Cataloge ge 3.control and_automation-12_vat300_e_c4-5_rev_a
1. 4. Operation Panel
4-5 Changing modes
The parameters used differ according to the control mode (C30-0:f0).
The parameters include the V/f control, the IM vector control (sensor-less, with sensor) and the PM
motor control with sensor.
These parameters are divided into the block No. (mode), main No. and sub-No. for each function.
4-5-1 V/f control (C30-0 f0 = 1) mode
The configuration of the parameters is shown in Fig. 4-5-1.
4 – 27
Output frequency monitor (d00-0, 1, 4, 5)
Frequency setting monitor (d01-0, 1, 4)
Current monitor (d02-0 to 4, 7 to 9)
Voltage monitor (d03-0 to 3)
Sequence status (d04-0 to 7)
Minor fault monitor (d05-0, 1)
Pattern run monitor (d06-0, 1)
Pump operation status monitor (d07-0 to 4)
Analog input random scale display (d08-0 to 2)
Input display (d08-3 to C)
Built-in PLC monitor (d10-0 to 3)
STP run monitor (d13-0 to 5)
Extended monitor (d20-0 to 4)
Maintenance monitor (d21-0 to 3)
Automatic tuning (d22-0)
Hardware monitor (d30-0 to 5)
Mode
Monitor mode : Monitors (displays) the internal status.
Knob or
Key
(Continued on next page)
Fig. 4-5-1 (1) Parameter configuration
RST
MOD
Key
Frequency setting (A00-0, 1)
Acceleration/deceleration time (A01-0, 1)
Torque boost (A02-0 to 6)
DC Brake (A03-0, 1)
Custom parameters (A04-0 to 7)
Parameter B and C indicatory skip (A05-0 to 2)
Block-A Parameter Mode
Fault history monitor
Minor failure past record
indication
Parameter A, B and C
modification list entry
Sequence input display
(dedicated for LCD panel)
Sequence output display
(dedicated for LCD panel)
Knob or
Key
: Parameters changed frequently
during the normal usage state.
2. 4. Operation Panel
Fig. 4-5-1 (2) Parameter configuration
4 – 28
Basic function settings
Output rating (B00-0 to 7)
Motor circuit constant (IM) (B02-0, 1, 4, 5)
Frequency skip (B05-0 to 5)
Gearing comparative setting (B06-0, 1, 3, 4, 6, 7, 9, A, C, D)
Upper/Lower limit setting (B07-0, 1)
Extended function settings
: Parameters changed infrequently during the normal usage
state
(Continued on next page)
Acceleration/deceleration time setting (B10-0 to 6)
Program frequency (speed) setting (B11-0 to 8)
Automatic braking on power failure setting (B12-0 to 6)
V/f middle point setting (B17-0 to B)
Current limit (B18-0 to 8)
Automatic tuning function (B19-0 to 2)
Auxiliary drive 0 exclusive setting (B20-0 to B23-4)
Auxiliary drive 1 exclusive setting (B24-0 to B27-4)
Auxiliary drive 2 exclusive setting (B28-0 to B2B-4)
Auxiliary drive 3 exclusive setting (B2C-0 to B2F-4)
Speed control extended function (B30-4)
Software option function settings
Software option function (B40-0)
Program ramp – acceleration (B41-0 to 7)
Program ramp – deceleration (B42-0 to 7)
PID control (B43-0 to A)
Multi-pump control (B44-0 to 6)
Traverse run (B45-0 to 6)
External brake control (B46-0 to 5)
Simple ASR control (B47-0 to 6)
Pattern run (B50-0 to B59-3)
Spinning frame operation (B60-0 to B76-6)
Block-B Parameter Mode
Knob or
Key
RST
MOD
Key
3. 4. Operation Panel
(Note) At the default setting, only the basic functions are displayed. The extended function, software
option function, hardware option function parameters are skipped.
Thus, to change these parameters, change parameter A05-0 to 2 (parameter B, C block skip
setting), so that the target parameters are displayed.
