Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
E3.pdf
1. REVISIONS:
DESIGN BY:
CADD BY:
CHECKED BY:
APPROVED BY:
DATE:
OWNER:
LOCATION:
NOTE:
Republic Act 545
This drawing as an instrument of
service is a property of registered
Architect and as such must not be
reproduced or copied in part or in
whole without his permission. All
drawing are to be returned when no
longer in use.
LIC. NO.:
TIN. NO.:
DATE:
PLACE ISSUED:
PTR. NO.:
ELECTRICAL ENGINEER
LIC. NO.:
TIN. NO.:
DATE:
PLACE ISSUED:
PTR. NO.:
OFFICE IMPROVEMENT ALVEO FINANCIAL TOWER
31ST FLOOR - UNIT 3102
6794 AYALA AVENUE, COR. SALCEDO, MAKATI CENTRAL BUSINESS CENTER, MAKATI CITY
SHEET CONTENTS: SHEET NO.:
AS SHOWN
E
3
PROJECT:
MR. ICHIRO CHUJO
GENERAL NOTES:
1. ALL WORKS INDICATED HEREIN SHALL BE DONE IN ACCORDANCE WITH THE
LATEST PROVISIONS ON THE LATES EDITION OF THE PHILIPPINE ELECTRICAL CODE,
THE ORDINANCES OF THE LOCAL ENFORCING AUTHORITY AND REQUIREMENTS OF
THE LOCAL POWER COMPANY.
2. ALL MATERIALS TO BE USED SHALL BE NEW AND ISTALLED IN APPLICATION FOR
WHICH THEY ARE INTENDED.
3. ALL METALLIC CONDUITS SHALL BE PROPERLY GROUNDED AND ROUNDED BY
MEANS OF COPPER STRAPS.
4. MINIMUM SIZE OF WIRE SHALL BE 2.0MM 2 THW 15MMØ CONDUITS UNLESS NOTED
ON PLANS.
5. LIGHTING BRANCH CIRCUITS WITHOUT DESIGNATIONS SHALL BE 2 -WIRE,
3.5MM 2 THW IN 15MM Ø CONDUITS.
6. MOUNTING HEIGHTS SHALL BE AS FOLLOWS:
6.1. ELECTRICAL PANEL 1700MM FROM FFL
6.2. SWITCHES 1370MM FROM FFL
6.3. CONVENIENCE OUTLET 300MM FROM FFL
7. ALL CONDUIT PIPES SHALL BE POLYVINYL CHLORIDE EXCEPT WHEN OTHERWISE
NOTED. CONDUIT PIPES EMBEDDED IN DIRECT CONTACT WITH THE SOIL SHALL BE
COATED OF ASPHALT PAINT, WRAPPED IN ASPHALT TAPE, AND FINALLY ANOTHER
COAT OF ASPHALT PAINT UNLESS OTHERWISE NOTED.
8. EXPOSED CONDUIT RUNS SHALL BE INSTALLED PARALLEL TO OR PERPENDICULAR
WITH THE BUILDING LINE AND SUPPORTED BY A CONDUIT CLAMP FOR EVERY 1.50
METERS.
9. WHENEVER NECESSARY, PULL BOX SHALL BE PROVIDED EVEN IT IS NOT
INDICATED IN THE PLANS.
10. ALL ELECTRICAL WORKS SHALL BE UNDER THE DIRECT AND IMMEDIATE
SUPERVISION OF A DULY LICENSED ELECTRICAL ENGINEER.
SCHEDULE OF LOADS
CKT
NO.:
LOAD DESCRIPTION
NO. OF
LOADS
APPROX.
