Harmonic Mitigation in Distribution System
Nyein Nyein Chan
Department of Electrical Power Engineering
ABSTRACT
The advent of power electronics and computerized
equipment in recent decades has brought enhanced
efficiency and improved system but at the same time
also created harmonics and waveform distortion to the
power system network. Due to the growing use of
nonlinear load equipment and new technologies in
buildings, harmonic currents and voltages generated
in distribution systems pose a new problem for
electrical engineers. This is a serious problem when
power quality is a prime concern. Harmonics are the
main types of power quality problem that are very
common to the power system containing electric arc
furnace (EAF). Electric arc furnace (EAFs) are widely
used in steelmaking and in melting of nonferrous
metals. In this paper, EAF is presented guide lines for
the accurate evaluation of harmonics generated in
No.(3) Steel Mill, Ywama, Yangon. Passive filters
have been most commonly used to limit the flow of
harmonic currents in distribution systems. Their
performance is limited to a few harmonics, and they
can introduce resonance in the power system.
KEY WORDS: Simulation by Using Matlab Software,
Passive Filters, Nonlinear Load, Total Harmonic
Distortion, Electric Arc Furnace, IEEE Std 519
1. INTRODUCTION
Harmonics are a mathematical way of describing
distortion to a voltage or current waveform. The term
harmonic refers to a component of a waveform that
occurs at an integer multiple of the fundamental
frequency [1]. And the objective of the electric utility
is to deliver sinusoidal voltage at fairly constant
magnitude throughout their system. There are
nonlinear loads on the system that produce harmonic
currents. These non-linear elements generate network
voltages with frequencies different from the network
frequency or absorb currents with non
waveforms. The widespread and growing of these
International Journal of Trend in Scientific Research and Development (IJTSRD)
International Open Access Journal | www.ijtsrd.com
ISSN No: 2456 - 6470 | Volume - 3 | Issue – 1 | Nov
www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018
n Distribution System by using Passive Filters
Nyein Nyein Chan1
, Hnin Wai Hlaing2
1
Assistant Lecture, 2
Professor
Electrical Power Engineering, Technological University Thanlyin, Thanlyin
The advent of power electronics and computerized
equipment in recent decades has brought enhanced
efficiency and improved system but at the same time
also created harmonics and waveform distortion to the
power system network. Due to the growing use of
inear load equipment and new technologies in
buildings, harmonic currents and voltages generated
in distribution systems pose a new problem for
electrical engineers. This is a serious problem when
power quality is a prime concern. Harmonics are the
pes of power quality problem that are very
common to the power system containing electric arc
furnace (EAF). Electric arc furnace (EAFs) are widely
used in steelmaking and in melting of nonferrous
metals. In this paper, EAF is presented guide lines for
accurate evaluation of harmonics generated in
No.(3) Steel Mill, Ywama, Yangon. Passive filters
have been most commonly used to limit the flow of
harmonic currents in distribution systems. Their
performance is limited to a few harmonics, and they
oduce resonance in the power system.
Simulation by Using Matlab Software,
Passive Filters, Nonlinear Load, Total Harmonic
Distortion, Electric Arc Furnace, IEEE Std 519-1992.
Harmonics are a mathematical way of describing
distortion to a voltage or current waveform. The term
harmonic refers to a component of a waveform that
occurs at an integer multiple of the fundamental
frequency [1]. And the objective of the electric utility
is to deliver sinusoidal voltage at fairly constant
magnitude throughout their system. There are
nonlinear loads on the system that produce harmonic
linear elements generate network
voltages with frequencies different from the network
frequency or absorb currents with non-sinusoidal
waveforms. The widespread and growing of these
loads has greatly increased the flow of harmonic
currents on facility distribution systems. The interest
on problems related to non linear devices and their
influence on the systems increased considerably since
1980. This is due to the development of new power
semiconductor devices and, as a consequence, the
development of new converters that affects linearity
in electric power signals substantially. The increa
on the utilization of electronic equipment modified
the sinusoidal nature of electrical signals. These
equipments increase the current waveform distortion
and as a consequence, increment the voltage
waveform distortion [2] [3].
The electric arc furnace is either AC or DC operated.
It transfer the electric energy (electric arc) to melt the
scrap material held by the furnace. The arc produced
between the electrodes low voltages and high current
supplied by the furnace transformer. [5].
II. PRINCIPLE OF ARC F
OPERATION
The operation of electric arc furnace can be divided in
into intervals namely melting and refining periods.
The refining period is further divided in several
stages. During the melting stage, the electrode is
lowered through a hydraulic ac
maintain the stable arc. The furnace draws active
power in this condition. More and more buckets of
scrap material are added into the furnace during the
melting stages. During the refining stage, a long arc is
established. The factors involved during the operation
of the furnace are electrode position, electrode arm
control scheme, supply voltage, operation reactance
and the materials used for melting and refining. The
installations of both AC and DC electric arc furnace
[4] have been shown in figure.1(a) and 1(b)
respectively as shown.
Research and Development (IJTSRD)
www.ijtsrd.com
1 | Nov – Dec 2018
Dec 2018 Page: 548
sing Passive Filters
Thanlyin, Myanmar
loads has greatly increased the flow of harmonic
currents on facility distribution systems. The interest
on problems related to non linear devices and their
nfluence on the systems increased considerably since
1980. This is due to the development of new power
semiconductor devices and, as a consequence, the
development of new converters that affects linearity
in electric power signals substantially. The increase
on the utilization of electronic equipment modified
the sinusoidal nature of electrical signals. These
equipments increase the current waveform distortion
and as a consequence, increment the voltage
is either AC or DC operated.
It transfer the electric energy (electric arc) to melt the
scrap material held by the furnace. The arc produced
between the electrodes low voltages and high current
supplied by the furnace transformer. [5].
PRINCIPLE OF ARC FURNACE
The operation of electric arc furnace can be divided in
into intervals namely melting and refining periods.
The refining period is further divided in several
stages. During the melting stage, the electrode is
lowered through a hydraulic actuator system to
maintain the stable arc. The furnace draws active
power in this condition. More and more buckets of
scrap material are added into the furnace during the
melting stages. During the refining stage, a long arc is
lved during the operation
of the furnace are electrode position, electrode arm
control scheme, supply voltage, operation reactance
and the materials used for melting and refining. The
installations of both AC and DC electric arc furnace
in figure.1(a) and 1(b)
International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456
@ IJTSRD | Available Online @ www.ijtsrd.com
Figure 1(a) Installation of AC Arc Furnace
Figure 1(b) Installation of DC Arc Furnace
A transformer directly energizes furnace electrodes in
a high current circuit in AC arc furnace , whereas DC
furnace employ a controlled rectifier to supply dc to
the furnace electrodes. Arc furnace operation may be
classified into stages, depending on the status of the
melt and the time lapse from the initial energizing of
the unit. During the melting period, pieces o
create momentary short circuits on the secondary side
of the furnace transformer. These load changes effect
the arc characteristics, causing fluctuations of current.
The current fluctuations cause variations in reactive
power, which cause a momentary voltage drop or
flicker, both at the supply bus and at nearby buses in
the interconnected system. The arc currents are more
uniform during the refining period and result in less
impact on the power quality of the system. Arc
furnaces also create harmonic load currents and
asynchronous spectral components. Harmonics
represent an important power quality issue, because
they may cause undesirable operating conditions.
Figure.2 Complete Model of No (3) Ywama Steel
Mill
100MVA
66kV Source
60MVA
66/33kV TR
15
33/11
15MVA
33/11kV TR
33kV Bus bar 33kV Bus bar
12MVA
11/0.42kV TR
8MVA
11/0.2kV TR
SVC
EAF
Furnace
LRF
Furnace
5MVA
11/0.4kV TR
2.5MVA
11/0.4kV
11kV Bus bar
11kV Bus bar
Wire
Production
Bolt Nut
Production
Index::
TR =Transformer
International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456
www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018
Figure 1(a) Installation of AC Arc Furnace
Figure 1(b) Installation of DC Arc Furnace
A transformer directly energizes furnace electrodes in
a high current circuit in AC arc furnace , whereas DC
e employ a controlled rectifier to supply dc to
the furnace electrodes. Arc furnace operation may be
classified into stages, depending on the status of the
melt and the time lapse from the initial energizing of
the unit. During the melting period, pieces of steel
create momentary short circuits on the secondary side
of the furnace transformer. These load changes effect
the arc characteristics, causing fluctuations of current.
The current fluctuations cause variations in reactive
ary voltage drop or
flicker, both at the supply bus and at nearby buses in
the interconnected system. The arc currents are more
uniform during the refining period and result in less
impact on the power quality of the system. Arc
ic load currents and
asynchronous spectral components. Harmonics
represent an important power quality issue, because
they may cause undesirable operating conditions.
Figure.2 Complete Model of No (3) Ywama Steel
III. VOLTAGE AND CURRENT HARMONIC
LIMITS
According to IEEE Std 519-
distortion on power system 69kV and below is limited
to 5.0% total harmonic distorti
individual harmonic limited to 3%. The current
harmonic limits vary based on the short circuit
strength of the system they are being injected into.
Essentially, the more system is able to handle
harmonic currents, the more the customer i
to inject [6].
Table .1 IEEE Std 519-1992 Harmonic Voltage
Limits Voltage Distortion Limits
Bus Voltage at
PCC
Individual
Voltage
Distortion (%)
Below 69kV 3.0
69kV to 161kV 1.5
161kV and
above
1.0
Table .2 IEEE Std 519-1992 Harmonic Current Limits
Current Distortion Limits for General Distribution
Systems (120V Through 69kV)
Maximum Harmonic Current Distortion in
Percent of IL
Individual Harmonic Order ( Odd Harmonic )
ISC/IL <11
11-
16
17
22
<20 4.0 2.0 1.5
20<50 7.0 3.5 2.5
50<100 10.0 4.5 4.0
100<1000 12.0 5.5 5.0
>1000 15.0 7.0 6.0
IV. HARMONIC FILTERS
Harmonics currents are created by nonlinear loads
that generate non-sinusoidal current on distribution
power system. Nonlinear devices such as power
electronics converters can inject harmonics alternating
currents (AC) in the electrical power system.
Therefore, the growing use of nonlinear loads in
commercial, residential and industrial are becoming
more harmonic problems at utilities and customers
sides. Harmonics are the most important drawbacks of
power quality in the power distribution system. With
the increase of nonlinear loads in the power system,
more and more harmonic mitigation techniques are
required. There are three types of filter
15MVA
11kV TR
MVA
kV TR
2MVA
11/6.6kV TR
Nut
uction
Crusher Motor
International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456-6470
Dec 2018 Page: 549
VOLTAGE AND CURRENT HARMONIC
1992, harmonic voltage
distortion on power system 69kV and below is limited
to 5.0% total harmonic distortion (THD) with each
individual harmonic limited to 3%. The current
harmonic limits vary based on the short circuit
strength of the system they are being injected into.
Essentially, the more system is able to handle
harmonic currents, the more the customer is allowed
1992 Harmonic Voltage
Voltage Distortion Limits
Individual
Voltage
Distortion (%)
Total Voltage
Distortion
