1. Instruction Sheet
AMPTRAC*, Cat 5e, 408–8682
Modular, Universal Wiring, Patch Panels 21 AUG 02 Rev A
NOTE
Although a 22–26 AWG wire size is recommended, some types of insulation (due to outer diameter measurement or material) may
not terminate properly. Outside diameters of 1.27 mm [.050 in.] or larger are not typically recommended. Although, depending on
the type of insulation, larger diameters may make acceptable terminations. Some wire types falling below 1.27 mm [.050 in.]
diameter may not terminate properly because of a tougher insulation type.
Qualification testing was conducted using 22–26 AWG wire with an outside diameter of 0.91 mm [.036 in.].
Standard 483 mm [19 In.] Identification Label
Panel Rack with 10–32 or (Customer Supplied)
12–24 Tapped Holes The 110Connect Blocks may be
terminated with Standard Impact
Tool 558418–1, Pro Impact Tool
1375308–1, Universal Wire
Insertion Tool, or 788J1–Type
5–Pair Tool. Remove loose wire
pieces. If tool does not properly
trim wires, replace tool blade.
Use of other cutting tools to trim
wires may damage patch panel.
Sensor Contact Area
(Typ)
Cutoff
Blade Insertion
Blade
10–32 or 12–24
Steel Screw
Figure 1
1. INTRODUCTION 2. DESCRIPTION
Each panel includes the necessary mounting
This instruction sheet covers the installation hardware, universal T568A/T568B wiring labels, and
procedures for AMPTRAC, Cat 5e, Modular, cable management cable ties. See Figures 1 and 2.
Universal Wiring, Patch Panels 1435361–1 and
1435362–1. The panels can be mounted on any
standard 483 mm [19 in.] equipment rack or 3. INSTALLATION PROCEDURES (Figure 2)
communication cabinet as shown in Figure 1.
3.1. General Instructions
NOTE All dimensions are in millimeters [with inches in Unpack assembly and install universal wiring labels,
brackets]. Figures are not drawn to scale. with the T568A or T568B side facing up, to match the
wiring pattern being used at the outlet. Match label
Reasons for revision of this instruction sheet are port numbers to port numbers on front of panel.
provided in Section 4, REVISION SUMMARY. Assemble cable ties or cable management bar(s).
E2002 Tyco Electronics Corporation, Harrisburg, PA. This controlled document is subject to change. TOOLING ASSISTANCE CENTER 1–800–722–1111 1 of 2
All International Rights Reserved. For latest revision call the AMP FAX* number. AMP FAX/PRODUCT INFO 1–800–522–6752
AMP and Tyco are trademarks. For more information on NETCONNECT* products, For Regional Customer Service, visit our website at LOC B
*Trademark visit our website at www.ampnetconnect.com www.tycoelectronics.com
Other products, logos, and company names used are the property of their respective owners.
2. AMPTRAC, Cat 5e, Modular, Universal Wiring, Patch Panels 408–8682
Rack
T568B Side T568A Side
or
Tear Along Perforations
Wiring Label
Cable Tie – Do Not
Overtighten
Sheet of Universal Wiring Labels
Bend Radius Not Less Than
Four Times Cable Diameter
Color Marks on T568A Side of Wiring Label
Release Feature May
Tie Release be Used to Add
[ BLU GRN ORG BRN ]
Cables or Loosen
GRN WHT
WHT GRN
ORG WHT
WHT ORG
BRN WHT
WHT BRN
Cable Tie
BLU WHT
WHT BLU
Cable Tie Cable Tie
Application Holder
Color Marks on T568B Side of Wiring Label Cables
[ BLU ORG GRN BRN ]
Cable Management Bar 406042–1 (63.5 mm [2.50 In.] Deep)
ORG WHT
WHT ORG
GRN WHT
WHT GRN
BRN WHT
WHT BRN
BLU WHT
WHT BLU
or 557548–1 (127 mm [5 In.] Deep)
Mounts Directly to Rack
(Bar Purchased Separately)
Allow No More than Cable
13 mm [0.5 In.] to Strip Back Minimum
Amount of Cable Cable Ties
Untwist (Customer Supplied)
Jacket
Figure 2
3.2. Special Instructions for Category 5 Enhanced 4. REVISION SUMMARY
Applications
Per EC 0990–1237–02:
NOTE At all times, the wiring practices must comply
with practices of ANSI/TIA/EIA–568–A S Added Pro–Impact Tool reference to Figure 1
Specification.
Guidelines covered in the above specification and
shown in Figure 2 must be followed.
2 of 2 Rev A