CONTENTS2
►INTRODUCTION
►CODES
►SOFTWARES
►STATEMENT OF PROJECT
►LOADS ON THE STRUCTURES
►OBJECTIVES OF STRUCTURE DESIGN
►DESIGN AND ANALYSIS
►REFERENCES
INTRODUCTION3
 Our project is based on the design and analysis of the multi-storied
buildings
 Analysis is done through using the STAAD-PRO
 Notation adopted through out the project is same as in IS:456-2000
CODES4
►IS-456:2000 :DESIGN CODE FOR RCC STRUCTURES
►IS-875(PART 1) :CODE FOR DEAD LOADS
►IS-875(PART 2) :CODE FOR IMPOSED LOADS
►IS-875(PART 3) :CODE FOR WIND LOADS
►IS-1893-2002: CRITERIA FOR EARTHQUAKE
RESISTANT DESIGN OF STRUCTURES
SOFTWARES5
STAAD.PRO V8i AutoCAD 2014
OBJECTIVES
Carrying out a complete analysis and design of the main
structural elements of a multi-storey building including slabs,
columns, shear walls and foundations.
To learn the concept of lateral and vertical loading on the
building.
Getting familiar with structural softwares ( AutoCAD,
STAAD.Pro).
Getting real life experience with engineering practices
Structural detailing of elements and the system.
6
SALIENT FEATURES7
Location: KOLKATA
Utility of buildings: RESIDENTIAL
Type of construction : RCC FRAMED STRUCTURE
Floor height: 3.0 m
Type of walls : BRICK WALL
AREA
1.5 Acre
8
THE HOUSING COMPLEX(3D)9
DESIGN AND ANALYSIS OF G+5
APARTMENT BLOCK
10
THE FLOOR PLAN OF THE APARTMENT BLOCK
AREA = 3420 sq.ft
11
GEOMETRIC DETAILS12
 Ground floor : 3.0M
 Floor height : 3.0M
 Height of plinth : 1.5M from below
foundation
MATERIAL DETAILS13
 Concrete Grade : M25
 All steel grade : Fe415 grade
 Type of steel bars : HYSD
 Bearing capacity of Soil : >180 KN/M2
DIFFERENT TYPES OF LOADS ON THE
STRUCTURES
14
 Dead loads
 Imposed loads
 Wind loads
 Seismic loads
DEAD LOADS15
Involves self weight of-
 RCC slab
 Beams & columns
 Plinth
 Walls
IMPOSED LOADS16
 Imposed loads also known live loads
 Loads over the floor i.e. Load of persons it is
calculated as 1 KN/m2
 This load is applied over the length of structure
WIND LOADS17
 Wind is air in motion
 Wind loads are calculated according to IS:875(part 3)
 Intensity of wind and exposure are applied in the direction
as required
LOAD COMBINATIONS18
 The structures should be analysed for combination of loads as in practice
we have numbers of loads in various directions act
 Some of the combinations to be checked are
 1.5(DL+LL)
 1.5(DL+WL)
 1.5(DL+LL+WL)
OBJECTIVES OF STRUCTURAL DESIGN
19
 Structure designed should satisfy the criterion of ultimate
strength.
 Structures should satisfy the serviceability.
 It should satisfy the stability against overturning, sliding, and
buckling.
MAIN OBJECTIVES OF THE DESIGN20
 Foundation design
 Column design
 Beam design
 Slab design
DESIGN PRINCIPLE, ASSUMPTION AND NOTATION
ASSUMED
21
 The notation adopted through out the work is same as in IS 456-2000
 Using partial safety factors for loads in accordance with clause 36.4 of IS 456-
2000
 Partial safety factor for material in accordance with clause 36.4.2 IS456-2000 is
taken as 1.5 for concrete and 1.15 for steel
 (D.L+L.L) 1.5
 (D.L +L.L+W.L) 1.2
DENSITY OF MATERIALS USED22
MATERIAL Density
1.Plain concrete 24.0 kn /m3
2.Reinforced 25.0 k /m3
3.Flooring material(c.m) 20.0kn/m3
4.Brick masonry 19.0kn/m3
LIVE LOADS: In accordance with IS 875
1.Live load on slab =3.0kn/m3
2.Live load on passage =3.0kn/m3
3.Live load on stair =3.0kn/m3
ANALYSIS
23
 Analysis is done using STAD PRO developed by BENTLEY
 Once the loads and load combinations are assigned to the structures,
analysis is to be done
 Analysis is done for RCC structure
CENTRE LINE DIAGRAM24
FLOOR SLAB SYSTEM25
GROUP OF SLAB26
Panel No. Lx Ly Ly/Lx Boundary Condition
S1 3.9 4.1 1.05 Two adjacent edges discontinuous
S2 2.9 4.1 1.41 One short end discontinuous
S3 3.6 4.1 1.14 Two adjacent edges discontinuous
S4 2.0 3.9 1.95 One short end discontinuous
S5 2.0 2.9 1.45 Interior panel
S6 2.0 3.6 1.80 Interior panel
27
Effective depth = Lx/(basic L/d ratio×1.5)
Assume a clear cover of 20mm and 8mm ø bars,
Overall depth D’ = dx +20 + 8/2 = dx + 24,
Provide overall depth D,
Effective depth dx = D-24; dy = dx–8; d = (dx + dy )/2;
OVERALL DEPTH CALCULATION28
Panel Lx(mm) Ly(mm) L/d*M.F dx(mm) D’(mm) Dprovided dx dy d
S1 3900 4100 34.5 113.04 137.04 140 116 108 112
S2 2900 4100 34.5 84.06 108.06 110 86 78 82
S3 3600 4100 34.5 104.35 128.35 130 106 98 102
S4 2000 3900 34.5 57.97 81.97 90 66 58 62
S5 2000 2900 30 66.67 90.67 100 76 68 72
S6 2000 3600 30 66.67 90.67 100 76 68 72
For practical purposes, let us provide an overall depth of slab system 140mm.
LOADING ON SLAB29
Self-weight of slab = 0.14 × 25 = 3.5 kN/m2
Load due to floor finishing = 1.5 kN/m2
Self-weight of ceiling plaster = 0.008 × 20 = 0.16 kN/m2
Self-weight partition wall = 1 kN/m2
Live load = 4 kN/m2
Total load = 10.16 kN/m2
Factored load = 15.24 kN/m2
DESIGN MOMENTS30
Panel S1 S2 S3 S4 S5 S6
Load wu(kN) 15.24 15.24 15.24 15.24 15.24 15.24
Span Lx(m) 3.9 2.9 3.6 2.0 2.0 2.0
Short span
moment
coefficient
αx
+ 0.0375 0.0413 0.042 0.0512 0.040 0.0456
αx
- 0.05 0.0552 0.055 0.0672 0.052 0.0608
Long span
moment
coefficient
αy
+ 0.035 0.028 0.035 0.028 0.024 0.024
αy
- 0.047 0.037 0.047 0.037 0.032 0.032
Short span
moments
(kN-m/m)
Mux
+ 8.6925 5.2933 8.2954 3.1211 2.4384 2.7798
Mux
- 11.5900 7.0749 10.8631 4.0965 3.1699 3.7064
Long span
moments
(kN-m/m)
Muy
+ 8.1130 3.5887 6.9129 1.7069 1.4630 1.4630
Muy
- 10.8946 4.7422 9.2830 2.2555 1.9507 1.9507
REINFORCEMENTS DETAILS31
32
PRELIMINARY SIZE DESIGN33
Choosing L/10= d
In longitudinal direction= 3900/10= 390mm= d1
D1= 420mm= 0.42m
In transverse direction= 4100/10= 410mm= d2
D2= 440mm= 0.44m
Let us take a width of 300mm= 0.30m
Member Cross Section c/c
B1,B4,B5,B8,B9,B12,B13,B16,B17,B20,B21,B24,B25,B28,B29,B32 300 x 440 4.1
B33,B34,B35,B36,B37,B63,B64,B65,B66,B67 300 x 420 3.9
B43,B44,B45,B46,B47,B48,B49,B50,B51,B52,B53,B54,B55,B56,B57 300 x 420 3.6
B38,B39,B40,B41,B42, B58,B59,B60,B61,B62 300 x 420 2.9
B2,B3,B6,B7,B10,B11,B14,B15,B18,B19,B22,B23,B26,B27,B30,B31 300 x 440 2.0
PRELIMINARY SIZE CALCULATION OF COLUMNS34
DESIGN OF STAIR35
Height of each flight = 1.5m
Rise = 150mm
Tread = 250mm
Thickness of waist slab = 200mm
Provided 12mmø bars at a clear cover of 15mm.
