SEISMIC DESIGN OF MULTISTOREY
Pamela Jennifer J P
1
PG Scholar, Department of Civil Engineering, Adhiyamaan College
2
Assistant Professor, Department of Civil Engineering, Adhiyamaan College
3
HOD, Department of Civil Engineering, Adhiyamaan College
Earthquake is a major phenomenon which cause failure to the Reinforced Concrete(RC) structure. The necessity of designing the
structure as per codal provision is must for all kind of structure. In this
for study. The Linear static analysis was done using American, European and Indian Codes. The building is modeled and
analysed using ETABS software. All the required parameters for analysis was taken a
storey deflection, storey drift and base shear were compared. The displacement, storey shear and storey displacement obtained
from ACI code design is more when compared with other code’s analysis result.
Keywords: Displacement, Shear, Drift, Seismic
-------------------------------------------------------------------
1. HEADING 1
1.INTRODUCTION
Earthquake resistant structures are capable of resisting
lateral and vertical forces acting on the structures. But no
structures can entirely survive during earthquake without
any damages. According to codes, earthquake resistant
structures are designed to withstand expected earthquake
atleast to occur once during the design life of the stru
Reinforced concrete buildings are analysed and designed to
meet the requirements of relevant codes of practice. Such
buildings designed as per codal provision will survive
during earthquake with minor damages of structural
elements
The following codes are used for analysis purpose;
1. Indian Standard Code
IS 1893(Part 1):2002 and IS13920:1993.
2. European code
EUROCODE 8: 1998
3. American code
ASCE 7-05
Linear Static analysis is applying load in linear pattern.
2. MODELLING AND ANALYSIS
A multi-storey building of G+10 with 3x3 bays is
considered for this study as shown in fig 1. The base
dimension of the plan is 9m x 9m. the typical storey height
is 3m for all storeys. The structural elements are considered
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319
_______________________________________________________________________________________
, Available @ http://www.ijret.org
SEISMIC DESIGN OF MULTISTOREYED RC BUILDING USING
VARIOUS CODES
Pamela Jennifer J P1
, Jegidha. K. J2
, Sureshbabu. S3
Civil Engineering, Adhiyamaan College of Engineering, Hosur,
pamejenni12@gmail.com
Civil Engineering, Adhiyamaan College of Engineering Hosur, Krishnagiri,
India.
jegi.kj@gmail.com
Civil Engineering, Adhiyamaan College of Engineering Hosur, Krishnagiri,
Abstract
Earthquake is a major phenomenon which cause failure to the Reinforced Concrete(RC) structure. The necessity of designing the
structure as per codal provision is must for all kind of structure. In this research, a building of regular plan of G+10 was taken
for study. The Linear static analysis was done using American, European and Indian Codes. The building is modeled and
analysed using ETABS software. All the required parameters for analysis was taken as per respective codes. Various response like
storey deflection, storey drift and base shear were compared. The displacement, storey shear and storey displacement obtained
from ACI code design is more when compared with other code’s analysis result.
Seismic Analysis
-------------------------------------------------------------------***---------------------------------------
Earthquake resistant structures are capable of resisting
ting on the structures. But no
structures can entirely survive during earthquake without
any damages. According to codes, earthquake resistant
structures are designed to withstand expected earthquake
atleast to occur once during the design life of the structure.
Reinforced concrete buildings are analysed and designed to
meet the requirements of relevant codes of practice. Such
buildings designed as per codal provision will survive
during earthquake with minor damages of structural
codes are used for analysis purpose;
d in linear pattern.
storey building of G+10 with 3x3 bays is
considered for this study as shown in fig 1. The base
dimension of the plan is 9m x 9m. the typical storey height
is 3m for all storeys. The structural elements are considered
as square for all storeys. The
three codal provisions as mentioned above. A Linear Static
analysis is done using ETABS 2015. The model is studied
for all three code for severe zone with medium soil
condition.
2.1 PLAN AND ELEVATION OF THE
BUILDING
MODEL: Plan and Elevation of the building
Fig (1). Plan of frame
eISSN: 2319-1163 | pISSN: 2321-7308
_____________________________
314
RC BUILDING USING
3
Engineering, Hosur, Krishnagiri, India.
Engineering Hosur, Krishnagiri,
Engineering Hosur, Krishnagiri, India
Earthquake is a major phenomenon which cause failure to the Reinforced Concrete(RC) structure. The necessity of designing the
research, a building of regular plan of G+10 was taken
for study. The Linear static analysis was done using American, European and Indian Codes. The building is modeled and
s per respective codes. Various response like
storey deflection, storey drift and base shear were compared. The displacement, storey shear and storey displacement obtained
----------------------------------------------------------------------
as square for all storeys. The building is designed for all
three codal provisions as mentioned above. A Linear Static
analysis is done using ETABS 2015. The model is studied
for all three code for severe zone with medium soil
2.1 PLAN AND ELEVATION OF THE
Plan and Elevation of the building
Plan of frame
IJRET: International Journal of Research in Engineering and Technology
__________________________________________________________
Volume: 05 Issue: 02 | Feb-2016, Available @
Fig (2). Elevation of frame
Table 1- Preliminary Data
DETAILS OF
BUILDING
FOR ALL STORIES
Number of storey G+10
Storey Height 3m
Beam size 230m* 600m
Column size 230m* 600m
Slab Thickness 125m
Wall Thickness 230mm
Grade of Concrete M25
Grade of Steel Fe415
2.2 METHODOLOGY OF THE PROJECT
In this study, linear static analysis is done to find out the
response of the building. The storey displacement, shear and
drift is determined using ETABS software. The building is
designed and detailed as per the codes and the results were
compared and discussed.
3. RESULTS AND DISCUSSIONS
3.1 RESULTS FOR EACH CASES
Case(i). Analysis result obtained using IS Code
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319
_______________________________________________________________________________________
, Available @ http://www.ijret.org
FOR ALL STORIES
230m* 600m
230m* 600m
2.2 METHODOLOGY OF THE PROJECT
In this study, linear static analysis is done to find out the
response of the building. The storey displacement, shear and
ETABS software. The building is
designed and detailed as per the codes and the results were
Case(i). Analysis result obtained using IS Code
Fig (3)
Fig (4)
Fig (5)
Fig (3),(4),(5). Shows the displacement , shear and drift for
the building
0
20
40
60
80
100
0 10
DISPLACEMENT
STOREY
DISPLACEMENT(mm)
0
200
400
600
800
1000
0 10
STOREYSHEAR
