An effort
by
Virendra Sahdev
Introduction to IEC 61439:
A new standard on
Switchgear & Controlgear
Assemblies
IEC 60439 vs IEC 61439
 The new series of IEC 61439 standards were published in January 2009.
The new standard follows the philosophy of IEC 60947 series i.e. IEC 61439-1 is
‘General Rules’ standard to be referred to by subsidiary product parts
of IEC 61439 series. (Refer Table 1 below)
Introduction
 One of the main features of IEC 61439-1 is that the discrimination between
Type Tested Assemblies (TTA) and Partially Type Tested Assemblies (PTTA) has
been eliminated by the verification approach.
The three different but equivalent types of verification methods are introduced
and these are;
a) Verification by Testing.
b) Verification by Calculation/ Measurement.
c) Verification by Design rules.
The requirements regarding short circuit performance, temperature rise,
dielectric properties and rated diversity factor have been covered in more detail.
Introduction
Main Functions
Main Functions
Main Functions
Main Functions

Verification Requirements
Verification Requirements
Examples of the limitations and margins applied to
verification without type test include:
All assemblies connected to a supply with a prospective short circuit
current in excess of 10kA rms or having a cut-off current of 17kA peak must
be of a type-tested design or the verification must be an interpolation from a
reference design. Under no circumstances can the assigned short circuit
current rating be higher than that of the reference design.
So as to take account of the air temperature within the enclosure, thermal
interactions and possible hot spots; components within a circuit that has not
been temperature rise tested, must be de-rated to 80% of their free air
current rating.
Comparison of the power loss of the components within an assembly with
the known heat dissipation capability of an enclosure, is restricted to
assemblies having a rating of 630A.
Confirmation of temperature rise performance by calculation is limited to
assemblies with a rating not exceeding 1600A. Test or interpolation from a
tested design must be used to verify higher ratings.
Verification Requirements
Verification of temperature rise
For multiple compartment assembly, verification by calculation can be done up to
rated current of 1600 A only.
Assemblies, verified by design rule from a similar tested assembly, should comply
with the following:
oFunctional units shall belong to the same group as functional unit selected
for test.
oSame type of construction.
oSame or increased overall dimensions.
oSame or reduced internal separation.
oSame or reduced power losses in the same section of assembly.
oSame or reduced number of outgoing circuit for every section.
Rated diversity factor (RDF) is elaborated in more details with incoming and
outgoing circuit diagrams.
The average ambient temperature for the duration of test shall not exceed 35 oC.
Salient features of IEC 61439
Rated divers1ty factor (RDF):
The rated diversity factor is the per unit value of the rated current, assigned by the
assembly manufacturer, to which outgoing circuits of an assembly can be
continuously and simultaneously loaded taking into account the mutual thermal
influences.
Rated diversity factor can be stated:
• for groups of circuits;
• for the whole assembly.
The rated diversity factor multiplied by the rated current of the circuits shall be
equal to or higher than the assumed loading of the outgoing circuits. The assumed
loading of outgoing circuits shall be addressed by the relevant assembly standard,
The rated diversity factor is applicable with the ASSEMBLY operating at rated
current (lnA)
Salient features of IEC 61439
Short circuit withstand test
Following requirements are greater than or equal to reference design:
oCross-sectional dimensions of the busbars and connections
o Spacing of the busbars and connections
o SCPDs are equivalent, i.e. of the same make with the same or better I2t based on
the device manufacturer’s data
Following requirements are less than or equal to reference design:
oShort circuit rating of each circuit
o Busbar supports spacing
o Length of unprotected live conductors of each nonprotected circuit
Following requirements are same as that of reference design
o Conductor material and its properties
o Enclosure design, type and dimensions
o Compartment mechanical design and dimensions
If all the above requirements are satisfied, then further verification by
calculation or actual testing is not required.
Salient features of IEC 61439
Short circuit withstand test
Following requirements are greater than or equal to reference design:
oCross-sectional dimensions of the busbars and connections
o Spacing of the busbars and connections
o SCPDs are equivalent, i.e. of the same make with the same or better I2t based on
the device manufacturer’s data
Following requirements are less than or equal to reference design:
oShort circuit rating of each circuit
o Busbar supports spacing
o Length of unprotected live conductors of each nonprotected circuit
Following requirements are same as that of reference design
o Conductor material and its properties
o Enclosure design, type and dimensions
o Compartment mechanical design and dimensions
If all the above requirements are satisfied, then further verification by
calculation or actual testing is not required.
Salient features of IEC 61439
Short circuit withstand test
Following requirements are greater than or equal to reference design:
oCross-sectional dimensions of the busbars and connections
o Spacing of the busbars and connections
o SCPDs are equivalent, i.e. of the same make with the same or better I2t based on
the device manufacturer’s data
Following requirements are less than or equal to reference design:
oShort circuit rating of each circuit
o Busbar supports spacing
o Length of unprotected live conductors of each nonprotected circuit
Following requirements are same as that of reference design
o Conductor material and its properties
o Enclosure design, type and dimensions
o Compartment mechanical design and dimensions
If all the above requirements are satisfied, then further verification by
calculation or actual testing is not required.
Salient features of IEC 61439
Power frequency withstand voltage
The values of dielectric test voltage are reduced corresponding to rated insulation
voltage (Refer Table 3)
Salient features of IEC 61439
Impulse voltage withstand test
oVerification is mandatory either by test or by design rules.
o Test is not required when clearances in the assembly are 1.5 times the specified
value in Table - 4.
Salient features of IEC 61439
Degree of protection
oThe IPX1 to IPX6 tests on an assembly are deemed to be failure if water
comes into contact with electrical equipment housed within the enclosure.
o Requirements for ‘empty enclosures for assemblies (IEC 62208)’ have been
incorporated in the standard.
Mechanical operation
o Rated numbers of operating cycles have been increased from 50 to 200.
Protection provided by barriers
oThe protection provided by horizontal top surfaces of easily accessible barriers is
changed from IPXXB (the protection of person against access to hazardous parts
with finger) to IPXXD (the protection of person against access to hazardous parts
with wire).
Cross-section area of neutral
o 100% - for phase cross section area upto 16 mm2
o 50 % - for phase cross section area above 16 mm2, with a minimum of 16 mm2
o For conductor other than copper, the cross section should be greater than
equivalent copper conductor
Salient features of IEC 61439
Degree of protection
oThe protection provided by horizontal top surfaces of easily accessible barriers is
changed from IPXXB (the protection of person against access to hazardous parts
with finger) to IPXXD (the protection of person against access to hazardous parts
with wire).
Salient features of IEC 61439
Additional Tests in IEC 61439
Resistance to corrosion Test
Purpose:
oTo ensure that deterioration of metallic component caused by corrosion shall not
impair the mechanical strength of switchboard.
Procedure:
oThe test is carried out on a typical switchboard enclosure or on a representative
sample showing the same constructional details.
• 6 cycles of 24 hr each to Damp Heat Cycling Test according to IEC 60068-2-30 at
(40±3) o C & relative humidity of 95%.
Salient features of IEC 61439
Additional Tests in IEC 61439
Verification of Thermal stability
Purpose:
oTo check the thermal properties of the enclosure
Procedure:
o The specimen is kept in a heating chamber at 70 o C for 7 days. After that the
sample is kept
at ambient temperature for 4 days.
Assessment criteria:
o The sample shall show no cracks nor shall the material become sticky or greasy
Sample is pressed with the forefinger wrapped in a dry cloth with a force of 5 N; no
traces of cloth shall remain on the sample.
Salient features of IEC 61439
Additional Tests in IEC 61439
Verification of resistance of insulating materials to heat
Purpose:
To ensure the properties of insulating material to normal heat
Procedure:
o A ball pressure test apparatus is used to verify the suitability of insulating materials.
The test shall be carried out on an insulating material of minimum 2 mm thickness.
The test shall be made in a heating cabinet at a temperature as stated below:
o parts supporting live components – 125 o C
o other parts – 70 o C
o After 1 hr, the sample is removed and cooled within 10 s to approx. room temperature
by immersion in cold water.
Assessment criteria:
The diameter of the impression caused by the ball shall be measured and shall not
exceed 2 mm.
Salient features of IEC 61439
Additional Tests in IEC 61439
Resistance to abnormal heat & fire (Glow Wire Test)
Purpose:
Glow wire test checks the capability of insulation material to handle thermal stresses
produced by sources of heat or ignition.
Procedure:
Sample: Thinnest wall thickness of the completed application.
Pre-treatment: 24 hours at 23 o C at 50% RH.
Temperatures of glow wire: 650, 850 or 960 degrees C (depending on the
relevant specification).
•960 degrees C for parts necessary to retain cur rent carrying parts in position;
•850 degrees C for enclosures intended for mounting in hollow walls:
•650 degrees C for all other parts, including parts necessary to retain the protective
conductor.
Force: 1 N
Contact time: 30 s
Assessment criteria:
There is no flame and glowing on the sample or flames/glowing of the sample
extinguish within 30 s. The cotton or the paper underlay doesn’t ignite or burn.
Salient features of IEC 61439
Additional Tests in IEC 61439
Resistance to UV radiation
Purpose:
The UV radiation causes deterioration of synthetic material used for enclosures.
Procedure:
UV Test according to ISO 4892 – 2 method A; 1000 cycles of 5 min of watering and 25 min.
of dry period with xenon lamp providing a total test period of 500 hrs. The value of
temperature and humidity for the test are (65±3) o C and (65±5) %.
Assessment criteria:
Adherence of synthetic material (according to ISO 2409) shall have minimum 50%
retention. Sample shall not show cracks or deterioration visible to normal or corrected
vision without any additional magnification. This test is not required if synthetic material
supplier demonstrates that materials of same thickness or thinner comply with this
requirement.
NOTE: This test is applicable only for enclosures and external parts of ASSEMBLIES
intended to be installed Outdoors.
Salient features of IEC 61439
Additional Tests in IEC 61439
Lifting:
Purpose:
To ensure that there should be no damage to the panel during transportation & installation.
Procedure:
o The test is carried out on a sample having weight 1.25 times its maximum shipping weight.
o From a standstill position, the ASSEMBLY shall be raised smoothly without jerking in a vertical
plane to a height of (1±0.1) m and lowered in the same manner to a standstill
position. This test is repeated a further two times.
o After this the ASSEMBLY is raised up and suspended for 30 min at a height of (1±0.1) m without
any movement.
o Following this test the ASSEMBLY shall be raised smoothly without jerking from a standstill
position to a height of (1±0.1) m and moved (10±0.5) m horizontally, then lowered to a standstill
position.
o This sequence shall be carried out three times at uniform speed, each sequence being carried
out within 1 min.
Assessment criteria:
During the test, with the test weights in place, the ASSEMBLY shall show no deflections and after
the test show no cracks or permanent distortions visible to normal or corrected vision without
additional magnification, which could impair any of its characteristics.
Salient features of IEC 61439
Additional Tests in IEC 61439
Mechanical Impact Test
Purpose:
This test measures resistance of an enclosure towards external Mechanical Impact. The degree of
protection provided by an enclosure against impacts is indicated by the letters IK followed by two
digits depending on its ability to withstand the impact (as per IEC 62262).
Procedure:
o Number of impacts on each exposed face shall be five unless otherwise specified in relevant
product standard.
o The impacts shall be evenly distributed on the faces of the enclosure under test.
o At the surrounding of any point of enclosure, not more than three impacts shall be applied.
Assessment Criteria:
o Structural integrity shall be maintained.
o Degree of protection (IP) shall be unaffected.
o Functionality of electrical products shall not be hampered.
NOTE: Mechanical Impact test is not applicable to low voltage power switchgear and controlgear
(PSC) assemblies.
Salient features of IEC 61439
Additional Tests in IEC 61439
Marking:
Purpose:
To ensure that the markings are legible.
Procedure:
Marking made by moulding, pressing, engraving or similar
shall not be submitted to the following test.
The test is made by rubbing the marking by hand for 15 s
with a piece of cloth soaked in water and then for 15 s with a
piece of cloth soaked with petroleum spirit.
Assessment criteria:
After the test the marking shall be legible to normal or
corrected vision without additional magnification.
Salient features of IEC 61439
Previously a manufacturer had to assign a current rating to each circuit, but they
were never required by the standard to prove its rating. In accordance with the new
standard, the manufacturers have to verify the rating of each type of circuit.
Each type of circuit will have its rating verified within the assembly and the
capability of the assembly as a whole will be proven by loading adjacent outgoing
circuits to their rated current, multiplied by the diversity factor.
Historically it has been assumed that if nothing was said, the neutral could have a
current rating equal to 50% of that of its associated phase. However, because this
has not been stipulated in any low-voltage standards for many years, any query
could only be answered by it’s custom and practice. IEC 61439 includes a default
current rating in accordance with custom and practice for circuits with conductors
above 16mm², but a specifier can ask for a higher rating to suit the needs of his
application.
In addition the ongoing question in respect of forms of separation has been
answered.
A device’s integral enclosure, for example the case of a moulded case circuit
breaker, is
defined as a means of providing separation from an adjacent circuit.
Ambiguities clarified
Open-type and enclosed assemblies
- Enclosed assembly
An assembly is enclosed when there are protected panels on all its sides so as to provide a degree of protection
against direct contact not lower than IPXXB . Assemblies intended to be installed in common environments
shall be of enclosed type
- Open-type assembly
An assembly, with or without front covering, in which the live parts of the electrical equipment are accessible.
Such assemblies can be used only in places where skilled persons have access for their use.
External design
- Cubicle-type (column)
Used for large distribution and control equipment; mechanically joined multi-cubicle-type assemblies
are obtained by combining side by side more cubicle-type
assemblies.
- Desk-type
Used to control complex machines or plants in mechanical, iron and steel and chemical industries.
- Box-type
Intended to be mounted on a vertical plane, both jutting out as well as built-in; such assemblies are used
mainly for the department or area distribution in industrial or service sector environments.
- Multi-box-type
A combination of boxes, generally of protected type and with fixing flanges, each housing a functional
unit which may be an automatic circuit-breaker, a starter, a
socket completed with a blocking or protective circuitbreaker.
Classification of assemblies
Conditions of installation
- Assembly for indoor installation
Assembly which is designed for use in locations where the normal service
Conditions for indoor use as specified in the Std. IEC 61439-1 are fulfilled.
- Assembly for indoor installation
Assembly which is designed for use in locations where the normal service
conditions for outdoor use as specified in the Std. IEC 61439-1 are fulfilled.
- Stationary assembly
Assembly which is designed to be fixed at its place of installation, for instance to
the floor or to a wall, and to be used at this place.
- Movable assembly
Assembly which is designed so that it can readily be moved from one place of use to
another.
Classification of assemblies
With the ever-increasing pressures of demand for higher network
utilization, assembly design optimization and more stringent safety,
the changes included in the assembly standard IEC 61439-2 are
important and overdue.
All assemblies that do not have a specific product standard are
covered and there is no opportunity to avoid compliance.
In the new standard, the methods of confirming design performance
are practical and pragmatic, reflecting the different market needs
and ways in which assemblies are produced. Several alternative and
equivalent means of verifying a particular characteristic of an
assembly are included. These are defined and their use restricted.
Where alternatives to type tests are used, a compensatory approach is
taken and margins are added to ensure equivalence. Overall, the
standard is performance based.
Conclusion
IEC 61439-1 - Low-voltage switchgear and controlgear assemblies –
Part 1: General Rules
IEC 61439-2 - Low-voltage switchgear and controlgear assemblies –
Part 2: Power switchgear and controlgear assemblies
Introduction to IEC 61439: A new standard on Switchgear & Controlgear
Assemblies by Mr. A P Rao; Mr. D A Chavan; Mr. P Patel; Mr. T N Shah
Switchgear Design & Development Center
Improving safety and performance in electrical assemblies - A guide to IEC 61439-
2 by Schneider Electric
IEC 61439 The new Standard for Low-Voltage Switchgear Assemblies –
Changes and Effects in respect of Tests by GE Ronald Borchert, IPH Berlin
The new IEC 61439 Series – Technical Seminar, 10th November, 2010 – Singapore,
KEMA Quality
Bibliography
pdfslide.net_iec-61439pptx.pptx