Provided 8 mm ø bars @ 160mm c/c
UP
WIND LOAD ANALYSIS36
• Design wind speed (Vz)= k1k2k3Vb
Vb= 50 m/s
k1= probability factor (risk coefficient) = 1(Table-1, IS: 875(Part 3)- 1987)
k2= terrain, height, and structure size factor. Our building is in terrain category -2 &
class A(Table-2, IS: 875(Part 3)- 1987)
k3= topography factor= 1(IS: 875(Part 3)- 1987)
Therefore design wind speed= Vz = 50 × 1×k2 × 1
• F= Cf×Ae× pz
F= the force acting in a direction
Cf= Force coefficient for the building.
Ae= effective frontal area.
pz= the total wind load on that particular building or structure
DESIGN WIND SPEED AND PRESSURE37
Height from
ground
k2 Vz (m/s) Pz (kN/m2)
18 1.06 53 1.685
15 1.05 52.5 1.653
12 1.02 51 1.560
9 1.00 50 1.500
6 1.00 50 1.500
3 1.00 50 1.500
FORCE CALCULATION
38
Floor Along short direction
Total Force = 1.19Aepz(kN)
Along long direction
Total Force = 1.05Aepz(kN)
At roof level 1.19x(1+3/2)x24.4x1.685= 122.31 1.05x(1+3/2)x12.2x1.685=53.96
4th 1.19x(2x3/2)x24.4x1.653= 143.99 1.05x(2x3/2)x12.2x1.653= 63.52
3rd 1.19x(2x3/2)x24.4x1.560= 133.66 1.05x(2x3/2)x12.2x1.560= 59.95
2nd 1.19x(2x3/2)x24.4x1.5= 130.662 1.05x(2x3/2)x12.2x1.5= 57.64
1st 1.19x(2x3/2)x24.4x1.5= 130.662 1.05x(2x3/2)x12.2x1.5= 57.64
Ground 1.19x(2x3/2)x24.4x1.5= 130.662 1.05x(2x3/2)x12.2x1.5= 57.64
CALCULATION OF WIND FORCE AT PER FRAME
IN SHORT & LONG DIRECTION
39
Floor pz(kN/m2)
Along short direction Along long direction
Total Force =
1.19Aepz(kN)
Force per
frame(kN)
Total Force =
1.05Aepz(kN)
Force per
frame(kN)
5th 1.685 122.31 15.29 53.96 10.79
4th 1.653 143.99 18.00 63.52 12.70
3rd 1.560 133.66 16.71 59.95 11.99
2nd 1.500 130.662 16.33 57.64 11.53
1st 1.500 130.662 16.33 57.64 11.53
Ground 1.500 130.662 16.33 57.64 11.53
SEISMIC LOAD ANALYSIS
40
• Design seismic load has been calculated by seismic coefficient method
• Total load on roof = 3107.96 kN
• Total loading per floor = 4791.32 kN
• For seismic zone3, the zone factor is 0.16(Table-2, IS: 1893). Being a residential building,
the importance factor is 1(Table 5, IS: 1893-1984)
• The building has a special moment resisting frame and hence R=5.
• Total seismic weight of the structure = 3107.96 + (4791.32×5) = 27064.56 kN
• Design seismic base shear = Vb = 1082.58 kN
LATERAL LOAD DISTRIBUTION AS PER STATIC METHOD41
Floor Height Wi(kN) Wihi
2
𝐖𝐢 𝐡𝐢
𝟐
𝐖𝐢 𝐡𝐢
𝟐
Qi=Vb×
𝐖𝐢
𝐡𝐢
𝟐
𝐖𝐢
𝐡𝐢
𝟐
Roof 18 3107.96 55943.28 0.21 218.13
5th 15 4791.32 71869.80 0.26 280.23
4th 12 4791.32 57495.84 0.21 224.18
3rd 9 4791.32 43121.88 0.16 168.14
2nd 6 4791.32 28747.92 0.11 112.09
1st 3 4791.32 14373.96 0.05 56.05
Total= 271552.68
CALCULATION OF LATERAL FORCE PER FRAME IN
SHORT & LONG DIRECTION
42
Floor
Along short direction Along long direction
Total force(kN)
Force per
frame(kN)
Total force(kN) Force per frame(kN)
Roof 218.13 27.27 218.13 43.63
5th 280.23 35.03 280.23 56.05
4th 224.18 28.02 224.18 44.84
3rd 168.14 21.02 168.14 33.63
2nd 112.09 14.01 112.09 22.42
1st 56.05 7.01 56.05 11.21
DESIGN OF FOUNDATION43
Isolated square foundation would be provided to columns situated along the perimeter
Ultimate load coming on the column = Pu = 1022.91 kN
Approximate weight of the footing @10% of the column load = w’ =102.291 kN
Total load = 1125.201 kN
Safe bearing capacity of soil = 280 kN/m2
Area of the foundation =
1125.20
280
= 4 m2
Side of the footing = 4 = 2 m
Provide a square footing of size 2m×2m.
Net upward pressure intensity =
1125.201×1000
2×2
= 281300.25N/m2
44 Depth from B.M consideration:
Critical section for bending moment is shown in the figure.
Projection beyond critical section =
2000−300
2
= 850 mm
Maximum B.M = M = p0B/8 ×(L-a)2 = 281300.25×2×0.85×0.425 =
203239.4306 Nm
Factored moment = Mu = 1.5×203239.4306 = 304859.1459 Nm
Equating Mu,lim to Mu
0.138fck300d2 = 304859.1459
d = 542.72 mm
Providing 12mmø bars @ a clear cover of 60mm.
Effective cover to upper layer of bars = 60+12+6 = 78mm
Overall depth required = 542.72+78 = 620.72mm
The overall depth may be increased by 30% to limit the shear stresses.
Overall depth = 1.3×643.46 = 806.94mm= 810mm
45
Depth from punching shear consideration:
Punching load = column load – reaction on the column area = 1022910 -(281300.25×0.352) = 988450.7194 N
Factored punching load = 1.5×988450.7194 = 1482676.079 N
Design punching shear stress for M25 concrete= 2.1 N/mm2
Equating punching shear resistance to factored punching load,
4×350×D×2.1 = 1482676.079
D= 504.91 mm
Hence let us provide an overall depth of 840mm as determined earlier.
Actual effective depth = d= 840-78 = 762mm.
Mu/bd2 =
304859.1459×1000
350×762×762
= 1.5
% of steel required, pt = 50[
1− 1−
4.6×1.5
25
415
25
] = 0.45%
Ast = (0.45/100)×350×762 = 1200.15mm2
Provide 12-12mmø (1357.168mm2)
Provide also 12-12mmø in the other principle direction also.
46 The critical section for two-way shear is taken at the periphery surrounding the column at a distance of half the
effective depth from the face of the column.
Overall depth of the footing at a distance (762/2) = 381mm from the column face.
=840 -
(840−400)×381
1022.91
= 676.11mm
Effective depth at this section = d’= 676.11-78 = 598.11mm
Critical parameter = b’ = 4(350+762) = 4448 mm
Shear force at this section = V = 281300.25(22 – .352) = 1090741.719 N
Factored shear = Vu = 1.5 × 1090741.719 = 1636112.58 N
Nominal shear stress = Tv =
1636112.58
4448×598.11
= 0.61 N/mm2
ßc =
𝑠ℎ𝑜𝑟𝑡 𝑠𝑖𝑑𝑒 𝑜𝑓 𝑡ℎ𝑒 𝑐𝑜𝑙𝑢𝑚𝑛 𝑠𝑒𝑐𝑡𝑖𝑜𝑛
𝑙𝑜𝑛𝑔 𝑠𝑖𝑑𝑒 𝑜𝑓 𝑡ℎ𝑒 𝑐𝑜𝑙𝑢𝑚𝑛 𝑠𝑒𝑐𝑡𝑖𝑜𝑛
= 1
Ks = 0.5+ ßc = 1.5
Permissible design shear strength Tc = Ks × .25 𝑓𝑐𝑘 = 1.875 N/mm2
Therefore Ʈv < Ʈc
Check for two-way shear
FOUNDATION REINFORCEMENT47
CONCLUSION & FUTURE SCOPE48
 Using staad.pro software, the design consideration has been taken as
per codes.
 We have only done the design & analysis part of the buildings using
staad.pro & AutoCAD softwares, further we want to design the
building components manually in the future and want to make a
detailed estimation. We would like to compare the design using
software & manually.
REFERENCES49
 Structural analysis by S.RAMAMRUTHAM
 IS456-2000 CODE used
 SP16 CODE used
 AUTO CAD & STAAD PRO packages
 Design of RCC structures by B.C PUNMIA
 IS875, IS 1893-2002
 Various websites
50

