GETCO/E/06TS – CB/R3 May12
Page 1 of 26
GUJARAT ENERGY TRANSMISSION
CORPORATION LTD.
SARADAR PATEL VIDYUT BHAVAN,
RACE COURSE, BARODA – 390 007.
TECHNICAL SPECIFICATION
FOR
66 kV SF6 CIRCUIT BREAKER
(SPRING OPERATED)
GETCO/E/06TS – CB/R3 May12
GETCO/E/06TS – CB/R3 May12
Page 2 of 26
SPECIAL INSTRUCTIONS TO BIDDER
Please read following instructions carefully before submitting your bid.
1. All the drawings, i.e. elevation, side view, plan, cross sectional view etc., in AutoCAD
format and manuals in PDF format, for offered item shall be submitted. Also the hard
copies as per specification shall be submitted.
2. The bidder shall submit Quality Assurance Plan with the technical bid.
3. The bidder shall have to submit all the required type test reports for the offered item. In
absence of this, the evaluation shall be carried out accordingly as non-submission of type
test reports.
4. The bidder must fill up all the points of GTP for offered item/s. Instead of indicating “refer
drawing, or as per IS/IEC”, the exact value/s must be filled in.
5. All the points other than GTP, which are asked to confirm in technical specifications must
be submitted separately with the bid.
6. The bidder is required to impart training in view of manufacture, assembly, erection,
operation and maintenance for offered item, at his works, to the person/s identified by
GETCO, in the event of an order, free of cost. The cost of logistics will be bear by
GETCO.
7. Please note that the evaluation will be carried out on the strength of content of bid only.
No further correspondence will be made.
8. The bidder shall bring out all the technical deviation/s only at the specified annexure.
GETCO/E/06TS – CB/R3 May12
Page 3 of 26
QUALIFYING REQUIREMENT DATA
(For Supply)
Bidder to satisfy all the following requirements.
1) The bidder shall be Original Equipment Manufacturer
(OEM). The offered equipment have to be designed,
manufactured and tested as per relevant IS/IEC with
latest amendments.
2) The minimum requirement of manufacturing capacity of
offered type, size and rating of equipment shall be FIVE
times tender/ bid quantity. The bidder should indicate
manufacturing capacity by submitting latest updated
certificate of a Chartered Engineer (CE).
3) Equipment proposed shall be of similar or higher rating
and in service for a minimum period of THREE (3) years
and satisfactory performance certificate in respect of this
is to be available and submitted.
4) The bidder should clearly indicate the quantity and Single
Value Contract executed during last FIVE (5) years, for
the offered equipment. Bidder should have executed one
single contract during last five years for the quantity
equivalent to tender / bid.
The details are to be submitted in following format,
Sr.
No
ITEMS
SUPPL
IED
TO
ORDER
REFEREN
CE No. &
DATE
ITEMS QUANTITY ORDER
FULLY
EXECUTED.
YES/NO
STATUS, IF
ORDER
UNDER
EXECUTION
REMARK
e) Equipment offered shall have Type Test Certificates from
accredited laboratory (accredited based on ISO/IEC
Guide 25 / 17025 or EN 45001 by the National accredition
body of the country where laboratory is located), as per
IEC / IS / technical specification. The type test reports
shall not be older than FIVE years and shall be valid up to
expiry of validity of offer.
GETCO/E/06TS – CB/R3 May12
Page 4 of 26
TECHNICAL SPECIFICATION FOR
66 kV SF6 GAS CIRCUIT BREAKER
SECTION – I
GENERAL TECHNICAL REQUIREMENTS
1.1 SCOPE :
1.1.1 This section covers the design, manufacture, testing, inspection,
supply and delivery of 66 kV SF6 gas Circuit Breakers SPRING
operated, along with associated accessories and complete in all
respects specified in the schedule of requirements.
1.2 APPLICABLE STANDARDS:
1.2.1 The equipment to be supplied under this specification shall conform to
the latest issue of standards, rules and codes some of which are
mentioned below.
