Six stored Hospital Building in Dhaka
1. Welcome to the Presentation
about a Hospital Building
STAMFORD UNIVERSITY BANGLADESH
2. Course Title: Computer Aided Structural Design
Course Code : CEN 416
Department of Civil Engineering
Course Teacher: Soumya Suhreed Das
Senior Lecturer,
Department of Civil Engineering
Stamford University Bangladesh
3. Name Student ID
Kauser Ahmed Himel CEN 062 09 446
Nazmul Hasan Diptu CEN 062 09 450
Hasunat Sayemin CEN 062 09 416
Mohammad Amin Jesan CEN 062 09 482
Md. Tanvir Hasan CEN 062 09 475
Md. Sojib Mostofa CEN 062 09 458
Md. Akramul Haque CEN 062 09 503
Group No: 06
37. Manual Hand Calculation:
Z= Zone Coefficient = Zone 2= 0.15
I= Importance Coefficient =1
R =Response modification= 8
S= Site coefficient = 1.5
hn = 66 ft
Ct = 0.03ft
T = Cthn3/4 (<0.7) = 0.03*(66')3/4= 0.694671 S
C= 1.25 S/T2/3 (<2.75) = 1.25*1.5/(0.694671^2/3)=
2.390462
Base shear V=ZIC/R
We cannot calculate Volume V
So, V/W =ZIC/R=0.039841029*100
= 3.984102937
Earthquake Load calculation as per BNBC 2006
39. From Etabs Calculate Base shear
Base Shear: V/W
From Etabs we found, DL=8851.8
FF=2027.05
PW=1217.7
EQx = Eqy = 472.81
W= DL+FF+PW=12096.55
So V/W = 12096.55/472.81 = 0.039086351*100 =3.908635107
Variation = ((3.984102937-3.908635107)/ 3.984102937)*100
= 1.894224% <5% ok
This calculation presents the automatically generated lateral seismic loads for load
pattern EQX & EQY according to UBC 94, as calculated by ETABS.
Earthquake Load calculation as per BNBC 2006