STOREY
STOREY SHEAR(KN)
0
0.0005
0.001
0.0015
0.002
0.0025
0.003
0.0035
0.004
0 5
SOREYDRIFT
STOREY
STOREY DRIFT
eISSN: 2319-1163 | pISSN: 2321-7308
_____________________________
315
Fig (3)
Fig (4)
Fig (5)
hows the displacement , shear and drift for
the building
20
STOREY
DISPLACEMENT(mm)
DISPLACE
MENT(m
m)
20
STOREY
STOREY SHEAR(KN)
STOREY
SHEAR(KN
)
10 15
STOREY
STOREY DRIFT
STOREY
DRIFT
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 05 Issue: 02 | Feb-2016, Available @ http://www.ijret.org 316
Case (ii) Analysis Result obtained using EURO code
Fig (6)
Fig(7)
Fig (8)
Fig (6),(7)&(8). Shows the shear,displacementand drift of
the structure
Case (iii) Analysis Result obtained using ACI code
Fig (9)
Fig (10)
Fig(11)
Fig (9),(10)&(11) shows the displacement, shear and drift of
the structure
0
100
200
300
400
500
600
700
0 10 20
STOREYSHEAR
STOREY
STOREY SHEAR(KN)
STOREY
SHEAR(KN
)
0
10
20
30
40
50
0 10 20
DISPLACEMENT
STOREY
DISPLACEMENT (mm)
DISPLACEM
ENT (mm)
0
0.0005
0.001
0.0015
0.002
0.0025
0 5 10 15
STOREYDRIFT
STOREY
STOREY DRIFT
STOREY
DRIFT
0
50
100
150
200
0 10 20
STOREYDISPLACEMENT
STOREY
STOREY
DISPLACEMENT(mm
)
STOREY
DISPLACE
MENT(m
m)
0
200
400
600
800
1000
1200
0 10 20
STOREYSHEAR
STOREY
SROREY SHEAR(KN)
SROREY
SHEAR(KN)
0
0.002
0.004
0.006
0.008
0.01
0.012
0.014
0.016
0 5 10 15
STOREYDRIFT
STOREY
STOREY DRIFT
STOREY
DRIFT
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 05 Issue: 02 | Feb-2016, Available @ http://www.ijret.org 317
3.2 COMPARATIVE ANALYSIS
3.2.1 STOREY DISPLACEMENT:
Table 2. Comparison result of Displacement
Storey IS CODE EURO CODE ACI CODE
Base 0 0 0
1 9.4 5.2 45.7
2 20.1 11 61.4
3 30.9 16.7 75.9
4 41.7 22.2 89.9
5 52.3 27.3 103.1
6 62.2 32 115.3
7 71.3 36.1 126
8 79.2 39.5 134.8
9 85.3 42.1 141.5
10 89.3 43.7 145.7
Fig 12. Comparison result of Displacement for all cases
3.2.2 STOREY SHEAR:
Table 3. Comparison result of Storey Shear
Storey IS CODE EURO CODE ACI CODE
Base 0 0 0
1 880.75 618.4 1037.6
2 878.44 607.09 1025.56
3 869.19 584.47 996.93
4 848.39 550.54 949.39
5 811.41 505.3 881.29
6 753.63 448.76 791.28
7 670.42 380.896 678.23
8 557.17 301.73 541.15
9 409.25 211.25 379.17
10 222.03 109.46 191.49
Fig 13. Comparison result of Storey shear for all cases
3.2.3 STOREY DRIFT:
Table 4. Comparison result of Storey Drift
Storey IS CODE EURO CODE ACI CODE
Base 0 0 0
1 0.003136 0.00175 0.0152
2 0.003555 0.00192 0.0052
3 0.003612 0.00189 0.0048
4 0.003602 0.00183 0.0047
5 0.003513 0.00172 0.0044
6 0.003329 0.00156 0.0041
7 0.003033 0.00137 0.0036
8 0.00261 0.00113 0.0029
9 0.002043 0.00086 0.0022
10 0.001327 0.00055 0.0014
Fig 14. Comparison result of Storey Drift for all cases
4. CONCLUSIONS
 The analysis as per ACI code shows more displacement,
storey shear and storey drift when compared with IS
standard and Euro code.
 The displacement, shear and drift is maximum for first
story for all cases.
 Comparing IS and EURO code, the displacement is
increased by 50% for all stories as per IS code than
EURO code. For Euro and ACI code, the displacement is
varied from 88% to 70% from the base to top storey.
0
20
40
60
80
100
120
140
160
0 5 10 15
DISPLACEMENT
STOREY
DISPLACEMENT(mm)
IS CODE
EURO CODE
ACI CODE
0
500
1000
1500
0 5 10 15
STOREYSHEAR
STOREY
STOREY SHEAR(mm)
IS CODE
EURO CODE
ACI CODE
0
0.005
0.01
0.015
0.02
0 5 10 15
IS CODE
EURO
CODE
ACI CODE
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308
_______________________________________________________________________________________
Volume: 05 Issue: 02 | Feb-2016, Available @ http://www.ijret.org 318
 Comparing the storey shear for EURO and IS code, the
value varies from 30% to 50% from base to top floor.
For EURO and ACI codes, the shear varies from 40% to
43%.
 Comparing the Storey Drift for EURO and IS code, the
value varies from 44% to 59%. For EURO and ACI
codes , the drift varies from 88% to 60%.
5. REFERENCES
[1] Jaya Prakash Kadali,M.K.M.V.Rathnam Static
Analysis of Multistoreyed RC Buildings By Using
Pushover Methodology International Journal for
Innovative Research in Science & Technology
Volume1,Issue 8, January 2015 pp113-124.1989.
[2] Mr.K.Lova Raju, Dr.K.V.G.D.Balaji,” Effective
location of shear wall on performance of building
frame subjected to earthquake load,” International
Advanced Research Journal in Science, Engineering
and Technology Vol. 2, Issue 1, January 2015,pp 33-
36.
[3] Md. Rashedul Kabir, Debasish Sen, Md. Mashfiqul
Islam I,”Response of multi-storey regular and irregular
buildings of identical weight under static and dynamic
loading in context of Bangladesh,” International
journal of Civil and Structural Engineering, Volume 5,
No 3, February 2015, pp 252-260.
[4] Akshay V. Raut, Prof. RVRK Prasad, “Pushover
Analysis of G+3 Reinforced Concrete Building with
soft storey,” IOSR Journal of Mechanical and Civil
Engineering , Volume 11, Issue 4 Ver. I (Jul- Aug.
2014), PP 25-29
[5] Lakshmi K.O, Prof. Jayasree Ramanujan, Mrs. Bindu
Sunil, Dr. Laju Kottallil, Prof. Mercy Joseph
Poweth,“Effect of shear wall location in buildings
subjected to seismic loads,” ISOI Journal of
Engineering and Computer science, Volume 1 Issue
1;2014, Page No. 07-17,
[6] Nitin Choudhary, Prof. Mahendra Wadia, “Pushover
Analysis of R.C. Frame Building with Shear Wall,”
IOSR Journal of Mechanical and Civil Engineering ,
volume 11, Issue 2 Ver. V (Mar- Apr. 2014), PP 09-13
[7] Riza Ainul Hakim, Mohammed Sohaib Alama, Samir
A. Ashour, “Seismic Assessment of an RC Building
Using Pushover Analysis,” Engineering, Technology &
Applied Science Research Vol. 4, No. 3, 2014, pp:631-
635.
[8] Praveen Rathod ,Dr.S.S.Dyavanal, “Non-Linear Static
Analysis of G+6 Storeyed RC Buildings with Openings in
Infill Walls,” Int. Journal of Engineering Research and
Applications, Vol. 4, Issue 9( Version 5), September 2014,
pp.51-58.
[9] A.Cinitha, P.K. Umesha, Nagesh R. Iyer, “Nonlinear Static
Analysis to Assess Seismic Performance and Vulnerability
of Code - Conforming RC Buildings,” WSEAS
TRANSACTIONS on APPLIED and THEORETICAL
MECHANICS, Issue 1, Volume 7, January 2012,pp39-48.
[10] C. Bhatt, R. Bento, “A Comparison between American and
European codes on the Non Linear Static Analysis of RC
Buildings,” 15th
World Conference on Earthquake
Engineering, Lisbon 2012
[11] IS 1893 (Part 1): 2002 Indian Standard Criteria for
Earthquake Resistant Design of Structures, Bureau of
Indian Standards, New Delhi 110002.
[12] IS 456-1964, 1978, 2000 Indian Standard Code of
Practice for Plain and Reinforced Concrete, Indian
Standards Institution, New Delhi-110002
[13] Applied Technology Council, ATC-40,(1996),
“Seismic Evaluation and Retrofit of Concrete
Buildings”, Vol.1 and 2, California.
[14] ACI Manual of Concrete Practice 2008,Part3,American
Concrete Institute
[15] Eurocode 8-Design of structures for earthquake
resistance-Part3: Assessment and retrofitting of
buildings, BS EN 1998-3:2005.
[16] FEMA 440 , “ Improvement of Nonlinear Static
Seismic Analysis Procedures”, ATC 55 for the the
Federal Emergency ManagementAgency, Washington,
D.C, 2005.
[17] ASCE 7-05- Minimum Design loads for Building and
other structures
[18]EUROCODE8- Design of structures for Earthquake
Resistant

