations, events, people, groups or communities
that are being addressed and that are intended to be analyzed [26].
Likewise, the research is correlational, since it will seek to determine the association level of the
values monitored by the SCADA Supervision and Control system, in order to establish if these measured
pressure and flow values are consistent with each other, thus validating the optimal performance of the fire
fighting system. Correlational research is a type of non-experimental research method in which an
investigator seeks to determine a degree of association between two variables [27]. Understand and evaluate
the statistical relationship between them without influencing the behavior of any variable.
3.2. Population and sample
The population is made up of the only analysis unit that in this case is represented by the automated
fire system using a Programmable Logic Controller; In this sense, by having a single analysis unit, the
population will also be represented only by the Automated Fire System through PLC [28].
3.3. Data collection
The data will be collected through observation through annotations in technical reports, which will
be obtained from the values provided by the same SCADA supervision and control system, which will be
permanently monitoring the fire system and its operational indicators [29]. It is important to specify that the
indicators to monitor are the pressure and flow of the Electric pump every time the sprinklers are activated.
4. RESULTS AND DISCUSSION
4.1. Results
Implemented the supervision and control system by SCADA for the automated fire fighting system,
prototype level the following results were obtained. In a first test: when the warehouse sensor detected the
fire, solenoid valve 1 was activated, with which the Water Pump operated at a low speed of 45 rpm
(revolutions per minute) and in the tank it can be observed that the pressure is 0.24 bar (pressure unit) and the
tank level was quantified in 14 Liters, all the lighting system and outlet were turned off in order to avoid
short circuits (the indicators light up in red), as shown in Figure 7.
Indonesian J Elec Eng & Comp Sci ISSN: 2502-4752 
Supervision and control by SCADA of an automated fire system (Omar Chamorro-Atalaya)
97
In a second test: when fire was generated in three zones, solenoid valve 1, solenoid valve 2 and
solenoid valve 3 were activated, with which the water pump operated at a high speed of 60 rpm and in the
tank the water level is 10.5 Liters, and the measured pressure turned out to be 0.6 bar, which is seen to
increase when more solenoid valves are added; as shown in Figure 8.
Figure 7. Result obtained from the pump pressure due to actuation of a solenoid valve
Figure 8. Result obtained from the pump pressure due to the actuation of three solenoid valves
Now in order to establish the level of correlation of the collected data, next I will perform the data
processing for each scenario, using the Pearson's correlation coefficient, because the variables under study
are of a quantitative type [30], for which the Spss V25 Statistics software will be used. Table 1 shows the
highly significant correlation.
Table 1. Pearson correlation analysis result
Flow
(liters/minute)
Pressure
(bar)
Flow
(liters/minute)
Pearson
Correlation
A powered sprayer 1 0.977**
Two powered sprinklers 1 0.983**
Three powered sprinklers 1 0.977**
Pressure
(bar)
Pearson
Correlation
A powered sprayer 0.977** 1
Two powered sprinklers 0.983** 1
Three powered sprinklers 0.977** 1
**. The correlation is significant at the level 0.01 (bilateral).
 ISSN: 2502-4752
Indonesian J Elec Eng & Comp Sci, Vol. 21, No. 1, January 2021 : 92 - 100
98
Additionally, the dispersion model of the collected data (pressure and flow) is determined through
the SCADA supervision and control system, in order to validate them. In this sense, the statistical software
Spss V25 will be used. From Figure 9, it is shown that the model that best represents the behavior of the data
collected in its three scenarios is the quadratic one; so also in Table 2, the determination coefficients R2
,
obtained from the Spss V25 Software, are shown for each of the scenarios analyzed.
Figure 9. Dispersion model of the collected data
Table 2. Result of the R2
of other dispersion
models analyzed
Equation
Model Summary
R 2 SIG.
A powered sprayer 0.988 0.000
Two powered sprinklers 0.999 0.000
Three powered sprinklers 0.999 0.000
4.2. Discussions
In relation to the results obtained, and having carried out the correlation analysis and the dispersion
model of the data obtained as part of the investigation. In relation to the objectives set as part of the
investigation, the following discussions are detailed below:
In reference to the supervision and control of the operating parameters of a prototype fire fighting
system, through a supervision and control system implemented through SCADA, it was possible to carry out
the effective monitoring of the operating parameters such as pressure and flow. Achieving that there is a
correlation between the variables under analysis, for the three scenarios proposed. In this sense, in the
investigation carried out by Rodriguez (2018), he points out that the SCADA system allowed monitoring the
pressure and flow parameters of a fire-fighting system, guaranteeing its operation, achieving a correlation of
its significant level variables [31].
Referring to the dispersion model that describes the behavior of the collected data such as pressure
and flow, it was found that in all three scenarios the model that best represents the quadratic model; in this
regard in the thesis related by Naranjo and Salazar (2016), a sign that the design and implementation of the
SCADA system allowed to monitor the pressure and flow rate of the system against fire, achieving to
determine that the behavior of said variables was of exponential type [32]. In this regard, this result could be
discussed because the control or regulation is not carried out through a frequency inverter but on the contrary,
they implement an Integrative and derivative proportional controller in the PLC; which does not allow to
achieve a better precision in the regulation of pressure and flow.
5. CONCLUSION
It is concluded that it managed to monitor and supervise the operating parameters such as pressure
and flow of a prototype fire fighting system, through a supervision and control system implemented through
SCADA, using the OPC KepServerEX6, which allowed the integration of the PLC, the human-machine
interface and the computer, ensuring that the monitored results for both pressure and flow are consistent and
reliable; It was possible to determine the level of correlation between the indicators to be monitored by the
SCADA system, under three scenarios, that is, when the drive is in a single sprinkler, or in two sprinklers or
in three sprinklers, a correlation level was obtained as a result. Highly significant equal to 0.977, 0.983 and
0.997 respectively.
Finally, it is concluded that it was possible to determine the dispersion model of the indicators
monitored by the SCADA system (pressure and flow), making an analysis of various dispersion models, such
as the linear, quadratic and exponential models using their determination fator, obtaining that the model that
Indonesian J Elec Eng & Comp Sci ISSN: 2502-4752 
Supervision and control by SCADA of an automated fire system (Omar Chamorro-Atalaya)
99
best represents the behavior in the three cases is the quadratic dispersion model, with an average
determination factor of 0.99 in the three scenarios experienced.