THDV (%)
5.0
2.5
1.5
1992 Harmonic Current Limits
Current Distortion Limits for General Distribution
Systems (120V Through 69kV)
Maximum Harmonic Current Distortion in
Percent of IL
Individual Harmonic Order ( Odd Harmonic )
17-
22
23-
35
>35 TDD
1.5 0.6 0.5 5.0
2.5 1.0 0.5 8.0
4.0 1.5 0.7 12.0
5.0 2.0 1.0 15.0
6.0 2.5 1.4 20.0
HARMONIC FILTERS
Harmonics currents are created by nonlinear loads
sinusoidal current on distribution
power system. Nonlinear devices such as power
electronics converters can inject harmonics alternating
currents (AC) in the electrical power system.
fore, the growing use of nonlinear loads in
commercial, residential and industrial are becoming
more harmonic problems at utilities and customers
sides. Harmonics are the most important drawbacks of
power quality in the power distribution system. With
increase of nonlinear loads in the power system,
more and more harmonic mitigation techniques are
required. There are three types of filter
International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456
@ IJTSRD | Available Online @ www.ijtsrd.com
1. Passive Filters
2. Active Filters
3. Hybrid Filters [8][9].
Passive Filters:
Passive filters are basically topologies or
arrangements of R, L, and C elements connected in
different combinations to gain desired suppression of
harmonics. They are employed either to shunt the
harmonic currents off the line or to block their flow
between parts of the system by tuning the elements to
create a resonance at a selected frequency. They also
provide the reactive power compensation to the
system and hence improve the power quality.
However, they have the disadvantage of potentially
interacting adversely with the power system and the
performance of passive filter depends mainly on the
system source impedance. On the other hand they can
be used for elimination of a particular harmonic
frequency, so number of passive filters increase with
increase of harmonics on the system.
They can be classified into:
1. Passive Shunt Filter
2. Passive Series Filter
a. i. Passive Shunt Filter
C C
L L
Figure .3 Shunt filter connection
Passive filters are connected in parallel with the
system. Figure .3 illustrates the parallel passive filter
connection. The shunt may be grounded in one of its
terminations, and then it will be passed only for the
tuned harmonic current and a part of the fundamental
current. The passive shunt type filter is that
carry fraction of current so the whole system AC
power losses are reduced compare to series type filter.
V. ii. Passive Series Filter
Figure .4 Series filter connection
Passive filters are connected in series with the system.
Figure .4 illustrates the series passive filter
International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456
www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018
Passive filters are basically topologies or
arrangements of R, L, and C elements connected in
different combinations to gain desired suppression of
harmonics. They are employed either to shunt the
harmonic currents off the line or to block their flow
en parts of the system by tuning the elements to
create a resonance at a selected frequency. They also
provide the reactive power compensation to the
system and hence improve the power quality.
However, they have the disadvantage of potentially
g adversely with the power system and the
performance of passive filter depends mainly on the
system source impedance. On the other hand they can
be used for elimination of a particular harmonic
frequency, so number of passive filters increase with
Figure .3 Shunt filter connection
Passive filters are connected in parallel with the
Figure .3 illustrates the parallel passive filter
connection. The shunt may be grounded in one of its
terminations, and then it will be passed only for the
tuned harmonic current and a part of the fundamental
current. The passive shunt type filter is that it only
carry fraction of current so the whole system AC
power losses are reduced compare to series type filter.
ii. Passive Series Filter
Figure .4 Series filter connection
Passive filters are connected in series with the system.
Figure .4 illustrates the series passive filter
connection. A passive type series passive filter has
property of purely inductive type or LC tuned
characteristics. The main component of passive serie
filter in AC line reactor and DC link filter.
V. SIMULATION MODELS AND RESULTS
Figure .5 Simulation Model of Electric Arc Furnace
without Filter in No.(3) Ywama Steel Mill
Figure.6 Total Harmonic Distortion Voltage
Waveform without Filter for EAF wit
to fundamental)
Figure.7 Total Harmonic Distortion Voltage
Waveform without Filter for EAF with List (relative
to fundamental)
Figure.8 Total Harmonic Distortion Current
Waveform without Filter for EAF with Bar (relative
to fundamenta
International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456-6470
Dec 2018 Page: 550
connection. A passive type series passive filter has
property of purely inductive type or LC tuned
characteristics. The main component of passive series
filter in AC line reactor and DC link filter.
SIMULATION MODELS AND RESULTS
Figure .5 Simulation Model of Electric Arc Furnace
without Filter in No.(3) Ywama Steel Mill
Figure.6 Total Harmonic Distortion Voltage
Waveform without Filter for EAF with Bar (relative
to fundamental)
Figure.7 Total Harmonic Distortion Voltage
Waveform without Filter for EAF with List (relative
to fundamental)
Figure.8 Total Harmonic Distortion Current
Waveform without Filter for EAF with Bar (relative
to fundamental)
International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456
@ IJTSRD | Available Online @ www.ijtsrd.com
Figure.9 Total Harmonic Distortion Current
Waveform without Filter for EAF with List (relative
to fundamental)
Figure.10 Simulation Model of Electric Arc Furnace
with Passive Filter (PF)
Figure.11 Total Harmonic Distortion Voltage
Waveform with PF for EAF with Bar (relative to
fundamental)
Figure.12 Total Harmonic Distortion Voltage
Waveform with PF for EAF with List (relative to
fundamental)
International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456
www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018
Figure.9 Total Harmonic Distortion Current
Waveform without Filter for EAF with List (relative
Figure.10 Simulation Model of Electric Arc Furnace
Figure.11 Total Harmonic Distortion Voltage
Waveform with PF for EAF with Bar (relative to
Figure.12 Total Harmonic Distortion Voltage
Waveform with PF for EAF with List (relative to
Figure.13 Total Harmonic Distortion Curre
Waveform with PF for EAF with Bar (relative to
fundamental)
Figure.14 Total Harmonic Distortion Current
Waveform with PF for EAF with List (relative to
fundamental)
Table.3 Comparison of Total Harmonics Voltage &
Current Distortion % without and wit
System THD
Without Filter 24.73%
With Passive Filter 2.62%
VI. CONCLUSION AND FUTURE SCOPE
The new block developed proved to be effective in
harmonic distortion analysis in a steel plants as
carried out in this paper. Here the total harmonic
distortion (THD) was measured by the THD block in
Simulink. The distortion for both voltage and current
due to the steel plant were excessive and could be
mitigated using passive filter of commensurable
design in proposed. According to the simulation
results above the figures, the THD
and THDI(%) is 8.26% at the point of common
coupling (PCC) without using the mitigation
techniques in present conditions. The harmonic
twenty orders are measured and among them, 11
13th
orders are dominant in No.(3) Steel Mill
(Ywama, Yangon). After using the passive harmonic
filters, the THDV is 2.62% and
fundamental value, thus meeting the limit of harmonic
standard of IEEE Standard 519
is harmonic mitigation in distribution system by using
active and hybrid harmonic filters.
International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456-6470
Dec 2018 Page: 551
Figure.13 Total Harmonic Distortion Current
Waveform with PF for EAF with Bar (relative to
fundamental)
Figure.14 Total Harmonic Distortion Current
Waveform with PF for EAF with List (relative to
fundamental)
Table.3 Comparison of Total Harmonics Voltage &
Current Distortion % without and with PF
THDV (%) THDI (%)
24.73% 8.26%
2.62% 1.52%
CONCLUSION AND FUTURE SCOPE
The new block developed proved to be effective in
harmonic distortion analysis in a steel plants as
carried out in this paper. Here the total harmonic
distortion (THD) was measured by the THD block in
Simulink. The distortion for both voltage and current
ue to the steel plant were excessive and could be
mitigated using passive filter of commensurable
design in proposed. According to the simulation
results above the figures, the THDV(%) is 24.73%
and THDI(%) is 8.26% at the point of common
without using the mitigation
techniques in present conditions. The harmonic
twenty orders are measured and among them, 11st
and
orders are dominant in No.(3) Steel Mill
(Ywama, Yangon). After using the passive harmonic
is 2.62% and THDI is 1.52% of the
fundamental value, thus meeting the limit of harmonic
standard of IEEE Standard 519-1992. The future work
is harmonic mitigation in distribution system by using
active and hybrid harmonic filters.
International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456
@ IJTSRD | Available Online @ www.ijtsrd.com
ACKNOWLEDGMENTS
I greatly appreciate to all teachers from the
Department of Electrical Power Engineering,
Technological University (Thanlyin) who work in
Research.
I would like to give great thanks to Research
Department of Electrical Power Engineering,
Technological University (Thanlyin) f
permission to study related on-going research
projects.
REFERENCES
1. Ashok, S. “Harmonic in distribution system of an
educational institution” IEEE transactions on
power quality 98 pages 145-150, 1998.
2. Alejandro O.M. and Gustavo A.R. “Instantaneous
p-q theory for harmonic compensation via shunt
active power filter” IEEE transactions on power
electronics and power quality applications, page
1-4, 2013.
3. Jamil M. “Harmonics in Adjustable Speed Drives”
IEEE transactions on information and emerging
technologies, page 1-6, 2007.
International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456
www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018
to all teachers from the
Department of Electrical Power Engineering,
Technological University (Thanlyin) who work in
I would like to give great thanks to Research
Department of Electrical Power Engineering,
Technological University (Thanlyin) for kind
going research
Ashok, S. “Harmonic in distribution system of an
educational institution” IEEE transactions on
150, 1998.
Alejandro O.M. and Gustavo A.R. “Instantaneous
q theory for harmonic compensation via shunt
active power filter” IEEE transactions on power
electronics and power quality applications, page
Jamil M. “Harmonics in Adjustable Speed Drives”
IEEE transactions on information and emerging
4. Reuben F. Burch IV, Senior Member, IEEE
“Thoughts on Improving the Electric Arc Furnace
Model”.
5. Amarjeet Singh, Ravindra Kumar Singh, Asheesh
Kumar Singh “Power Quality Issue of Electric
Arc Furnace and their Mitigations
ISSN: 2349-6495(p) 2456
4, Apr-2017.
6. Thomas M. Blooming, P.E, Daniel J. Carnovale
P.E. “Application of IEEE Std 519
Harmonic Limits”.
7. Rooh UI Amin Shaikh, Abdul Basit Lashari, Irfan
Ansari, “Harmonic Analysis and Mitigation U
Passive Filters” January, 2015.
8. Rustemli, S. and Cengiz, M.S. 2016, “Passive
Filter Solution and Simulation Perfornance in
Industrial Plants”. Bitlis Eren University J Science
and Technology, Turkey.
9. Nassif, A.B., Xu, W. and Freitas
Investigation on the Selection of Filter Topologes
for Passive Filter Applications”. IEEE PES
General Meeting, 2009.
International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456-6470
Dec 2018 Page: 552
Reuben F. Burch IV, Senior Member, IEEE
“Thoughts on Improving the Electric Arc Furnace
Amarjeet Singh, Ravindra Kumar Singh, Asheesh
Kumar Singh “Power Quality Issue of Electric
Arc Furnace and their Mitigations – A Review”,
6495(p) 2456-1908(O), Vol-4, Issue-
Thomas M. Blooming, P.E, Daniel J. Carnovale
P.E. “Application of IEEE Std 519-1992
Rooh UI Amin Shaikh, Abdul Basit Lashari, Irfan
Ansari, “Harmonic Analysis and Mitigation Using
Passive Filters” January, 2015.
Rustemli, S. and Cengiz, M.S. 2016, “Passive
Filter Solution and Simulation Perfornance in
Industrial Plants”. Bitlis Eren University J Science
Nassif, A.B., Xu, W. and Freitas, W.2009, “An
Investigation on the Selection of Filter Topologes
for Passive Filter Applications”. IEEE PES