More Related Content

What's hot

Group housing case study
Group housing case studyGroup housing case study
Group housing case studyVishwas Sahni
 
LITERATURE REVIEW AND CASE STUDY FOR RESIDENCE DESIGN
LITERATURE REVIEW AND CASE STUDY FOR RESIDENCE DESIGNLITERATURE REVIEW AND CASE STUDY FOR RESIDENCE DESIGN
LITERATURE REVIEW AND CASE STUDY FOR RESIDENCE DESIGNritikchaudhary15
 
PREFABRICATED CONSTRUCTION CASE STUDY: THE HEMISPHERE
PREFABRICATED CONSTRUCTION CASE STUDY: THE HEMISPHEREPREFABRICATED CONSTRUCTION CASE STUDY: THE HEMISPHERE
PREFABRICATED CONSTRUCTION CASE STUDY: THE HEMISPHEREShivangi Saini
 
Tall buildings case studies
Tall buildings   case studiesTall buildings   case studies
Tall buildings case studiesSoumitra Smart
 
basic structural system in architecture
basic structural system in architecturebasic structural system in architecture
basic structural system in architectureshahul130103
 
High-Rise Iconic Buildings
High-Rise Iconic BuildingsHigh-Rise Iconic Buildings
High-Rise Iconic BuildingsDania Abdel-aziz
 
Shell structures- advanced building construction
Shell structures- advanced building constructionShell structures- advanced building construction
Shell structures- advanced building constructionShweta Modi
 
Frank lloyd wright 303
Frank lloyd wright 303Frank lloyd wright 303
Frank lloyd wright 303Mohd Kashif
 
Geodesic Dome - History and Construction
Geodesic Dome - History and ConstructionGeodesic Dome - History and Construction
Geodesic Dome - History and ConstructionAzra Maliha
 
Architectural skills development centre
Architectural skills development centreArchitectural skills development centre
Architectural skills development centrePrachi Gupta
 
Hostel : Literature Study
Hostel : Literature StudyHostel : Literature Study
Hostel : Literature StudyKaranSD2
 

What's hot (20)

Group housing case study
Group housing case studyGroup housing case study
Group housing case study
 
Post slab presentation
Post slab presentationPost slab presentation
Post slab presentation
 
LITERATURE REVIEW AND CASE STUDY FOR RESIDENCE DESIGN
LITERATURE REVIEW AND CASE STUDY FOR RESIDENCE DESIGNLITERATURE REVIEW AND CASE STUDY FOR RESIDENCE DESIGN
LITERATURE REVIEW AND CASE STUDY FOR RESIDENCE DESIGN
 
PREFABRICATED CONSTRUCTION CASE STUDY: THE HEMISPHERE
PREFABRICATED CONSTRUCTION CASE STUDY: THE HEMISPHEREPREFABRICATED CONSTRUCTION CASE STUDY: THE HEMISPHERE
PREFABRICATED CONSTRUCTION CASE STUDY: THE HEMISPHERE
 
Tall buildings case studies
Tall buildings   case studiesTall buildings   case studies
Tall buildings case studies
 
basic structural system in architecture
basic structural system in architecturebasic structural system in architecture
basic structural system in architecture
 
Highrise structure
Highrise structureHighrise structure
Highrise structure
 
High-Rise Iconic Buildings
High-Rise Iconic BuildingsHigh-Rise Iconic Buildings
High-Rise Iconic Buildings
 
Shell structures- advanced building construction
Shell structures- advanced building constructionShell structures- advanced building construction
Shell structures- advanced building construction
 
HOT AND DRY CLIMATE -CASE STUDY
HOT AND DRY CLIMATE -CASE STUDYHOT AND DRY CLIMATE -CASE STUDY
HOT AND DRY CLIMATE -CASE STUDY
 
Frank lloyd wright 303
Frank lloyd wright 303Frank lloyd wright 303
Frank lloyd wright 303
 
Hassan fathy
Hassan fathyHassan fathy
Hassan fathy
 
Waffle slab
Waffle slabWaffle slab
Waffle slab
 
Report on High Rise buildings.
Report  on High Rise buildings.  Report  on High Rise buildings.
Report on High Rise buildings.
 
