ISr3370(PartlII)-1967
Indian Standard ( Reaffirmcd lggl )
CODE OF PRACTICE FOR
CONCRETE STRUCTURES FOR
THE STORAGE, OF LIQUIDS
PART III PRESTRESSED CONCRETE STRUCTURES
( Ninth Reprint APRIL 1992 )
UDC 621.642.3:624.953:666,984
@ICopyright 1968
BUREAU OF IN.DIAN STANDARDS
MANAK BHAVAN. 9 BAHADUR SHAH ZAFAR MAR0
NBWDELllIIlOOOZ
Gr 3 January 1968
( Reaffirmed 1999 )
IS : 3370( Part III ) - 1967
Indian Standard
CODE OF PRACTICE FOR
CONCRETE STRUCTURES FOR
THE STORAGE OF LIQUIDS
PART III PRESTRESSED CONCRETE STRUCTURES
Cement and Concrete Sedtional Committee, BDC 2
Chairman Re@senting
SHRI K. K. NAMBIAR The Concrete Association of India, Bombay
Members
Sam M. A. MEHTA ( Alternate to
Shri K. K. Nambiar )
SHRI K.F. ANTIA M.N. Dastur & Co ( Pvt ) Ltd, Calcutta
SHRI A. P. BA~CHI Sahu Cement Service, New Delhi
SHRI P. S. BHATNA~AR
DR S. K. CHOPRA
Bhakra & Beas Designs Organization! New Delhi
~Central Building Research Instttute ( CSIR ),
Roorkee
SHRIJ. S. SHARMA (Alternate)
DIRECTOR( CSM ) Central Water & Power Commission
DIRECTOR( DAMSIII ) ( Alkvnate 1
DR R. K. GHOSH
SHRI B. K. GUHA
SUPERINTENDWO ENGINEER,
2nd CIRCLE( .Altemate )
DR R. R. HATTIANGADI
SHRI ~;,“,J~; ( Akvnatc )
JOINT STANDARDS
(B&S)
DEPIJTYDIRECTORSTANDARDS
(B&S) (Alternate)
SHRt S. B. Josm
PROF S. R. ME~RA
-Indian Roads Congress, New Delhi
Central Public Works Department, New Delhi
DR R. K. GHOSH( Alternate )
SHRI S. N. MUKERJI National Test House, Calcutta
SHRI E. K. RAMCWANDRAN( Alternate )
SHRI ERACH A. NADIRSHAH Institution of Engineers ( India ), Calcutta
BRIGNARESH PRA~AD Engineer-in-Chief’s Branch, Army Headquarters
SHRI C. B. PATEL National Buildings Organization
SHRIRABINDERSINGH( Alternate )
SWRII. L. PATEL Directorate General of Supplies & Disposals
SHRl T. N. S. RAO Gammon India Ltd, Bombay
SIIRI S. R. PINHEIRO(Alternate)
( Continued on page 2 )
The Associated Cement Companies Ltd, Bombay
Research, . Designs & Standards Organization
( Ministry of Railways )
S.B. Joshi & Co Ltd, Bombay
Cent;talhyd Research Institute ( CSIR ), New
BUREAU OF INDIAN STANDARDS
bl.ANAK BIIAVAN, 9 RAHADUR SHAH ZAFAR MARG
NEW DILHI 110002
ISr337O(Part III)-1967
( conrt2wdffm pugs1)
Members
~PRESENTATIVE
REPRESENTATIVE
SHRI K. G. SALVI
Rcplczating
Geological Survey of India, Calcutta
The India Cements Ltd, Madras
SI-IRI c. L. &WJWAL ( Alternate)
Hindustan Housing Factory Ltd, New Delhi
]3R s. SARKAR
SHRI Z. GEORGE ( Altarnate )
Struct~o~k&neering Research Centre ( CSIR ),
SECriETARY Central Board of Irrigation & Power, New Delhi
SIiRl L. SWAROOP
SHRI A. V. RAMANA(Alternate)
Dalmia Cement ( Bharat ) Ltd, New Delhi
SHRI J. -2. TREHAN
SHRI N. H. KESWANI ( Alternate)
Roads Wing, Ministry of Transport
DR H. C. VISVESVARAYA Cement Research Institute of India, New Delhi
SHRSR. NAOARAJAN,
Director ( Civ Engg )
Director General, ISI ( Ex-oficio Member )
Secretary
SHRIY. R. TANEJA
Deputy Director ( Civ Engg ), IS1
Concrete Subcommittee, BDC 2 : 2
Convener
Sxnt S. B. JOSHI S.B. Joshi & Co Ltd, Bombay
Members
SHRI B. D. AHUJA
SHRI P. C. JAIN ( Alternate)
National Buildings Organization
SHRI K. F. ANTIA
SHRI B, C. PATEL ( Alternate)
M.N. Dastur & Co ( Pvt) Ltd, Calcutta
SHRI A. P. BACXXI Sahu Cement Service, New Delhi
SHRI B. K. CHOKSI In personal capacity ( M60 Cusrow Bag, Bombay )
DR S. K. C~OPRA Central Building Research Institute ( CSIR ),
Roorkee -
DR I. C. Dos M. PAIS CUDDOU Central Water 82 Power Commission
DIRECTOR.( DAMSI ) ( Alternate )
DEPU~ DIRECTOR STANDARM Research, Designs and Standards Organization
(B&S) ( Ministry of Railways )
ASSISTANTDIRECTOR STAND
ARDS(B&S) (Altematc)
DIRECTOR * ’ . Hyderabad Engineering Research Laboratory,
Hyderabad
DIRECTOR-IN-CHARGE
SHRIV. N. GUNAJI
SHRI V. K. GUPTA
SHRI K. K. NAMBIAR
SHRI C. L. N. IYENGAR
DR M. L. PURI
Geological Survey of India, Lucknow
Public Works Department, Maharashtra
Engineer-in-Chief’s Branch, Army Headquarters
The Concrete Association of India, Bombay
( Alternate )
Centr$hXoad Research Institute ( CSIR), New
( Continuedonhuge 12 )
2
i-
IS : 3370 ( Part III ) - 1967
Indian Standard
CODE OF PRACTICE FOR
CONCRETE STRUCTURES FOR
THE STORAGE OF LIQUIDS
PART III PRESTRESSED CONCRETE STRUCTURES
0. FOREWORD
0.1 This Indian Standard was adopted by the Indian Standards Institu-
tion on 20 October 1967, after the draft finahzed by the Cement and
Concrete Sectional Committee had been approved by the Civil Engincer-
ing Division Council.
0.2 The need for a code covering the design and construction of reinforced
concrete and prestressed concrete structures for the storage of liquids has
been long felt in this country. So far engineers, designers and builders in
this country have been adapting mainly the recommendations of the
Institution of Civil Engineers, London, and more recently some of the
recommendations of the Portland Cement Association. The conditions in
this country, however, differ in many ways from those prevailing in UK
and USA; for instance, climatic and weather conditions are sub,jccted
generally to larger variations, matLrials for concrete differ considerably in
their physical properties and the prevailing practices in construction have
special influence on the,methods of use of reinforced and prestrcs;ed co*>-
Crete. The need was, therefore, felt to give clue consideration to these
factors in the practices followed in the country with a view to fully satisf! ~ng
the functional requirements of structures for the storage of liquids. In
order to fulfil this need, formulation of ‘ Indian Standard code of practice
for concrete structures for the storage of liquids’ was undertaken which is
being issued in parts. This part [ IS : 3370 ( Part III )-1967 ] deals with
prestressed concrete structures. The other parts of the code are the
following:
Part I General requirements
Part II Reinforced concrete structures
Part IV Design tables
0.3 Although the provisions of this standard cover mainly structures for
the storage of liquids, the general provisions of this code may also be
applied, with such modifications as found necessary, to suit the special
conditions in the design of reinforced concrete and prestressed concrete,
structures for the conveyance of liquids, such as aqueducts and super-
passages.
3
IS : 3370 ( Part III ) - 1967
0.4 While the common methods of design and construction have been
covered in this code, design of structures of special forms or under unusual
circumstances should be left to the judgment of the engineer and in
such cases special systems of design and construction may be permitted on
production of satisfactory evidence regarding their adequacy and safety by
analysis or test or both.
0.5 In this standard it has been assumed that the design of prestressed
concrete liquid retaining structures is entrusted to a qualified engineer and
that the execution of the work is carried out under the direction of an
experienced supervisor.
0.6 All requirements of IS : 456-1964” and IS : 1343-1960t in so far as
they apply, shall be deemed to form part of this code except where other-
wise laid down in this code.
0.7 The Sectional Committee responsible for the preparation .of this
standard has taken into consideration the views of engineers, and techno-
logists and has related the standard to the practices followed in the country
in this field. Due weightage has also been given to the need for inter-
national co-ordination between the standards prevailing in different
countries of the world. These considerations led the Sectional Committee
to derive assistance from published materials of the following organiza-
tions:
British Standards Institution
Portland Cement Association, Chicago, USA
Institution of Civil Engineers, London.
0.8 For the purpose of deciding whether a particular requirement of this
standard is complied with, the final value, observed or calculated, express-
ing the result of a test or analysis, shall be rounded off in accordance
with IS : 2-1960$. The number of significant places retained in the
rounded off value should be the same as that of the specified value
in this standard.
1. SCOPE
1.1 This standard (Part III ) lays down the requirements applicable
specifically to the prestressed concrete structures for the storage of liquids,
mainly water. These requirements are in addition to the general
requirements laid down in IS : 3370 ( Part I )-1965s.
*Code of practicefor plain and reinforced concrete ( secondrevision ).
tCode of practice for prestressed concrete.
SRules for rounding off numerical valua( r&d ).
$Code of practice for concrete structures for the storage of liquids: Part I General
requirements.
4
f
c
IS:337O(Part III)-1967
1.2 This code does not cover the requirements for reinforced and pre-
stressed concrete structures for storage of hot liquids and liquids of low
viscosity and high penetrating power lie petrol, diesel oil, etc. Special
problems of shrinkage arising in the storage of non-aqueous liquids and