More Related Content

What's hot

Unified power quality conditioner for compensating power quality problem ad
Unified power quality conditioner for compensating power quality problem adUnified power quality conditioner for compensating power quality problem ad
Unified power quality conditioner for compensating power quality problem adIAEME Publication
 
A Svc Light Based Technique for Power Quality Improvement for Grid Connected ...
A Svc Light Based Technique for Power Quality Improvement for Grid Connected ...A Svc Light Based Technique for Power Quality Improvement for Grid Connected ...
A Svc Light Based Technique for Power Quality Improvement for Grid Connected ...IOSR Journals
 
Analysis for underground cable system, lakeside pokhara
Analysis for underground cable system, lakeside pokharaAnalysis for underground cable system, lakeside pokhara
Analysis for underground cable system, lakeside pokharaBishal Rimal
 
High PV Penetration Impact on European-based LV Residential Network
High PV Penetration Impact on European-based LV Residential NetworkHigh PV Penetration Impact on European-based LV Residential Network
High PV Penetration Impact on European-based LV Residential NetworkTELKOMNIKA JOURNAL
 
NEW STATCOM CONTROL SCHEME FOR POWER QUALITY IMPROVEMENT IN WIND FARM.
NEW STATCOM CONTROL SCHEME FOR POWER QUALITY IMPROVEMENT IN WIND FARM.NEW STATCOM CONTROL SCHEME FOR POWER QUALITY IMPROVEMENT IN WIND FARM.
NEW STATCOM CONTROL SCHEME FOR POWER QUALITY IMPROVEMENT IN WIND FARM.sannuthi yaramapu
 
Transmission and distribution system of nepal
Transmission and distribution system of nepalTransmission and distribution system of nepal
Transmission and distribution system of nepalBishal Rimal
 
An improved iupqc controller to provide additional grid voltage regulation as...
An improved iupqc controller to provide additional grid voltage regulation as...An improved iupqc controller to provide additional grid voltage regulation as...
An improved iupqc controller to provide additional grid voltage regulation as...LeMeniz Infotech
 
statcom-grid connected wind energy generating system for power qualityy impro...
statcom-grid connected wind energy generating system for power qualityy impro...statcom-grid connected wind energy generating system for power qualityy impro...
statcom-grid connected wind energy generating system for power qualityy impro...Venu Gopal
 
ANALYSIS AND SIMULATION OF HARMONICS FOR VARIOUS RESIDENTIAL LOADS USING SIMU...
ANALYSIS AND SIMULATION OF HARMONICS FOR VARIOUS RESIDENTIAL LOADS USING SIMU...ANALYSIS AND SIMULATION OF HARMONICS FOR VARIOUS RESIDENTIAL LOADS USING SIMU...
ANALYSIS AND SIMULATION OF HARMONICS FOR VARIOUS RESIDENTIAL LOADS USING SIMU...ijiert bestjournal
 
PV Integrated to Micro grid for power quality improvement
PV Integrated to Micro grid for power quality improvementPV Integrated to Micro grid for power quality improvement
PV Integrated to Micro grid for power quality improvementNiteesh Shanbog
 
Power Quality Improvement by UPQC based on Voltage Source Converters
Power Quality Improvement by UPQC based on Voltage Source ConvertersPower Quality Improvement by UPQC based on Voltage Source Converters
Power Quality Improvement by UPQC based on Voltage Source ConvertersIJRST Journal
 
1. power system losses introduction
1. power system losses introduction1. power system losses introduction
1. power system losses introductionYusuf A. KHALIL
 
Power Quality Improvement in Power System using UPFC
Power Quality Improvement in Power System using UPFCPower Quality Improvement in Power System using UPFC
Power Quality Improvement in Power System using UPFCijtsrd
 
Analysis of Power Factor Improvement Techniques in case of Non Linear System ...
Analysis of Power Factor Improvement Techniques in case of Non Linear System ...Analysis of Power Factor Improvement Techniques in case of Non Linear System ...
Analysis of Power Factor Improvement Techniques in case of Non Linear System ...Kaustubh Nande
 

What's hot (20)

Power quality issues ppt
Power quality issues pptPower quality issues ppt
Power quality issues ppt
 
Unified power quality conditioner for compensating power quality problem ad
Unified power quality conditioner for compensating power quality problem adUnified power quality conditioner for compensating power quality problem ad
Unified power quality conditioner for compensating power quality problem ad
 
A Svc Light Based Technique for Power Quality Improvement for Grid Connected ...
A Svc Light Based Technique for Power Quality Improvement for Grid Connected ...A Svc Light Based Technique for Power Quality Improvement for Grid Connected ...
A Svc Light Based Technique for Power Quality Improvement for Grid Connected ...
 