Geodesic Dome - History and Construction
Geodesic Dome - History and ConstructionGeodesic Dome - History and Construction
Geodesic Dome - History and Construction
 
Charles correa
Charles correaCharles correa
Charles correa
 
Architectural skills development centre
Architectural skills development centreArchitectural skills development centre
Architectural skills development centre
 
The cables structure system
The cables structure systemThe cables structure system
The cables structure system
 
Space frame
Space frameSpace frame
Space frame
 
Hostel : Literature Study
Hostel : Literature StudyHostel : Literature Study
Hostel : Literature Study
 

Similar to Design of housing apartment

60334188-Analysis-and-Design-of-a-Multi-Storey-Reinforced-Concrete.ppt
60334188-Analysis-and-Design-of-a-Multi-Storey-Reinforced-Concrete.ppt60334188-Analysis-and-Design-of-a-Multi-Storey-Reinforced-Concrete.ppt
60334188-Analysis-and-Design-of-a-Multi-Storey-Reinforced-Concrete.pptJarsoBuke
 
Analysis Reinforced Concrete.ppt
Analysis  Reinforced Concrete.pptAnalysis  Reinforced Concrete.ppt
Analysis Reinforced Concrete.pptMOHNIKASAMINENI
 
Chapter 1-types of structures and loads
Chapter 1-types of structures and loadsChapter 1-types of structures and loads
Chapter 1-types of structures and loadsISET NABEUL
 
DESIGN OF G+20 MULTISTOREY BUILDING
DESIGN OF G+20 MULTISTOREY BUILDINGDESIGN OF G+20 MULTISTOREY BUILDING
DESIGN OF G+20 MULTISTOREY BUILDINGAnjneya Srivastava
 
Analysis and Design of Residential building.pptx
Analysis and Design of Residential building.pptxAnalysis and Design of Residential building.pptx
Analysis and Design of Residential building.pptxDP NITHIN
 
Design of Various Types of Industrial Buildings and Their Comparison
Design of Various Types of Industrial Buildings and Their ComparisonDesign of Various Types of Industrial Buildings and Their Comparison
Design of Various Types of Industrial Buildings and Their ComparisonIRJESJOURNAL
 
Wind-Analysis-Building Sdas.ppt
Wind-Analysis-Building Sdas.pptWind-Analysis-Building Sdas.ppt
Wind-Analysis-Building Sdas.pptSougata Das
 
Assignement 2: Structural Analysis
Assignement 2: Structural AnalysisAssignement 2: Structural Analysis
Assignement 2: Structural AnalysisDavidJPCChai
 
Evaluation of Fixed Base vs. Base Isolated Building Systems
Evaluation of Fixed Base vs. Base Isolated Building SystemsEvaluation of Fixed Base vs. Base Isolated Building Systems
Evaluation of Fixed Base vs. Base Isolated Building SystemsIJERD Editor
 
DESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERING
DESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERINGDESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERING
DESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERINGLiyaWilson4
 
COMPARISON BETWEEN VARIOUS STEEL SECTION BY USING IS CODE AND EURO CODE
COMPARISON BETWEEN VARIOUS STEEL SECTION BY USING IS CODE AND EURO CODECOMPARISON BETWEEN VARIOUS STEEL SECTION BY USING IS CODE AND EURO CODE
COMPARISON BETWEEN VARIOUS STEEL SECTION BY USING IS CODE AND EURO CODEIRJET Journal
 
analysis and design of telecommunication tower
analysis and design of telecommunication toweranalysis and design of telecommunication tower
analysis and design of telecommunication towerRohithasangaraju
 
Example314b taskgroupb-c-120730160543-phpapp01
Example314b taskgroupb-c-120730160543-phpapp01Example314b taskgroupb-c-120730160543-phpapp01
Example314b taskgroupb-c-120730160543-phpapp01Ramil Artates
 
final internship ppt.pptx
final internship ppt.pptxfinal internship ppt.pptx
final internship ppt.pptxKiranKr32
 

Similar to Design of housing apartment (20)

G.p presentation
G.p presentationG.p presentation
G.p presentation
 
60334188-Analysis-and-Design-of-a-Multi-Storey-Reinforced-Concrete.ppt
60334188-Analysis-and-Design-of-a-Multi-Storey-Reinforced-Concrete.ppt60334188-Analysis-and-Design-of-a-Multi-Storey-Reinforced-Concrete.ppt
60334188-Analysis-and-Design-of-a-Multi-Storey-Reinforced-Concrete.ppt
 
Analysis Reinforced Concrete.ppt
Analysis  Reinforced Concrete.pptAnalysis  Reinforced Concrete.ppt
Analysis Reinforced Concrete.ppt
 
Fianl Year Project.pptx
Fianl Year Project.pptxFianl Year Project.pptx
Fianl Year Project.pptx
 
Chapter 1-types of structures and loads
Chapter 1-types of structures and loadsChapter 1-types of structures and loads
Chapter 1-types of structures and loads
 
Reinforced Concrete.ppt
Reinforced Concrete.pptReinforced Concrete.ppt
Reinforced Concrete.ppt
 
DESIGN OF G+20 MULTISTOREY BUILDING
DESIGN OF G+20 MULTISTOREY BUILDINGDESIGN OF G+20 MULTISTOREY BUILDING
DESIGN OF G+20 MULTISTOREY BUILDING
 
Analysis and Design of Residential building.pptx
Analysis and Design of Residential building.pptxAnalysis and Design of Residential building.pptx
Analysis and Design of Residential building.pptx
 
ppt.pptx
ppt.pptxppt.pptx
ppt.pptx
 
Design of Various Types of Industrial Buildings and Their Comparison
Design of Various Types of Industrial Buildings and Their ComparisonDesign of Various Types of Industrial Buildings and Their Comparison
Design of Various Types of Industrial Buildings and Their Comparison
 
Wind-Analysis-Building Sdas.ppt
Wind-Analysis-Building Sdas.pptWind-Analysis-Building Sdas.ppt
Wind-Analysis-Building Sdas.ppt
 
Assignement 2: Structural Analysis
Assignement 2: Structural AnalysisAssignement 2: Structural Analysis
Assignement 2: Structural Analysis
 
Evaluation of Fixed Base vs. Base Isolated Building Systems
Evaluation of Fixed Base vs. Base Isolated Building SystemsEvaluation of Fixed Base vs. Base Isolated Building Systems
Evaluation of Fixed Base vs. Base Isolated Building Systems
 
unit-3.ppt
unit-3.pptunit-3.ppt
unit-3.ppt
 
DESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERING
DESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERINGDESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERING
DESIGN OF DECK SLAB AND GIRDERS- BRIDGE ENGINEERING
 