Fig. 4-5-1 (3) Parameter configuration
4 – 29
Start interlock (C20-0 to 3)
Retry/pick-up (C21-0 to 4)
Overload (C22-0 to 7)
Speed detection error monitor (C24-1 to 3)
High-efficiency operation (C25-0 to 2)
Standard serial (C26-0 to 7)
Password No. (C28-0, 1)
Basic function settings
Control methods (C00-0 to 7)
Start/stop frequency (C01-0, 1)
Various setting input selection (C02-0, 1)
Sequence input terminal function – 1 (C03-0 to F)
Sequence input terminal function – 2 (C04-0 to F)
Sequence input terminal function – 3 (C05-0 to F)
Analog input terminal function (C07-0 to 5)
Automatic start setting (C08-0)
Parameter protection/operation locks (C09-0 to 4, 6, 7)
Custom parameter register (C10-0 to 7)
Operation panel mode setting (C11-0 to 7)
Setting input terminal function (C12-0 to F)
Output terminal function (C13-0 to F)
Meter output gain (C14-0 to B)
Status output detection level (C15-0 to E)
: Parameters changed infrequently during the normal usage
state
Block-C Parameter Mode
Hardware option function setting
Control mode selection (C30-0)
Main circuit option selection (C31-0 to 3)
PC (parallel) interface (future) (C32-0 to 2)
Sequence output terminal function (C33-0 to 3)
Field network interface (C34-0 to 7)
Encoder setting 1 (C50-0 to 3)
Extended function setting
Parameter Control (U00-0)
Password No. setting (U00-1)
Built-in PLC setting (U10-0 to U67-7)
Knob or
Key
RST
MOD
Key
Utility mode U
4. 4. Operation Panel
4-5-2 IM speed sensor-less vector control (C30-0 f0 = 2),
IM vector control with speed sensor (C30-0 f0 = 3)
The configuration of the parameters is shown in Fig. 4-5-2.
Fig. 4-5-2 (1) Parameter configuration
4 – 30
Output frequency monitor (d00-0 to 5)
Frequency setting monitor (d01-2 to 4)
Current monitor (d02-0 to 9)
Voltage monitor (d03-0 to 3)
Sequence status (d04-0 to 7)
Minor fault monitor (d05-0, 1)
Pattern run monitor (d06-0, 1)
Analog input random scale display (d08-0 to 2)
Input display (d08-3 to C)
Built-in PLC monitor (d10-0 to 3)
Torque setting monitor (d11-0 to 5)
Slip (d12-0)
Automatic torque bias (d14-0)
Extended monitor (d20-0 to 4)
Maintenance monitor (d21-0 to 3)
Automatic tuning (d22-0)
Hardware monitor (d30-0 to 5)
Mode
Monitor mode : Monitors (displays) the internal status.
: Parameters changed frequently during the normal
usage state.
Frequency setting (A00-2 to 3)
Acceleration/deceleration time (A01-0, 1)
DC Brake (A03-1 to 2)
Custom parameters (A04-0 to 7)
Parameter B and C indicatory skip (A05-0 to 2)
ASR control constant (A10-0 to 5)
ACR control constant (A11-0 to 3)
Knob or
Key
Knob or
Key
RST
MOD
Key
Block-A Parameter Mode
Fault history monitor
Minor failure past record
indication
Parameter A, B and C
modification list entry
Sequence input display
(dedicated for LCD panel)
Sequence output display
(dedicated for LCD panel)
(Continued on next page)
5. 4. Operation Panel
Fig. 4-5-2 (2) Parameter configuration
4 – 31
Output rating (B01-0 to 9)
Motor circuit constant (IM) (B02-0 to 9)
Gearing comparative setting (B06-0, 2, 3, 5, 6, 8, 9, B, C, E)
Upper/Lower limit setting (B07-2, 3)
Basic function settings
Software option function settings
Software option function (B40-0)
Program ramp – acceleration (B41-0 to 7)
Program ramp – deceleration (B42-0 to 7)
PID control (B43-0 to A)
Traverse run (B45-0 to 6)
External brake control (B46-0 to 5)
Pattern run (B50-0 to B59-3)
Extended function setting
Acceleration/deceleration time setting (B10-0 to 6)
Program frequency (speed) setting (B11-0 to 8)
Automatic braking on power failure setting (B12-0, 1)
Local setting (B13-0 to 9)
ASR dead band setting (B14-0)
Machine time constant setting 2 (B15-0)
Automatic torque bias setting (B16-0 to B)
Current limit (B18-0 to 8)
Automatic tuning function (B19-0 to 2)
Auxiliary drive 0 exclusive setting (B20-0 to B23-4)
Auxiliary drive 1 exclusive setting (B24-0 to B27-4)
Auxiliary drive 2 exclusive setting (B28-0 to B2B-4)
Auxiliary drive 3 exclusive setting (B2C-0 to B2F-4)
Speed control extended function (B30-0 to 8)
Sensor-less control function (B31-0 to 6)
Vector control compensation selection (B32-0 to 4)
M fluctuation compensation table reference speed (B33-0 to 7)
M fluctuation compensation (B34-0 to 7)
: Parameters changed infrequently during the normal
usage state
(Continued on next page)
Knob or
Key
RST
MOD
Key
Block-B Parameter Mode
6. 4. Operation Panel
(Note) At the default setting, only the basic functions are displayed. The extended function, software
option function, hardware option function parameters are skipped.
Thus, to change these parameters, change parameter A05-0 to 2 (parameter B, C block skip
setting), so that the target parameters are displayed.