ACKNOWLEDGEMENTS
The authors wish to recognize and thank the National Technological University of South Lima for
their support of this investigation.
REFERENCES
[1] L. Orbe, “Analysis of Risks oriented to fires and proposal for improvement to be taken in the facilities of district
17D07 under the Ministry of Health,” M.S.thesis, University of the Americas, Quito, Ecuador, 2017.
[2] F. Fernández and J. Duarte, “Automation for monitoring and control of a group generator with electric start,”
Engineering and Technology Magazine, pp. 262-271, 2017.
[3] M. Poblete, et al., “Comprehensive system of supervision and control of occupational safety facilities in a UCO
department building,” Granada Conference Center, España, XV Adaluz Congress of Occupational Safety and
Health, pp. 47-56, 2015.
[4] A. Hahnemann, et al., “Fire safety evaluation: Alternative method applied to Brazilian Buildings,” Magazine of the
Latin American Association for Quality Control, Pathology and Recovery of Construction, pp. 186-199, 2017.
[5] D. Carrero, “Design of a Supervisory Control and Data Acquisition System (SCADA) for remote monitoring of
Energy systems,” M.S.thesis, University of Carabobo, Valencia, Venezuela, 2018.
[6] I. Antesana and A. Medina, “Edificis B.M.S Centralized Contreol System,” M.S.thesis, Catholic University of
Cordoba, Cordoba, Argentina, 2016.
[7] O. Ruiz, “Hydraulic fire protection systems, Design, Construction, Operation and Maintenance,” M.S.thesis,
Colombian School of Engineering Julio Garavito, Bogota, Colombia, 2016.
[8] G. Vargas, “Design and Description of an Automated Fire Protection System on a 45 meter yacht from Length,”
M.S. thesis, Catholic University of Santiago de Guayaquil, Guayaquil, Ecuador, 2016.
[9] L. García and E. Villarreal, “Implementation of a SCADA system for the automation of a biotechnology laboratory
of biological safety level,” Scientific threshold, vol. 14, pp. 119-129, 2018.
[10] J. Romero, “Control and Protection System against Fires for the General Hospital of Macas in the Province of
Morona Santiago,” M.S.thesis, Technical University of Ambato, Ambato, Ecuador, 2017.
[11] E. Cabrera and A. Aloma, “Fire Protection System for the Oil Industry,” Journal Hydraulic and Environmental
Engineering, pp. 33-47, 2016.
[12] J. Poma, et al., “Design, construction and implementation of an automated integrating system for flow, pressure and
temperature modules of the advanced manufacturing center,” Journal Systems and computing, pp. 90-95, 2017.
[13] J. Flores, “Supervision, Control and Integration by PLC of a Process that Simulates the Selection and Drilling of
Parts,” M.S. thesis, Polytechnic University of Catalonia, Catalunya, España, 2017.
[14] R. Andrade, “Teaching module to control water level and flow using SCADA system, PLC and PID algorithm,”
Journal RIEMAT, vol. 4, pp. 50-62, 2018.
[15] G. Sánchez and A. Custodio, “Development of SCADA system for flow control based on LINUX,” University,
Science and Technology, vol. 11, no. 44, pp. 121-128, 2017.
[16] G. Zapata, et al., “Aportes Metodológicos para el Diseño de Sistemas de Supervisión de Procesos Continuos,”
Journal Technological information, vol. 22, no. 3, pp. 97-114, 2010.
[17] E. Lopez, “SCADA Systems in Industrial Automation,” Journal Technology in Progress, pp. 3-14, 2017.
[18] L. Barzaga, et al., “SCADA Systems for the Automation of CIGB Production Processes,” Journal Electronic
Engineering, Automation and Communications, pp. 20-37, 2016.
[19] A. Rodríguez, et al., “Synchronization and Integration in SCADA of a process desalination,” Journal Electronic
Engineering, Automation and Communications, pp. 334-354, 2019.
[20] M. Ruiz, “Design of a SCADA module for practical teaching with Profibus communication and S7-1200 PLC’s for
the laboratory of the School of Electronic Engineering of the UNP,” M.S.thesis, National University of Piura, Piura,
Perú, 2016.
[21] J. Aguinsaca and C. Miranda, “Modeling and Monitoring of the Electrical System of the CT2 Transformation
Chamber,” M.S.thesis, University of the Armed Forces, Latacunga, Ecuador, 2016.
[22] J. Quezada, et al., “Design and implementation of a control and monitoring system based on HMI-PLC for a
drinking water well,” Engineering, research and technology, vol. 15, no. 1, pp. 41-50, 2018.
[23] I. Silipú, “Design of a SCADA System using Wonderware System Platform for monitoring the Electric
Interconnected of Lot 1AB of PlusPetrol,” M.S.thesis, Pedro Ruiz Gallo National University, Lambayeque, Perú,
2016.
[24] W. Ramos, “Design of a Semiautomatic Control using PLC s7-200 with SCADA Interface of a Biological Sludge
Water Treatment Plant,” M.S.thesis, National University of the Altiplano, Puno, Perú, 2016.
[25] J. Molano and L. Rodriguez, “Design of the Fire Fighting and Detection system for the Technological faculty of the
Francisco José Caldas District University,” M.S.thesis, Francisco José Caldas District University, Bogota,
Colombia, 2017.
[26] C. Bernal, “Investigation methodology,” Pearson Education, 2016.
[27] F. Arias, “The Research Project,” Sexta Edición, Mexico D.F, Mexico, Episteme, 2016.
 ISSN: 2502-4752
Indonesian J Elec Eng & Comp Sci, Vol. 21, No. 1, January 2021 : 92 - 100
100
[28] O. Atalaya, “Fire System for an Automated Electrical Substation via Programmable Logic Controller,” Advances in
Science, Technology and Engineering Systems Journal, vol. 4, no. 6, pp. 353-359, 2019.
[29] R. Hernandez, “Investigation methodology,” Décima Edición, Mexico D.F, Mexico, Mc Graw Hill, 2016.
[30] A. Hernández, et al., “Cientific investigation methodology,” Alicante: Ed. Innovation and Development Area,
2018.
[31] N. Rodriguez, “SCADA design to monitor fire alarms at the Lambayeque Chiclayo Regional Hospital,” M.S.thesis,
Cesar Vallejo University, Chiclayo, Perú, 2018.
[32] C. Naranjo and C. Salazar, “Design and implementation of a SCADA for the Supervision and Automatic Control of
the Fire System,” M.S.thesis, Salesina Polytechnic University of Quito, Quito, Ecuador, 2016.
BIOGRAPHIES OF AUTHORS
Omar Freddy Chamorro Atalaya is Electronic engineer, school and enabled with master's
degree in systems engineering. Master teacher in the industrial automation course. Professional
experience in industrial network automation projects in drinking water systems. Author of
several scientific articles in journals indexed in Scopus, in different areas, such as: Supervision
and Process Control, Industrial Automation, Solar Panels and Automation of Fire Systems.
Dora Yvonne Arce Santillan is graduated in electrician mechanical engineer at the National
Technological University of Lima Sur, colleged and enabled. With studies of Master in
Electrical Engineering with mention in Project Management. Author of several scientific articles
in journals indexed in Scopus, in different areas, such as: Supervision and Process Control,
Industrial Automation, Solar Panels, Automation of Fire Systems and Behavioral Sciences.
Teodoro Neri Diaz Leyva. He holds a Master's Degree in Systems Engineering, Professional
Title of Systems Engineer from the Federico Villarreal National University. He teaches at the
National Technological University of Lima Sur, specialized in Programming Languages,
Database, Software Engineering and Artificial Intelligence.
Martín Diaz Choque is is graduated electrician mechanical engineer at the National
Technological University of Lima Sur. Author of several scientific articles in journals indexed in
Scopus, in different areas, such as: Supervision and Process Control, Industrial Automation,
Solar Panels, Automation of Fire Systems and Behavioral Sciences.