COMPARISON BETWEEN VARIOUS STEEL SECTION BY USING IS CODE AND EURO CODE
COMPARISON BETWEEN VARIOUS STEEL SECTION BY USING IS CODE AND EURO CODECOMPARISON BETWEEN VARIOUS STEEL SECTION BY USING IS CODE AND EURO CODE
COMPARISON BETWEEN VARIOUS STEEL SECTION BY USING IS CODE AND EURO CODE
 
analysis and design of telecommunication tower
analysis and design of telecommunication toweranalysis and design of telecommunication tower
analysis and design of telecommunication tower
 
Example314b taskgroupb-c-120730160543-phpapp01
Example314b taskgroupb-c-120730160543-phpapp01Example314b taskgroupb-c-120730160543-phpapp01
Example314b taskgroupb-c-120730160543-phpapp01
 
final internship ppt.pptx
final internship ppt.pptxfinal internship ppt.pptx
final internship ppt.pptx
 
Rectangular tank
Rectangular tankRectangular tank
Rectangular tank
 

Recently uploaded

CBD Belapur Individual Call Girls In 08976425520 Panvel Only Genuine Call Girls
CBD Belapur Individual Call Girls In 08976425520 Panvel Only Genuine Call GirlsCBD Belapur Individual Call Girls In 08976425520 Panvel Only Genuine Call Girls
CBD Belapur Individual Call Girls In 08976425520 Panvel Only Genuine Call Girlsmodelanjalisharma4
 
VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...
VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...
VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...Call Girls in Nagpur High Profile
 
Petrosains Drama Competition (PSDC).pptx
Petrosains Drama Competition (PSDC).pptxPetrosains Drama Competition (PSDC).pptx
Petrosains Drama Competition (PSDC).pptxIgnatiusAbrahamBalin
 
The_Canvas_of_Creative_Mastery_Newsletter_April_2024_Version.pdf
The_Canvas_of_Creative_Mastery_Newsletter_April_2024_Version.pdfThe_Canvas_of_Creative_Mastery_Newsletter_April_2024_Version.pdf
The_Canvas_of_Creative_Mastery_Newsletter_April_2024_Version.pdfAmirYakdi
 
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service 🧵
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service  🧵CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service  🧵
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service 🧵anilsa9823
 
Peaches App development presentation deck
Peaches App development presentation deckPeaches App development presentation deck
Peaches App development presentation decktbatkhuu1
 
AMBER GRAIN EMBROIDERY | Growing folklore elements | Root-based materials, w...
AMBER GRAIN EMBROIDERY | Growing folklore elements |  Root-based materials, w...AMBER GRAIN EMBROIDERY | Growing folklore elements |  Root-based materials, w...
AMBER GRAIN EMBROIDERY | Growing folklore elements | Root-based materials, w...BarusRa
 
Kurla Call Girls Pooja Nehwal📞 9892124323 ✅ Vashi Call Service Available Nea...
Kurla Call Girls Pooja Nehwal📞 9892124323 ✅  Vashi Call Service Available Nea...Kurla Call Girls Pooja Nehwal📞 9892124323 ✅  Vashi Call Service Available Nea...
Kurla Call Girls Pooja Nehwal📞 9892124323 ✅ Vashi Call Service Available Nea...Pooja Nehwal
 
Escorts Service Basapura ☎ 7737669865☎ Book Your One night Stand (Bangalore)
Escorts Service Basapura ☎ 7737669865☎ Book Your One night Stand (Bangalore)Escorts Service Basapura ☎ 7737669865☎ Book Your One night Stand (Bangalore)
Escorts Service Basapura ☎ 7737669865☎ Book Your One night Stand (Bangalore)amitlee9823
 
Design Inspiration for College by Slidesgo.pptx
Design Inspiration for College by Slidesgo.pptxDesign Inspiration for College by Slidesgo.pptx
Design Inspiration for College by Slidesgo.pptxTusharBahuguna2
 
VIP Kolkata Call Girl Gariahat 👉 8250192130 Available With Room
VIP Kolkata Call Girl Gariahat 👉 8250192130  Available With RoomVIP Kolkata Call Girl Gariahat 👉 8250192130  Available With Room
VIP Kolkata Call Girl Gariahat 👉 8250192130 Available With Roomdivyansh0kumar0
 
DragonBall PowerPoint Template for demo.pptx
DragonBall PowerPoint Template for demo.pptxDragonBall PowerPoint Template for demo.pptx
DragonBall PowerPoint Template for demo.pptxmirandajeremy200221
 
VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130
VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130
VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130Suhani Kapoor
 
Fashion trends before and after covid.pptx
Fashion trends before and after covid.pptxFashion trends before and after covid.pptx
Fashion trends before and after covid.pptxVanshNarang19
 
Verified Trusted Call Girls Adugodi💘 9352852248 Good Looking standard Profil...
Verified Trusted Call Girls Adugodi💘 9352852248  Good Looking standard Profil...Verified Trusted Call Girls Adugodi💘 9352852248  Good Looking standard Profil...
Verified Trusted Call Girls Adugodi💘 9352852248 Good Looking standard Profil...kumaririma588
 
SD_The MATATAG Curriculum Training Design.pptx
SD_The MATATAG Curriculum Training Design.pptxSD_The MATATAG Curriculum Training Design.pptx
SD_The MATATAG Curriculum Training Design.pptxjanettecruzeiro1
 
Kala jadu for love marriage | Real amil baba | Famous amil baba | kala jadu n...
Kala jadu for love marriage | Real amil baba | Famous amil baba | kala jadu n...Kala jadu for love marriage | Real amil baba | Famous amil baba | kala jadu n...
Kala jadu for love marriage | Real amil baba | Famous amil baba | kala jadu n...babafaisel
 
Booking open Available Pune Call Girls Nanded City 6297143586 Call Hot India...
Booking open Available Pune Call Girls Nanded City  6297143586 Call Hot India...Booking open Available Pune Call Girls Nanded City  6297143586 Call Hot India...
Booking open Available Pune Call Girls Nanded City 6297143586 Call Hot India...Call Girls in Nagpur High Profile
 
WAEC Carpentry and Joinery Past Questions
WAEC Carpentry and Joinery Past QuestionsWAEC Carpentry and Joinery Past Questions
WAEC Carpentry and Joinery Past QuestionsCharles Obaleagbon
 

Recently uploaded (20)

CBD Belapur Individual Call Girls In 08976425520 Panvel Only Genuine Call Girls
CBD Belapur Individual Call Girls In 08976425520 Panvel Only Genuine Call GirlsCBD Belapur Individual Call Girls In 08976425520 Panvel Only Genuine Call Girls
CBD Belapur Individual Call Girls In 08976425520 Panvel Only Genuine Call Girls
 
VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...
VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...
VVIP Pune Call Girls Hadapsar (7001035870) Pune Escorts Nearby with Complete ...
 
