Guide for Transformer
Maintenance
Tutorial of Cigre Working Group A2.34
Convener: Claude Rajotte, Canada
1
Outline
Introduction
Maintenance strategy
Maintenance process
Component selection and maintenance
Maintenance action catalogue
Major work – transformer repair
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 2
• Prepared to help transformer users define and apply
best practices to transformer maintenance
• Includes transformers rated 69 kV and above, and
larger than 25 MVA
• Subjects covered - best practice, checking and
testing to evaluate transformer condition, intervals for
the various actions, advanced maintenance activities,
human and material factors
Guide for Transformer
Maintenance
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 3
Commissioning
T ransformer
Operation
TBMTB CM
Corrective
Maintenance
Major W ork
On-site or in
W orkshop
OK Interpretation
Apply Special T ests and/or Intensive
M onitoring (if needed)
Normal?
Y ES
NO
Major work Minor work
Technical &
Economic
Evaluation
Refurbish
or Repair
Scrap &
Replace
E nd of Life
OLCM
Condition A ssessment
Maintenance Strategy (TBM, CBM, RCM)
Tests & Checks
C BM
Transformer
Operation and
Maintenance Cycle
Time Based
Condition
Monitoring
Condition
Based
Maintenance
On-line
Condition
Monitoring
Time Based
Maintenance
TBCM
CBM
OLCM
TBM
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 4
Outline
Introduction
Maintenance strategy
Maintenance process
Component selection and maintenance
Maintenance action catalogue
Major work – transformer repair
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 5
Maintenance Strategy
Importance of Transformer Maintenance
Life
Used Possible Impacts of Lack of Maintenance
- Baseline data not recorded, commissioning errors missed
- Failure to detect early life problems within warranty period
- Oil oxidation begins
- OLTC contacts wear (medium and heavy loads)
- Weathering and UV takes affect
- Trends in condition not observed
- Corrosion in severe environments
- Visible affects of weathering and UV
- Transducers go out of calibration
- Fan and pump bearing wear
- Trends in condition not observed
- Gaskets and seals lose resilience, oil leaks manifest
- Oil decay products affect paper insulation
- Weathered paint, edge and spot corrosion
- Miss opportunity to intercept accelerated ageing
- Miss benefits of implementing a mid-life intervention
- Uncertainty on remnant life
- Oxidation and hydrolysis enters accelerated ageing stage
- Paper DP drops, sometimes prematurely
- OLTC and bushing failure rates increase
- Paint system protection fails
NEW
20%
40%
60%
80%
100%
- Expect sludge if oil has been in poor condition
- Exposure causes device malfunctions
- Wiring and cable insulation en-brittle
- Bad oil leaks need regular topping up
- Dielectric withstand diminishes (moisture)
- Expensive failure (often bushing or OLTC)
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 6
The condition begins
to deteriorate
Y
Z
The condition change
becomes detectable
Good Condition
X
The condition has
deteriorated to the
point of failure
Time
Failure
Maintenance Strategy
Theoretical Transformer Condition Degradation
- detect initial changes in condition that are relatively small compared
to the deterioration necessary for failure to occur
- have measurement or inspection intervals that are smaller than
∆T[XY]+∆T[YZ] to allow detection before failure occurs
- have a period of time ∆T[YZ] that is long enough to be able to take
the preventive action (ex: transformer outage)
To be technically feasible, a condition assessment task should have the ability to:
∆T[XY] ∆T[YZ]
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 7
Maintenance Strategy
Survey on Maintenance Practices
• There were significant differences on the task intervals for "visits“
• Oil test task intervals were generally in accordance with IEC 60422
• A majority of respondents used Electrical tests on a "Conditional
based" criterion only - CBM
• For "Accessories verification", task intervals varied significantly (from 1
to 12 years)
• OLTC task intervals varied between 4 and 12 years
• Bushing maintenance practices varied significantly between utilities
KEY FINDINGS
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 8
• Generally, the intervals between visits were longer than for GSU
users and also varied greatly
• Continuous DGA monitoring was used intensively by 50% of the
respondents, particularly on their critical units
• Electrical tests were performed by two thirds of the respondents
For GSU transformers, it was observed that:
• Visits were made at significantly shorter intervals
• Periodic sampling for dissolved gas analysis (DGA), by the majority,
were at intervals of one year or less
• Continuous DGA monitoring was not often applied, probably due to
the proximity of a maintenance crew
• A minority of respondents were performing electrical tests
periodically
For Transmission transformers, it was observed that:
Maintenance Strategy
Survey on Maintenance Practices
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 9
• Transformer characteristics and specifications
• The quality of the components installed on the transformer
• The required duty of the transformer (load, OLTC operation)
• The transformer environment (temperature, humidity)
• Historical transformer failure rate and failure types
• The level of transformer redundancy and the consequences of
unavailability
• The failure mode and its effects on substation safety
• Company culture and focus based on maintenance
• The availability and costs of labour
• The degree of implementation of modern technologies
• The presence of a maintenance optimization program
The survey showed that maintenance practices varied significantly
between transformer users.
Factors that can influence maintenance practice and effort:
Maintenance Strategy
Survey on Maintenance Practices
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 10
Maintenance Strategy
TBM and TBCM Maintenance Intervals
Action Task Interval Remark
Light Regular Intensive
Visit 6 m 1 m 1 d In service
Detailed visual
inspection
1 y 3 m 2 w In service
DGA 2 y 1 y 3 m Task interval may differ with monitoring
Oil tests 6 y 2 y 1 y
Cooling system cleaning Conditional Conditional Any Interval Outage may be required
Accessories verification 12 y or Cond. 6-8 y 1-2 y Outage required
Electrical basic tests Conditional Conditional Any Interval Outage required
Insulation tests (DF or
PF)
Conditional 6-8 y 2-4 y Outage required
OLTC internal inspection 12 y 6-8 y 4 y Consider number of operation,
technology and manufacturer
recommendations
Survey showed many tasks were performed conditionally - CBM
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 11
Regular
The intensity of these maintenance task intervals:
Light
• Transformer equipped with components known to be very reliable
• Low load and low number of tap-changer operations
• Transformer does not operate in a harsh environment
• Advanced technology that requires less maintenance
• Low consequences from unexpected failure
Intensive
• Components that are known to require frequent attention
• High load, high number of OLTC operations
• Transformer operates in a harsh environment
• Older transformer technologies
• High consequences from unexpected failure
Maintenance Strategy
TBM and TBCM Maintenance Intervals
• Any situation between these two
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 12
Maintenance Strategy
Condition Based Maintenance – Oil Test Results
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 13
Maintenance Strategy
Monitoring
On-line Monitoring
Data, measurements or samples (oil) are collected while the transformer is
energized and in service. If these are performed at discrete intervals (in
‘visits’) then they provide only ‘snapshots’ of the transformer’s condition.
Continuous On-line Monitoring
Data, measurements or samples are collected in a continuum by
transducers, sometimes at discrete sampling rates, while the transformer is
energized and in service. This captures real time data to provide trends in
transformer condition.
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 14
Maintenance Strategy
Continuous On-line Monitoring
Modern continuous on-line monitoring adds an intelligent electronic device
(IED) to the monitoring transducer(s). These devices have a measurement
mechanism, that together with internal signal and data processing
capabilities, can be described as ‘smart sensors’ or ‘smart systems’
capable of providing multiple measurement and control functions.
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 15
Maintenance Strategy
Continuous DGA On-Line Monitoring
• This is the most commonly used on-line monitoring technology for
transformers because:
- It is a very good indicator for most transformer incipient faults
- Early detection of incipient faults often avoids major failure
• DGA sensor technologies include fuel cell, chromatography,
semiconductor, photo-acoustic spectroscopy, thermal conductivity
• Depending on the technology chosen, these systems can provide:
- A single measurement of one specific gas
- A single measurement of a composition of several gases with
specific proportions and sensitivities
- Multiple measurements of different gases
• Gas-in-oil monitors often include a built-in moisture sensor
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 16
• Systems with models or algorithms that calculate
winding hot spot temperatures, rate of ageing of
paper insulation, moisture content in paper or
barriers, and effectiveness of cooling systems
• Monitors condenser bushings by measuring
leakage current through their capacitance taps
• OLTC monitoring including mechanical conditions
of the drive system, contact wear, temperature
differential, dissolved gas analysis, tap position
tracking/counting
• Partial discharge detection using electrical,
acoustical, or UHF signals
Maintenance Strategy
Other On-Line Monitoring Technologies
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 17
Outline
Introduction
Maintenance strategy
Maintenance process
Component selection and maintenance
Maintenance action catalogue
Major work – transformer repair
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 18
Planning Organization Execution Recording
Optimization
Maintenance Process
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 19
• General information about the transformer (type, power, voltage)
• Types of maintenance work to be done with relevant triggering points
(time interval, event, condition, result of diagnostics) and operational
status (energized, de-energized, or both de-energized and disconnected)
• Qualifications and skills required to perform individual maintenance works
• List of tasks related to individual maintenance works and the associated
time required
• Excerpt from, or reference to manufacturer’s manual giving detailed
information (work steps, sequence, tools, material, safety aspects)
• Maintenance report forms
• Source of information for maintenance data collection and reporting –
based on standard report forms
A guideline would include:
Maintenance Process
Maintenance Planning– Maintenance Guidelines
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 20
• Equipment Inventory
• Computerized Maintenance Guidelines
• Task lists and Operations
• Maintenance plan
• Maintenance schedules
• Work orders
• Outage Planning
• Maintenance task tracking
Maintenance Planning – Computer Aided
Maintenance Management Systems (MMS)
There are different computer aided tools for maintenance planning used
by different utilities. All have this similar structure:
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 21
