Monitoring and Control of Power System Oscillations using
FACTS/HVDC and Wide-area Phasor Measurements
Mats Larsson*a
, Petr Korbaa
, Walter Sattingerb
, Priscilla Owena
ABB Switzerland Ltd. a
, swissgrid agb
Switzerland
SUMMARY
Power oscillations are a growing concern among power system operators worldwide. Traditionally, the
main countermeasure against dangerous power oscillations has been the installation of power system
stabilizers (PSS). Essentially, the potential for inter-area power oscillations depends on the strength of
the tie lines between different areas and the load on the ties. From a European perspective, with the
anticipated integration of remote renewable energy sources such as offshore wind power from the
North-sea region and solar power from southern Europe or Africa, we can expect the average
transmission distances to grow and consequently also tie line flows. Unless tie lines are also reinforced
we expect more oscillation events in the European grid in the future.
From an operational point of view, it is of high priority to be able to estimate the damping of
oscillatory modes reliably in real-time in order to take appropriate and timely measures in case
damping becomes poor. Recent developments in wide-area phasor monitoring have resulted in a new
power oscillation monitoring algorithm that uses multiple measurements from different locations in
the grid. An equivalent system model of the power grid is estimated in real-time and based on this
model, the damping and frequency as well the activity of oscillatory modes can be determined from
ambient process variations. As basis for this, a wide-area measurement system (WAMS) can provide
time synchronized signals from phasor measurement units (PMUs) that can measure voltage, current
and frequency with adequate accuracy and resolution in time. This paper shows results from pilot
operation of the new application at swissgrid, including recordings from an actual and representative
event in the continental ENTSO-E interconnected power system. This example demonstrates the
performance of the new application as well as provides information about the oscillatory modes
present in the continental ENTSO-E system today.
Furthermore, FACTS and HVDC systems can serve as powerful actuators to control inter-area
oscillations, provided they are equipped with appropriate controller extensions. Particularly for the
control and management of inter-area oscillations, remote measurements have proven useful. The
paper outlines the technical aspects and suggests a design procedure for controller extensions based on
local or remote measurement for the purpose of inter-area oscillation damping.
KEYWORDS
Power oscillation, wide-area monitoring and control, phasor measurement, FACTS/HVDC, PMU,
small disturbance stability, power system dynamics, power system control
*
Mats.Larsson@ch.abb.com
21, rue d’Artois, F-75008 PARIS CIGRE 2012
http : //www.cigre.org B5-119
1
1. INTRODUCTION
Wide-area monitoring systems (WAMS) offer the possibility of supervision of power system dynamic
phenomena. They are based on phasor measurement units which are most often synchronized using a
global positioning system (GPS) clock to provide time-synchronized voltage and current phasor, as
well as frequency measurements with synchronization accuracy better than microseconds [1-4].
This paper describes a new damping estimation application that employs WAMS data to estimate the
damping of oscillatory modes from ambient data before a disturbance [5-7]. This can give an
indication of the damping of transient oscillations that will follow a disturbance, once it occurs. The
application is based on a system identification procedure that is carried out in real-time using a sliding
measurement window. If the transfer between two grid areas is limited by inadequate damping, the
damping monitor can assist in maximizing the power transfer capability by providing a faster and
more accurate view of the current situation than one obtained via off-line dynamic simulations. This is
possible since the PMU measurements are not subject to modeling errors that are potentially present in
the off-line simulation models. Such modeling errors could lead to definition of overly conservative or
even inadequate transfer limits. The new damping monitoring application also identifies the parts of
the power system that participate in a detected oscillation through modal activity information that can
be used to determine the root cause of a poorly damped oscillatory mode, and serve as starting point
for the definition of improvement measures.
Furthermore, any fast power electronic devices able to directly or indirectly modulate electric power
flows (such as FACTS, HVDC or the excitation systems of synchronous generators), can be used as
actuators to improve poor damping, provided they are equipped with appropriate controller extensions
[8-10].
2. DEFINITIONS OF MODAL DAMPING AND FREQUENCY
In the case of a single wide area electromechanical oscillation mode, the relationship between power
flow, y(t), and the unmeasured load demand, u(t), can be modeled by a second order linearization
(1)
2
2
2
2 n n
d y dy
y t u t
dtdt
where is the damping ratio and n is the natural frequency of the oscillation. If is positive and less
than one, an impulsive change in ( )u t gives a decaying transient oscillating response. This response
typically occurs after a fault or major system disturbance and is called a transient or ring down. On the
other hand, random changes in ( )u t excite a persistent oscillation at the natural frequency, which may
be of small amplitude and largely hidden in noise. This is called ambient conditions.
Eigenvalues are the complex roots, 1 and 2, of the characteristic equation arising from (1). There are
also many ways to estimate eigenvalues from time series of measurements y(t), including subspace
identification which is used in this paper. If the eigenvalue is expressed in Cartesian form as
i = ± j t, an the expression for damping ratio is 2 2
t . Another common measure is the
time domain damping which can easily be obtained as the ratio of two successive peaks in a recorded
oscillation as illustrated in Figure 3, or from the eigenvalues as
2 2
2
1 t
td e . Throughout this paper
the general term damping refers to the time domain damping td .
3. DAMPING MONITORING OF POWER OSCILLATIONS USING AMBIENT DATA
The application is based on a system identification procedure that is carried out using a sliding
window. This yields a time-varying dynamic equivalent of the power system, which is analyzed using
modal analysis, resulting in the desired information about the active inter-area modes in real-time. The
information includes:
The number of detected active oscillation modes
The frequency and damping of each mode.
2
The amplitude of the oscillations in each mode and in each measurement signal.
The modal observability, i.e., a measure of how well and the relative phase in which each
oscillatory mode is visible in each measurement signal.
The configuration of the application defines:
The selection of measurements to use as input. Experience has shown that voltage angle
difference measurements and frequency measurements are particularly useful for this purpose.
A general rule is to select measurement from the edges of the system since they usually offer
the highest observability of inter-area modes.
The length of the sliding window which is typically around 10-15 min.
The update rate which is typically once every 30 seconds.
Maximum number of modes to detect and strategy for selection and sorting of the identified
modes. The different strategies include ranking by lowest damping, proximity to certain
known oscillation frequency and sorting by absolute mode frequency.
The mathematical background of the algorithm and results from simulation experiments as well as
measurements in the Scandinavian power grid are described in [5,6] and has been benchmarked
against other damping monitoring algorithms in [7].
4. WIDE-AREA MONITORING SYSTEM AT SWISSGRID
Since 2004, swissgrid has been monitoring the Swiss transmission grid using PMUs [2-4]. The system
has been successively extended and is now interconnected with WAMS systems from the same vendor
at Verbund, Austria and at HEP in Croatia, enabling real-time exchange of phasor data. Additionally,
phasor measurements are exchanged with WAMS systems from other vendors in Denmark, Slovenia,
Italy, Portugal, Greece and Turkey. Phasor data is exchanged using the SynchroPhasor standard
protocols over a secure Inter-TSO communication network. In total, the WAMS system collects data
from 22 PMUs with the full time resolution of 10 Hz. The setup now has excellent capabilities for
monitoring inter-area oscillations in the ENTSO-E Continental European Synchronous Area (CESA).
The architecture of the hierarchical WAMS system at swissgrid is illustrated in Figure 1.
Figure 1 - Architecture of the hierarchical WAMS system at swissgrid.
3
5. CASE STUDY: ENTSO-E CESA
A large interconnected power system such as the ENTSO-E Continental European Synchronous Area
(CESA), which spans from Portugal to the West, Denmark to the North, Italy in the South and Greece
in the East, harbors a large number of oscillatory modes. These modes range from local plant modes
with relatively high frequency of 0.9-2 Hz to the slow dominant inter-area modes that relate to the
coherent speed variations of generators in entire network areas against those in other areas. Although
the damping monitoring application will detect also local modes, the investigation here focuses on the
inter-area modes. Since September 2010, the Turkish power grid is connected to the ENTSO-E CESA
system, currently in trial operation. As discussed below, the connection of Turkey resulted in a new
dominant mode.
The new damping monitoring application has been in pilot operation at swissgrid since December
2010, and has continuously monitored the damping and frequency of inter-area modes in the CESA
system. The application has been configured to use real-time frequency measurements with a time
resolution of 10 Hz from the seven locations shown with circles in Figure 2. This figure also illustrates
the inter-area oscillation modes that have been detected by the damping monitoring application in the
CESA system.
The East-west mode involves coherent movement of generators in Portugal and Spain against those in
Turkey. This mode typically shows a frequency of 0.13-0.15 Hz and appeared following the
connection of Turkey. Under normal operating conditions, this is the dominant mode with the most
oscillatory energy. Prior to the connection, detailed simulation studies and measures were taken to
ensure damping of this anticipated mode. Those measures included for example retuning power
system stabilizers to damp this new inter-area mode and the addition of active shunt compensation
such as STATCOMM and SVC with damping modules. The field recordings using WAMS indicate
that those measures have been effective. The estimated time-domain damping ( td ) most of the time is
in the interval 45-70% which we consider adequate.
Figure 2 - Map display showing the dominant inter-area modes in the ENTSO-E grid. The circles indicate
the location of the PMU frequency measurement used by the damping monitoring application.
4
The Former East-west mode involves coherent movement of generators in Portugal and Spain against
those in Greece. This mode typically exhibits a frequency of around 0.17-0.2 Hz and is best visible in
frequency measurements from Greece and from Portugal. Nowadays, this mode mostly also has good
time-domain damping ( td ) around 40-50 %.
The North-south mode involves coherent movement of generators in southern Italy against northern
Germany and Denmark. This mode typically exhibits a frequency of around 0.23-0.27 Hz. Good
measurement signals for observation of this mode are frequency and voltage angle measurements from
southern Italy or Denmark, or active power flow measurement on the cross-border lines between Italy
and Switzerland. Because of the significantly lower combined rotating mass of generation units in