More Related Content

What's hot

Designofmulti storeyedbuildingsusingstaadpro-140603003704-phpapp01
Designofmulti storeyedbuildingsusingstaadpro-140603003704-phpapp01Designofmulti storeyedbuildingsusingstaadpro-140603003704-phpapp01
Designofmulti storeyedbuildingsusingstaadpro-140603003704-phpapp01
Ramil Artates
 

What's hot (20)

Design of multi storey building resting on single column
Design of multi storey building resting on single columnDesign of multi storey building resting on single column
Design of multi storey building resting on single column
 
A presentation on g+6 building by Staad pro and Autocad
A presentation on g+6 building by Staad pro and AutocadA presentation on g+6 building by Staad pro and Autocad
A presentation on g+6 building by Staad pro and Autocad
 
IRJET- Analysis of G+20 RCC Bare Framed Structures with Different Types o...
IRJET-  	  Analysis of G+20 RCC Bare Framed Structures with Different Types o...IRJET-  	  Analysis of G+20 RCC Bare Framed Structures with Different Types o...
IRJET- Analysis of G+20 RCC Bare Framed Structures with Different Types o...
 
Chapter02.structural design using staad pro
Chapter02.structural design using staad proChapter02.structural design using staad pro
Chapter02.structural design using staad pro
 
Wind Analysis and Design of G+11 Storied Building using STAAD-Pro
Wind Analysis and Design of G+11 Storied Building using STAAD-ProWind Analysis and Design of G+11 Storied Building using STAAD-Pro
Wind Analysis and Design of G+11 Storied Building using STAAD-Pro
 
Designofmulti storeyedbuildingsusingstaadpro-140603003704-phpapp01
Designofmulti storeyedbuildingsusingstaadpro-140603003704-phpapp01Designofmulti storeyedbuildingsusingstaadpro-140603003704-phpapp01
Designofmulti storeyedbuildingsusingstaadpro-140603003704-phpapp01
 
ANALYSIS & DESIGN OF G+3 STORIED REINFORCED CONCRETE BUILDING
ANALYSIS & DESIGN OF G+3 STORIED REINFORCED CONCRETE BUILDING ANALYSIS & DESIGN OF G+3 STORIED REINFORCED CONCRETE BUILDING
ANALYSIS & DESIGN OF G+3 STORIED REINFORCED CONCRETE BUILDING
 
IRJET- Design and Analysis of Residential Multistory Building (G+5) by using ...
IRJET- Design and Analysis of Residential Multistory Building (G+5) by using ...IRJET- Design and Analysis of Residential Multistory Building (G+5) by using ...
IRJET- Design and Analysis of Residential Multistory Building (G+5) by using ...
 
Analysis of 3+ story building in staad pro
Analysis of 3+ story building in staad proAnalysis of 3+ story building in staad pro
Analysis of 3+ story building in staad pro
 
residential buliding by stadd pro
residential buliding by stadd proresidential buliding by stadd pro
residential buliding by stadd pro
 
Dynamic Analysis of Multistorey framed structure with roof tower
Dynamic Analysis of Multistorey framed structure with roof towerDynamic Analysis of Multistorey framed structure with roof tower
Dynamic Analysis of Multistorey framed structure with roof tower
 
Structural anaysis and design of g + 5 storey building using bentley stadd pr...
Structural anaysis and design of g + 5 storey building using bentley stadd pr...Structural anaysis and design of g + 5 storey building using bentley stadd pr...
Structural anaysis and design of g + 5 storey building using bentley stadd pr...
 
ANALYSIS AND DESIGN OF MULTI STOREY (G+5) COMMERCIAL BUILDING BY STAAD PRO AN...
ANALYSIS AND DESIGN OF MULTI STOREY (G+5) COMMERCIAL BUILDING BY STAAD PRO AN...ANALYSIS AND DESIGN OF MULTI STOREY (G+5) COMMERCIAL BUILDING BY STAAD PRO AN...
ANALYSIS AND DESIGN OF MULTI STOREY (G+5) COMMERCIAL BUILDING BY STAAD PRO AN...
 