Planning Organization Execution Recording
Optimization
Maintenance Process
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 22
Level 1:
Actions to be taken on certain transformer components, and generally
described in a maintenance manual issued by the manufacturer.
Examples: control operations, check of oil levels, exchange of
consumable materials
Maintenance Organization
5 Levels of Competence
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 23
Level 2:
Actions performed with basic written procedures and/or supporting
equipment or devices, which are simple to use or to assemble, being part
of the transformer or external to it.
Examples: replacement / exchange of accessories or parts, routine
checks.
Maintenance Organization
5 Levels of Competence
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 24
Level 3:
Actions performed with complex written procedures or the use of special
supporting equipment. Personnel are trained in using complex tools or
processes.
Examples: exchange of an original part or component, complex setting or
re-setting
Maintenance Organization
5 Levels of Competence
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 25
Level 4:
Actions performed requiring personnel trained in special techniques or
technologies and utilization of special tools, and/or supporting equipment.
Examples: modifications and upgrading activities, changes in functions,
changes in the way of operation and use.
Maintenance Organization
5 Levels of Competence
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 26
Level 5:
Actions needing specialist technical knowledge and with the support of
industrial processes, industrial equipment or devices.
Examples: complete inspections or revisions which require detailed
dismantling of the equipment, its reconstruction, replacement of obsolete
or worn parts or components.
Maintenance Organization
5 Levels of Competence
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 27
Planning Organization Execution Recording
Optimization
Maintenance Process
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 28
• ground all bushings to avoid induction
• use working at height safety measures
• beware all bushings and leads when testing
• beware opening pressurized access covers
• identify and isolate cubicle auxiliary supplies
• deactivate springs whilst working on OLTC
• treat all tanks as confined spaces
• beware of nitrogen gas filling
• vent explosive gases accumulated by OLTCs or faults
• perform a risk assessment on the need to deactivate the fire
extinguishing system
Maintenance Execution
Safety
Some safety aspects that have to be considered when working on a
transformer:
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 29
Planning Organization Execution Recording
Optimization
Maintenance Process
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 30
Maintenance Recording
Corrective Maintenance Tracking
Data recorded for corrective maintenance should contain:
• Unique identification of the transformer and its properties and location
• Transformer location details
• Time of maintenance action
• Environmental conditions on site during maintenance action:
Temperature, wind, rain, storm, humidity
• Components, parts and material used and the parts replaced
• Photographs: The ‘as found’ and ‘return to service’ condition, providing a
reference for future work
• Tests results taken before a return to service
• Problem description: Failure, symptoms and circumstances
• Problem cause: Data on what was causal to the failure or malfunction (in
some cases the root-cause may not be obvious and requires more
detailed diagnosis and investigation)
• Remedy / Action: A report of the remedial action taken
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 31
Planning Organization Execution Recording
Optimization
Maintenance Process
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 32
Maintenance Optimization
Reliability Centred Maintenance
A combination of TBM, TBCM, CBM and OLCM is often used to maintain
large complex assets such as power transformers.
Reliability Centred Maintenance: The extent of maintenance to be
performed is proportional to the level of risk associated with the
transformer
Risk = likelihood of failure * failure consequence
The likelihood of failure can be represented by the "Health Index" of the
unit (obsolescence, service history, technical condition)
Failure consequence can also be mitigated by various control measures
(protection upgrade, contingency plan, fire wall, oil containment)
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 33
Outline
Introduction
Maintenance strategy
Maintenance process
Component selection and maintenance
Maintenance action catalogue
Major work – transformer repair
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 34
Component Selection and Maintenance
Transformer maintenance effort is strongly related to component selection.
- Bushings
- Oil preservation systems
- Cooling systems
- Gaskets
- Gauges, indicators and relays
- Control cabinets
- Current transformers
- On-load tap changers
- De-energized tap changers
- Surge arresters
- Transformer active part
- Sensing and monitoring devices
This is because transformer components vary in quality, initial cost,
maintainability, technology, reliability, life expectancy and potential for its
failure and the consequences.
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 35
Component Selection and Maintenance
Bushings
Oil Impregnated Paper (OIP) Bushings
Advantages Disadvantages
- Very long history with relatively good
performances
- Very low partial discharge – can be used at
any voltage level
- Relatively low cost
- Minimal handling and storage requirements
- DGA diagnostics are possible
- Vulnerable to insulating oil leaks and water
ingress if the gasket/sealing system is
compromised
- Higher risk of bushing explosion and
resultant transformer fire
- Positioning angle during transportation,
handling and storage
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 36
Component Selection and Maintenance
Bushings
Resin Impregnated Paper (RIP) Bushings
Advantages Disadvantages
-Non-flammable core
-Bushing failure is less likely to release main
tank oil
-The core is less likely to be affected by
water ingress
-Very low partial discharge levels – can be
used at any voltage level
- No constraints on the attitude of the bushing
during transportation, handling and storage
-Relatively higher costs
-Constraints on handling and storage
-The oil end of the body must be protected
from moisture during storage
- Oil end of the bushing is susceptible to
transport damage
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 37
Porcelain Insulators
Composite Insulators
Component Selection and Maintenance
Bushings
Advantages Disadvantages
-No ageing
- Long history of good reliability
-Could create exploding projectiles if the
bushing fails
-Relatively fragile in the event of shock or
heavy force
- Makes the bushing relatively heavy
Advantages Disadvantages
-Relatively lightweight
-Lower risk of projectiles in the event of a
bushing failure
-High seismic withstand capability
- Better hydrophobicity in polluted conditions
-Less field experience compare to porcelain
- Long term reliability is not known, early
examples have suffered from surface
deterioration
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 38
Component Selection and Maintenance
Bushings
Types of Bushing Connections
Draw Solid Bottom Draw
Lead Conductor Connected Rod
Black denotes the current path
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 39
Outline
Introduction
Maintenance strategy
Maintenance process
Component selection and maintenance
Maintenance action catalogue
Major work – transformer repair
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 40
Maintenance Action Catalogue
Electrical Tests and DGA Diagnostic Matrix
Frequency Response Analysis
Dissolved Gas Analysis
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 41
Maintenance Action Catalogue
Electrical Test Example – Winding Resistance
Detectable
failures
Contact problems on the tap selector, contact problems on the diverter switch, broken
conductors, broken parallel strands, shorted winding disks, shorted winding layers, poor
bushing connections
Indication High internal temperatures, normally indicated by the DGA
Test method A constant current source is used to feed a DC current into the winding. The test current and
the voltage across the winding are measured and the resistance value is calculated. The
accuracy of the equipment should guarantee that differences of 1% or even lower can be
detected. Since the winding resistances are small, the test set should be connected in 4-wire
technology. A relatively high no-load voltage enables a quick saturation of the core and a fast
reaching of the stationary final value. It is recommended to measure the resistance for all taps of
the OLTC. The resistance values should be corrected to 75°C according to IEC 60076 Part 1
Reference Test report of the manufacturer, fingerprint measurements
Interpretation The measured winding resistance should not differ more than about 1% compared to the
factory test report, if the winding temperature at measurement conditions is corrected to the
factory conditions. Difference between phases usually less than 2-3%; Comparison between
HV and LV resistance is usually in the order of the square of the winding ratio, when losses are
balanced between HV and LV
Comments In comparison to the LV winding, the resistance of the HV winding is much higher. Therefore
identification of contact problems can be less sensitive on the HV side than the LV side. If the LV
windings have very low resistance values, in the order of a few mΩ, it can be helpful to use the HV
winding of the same limb in serial connection to get faster stabilization of the measurement current. The
time needed to get stable readings can be in the order of tens of minutes for very low resistance values
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 42
Maintenance Action Catalogue
Dissolved Gas Analysis
• One of the most useful and widely applied diagnostic tools
• Gases commonly measured: Hydrogen (H2), Methane (CH4), Ethane
(C2H6), Ethylene (C2H4), Acetylene (C2H2), Carbon Monoxide (CO),
Carbon Dioxide (CO2), Oxygen (O2) and Nitrogen (N2)
• No consensus about the absolute maximum level acceptable for each gas
• Considers both gassing rates and absolute values of the different gases
• Algorithms are used to:
- Identify significant gases because they exceed a limit value
- Evaluate gassing rates by comparing with previous gas
concentrations
- Assign weightings to each gas (because each gas is not produced by
the same amount of energy)
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 43
There are several methods used to interpret DGA results. Commonly, gas
ratios are used to match the DGA gas profile to the generation source in the
transformer (incipient faults), and identify the level of energy (temperature)
required to produce them.
Depending on the DGA profile (ratios), the gassing may be associated with:
- Thermal faults of low temperature
- Thermal faults of medium temperature
- Thermal faults of high temperature
- Discharges of low energy
- Discharges of high energy
- Partial discharge activity
Maintenance Action Catalogue
Dissolved Gas Analysis
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 44
Tests for in-service oils:
• GROUP 1: Minimum monitoring to ensure the oil is suitable for
continued use - colour, water content, breakdown voltage, interfacial
tension, acidity, dissipation/power factor and resistivity
• GROUP 2: Additional tests that obtain specific information about the