Petrosains Drama Competition (PSDC).pptx
Petrosains Drama Competition (PSDC).pptxPetrosains Drama Competition (PSDC).pptx
Petrosains Drama Competition (PSDC).pptx
 
The_Canvas_of_Creative_Mastery_Newsletter_April_2024_Version.pdf
The_Canvas_of_Creative_Mastery_Newsletter_April_2024_Version.pdfThe_Canvas_of_Creative_Mastery_Newsletter_April_2024_Version.pdf
The_Canvas_of_Creative_Mastery_Newsletter_April_2024_Version.pdf
 
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service 🧵
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service  🧵CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service  🧵
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service 🧵
 
Peaches App development presentation deck
Peaches App development presentation deckPeaches App development presentation deck
Peaches App development presentation deck
 
young call girls in Vivek Vihar🔝 9953056974 🔝 Delhi escort Service
young call girls in Vivek Vihar🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Vivek Vihar🔝 9953056974 🔝 Delhi escort Service
young call girls in Vivek Vihar🔝 9953056974 🔝 Delhi escort Service
 
AMBER GRAIN EMBROIDERY | Growing folklore elements | Root-based materials, w...
AMBER GRAIN EMBROIDERY | Growing folklore elements |  Root-based materials, w...AMBER GRAIN EMBROIDERY | Growing folklore elements |  Root-based materials, w...
AMBER GRAIN EMBROIDERY | Growing folklore elements | Root-based materials, w...
 
Kurla Call Girls Pooja Nehwal📞 9892124323 ✅ Vashi Call Service Available Nea...
Kurla Call Girls Pooja Nehwal📞 9892124323 ✅  Vashi Call Service Available Nea...Kurla Call Girls Pooja Nehwal📞 9892124323 ✅  Vashi Call Service Available Nea...
Kurla Call Girls Pooja Nehwal📞 9892124323 ✅ Vashi Call Service Available Nea...
 
Escorts Service Basapura ☎ 7737669865☎ Book Your One night Stand (Bangalore)
Escorts Service Basapura ☎ 7737669865☎ Book Your One night Stand (Bangalore)Escorts Service Basapura ☎ 7737669865☎ Book Your One night Stand (Bangalore)
Escorts Service Basapura ☎ 7737669865☎ Book Your One night Stand (Bangalore)
 
Design Inspiration for College by Slidesgo.pptx
Design Inspiration for College by Slidesgo.pptxDesign Inspiration for College by Slidesgo.pptx
Design Inspiration for College by Slidesgo.pptx
 
VIP Kolkata Call Girl Gariahat 👉 8250192130 Available With Room
VIP Kolkata Call Girl Gariahat 👉 8250192130  Available With RoomVIP Kolkata Call Girl Gariahat 👉 8250192130  Available With Room
VIP Kolkata Call Girl Gariahat 👉 8250192130 Available With Room
 
DragonBall PowerPoint Template for demo.pptx
DragonBall PowerPoint Template for demo.pptxDragonBall PowerPoint Template for demo.pptx
DragonBall PowerPoint Template for demo.pptx
 
VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130
VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130
VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130
 
Fashion trends before and after covid.pptx
Fashion trends before and after covid.pptxFashion trends before and after covid.pptx
Fashion trends before and after covid.pptx
 
Verified Trusted Call Girls Adugodi💘 9352852248 Good Looking standard Profil...
Verified Trusted Call Girls Adugodi💘 9352852248  Good Looking standard Profil...Verified Trusted Call Girls Adugodi💘 9352852248  Good Looking standard Profil...
Verified Trusted Call Girls Adugodi💘 9352852248 Good Looking standard Profil...
 
SD_The MATATAG Curriculum Training Design.pptx
SD_The MATATAG Curriculum Training Design.pptxSD_The MATATAG Curriculum Training Design.pptx
SD_The MATATAG Curriculum Training Design.pptx
 
Kala jadu for love marriage | Real amil baba | Famous amil baba | kala jadu n...
Kala jadu for love marriage | Real amil baba | Famous amil baba | kala jadu n...Kala jadu for love marriage | Real amil baba | Famous amil baba | kala jadu n...
Kala jadu for love marriage | Real amil baba | Famous amil baba | kala jadu n...
 
Booking open Available Pune Call Girls Nanded City 6297143586 Call Hot India...
Booking open Available Pune Call Girls Nanded City  6297143586 Call Hot India...Booking open Available Pune Call Girls Nanded City  6297143586 Call Hot India...
Booking open Available Pune Call Girls Nanded City 6297143586 Call Hot India...
 
WAEC Carpentry and Joinery Past Questions
WAEC Carpentry and Joinery Past QuestionsWAEC Carpentry and Joinery Past Questions
WAEC Carpentry and Joinery Past Questions
 