Project
ProjectProject
Project
 
DESIGN OF G+20 MULTISTOREY BUILDING
DESIGN OF G+20 MULTISTOREY BUILDINGDESIGN OF G+20 MULTISTOREY BUILDING
DESIGN OF G+20 MULTISTOREY BUILDING
 
Construction stage analysis of rcc frames project report
Construction stage analysis of rcc frames   project reportConstruction stage analysis of rcc frames   project report
Construction stage analysis of rcc frames project report
 
Staad Pro Intro
Staad Pro IntroStaad Pro Intro
Staad Pro Intro
 
REPORT ON G+4 RCC HOSTEL BUILDING ANALYSIS AND DESIGN USING STAAD PRO SOFTWARE
REPORT ON G+4 RCC HOSTEL BUILDING ANALYSIS AND DESIGN USING STAAD PRO SOFTWAREREPORT ON G+4 RCC HOSTEL BUILDING ANALYSIS AND DESIGN USING STAAD PRO SOFTWARE
REPORT ON G+4 RCC HOSTEL BUILDING ANALYSIS AND DESIGN USING STAAD PRO SOFTWARE
 
Design of G+8 RCC Training Institute & Hostel Block
Design of G+8 RCC Training Institute & Hostel BlockDesign of G+8 RCC Training Institute & Hostel Block
Design of G+8 RCC Training Institute & Hostel Block
 
staad pro
staad prostaad pro
staad pro
 

Viewers also liked

Hagerman ACI Baltimore 2012
Hagerman ACI Baltimore 2012Hagerman ACI Baltimore 2012
Hagerman ACI Baltimore 2012
Hammer_Hand
 
DYNAMIC ANALYSIS DESIGN AND DETAILING OF OFFICE BUILDING BY USING STRAP
DYNAMIC ANALYSIS DESIGN AND DETAILING OF OFFICE BUILDING BY USING STRAPDYNAMIC ANALYSIS DESIGN AND DETAILING OF OFFICE BUILDING BY USING STRAP
DYNAMIC ANALYSIS DESIGN AND DETAILING OF OFFICE BUILDING BY USING STRAP
IAEME Publication
 
Seismicity of pakistan
Seismicity of pakistanSeismicity of pakistan
Seismicity of pakistan
Rizwan Samor
 

Viewers also liked (20)

Aci 318 08-seismic-requirements-l e garcia
Aci 318 08-seismic-requirements-l e garciaAci 318 08-seismic-requirements-l e garcia
Aci 318 08-seismic-requirements-l e garcia
 
Earthquake Resistant Design Techniques
Earthquake Resistant Design TechniquesEarthquake Resistant Design Techniques
Earthquake Resistant Design Techniques
 
Earthquake and earthquake resistant design
Earthquake   and earthquake resistant designEarthquake   and earthquake resistant design
Earthquake and earthquake resistant design
 
Multi storey building design of 7 storey commercial building
Multi storey building design of 7 storey commercial buildingMulti storey building design of 7 storey commercial building
Multi storey building design of 7 storey commercial building
 
Design and analasys of a g+2 residential building
Design and analasys of a g+2 residential building Design and analasys of a g+2 residential building
Design and analasys of a g+2 residential building
 
DESIGN AND ANALAYSIS OF MULTI STOREY BUILDING USING STAAD PRO
DESIGN AND ANALAYSIS OF MULTI STOREY BUILDING USING STAAD PRODESIGN AND ANALAYSIS OF MULTI STOREY BUILDING USING STAAD PRO
DESIGN AND ANALAYSIS OF MULTI STOREY BUILDING USING STAAD PRO
 
Hagerman ACI Baltimore 2012
Hagerman ACI Baltimore 2012Hagerman ACI Baltimore 2012
Hagerman ACI Baltimore 2012
 
Earthquake resistant building
Earthquake resistant buildingEarthquake resistant building
Earthquake resistant building
 
Earthquake Resistent Structures
Earthquake Resistent StructuresEarthquake Resistent Structures
Earthquake Resistent Structures
 
DESIGN AND ANALYSIS OF MULTI STORIED STRUCTURES USING STATIC NON LINEAR ANALYSIS
DESIGN AND ANALYSIS OF MULTI STORIED STRUCTURES USING STATIC NON LINEAR ANALYSISDESIGN AND ANALYSIS OF MULTI STORIED STRUCTURES USING STATIC NON LINEAR ANALYSIS
DESIGN AND ANALYSIS OF MULTI STORIED STRUCTURES USING STATIC NON LINEAR ANALYSIS
 
Driving Innovation: A Path to Digitization, Speed and Visibility in an Applic...
Driving Innovation: A Path to Digitization, Speed and Visibility in an Applic...Driving Innovation: A Path to Digitization, Speed and Visibility in an Applic...
Driving Innovation: A Path to Digitization, Speed and Visibility in an Applic...
 
DYNAMIC ANALYSIS DESIGN AND DETAILING OF OFFICE BUILDING BY USING STRAP
DYNAMIC ANALYSIS DESIGN AND DETAILING OF OFFICE BUILDING BY USING STRAPDYNAMIC ANALYSIS DESIGN AND DETAILING OF OFFICE BUILDING BY USING STRAP
DYNAMIC ANALYSIS DESIGN AND DETAILING OF OFFICE BUILDING BY USING STRAP
 
Clarity
ClarityClarity
Clarity
 
Dampness in building
Dampness in buildingDampness in building
Dampness in building
 
Special moment frames aci 318 - اطارات مقاومة للعزوم
Special moment frames aci   318 - اطارات مقاومة للعزوم Special moment frames aci   318 - اطارات مقاومة للعزوم
Special moment frames aci 318 - اطارات مقاومة للعزوم
 
DESIGN OF HOSTEL BUILDING G+5
DESIGN OF HOSTEL BUILDING G+5DESIGN OF HOSTEL BUILDING G+5
DESIGN OF HOSTEL BUILDING G+5
 
Chapter02.structural design using staad pro
Chapter02.structural design using staad proChapter02.structural design using staad pro
Chapter02.structural design using staad pro
 
Slides Earthquake Resistant Design part2
Slides Earthquake Resistant Design part2Slides Earthquake Resistant Design part2
Slides Earthquake Resistant Design part2
 
Rcc structure design by etabs (acecoms)
Rcc structure design by etabs (acecoms)Rcc structure design by etabs (acecoms)
Rcc structure design by etabs (acecoms)
 
Seismicity of pakistan
Seismicity of pakistanSeismicity of pakistan
Seismicity of pakistan
 

Similar to Seismic design of multistoreyed rc building using various codes

Similar to Seismic design of multistoreyed rc building using various codes (20)

IRJET- Design of Earthquake Resistant Structure of Multi-Story RCC Building
IRJET- Design of Earthquake Resistant Structure of Multi-Story RCC BuildingIRJET- Design of Earthquake Resistant Structure of Multi-Story RCC Building
IRJET- Design of Earthquake Resistant Structure of Multi-Story RCC Building
 
Analysis and Design of Commercial Building using ETABS
Analysis and Design of Commercial Building using ETABSAnalysis and Design of Commercial Building using ETABS
Analysis and Design of Commercial Building using ETABS
 
DYNAMIC ANALYSIS OF SHEAR BUILDING AT DIFFERENT LOCATIONS IN DIFFERENT SEISMI...
DYNAMIC ANALYSIS OF SHEAR BUILDING AT DIFFERENT LOCATIONS IN DIFFERENT SEISMI...DYNAMIC ANALYSIS OF SHEAR BUILDING AT DIFFERENT LOCATIONS IN DIFFERENT SEISMI...
DYNAMIC ANALYSIS OF SHEAR BUILDING AT DIFFERENT LOCATIONS IN DIFFERENT SEISMI...
 