southern Italy the amplitude in the frequency measurements is there much higher here compared to the
measurement from Denmark. The WAMS recordings show that this mode typically exhibits the lowest
damping of the three dominant modes, although a significant improvement can be seen during the
second half of 2011.
The results of the damping monitoring application correspond well with anticipations from system
studies and engineering expectations regarding the dynamic characteristics of the ENTSO-E CESA
system.
5.1 Huge Power Generation Loss in Turkey
On October 25, 2011, five units of a major hydro generation plant were tripped due to a nearby busbar
failure. The result was the loss of around 1300 MW generation in the Turkish part of the
interconnected grid, which as expected excited the East-west mode. As designed, a system protection
scheme (SPS) in the Turkish grid executed around 270 MW of load shedding in the Turkish part of the
system to protect tie lines to Greece and Bulgaria.
Figure 3 shows the frequency response in Temelli, Turkey, following the generation loss as recorded
by the swissgrid WAMS. Following the trip there is a rapid decline in the local frequency of around
100 mHz followed by a well damped oscillation. From the figure, the time-domain damping ( td ) of
the transient oscillation can be determined to be approximately 70%.
Figure 3 - Frequency response in Temelli following the hydro generation plant trip at 14.59 on October
25, 2011 recorded by the swissgrid WAMS. Time axis is in seconds after 14.30 CET.
Frequencydeviation(mHz)
21
78
24
74
5
5.2 Results of the Damping Monitoring Application
Figure 4 shows the estimated modal damping and frequency during half an hour before the event,
illustrated by red asterisks, and half an hour after the event, illustrated by blue crosses. Clusters
corresponding to the known oscillatory modes are clearly visible. In the top left of the diagram the
cluster corresponding to the North-south mode with a detected frequency of around 0.25 Hz, and
average damping of 30% is visible. The clusters from before and after the disturbance are mostly
overlapping. Thus we can draw the conclusion that the event had no significant effect on the damping
or frequency of the North-south mode.
The cluster around 0.18-0.19 Hz corresponds to the Former East-west mode. The average damping
before the disturbance was around 60% and around 50% after. This indicates that the event has caused
a reduction of the damping of around 10%. However, the damping of this mode is still to be
considered adequate after the disturbance. The reason for the reduction in damping is not yet clear, but
a plausible explanation is that the load that was disconnected by the system protection scheme was
mostly of an industrial nature, and may have been contributing to the damping of this mode. Another
explanation could be that the flow patterns in the grid changed in a way leading to lower damping of
this mode.
The cluster to the bottom right in the figure corresponds to the East-west mode with frequency 0.13 Hz
and average damping of 60% before as well as after the disturbance. Thus, we can conclude that the
plant trip appears not to have significantly changed the damping of this mode, and that adequate
damping resources were available even though the lost generation units were equipped with power
system stabilizers tuned to damp out this mode.
An interesting observation is that the damping monitoring application was able to determine the post-
disturbance damping of the East-west mode close to its true damping using only the ambient pre-
disturbance data. This gives additional confidence in its effectiveness as an early-warning system
against poorly damped oscillation that may arise also due to transient events.
-10 %
Figure 4 – Scatter plot showing the output of the damping monitoring algorithm for 59 executions of
between 14.30 CET and 14.59 CET marked with red asterisks, and for 61 executions between 15.00 CET
and 15.30 CET marked with blue crosses.
6
6. DAMPING OF POWER-OSCILLATIONS USING WAMS AND FACTS/HVDC
The most common practice today, is to use power system stabilizers (PSS) applied as an auxiliary
input to the voltage set-point of the automatic voltage regulator (AVR) of large synchronous
generators. However, any fast power electronic devices that can modulate directly or indirectly
electric power flows (such as FACTS or HVDC), can be used as actuators to deal with the problem of
poorly damped electromechanical oscillations in large electric power systems [8-10]. However, the
effectiveness of the actuators for damping control, be it FACTS/HVDC or synchronous generators,
largely depends on the tuning of the damping extensions and on the location of the actuator.
Furthermore, generators and transmission network often belong to different entities with different
interests. Thus, network operators are increasingly considering network components such as HVDC
and FACTS devices to be equipped with damping controllers having the functionality equivalent and
in some respects surpassing that of power system stabilizers [8,9].
There is no unique way of tuning a damping controller extension for a FACTS/HVDC or a
synchronous generator; however, in the industry have been created appropriate tools for tuning of
standardized structures of PSS for synchronous generators [11]. This PSS tuning procedure aims at
fulfilling the following three goals:
Local mode oscillations, i.e., those with the frequencies above 0.7Hz, must be well damped.
The PSS should also provide adequate damping for inter-area mode oscillations.
The PSS should not over-modulate the control signal.
The idea behind the wide-area approach to power system stabilizers is in principle very simple: Extend
the number of signals, which can be considered as a feedback for control (i.e. including the remote
signals available through WAMS), and select between them carefully those with the highest
observability of the oscillatory modes to be damped. Hence, the selection of the proper feedback
signal is herewith the first and very important step in the stabilizing controller design. In practice, one
can use as a starting point the measured signals collected from the installed PMUs and identify this
model. And, this is exactly what is happening when running the same algorithm as used in the
damping monitoring applications described in the previous sections - however, extended with input
channels corresponding to the considered actuators [12].
Applying the above mentioned concept to the identified power system model for the selected input and
output channels and the critical modes, one can get the information which measurements should be
ideally used as feedback signals in the damping control loops. In all cases investigated so far (see e.g.
[9],[10],[12]), the remote signals were in the analysis classified as superior to the local ones. And, the
resulting controllers (having the same structure but using remote signals) outperformed the
conventional local ones.
Based on the collected experience, due to high modal observability of the critical oscillatory modes in
the selected remote feedback signals one can observe the following tendencies:
With wide-area controllers, the damping of all critical modes can be more easily achieved and
demonstrated in both frequency domain (for linear or linearized system model) as well as in
the time domain.
In addition, the wide-area controllers have smaller gain across all frequencies, and therefore,
they are inherently more robust and require less control energy those based on local feedback
signal, to achieve the same damping.
The price to be paid for the wide-area solution is higher investments into communication
infrastructure to enable a reliable transfer of all required measurements from the remote place
where they are captured to the generator excitation system. In general, the local measurements
are still more reliable.
Another advantage of the local approach is that only basic data and less information about the
power system are required for the proper controller tuning, whereas the wide-area design
requires an equivalent linear power system model, which can be created using a power system
tool or through system identification.
7
7. CONCLUSION
The paper demonstrates the use of a new multivariable damping monitoring algorithm for the purpose
of supervision of inter-area oscillations in power networks. The application results are validated
against the measured response following a generator trip in the Turkish power network that caused an
oscillation visible along the East-west direction in the entire ENTSO-E continental Europe grid. The
application was able to determine the damping of various oscillatory modes accurately using only the
pre-disturbance data from ambient conditions. That is, the true damping of the post-disturbance
transient oscillation in the East-west mode agreed well with the damping estimated by the damping
monitoring application prior to its occurrence.
It is a common practice for the power system stabilizers to be designed using local measurements and
synchronous generators only. Similarly, HVDC and FACTS devices can be used to improve damping.
The use of properly selected feedback signals and actuators yields a superior performance and
robustness of the designed controllers to damp the critical oscillatory modes, thanks to higher modal
observability and controllability which leads to lower gains and better robustness of the feedback
control loops. It is however, important to realize that the solution based on remote feedback has also a
higher technical complexity and cost. Hence, the cost/benefit ratio shall influence the decision on
which solution will be applied in practice on a case to case basis.
8. ACKNOWLEDGEMENT
The authors gratefully acknowledge Valentin Buergler at ABB Switzerland for his support regarding
management of and data export from the swissgrid WAMS system, and the support and intensive
collaboration of Giorgio Giannuzzi, Rui Pestana, Yiannis Blanas, Samuel Thomasson, Yildiz
Durukan, Zdeslav Cerina, Leon Koricki and Gregor Wizmann in exchanging PMU data information
on a pan-European level.
REFERENCES
[1] M. Zima, M. Larsson, P. Korba et. al., “Design Aspects for Wide-Area Monitoring and Control
Systems”, Proceedings of the IEEE, vol. 93, no. 5, 2005, pp 980—996.
[2] W. Sattinger, J. Bertsch and P. Reinhardt, “Operational Experience with Wide Area Monitoring
Systems”, CIGRE 2006 Session, B5-216.
[3] W. Sattinger, R. Baumann and P. Rothermann, “A new dimension in grid monitoring”,
Transmission & Distribution World, 2 2007, pp 54-60.
[4] A.G. Phadke, “The Wide World of Wide-area Measurement”, IEEE Power & Energy Magazine,
2008, p.52-65.
[5] M. Larsson, D.S. Laila, “Monitoring of inter-area oscillations under ambient conditions using
subspace identification”, PES '09. IEEE, 2009.
[6] J. Turunen, M. Larsson, P. Korba, et. al., ”Experiences and Future Plans in Monitoring the Inter-
area Power Oscillation Damping”, PES '08. IEEE, 2008.
[7] J. Turunen, J. Thabirajahm, M. Larsson et.al., “Comparison of Three Electromechanical
Oscillation Damping Estimation Methods”, IEEE Transactions on Power Systems, vol. 26, no. 4, pp.
2398—2407, 2011.
[8] R. Sadikovic, P. Korba and G. Andersson, “Application of FACTS Devices for Damping of Power
System Oscillations”, PowerTech, St. Petersburg, Russia, June 27-30, 2005.
[9] P. Korba, K. Uhlen, “Wide-Area Monitoring of Electromechanical Oscillations in the NORDIC
Power System: a Practical Experience”, IET Proceedings on GTD, vol. 4, no. 10, pp. 1115-1126,
2010.
[10] P. Korba, V. Knazkins, M. Larsson, “Extended Power System Stabilizer with Synchronized
Phasor measurement”, PSCC 2011, 2011.
[11] IEEE Recommended Practice for Excitation System Models for Power System Stability Studies,
April. 2006. IEEE Standard 421.5™-2005 (Revision of IEEE Std 421.5-1992).
[12] E. Johansson, K. Uhlen, A. B. Leirbukt, P. Korba et.al., “Coordinating Power Oscillation
Damping Control using Wide Area Measurements”, PSCE ‘09, IEEE, 2009.