quality of the oil and also used to assist in the evaluation of the oil for
continued use – particle count, oxidation stability, sediment and sludge
• GROUP 3: Tests used to determine the suitability of the oil for use in
the transformer and the oil’s environmental compliance – corrosive
sulphur and PCB
Maintenance Action Catalogue
Oil Tests
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 45
Maintenance Action Catalogue
Relation between Transformer Problems and
Main Parameters of the Oil
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 46
Maintenance Action Catalogue
Diagnostic Capabilities of Different OLTC Tests
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 47
Maintenance Action Catalogue
Maintenance Inspection Tasks
• Thermography
• Main tank and conservator
• Cooling system
• Accessories
• Transformer cabinets
• On-Load Tapchanger
• Buchholz relay operation
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 48
Maintenance Action Catalogue
Insulation Drying
• Remaining moisture in insulation during manufacturing
• Humid air from outside during transportation and/or assembling in
substation
• Humid air from outside through the breather (non sealed)
• Moisture ingress through gaskets
• Chemical decomposition of cellulose
• Moisture absorption due to exposure during maintenance
• Topping-up of oil level made with humid oil (non dried)
The moisture in a transformer is generated by several sources:
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 49
A 1% increase in the moisture content of paper has the same effect as
an increase in operating temperature of 8°C (doubling the rate of
depolymerisation)
- Accelerated ageing of the transformer insulation
- Moisture in the oil combined with particles reduces the breakdown voltage
of the oil and increases the risk of static electrification, partial discharge
activity and tracking
- High water content in cellulose
increases the risk of bubbling
during sudden overload or
thermal stress, and the risk of
dielectric breakdown
Reference: CIGRE Brochure #349 Moisture Equilibrium and
Moisture Migration within Transformer Insulation System
Maintenance Action Catalogue
Risks of Not Drying Insulation
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 50
• On-line oil dryers - molecular sieve
• Hot oil circulation
• Hot oil + vacuum / hot oil + vacuum + hot oil spray / hot oil + vacuum
‘+ cold trap
• Low frequency heating (LFH) / LFH + hot oil spray
• Vapour phase
Transformer Hot oil + Vacuum
(24 h / day)
LFH + Oil Spray
110 MVA / 70 kV 8 days 4 days
400 MVA / 400 kV 20-30 days 9 days
The typical time needed to dry a transformer from initial moisture
in the solid insulation of 3% to remaining moisture of 1%:
Maintenance Action Catalogue
Drying Techniques
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 51
Maintenance Action Catalogue
Physical and Chemical Oil Treatments
• Reclamation is defined by the IEC as “a
process that eliminates or reduces soluble
and insoluble polar contaminants from the oil
by chemical and physical processing”.
• The contaminants in question are mostly
oxidation products predominately in the oil but
also on the solid insulation.
• Chemical and physical processing is typically
a combination of treatment with a sorbent
material and filtering.
• Oil reclamation scenarios: on-site on-line, on
site off-line, tank to tank, large scale
reclaiming
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 52
Oil reclamation treatment is recommended because:
• An increase in oil acidity accelerates paper ageing
• Timely treatment, before advanced degradation, is important if the oil
quality is to be maintained.
Maintenance Action Catalogue
Importance of Oil Treatments
3 oil treatments used for corrosive sulphur problems:
• Adding metal passivator
• Removal of corrosive sulphur
• Oil exchange
Reference: CIGRE Brochure #378
Copper Sulphide in Transformer Insulation
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 53
Maintenance Action Catalogue
Precautions for Invasive Work
Work that requires oil to be partially or completely removed
from the transformer may be regarded as invasive.
Invasive work requires certain precautions to be taken
because the transformer insulation is very sensitive to
moisture, trapped air or gas bubbles, and particulate
contaminants.
Contaminants may easily be introduced either from airborne
dust and humidity, or directly from people, tools and
materials entering the transformer.
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 54
Maintenance Action Catalogue
Precautions for Invasive Work - Examples
Planning the Work
Evaluation of the amount of oil required to carry out, if the work required to access into
the tank, proper confined space training, plans and permit, plan to reduce the
exposure time to minimum, evaluate the ability of the tank to withstand vacuum
Draining the Transformer
Use of dry air to during oil draining, apply a positive pressure if the tank is left empty,
avoid any loss of oil into the environment
Access to the Transformer
Extreme cleanliness, continuous flow of dry air entering the tank, suitable safety
precautions need to be taken, gaskets replacement, cleaning cloths and boots, be
aware of the compatibility of solvents, paints, glues and other chemicals, tools should
be tethered and an inventory be kept
Refilling the Transformer
Vacuum filled (if the transformer was originally vacuum filled), air leaks elimination,
remove any free water on the tank, use dry oil and use a reconditioning plan, limit the
oil flow velocity, winding connected to earth, apply a standing time following oil filling
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 55
Outline
Introduction
Maintenance strategy
Maintenance process
Component selection and maintenance
Maintenance action catalogue
Major work – transformer repair
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 56
Major Work – Transformer Repair
Definition
On-site repair is invasive work, performed in-situ, where it is necessary to
partly or completely drain oil and remove the main covers in order to
repair or upgrade the transformer .
The level of expertise and the need for high voltage tests may vary,
depending on the complexity of the work.
Repairs are categorized as follows:
- Minor repairs such as replacement
of bushings or tap changers, repair
of connections
- Major repairs such as exchange of
windings, repair of the core,
modifications or upgrades
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 57
Major Work – Transformer Repair
Advantages of On-site Repair
• Transportation difficult or impossible:
disused railway, axle load limits,
changed road alignment, bridges,
roundabouts
• High transportation costs
• High transportation risks: poor road
conditions, heavily aged insulation
• Reduced down-time by avoiding
transportation: avoid higher losses in
the network due to changes in
optimum power flow, loss of energy
sales, loss of water in a hydro plant,
penalty in case of non delivery of
energy; time saving 1 - 3 months
On-site repair might have advantages over factory repair:
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 58
Major Work – Transformer Repair
Process
• The process of on-site major repair can with appropriate resources and
planning effectively emulate a workshop repair. Some adaptations are
needed due to site conditions.
• A detailed plan for each activity will allow adequate time for the
equipment and material to arrive at the proper phase of the repair.
Planning should be updated daily by the site supervisor and reviewed
periodically. Site personnel require regular contact with their service
centre or factory for logistical, administrative and technical support.
• On-site repair requires excellent logistics, competent planning as well as
the flexibility to adapt to the unforeseen (inherent to most repair
situations) in order to minimize delays to the schedule.
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 59
Major Work – Transformer Repair
Testing
Site testing extends the repair time and represents significant costs.
However, these tests will reduce future risk of unexpected failure.
In defining the scope of site testing, the following aspects should be
considered:
• Type of repair and scope of work (replacing
bushings, winding replacement)
• Possible consequences of a failure
• Stress from the network (lightning, short-circuit,
overload)
• Urgency and loss of production due to down-
time
• Repair/refurbishment versus replacement
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 60
Suggested categories of on-site testing:
Transformer
Category
Characteristics
Category 1 - Nominal Voltage < 72.5 kV
- Units with no critical loss of production in case of failure, or with good redundancy or a
‘’’spare unit
- Limited risk of fire in case of failure (collateral damages)
- Repair of connections, replacement of bushing or OLTC
- No expected overload. Good protection system. Low risk of short-circuit on the network
- Urgency to put the units back in service to meet operation constraints
- No availability of testing equipment
Category 2 - Nominal Voltage >=72.5kV and < 170 kV
- Repair involving work on the active part
Category 3 - Nominal Voltage >=170kV and <= 300 kV
- Transformers with severe consequences in case of failure and/or significant loss of ’’
production - generation or industrial applications
- Transformer with no spare unit
Category 4 - Nominal Voltage > 300 kV
- Repair that incorporates a new winding design
- Upgrade with new design to reach higher MVA / Voltage.
- Transformers with high lightning exposure
Major Work – Transformer Repair
Testing
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 61
Category Recommended tests
Category 1 - Low voltage tests: winding resistance, ratio, insulation resistance of windings & core, power factor
- Functional tests and checks on indicators, control circuits, relays and OLTC
- Dielectric Response (DR) and Frequency Response Analysis (FRA) as a fingerprint
- Continuous increase of voltage whenever possible (GSU) without any load: 20%–100% Un
- Connection to the network with no load at 100% Un for 12 hours with monitoring of gas (preferably
on-line or off-line after one hour and then every 3 hours). In any case, the results of DGA should be
analyzed before putting the transformer back under load
- Incremental load rise (whenever possible)
- Monthly follow-up of DGA over a 6 month period
Category 2 - Same tests as for Category 1
- Induced voltage tests with partial discharge (PD) measurement according to IEC 60076-3 or IEEE
‘’C57.12.00 standard
Category 3 - Same tests as for Category 2
- In case of delta connected HV windings, separate source AC withstand voltage test (applied voltage
‘’test) at 80% of the nominal voltage test according to IEC 60076-3 or IEEE C57.12.00 standard
Category 4 - Same tests as for Category 3
- Lightning impulse test, switching impulse test and chopped impulse test may be performed;
‘’nevertheless, the added value of these has to be evaluated (costs involved, availability of test
‘’equipments)
Major Work – Transformer Repair
Testing
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 62
Major Work – Transformer Repair
Economics
Case Examples:
- Problematic transportation
- Problematic outage time
- Repair of a faulted unit with core repair and windings replacement
Factors to consider:
- Costs of material and labour
- Core and winding losses
- Transportation
- Outage time
- Reliability and Tests
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 63
Major Work – Transformer Repair
Environmental Considerations
Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 64