the measures necessary where chemical attack is possible, are also not dealt
with. The recommendations, however, may generally be applicable to the
storage at normal temperatures of aqueous liquids and solutions which
have no detrimental action on concrete and steel or where sufficient
precautions are taken to ensure protection of concrete and steel from
damage due to action of such liquids as in the case of sewage.
2. GENERAL REQ-MENTS
2.1 Design and construction of prestressed concrete liquid retaining
structures shall comply with the requirements of IS : 3370 (Part I )-1965*.
3. DESIGN
3.1 General - Provisions shall be made for all conditions of stresses that
may occur in accordance with the principles of mechanics; recognised
methods of design and sound engineering practice. In particular, adequate
consideration shall be given to the effects of monolithic construction in the
assessment of bending moments and shear.
3.1.1 Before taking up the detailed design the designer should satisfy
himself on the correct estimation of loads and on the adequate statical
equilibrium of the structure, particularly in regard to safety against over-
turning of overhanging members; in the latter case the general arrange-
ment should be such that statical equilibrium’ should be satisfied even
when the overturning moment is doubled.
3.2 Basis of Design
3.2.1 General basis of design shall be in line with the recommendations
of IS : 1343-19607 except where otherwise specified in this code. The
members other than those specified in 3.2.2 ghall.be designed in accordance
with the requirements of IS : 1343-1960t.
3.2.2 The design of members in contact with the liquid on any face or
enclosing the space above the liquid shall be based on consideration of
adequate resistance to cracking as well as adequate strength, and the
following basic requirements should also be satisfied:
a) The computed stresses in the concrete and in the steel shall not
exceed the permissible stresses given in 3.3 and 3.4, during
transfer, handling and construction, and under working loads.
*Code of practice for concrete structures for the storage d-liquids : Part I General
requirements. ‘I
tGode of practice for prestressed concrete.
5
ISt337O(Part III)..196o
W
4
4
4
Cracking of the liquid retaining face should be entirely avoided.
The liquid retaining face should be checked against cracking with
a load factor [that is the ratio ofthe total ( dead + live j load at
cracking to the total ( dead + live) working load ] of l-2.
In estimating the resistance to cracking, the stresses in any cross-
section should be calculated as for a homogeneous material,
making allowance for all losses in steel tension.
The ultimate load at failure ( dead + live ) should not be less than
twice the working ( dead + live ) load.
Where found necessary provision should be made by suitable joints
or otherwise to allow for elastic distortions of the structure during
the process of prestressing.
3.2.3 For cylindrical tanks, additional requirements as specified in 7.1
should also be satisfied.
3.3 Permissible Stresses in Concrete
3.3.1 The permissible stresses in the concrete due to prestressing
operations and working loads, and the modulus of elasticity of concrete
shall be as specified in IS : 1343-1960*.
3.3.2 For estimation of resistance to cracking, the limiting tensile
strength of concrete shall be assumed to have the values specified in
Table 1.
TAB& 1 LIMFIZNG TENSILE STRENGTH OF CONCRETE FOR RSTXMA-
TION OF RESIST~oETOmcRAZTOIN PRESTRESSED
MINIMUMWORK CUBE DIRECT TENSILE
L2ZEEZi~~2*
STRENI~TH
kg/=+
kg/cm*
(1) (2)
350 16
400 17
450 18
500 19
550 20
600 21
650 22
*Code of practicefor preatraredconcrete.
6
BENDINGTENSILE
STRENGTH
kg/cm2
(3)
32
34
36
38 .:
40
42 i
43 1
k-
E
IS:3370(Part III)-1967
3.4 Permissible Stresses in Steel
1
3.4.1 The permissible stresses in prestressing steel and the modulus of
elasticity of steel shall be as specified in IS : 1343-1960*.
3.4.2 Where circumferential wires or bars are tensioned by means of
jacks, the losses due to friction may be found by reducing the coefficient of
friction to 80 percent of that given in IS : 1343-1960*.
3.5 Shrinkage and Creep of Concrete -The provisions regarding
shrinkage and creep shall comply with the requirements of IS : 1343-1960*.
3.5.1 Where reservoirs are protected with an internal impermeable
lining, consideration should be given to the possibility of concrete
eventually drying out. Unless the engineer is satisfied that the lining has
sufficient crack-bridging properties, allowance for the increased effect of
drying shrinkage should be made .in the design.
3.6 Losses in Prestress -While assessing the stresses in concrete and
steel during tensioning operations and later in service, due regard shall be
paid to all losses and variations in stress resulting from creep of concrete
and steel, the shrinkage of concrete, the shortening of concrete at transfer,
friction and slip of anchorage. Requirements in this respect specified in
IS : 1343-1960* shall be complied with.
4. FLOORS
4.1 Provision of Movement Joints - Movement joints shall be provided
in accordance with 8 of IS : 3370 ( Part I )-1965t.
4.2 Floors of Tanks Resting on Ground - If the tank is resting directly
on ground, its floor may be constructed of concrete with the nominal per-
centage of reinforcement ( not less than 0.15 percent of gross cross-sectional
area of concrete ) provided that it is established that the ground will
carry the load without appreciable subsidence in any part and that the
concrete floor is cast in panels not more than 4.5 metres square with
contraction or expansion joints between: In such cases a screed layer of
concrete not less than 75 mm thick shall first be placed on the ground and
covered over with a sliding layer of bitumen paper or other suitable
material to destroy the bond between the screed and floor concrete.
4.2.1 Under normal circumstances the screed layer shall not be of grade
not leaner than Ml00 specified in Table 3 of IS: 456-1964$; where
*Codeofpracticeforprestrcsxd concrete.
tCode of p~~ticc for concretestructureafor the storageof liquidr : Part I General
rcquiremcntn.
JCodc ofpracticeforplainandreinforcedconcrete(scondrrpision).
7
ISr337O(Part III)-1967
injurious soils or aggressive water are expected, the screed layer shall be of
grade not leaner than Ml50 specified in Table 3 of IS : 456-1964* and if
necessary a sulphate resisting or other special cement should be used.
5. WALLS
5.1 Provision of Joints
5.1.1 Sliding Joints at the Base of the Wall - Where it is desired to. allow
the wall to expand or contract separately from the floor, or to prevent
moments at the base of the wall owing to its fixity with the floor, sliding
joints may be employed.
5.1.1.1 Considerations affecting the spacing of vertical movements
joints are discussed in-8 of IS : 3370 ( Part I )-19657. While the majority
of these joints may be of the partial or complete contraction type sufficient
joints of the expansion type should be provided to satisfy the requirements
of 8 of IS : 3370 ( Part I )-1965t.
5.2 Effect of Earth Pressure -When a reservoir wall is built in the
ground or has earth embanked against it, relief in bending moment due to
simultaneous action of water pressure inside the wall and earth pressure
outside the wall may be made, provided that:
a) there is no risk of slip in the embankment or fear of a reduction
in the earth pressure arising from shrinkage or other causes; and
b) the earth pressure allowed by way of relief in the bending
moment caused by internal water pressure should be the minimum
which can be relied upon under the most unfavourable conditions
possible, including those under which the reservoir is to be tested
for watertightness.
6. ROOFS
6.1 Provision of Movement Joints - To avoid the possibility of sym-
pathetic cracking, it is important to ensure that movement joints in the
roof correspond with those in walls, if roof and walls are monolithic. If
provision is made by means of a sliding joint for movement between the
roof and the wall, correspondence of joints is not so important.
6.2 Loading -’ Fixed covers of tanks should be designed for gravity loads,
such as the weight of roof slab, earth cover, if any, live loads, and
mechanical equipment. They ‘should also be designed for upward load if
the tank is subjected to internal gas pressure.
*Code of practice for plain and reinforcedconcrete ( secondrmisim ).
*Code of practice for concrete structures for the storage of liquids: Part I General
requirements.
8-
IS:337O(Part III)-1967
6.2.1 A superficial load sufficient to ensure safety with the unequal
intensity of loading which occurs during the placing of the earth cover
should be allowed for in designing roofs. The engineer should specify a
loading under these temporary conditions, which should not be exceeded.
In designing the roof, allowance should be made for the temporary