More Related Content

What's hot

Frequency Response Assessment: Parameter Identification of Simplified Governo...
Frequency Response Assessment: Parameter Identification of Simplified Governo...Frequency Response Assessment: Parameter Identification of Simplified Governo...
Frequency Response Assessment: Parameter Identification of Simplified Governo...Power System Operation
 
Transformer-Less UPFC for Wind Turbine Applications
Transformer-Less UPFC for Wind Turbine ApplicationsTransformer-Less UPFC for Wind Turbine Applications
Transformer-Less UPFC for Wind Turbine ApplicationsIJMTST Journal
 
Sensitivity based optimal location of tcsc for improvement of power system se...
Sensitivity based optimal location of tcsc for improvement of power system se...Sensitivity based optimal location of tcsc for improvement of power system se...
Sensitivity based optimal location of tcsc for improvement of power system se...eSAT Publishing House
 
IRJET-An Enhanced Scheme for Detecting Under-Voltage and Over-Voltage using F...
IRJET-An Enhanced Scheme for Detecting Under-Voltage and Over-Voltage using F...IRJET-An Enhanced Scheme for Detecting Under-Voltage and Over-Voltage using F...
IRJET-An Enhanced Scheme for Detecting Under-Voltage and Over-Voltage using F...IRJET Journal
 