More Related Content

Similar to Supervision and control by SCADA of an automated fire system

FAULT DETECTION AND DIAGNOSIS OF INDUCTION MACHINE WITH ON-LINE PARAMETER PR...
FAULT DETECTION AND DIAGNOSIS OF INDUCTION MACHINE  WITH ON-LINE PARAMETER PR...FAULT DETECTION AND DIAGNOSIS OF INDUCTION MACHINE  WITH ON-LINE PARAMETER PR...
FAULT DETECTION AND DIAGNOSIS OF INDUCTION MACHINE WITH ON-LINE PARAMETER PR...Sheikh R Manihar Ahmed
 
Introduction to Digital Computer Control System
Introduction to Digital Computer Control SystemIntroduction to Digital Computer Control System
Introduction to Digital Computer Control Systemturna67
 
Review of Online Monitoring of status of air for Automation with alarm
Review of Online Monitoring of status of air for Automation with alarmReview of Online Monitoring of status of air for Automation with alarm
Review of Online Monitoring of status of air for Automation with alarmiosrjce
 
PLC BASED PID IMPLEMENTATION IN PROCESS CONTROL OF TEMPERATURE FLOW AND LEVEL
PLC BASED PID IMPLEMENTATION IN PROCESS CONTROL OF TEMPERATURE FLOW AND LEVELPLC BASED PID IMPLEMENTATION IN PROCESS CONTROL OF TEMPERATURE FLOW AND LEVEL
PLC BASED PID IMPLEMENTATION IN PROCESS CONTROL OF TEMPERATURE FLOW AND LEVELIAEME Publication
 
Plc based pid implementation in process control of temperature flow and level
Plc based pid implementation in process control of temperature flow and levelPlc based pid implementation in process control of temperature flow and level
Plc based pid implementation in process control of temperature flow and levelIAEME Publication
 
An educational fuzzy temperature control system
An educational fuzzy temperature control system An educational fuzzy temperature control system
An educational fuzzy temperature control system IJECEIAES
 
IRJET- Building Management System and its Network Design
IRJET- Building Management System and its Network DesignIRJET- Building Management System and its Network Design
IRJET- Building Management System and its Network DesignIRJET Journal
 
SCADA - Wikipedia, the free encyclopedia
SCADA - Wikipedia, the free encyclopediaSCADA - Wikipedia, the free encyclopedia
SCADA - Wikipedia, the free encyclopediaRaj Bakshi
 
Design and simulation of remote monitoring of the intelligent automatic contr...
Design and simulation of remote monitoring of the intelligent automatic contr...Design and simulation of remote monitoring of the intelligent automatic contr...
Design and simulation of remote monitoring of the intelligent automatic contr...IAESIJAI
 
Monitoring and Controlling Of Electric Overhead Travelling Crane Using PLC an...
Monitoring and Controlling Of Electric Overhead Travelling Crane Using PLC an...Monitoring and Controlling Of Electric Overhead Travelling Crane Using PLC an...
Monitoring and Controlling Of Electric Overhead Travelling Crane Using PLC an...paperpublications3
 
Annunciator for Hazard Prevention & Temperature Control
Annunciator for Hazard Prevention & Temperature ControlAnnunciator for Hazard Prevention & Temperature Control
Annunciator for Hazard Prevention & Temperature ControlIOSR Journals
 
Introduction To SCADA
Introduction To SCADAIntroduction To SCADA
Introduction To SCADAKunal gupta
 
Arm Based Real Time Monitoring and Controlling of Industrial Parameters Using...
Arm Based Real Time Monitoring and Controlling of Industrial Parameters Using...Arm Based Real Time Monitoring and Controlling of Industrial Parameters Using...
Arm Based Real Time Monitoring and Controlling of Industrial Parameters Using...IJTET Journal
 
Simulation and Implementation of PLC Based for Detecting Burned Potato Chips ...
Simulation and Implementation of PLC Based for Detecting Burned Potato Chips ...Simulation and Implementation of PLC Based for Detecting Burned Potato Chips ...
Simulation and Implementation of PLC Based for Detecting Burned Potato Chips ...ijtsrd
 

Similar to Supervision and control by SCADA of an automated fire system (20)

Scada in hydropower plant
Scada  in  hydropower plantScada  in  hydropower plant
Scada in hydropower plant
 
FAULT DETECTION AND DIAGNOSIS OF INDUCTION MACHINE WITH ON-LINE PARAMETER PR...
FAULT DETECTION AND DIAGNOSIS OF INDUCTION MACHINE  WITH ON-LINE PARAMETER PR...FAULT DETECTION AND DIAGNOSIS OF INDUCTION MACHINE  WITH ON-LINE PARAMETER PR...
FAULT DETECTION AND DIAGNOSIS OF INDUCTION MACHINE WITH ON-LINE PARAMETER PR...
 
Introduction to Digital Computer Control System
Introduction to Digital Computer Control SystemIntroduction to Digital Computer Control System
Introduction to Digital Computer Control System
 
M010629597
M010629597M010629597
M010629597
 
Review of Online Monitoring of status of air for Automation with alarm
Review of Online Monitoring of status of air for Automation with alarmReview of Online Monitoring of status of air for Automation with alarm
Review of Online Monitoring of status of air for Automation with alarm
 
PLC BASED PID IMPLEMENTATION IN PROCESS CONTROL OF TEMPERATURE FLOW AND LEVEL
PLC BASED PID IMPLEMENTATION IN PROCESS CONTROL OF TEMPERATURE FLOW AND LEVELPLC BASED PID IMPLEMENTATION IN PROCESS CONTROL OF TEMPERATURE FLOW AND LEVEL
PLC BASED PID IMPLEMENTATION IN PROCESS CONTROL OF TEMPERATURE FLOW AND LEVEL
 
Plc based pid implementation in process control of temperature flow and level
Plc based pid implementation in process control of temperature flow and levelPlc based pid implementation in process control of temperature flow and level
Plc based pid implementation in process control of temperature flow and level
 
An educational fuzzy temperature control system
An educational fuzzy temperature control system An educational fuzzy temperature control system
An educational fuzzy temperature control system
 
IRJET- Building Management System and its Network Design
IRJET- Building Management System and its Network DesignIRJET- Building Management System and its Network Design
IRJET- Building Management System and its Network Design
 
SCADA - Wikipedia, the free encyclopedia
SCADA - Wikipedia, the free encyclopediaSCADA - Wikipedia, the free encyclopedia
SCADA - Wikipedia, the free encyclopedia
 
Design and simulation of remote monitoring of the intelligent automatic contr...
Design and simulation of remote monitoring of the intelligent automatic contr...Design and simulation of remote monitoring of the intelligent automatic contr...
Design and simulation of remote monitoring of the intelligent automatic contr...
 
Monitoring and Controlling Of Electric Overhead Travelling Crane Using PLC an...
Monitoring and Controlling Of Electric Overhead Travelling Crane Using PLC an...Monitoring and Controlling Of Electric Overhead Travelling Crane Using PLC an...
Monitoring and Controlling Of Electric Overhead Travelling Crane Using PLC an...
 