condition of some spans loaded and other spans unloaded, even though in
the final state the load may be small and evenly distributed.
6.2.2 In tanks having fixed or floating covers the gas pressure developed
above liquid surface shall be added to liquid pressure.
6.3 Watertightness - In case of tanks intended for the storage of water
for domestic purposes, the roof shall be made watertight. This may be
achieved by limiting the stresses as for the rest of the tank, or by the use
of a covering of waterproof membrane or similar other efficient means.
6.4 Protection Against Corrosion -Protective measures shall be pro-
vided to the underside of the roof to prevent it from corrosion due to
condensation, or alternatively, the underside of the roof shall be designed
as a liquid retaining face, particular care being taken that the stipulations
regarding minimum cover to reinforcement are adhered to.
7. CYLINDRICAL, TANKS
7.1 Stresses -- In the design of prestressed concrete cylindrical tanks, the
following stresses in steel and concrete after allowing for all losses should
be investigated and their values should be within the limits prescribed
in 3.3 and 3.4, except where otherwise specified below:
a>
b)
C>
4
4
Maximum tensile stress in hoop steel or longitudinal steel at
working load should not exceed the limits specified in 3.4.
The princi
P
al compressive stress in concrete should not exceed
one-third o the specified works cube strength.
The average shear stress on the gross cross-section of the concrete
should not exceed & of the specified works cube strength.
When the tank is full, there should be a compression in the
concrete at all points of at least 7 kg/cm2.
When the tank is empty, there should at no point be a tensile
stress greater than 10 kg/cm2. Where the tank is to be emptied
and filled at frequent intervals, or may be left empty for a
prolonged period, it is desirable to design the tank so-that there
is a residual compression when the tank is empty as well as when
full.
7.2 The base of the wall may be designed either fixed with the floor or as
sliding or hinged at the junction with the floor.
9
IS : 3370( Part III ) - 1967
72.1 Except in case of unyielding solid rocky sub-grade, care should be
taken to minimize the danger or local settlement. This can be done by
designing the floor as a thin membrane and by providing a foundation
ring under the wall.
7.3 When at the base of the wall, hinged or sliding conditions prevail:
a) any advantage offered by the restraining effects should be ignored,
and
b) the moments in the region of the wall base in the direction
parallel to axis of the tank ( usually vertical ) caused by the
restraining effects of prestressing at the wall base should be counted
for. Values given in tables in IS : 3370 ( Part IV )* may be helpful
to assess tliese moments.
7.4 The ring prestressing should be designed in all cases on the assumption
that the wall-foot is free to slide without frictional resistance. When the
foot of the wall is free to slide, a longitudinal moment should be assumed
on the basis of a restraint equal to one-half of that provided by a pinned
foot. In other cases the longitudinal moment should be assessed on the
actual degree of restraint tit the wall-foot.
7.5 Allowance should be made for the longitudinal moment induced by
the transverse stressing in the partially wound condition. The maximum
value of the flexural stress in the longitudinal section from this cause may
be assumed to be numerically equal to O-3times the ring compression stress.
7.6 Prestressing should be provided in the transverse and longitudinal
cross-section so as to contain these effects within the critical stresses
specified.
7.7 Prestressing wire may be placed outside the walls generally, provided
this is protected with pneumatic mortar to provide 40 mm cover over the
wire. In malignant atmospheres, such as in heavy industrial areas or near
the sea the cables should be placed inside the walls and grouted.
7.8 When the stressing of the prestressing wires is proposed to be carried
out with wires .in position, anchorages may advantageously be staggered
and placed at suitable points of the cylinder with a veiw to off setting the
heavy frictional lo&es.
7.9 The worst conditions of stresses resulting from the pressure of contained
liquid, surrounding pressure, if any, temperature, shrinkage, restraint
from roof, etc, should be considered.
7.10 Necessity of prestressing the cylinder wall in the direction of the axis
of the cylinder ( vertical ) should always be investigated.
*Code of practice for concrete structuresfor the storageof liquids: Part IV D&m
tables.
10
ISr3370(Part III).1967
f 7.11 Longitudinal prestressing may be replaced with a reinforced concrete
section satisfying the requirements of IS : 3370 ( Part II )-1965*.
8. DETAILING
8.1 Concrete Cover - The minimum cover to prestressing rods, wires or
cables, and to sheathings and spacers, if present, shall be 35 mm on the
liquid face.
8.1.1 For faces away from the liquid and for parts of structure not in
contact with the liquid, the cover shall conform to the requirements of
IS : 1343-1960t.
8.2 Spacing of Prestressing Steel - The requirements of IS : 1343;
1960-t shall be complied with.
9. WORKMANSHIP, INSPECTION AND TESTING
9.1 In addition to the requirements specified in IS : 3370 ( Part I )-1965$,
the requirements of IS : 1343-1960t shall be complied with.
*Code of practice for concrete structures for the storage of liquid : Part II Reinforced
concrete structures.
tCode of practice for prestressed concrete.
ICode of practice for concrete structures for the storage of liquids : Part I General
requirements.
Is: 337O(PartIII)-1967
(Continuedj-om page 2 )
Members Representing
PROF G. S. RAMASWAMY Stru~ct~e3ngineering Research Centre ( CSIR ),
Da S. SARKAR ( Ahmate)
SHRI T. N. S. RAO Gammon-India Ltd, Bombay
SHRI S. R. PINHEIRO (Al&mute)
SUET.RINTEND)WG ENGINEER, END CentraPPublic Works Department
CIRCLE
SHRI S. G. VAIDYA (Alternate j
SHRI J. M. TREHAN Roads Wing, Ministry of Transport
SHRI R. PZ SIKKA ( Alternate )
DR H. C. VISVESVARAYA Cement Research Institute of India, New Delhi
BUREAU OF INDIAN STANDARDS
He8dquerters :
Manak Bhavan, 9 Bahadur Shah Zafar Marg. NEW DELHI 110002
Telephones : 331 01 31 Telegrams : Manaksanstha
331 13 75 (Common to all Offices)
Regional Offices :
Central : Manak Bhavan, 9. Bahadur Shah Zafar Marg
NEW DELHI 110002
* Eastern : 1114 C.I.T. Scheme VII M.
V.I.P. Road, Maniktola, CALCUTTA 700054
Northern : SC0 445-446, Sector 35-C, CHANDIGARH 160036
Southern :
t W&tern
C.I.T. Campus, IV Cross Road, MADRAS 6001 I3
: Manakalava. E9 MIDC. Marol. Andheri (East).
t
BOMBAY’400093
Branch Offices :
‘Pushpak’, Nurmohamed Shaikh Marg. Khanpur, AHMADABAD 380001
Peenya Industrial Area, I st Stage, Bangalore-Tumkur Road,
BANGALORE 560058
Gangotri Complex, 5th Floor, Bhadbhada Road, T.T. Nagar, 55402l
BHOPAL 462003
Plot No. 82/83, Lewis Road, BHUBANESHWAR 751002 53627
Kalai Kathir Building, 6/48-A Avanasi Road, COIMBATORE 641037 267 05
Quality Marking Centre, N.H. IV, N.I.T., FARIDABAD 121001 -
Savitri Complex, I I6 G. T. Road, GHAZIABAD 201001 8-71 19 96
53/5 Ward No. 29. R.G. Barua Road, 5th Bv-lane. 331 77
G~~wAHAT~ 781003
5-8-560 L. N. Gupta Marg, ( Nampally Station Road )
HYDERABAD 500001
RI4 Yudhister Marg, C Scheme, JAIPUR 302005
117/418 B Sarvodaya Nagar, KANPUR 208005
Plot No. A-9, House No. 561/63. Sindhu Nagar. Kanpur Roaa.
LUCKNOW 226005
Patliputra Industrial Estate. PATNA 800013
District Industries Centre Complex. Bagh-e-Ali Maidan.
SRINAGAR 190011
T. C. NO. 14/142I, University P. 0.. Palayam.
THIRUVANANTHAPURAM 695034
Inspection Offices (With Sale Point) :
Pushpanjali. First Floor, 205-A West High Court Road.
Shankar Nagar Square, NAGPUR 440010
Institution of -Engineers (India) Building, 1332 Shivaji Nagar.
PUNE 411005
‘Sales Office Calcutta is at 5 Chowringhee Approach,
P. 0. Princep Street, CALCUTTA
t Sales Office is at Novelty Chambers, Grant Road, BOMBAY
3 Sales Office is at Unity Building, Narasimharaja Square,
BANGALORE
Telephone
I
331 01 31
3311375
37 86 62
21843
41 2916
6329295
26348
3949 55
231083
6 34 71
21 68 76
5 55 07
6 23 05
-
621 04
52 61 71 i.
5 24 35
27 68 00
896528
223971
AMENDMENTND. 1 OCTOBER 1981
TO
IS:3370(PartIII)-1967 CODE OF PRACTICE FOR
CONCRETE STRUCTURESFOR THE STDRAGE Df LfOUIDS
PART III PRESTRESSED CONCRETE STRUGTURE;
Alteration-----
(Paga 3, czaras 0.3) - Substitute the follqving
for the existing clauirc:
‘0.3 Although the provisions of this code cover ma.inlY
structures for the storage of liquids, the general
requirements given in Part I of this code raj
generally appl;ir to the design of reinforced concrete
and preatresscd concrete structures for the conreyance
or l+Jida, such as aqueducts and superpassages; the
other requlruscnts given in the code may also be
applied vith appropriate modifications.'
(@DC 2)
ReprographyUnit, BIS, New Delhi, India