WIDE AREA PROTECTION IN POWER SYSTEMS
WIDE AREA PROTECTION IN POWER SYSTEMSWIDE AREA PROTECTION IN POWER SYSTEMS
WIDE AREA PROTECTION IN POWER SYSTEMSmanogna gwen
 
Wavelet-Based Fault Location and Distance Protection Method for Transmission ...
Wavelet-Based Fault Location and Distance Protection Method for Transmission ...Wavelet-Based Fault Location and Distance Protection Method for Transmission ...
Wavelet-Based Fault Location and Distance Protection Method for Transmission ...IJERA Editor
 
System for reception and transmission of telluic waves by eric dollard
System for reception and transmission of telluic waves by eric dollardSystem for reception and transmission of telluic waves by eric dollard
System for reception and transmission of telluic waves by eric dollardPublicLeaker
 
Efficacy of Facts in Power Oscillation Damping and Renewable Integration
Efficacy of Facts in Power Oscillation Damping and Renewable IntegrationEfficacy of Facts in Power Oscillation Damping and Renewable Integration
Efficacy of Facts in Power Oscillation Damping and Renewable IntegrationIOSRJEEE
 
A Novel Approach for Fault Location of Overhead Transmission Line With Noncon...
A Novel Approach for Fault Location of Overhead Transmission Line With Noncon...A Novel Approach for Fault Location of Overhead Transmission Line With Noncon...
A Novel Approach for Fault Location of Overhead Transmission Line With Noncon...Nidheesh Namboodhiri
 
An Expert System For Power Plants Paper Presentation
An Expert System For Power Plants Paper PresentationAn Expert System For Power Plants Paper Presentation
An Expert System For Power Plants Paper Presentationguestac67362
 
A overview on WAMS/PMU.
A overview on WAMS/PMU.A overview on WAMS/PMU.
A overview on WAMS/PMU.Rahul Singh
 

What's hot (20)

Power electronics application: FACTS controller
Power electronics application: FACTS controller   Power electronics application: FACTS controller
Power electronics application: FACTS controller
 
Frequency Response Assessment: Parameter Identification of Simplified Governo...
Frequency Response Assessment: Parameter Identification of Simplified Governo...Frequency Response Assessment: Parameter Identification of Simplified Governo...
Frequency Response Assessment: Parameter Identification of Simplified Governo...
 
Transformer-Less UPFC for Wind Turbine Applications
Transformer-Less UPFC for Wind Turbine ApplicationsTransformer-Less UPFC for Wind Turbine Applications
Transformer-Less UPFC for Wind Turbine Applications
 
Sensitivity based optimal location of tcsc for improvement of power system se...
Sensitivity based optimal location of tcsc for improvement of power system se...Sensitivity based optimal location of tcsc for improvement of power system se...
Sensitivity based optimal location of tcsc for improvement of power system se...
 
IRJET-An Enhanced Scheme for Detecting Under-Voltage and Over-Voltage using F...
IRJET-An Enhanced Scheme for Detecting Under-Voltage and Over-Voltage using F...IRJET-An Enhanced Scheme for Detecting Under-Voltage and Over-Voltage using F...
IRJET-An Enhanced Scheme for Detecting Under-Voltage and Over-Voltage using F...
 
Smart Grid & WAMS
Smart Grid & WAMSSmart Grid & WAMS
Smart Grid & WAMS
 
Fault location techniques in smart distribution system
Fault location techniques in smart distribution systemFault location techniques in smart distribution system
Fault location techniques in smart distribution system
 
Al4201250256
Al4201250256Al4201250256
Al4201250256
 
WIDE AREA PROTECTION IN POWER SYSTEMS
WIDE AREA PROTECTION IN POWER SYSTEMSWIDE AREA PROTECTION IN POWER SYSTEMS
WIDE AREA PROTECTION IN POWER SYSTEMS
 
Wide area monitoring, protection and control in future smart grid
Wide area monitoring, protection and control in future smart gridWide area monitoring, protection and control in future smart grid
Wide area monitoring, protection and control in future smart grid
 
Wavelet-Based Fault Location and Distance Protection Method for Transmission ...
Wavelet-Based Fault Location and Distance Protection Method for Transmission ...Wavelet-Based Fault Location and Distance Protection Method for Transmission ...
Wavelet-Based Fault Location and Distance Protection Method for Transmission ...
 
System for reception and transmission of telluic waves by eric dollard
System for reception and transmission of telluic waves by eric dollardSystem for reception and transmission of telluic waves by eric dollard
System for reception and transmission of telluic waves by eric dollard
 
C1081826
C1081826C1081826
C1081826
 
Efficacy of Facts in Power Oscillation Damping and Renewable Integration
Efficacy of Facts in Power Oscillation Damping and Renewable IntegrationEfficacy of Facts in Power Oscillation Damping and Renewable Integration
Efficacy of Facts in Power Oscillation Damping and Renewable Integration
 
Maximum power point tracking algorithms for wind energy systems
Maximum power point tracking algorithms for wind energy systemsMaximum power point tracking algorithms for wind energy systems
Maximum power point tracking algorithms for wind energy systems
 
A Novel Approach for Fault Location of Overhead Transmission Line With Noncon...
A Novel Approach for Fault Location of Overhead Transmission Line With Noncon...A Novel Approach for Fault Location of Overhead Transmission Line With Noncon...
A Novel Approach for Fault Location of Overhead Transmission Line With Noncon...
 
An Expert System For Power Plants Paper Presentation
An Expert System For Power Plants Paper PresentationAn Expert System For Power Plants Paper Presentation
An Expert System For Power Plants Paper Presentation
 
On radio frequency
On radio frequencyOn radio frequency
On radio frequency
 
A overview on WAMS/PMU.
A overview on WAMS/PMU.A overview on WAMS/PMU.
A overview on WAMS/PMU.
 
Energy storage systems control methods in micro grids Class-30, Subject: Di...
Energy storage systems control methods in micro grids Class-30,  Subject:  Di...Energy storage systems control methods in micro grids Class-30,  Subject:  Di...
Energy storage systems control methods in micro grids Class-30, Subject: Di...
 

Similar to Monitoring and control of power system oscillations using wide-area measurements

Analysis and Damping of Inter-Area Oscillations in the UCTE/CENTREL Power System
Analysis and Damping of Inter-Area Oscillations in the UCTE/CENTREL Power SystemAnalysis and Damping of Inter-Area Oscillations in the UCTE/CENTREL Power System
Analysis and Damping of Inter-Area Oscillations in the UCTE/CENTREL Power SystemPower System Operation
 
A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...
A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...
A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...Power System Operation
 
Joint State and Parameter Estimation by Extended Kalman Filter (EKF) technique
Joint State and Parameter Estimation by Extended Kalman Filter (EKF) techniqueJoint State and Parameter Estimation by Extended Kalman Filter (EKF) technique
Joint State and Parameter Estimation by Extended Kalman Filter (EKF) techniqueIJERD Editor
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...ijfls
 
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...Wireilla
 
Reliability analysis of pmu using hidden markov model
Reliability analysis of pmu using hidden markov modelReliability analysis of pmu using hidden markov model
Reliability analysis of pmu using hidden markov modelamaresh1234
 
