RESIDENCE
GUNER
P0.1
PLUMBING GENERAL
NOTES
PLUMBING GENERAL NOTES
1. THE ARCHITECTURAL DESIGN DRAWINGS SHALL INDICATE THE
EXACT LOCATIONS AND MOUNTING HEIGHTS OF ALL PLUMBING
FIXTURES.
2. THE ARCHITECTURAL DESIGN DRAWINGS SHALL INDICATE ALL
ACCESSIBLE FIXTURE LOCATIONS AND MOUNTING HEIGHTS.
FURNISH ALL EXPOSED HOT WATER AND DRAIN PIPING BELOW
ACCESSIBLE LAVATORIES AND SINKS WITH INSULATION. ALL
WATER CLOSET FLUSHING LEVERS SHALL BE TO THE WIDE SIDE
OF THE STALL.
3. TRAPS FOR ALL LAVATORIES AND SINKS SHALL TRAP STRAIGHT
BACK TO WALL WITH ALL REQUIRED OFFSETS HAPPENING
WITHIN THE WALL.
4. ALL PLUMBING WORK SHALL BE INSTALLED TO AVOID
INTERFERENCE WITH ELECTRICAL AND MECHANICAL
EQUIPMENT AND STRUCTURAL FRAMING.
5. ALL CLEANOUTS SHALL BE INSTALLED WHERE EASILY
ACCESSIBLE. THE CONTRACTOR SHALL COORDINATE ALL
CLEANOUT LOCATIONS WITH ALL EQUIPMENT, CABINETS AND
OTHER OBSTRUCTION PRIOR TO ANY INSTALLATION.
CLEANOUTS MUST BE EXTENDED TO FLUSH WITH FINISHED
WALL.
6. ALL PLUMBING FIXTURE VENTS SHALL TERMINATE A MINIMUM OF
12 INCHES FROM ANY VERTICAL SURFACE AND 10 FEET FROM
ANY OUTSIDE AIR INTAKES.
7. ALL VALVES, UNIONS, ETC. TO BE SAME SIZE AS PIPE UNLESS
OTHERWISE INDICATED ON PLANS.
8. UNIONS SHALL BE PROVIDED AND INSTALLED AFTER EACH
VALVE AND PRIOR TO ALL EQUIPMENT CONNECTIONS.
9. ALL WORK AND MATERIAL SHALL BE IN COMPLIANCE WITH AND
PERFORMED AND INSTALLED INCOMFORMANCE WITH THE
FOLLOWING CODES AS ADOPTED AND AMENDED BY THE
INSPECTING AUTHORITY. NOTHING IN THESE DRAWINGS IS TO BE
CONSTRUED TO PERMIT WORK NOT CONFORMING TO THESE
CODES OR OTHERS APPLICABLE TO THIS PROJECT:
BUILDING STANDARDS ADMINISTRATIVE CODE, PART 1, TITLE 24
C.C.R. 2013 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24
C.C.R.
2013 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24
C.C.R.
2013 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24
C.C.R.
2013 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R.
2013 CALIFORNIA ENERGY CODE, PART 6, TITLE 24 C.C.R.
2013 CALIFORNIA FIRE CODE (CFC), PART 9, TITLE 24 C.C.R.,
2013 CALIFORNIA REFERENCED STANDARDS, PART 12, TITLE 24
C.C.R. 2013 TITLE 19, CCR, PUBLIC SAFETY, STATE FIRE
MARSHAL REGULATIONS 2013 NFPA 13 - AUTOMATIC SPRINKLER
SYSTEMS
10. BEFORE FABRICATION OR INSTALLATION THE CONTRACTOR
SHALL VERIFY EXACT LOCATIONS OF ALL MECHANICAL
EQUIPMENT AND EQUIPMENT PROVIDED UNDER OTHER
SECTIONS OF SPECIFICATIONS. ROUGH-IN LOCATIONS AND
REQUIREMENTS SHALL BE COORDINATED IN THE FIELD.
11. ALL SEWER AND VENT PIPING SHALL SLOPE AT 2%.
12. ALL VALVES, TRAP PRIMERS, WATER HAMMER ARRESTERS OR
OTHER EQUIPMENT LOCATED IN WALLS OR ABOVE
NON-ACCESSIBLE CEILINGS SHALL BE INSTALLED BEHIND AN
ACCESS PANEL. ALL PIPING & DEVICES SHALL BE INSTALLED
ABOVE CEILING, WITHIN WALLS, BELOW FLOORS, OR OTHERWISE
CONCEALED. EXCEPT PIPING AND DEVICES INSTALLED IN
MECHANICAL ROOMS AND OTHER UNFINISHED SPACES.
13. ALL PLUMBING FIXTURES AND EQUIPMENT SHALL BE CERTIFIED
BY THE CALIFORNIA STATE ENERGY COMMISSION TO COMPLY
WITH EFFICIENCY STANDARDS PER SECTION 110 OF THE
TITLE-24 REGULATIONS.
14. ALL HOT WATER SUPPLY & RETURN PIPING SHALL BE
INSULATED. INSULATION SHALL HAVE A FLAME SPREAD OF NOT
MORE THAN 25 AND A SMOKE DENSITY NOT EXCEEDING 50 PER
CMC SEC. 12.1.2.1.8 SEE SPECIFICATION FOR OTHER
REQUIREMENTS.
15. PIPING THROUGH FIRE RATED WALLS SHALL BE PROTECTED PER
U.L. FIRE RESISTANCE SYSTEM NO. WL1001. THE
ARCHITECTURAL DESIGN DRAWINGS SHALL INDICATE ALL
RATED WALL LOCATIONS.
16. SEISMIC BRACING AND ANCHORAGE REQUIREMENTS ARE AS
FOLLOWS:
A. THE SEISMIC ANCHORAGE FOR ALL MECHANICAL AND
ELECTRICAL EQUIPMENT SHALL BE DESIGNED TO
WITHSTAND A LATERAL FORCE:
1. CALCULATED AS SPECIFIED IN SECTION 1632A AND TABLE
16A-0 OF THE VOL. 2, TITLE 24, 2013 CBC.
B. THE ATTACHMENT OF THE FOLLOWING ITEMS SHALL BE
DESIGNED TO RESIST THE FORCES PRESCRIBED IN PART 2,
TITLE 24, 2013 CBC:
1. EQUIPMENT WEIGHING LESS THAN 400 LBS. SUPPORTED
DIRECTLY ON FLOOR OR ROOF.
2. FURNITURE REQUIRED TO BE ATTACHED IN ACCORDANCE
WITH PART 2, TITLE 24, C.C.R.
3. TEMPORARY OR MOBILE EQUIPMENT.
4. EQUIPMENT WEIGHING LESS THAN 20 LBS. SUPPORTED BY
VIBRATION ISOLATORS.
5. EQUIPMENT WEIGHING LESS THAN 20 LBS. SUSPENDED
FROM A ROOF OR HUNG FROM A WALL.
17. THE PLUMBING CONTRACTOR SHALL PROVIDE THE WATER &
SEWER SYSTEMS TO A POINT OF CONNECTION 5'-0" OUTSIDE OF
THE BUILDING. PIPING BEYOND THIS POINT IS SPECIFIED UNDER
ANOTHER SECTION OF THE SPECIFICATIONS AND SHALL BE AS
SHOWN ON THE CIVIL DRAWINGS. FINAL CONNECTIONS TO SITE
PIPING SHALL BE BY THE PLUMBING CONTRACTOR.
18. WATER HAMMER ARRESTERS SHALL BE PROVIDED WHERE
REQUIRED AND NECESSARY FOR AND TO ALL FIXTURES,
EQUIPMENT OR APPLIANCES WITH QUICK CLOSING VALVE AND
SHALL BE OF TYPE SPECIFIED.
19. ALL PIPE SIZES SHALL BE THE SAME AS THE UPSTREAM PIPE
SIZES UNLESS OTHERWISE INDICATED ON PLAN.
20. CLEANOUT SHALL BE PROVIDED AS PER CPC SECTION 707.
21. NO STRUCTURAL MEMBER SHALL BE CUT, NEITHER DRILLED
NOR NOTCHED 24. WITHOUT PRIOR WRITTEN AUTHORIZATION
FROM THE STRUCTURAL ENGINEER.
22. THESE DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC AND ARE
NOT INTENDED TO INDICATE ALL DETAILS AND NECESSARY
OFFSETS OF PIPING. THE CONTRACTOR SHALL INSTALL
MATERIAL AND EQUIPMENT IN A MANNER AS TO CONFORM TO
STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE HEADROOM,
AND KEEP OPENINGS AND PASSAGEWAYS CLEAR. ALL
INSTALLATIONS SHALL BE CONSISTENT WITH NORMALLY
ACCEPTABLE INDUSTRY STANDARDS. THE CONTRACTOR SHALL
NOTIFY THE ARCHITECT IN WRITING OF ANY DISCREPANCIES OR
CONFLICTS THAT WOULD EFFECT THE SYSTEM PERFORMANCE
OR INCUR ADDITIONAL COSTS. THIS NOTIFICATION SHALL BE
SUBMITTED PRIOR TO INSTALLATION OF THE ITEMS
CONCERNED.
23. NOT USED
24. PROVIDE COMPLETE CONDENSATE DRAIN PIPING FOR ALL AC
UNITS AND DISCHARGE CONDENSATE TO AN APPROVED
RECEPTOR.
25. ALL LAYOUTS, PIPE SIZES, FIXTURE & EQUIPMENT SELECTIONS
SHOWN ON THESE PLANS ARE FOR REFERENCE ONLY. THE
CONTRACTOR SHALL PROVIDE A COMPLETE PLUMBING SYSTEM.
THE DESIGN, CALCULATIONS, FIXTURE, TRIM, EQUIPMENT AND
MATERIALS SELECTIONS & DRAWINGS SHALL BE SUBMITTED
FOR REVIEW AND APPROVAL AS SPECIFIED.
26. INSULATION THICKNESS AND R-VALUES SHALL EXCEED THE
REQUIREMENTS OF TITLE 24 BY AT LEAST 20 PERCENT OR NEXT
LARGER STANDARD SIZE, WHICH EVER IS GREATER. PIPE
INSULATION SHALL BE NOT LESS THAN 1.0 INCH THICK, NOT
INCLUDING THE MOISTURE BARRIER OR EXTERIOR JACKET
THICKNESS.
27. ALL GAS PRESSURE REGULATOR SHALL BE LOCATED AT
GROUND LEVEL OR CLOSE TO APPLIANCE AND LOCATIONS
SHALL BE COORDINATED WITH THE ARCHITECT FOR APPROVAL.
SIZE AND INSTALLATION SHALL BE AS PER MANUFACTURER'S
RECOMMENDATIONS. NO MEDIUM PRESSURE GAS INSIDE THE
BUILDING.
28. NO GAS & WATER PIPE SHALL BE INSTALLED UNDER BUILDING
SLAB. GAS & WATER PIPES SHALL RISE TIGHT AGAINST
EXTERIOR WALL UP TO MIN. 18" AFF AND PENETRATE INTO
BUILDING. PROVIDE SHUT-OFF VALVE AND REGULATOR ABOVE
GRADE AT INCOMING GAS RISERS.
29. CONTRACTOR SHALL CAREFULLY REVIEW THESE PLANS AND
SPECIFICATIONS PRIOR TO BID. CONTRACTOR SHALL ALSO
REVIEW PLANS AND SPECIFICATIONS OF OTHER RELATED
TRADES (INCLUDING MECHANICAL, CIVIL, STRUCTURAL, AND
ELECTRICAL) PRIOR TO BID TO INSURE AN ACCURATE
UNDERSTANDING OF EXACT SCOPE OF WORK. ANY ITEMS
REQUIRING DESCRIPTION CLARIFICATION SHALL BE BROUGHT
TO THE ATTENTION OF THE ARCHITECT IN SUFFICIENT TIME TO
BE INCORPORATED INTO THE BID.
30. ALL PLUMBING SYSTEM COMPONENTS SHALL MEET OR EXCEED
THE REQUIREMENTS OF C.B.C. (CALIFORNIA EDITION), CMC, CPC,
NEC, NFPA, ASTM, ANSI, AND ALL LOCAL AND STATE CODE
REQUIREMENTS.
31. ALL PLUMBING EQUIPMENT LISTED IN (CCR) SECTION 113 OF THE
2013 CALIFORNIA CODE OF REGULATIONS, TITLE-24, PART 1,
ENERGY EFFICIENCY STANDARDS MUST BE CERTIFIED BY THE
MANUFACTURER TO MEET OR EXCEED SPECIFICATIONS OR
EFFICIENCIES ADOPTED BY THE CEC.
32. ALL PIPING EXPOSED TO WEATHER SHALL BE METALLIC.
33. ALL FERROUS PIPING EXPOSED TO WEATHER SHALL BE
GALVANIZED.
34. ALL PIPES, FITTINGS AND FIXTURES USED TO CONVEY POTABLE
WATER SHALL BE LEAD FREE IN COMPLIANCE WITH CALIFORNIA
AB 1953.
35. ALL INSULATING MATERIALS INSTALLED MUST BE CERTIFIED BY
CALIFORNIA ENERGY COMMISSION TO MEET C.E.C. ENERGY
EFFICIENCY STANDARDS (E.E.S.) SECTION 120.3 AND SECTION
1201.3.2.1.1 OF CMC (CALIFORNIA EDITION).
36. ALL INSULATION INSTALLED SHALL MEET THE FLAME SPREAD
AND SMOKE DENSITY REQUIREMENTS OF SECTION 719 OF THE
2013 CBC.
37. ALL GAS APPLIANCES MUST HAVE PILOTLESS IGNITION SYSTEM
IN ACCORDANCE WITH SECTION 115 OF THE 2013 CALIFORNIA
CODE OF REGULATIONS, TITLE-24, PART 1, ENERGY EFFICIENCY
STANDARDS, TABLE 4-4.
38. ALL FIXTURES REQUIRED TO BE ACCESSIBLE SHALL BE
INSTALLED AS PER THE LATEST REQUIREMENTS OF TITLE 24
AND ADA (AMERICANS WITH DISABILITIES ACT).
39. CROSS CONNECTION PROTECTION SHALL BE PROVIDED AT ALL
POTABLE WATER SUPPLIED APPLIANCES AND EQUIPMENT
(OTHER THAN THOSE LISTED IN INFORMATION BULLETIN 103).
40. ALL HEATERS FOR DOMESTIC HOT WATER MUST BE CERTIFIED
BY THE MANUFACTURER TO MEET THE SPECIFICATIONS OR
EFFICIENCIES AS ADOPTED BY THE CEC. IN ACCORDANCE WITH
SECTION 110.1 OF THE CCR AND ENERGY EFFICIENCY
STANDARDS RESIDENTIAL NON-RESIDENTIAL.
41. A WATER HEATER PRESSURE AND TEMPERATURE RELIEF DRAIN
THAT TERMINATES OUTSIDE THE BUILDING SHALL COMPLY WITH
SECTION 608.5 OF CPC.
42. WATER HEATER SHALL BE ANCHORED OR STRAPPED TO RESIST
HORIZONTAL DISPLACEMENT DUE TO EARTHQUAKE MOTION PER
SECTION 508.2 OF CPC.
43. WATER HEATER SHALL COMPLY WITH SECTION 608.3 OF CPC,
FOR THERMAL EXPANSION REQUIREMENTS.
44. LAVATORY FAUCETS IN PUBLIC RESTROOM SHALL BE SELF
CLOSING TYPE.
45. NON RESIDENTIAL LAVATORY FAUCETS SHALL BE 0.4 GPM
MAXIMUM.
46. METERING FAUCETS SHALL BE 0.5 GPM MAXIMUM.
47. KITCHEN FAUCETS AND WASH FOUNTAINS SHALL BE 1.8 GPM
MAXIMUM.
48. WATER CLOSETS (GRAVITY TANK TYPE, FLUSHOMETER TANK,
FLUSHOMETER VALVE AND ELECTROMECHANICAL HYDRAULIC
TYPE) SHALL BE 1.28 GPF MAXIMUM.
49. URINALS SHALL BE 0.5 GPF MAXIMUM.
DENTAL AIR
POINT OF CONNECTION / POINT OF DISCONNECTION
PLUMBING LEGEND
DWG/DWGS DRAWING/DRAWINGS
PSI POUNDS PER SQUARE INCH
POUNDS PER SQUARE INCH
EQUIPMENT IDENTIFICATION SYMBOL
W.C.
SOV
VTR
SQ FT
TYP
SPEC
P&TRV
QTY
WATER COLUMN
PRESSURE AND TEMPERATURE RELIEF VALVE
SHUT OFF VALVE
VENT THRU ROOF
SQUARE FEET
TYPICAL
SPECIFICATION
QUANTITY
GALV GALVANIZED
PD
OPER
NTS
MTD
MIN
MS
MECH
MAX
IPS
I.E.
HD
MOP SINK / SERVICE SINK
PRESSURE DROP
NOT TO SCALE
OPERATING
MOUNTED
MINIMUM
MECHANICAL
MAXIMUM
IRON PIPE SIZE
INVERT ELEVATION
HEAD
FT HD
GPM
GA
GPF
FH
FT
FFE
ELECT
ELEV
EA
DN
GALLONS PER MINUTE
GALLONS PER FLUSH
FINISHED FLOOR ELEVATION
FEET OF HEAD
GAUGE
FUME HOOD
FEET
DEGREES FAHRENHEIT
ELECTRICAL
ELEVATION
EACH
DOWN
AFF
B/G
B/S
C.I.
DF
B/C
ARCH
AFG
FS
SOV
GPR
FD
ABOVE FINISHED FLOOR
ARCHITECT OR ARCHITECTURAL
ABOVE FINISHED GRADE
BELOW GRADE
DRINKING FOUNTAIN
CAST IRON
BELOW SLAB
BELOW COUNTER
GAS PRESSURE REGULATOR
PLUG VALVE / GAS COCK
PRESSURE GUAGE
SHUT OFF VALVE
FLOOR SINK
FLOOR DRAIN
FCO/COTG
WCO
WHA
CD CD
DIRECTION OF FLOW
PIPE SLOPE & DIRECTION OF FALL
FLOOR CLEANOUT OR CLEANOUT TO GRADE
WATER HAMMER ARRESTOR
WALL CLEANOUT
PIPE CONTINUATION
PIPE BREAK
THERMOMETER
CONDENSATE DRAIN PIPING
PIPE BRANCH - TOP CONNECTION
PIPE BRANCH - BOTTOM CONNECTION
PIPE BRANCH - SIDE CONNECTION
PIPE CAP
PIPE DOWN
PIPE UP
DCA
G
HW
G
HWR
DCA
VT
CW
SYMBOL
W
POC/POD
W
ABBREVIATION
DOMESTIC HOT WATER RETURN
DOMESTIC COLD WATER PIPING
NATURAL GAS PIPING - 8" WATER COLUMN
DOMESTIC HOT WATER
SANITARY VENT PIPING
SANITARY OR WASTE PIPING
EQUIPMENT IDENTIFIER
EQUIPMENT TYPE
DESCRIPTION
DVAC DVAC DENTAL VACUUM
HB (+18")
PW W PRESSURIZED WASTE PIPING
M
RESIDENCE
GUNER
P0.2
PLUMBING
CALCULATIONS
AND EQUIPMENT
SCHEDULES
PLUMBING FIXTURE SCHEDULE
ITEM WASTE TRAP VENT CW HW MOUNT DESCRIPTION
4" 4" 2" 1
2" -- FLOOR
WATER CLOSET (FLUSH TANK): "TOTO" MS970CEMFG WASHLET WITH
INTEGRATED G500, 1.28 GPF AND 0.9 GPF. DUAL FLUSH, ELONGATED
BOWL, 12" ROUGH-IN.
2" 2" 2" 1
2" 1
2" FLOOR
BATHTUB: SEE ARCHITECTURAL SPECIFICATIONS
2" 2" 2" 1
2" 1
2" FLOOR
BATHTUB: SEE ARCHITECTURAL SPECIFICATIONS
2" 2" 2" 1
2" 1
2" FLOOR
6 SHOWER HEAD: SEE ARCH PLANS FOR TILED SHOWER, PROVIDE
FITTINGS "KOHLER" K-13688 SHALL HAVE A FLOW OF 2.5 GPM.
PROVIDE DIVERTER VALVE CONTROL 3 SHOWER HEAD ONLY. PIPE
6 SHOWER HEAD TO HAVE 2 DIVERTER VALVE. EACH DIVERTER
VALVE SHALL CONTROL 3 SHOWER HEAD ONLY. INSTALL PER
MANUFACTURER'S RECOMMENDATION AND INSTRUCTION MANUAL
OR EQUAL
2" 2" 2" 1
2" 1
2" FLOOR
2 SHOWER HEAD: SEE ARCH PLANS FOR TILED SHOWER, PROVIDE
FITTINGS "KOHLER" K-13688 SHALL HAVE A FLOW OF 2.5 GPM.
PROVIDE DIVERTER VALVE TO CONTROL SINGLE SHOWER HEAD
ONLY. INSTALL PER MANUFACTURER'S RECOMMENDATION AND
INSTRUCTION MANUAL OR EQUAL
2" 2" 2" 1
2" 1
2" FLOOR
SHOWER HEAD: SEE ARCH PLANS FOR TILED SHOWER, PROVIDE
FITTINGS "KOHLER" K-13688 SHALL HAVE A FLOW OF 2.5 GPM.
2" 2" 2" 1
2" 1
2" FLOOR
LAVATORY: WITH 8" ON CENTER. SEE ARCHITECTURAL DRAWINGS
FOR SPECIFICATIONS. PROVIDE FAUCET "KOHLER" OBLO
WIDESPREAD BATHROOM SINK FAUCET K-10086-9, METAL
CONSTRUCTION, BRASS VALVE BODIES. 1.5 GPM
2" 2" 2" 1
2" 1
2" WALL
LLAVATORY: WITH 8" ON CENTER. SEE ARCHITECTURAL DRAWINGS
FOR SPECIFICATIONS. PROVIDE FAUCET "KOHLER" OBLO
WIDESPREAD BATHROOM SINK FAUCET K-10086-9, METAL
CONSTRUCTION, BRASS VALVE BODIES. 1.5 GPAUCET PER ARCH
SPECIFICATION
2" 2" 1 1
2" 1
2" 1
2" WALL
KITCHEN SINK: "JUST". 16 GAUGE TYPE 304, 18-8 STAINLESS STEEL.
SEAMLESS DIE-DRAWN CONSTRUCTION. SELF RIMMING TOP
MOUNT GRIP-RIM PLUS WITH STAINLESS STEEL MOUNTING
CHANNELS. PROVIDE FAUCET "BLANCO CULINA MODEL 441331
2.2 GPM.PROVIDE 3/4HP IN-SINKEARATOR GARBAGE DISPOSER.
ELECTRICAL 120 VOLTS, 60HZ, 1725 RPM, 9.5 AMPS
2" 2" 1 1
2" 1
2" 1
2" WALL
LAUNDRY TUB: "JUST" . 16 GAUGE TYPE 304, 18-8 STAINLESS STEEL.
SEAMLESS DIE-DRAWN CONSTRUCTION. SELF RIMMING TOP
MOUNT GRIP-RIM PLUS WITH STAINLESS STEEL MOUNTING
CHANNELS. PROVIDE FAUCET PER ARCHITECTS
SPECIFICATION/OWNER
2" 2" 2" -- -- FLOOR
FLOOR SINK: "ZURN" 1901-2 HALF GRATE RECEPTOR 12"x12"x8"
DEEP CAST IRON BODY AND SQUARE SLOTTED MEDIUM DUTY
GRATE WITH ACID RESISTANT PORCELAIN ENAMEL INTERIOR AND
TOP. COMPLETE WITH ABS ANTI-SPLASH INTERIOR BOTTOM
STRAINER
2" 2" 2 1
2" 1
2" ``
CLOTHESWASHER BOX OUTLET: "LSP" KAHUNA OUTLET BOX WITH
HAMMER ARRESTERS, PLASTIC SIMPLEX HANDLE, CLEAR COVER
AND OPTIONAL CONDENSATE OB-2111
2" 2" 2" -- -- FLOOR
FLOOR DRAIN: "ZURN" Z-415 FLOOR DRAIN. D.C.C.I. BODY WITH
BOTTOM OUTLET, COMBINATION INVERTIBLE MEMBRANE CLAMP
AND ADJUSTABLE COLLAR WITH TYPE "B" POLISHED NICKLE
BRONZE STRAINER. PROVIDE TRAP PRIMER CONNECTION
WC-1
BTH-1
BTH-2
SHR-1
SHR-2
SHR-3
LV-1
LV-2
KS-1
LT-1
FS-1
CWB-1
FD-1
FIXTURE DATA AND WATER CALCULATION
ITEM DESCRIPTION NO. OF FIXT WFU 'S DFU 'S CW HW SEWER
WC-1 WATER CLOSET (TANK TYPE) 10 2.5 4.0 25.0 0 40.0
LV-1 LAVATORY 10 1.0 1.0 10.0 7.5 10.0
LV-2 LAVATORY 2 1.0 1.0 2.0 1.5 2.0
BTH-1 BATH TUB 5 4.0 2.0 20.0 15.0 10.0
BTH-2 BATH TUB 2 4.0 2.0 8.0 6.0 4.0
SHR-1 SHOWER ( 6 HEADS) 6 4.0 2.0 24.0 18.0 12.0
SHR-2 SHOWER ( 2 HEADS) 2 4.0 2.0 8.0 6.0 4.0
SHR-3 SHOWER ( 1 HEADS) 1 4.0 2.0 4.0 3.0 2.0
KS-1 KITCHEN SINK 4 1.5 2.0 6.0 4.5 8.0
-- DISHWASHER 4 1.5 1.0 6.0 4.5 4.0
CWB-1 CLOTHESWASHER 3 4.0 3.0 12.0 9.0 9.0
LT-1 LAUNDRY TUB 1 1.5 2.0 1.5 1.1 2.0
FD-1 FLOOR DRAIN 1 0 2.0 0 0.0 2.0
FS-1 FLOOR SINK 0 0 2.0 0 0.0 0.0
HB-1 HOSE BIBB 1 2.5 0.0 2.5 0 0.0
HB-1 HOSE BIBB (ADDITIONAL) 9 1.0 0.0 9.0 0 0.0
TOTAL WFU'S, DFU'S 0 0 138.0 76.1 109.0