More Related Content

What's hot

Raychem Saudi Arabia Ltd|AKBAR TRADING EST. SAUDI ARABIA| Lv joints TYCO- RA...
Raychem Saudi Arabia Ltd|AKBAR TRADING EST. SAUDI ARABIA| Lv joints  TYCO- RA...Raychem Saudi Arabia Ltd|AKBAR TRADING EST. SAUDI ARABIA| Lv joints  TYCO- RA...
Raychem Saudi Arabia Ltd|AKBAR TRADING EST. SAUDI ARABIA| Lv joints TYCO- RA...AKBAR TRADING
 
Transformer testing
Transformer testingTransformer testing
Transformer testingajayknows
 
Iec 61439 for_low_voltage_switchgear_and
Iec 61439 for_low_voltage_switchgear_andIec 61439 for_low_voltage_switchgear_and
Iec 61439 for_low_voltage_switchgear_andssuserfd2587
 
03. mantenimiento preventivo de transformadores abb
03. mantenimiento preventivo de transformadores  abb03. mantenimiento preventivo de transformadores  abb
03. mantenimiento preventivo de transformadores abbRAFAELFLORES167
 
BS 7671 - 18th Edition Widescreen PP Rev 4
BS 7671 - 18th Edition Widescreen PP Rev 4BS 7671 - 18th Edition Widescreen PP Rev 4
BS 7671 - 18th Edition Widescreen PP Rev 4Paul Meenan
 