Fig. 4-5-2 (3) Parameter configuration
4 – 32
Basic function settings
Control methods (C00-0 to 7)
Various setting input selection (C02-0 to 8)
Sequence input terminal function – 1 (C03-0 to F)
Sequence input terminal function – 2 (C04-0 to F)
Sequence input terminal function – 3 (C05-0 to F)
Sequence input terminal function – 4 (C06-0 to A)
Analog input terminal function (C07-0 to A)
Automatic start setting (C08-0)
Parameter protection/operation locks (C09-0 to 7)
Custom parameter register (C10-0 to 7)
Operation panel mode setting (C11-0 to 7)
Setting input terminal function (C12-0 to F)
Output terminal function (C13-0 to F)
Meter output gain (C14-0 to B)
Status output detection level (C15-0 to E)
: Parameters changed infrequently during the normal
usage state
Block-C Parameter Mode
Hardware option function settings
Control mode selection (C30-0)
Main circuit option selection (C31-0 to 3)
PC (parallel) interface (future) (C32-0 to 2)
Sequence output terminal function (C33-0 to 3)
Field network interface (C34-0 to 7)
Encoder setting (C50-0 to 3)
Start interlock (C20-0 to 3)
Retry/pick-up (C21-0 to 3, 5 to 7)
Overload (C22-0 to 7)
Speed detection error monitor (C24-0 to 7)
High-efficiency operation (C25-0 to 2)
Standard serial (C26-0 to 7)
Password No. (C28-0, 1)
Extend function settings
Parameter Control (U00-0)
Password No. setting (U00-1)
Built-in PLC setting (U10-0 to U67-7)
Utility mode U
Knob or
Key
RST
MOD
Key
7. 4. Operation Panel
4-5-3 PM motor control mode with sensor (C30-0 f0 = 4)
The configuration of the parameters is shown in Fig. 4-5-3.
4 – 33
Output frequency monitor (d00-0 to 5)
Frequency setting monitor (d01-2 to 4)
Current monitor (d02-0 to 9)
Voltage monitor (d03-0 to 3)
Sequence status (d04-0 to 7)
Minor fault monitor (d05-0, 1)
Pattern run monitor (d06-0, 1)
Analog input random scale display (d08-0 to 2)
Input display (d08-3 to C)
Built-in PLC monitor (d10-0 to 3)
Torque setting monitor (d11-0 to 5)
Automatic torque bias (d14-0)
Electric angle monitor (d15-0)
Magnetic pole position estimation monitor(d16-0 to 3)
Extended monitor (d20-0 to 4)
Maintenance monitor (d21-0 to 3)
Hardware monitor (d30-0 to 5)
: Monitors (displays) the internal status.
(Continued on next page)
: Parameters changed frequently during the normal
usage state.
Frequency setting (A00-2, 3)
Acceleration/deceleration time (A01-0, 1)
DC Brake (A03-1, 2)
Custom parameters (A04-0 to 7)
Parameter B and C indicatory skip (A05-0 to 2)
ASR control constant (A10-0 to 5)
ACR control constant (A11-2, 3)
ACR control constant (PM motor) (A20-0 to 3)
Fig. 4-5-3 (1) Parameter configuration
Knob or
Key
Block-A Parameter Mode
Knob or
Key
RST
MOD
Key
Mode
Monitor mode
Fault history monitor
Minor failure past record
indication
Parameter A, B and C
modification list entry
Sequence input display
(dedicated for LCD panel)
Sequence output display
(dedicated for LCD panel)
8. 4. Operation Panel
Fig. 4-5-3 (2) Parameter configuration
4 – 34
Basic function settings
Software option function settings
Software option function (B40-0)
Program ramp – acceleration (B41-0 to 7)
Program ramp – deceleration (B42-0 to 7)
PID control (B43-0 to A)
Traverse run (B45-0 to 6)
External brake control (B46-0 to 5)
Pattern run (B50-0 to B59-3)
Extended function setting
Acceleration/deceleration time setting (B10-0 to 6)
Program frequency (speed) setting (B11-0 to 8)
Automatic braking on power failure setting (B12-0, 1)
Local setting (B13-0 to 9)
ASR dead band setting (B14-0)
Machine time constant setting 2 (B15-0)
Automatic torque bias setting (B16-0 to B)
Current limit (B18-0 to 8)
Automatic tuning function (B19-0)
Auxiliary drive 0 exclusive setting (B20-0 to B23-4)
Auxiliary drive 1 exclusive setting (B24-0 to B27-4)
Auxiliary drive 2 exclusive setting (B28-0 to B2B-4)
Auxiliary drive 3 exclusive setting (B2C-0 to B2F-4)
Speed control extended function (B30-0 to 8)
Vector control compensation selection (B32-4 to 6)
Voltage saturation prevention control constant (B35-0 to 4)
Field weakening electric current table (B36-0 to 6)
Torque to Iq conversion adjustment coefficient table (B38-0 to 6)
Pole position presumption (B39-0 to 5)
: Parameters changed infrequently during the normal
usage state
Block-B Parameter Mode
(Continued on next page)
Output rating (B01-0 to 9)
Motor circuit constant (PM) (B03-0 to 5)
Gearing comparative setting (B06-0, 2, 3, 5, 6, 8, 9, B, C, E)
Upper/Lower limit setting (B07-2, 3)Knob or
Key
RST
MOD
Key
9. 4. Operation Panel
(Note) At the default setting, only the basic functions are displayed. The extended function, software
option function, hardware option function parameters are skipped.