MAIN DOMESTIC WATER SUPPLY SIZING BASE ON LATEST EDITION
CPC 2013 TABLE A-2, CHART A-4
COLD WATER FIXTURES UNITS = 53 GPM
HOT WATER FIXTURES UNITS = 37 GPM
COLD WATER PIPING SIZING
VELOCITY NOT TO EXCEED
8 FEET PER SECOND
PIPE DIA GPM
FT FIXT
UNIT
FV FIXT
UNIT
VELOCITY
1
2" 2.7 -- -- 3.2
3
4" 7.3 3 -- 4.9
1" 15.7 11 5 5.8
1 1
4" 26.5 41 9 6.9
1 1
2" 40.6 89 28 7.9
2" 71.3 232 114 8.0
2 1
2" 119.6 477 361 8.0
3" 177.7 801 756 8.0
FIXTURE EQUIPMENT SCHEDULE
ITEM LOCATION DESCRIPTION
OUTDOOR
TANKLESS WATER HEATER: "NORITZ" MODEL NC380-SV-ASME-LP SERIES OUTDOOR UNIT. WATER HEATER
WATER HEATER IS RATED 150 PSI WORKING PRESSURE AND 300 PSI TEST PRESSURE. GAS SUPPLY
PRESSURE SHALL BE 4.0" TO 10.5"WC FOR NATURAL GAS. PROVIDE OUTDOOR CAP VC-132. 19.1" WIDTH x
11.8 DEPTH x 29.7 HEIGHT.
INDOOR
TANKLESS WATER HEATER: "NORITZ" MODEL NC 380-SV-ASME-LP INDOOR WITH VENT CAP, MAXIMUM FLOW
OF 13.2 GPM, MINIMUM ACTIVATION FLUE 0.7GPM, 380,000 BTUH INPUT. POWER SUPPLY 120VAC (60 HZ)
CURRENT DRAW 3.091 AMPS, 5" EXHAUST VENT DIAMETER, CATEGORY III STAINLESS STEEL. MAXIMUM
VENT LENGTH WITH 1 ELBOW 45 FEET. REFER TO MANUFACTURER'S INSTALLATION MANUAL
INDOOR
TANKLESS WATER HEATER: "NORITZ" MODEL NRC98-DV-LP INDOOR, MAXIMUM FLOW OF 9.8 GPM, MINIMUM
ACTIVATION FLOW 0.5GPM, 180,000 BTUH INPUT. POWER SUPPLY 120VAC (60 HZ) CURRENT DRAW
1.I775 AMPS, 3" PVC SCHEDULE 40 AIR INTAKE AND EXHAUST. 4 ELBOWS = 35 FEET MAX. STRAIGHT VENT, 3
ELBOWS = 41 FEET MAX. STRAIGHT VENT, 2 ELBOWS = 47 FEET MAX. STRAIGHT VENT. 1 ELBOWS = 53 FEET
MAX. STRAIGHT VENT. REFER TO MANUFACTURER'S INSTALLATION
SEE PLAN
WATER HAMMER ARRESTERS: "SIOUX CHIEF" HYDRA RESTER WATER HAMMER ARRESTOR WITH HARD
DRAWN SEAMLESS TYPE "K" COPPER BODY.
SEE PLAN
TRAP PRIMER: "MIFAB" #M-500 PRESSURE DROP ACTIVATED, BRASS CONSTRUCTION, PROVIDE WITH M1-DU
4-WAY DISTRIBUTION UNIT (IF APPLICABLE), PROVIDE WITH ACCESS PANEL.
WATER HEATER
ROOM
EXPANSION TANK: "FLEXCON" PH-5 2.1 GALLONS 11" HEIGHT X 8" DIAMETER, 5LBS TOTAL WEIGHT. MAXIMUM
PRE-CHARGE 40 PSIG.
COLD WATER PIPING SIZING
VELOCITY NOT TO EXCEED
5 FEET PER SECOND
PIPE DIA GPM
FT FIXT
UNIT
FV FIXT
UNIT
VELOCITY
1
2" 2.7 -- -- 5.0
3
4" 7.3 3 -- 5.0
1" 13.4 8 -- 5.0
1 1
4" 19.6 20 6 5.0
1 1
2" 27.5 31 10 5.0
2" 46.4 117 41 5.0
2 1
2" 72.3 306 117 5.0
3" 115.6 456 340 5.0
FRICTION LOSSES
PRESSURE PER CIVIL DESIGN FOR WELL TANK ELEVATION IN RELATION TO FINISHED FLOOR ELEVATION 75 PSI
LENGTH OF DOMESTIC WATER SYSTEM FROM WELL TANK TO THE FURTHEST RUN. 477 FT
EXISTNG 3/4" WATER METER -- PSI
BACKFLOW PREVENTER 11 PSI
PRESSURE REGULATOR 0 PSI
TOTAL LOSSES 11 PSI
PRESSURE INSIDE THE BUILDING 66 PSI
STATIC HEIGHT 25 FT
RESIDUAL PRESSURE: 25 PSI
PRESSURE AVAILABLE FOR FRICTION LOSS 30.25 PSI
ALLOWABLE FRICTION LOSS PER HUNDRED FEET 6.3 PSI
39. AT THE TIME OF ROUGH INSTALLATION AND DURING STORAGE ON THE CONSTRUCTION SITE UNTIL
FINAL STARTUP OF THE HEATING, COOLING AND VENTILATING EQUIPMENT, ALL DUCT AND OTHER
RELATED AIR DISTRIBUTION COMPONENT OPENINGS SHALL BE COVERED WITH TAPE, PLASTIC,
SHEET METAL OR OTHER METHODS ACCEPTABLE TO THE ENFORCING AGENCY TO REDUCE DUST,
WATER AND DEBRIS WHICH MAY ENTER SYSTEM (CAL GREEN SECTION 5.504.3).
40. WATER HEATER SHALL BE ANCHORED OR STRAPPED TO RESIST HORIZONTAL DISPLACEMENT DUE
TO EARTHQUAKE MOTION PER SECTION 507.2 CPC
41. TOILET FLUSH CONTROLS SHALL COMPLY WITH THE FOLLOWING
A. MOUNTED MAXIMUM 44 INCHES ABOVE FLOOR
B. MOUNTED ON OPEN SIDE OF TOILET
C. OPERABLE WITH MAXIMUM 5 POUNDS OF FORCE
D. OPERABLE WITH ONE HAND AND WITHOUT TIGHT GRASPING, PINCHING, OR TWISTING OF WRIST
PLUMBING GENERAL NOTES CONT.
TABLE 5.303.2.3 FIXTURE FLOW RATES
FIXTURE TYPE MAXIMUM FLOW RATE @ 20% REDUCTION
SHOWER HEAD 2.5 GPM @ 80 PSI
LAVATORY FAUCET - NON RESIDENTIAL 0.4 GPM @ 60 PSI
KITCHEN FAUCETS - RESIDENTIAL AND
NON-RESIDENTAIAL
1.8 GPM @ 60 PSI
WASH FOUNTAINS 1.8(RIM SPACE (IN)/20 GPM @ 60 PSI)
METERING FAUCETS 0.20 GALLONS PER CYCLE
METERING FAUCETS FOR WASH FOUNTAINS 1.8(RIM SPACE (IN)/20 GPM @ 60 PSI)
GRAVITY TANK TYPE WATER CLOSETS 1.28 GALLONS PER FLUSH
FLUSHOMETER TANK TYPE WATER HEATERS 1.28 GALLONS PER FLUSH
FLUSHOMETER VALVE WATER CLOSETS 1.28 GALLONS PER FLUSH
ELECTROMECHANICAL HYDRAULIC WATER
CLOSETS
1.28 GALLONS PER FLUSH
URINALS 0.5 GALLONS PER FLUSH
NOTE NO.1
INCLUDES SINGLE AND DUAL FLUSH WATER CLOSETS WITH AN EFFECTIVE FLUSH OF 1.28 GALLONS OR
LESS:
SINGLE FLUSH TOILETS - THE EFFECTIVE FLUSH VOLUME SHALL NOT EXCEED 1.28 GALLONS . THE
EFFECTIVE FLUSH VOLUME IS THE AVERAGE FLUSH VOLUME WHEN TESTED IN ACCORDANCE WITH
ASME A 112.19.233.2.
DUAL FLUSH TOILETS - THE EFFECTIVE FLUSH VOLUME SHALL NOT EXCEED 1.28 GALLONS . THE
EFFECTIVE FLUSH VOLUME IS DEFINED AS THE COMPOSITE, AVERAGE FLUSH VOLUME OF TWO
REDUCED FLUSHES AND ONE FULL FLUSH. FLUSH VOLUMES WILL BE TESTED IN ACCORDANCE WITH
ASME A 112.19.2 AND ASME A 112.19.14.
TABLE 5.303.4
STANDARDS FOR PLUMBING FIXTURES AND FIXTURE FITTINGS
WATER CLOSETS (TOILETS) -FLUSHOMETER
VALVE-TYPE SINGLE FLUSH, MAXIMUM FLUSH
VOLUME
ASME A 112.19.2/CSA B45.I - 1.28 GAL (4.8 L)
WATER CLOSETS (TOILETS) -FLUSHOMETER
VALVE-TYPE DUAL FLUSH, MAXIMUM FLUSH
VOLUME
ASME A 112.19.14 AND U.S. EPA WATERSENSE
TENK-TYPE HIGH EFFICIENCY TOILET
SPECIFICATION - 1.28 GAL (4.8 L)
URINALS, MAXIMUM FLUSH VAVLE
ASME A 112.19.2/CSA B45.1 - 0.5 GAL (1.9 L)
PUBLIC LAVATORY FAUCETS:
MAXIMUM FLOW RATE -0.5 GPM (1.9 L/MIN) ASME A 112.18.1/CSA B125.1
PUBLIC METERING SELF-CLOSING FAUCETS:
MAXIMUM WATER USE - 0.25 GAL (1.0 L) PER
METERING CYCLE
ASME A 112.18.1/CSA B 125.1
CALIFORNIA GREEN BUILDING
STANDARDS CODE 2013
CHAPTER 3 - GREEN BUILIDNG
SECTION 301 GENERAL
301.1 SCOPE. BUILDINGS SHALL BE DESIGNED TO INCLUDE THE GREEN BUILDING
MEASURES SPECIFIED AS MANDATORY IN THE APPLICATION CHECKLISTS
CONTAINED IN THIS CODE. VOLUNTARY GREEN BUILDING MEASURES ARE ALSO
INCLUDED IN THE APPLICATION CHECKLISTS AND MAY BE INCLUDED IN THE
DESIGN AND CONSTRUCTION OF STRUCTURES COVERED BY THIS CODE, BUT ARE
NOT REQUIRED UNLESS ADOPTED BY A CITY, COUNTY, OR CITY AND COUNTY AS
SPECIFIED IN SECTION 101.7.
SECTION 303 PHASED PROJECTS
301.1 SCOPE. BUILDINGS SHALL BE DESIGNED TO INCLUDE THE GREEN BUILDING
MEASURES SPECIFIED AS MANDATORY IN THE APPLICATION CHECKLISTS
CONTAINED IN THIS CODE. VOLUNTARY GREEN BUILDING MEASURES ARE ALSO
INCLUDED IN THE APPLICATION CHECKLISTS AND MAY BE INCLUDED IN THE
DESIGN AND CONSTRUCTION OF STRUCTURES COVERED BY THIS CODE, BUT ARE
NOT REQUIRED UNLESS ADOPTED BY A CITY, COUNTY, OR CITY AND COUNTY AS
SPECIFIED IN SECTION 101.7.
303.1.1 TENANT IMPROVEMENTS. THE PROVISIONS OF THIS CODE SHALL APPLY
ONLY TO THE INITIAL TENANT OR OCCUPANT IMPROVEMENTS TO A PROJECT.
SECTION 306 VOLUNTARY MEASURES
306.1 PURPOSE. VOLUNTARY MEASURES ARE INTENDED TO FURTHER
ENCOURAGE BUILDING PRACTICES THAT IMPROVE PUBLIC HEALTH, SAFETY AND
GENERAL WELFARE BY PROMOTING THE USE OF BUILDING CONCEPTS WHICH
MINIMIZE THE BUILDING'S IMPACT ON THE ENVIRONMENT, PROMOTE A MORE
SUSTAINABLE DESIGN AND HIGH-PERFORMANCE EDUCATIONAL FACILITIES.
CHAPTER 5 - NON RESIDENTIAL MANDATORY MEASURES
DIVISION 5.1 - PLANING AND DESIGN
SECTION 5.101 GENERAL
SECTION 5.101 GENERAL
5.01 PURPOSE. THE PROVISIONS OF THIS CHAPTER OUTLINE PLANNING, DESIGN
AND DEVELOPMENT METHODS THAT INCLUDE ENVIRONMENTALLY RESPONSIBLE
SITE SELECTION, BUILDING DESIGN, BUILDING SITING AND DEVELOPMENT TO
PROTECT, RESTORE AND ENHANCE THE ENVIRONMENTAL QUALITY OF THE SITE
AND RESPECT THE INTEGRITY OF ADJACENT PROPERTIES.
DIVISION 5.2 - ENERGY EFFICIENCY
SECTION 5.201 GENERAL
5.201.1 SCOPE. FOR THE PURPOSES OF MANDATORY ENERGY EFFICIENCY
STANDARDS IN THIS CODE, THE CALIFORNIA ENERGY COMMISSION WILL
CONTINUE TO ADOPT MANDATORY BUILDING STANDARDS.
NOTE: IT IS THE INTENT OF THIS CODE TO ENCOURAGE BUILDINGS TO ACHIEVE
EXEMPLARY PERFORMANCE IN THE AREA OF ENERGY EFFICIENCY. FOR THE
PURPOSES OF ENERGY EFFICIENCY STANDARDS, THE CALIFORNIA ENERGY
COMMISSION BELIEVES SPECIFICALLY, A GREEN BUILDING SHOULD ACHIEVE
AT LEAST A 15 PERCENT REDUCTION IN ENERGY USAGE WHEN COMPARED TO
THE STATE'S MANDATORY ENERGY EFFICIENCY STANDARDS.
DIVISION 5.3 - WATER EFFICIENCY AND CONSERVATION
SECTION 5.301 GENERAL
5.301.1 SCOPE.
THE PROVISIONS OF THIS CHAPTER SHALL ESTABLISH THE MEANS OF
CONSERVING WATER USED INDOORS, OUTDOORS AND IN WASTEWATER
CONVEYANCE.
1. EACH PLUMBING FIXTURE AND FITTING SHALL BE MEET THE 20 PERCENT
REDUCED FLOW RATE SPECIFIED IN TABLE 5.303.2.3, OR
2. A CALCULATION DEMONSTRATING A 20 PERCENT REDUCTION IN THE
BUILDING "WATER USE BASELINE" AS ESTABLISHED IN TABLE 5.303.2.2
SHALL BE PROVIDED.
5.303.2 TWENTY PERCENT SAVINGS.
A SCHEDULE OF PLUMBING FIXTURES AND FIXTURE FITTINGS THAT WILL REDUCE
THE OVERALL USE OF POTABLE WATER WITHIN THE BUILDING BY 20 PERCENT
SHALL BE PROVIDED. THE REDUCTION SHALL BE BASED ON THE MAXIMUM
ALLOWABLE WATER USE PER PLUMBING FIXTURE AND FITTINGS AS REQUIRED BY
THE CALIFORNIA BUILDING STANDARDS CODE. THE 20 PERCENT REDUCTION IN
POTABLE WATER USE SHALL BE DEMONSTRATED BY ONE OF THE FOLLOWING
METHODS:
5.303.4 WASTEWATER REDUCTION.
EACH BUILDING SHALL REDUCE BY 20 PERCENT WASTEWATER BY ONE OF THE
FOLLOWING METHODS.
5.303.2 TWENTY PERCENT SAVINGS.
A SCHEDULE OF PLUMBING FIXTURES AND FIXTURE FITTINGS THAT WILL REDUCE
THE OVERALL USE OF POTABLE WATER WITHIN THE BUILDING BY 20 PERCENT
SHALL BE PROVIDED. THE REDUCTION SHALL BE BASED ON THE MAXIMUM
ALLOWABLE WATER USE PER PLUMBING FIXTURE AND FITTINGS AS REQUIRED BY
THE CALIFORNIA BUILDING STANDARDS CODE. THE 20 PERCENT REDUCTION IN
POTABLE WATER USE SHALL BE DEMONSTRATED BY ONE OF THE FOLLOWING
METHODS:
PIPE MATERIAL SCHEDULE
DOMESTIC WATER PIPING ABOVE GRADE
TYPE "L" COPPER TUBING, HARD DRAWN CONFORMING TO ASTM B 88, WITH WROUGHT COPPER SOLDER
SWEAT FITTINGS CONFORMING TO ASTM B 16.22. PROVIDE LABELING AND INSULATION
DOMESTIC WATER PIPING UNDERGROUND OR BELOW SLAB:
TYPE "K" HARD COPPER TUBING ANNEALED, WITH NO FITTINGS CONFORMING TO ASTM B 88.
SEWER WASTE & VENT PIPING : PVC SCHEDULE 40 SOLID WALL PIPE AND PVC DWV FITTING SYSTEM. PVC
SCHEDULE 40 PIPE SHALL BE IRON PIPE SIZE (IPS) CONFORMING TO ASTM D 1785 AND ASTM D 2665.
FITTINGS SHALL CONFORM TO ASTM 2665. BURIED PIPE SHALL BE INSTALLED IN ACCORDANCE WITH ASTM D
2321 AND ASTM F 1665. SOLVENT CEMENT JOINTS SHALL BE MADE IN TWO STEPS PROCESS WITH TRAP
PRIMER CONFORMING TO ASTM F 656 AND SOLVENT CEMENT CONFORMING TO ASTM D 25 64
CONDENSATE DRAIN PIPING ABOVE GRADE: TYPE "M" COPPER TUBING, HARD DRAWN CONFORMING TO
ASTM B 88, WITH WROUGHT COPPER SOLDER SWEAT FITTINGS CONFORMING TO ASTM B 16.22. PROVIDE
INSULATION AND LABELING
CONDENSATE DRAIN PIPING BELOW GRADE: PVC SCHEDULE 40 PIPE AND FITTINGS SHALL BE
MANUFACTURED FROM VIRGIN RIGID PVC VINYL COMPOUND A CELL CLASS OF 12454 AS IDENTIFIED IN ASTM
D 1784
NATURAL GAS PIPING ABOVE GRADE: SCHEDULE 40 BLACK STEEL, CONFORMING TO ASTM A53 WITH 150
PSIG MALLEABLE IRON THREADED FITTINGS CONFORMING TO ANSI/ASME B16.3. PROVIDE LABELING
LIQUIFIED PETROLUEM GAS PIPING EXPOSED TO WHEATHER: SCHEDULE 40 GALVANIZED STEEL,
CONFORMING TO ASTM A53 WITH 150 PSIG MALLEABLE IRON THREADED FITTINGS CONFORMING TO
ANSI/ASME B16.3. PROVIDE LABELING
LIQUIDFIED PETROLUEM GAS PIPING BELOW GRADE: - POLYETHYLENE WITH FUSION WELD JOINTS.
4"S
4"S
4"S
LPG
2"CW
LPG TANK
4"S
M
RESIDENCE
GUNER
PLUMBING SITE
PLAN
Man Cave
Exercise Rm
Stg. 3 Stg. 1
Bath
Game Rm
Cellar
Porch
Pool
Stg. 2
Elev
CL.
REF
CL.
ICE
REF.
134'-0"
134'-0"
Stairs 1
WINE
DW
144'-0"
144'-0"
18'-0" 32'-0" 18'-0"
5'-0"
20'-0"
24'-0"
6'-0"
4'-0"
16'-0"
24'-0"
6'-0"
50'-0" 30'-0"
4'-0"
6'-6"
Bath
D
W
BTH-1
2"VT-UP
KS-1
WC-1
LV-1
WC-1
BTH-1
LV-1
4"FCO
4"FCO
CWB-1
4"W TO SEPTIC TANK
2"VT-UP
4"W
4"W 2"W
4"W
4"W
2"VT-UP
2"VT-UP
FS-1
FAU # 3
FAU # 1 FAU # 2
ROUTE
CONDENSATE
DRAIN TO SPILL
INTO DRYWELL
ROUTE
CONDENSATE
DRAIN TO SPILL
INTO DRYWELL
M
RESIDENCE
GUNER
P2.0
PLUMBING
BASEMENT LEVEL
WASTE AND VENT
PLAN
1/2 Bath
Butler's Pantry
Laundry
Stg. Pantry
CL.
Retreat
WC
Master Br
Great Rm
Dining
Kitchen
Foyer
Porch
Courtyard
Garage
Work Shop
Agricultural Garage
Driveway
Motor Court
PG&E
TRASH
Hall
Powder
Elev
CL.
HOOD
AND
FAN
2'-6"
OVEN
FREEZER
134'-0"
134'-0"
Stairs 2
Stairs 1
DW
DW
144'-0"
144'-0"
D
W
CRAWL SPACE
44'-0" 18'-0" 32'-0" 18'-0" 6'-0"
13'-0" 5'-0"
6'-0"
6'-0"
16'-0"
32'-0"
20'-0"
20'-0"
24'-0"
6'-0"
8'-0" 56'-0" 8'-0" 16'-0" 32'-0" 18'-0" 6'-0"
22'-0"
32'-0"
20'-0"
14'-0"
16'-0"
24'-0"
6'-0"
10'-0"
12'-0"
8'-0"
16'-0"
8'-0"
20'-6" 21'-6" 8'-0" 6'-0"
10'-0"
REF
Patio
Entry
Porch
CL.
Rm
D
D
TO 2ND FLR.
TO 2ND FLR.
DW
Master Bath
3"W-UP TO
WC-1 ABV
2"W-UP TO
BTH-1 ABV
KS-1
WC-1 LV-1
CWB-1
LT-1
FD-1
KS-1
2"VT-UP
2"W-UP TO
LV-1 ABV
4"W-UP TO
WC-1 ABV
2"W-UP TO
BTH-1 ABV
4"W-UP
2"W-UP TO
LV-1 ABV
2"VT-UP
2"W-UP TO
BTH-1 ABV
2"VT-UP
4"W-UP
LV-1
WC-1
WC-1
SHD-1
SHR-1 TYP/6
LV-2
LV-2
LV-2
4"W
2"VT-UP
4"W-UP
4"W
4"W
4"W
4"W
3"W
3"W
4"W-UP TO
2ND FLR
CEILING
SPACE
2"W-UP TO
CWB-1 ABV
2"W-UP TO
LV-1 ABV
4"W-UP TO
WC-1 ABV
2"W-UP TO
BTH-1 ABV
2"VT-UP
2"VT-UP
4"W-UP AND DN
4"W-DN TO
TO B/G
2"VT-UP
ROUTE 4"W TO
SEPTIC TANK.
SEE CIVL
ROUTE 4"W TO
SEPTIC TANK.
SEE CIVL
4"GCO
4"GCO
BTH-2
2"VT-UP
2"VT-UP
OFFSET VENT
AND ROUTE AS
INDICATED
4"FCO
ROUTE TO SEPTIC TANK
2"VT-DN
2"VT-UP FROM
BELOW FLR
2"VT-DN
M
RESIDENCE
GUNER
P2.1
PLUMBING FIRST
LEVEL WASTE AND
VENT PLAN
Br 4
Br 3
Den
Jr. Br.
Open to Foyer
Bath
CL.
Bath 4
Elev
Balcony
CL.
Living
Br 6
Br 5
Kitchenette
Dining
Bath
CL.
CL.
REF
D/W
Powder
TUB
W/D
134'-0"
134'-0"
Stairs 2
Stairs 1
Deck
144'-0"
144'-0"
7'-10" 56'-0"
8'-0"
24'-0" 32'-0" 18'-0" 6'-0"
22'-0"
42'-0"
24'-0"
16'-0"
24'-0"
6'-0"
22'-0"
42'-0"
24'-0"
16'-0"
12'-0"
12'-0"
6'-0"
18'-0" 26'-0" 12'-0" 18'-0"
13'-0" 5'-0"
CL.
Open to
Courtyard
Bath 3
Br 3
2"VT-UP,
2"VTR
2"VT-UP, 2"VTR
3"VT-UP, 3"VTR
2"VT-DN
3"VT-UP,
3"VTR
WC-1
LV-1
WC-1
BTH-2
SHD-1
SHR-1
TYP/2
BTH-1
WC-1
LV-1
2"VT-UP, 2"VTR
BTH-1
WC-1
WC-1
LV-1
CWB-1
KS-1
BTH-1
2"VT-DN
2"VTR
2"W-UP TO
SHOWER ABV
2"W-UP TO LV-2 ABV
4"W-UP TO WC-1 ABV
2"VT-UP
4"W-DN
M
RESIDENCE
GUNER
P2.2
PLUMBING SECOND
LEVEL WASTE AND
VENT PLAN
Green House
Roof Top Garden
Roof Below
134'-0"
134'-0"
Stairs 2
144'-0"
144'-0"
22'-0"
16'-0"
8'-0" 20'-6" 30'-0"
Utility
WC-1
SHR-2
LV-2
M
RESIDENCE
GUNER
P2.3
PLUMBING THIRD
LEVEL WASTE AND
VENT PLAN
Man Cave
Exercise Rm
Stg. 3 Stg. 1
Bath
Game Rm
Cellar
Porch
Pool
Stg. 2
Elev
CL.
REF
CL.
ICE
REF.
134'-0"
134'-0"
Stairs 1
WINE
DW
144'-0"
144'-0"
18'-0" 32'-0" 18'-0"
5'-0"
20'-0"
24'-0"
6'-0"
4'-0"
16'-0"
24'-0"
6'-0"
50'-0" 30'-0"
4'-0"
6'-6"
Bath
D
W
1" HOT WATER UP
1" COLD WATER UP
1/2"HW UP
1"CW-UP
HB-1
HB-1
HB-1
LPG UP
3/4"
3/4"
1/2"-DN
1/2"DN
1/2"DN
3/4"
1/2"-DN
CWB-1
1"
1"
1/2"DN
1/2"DN
3/4"
3/4"
1/2"
FAU # 3
FAU # 1 FAU # 2
1/2''STUB FOR
ICE MAKER
LPG
LPG
LPG UP
LPG
M
RESIDENCE
GUNER
P3.0
PLUMBING
BASEMENT LEVEL
WATER PIPING PLAN
1/2 Bath
Butler's Pantry
Laundry
Stg. Pantry
CL.
Retreat
WC
Master Br
Great Rm
Dining
Kitchen
Foyer
Porch
Courtyard
Garage
Work Shop
Agricultural Garage
Driveway
Motor Court
PG&E
TRASH
Hall
Powder
Elev
CL.
HOOD
AND
FAN
2'-6"
OVEN
FREEZER
134'-0"
134'-0"
Stairs 2
Stairs 1
DW
DW
144'-0"
144'-0"
D
W
CRAWL SPACE
44'-0" 18'-0" 32'-0" 18'-0" 6'-0"
13'-0" 5'-0"
6'-0"
6'-0"
16'-0"
32'-0"
20'-0"
20'-0"
24'-0"
6'-0"
8'-0" 56'-0" 8'-0" 16'-0" 32'-0" 18'-0" 6'-0"
22'-0"
32'-0"
20'-0"
14'-0"
16'-0"
24'-0"
6'-0"
10'-0"
12'-0"
8'-0"
16'-0"
8'-0"
20'-6" 21'-6" 8'-0" 6'-0"
10'-0"
REF
Patio
Entry
Porch
CL.
Rm
D
D
TO 2ND FLR.
TO 2ND FLR.
DW
Master Bath