IEEE-Alberta_Partial-Discharge.pdf
IEEE-Alberta_Partial-Discharge.pdfIEEE-Alberta_Partial-Discharge.pdf
IEEE-Alberta_Partial-Discharge.pdfNitinPandya14
 
Presentación tableros
Presentación tablerosPresentación tableros
Presentación tablerosPablo Maril
 
Vacuum Circuit Breaker (VCB) Working and Applications | Uses Of VCB
Vacuum Circuit Breaker (VCB) Working and Applications | Uses Of VCB Vacuum Circuit Breaker (VCB) Working and Applications | Uses Of VCB
Vacuum Circuit Breaker (VCB) Working and Applications | Uses Of VCB System Protection
 
Panel LV Type Test Blokset Schneider
Panel LV Type Test Blokset SchneiderPanel LV Type Test Blokset Schneider
Panel LV Type Test Blokset SchneiderHenry Yosua Sidabutar
 
2.components in a substation breaker
2.components in a substation   breaker2.components in a substation   breaker
2.components in a substation breakerayyadurai SHANMUGAM
 
An introduction to FUSES
An introduction to FUSESAn introduction to FUSES
An introduction to FUSESPraveen Kumar
 
Switchgear.pptx
Switchgear.pptxSwitchgear.pptx
Switchgear.pptxsatabdi8
 
Furan Testing of Transformers Oil
Furan Testing of Transformers OilFuran Testing of Transformers Oil
Furan Testing of Transformers OilNitish Kumar
 
Tan delta test for power transformers
Tan delta test for power transformersTan delta test for power transformers
Tan delta test for power transformersjibinjoy1988
 
Dissolved gas analysis of power transformer oil
Dissolved gas analysis of power transformer oilDissolved gas analysis of power transformer oil
Dissolved gas analysis of power transformer oilSHIVAJI CHOUDHURY
 
Example of Substation Maintenance & Assessment Audits for Training - Niels In...
Example of Substation Maintenance & Assessment Audits for Training - Niels In...Example of Substation Maintenance & Assessment Audits for Training - Niels In...
Example of Substation Maintenance & Assessment Audits for Training - Niels In...Niels Inderbiethen
 

What's hot (20)

Raychem Saudi Arabia Ltd|AKBAR TRADING EST. SAUDI ARABIA| Lv joints TYCO- RA...
Raychem Saudi Arabia Ltd|AKBAR TRADING EST. SAUDI ARABIA| Lv joints  TYCO- RA...Raychem Saudi Arabia Ltd|AKBAR TRADING EST. SAUDI ARABIA| Lv joints  TYCO- RA...
Raychem Saudi Arabia Ltd|AKBAR TRADING EST. SAUDI ARABIA| Lv joints TYCO- RA...
 
adw2q2qsad
adw2q2qsadadw2q2qsad
adw2q2qsad
 
Transformer testing
Transformer testingTransformer testing
Transformer testing
 
Iec 61439 for_low_voltage_switchgear_and
Iec 61439 for_low_voltage_switchgear_andIec 61439 for_low_voltage_switchgear_and
Iec 61439 for_low_voltage_switchgear_and
 
RTCC & AVR
RTCC & AVRRTCC & AVR
RTCC & AVR
 
EHVAC TRANSMISSION LINE MAINTENANCE TECHNIQUES IN INDIAN PERSPECTIVE-A REVIEW
EHVAC TRANSMISSION LINE MAINTENANCE TECHNIQUES IN INDIAN PERSPECTIVE-A REVIEWEHVAC TRANSMISSION LINE MAINTENANCE TECHNIQUES IN INDIAN PERSPECTIVE-A REVIEW
EHVAC TRANSMISSION LINE MAINTENANCE TECHNIQUES IN INDIAN PERSPECTIVE-A REVIEW
 
03. mantenimiento preventivo de transformadores abb
03. mantenimiento preventivo de transformadores  abb03. mantenimiento preventivo de transformadores  abb
03. mantenimiento preventivo de transformadores abb
 
BS 7671 - 18th Edition Widescreen PP Rev 4
BS 7671 - 18th Edition Widescreen PP Rev 4BS 7671 - 18th Edition Widescreen PP Rev 4
BS 7671 - 18th Edition Widescreen PP Rev 4
 
IEEE-Alberta_Partial-Discharge.pdf
IEEE-Alberta_Partial-Discharge.pdfIEEE-Alberta_Partial-Discharge.pdf
IEEE-Alberta_Partial-Discharge.pdf
 
Presentación tableros
Presentación tablerosPresentación tableros
Presentación tableros
 
Vcb ppt.
Vcb ppt.Vcb ppt.
Vcb ppt.
 
Vacuum Circuit Breaker (VCB) Working and Applications | Uses Of VCB
Vacuum Circuit Breaker (VCB) Working and Applications | Uses Of VCB Vacuum Circuit Breaker (VCB) Working and Applications | Uses Of VCB
Vacuum Circuit Breaker (VCB) Working and Applications | Uses Of VCB
 
Panel LV Type Test Blokset Schneider
Panel LV Type Test Blokset SchneiderPanel LV Type Test Blokset Schneider
Panel LV Type Test Blokset Schneider
 
2.components in a substation breaker
2.components in a substation   breaker2.components in a substation   breaker
2.components in a substation breaker
 
An introduction to FUSES
An introduction to FUSESAn introduction to FUSES
An introduction to FUSES
 
Switchgear.pptx
Switchgear.pptxSwitchgear.pptx
Switchgear.pptx
 
Furan Testing of Transformers Oil
Furan Testing of Transformers OilFuran Testing of Transformers Oil
Furan Testing of Transformers Oil
 
Tan delta test for power transformers
Tan delta test for power transformersTan delta test for power transformers
Tan delta test for power transformers
 
Dissolved gas analysis of power transformer oil
Dissolved gas analysis of power transformer oilDissolved gas analysis of power transformer oil
Dissolved gas analysis of power transformer oil
 
Example of Substation Maintenance & Assessment Audits for Training - Niels In...
Example of Substation Maintenance & Assessment Audits for Training - Niels In...Example of Substation Maintenance & Assessment Audits for Training - Niels In...
Example of Substation Maintenance & Assessment Audits for Training - Niels In...
 