Annunciator for Hazard Prevention & Temperature Control
Annunciator for Hazard Prevention & Temperature ControlAnnunciator for Hazard Prevention & Temperature Control
Annunciator for Hazard Prevention & Temperature Control
 
Introduction To SCADA
Introduction To SCADAIntroduction To SCADA
Introduction To SCADA
 
Ajal 3
Ajal 3Ajal 3
Ajal 3
 
Plc & Scada report 4
Plc & Scada report 4Plc & Scada report 4
Plc & Scada report 4
 
Automation
AutomationAutomation
Automation
 
report
reportreport
report
 
Arm Based Real Time Monitoring and Controlling of Industrial Parameters Using...
Arm Based Real Time Monitoring and Controlling of Industrial Parameters Using...Arm Based Real Time Monitoring and Controlling of Industrial Parameters Using...
Arm Based Real Time Monitoring and Controlling of Industrial Parameters Using...
 
Simulation and Implementation of PLC Based for Detecting Burned Potato Chips ...
Simulation and Implementation of PLC Based for Detecting Burned Potato Chips ...Simulation and Implementation of PLC Based for Detecting Burned Potato Chips ...
Simulation and Implementation of PLC Based for Detecting Burned Potato Chips ...
 

More from nooriasukmaningtyas

A deep learning approach based on stochastic gradient descent and least absol...
A deep learning approach based on stochastic gradient descent and least absol...A deep learning approach based on stochastic gradient descent and least absol...
A deep learning approach based on stochastic gradient descent and least absol...nooriasukmaningtyas
 
Automated breast cancer detection system from breast mammogram using deep neu...
Automated breast cancer detection system from breast mammogram using deep neu...Automated breast cancer detection system from breast mammogram using deep neu...
Automated breast cancer detection system from breast mammogram using deep neu...nooriasukmaningtyas
 
Max stable set problem to found the initial centroids in clustering problem
Max stable set problem to found the initial centroids in clustering problemMax stable set problem to found the initial centroids in clustering problem
Max stable set problem to found the initial centroids in clustering problemnooriasukmaningtyas
 
Intelligent aquaculture system for pisciculture simulation using deep learnin...
Intelligent aquaculture system for pisciculture simulation using deep learnin...Intelligent aquaculture system for pisciculture simulation using deep learnin...
Intelligent aquaculture system for pisciculture simulation using deep learnin...nooriasukmaningtyas
 
Effective task scheduling algorithm in cloud computing with quality of servic...
Effective task scheduling algorithm in cloud computing with quality of servic...Effective task scheduling algorithm in cloud computing with quality of servic...
Effective task scheduling algorithm in cloud computing with quality of servic...nooriasukmaningtyas
 
Fixed point theorem between cone metric space and quasi-cone metric space
Fixed point theorem between cone metric space and quasi-cone metric spaceFixed point theorem between cone metric space and quasi-cone metric space
Fixed point theorem between cone metric space and quasi-cone metric spacenooriasukmaningtyas
 
Design of an environmental management information system for the Universidad ...
Design of an environmental management information system for the Universidad ...Design of an environmental management information system for the Universidad ...
Design of an environmental management information system for the Universidad ...nooriasukmaningtyas
 
K-NN supervised learning algorithm in the predictive analysis of the quality ...
K-NN supervised learning algorithm in the predictive analysis of the quality ...K-NN supervised learning algorithm in the predictive analysis of the quality ...
K-NN supervised learning algorithm in the predictive analysis of the quality ...nooriasukmaningtyas
 
Systematic literature review on university website quality
Systematic literature review on university website qualitySystematic literature review on university website quality
Systematic literature review on university website qualitynooriasukmaningtyas
 
An intelligent irrigation system based on internet of things (IoT) to minimiz...
An intelligent irrigation system based on internet of things (IoT) to minimiz...An intelligent irrigation system based on internet of things (IoT) to minimiz...
An intelligent irrigation system based on internet of things (IoT) to minimiz...nooriasukmaningtyas
 
Enhancement of observability using Kubernetes operator
Enhancement of observability using Kubernetes operatorEnhancement of observability using Kubernetes operator
Enhancement of observability using Kubernetes operatornooriasukmaningtyas
 
Customer churn analysis using XGBoosted decision trees
Customer churn analysis using XGBoosted decision treesCustomer churn analysis using XGBoosted decision trees
Customer churn analysis using XGBoosted decision treesnooriasukmaningtyas
 
Smart solution for reducing COVID-19 risk using internet of things
Smart solution for reducing COVID-19 risk using internet of thingsSmart solution for reducing COVID-19 risk using internet of things
Smart solution for reducing COVID-19 risk using internet of thingsnooriasukmaningtyas
 
Development of computer-based learning system for learning behavior analytics
Development of computer-based learning system for learning behavior analyticsDevelopment of computer-based learning system for learning behavior analytics
Development of computer-based learning system for learning behavior analyticsnooriasukmaningtyas
 
Efficiency of hybrid algorithm for COVID-19 online screening test based on it...
Efficiency of hybrid algorithm for COVID-19 online screening test based on it...Efficiency of hybrid algorithm for COVID-19 online screening test based on it...
Efficiency of hybrid algorithm for COVID-19 online screening test based on it...nooriasukmaningtyas
 
Comparative study of low power wide area network based on internet of things ...
Comparative study of low power wide area network based on internet of things ...Comparative study of low power wide area network based on internet of things ...
Comparative study of low power wide area network based on internet of things ...nooriasukmaningtyas
 
Fog attenuation penalty analysis in terrestrial optical wireless communicatio...
Fog attenuation penalty analysis in terrestrial optical wireless communicatio...Fog attenuation penalty analysis in terrestrial optical wireless communicatio...
Fog attenuation penalty analysis in terrestrial optical wireless communicatio...nooriasukmaningtyas
 
An approach for slow distributed denial of service attack detection and allev...
An approach for slow distributed denial of service attack detection and allev...An approach for slow distributed denial of service attack detection and allev...
An approach for slow distributed denial of service attack detection and allev...nooriasukmaningtyas
 
Design and simulation double Ku-band Vivaldi antenna
Design and simulation double Ku-band Vivaldi antennaDesign and simulation double Ku-band Vivaldi antenna
Design and simulation double Ku-band Vivaldi antennanooriasukmaningtyas
 
Coverage enhancements of vehicles users using mobile stations at 5G cellular ...
Coverage enhancements of vehicles users using mobile stations at 5G cellular ...Coverage enhancements of vehicles users using mobile stations at 5G cellular ...
Coverage enhancements of vehicles users using mobile stations at 5G cellular ...nooriasukmaningtyas
 

More from nooriasukmaningtyas (20)

A deep learning approach based on stochastic gradient descent and least absol...
A deep learning approach based on stochastic gradient descent and least absol...A deep learning approach based on stochastic gradient descent and least absol...
A deep learning approach based on stochastic gradient descent and least absol...
 
Automated breast cancer detection system from breast mammogram using deep neu...
Automated breast cancer detection system from breast mammogram using deep neu...Automated breast cancer detection system from breast mammogram using deep neu...
Automated breast cancer detection system from breast mammogram using deep neu...
 
Max stable set problem to found the initial centroids in clustering problem
Max stable set problem to found the initial centroids in clustering problemMax stable set problem to found the initial centroids in clustering problem
Max stable set problem to found the initial centroids in clustering problem
 
Intelligent aquaculture system for pisciculture simulation using deep learnin...
Intelligent aquaculture system for pisciculture simulation using deep learnin...Intelligent aquaculture system for pisciculture simulation using deep learnin...
Intelligent aquaculture system for pisciculture simulation using deep learnin...
 