More Related Content

What's hot

Tan delta test for power transformers
Tan delta test for power transformersTan delta test for power transformers
Tan delta test for power transformersjibinjoy1988
 
Fundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Fundamentals of Power System protection by Y.G.Paithankar and S.R.BhideFundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Fundamentals of Power System protection by Y.G.Paithankar and S.R.BhideSourabh Ghosh
 
IEEE Guide for the Application and Interpretation of FRA for oil Transformer
IEEE Guide for the Application and Interpretation of FRA for oil TransformerIEEE Guide for the Application and Interpretation of FRA for oil Transformer
IEEE Guide for the Application and Interpretation of FRA for oil TransformerAHMED MOHAMED HEGAB
 
High Voltage DC Transmission
High Voltage DC TransmissionHigh Voltage DC Transmission
High Voltage DC Transmissionkrishna koundinya
 
A basic guide to Creepage and Clearance.pdf
A basic guide to Creepage and Clearance.pdfA basic guide to Creepage and Clearance.pdf
A basic guide to Creepage and Clearance.pdfValentinoRadaelli
 
Transformer testing
Transformer testingTransformer testing
Transformer testingajayknows
 
RTV silicone coating to protect high voltage networks
RTV silicone coating to protect high voltage networksRTV silicone coating to protect high voltage networks
RTV silicone coating to protect high voltage networksImad Kanouni Moubtadi
 
Solar pv plant quality assurance checkpoints v2
Solar pv plant   quality assurance checkpoints v2Solar pv plant   quality assurance checkpoints v2
Solar pv plant quality assurance checkpoints v2sanjay vashishtha
 
Electrical Grid Substation
Electrical Grid SubstationElectrical Grid Substation
Electrical Grid SubstationAng Sovann
 
Medicion y comprobacion de resistencia de aislamiento
Medicion y comprobacion de resistencia de aislamientoMedicion y comprobacion de resistencia de aislamiento
Medicion y comprobacion de resistencia de aislamientoivan castro
 
09_C_3_100 percent - Stator Earth Fault Protection.ppt
09_C_3_100 percent - Stator Earth Fault Protection.ppt09_C_3_100 percent - Stator Earth Fault Protection.ppt
09_C_3_100 percent - Stator Earth Fault Protection.pptMAHMOUDMOHAMED431205
 
Commissioning of Electrical Equipment or systems.ppt
Commissioning of Electrical Equipment or systems.pptCommissioning of Electrical Equipment or systems.ppt
Commissioning of Electrical Equipment or systems.pptAlemayehuAsmare
 
Protection Relays Numbering (ANSI)
Protection Relays Numbering (ANSI)Protection Relays Numbering (ANSI)
Protection Relays Numbering (ANSI)AHMED MOHAMED HEGAB
 
Basics of electrical control panel
Basics of electrical control panelBasics of electrical control panel
Basics of electrical control panelCHACKOCHEN MATHEW
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)J. FR
 
Sample calculation-for-differential-relays
Sample calculation-for-differential-relaysSample calculation-for-differential-relays
Sample calculation-for-differential-relaysRoberto Costa
 
Power system Protection Services in India
Power system Protection Services in IndiaPower system Protection Services in India
Power system Protection Services in IndiaSystem Protection
 
Nema standards publication mg 2 2001
Nema standards publication mg 2 2001Nema standards publication mg 2 2001
Nema standards publication mg 2 2001Danilo Poma Muñoz
 

What's hot (20)

Tan delta test for power transformers
Tan delta test for power transformersTan delta test for power transformers
Tan delta test for power transformers
 
Fundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Fundamentals of Power System protection by Y.G.Paithankar and S.R.BhideFundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Fundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
 
PARTIAL DISCHARGES IN TRANSFORMERS
PARTIAL DISCHARGES IN TRANSFORMERSPARTIAL DISCHARGES IN TRANSFORMERS
PARTIAL DISCHARGES IN TRANSFORMERS
 
Testing of transformer
Testing of transformerTesting of transformer
Testing of transformer
 
IEEE Guide for the Application and Interpretation of FRA for oil Transformer
IEEE Guide for the Application and Interpretation of FRA for oil TransformerIEEE Guide for the Application and Interpretation of FRA for oil Transformer
IEEE Guide for the Application and Interpretation of FRA for oil Transformer
 
High Voltage DC Transmission
High Voltage DC TransmissionHigh Voltage DC Transmission
High Voltage DC Transmission
 
A basic guide to Creepage and Clearance.pdf
A basic guide to Creepage and Clearance.pdfA basic guide to Creepage and Clearance.pdf
A basic guide to Creepage and Clearance.pdf
 
Transformer testing
Transformer testingTransformer testing
Transformer testing
 
RTV silicone coating to protect high voltage networks
RTV silicone coating to protect high voltage networksRTV silicone coating to protect high voltage networks
RTV silicone coating to protect high voltage networks
 
Solar pv plant quality assurance checkpoints v2
Solar pv plant   quality assurance checkpoints v2Solar pv plant   quality assurance checkpoints v2
Solar pv plant quality assurance checkpoints v2
 
Electrical Grid Substation
Electrical Grid SubstationElectrical Grid Substation
Electrical Grid Substation
 
Medicion y comprobacion de resistencia de aislamiento
Medicion y comprobacion de resistencia de aislamientoMedicion y comprobacion de resistencia de aislamiento
Medicion y comprobacion de resistencia de aislamiento
 
09_C_3_100 percent - Stator Earth Fault Protection.ppt
09_C_3_100 percent - Stator Earth Fault Protection.ppt09_C_3_100 percent - Stator Earth Fault Protection.ppt
09_C_3_100 percent - Stator Earth Fault Protection.ppt
 
Commissioning of Electrical Equipment or systems.ppt
Commissioning of Electrical Equipment or systems.pptCommissioning of Electrical Equipment or systems.ppt
Commissioning of Electrical Equipment or systems.ppt
 
Protection Relays Numbering (ANSI)
Protection Relays Numbering (ANSI)Protection Relays Numbering (ANSI)
Protection Relays Numbering (ANSI)
 
Basics of electrical control panel
Basics of electrical control panelBasics of electrical control panel
Basics of electrical control panel
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
 
Sample calculation-for-differential-relays
Sample calculation-for-differential-relaysSample calculation-for-differential-relays
Sample calculation-for-differential-relays
 
Power system Protection Services in India
Power system Protection Services in IndiaPower system Protection Services in India
Power system Protection Services in India
 
Nema standards publication mg 2 2001
Nema standards publication mg 2 2001Nema standards publication mg 2 2001
Nema standards publication mg 2 2001
 