1. IEC-62271/ IS 13118 Specification for alternating current Circuit
breaker
2. IEC-60376 Specification and acceptance of new Supply of
sulfur Hexafluoride.
3. IS: 2147 Degree of protection provided for Enclosures
for low voltage switchgear and control gear.
4. IS: 375 Marking and arrangement for switchgear bus-
bar, main connections and auxiliary wiring.
5. IS: 325 Specification for 3ph induction motor.
6. IS: 2516 Specification for circuit breaker.
7. IS: 2099 High voltage porcelain bushing.
9. IS: 2629 Recommended practice for hot dip galvanizing
of iron and steel.
The components & accessories to be used in the manufacture of circuit
breaker shall conform to relevant Indian Standards/the standard
specified under respective clause in this specification.
However, in the event the offered breakers confirming to any other
standard, salient points of differences between the standard
adopted and the specified standards shall be clearly indicated in the
offer.
GETCO/E/06TS – CB/R3 May12
Page 5 of 26
1.3 DRAWINGS/DOCUMENTS:
1.3.1 The bidder shall furnish the drawings in triplicate incorporating the
following particulars.
a) Drawing showing the general outlines dimensions of circuit
breakers, with clear identification of parts / items.
b) Drawing showing control cabinets and circuit diagrams for operating
mechanism of circuit breakers.
c) Drawing showing the complete operation cycle of the circuit breaker
with description.
d) Compression type terminal connectors for the breakers.
e) All the documents required shall be submitted over and above as
indicated in Section - V of the specification.
1.3.1.1 The Bidder shall submit the following drawings within 15 days from
the date of receipt of clear order: -
a) Outline dimensional drawings showing all parts / items, transport
weight etc. of circuit breaker & its support structure.
b) Detailed drawings of operating mechanism of circuit breakers.
c) Wiring and control diagram.
d) Drawings of foundation details, mounting structures, spacing of
bolts etc.
e) Compression type terminal connectors, with STC rating, bill of
materials, etc., complete with all dimensions.
f) MQP, FQP, erection, operation & maintenance manuals.
1.3.1.2 The bidder may also, submit any other drawings found necessary in
addition to the drawings stated above.
1.4.1 GENERAL DESIGN FEATURES OF CIRCUIT BREAKERS:
1.4.1.1 The circuit breakers shall be capable of rapid and smooth
interruption of currents under all conditions completely suppressing
all undesirable phenomena even under the most severe and
persistent short circuit conditions or when interrupting small
currents or leading or lagging reactive currents. The circuit breakers
shall be ‘Restrike-Free’ under all operating conditions. The details
of any device incorporated to limit or control the rate of rise of
restriking voltage across, the circuit breaker contacts shall be
stated. The over voltages caused by circuit breaker while switching
inductive or capacitive loads shall not exceed 2.5 times the highest
phase to neutral voltage. The actual make and break times for the
circuit breakers throughout the ranges of their operating duties shall
be stated in the offer and guaranteed.
1.4.1.2 The arc quenching chambers shall have devices to ensure almost
uniform distribution of voltage across the interrupters.
GETCO/E/06TS – CB/R3 May12
Page 6 of 26
1.4.1.3 Breaking Capacity:
The interrupting capacity of the breaker for kilometric faults (short
line faults) shall be equal to its interrupting capacity as per IS:
13118 / IEC 62271 and shall be stated in the tender. The details of
tests conducted for confirming the capability of the breakers under
kilometric fault conditions shall be furnished in the offer.
1.4.1.4 The circuit breakers shall be designed for interrupting line charging
currents without undue rise in the voltage on supply side and
without any restrike and without showing signs of undue strain. The
guaranteed over voltage which shall not be exceeded while
interrupting the line charging currents as specified under the Clause
2.4.10 of Section-II of this specification shall be stated in the offer.
1.4.1.5 The circuit breakers shall be capable of interrupting small inductive
currents (occurring while switching off unloaded transformer)
without giving rise to undue over voltage and without restrikes. The
maximum over voltage value which will not be exceeded under
such conditions shall be stated in the offer, and in conformity to this,
test reports along with oscillograph shall be furnished in the offer.