Effective task scheduling algorithm in cloud computing with quality of servic...
Effective task scheduling algorithm in cloud computing with quality of servic...Effective task scheduling algorithm in cloud computing with quality of servic...
Effective task scheduling algorithm in cloud computing with quality of servic...
 
Fixed point theorem between cone metric space and quasi-cone metric space
Fixed point theorem between cone metric space and quasi-cone metric spaceFixed point theorem between cone metric space and quasi-cone metric space
Fixed point theorem between cone metric space and quasi-cone metric space
 
Design of an environmental management information system for the Universidad ...
Design of an environmental management information system for the Universidad ...Design of an environmental management information system for the Universidad ...
Design of an environmental management information system for the Universidad ...
 
K-NN supervised learning algorithm in the predictive analysis of the quality ...
K-NN supervised learning algorithm in the predictive analysis of the quality ...K-NN supervised learning algorithm in the predictive analysis of the quality ...
K-NN supervised learning algorithm in the predictive analysis of the quality ...
 
Systematic literature review on university website quality
Systematic literature review on university website qualitySystematic literature review on university website quality
Systematic literature review on university website quality
 
An intelligent irrigation system based on internet of things (IoT) to minimiz...
An intelligent irrigation system based on internet of things (IoT) to minimiz...An intelligent irrigation system based on internet of things (IoT) to minimiz...
An intelligent irrigation system based on internet of things (IoT) to minimiz...
 
Enhancement of observability using Kubernetes operator
Enhancement of observability using Kubernetes operatorEnhancement of observability using Kubernetes operator
Enhancement of observability using Kubernetes operator
 
Customer churn analysis using XGBoosted decision trees
Customer churn analysis using XGBoosted decision treesCustomer churn analysis using XGBoosted decision trees
Customer churn analysis using XGBoosted decision trees
 
Smart solution for reducing COVID-19 risk using internet of things
Smart solution for reducing COVID-19 risk using internet of thingsSmart solution for reducing COVID-19 risk using internet of things
Smart solution for reducing COVID-19 risk using internet of things
 
Development of computer-based learning system for learning behavior analytics
Development of computer-based learning system for learning behavior analyticsDevelopment of computer-based learning system for learning behavior analytics
Development of computer-based learning system for learning behavior analytics
 
Efficiency of hybrid algorithm for COVID-19 online screening test based on it...
Efficiency of hybrid algorithm for COVID-19 online screening test based on it...Efficiency of hybrid algorithm for COVID-19 online screening test based on it...
Efficiency of hybrid algorithm for COVID-19 online screening test based on it...
 
Comparative study of low power wide area network based on internet of things ...
Comparative study of low power wide area network based on internet of things ...Comparative study of low power wide area network based on internet of things ...
Comparative study of low power wide area network based on internet of things ...
 
Fog attenuation penalty analysis in terrestrial optical wireless communicatio...
Fog attenuation penalty analysis in terrestrial optical wireless communicatio...Fog attenuation penalty analysis in terrestrial optical wireless communicatio...
Fog attenuation penalty analysis in terrestrial optical wireless communicatio...
 
An approach for slow distributed denial of service attack detection and allev...
An approach for slow distributed denial of service attack detection and allev...An approach for slow distributed denial of service attack detection and allev...
An approach for slow distributed denial of service attack detection and allev...
 
Design and simulation double Ku-band Vivaldi antenna
Design and simulation double Ku-band Vivaldi antennaDesign and simulation double Ku-band Vivaldi antenna
Design and simulation double Ku-band Vivaldi antenna
 
Coverage enhancements of vehicles users using mobile stations at 5G cellular ...
Coverage enhancements of vehicles users using mobile stations at 5G cellular ...Coverage enhancements of vehicles users using mobile stations at 5G cellular ...
Coverage enhancements of vehicles users using mobile stations at 5G cellular ...
 

Recently uploaded

High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 

Recently uploaded (20)