Analysis for underground cable system, lakeside pokhara
Analysis for underground cable system, lakeside pokharaAnalysis for underground cable system, lakeside pokhara
Analysis for underground cable system, lakeside pokhara
 
High PV Penetration Impact on European-based LV Residential Network
High PV Penetration Impact on European-based LV Residential NetworkHigh PV Penetration Impact on European-based LV Residential Network
High PV Penetration Impact on European-based LV Residential Network
 
NEW STATCOM CONTROL SCHEME FOR POWER QUALITY IMPROVEMENT IN WIND FARM.
NEW STATCOM CONTROL SCHEME FOR POWER QUALITY IMPROVEMENT IN WIND FARM.NEW STATCOM CONTROL SCHEME FOR POWER QUALITY IMPROVEMENT IN WIND FARM.
NEW STATCOM CONTROL SCHEME FOR POWER QUALITY IMPROVEMENT IN WIND FARM.
 
Transmission and distribution system of nepal
Transmission and distribution system of nepalTransmission and distribution system of nepal
Transmission and distribution system of nepal
 
An improved iupqc controller to provide additional grid voltage regulation as...
An improved iupqc controller to provide additional grid voltage regulation as...An improved iupqc controller to provide additional grid voltage regulation as...
An improved iupqc controller to provide additional grid voltage regulation as...
 
statcom-grid connected wind energy generating system for power qualityy impro...
statcom-grid connected wind energy generating system for power qualityy impro...statcom-grid connected wind energy generating system for power qualityy impro...
statcom-grid connected wind energy generating system for power qualityy impro...
 
Power quality.ppt
Power quality.pptPower quality.ppt
Power quality.ppt
 
ANALYSIS AND SIMULATION OF HARMONICS FOR VARIOUS RESIDENTIAL LOADS USING SIMU...
ANALYSIS AND SIMULATION OF HARMONICS FOR VARIOUS RESIDENTIAL LOADS USING SIMU...ANALYSIS AND SIMULATION OF HARMONICS FOR VARIOUS RESIDENTIAL LOADS USING SIMU...
ANALYSIS AND SIMULATION OF HARMONICS FOR VARIOUS RESIDENTIAL LOADS USING SIMU...
 
PV Integrated to Micro grid for power quality improvement
PV Integrated to Micro grid for power quality improvementPV Integrated to Micro grid for power quality improvement
PV Integrated to Micro grid for power quality improvement
 
1 elecrical systems
1 elecrical systems1 elecrical systems
1 elecrical systems
 
Power Quality Improvement by UPQC based on Voltage Source Converters
Power Quality Improvement by UPQC based on Voltage Source ConvertersPower Quality Improvement by UPQC based on Voltage Source Converters
Power Quality Improvement by UPQC based on Voltage Source Converters
 
Electric power system
Electric power systemElectric power system
Electric power system
 
1. power system losses introduction
1. power system losses introduction1. power system losses introduction
1. power system losses introduction
 
Power Quality Improvement in Power System using UPFC
Power Quality Improvement in Power System using UPFCPower Quality Improvement in Power System using UPFC
Power Quality Improvement in Power System using UPFC
 
Sliding mode control of Vienna rectifier with output voltage control
Sliding mode control of Vienna rectifier with output voltage controlSliding mode control of Vienna rectifier with output voltage control
Sliding mode control of Vienna rectifier with output voltage control
 
An Overview Of Power Quality
An Overview Of Power QualityAn Overview Of Power Quality
An Overview Of Power Quality
 
Analysis of Power Factor Improvement Techniques in case of Non Linear System ...
Analysis of Power Factor Improvement Techniques in case of Non Linear System ...Analysis of Power Factor Improvement Techniques in case of Non Linear System ...
Analysis of Power Factor Improvement Techniques in case of Non Linear System ...
 

Similar to Harmonic Mitigation in Distribution System by using Passive Filters

Simulation and Results of Static Var Compensator for Electric Arc Furnace No ...
Simulation and Results of Static Var Compensator for Electric Arc Furnace No ...Simulation and Results of Static Var Compensator for Electric Arc Furnace No ...
Simulation and Results of Static Var Compensator for Electric Arc Furnace No ...ijtsrd
 
DC-AC Inverter using SRF Hysteresis Current Controller for Interfacing Photo-...
DC-AC Inverter using SRF Hysteresis Current Controller for Interfacing Photo-...DC-AC Inverter using SRF Hysteresis Current Controller for Interfacing Photo-...
DC-AC Inverter using SRF Hysteresis Current Controller for Interfacing Photo-...IRJET Journal
 
A CONTROL APPROACH FOR GRID INTERFACING INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...
A CONTROL APPROACH FOR GRID INTERFACING  INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...A CONTROL APPROACH FOR GRID INTERFACING  INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...
A CONTROL APPROACH FOR GRID INTERFACING INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...IJMER
 
IRJET-Power Quality Effects on Nonlinear Loads
IRJET-Power Quality Effects on Nonlinear LoadsIRJET-Power Quality Effects on Nonlinear Loads
IRJET-Power Quality Effects on Nonlinear LoadsIRJET Journal
 
Power Quality Problems Related with the Interconnection of Wind Farms to the ...
Power Quality Problems Related with the Interconnection of Wind Farms to the ...Power Quality Problems Related with the Interconnection of Wind Farms to the ...
Power Quality Problems Related with the Interconnection of Wind Farms to the ...IRJET Journal
 
ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF R...
 ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF R... ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF R...
ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF R...ijiert bestjournal
 
Harmonic enhancement in microgrid with applications on sensitive loads
Harmonic enhancement in microgrid with applications on sensitive loadsHarmonic enhancement in microgrid with applications on sensitive loads
Harmonic enhancement in microgrid with applications on sensitive loadsIJECEIAES
 
INSTANTANEOUS POWER AND CURRENT STRATEGIES FOR CURRENT HARMONICS CANCELLATION...
INSTANTANEOUS POWER AND CURRENT STRATEGIES FOR CURRENT HARMONICS CANCELLATION...INSTANTANEOUS POWER AND CURRENT STRATEGIES FOR CURRENT HARMONICS CANCELLATION...
INSTANTANEOUS POWER AND CURRENT STRATEGIES FOR CURRENT HARMONICS CANCELLATION...ijiert bestjournal
 
AN OUTLINE OF HARMONICS AND MULTILEVEL
AN OUTLINE OF HARMONICS AND MULTILEVELAN OUTLINE OF HARMONICS AND MULTILEVEL
AN OUTLINE OF HARMONICS AND MULTILEVELIRJET Journal
 
Dynamic Power Factor Correction in a Non Linear Environment
Dynamic Power Factor Correction in a Non Linear EnvironmentDynamic Power Factor Correction in a Non Linear Environment
Dynamic Power Factor Correction in a Non Linear Environmentiosrjce
 
windfarmgridissues.pdf
windfarmgridissues.pdfwindfarmgridissues.pdf
windfarmgridissues.pdfsundeepsiddula
 
Wind farm grid issues
Wind farm grid issuesWind farm grid issues
Wind farm grid issuesRohil Kumar
 
Voltage Flicker Mitigation in Electric Arc Furnace using D-STATCOM
Voltage Flicker Mitigation in Electric Arc Furnace using D-STATCOMVoltage Flicker Mitigation in Electric Arc Furnace using D-STATCOM
Voltage Flicker Mitigation in Electric Arc Furnace using D-STATCOMIAES-IJPEDS
 
A Novel Technique for Enhancing Active and Reactive Power Quality for Renewab...
A Novel Technique for Enhancing Active and Reactive Power Quality for Renewab...A Novel Technique for Enhancing Active and Reactive Power Quality for Renewab...
A Novel Technique for Enhancing Active and Reactive Power Quality for Renewab...IJMER
 
Modeling and analysis of transformer
Modeling and analysis of transformerModeling and analysis of transformer
Modeling and analysis of transformerIJARIIT
 

Similar to Harmonic Mitigation in Distribution System by using Passive Filters (20)

Simulation and Results of Static Var Compensator for Electric Arc Furnace No ...
Simulation and Results of Static Var Compensator for Electric Arc Furnace No ...Simulation and Results of Static Var Compensator for Electric Arc Furnace No ...
Simulation and Results of Static Var Compensator for Electric Arc Furnace No ...
 
DC-AC Inverter using SRF Hysteresis Current Controller for Interfacing Photo-...
DC-AC Inverter using SRF Hysteresis Current Controller for Interfacing Photo-...DC-AC Inverter using SRF Hysteresis Current Controller for Interfacing Photo-...
DC-AC Inverter using SRF Hysteresis Current Controller for Interfacing Photo-...
 
A CONTROL APPROACH FOR GRID INTERFACING INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...
A CONTROL APPROACH FOR GRID INTERFACING  INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...A CONTROL APPROACH FOR GRID INTERFACING  INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...
A CONTROL APPROACH FOR GRID INTERFACING INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...
 
IRJET-Power Quality Effects on Nonlinear Loads
IRJET-Power Quality Effects on Nonlinear LoadsIRJET-Power Quality Effects on Nonlinear Loads
IRJET-Power Quality Effects on Nonlinear Loads
 
Power Quality Problems Related with the Interconnection of Wind Farms to the ...
Power Quality Problems Related with the Interconnection of Wind Farms to the ...Power Quality Problems Related with the Interconnection of Wind Farms to the ...
Power Quality Problems Related with the Interconnection of Wind Farms to the ...
 
ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF R...
 ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF R... ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF R...
ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF R...
 