APPLICATION OF GPS IN POWER SECTOR@1.ppt
APPLICATION OF GPS IN POWER SECTOR@1.pptAPPLICATION OF GPS IN POWER SECTOR@1.ppt
APPLICATION OF GPS IN POWER SECTOR@1.pptAmitKumarSahu56
 
Real-Time Monitoring of Power Oscillations Modal Damping in the European System
Real-Time Monitoring of Power Oscillations Modal Damping in the European SystemReal-Time Monitoring of Power Oscillations Modal Damping in the European System
Real-Time Monitoring of Power Oscillations Modal Damping in the European SystemPower System Operation
 
Icaee paper id 116.pdf
Icaee paper id 116.pdfIcaee paper id 116.pdf
Icaee paper id 116.pdfshariful islam
 
An Algorithm Based On Discrete Wavelet Transform For Faults Detection, Locati...
An Algorithm Based On Discrete Wavelet Transform For Faults Detection, Locati...An Algorithm Based On Discrete Wavelet Transform For Faults Detection, Locati...
An Algorithm Based On Discrete Wavelet Transform For Faults Detection, Locati...paperpublications3
 
6843 traveling wave_ag_20171107_web2
6843 traveling wave_ag_20171107_web26843 traveling wave_ag_20171107_web2
6843 traveling wave_ag_20171107_web2HAYMANOTTAKELE1
 
Adaptive and inteligence
Adaptive and inteligenceAdaptive and inteligence
Adaptive and inteligenceFinitoTheEnd
 
The Need for Enhanced Power System Modelling Techniques and Simulation Tools
The Need for Enhanced Power System Modelling Techniques and Simulation ToolsThe Need for Enhanced Power System Modelling Techniques and Simulation Tools
The Need for Enhanced Power System Modelling Techniques and Simulation ToolsPower System Operation
 
Summary Presentation on PMU Based Transmission Line Protection Scheme
Summary Presentation on PMU Based Transmission Line Protection Scheme Summary Presentation on PMU Based Transmission Line Protection Scheme
Summary Presentation on PMU Based Transmission Line Protection Scheme Samuel Okhuegbe
 
Phasor measurement unit
Phasor measurement unitPhasor measurement unit
Phasor measurement unitSathriGiridhar
 

Similar to Monitoring and control of power system oscillations using wide-area measurements (20)

Analysis and Damping of Inter-Area Oscillations in the UCTE/CENTREL Power System
Analysis and Damping of Inter-Area Oscillations in the UCTE/CENTREL Power SystemAnalysis and Damping of Inter-Area Oscillations in the UCTE/CENTREL Power System
Analysis and Damping of Inter-Area Oscillations in the UCTE/CENTREL Power System
 
A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...
A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...
A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...
 
Joint State and Parameter Estimation by Extended Kalman Filter (EKF) technique
Joint State and Parameter Estimation by Extended Kalman Filter (EKF) techniqueJoint State and Parameter Estimation by Extended Kalman Filter (EKF) technique
Joint State and Parameter Estimation by Extended Kalman Filter (EKF) technique
 
I0423056065
I0423056065I0423056065
I0423056065
 
E1082935
E1082935E1082935
E1082935
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
 
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
WAVELET- FUZZY BASED MULTI TERMINAL TRANSMISSION SYSTEM PROTECTION SCHEME IN ...
 
Reliability analysis of pmu using hidden markov model
Reliability analysis of pmu using hidden markov modelReliability analysis of pmu using hidden markov model
Reliability analysis of pmu using hidden markov model
 
APPLICATION OF GPS IN POWER SECTOR@1.ppt
APPLICATION OF GPS IN POWER SECTOR@1.pptAPPLICATION OF GPS IN POWER SECTOR@1.ppt
APPLICATION OF GPS IN POWER SECTOR@1.ppt
 
Real-Time Monitoring of Power Oscillations Modal Damping in the European System
Real-Time Monitoring of Power Oscillations Modal Damping in the European SystemReal-Time Monitoring of Power Oscillations Modal Damping in the European System
Real-Time Monitoring of Power Oscillations Modal Damping in the European System
 
Icaee paper id 116.pdf
Icaee paper id 116.pdfIcaee paper id 116.pdf
Icaee paper id 116.pdf
 
An Algorithm Based On Discrete Wavelet Transform For Faults Detection, Locati...
An Algorithm Based On Discrete Wavelet Transform For Faults Detection, Locati...An Algorithm Based On Discrete Wavelet Transform For Faults Detection, Locati...
An Algorithm Based On Discrete Wavelet Transform For Faults Detection, Locati...
 
6843 traveling wave_ag_20171107_web2
6843 traveling wave_ag_20171107_web26843 traveling wave_ag_20171107_web2
6843 traveling wave_ag_20171107_web2
 
38
3838
38
 
Adaptive and inteligence
Adaptive and inteligenceAdaptive and inteligence
Adaptive and inteligence
 
The Need for Enhanced Power System Modelling Techniques and Simulation Tools
The Need for Enhanced Power System Modelling Techniques and Simulation ToolsThe Need for Enhanced Power System Modelling Techniques and Simulation Tools
The Need for Enhanced Power System Modelling Techniques and Simulation Tools
 
Summary Presentation on PMU Based Transmission Line Protection Scheme
Summary Presentation on PMU Based Transmission Line Protection Scheme Summary Presentation on PMU Based Transmission Line Protection Scheme
Summary Presentation on PMU Based Transmission Line Protection Scheme
 
Phasor Measurement Unit (PMU)
 Phasor Measurement Unit (PMU) Phasor Measurement Unit (PMU)
Phasor Measurement Unit (PMU)
 
Phasor measurement unit
Phasor measurement unitPhasor measurement unit
Phasor measurement unit
 

More from Power System Operation

Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panelsPower System Operation
 
Big Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsBig Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsPower System Operation
 
SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action SchemePower System Operation
 
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...Power System Operation
 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePower System Operation
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)Power System Operation
 
Electrical Transmission Tower Types - Design & Parts
Electrical Transmission Tower  Types - Design & PartsElectrical Transmission Tower  Types - Design & Parts
Electrical Transmission Tower Types - Design & PartsPower System Operation
 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools Power System Operation
 
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
Power Quality  Trends in the Transition to  Carbon-Free Electrical Energy SystemPower Quality  Trends in the Transition to  Carbon-Free Electrical Energy System
Power Quality Trends in the Transition to Carbon-Free Electrical Energy SystemPower System Operation
 

More from Power System Operation (20)

ENERGY TRANSITION OUTLOOK 2021
ENERGY TRANSITION OUTLOOK  2021ENERGY TRANSITION OUTLOOK  2021
ENERGY TRANSITION OUTLOOK 2021
 
Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panels
 
What does peak shaving mean
What does peak shaving meanWhat does peak shaving mean
What does peak shaving mean
 
What's short circuit level
What's short circuit levelWhat's short circuit level
What's short circuit level
 
Power System Restoration Guide
Power System Restoration Guide  Power System Restoration Guide
Power System Restoration Guide
 
Big Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsBig Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid Operations
 
SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action Scheme
 
Substation Neutral Earthing
Substation Neutral EarthingSubstation Neutral Earthing
Substation Neutral Earthing
 
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground Resistance
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
 