High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 

Supervision and control by SCADA of an automated fire system

  • 1. Indonesian Journal of Electrical Engineering and Computer Science Vol. 21, No. 1, January 2021, pp. 92~100 ISSN: 2502-4752, DOI: 10.11591/ijeecs.v21.i1.pp92-100  92 Journal homepage: http://ijeecs.iaescore.com Supervision and control by SCADA of an automated fire system Omar Chamorro-Atalaya, Dora Arce-Santillan, Teodoro Diaz-Leyva, Martin Diaz-Choque Faculty of Engineering and Management, National Technological University of Lima Sur (UNTELS), Villa El Salvador, Perú Article Info ABSTRACT Article history: Received May 23, 2020 Revised Jul 28, 2020 Accepted Aug 8, 2020 The purpose of this article is to describe the development of a prototype of a monitoring and control system for a fire-fighting system, implemented through SCADA (supervisory control and data acquisition) for which the OPC (OLE for process control) is known. Known KepServerEX6 (single data source connectivity platform), with which the integration of the PLC (programmable logic controller), the human-machine interface (HMI) and the computer will be controlled, with the application of monitoring the operating parameters of a fire fighting system. These parameters are the pressure and flow of the electric pump, the values of the parameters are regularly controlled automatically by means of a frequency variator, according to the sprinkler actuation, the variator varies its operating frequency until achieving the optimal pressure and flow values. The level of correlation between the indicators to be monitored by the SCADA system is highly significant, equal to 0.977, 0.983 and 0.997 respectively. In addition, the dispersion model of the indicators monitored by the SCADA system will be determined, is the quadratic, with a determination factor of 0.999. Keywords: Automated control Open protocol communication Programmable logic controller Scada Sprayer Supervision Variable frequency drive This is an open access article under the CC BY-SA license. Corresponding Author: Omar Freddy Chamorro Atalaya Av. Central y Av. Bolivar Sector 3, Grupo 1A - 03, Villa El Salvador, Peru Email: omar_chamorro1@hotmail.com 1. INTRODUCTION Every organization where people work is exposed to the presence of risks, conditioned by the environment in which its activities are carried out [1]. In case of not being controlled these risks can be triggered by accidents and damage to property, which can be caused by natural effects or by acciodentes of people as part of their routine activities [2]. From the field of research, development and innovation and taking into account the evolution of technology, there are various electronic solutions that improve conditions in terms of security and fire protection in companies [3]. The risk of fire and explosion are two of the most important risks that must be controlled in the workplace. Electronic systems reduce response time to emergencies [4]. In the industry there are vital systems and equipment to keep the company's production process active, ensuring the availability and operation of all the emergency equipment present in the facilities [5]. To guarantee operational continuity in vital critical process and industrial safety equipment, a system is required to monitor the operating and operational parameters of the fire protection system [6]. A fire protection system is essential in all types of industrial warehouses, companies or buildings to safeguard human lives and minimize the economic losses caused by fire [7]. To determine the necessary prevention and protection measures that help reduce the risk of fire in buildings, the degree of risk must be evaluated [8]. It is important in this type of project to monitor and control the project from the beginning of the design to the operation and maintenance of the system, [9] defining the quality control mechanisms, the operational tests and the
  • 2. Indonesian J Elec Eng & Comp Sci ISSN: 2502-4752  Supervision and control by SCADA of an automated fire system (Omar Chamorro-Atalaya) 93 procedures that must be carried out for its correct operation ensuring that its pressure and flow indicators are adequate permanently [10]. In the case of underdeveloped countries that often do not have the economic resources necessary to invest in high-tech fire systems, which are usually very expensive and their function is only to protect, they make industries ignore this type of systems, the same that would harbor a high risk for the life of the workers [11]. For this reason, technology motivates companies to apply methodologies to control their processes [12]. The control and supervision in real time of a process is carried out through a control system called SCADA [13] which has hardware and software components that allow to supervise and control the industrial process [14]. This system monitors the process data for further processing and provides a communication interface between the user and the machine [15]. Process supervision generally refers to decision-making activities aimed at maintaining the functioning of the system [16]. The SCADA control system refers to control, supervision and data acquisition that allows the management and control of any local or remote system thanks to a graphical interface that communicates the user with the system [17]. A SCADA system is an application or set of software applications specially designed to work on production control computers, with access to the plant through digital communication with instruments and actuators, and a high-level graphic interface for the operator (touch screens, mice or cursors, styluses, etc.) [18]. It has the benefits of reducing engineering costs, time and risk through easy integration with all devices in the plant [19]. In order to integrate the SCADA system with the other components of the automated process, an OPC is used, which allows interoperability for the safe and reliable exchange of information in the space of industrial automation and in other industries [20]. It is used to ensure a continuous flow of information and overcome communication problems between controller devices or applications from multiple providers [21]. Also, the human machine interface (HMI), are used to represent the reality of processes [22]. The OPC standard is based on a series of specifications developed by industry vendors, end users and software developers and managed by the OPC that serve to define the interface between clients and servers, real-time data access, alarm monitoring and events, access to history among other applications [23]. OPC Servers are bi-directional connectors that allow you to "read from" and "write to" a Data source [24]. The relationship between the OPC Server and the OPC Client is of the master/slave type, which means that an OPC Server will only transfer data from/to a Data Source if an OPC Client requests it [25]. In this sense, the purpose of this article is to describe the development of a monitoring and control system implemented through SCADA, by using the OPC KepServerEX6, with which the integration of the programmable logic controller, the human-machine interface (HMI) will be achieved. And the computer, in order to monitor and control the parameters of a fire-fighting system, which is automated by means of a PLC; these parameters to control are the pressure and flow of the pump, when the sprinklers are activated. 2. PROCEDURE In order to control and supervise the operating parameters (pressure and flow) of the fire fighting system, implemented for an industrial warehouse, initially as a prototype, the architecture outlining the components is specified in Figure 1 of the industrial network. Figure 1. Network architecture of the control and supervision system of the fire fighting system Established the network architecture of the components that allow the supervision and control of the operating parameters of the fire fighting system, the procedure for programming the programmable logic controller and SCADA is shown Figure 2. SQL DB OPC SERVER ORDENADOR SCADA- HMI TCP /IP CONTROLLER S7-1212C-2DP PROFIBUS DECENTRALIZED PERIPHERY
  • 3.  ISSN: 2502-4752 Indonesian J Elec Eng & Comp Sci, Vol. 21, No. 1, January 2021 : 92 - 100 94 Initially, a variable table is created in which analog (0-10 volts) digital inputs (Boolean type) and digital outputs (Boolean type) are specified in the programmable logic controller register. Once the input and output variables are specified, programming is carried out in the PLC so that synergy is established between all the components that participate in the fire fighting system for monitoring and supervision. In Figure 2, the first segment of the programming of the fire system automation is shown, in which a block (type SR) called system (M0.0) is created in which a start button (start) is connected to the SET input and at the REST input, a normally closed (NC) button is connected, which is denially called ina stop, and at the output of the SR (Set Rest) block, a digital output Q0.3 is connected, indicating that the system is found on or off. One of the NA (normally open) contacts of the system block (M0.0) is in series with all the segments of the program in order to control them. Figure 3 shows the programming the frequency variator who will regulate the operation speed of the electric pump, which requires the use of 3 speeds (low, medium, high), which the PLC will control the variator (simatic V20). Furthermore, sensor 1 (I0.2), sensor 2 (I0.3) and sensor 3 (I0.4) are in parallel and all of them in series with the NC contacts (normally closed) of the average speeds (M0.3), high (M0.4) and with the NO contact of the system (M0.0), which control the switching on and off of the low speed (M0.2) and the hmi pump (M0.1). Figure 4 shows the programming of the on and off of the lighting and outlet outputs. In the third segment of this programming, the NO contacts of solenoid valves 1 (Q0.0), 2 (Q0.1) and 3 (Q0.2) are shown in series with the NO contact of the system (M0.0), the which control the lighting output (Q0.4) and outlet (Q0.5). Figure 2. Ignition system programming Figure 3. Programming the frequency inverter speeds