More Related Content

What's hot

26678635 is-code-1343-for-pre-stressed-concrete
26678635 is-code-1343-for-pre-stressed-concrete26678635 is-code-1343-for-pre-stressed-concrete
26678635 is-code-1343-for-pre-stressed-concreteAlok Kumar
 
Is 1343 2012
Is 1343 2012Is 1343 2012
Is 1343 2012Jeevan Reddy
 
100 sadanand v. deshpande - 7344983 - clustered surface preparation for sil...
100   sadanand v. deshpande - 7344983 - clustered surface preparation for sil...100   sadanand v. deshpande - 7344983 - clustered surface preparation for sil...
100 sadanand v. deshpande - 7344983 - clustered surface preparation for sil...Mello_Patent_Registry
 
0505_GC2010_The_Upper_Cretaceous_Bad_Heart_Ooidal_Ironstones
0505_GC2010_The_Upper_Cretaceous_Bad_Heart_Ooidal_Ironstones0505_GC2010_The_Upper_Cretaceous_Bad_Heart_Ooidal_Ironstones
0505_GC2010_The_Upper_Cretaceous_Bad_Heart_Ooidal_Ironstonesjonsli
 
Crimson Publishers-Micro Structural Features Induced by Sheet Hydroforming of...
Crimson Publishers-Micro Structural Features Induced by Sheet Hydroforming of...Crimson Publishers-Micro Structural Features Induced by Sheet Hydroforming of...
Crimson Publishers-Micro Structural Features Induced by Sheet Hydroforming of...CrimsonPublishersRDMS
 

What's hot (14)

26678635 is-code-1343-for-pre-stressed-concrete
26678635 is-code-1343-for-pre-stressed-concrete26678635 is-code-1343-for-pre-stressed-concrete
26678635 is-code-1343-for-pre-stressed-concrete
 
2386 8
2386 82386 8
2386 8
 
2174
21742174
2174
 
Is 1343 2012
Is 1343 2012Is 1343 2012
Is 1343 2012
 
5820
58205820
5820
 
6512
65126512
6512
 
2386 2
2386 22386 2
2386 2
 
432 1
432 1432 1
432 1
 
2770 1
2770 12770 1
2770 1
 
2686
26862686
2686
 
100 sadanand v. deshpande - 7344983 - clustered surface preparation for sil...
100   sadanand v. deshpande - 7344983 - clustered surface preparation for sil...100   sadanand v. deshpande - 7344983 - clustered surface preparation for sil...
100 sadanand v. deshpande - 7344983 - clustered surface preparation for sil...
 
Is 875 wind load
Is 875   wind loadIs 875   wind load
Is 875 wind load
 
0505_GC2010_The_Upper_Cretaceous_Bad_Heart_Ooidal_Ironstones
0505_GC2010_The_Upper_Cretaceous_Bad_Heart_Ooidal_Ironstones0505_GC2010_The_Upper_Cretaceous_Bad_Heart_Ooidal_Ironstones
0505_GC2010_The_Upper_Cretaceous_Bad_Heart_Ooidal_Ironstones
 
Crimson Publishers-Micro Structural Features Induced by Sheet Hydroforming of...
Crimson Publishers-Micro Structural Features Induced by Sheet Hydroforming of...Crimson Publishers-Micro Structural Features Induced by Sheet Hydroforming of...
Crimson Publishers-Micro Structural Features Induced by Sheet Hydroforming of...
 

Viewers also liked (19)

3808
38083808
3808
 
1200 8
1200 81200 8
1200 8
 
3085
30853085
3085
 
1200 3
1200 31200 3
1200 3
 
2541
25412541
2541
 
2395 1
2395 12395 1
2395 1
 
2090
20902090
2090
 
1916
19161916
1916
 
432 2
432 2432 2
432 2
 
2571
25712571
2571
 
2905
29052905
2905
 
1200 10
1200 101200 10
1200 10
 
2911 3
2911 32911 3
2911 3
 
2911 2
2911 22911 2
2911 2
 
3873
38733873
3873
 
1200 15
1200 151200 15
1200 15
 
2542 2 1
2542 2 12542 2 1
2542 2 1
 
800
800800
800
 
4090
40904090
4090
 

Similar to 3370 3 (20)

6041
60416041
6041
 
383.pdf
383.pdf383.pdf
383.pdf
 
2386 4
2386 42386 4
2386 4
 
2911 1 2
2911 1 22911 1 2
2911 1 2
 
2386 3
2386 32386 3
2386 3
 
6461 9
6461 96461 9
6461 9
 
1343
13431343
1343
 
6509
65096509
6509
 
2386 1
2386 12386 1
2386 1
 
783
783783
783
 
2185 1
2185 12185 1
2185 1
 
6923
69236923
6923
 
5751
57515751
5751
 
4996
49964996
4996
 
516
516516
516
 
2506
25062506
2506
 
2572
25722572
2572
 
6523
65236523
6523
 
1332
13321332
1332
 
2502
25022502
2502
 

More from Boopathi Yoganathan (20)

28-5.21 Company Profile of Pyrmaid structural consultant.pptx
28-5.21 Company Profile of Pyrmaid structural consultant.pptx28-5.21 Company Profile of Pyrmaid structural consultant.pptx
28-5.21 Company Profile of Pyrmaid structural consultant.pptx
 
Front page upto content new
Front page upto content newFront page upto content new
Front page upto content new
 
Book report new
Book report newBook report new
Book report new
 
Fem
FemFem
Fem
 
Exopy injection
Exopy injectionExopy injection
Exopy injection
 
Embedded
EmbeddedEmbedded
Embedded
 
Earthquakes seminar
Earthquakes seminarEarthquakes seminar
Earthquakes seminar
 
10334
1033410334
10334
 
10302
1030210302
10302
 
10297
1029710297
10297
 
9527 1
9527 19527 1
9527 1
 
9459
94599459
9459
 
9456
94569456
9456
 
9429
94299429
9429
 
9417
94179417
9417
 
7873
78737873
7873
 
7563
75637563
7563
 
7500
75007500
7500
 
7436 2
7436 27436 2
7436 2
 
7436 1
7436 17436 1
7436 1
 

Recently uploaded

Choosing the Right CBSE School A Comprehensive Guide for Parents
Choosing the Right CBSE School A Comprehensive Guide for ParentsChoosing the Right CBSE School A Comprehensive Guide for Parents
Choosing the Right CBSE School A Comprehensive Guide for Parentsnavabharathschool99
 