Similar to A2.34+transformer+maintenance+tutorial

Cutler-Hammer Maintenance Program LTM 2010
Cutler-Hammer Maintenance Program LTM 2010Cutler-Hammer Maintenance Program LTM 2010
Cutler-Hammer Maintenance Program LTM 2010p6q4ck9dyn
 
Qualitrol | Vault Monitoring
Qualitrol | Vault MonitoringQualitrol | Vault Monitoring
Qualitrol | Vault MonitoringSean Wallace
 
Appraisal ppt ankur
Appraisal ppt ankurAppraisal ppt ankur
Appraisal ppt ankurAnkur Mishra
 
steam-turbine-generator-overhaul-and-inspection-epri.pdf
steam-turbine-generator-overhaul-and-inspection-epri.pdfsteam-turbine-generator-overhaul-and-inspection-epri.pdf
steam-turbine-generator-overhaul-and-inspection-epri.pdfchintanraval24
 
Transformer asset management
Transformer asset managementTransformer asset management
Transformer asset managementMuthar Hussain
 
ddc_controls_part_1_pnwd-sa-883dddds4.pdf
ddc_controls_part_1_pnwd-sa-883dddds4.pdfddc_controls_part_1_pnwd-sa-883dddds4.pdf
ddc_controls_part_1_pnwd-sa-883dddds4.pdfnqmanuntag
 
TSE SCADA Design presentation new
TSE SCADA Design presentation newTSE SCADA Design presentation new
TSE SCADA Design presentation newMohamed ElSirsy
 
Ultrasonic guided waves application on oil and gas pipeline
Ultrasonic guided waves application on oil and gas pipelineUltrasonic guided waves application on oil and gas pipeline
Ultrasonic guided waves application on oil and gas pipelineMohammad Javad Ranjbar
 
project presentation on "THMC"
project presentation on "THMC"project presentation on "THMC"
project presentation on "THMC"Teja venkat
 
11.methods to determine the overall health and condition of large power trans...
11.methods to determine the overall health and condition of large power trans...11.methods to determine the overall health and condition of large power trans...
11.methods to determine the overall health and condition of large power trans...Alexander Decker
 
Methods to determine the overall health and condition of large power transfor...
Methods to determine the overall health and condition of large power transfor...Methods to determine the overall health and condition of large power transfor...
Methods to determine the overall health and condition of large power transfor...Alexander Decker
 
Transfomer diagnostics/sanjeet-1308143
Transfomer diagnostics/sanjeet-1308143Transfomer diagnostics/sanjeet-1308143
Transfomer diagnostics/sanjeet-1308143sanjeet kumar
 
Industrial monitoring and control systems using andriod application
Industrial monitoring and control systems using andriod applicationIndustrial monitoring and control systems using andriod application
Industrial monitoring and control systems using andriod applicationAvinash Vemula
 
PDM IMPLIMENTATION
PDM IMPLIMENTATIONPDM IMPLIMENTATION
PDM IMPLIMENTATIONUttam Misra
 
POWER TRANSFORMER UDAIPUR 29022012.ppt
POWER TRANSFORMER UDAIPUR 29022012.pptPOWER TRANSFORMER UDAIPUR 29022012.ppt
POWER TRANSFORMER UDAIPUR 29022012.pptPOOJAOHRI2
 

Similar to A2.34+transformer+maintenance+tutorial (20)

EIT_Presentation
EIT_PresentationEIT_Presentation
EIT_Presentation
 
Cutler-Hammer Maintenance Program LTM 2010
Cutler-Hammer Maintenance Program LTM 2010Cutler-Hammer Maintenance Program LTM 2010
Cutler-Hammer Maintenance Program LTM 2010
 
Qualitrol | Vault Monitoring
Qualitrol | Vault MonitoringQualitrol | Vault Monitoring
Qualitrol | Vault Monitoring
 
SD.pptx
SD.pptxSD.pptx
SD.pptx
 
Appraisal ppt ankur
Appraisal ppt ankurAppraisal ppt ankur
Appraisal ppt ankur
 
steam-turbine-generator-overhaul-and-inspection-epri.pdf
steam-turbine-generator-overhaul-and-inspection-epri.pdfsteam-turbine-generator-overhaul-and-inspection-epri.pdf
steam-turbine-generator-overhaul-and-inspection-epri.pdf
 
Transformer asset management
Transformer asset managementTransformer asset management
Transformer asset management
 
ddc_controls_part_1_pnwd-sa-883dddds4.pdf
ddc_controls_part_1_pnwd-sa-883dddds4.pdfddc_controls_part_1_pnwd-sa-883dddds4.pdf
ddc_controls_part_1_pnwd-sa-883dddds4.pdf
 
Relay testing procedure
Relay testing procedure Relay testing procedure
Relay testing procedure
 
TSE SCADA Design presentation new
TSE SCADA Design presentation newTSE SCADA Design presentation new
TSE SCADA Design presentation new
 
Ultrasonic guided waves application on oil and gas pipeline
Ultrasonic guided waves application on oil and gas pipelineUltrasonic guided waves application on oil and gas pipeline
Ultrasonic guided waves application on oil and gas pipeline
 
project presentation on "THMC"
project presentation on "THMC"project presentation on "THMC"
project presentation on "THMC"
 
11.methods to determine the overall health and condition of large power trans...
11.methods to determine the overall health and condition of large power trans...11.methods to determine the overall health and condition of large power trans...
11.methods to determine the overall health and condition of large power trans...
 
Methods to determine the overall health and condition of large power transfor...
Methods to determine the overall health and condition of large power transfor...Methods to determine the overall health and condition of large power transfor...
Methods to determine the overall health and condition of large power transfor...
 
Transfomer diagnostics/sanjeet-1308143
Transfomer diagnostics/sanjeet-1308143Transfomer diagnostics/sanjeet-1308143
Transfomer diagnostics/sanjeet-1308143
 
Fusing Metering Voltages for High Capacity Circuits
Fusing Metering Voltages for High Capacity CircuitsFusing Metering Voltages for High Capacity Circuits
Fusing Metering Voltages for High Capacity Circuits
 
Preventive maintenance
Preventive maintenancePreventive maintenance
Preventive maintenance
 
Industrial monitoring and control systems using andriod application
Industrial monitoring and control systems using andriod applicationIndustrial monitoring and control systems using andriod application
Industrial monitoring and control systems using andriod application
 
PDM IMPLIMENTATION
PDM IMPLIMENTATIONPDM IMPLIMENTATION
PDM IMPLIMENTATION
 
POWER TRANSFORMER UDAIPUR 29022012.ppt
POWER TRANSFORMER UDAIPUR 29022012.pptPOWER TRANSFORMER UDAIPUR 29022012.ppt
POWER TRANSFORMER UDAIPUR 29022012.ppt
 

Recently uploaded

Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfme23b1001
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptSAURABHKUMAR892774
 
Introduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxIntroduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxk795866
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
DATA ANALYTICS PPT definition usage example
DATA ANALYTICS PPT definition usage exampleDATA ANALYTICS PPT definition usage example
DATA ANALYTICS PPT definition usage examplePragyanshuParadkar1
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...asadnawaz62
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .Satyam Kumar
 
Work Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvWork Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvLewisJB
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)dollysharma2066
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 

Recently uploaded (20)

Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdf
 
Arduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.pptArduino_CSE ece ppt for working and principal of arduino.ppt
Arduino_CSE ece ppt for working and principal of arduino.ppt
 
Introduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxIntroduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptx
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
DATA ANALYTICS PPT definition usage example
DATA ANALYTICS PPT definition usage exampleDATA ANALYTICS PPT definition usage example
DATA ANALYTICS PPT definition usage example
 
Design and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdfDesign and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdf
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .
 