IRJET-Fast and Secure Cloud Big Data Dedup
IRJET-Fast and Secure Cloud Big Data DedupIRJET-Fast and Secure Cloud Big Data Dedup
IRJET-Fast and Secure Cloud Big Data Dedup
 
Earth quake response of different shapes of mivan wall tall buildings
Earth quake response of different shapes of mivan wall tall buildingsEarth quake response of different shapes of mivan wall tall buildings
Earth quake response of different shapes of mivan wall tall buildings
 
DIA-Grid Structures
DIA-Grid StructuresDIA-Grid Structures
DIA-Grid Structures
 
IRJET- Planning, Analyzing and Design of High Rise Building using Etabs
IRJET- Planning, Analyzing and Design of High Rise Building using EtabsIRJET- Planning, Analyzing and Design of High Rise Building using Etabs
IRJET- Planning, Analyzing and Design of High Rise Building using Etabs
 
Seismic Response of Vertically Irregular Structure with Composite Columns
Seismic Response of Vertically Irregular Structure with Composite ColumnsSeismic Response of Vertically Irregular Structure with Composite Columns
Seismic Response of Vertically Irregular Structure with Composite Columns
 
“Comparative Study of G+16 Building Regular and Irregular buildings Design wi...
“Comparative Study of G+16 Building Regular and Irregular buildings Design wi...“Comparative Study of G+16 Building Regular and Irregular buildings Design wi...
“Comparative Study of G+16 Building Regular and Irregular buildings Design wi...
 
IRJET- Seismic Analysis of Plan Regular and Irregular Buildings
IRJET- Seismic Analysis of Plan Regular and Irregular BuildingsIRJET- Seismic Analysis of Plan Regular and Irregular Buildings
IRJET- Seismic Analysis of Plan Regular and Irregular Buildings
 
Optimum Design of Concrete Diagrid Building and its Comparison with Conventio...
Optimum Design of Concrete Diagrid Building and its Comparison with Conventio...Optimum Design of Concrete Diagrid Building and its Comparison with Conventio...
Optimum Design of Concrete Diagrid Building and its Comparison with Conventio...
 
Comparative Analysis Of Different Irregular Building With Regular Building
Comparative Analysis Of Different Irregular Building With Regular BuildingComparative Analysis Of Different Irregular Building With Regular Building
Comparative Analysis Of Different Irregular Building With Regular Building
 
IJSRED-V2I3P28
IJSRED-V2I3P28IJSRED-V2I3P28
IJSRED-V2I3P28
 
Study on Behavior of Diagrids Under Seismic Loads Compared to Conventional Mo...
Study on Behavior of Diagrids Under Seismic Loads Compared to Conventional Mo...Study on Behavior of Diagrids Under Seismic Loads Compared to Conventional Mo...
Study on Behavior of Diagrids Under Seismic Loads Compared to Conventional Mo...
 
Seismic Analysis of Multistory Building with and without Floating Column
Seismic Analysis of Multistory Building with and without Floating ColumnSeismic Analysis of Multistory Building with and without Floating Column
Seismic Analysis of Multistory Building with and without Floating Column
 
Analysis, Design and Estimation of Basement +G+2 Residential Building
Analysis, Design and Estimation of Basement +G+2 Residential BuildingAnalysis, Design and Estimation of Basement +G+2 Residential Building
Analysis, Design and Estimation of Basement +G+2 Residential Building
 
IRJET-Analysis of RC Structure with and without Shear Wall and Optimum Locati...
IRJET-Analysis of RC Structure with and without Shear Wall and Optimum Locati...IRJET-Analysis of RC Structure with and without Shear Wall and Optimum Locati...
IRJET-Analysis of RC Structure with and without Shear Wall and Optimum Locati...
 
IRJET- Study on Soft Storey Effect of Plan Regular and Irregular RC Frame...
IRJET-  	  Study on Soft Storey Effect of Plan Regular and Irregular RC Frame...IRJET-  	  Study on Soft Storey Effect of Plan Regular and Irregular RC Frame...
IRJET- Study on Soft Storey Effect of Plan Regular and Irregular RC Frame...
 
Seismic evelution of rc space frame with rectangular and equivalent square co...
Seismic evelution of rc space frame with rectangular and equivalent square co...Seismic evelution of rc space frame with rectangular and equivalent square co...
Seismic evelution of rc space frame with rectangular and equivalent square co...
 
IRJET- Performance of High Rise Building under Seismic and Wind Excitation fo...
IRJET- Performance of High Rise Building under Seismic and Wind Excitation fo...IRJET- Performance of High Rise Building under Seismic and Wind Excitation fo...
IRJET- Performance of High Rise Building under Seismic and Wind Excitation fo...
 

More from eSAT Journals

Material management in construction – a case study
Material management in construction – a case studyMaterial management in construction – a case study
Material management in construction – a case study
eSAT Journals
 
Laboratory studies of dense bituminous mixes ii with reclaimed asphalt materials
Laboratory studies of dense bituminous mixes ii with reclaimed asphalt materialsLaboratory studies of dense bituminous mixes ii with reclaimed asphalt materials
Laboratory studies of dense bituminous mixes ii with reclaimed asphalt materials
eSAT Journals
 
Geographical information system (gis) for water resources management
Geographical information system (gis) for water resources managementGeographical information system (gis) for water resources management
Geographical information system (gis) for water resources management
eSAT Journals
 
Estimation of surface runoff in nallur amanikere watershed using scs cn method
Estimation of surface runoff in nallur amanikere watershed using scs cn methodEstimation of surface runoff in nallur amanikere watershed using scs cn method
Estimation of surface runoff in nallur amanikere watershed using scs cn method
eSAT Journals
 
Effect of variation of plastic hinge length on the results of non linear anal...
Effect of variation of plastic hinge length on the results of non linear anal...Effect of variation of plastic hinge length on the results of non linear anal...
Effect of variation of plastic hinge length on the results of non linear anal...
eSAT Journals
 

More from eSAT Journals (20)

Mechanical properties of hybrid fiber reinforced concrete for pavements
Mechanical properties of hybrid fiber reinforced concrete for pavementsMechanical properties of hybrid fiber reinforced concrete for pavements
Mechanical properties of hybrid fiber reinforced concrete for pavements
 
Material management in construction – a case study
Material management in construction – a case studyMaterial management in construction – a case study
Material management in construction – a case study
 
Managing drought short term strategies in semi arid regions a case study
Managing drought    short term strategies in semi arid regions  a case studyManaging drought    short term strategies in semi arid regions  a case study
Managing drought short term strategies in semi arid regions a case study
 
Life cycle cost analysis of overlay for an urban road in bangalore
Life cycle cost analysis of overlay for an urban road in bangaloreLife cycle cost analysis of overlay for an urban road in bangalore
Life cycle cost analysis of overlay for an urban road in bangalore
 
Laboratory studies of dense bituminous mixes ii with reclaimed asphalt materials
Laboratory studies of dense bituminous mixes ii with reclaimed asphalt materialsLaboratory studies of dense bituminous mixes ii with reclaimed asphalt materials
Laboratory studies of dense bituminous mixes ii with reclaimed asphalt materials
 
Laboratory investigation of expansive soil stabilized with natural inorganic ...
Laboratory investigation of expansive soil stabilized with natural inorganic ...Laboratory investigation of expansive soil stabilized with natural inorganic ...
Laboratory investigation of expansive soil stabilized with natural inorganic ...
 