  • 4. Indonesian J Elec Eng & Comp Sci ISSN: 2502-4752  Supervision and control by SCADA of an automated fire system (Omar Chamorro-Atalaya) 95 In Figure 5, the alarm programming is carried out, in this function block, the warning alarms are found, it is observed in segment 1 that sensor 1 (I0.2) is in series with the data blocks_1 of sensors 1 and 2 (DB1.DBX0.3), 1 and 3 (DB1.DBX0.4), 1 and 2 and 3 (DB1.DBX0.6), the same ones that allow the control of the output of data block_1 Sensor 1 (DB1.DBX0.0). Sensor 2 (I0.3) is in series with data blocks_1 of sensors 1 and 2 (DB1.DBX0.3), 2 and 3 (DB1.DBX0.5), 1 and 2 and 3 (DB1. DBX0.6), which control the output of data block_1 of sensor 2 (DB1.DBX0.1). Sensor 3 (I0.4) is in series with data blocks_1 of sensors 1 and 3 (DB1.DBX0.4), 2 and 3 (DB1.DBX0.5), 1 and 2 and 3 (DB1. DBX0.6), which control the output of data block_1 of sensor 3 (DB1.DBX0.2). Figure 4. Programming the lighting on and off and outlets Figure 5. Programming the alarm history function block Also in relation to the previous figure, in the function block in which the warning alarms are located, we see that in segment 2, sensor 1 (I0.2) and sensor 2 (I0.3) are in series with the data block_1 of sensors 1 and 2 and 3 (DB1.DBX0.6), which control the output of data block_1 of sensors 1 and 2 (DB1.DBX0.3). Sensor 2 (I0.3) and sensor 3 (I0.4) are in series with data block_1 of sensors 1 and 2 and 3 (DB1.DBX0.6), which control the output of data block_1 from sensors 2 and 3 (DB1.DBX0.5). Sensor 1 (I0.2) and sensor 3 (I0.4) are in series with data block_1 of sensors 1 and 2 and 3 (DB1.DBX0.6), which control the output of data block_1 from sensors 1 and 3 (DB1.DBX0.4).
  • 5.  ISSN: 2502-4752 Indonesian J Elec Eng & Comp Sci, Vol. 21, No. 1, January 2021 : 92 - 100 96 Regarding SCADA, an OPC (KEP SERVER EX6) will be used, which will integrate the PLC, hmi and computer. For this, a table of variables that are related to the PLC and that are in the OPC will be created in order to connect it with the Wonderware (INTOCH) to perform the SCADA. Figure 6 shows the programming for managing alarms in the InTouch, associated with the variables defined in the KepServerEX6. Figure 6. Programming the alarms on the InTouch 3. RESEARCH METHOD 3.1. Research level The research carried out is descriptive, since it initially seeks to describe the operating conditions of an automated fire system using a programmable Logico controller, and for the purposes of monitoring and controlling its operation, a Supervision and Control (SCADA) system will be used). Descriptive research is what is used, as the name implies, to describe the reality of situations, events, people, groups or communities that are being addressed and that are intended to be analyzed [26]. Likewise, the research is correlational, since it will seek to determine the association level of the values monitored by the SCADA Supervision and Control system, in order to establish if these measured pressure and flow values are consistent with each other, thus validating the optimal performance of the fire fighting system. Correlational research is a type of non-experimental research method in which an investigator seeks to determine a degree of association between two variables [27]. Understand and evaluate the statistical relationship between them without influencing the behavior of any variable. 3.2. Population and sample The population is made up of the only analysis unit that in this case is represented by the automated fire system using a Programmable Logic Controller; In this sense, by having a single analysis unit, the population will also be represented only by the Automated Fire System through PLC [28]. 3.3. Data collection The data will be collected through observation through annotations in technical reports, which will be obtained from the values provided by the same SCADA supervision and control system, which will be permanently monitoring the fire system and its operational indicators [29]. It is important to specify that the indicators to monitor are the pressure and flow of the Electric pump every time the sprinklers are activated. 4. RESULTS AND DISCUSSION 4.1. Results Implemented the supervision and control system by SCADA for the automated fire fighting system, prototype level the following results were obtained. In a first test: when the warehouse sensor detected the fire, solenoid valve 1 was activated, with which the Water Pump operated at a low speed of 45 rpm (revolutions per minute) and in the tank it can be observed that the pressure is 0.24 bar (pressure unit) and the tank level was quantified in 14 Liters, all the lighting system and outlet were turned off in order to avoid short circuits (the indicators light up in red), as shown in Figure 7.
  • 6. Indonesian J Elec Eng & Comp Sci ISSN: 2502-4752  Supervision and control by SCADA of an automated fire system (Omar Chamorro-Atalaya) 97 In a second test: when fire was generated in three zones, solenoid valve 1, solenoid valve 2 and solenoid valve 3 were activated, with which the water pump operated at a high speed of 60 rpm and in the tank the water level is 10.5 Liters, and the measured pressure turned out to be 0.6 bar, which is seen to increase when more solenoid valves are added; as shown in Figure 8. Figure 7. Result obtained from the pump pressure due to actuation of a solenoid valve Figure 8. Result obtained from the pump pressure due to the actuation of three solenoid valves Now in order to establish the level of correlation of the collected data, next I will perform the data processing for each scenario, using the Pearson's correlation coefficient, because the variables under study are of a quantitative type [30], for which the Spss V25 Statistics software will be used. Table 1 shows the highly significant correlation. Table 1. Pearson correlation analysis result Flow (liters/minute) Pressure (bar) Flow (liters/minute) Pearson Correlation A powered sprayer 1 0.977** Two powered sprinklers 1 0.983** Three powered sprinklers 1 0.977** Pressure (bar) Pearson Correlation A powered sprayer 0.977** 1 Two powered sprinklers 0.983** 1 Three powered sprinklers 0.977** 1 **. The correlation is significant at the level 0.01 (bilateral).
  • 7.  ISSN: 2502-4752 Indonesian J Elec Eng & Comp Sci, Vol. 21, No. 1, January 2021 : 92 - 100 98 Additionally, the dispersion model of the collected data (pressure and flow) is determined through the SCADA supervision and control system, in order to validate them. In this sense, the statistical software Spss V25 will be used. From Figure 9, it is shown that the model that best represents the behavior of the data collected in its three scenarios is the quadratic one; so also in Table 2, the determination coefficients R2 , obtained from the Spss V25 Software, are shown for each of the scenarios analyzed. Figure 9. Dispersion model of the collected data Table 2. Result of the R2 of other dispersion models analyzed Equation Model Summary R 2 SIG. A powered sprayer 0.988 0.000 Two powered sprinklers 0.999 0.000 Three powered sprinklers 0.999 0.000 4.2. Discussions In relation to the results obtained, and having carried out the correlation analysis and the dispersion model of the data obtained as part of the investigation. In relation to the objectives set as part of the investigation, the following discussions are detailed below: In reference to the supervision and control of the operating parameters of a prototype fire fighting system, through a supervision and control system implemented through SCADA, it was possible to carry out the effective monitoring of the operating parameters such as pressure and flow. Achieving that there is a correlation between the variables under analysis, for the three scenarios proposed. In this sense, in the investigation carried out by Rodriguez (2018), he points out that the SCADA system allowed monitoring the pressure and flow parameters of a fire-fighting system, guaranteeing its operation, achieving a correlation of its significant level variables [31]. Referring to the dispersion model that describes the behavior of the collected data such as pressure and flow, it was found that in all three scenarios the model that best represents the quadratic model; in this regard in the thesis related by Naranjo and Salazar (2016), a sign that the design and implementation of the SCADA system allowed to monitor the pressure and flow rate of the system against fire, achieving to determine that the behavior