Work Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvWork Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvv
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
Call Us ≽ 8377877756 ≼ Call Girls In Shastri Nagar (Delhi)
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 

A2.34+transformer+maintenance+tutorial

  • 1. Guide for Transformer Maintenance Tutorial of Cigre Working Group A2.34 Convener: Claude Rajotte, Canada 1
  • 2. Outline Introduction Maintenance strategy Maintenance process Component selection and maintenance Maintenance action catalogue Major work – transformer repair Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 2
  • 3. • Prepared to help transformer users define and apply best practices to transformer maintenance • Includes transformers rated 69 kV and above, and larger than 25 MVA • Subjects covered - best practice, checking and testing to evaluate transformer condition, intervals for the various actions, advanced maintenance activities, human and material factors Guide for Transformer Maintenance Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 3
  • 4. Commissioning T ransformer Operation TBMTB CM Corrective Maintenance Major W ork On-site or in W orkshop OK Interpretation Apply Special T ests and/or Intensive M onitoring (if needed) Normal? Y ES NO Major work Minor work Technical & Economic Evaluation Refurbish or Repair Scrap & Replace E nd of Life OLCM Condition A ssessment Maintenance Strategy (TBM, CBM, RCM) Tests & Checks C BM Transformer Operation and Maintenance Cycle Time Based Condition Monitoring Condition Based Maintenance On-line Condition Monitoring Time Based Maintenance TBCM CBM OLCM TBM Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 4
  • 5. Outline Introduction Maintenance strategy Maintenance process Component selection and maintenance Maintenance action catalogue Major work – transformer repair Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 5
  • 6. Maintenance Strategy Importance of Transformer Maintenance Life Used Possible Impacts of Lack of Maintenance - Baseline data not recorded, commissioning errors missed - Failure to detect early life problems within warranty period - Oil oxidation begins - OLTC contacts wear (medium and heavy loads) - Weathering and UV takes affect - Trends in condition not observed - Corrosion in severe environments - Visible affects of weathering and UV - Transducers go out of calibration - Fan and pump bearing wear - Trends in condition not observed - Gaskets and seals lose resilience, oil leaks manifest - Oil decay products affect paper insulation - Weathered paint, edge and spot corrosion - Miss opportunity to intercept accelerated ageing - Miss benefits of implementing a mid-life intervention - Uncertainty on remnant life - Oxidation and hydrolysis enters accelerated ageing stage - Paper DP drops, sometimes prematurely - OLTC and bushing failure rates increase - Paint system protection fails NEW 20% 40% 60% 80% 100% - Expect sludge if oil has been in poor condition - Exposure causes device malfunctions - Wiring and cable insulation en-brittle - Bad oil leaks need regular topping up - Dielectric withstand diminishes (moisture) - Expensive failure (often bushing or OLTC) Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 6
  • 7. The condition begins to deteriorate Y Z The condition change becomes detectable Good Condition X The condition has deteriorated to the point of failure Time Failure Maintenance Strategy Theoretical Transformer Condition Degradation - detect initial changes in condition that are relatively small compared to the deterioration necessary for failure to occur - have measurement or inspection intervals that are smaller than ∆T[XY]+∆T[YZ] to allow detection before failure occurs - have a period of time ∆T[YZ] that is long enough to be able to take the preventive action (ex: transformer outage) To be technically feasible, a condition assessment task should have the ability to: ∆T[XY] ∆T[YZ] Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 7
  • 8. Maintenance Strategy Survey on Maintenance Practices • There were significant differences on the task intervals for "visits“ • Oil test task intervals were generally in accordance with IEC 60422 • A majority of respondents used Electrical tests on a "Conditional based" criterion only - CBM • For "Accessories verification", task intervals varied significantly (from 1 to 12 years) • OLTC task intervals varied between 4 and 12 years • Bushing maintenance practices varied significantly between utilities KEY FINDINGS Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 8
  • 9. • Generally, the intervals between visits were longer than for GSU users and also varied greatly • Continuous DGA monitoring was used intensively by 50% of the respondents, particularly on their critical units • Electrical tests were performed by two thirds of the respondents For GSU transformers, it was observed that: • Visits were made at significantly shorter intervals • Periodic sampling for dissolved gas analysis (DGA), by the majority, were at intervals of one year or less • Continuous DGA monitoring was not often applied, probably due to the proximity of a maintenance crew • A minority of respondents were performing electrical tests periodically For Transmission transformers, it was observed that: Maintenance Strategy Survey on Maintenance Practices Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 9
  • 10. • Transformer characteristics and specifications • The quality of the components installed on the transformer • The required duty of the transformer (load, OLTC operation) • The transformer environment (temperature, humidity) • Historical transformer failure rate and failure types • The level of transformer redundancy and the consequences of unavailability • The failure mode and its effects on substation safety • Company culture and focus based on maintenance • The availability and costs of labour • The degree of implementation of modern technologies • The presence of a maintenance optimization program The survey showed that maintenance practices varied significantly between transformer users. Factors that can influence maintenance practice and effort: Maintenance Strategy Survey on Maintenance Practices Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 10
  • 11. Maintenance Strategy TBM and TBCM Maintenance Intervals Action Task Interval Remark Light Regular Intensive Visit 6 m 1 m 1 d In service Detailed visual inspection 1 y 3 m 2 w In service DGA 2 y 1 y 3 m Task interval may differ with monitoring Oil tests 6 y 2 y 1 y Cooling system cleaning Conditional Conditional Any Interval Outage may be required Accessories verification 12 y or Cond. 6-8 y 1-2 y Outage required Electrical basic tests Conditional Conditional Any Interval Outage required Insulation tests (DF or PF) Conditional 6-8 y 2-4 y Outage required OLTC internal inspection 12 y 6-8 y 4 y Consider number of operation, technology and manufacturer recommendations Survey showed many tasks were performed conditionally - CBM Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 11
  • 12. Regular The intensity of these maintenance task intervals: Light • Transformer equipped with components known to be very reliable • Low load and low number of tap-changer operations • Transformer does not operate in a harsh environment • Advanced technology that requires less maintenance • Low consequences from unexpected failure Intensive • Components that are known to require frequent attention • High load, high number of OLTC operations • Transformer operates in a harsh environment • Older transformer technologies • High consequences from unexpected failure Maintenance Strategy TBM and TBCM Maintenance Intervals • Any situation between these two Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 12
  • 13. Maintenance Strategy Condition Based Maintenance – Oil Test Results Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 13
  • 14. Maintenance Strategy Monitoring On-line Monitoring Data, measurements or samples (oil) are collected while the transformer is energized and in service. If these are performed at discrete intervals (in ‘visits’) then they provide only ‘snapshots’ of the transformer’s condition. Continuous On-line Monitoring Data, measurements or samples are collected in a continuum by transducers, sometimes at discrete sampling rates, while the transformer is energized and in service. This captures real time data to provide trends in transformer condition. Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 14
  • 15. Maintenance Strategy Continuous On-line Monitoring Modern continuous on-line monitoring adds an intelligent electronic device (IED) to the monitoring transducer(s). These devices have a measurement mechanism, that together with internal signal and data processing capabilities, can be described as ‘smart sensors’ or ‘smart systems’ capable of providing multiple measurement and control functions. Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 15
  • 16. Maintenance Strategy Continuous DGA On-Line Monitoring • This is the most commonly used on-line monitoring technology for transformers because: - It is a very good indicator for most transformer incipient faults - Early detection of incipient faults often avoids major failure • DGA sensor technologies include fuel cell, chromatography, semiconductor, photo-acoustic spectroscopy, thermal conductivity • Depending on the technology chosen, these systems can provide: - A single measurement of one specific gas - A single measurement of a composition of several gases with specific proportions and sensitivities - Multiple measurements of different gases • Gas-in-oil monitors often include a built-in moisture sensor Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 16
  • 17. • Systems with models or algorithms that calculate winding hot spot temperatures, rate of ageing of paper insulation, moisture content in paper or barriers, and effectiveness of cooling systems • Monitors condenser bushings by measuring leakage current through their capacitance taps • OLTC monitoring including mechanical conditions of the drive system, contact wear, temperature differential, dissolved gas analysis, tap position tracking/counting • Partial discharge detection using electrical, acoustical, or UHF signals Maintenance Strategy Other On-Line Monitoring Technologies Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 17
  • 18. Outline Introduction Maintenance strategy Maintenance process Component selection and maintenance Maintenance action catalogue Major work – transformer repair Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 18
  • 19. Planning Organization Execution Recording Optimization Maintenance Process Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 19
  • 20. • General information about the transformer (type, power, voltage) • Types of maintenance work to be done with relevant triggering points (time interval, event, condition, result of diagnostics) and operational status (energized, de-energized, or both de-energized and disconnected) • Qualifications and skills required to perform individual maintenance works • List of tasks related to individual maintenance works and the associated time required • Excerpt from, or reference to manufacturer’s manual giving detailed information (work steps, sequence, tools, material, safety aspects) • Maintenance report forms • Source of information for maintenance data collection and reporting – based on standard report forms A guideline would include: Maintenance Process Maintenance Planning– Maintenance Guidelines Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 20
  • 21. • Equipment Inventory • Computerized Maintenance Guidelines • Task lists and Operations • Maintenance plan • Maintenance schedules • Work orders • Outage Planning • Maintenance task tracking Maintenance Planning – Computer Aided Maintenance Management Systems (MMS) There are different computer aided tools for maintenance planning used by different utilities. All have this similar structure: Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 21