Electrical Transmission Tower Types - Design & Parts
Electrical Transmission Tower  Types - Design & PartsElectrical Transmission Tower  Types - Design & Parts
Electrical Transmission Tower Types - Design & Parts
 
What is load management
What is load managementWhat is load management
What is load management
 
What does merit order mean
What does merit order meanWhat does merit order mean
What does merit order mean
 
What are Balancing Services ?
What are  Balancing Services ?What are  Balancing Services ?
What are Balancing Services ?
 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
 
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
Power Quality  Trends in the Transition to  Carbon-Free Electrical Energy SystemPower Quality  Trends in the Transition to  Carbon-Free Electrical Energy System
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
 
Power Purchase Agreement PPA
Power Purchase Agreement PPA Power Purchase Agreement PPA
Power Purchase Agreement PPA
 
Harmonic study and analysis
Harmonic study and analysisHarmonic study and analysis
Harmonic study and analysis
 
What is leakage current testing
What is leakage current testingWhat is leakage current testing
What is leakage current testing
 

Recently uploaded

Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
High Profile Call Girls Dahisar Arpita 9907093804 Independent Escort Service ...
High Profile Call Girls Dahisar Arpita 9907093804 Independent Escort Service ...High Profile Call Girls Dahisar Arpita 9907093804 Independent Escort Service ...
High Profile Call Girls Dahisar Arpita 9907093804 Independent Escort Service ...Call girls in Ahmedabad High profile
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxhumanexperienceaaa
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 

Recently uploaded (20)

Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
High Profile Call Girls Dahisar Arpita 9907093804 Independent Escort Service ...
High Profile Call Girls Dahisar Arpita 9907093804 Independent Escort Service ...High Profile Call Girls Dahisar Arpita 9907093804 Independent Escort Service ...
High Profile Call Girls Dahisar Arpita 9907093804 Independent Escort Service ...
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 