Similar to pdfslide.net_iec-61439pptx.pptx

Busbar Presentation2.pdf
Busbar Presentation2.pdfBusbar Presentation2.pdf
Busbar Presentation2.pdfNooruddinKhan22
 
06612 iec zerti_rz11_e
06612 iec zerti_rz11_e06612 iec zerti_rz11_e
06612 iec zerti_rz11_eCesar Chilet
 
Isolator and bushing
Isolator and bushingIsolator and bushing
Isolator and bushingNovia Putri
 
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...Ali Sepehri
 
2015 Arc Flash Conference MV Switchgear Standards
2015 Arc Flash Conference MV Switchgear Standards2015 Arc Flash Conference MV Switchgear Standards
2015 Arc Flash Conference MV Switchgear StandardsBryan Johnson
 
Benefits of using iec 61439 standard in electrical busbar systems
Benefits of using iec 61439 standard in electrical busbar systemsBenefits of using iec 61439 standard in electrical busbar systems
Benefits of using iec 61439 standard in electrical busbar systemsMessung Electrical Engineering
 
FAQ's: new-switchboard-standard-as-nzs-61439
FAQ's: new-switchboard-standard-as-nzs-61439FAQ's: new-switchboard-standard-as-nzs-61439
FAQ's: new-switchboard-standard-as-nzs-61439Dara Switchboards
 
Shyam cable catalogue
Shyam cable catalogueShyam cable catalogue
Shyam cable catalogueuibsamit87
 
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERDIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERRitesh Kumawat
 
Customer webinar 5
Customer webinar 5Customer webinar 5
Customer webinar 5gbsdirect
 
13-Webinar-Transformer-Maintenance-Testing-Fundamentals-06-26-18.pdf
13-Webinar-Transformer-Maintenance-Testing-Fundamentals-06-26-18.pdf13-Webinar-Transformer-Maintenance-Testing-Fundamentals-06-26-18.pdf
13-Webinar-Transformer-Maintenance-Testing-Fundamentals-06-26-18.pdfvikram desai
 
A study on IEC 60947- 2 amendments
A study on IEC 60947- 2 amendmentsA study on IEC 60947- 2 amendments
A study on IEC 60947- 2 amendmentsricha diptisikha
 
Development and testing of ipc
Development and testing of ipcDevelopment and testing of ipc
Development and testing of ipcHarish Agarwal
 
Pfisterer Electrical Safety Equipment - Voltage Detectors, Phase Comparators,...
Pfisterer Electrical Safety Equipment - Voltage Detectors, Phase Comparators,...Pfisterer Electrical Safety Equipment - Voltage Detectors, Phase Comparators,...
Pfisterer Electrical Safety Equipment - Voltage Detectors, Phase Comparators,...Thorne & Derrick International
 
conf-type-test-2007-03.ppt
conf-type-test-2007-03.pptconf-type-test-2007-03.ppt
conf-type-test-2007-03.pptssuser1f60f6
 
Quality control (training course)
Quality control (training course)Quality control (training course)
Quality control (training course)fikireyesus
 
Quality control (training course)
Quality control (training course)Quality control (training course)
Quality control (training course)fikireyesus
 
Safety On Rangehood from A perspective of UL 507
Safety On Rangehood from A perspective of UL 507Safety On Rangehood from A perspective of UL 507
Safety On Rangehood from A perspective of UL 507W LY
 

Similar to pdfslide.net_iec-61439pptx.pptx (20)

Busbar Presentation2.pdf
Busbar Presentation2.pdfBusbar Presentation2.pdf
Busbar Presentation2.pdf
 
06612 iec zerti_rz11_e
06612 iec zerti_rz11_e06612 iec zerti_rz11_e
06612 iec zerti_rz11_e
 
Isolator and bushing
Isolator and bushingIsolator and bushing
Isolator and bushing
 
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
 
2015 Arc Flash Conference MV Switchgear Standards
2015 Arc Flash Conference MV Switchgear Standards2015 Arc Flash Conference MV Switchgear Standards
2015 Arc Flash Conference MV Switchgear Standards
 
Benefits of using iec 61439 standard in electrical busbar systems
Benefits of using iec 61439 standard in electrical busbar systemsBenefits of using iec 61439 standard in electrical busbar systems
Benefits of using iec 61439 standard in electrical busbar systems
 
FAQ's: new-switchboard-standard-as-nzs-61439
FAQ's: new-switchboard-standard-as-nzs-61439FAQ's: new-switchboard-standard-as-nzs-61439
FAQ's: new-switchboard-standard-as-nzs-61439
 
Shyam cable catalogue
Shyam cable catalogueShyam cable catalogue
Shyam cable catalogue
 
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERDIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
 
Customer webinar 5
Customer webinar 5Customer webinar 5
Customer webinar 5
 
13-Webinar-Transformer-Maintenance-Testing-Fundamentals-06-26-18.pdf
13-Webinar-Transformer-Maintenance-Testing-Fundamentals-06-26-18.pdf13-Webinar-Transformer-Maintenance-Testing-Fundamentals-06-26-18.pdf
13-Webinar-Transformer-Maintenance-Testing-Fundamentals-06-26-18.pdf
 
A study on IEC 60947- 2 amendments
A study on IEC 60947- 2 amendmentsA study on IEC 60947- 2 amendments
A study on IEC 60947- 2 amendments
 
Development and testing of ipc
Development and testing of ipcDevelopment and testing of ipc
Development and testing of ipc
 
Test Switch Operation, Specifications & Accesories
Test Switch Operation, Specifications & Accesories Test Switch Operation, Specifications & Accesories
Test Switch Operation, Specifications & Accesories
 