  • 22. Planning Organization Execution Recording Optimization Maintenance Process Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 22
  • 23. Level 1: Actions to be taken on certain transformer components, and generally described in a maintenance manual issued by the manufacturer. Examples: control operations, check of oil levels, exchange of consumable materials Maintenance Organization 5 Levels of Competence Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 23
  • 24. Level 2: Actions performed with basic written procedures and/or supporting equipment or devices, which are simple to use or to assemble, being part of the transformer or external to it. Examples: replacement / exchange of accessories or parts, routine checks. Maintenance Organization 5 Levels of Competence Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 24
  • 25. Level 3: Actions performed with complex written procedures or the use of special supporting equipment. Personnel are trained in using complex tools or processes. Examples: exchange of an original part or component, complex setting or re-setting Maintenance Organization 5 Levels of Competence Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 25
  • 26. Level 4: Actions performed requiring personnel trained in special techniques or technologies and utilization of special tools, and/or supporting equipment. Examples: modifications and upgrading activities, changes in functions, changes in the way of operation and use. Maintenance Organization 5 Levels of Competence Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 26
  • 27. Level 5: Actions needing specialist technical knowledge and with the support of industrial processes, industrial equipment or devices. Examples: complete inspections or revisions which require detailed dismantling of the equipment, its reconstruction, replacement of obsolete or worn parts or components. Maintenance Organization 5 Levels of Competence Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 27
  • 28. Planning Organization Execution Recording Optimization Maintenance Process Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 28
  • 29. • ground all bushings to avoid induction • use working at height safety measures • beware all bushings and leads when testing • beware opening pressurized access covers • identify and isolate cubicle auxiliary supplies • deactivate springs whilst working on OLTC • treat all tanks as confined spaces • beware of nitrogen gas filling • vent explosive gases accumulated by OLTCs or faults • perform a risk assessment on the need to deactivate the fire extinguishing system Maintenance Execution Safety Some safety aspects that have to be considered when working on a transformer: Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 29
  • 30. Planning Organization Execution Recording Optimization Maintenance Process Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 30
  • 31. Maintenance Recording Corrective Maintenance Tracking Data recorded for corrective maintenance should contain: • Unique identification of the transformer and its properties and location • Transformer location details • Time of maintenance action • Environmental conditions on site during maintenance action: Temperature, wind, rain, storm, humidity • Components, parts and material used and the parts replaced • Photographs: The ‘as found’ and ‘return to service’ condition, providing a reference for future work • Tests results taken before a return to service • Problem description: Failure, symptoms and circumstances • Problem cause: Data on what was causal to the failure or malfunction (in some cases the root-cause may not be obvious and requires more detailed diagnosis and investigation) • Remedy / Action: A report of the remedial action taken Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 31
  • 32. Planning Organization Execution Recording Optimization Maintenance Process Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 32
  • 33. Maintenance Optimization Reliability Centred Maintenance A combination of TBM, TBCM, CBM and OLCM is often used to maintain large complex assets such as power transformers. Reliability Centred Maintenance: The extent of maintenance to be performed is proportional to the level of risk associated with the transformer Risk = likelihood of failure * failure consequence The likelihood of failure can be represented by the "Health Index" of the unit (obsolescence, service history, technical condition) Failure consequence can also be mitigated by various control measures (protection upgrade, contingency plan, fire wall, oil containment) Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 33
  • 34. Outline Introduction Maintenance strategy Maintenance process Component selection and maintenance Maintenance action catalogue Major work – transformer repair Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 34
  • 35. Component Selection and Maintenance Transformer maintenance effort is strongly related to component selection. - Bushings - Oil preservation systems - Cooling systems - Gaskets - Gauges, indicators and relays - Control cabinets - Current transformers - On-load tap changers - De-energized tap changers - Surge arresters - Transformer active part - Sensing and monitoring devices This is because transformer components vary in quality, initial cost, maintainability, technology, reliability, life expectancy and potential for its failure and the consequences. Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 35
  • 36. Component Selection and Maintenance Bushings Oil Impregnated Paper (OIP) Bushings Advantages Disadvantages - Very long history with relatively good performances - Very low partial discharge – can be used at any voltage level - Relatively low cost - Minimal handling and storage requirements - DGA diagnostics are possible - Vulnerable to insulating oil leaks and water ingress if the gasket/sealing system is compromised - Higher risk of bushing explosion and resultant transformer fire - Positioning angle during transportation, handling and storage Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 36
  • 37. Component Selection and Maintenance Bushings Resin Impregnated Paper (RIP) Bushings Advantages Disadvantages -Non-flammable core -Bushing failure is less likely to release main tank oil -The core is less likely to be affected by water ingress -Very low partial discharge levels – can be used at any voltage level - No constraints on the attitude of the bushing during transportation, handling and storage -Relatively higher costs -Constraints on handling and storage -The oil end of the body must be protected from moisture during storage - Oil end of the bushing is susceptible to transport damage Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 37
  • 38. Porcelain Insulators Composite Insulators Component Selection and Maintenance Bushings Advantages Disadvantages -No ageing - Long history of good reliability -Could create exploding projectiles if the bushing fails -Relatively fragile in the event of shock or heavy force - Makes the bushing relatively heavy Advantages Disadvantages -Relatively lightweight -Lower risk of projectiles in the event of a bushing failure -High seismic withstand capability - Better hydrophobicity in polluted conditions -Less field experience compare to porcelain - Long term reliability is not known, early examples have suffered from surface deterioration Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 38
  • 39. Component Selection and Maintenance Bushings Types of Bushing Connections Draw Solid Bottom Draw Lead Conductor Connected Rod Black denotes the current path Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 39
  • 40. Outline Introduction Maintenance strategy Maintenance process Component selection and maintenance Maintenance action catalogue Major work – transformer repair Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 40
  • 41. Maintenance Action Catalogue Electrical Tests and DGA Diagnostic Matrix Frequency Response Analysis Dissolved Gas Analysis Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 41
  • 42. Maintenance Action Catalogue Electrical Test Example – Winding Resistance Detectable failures Contact problems on the tap selector, contact problems on the diverter switch, broken conductors, broken parallel strands, shorted winding disks, shorted winding layers, poor bushing connections Indication High internal temperatures, normally indicated by the DGA Test method A constant current source is used to feed a DC current into the winding. The test current and the voltage across the winding are measured and the resistance value is calculated. The accuracy of the equipment should guarantee that differences of 1% or even lower can be detected. Since the winding resistances are small, the test set should be connected in 4-wire technology. A relatively high no-load voltage enables a quick saturation of the core and a fast reaching of the stationary final value. It is recommended to measure the resistance for all taps of the OLTC. The resistance values should be corrected to 75°C according to IEC 60076 Part 1 Reference Test report of the manufacturer, fingerprint measurements Interpretation The measured winding resistance should not differ more than about 1% compared to the factory test report, if the winding temperature at measurement conditions is corrected to the factory conditions. Difference between phases usually less than 2-3%; Comparison between HV and LV resistance is usually in the order of the square of the winding ratio, when losses are balanced between HV and LV Comments In comparison to the LV winding, the resistance of the HV winding is much higher. Therefore identification of contact problems can be less sensitive on the HV side than the LV side. If the LV windings have very low resistance values, in the order of a few mΩ, it can be helpful to use the HV winding of the same limb in serial connection to get faster stabilization of the measurement current. The time needed to get stable readings can be in the order of tens of minutes for very low resistance values Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 42
  • 43. Maintenance Action Catalogue Dissolved Gas Analysis • One of the most useful and widely applied diagnostic tools • Gases commonly measured: Hydrogen (H2), Methane (CH4), Ethane (C2H6), Ethylene (C2H4), Acetylene (C2H2), Carbon Monoxide (CO), Carbon Dioxide (CO2), Oxygen (O2) and Nitrogen (N2) • No consensus about the absolute maximum level acceptable for each gas • Considers both gassing rates and absolute values of the different gases • Algorithms are used to: - Identify significant gases because they exceed a limit value - Evaluate gassing rates by comparing with previous gas concentrations - Assign weightings to each gas (because each gas is not produced by the same amount of energy) Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 43
  • 44. There are several methods used to interpret DGA results. Commonly, gas ratios are used to match the DGA gas profile to the generation source in the transformer (incipient faults), and identify the level of energy (temperature) required to produce them. Depending on the DGA profile (ratios), the gassing may be associated with: - Thermal faults of low temperature - Thermal faults of medium temperature - Thermal faults of high temperature - Discharges of low energy - Discharges of high energy - Partial discharge activity Maintenance Action Catalogue Dissolved Gas Analysis Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 44