1.4.1.6 Restriking Voltage:
The circuit breakers shall be capable of interrupting the rated power
when the restriking voltage has a frequency of not less than 400 Hz
and with a restriking voltage having frequency of 2000 Hz. The
circuit breakers shall be capable of interrupting at least 50% of
nominal breaking capacity.
1.4.1.7 The measures adopted for ensuring proper operation at high rate of
rise of restriking voltage and for limiting the actual voltage values
across the breaks shall be described in the tender. The type
characteristics and rating of the resistor used, if any, to shunt the
breaker contacts and of the auxiliary switching devices used for
interrupting the resistor current shall be clearly stated.
1.4.1.8 Recovery voltage and power Factor:
The circuit breaker shall be capable of interrupting the rated power
with recovery voltage equal to the rated maximum line to line
service voltage at rated frequency and at a power factor not
exceeding 0.15.
1.4.1.9 The circuit breakers shall also be capable of satisfactory operation
even under conditions of phase opposition that may arise due to
faulty synchronizing. The maximum power which the breaker can
satisfactorily interrupt under phase opposition shall be stated in the
offer.
GETCO/E/06TS – CB/R3 May12
Page 7 of 26
1.4.1.10 The operating duty of the circuit breaker shall be as specified under
Clause - 2.4.12 of specific technical requirement for breakers.
1.4.2 Temperature Rise:
1.4.2.1 The temperature rise and the maximum temperature on any part of
the breaker when in service under continuous full load conditions
and exposed continuously to the direct sun-rays shall not exceed
the permissible limits as per relevant ISS. When the standard
specifies the limits of temperature rise, this shall not be exceeded
when corrected for the difference between ambient temperature at
site and the ambient temperature specified in the relevant
specification. The correction proposed shall be stated in offer and
shall be subject to the approval of the purchaser.
1.4.3 General Features of Circuit Breakers:
1.4.3.1 The circuit breakers shall be suitable for outdoor operation under
the climatic conditions specified in section-II of this specification.
1.4.3.1(a) The circuit breakers operating mechanism shall have two nos. of
tripping coils and one no. of closing coil for both 66 kV SF6 Gas CB
for better reliability. There shall be separate contactor for each coil.
1.4.3.2 Exposed live parts shall be placed high enough above ground to
meet the requirements of local safety codes.
1.4.3.3 All similar parts, particularly removable one and shall be
interchangeable with one another.
1.4.4 Insulation of the Circuit Breaker:
The insulation to ground, the insulation between open contacts and
the insulation between phases of the completely assembled circuit
breaker shall capable of withstanding satisfactorily die-electric test
voltages corresponding to BIL specified in Clause – 2.4.2 of this
specification.
1.4.5(a) The minimum clearances in open air shall be as under in case of
SF-6 Breakers:
Minimum clearance between phase : As per relevant IS.
Minimum clearance between live parts : As per relevant IS.
and grounded objects.
1.4.5(b) Adequate clearance in air shall be provided between phase and
from phase to ground. The clearance shall be such that the breaker
shall withstand the BIL specified in the specification. The minimum
clearance from live parts to ground level shall not be less than 4000
mm – including plinth height as 300 mm.
GETCO/E/06TS – CB/R3 May12
Page 8 of 26
1.4.6 Contacts of Circuit Breaker:
1.4.6.1 The main contacts shall have adequate area and contact pressure
for carrying the rated currents and the short time rated breaking
currents of the breaker without excessive temperature rise.
Contacts shall be easily replaceable and shall have a minimum of
movable parts and adjustments. The main contacts shall be first to
open and last to close so that burning of the contact may be
negligible.
1.4.7 Operating Mechanism of Circuit Breakers:
1.4.7.1 Circuit breakers shall be power operated by a motor compressed
spring charging mechanism; the mechanism will be trip-free
electrically and mechanically. The mechanism shall be strong, quick
in action and shall be removable without disturbing other parts of
the circuit breakers. All the working parts in the mechanism shall be
of corrosion resistant materials and all bearings which require
greasing, shall be equipped with pressure grease fittings. The
mechanism and breaker shall be such that the failure of any spring
will not prevent tripping and will not cause tripping or closing.