Visit to a blind student's school🧑‍🩯🧑‍🩯(community medicine)
Visit to a blind student's school🧑‍🩯🧑‍🩯(community medicine)Visit to a blind student's school🧑‍🩯🧑‍🩯(community medicine)
Visit to a blind student's school🧑‍🩯🧑‍🩯(community medicine)lakshayb543
 
Gas measurement O2,Co2,& ph) 04/2024.pptx
Gas measurement O2,Co2,& ph) 04/2024.pptxGas measurement O2,Co2,& ph) 04/2024.pptx
Gas measurement O2,Co2,& ph) 04/2024.pptxDr.Ibrahim Hassaan
 
How to do quick user assign in kanban in Odoo 17 ERP
How to do quick user assign in kanban in Odoo 17 ERPHow to do quick user assign in kanban in Odoo 17 ERP
How to do quick user assign in kanban in Odoo 17 ERPCeline George
 
Proudly South Africa powerpoint Thorisha.pptx
Proudly South Africa powerpoint Thorisha.pptxProudly South Africa powerpoint Thorisha.pptx
Proudly South Africa powerpoint Thorisha.pptxthorishapillay1
 
Difference Between Search & Browse Methods in Odoo 17
Difference Between Search & Browse Methods in Odoo 17Difference Between Search & Browse Methods in Odoo 17
Difference Between Search & Browse Methods in Odoo 17Celine George
 
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptx
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptxINTRODUCTION TO CATHOLIC CHRISTOLOGY.pptx
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptxHumphrey A Beña
 
What is Model Inheritance in Odoo 17 ERP
What is Model Inheritance in Odoo 17 ERPWhat is Model Inheritance in Odoo 17 ERP
What is Model Inheritance in Odoo 17 ERPCeline George
 
MULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptx
MULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptxMULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptx
MULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptxAnupkumar Sharma
 
Field Attribute Index Feature in Odoo 17
Field Attribute Index Feature in Odoo 17Field Attribute Index Feature in Odoo 17
Field Attribute Index Feature in Odoo 17Celine George
 
AMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdf
AMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdfAMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdf
AMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdfphamnguyenenglishnb
 
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdfLike-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdfMr Bounab Samir
 
ISYU TUNGKOL SA SEKSWLADIDA (ISSUE ABOUT SEXUALITY
ISYU TUNGKOL SA SEKSWLADIDA (ISSUE ABOUT SEXUALITYISYU TUNGKOL SA SEKSWLADIDA (ISSUE ABOUT SEXUALITY
ISYU TUNGKOL SA SEKSWLADIDA (ISSUE ABOUT SEXUALITYKayeClaireEstoconing
 
ACC 2024 Chronicles. Cardiology. Exam.pdf
ACC 2024 Chronicles. Cardiology. Exam.pdfACC 2024 Chronicles. Cardiology. Exam.pdf
ACC 2024 Chronicles. Cardiology. Exam.pdfSpandanaRallapalli
 

Recently uploaded (20)

LEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptx
LEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptxLEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptx
LEFT_ON_C'N_ PRELIMS_EL_DORADO_2024.pptx
 
Choosing the Right CBSE School A Comprehensive Guide for Parents
Choosing the Right CBSE School A Comprehensive Guide for ParentsChoosing the Right CBSE School A Comprehensive Guide for Parents
Choosing the Right CBSE School A Comprehensive Guide for Parents
 
YOUVE_GOT_EMAIL_PRELIMS_EL_DORADO_2024.pptx
YOUVE_GOT_EMAIL_PRELIMS_EL_DORADO_2024.pptxYOUVE_GOT_EMAIL_PRELIMS_EL_DORADO_2024.pptx
YOUVE_GOT_EMAIL_PRELIMS_EL_DORADO_2024.pptx
 
Visit to a blind student's school🧑‍🩯🧑‍🩯(community medicine)
Visit to a blind student's school🧑‍🩯🧑‍🩯(community medicine)Visit to a blind student's school🧑‍🩯🧑‍🩯(community medicine)
Visit to a blind student's school🧑‍🩯🧑‍🩯(community medicine)
 
TataKelola dan KamSiber Kecerdasan Buatan v022.pdf
TataKelola dan KamSiber Kecerdasan Buatan v022.pdfTataKelola dan KamSiber Kecerdasan Buatan v022.pdf
TataKelola dan KamSiber Kecerdasan Buatan v022.pdf
 
Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝
 
Gas measurement O2,Co2,& ph) 04/2024.pptx
Gas measurement O2,Co2,& ph) 04/2024.pptxGas measurement O2,Co2,& ph) 04/2024.pptx
Gas measurement O2,Co2,& ph) 04/2024.pptx
 
How to do quick user assign in kanban in Odoo 17 ERP
How to do quick user assign in kanban in Odoo 17 ERPHow to do quick user assign in kanban in Odoo 17 ERP
How to do quick user assign in kanban in Odoo 17 ERP
 
Proudly South Africa powerpoint Thorisha.pptx
Proudly South Africa powerpoint Thorisha.pptxProudly South Africa powerpoint Thorisha.pptx
Proudly South Africa powerpoint Thorisha.pptx
 
Difference Between Search & Browse Methods in Odoo 17
Difference Between Search & Browse Methods in Odoo 17Difference Between Search & Browse Methods in Odoo 17
Difference Between Search & Browse Methods in Odoo 17
 
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptx
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptxINTRODUCTION TO CATHOLIC CHRISTOLOGY.pptx
INTRODUCTION TO CATHOLIC CHRISTOLOGY.pptx
 
What is Model Inheritance in Odoo 17 ERP
What is Model Inheritance in Odoo 17 ERPWhat is Model Inheritance in Odoo 17 ERP
What is Model Inheritance in Odoo 17 ERP
 
OS-operating systems- ch04 (Threads) ...
OS-operating systems- ch04 (Threads) ...OS-operating systems- ch04 (Threads) ...
OS-operating systems- ch04 (Threads) ...
 
Raw materials used in Herbal Cosmetics.pptx
Raw materials used in Herbal Cosmetics.pptxRaw materials used in Herbal Cosmetics.pptx
Raw materials used in Herbal Cosmetics.pptx
 
MULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptx
MULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptxMULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptx
MULTIDISCIPLINRY NATURE OF THE ENVIRONMENTAL STUDIES.pptx
 
Field Attribute Index Feature in Odoo 17
Field Attribute Index Feature in Odoo 17Field Attribute Index Feature in Odoo 17
Field Attribute Index Feature in Odoo 17
 
AMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdf
AMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdfAMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdf
AMERICAN LANGUAGE HUB_Level2_Student'sBook_Answerkey.pdf
 
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdfLike-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
Like-prefer-love -hate+verb+ing & silent letters & citizenship text.pdf
 
ISYU TUNGKOL SA SEKSWLADIDA (ISSUE ABOUT SEXUALITY
ISYU TUNGKOL SA SEKSWLADIDA (ISSUE ABOUT SEXUALITYISYU TUNGKOL SA SEKSWLADIDA (ISSUE ABOUT SEXUALITY
ISYU TUNGKOL SA SEKSWLADIDA (ISSUE ABOUT SEXUALITY
 
ACC 2024 Chronicles. Cardiology. Exam.pdf
ACC 2024 Chronicles. Cardiology. Exam.pdfACC 2024 Chronicles. Cardiology. Exam.pdf
ACC 2024 Chronicles. Cardiology. Exam.pdf
 