Thus, to change these parameters, change parameter A05-0 to 2 (parameter B, C block skip
setting), so that the target parameters are displayed.
Fig. 4-5-3 (3) Parameter configuration
4 – 35
Control methods (C00-0 to 7)
Various setting input selection (C02-0 to 8)
Sequence input terminal function – 1 (C03-0 to F)
Sequence input terminal function – 2 (C04-0 to F)
Sequence input terminal function – 3 (C05-0 to F)
Sequence input terminal function – 4 (C06-1 to A)
Analog input terminal function (C07-0 to A)
Automatic start setting (C08-0)
Parameter protection/operation locks (C09-0 to 7)
Custom parameter register (C10-0 to 7)
Operation panel mode setting (C11-0 to 7)
Setting input terminal function (C12-0 to F)
Output terminal function (C13-0 to F)
Meter output gain (C14-0 to B)
Status output detection level (C15-0 to E)
Start interlock (C20-0 to 3)
Retry/pick-up (C21-0 to 3)
Overload (C22-0 to 7)
Speed detection error monitor (C24-0 to 2, 4 to 7)
High-efficiency operation (C25-0 to 2)
Standard serial transmission setting (C26-0 to 7)
Password No. (C28-0, 1)
Basic function settings
: Parameters changed infrequently during the normal
usage state
Block-C Parameter Mode
Hardware option function settings
Control mode selection (C30-0)
Main circuit option selection (C31-0 to 3)
PC (parallel) interface (future) (C32-0 to 2)
Sequence output terminal function (C33-0 to 3)
Field network interface (C34-0 to 7)
Encoder setting (C50-0, 2, 3)
Encoder setting (PM motor) (C51-0 to 9)
Extend function settings
Parameter Control (U00-0)
Password No. setting (U00-1)
Built-in PLC setting (U10-0 to U67-7)
Knob or
Key
RST
MOD
Key
Utility mode U
10. 4. Operation Panel
(Note) At the default setting, only the basic functions are displayed. The extended function, software
option function, hardware option function parameters are skipped.
Thus, to change these parameters, change parameter A05-0 to 2 (parameter B, C block skip
setting), so that the target parameters are displayed.
Fig. 4-5-3 (3) Parameter configuration
4 – 35
Control methods (C00-0 to 7)
Various setting input selection (C02-0 to 8)
Sequence input terminal function – 1 (C03-0 to F)
Sequence input terminal function – 2 (C04-0 to F)
Sequence input terminal function – 3 (C05-0 to F)
Sequence input terminal function – 4 (C06-1 to A)
Analog input terminal function (C07-0 to A)
Automatic start setting (C08-0)
Parameter protection/operation locks (C09-0 to 7)
Custom parameter register (C10-0 to 7)
Operation panel mode setting (C11-0 to 7)
Setting input terminal function (C12-0 to F)
Output terminal function (C13-0 to F)
Meter output gain (C14-0 to B)
Status output detection level (C15-0 to E)
Start interlock (C20-0 to 3)
Retry/pick-up (C21-0 to 3)
Overload (C22-0 to 7)
Speed detection error monitor (C24-0 to 2, 4 to 7)
High-efficiency operation (C25-0 to 2)
Standard serial transmission setting (C26-0 to 7)
Password No. (C28-0, 1)
Basic function settings
: Parameters changed infrequently during the normal
usage state
Block-C Parameter Mode
Hardware option function settings
Control mode selection (C30-0)
Main circuit option selection (C31-0 to 3)
PC (parallel) interface (future) (C32-0 to 2)
Sequence output terminal function (C33-0 to 3)
Field network interface (C34-0 to 7)
Encoder setting (C50-0, 2, 3)
Encoder setting (PM motor) (C51-0 to 9)
Extend function settings
Parameter Control (U00-0)
Password No. setting (U00-1)
Built-in PLC setting (U10-0 to U67-7)
Knob or
Key
RST
MOD
Key
Utility mode U