Influence of reinforcement on the behavior of hollow concrete block masonry p...
Influence of reinforcement on the behavior of hollow concrete block masonry p...Influence of reinforcement on the behavior of hollow concrete block masonry p...
Influence of reinforcement on the behavior of hollow concrete block masonry p...
 
Influence of compaction energy on soil stabilized with chemical stabilizer
Influence of compaction energy on soil stabilized with chemical stabilizerInfluence of compaction energy on soil stabilized with chemical stabilizer
Influence of compaction energy on soil stabilized with chemical stabilizer
 
Geographical information system (gis) for water resources management
Geographical information system (gis) for water resources managementGeographical information system (gis) for water resources management
Geographical information system (gis) for water resources management
 
Forest type mapping of bidar forest division, karnataka using geoinformatics ...
Forest type mapping of bidar forest division, karnataka using geoinformatics ...Forest type mapping of bidar forest division, karnataka using geoinformatics ...
Forest type mapping of bidar forest division, karnataka using geoinformatics ...
 
Factors influencing compressive strength of geopolymer concrete
Factors influencing compressive strength of geopolymer concreteFactors influencing compressive strength of geopolymer concrete
Factors influencing compressive strength of geopolymer concrete
 
Experimental investigation on circular hollow steel columns in filled with li...
Experimental investigation on circular hollow steel columns in filled with li...Experimental investigation on circular hollow steel columns in filled with li...
Experimental investigation on circular hollow steel columns in filled with li...
 
Experimental behavior of circular hsscfrc filled steel tubular columns under ...
Experimental behavior of circular hsscfrc filled steel tubular columns under ...Experimental behavior of circular hsscfrc filled steel tubular columns under ...
Experimental behavior of circular hsscfrc filled steel tubular columns under ...
 
Evaluation of punching shear in flat slabs
Evaluation of punching shear in flat slabsEvaluation of punching shear in flat slabs
Evaluation of punching shear in flat slabs
 
Evaluation of performance of intake tower dam for recent earthquake in india
Evaluation of performance of intake tower dam for recent earthquake in indiaEvaluation of performance of intake tower dam for recent earthquake in india
Evaluation of performance of intake tower dam for recent earthquake in india
 
Evaluation of operational efficiency of urban road network using travel time ...
Evaluation of operational efficiency of urban road network using travel time ...Evaluation of operational efficiency of urban road network using travel time ...
Evaluation of operational efficiency of urban road network using travel time ...
 
Estimation of surface runoff in nallur amanikere watershed using scs cn method
Estimation of surface runoff in nallur amanikere watershed using scs cn methodEstimation of surface runoff in nallur amanikere watershed using scs cn method
Estimation of surface runoff in nallur amanikere watershed using scs cn method
 
Estimation of morphometric parameters and runoff using rs & gis techniques
Estimation of morphometric parameters and runoff using rs & gis techniquesEstimation of morphometric parameters and runoff using rs & gis techniques
Estimation of morphometric parameters and runoff using rs & gis techniques
 
Effect of variation of plastic hinge length on the results of non linear anal...
Effect of variation of plastic hinge length on the results of non linear anal...Effect of variation of plastic hinge length on the results of non linear anal...
Effect of variation of plastic hinge length on the results of non linear anal...
 
Effect of use of recycled materials on indirect tensile strength of asphalt c...
Effect of use of recycled materials on indirect tensile strength of asphalt c...Effect of use of recycled materials on indirect tensile strength of asphalt c...
Effect of use of recycled materials on indirect tensile strength of asphalt c...
 

Recently uploaded

"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
mphochane1998
 
Digital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptxDigital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptx
pritamlangde
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
MayuraD1
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
Neometrix_Engineering_Pvt_Ltd
 

Recently uploaded (20)

Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdf
 
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxA CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
Learn the concepts of Thermodynamics on Magic Marks
Learn the concepts of Thermodynamics on Magic MarksLearn the concepts of Thermodynamics on Magic Marks
Learn the concepts of Thermodynamics on Magic Marks
 
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
 
Online electricity billing project report..pdf
Online electricity billing project report..pdfOnline electricity billing project report..pdf
Online electricity billing project report..pdf
 
Digital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptxDigital Communication Essentials: DPCM, DM, and ADM .pptx
Digital Communication Essentials: DPCM, DM, and ADM .pptx
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Introduction to Data Visualization,Matplotlib.pdf
Introduction to Data Visualization,Matplotlib.pdfIntroduction to Data Visualization,Matplotlib.pdf
Introduction to Data Visualization,Matplotlib.pdf
 
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptxOrlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
 
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best ServiceTamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
 
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKARHAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
 