1"CW-UP
CW & HW UP TO
2ND LEVEL
1"CW & HW-DN TO
BASEMENT LEVEL
CW & HW UP
TO 2ND LEVEL
CW-DN
HW-UP TO
2ND FLR
INDOOR TANK LESS
WATER HEATER
SERVING
2ND FLOOR THIS AREA
INDOOR TANKLESS
WATER HEATER SERVING
THE KITCHEN AND THE
BATHROOM ABOVE
OUTDOOR TANKLESS
WATER HEATER
SERVING MASTER
BEDROOM AND THE
BEDROOM ABOVE
LPG LPG
LPG
LPG
LPG TANK FOR
REFERENCE ONLY
BY CIVIL
2ND STAGE
REGULATOR.
FROM 5PSI TO
11"WC
HW-DN
5'-0"
1
1
CW P.O.C.
CW P.O.C.
BY CIVIL. FOR
REFERENCE ONLY
BY CIVIL. FOR
REFERENCE ONLY
PROVIDE
BACKWATER VALVE
BY CIVIL. FOR
REFERENCE ONLY
1ST STAGE
REGULATOR. FROM
HIGH PRESSURE TO
(5 PSI) MEDIUM
PRESSURE
LPG DOWN TO
BELOW GRADE
WELL TANK.
BY CIVIL. FOR
REFERENCE ONLY
LPG BELOW GRADE
LPG BELOW GRADE
2
2
PROVIDE 3" PVC SCHEDULE 40
EXHAUST AND INTAKE
3
3
LPG UP
LPG-DN
HB-1
HB-1
HB-1
4
5" DIAMETER VENT STAINLESS
STEEL CATEGORY VENT. INSTALL
PER MFR'S RECOMMENDATION
AND INSTALLATION GUIDE
HB-1
HB-1
HB-1
HB-1
2"
2" 2"
2"
2"
2"
1"
3/4"
1/2"DN
5
5
GAS PIPING DN
LPG
LPG
LPG
2ND STAGE
REGULATOR FROM 5
PSI TO 7"WC
2ND STAGE
REGULATOR FROM 5
PSI TO 7"WC
LPG DN TO
BASEMENT
1/2"CW &
HW DN
2"
1"
1/2"CW &
HW DN
1/2"DN
3/4"
1/2"DN
1/2" DN
3/4"
2"
1-1/4"-DN
1-1/4"DN
HB-1
3/4"
2"CW
2"CW
2"CW
CWB-1
HB-1
HB-1
2"
3/4"
LPG
LPG
2
M
RESIDENCE
GUNER
P3.1
PROVIDE TWO PERMANENT COMBUSTION AIR 14" X 28" HIGH AND LOW.
PER MANUFACTURER'S INSTALLATION GUIDE FOR NORIZT
INSTANTANEOUS WATER HEATER MANUAL INSTRUCTIONS PAGE 13.
ROUTE CONDENSATE DRAIN TO SPILL TO DAYLIGHT.
BUILDING MAIN SHUT-OFF VALVE INSIDE CONCRETE UTILITY BOX
MARKED "WATER".
SHUT-OFF VALVE. PROVIDE ACCESS PANEL IF LOCATED ABOVE
HARDLID CEILING.
PROVIDE "SYMMONS" DIVERTER VALVE TO CONTROL 3 SHOWER ONLY.
1
2
KEY NOTES:
3
4
1/2"
5
LPG DN
LPG UP
PLUMBING FIRST
LEVEL WATER
PIPING PLAN
Br 4
Br 3
Den
Jr. Br.
Open to Foyer
Bath
CL.
Bath 4
Elev
Balcony
CL.
Living
Br 6
Br 5
Kitchenette
Dining
Bath
CL.
CL.
REF
D/W
Powder
TUB
W/D
134'-0"
134'-0"
Stairs 2
Stairs 1
Deck
144'-0"
144'-0"
7'-10" 56'-0"
8'-0"
24'-0" 32'-0" 18'-0" 6'-0"
22'-0"
42'-0"
24'-0"
16'-0"
24'-0"
6'-0"
22'-0"
42'-0"
24'-0"
16'-0"
12'-0"
12'-0"
6'-0"
18'-0" 26'-0" 12'-0" 18'-0"
13'-0" 5'-0"
CL.
Open to
Courtyard
Bath 3
Br 3
1"CW & 1"HW DN
TO 1ST LEVEL
CW DN TO
1ST LEVEL
1"HW DN TO
1ST LEVEL
1"CW & 1"HW DN
TO 1ST LEVEL
LPG DN TO 1ST
LEVEL
1"CW & 1"HW DN
TO 3RD LEVEL
1/2"CW & HW DN
1/2"CW DN
1/2"CW & HW DN
1/2"CW-DN
1/2"CW & HW DN
1/2"CW & HW DN
1/2"CW & HW DN
1/2"CW & HW DN
1"
1"
3/4"
1/2"
1/2"
1"
1/2"CW-DN
1/2"CW & HW DN
1/2"CW & HW DN
1/2"CW & HW DN
1/2"CW-DN
1/2"HW-DN
1"
1"
1"
1"
3/4"
1"
CWB-1
LPG LPG
M
RESIDENCE
GUNER
P3.2
PLUMBING SECOND
LEVEL WATER
PIPING PLAN
Green House
Roof Top Garden
Roof Below
134'-0"
134'-0"
Stairs 2
144'-0"
144'-0"
22'-0"
16'-0"
8'-0" 20'-6" 30'-0"
Utility
1"CW & HW DN 1/2"CW & HW DN
1/2"CW-DN
1/2"CW & HW
DN
1"CW
M
RESIDENCE
GUNER
P3.3
PLUMBING THIRD
LEVEL WATER
PIPING PLAN
M
RESIDENCE
GUNER
P4.1
PLUMBING WASTE
AND VENT
DIAGRAM
SHR-1
FIRST LEVEL WC-1
LV-1
4"FCO
KS-1
SHR-1
WC-1
LV-1 CWB-1
4"FCO 4"FCO
BTH-1
WC-1
CWB-1
4"FCO
KS-1
4
SCALE: NONE
BASEMENT WASTE AND VENT DIAGRAM
4"W 2"W
4"W
2"W
2"WCO
4"W
4"W
3
SCALE: NONE
GUEST ROOM WASTE AND VENT DIAGRAM
FIRST LEVEL
SECOND LEVEL
SHR-1
WC-1
LV-1
4"FCO
2
SCALE: NONE
MASTER BEDROOM WASTE AND VENT DIAGRAM
1
SCALE: NONE
WASTE AND VENT DIAGRAM
WC-1
LV-2
BTH-2
LV-2
WC-1
LV-1 LV-1 LV-1
BTH-2 SHR-1
SEE BASEMENT "AA"
DIAGRAM THIS
SHEET FOR CONT
SEE MASTER "AA"
BEDROOM DIAGRAM
FOR CONTINUATION
FIRST LEVEL BTH-2
WC-1
LV-1
WC-1
LT-1
FD-1
CWB-1
KS-1
BTH-1
WC-1
LV-1
BUTLERS PANTRY
KS-1 LV-1
KITCHEN
DINING
BEDROOM-3
BEDROOM-4
SECOND LEVEL
SEE BASEMENT "BB"
DIAGRAM THIS
SHEET FOR CONT
SEE MASTER "BB"
BEDROOM DIAGRAM
FOR CONTINUATION
2"WCO 2"WCO 2"WCO 2"WCO
2"WCO
2"WCO
2"VT
2"VT
2"VT
3"VT
3"VT
2"VT
3"VT
2"W
4"W
4"W
4"W
2"W
2"VT
2"W
2"W 2"W
2"VT
2"VT
2"VT
2"VT
2"VT
2"VT
2"VT 2"VT 2"VT
2"VT
2"VT
3"VTR
2"W
2"W
4"W
4"W
4"W
4"W 4"W
4"W
4"W
2"W
4"W
4"W
4"W
4"W
4"FCO
2"WCO
2"W
2"WCO
2-1/2"W
2"WCO
2"W
2"WCO
2"W
2"VT
2"VT
2"VT
2"VT
2"VTR
4"W
2"WCO
2"VT
2"VT
2"VT
2"VT
2"VT
2"VT
2"VT
2"W
4"W
4"W
2"WCO
2"W
2"VT 2"VT 2"VT 2"VT 2"VT
2"WCO
2"W
4"W 4"W 4"W 4"W 4"W
2"W
2"VT
2"VT
2"VT
2"VT
2"VT
2"VT
2"W
2"VT
2"VT
2"VT
3"VTR
4"W
4"W
4"W
4"W
4"W
ROUTE TO SEPTIC TANK. FOR
CONTINUATION SEE CIVIL
DRAWINGS
ROUTE TO SEPTIC TANK. FOR
CONTINUATION SEE CIVIL
DRAWINGS
2"VT
2"VT
2"VT
4"W
4"W
2"VT
2"VT
2"VT
2"VT
2"VT
2"VT
2"VT
2"VT
2"VT
2"WCO
2"WCO
2"WCO 2"WCO
2"S
4"W 2"W
2"VT
2"W
2"W
2"W
4"W 4"W
4"W 4"W
4"W 4"W
2"VTR
THIRD LEVEL
LV-1
2"WCO
2"VT
2"VT
2"VTR
WC-1
SHR-1
LV-2
ROOF 2"VTR
2"WCO
2"W 4"W
2"W
4"W
4"W
2"VT
2"VT
2"VT
ROUTE TO SEPTIC TANK. FOR
CONTINUATION SEE CIVIL
DRAWINGS
ROUTE TO SEPTIC TANK. FOR
CONTINUATION SEE CIVIL
DRAWINGS
2"VT 2"VT 2"VT 2"VT
2"VT
2"WCO
BASEMENT LEVEL
FIRST LEVEL
2"W
M
RESIDENCE
GUNER
P4.2
PLUMBING COLD
AND HOT WATER
DIAGRAM
BTH-1
HB-1
LV-1
CWB-1
KS-1
DISHWASHER
HB-1
KS-1
KS-1
WC-1 LT-1 CWB-1 LV-1
BTH-1
WC-1
LV-1
BTH-1
WC-1
LV-1
BEDROOM
3
BEDROOM
4
CWB-1
WC-1 LV-1
BTH-1 KS-1
POOL
BATH
GAME
ROOM
BASEMENT LEVEL
FIRST LEVEL
SECOND LEVEL
THIRD LEVEL
LV-1
WC-1
WC-1 SHR-1 SHR-1 SHR-1 SHR-1 SHR-1 SHR-1
BTH-2
LV-2
LV-2
WC-1
LV-1
SHR-1 SHR-1
WC-1
BTH-2
WC-1 LV-1
LV-1
LV-1
MASTER BEDROOM
2"CW 2"CW
2"CW
3/4"CW
1"CW
1/2"CW
1/2"CW
1/2"HW
1/2"CW
1/2"CW
1/2"HW
1/2"CW
1/2"HW
1/2"CW
1/2"HW
1/2"CW
1/2"HW
1/2"CW
1/2"HW
1/2"CW
1/2"HW
1/2"CW
1/2"HW
1/2"CW
1/2"HW
1/2"CW
1/2"CW
1/2"HW
1/2"CW
COLD WATER PIPING SIZING
VELOCITY NOT TO EXCEED
8 FEET PER SECOND
PIPE DIA GPM
FT FIXT
UNIT
FV FIXT
UNIT
VELOCITY
1
2" 2.7 -- -- 3.2
3
4" 7.3 3 -- 4.9
1" 15.7 11 5 5.8
1 1
4" 26.5 41 9 6.9
1 1
2" 40.6 89 28 7.9
2" 71.3 232 114 8.0
2 1
2" 119.6 477 361 8.0
3" 177.7 801 756 8.0
COLD WATER PIPING SIZING
VELOCITY NOT TO EXCEED
5 FEET PER SECOND
PIPE DIA GPM
FT FIXT
UNIT
FV FIXT
UNIT
VELOCITY
1
2" 2.7 -- -- 5.0
3
4" 7.3 3 -- 5.0
1" 13.4 8 -- 5.0
1 1
4" 19.6 20 6 5.0
1 1
2" 27.5 31 10 5.0
2" 46.4 117 41 5.0
2 1
2" 72.3 306 117 5.0
3" 115.6 456 340 5.0
1-1/4"CW
1"CW
3/4"CW
3/4"CW
1-1/4"CW
1"CW 1-1/2"CW
2"CW
2"CW
2"CW
1/2"CW
1/2"HW
1/2"CW
1/2"HW
1/2"CW
1/2"HW
1/2"CW
1/2"HW
1/2"CW
1/2"HW
1/2"CW
1/2"HW
1/2"CW
1/2"CW
1/2"CW
1-1/4"CW 1-1/4"CW 1"CW
1-1/4"CW
1-1/4"CW
1-1/4"CW
1-1/4"CW
2"CW
2"CW
1-1/2"CW
1-1/2"HW
2"CW
2"CW
1/2"CW
1/2"HW
1/2"CW
1/2"HW
1/2"CW
1/2"HW
1/2"CW
1/2"CW
1/2"HW
1"CW
1-1/4"CW
1-1/4"CW
2"CW
2"CW
1/2"HW
1/2"CW
1/2"HW
1/2"CW
1/2"HW
1/2"CW
1/2"HW
1/2"CW
1/2"CW
3/4"CW
1-1/4"CW
1"CW
1"CW
3/4"HW
1"CW
1"HW
1"CW
2"CW
2"CW
1/2"HW
1/2"CW
1/2"HW
1/2"CW
1/2"HW
1/2"CW
1/2"HW
1/2"CW
2"CW
2"CW
2"CW
1/2"CW
3/4"
1
1/4"HW
1-1/4"CW
1-1/4"HW
1-1/4"HW
1-1/4"HW
1-1/4"HW
1-1/4"HW
1/2"HW
1/2"CW
1/2"CW
1/2"HW
1/2"CW
1/2"HW
1/2"CW
1"HW
1-1/4"CW
1/2"HW
1/2"CW
1/2"HW
3/4"CW
1"
1"HW
1-1/2"CW
1"CW
WELL TANK.
SEE CIVIL
FOR EXACT
LOCATION
(FOR
REFERENCE
ONLY)
SHUT-OFF VALVE
INSIDE
CONCRETE
UTILITY BOX
SHUT-OFF VALVE
INSIDE
CONCRETE
UTILITY BOX
LV-2
SHR-1
WC-1
1/2"HW
1"CW
1/2"HW
1/2"CW
3/4"HW
1"CW
3/4"CW
HB-1
3/4"CW
1-1/2"CW
1-1/4"CW
1"HW 1"
WC-1
HB-1
HB-1
3/4"CW
PROVIDE DIVERTER VALVE
"SYSMON" TO CONTROL 3
SHOWER HEAD. ONE SHOWER
SHALL BE ACTIVATED ONLY
PROVIDE DIVERTER VALVE
"SYSMON" TO CONTROL 3
SHOWER HEAD. ONE SHOWER
SHALL BE ACTIVATED ONLY
1-1/2"CW
MATCH
LINE
"AA"
MATCH
LINE
"AA"
HB-1
3/4"CW
1/2"HW
1/2"CW
3/4"CW
1/2"HW
1/2"CW
3/4"CW
1"HW
1-1/4"HW
1-1/4"HW
3/4"HW
3/4"CW
3/4"HW
1-1/2"CW
WATER HAMER
ARRESTER
WATER HAMER
ARRESTER
WATER HAMER
ARRESTER
WATER HAMER
ARRESTER
WATER HAMER
ARRESTER
WATER HAMER
ARRESTER
HB-1
1/2"CW
HB-1
1/2"CW
1"CW 1"CW
3/4"CW
HB-1
HB-1 HB-1
3/4"CW
3/4"CW
3/4"CW
WATER
HAMMER
ARRESTER
2"CW
BACKFLOW
PREVENTER
M
RESIDENCE
GUNER
P4.3
PLUMBING GAS
PIPING DIAGRAM
BASEMENT LEVEL
FIRST LEVEL
SECOND LEVEL
SECOND LEVEL
1
SCALE: NONE
GAS PIPING DIAGRAM
COOKING
RANGE
108 MBH
380 MBH
180 MBH
LPG TANK
(BY CIVIL FOR
REFERENCE
ONLY)
FIRST STAGE
REGULATOR FROM HIGH
PRESSURE TO 5 PSI
SECOND STAGE
REGULATOR FROM
MEDIUM PRESSURE
TO 11" WC
LPG LOAD
QUANTITY DESCRIPTION MBH TOTAL
2 WATER HEATER 380 760
1 WATER HEATER 180 180
2 COOKING RANGE 108 216
3 FIREPLACE 80 240
6 FURNACE 60 360
GRAND TOTAL 1756
TOTAL DEVELOPMENT FROM THE LPG TANK TO THE FURTHEST OUTLET IS
APPROXIMATE 200 FEET
LPG PIPE SIZING CHART
(7"-14"WC)
CFH
1
2" 67
3
4" 140
1" 265
1 1
4" 543
1 1
2" 814
LOW PRESSURE GAS BASE ON CPC
2013 TABLE 1216.2 )(27) (NFPA 54
TABLE 6.3(D)) @ 200 FT
LPG PIPE SIZING CHART
(5 PSI)
CFH
1
2" 1030
3
4" 2430
LOW PRESSURE GAS BASE ON CPC
2013 TABLE 1216.2 )(25) NFPA 54
TABLE 6.2(B) @ 200 FT
1/2"LPG (428 MBH)
1/2"LPG
1/2"LPG
SECOND STAGE
REGULATOR FROM
MEDIUM PRESSURE TO
11" WC
1" (188 MBH)
FURNACE
60 MBH
1"
(248
MBH)
1"
(180
MBH)
380 MBH
COOKING
RANGE
108 MBH
FURNACE
60 MBH
FURNACE
60 MBH
1-1/4"
(380
MBH)
3/4"
(60
MBH)
3/4"
(60
MBH)
3/4"
(60
MBH)
1" (140 MBH) 1" (200 MBH)
3/4"
(180
MBH)
1-1/2"
(688
MBH)
1"
(380
MBH)
FIREPLACE
GAS LOG
80 MBH
3/4" (80 MBH) 1-1/4" (260 MBH)
1-1/2"
(640
MBH)
3/4" LPG (1756 MBH)
FAU # 1
60 MBH
FAU # 2
60 MBH
FAU # 3
60 MBH
1"
(180
MBH)
3/4" LPG (1116 MBH)
FIREPLACE
GAS LOG
80 MBH
3/4"
(80
MBH)
SECOND STAGE
REGULATOR FROM
MEDIUM PRESSURE
TO 11" WC
1" (308 MBH)
3/4"
(80
MBH)
FIREPLACE
GAS LOG
80 MBH
1-1/4" (428 MBH)
1"
(108
MBH)
1/2" 1/2" 1/2"
3/4"
M
RESIDENCE
GUNER
P5.1
PLUMBING DETAILS
FINISHED PAVEMENT
RELIEF VALVE
BALL VALVE
OUTDOOR TANK LESS WATER HEATER
GAS LINE
UNION
OVERHEAD STRUCTURE
12''MIN
12''MIN
3'-0''
24''
29.7''
WINDOWS, DOORS
OPENING
11.8" DEPTH
EXPANSION TANK
DIRT LEG
COLD WATER SUPPLY
WINDOWS, DOORS
OPENING
1
HOT
WATER
SUPPLY
FINISHED FLOOR
SPILL INTO
DAYLIGHT
UNION (TYP)
INSTALL PER MANUFACTURER'S
REQUIREMENTS AND
SPECIFICATIONS
COLD WATER SUPPLY
GAS SUPPLY LINE
T & P (TYP)
S.0.V. (TYP)
LPG
HOT WATER SUPPLY LINE
CHECK VALVE
Vertical Vent Termination
Firestop
Firestop/
Support
Roof
Flashing
Roof
Jack
Storm
Collar
Rain
Cap
Hanger
Strap
Elbow
1' Min. - 3' Max.
Horizontal Vent Termination
Terminate at least 12" above grade or
above snow line.
Terminate at least 7' above a public walk-
way, 6' from the combustion air intake of
any appliance, and 3' from any other
building opening, gas utility meter, ser-
vice regulator etc.
" Terminate at least 3' above any forced air
inlet within 10', 4' below, 4' horizontally
from or 1' above any door, window, or
gravity air inlet into any building per National
Fuel Gas Code ANSI Z223.1/NFPA 54.
" Slope the horizontal vent 1/4" downwards
for every 12" toward the termination.
" Use a condensation drain if necessary.
" In the Commonwealth of Massachusetts
a carbon monoxide detector is required
for all side wall horizontally vented gas
fuel equipment. Please refer to Technical
Bulletin TB 010606 for full installation in-
structions.
Appliance
Adapter*
Elbow
Hanger
Straps
Wall
Thimble
Termination
1' Min. - 3' Max.
Terminate at least 6' from the combustion air
intake of any appliance, and 3' from any other
building opening, gas utility meter, service
regulator etc.
Enclose exterior vent systems below the roof
line to limit condensation and protect against
mechanical failure.
When the vent penetrates a floor or ceiling and is
not running in a fire rated shaft, a firestop and
support is required.
When the vent termination is located not less than
8' from a vertical wall or similar obstruc- tion,
terminate above the roof at least 2', but not more
than 6', in accordance with the National Fuel Gas
Code ANSI Z223.1/NFPA 54.
Provide vertical support every 12' or as required
by the vent pipe manufacturer's instructions.
Slope the horizontal vent 1/4" for every 12" to-
wards the drain tee.
A short horizontal section is recommended to
prevent debris from falling into the water heater.
Condensation
Drain (Install
According to
Local Codes)
Adapter not
required when
using Noritz
N-Vent.
1' minimum
recommended, but
not required. Avoid
installing elbow
directly on flue.
Appliance
Adapter*
1' minimum
recommended, but
not required. Avoid
installing elbow
directly on flue.
Slope vent
Downwards
Install a condensation drain in the horizontal
section of the venting. For installations in tight
spaces where there is not enough room to in-
stall two elbows and a horizontal drain tee, a
vertical drain tee may be substituted.
2
INDOOR TANK LESS WATER HEATER
3
CLOTHES WASHER MACHINE BOX DETAIL
4
TRAP PRIMER DETAIL
PRIMER PIPE
FLOOR FOR EVERY 2O FEET OF
NOTE:
TRAP PRIMER VALVE SHOULD
BE MOUNTED 12" ABOVE FINISHED
1/2"CW TRAP PRIMER SUPPLY
"T" FITTING (COPPER)
"PRECISION PLUMBING
PRODUCTS, INC. "TRAP PRIMER
VALVE
ACCESS PANEL. VERIFY
SIZE & LOCATION IN FIELD
COLD WATER HEADER
OR MAIN BRANCH IN
WALL
16" MINIMUM
1/2" MINIMUM
ANNEALED COPPER
TUBING (EACH FLOOR
DRAIN).
FINISHED
FLOOR
COPPER TUBE TO
FLOOR DRAIN TRAP
PRIMER CONNECTION
(TYP)
5
CONDENSATE CONNECTION TO UNIT DETAIL
FITTINGS OR
"U" BEND TRAP
AT 1/8" PER FOOT
SLOPE
3"
2'' MINIMUM
1-1/2'' MINIMUM
VENT FOR PIPE RUNS
GREATER THAN 15 FEET
CLEANOUT PLUG
(BY MECH)
FAN COIL UNIT
FOR REFERENCE
ONLY. INSTALL PER
MFR'S
REQUIREMENTS
BASE FLASHING BY
GEN'L. CONT'R.
CRIMP EDGE OVER PIPE IN A NEAT
MANNER TO PREVENT REDUCTION OF
EFFECTIVE VENT AREA.
SHEET COPPER OR LEAD
COUNTER FLASHING BY
PLBG. CONT'R. (TO MATCH
MATERIAL OF BASE
FLASHING). SEE ARCH
DWGS.
REFER TO ARCH.
DWGS. FOR ROOF
CONSTRUCTION.
REFER TO PLANS FOR SIZE
AND LOCATION
6
VENT THRU ROOF DETAIL
Before installing, check for the following:
Install in accordance with relevant building and mechanical codes, as well as any local, state or
national regulations, or in the absence of local and state codes, to the National Fuel Gas Code
ANSI Z223.1/NFPA 54 latest edition. In Canada, see NSCNGPIC for detailed requirements.
Item
Distance
from
combustibles
" Maintain the following clearances
from both combustible and
non-combustible materials.
Check Illustration
" If possible, leave 8" (200mm) or more on
either side of the unit to facilitate inspection.
" If possible, leave 24" (600mm) or more in
front of the unit to facilitate maintenance
and service if necessary.
" If possible, leave 3" (75mm) or more
above and below the vent pipe to facilitate
inspection and repair if necessary
Securing
of
space
for
repair/inspection
24" (600mm)
or more
Distance from
the side
12"
or more
2" (50mm)
or more
4"
or more
3" (75mm) or more
3" (75mm) or more
8" (200mm)
or more
8" (200mm)
or more
<When the indoor air supply>
" If the unit will be installed in the vicinity of
a permanent kitchen range or stove that
has the possibility of generating steam
that contains fats or oils, use a dividing
plate or other measure to ensure that the
unit is not exposed to air containing such
impurities.
* The dividing plate should be of noncom-
bust-ible material of a width greater than
the water heater.
Exhaust hood
Range
Dividing plate Water
heater
Cooking
Equipment
NIPPLE
GAS SUPPLY
EQUIPMENT
3"MIN.
CAP
PROVIDE FLEX CONNECTION PER
MANUFACTURERS REQUIREMENTS AND
RECOMMENDATION
EQUIPMENT GAS
SHUT-OFF VALVE
7
GAS CONNECTION TO EQUIPMENT
9
DRYWELL DETAIL
1/2" HOT
WATER
1/2" COLD
WATER
HOSE
BIBBS
WASHING MACHINE BOX
2" TRAP AND
WASTE PIPE
1 1/2" WASTE
WATER HAMMER ARRESTOR
-WADE MODEL W-5
FINISHED FLOOR
SPILL INTO
DAYLIGHT
UNION (TYP)
INSTALL PER MANUFACTURER'S
REQUIREMENTS AND SPECIFICATIONS
COLD WATER SUPPLY
GAS SUPPLY LINE
T & P (TYP)
S.0.V. (TYP)
LPG
HOT WATER SUPPLY LINE
CHECK VALVE
EXPANSION TANK
EXPANSION TANK
3'-0"
6" SAND FILL
BACKFILL
COVER
CORRUGATED
GALVANIZED IRON
ABS OR PVC PIPE
4"DIA PERFORATED
GRAVEL FILL
FINISHED
GRADE
2'-6"
DRAIN PIPE