1.4.7.2 The circuit breakers shall be designed for remote control from the
control room and there shall be provision for manual operation of
circuit breakers during maintenance and for local tripping and
closing by normal means.
1.4.7.3 The circuit breaker shall have a mechanical ‘ON-OFF’ indicator in
addition to facilities for remote electrical indicator.
1.4.7.4 The operating mechanism along with its accessories shall be
suitable for electrical operation and shall be mounted in a weather
proof cabinet with hinged doors located near the breakers. The
cabinet shall be suitable for IP 55 degree of protection. The
operation shall be possible from ground or necessary HDG
stand/platform of suitable height maintaining all safety clearance with
live parts shall be supplied as a part of breaker. The local control
switch and the breaker position indicator shall be provided in this
cabinet, which shall be free standing and supported by suitable
arrangement. The control circuit shall be designed to operate on
D.C. as specified in section-II of this specification. The closing and
opening coils shall be designed to operate satisfactorily at any
control voltage from 85% to 110% & 70% to 110% of the normal
voltage, respectively. A heater of adequate capacity with thermostat
shall be provided in the cabinet to avoid moisture condensation.
1.4.7.4(a) The terminal block shall of 1.1 KV voltage grade & shall be with
stud type connections instead of with screw types connections.
GETCO/E/06TS – CB/R3 May12
Page 9 of 26
1.4.8 Auxiliary switches:
1.4.8.1 A minimum number of 6 NC + 6 NO Auxiliary switches contacts
shall be provided on each circuit breaker for use in remote
indication control scheme of the circular breakers and for safety
interlocking. Special contacts for use with trip coils and auto
reclosing operation shall also be provided. Provision shall be made
for adding more auxiliary switches, if required. Auxiliary switches
shall be placed in weatherproof galvanized casing and current
rating of switches shall be mentioned in the offer.
1.5 BUSHING & INSULATORS:
1.5.1 The porcelain insulator used in manufacturing the bushings shall be
homogeneous, free from laminations, cavities and other flaws or
imperfection that might affect the mechanical or dielectric qualities.
All bushings of identical ratings shall be interchangeable. The
insulators shall conform to the latest edition of IS: 3447 or other
equivalent standard. The puncture strengths of the bushings shall
be greater than their flashover values. The bushings shall be
entirely free from external and internal corona. The protected and
total creepage distance of the bushings shall be suitable for heavily
polluted atmosphere. The minimum creepage distance of the
insulator shall be 1810 mm suitable for heaving polluted
atmosphere. The compressive and cantilever strength shall
conform to the relevant IS.
1.6 TERMINAL CONNECTORS AND EARTHING TERMINALS :
1.6.1 Compression joint type terminal connectors suitable for single or
twin ACSR panther/zebra/Moose as indicated in Schedule – A
of respective tender, shall be supplied and they shall be suitable
for both vertical and horizontal connections of the Transmission line
conductor or station bus bar. Suitable terminal earth connectors
(two Nos.) for earthing connections shall also be supplied. The
drawings for these connectors shall be submitted. SS bolt for
connector shall be provided with two Nos. of SS nuts (including lock
nut & one SS washer.
1.7 TROPICALISATION:
1.7.1 All control wiring, electric motors and accessories shall be protected
against fungus growth and other harmful effects due to tropical
environments.
1.8 GALVANIZING:
GETCO/E/06TS – CB/R3 May12
Page 10 of 26
1.8.1 All ferrous parts of breakers and bolts, nuts etc. shall be hot-dip
galvanized as per latest edition of IS: 2629. Support structure’s
galvanizing shall be done as per IS 4843 (latest edition). Electro
galvanized bolts nuts, & washers are also acceptable.