Ellis Patents Cable Cleats Guide - Black Book
Ellis Patents Cable Cleats Guide - Black BookEllis Patents Cable Cleats Guide - Black Book
Ellis Patents Cable Cleats Guide - Black Book
 
Pfisterer Electrical Safety Equipment - Voltage Detectors, Phase Comparators,...
Pfisterer Electrical Safety Equipment - Voltage Detectors, Phase Comparators,...Pfisterer Electrical Safety Equipment - Voltage Detectors, Phase Comparators,...
Pfisterer Electrical Safety Equipment - Voltage Detectors, Phase Comparators,...
 
conf-type-test-2007-03.ppt
conf-type-test-2007-03.pptconf-type-test-2007-03.ppt
conf-type-test-2007-03.ppt
 
Quality control (training course)
Quality control (training course)Quality control (training course)
Quality control (training course)
 
Quality control (training course)
Quality control (training course)Quality control (training course)
Quality control (training course)
 
Safety On Rangehood from A perspective of UL 507
Safety On Rangehood from A perspective of UL 507Safety On Rangehood from A perspective of UL 507
Safety On Rangehood from A perspective of UL 507
 

Recently uploaded

HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
High Profile Call Girls Dahisar Arpita 9907093804 Independent Escort Service ...
High Profile Call Girls Dahisar Arpita 9907093804 Independent Escort Service ...High Profile Call Girls Dahisar Arpita 9907093804 Independent Escort Service ...
High Profile Call Girls Dahisar Arpita 9907093804 Independent Escort Service ...Call girls in Ahmedabad High profile
 

Recently uploaded (20)

HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
High Profile Call Girls Dahisar Arpita 9907093804 Independent Escort Service ...
High Profile Call Girls Dahisar Arpita 9907093804 Independent Escort Service ...High Profile Call Girls Dahisar Arpita 9907093804 Independent Escort Service ...
High Profile Call Girls Dahisar Arpita 9907093804 Independent Escort Service ...
 