More Related Content

Similar to 05.18.2015 PLBG GUNER RESIDENCE.pdf

HA1522_TN20&21_Pennyworth_Option 01_DD_Final set_160309
HA1522_TN20&21_Pennyworth_Option 01_DD_Final set_160309HA1522_TN20&21_Pennyworth_Option 01_DD_Final set_160309
HA1522_TN20&21_Pennyworth_Option 01_DD_Final set_160309Altamash Khan
 
Elam Pricing Full Set 4.3.15
Elam Pricing Full Set 4.3.15Elam Pricing Full Set 4.3.15
Elam Pricing Full Set 4.3.15Sean Roper
 
North Campus Parking Garage
North Campus Parking GarageNorth Campus Parking Garage
North Campus Parking GarageTurner Solterman
 
Sample CAD DWG_ROTHMAN_Nicole Eng
Sample CAD DWG_ROTHMAN_Nicole EngSample CAD DWG_ROTHMAN_Nicole Eng
Sample CAD DWG_ROTHMAN_Nicole EngNicole Eng
 
2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revised2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revisedBasudev patra
 
NMohamed_PortfolioExtract
NMohamed_PortfolioExtractNMohamed_PortfolioExtract
NMohamed_PortfolioExtractNazima Mohamed
 
ADU Plan 5 - 1200 sqft (1).pdf
ADU Plan 5 - 1200 sqft (1).pdfADU Plan 5 - 1200 sqft (1).pdf
ADU Plan 5 - 1200 sqft (1).pdfDeniseMathre1
 
Regulation for cgd_technical_standard_071.8
Regulation for cgd_technical_standard_071.8Regulation for cgd_technical_standard_071.8
Regulation for cgd_technical_standard_071.8Nikhil Nangia
 