1.9 PAINTING:
1.9.1 Interior and exteriors of tanks, mechanisms, enclosures, cabinets
and other metal parts shall be thoroughly cleaned to remove all rust
scales, corrosion and other adhering foreign matter, steel surfaces
in contacts with insulation oil, as far as possible shall be painting
with not less than two coats of heat resistant, oil insoluble,
insulating varnish light-grey paint shade 631 as per IS:5 shall be
selected to withstand tropical heat and extremes of weather.
1.10 TEST AND TEST REPORTS:
1.10.1 Reports of following type tests carried out in NABL / Govt. approved
laboratory within five years prior to expiry of validity of offer, as per
IS: 13118 / IEC 62271-100 for A C circuit breakers shall be
submitted along with the offer :
(i) Lightning impulse withstand voltage test
(ii) Power frequency voltage withstand voltage test. (Dry as well as Wet)
(iii) Temperature rise test.
(iv) Measurement of resistance of main circuit
(v) Short time current withstand and peak current withstand Test
(vi) Mechanical endurance test
(vii) Duty cycle & Single phase short circuit test.
(viii) Out of phase making and breaking current test.
(ix) Capacitor current switching test for isolated neutral capacitor
banks.
(x) Line charging current switching test
(xi) Cable charging current switching test
(xii) Short line fault duty test
(xiii) Degree of protection test on cubicles
IMPORTANT NOTE: In case of non-submission of some of the type test reports, the
bidder shall confirm the submission of same before commencement of supply,
without affecting delivery schedule, from NABL accredited laboratory, free of cost.
In absence of this confirmation, the offer will be evaluated as non submission of
type test report.
1.10.2 Routine tests as per the latest edition of IS: 13118/IEC 62271 for
circuit breakers shall be carried out on each circuit breaker. All the
acceptance tests in presence of GETCO representative shall be carried
out on circuit breakers selected from offered lot.
GETCO/E/06TS – CB/R3 May12
Page 11 of 26
1.10.3 In addition to above, speed curves for each breaker shall be obtained
with the help of a suitable operation analyzer to determine the breaker
contact movement during opening, closing, auto-re-closing and trip free
operations under normal as well as limiting operating conditions (of
control voltage) The tests shall show the speed of contacts directly at
various stages of operation, travel of contacts, opening time, closing
time, shortest time between separation and meeting of contacts at
make-break operation and dynamic contact resistance measurement
(DCRM) etc.
1.10.4 The test reports for type tests and routine tests in respect of
associated items such as spring charging motors, instruments,
pressure switches, relays, terminal connectors, etc. as per the latest
edition of the relevant IS shall be supplied by the bidder. All the
routine test reports for all the breakers and for all the
insulators utilized shall be submitted with inspection report.
1.10.5 All tests reports for acceptance / routine tests shall be submitted in
spiral bound volume and got approved from the purchaser before
dispatching the breaker.
1.11 SPARE PARTS:
1.11.1 Bidder shall submit list of spares recommended by him for
satisfactory operation of the circuit breakers for first five years and
rate for each spare shall also be quoted. The purchaser will decide
the actual quantity of spare parts to be ordered on the basis of the
prices of the spare parts, quoted by the bidder.
1.12 TECHNICAL & GUARANTEED PARTICULARS :
The bidder shall furnish all guaranteed technical particulars as
called for in section - IV of this specification. Particulars which are
subject to guarantee shall be clearly stated offers not containing this
information will not be considered.
Deviation against any clause of this technical specification shall be
clearly described separately.
1.13 INSTRUCTION MANUALS:
1.13.1 Three copies of operation, maintenance and erection manuals in
English language shall be provided in each circuit breaker supplied.
The manuals shall be bound volumes and shall contain all the
drawings and instructions required for erection, operation and
maintenance and in addition the following particulars:
GETCO/E/06TS – CB/R3 May12
Page 12 of 26
a) Marked erection prints identifying the component parts of the circuit
breakers and current transformers as dispatched with the assembly
drawings.
b) Details dimensions, assembly and description of all the components
and catalogues for operation of the circuit breaker and accessories.
c) List of recommended spare parts of circuit breaker.