pdfslide.net_iec-61439pptx.pptx

  • 1. An effort by Virendra Sahdev Introduction to IEC 61439: A new standard on Switchgear & Controlgear Assemblies
  • 2. IEC 60439 vs IEC 61439
  • 3.  The new series of IEC 61439 standards were published in January 2009. The new standard follows the philosophy of IEC 60947 series i.e. IEC 61439-1 is ‘General Rules’ standard to be referred to by subsidiary product parts of IEC 61439 series. (Refer Table 1 below) Introduction
  • 4.  One of the main features of IEC 61439-1 is that the discrimination between Type Tested Assemblies (TTA) and Partially Type Tested Assemblies (PTTA) has been eliminated by the verification approach. The three different but equivalent types of verification methods are introduced and these are; a) Verification by Testing. b) Verification by Calculation/ Measurement. c) Verification by Design rules. The requirements regarding short circuit performance, temperature rise, dielectric properties and rated diversity factor have been covered in more detail. Introduction
  • 11. Examples of the limitations and margins applied to verification without type test include: All assemblies connected to a supply with a prospective short circuit current in excess of 10kA rms or having a cut-off current of 17kA peak must be of a type-tested design or the verification must be an interpolation from a reference design. Under no circumstances can the assigned short circuit current rating be higher than that of the reference design. So as to take account of the air temperature within the enclosure, thermal interactions and possible hot spots; components within a circuit that has not been temperature rise tested, must be de-rated to 80% of their free air current rating. Comparison of the power loss of the components within an assembly with the known heat dissipation capability of an enclosure, is restricted to assemblies having a rating of 630A. Confirmation of temperature rise performance by calculation is limited to assemblies with a rating not exceeding 1600A. Test or interpolation from a tested design must be used to verify higher ratings. Verification Requirements
  • 12. Verification of temperature rise For multiple compartment assembly, verification by calculation can be done up to rated current of 1600 A only. Assemblies, verified by design rule from a similar tested assembly, should comply with the following: oFunctional units shall belong to the same group as functional unit selected for test. oSame type of construction. oSame or increased overall dimensions. oSame or reduced internal separation. oSame or reduced power losses in the same section of assembly. oSame or reduced number of outgoing circuit for every section. Rated diversity factor (RDF) is elaborated in more details with incoming and outgoing circuit diagrams. The average ambient temperature for the duration of test shall not exceed 35 oC. Salient features of IEC 61439
  • 13. Rated divers1ty factor (RDF): The rated diversity factor is the per unit value of the rated current, assigned by the assembly manufacturer, to which outgoing circuits of an assembly can be continuously and simultaneously loaded taking into account the mutual thermal influences. Rated diversity factor can be stated: • for groups of circuits; • for the whole assembly. The rated diversity factor multiplied by the rated current of the circuits shall be equal to or higher than the assumed loading of the outgoing circuits. The assumed loading of outgoing circuits shall be addressed by the relevant assembly standard, The rated diversity factor is applicable with the ASSEMBLY operating at rated current (lnA) Salient features of IEC 61439
  • 14. Short circuit withstand test Following requirements are greater than or equal to reference design: oCross-sectional dimensions of the busbars and connections o Spacing of the busbars and connections o SCPDs are equivalent, i.e. of the same make with the same or better I2t based on the device manufacturer’s data Following requirements are less than or equal to reference design: oShort circuit rating of each circuit o Busbar supports spacing o Length of unprotected live conductors of each nonprotected circuit Following requirements are same as that of reference design o Conductor material and its properties o Enclosure design, type and dimensions o Compartment mechanical design and dimensions If all the above requirements are satisfied, then further verification by calculation or actual testing is not required. Salient features of IEC 61439
  • 15. Short circuit withstand test Following requirements are greater than or equal to reference design: oCross-sectional dimensions of the busbars and connections o Spacing of the busbars and connections o SCPDs are equivalent, i.e. of the same make with the same or better I2t based on the device manufacturer’s data Following requirements are less than or equal to reference design: oShort circuit rating of each circuit o Busbar supports spacing o Length of unprotected live conductors of each nonprotected circuit Following requirements are same as that of reference design o Conductor material and its properties o Enclosure design, type and dimensions o Compartment mechanical design and dimensions If all the above requirements are satisfied, then further verification by calculation or actual testing is not required. Salient features of IEC 61439
  • 16. Short circuit withstand test Following requirements are greater than or equal to reference design: oCross-sectional dimensions of the busbars and connections o Spacing of the busbars and connections o SCPDs are equivalent, i.e. of the same make with the same or better I2t based on the device manufacturer’s data Following requirements are less than or equal to reference design: oShort circuit rating of each circuit o Busbar supports spacing o Length of unprotected live conductors of each nonprotected circuit Following requirements are same as that of reference design o Conductor material and its properties o Enclosure design, type and dimensions o Compartment mechanical design and dimensions If all the above requirements are satisfied, then further verification by calculation or actual testing is not required. Salient features of IEC 61439
  • 17. Power frequency withstand voltage The values of dielectric test voltage are reduced corresponding to rated insulation voltage (Refer Table 3) Salient features of IEC 61439
  • 18. Impulse voltage withstand test oVerification is mandatory either by test or by design rules. o Test is not required when clearances in the assembly are 1.5 times the specified value in Table - 4. Salient features of IEC 61439
  • 19. Degree of protection oThe IPX1 to IPX6 tests on an assembly are deemed to be failure if water comes into contact with electrical equipment housed within the enclosure. o Requirements for ‘empty enclosures for assemblies (IEC 62208)’ have been incorporated in the standard. Mechanical operation o Rated numbers of operating cycles have been increased from 50 to 200. Protection provided by barriers oThe protection provided by horizontal top surfaces of easily accessible barriers is changed from IPXXB (the protection of person against access to hazardous parts with finger) to IPXXD (the protection of person against access to hazardous parts with wire). Cross-section area of neutral o 100% - for phase cross section area upto 16 mm2 o 50 % - for phase cross section area above 16 mm2, with a minimum of 16 mm2 o For conductor other than copper, the cross section should be greater than equivalent copper conductor Salient features of IEC 61439
  • 20. Degree of protection oThe protection provided by horizontal top surfaces of easily accessible barriers is changed from IPXXB (the protection of person against access to hazardous parts with finger) to IPXXD (the protection of person against access to hazardous parts with wire). Salient features of IEC 61439
  • 21. Additional Tests in IEC 61439 Resistance to corrosion Test Purpose: oTo ensure that deterioration of metallic component caused by corrosion shall not impair the mechanical strength of switchboard. Procedure: oThe test is carried out on a typical switchboard enclosure or on a representative sample showing the same constructional details. • 6 cycles of 24 hr each to Damp Heat Cycling Test according to IEC 60068-2-30 at (40±3) o C & relative humidity of 95%. Salient features of IEC 61439
  • 22. Additional Tests in IEC 61439 Verification of Thermal stability Purpose: oTo check the thermal properties of the enclosure Procedure: o The specimen is kept in a heating chamber at 70 o C for 7 days. After that the sample is kept at ambient temperature for 4 days. Assessment criteria: o The sample shall show no cracks nor shall the material become sticky or greasy Sample is pressed with the forefinger wrapped in a dry cloth with a force of 5 N; no traces of cloth shall remain on the sample. Salient features of IEC 61439
  • 23. Additional Tests in IEC 61439 Verification of resistance of insulating materials to heat Purpose: To ensure the properties of insulating material to normal heat Procedure: o A ball pressure test apparatus is used to verify the suitability of insulating materials. The test shall be carried out on an insulating material of minimum 2 mm thickness. The test shall be made in a heating cabinet at a temperature as stated below: o parts supporting live components – 125 o C o other parts – 70 o C o After 1 hr, the sample is removed and cooled within 10 s to approx. room temperature by immersion in cold water. Assessment criteria: The diameter of the impression caused by the ball shall be measured and shall not exceed 2 mm. Salient features of IEC 61439