Harmonic enhancement in microgrid with applications on sensitive loads
Harmonic enhancement in microgrid with applications on sensitive loadsHarmonic enhancement in microgrid with applications on sensitive loads
Harmonic enhancement in microgrid with applications on sensitive loads
 
INSTANTANEOUS POWER AND CURRENT STRATEGIES FOR CURRENT HARMONICS CANCELLATION...
INSTANTANEOUS POWER AND CURRENT STRATEGIES FOR CURRENT HARMONICS CANCELLATION...INSTANTANEOUS POWER AND CURRENT STRATEGIES FOR CURRENT HARMONICS CANCELLATION...
INSTANTANEOUS POWER AND CURRENT STRATEGIES FOR CURRENT HARMONICS CANCELLATION...
 
PARAMETRIC MODELING OF VOLTAGE DROP IN POWER DISTRIBUTION NETWORKS
PARAMETRIC MODELING OF VOLTAGE DROP IN POWER DISTRIBUTION NETWORKSPARAMETRIC MODELING OF VOLTAGE DROP IN POWER DISTRIBUTION NETWORKS
PARAMETRIC MODELING OF VOLTAGE DROP IN POWER DISTRIBUTION NETWORKS
 
AN OUTLINE OF HARMONICS AND MULTILEVEL
AN OUTLINE OF HARMONICS AND MULTILEVELAN OUTLINE OF HARMONICS AND MULTILEVEL
AN OUTLINE OF HARMONICS AND MULTILEVEL
 
Om2423682376
Om2423682376Om2423682376
Om2423682376
 
Me2420192024
Me2420192024Me2420192024
Me2420192024
 
Dynamic Power Factor Correction in a Non Linear Environment
Dynamic Power Factor Correction in a Non Linear EnvironmentDynamic Power Factor Correction in a Non Linear Environment
Dynamic Power Factor Correction in a Non Linear Environment
 
H010615159
H010615159H010615159
H010615159
 
Survey of dc motor
Survey of dc motorSurvey of dc motor
Survey of dc motor
 
windfarmgridissues.pdf
windfarmgridissues.pdfwindfarmgridissues.pdf
windfarmgridissues.pdf
 
Wind farm grid issues
Wind farm grid issuesWind farm grid issues
Wind farm grid issues
 
Voltage Flicker Mitigation in Electric Arc Furnace using D-STATCOM
Voltage Flicker Mitigation in Electric Arc Furnace using D-STATCOMVoltage Flicker Mitigation in Electric Arc Furnace using D-STATCOM
Voltage Flicker Mitigation in Electric Arc Furnace using D-STATCOM
 
A Novel Technique for Enhancing Active and Reactive Power Quality for Renewab...
A Novel Technique for Enhancing Active and Reactive Power Quality for Renewab...A Novel Technique for Enhancing Active and Reactive Power Quality for Renewab...
A Novel Technique for Enhancing Active and Reactive Power Quality for Renewab...
 
Modeling and analysis of transformer
Modeling and analysis of transformerModeling and analysis of transformer
Modeling and analysis of transformer
 

More from ijtsrd

‘Six Sigma Technique’ A Journey Through its Implementation
‘Six Sigma Technique’ A Journey Through its Implementation‘Six Sigma Technique’ A Journey Through its Implementation
‘Six Sigma Technique’ A Journey Through its Implementationijtsrd
 
Edge Computing in Space Enhancing Data Processing and Communication for Space...
Edge Computing in Space Enhancing Data Processing and Communication for Space...Edge Computing in Space Enhancing Data Processing and Communication for Space...
Edge Computing in Space Enhancing Data Processing and Communication for Space...ijtsrd
 
Dynamics of Communal Politics in 21st Century India Challenges and Prospects
Dynamics of Communal Politics in 21st Century India Challenges and ProspectsDynamics of Communal Politics in 21st Century India Challenges and Prospects
Dynamics of Communal Politics in 21st Century India Challenges and Prospectsijtsrd
 
Assess Perspective and Knowledge of Healthcare Providers Towards Elehealth in...
Assess Perspective and Knowledge of Healthcare Providers Towards Elehealth in...Assess Perspective and Knowledge of Healthcare Providers Towards Elehealth in...
Assess Perspective and Knowledge of Healthcare Providers Towards Elehealth in...ijtsrd
 
The Impact of Digital Media on the Decentralization of Power and the Erosion ...
The Impact of Digital Media on the Decentralization of Power and the Erosion ...The Impact of Digital Media on the Decentralization of Power and the Erosion ...
The Impact of Digital Media on the Decentralization of Power and the Erosion ...ijtsrd
 
Online Voices, Offline Impact Ambedkars Ideals and Socio Political Inclusion ...
Online Voices, Offline Impact Ambedkars Ideals and Socio Political Inclusion ...Online Voices, Offline Impact Ambedkars Ideals and Socio Political Inclusion ...
Online Voices, Offline Impact Ambedkars Ideals and Socio Political Inclusion ...ijtsrd
 
Problems and Challenges of Agro Entreprenurship A Study
Problems and Challenges of Agro Entreprenurship A StudyProblems and Challenges of Agro Entreprenurship A Study
Problems and Challenges of Agro Entreprenurship A Studyijtsrd
 
Comparative Analysis of Total Corporate Disclosure of Selected IT Companies o...
Comparative Analysis of Total Corporate Disclosure of Selected IT Companies o...Comparative Analysis of Total Corporate Disclosure of Selected IT Companies o...
Comparative Analysis of Total Corporate Disclosure of Selected IT Companies o...ijtsrd
 
The Impact of Educational Background and Professional Training on Human Right...
The Impact of Educational Background and Professional Training on Human Right...The Impact of Educational Background and Professional Training on Human Right...
The Impact of Educational Background and Professional Training on Human Right...ijtsrd
 
A Study on the Effective Teaching Learning Process in English Curriculum at t...
A Study on the Effective Teaching Learning Process in English Curriculum at t...A Study on the Effective Teaching Learning Process in English Curriculum at t...
A Study on the Effective Teaching Learning Process in English Curriculum at t...ijtsrd
 
The Role of Mentoring and Its Influence on the Effectiveness of the Teaching ...
The Role of Mentoring and Its Influence on the Effectiveness of the Teaching ...The Role of Mentoring and Its Influence on the Effectiveness of the Teaching ...
The Role of Mentoring and Its Influence on the Effectiveness of the Teaching ...ijtsrd
 
Design Simulation and Hardware Construction of an Arduino Microcontroller Bas...
Design Simulation and Hardware Construction of an Arduino Microcontroller Bas...Design Simulation and Hardware Construction of an Arduino Microcontroller Bas...
Design Simulation and Hardware Construction of an Arduino Microcontroller Bas...ijtsrd
 
Sustainable Energy by Paul A. Adekunte | Matthew N. O. Sadiku | Janet O. Sadiku
Sustainable Energy by Paul A. Adekunte | Matthew N. O. Sadiku | Janet O. SadikuSustainable Energy by Paul A. Adekunte | Matthew N. O. Sadiku | Janet O. Sadiku
Sustainable Energy by Paul A. Adekunte | Matthew N. O. Sadiku | Janet O. Sadikuijtsrd
 
Concepts for Sudan Survey Act Implementations Executive Regulations and Stand...
Concepts for Sudan Survey Act Implementations Executive Regulations and Stand...Concepts for Sudan Survey Act Implementations Executive Regulations and Stand...
Concepts for Sudan Survey Act Implementations Executive Regulations and Stand...ijtsrd
 
Towards the Implementation of the Sudan Interpolated Geoid Model Khartoum Sta...
Towards the Implementation of the Sudan Interpolated Geoid Model Khartoum Sta...Towards the Implementation of the Sudan Interpolated Geoid Model Khartoum Sta...
Towards the Implementation of the Sudan Interpolated Geoid Model Khartoum Sta...ijtsrd
 
Activating Geospatial Information for Sudans Sustainable Investment Map
Activating Geospatial Information for Sudans Sustainable Investment MapActivating Geospatial Information for Sudans Sustainable Investment Map
Activating Geospatial Information for Sudans Sustainable Investment Mapijtsrd
 
Educational Unity Embracing Diversity for a Stronger Society
Educational Unity Embracing Diversity for a Stronger SocietyEducational Unity Embracing Diversity for a Stronger Society
Educational Unity Embracing Diversity for a Stronger Societyijtsrd
 
Integration of Indian Indigenous Knowledge System in Management Prospects and...
Integration of Indian Indigenous Knowledge System in Management Prospects and...Integration of Indian Indigenous Knowledge System in Management Prospects and...
Integration of Indian Indigenous Knowledge System in Management Prospects and...ijtsrd
 
DeepMask Transforming Face Mask Identification for Better Pandemic Control in...
DeepMask Transforming Face Mask Identification for Better Pandemic Control in...DeepMask Transforming Face Mask Identification for Better Pandemic Control in...
DeepMask Transforming Face Mask Identification for Better Pandemic Control in...ijtsrd
 
Streamlining Data Collection eCRF Design and Machine Learning
Streamlining Data Collection eCRF Design and Machine LearningStreamlining Data Collection eCRF Design and Machine Learning
Streamlining Data Collection eCRF Design and Machine Learningijtsrd
 

More from ijtsrd (20)

‘Six Sigma Technique’ A Journey Through its Implementation
‘Six Sigma Technique’ A Journey Through its Implementation‘Six Sigma Technique’ A Journey Through its Implementation
‘Six Sigma Technique’ A Journey Through its Implementation
 
Edge Computing in Space Enhancing Data Processing and Communication for Space...
Edge Computing in Space Enhancing Data Processing and Communication for Space...Edge Computing in Space Enhancing Data Processing and Communication for Space...
Edge Computing in Space Enhancing Data Processing and Communication for Space...
 