Monitoring and control of power system oscillations using wide-area measurements

  • 1. 0 Monitoring and Control of Power System Oscillations using FACTS/HVDC and Wide-area Phasor Measurements Mats Larsson*a , Petr Korbaa , Walter Sattingerb , Priscilla Owena ABB Switzerland Ltd. a , swissgrid agb Switzerland SUMMARY Power oscillations are a growing concern among power system operators worldwide. Traditionally, the main countermeasure against dangerous power oscillations has been the installation of power system stabilizers (PSS). Essentially, the potential for inter-area power oscillations depends on the strength of the tie lines between different areas and the load on the ties. From a European perspective, with the anticipated integration of remote renewable energy sources such as offshore wind power from the North-sea region and solar power from southern Europe or Africa, we can expect the average transmission distances to grow and consequently also tie line flows. Unless tie lines are also reinforced we expect more oscillation events in the European grid in the future. From an operational point of view, it is of high priority to be able to estimate the damping of oscillatory modes reliably in real-time in order to take appropriate and timely measures in case damping becomes poor. Recent developments in wide-area phasor monitoring have resulted in a new power oscillation monitoring algorithm that uses multiple measurements from different locations in the grid. An equivalent system model of the power grid is estimated in real-time and based on this model, the damping and frequency as well the activity of oscillatory modes can be determined from ambient process variations. As basis for this, a wide-area measurement system (WAMS) can provide time synchronized signals from phasor measurement units (PMUs) that can measure voltage, current and frequency with adequate accuracy and resolution in time. This paper shows results from pilot operation of the new application at swissgrid, including recordings from an actual and representative event in the continental ENTSO-E interconnected power system. This example demonstrates the performance of the new application as well as provides information about the oscillatory modes present in the continental ENTSO-E system today. Furthermore, FACTS and HVDC systems can serve as powerful actuators to control inter-area oscillations, provided they are equipped with appropriate controller extensions. Particularly for the control and management of inter-area oscillations, remote measurements have proven useful. The paper outlines the technical aspects and suggests a design procedure for controller extensions based on local or remote measurement for the purpose of inter-area oscillation damping. KEYWORDS Power oscillation, wide-area monitoring and control, phasor measurement, FACTS/HVDC, PMU, small disturbance stability, power system dynamics, power system control * Mats.Larsson@ch.abb.com 21, rue d’Artois, F-75008 PARIS CIGRE 2012 http : //www.cigre.org B5-119
  • 2. 1 1. INTRODUCTION Wide-area monitoring systems (WAMS) offer the possibility of supervision of power system dynamic phenomena. They are based on phasor measurement units which are most often synchronized using a global positioning system (GPS) clock to provide time-synchronized voltage and current phasor, as well as frequency measurements with synchronization accuracy better than microseconds [1-4]. This paper describes a new damping estimation application that employs WAMS data to estimate the damping of oscillatory modes from ambient data before a disturbance [5-7]. This can give an indication of the damping of transient oscillations that will follow a disturbance, once it occurs. The application is based on a system identification procedure that is carried out in real-time using a sliding measurement window. If the transfer between two grid areas is limited by inadequate damping, the damping monitor can assist in maximizing the power transfer capability by providing a faster and more accurate view of the current situation than one obtained via off-line dynamic simulations. This is possible since the PMU measurements are not subject to modeling errors that are potentially present in the off-line simulation models. Such modeling errors could lead to definition of overly conservative or even inadequate transfer limits. The new damping monitoring application also identifies the parts of the power system that participate in a detected oscillation through modal activity information that can be used to determine the root cause of a poorly damped oscillatory mode, and serve as starting point for the definition of improvement measures. Furthermore, any fast power electronic devices able to directly or indirectly modulate electric power flows (such as FACTS, HVDC or the excitation systems of synchronous generators), can be used as actuators to improve poor damping, provided they are equipped with appropriate controller extensions [8-10]. 2. DEFINITIONS OF MODAL DAMPING AND FREQUENCY In the case of a single wide area electromechanical oscillation mode, the relationship between power flow, y(t), and the unmeasured load demand, u(t), can be modeled by a second order linearization (1) 2 2 2 2 n n d y dy y t u t dtdt where is the damping ratio and n is the natural frequency of the oscillation. If is positive and less than one, an impulsive change in ( )u t gives a decaying transient oscillating response. This response typically occurs after a fault or major system disturbance and is called a transient or ring down. On the other hand, random changes in ( )u t excite a persistent oscillation at the natural frequency, which may be of small amplitude and largely hidden in noise. This is called ambient conditions. Eigenvalues are the complex roots, 1 and 2, of the characteristic equation arising from (1). There are also many ways to estimate eigenvalues from time series of measurements y(t), including subspace identification which is used in this paper. If the eigenvalue is expressed in Cartesian form as i = ± j t, an the expression for damping ratio is 2 2 t . Another common measure is the time domain damping which can easily be obtained as the ratio of two successive peaks in a recorded oscillation as illustrated in Figure 3, or from the eigenvalues as 2 2 2 1 t td e . Throughout this paper the general term damping refers to the time domain damping td . 3. DAMPING MONITORING OF POWER OSCILLATIONS USING AMBIENT DATA The application is based on a system identification procedure that is carried out using a sliding window. This yields a time-varying dynamic equivalent of the power system, which is analyzed using modal analysis, resulting in the desired information about the active inter-area modes in real-time. The information includes: The number of detected active oscillation modes The frequency and damping of each mode.
  • 3. 2 The amplitude of the oscillations in each mode and in each measurement signal. The modal observability, i.e., a measure of how well and the relative phase in which each oscillatory mode is visible in each measurement signal. The configuration of the application defines: The selection of measurements to use as input. Experience has shown that voltage angle difference measurements and frequency measurements are particularly useful for this purpose. A general rule is to select measurement from the edges of the system since they usually offer the highest observability of inter-area modes. The length of the sliding window which is typically around 10-15 min. The update rate which is typically once every 30 seconds. Maximum number of modes to detect and strategy for selection and sorting of the identified modes. The different strategies include ranking by lowest damping, proximity to certain known oscillation frequency and sorting by absolute mode frequency. The mathematical background of the algorithm and results from simulation experiments as well as measurements in the Scandinavian power grid are described in [5,6] and has been benchmarked against other damping monitoring algorithms in [7]. 4. WIDE-AREA MONITORING SYSTEM AT SWISSGRID Since 2004, swissgrid has been monitoring the Swiss transmission grid using PMUs [2-4]. The system has been successively extended and is now interconnected with WAMS systems from the same vendor at Verbund, Austria and at HEP in Croatia, enabling real-time exchange of phasor data. Additionally, phasor measurements are exchanged with WAMS systems from other vendors in Denmark, Slovenia, Italy, Portugal, Greece and Turkey. Phasor data is exchanged using the SynchroPhasor standard protocols over a secure Inter-TSO communication network. In total, the WAMS system collects data from 22 PMUs with the full time resolution of 10 Hz. The setup now has excellent capabilities for monitoring inter-area oscillations in the ENTSO-E Continental European Synchronous Area (CESA). The architecture of the hierarchical WAMS system at swissgrid is illustrated in Figure 1. Figure 1 - Architecture of the hierarchical WAMS system at swissgrid.
  • 4. 3 5. CASE STUDY: ENTSO-E CESA A large interconnected power system such as the ENTSO-E Continental European Synchronous Area (CESA), which spans from Portugal to the West, Denmark to the North, Italy in the South and Greece in the East, harbors a large number of oscillatory modes. These modes range from local plant modes with relatively high frequency of 0.9-2 Hz to the slow dominant inter-area modes that relate to the coherent speed variations of generators in entire network areas against those in other areas. Although the damping monitoring application will detect also local modes, the investigation here focuses on the inter-area modes. Since September 2010, the Turkish power grid is connected to the ENTSO-E CESA system, currently in trial operation. As discussed below, the connection of Turkey resulted in a new dominant mode. The new damping monitoring application has been in pilot operation at swissgrid since December 2010, and has continuously monitored the damping and frequency of inter-area modes in the CESA system. The application has been configured to use real-time frequency measurements with a time resolution of 10 Hz from the seven locations shown with circles in Figure 2. This figure also illustrates the inter-area oscillation modes that have been detected by the damping monitoring application in the CESA system. The East-west mode involves coherent movement of generators in Portugal and Spain against those in Turkey. This mode typically shows a frequency of 0.13-0.15 Hz and appeared following the connection of Turkey. Under normal operating conditions, this is the dominant mode with the most oscillatory energy. Prior to the connection, detailed simulation studies and measures were taken to ensure damping of this anticipated mode. Those measures included for example retuning power system stabilizers to damp this new inter-area mode and the addition of active shunt compensation such as STATCOMM and SVC with damping modules. The field recordings using WAMS indicate that those measures have been effective. The estimated time-domain damping ( td ) most of the time is in the interval 45-70% which we consider adequate. Figure 2 - Map display showing the dominant inter-area modes in the ENTSO-E grid. The circles indicate the location of the PMU frequency measurement used by the damping monitoring application.