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 

Seismic design of multistoreyed rc building using various codes

  • 1. IJRET: International Journal of Research in Engineering and Technology __________________________________________________________ Volume: 05 Issue: 02 | Feb-2016, Available @ SEISMIC DESIGN OF MULTISTOREY Pamela Jennifer J P 1 PG Scholar, Department of Civil Engineering, Adhiyamaan College 2 Assistant Professor, Department of Civil Engineering, Adhiyamaan College 3 HOD, Department of Civil Engineering, Adhiyamaan College Earthquake is a major phenomenon which cause failure to the Reinforced Concrete(RC) structure. The necessity of designing the structure as per codal provision is must for all kind of structure. In this for study. The Linear static analysis was done using American, European and Indian Codes. The building is modeled and analysed using ETABS software. All the required parameters for analysis was taken a storey deflection, storey drift and base shear were compared. The displacement, storey shear and storey displacement obtained from ACI code design is more when compared with other code’s analysis result. Keywords: Displacement, Shear, Drift, Seismic ------------------------------------------------------------------- 1. HEADING 1 1.INTRODUCTION Earthquake resistant structures are capable of resisting lateral and vertical forces acting on the structures. But no structures can entirely survive during earthquake without any damages. According to codes, earthquake resistant structures are designed to withstand expected earthquake atleast to occur once during the design life of the stru Reinforced concrete buildings are analysed and designed to meet the requirements of relevant codes of practice. Such buildings designed as per codal provision will survive during earthquake with minor damages of structural elements The following codes are used for analysis purpose; 1. Indian Standard Code IS 1893(Part 1):2002 and IS13920:1993. 2. European code EUROCODE 8: 1998 3. American code ASCE 7-05 Linear Static analysis is applying load in linear pattern. 2. MODELLING AND ANALYSIS A multi-storey building of G+10 with 3x3 bays is considered for this study as shown in fig 1. The base dimension of the plan is 9m x 9m. the typical storey height is 3m for all storeys. The structural elements are considered IJRET: International Journal of Research in Engineering and Technology eISSN: 2319 _______________________________________________________________________________________ , Available @ http://www.ijret.org SEISMIC DESIGN OF MULTISTOREYED RC BUILDING USING VARIOUS CODES Pamela Jennifer J P1 , Jegidha. K. J2 , Sureshbabu. S3 Civil Engineering, Adhiyamaan College of Engineering, Hosur, pamejenni12@gmail.com Civil Engineering, Adhiyamaan College of Engineering Hosur, Krishnagiri, India. jegi.kj@gmail.com Civil Engineering, Adhiyamaan College of Engineering Hosur, Krishnagiri, Abstract Earthquake is a major phenomenon which cause failure to the Reinforced Concrete(RC) structure. The necessity of designing the structure as per codal provision is must for all kind of structure. In this research, a building of regular plan of G+10 was taken for study. The Linear static analysis was done using American, European and Indian Codes. The building is modeled and analysed using ETABS software. All the required parameters for analysis was taken as per respective codes. Various response like storey deflection, storey drift and base shear were compared. The displacement, storey shear and storey displacement obtained from ACI code design is more when compared with other code’s analysis result. Seismic Analysis -------------------------------------------------------------------***--------------------------------------- Earthquake resistant structures are capable of resisting ting on the structures. But no structures can entirely survive during earthquake without any damages. According to codes, earthquake resistant structures are designed to withstand expected earthquake atleast to occur once during the design life of the structure. Reinforced concrete buildings are analysed and designed to meet the requirements of relevant codes of practice. Such buildings designed as per codal provision will survive during earthquake with minor damages of structural codes are used for analysis purpose; d in linear pattern. storey building of G+10 with 3x3 bays is considered for this study as shown in fig 1. The base dimension of the plan is 9m x 9m. the typical storey height is 3m for all storeys. The structural elements are considered as square for all storeys. The three codal provisions as mentioned above. A Linear Static analysis is done using ETABS 2015. The model is studied for all three code for severe zone with medium soil condition. 2.1 PLAN AND ELEVATION OF THE BUILDING MODEL: Plan and Elevation of the building Fig (1). Plan of frame eISSN: 2319-1163 | pISSN: 2321-7308 _____________________________ 314 RC BUILDING USING 3 Engineering, Hosur, Krishnagiri, India. Engineering Hosur, Krishnagiri, Engineering Hosur, Krishnagiri, India Earthquake is a major phenomenon which cause failure to the Reinforced Concrete(RC) structure. The necessity of designing the research, a building of regular plan of G+10 was taken for study. The Linear static analysis was done using American, European and Indian Codes. The building is modeled and s per respective codes. Various response like storey deflection, storey drift and base shear were compared. The displacement, storey shear and storey displacement obtained ---------------------------------------------------------------------- as square for all storeys. The building is designed for all three codal provisions as mentioned above. A Linear Static analysis is done using ETABS 2015. The model is studied for all three code for severe zone with medium soil 2.1 PLAN AND ELEVATION OF THE Plan and Elevation of the building Plan of frame
  • 2. IJRET: International Journal of Research in Engineering and Technology __________________________________________________________ Volume: 05 Issue: 02 | Feb-2016, Available @ Fig (2). Elevation of frame Table 1- Preliminary Data DETAILS OF BUILDING FOR ALL STORIES Number of storey G+10 Storey Height 3m Beam size 230m* 600m Column size 230m* 600m Slab Thickness 125m Wall Thickness 230mm Grade of Concrete M25 Grade of Steel Fe415 2.2 METHODOLOGY OF THE PROJECT In this study, linear static analysis is done to find out the response of the building. The storey displacement, shear and drift is determined using ETABS software. The building is designed and detailed as per the codes and the results were compared and discussed. 3. RESULTS AND DISCUSSIONS 3.1 RESULTS FOR EACH CASES Case(i). Analysis result obtained using IS Code IJRET: International Journal of Research in Engineering and Technology eISSN: 2319 _______________________________________________________________________________________ , Available @ http://www.ijret.org FOR ALL STORIES 230m* 600m 230m* 600m 2.2 METHODOLOGY OF THE PROJECT In this study, linear static analysis is done to find out the response of the building. The storey displacement, shear and ETABS software. The building is designed and detailed as per the codes and the results were Case(i). Analysis result obtained using IS Code Fig (3) Fig (4) Fig (5) Fig (3),(4),(5). Shows the displacement , shear and drift for the building 0 20 40 60 80 100 0 10 DISPLACEMENT STOREY DISPLACEMENT(mm) 0 200 400 600 800 1000 0 10 STOREYSHEAR STOREY STOREY SHEAR(KN) 0 0.0005 0.001 0.0015 0.002 0.0025 0.003 0.0035 0.004 0 5 SOREYDRIFT STOREY STOREY DRIFT eISSN: 2319-1163 | pISSN: 2321-7308 _____________________________ 315 Fig (3) Fig (4) Fig (5) hows the displacement , shear and drift for the building 20 STOREY DISPLACEMENT(mm) DISPLACE MENT(m m) 20 STOREY STOREY SHEAR(KN) STOREY SHEAR(KN ) 10 15 STOREY STOREY DRIFT STOREY DRIFT