Design of housing apartment

  • 1.
  • 2. CONTENTS2 ►INTRODUCTION ►CODES ►SOFTWARES ►STATEMENT OF PROJECT ►LOADS ON THE STRUCTURES ►OBJECTIVES OF STRUCTURE DESIGN ►DESIGN AND ANALYSIS ►REFERENCES
  • 3. INTRODUCTION3  Our project is based on the design and analysis of the multi-storied buildings  Analysis is done through using the STAAD-PRO  Notation adopted through out the project is same as in IS:456-2000
  • 4. CODES4 ►IS-456:2000 :DESIGN CODE FOR RCC STRUCTURES ►IS-875(PART 1) :CODE FOR DEAD LOADS ►IS-875(PART 2) :CODE FOR IMPOSED LOADS ►IS-875(PART 3) :CODE FOR WIND LOADS ►IS-1893-2002: CRITERIA FOR EARTHQUAKE RESISTANT DESIGN OF STRUCTURES
  • 6. OBJECTIVES Carrying out a complete analysis and design of the main structural elements of a multi-storey building including slabs, columns, shear walls and foundations. To learn the concept of lateral and vertical loading on the building. Getting familiar with structural softwares ( AutoCAD, STAAD.Pro). Getting real life experience with engineering practices Structural detailing of elements and the system. 6
  • 7. SALIENT FEATURES7 Location: KOLKATA Utility of buildings: RESIDENTIAL Type of construction : RCC FRAMED STRUCTURE Floor height: 3.0 m Type of walls : BRICK WALL
  • 10. DESIGN AND ANALYSIS OF G+5 APARTMENT BLOCK 10
  • 11. THE FLOOR PLAN OF THE APARTMENT BLOCK AREA = 3420 sq.ft 11
  • 12. GEOMETRIC DETAILS12  Ground floor : 3.0M  Floor height : 3.0M  Height of plinth : 1.5M from below foundation
  • 13. MATERIAL DETAILS13  Concrete Grade : M25  All steel grade : Fe415 grade  Type of steel bars : HYSD  Bearing capacity of Soil : >180 KN/M2
  • 14. DIFFERENT TYPES OF LOADS ON THE STRUCTURES 14  Dead loads  Imposed loads  Wind loads  Seismic loads
  • 15. DEAD LOADS15 Involves self weight of-  RCC slab  Beams & columns  Plinth  Walls
  • 16. IMPOSED LOADS16  Imposed loads also known live loads  Loads over the floor i.e. Load of persons it is calculated as 1 KN/m2  This load is applied over the length of structure
  • 17. WIND LOADS17  Wind is air in motion  Wind loads are calculated according to IS:875(part 3)  Intensity of wind and exposure are applied in the direction as required
  • 18. LOAD COMBINATIONS18  The structures should be analysed for combination of loads as in practice we have numbers of loads in various directions act  Some of the combinations to be checked are  1.5(DL+LL)  1.5(DL+WL)  1.5(DL+LL+WL)
  • 19. OBJECTIVES OF STRUCTURAL DESIGN 19  Structure designed should satisfy the criterion of ultimate strength.  Structures should satisfy the serviceability.  It should satisfy the stability against overturning, sliding, and buckling.
  • 20. MAIN OBJECTIVES OF THE DESIGN20  Foundation design  Column design  Beam design  Slab design
  • 21. DESIGN PRINCIPLE, ASSUMPTION AND NOTATION ASSUMED 21  The notation adopted through out the work is same as in IS 456-2000  Using partial safety factors for loads in accordance with clause 36.4 of IS 456- 2000  Partial safety factor for material in accordance with clause 36.4.2 IS456-2000 is taken as 1.5 for concrete and 1.15 for steel  (D.L+L.L) 1.5  (D.L +L.L+W.L) 1.2
  • 22. DENSITY OF MATERIALS USED22 MATERIAL Density 1.Plain concrete 24.0 kn /m3 2.Reinforced 25.0 k /m3 3.Flooring material(c.m) 20.0kn/m3 4.Brick masonry 19.0kn/m3 LIVE LOADS: In accordance with IS 875 1.Live load on slab =3.0kn/m3 2.Live load on passage =3.0kn/m3 3.Live load on stair =3.0kn/m3
  • 23. ANALYSIS 23  Analysis is done using STAD PRO developed by BENTLEY  Once the loads and load combinations are assigned to the structures, analysis is to be done  Analysis is done for RCC structure
  • 26. GROUP OF SLAB26 Panel No. Lx Ly Ly/Lx Boundary Condition S1 3.9 4.1 1.05 Two adjacent edges discontinuous S2 2.9 4.1 1.41 One short end discontinuous S3 3.6 4.1 1.14 Two adjacent edges discontinuous S4 2.0 3.9 1.95 One short end discontinuous S5 2.0 2.9 1.45 Interior panel S6 2.0 3.6 1.80 Interior panel
  • 27. 27 Effective depth = Lx/(basic L/d ratio×1.5) Assume a clear cover of 20mm and 8mm ø bars, Overall depth D’ = dx +20 + 8/2 = dx + 24, Provide overall depth D, Effective depth dx = D-24; dy = dx–8; d = (dx + dy )/2;
  • 28. OVERALL DEPTH CALCULATION28 Panel Lx(mm) Ly(mm) L/d*M.F dx(mm) D’(mm) Dprovided dx dy d S1 3900 4100 34.5 113.04 137.04 140 116 108 112 S2 2900 4100 34.5 84.06 108.06 110 86 78 82 S3 3600 4100 34.5 104.35 128.35 130 106 98 102 S4 2000 3900 34.5 57.97 81.97 90 66 58 62 S5 2000 2900 30 66.67 90.67 100 76 68 72 S6 2000 3600 30 66.67 90.67 100 76 68 72 For practical purposes, let us provide an overall depth of slab system 140mm.
  • 29. LOADING ON SLAB29 Self-weight of slab = 0.14 × 25 = 3.5 kN/m2 Load due to floor finishing = 1.5 kN/m2 Self-weight of ceiling plaster = 0.008 × 20 = 0.16 kN/m2 Self-weight partition wall = 1 kN/m2 Live load = 4 kN/m2 Total load = 10.16 kN/m2 Factored load = 15.24 kN/m2
  • 30. DESIGN MOMENTS30 Panel S1 S2 S3 S4 S5 S6 Load wu(kN) 15.24 15.24 15.24 15.24 15.24 15.24 Span Lx(m) 3.9 2.9 3.6 2.0 2.0 2.0 Short span moment coefficient αx + 0.0375 0.0413 0.042 0.0512 0.040 0.0456 αx - 0.05 0.0552 0.055 0.0672 0.052 0.0608 Long span moment coefficient αy + 0.035 0.028 0.035 0.028 0.024 0.024 αy - 0.047 0.037 0.047 0.037 0.032 0.032 Short span moments (kN-m/m) Mux + 8.6925 5.2933 8.2954 3.1211 2.4384 2.7798 Mux - 11.5900 7.0749 10.8631 4.0965 3.1699 3.7064 Long span moments (kN-m/m) Muy + 8.1130 3.5887 6.9129 1.7069 1.4630 1.4630 Muy - 10.8946 4.7422 9.2830 2.2555 1.9507 1.9507
  • 32. 32
  • 33. PRELIMINARY SIZE DESIGN33 Choosing L/10= d In longitudinal direction= 3900/10= 390mm= d1 D1= 420mm= 0.42m In transverse direction= 4100/10= 410mm= d2 D2= 440mm= 0.44m Let us take a width of 300mm= 0.30m Member Cross Section c/c B1,B4,B5,B8,B9,B12,B13,B16,B17,B20,B21,B24,B25,B28,B29,B32 300 x 440 4.1 B33,B34,B35,B36,B37,B63,B64,B65,B66,B67 300 x 420 3.9 B43,B44,B45,B46,B47,B48,B49,B50,B51,B52,B53,B54,B55,B56,B57 300 x 420 3.6 B38,B39,B40,B41,B42, B58,B59,B60,B61,B62 300 x 420 2.9 B2,B3,B6,B7,B10,B11,B14,B15,B18,B19,B22,B23,B26,B27,B30,B31 300 x 440 2.0
  • 35. DESIGN OF STAIR35 Height of each flight = 1.5m Rise = 150mm Tread = 250mm Thickness of waist slab = 200mm Provided 12mmø bars at a clear cover of 15mm. Provided 8 mm ø bars @ 160mm c/c UP