  • 45. Tests for in-service oils: • GROUP 1: Minimum monitoring to ensure the oil is suitable for continued use - colour, water content, breakdown voltage, interfacial tension, acidity, dissipation/power factor and resistivity • GROUP 2: Additional tests that obtain specific information about the quality of the oil and also used to assist in the evaluation of the oil for continued use – particle count, oxidation stability, sediment and sludge • GROUP 3: Tests used to determine the suitability of the oil for use in the transformer and the oil’s environmental compliance – corrosive sulphur and PCB Maintenance Action Catalogue Oil Tests Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 45
  • 46. Maintenance Action Catalogue Relation between Transformer Problems and Main Parameters of the Oil Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 46
  • 47. Maintenance Action Catalogue Diagnostic Capabilities of Different OLTC Tests Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 47
  • 48. Maintenance Action Catalogue Maintenance Inspection Tasks • Thermography • Main tank and conservator • Cooling system • Accessories • Transformer cabinets • On-Load Tapchanger • Buchholz relay operation Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 48
  • 49. Maintenance Action Catalogue Insulation Drying • Remaining moisture in insulation during manufacturing • Humid air from outside during transportation and/or assembling in substation • Humid air from outside through the breather (non sealed) • Moisture ingress through gaskets • Chemical decomposition of cellulose • Moisture absorption due to exposure during maintenance • Topping-up of oil level made with humid oil (non dried) The moisture in a transformer is generated by several sources: Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 49
  • 50. A 1% increase in the moisture content of paper has the same effect as an increase in operating temperature of 8°C (doubling the rate of depolymerisation) - Accelerated ageing of the transformer insulation - Moisture in the oil combined with particles reduces the breakdown voltage of the oil and increases the risk of static electrification, partial discharge activity and tracking - High water content in cellulose increases the risk of bubbling during sudden overload or thermal stress, and the risk of dielectric breakdown Reference: CIGRE Brochure #349 Moisture Equilibrium and Moisture Migration within Transformer Insulation System Maintenance Action Catalogue Risks of Not Drying Insulation Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 50
  • 51. • On-line oil dryers - molecular sieve • Hot oil circulation • Hot oil + vacuum / hot oil + vacuum + hot oil spray / hot oil + vacuum ‘+ cold trap • Low frequency heating (LFH) / LFH + hot oil spray • Vapour phase Transformer Hot oil + Vacuum (24 h / day) LFH + Oil Spray 110 MVA / 70 kV 8 days 4 days 400 MVA / 400 kV 20-30 days 9 days The typical time needed to dry a transformer from initial moisture in the solid insulation of 3% to remaining moisture of 1%: Maintenance Action Catalogue Drying Techniques Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 51
  • 52. Maintenance Action Catalogue Physical and Chemical Oil Treatments • Reclamation is defined by the IEC as “a process that eliminates or reduces soluble and insoluble polar contaminants from the oil by chemical and physical processing”. • The contaminants in question are mostly oxidation products predominately in the oil but also on the solid insulation. • Chemical and physical processing is typically a combination of treatment with a sorbent material and filtering. • Oil reclamation scenarios: on-site on-line, on site off-line, tank to tank, large scale reclaiming Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 52
  • 53. Oil reclamation treatment is recommended because: • An increase in oil acidity accelerates paper ageing • Timely treatment, before advanced degradation, is important if the oil quality is to be maintained. Maintenance Action Catalogue Importance of Oil Treatments 3 oil treatments used for corrosive sulphur problems: • Adding metal passivator • Removal of corrosive sulphur • Oil exchange Reference: CIGRE Brochure #378 Copper Sulphide in Transformer Insulation Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 53
  • 54. Maintenance Action Catalogue Precautions for Invasive Work Work that requires oil to be partially or completely removed from the transformer may be regarded as invasive. Invasive work requires certain precautions to be taken because the transformer insulation is very sensitive to moisture, trapped air or gas bubbles, and particulate contaminants. Contaminants may easily be introduced either from airborne dust and humidity, or directly from people, tools and materials entering the transformer. Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 54
  • 55. Maintenance Action Catalogue Precautions for Invasive Work - Examples Planning the Work Evaluation of the amount of oil required to carry out, if the work required to access into the tank, proper confined space training, plans and permit, plan to reduce the exposure time to minimum, evaluate the ability of the tank to withstand vacuum Draining the Transformer Use of dry air to during oil draining, apply a positive pressure if the tank is left empty, avoid any loss of oil into the environment Access to the Transformer Extreme cleanliness, continuous flow of dry air entering the tank, suitable safety precautions need to be taken, gaskets replacement, cleaning cloths and boots, be aware of the compatibility of solvents, paints, glues and other chemicals, tools should be tethered and an inventory be kept Refilling the Transformer Vacuum filled (if the transformer was originally vacuum filled), air leaks elimination, remove any free water on the tank, use dry oil and use a reconditioning plan, limit the oil flow velocity, winding connected to earth, apply a standing time following oil filling Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 55
  • 56. Outline Introduction Maintenance strategy Maintenance process Component selection and maintenance Maintenance action catalogue Major work – transformer repair Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 56
  • 57. Major Work – Transformer Repair Definition On-site repair is invasive work, performed in-situ, where it is necessary to partly or completely drain oil and remove the main covers in order to repair or upgrade the transformer . The level of expertise and the need for high voltage tests may vary, depending on the complexity of the work. Repairs are categorized as follows: - Minor repairs such as replacement of bushings or tap changers, repair of connections - Major repairs such as exchange of windings, repair of the core, modifications or upgrades Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 57
  • 58. Major Work – Transformer Repair Advantages of On-site Repair • Transportation difficult or impossible: disused railway, axle load limits, changed road alignment, bridges, roundabouts • High transportation costs • High transportation risks: poor road conditions, heavily aged insulation • Reduced down-time by avoiding transportation: avoid higher losses in the network due to changes in optimum power flow, loss of energy sales, loss of water in a hydro plant, penalty in case of non delivery of energy; time saving 1 - 3 months On-site repair might have advantages over factory repair: Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 58
  • 59. Major Work – Transformer Repair Process • The process of on-site major repair can with appropriate resources and planning effectively emulate a workshop repair. Some adaptations are needed due to site conditions. • A detailed plan for each activity will allow adequate time for the equipment and material to arrive at the proper phase of the repair. Planning should be updated daily by the site supervisor and reviewed periodically. Site personnel require regular contact with their service centre or factory for logistical, administrative and technical support. • On-site repair requires excellent logistics, competent planning as well as the flexibility to adapt to the unforeseen (inherent to most repair situations) in order to minimize delays to the schedule. Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 59
  • 60. Major Work – Transformer Repair Testing Site testing extends the repair time and represents significant costs. However, these tests will reduce future risk of unexpected failure. In defining the scope of site testing, the following aspects should be considered: • Type of repair and scope of work (replacing bushings, winding replacement) • Possible consequences of a failure • Stress from the network (lightning, short-circuit, overload) • Urgency and loss of production due to down- time • Repair/refurbishment versus replacement Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 60
  • 61. Suggested categories of on-site testing: Transformer Category Characteristics Category 1 - Nominal Voltage < 72.5 kV - Units with no critical loss of production in case of failure, or with good redundancy or a ‘’’spare unit - Limited risk of fire in case of failure (collateral damages) - Repair of connections, replacement of bushing or OLTC - No expected overload. Good protection system. Low risk of short-circuit on the network - Urgency to put the units back in service to meet operation constraints - No availability of testing equipment Category 2 - Nominal Voltage >=72.5kV and < 170 kV - Repair involving work on the active part Category 3 - Nominal Voltage >=170kV and <= 300 kV - Transformers with severe consequences in case of failure and/or significant loss of ’’ production - generation or industrial applications - Transformer with no spare unit Category 4 - Nominal Voltage > 300 kV - Repair that incorporates a new winding design - Upgrade with new design to reach higher MVA / Voltage. - Transformers with high lightning exposure Major Work – Transformer Repair Testing Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 61
  • 62. Category Recommended tests Category 1 - Low voltage tests: winding resistance, ratio, insulation resistance of windings & core, power factor - Functional tests and checks on indicators, control circuits, relays and OLTC - Dielectric Response (DR) and Frequency Response Analysis (FRA) as a fingerprint - Continuous increase of voltage whenever possible (GSU) without any load: 20%–100% Un - Connection to the network with no load at 100% Un for 12 hours with monitoring of gas (preferably on-line or off-line after one hour and then every 3 hours). In any case, the results of DGA should be analyzed before putting the transformer back under load - Incremental load rise (whenever possible) - Monthly follow-up of DGA over a 6 month period Category 2 - Same tests as for Category 1 - Induced voltage tests with partial discharge (PD) measurement according to IEC 60076-3 or IEEE ‘’C57.12.00 standard Category 3 - Same tests as for Category 2 - In case of delta connected HV windings, separate source AC withstand voltage test (applied voltage ‘’test) at 80% of the nominal voltage test according to IEC 60076-3 or IEEE C57.12.00 standard Category 4 - Same tests as for Category 3 - Lightning impulse test, switching impulse test and chopped impulse test may be performed; ‘’nevertheless, the added value of these has to be evaluated (costs involved, availability of test ‘’equipments) Major Work – Transformer Repair Testing Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 62
  • 63. Major Work – Transformer Repair Economics Case Examples: - Problematic transportation - Problematic outage time - Repair of a faulted unit with core repair and windings replacement Factors to consider: - Costs of material and labour - Core and winding losses - Transportation - Outage time - Reliability and Tests Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 63
  • 64. Major Work – Transformer Repair Environmental Considerations Guide for Transformer maintenance – Tutorial of Cigre WG A2.34 64