15RDM01-Academy Demo Plan
15RDM01-Academy Demo Plan15RDM01-Academy Demo Plan
15RDM01-Academy Demo PlanKevin Stober
 
The Fragrance Outlet - Grand Rapids, MI 8.20.15
The Fragrance Outlet - Grand Rapids, MI 8.20.15The Fragrance Outlet - Grand Rapids, MI 8.20.15
The Fragrance Outlet - Grand Rapids, MI 8.20.15Antoinette Pope
 
Electricty wiring code 2016
Electricty wiring code 2016Electricty wiring code 2016
Electricty wiring code 2016Manikandan Mani
 
Utility Basic Details in Ahmedabad Railway Station Re Development.pptx
Utility Basic Details in Ahmedabad Railway Station Re Development.pptxUtility Basic Details in Ahmedabad Railway Station Re Development.pptx
Utility Basic Details in Ahmedabad Railway Station Re Development.pptxMoturiVinodKumar
 
Subpart K - Electrical
Subpart K - ElectricalSubpart K - Electrical
Subpart K - ElectricalFFSafety
 
04-3-TS_Vol-II_,Sec-IV,_Pre_Comm_R1.pdf
04-3-TS_Vol-II_,Sec-IV,_Pre_Comm_R1.pdf04-3-TS_Vol-II_,Sec-IV,_Pre_Comm_R1.pdf
04-3-TS_Vol-II_,Sec-IV,_Pre_Comm_R1.pdfAnonymouscj7JdRbDb
 

Similar to 05.18.2015 PLBG GUNER RESIDENCE.pdf (20)

HA1522_TN20&21_Pennyworth_Option 01_DD_Final set_160309
HA1522_TN20&21_Pennyworth_Option 01_DD_Final set_160309HA1522_TN20&21_Pennyworth_Option 01_DD_Final set_160309
HA1522_TN20&21_Pennyworth_Option 01_DD_Final set_160309
 
Elam Pricing Full Set 4.3.15
Elam Pricing Full Set 4.3.15Elam Pricing Full Set 4.3.15
Elam Pricing Full Set 4.3.15
 
North Campus Parking Garage
North Campus Parking GarageNorth Campus Parking Garage
North Campus Parking Garage
 
Sample CAD DWG_ROTHMAN_Nicole Eng
Sample CAD DWG_ROTHMAN_Nicole EngSample CAD DWG_ROTHMAN_Nicole Eng
Sample CAD DWG_ROTHMAN_Nicole Eng
 
SAMPLE PORTFOLIO
SAMPLE PORTFOLIOSAMPLE PORTFOLIO
SAMPLE PORTFOLIO
 
2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revised2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revised
 
E3.pdf
E3.pdfE3.pdf
E3.pdf
 
NMohamed_PortfolioExtract
NMohamed_PortfolioExtractNMohamed_PortfolioExtract
NMohamed_PortfolioExtract
 
ADU Plan 5 - 1200 sqft (1).pdf
ADU Plan 5 - 1200 sqft (1).pdfADU Plan 5 - 1200 sqft (1).pdf
ADU Plan 5 - 1200 sqft (1).pdf
 
IS252_PAA
IS252_PAAIS252_PAA
IS252_PAA
 
Regulation for cgd_technical_standard_071.8
Regulation for cgd_technical_standard_071.8Regulation for cgd_technical_standard_071.8
Regulation for cgd_technical_standard_071.8
 
15RDM01-Academy Demo Plan
15RDM01-Academy Demo Plan15RDM01-Academy Demo Plan
15RDM01-Academy Demo Plan
 
66 k v_sf6_bkr_r3_may12
66 k v_sf6_bkr_r3_may1266 k v_sf6_bkr_r3_may12
66 k v_sf6_bkr_r3_may12
 
The Fragrance Outlet - Grand Rapids, MI 8.20.15
The Fragrance Outlet - Grand Rapids, MI 8.20.15The Fragrance Outlet - Grand Rapids, MI 8.20.15
The Fragrance Outlet - Grand Rapids, MI 8.20.15
 
Electricty wiring code 2016
Electricty wiring code 2016Electricty wiring code 2016
Electricty wiring code 2016
 
Utility Basic Details in Ahmedabad Railway Station Re Development.pptx
Utility Basic Details in Ahmedabad Railway Station Re Development.pptxUtility Basic Details in Ahmedabad Railway Station Re Development.pptx
Utility Basic Details in Ahmedabad Railway Station Re Development.pptx
 
General structural notes
General structural notesGeneral structural notes
General structural notes
 
Subpart K - Electrical
Subpart K - ElectricalSubpart K - Electrical
Subpart K - Electrical
 
KFC - Surprise, AZ
KFC - Surprise, AZKFC - Surprise, AZ
KFC - Surprise, AZ
 
04-3-TS_Vol-II_,Sec-IV,_Pre_Comm_R1.pdf
04-3-TS_Vol-II_,Sec-IV,_Pre_Comm_R1.pdf04-3-TS_Vol-II_,Sec-IV,_Pre_Comm_R1.pdf
04-3-TS_Vol-II_,Sec-IV,_Pre_Comm_R1.pdf
 

Recently uploaded

Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 

Recently uploaded (20)

Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 

05.18.2015 PLBG GUNER RESIDENCE.pdf

  • 1. M RESIDENCE GUNER P0.1 PLUMBING GENERAL NOTES PLUMBING GENERAL NOTES 1. THE ARCHITECTURAL DESIGN DRAWINGS SHALL INDICATE THE EXACT LOCATIONS AND MOUNTING HEIGHTS OF ALL PLUMBING FIXTURES. 2. THE ARCHITECTURAL DESIGN DRAWINGS SHALL INDICATE ALL ACCESSIBLE FIXTURE LOCATIONS AND MOUNTING HEIGHTS. FURNISH ALL EXPOSED HOT WATER AND DRAIN PIPING BELOW ACCESSIBLE LAVATORIES AND SINKS WITH INSULATION. ALL WATER CLOSET FLUSHING LEVERS SHALL BE TO THE WIDE SIDE OF THE STALL. 3. TRAPS FOR ALL LAVATORIES AND SINKS SHALL TRAP STRAIGHT BACK TO WALL WITH ALL REQUIRED OFFSETS HAPPENING WITHIN THE WALL. 4. ALL PLUMBING WORK SHALL BE INSTALLED TO AVOID INTERFERENCE WITH ELECTRICAL AND MECHANICAL EQUIPMENT AND STRUCTURAL FRAMING. 5. ALL CLEANOUTS SHALL BE INSTALLED WHERE EASILY ACCESSIBLE. THE CONTRACTOR SHALL COORDINATE ALL CLEANOUT LOCATIONS WITH ALL EQUIPMENT, CABINETS AND OTHER OBSTRUCTION PRIOR TO ANY INSTALLATION. CLEANOUTS MUST BE EXTENDED TO FLUSH WITH FINISHED WALL. 6. ALL PLUMBING FIXTURE VENTS SHALL TERMINATE A MINIMUM OF 12 INCHES FROM ANY VERTICAL SURFACE AND 10 FEET FROM ANY OUTSIDE AIR INTAKES. 7. ALL VALVES, UNIONS, ETC. TO BE SAME SIZE AS PIPE UNLESS OTHERWISE INDICATED ON PLANS. 8. UNIONS SHALL BE PROVIDED AND INSTALLED AFTER EACH VALVE AND PRIOR TO ALL EQUIPMENT CONNECTIONS. 9. ALL WORK AND MATERIAL SHALL BE IN COMPLIANCE WITH AND PERFORMED AND INSTALLED INCOMFORMANCE WITH THE FOLLOWING CODES AS ADOPTED AND AMENDED BY THE INSPECTING AUTHORITY. NOTHING IN THESE DRAWINGS IS TO BE CONSTRUED TO PERMIT WORK NOT CONFORMING TO THESE CODES OR OTHERS APPLICABLE TO THIS PROJECT: BUILDING STANDARDS ADMINISTRATIVE CODE, PART 1, TITLE 24 C.C.R. 2013 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24 C.C.R. 2013 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 C.C.R. 2013 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 C.C.R. 2013 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R. 2013 CALIFORNIA ENERGY CODE, PART 6, TITLE 24 C.C.R. 2013 CALIFORNIA FIRE CODE (CFC), PART 9, TITLE 24 C.C.R., 2013 CALIFORNIA REFERENCED STANDARDS, PART 12, TITLE 24 C.C.R. 2013 TITLE 19, CCR, PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS 2013 NFPA 13 - AUTOMATIC SPRINKLER SYSTEMS 10. BEFORE FABRICATION OR INSTALLATION THE CONTRACTOR SHALL VERIFY EXACT LOCATIONS OF ALL MECHANICAL EQUIPMENT AND EQUIPMENT PROVIDED UNDER OTHER SECTIONS OF SPECIFICATIONS. ROUGH-IN LOCATIONS AND REQUIREMENTS SHALL BE COORDINATED IN THE FIELD. 11. ALL SEWER AND VENT PIPING SHALL SLOPE AT 2%. 12. ALL VALVES, TRAP PRIMERS, WATER HAMMER ARRESTERS OR OTHER EQUIPMENT LOCATED IN WALLS OR ABOVE NON-ACCESSIBLE CEILINGS SHALL BE INSTALLED BEHIND AN ACCESS PANEL. ALL PIPING & DEVICES SHALL BE INSTALLED ABOVE CEILING, WITHIN WALLS, BELOW FLOORS, OR OTHERWISE CONCEALED. EXCEPT PIPING AND DEVICES INSTALLED IN MECHANICAL ROOMS AND OTHER UNFINISHED SPACES. 13. ALL PLUMBING FIXTURES AND EQUIPMENT SHALL BE CERTIFIED BY THE CALIFORNIA STATE ENERGY COMMISSION TO COMPLY WITH EFFICIENCY STANDARDS PER SECTION 110 OF THE TITLE-24 REGULATIONS. 14. ALL HOT WATER SUPPLY & RETURN PIPING SHALL BE INSULATED. INSULATION SHALL HAVE A FLAME SPREAD OF NOT MORE THAN 25 AND A SMOKE DENSITY NOT EXCEEDING 50 PER CMC SEC. 12.1.2.1.8 SEE SPECIFICATION FOR OTHER REQUIREMENTS. 15. PIPING THROUGH FIRE RATED WALLS SHALL BE PROTECTED PER U.L. FIRE RESISTANCE SYSTEM NO. WL1001. THE ARCHITECTURAL DESIGN DRAWINGS SHALL INDICATE ALL RATED WALL LOCATIONS. 16. SEISMIC BRACING AND ANCHORAGE REQUIREMENTS ARE AS FOLLOWS: A. THE SEISMIC ANCHORAGE FOR ALL MECHANICAL AND ELECTRICAL EQUIPMENT SHALL BE DESIGNED TO WITHSTAND A LATERAL FORCE: 1. CALCULATED AS SPECIFIED IN SECTION 1632A AND TABLE 16A-0 OF THE VOL. 2, TITLE 24, 2013 CBC. B. THE ATTACHMENT OF THE FOLLOWING ITEMS SHALL BE DESIGNED TO RESIST THE FORCES PRESCRIBED IN PART 2, TITLE 24, 2013 CBC: 1. EQUIPMENT WEIGHING LESS THAN 400 LBS. SUPPORTED DIRECTLY ON FLOOR OR ROOF. 2. FURNITURE REQUIRED TO BE ATTACHED IN ACCORDANCE WITH PART 2, TITLE 24, C.C.R. 3. TEMPORARY OR MOBILE EQUIPMENT. 4. EQUIPMENT WEIGHING LESS THAN 20 LBS. SUPPORTED BY VIBRATION ISOLATORS. 5. EQUIPMENT WEIGHING LESS THAN 20 LBS. SUSPENDED FROM A ROOF OR HUNG FROM A WALL. 17. THE PLUMBING CONTRACTOR SHALL PROVIDE THE WATER & SEWER SYSTEMS TO A POINT OF CONNECTION 5'-0" OUTSIDE OF THE BUILDING. PIPING BEYOND THIS POINT IS SPECIFIED UNDER ANOTHER SECTION OF THE SPECIFICATIONS AND SHALL BE AS SHOWN ON THE CIVIL DRAWINGS. FINAL CONNECTIONS TO SITE PIPING SHALL BE BY THE PLUMBING CONTRACTOR. 18. WATER HAMMER ARRESTERS SHALL BE PROVIDED WHERE REQUIRED AND NECESSARY FOR AND TO ALL FIXTURES, EQUIPMENT OR APPLIANCES WITH QUICK CLOSING VALVE AND SHALL BE OF TYPE SPECIFIED. 19. ALL PIPE SIZES SHALL BE THE SAME AS THE UPSTREAM PIPE SIZES UNLESS OTHERWISE INDICATED ON PLAN. 20. CLEANOUT SHALL BE PROVIDED AS PER CPC SECTION 707. 21. NO STRUCTURAL MEMBER SHALL BE CUT, NEITHER DRILLED NOR NOTCHED 24. WITHOUT PRIOR WRITTEN AUTHORIZATION FROM THE STRUCTURAL ENGINEER. 22. THESE DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC AND ARE NOT INTENDED TO INDICATE ALL DETAILS AND NECESSARY OFFSETS OF PIPING. THE CONTRACTOR SHALL INSTALL MATERIAL AND EQUIPMENT IN A MANNER AS TO CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE HEADROOM, AND KEEP OPENINGS AND PASSAGEWAYS CLEAR. ALL INSTALLATIONS SHALL BE CONSISTENT WITH NORMALLY ACCEPTABLE INDUSTRY STANDARDS. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT IN WRITING OF ANY DISCREPANCIES OR CONFLICTS THAT WOULD EFFECT THE SYSTEM PERFORMANCE OR INCUR ADDITIONAL COSTS. THIS NOTIFICATION SHALL BE SUBMITTED PRIOR TO INSTALLATION OF THE ITEMS CONCERNED. 23. NOT USED 24. PROVIDE COMPLETE CONDENSATE DRAIN PIPING FOR ALL AC UNITS AND DISCHARGE CONDENSATE TO AN APPROVED RECEPTOR. 25. ALL LAYOUTS, PIPE SIZES, FIXTURE & EQUIPMENT SELECTIONS SHOWN ON THESE PLANS ARE FOR REFERENCE ONLY. THE CONTRACTOR SHALL PROVIDE A COMPLETE PLUMBING SYSTEM. THE DESIGN, CALCULATIONS, FIXTURE, TRIM, EQUIPMENT AND MATERIALS SELECTIONS & DRAWINGS SHALL BE SUBMITTED FOR REVIEW AND APPROVAL AS SPECIFIED. 26. INSULATION THICKNESS AND R-VALUES SHALL EXCEED THE REQUIREMENTS OF TITLE 24 BY AT LEAST 20 PERCENT OR NEXT LARGER STANDARD SIZE, WHICH EVER IS GREATER. PIPE INSULATION SHALL BE NOT LESS THAN 1.0 INCH THICK, NOT INCLUDING THE MOISTURE BARRIER OR EXTERIOR JACKET THICKNESS. 27. ALL GAS PRESSURE REGULATOR SHALL BE LOCATED AT GROUND LEVEL OR CLOSE TO APPLIANCE AND LOCATIONS SHALL BE COORDINATED WITH THE ARCHITECT FOR APPROVAL. SIZE AND INSTALLATION SHALL BE AS PER MANUFACTURER'S RECOMMENDATIONS. NO MEDIUM PRESSURE GAS INSIDE THE BUILDING. 28. NO GAS & WATER PIPE SHALL BE INSTALLED UNDER BUILDING SLAB. GAS & WATER PIPES SHALL RISE TIGHT AGAINST EXTERIOR WALL UP TO MIN. 18" AFF AND PENETRATE INTO BUILDING. PROVIDE SHUT-OFF VALVE AND REGULATOR ABOVE GRADE AT INCOMING GAS RISERS. 29. CONTRACTOR SHALL CAREFULLY REVIEW THESE PLANS AND SPECIFICATIONS PRIOR TO BID. CONTRACTOR SHALL ALSO REVIEW PLANS AND SPECIFICATIONS OF OTHER RELATED TRADES (INCLUDING MECHANICAL, CIVIL, STRUCTURAL, AND ELECTRICAL) PRIOR TO BID TO INSURE AN ACCURATE UNDERSTANDING OF EXACT SCOPE OF WORK. ANY ITEMS REQUIRING DESCRIPTION CLARIFICATION SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT IN SUFFICIENT TIME TO BE INCORPORATED INTO THE BID. 30. ALL PLUMBING SYSTEM COMPONENTS SHALL MEET OR EXCEED THE REQUIREMENTS OF C.B.C. (CALIFORNIA EDITION), CMC, CPC, NEC, NFPA, ASTM, ANSI, AND ALL LOCAL AND STATE CODE REQUIREMENTS. 31. ALL PLUMBING EQUIPMENT LISTED IN (CCR) SECTION 113 OF THE 2013 CALIFORNIA CODE OF REGULATIONS, TITLE-24, PART 1, ENERGY EFFICIENCY STANDARDS MUST BE CERTIFIED BY THE MANUFACTURER TO MEET OR EXCEED SPECIFICATIONS OR EFFICIENCIES ADOPTED BY THE CEC. 32. ALL PIPING EXPOSED TO WEATHER SHALL BE METALLIC. 33. ALL FERROUS PIPING EXPOSED TO WEATHER SHALL BE GALVANIZED. 34. ALL PIPES, FITTINGS AND FIXTURES USED TO CONVEY POTABLE WATER SHALL BE LEAD FREE IN COMPLIANCE WITH CALIFORNIA AB 1953. 35. ALL INSULATING MATERIALS INSTALLED MUST BE CERTIFIED BY CALIFORNIA ENERGY COMMISSION TO MEET C.E.C. ENERGY EFFICIENCY STANDARDS (E.E.S.) SECTION 120.3 AND SECTION 1201.3.2.1.1 OF CMC (CALIFORNIA EDITION). 36. ALL INSULATION INSTALLED SHALL MEET THE FLAME SPREAD AND SMOKE DENSITY REQUIREMENTS OF SECTION 719 OF THE 2013 CBC. 37. ALL GAS APPLIANCES MUST HAVE PILOTLESS IGNITION SYSTEM IN ACCORDANCE WITH SECTION 115 OF THE 2013 CALIFORNIA CODE OF REGULATIONS, TITLE-24, PART 1, ENERGY EFFICIENCY STANDARDS, TABLE 4-4. 38. ALL FIXTURES REQUIRED TO BE ACCESSIBLE SHALL BE INSTALLED AS PER THE LATEST REQUIREMENTS OF TITLE 24 AND ADA (AMERICANS WITH DISABILITIES ACT). 39. CROSS CONNECTION PROTECTION SHALL BE PROVIDED AT ALL POTABLE WATER SUPPLIED APPLIANCES AND EQUIPMENT (OTHER THAN THOSE LISTED IN INFORMATION BULLETIN 103). 40. ALL HEATERS FOR DOMESTIC HOT WATER MUST BE CERTIFIED BY THE MANUFACTURER TO MEET THE SPECIFICATIONS OR EFFICIENCIES AS ADOPTED BY THE CEC. IN ACCORDANCE WITH SECTION 110.1 OF THE CCR AND ENERGY EFFICIENCY STANDARDS RESIDENTIAL NON-RESIDENTIAL. 41. A WATER HEATER PRESSURE AND TEMPERATURE RELIEF DRAIN THAT TERMINATES OUTSIDE THE BUILDING SHALL COMPLY WITH SECTION 608.5 OF CPC. 42. WATER HEATER SHALL BE ANCHORED OR STRAPPED TO RESIST HORIZONTAL DISPLACEMENT DUE TO EARTHQUAKE MOTION PER SECTION 508.2 OF CPC. 43. WATER HEATER SHALL COMPLY WITH SECTION 608.3 OF CPC, FOR THERMAL EXPANSION REQUIREMENTS. 44. LAVATORY FAUCETS IN PUBLIC RESTROOM SHALL BE SELF CLOSING TYPE. 45. NON RESIDENTIAL LAVATORY FAUCETS SHALL BE 0.4 GPM MAXIMUM. 46. METERING FAUCETS SHALL BE 0.5 GPM MAXIMUM. 47. KITCHEN FAUCETS AND WASH FOUNTAINS SHALL BE 1.8 GPM MAXIMUM. 48. WATER CLOSETS (GRAVITY TANK TYPE, FLUSHOMETER TANK, FLUSHOMETER VALVE AND ELECTROMECHANICAL HYDRAULIC TYPE) SHALL BE 1.28 GPF MAXIMUM. 49. URINALS SHALL BE 0.5 GPF MAXIMUM. DENTAL AIR POINT OF CONNECTION / POINT OF DISCONNECTION PLUMBING LEGEND DWG/DWGS DRAWING/DRAWINGS PSI POUNDS PER SQUARE INCH POUNDS PER SQUARE INCH EQUIPMENT IDENTIFICATION SYMBOL W.C. SOV VTR SQ FT TYP SPEC P&TRV QTY WATER COLUMN PRESSURE AND TEMPERATURE RELIEF VALVE SHUT OFF VALVE VENT THRU ROOF SQUARE FEET TYPICAL SPECIFICATION QUANTITY GALV GALVANIZED PD OPER NTS MTD MIN MS MECH MAX IPS I.E. HD MOP SINK / SERVICE SINK PRESSURE DROP NOT TO SCALE OPERATING MOUNTED MINIMUM MECHANICAL MAXIMUM IRON PIPE SIZE INVERT ELEVATION HEAD FT HD GPM GA GPF FH FT FFE ELECT ELEV EA DN GALLONS PER MINUTE GALLONS PER FLUSH FINISHED FLOOR ELEVATION FEET OF HEAD GAUGE FUME HOOD FEET DEGREES FAHRENHEIT ELECTRICAL ELEVATION EACH DOWN AFF B/G B/S C.I. DF B/C ARCH AFG FS SOV GPR FD ABOVE FINISHED FLOOR ARCHITECT OR ARCHITECTURAL ABOVE FINISHED GRADE BELOW GRADE DRINKING FOUNTAIN CAST IRON BELOW SLAB BELOW COUNTER GAS PRESSURE REGULATOR PLUG VALVE / GAS COCK PRESSURE GUAGE SHUT OFF VALVE FLOOR SINK FLOOR DRAIN FCO/COTG WCO WHA CD CD DIRECTION OF FLOW PIPE SLOPE & DIRECTION OF FALL FLOOR CLEANOUT OR CLEANOUT TO GRADE WATER HAMMER ARRESTOR WALL CLEANOUT PIPE CONTINUATION PIPE BREAK THERMOMETER CONDENSATE DRAIN PIPING PIPE BRANCH - TOP CONNECTION PIPE BRANCH - BOTTOM CONNECTION PIPE BRANCH - SIDE CONNECTION PIPE CAP PIPE DOWN PIPE UP DCA G HW G HWR DCA VT CW SYMBOL W POC/POD W ABBREVIATION DOMESTIC HOT WATER RETURN DOMESTIC COLD WATER PIPING NATURAL GAS PIPING - 8" WATER COLUMN DOMESTIC HOT WATER SANITARY VENT PIPING SANITARY OR WASTE PIPING EQUIPMENT IDENTIFIER EQUIPMENT TYPE DESCRIPTION DVAC DVAC DENTAL VACUUM HB (+18") PW W PRESSURIZED WASTE PIPING
  • 2. M RESIDENCE GUNER P0.2 PLUMBING CALCULATIONS AND EQUIPMENT SCHEDULES PLUMBING FIXTURE SCHEDULE ITEM WASTE TRAP VENT CW HW MOUNT DESCRIPTION 4" 4" 2" 1 2" -- FLOOR WATER CLOSET (FLUSH TANK): "TOTO" MS970CEMFG WASHLET WITH INTEGRATED G500, 1.28 GPF AND 0.9 GPF. DUAL FLUSH, ELONGATED BOWL, 12" ROUGH-IN. 2" 2" 2" 1 2" 1 2" FLOOR BATHTUB: SEE ARCHITECTURAL SPECIFICATIONS 2" 2" 2" 1 2" 1 2" FLOOR BATHTUB: SEE ARCHITECTURAL SPECIFICATIONS 2" 2" 2" 1 2" 1 2" FLOOR 6 SHOWER HEAD: SEE ARCH PLANS FOR TILED SHOWER, PROVIDE FITTINGS "KOHLER" K-13688 SHALL HAVE A FLOW OF 2.5 GPM. PROVIDE DIVERTER VALVE CONTROL 3 SHOWER HEAD ONLY. PIPE 6 SHOWER HEAD TO HAVE 2 DIVERTER VALVE. EACH DIVERTER VALVE SHALL CONTROL 3 SHOWER HEAD ONLY. INSTALL PER MANUFACTURER'S RECOMMENDATION AND INSTRUCTION MANUAL OR EQUAL 2" 2" 2" 1 2" 1 2" FLOOR 2 SHOWER HEAD: SEE ARCH PLANS FOR TILED SHOWER, PROVIDE FITTINGS "KOHLER" K-13688 SHALL HAVE A FLOW OF 2.5 GPM. PROVIDE DIVERTER VALVE TO CONTROL SINGLE SHOWER HEAD ONLY. INSTALL PER MANUFACTURER'S RECOMMENDATION AND INSTRUCTION MANUAL OR EQUAL 2" 2" 2" 1 2" 1 2" FLOOR SHOWER HEAD: SEE ARCH PLANS FOR TILED SHOWER, PROVIDE FITTINGS "KOHLER" K-13688 SHALL HAVE A FLOW OF 2.5 GPM. 2" 2" 2" 1 2" 1 2" FLOOR LAVATORY: WITH 8" ON CENTER. SEE ARCHITECTURAL DRAWINGS FOR SPECIFICATIONS. PROVIDE FAUCET "KOHLER" OBLO WIDESPREAD BATHROOM SINK FAUCET K-10086-9, METAL CONSTRUCTION, BRASS VALVE BODIES. 1.5 GPM 2" 2" 2" 1 2" 1 2" WALL LLAVATORY: WITH 8" ON CENTER. SEE ARCHITECTURAL DRAWINGS FOR SPECIFICATIONS. PROVIDE FAUCET "KOHLER" OBLO WIDESPREAD BATHROOM SINK FAUCET K-10086-9, METAL CONSTRUCTION, BRASS VALVE BODIES. 1.5 GPAUCET PER ARCH SPECIFICATION 2" 2" 1 1 2" 1 2" 1 2" WALL KITCHEN SINK: "JUST". 16 GAUGE TYPE 304, 18-8 STAINLESS STEEL. SEAMLESS DIE-DRAWN CONSTRUCTION. SELF RIMMING TOP MOUNT GRIP-RIM PLUS WITH STAINLESS STEEL MOUNTING CHANNELS. PROVIDE FAUCET "BLANCO CULINA MODEL 441331 2.2 GPM.PROVIDE 3/4HP IN-SINKEARATOR GARBAGE DISPOSER. ELECTRICAL 120 VOLTS, 60HZ, 1725 RPM, 9.5 AMPS 2" 2" 1 1 2" 1 2" 1 2" WALL LAUNDRY TUB: "JUST" . 16 GAUGE TYPE 304, 18-8 STAINLESS STEEL. SEAMLESS DIE-DRAWN CONSTRUCTION. SELF RIMMING TOP MOUNT GRIP-RIM PLUS WITH STAINLESS STEEL MOUNTING CHANNELS. PROVIDE FAUCET PER ARCHITECTS SPECIFICATION/OWNER 2" 2" 2" -- -- FLOOR FLOOR SINK: "ZURN" 1901-2 HALF GRATE RECEPTOR 12"x12"x8" DEEP CAST IRON BODY AND SQUARE SLOTTED MEDIUM DUTY GRATE WITH ACID RESISTANT PORCELAIN ENAMEL INTERIOR AND TOP. COMPLETE WITH ABS ANTI-SPLASH INTERIOR BOTTOM STRAINER 2" 2" 2 1 2" 1 2" `` CLOTHESWASHER BOX OUTLET: "LSP" KAHUNA OUTLET BOX WITH HAMMER ARRESTERS, PLASTIC SIMPLEX HANDLE, CLEAR COVER AND OPTIONAL CONDENSATE OB-2111 2" 2" 2" -- -- FLOOR FLOOR DRAIN: "ZURN" Z-415 FLOOR DRAIN. D.C.C.I. BODY WITH BOTTOM OUTLET, COMBINATION INVERTIBLE MEMBRANE CLAMP AND ADJUSTABLE COLLAR WITH TYPE "B" POLISHED NICKLE BRONZE STRAINER. PROVIDE TRAP PRIMER CONNECTION WC-1 BTH-1 BTH-2 SHR-1 SHR-2 SHR-3 LV-1 LV-2 KS-1 LT-1 FS-1 CWB-1 FD-1 FIXTURE DATA AND WATER CALCULATION ITEM DESCRIPTION NO. OF FIXT WFU 'S DFU 'S CW HW SEWER WC-1 WATER CLOSET (TANK TYPE) 10 2.5 4.0 25.0 0 40.0 LV-1 LAVATORY 10 1.0 1.0 10.0 7.5 10.0 LV-2 LAVATORY 2 1.0 1.0 2.0 1.5 2.0 BTH-1 BATH TUB 5 4.0 2.0 20.0 15.0 10.0 BTH-2 BATH TUB 2 4.0 2.0 8.0 6.0 4.0 SHR-1 SHOWER ( 6 HEADS) 6 4.0 2.0 24.0 18.0 12.0 SHR-2 SHOWER ( 2 HEADS) 2 4.0 2.0 8.0 6.0 4.0 SHR-3 SHOWER ( 1 HEADS) 1 4.0 2.0 4.0 3.0 2.0 KS-1 KITCHEN SINK 4 1.5 2.0 6.0 4.5 8.0 -- DISHWASHER 4 1.5 1.0 6.0 4.5 4.0 CWB-1 CLOTHESWASHER 3 4.0 3.0 12.0 9.0 9.0 LT-1 LAUNDRY TUB 1 1.5 2.0 1.5 1.1 2.0 FD-1 FLOOR DRAIN 1 0 2.0 0 0.0 2.0 FS-1 FLOOR SINK 0 0 2.0 0 0.0 0.0 HB-1 HOSE BIBB 1 2.5 0.0 2.5 0 0.0 HB-1 HOSE BIBB (ADDITIONAL) 9 1.0 0.0 9.0 0 0.0 TOTAL WFU'S, DFU'S 0 0 138.0 76.1 109.0 MAIN DOMESTIC WATER SUPPLY SIZING BASE ON LATEST EDITION CPC 2013 TABLE A-2, CHART A-4 COLD WATER FIXTURES UNITS = 53 GPM HOT WATER FIXTURES UNITS = 37 GPM COLD WATER PIPING SIZING VELOCITY NOT TO EXCEED 8 FEET PER SECOND PIPE DIA GPM FT FIXT UNIT FV FIXT UNIT VELOCITY 1 2" 2.7 -- -- 3.2 3 4" 7.3 3 -- 4.9 1" 15.7 11 5 5.8 1 1 4" 26.5 41 9 6.9 1 1 2" 40.6 89 28 7.9 2" 71.3 232 114 8.0 2 1 2" 119.6 477 361 8.0 3" 177.7 801 756 8.0 FIXTURE EQUIPMENT SCHEDULE ITEM LOCATION DESCRIPTION OUTDOOR TANKLESS WATER HEATER: "NORITZ" MODEL NC380-SV-ASME-LP SERIES OUTDOOR UNIT. WATER HEATER WATER HEATER IS RATED 150 PSI WORKING PRESSURE AND 300 PSI TEST PRESSURE. GAS SUPPLY PRESSURE SHALL BE 4.0" TO 10.5"WC FOR NATURAL GAS. PROVIDE OUTDOOR CAP VC-132. 