  • 36. WIND LOAD ANALYSIS36 • Design wind speed (Vz)= k1k2k3Vb Vb= 50 m/s k1= probability factor (risk coefficient) = 1(Table-1, IS: 875(Part 3)- 1987) k2= terrain, height, and structure size factor. Our building is in terrain category -2 & class A(Table-2, IS: 875(Part 3)- 1987) k3= topography factor= 1(IS: 875(Part 3)- 1987) Therefore design wind speed= Vz = 50 × 1×k2 × 1 • F= Cf×Ae× pz F= the force acting in a direction Cf= Force coefficient for the building. Ae= effective frontal area. pz= the total wind load on that particular building or structure
  • 37. DESIGN WIND SPEED AND PRESSURE37 Height from ground k2 Vz (m/s) Pz (kN/m2) 18 1.06 53 1.685 15 1.05 52.5 1.653 12 1.02 51 1.560 9 1.00 50 1.500 6 1.00 50 1.500 3 1.00 50 1.500
  • 38. FORCE CALCULATION 38 Floor Along short direction Total Force = 1.19Aepz(kN) Along long direction Total Force = 1.05Aepz(kN) At roof level 1.19x(1+3/2)x24.4x1.685= 122.31 1.05x(1+3/2)x12.2x1.685=53.96 4th 1.19x(2x3/2)x24.4x1.653= 143.99 1.05x(2x3/2)x12.2x1.653= 63.52 3rd 1.19x(2x3/2)x24.4x1.560= 133.66 1.05x(2x3/2)x12.2x1.560= 59.95 2nd 1.19x(2x3/2)x24.4x1.5= 130.662 1.05x(2x3/2)x12.2x1.5= 57.64 1st 1.19x(2x3/2)x24.4x1.5= 130.662 1.05x(2x3/2)x12.2x1.5= 57.64 Ground 1.19x(2x3/2)x24.4x1.5= 130.662 1.05x(2x3/2)x12.2x1.5= 57.64
  • 39. CALCULATION OF WIND FORCE AT PER FRAME IN SHORT & LONG DIRECTION 39 Floor pz(kN/m2) Along short direction Along long direction Total Force = 1.19Aepz(kN) Force per frame(kN) Total Force = 1.05Aepz(kN) Force per frame(kN) 5th 1.685 122.31 15.29 53.96 10.79 4th 1.653 143.99 18.00 63.52 12.70 3rd 1.560 133.66 16.71 59.95 11.99 2nd 1.500 130.662 16.33 57.64 11.53 1st 1.500 130.662 16.33 57.64 11.53 Ground 1.500 130.662 16.33 57.64 11.53
  • 40. SEISMIC LOAD ANALYSIS 40 • Design seismic load has been calculated by seismic coefficient method • Total load on roof = 3107.96 kN • Total loading per floor = 4791.32 kN • For seismic zone3, the zone factor is 0.16(Table-2, IS: 1893). Being a residential building, the importance factor is 1(Table 5, IS: 1893-1984) • The building has a special moment resisting frame and hence R=5. • Total seismic weight of the structure = 3107.96 + (4791.32×5) = 27064.56 kN • Design seismic base shear = Vb = 1082.58 kN
  • 41. LATERAL LOAD DISTRIBUTION AS PER STATIC METHOD41 Floor Height Wi(kN) Wihi 2 𝐖𝐢 𝐡𝐢 𝟐 𝐖𝐢 𝐡𝐢 𝟐 Qi=Vb× 𝐖𝐢 𝐡𝐢 𝟐 𝐖𝐢 𝐡𝐢 𝟐 Roof 18 3107.96 55943.28 0.21 218.13 5th 15 4791.32 71869.80 0.26 280.23 4th 12 4791.32 57495.84 0.21 224.18 3rd 9 4791.32 43121.88 0.16 168.14 2nd 6 4791.32 28747.92 0.11 112.09 1st 3 4791.32 14373.96 0.05 56.05 Total= 271552.68
  • 42. CALCULATION OF LATERAL FORCE PER FRAME IN SHORT & LONG DIRECTION 42 Floor Along short direction Along long direction Total force(kN) Force per frame(kN) Total force(kN) Force per frame(kN) Roof 218.13 27.27 218.13 43.63 5th 280.23 35.03 280.23 56.05 4th 224.18 28.02 224.18 44.84 3rd 168.14 21.02 168.14 33.63 2nd 112.09 14.01 112.09 22.42 1st 56.05 7.01 56.05 11.21
  • 43. DESIGN OF FOUNDATION43 Isolated square foundation would be provided to columns situated along the perimeter Ultimate load coming on the column = Pu = 1022.91 kN Approximate weight of the footing @10% of the column load = w’ =102.291 kN Total load = 1125.201 kN Safe bearing capacity of soil = 280 kN/m2 Area of the foundation = 1125.20 280 = 4 m2 Side of the footing = 4 = 2 m Provide a square footing of size 2m×2m. Net upward pressure intensity = 1125.201×1000 2×2 = 281300.25N/m2
  • 44. 44 Depth from B.M consideration: Critical section for bending moment is shown in the figure. Projection beyond critical section = 2000−300 2 = 850 mm Maximum B.M = M = p0B/8 ×(L-a)2 = 281300.25×2×0.85×0.425 = 203239.4306 Nm Factored moment = Mu = 1.5×203239.4306 = 304859.1459 Nm Equating Mu,lim to Mu 0.138fck300d2 = 304859.1459 d = 542.72 mm Providing 12mmø bars @ a clear cover of 60mm. Effective cover to upper layer of bars = 60+12+6 = 78mm Overall depth required = 542.72+78 = 620.72mm The overall depth may be increased by 30% to limit the shear stresses. Overall depth = 1.3×643.46 = 806.94mm= 810mm
  • 45. 45 Depth from punching shear consideration: Punching load = column load – reaction on the column area = 1022910 -(281300.25×0.352) = 988450.7194 N Factored punching load = 1.5×988450.7194 = 1482676.079 N Design punching shear stress for M25 concrete= 2.1 N/mm2 Equating punching shear resistance to factored punching load, 4×350×D×2.1 = 1482676.079 D= 504.91 mm Hence let us provide an overall depth of 840mm as determined earlier. Actual effective depth = d= 840-78 = 762mm. Mu/bd2 = 304859.1459×1000 350×762×762 = 1.5 % of steel required, pt = 50[ 1− 1− 4.6×1.5 25 415 25 ] = 0.45% Ast = (0.45/100)×350×762 = 1200.15mm2 Provide 12-12mmø (1357.168mm2) Provide also 12-12mmø in the other principle direction also.
  • 46. 46 The critical section for two-way shear is taken at the periphery surrounding the column at a distance of half the effective depth from the face of the column. Overall depth of the footing at a distance (762/2) = 381mm from the column face. =840 - (840−400)×381 1022.91 = 676.11mm Effective depth at this section = d’= 676.11-78 = 598.11mm Critical parameter = b’ = 4(350+762) = 4448 mm Shear force at this section = V = 281300.25(22 – .352) = 1090741.719 N Factored shear = Vu = 1.5 × 1090741.719 = 1636112.58 N Nominal shear stress = Tv = 1636112.58 4448×598.11 = 0.61 N/mm2 ßc = 𝑠ℎ𝑜𝑟𝑡 𝑠𝑖𝑑𝑒 𝑜𝑓 𝑡ℎ𝑒 𝑐𝑜𝑙𝑢𝑚𝑛 𝑠𝑒𝑐𝑡𝑖𝑜𝑛 𝑙𝑜𝑛𝑔 𝑠𝑖𝑑𝑒 𝑜𝑓 𝑡ℎ𝑒 𝑐𝑜𝑙𝑢𝑚𝑛 𝑠𝑒𝑐𝑡𝑖𝑜𝑛 = 1 Ks = 0.5+ ßc = 1.5 Permissible design shear strength Tc = Ks × .25 𝑓𝑐𝑘 = 1.875 N/mm2 Therefore Ʈv < Ʈc Check for two-way shear
  • 48. CONCLUSION & FUTURE SCOPE48  Using staad.pro software, the design consideration has been taken as per codes.  We have only done the design & analysis part of the buildings using staad.pro & AutoCAD softwares, further we want to design the building components manually in the future and want to make a detailed estimation. We would like to compare the design using software & manually.
  • 49. REFERENCES49  Structural analysis by S.RAMAMRUTHAM  IS456-2000 CODE used  SP16 CODE used  AUTO CAD & STAAD PRO packages  Design of RCC structures by B.C PUNMIA  IS875, IS 1893-2002  Various websites
  • 50. 50