  • 5. 4 The Former East-west mode involves coherent movement of generators in Portugal and Spain against those in Greece. This mode typically exhibits a frequency of around 0.17-0.2 Hz and is best visible in frequency measurements from Greece and from Portugal. Nowadays, this mode mostly also has good time-domain damping ( td ) around 40-50 %. The North-south mode involves coherent movement of generators in southern Italy against northern Germany and Denmark. This mode typically exhibits a frequency of around 0.23-0.27 Hz. Good measurement signals for observation of this mode are frequency and voltage angle measurements from southern Italy or Denmark, or active power flow measurement on the cross-border lines between Italy and Switzerland. Because of the significantly lower combined rotating mass of generation units in southern Italy the amplitude in the frequency measurements is there much higher here compared to the measurement from Denmark. The WAMS recordings show that this mode typically exhibits the lowest damping of the three dominant modes, although a significant improvement can be seen during the second half of 2011. The results of the damping monitoring application correspond well with anticipations from system studies and engineering expectations regarding the dynamic characteristics of the ENTSO-E CESA system. 5.1 Huge Power Generation Loss in Turkey On October 25, 2011, five units of a major hydro generation plant were tripped due to a nearby busbar failure. The result was the loss of around 1300 MW generation in the Turkish part of the interconnected grid, which as expected excited the East-west mode. As designed, a system protection scheme (SPS) in the Turkish grid executed around 270 MW of load shedding in the Turkish part of the system to protect tie lines to Greece and Bulgaria. Figure 3 shows the frequency response in Temelli, Turkey, following the generation loss as recorded by the swissgrid WAMS. Following the trip there is a rapid decline in the local frequency of around 100 mHz followed by a well damped oscillation. From the figure, the time-domain damping ( td ) of the transient oscillation can be determined to be approximately 70%. Figure 3 - Frequency response in Temelli following the hydro generation plant trip at 14.59 on October 25, 2011 recorded by the swissgrid WAMS. Time axis is in seconds after 14.30 CET. Frequencydeviation(mHz) 21 78 24 74
  • 6. 5 5.2 Results of the Damping Monitoring Application Figure 4 shows the estimated modal damping and frequency during half an hour before the event, illustrated by red asterisks, and half an hour after the event, illustrated by blue crosses. Clusters corresponding to the known oscillatory modes are clearly visible. In the top left of the diagram the cluster corresponding to the North-south mode with a detected frequency of around 0.25 Hz, and average damping of 30% is visible. The clusters from before and after the disturbance are mostly overlapping. Thus we can draw the conclusion that the event had no significant effect on the damping or frequency of the North-south mode. The cluster around 0.18-0.19 Hz corresponds to the Former East-west mode. The average damping before the disturbance was around 60% and around 50% after. This indicates that the event has caused a reduction of the damping of around 10%. However, the damping of this mode is still to be considered adequate after the disturbance. The reason for the reduction in damping is not yet clear, but a plausible explanation is that the load that was disconnected by the system protection scheme was mostly of an industrial nature, and may have been contributing to the damping of this mode. Another explanation could be that the flow patterns in the grid changed in a way leading to lower damping of this mode. The cluster to the bottom right in the figure corresponds to the East-west mode with frequency 0.13 Hz and average damping of 60% before as well as after the disturbance. Thus, we can conclude that the plant trip appears not to have significantly changed the damping of this mode, and that adequate damping resources were available even though the lost generation units were equipped with power system stabilizers tuned to damp out this mode. An interesting observation is that the damping monitoring application was able to determine the post- disturbance damping of the East-west mode close to its true damping using only the ambient pre- disturbance data. This gives additional confidence in its effectiveness as an early-warning system against poorly damped oscillation that may arise also due to transient events. -10 % Figure 4 – Scatter plot showing the output of the damping monitoring algorithm for 59 executions of between 14.30 CET and 14.59 CET marked with red asterisks, and for 61 executions between 15.00 CET and 15.30 CET marked with blue crosses.
  • 7. 6 6. DAMPING OF POWER-OSCILLATIONS USING WAMS AND FACTS/HVDC The most common practice today, is to use power system stabilizers (PSS) applied as an auxiliary input to the voltage set-point of the automatic voltage regulator (AVR) of large synchronous generators. However, any fast power electronic devices that can modulate directly or indirectly electric power flows (such as FACTS or HVDC), can be used as actuators to deal with the problem of poorly damped electromechanical oscillations in large electric power systems [8-10]. However, the effectiveness of the actuators for damping control, be it FACTS/HVDC or synchronous generators, largely depends on the tuning of the damping extensions and on the location of the actuator. Furthermore, generators and transmission network often belong to different entities with different interests. Thus, network operators are increasingly considering network components such as HVDC and FACTS devices to be equipped with damping controllers having the functionality equivalent and in some respects surpassing that of power system stabilizers [8,9]. There is no unique way of tuning a damping controller extension for a FACTS/HVDC or a synchronous generator; however, in the industry have been created appropriate tools for tuning of standardized structures of PSS for synchronous generators [11]. This PSS tuning procedure aims at fulfilling the following three goals: Local mode oscillations, i.e., those with the frequencies above 0.7Hz, must be well damped. The PSS should also provide adequate damping for inter-area mode oscillations. The PSS should not over-modulate the control signal. The idea behind the wide-area approach to power system stabilizers is in principle very simple: Extend the number of signals, which can be considered as a feedback for control (i.e. including the remote signals available through WAMS), and select between them carefully those with the highest observability of the oscillatory modes to be damped. Hence, the selection of the proper feedback signal is herewith the first and very important step in the stabilizing controller design. In practice, one can use as a starting point the measured signals collected from the installed PMUs and identify this model. And, this is exactly what is happening when running the same algorithm as used in the damping monitoring applications described in the previous sections - however, extended with input channels corresponding to the considered actuators [12]. Applying the above mentioned concept to the identified power system model for the selected input and output channels and the critical modes, one can get the information which measurements should be ideally used as feedback signals in the damping control loops. In all cases investigated so far (see e.g. [9],[10],[12]), the remote signals were in the analysis classified as superior to the local ones. And, the resulting controllers (having the same structure but using remote signals) outperformed the conventional local ones. Based on the collected experience, due to high modal observability of the critical oscillatory modes in the selected remote feedback signals one can observe the following tendencies: With wide-area controllers, the damping of all critical modes can be more easily achieved and demonstrated in both frequency domain (for linear or linearized system model) as well as in the time domain. In addition, the wide-area controllers have smaller gain across all frequencies, and therefore, they are inherently more robust and require less control energy those based on local feedback signal, to achieve the same damping. The price to be paid for the wide-area solution is higher investments into communication infrastructure to enable a reliable transfer of all required measurements from the remote place where they are captured to the generator excitation system. In general, the local measurements are still more reliable. Another advantage of the local approach is that only basic data and less information about the power system are required for the proper controller tuning, whereas the wide-area design requires an equivalent linear power system model, which can be created using a power system tool or through system identification.
  • 8. 7 7. CONCLUSION The paper demonstrates the use of a new multivariable damping monitoring algorithm for the purpose of supervision of inter-area oscillations in power networks. The application results are validated against the measured response following a generator trip in the Turkish power network that caused an oscillation visible along the East-west direction in the entire ENTSO-E continental Europe grid. The application was able to determine the damping of various oscillatory modes accurately using only the pre-disturbance data from ambient conditions. That is, the true damping of the post-disturbance transient oscillation in the East-west mode agreed well with the damping estimated by the damping monitoring application prior to its occurrence. It is a common practice for the power system stabilizers to be designed using local measurements and synchronous generators only. Similarly, HVDC and FACTS devices can be used to improve damping. The use of properly selected feedback signals and actuators yields a superior performance and robustness of the designed controllers to damp the critical oscillatory modes, thanks to higher modal observability and controllability which leads to lower gains and better robustness of the feedback control loops. It is however, important to realize that the solution based on remote feedback has also a higher technical complexity and cost. Hence, the cost/benefit ratio shall influence the decision on which solution will be applied in practice on a case to case basis. 8. ACKNOWLEDGEMENT The authors gratefully acknowledge Valentin Buergler at ABB Switzerland for his support regarding management of and data export from the swissgrid WAMS system, and the support and intensive collaboration of Giorgio Giannuzzi, Rui Pestana, Yiannis Blanas, Samuel Thomasson, Yildiz Durukan, Zdeslav Cerina, Leon Koricki and Gregor Wizmann in exchanging PMU data information on a pan-European level. REFERENCES [1] M. Zima, M. Larsson, P. Korba et. al., “Design Aspects for Wide-Area Monitoring and Control Systems”, Proceedings of the IEEE, vol. 93, no. 5, 2005, pp 980—996. [2] W. Sattinger, J. Bertsch and P. Reinhardt, “Operational Experience with Wide Area Monitoring Systems”, CIGRE 2006 Session, B5-216. [3] W. Sattinger, R. Baumann and P. Rothermann, “A new dimension in grid monitoring”, Transmission & Distribution World, 2 2007, pp 54-60. [4] A.G. Phadke, “The Wide World of Wide-area Measurement”, IEEE Power & Energy Magazine, 2008, p.52-65. [5] M. Larsson, D.S. Laila, “Monitoring of inter-area oscillations under ambient conditions using subspace identification”, PES '09. IEEE, 2009. [6] J. Turunen, M. Larsson, P. Korba, et. al., ”Experiences and Future Plans in Monitoring the Inter- area Power Oscillation Damping”, PES '08. IEEE, 2008. [7] J. Turunen, J. Thabirajahm, M. Larsson et.al., “Comparison of Three Electromechanical Oscillation Damping Estimation Methods”, IEEE Transactions on Power Systems, vol. 26, no. 4, pp. 2398—2407, 2011. [8] R. Sadikovic, P. Korba and G. Andersson, “Application of FACTS Devices for Damping of Power System Oscillations”, PowerTech, St. Petersburg, Russia, June 27-30, 2005. [9] P. Korba, K. Uhlen, “Wide-Area Monitoring of Electromechanical Oscillations in the NORDIC Power System: a Practical Experience”, IET Proceedings on GTD, vol. 4, no. 10, pp. 1115-1126, 2010. [10] P. Korba, V. Knazkins, M. Larsson, “Extended Power System Stabilizer with Synchronized Phasor measurement”, PSCC 2011, 2011. [11] IEEE Recommended Practice for Excitation System Models for Power System Stability Studies, April. 2006. IEEE Standard 421.5™-2005 (Revision of IEEE Std 421.5-1992). [12] E. Johansson, K. Uhlen, A. B. Leirbukt, P. Korba et.al., “Coordinating Power Oscillation Damping Control using Wide Area Measurements”, PSCE ‘09, IEEE, 2009.