3370 3

  • 1. T ISr3370(PartlII)-1967 Indian Standard ( Reaffirmcd lggl ) CODE OF PRACTICE FOR CONCRETE STRUCTURES FOR THE STORAGE, OF LIQUIDS PART III PRESTRESSED CONCRETE STRUCTURES ( Ninth Reprint APRIL 1992 ) UDC 621.642.3:624.953:666,984 @ICopyright 1968 BUREAU OF IN.DIAN STANDARDS MANAK BHAVAN. 9 BAHADUR SHAH ZAFAR MAR0 NBWDELllIIlOOOZ Gr 3 January 1968 ( Reaffirmed 1999 )
  • 2. IS : 3370( Part III ) - 1967 Indian Standard CODE OF PRACTICE FOR CONCRETE STRUCTURES FOR THE STORAGE OF LIQUIDS PART III PRESTRESSED CONCRETE STRUCTURES Cement and Concrete Sedtional Committee, BDC 2 Chairman Re@senting SHRI K. K. NAMBIAR The Concrete Association of India, Bombay Members Sam M. A. MEHTA ( Alternate to Shri K. K. Nambiar ) SHRI K.F. ANTIA M.N. Dastur & Co ( Pvt ) Ltd, Calcutta SHRI A. P. BA~CHI Sahu Cement Service, New Delhi SHRI P. S. BHATNA~AR DR S. K. CHOPRA Bhakra & Beas Designs Organization! New Delhi ~Central Building Research Instttute ( CSIR ), Roorkee SHRIJ. S. SHARMA (Alternate) DIRECTOR( CSM ) Central Water & Power Commission DIRECTOR( DAMSIII ) ( Alkvnate 1 DR R. K. GHOSH SHRI B. K. GUHA SUPERINTENDWO ENGINEER, 2nd CIRCLE( .Altemate ) DR R. R. HATTIANGADI SHRI ~;,“,J~; ( Akvnatc ) JOINT STANDARDS (B&S) DEPIJTYDIRECTORSTANDARDS (B&S) (Alternate) SHRt S. B. Josm PROF S. R. ME~RA -Indian Roads Congress, New Delhi Central Public Works Department, New Delhi DR R. K. GHOSH( Alternate ) SHRI S. N. MUKERJI National Test House, Calcutta SHRI E. K. RAMCWANDRAN( Alternate ) SHRI ERACH A. NADIRSHAH Institution of Engineers ( India ), Calcutta BRIGNARESH PRA~AD Engineer-in-Chief’s Branch, Army Headquarters SHRI C. B. PATEL National Buildings Organization SHRIRABINDERSINGH( Alternate ) SWRII. L. PATEL Directorate General of Supplies & Disposals SHRl T. N. S. RAO Gammon India Ltd, Bombay SIIRI S. R. PINHEIRO(Alternate) ( Continued on page 2 ) The Associated Cement Companies Ltd, Bombay Research, . Designs & Standards Organization ( Ministry of Railways ) S.B. Joshi & Co Ltd, Bombay Cent;talhyd Research Institute ( CSIR ), New BUREAU OF INDIAN STANDARDS bl.ANAK BIIAVAN, 9 RAHADUR SHAH ZAFAR MARG NEW DILHI 110002
  • 3. ISr337O(Part III)-1967 ( conrt2wdffm pugs1) Members ~PRESENTATIVE REPRESENTATIVE SHRI K. G. SALVI Rcplczating Geological Survey of India, Calcutta The India Cements Ltd, Madras SI-IRI c. L. &WJWAL ( Alternate) Hindustan Housing Factory Ltd, New Delhi ]3R s. SARKAR SHRI Z. GEORGE ( Altarnate ) Struct~o~k&neering Research Centre ( CSIR ), SECriETARY Central Board of Irrigation & Power, New Delhi SIiRl L. SWAROOP SHRI A. V. RAMANA(Alternate) Dalmia Cement ( Bharat ) Ltd, New Delhi SHRI J. -2. TREHAN SHRI N. H. KESWANI ( Alternate) Roads Wing, Ministry of Transport DR H. C. VISVESVARAYA Cement Research Institute of India, New Delhi SHRSR. NAOARAJAN, Director ( Civ Engg ) Director General, ISI ( Ex-oficio Member ) Secretary SHRIY. R. TANEJA Deputy Director ( Civ Engg ), IS1 Concrete Subcommittee, BDC 2 : 2 Convener Sxnt S. B. JOSHI S.B. Joshi & Co Ltd, Bombay Members SHRI B. D. AHUJA SHRI P. C. JAIN ( Alternate) National Buildings Organization SHRI K. F. ANTIA SHRI B, C. PATEL ( Alternate) M.N. Dastur & Co ( Pvt) Ltd, Calcutta SHRI A. P. BACXXI Sahu Cement Service, New Delhi SHRI B. K. CHOKSI In personal capacity ( M60 Cusrow Bag, Bombay ) DR S. K. C~OPRA Central Building Research Institute ( CSIR ), Roorkee - DR I. C. Dos M. PAIS CUDDOU Central Water 82 Power Commission DIRECTOR.( DAMSI ) ( Alternate ) DEPU~ DIRECTOR STANDARM Research, Designs and Standards Organization (B&S) ( Ministry of Railways ) ASSISTANTDIRECTOR STAND ARDS(B&S) (Altematc) DIRECTOR * ’ . Hyderabad Engineering Research Laboratory, Hyderabad DIRECTOR-IN-CHARGE SHRIV. N. GUNAJI SHRI V. K. GUPTA SHRI K. K. NAMBIAR SHRI C. L. N. IYENGAR DR M. L. PURI Geological Survey of India, Lucknow Public Works Department, Maharashtra Engineer-in-Chief’s Branch, Army Headquarters The Concrete Association of India, Bombay ( Alternate ) Centr$hXoad Research Institute ( CSIR), New ( Continuedonhuge 12 ) 2 i-
  • 4. IS : 3370 ( Part III ) - 1967 Indian Standard CODE OF PRACTICE FOR CONCRETE STRUCTURES FOR THE STORAGE OF LIQUIDS PART III PRESTRESSED CONCRETE STRUCTURES 0. FOREWORD 0.1 This Indian Standard was adopted by the Indian Standards Institu- tion on 20 October 1967, after the draft finahzed by the Cement and Concrete Sectional Committee had been approved by the Civil Engincer- ing Division Council. 0.2 The need for a code covering the design and construction of reinforced concrete and prestressed concrete structures for the storage of liquids has been long felt in this country. So far engineers, designers and builders in this country have been adapting mainly the recommendations of the Institution of Civil Engineers, London, and more recently some of the recommendations of the Portland Cement Association. The conditions in this country, however, differ in many ways from those prevailing in UK and USA; for instance, climatic and weather conditions are sub,jccted generally to larger variations, matLrials for concrete differ considerably in their physical properties and the prevailing practices in construction have special influence on the,methods of use of reinforced and prestrcs;ed co*>- Crete. The need was, therefore, felt to give clue consideration to these factors in the practices followed in the country with a view to fully satisf! ~ng the functional requirements of structures for the storage of liquids. In order to fulfil this need, formulation of ‘ Indian Standard code of practice for concrete structures for the storage of liquids’ was undertaken which is being issued in parts. This part [ IS : 3370 ( Part III )-1967 ] deals with prestressed concrete structures. The other parts of the code are the following: Part I General requirements Part II Reinforced concrete structures Part IV Design tables 0.3 Although the provisions of this standard cover mainly structures for the storage of liquids, the general provisions of this code may also be applied, with such modifications as found necessary, to suit the special conditions in the design of reinforced concrete and prestressed concrete, structures for the conveyance of liquids, such as aqueducts and super- passages. 3
  • 5. IS : 3370 ( Part III ) - 1967 0.4 While the common methods of design and construction have been covered in this code, design of structures of special forms or under unusual circumstances should be left to the judgment of the engineer and in such cases special systems of design and construction may be permitted on production of satisfactory evidence regarding their adequacy and safety by analysis or test or both. 0.5 In this standard it has been assumed that the design of prestressed concrete liquid retaining structures is entrusted to a qualified engineer and that the execution of the work is carried out under the direction of an experienced supervisor. 0.6 All requirements of IS : 456-1964” and IS : 1343-1960t in so far as they apply, shall be deemed to form part of this code except where other- wise laid down in this code. 0.7 The Sectional Committee responsible for the preparation .of this standard has taken into consideration the views of engineers, and techno- logists and has related the standard to the practices followed in the country in this field. Due weightage has also been given to the need for inter- national co-ordination between the standards prevailing in different countries of the world. These considerations led the Sectional Committee to derive assistance from published materials of the following organiza- tions: British Standards Institution Portland Cement Association, Chicago, USA Institution of Civil Engineers, London. 0.8 For the purpose of deciding whether a particular requirement of this standard is complied with, the final value, observed or calculated, express- ing the result of a test or analysis, shall be rounded off in accordance with IS : 2-1960$. The number of significant places retained in the rounded off value should be the same as that of the specified value in this standard. 1. SCOPE 1.1 This standard (Part III ) lays down the requirements applicable specifically to the prestressed concrete structures for the storage of liquids, mainly water. These requirements are in addition to the general requirements laid down in IS : 3370 ( Part I )-1965s. *Code of practicefor plain and reinforced concrete ( secondrevision ). tCode of practice for prestressed concrete. SRules for rounding off numerical valua( r&d ). $Code of practice for concrete structures for the storage of liquids: Part I General requirements. 4 f c
