27. NOTE
‣ The Reference Radiant Panel Test
ASTM D-2859 and NFPA® 253 are also
established testing methodologies to
determine the suitability of textile wall
and ceiling coverings.
28. The smoke developed rating measures an area’s
relative visual obscurity from smoke generated by
burning material.
29. The smoke developed rating measures an area’s
relative visual obscurity from smoke generated by
burning material.
30. Smoke developed rating has limited usability
when a builder decides what materials to use.
97. What are the limitations of smoke detectors?
Door closers can be used with sliding
or swinging fire doors.
98. What are the limitations of smoke detectors?
A self-closing door is normally closed, and when
opened and released will return to the closed position.
99. What are the limitations of smoke detectors?
Door operators open and close a door
for normal use.
100. What are the limitations of smoke detectors?
Glazing can be used in partitions and fire doors
where visibility is desired and a fire rating is
required.
101. What are the limitations of smoke detectors?
The first type of fire-rated glazing
available was wired glass.
102. What are the limitations of smoke detectors?
Modern fire-rated glazing does not
include embedded steel wire.
103. What are the limitations of smoke detectors?
Fire doors are the most common
application of fire-rated glazing.
104. What are the limitations of smoke detectors?
Louvers may be installed in a fire door to permit
ventilation while the door is closed under normal
conditions.
105. What are the limitations of smoke detectors?
For compartmentation to be effect, doors
protecting the openings must operate correctly
under fire conditions.
106. What are the limitations of smoke detectors?
Failure of fire doors to close properly is
a common occurrence in fire conditions.
107. What are the limitations of smoke detectors?
CAUTION
‣ Any fire door can fail and become
nonoperational during a fire. Fire
fighting tactics should include
resources to accommodate a door
fixed in a closed or open position.
108. What are the limitations of smoke detectors?
Fire doors are tested in accordance with
the procedures contained in NFPA® 252.
109. What are the limitations of smoke detectors?
Many of the same laboratories that test interior
finishes and building materials also test fire
doors.
110. What are the limitations of smoke detectors?
The fire door must remain securely in its frame
during the flame test.
111. What are the limitations of smoke detectors?
It is important to keep combustibles away from
permanently closed fire doors in fire walls.
112. What are the limitations of smoke detectors?
There is a second criterion for fire
door acceptability.
113. What are the limitations of smoke detectors?
Fire doors that pass testing are marked with a
label or plate on the top or on the hinge side of
the door.
Courtesy
of
Ed
Prendergast
114. What are the limitations of smoke detectors?
A door’s rating information can help building and
fire inspectors determine the opening’s
protection.
115. What are the limitations of smoke detectors?
CAUTION
‣ Do not assume an assembly is rated
simply because the opening has rated
protection.