Dynamics of Communal Politics in 21st Century India Challenges and Prospects
Dynamics of Communal Politics in 21st Century India Challenges and ProspectsDynamics of Communal Politics in 21st Century India Challenges and Prospects
Dynamics of Communal Politics in 21st Century India Challenges and Prospects
 
Assess Perspective and Knowledge of Healthcare Providers Towards Elehealth in...
Assess Perspective and Knowledge of Healthcare Providers Towards Elehealth in...Assess Perspective and Knowledge of Healthcare Providers Towards Elehealth in...
Assess Perspective and Knowledge of Healthcare Providers Towards Elehealth in...
 
The Impact of Digital Media on the Decentralization of Power and the Erosion ...
The Impact of Digital Media on the Decentralization of Power and the Erosion ...The Impact of Digital Media on the Decentralization of Power and the Erosion ...
The Impact of Digital Media on the Decentralization of Power and the Erosion ...
 
Online Voices, Offline Impact Ambedkars Ideals and Socio Political Inclusion ...
Online Voices, Offline Impact Ambedkars Ideals and Socio Political Inclusion ...Online Voices, Offline Impact Ambedkars Ideals and Socio Political Inclusion ...
Online Voices, Offline Impact Ambedkars Ideals and Socio Political Inclusion ...
 
Problems and Challenges of Agro Entreprenurship A Study
Problems and Challenges of Agro Entreprenurship A StudyProblems and Challenges of Agro Entreprenurship A Study
Problems and Challenges of Agro Entreprenurship A Study
 
Comparative Analysis of Total Corporate Disclosure of Selected IT Companies o...
Comparative Analysis of Total Corporate Disclosure of Selected IT Companies o...Comparative Analysis of Total Corporate Disclosure of Selected IT Companies o...
Comparative Analysis of Total Corporate Disclosure of Selected IT Companies o...
 
The Impact of Educational Background and Professional Training on Human Right...
The Impact of Educational Background and Professional Training on Human Right...The Impact of Educational Background and Professional Training on Human Right...
The Impact of Educational Background and Professional Training on Human Right...
 
A Study on the Effective Teaching Learning Process in English Curriculum at t...
A Study on the Effective Teaching Learning Process in English Curriculum at t...A Study on the Effective Teaching Learning Process in English Curriculum at t...
A Study on the Effective Teaching Learning Process in English Curriculum at t...
 
The Role of Mentoring and Its Influence on the Effectiveness of the Teaching ...
The Role of Mentoring and Its Influence on the Effectiveness of the Teaching ...The Role of Mentoring and Its Influence on the Effectiveness of the Teaching ...
The Role of Mentoring and Its Influence on the Effectiveness of the Teaching ...
 
Design Simulation and Hardware Construction of an Arduino Microcontroller Bas...
Design Simulation and Hardware Construction of an Arduino Microcontroller Bas...Design Simulation and Hardware Construction of an Arduino Microcontroller Bas...
Design Simulation and Hardware Construction of an Arduino Microcontroller Bas...
 
Sustainable Energy by Paul A. Adekunte | Matthew N. O. Sadiku | Janet O. Sadiku
Sustainable Energy by Paul A. Adekunte | Matthew N. O. Sadiku | Janet O. SadikuSustainable Energy by Paul A. Adekunte | Matthew N. O. Sadiku | Janet O. Sadiku
Sustainable Energy by Paul A. Adekunte | Matthew N. O. Sadiku | Janet O. Sadiku
 
Concepts for Sudan Survey Act Implementations Executive Regulations and Stand...
Concepts for Sudan Survey Act Implementations Executive Regulations and Stand...Concepts for Sudan Survey Act Implementations Executive Regulations and Stand...
Concepts for Sudan Survey Act Implementations Executive Regulations and Stand...
 
Towards the Implementation of the Sudan Interpolated Geoid Model Khartoum Sta...
Towards the Implementation of the Sudan Interpolated Geoid Model Khartoum Sta...Towards the Implementation of the Sudan Interpolated Geoid Model Khartoum Sta...
Towards the Implementation of the Sudan Interpolated Geoid Model Khartoum Sta...
 
Activating Geospatial Information for Sudans Sustainable Investment Map
Activating Geospatial Information for Sudans Sustainable Investment MapActivating Geospatial Information for Sudans Sustainable Investment Map
Activating Geospatial Information for Sudans Sustainable Investment Map
 
Educational Unity Embracing Diversity for a Stronger Society
Educational Unity Embracing Diversity for a Stronger SocietyEducational Unity Embracing Diversity for a Stronger Society
Educational Unity Embracing Diversity for a Stronger Society
 
Integration of Indian Indigenous Knowledge System in Management Prospects and...
Integration of Indian Indigenous Knowledge System in Management Prospects and...Integration of Indian Indigenous Knowledge System in Management Prospects and...
Integration of Indian Indigenous Knowledge System in Management Prospects and...
 
DeepMask Transforming Face Mask Identification for Better Pandemic Control in...
DeepMask Transforming Face Mask Identification for Better Pandemic Control in...DeepMask Transforming Face Mask Identification for Better Pandemic Control in...
DeepMask Transforming Face Mask Identification for Better Pandemic Control in...
 
Streamlining Data Collection eCRF Design and Machine Learning
Streamlining Data Collection eCRF Design and Machine LearningStreamlining Data Collection eCRF Design and Machine Learning
Streamlining Data Collection eCRF Design and Machine Learning
 

Recently uploaded

College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxhumanexperienceaaa
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 

Recently uploaded (20)