  • 3. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 05 Issue: 02 | Feb-2016, Available @ http://www.ijret.org 316 Case (ii) Analysis Result obtained using EURO code Fig (6) Fig(7) Fig (8) Fig (6),(7)&(8). Shows the shear,displacementand drift of the structure Case (iii) Analysis Result obtained using ACI code Fig (9) Fig (10) Fig(11) Fig (9),(10)&(11) shows the displacement, shear and drift of the structure 0 100 200 300 400 500 600 700 0 10 20 STOREYSHEAR STOREY STOREY SHEAR(KN) STOREY SHEAR(KN ) 0 10 20 30 40 50 0 10 20 DISPLACEMENT STOREY DISPLACEMENT (mm) DISPLACEM ENT (mm) 0 0.0005 0.001 0.0015 0.002 0.0025 0 5 10 15 STOREYDRIFT STOREY STOREY DRIFT STOREY DRIFT 0 50 100 150 200 0 10 20 STOREYDISPLACEMENT STOREY STOREY DISPLACEMENT(mm ) STOREY DISPLACE MENT(m m) 0 200 400 600 800 1000 1200 0 10 20 STOREYSHEAR STOREY SROREY SHEAR(KN) SROREY SHEAR(KN) 0 0.002 0.004 0.006 0.008 0.01 0.012 0.014 0.016 0 5 10 15 STOREYDRIFT STOREY STOREY DRIFT STOREY DRIFT
  • 4. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 05 Issue: 02 | Feb-2016, Available @ http://www.ijret.org 317 3.2 COMPARATIVE ANALYSIS 3.2.1 STOREY DISPLACEMENT: Table 2. Comparison result of Displacement Storey IS CODE EURO CODE ACI CODE Base 0 0 0 1 9.4 5.2 45.7 2 20.1 11 61.4 3 30.9 16.7 75.9 4 41.7 22.2 89.9 5 52.3 27.3 103.1 6 62.2 32 115.3 7 71.3 36.1 126 8 79.2 39.5 134.8 9 85.3 42.1 141.5 10 89.3 43.7 145.7 Fig 12. Comparison result of Displacement for all cases 3.2.2 STOREY SHEAR: Table 3. Comparison result of Storey Shear Storey IS CODE EURO CODE ACI CODE Base 0 0 0 1 880.75 618.4 1037.6 2 878.44 607.09 1025.56 3 869.19 584.47 996.93 4 848.39 550.54 949.39 5 811.41 505.3 881.29 6 753.63 448.76 791.28 7 670.42 380.896 678.23 8 557.17 301.73 541.15 9 409.25 211.25 379.17 10 222.03 109.46 191.49 Fig 13. Comparison result of Storey shear for all cases 3.2.3 STOREY DRIFT: Table 4. Comparison result of Storey Drift Storey IS CODE EURO CODE ACI CODE Base 0 0 0 1 0.003136 0.00175 0.0152 2 0.003555 0.00192 0.0052 3 0.003612 0.00189 0.0048 4 0.003602 0.00183 0.0047 5 0.003513 0.00172 0.0044 6 0.003329 0.00156 0.0041 7 0.003033 0.00137 0.0036 8 0.00261 0.00113 0.0029 9 0.002043 0.00086 0.0022 10 0.001327 0.00055 0.0014 Fig 14. Comparison result of Storey Drift for all cases 4. CONCLUSIONS  The analysis as per ACI code shows more displacement, storey shear and storey drift when compared with IS standard and Euro code.  The displacement, shear and drift is maximum for first story for all cases.  Comparing IS and EURO code, the displacement is increased by 50% for all stories as per IS code than EURO code. For Euro and ACI code, the displacement is varied from 88% to 70% from the base to top storey. 0 20 40 60 80 100 120 140 160 0 5 10 15 DISPLACEMENT STOREY DISPLACEMENT(mm) IS CODE EURO CODE ACI CODE 0 500 1000 1500 0 5 10 15 STOREYSHEAR STOREY STOREY SHEAR(mm) IS CODE EURO CODE ACI CODE 0 0.005 0.01 0.015 0.02 0 5 10 15 IS CODE EURO CODE ACI CODE
  • 5. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 05 Issue: 02 | Feb-2016, Available @ http://www.ijret.org 318  Comparing the storey shear for EURO and IS code, the value varies from 30% to 50% from base to top floor. For EURO and ACI codes, the shear varies from 40% to 43%.  Comparing the Storey Drift for EURO and IS code, the value varies from 44% to 59%. For EURO and ACI codes , the drift varies from 88% to 60%. 5. REFERENCES [1] Jaya Prakash Kadali,M.K.M.V.Rathnam Static Analysis of Multistoreyed RC Buildings By Using Pushover Methodology International Journal for Innovative Research in Science & Technology Volume1,Issue 8, January 2015 pp113-124.1989. [2] Mr.K.Lova Raju, Dr.K.V.G.D.Balaji,” Effective location of shear wall on performance of building frame subjected to earthquake load,” International Advanced Research Journal in Science, Engineering and Technology Vol. 2, Issue 1, January 2015,pp 33- 36. [3] Md. Rashedul Kabir, Debasish Sen, Md. Mashfiqul Islam I,”Response of multi-storey regular and irregular buildings of identical weight under static and dynamic loading in context of Bangladesh,” International journal of Civil and Structural Engineering, Volume 5, No 3, February 2015, pp 252-260. [4] Akshay V. Raut, Prof. RVRK Prasad, “Pushover Analysis of G+3 Reinforced Concrete Building with soft storey,” IOSR Journal of Mechanical and Civil Engineering , Volume 11, Issue 4 Ver. I (Jul- Aug. 2014), PP 25-29 [5] Lakshmi K.O, Prof. Jayasree Ramanujan, Mrs. Bindu Sunil, Dr. Laju Kottallil, Prof. Mercy Joseph Poweth,“Effect of shear wall location in buildings subjected to seismic loads,” ISOI Journal of Engineering and Computer science, Volume 1 Issue 1;2014, Page No. 07-17, [6] Nitin Choudhary, Prof. Mahendra Wadia, “Pushover Analysis of R.C. Frame Building with Shear Wall,” IOSR Journal of Mechanical and Civil Engineering , volume 11, Issue 2 Ver. V (Mar- Apr. 2014), PP 09-13 [7] Riza Ainul Hakim, Mohammed Sohaib Alama, Samir A. Ashour, “Seismic Assessment of an RC Building Using Pushover Analysis,” Engineering, Technology & Applied Science Research Vol. 4, No. 3, 2014, pp:631- 635. [8] Praveen Rathod ,Dr.S.S.Dyavanal, “Non-Linear Static Analysis of G+6 Storeyed RC Buildings with Openings in Infill Walls,” Int. Journal of Engineering Research and Applications, Vol. 4, Issue 9( Version 5), September 2014, pp.51-58. [9] A.Cinitha, P.K. Umesha, Nagesh R. Iyer, “Nonlinear Static Analysis to Assess Seismic Performance and Vulnerability of Code - Conforming RC Buildings,” WSEAS TRANSACTIONS on APPLIED and THEORETICAL MECHANICS, Issue 1, Volume 7, January 2012,pp39-48. [10] C. Bhatt, R. Bento, “A Comparison between American and European codes on the Non Linear Static Analysis of RC Buildings,” 15th World Conference on Earthquake Engineering, Lisbon 2012 [11] IS 1893 (Part 1): 2002 Indian Standard Criteria for Earthquake Resistant Design of Structures, Bureau of Indian Standards, New Delhi 110002. [12] IS 456-1964, 1978, 2000 Indian Standard Code of Practice for Plain and Reinforced Concrete, Indian Standards Institution, New Delhi-110002 [13] Applied Technology Council, ATC-40,(1996), “Seismic Evaluation and Retrofit of Concrete Buildings”, Vol.1 and 2, California. [14] ACI Manual of Concrete Practice 2008,Part3,American Concrete Institute [15] Eurocode 8-Design of structures for earthquake resistance-Part3: Assessment and retrofitting of buildings, BS EN 1998-3:2005. [16] FEMA 440 , “ Improvement of Nonlinear Static Seismic Analysis Procedures”, ATC 55 for the the Federal Emergency ManagementAgency, Washington, D.C, 2005. [17] ASCE 7-05- Minimum Design loads for Building and other structures [18]EUROCODE8- Design of structures for Earthquake Resistant