  • 24. Additional Tests in IEC 61439 Resistance to abnormal heat & fire (Glow Wire Test) Purpose: Glow wire test checks the capability of insulation material to handle thermal stresses produced by sources of heat or ignition. Procedure: Sample: Thinnest wall thickness of the completed application. Pre-treatment: 24 hours at 23 o C at 50% RH. Temperatures of glow wire: 650, 850 or 960 degrees C (depending on the relevant specification). •960 degrees C for parts necessary to retain cur rent carrying parts in position; •850 degrees C for enclosures intended for mounting in hollow walls: •650 degrees C for all other parts, including parts necessary to retain the protective conductor. Force: 1 N Contact time: 30 s Assessment criteria: There is no flame and glowing on the sample or flames/glowing of the sample extinguish within 30 s. The cotton or the paper underlay doesn’t ignite or burn. Salient features of IEC 61439
  • 25. Additional Tests in IEC 61439 Resistance to UV radiation Purpose: The UV radiation causes deterioration of synthetic material used for enclosures. Procedure: UV Test according to ISO 4892 – 2 method A; 1000 cycles of 5 min of watering and 25 min. of dry period with xenon lamp providing a total test period of 500 hrs. The value of temperature and humidity for the test are (65±3) o C and (65±5) %. Assessment criteria: Adherence of synthetic material (according to ISO 2409) shall have minimum 50% retention. Sample shall not show cracks or deterioration visible to normal or corrected vision without any additional magnification. This test is not required if synthetic material supplier demonstrates that materials of same thickness or thinner comply with this requirement. NOTE: This test is applicable only for enclosures and external parts of ASSEMBLIES intended to be installed Outdoors. Salient features of IEC 61439
  • 26. Additional Tests in IEC 61439 Lifting: Purpose: To ensure that there should be no damage to the panel during transportation & installation. Procedure: o The test is carried out on a sample having weight 1.25 times its maximum shipping weight. o From a standstill position, the ASSEMBLY shall be raised smoothly without jerking in a vertical plane to a height of (1±0.1) m and lowered in the same manner to a standstill position. This test is repeated a further two times. o After this the ASSEMBLY is raised up and suspended for 30 min at a height of (1±0.1) m without any movement. o Following this test the ASSEMBLY shall be raised smoothly without jerking from a standstill position to a height of (1±0.1) m and moved (10±0.5) m horizontally, then lowered to a standstill position. o This sequence shall be carried out three times at uniform speed, each sequence being carried out within 1 min. Assessment criteria: During the test, with the test weights in place, the ASSEMBLY shall show no deflections and after the test show no cracks or permanent distortions visible to normal or corrected vision without additional magnification, which could impair any of its characteristics. Salient features of IEC 61439
  • 27. Additional Tests in IEC 61439 Mechanical Impact Test Purpose: This test measures resistance of an enclosure towards external Mechanical Impact. The degree of protection provided by an enclosure against impacts is indicated by the letters IK followed by two digits depending on its ability to withstand the impact (as per IEC 62262). Procedure: o Number of impacts on each exposed face shall be five unless otherwise specified in relevant product standard. o The impacts shall be evenly distributed on the faces of the enclosure under test. o At the surrounding of any point of enclosure, not more than three impacts shall be applied. Assessment Criteria: o Structural integrity shall be maintained. o Degree of protection (IP) shall be unaffected. o Functionality of electrical products shall not be hampered. NOTE: Mechanical Impact test is not applicable to low voltage power switchgear and controlgear (PSC) assemblies. Salient features of IEC 61439
  • 28. Additional Tests in IEC 61439 Marking: Purpose: To ensure that the markings are legible. Procedure: Marking made by moulding, pressing, engraving or similar shall not be submitted to the following test. The test is made by rubbing the marking by hand for 15 s with a piece of cloth soaked in water and then for 15 s with a piece of cloth soaked with petroleum spirit. Assessment criteria: After the test the marking shall be legible to normal or corrected vision without additional magnification. Salient features of IEC 61439
  • 29. Previously a manufacturer had to assign a current rating to each circuit, but they were never required by the standard to prove its rating. In accordance with the new standard, the manufacturers have to verify the rating of each type of circuit. Each type of circuit will have its rating verified within the assembly and the capability of the assembly as a whole will be proven by loading adjacent outgoing circuits to their rated current, multiplied by the diversity factor. Historically it has been assumed that if nothing was said, the neutral could have a current rating equal to 50% of that of its associated phase. However, because this has not been stipulated in any low-voltage standards for many years, any query could only be answered by it’s custom and practice. IEC 61439 includes a default current rating in accordance with custom and practice for circuits with conductors above 16mm², but a specifier can ask for a higher rating to suit the needs of his application. In addition the ongoing question in respect of forms of separation has been answered. A device’s integral enclosure, for example the case of a moulded case circuit breaker, is defined as a means of providing separation from an adjacent circuit. Ambiguities clarified
  • 30. Open-type and enclosed assemblies - Enclosed assembly An assembly is enclosed when there are protected panels on all its sides so as to provide a degree of protection against direct contact not lower than IPXXB . Assemblies intended to be installed in common environments shall be of enclosed type - Open-type assembly An assembly, with or without front covering, in which the live parts of the electrical equipment are accessible. Such assemblies can be used only in places where skilled persons have access for their use. External design - Cubicle-type (column) Used for large distribution and control equipment; mechanically joined multi-cubicle-type assemblies are obtained by combining side by side more cubicle-type assemblies. - Desk-type Used to control complex machines or plants in mechanical, iron and steel and chemical industries. - Box-type Intended to be mounted on a vertical plane, both jutting out as well as built-in; such assemblies are used mainly for the department or area distribution in industrial or service sector environments. - Multi-box-type A combination of boxes, generally of protected type and with fixing flanges, each housing a functional unit which may be an automatic circuit-breaker, a starter, a socket completed with a blocking or protective circuitbreaker. Classification of assemblies
  • 31. Conditions of installation - Assembly for indoor installation Assembly which is designed for use in locations where the normal service Conditions for indoor use as specified in the Std. IEC 61439-1 are fulfilled. - Assembly for indoor installation Assembly which is designed for use in locations where the normal service conditions for outdoor use as specified in the Std. IEC 61439-1 are fulfilled. - Stationary assembly Assembly which is designed to be fixed at its place of installation, for instance to the floor or to a wall, and to be used at this place. - Movable assembly Assembly which is designed so that it can readily be moved from one place of use to another. Classification of assemblies
  • 32. With the ever-increasing pressures of demand for higher network utilization, assembly design optimization and more stringent safety, the changes included in the assembly standard IEC 61439-2 are important and overdue. All assemblies that do not have a specific product standard are covered and there is no opportunity to avoid compliance. In the new standard, the methods of confirming design performance are practical and pragmatic, reflecting the different market needs and ways in which assemblies are produced. Several alternative and equivalent means of verifying a particular characteristic of an assembly are included. These are defined and their use restricted. Where alternatives to type tests are used, a compensatory approach is taken and margins are added to ensure equivalence. Overall, the standard is performance based. Conclusion
  • 33. IEC 61439-1 - Low-voltage switchgear and controlgear assemblies – Part 1: General Rules IEC 61439-2 - Low-voltage switchgear and controlgear assemblies – Part 2: Power switchgear and controlgear assemblies Introduction to IEC 61439: A new standard on Switchgear & Controlgear Assemblies by Mr. A P Rao; Mr. D A Chavan; Mr. P Patel; Mr. T N Shah Switchgear Design & Development Center Improving safety and performance in electrical assemblies - A guide to IEC 61439- 2 by Schneider Electric IEC 61439 The new Standard for Low-Voltage Switchgear Assemblies – Changes and Effects in respect of Tests by GE Ronald Borchert, IPH Berlin The new IEC 61439 Series – Technical Seminar, 10th November, 2010 – Singapore, KEMA Quality Bibliography