  • 6. IS:337O(Part III)-1967 1.2 This code does not cover the requirements for reinforced and pre- stressed concrete structures for storage of hot liquids and liquids of low viscosity and high penetrating power lie petrol, diesel oil, etc. Special problems of shrinkage arising in the storage of non-aqueous liquids and the measures necessary where chemical attack is possible, are also not dealt with. The recommendations, however, may generally be applicable to the storage at normal temperatures of aqueous liquids and solutions which have no detrimental action on concrete and steel or where sufficient precautions are taken to ensure protection of concrete and steel from damage due to action of such liquids as in the case of sewage. 2. GENERAL REQ-MENTS 2.1 Design and construction of prestressed concrete liquid retaining structures shall comply with the requirements of IS : 3370 (Part I )-1965*. 3. DESIGN 3.1 General - Provisions shall be made for all conditions of stresses that may occur in accordance with the principles of mechanics; recognised methods of design and sound engineering practice. In particular, adequate consideration shall be given to the effects of monolithic construction in the assessment of bending moments and shear. 3.1.1 Before taking up the detailed design the designer should satisfy himself on the correct estimation of loads and on the adequate statical equilibrium of the structure, particularly in regard to safety against over- turning of overhanging members; in the latter case the general arrange- ment should be such that statical equilibrium’ should be satisfied even when the overturning moment is doubled. 3.2 Basis of Design 3.2.1 General basis of design shall be in line with the recommendations of IS : 1343-19607 except where otherwise specified in this code. The members other than those specified in 3.2.2 ghall.be designed in accordance with the requirements of IS : 1343-1960t. 3.2.2 The design of members in contact with the liquid on any face or enclosing the space above the liquid shall be based on consideration of adequate resistance to cracking as well as adequate strength, and the following basic requirements should also be satisfied: a) The computed stresses in the concrete and in the steel shall not exceed the permissible stresses given in 3.3 and 3.4, during transfer, handling and construction, and under working loads. *Code of practice for concrete structures for the storage d-liquids : Part I General requirements. ‘I tGode of practice for prestressed concrete. 5
  • 7. ISt337O(Part III)..196o W 4 4 4 Cracking of the liquid retaining face should be entirely avoided. The liquid retaining face should be checked against cracking with a load factor [that is the ratio ofthe total ( dead + live j load at cracking to the total ( dead + live) working load ] of l-2. In estimating the resistance to cracking, the stresses in any cross- section should be calculated as for a homogeneous material, making allowance for all losses in steel tension. The ultimate load at failure ( dead + live ) should not be less than twice the working ( dead + live ) load. Where found necessary provision should be made by suitable joints or otherwise to allow for elastic distortions of the structure during the process of prestressing. 3.2.3 For cylindrical tanks, additional requirements as specified in 7.1 should also be satisfied. 3.3 Permissible Stresses in Concrete 3.3.1 The permissible stresses in the concrete due to prestressing operations and working loads, and the modulus of elasticity of concrete shall be as specified in IS : 1343-1960*. 3.3.2 For estimation of resistance to cracking, the limiting tensile strength of concrete shall be assumed to have the values specified in Table 1. TAB& 1 LIMFIZNG TENSILE STRENGTH OF CONCRETE FOR RSTXMA- TION OF RESIST~oETOmcRAZTOIN PRESTRESSED MINIMUMWORK CUBE DIRECT TENSILE L2ZEEZi~~2* STRENI~TH kg/=+ kg/cm* (1) (2) 350 16 400 17 450 18 500 19 550 20 600 21 650 22 *Code of practicefor preatraredconcrete. 6 BENDINGTENSILE STRENGTH kg/cm2 (3) 32 34 36 38 .: 40 42 i 43 1 k- E
  • 8. IS:3370(Part III)-1967 3.4 Permissible Stresses in Steel 1 3.4.1 The permissible stresses in prestressing steel and the modulus of elasticity of steel shall be as specified in IS : 1343-1960*. 3.4.2 Where circumferential wires or bars are tensioned by means of jacks, the losses due to friction may be found by reducing the coefficient of friction to 80 percent of that given in IS : 1343-1960*. 3.5 Shrinkage and Creep of Concrete -The provisions regarding shrinkage and creep shall comply with the requirements of IS : 1343-1960*. 3.5.1 Where reservoirs are protected with an internal impermeable lining, consideration should be given to the possibility of concrete eventually drying out. Unless the engineer is satisfied that the lining has sufficient crack-bridging properties, allowance for the increased effect of drying shrinkage should be made .in the design. 3.6 Losses in Prestress -While assessing the stresses in concrete and steel during tensioning operations and later in service, due regard shall be paid to all losses and variations in stress resulting from creep of concrete and steel, the shrinkage of concrete, the shortening of concrete at transfer, friction and slip of anchorage. Requirements in this respect specified in IS : 1343-1960* shall be complied with. 4. FLOORS 4.1 Provision of Movement Joints - Movement joints shall be provided in accordance with 8 of IS : 3370 ( Part I )-1965t. 4.2 Floors of Tanks Resting on Ground - If the tank is resting directly on ground, its floor may be constructed of concrete with the nominal per- centage of reinforcement ( not less than 0.15 percent of gross cross-sectional area of concrete ) provided that it is established that the ground will carry the load without appreciable subsidence in any part and that the concrete floor is cast in panels not more than 4.5 metres square with contraction or expansion joints between: In such cases a screed layer of concrete not less than 75 mm thick shall first be placed on the ground and covered over with a sliding layer of bitumen paper or other suitable material to destroy the bond between the screed and floor concrete. 4.2.1 Under normal circumstances the screed layer shall not be of grade not leaner than Ml00 specified in Table 3 of IS: 456-1964$; where *Codeofpracticeforprestrcsxd concrete. tCode of p~~ticc for concretestructureafor the storageof liquidr : Part I General rcquiremcntn. JCodc ofpracticeforplainandreinforcedconcrete(scondrrpision). 7
  • 9. ISr337O(Part III)-1967 injurious soils or aggressive water are expected, the screed layer shall be of grade not leaner than Ml50 specified in Table 3 of IS : 456-1964* and if necessary a sulphate resisting or other special cement should be used. 5. WALLS 5.1 Provision of Joints 5.1.1 Sliding Joints at the Base of the Wall - Where it is desired to. allow the wall to expand or contract separately from the floor, or to prevent moments at the base of the wall owing to its fixity with the floor, sliding joints may be employed. 5.1.1.1 Considerations affecting the spacing of vertical movements joints are discussed in-8 of IS : 3370 ( Part I )-19657. While the majority of these joints may be of the partial or complete contraction type sufficient joints of the expansion type should be provided to satisfy the requirements of 8 of IS : 3370 ( Part I )-1965t. 5.2 Effect of Earth Pressure -When a reservoir wall is built in the ground or has earth embanked against it, relief in bending moment due to simultaneous action of water pressure inside the wall and earth pressure outside the wall may be made, provided that: a) there is no risk of slip in the embankment or fear of a reduction in the earth pressure arising from shrinkage or other causes; and b) the earth pressure allowed by way of relief in the bending moment caused by internal water pressure should be the minimum which can be relied upon under the most unfavourable conditions possible, including those under which the reservoir is to be tested for watertightness. 6. ROOFS 6.1 Provision of Movement Joints - To avoid the possibility of sym- pathetic cracking, it is important to ensure that movement joints in the roof correspond with those in walls, if roof and walls are monolithic. If provision is made by means of a sliding joint for movement between the roof and the wall, correspondence of joints is not so important. 6.2 Loading -’ Fixed covers of tanks should be designed for gravity loads, such as the weight of roof slab, earth cover, if any, live loads, and mechanical equipment. They ‘should also be designed for upward load if the tank is subjected to internal gas pressure. *Code of practice for plain and reinforcedconcrete ( secondrmisim ). *Code of practice for concrete structures for the storage of liquids: Part I General requirements. 8-