College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 

Harmonic Mitigation in Distribution System by using Passive Filters

  • 1. International Journal of Trend in International Open Access Journal ISSN No: 2456 @ IJTSRD | Available Online @ www.ijtsrd.com Harmonic Mitigation in Distribution System Nyein Nyein Chan Department of Electrical Power Engineering ABSTRACT The advent of power electronics and computerized equipment in recent decades has brought enhanced efficiency and improved system but at the same time also created harmonics and waveform distortion to the power system network. Due to the growing use of nonlinear load equipment and new technologies in buildings, harmonic currents and voltages generated in distribution systems pose a new problem for electrical engineers. This is a serious problem when power quality is a prime concern. Harmonics are the main types of power quality problem that are very common to the power system containing electric arc furnace (EAF). Electric arc furnace (EAFs) are widely used in steelmaking and in melting of nonferrous metals. In this paper, EAF is presented guide lines for the accurate evaluation of harmonics generated in No.(3) Steel Mill, Ywama, Yangon. Passive filters have been most commonly used to limit the flow of harmonic currents in distribution systems. Their performance is limited to a few harmonics, and they can introduce resonance in the power system. KEY WORDS: Simulation by Using Matlab Software, Passive Filters, Nonlinear Load, Total Harmonic Distortion, Electric Arc Furnace, IEEE Std 519 1. INTRODUCTION Harmonics are a mathematical way of describing distortion to a voltage or current waveform. The term harmonic refers to a component of a waveform that occurs at an integer multiple of the fundamental frequency [1]. And the objective of the electric utility is to deliver sinusoidal voltage at fairly constant magnitude throughout their system. There are nonlinear loads on the system that produce harmonic currents. These non-linear elements generate network voltages with frequencies different from the network frequency or absorb currents with non waveforms. The widespread and growing of these International Journal of Trend in Scientific Research and Development (IJTSRD) International Open Access Journal | www.ijtsrd.com ISSN No: 2456 - 6470 | Volume - 3 | Issue – 1 | Nov www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018 n Distribution System by using Passive Filters Nyein Nyein Chan1 , Hnin Wai Hlaing2 1 Assistant Lecture, 2 Professor Electrical Power Engineering, Technological University Thanlyin, Thanlyin The advent of power electronics and computerized equipment in recent decades has brought enhanced efficiency and improved system but at the same time also created harmonics and waveform distortion to the power system network. Due to the growing use of inear load equipment and new technologies in buildings, harmonic currents and voltages generated in distribution systems pose a new problem for electrical engineers. This is a serious problem when power quality is a prime concern. Harmonics are the pes of power quality problem that are very common to the power system containing electric arc furnace (EAF). Electric arc furnace (EAFs) are widely used in steelmaking and in melting of nonferrous metals. In this paper, EAF is presented guide lines for accurate evaluation of harmonics generated in No.(3) Steel Mill, Ywama, Yangon. Passive filters have been most commonly used to limit the flow of harmonic currents in distribution systems. Their performance is limited to a few harmonics, and they oduce resonance in the power system. Simulation by Using Matlab Software, Passive Filters, Nonlinear Load, Total Harmonic Distortion, Electric Arc Furnace, IEEE Std 519-1992. Harmonics are a mathematical way of describing distortion to a voltage or current waveform. The term harmonic refers to a component of a waveform that occurs at an integer multiple of the fundamental frequency [1]. And the objective of the electric utility is to deliver sinusoidal voltage at fairly constant magnitude throughout their system. There are nonlinear loads on the system that produce harmonic linear elements generate network voltages with frequencies different from the network frequency or absorb currents with non-sinusoidal waveforms. The widespread and growing of these loads has greatly increased the flow of harmonic currents on facility distribution systems. The interest on problems related to non linear devices and their influence on the systems increased considerably since 1980. This is due to the development of new power semiconductor devices and, as a consequence, the development of new converters that affects linearity in electric power signals substantially. The increa on the utilization of electronic equipment modified the sinusoidal nature of electrical signals. These equipments increase the current waveform distortion and as a consequence, increment the voltage waveform distortion [2] [3]. The electric arc furnace is either AC or DC operated. It transfer the electric energy (electric arc) to melt the scrap material held by the furnace. The arc produced between the electrodes low voltages and high current supplied by the furnace transformer. [5]. II. PRINCIPLE OF ARC F OPERATION The operation of electric arc furnace can be divided in into intervals namely melting and refining periods. The refining period is further divided in several stages. During the melting stage, the electrode is lowered through a hydraulic ac maintain the stable arc. The furnace draws active power in this condition. More and more buckets of scrap material are added into the furnace during the melting stages. During the refining stage, a long arc is established. The factors involved during the operation of the furnace are electrode position, electrode arm control scheme, supply voltage, operation reactance and the materials used for melting and refining. The installations of both AC and DC electric arc furnace [4] have been shown in figure.1(a) and 1(b) respectively as shown. Research and Development (IJTSRD) www.ijtsrd.com 1 | Nov – Dec 2018 Dec 2018 Page: 548 sing Passive Filters Thanlyin, Myanmar loads has greatly increased the flow of harmonic currents on facility distribution systems. The interest on problems related to non linear devices and their nfluence on the systems increased considerably since 1980. This is due to the development of new power semiconductor devices and, as a consequence, the development of new converters that affects linearity in electric power signals substantially. The increase on the utilization of electronic equipment modified the sinusoidal nature of electrical signals. These equipments increase the current waveform distortion and as a consequence, increment the voltage is either AC or DC operated. It transfer the electric energy (electric arc) to melt the scrap material held by the furnace. The arc produced between the electrodes low voltages and high current supplied by the furnace transformer. [5]. PRINCIPLE OF ARC FURNACE The operation of electric arc furnace can be divided in into intervals namely melting and refining periods. The refining period is further divided in several stages. During the melting stage, the electrode is lowered through a hydraulic actuator system to maintain the stable arc. The furnace draws active power in this condition. More and more buckets of scrap material are added into the furnace during the melting stages. During the refining stage, a long arc is lved during the operation of the furnace are electrode position, electrode arm control scheme, supply voltage, operation reactance and the materials used for melting and refining. The installations of both AC and DC electric arc furnace in figure.1(a) and 1(b)
  • 2. International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456 @ IJTSRD | Available Online @ www.ijtsrd.com Figure 1(a) Installation of AC Arc Furnace Figure 1(b) Installation of DC Arc Furnace A transformer directly energizes furnace electrodes in a high current circuit in AC arc furnace , whereas DC furnace employ a controlled rectifier to supply dc to the furnace electrodes. Arc furnace operation may be classified into stages, depending on the status of the melt and the time lapse from the initial energizing of the unit. During the melting period, pieces o create momentary short circuits on the secondary side of the furnace transformer. These load changes effect the arc characteristics, causing fluctuations of current. The current fluctuations cause variations in reactive power, which cause a momentary voltage drop or flicker, both at the supply bus and at nearby buses in the interconnected system. The arc currents are more uniform during the refining period and result in less impact on the power quality of the system. Arc furnaces also create harmonic load currents and asynchronous spectral components. Harmonics represent an important power quality issue, because they may cause undesirable operating conditions. Figure.2 Complete Model of No (3) Ywama Steel Mill 100MVA 66kV Source 60MVA 66/33kV TR 15 33/11 15MVA 33/11kV TR 33kV Bus bar 33kV Bus bar 12MVA 11/0.42kV TR 8MVA 11/0.2kV TR SVC EAF Furnace LRF Furnace 5MVA 11/0.4kV TR 2.5MVA 11/0.4kV 11kV Bus bar 11kV Bus bar Wire Production Bolt Nut Production Index:: TR =Transformer International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456 www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018 Figure 1(a) Installation of AC Arc Furnace Figure 1(b) Installation of DC Arc Furnace A transformer directly energizes furnace electrodes in a high current circuit in AC arc furnace , whereas DC e employ a controlled rectifier to supply dc to the furnace electrodes. Arc furnace operation may be classified into stages, depending on the status of the melt and the time lapse from the initial energizing of the unit. During the melting period, pieces of steel create momentary short circuits on the secondary side of the furnace transformer. These load changes effect the arc characteristics, causing fluctuations of current. The current fluctuations cause variations in reactive ary voltage drop or flicker, both at the supply bus and at nearby buses in the interconnected system. The arc currents are more uniform during the refining period and result in less impact on the power quality of the system. Arc ic load currents and asynchronous spectral components. Harmonics represent an important power quality issue, because they may cause undesirable operating conditions. Figure.2 Complete Model of No (3) Ywama Steel III. VOLTAGE AND CURRENT HARMONIC LIMITS According to IEEE Std 519- distortion on power system 69kV and below is limited to 5.0% total harmonic distorti individual harmonic limited to 3%. The current harmonic limits vary based on the short circuit strength of the system they are being injected into. Essentially, the more system is able to handle harmonic currents, the more the customer i to inject [6]. Table .1 IEEE Std 519-1992 Harmonic Voltage Limits Voltage Distortion Limits Bus Voltage at PCC Individual Voltage Distortion (%) Below 69kV 3.0 69kV to 161kV 1.5 161kV and above 1.0 Table .2 IEEE Std 519-1992 Harmonic Current Limits Current Distortion Limits for General Distribution Systems (120V Through 69kV) Maximum Harmonic Current Distortion in Percent of IL Individual Harmonic Order ( Odd Harmonic ) ISC/IL <11 11- 16 17 22 <20 4.0 2.0 1.5 20<50 7.0 3.5 2.5 50<100 10.0 4.5 4.0 100<1000 12.0 5.5 5.0 >1000 15.0 7.0 6.0 IV. HARMONIC FILTERS Harmonics currents are created by nonlinear loads that generate non-sinusoidal current on distribution power system. Nonlinear devices such as power electronics converters can inject harmonics alternating currents (AC) in the electrical power system. Therefore, the growing use of nonlinear loads in commercial, residential and industrial are becoming more harmonic problems at utilities and customers sides. Harmonics are the most important drawbacks of power quality in the power distribution system. With the increase of nonlinear loads in the power system, more and more harmonic mitigation techniques are required. There are three types of filter 15MVA 11kV TR MVA kV TR 2MVA 11/6.6kV TR Nut uction Crusher Motor International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456-6470 Dec 2018 Page: 549 VOLTAGE AND CURRENT HARMONIC 1992, harmonic voltage distortion on power system 69kV and below is limited to 5.0% total harmonic distortion (THD) with each individual harmonic limited to 3%. The current harmonic limits vary based on the short circuit strength of the system they are being injected into. Essentially, the more system is able to handle harmonic currents, the more the customer is allowed 1992 Harmonic Voltage Voltage Distortion Limits Individual Voltage Distortion (%) Total Voltage Distortion THDV (%) 5.0 2.5 1.5 1992 Harmonic Current Limits Current Distortion Limits for General Distribution Systems (120V Through 69kV) Maximum Harmonic Current Distortion in Percent of IL Individual Harmonic Order ( Odd Harmonic ) 17- 22 23- 35 >35 TDD 1.5 0.6 0.5 5.0 2.5 1.0 0.5 8.0 4.0 1.5 0.7 12.0 5.0 2.0 1.0 15.0 6.0 2.5 1.4 20.0 HARMONIC FILTERS Harmonics currents are created by nonlinear loads sinusoidal current on distribution power system. Nonlinear devices such as power electronics converters can inject harmonics alternating currents (AC) in the electrical power system. fore, the growing use of nonlinear loads in commercial, residential and industrial are becoming more harmonic problems at utilities and customers sides. Harmonics are the most important drawbacks of power quality in the power distribution system. With increase of nonlinear loads in the power system, more and more harmonic mitigation techniques are required. There are three types of filter