VA PER
OUTLET
TOTAL
VA VOLTS
TOTAL
LOAD
AMPS
CB RATING
AT POLE kAIC
WIRE SIZE AND DIAMETER
OF CONDUIT PIPE
1 LIGHTING OUTLET (LO) 12 50 600 230 4.08 20AT 2 10
2 LIGHTING OUTLET (LO) 10 50 500 230 3.40 20AT 2 10
3
CONVENIENCE OUTLET
(CO)
7 180 1260 230 8.56 30AT 2 10
4
CONVENIENCE OUTLET
(CO) 6 180 1080 230 7.34 30AT 2 10
5 REFRIGERATOR 1 1200 1200 230 8.15 30AT 2 10
6
CCTV - AUXILIARY
POWER PANEL (APP)
1 200 200 230 1.36 30AT 2 10
7
AIR CONDITION UNIT
1
(ACU1)
1 1500 1500 230 10.19 30AT 2 10
8
AIR CONDITION UNIT 2
(ACU2)
1 1500 1500 230 10.19 30AT 2 10
9 EMERGENCY
LIGHT
10
11 SPARE
12 SPARE
TOTAL
11,200.00 70.39
COMPUTATION NOTES
IT = (VAT / VOLTS) * 1.25
IT = (11,200.00 /230) * 1.25
IT = 48.70 * 1.25
IT = 60.87 AT
MAIN FEEDER LINE:
3 - 22MM 2 THHN WIRE AND 1 - 5.5MM 2 TWG WIRE IN 20MM Ø RSC PIPE
MAIN DISCONECTING CIRCUIT:
100AT, 60AF, 3P, 230V
SCALE
UNIT 3102 SCHEDULE OF LOADS
1:100MTRS
E-2
1
20AT
20AT
1 2
3 4
5 6
7 8
9 10
11 12
LIGHTING OUTLET
CONVENIENCE OUTLET
CCTV - AUXILIARY
POWER PANEL
AIR CONDITIONING UNIT 2
SPARE
LIGHTING OUTLET
CONVENIENCE OUTLET
REFRIGERATOR OUTLET
AIR CONDITIONING UNIT 1
SPARE
30AT 30AT
30AT
30AT
20AT
30AT
30AT
20AT
30AT
30AT
100AT, ? AF, 3P
MAIN CIRCUIT
M
FROM MAIN ELECTRICAL
SOURCE, INPUT 230V 3P
SUB METER 2 - 22MM2 THHN AND 1 - 5.5MM2 TWG WIRE
IN 20MM Ø RSC PIPE
LIGHTING AND POWER PANEL RISER DIAGRAM
SCALE
UNIT 3102 RISER DIAGRAM
1:100MTRS
E-2
2
UNINTERRUPTIBLE POWER SUPPLY
(UPS) SYSTEM
(VERIFY MANUFACTURER'S
SPECIFICATIONS AND DETAILED
CONNECTIONS)
230VAC
15AMPS FUSE
12VDC
10AMPS FUSE
POWER DISTRIBUTION TO
SECURITY CAMERAS
USE TERMINAL SPLITTER IF
NECESSARY
6
FROM PPL CKT 6
CCTV - AUXILIARY POWER PANEL (APP)
230VAC INPUT
12VDC
OUTPUT
VERIFY CCTV - AUXILIARY POWER
PANEL MANUFACTURER'S
DETAILED SPECIFICATION AND
CONNECTION
RR DE GUZMAN CONST. & DEV'T CORP.
BLK 8 LOT 2 PRISTINA COMMERCIAL,
BUHAY NA TUBIG, IMUS, CAVITE
TEL. NO.: (046) 683-0916 / EMAIL:
rrgconstruct@yahoo.com
EMERGENCY
LIGHT
3
3
20AT
20AT
EMERGENCY LIGHT EMERGENCY LIGHT
7 180 1260 230 8.56 30AT 2 10
7 180 1260 230 8.56 30AT 2 10
2 10
2 10
540
540
230
230
MR. HILARIO M. ESCOBIA
ARCHITECT
3.67
3.67
180
180
2- 3.5 MM² THHN & 1 -2.0MM
TWG IN 15MM PVC CONDUIT PIPE
2- 3.5 MM² THHN & 1 -2.0MM
TWG IN 15MM PVC CONDUIT PIPE
2- 3.5 MM² THHN & 1 -2.0MM
TWG IN 15MM PVC CONDUIT PIPE
2- 3.5 MM² THHN & 1 -2.0MM
TWG IN 15MM PVC CONDUIT PIPE
2- 3.5 MM² THHN & 1 -2.0MM
TWG IN 15MM PVC CONDUIT PIPE
2- 3.5 MM² THHN & 1 -2.0MM
TWG IN 15MM PVC CONDUIT PIPE
2- 3.5 MM² THHN & 1 -2.0MM
TWG IN 15MM PVC CONDUIT PIPE
2- 3.5 MM² THHN & 1 -2.0MM
TWG IN 15MM PVC CONDUIT PIPE
2- 3.5 MM² THHN & 1 -2.0MM
TWG IN 15MM PVC CONDUIT PIPE
2- 3.5 MM² THHN & 1 -2.0MM
TWG IN 15MM PVC CONDUIT PIPE
2- 5.5 MM² THHN & 1 -2.0MM
TWG IN 20MM PVC CONDUIT PIPE
2- 5.5 MM² THHN & 1 -2.0MM
TWG IN 20MM PVC CONDUIT PIPE