GETCO/E/06TS – CB/R3 May12
Page 13 of 26
TECHNICAL SPECIFICATION FOR
66 kV SF6 GAS CIRCUIT BREAKER
SECTION – II
TECHNICAL REQUIREMENTS
2.1 SCOPE:
This section covers the specific technical requirements, climatic and
Isoceraunic conditions and system particulars for which the circuit
breakers shall be offered as per the General Technical
Requirements given in Section-I of this specification and the
schedule of requirements specified herein.
2.2 CLIMATIC & ISOKERAUNIC CONDITIONS:
2.2.1 The climatic conditions under which the breaker shall operate
satisfactorily are as follows:
a) Maximum ambient temperature of air
in shade (0
C).
: 500
C
b) Minimum ambient temperature of air
in shade (0
C).
: 40
C
c) Maximum daily average ambient
temperature (0
C).
: 400
C
d) Maximum yearly average ambient
temperature (0
C).
: 300
C
e) Maximum relative humidity (%). : 95 %
f) Average number of thunderstorm
days / annum.
: 15
g) Average annual rainfall (Cm.) : 150 cm.
h) Maximum wind pressure (Kg/m2) : 150 kg/M2
.
i) Height above mean see level (m). : Not exceeding
1000 meters.
GETCO/E/06TS – CB/R3 May12
Page 14 of 26
2.2.2 All breakers offered shall be suitable for continuous satisfactory
operation at the full rated capacity under the above climatic
conditions.
2.2.3 Since the sub-station may be near seashore or Industrial area, the
breaker offered shall be suitable for heavily polluted atmosphere.
2.3 SYSTEM DETAILS:
i) Nominal system voltage : 66 kV
ii) Maximum rated voltage : 72.5 kV
iii) Frequency : 50 Cycle / Second.
iv) Number of phases : 3
v) Neutral Earthing : Solidly earthed.
vi) Auxiliary power supply : 1) 240 Volts 1-φ & 415
Volts 3-φ, 50 Hz A.C., with
the variation of frequency
± 5% and voltage + 10% &
-15%.
2) 110 Volts or 220 Volts
2-wire D.C. supply subject
to variations of ± 10%.
2.4 The circuit breakers shall be complete with following technical
requirements. :
11) Number of Poles : 3
2) Basic Insulation level
1) 1.2/50 Microsecond
impulse withstand voltage.
2) On Minute Power
Frequency withstand
voltage.
:
:
350 kVp
140 kV rms
3) Rated normal current : 1600 Amps.
3a) Rated symmetrical breaking
capacity at highest system
voltage.
: 3000 MVA
GETCO/E/06TS – CB/R3 May12
Page 15 of 26
4) Rated short circuit breaking
capacity.
: 31.5 kA rms
5) Rated duration of short circuit : 3 second.
6) Total break time for any
current upto the rated
breaking current.
: 3 cycles
7) Closing time. : Not more than 10 cycles.
8) Rated characteristics for short
line faults
: As per IS: 13118 / IEC
62271.
9) Rated transient recovery
voltage for terminal fault.
: As per IS: 13118 / IEC
62271.
10) Rated line charging current
breaking capacity.
: 10 Amps.
11) Rated short circuit making
current.
: 78.75 kAp
12) Rated operating duty : O–0.3 S–CO–3 M–CO
13) Rated SF6 Gas pressure (AT
200
C).
: 5 kg / Cm2
14) Total creepage distance for
heavily polluted atmosphere.
: 1810 mm min.
15) Live part to plinth level
clearance in mm
: 4000 mm
2.5 EARTH QUAKE & WIND DESIGN LOADS:
Each circuit breaker including its supporting structure shall be
designed to withstand required earthquake acceleration of 0.08 x 2
g and with wind loads of 150 Kg/m2 on the projected area (non-
simultaneous) without damage to component parts and without
impairment of operation.