19.1" WIDTH x 11.8 DEPTH x 29.7 HEIGHT. INDOOR TANKLESS WATER HEATER: "NORITZ" MODEL NC 380-SV-ASME-LP INDOOR WITH VENT CAP, MAXIMUM FLOW OF 13.2 GPM, MINIMUM ACTIVATION FLUE 0.7GPM, 380,000 BTUH INPUT. POWER SUPPLY 120VAC (60 HZ) CURRENT DRAW 3.091 AMPS, 5" EXHAUST VENT DIAMETER, CATEGORY III STAINLESS STEEL. MAXIMUM VENT LENGTH WITH 1 ELBOW 45 FEET. REFER TO MANUFACTURER'S INSTALLATION MANUAL INDOOR TANKLESS WATER HEATER: "NORITZ" MODEL NRC98-DV-LP INDOOR, MAXIMUM FLOW OF 9.8 GPM, MINIMUM ACTIVATION FLOW 0.5GPM, 180,000 BTUH INPUT. POWER SUPPLY 120VAC (60 HZ) CURRENT DRAW 1.I775 AMPS, 3" PVC SCHEDULE 40 AIR INTAKE AND EXHAUST. 4 ELBOWS = 35 FEET MAX. STRAIGHT VENT, 3 ELBOWS = 41 FEET MAX. STRAIGHT VENT, 2 ELBOWS = 47 FEET MAX. STRAIGHT VENT. 1 ELBOWS = 53 FEET MAX. STRAIGHT VENT. REFER TO MANUFACTURER'S INSTALLATION SEE PLAN WATER HAMMER ARRESTERS: "SIOUX CHIEF" HYDRA RESTER WATER HAMMER ARRESTOR WITH HARD DRAWN SEAMLESS TYPE "K" COPPER BODY. SEE PLAN TRAP PRIMER: "MIFAB" #M-500 PRESSURE DROP ACTIVATED, BRASS CONSTRUCTION, PROVIDE WITH M1-DU 4-WAY DISTRIBUTION UNIT (IF APPLICABLE), PROVIDE WITH ACCESS PANEL. WATER HEATER ROOM EXPANSION TANK: "FLEXCON" PH-5 2.1 GALLONS 11" HEIGHT X 8" DIAMETER, 5LBS TOTAL WEIGHT. MAXIMUM PRE-CHARGE 40 PSIG. COLD WATER PIPING SIZING VELOCITY NOT TO EXCEED 5 FEET PER SECOND PIPE DIA GPM FT FIXT UNIT FV FIXT UNIT VELOCITY 1 2" 2.7 -- -- 5.0 3 4" 7.3 3 -- 5.0 1" 13.4 8 -- 5.0 1 1 4" 19.6 20 6 5.0 1 1 2" 27.5 31 10 5.0 2" 46.4 117 41 5.0 2 1 2" 72.3 306 117 5.0 3" 115.6 456 340 5.0 FRICTION LOSSES PRESSURE PER CIVIL DESIGN FOR WELL TANK ELEVATION IN RELATION TO FINISHED FLOOR ELEVATION 75 PSI LENGTH OF DOMESTIC WATER SYSTEM FROM WELL TANK TO THE FURTHEST RUN. 477 FT EXISTNG 3/4" WATER METER -- PSI BACKFLOW PREVENTER 11 PSI PRESSURE REGULATOR 0 PSI TOTAL LOSSES 11 PSI PRESSURE INSIDE THE BUILDING 66 PSI STATIC HEIGHT 25 FT RESIDUAL PRESSURE: 25 PSI PRESSURE AVAILABLE FOR FRICTION LOSS 30.25 PSI ALLOWABLE FRICTION LOSS PER HUNDRED FEET 6.3 PSI 39. AT THE TIME OF ROUGH INSTALLATION AND DURING STORAGE ON THE CONSTRUCTION SITE UNTIL FINAL STARTUP OF THE HEATING, COOLING AND VENTILATING EQUIPMENT, ALL DUCT AND OTHER RELATED AIR DISTRIBUTION COMPONENT OPENINGS SHALL BE COVERED WITH TAPE, PLASTIC, SHEET METAL OR OTHER METHODS ACCEPTABLE TO THE ENFORCING AGENCY TO REDUCE DUST, WATER AND DEBRIS WHICH MAY ENTER SYSTEM (CAL GREEN SECTION 5.504.3). 40. WATER HEATER SHALL BE ANCHORED OR STRAPPED TO RESIST HORIZONTAL DISPLACEMENT DUE TO EARTHQUAKE MOTION PER SECTION 507.2 CPC 41. TOILET FLUSH CONTROLS SHALL COMPLY WITH THE FOLLOWING A. MOUNTED MAXIMUM 44 INCHES ABOVE FLOOR B. MOUNTED ON OPEN SIDE OF TOILET C. OPERABLE WITH MAXIMUM 5 POUNDS OF FORCE D. OPERABLE WITH ONE HAND AND WITHOUT TIGHT GRASPING, PINCHING, OR TWISTING OF WRIST PLUMBING GENERAL NOTES CONT. TABLE 5.303.2.3 FIXTURE FLOW RATES FIXTURE TYPE MAXIMUM FLOW RATE @ 20% REDUCTION SHOWER HEAD 2.5 GPM @ 80 PSI LAVATORY FAUCET - NON RESIDENTIAL 0.4 GPM @ 60 PSI KITCHEN FAUCETS - RESIDENTIAL AND NON-RESIDENTAIAL 1.8 GPM @ 60 PSI WASH FOUNTAINS 1.8(RIM SPACE (IN)/20 GPM @ 60 PSI) METERING FAUCETS 0.20 GALLONS PER CYCLE METERING FAUCETS FOR WASH FOUNTAINS 1.8(RIM SPACE (IN)/20 GPM @ 60 PSI) GRAVITY TANK TYPE WATER CLOSETS 1.28 GALLONS PER FLUSH FLUSHOMETER TANK TYPE WATER HEATERS 1.28 GALLONS PER FLUSH FLUSHOMETER VALVE WATER CLOSETS 1.28 GALLONS PER FLUSH ELECTROMECHANICAL HYDRAULIC WATER CLOSETS 1.28 GALLONS PER FLUSH URINALS 0.5 GALLONS PER FLUSH NOTE NO.1 INCLUDES SINGLE AND DUAL FLUSH WATER CLOSETS WITH AN EFFECTIVE FLUSH OF 1.28 GALLONS OR LESS: SINGLE FLUSH TOILETS - THE EFFECTIVE FLUSH VOLUME SHALL NOT EXCEED 1.28 GALLONS . THE EFFECTIVE FLUSH VOLUME IS THE AVERAGE FLUSH VOLUME WHEN TESTED IN ACCORDANCE WITH ASME A 112.19.233.2. DUAL FLUSH TOILETS - THE EFFECTIVE FLUSH VOLUME SHALL NOT EXCEED 1.28 GALLONS . THE EFFECTIVE FLUSH VOLUME IS DEFINED AS THE COMPOSITE, AVERAGE FLUSH VOLUME OF TWO REDUCED FLUSHES AND ONE FULL FLUSH. FLUSH VOLUMES WILL BE TESTED IN ACCORDANCE WITH ASME A 112.19.2 AND ASME A 112.19.14. TABLE 5.303.4 STANDARDS FOR PLUMBING FIXTURES AND FIXTURE FITTINGS WATER CLOSETS (TOILETS) -FLUSHOMETER VALVE-TYPE SINGLE FLUSH, MAXIMUM FLUSH VOLUME ASME A 112.19.2/CSA B45.I - 1.28 GAL (4.8 L) WATER CLOSETS (TOILETS) -FLUSHOMETER VALVE-TYPE DUAL FLUSH, MAXIMUM FLUSH VOLUME ASME A 112.19.14 AND U.S. EPA WATERSENSE TENK-TYPE HIGH EFFICIENCY TOILET SPECIFICATION - 1.28 GAL (4.8 L) URINALS, MAXIMUM FLUSH VAVLE ASME A 112.19.2/CSA B45.1 - 0.5 GAL (1.9 L) PUBLIC LAVATORY FAUCETS: MAXIMUM FLOW RATE -0.5 GPM (1.9 L/MIN) ASME A 112.18.1/CSA B125.1 PUBLIC METERING SELF-CLOSING FAUCETS: MAXIMUM WATER USE - 0.25 GAL (1.0 L) PER METERING CYCLE ASME A 112.18.1/CSA B 125.1 CALIFORNIA GREEN BUILDING STANDARDS CODE 2013 CHAPTER 3 - GREEN BUILIDNG SECTION 301 GENERAL 301.1 SCOPE. BUILDINGS SHALL BE DESIGNED TO INCLUDE THE GREEN BUILDING MEASURES SPECIFIED AS MANDATORY IN THE APPLICATION CHECKLISTS CONTAINED IN THIS CODE. VOLUNTARY GREEN BUILDING MEASURES ARE ALSO INCLUDED IN THE APPLICATION CHECKLISTS AND MAY BE INCLUDED IN THE DESIGN AND CONSTRUCTION OF STRUCTURES COVERED BY THIS CODE, BUT ARE NOT REQUIRED UNLESS ADOPTED BY A CITY, COUNTY, OR CITY AND COUNTY AS SPECIFIED IN SECTION 101.7. SECTION 303 PHASED PROJECTS 301.1 SCOPE. BUILDINGS SHALL BE DESIGNED TO INCLUDE THE GREEN BUILDING MEASURES SPECIFIED AS MANDATORY IN THE APPLICATION CHECKLISTS CONTAINED IN THIS CODE. VOLUNTARY GREEN BUILDING MEASURES ARE ALSO INCLUDED IN THE APPLICATION CHECKLISTS AND MAY BE INCLUDED IN THE DESIGN AND CONSTRUCTION OF STRUCTURES COVERED BY THIS CODE, BUT ARE NOT REQUIRED UNLESS ADOPTED BY A CITY, COUNTY, OR CITY AND COUNTY AS SPECIFIED IN SECTION 101.7. 303.1.1 TENANT IMPROVEMENTS. THE PROVISIONS OF THIS CODE SHALL APPLY ONLY TO THE INITIAL TENANT OR OCCUPANT IMPROVEMENTS TO A PROJECT. SECTION 306 VOLUNTARY MEASURES 306.1 PURPOSE. VOLUNTARY MEASURES ARE INTENDED TO FURTHER ENCOURAGE BUILDING PRACTICES THAT IMPROVE PUBLIC HEALTH, SAFETY AND GENERAL WELFARE BY PROMOTING THE USE OF BUILDING CONCEPTS WHICH MINIMIZE THE BUILDING'S IMPACT ON THE ENVIRONMENT, PROMOTE A MORE SUSTAINABLE DESIGN AND HIGH-PERFORMANCE EDUCATIONAL FACILITIES. CHAPTER 5 - NON RESIDENTIAL MANDATORY MEASURES DIVISION 5.1 - PLANING AND DESIGN SECTION 5.101 GENERAL SECTION 5.101 GENERAL 5.01 PURPOSE. THE PROVISIONS OF THIS CHAPTER OUTLINE PLANNING, DESIGN AND DEVELOPMENT METHODS THAT INCLUDE ENVIRONMENTALLY RESPONSIBLE SITE SELECTION, BUILDING DESIGN, BUILDING SITING AND DEVELOPMENT TO PROTECT, RESTORE AND ENHANCE THE ENVIRONMENTAL QUALITY OF THE SITE AND RESPECT THE INTEGRITY OF ADJACENT PROPERTIES. DIVISION 5.2 - ENERGY EFFICIENCY SECTION 5.201 GENERAL 5.201.1 SCOPE. FOR THE PURPOSES OF MANDATORY ENERGY EFFICIENCY STANDARDS IN THIS CODE, THE CALIFORNIA ENERGY COMMISSION WILL CONTINUE TO ADOPT MANDATORY BUILDING STANDARDS. NOTE: IT IS THE INTENT OF THIS CODE TO ENCOURAGE BUILDINGS TO ACHIEVE EXEMPLARY PERFORMANCE IN THE AREA OF ENERGY EFFICIENCY. FOR THE PURPOSES OF ENERGY EFFICIENCY STANDARDS, THE CALIFORNIA ENERGY COMMISSION BELIEVES SPECIFICALLY, A GREEN BUILDING SHOULD ACHIEVE AT LEAST A 15 PERCENT REDUCTION IN ENERGY USAGE WHEN COMPARED TO THE STATE'S MANDATORY ENERGY EFFICIENCY STANDARDS. DIVISION 5.3 - WATER EFFICIENCY AND CONSERVATION SECTION 5.301 GENERAL 5.301.1 SCOPE. THE PROVISIONS OF THIS CHAPTER SHALL ESTABLISH THE MEANS OF CONSERVING WATER USED INDOORS, OUTDOORS AND IN WASTEWATER CONVEYANCE. 1. EACH PLUMBING FIXTURE AND FITTING SHALL BE MEET THE 20 PERCENT REDUCED FLOW RATE SPECIFIED IN TABLE 5.303.2.3, OR 2. A CALCULATION DEMONSTRATING A 20 PERCENT REDUCTION IN THE BUILDING "WATER USE BASELINE" AS ESTABLISHED IN TABLE 5.303.2.2 SHALL BE PROVIDED. 5.303.2 TWENTY PERCENT SAVINGS. A SCHEDULE OF PLUMBING FIXTURES AND FIXTURE FITTINGS THAT WILL REDUCE THE OVERALL USE OF POTABLE WATER WITHIN THE BUILDING BY 20 PERCENT SHALL BE PROVIDED. THE REDUCTION SHALL BE BASED ON THE MAXIMUM ALLOWABLE WATER USE PER PLUMBING FIXTURE AND FITTINGS AS REQUIRED BY THE CALIFORNIA BUILDING STANDARDS CODE. THE 20 PERCENT REDUCTION IN POTABLE WATER USE SHALL BE DEMONSTRATED BY ONE OF THE FOLLOWING METHODS: 5.303.4 WASTEWATER REDUCTION. EACH BUILDING SHALL REDUCE BY 20 PERCENT WASTEWATER BY ONE OF THE FOLLOWING METHODS. 5.303.2 TWENTY PERCENT SAVINGS. A SCHEDULE OF PLUMBING FIXTURES AND FIXTURE FITTINGS THAT WILL REDUCE THE OVERALL USE OF POTABLE WATER WITHIN THE BUILDING BY 20 PERCENT SHALL BE PROVIDED. THE REDUCTION SHALL BE BASED ON THE MAXIMUM ALLOWABLE WATER USE PER PLUMBING FIXTURE AND FITTINGS AS REQUIRED BY THE CALIFORNIA BUILDING STANDARDS CODE. THE 20 PERCENT REDUCTION IN POTABLE WATER USE SHALL BE DEMONSTRATED BY ONE OF THE FOLLOWING METHODS: PIPE MATERIAL SCHEDULE DOMESTIC WATER PIPING ABOVE GRADE TYPE "L" COPPER TUBING, HARD DRAWN CONFORMING TO ASTM B 88, WITH WROUGHT COPPER SOLDER SWEAT FITTINGS CONFORMING TO ASTM B 16.22. PROVIDE LABELING AND INSULATION DOMESTIC WATER PIPING UNDERGROUND OR BELOW SLAB: TYPE "K" HARD COPPER TUBING ANNEALED, WITH NO FITTINGS CONFORMING TO ASTM B 88. SEWER WASTE & VENT PIPING : PVC SCHEDULE 40 SOLID WALL PIPE AND PVC DWV FITTING SYSTEM. PVC SCHEDULE 40 PIPE SHALL BE IRON PIPE SIZE (IPS) CONFORMING TO ASTM D 1785 AND ASTM D 2665. FITTINGS SHALL CONFORM TO ASTM 2665. BURIED PIPE SHALL BE INSTALLED IN ACCORDANCE WITH ASTM D 2321 AND ASTM F 1665. SOLVENT CEMENT JOINTS SHALL BE MADE IN TWO STEPS PROCESS WITH TRAP PRIMER CONFORMING TO ASTM F 656 AND SOLVENT CEMENT CONFORMING TO ASTM D 25 64 CONDENSATE DRAIN PIPING ABOVE GRADE: TYPE "M" COPPER TUBING, HARD DRAWN CONFORMING TO ASTM B 88, WITH WROUGHT COPPER SOLDER SWEAT FITTINGS CONFORMING TO ASTM B 16.22. PROVIDE INSULATION AND LABELING CONDENSATE DRAIN PIPING BELOW GRADE: PVC SCHEDULE 40 PIPE AND FITTINGS SHALL BE MANUFACTURED FROM VIRGIN RIGID PVC VINYL COMPOUND A CELL CLASS OF 12454 AS IDENTIFIED IN ASTM D 1784 NATURAL GAS PIPING ABOVE GRADE: SCHEDULE 40 BLACK STEEL, CONFORMING TO ASTM A53 WITH 150 PSIG MALLEABLE IRON THREADED FITTINGS CONFORMING TO ANSI/ASME B16.3. PROVIDE LABELING LIQUIFIED PETROLUEM GAS PIPING EXPOSED TO WHEATHER: SCHEDULE 40 GALVANIZED STEEL, CONFORMING TO ASTM A53 WITH 150 PSIG MALLEABLE IRON THREADED FITTINGS CONFORMING TO ANSI/ASME B16.3. PROVIDE LABELING LIQUIDFIED PETROLUEM GAS PIPING BELOW GRADE: - POLYETHYLENE WITH FUSION WELD JOINTS.
  • 4. Man Cave Exercise Rm Stg. 3 Stg. 1 Bath Game Rm Cellar Porch Pool Stg. 2 Elev CL. REF CL. ICE REF. 134'-0" 134'-0" Stairs 1 WINE DW 144'-0" 144'-0" 18'-0" 32'-0" 18'-0" 5'-0" 20'-0" 24'-0" 6'-0" 4'-0" 16'-0" 24'-0" 6'-0" 50'-0" 30'-0" 4'-0" 6'-6" Bath D W BTH-1 2"VT-UP KS-1 WC-1 LV-1 WC-1 BTH-1 LV-1 4"FCO 4"FCO CWB-1 4"W TO SEPTIC TANK 2"VT-UP 4"W 4"W 2"W 4"W 4"W 2"VT-UP 2"VT-UP FS-1 FAU # 3 FAU # 1 FAU # 2 ROUTE CONDENSATE DRAIN TO SPILL INTO DRYWELL ROUTE CONDENSATE DRAIN TO SPILL INTO DRYWELL M RESIDENCE GUNER P2.0 PLUMBING BASEMENT LEVEL WASTE AND VENT PLAN
  • 5. 1/2 Bath Butler's Pantry Laundry Stg. Pantry CL. Retreat WC Master Br Great Rm Dining Kitchen Foyer Porch Courtyard Garage Work Shop Agricultural Garage Driveway Motor Court PG&E TRASH Hall Powder Elev CL. HOOD AND FAN 2'-6" OVEN FREEZER 134'-0" 134'-0" Stairs 2 Stairs 1 DW DW 144'-0" 144'-0" D W CRAWL SPACE 44'-0" 18'-0" 32'-0" 18'-0" 6'-0" 13'-0" 5'-0" 6'-0" 6'-0" 16'-0" 32'-0" 20'-0" 20'-0" 24'-0" 6'-0" 8'-0" 56'-0" 8'-0" 16'-0" 32'-0" 18'-0" 6'-0" 22'-0" 32'-0" 20'-0" 14'-0" 16'-0" 24'-0" 6'-0" 10'-0" 12'-0" 8'-0" 16'-0" 8'-0" 20'-6" 21'-6" 8'-0" 6'-0" 10'-0" REF Patio Entry Porch CL. Rm D D TO 2ND FLR. TO 2ND FLR. DW Master Bath 3"W-UP TO WC-1 ABV 2"W-UP TO BTH-1 ABV KS-1 WC-1 LV-1 CWB-1 LT-1 FD-1 KS-1 2"VT-UP 2"W-UP TO LV-1 ABV 4"W-UP TO WC-1 ABV 2"W-UP TO BTH-1 ABV 4"W-UP 2"W-UP TO LV-1 ABV 2"VT-UP 2"W-UP TO BTH-1 ABV 2"VT-UP 4"W-UP LV-1 WC-1 WC-1 SHD-1 SHR-1 TYP/6 LV-2 LV-2 LV-2 4"W 2"VT-UP 4"W-UP 4"W 4"W 4"W 4"W 3"W 3"W 4"W-UP TO 2ND FLR CEILING SPACE 2"W-UP TO CWB-1 ABV 2"W-UP TO LV-1 ABV 4"W-UP TO WC-1 ABV 2"W-UP TO BTH-1 ABV 2"VT-UP 2"VT-UP 4"W-UP AND DN 4"W-DN TO TO B/G 2"VT-UP ROUTE 4"W TO SEPTIC TANK. SEE CIVL ROUTE 4"W TO SEPTIC TANK. SEE CIVL 4"GCO 4"GCO BTH-2 2"VT-UP 2"VT-UP OFFSET VENT AND ROUTE AS INDICATED 4"FCO ROUTE TO SEPTIC TANK 2"VT-DN 2"VT-UP FROM BELOW FLR 2"VT-DN M RESIDENCE GUNER P2.1 PLUMBING FIRST LEVEL WASTE AND VENT PLAN
  • 6. Br 4 Br 3 Den Jr. Br. Open to Foyer Bath CL. Bath 4 Elev Balcony CL. Living Br 6 Br 5 Kitchenette Dining Bath CL. CL. REF D/W Powder TUB W/D 134'-0" 134'-0" Stairs 2 Stairs 1 Deck 144'-0" 144'-0" 7'-10" 56'-0" 8'-0" 24'-0" 32'-0" 18'-0" 6'-0" 22'-0" 42'-0" 24'-0" 16'-0" 24'-0" 6'-0" 22'-0" 42'-0" 24'-0" 16'-0" 12'-0" 12'-0" 6'-0" 18'-0" 26'-0" 12'-0" 18'-0" 13'-0" 5'-0" CL. Open to Courtyard Bath 3 Br 3 2"VT-UP, 2"VTR 2"VT-UP, 2"VTR 3"VT-UP, 3"VTR 2"VT-DN 3"VT-UP, 3"VTR WC-1 LV-1 WC-1 BTH-2 SHD-1 SHR-1 TYP/2 BTH-1 WC-1 LV-1 2"VT-UP, 2"VTR BTH-1 WC-1 WC-1 LV-1 CWB-1 KS-1 BTH-1 2"VT-DN 2"VTR 2"W-UP TO SHOWER ABV 2"W-UP TO LV-2 ABV 4"W-UP TO WC-1 ABV 2"VT-UP 4"W-DN M RESIDENCE GUNER P2.2 PLUMBING SECOND LEVEL WASTE AND VENT PLAN
  • 7. Green House Roof Top Garden Roof Below 134'-0" 134'-0" Stairs 2 144'-0" 144'-0" 22'-0" 16'-0" 8'-0" 20'-6" 30'-0" Utility WC-1 SHR-2 LV-2 M RESIDENCE GUNER P2.3 PLUMBING THIRD LEVEL WASTE AND VENT PLAN
  • 8. Man Cave Exercise Rm Stg. 3 Stg. 1 Bath Game Rm Cellar Porch Pool Stg. 2 Elev CL. REF CL. ICE REF. 134'-0" 134'-0" Stairs 1 WINE DW 144'-0" 144'-0" 18'-0" 32'-0" 18'-0" 5'-0" 20'-0" 24'-0" 6'-0" 4'-0" 16'-0" 24'-0" 6'-0" 50'-0" 30'-0" 4'-0" 6'-6" Bath D W 1" HOT WATER UP 1" COLD WATER UP 1/2"HW UP 1"CW-UP HB-1 HB-1 HB-1 LPG UP 3/4" 3/4" 1/2"-DN 1/2"DN 1/2"DN 3/4" 1/2"-DN CWB-1 1" 1" 1/2"DN 1/2"DN 3/4" 3/4" 1/2" FAU # 3 FAU # 1 FAU # 2 1/2''STUB FOR ICE MAKER LPG LPG LPG UP LPG M RESIDENCE GUNER P3.0 PLUMBING BASEMENT LEVEL WATER PIPING PLAN