  • 10. IS:337O(Part III)-1967 6.2.1 A superficial load sufficient to ensure safety with the unequal intensity of loading which occurs during the placing of the earth cover should be allowed for in designing roofs. The engineer should specify a loading under these temporary conditions, which should not be exceeded. In designing the roof, allowance should be made for the temporary condition of some spans loaded and other spans unloaded, even though in the final state the load may be small and evenly distributed. 6.2.2 In tanks having fixed or floating covers the gas pressure developed above liquid surface shall be added to liquid pressure. 6.3 Watertightness - In case of tanks intended for the storage of water for domestic purposes, the roof shall be made watertight. This may be achieved by limiting the stresses as for the rest of the tank, or by the use of a covering of waterproof membrane or similar other efficient means. 6.4 Protection Against Corrosion -Protective measures shall be pro- vided to the underside of the roof to prevent it from corrosion due to condensation, or alternatively, the underside of the roof shall be designed as a liquid retaining face, particular care being taken that the stipulations regarding minimum cover to reinforcement are adhered to. 7. CYLINDRICAL, TANKS 7.1 Stresses -- In the design of prestressed concrete cylindrical tanks, the following stresses in steel and concrete after allowing for all losses should be investigated and their values should be within the limits prescribed in 3.3 and 3.4, except where otherwise specified below: a> b) C> 4 4 Maximum tensile stress in hoop steel or longitudinal steel at working load should not exceed the limits specified in 3.4. The princi P al compressive stress in concrete should not exceed one-third o the specified works cube strength. The average shear stress on the gross cross-section of the concrete should not exceed & of the specified works cube strength. When the tank is full, there should be a compression in the concrete at all points of at least 7 kg/cm2. When the tank is empty, there should at no point be a tensile stress greater than 10 kg/cm2. Where the tank is to be emptied and filled at frequent intervals, or may be left empty for a prolonged period, it is desirable to design the tank so-that there is a residual compression when the tank is empty as well as when full. 7.2 The base of the wall may be designed either fixed with the floor or as sliding or hinged at the junction with the floor. 9
  • 11. IS : 3370( Part III ) - 1967 72.1 Except in case of unyielding solid rocky sub-grade, care should be taken to minimize the danger or local settlement. This can be done by designing the floor as a thin membrane and by providing a foundation ring under the wall. 7.3 When at the base of the wall, hinged or sliding conditions prevail: a) any advantage offered by the restraining effects should be ignored, and b) the moments in the region of the wall base in the direction parallel to axis of the tank ( usually vertical ) caused by the restraining effects of prestressing at the wall base should be counted for. Values given in tables in IS : 3370 ( Part IV )* may be helpful to assess tliese moments. 7.4 The ring prestressing should be designed in all cases on the assumption that the wall-foot is free to slide without frictional resistance. When the foot of the wall is free to slide, a longitudinal moment should be assumed on the basis of a restraint equal to one-half of that provided by a pinned foot. In other cases the longitudinal moment should be assessed on the actual degree of restraint tit the wall-foot. 7.5 Allowance should be made for the longitudinal moment induced by the transverse stressing in the partially wound condition. The maximum value of the flexural stress in the longitudinal section from this cause may be assumed to be numerically equal to O-3times the ring compression stress. 7.6 Prestressing should be provided in the transverse and longitudinal cross-section so as to contain these effects within the critical stresses specified. 7.7 Prestressing wire may be placed outside the walls generally, provided this is protected with pneumatic mortar to provide 40 mm cover over the wire. In malignant atmospheres, such as in heavy industrial areas or near the sea the cables should be placed inside the walls and grouted. 7.8 When the stressing of the prestressing wires is proposed to be carried out with wires .in position, anchorages may advantageously be staggered and placed at suitable points of the cylinder with a veiw to off setting the heavy frictional lo&es. 7.9 The worst conditions of stresses resulting from the pressure of contained liquid, surrounding pressure, if any, temperature, shrinkage, restraint from roof, etc, should be considered. 7.10 Necessity of prestressing the cylinder wall in the direction of the axis of the cylinder ( vertical ) should always be investigated. *Code of practice for concrete structuresfor the storageof liquids: Part IV D&m tables. 10
  • 12. ISr3370(Part III).1967 f 7.11 Longitudinal prestressing may be replaced with a reinforced concrete section satisfying the requirements of IS : 3370 ( Part II )-1965*. 8. DETAILING 8.1 Concrete Cover - The minimum cover to prestressing rods, wires or cables, and to sheathings and spacers, if present, shall be 35 mm on the liquid face. 8.1.1 For faces away from the liquid and for parts of structure not in contact with the liquid, the cover shall conform to the requirements of IS : 1343-1960t. 8.2 Spacing of Prestressing Steel - The requirements of IS : 1343; 1960-t shall be complied with. 9. WORKMANSHIP, INSPECTION AND TESTING 9.1 In addition to the requirements specified in IS : 3370 ( Part I )-1965$, the requirements of IS : 1343-1960t shall be complied with. *Code of practice for concrete structures for the storage of liquid : Part II Reinforced concrete structures. tCode of practice for prestressed concrete. ICode of practice for concrete structures for the storage of liquids : Part I General requirements.
  • 13. Is: 337O(PartIII)-1967 (Continuedj-om page 2 ) Members Representing PROF G. S. RAMASWAMY Stru~ct~e3ngineering Research Centre ( CSIR ), Da S. SARKAR ( Ahmate) SHRI T. N. S. RAO Gammon-India Ltd, Bombay SHRI S. R. PINHEIRO (Al&mute) SUET.RINTEND)WG ENGINEER, END CentraPPublic Works Department CIRCLE SHRI S. G. VAIDYA (Alternate j SHRI J. M. TREHAN Roads Wing, Ministry of Transport SHRI R. PZ SIKKA ( Alternate ) DR H. C. VISVESVARAYA Cement Research Institute of India, New Delhi
  • 14. BUREAU OF INDIAN STANDARDS He8dquerters : Manak Bhavan, 9 Bahadur Shah Zafar Marg. NEW DELHI 110002 Telephones : 331 01 31 Telegrams : Manaksanstha 331 13 75 (Common to all Offices) Regional Offices : Central : Manak Bhavan, 9. Bahadur Shah Zafar Marg NEW DELHI 110002 * Eastern : 1114 C.I.T. Scheme VII M. V.I.P. Road, Maniktola, CALCUTTA 700054 Northern : SC0 445-446, Sector 35-C, CHANDIGARH 160036 Southern : t W&tern C.I.T. Campus, IV Cross Road, MADRAS 6001 I3 : Manakalava. E9 MIDC. Marol. Andheri (East). t BOMBAY’400093 Branch Offices : ‘Pushpak’, Nurmohamed Shaikh Marg. Khanpur, AHMADABAD 380001 Peenya Industrial Area, I st Stage, Bangalore-Tumkur Road, BANGALORE 560058 Gangotri Complex, 5th Floor, Bhadbhada Road, T.T. Nagar, 55402l BHOPAL 462003 Plot No. 82/83, Lewis Road, BHUBANESHWAR 751002 53627 Kalai Kathir Building, 6/48-A Avanasi Road, COIMBATORE 641037 267 05 Quality Marking Centre, N.H. IV, N.I.T., FARIDABAD 121001 - Savitri Complex, I I6 G. T. Road, GHAZIABAD 201001 8-71 19 96 53/5 Ward No. 29. R.G. Barua Road, 5th Bv-lane. 331 77 G~~wAHAT~ 781003 5-8-560 L. N. Gupta Marg, ( Nampally Station Road ) HYDERABAD 500001 RI4 Yudhister Marg, C Scheme, JAIPUR 302005 117/418 B Sarvodaya Nagar, KANPUR 208005 Plot No. A-9, House No. 561/63. Sindhu Nagar. Kanpur Roaa. LUCKNOW 226005 Patliputra Industrial Estate. PATNA 800013 District Industries Centre Complex. Bagh-e-Ali Maidan. SRINAGAR 190011 T. C. NO. 14/142I, University P. 0.. Palayam. THIRUVANANTHAPURAM 695034 Inspection Offices (With Sale Point) : Pushpanjali. First Floor, 205-A West High Court Road. Shankar Nagar Square, NAGPUR 440010 Institution of -Engineers (India) Building, 1332 Shivaji Nagar. PUNE 411005 ‘Sales Office Calcutta is at 5 Chowringhee Approach, P. 0. Princep Street, CALCUTTA t Sales Office is at Novelty Chambers, Grant Road, BOMBAY 3 Sales Office is at Unity Building, Narasimharaja Square, BANGALORE Telephone I 331 01 31 3311375 37 86 62 21843 41 2916 6329295 26348 3949 55 231083 6 34 71 21 68 76 5 55 07 6 23 05 - 621 04 52 61 71 i. 5 24 35 27 68 00 896528 223971
  • 15. AMENDMENTND. 1 OCTOBER 1981 TO IS:3370(PartIII)-1967 CODE OF PRACTICE FOR CONCRETE STRUCTURESFOR THE STDRAGE Df LfOUIDS PART III PRESTRESSED CONCRETE STRUGTURE; Alteration----- (Paga 3, czaras 0.3) - Substitute the follqving for the existing clauirc: ‘0.3 Although the provisions of this code cover ma.inlY structures for the storage of liquids, the general requirements given in Part I of this code raj generally appl;ir to the design of reinforced concrete and preatresscd concrete structures for the conreyance or l+Jida, such as aqueducts and superpassages; the other requlruscnts given in the code may also be applied vith appropriate modifications.' (@DC 2) ReprographyUnit, BIS, New Delhi, India