of said variables was of exponential type [32]. In this regard, this result could be discussed because the control or regulation is not carried out through a frequency inverter but on the contrary, they implement an Integrative and derivative proportional controller in the PLC; which does not allow to achieve a better precision in the regulation of pressure and flow. 5. CONCLUSION It is concluded that it managed to monitor and supervise the operating parameters such as pressure and flow of a prototype fire fighting system, through a supervision and control system implemented through SCADA, using the OPC KepServerEX6, which allowed the integration of the PLC, the human-machine interface and the computer, ensuring that the monitored results for both pressure and flow are consistent and reliable; It was possible to determine the level of correlation between the indicators to be monitored by the SCADA system, under three scenarios, that is, when the drive is in a single sprinkler, or in two sprinklers or in three sprinklers, a correlation level was obtained as a result. Highly significant equal to 0.977, 0.983 and 0.997 respectively. Finally, it is concluded that it was possible to determine the dispersion model of the indicators monitored by the SCADA system (pressure and flow), making an analysis of various dispersion models, such as the linear, quadratic and exponential models using their determination fator, obtaining that the model that
  • 8. Indonesian J Elec Eng & Comp Sci ISSN: 2502-4752  Supervision and control by SCADA of an automated fire system (Omar Chamorro-Atalaya) 99 best represents the behavior in the three cases is the quadratic dispersion model, with an average determination factor of 0.99 in the three scenarios experienced. ACKNOWLEDGEMENTS The authors wish to recognize and thank the National Technological University of South Lima for their support of this investigation. REFERENCES [1] L. Orbe, “Analysis of Risks oriented to fires and proposal for improvement to be taken in the facilities of district 17D07 under the Ministry of Health,” M.S.thesis, University of the Americas, Quito, Ecuador, 2017. [2] F. Fernández and J. Duarte, “Automation for monitoring and control of a group generator with electric start,” Engineering and Technology Magazine, pp. 262-271, 2017. [3] M. Poblete, et al., “Comprehensive system of supervision and control of occupational safety facilities in a UCO department building,” Granada Conference Center, España, XV Adaluz Congress of Occupational Safety and Health, pp. 47-56, 2015. [4] A. Hahnemann, et al., “Fire safety evaluation: Alternative method applied to Brazilian Buildings,” Magazine of the Latin American Association for Quality Control, Pathology and Recovery of Construction, pp. 186-199, 2017. [5] D. Carrero, “Design of a Supervisory Control and Data Acquisition System (SCADA) for remote monitoring of Energy systems,” M.S.thesis, University of Carabobo, Valencia, Venezuela, 2018. [6] I. Antesana and A. Medina, “Edificis B.M.S Centralized Contreol System,” M.S.thesis, Catholic University of Cordoba, Cordoba, Argentina, 2016. [7] O. Ruiz, “Hydraulic fire protection systems, Design, Construction, Operation and Maintenance,” M.S.thesis, Colombian School of Engineering Julio Garavito, Bogota, Colombia, 2016. [8] G. Vargas, “Design and Description of an Automated Fire Protection System on a 45 meter yacht from Length,” M.S. thesis, Catholic University of Santiago de Guayaquil, Guayaquil, Ecuador, 2016. [9] L. García and E. Villarreal, “Implementation of a SCADA system for the automation of a biotechnology laboratory of biological safety level,” Scientific threshold, vol. 14, pp. 119-129, 2018. [10] J. Romero, “Control and Protection System against Fires for the General Hospital of Macas in the Province of Morona Santiago,” M.S.thesis, Technical University of Ambato, Ambato, Ecuador, 2017. [11] E. Cabrera and A. Aloma, “Fire Protection System for the Oil Industry,” Journal Hydraulic and Environmental Engineering, pp. 33-47, 2016. [12] J. Poma, et al., “Design, construction and implementation of an automated integrating system for flow, pressure and temperature modules of the advanced manufacturing center,” Journal Systems and computing, pp. 90-95, 2017. [13] J. Flores, “Supervision, Control and Integration by PLC of a Process that Simulates the Selection and Drilling of Parts,” M.S. thesis, Polytechnic University of Catalonia, Catalunya, España, 2017. [14] R. Andrade, “Teaching module to control water level and flow using SCADA system, PLC and PID algorithm,” Journal RIEMAT, vol. 4, pp. 50-62, 2018. [15] G. Sánchez and A. Custodio, “Development of SCADA system for flow control based on LINUX,” University, Science and Technology, vol. 11, no. 44, pp. 121-128, 2017. [16] G. Zapata, et al., “Aportes Metodológicos para el Diseño de Sistemas de Supervisión de Procesos Continuos,” Journal Technological information, vol. 22, no. 3, pp. 97-114, 2010. [17] E. Lopez, “SCADA Systems in Industrial Automation,” Journal Technology in Progress, pp. 3-14, 2017. [18] L. Barzaga, et al., “SCADA Systems for the Automation of CIGB Production Processes,” Journal Electronic Engineering, Automation and Communications, pp. 20-37, 2016. [19] A. Rodríguez, et al., “Synchronization and Integration in SCADA of a process desalination,” Journal Electronic Engineering, Automation and Communications, pp. 334-354, 2019. [20] M. Ruiz, “Design of a SCADA module for practical teaching with Profibus communication and S7-1200 PLC’s for the laboratory of the School of Electronic Engineering of the UNP,” M.S.thesis, National University of Piura, Piura, Perú, 2016. [21] J. Aguinsaca and C. Miranda, “Modeling and Monitoring of the Electrical System of the CT2 Transformation Chamber,” M.S.thesis, University of the Armed Forces, Latacunga, Ecuador, 2016. [22] J. Quezada, et al., “Design and implementation of a control and monitoring system based on HMI-PLC for a drinking water well,” Engineering, research and technology, vol. 15, no. 1, pp. 41-50, 2018. [23] I. Silipú, “Design of a SCADA System using Wonderware System Platform for monitoring the Electric Interconnected of Lot 1AB of PlusPetrol,” M.S.thesis, Pedro Ruiz Gallo National University, Lambayeque, Perú, 2016. [24] W. Ramos, “Design of a Semiautomatic Control using PLC s7-200 with SCADA Interface of a Biological Sludge Water Treatment Plant,” M.S.thesis, National University of the Altiplano, Puno, Perú, 2016. [25] J. Molano and L. Rodriguez, “Design of the Fire Fighting and Detection system for the Technological faculty of the Francisco José Caldas District University,” M.S.thesis, Francisco José Caldas District University, Bogota, Colombia, 2017. [26] C. Bernal, “Investigation methodology,” Pearson Education, 2016. [27] F. Arias, “The Research Project,” Sexta Edición, Mexico D.F, Mexico, Episteme, 2016.
  • 9.  ISSN: 2502-4752 Indonesian J Elec Eng & Comp Sci, Vol. 21, No. 1, January 2021 : 92 - 100 100 [28] O. Atalaya, “Fire System for an Automated Electrical Substation via Programmable Logic Controller,” Advances in Science, Technology and Engineering Systems Journal, vol. 4, no. 6, pp. 353-359, 2019. [29] R. Hernandez, “Investigation methodology,” Décima Edición, Mexico D.F, Mexico, Mc Graw Hill, 2016. [30] A. Hernández, et al., “Cientific investigation methodology,” Alicante: Ed. Innovation and Development Area, 2018. [31] N. Rodriguez, “SCADA design to monitor fire alarms at the Lambayeque Chiclayo Regional Hospital,” M.S.thesis, Cesar Vallejo University, Chiclayo, Perú, 2018. [32] C. Naranjo and C. Salazar, “Design and implementation of a SCADA for the Supervision and Automatic Control of the Fire System,” M.S.thesis, Salesina Polytechnic University of Quito, Quito, Ecuador, 2016. BIOGRAPHIES OF AUTHORS Omar Freddy Chamorro Atalaya is Electronic engineer, school and enabled with master's degree in systems engineering. Master teacher in the industrial automation course. Professional experience in industrial network automation projects in drinking water systems. Author of several scientific articles in journals indexed in Scopus, in different areas, such as: Supervision and Process Control, Industrial Automation, Solar Panels and Automation of Fire Systems. Dora Yvonne Arce Santillan is graduated in electrician mechanical engineer at the National Technological University of Lima Sur, colleged and enabled. With studies of Master in Electrical Engineering with mention in Project Management. Author of several scientific articles in journals indexed in Scopus, in different areas, such as: Supervision and Process Control, Industrial Automation, Solar Panels, Automation of Fire Systems and Behavioral Sciences. Teodoro Neri Diaz Leyva. He holds a Master's Degree in Systems Engineering, Professional Title of Systems Engineer from the Federico Villarreal National University. He teaches at the National Technological University of Lima Sur, specialized in Programming Languages, Database, Software Engineering and Artificial Intelligence. Martín Diaz Choque is is graduated electrician mechanical engineer at the National Technological University of Lima Sur. Author of several scientific articles in journals indexed in Scopus, in different areas, such as: Supervision and Process Control, Industrial Automation, Solar Panels, Automation of Fire Systems and Behavioral Sciences.