  • 9. 1/2 Bath Butler's Pantry Laundry Stg. Pantry CL. Retreat WC Master Br Great Rm Dining Kitchen Foyer Porch Courtyard Garage Work Shop Agricultural Garage Driveway Motor Court PG&E TRASH Hall Powder Elev CL. HOOD AND FAN 2'-6" OVEN FREEZER 134'-0" 134'-0" Stairs 2 Stairs 1 DW DW 144'-0" 144'-0" D W CRAWL SPACE 44'-0" 18'-0" 32'-0" 18'-0" 6'-0" 13'-0" 5'-0" 6'-0" 6'-0" 16'-0" 32'-0" 20'-0" 20'-0" 24'-0" 6'-0" 8'-0" 56'-0" 8'-0" 16'-0" 32'-0" 18'-0" 6'-0" 22'-0" 32'-0" 20'-0" 14'-0" 16'-0" 24'-0" 6'-0" 10'-0" 12'-0" 8'-0" 16'-0" 8'-0" 20'-6" 21'-6" 8'-0" 6'-0" 10'-0" REF Patio Entry Porch CL. Rm D D TO 2ND FLR. TO 2ND FLR. DW Master Bath 1"CW-UP CW & HW UP TO 2ND LEVEL 1"CW & HW-DN TO BASEMENT LEVEL CW & HW UP TO 2ND LEVEL CW-DN HW-UP TO 2ND FLR INDOOR TANK LESS WATER HEATER SERVING 2ND FLOOR THIS AREA INDOOR TANKLESS WATER HEATER SERVING THE KITCHEN AND THE BATHROOM ABOVE OUTDOOR TANKLESS WATER HEATER SERVING MASTER BEDROOM AND THE BEDROOM ABOVE LPG LPG LPG LPG LPG TANK FOR REFERENCE ONLY BY CIVIL 2ND STAGE REGULATOR. FROM 5PSI TO 11"WC HW-DN 5'-0" 1 1 CW P.O.C. CW P.O.C. BY CIVIL. FOR REFERENCE ONLY BY CIVIL. FOR REFERENCE ONLY PROVIDE BACKWATER VALVE BY CIVIL. FOR REFERENCE ONLY 1ST STAGE REGULATOR. FROM HIGH PRESSURE TO (5 PSI) MEDIUM PRESSURE LPG DOWN TO BELOW GRADE WELL TANK. BY CIVIL. FOR REFERENCE ONLY LPG BELOW GRADE LPG BELOW GRADE 2 2 PROVIDE 3" PVC SCHEDULE 40 EXHAUST AND INTAKE 3 3 LPG UP LPG-DN HB-1 HB-1 HB-1 4 5" DIAMETER VENT STAINLESS STEEL CATEGORY VENT. INSTALL PER MFR'S RECOMMENDATION AND INSTALLATION GUIDE HB-1 HB-1 HB-1 HB-1 2" 2" 2" 2" 2" 2" 1" 3/4" 1/2"DN 5 5 GAS PIPING DN LPG LPG LPG 2ND STAGE REGULATOR FROM 5 PSI TO 7"WC 2ND STAGE REGULATOR FROM 5 PSI TO 7"WC LPG DN TO BASEMENT 1/2"CW & HW DN 2" 1" 1/2"CW & HW DN 1/2"DN 3/4" 1/2"DN 1/2" DN 3/4" 2" 1-1/4"-DN 1-1/4"DN HB-1 3/4" 2"CW 2"CW 2"CW CWB-1 HB-1 HB-1 2" 3/4" LPG LPG 2 M RESIDENCE GUNER P3.1 PROVIDE TWO PERMANENT COMBUSTION AIR 14" X 28" HIGH AND LOW. PER MANUFACTURER'S INSTALLATION GUIDE FOR NORIZT INSTANTANEOUS WATER HEATER MANUAL INSTRUCTIONS PAGE 13. ROUTE CONDENSATE DRAIN TO SPILL TO DAYLIGHT. BUILDING MAIN SHUT-OFF VALVE INSIDE CONCRETE UTILITY BOX MARKED "WATER". SHUT-OFF VALVE. PROVIDE ACCESS PANEL IF LOCATED ABOVE HARDLID CEILING. PROVIDE "SYMMONS" DIVERTER VALVE TO CONTROL 3 SHOWER ONLY. 1 2 KEY NOTES: 3 4 1/2" 5 LPG DN LPG UP PLUMBING FIRST LEVEL WATER PIPING PLAN
  • 10. Br 4 Br 3 Den Jr. Br. Open to Foyer Bath CL. Bath 4 Elev Balcony CL. Living Br 6 Br 5 Kitchenette Dining Bath CL. CL. REF D/W Powder TUB W/D 134'-0" 134'-0" Stairs 2 Stairs 1 Deck 144'-0" 144'-0" 7'-10" 56'-0" 8'-0" 24'-0" 32'-0" 18'-0" 6'-0" 22'-0" 42'-0" 24'-0" 16'-0" 24'-0" 6'-0" 22'-0" 42'-0" 24'-0" 16'-0" 12'-0" 12'-0" 6'-0" 18'-0" 26'-0" 12'-0" 18'-0" 13'-0" 5'-0" CL. Open to Courtyard Bath 3 Br 3 1"CW & 1"HW DN TO 1ST LEVEL CW DN TO 1ST LEVEL 1"HW DN TO 1ST LEVEL 1"CW & 1"HW DN TO 1ST LEVEL LPG DN TO 1ST LEVEL 1"CW & 1"HW DN TO 3RD LEVEL 1/2"CW & HW DN 1/2"CW DN 1/2"CW & HW DN 1/2"CW-DN 1/2"CW & HW DN 1/2"CW & HW DN 1/2"CW & HW DN 1/2"CW & HW DN 1" 1" 3/4" 1/2" 1/2" 1" 1/2"CW-DN 1/2"CW & HW DN 1/2"CW & HW DN 1/2"CW & HW DN 1/2"CW-DN 1/2"HW-DN 1" 1" 1" 1" 3/4" 1" CWB-1 LPG LPG M RESIDENCE GUNER P3.2 PLUMBING SECOND LEVEL WATER PIPING PLAN
  • 11. Green House Roof Top Garden Roof Below 134'-0" 134'-0" Stairs 2 144'-0" 144'-0" 22'-0" 16'-0" 8'-0" 20'-6" 30'-0" Utility 1"CW & HW DN 1/2"CW & HW DN 1/2"CW-DN 1/2"CW & HW DN 1"CW M RESIDENCE GUNER P3.3 PLUMBING THIRD LEVEL WATER PIPING PLAN
  • 12. M RESIDENCE GUNER P4.1 PLUMBING WASTE AND VENT DIAGRAM SHR-1 FIRST LEVEL WC-1 LV-1 4"FCO KS-1 SHR-1 WC-1 LV-1 CWB-1 4"FCO 4"FCO BTH-1 WC-1 CWB-1 4"FCO KS-1 4 SCALE: NONE BASEMENT WASTE AND VENT DIAGRAM 4"W 2"W 4"W 2"W 2"WCO 4"W 4"W 3 SCALE: NONE GUEST ROOM WASTE AND VENT DIAGRAM FIRST LEVEL SECOND LEVEL SHR-1 WC-1 LV-1 4"FCO 2 SCALE: NONE MASTER BEDROOM WASTE AND VENT DIAGRAM 1 SCALE: NONE WASTE AND VENT DIAGRAM WC-1 LV-2 BTH-2 LV-2 WC-1 LV-1 LV-1 LV-1 BTH-2 SHR-1 SEE BASEMENT "AA" DIAGRAM THIS SHEET FOR CONT SEE MASTER "AA" BEDROOM DIAGRAM FOR CONTINUATION FIRST LEVEL BTH-2 WC-1 LV-1 WC-1 LT-1 FD-1 CWB-1 KS-1 BTH-1 WC-1 LV-1 BUTLERS PANTRY KS-1 LV-1 KITCHEN DINING BEDROOM-3 BEDROOM-4 SECOND LEVEL SEE BASEMENT "BB" DIAGRAM THIS SHEET FOR CONT SEE MASTER "BB" BEDROOM DIAGRAM FOR CONTINUATION 2"WCO 2"WCO 2"WCO 2"WCO 2"WCO 2"WCO 2"VT 2"VT 2"VT 3"VT 3"VT 2"VT 3"VT 2"W 4"W 4"W 4"W 2"W 2"VT 2"W 2"W 2"W 2"VT 2"VT 2"VT 2"VT 2"VT 2"VT 2"VT 2"VT 2"VT 2"VT 2"VT 3"VTR 2"W 2"W 4"W 4"W 4"W 4"W 4"W 4"W 4"W 2"W 4"W 4"W 4"W 4"W 4"FCO 2"WCO 2"W 2"WCO 2-1/2"W 2"WCO 2"W 2"WCO 2"W 2"VT 2"VT 2"VT 2"VT 2"VTR 4"W 2"WCO 2"VT 2"VT 2"VT 2"VT 2"VT 2"VT 2"VT 2"W 4"W 4"W 2"WCO 2"W 2"VT 2"VT 2"VT 2"VT 2"VT 2"WCO 2"W 4"W 4"W 4"W 4"W 4"W 2"W 2"VT 2"VT 2"VT 2"VT 2"VT 2"VT 2"W 2"VT 2"VT 2"VT 3"VTR 4"W 4"W 4"W 4"W 4"W ROUTE TO SEPTIC TANK. FOR CONTINUATION SEE CIVIL DRAWINGS ROUTE TO SEPTIC TANK. FOR CONTINUATION SEE CIVIL DRAWINGS 2"VT 2"VT 2"VT 4"W 4"W 2"VT 2"VT 2"VT 2"VT 2"VT 2"VT 2"VT 2"VT 2"VT 2"WCO 2"WCO 2"WCO 2"WCO 2"S 4"W 2"W 2"VT 2"W 2"W 2"W 4"W 4"W 4"W 4"W 4"W 4"W 2"VTR THIRD LEVEL LV-1 2"WCO 2"VT 2"VT 2"VTR WC-1 SHR-1 LV-2 ROOF 2"VTR 2"WCO 2"W 4"W 2"W 4"W 4"W 2"VT 2"VT 2"VT ROUTE TO SEPTIC TANK. FOR CONTINUATION SEE CIVIL DRAWINGS ROUTE TO SEPTIC TANK. FOR CONTINUATION SEE CIVIL DRAWINGS 2"VT 2"VT 2"VT 2"VT 2"VT 2"WCO BASEMENT LEVEL FIRST LEVEL 2"W
  • 13. M RESIDENCE GUNER P4.2 PLUMBING COLD AND HOT WATER DIAGRAM BTH-1 HB-1 LV-1 CWB-1 KS-1 DISHWASHER HB-1 KS-1 KS-1 WC-1 LT-1 CWB-1 LV-1 BTH-1 WC-1 LV-1 BTH-1 WC-1 LV-1 BEDROOM 3 BEDROOM 4 CWB-1 WC-1 LV-1 BTH-1 KS-1 POOL BATH GAME ROOM BASEMENT LEVEL FIRST LEVEL SECOND LEVEL THIRD LEVEL LV-1 WC-1 WC-1 SHR-1 SHR-1 SHR-1 SHR-1 SHR-1 SHR-1 BTH-2 LV-2 LV-2 WC-1 LV-1 SHR-1 SHR-1 WC-1 BTH-2 WC-1 LV-1 LV-1 LV-1 MASTER BEDROOM 2"CW 2"CW 2"CW 3/4"CW 1"CW 1/2"CW 1/2"CW 1/2"HW 1/2"CW 1/2"CW 1/2"HW 1/2"CW 1/2"HW 1/2"CW 1/2"HW 1/2"CW 1/2"HW 1/2"CW 1/2"HW 1/2"CW 1/2"HW 1/2"CW 1/2"HW 1/2"CW 1/2"HW 1/2"CW 1/2"CW 1/2"HW 1/2"CW COLD WATER PIPING SIZING VELOCITY NOT TO EXCEED 8 FEET PER SECOND PIPE DIA GPM FT FIXT UNIT FV FIXT UNIT VELOCITY 1 2" 2.7 -- -- 3.2 3 4" 7.3 3 -- 4.9 1" 15.7 11 5 5.8 1 1 4" 26.5 41 9 6.9 1 1 2" 40.6 89 28 7.9 2" 71.3 232 114 8.0 2 1 2" 119.6 477 361 8.0 3" 177.7 801 756 8.0 COLD WATER PIPING SIZING VELOCITY NOT TO EXCEED 5 FEET PER SECOND PIPE DIA GPM FT FIXT UNIT FV FIXT UNIT VELOCITY 1 2" 2.7 -- -- 5.0 3 4" 7.3 3 -- 5.0 1" 13.4 8 -- 5.0 1 1 4" 19.6 20 6 5.0 1 1 2" 27.5 31 10 5.0 2" 46.4 117 41 5.0 2 1 2" 72.3 306 117 5.0 3" 115.6 456 340 5.0 1-1/4"CW 1"CW 3/4"CW 3/4"CW 1-1/4"CW 1"CW 1-1/2"CW 2"CW 2"CW 2"CW 1/2"CW 1/2"HW 1/2"CW 1/2"HW 1/2"CW 1/2"HW 1/2"CW 1/2"HW 1/2"CW 1/2"HW 1/2"CW 1/2"HW 1/2"CW 1/2"CW 1/2"CW 1-1/4"CW 1-1/4"CW 1"CW 1-1/4"CW 1-1/4"CW 1-1/4"CW 1-1/4"CW 2"CW 2"CW 1-1/2"CW 1-1/2"HW 2"CW 2"CW 1/2"CW 1/2"HW 1/2"CW 1/2"HW 1/2"CW 1/2"HW 1/2"CW 1/2"CW 1/2"HW 1"CW 1-1/4"CW 1-1/4"CW 2"CW 2"CW 1/2"HW 1/2"CW 1/2"HW 1/2"CW 1/2"HW 1/2"CW 1/2"HW 1/2"CW 1/2"CW 3/4"CW 1-1/4"CW 1"CW 1"CW 3/4"HW 1"CW 1"HW 1"CW 2"CW 2"CW 1/2"HW 1/2"CW 1/2"HW 1/2"CW 1/2"HW 1/2"CW 1/2"HW 1/2"CW 2"CW 2"CW 2"CW 1/2"CW 3/4" 1 1/4"HW 1-1/4"CW 1-1/4"HW 1-1/4"HW 1-1/4"HW 1-1/4"HW 1-1/4"HW 1/2"HW 1/2"CW 1/2"CW 1/2"HW 1/2"CW 1/2"HW 1/2"CW 1"HW 1-1/4"CW 1/2"HW 1/2"CW 1/2"HW 3/4"CW 1" 1"HW 1-1/2"CW 1"CW WELL TANK. SEE CIVIL FOR EXACT LOCATION (FOR REFERENCE ONLY) SHUT-OFF VALVE INSIDE CONCRETE UTILITY BOX SHUT-OFF VALVE INSIDE CONCRETE UTILITY BOX LV-2 SHR-1 WC-1 1/2"HW 1"CW 1/2"HW 1/2"CW 3/4"HW 1"CW 3/4"CW HB-1 3/4"CW 1-1/2"CW 1-1/4"CW 1"HW 1" WC-1 HB-1 HB-1 3/4"CW PROVIDE DIVERTER VALVE "SYSMON" TO CONTROL 3 SHOWER HEAD. ONE SHOWER SHALL BE ACTIVATED ONLY PROVIDE DIVERTER VALVE "SYSMON" TO CONTROL 3 SHOWER HEAD. ONE SHOWER SHALL BE ACTIVATED ONLY 1-1/2"CW MATCH LINE "AA" MATCH LINE "AA" HB-1 3/4"CW 1/2"HW 1/2"CW 3/4"CW 1/2"HW 1/2"CW 3/4"CW 1"HW 1-1/4"HW 1-1/4"HW 3/4"HW 3/4"CW 3/4"HW 1-1/2"CW WATER HAMER ARRESTER WATER HAMER ARRESTER WATER HAMER ARRESTER WATER HAMER ARRESTER WATER HAMER ARRESTER WATER HAMER ARRESTER HB-1 1/2"CW HB-1 1/2"CW 1"CW 1"CW 3/4"CW HB-1 HB-1 HB-1 3/4"CW 3/4"CW 3/4"CW WATER HAMMER ARRESTER 2"CW BACKFLOW PREVENTER
  • 14. M RESIDENCE GUNER P4.3 PLUMBING GAS PIPING DIAGRAM BASEMENT LEVEL FIRST LEVEL SECOND LEVEL SECOND LEVEL 1 SCALE: NONE GAS PIPING DIAGRAM COOKING RANGE 108 MBH 380 MBH 180 MBH LPG TANK (BY CIVIL FOR REFERENCE ONLY) FIRST STAGE REGULATOR FROM HIGH PRESSURE TO 5 PSI SECOND STAGE REGULATOR FROM MEDIUM PRESSURE TO 11" WC LPG LOAD QUANTITY DESCRIPTION MBH TOTAL 2 WATER HEATER 380 760 1 WATER HEATER 180 180 2 COOKING RANGE 108 216 3 FIREPLACE 80 240 6 FURNACE 60 360 GRAND TOTAL 1756 TOTAL DEVELOPMENT FROM THE LPG TANK TO THE FURTHEST OUTLET IS APPROXIMATE 200 FEET LPG PIPE SIZING CHART (7"-14"WC) CFH 1 2" 67 3 4" 140 1" 265 1 1 4" 543 1 1 2" 814 LOW PRESSURE GAS BASE ON CPC 2013 TABLE 1216.2 )(27) (NFPA 54 TABLE 6.3(D)) @ 200 FT LPG PIPE SIZING CHART (5 PSI) CFH 1 2" 1030 3 4" 2430 LOW PRESSURE GAS BASE ON CPC 2013 TABLE 1216.2 )(25) NFPA 54 TABLE 6.2(B) @ 200 FT 1/2"LPG (428 MBH) 1/2"LPG 1/2"LPG SECOND STAGE REGULATOR FROM MEDIUM PRESSURE TO 11" WC 1" (188 MBH) FURNACE 60 MBH 1" (248 MBH) 1" (180 MBH) 380 MBH COOKING RANGE 108 MBH FURNACE 60 MBH FURNACE 60 MBH 1-1/4" (380 MBH) 3/4" (60 MBH) 3/4" (60 MBH) 3/4" (60 MBH) 1" (140 MBH) 1" (200 MBH) 3/4" (180 MBH) 1-1/2" (688 MBH) 1" (380 MBH) FIREPLACE GAS LOG 80 MBH 3/4" (80 MBH) 1-1/4" (260 MBH) 1-1/2" (640 MBH) 3/4" LPG (1756 MBH) FAU # 1 60 MBH FAU # 2 60 MBH FAU # 3 60 MBH 1" (180 MBH) 3/4" LPG (1116 MBH) FIREPLACE GAS LOG 80 MBH 3/4" (80 MBH) SECOND STAGE REGULATOR FROM MEDIUM PRESSURE TO 11" WC 1" (308 MBH) 3/4" (80 MBH) FIREPLACE GAS LOG 80 MBH 1-1/4" (428 MBH) 1" (108 MBH) 1/2" 1/2" 1/2" 3/4"
  • 15. M RESIDENCE GUNER P5.1 PLUMBING DETAILS FINISHED PAVEMENT RELIEF VALVE BALL VALVE OUTDOOR TANK LESS WATER HEATER GAS LINE UNION OVERHEAD STRUCTURE 12''MIN 12''MIN 3'-0'' 24'' 29.7'' WINDOWS, DOORS OPENING 11.8" DEPTH EXPANSION TANK DIRT LEG COLD WATER SUPPLY WINDOWS, DOORS OPENING 1 HOT WATER SUPPLY FINISHED FLOOR SPILL INTO DAYLIGHT UNION (TYP) INSTALL PER MANUFACTURER'S REQUIREMENTS AND SPECIFICATIONS COLD WATER SUPPLY GAS SUPPLY LINE T & P (TYP) S.0.V. (TYP) LPG HOT WATER SUPPLY LINE CHECK VALVE Vertical Vent Termination Firestop Firestop/ Support Roof Flashing Roof Jack Storm Collar Rain Cap Hanger Strap Elbow 1' Min. - 3' Max. Horizontal Vent Termination Terminate at least 12" above grade or above snow line. Terminate at least 7' above a public walk- way, 6' from the combustion air intake of any appliance, and 3' from any other building opening, gas utility meter, ser- vice regulator etc. " Terminate at least 3' above any forced air inlet within 10', 4' below, 4' horizontally from or 1' above any door, window, or gravity air inlet into any building per National Fuel Gas Code ANSI Z223.1/NFPA 54. " Slope the horizontal vent 1/4" downwards for every 12" toward the termination. " Use a condensation drain if necessary. " In the Commonwealth of Massachusetts a carbon monoxide detector is required for all side wall horizontally vented gas fuel equipment. Please refer to Technical Bulletin TB 010606 for full installation in- structions. Appliance Adapter* Elbow Hanger Straps Wall Thimble Termination 1' Min. - 3' Max. Terminate at least 6' from the combustion air intake of any appliance, and 3' from any other building opening, gas utility meter, service regulator etc. Enclose exterior vent systems below the roof line to limit condensation and protect against mechanical failure. When the vent penetrates a floor or ceiling and is not running in a fire rated shaft, a firestop and support is required. When the vent termination is located not less than 8' from a vertical wall or similar obstruc- tion, terminate above the roof at least 2', but not more than 6', in accordance with the National Fuel Gas Code ANSI Z223.1/NFPA 54. Provide vertical support every 12' or as required by the vent pipe manufacturer's instructions. Slope the horizontal vent 1/4" for every 12" to- wards the drain tee. A short horizontal section is recommended to prevent debris from falling into the water heater. Condensation Drain (Install According to Local Codes) Adapter not required when using Noritz N-Vent. 1' minimum recommended, but not required. Avoid installing elbow directly on flue. Appliance Adapter* 1' minimum recommended, but not required. Avoid installing elbow directly on flue. Slope vent Downwards Install a condensation drain in the horizontal section of the venting. For installations in tight spaces where there is not enough room to in- stall two elbows and a horizontal drain tee, a vertical drain tee may be substituted. 2 INDOOR TANK LESS WATER HEATER 3 CLOTHES WASHER MACHINE BOX DETAIL 4 TRAP PRIMER DETAIL PRIMER PIPE FLOOR FOR EVERY 2O FEET OF NOTE: TRAP PRIMER VALVE SHOULD BE MOUNTED 12" ABOVE FINISHED 1/2"CW TRAP PRIMER SUPPLY "T" FITTING (COPPER) "PRECISION PLUMBING PRODUCTS, INC. "TRAP PRIMER VALVE ACCESS PANEL. VERIFY SIZE & LOCATION IN FIELD COLD WATER HEADER OR MAIN BRANCH IN WALL 16" MINIMUM 1/2" MINIMUM ANNEALED COPPER TUBING (EACH FLOOR DRAIN). FINISHED FLOOR COPPER TUBE TO FLOOR DRAIN TRAP PRIMER CONNECTION (TYP) 5 CONDENSATE CONNECTION TO UNIT DETAIL FITTINGS OR "U" BEND TRAP AT 1/8" PER FOOT SLOPE 3" 2'' MINIMUM 1-1/2'' MINIMUM VENT FOR PIPE RUNS GREATER THAN 15 FEET CLEANOUT PLUG (BY MECH) FAN COIL UNIT FOR REFERENCE ONLY. INSTALL PER MFR'S REQUIREMENTS BASE FLASHING BY GEN'L. CONT'R. CRIMP EDGE OVER PIPE IN A NEAT MANNER TO PREVENT REDUCTION OF EFFECTIVE VENT AREA. SHEET COPPER OR LEAD COUNTER FLASHING BY PLBG. CONT'R. (TO MATCH MATERIAL OF BASE FLASHING). SEE ARCH DWGS. REFER TO ARCH. DWGS. FOR ROOF CONSTRUCTION. REFER TO PLANS FOR SIZE AND LOCATION 6 VENT THRU ROOF DETAIL Before installing, check for the following: Install in accordance with relevant building and mechanical codes, as well as any local, state or national regulations, or in the absence of local and state codes, to the National Fuel Gas Code ANSI Z223.1/NFPA 54 latest edition. In Canada, see NSCNGPIC for detailed requirements. Item Distance from combustibles " Maintain the following clearances from both combustible and non-combustible materials. Check Illustration " If possible, leave 8" (200mm) or more on either side of the unit to facilitate inspection. " If possible, leave 24" (600mm) or more in front of the unit to facilitate maintenance and service if necessary. " If possible, leave 3" (75mm) or more above and below the vent pipe to facilitate inspection and repair if necessary Securing of space for repair/inspection 24" (600mm) or more Distance from the side 12" or more 2" (50mm) or more 4" or more 3" (75mm) or more 3" (75mm) or more 8" (200mm) or more 8" (200mm) or more <When the indoor air supply> " If the unit will be installed in the vicinity of a permanent kitchen range or stove that has the possibility of generating steam that contains fats or oils, use a dividing plate or other measure to ensure that the unit is not exposed to air containing such impurities. * The dividing plate should be of noncom- bust-ible material of a width greater than the water heater. Exhaust hood Range Dividing plate Water heater Cooking Equipment NIPPLE GAS SUPPLY EQUIPMENT 3"MIN. CAP PROVIDE FLEX CONNECTION PER MANUFACTURERS REQUIREMENTS AND RECOMMENDATION EQUIPMENT GAS SHUT-OFF VALVE 7 GAS CONNECTION TO EQUIPMENT 9 DRYWELL DETAIL 1/2" HOT WATER 1/2" COLD WATER HOSE BIBBS WASHING MACHINE BOX 2" TRAP AND WASTE PIPE 1 1/2" WASTE WATER HAMMER ARRESTOR -WADE MODEL W-5 FINISHED FLOOR SPILL INTO DAYLIGHT UNION (TYP) INSTALL PER MANUFACTURER'S REQUIREMENTS AND SPECIFICATIONS COLD WATER SUPPLY GAS SUPPLY LINE T & P (TYP) S.0.V. (TYP) LPG HOT WATER SUPPLY LINE CHECK VALVE EXPANSION TANK EXPANSION TANK 3'-0" 6" SAND FILL BACKFILL COVER CORRUGATED GALVANIZED IRON ABS OR PVC PIPE 4"DIA PERFORATED GRAVEL FILL FINISHED GRADE 2'-6" DRAIN PIPE