  • 3. International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456 @ IJTSRD | Available Online @ www.ijtsrd.com 1. Passive Filters 2. Active Filters 3. Hybrid Filters [8][9]. Passive Filters: Passive filters are basically topologies or arrangements of R, L, and C elements connected in different combinations to gain desired suppression of harmonics. They are employed either to shunt the harmonic currents off the line or to block their flow between parts of the system by tuning the elements to create a resonance at a selected frequency. They also provide the reactive power compensation to the system and hence improve the power quality. However, they have the disadvantage of potentially interacting adversely with the power system and the performance of passive filter depends mainly on the system source impedance. On the other hand they can be used for elimination of a particular harmonic frequency, so number of passive filters increase with increase of harmonics on the system. They can be classified into: 1. Passive Shunt Filter 2. Passive Series Filter a. i. Passive Shunt Filter C C L L Figure .3 Shunt filter connection Passive filters are connected in parallel with the system. Figure .3 illustrates the parallel passive filter connection. The shunt may be grounded in one of its terminations, and then it will be passed only for the tuned harmonic current and a part of the fundamental current. The passive shunt type filter is that carry fraction of current so the whole system AC power losses are reduced compare to series type filter. V. ii. Passive Series Filter Figure .4 Series filter connection Passive filters are connected in series with the system. Figure .4 illustrates the series passive filter International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456 www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018 Passive filters are basically topologies or arrangements of R, L, and C elements connected in different combinations to gain desired suppression of harmonics. They are employed either to shunt the harmonic currents off the line or to block their flow en parts of the system by tuning the elements to create a resonance at a selected frequency. They also provide the reactive power compensation to the system and hence improve the power quality. However, they have the disadvantage of potentially g adversely with the power system and the performance of passive filter depends mainly on the system source impedance. On the other hand they can be used for elimination of a particular harmonic frequency, so number of passive filters increase with Figure .3 Shunt filter connection Passive filters are connected in parallel with the Figure .3 illustrates the parallel passive filter connection. The shunt may be grounded in one of its terminations, and then it will be passed only for the tuned harmonic current and a part of the fundamental current. The passive shunt type filter is that it only carry fraction of current so the whole system AC power losses are reduced compare to series type filter. ii. Passive Series Filter Figure .4 Series filter connection Passive filters are connected in series with the system. Figure .4 illustrates the series passive filter connection. A passive type series passive filter has property of purely inductive type or LC tuned characteristics. The main component of passive serie filter in AC line reactor and DC link filter. V. SIMULATION MODELS AND RESULTS Figure .5 Simulation Model of Electric Arc Furnace without Filter in No.(3) Ywama Steel Mill Figure.6 Total Harmonic Distortion Voltage Waveform without Filter for EAF wit to fundamental) Figure.7 Total Harmonic Distortion Voltage Waveform without Filter for EAF with List (relative to fundamental) Figure.8 Total Harmonic Distortion Current Waveform without Filter for EAF with Bar (relative to fundamenta International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456-6470 Dec 2018 Page: 550 connection. A passive type series passive filter has property of purely inductive type or LC tuned characteristics. The main component of passive series filter in AC line reactor and DC link filter. SIMULATION MODELS AND RESULTS Figure .5 Simulation Model of Electric Arc Furnace without Filter in No.(3) Ywama Steel Mill Figure.6 Total Harmonic Distortion Voltage Waveform without Filter for EAF with Bar (relative to fundamental) Figure.7 Total Harmonic Distortion Voltage Waveform without Filter for EAF with List (relative to fundamental) Figure.8 Total Harmonic Distortion Current Waveform without Filter for EAF with Bar (relative to fundamental)
  • 4. International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456 @ IJTSRD | Available Online @ www.ijtsrd.com Figure.9 Total Harmonic Distortion Current Waveform without Filter for EAF with List (relative to fundamental) Figure.10 Simulation Model of Electric Arc Furnace with Passive Filter (PF) Figure.11 Total Harmonic Distortion Voltage Waveform with PF for EAF with Bar (relative to fundamental) Figure.12 Total Harmonic Distortion Voltage Waveform with PF for EAF with List (relative to fundamental) International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456 www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018 Figure.9 Total Harmonic Distortion Current Waveform without Filter for EAF with List (relative Figure.10 Simulation Model of Electric Arc Furnace Figure.11 Total Harmonic Distortion Voltage Waveform with PF for EAF with Bar (relative to Figure.12 Total Harmonic Distortion Voltage Waveform with PF for EAF with List (relative to Figure.13 Total Harmonic Distortion Curre Waveform with PF for EAF with Bar (relative to fundamental) Figure.14 Total Harmonic Distortion Current Waveform with PF for EAF with List (relative to fundamental) Table.3 Comparison of Total Harmonics Voltage & Current Distortion % without and wit System THD Without Filter 24.73% With Passive Filter 2.62% VI. CONCLUSION AND FUTURE SCOPE The new block developed proved to be effective in harmonic distortion analysis in a steel plants as carried out in this paper. Here the total harmonic distortion (THD) was measured by the THD block in Simulink. The distortion for both voltage and current due to the steel plant were excessive and could be mitigated using passive filter of commensurable design in proposed. According to the simulation results above the figures, the THD and THDI(%) is 8.26% at the point of common coupling (PCC) without using the mitigation techniques in present conditions. The harmonic twenty orders are measured and among them, 11 13th orders are dominant in No.(3) Steel Mill (Ywama, Yangon). After using the passive harmonic filters, the THDV is 2.62% and fundamental value, thus meeting the limit of harmonic standard of IEEE Standard 519 is harmonic mitigation in distribution system by using active and hybrid harmonic filters. International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456-6470 Dec 2018 Page: 551 Figure.13 Total Harmonic Distortion Current Waveform with PF for EAF with Bar (relative to fundamental) Figure.14 Total Harmonic Distortion Current Waveform with PF for EAF with List (relative to fundamental) Table.3 Comparison of Total Harmonics Voltage & Current Distortion % without and with PF THDV (%) THDI (%) 24.73% 8.26% 2.62% 1.52% CONCLUSION AND FUTURE SCOPE The new block developed proved to be effective in harmonic distortion analysis in a steel plants as carried out in this paper. Here the total harmonic distortion (THD) was measured by the THD block in Simulink. The distortion for both voltage and current ue to the steel plant were excessive and could be mitigated using passive filter of commensurable design in proposed. According to the simulation results above the figures, the THDV(%) is 24.73% and THDI(%) is 8.26% at the point of common without using the mitigation techniques in present conditions. The harmonic twenty orders are measured and among them, 11st and orders are dominant in No.(3) Steel Mill (Ywama, Yangon). After using the passive harmonic is 2.62% and THDI is 1.52% of the fundamental value, thus meeting the limit of harmonic standard of IEEE Standard 519-1992. The future work is harmonic mitigation in distribution system by using active and hybrid harmonic filters.
  • 5. International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456 @ IJTSRD | Available Online @ www.ijtsrd.com ACKNOWLEDGMENTS I greatly appreciate to all teachers from the Department of Electrical Power Engineering, Technological University (Thanlyin) who work in Research. I would like to give great thanks to Research Department of Electrical Power Engineering, Technological University (Thanlyin) f permission to study related on-going research projects. REFERENCES 1. Ashok, S. “Harmonic in distribution system of an educational institution” IEEE transactions on power quality 98 pages 145-150, 1998. 2. Alejandro O.M. and Gustavo A.R. “Instantaneous p-q theory for harmonic compensation via shunt active power filter” IEEE transactions on power electronics and power quality applications, page 1-4, 2013. 3. Jamil M. “Harmonics in Adjustable Speed Drives” IEEE transactions on information and emerging technologies, page 1-6, 2007. International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456 www.ijtsrd.com | Volume – 3 | Issue – 1 | Nov-Dec 2018 to all teachers from the Department of Electrical Power Engineering, Technological University (Thanlyin) who work in I would like to give great thanks to Research Department of Electrical Power Engineering, Technological University (Thanlyin) for kind going research Ashok, S. “Harmonic in distribution system of an educational institution” IEEE transactions on 150, 1998. Alejandro O.M. and Gustavo A.R. “Instantaneous q theory for harmonic compensation via shunt active power filter” IEEE transactions on power electronics and power quality applications, page Jamil M. “Harmonics in Adjustable Speed Drives” IEEE transactions on information and emerging 4. Reuben F. Burch IV, Senior Member, IEEE “Thoughts on Improving the Electric Arc Furnace Model”. 5. Amarjeet Singh, Ravindra Kumar Singh, Asheesh Kumar Singh “Power Quality Issue of Electric Arc Furnace and their Mitigations ISSN: 2349-6495(p) 2456 4, Apr-2017. 6. Thomas M. Blooming, P.E, Daniel J. Carnovale P.E. “Application of IEEE Std 519 Harmonic Limits”. 7. Rooh UI Amin Shaikh, Abdul Basit Lashari, Irfan Ansari, “Harmonic Analysis and Mitigation U Passive Filters” January, 2015. 8. Rustemli, S. and Cengiz, M.S. 2016, “Passive Filter Solution and Simulation Perfornance in Industrial Plants”. Bitlis Eren University J Science and Technology, Turkey. 9. Nassif, A.B., Xu, W. and Freitas Investigation on the Selection of Filter Topologes for Passive Filter Applications”. IEEE PES General Meeting, 2009. International Journal of Trend in Scientific Research and Development (IJTSRD) ISSN: 2456-6470 Dec 2018 Page: 552 Reuben F. Burch IV, Senior Member, IEEE “Thoughts on Improving the Electric Arc Furnace Amarjeet Singh, Ravindra Kumar Singh, Asheesh Kumar Singh “Power Quality Issue of Electric Arc Furnace and their Mitigations – A Review”, 6495(p) 2456-1908(O), Vol-4, Issue- Thomas M. Blooming, P.E, Daniel J. Carnovale P.E. “Application of IEEE Std 519-1992 Rooh UI Amin Shaikh, Abdul Basit Lashari, Irfan Ansari, “Harmonic Analysis and Mitigation Using Passive Filters” January, 2015. Rustemli, S. and Cengiz, M.S. 2016, “Passive Filter Solution and Simulation Perfornance in Industrial Plants”. Bitlis Eren University J Science Nassif, A.B., Xu, W. and Freitas, W.2009, “An Investigation on the Selection of Filter Topologes for Passive Filter Applications”. IEEE PES