GETCO/E/06TS – CB/R3 May12
Page 16 of 26
TECHNICAL SPECIFICATION FOR
66 kV SF6 GAS CIRCUIT BREAKER
SECTION – III
GENERAL DESIGN OF 66 kV SF6 GAS CIRCUIT BREAKER
3.2 GENERAL DESIGN FEATURE OF SF6 BREAKER:
3.2.1 SF6 Gas Circuit breaker shall consist of three identical single
phase units with common Spring operating mechanism suitable
for specified duty. Separate SF6 Gas Cylinder along with suitable
gas system, incorporating required gas stop valves, copper piping
of suitable size shall be provided. Required pressure switches as
stated in Cl. 1.4.8.2 shall be provided. Gas pressure gauge shall
be fitted on the common feed pipe to monitor the pressure of SF6
gas in the interrupter.
Absorbent shall also be provided in each interrupting unit to keep
the SF6 gas dry & absorb the decomposed product of SF6 gas,
formed during arcing.
Bidder shall give complete constructional details for SF6 gas
circuit breaker offered by them. The insulation level of porcelain of
the circuit breaker shall be so coordinated with that of the breaker
that flashover shall occur externally to the breaker.
3.2.2 In case of SF6 circuit breaker, it shall be possible to arrange for
either automatic tripping of the circuit breaker or tripping of circuit
breaker on fault and will be automatically locked when the
pressure in the individual interrupter reaches below the limit
value. Arrangements shall be made to prevent closing of the
breaker due to leakage of gas passing through the closing valve
without a positive impulse from the closing coil.
3.2.3 The SF6 gas used in the circuit Breaker shall comply in all
respect with the provisions of the latest edition of relevant
standard.
3.2.4 Inter Locks :
3.2.4(a) Pressure switches with the required pressure fitting must be
incorporated to ensure safety of breaker operation when SF6 gas
GETCO/E/06TS – CB/R3 May12
Page 17 of 26
pressure goes below the specified pressure range due to
leakage, the trip coil circuit & closing coil circuit must be cut-off.
The pressure switch shall generally be temperature compensated
gas pressure switch having two micro-switches, operating at
different pressures one for low pressure alarm and other for low
pressure cutout.
3.2.4(b) Additional dedicated pressure switch with 4 poles for Normal, Low gas,
Lockout, etc shall be provided for SCADA remote operations. L/R switch
shall have spare contacts.
3.2.4(c) Limit switch for motors shall be provided with 4 NO and 4 NC contacts.
GETCO/E/06TS – CB/R3 May12
Page 18 of 26
SECTION – IV
SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS
FOR 66KV SF-6 GAS Spring operated CIRCUIT BREAKERS
(TO BE FILLED IN & SIGNED BY THE BIDDER)
SN PARTICULARS
1. Name of Manufacturer :
2.
2.a
Type Designation of CB
Type designation of Spring mechanism
(as per Mech. Endu. test report)
:
:
3. Governing Standard :
4. Rated Voltage (KV) :
5. Maximum continuous rated service
voltage (KV)
:
6. Frequency (Hz) :
7. Whether outdoor breaker offered (Yes /
No)
:
8. Nominal current rating
i) Under standard condition. (Amp)
ii) Under site condition (Amp).
iii) Type test reports submitted of
(Amp)
:
:
:
9. Short time current rating (kA) for 3
seconds
:
10. Maximum temperature rise over ambient
temp. due to rated current in main
contacts measured after breaking test.
(0
C)
:
GETCO/E/06TS – CB/R3 May12
Page 19 of 26
SN PARTICULARS
11. Rated short circuit breaking current
a) Rated short circuit current (AC
component) (KV rms).
b) Percentage DC component
c) Asymmetrical breaking current
(including DC component (KA rms).
d) Rated symmetrical breaking capacity
in MVA FOR SF6 CB
:
:
:
12. Making capacity (kA Peak) :
13. Total breaking time (Milli-seconds) :
a) For interruption of 10% of the rated
capacity.
b) For interruption of 30% of the rated
capacity.
c) For interruption of 60% of rated
capacity.
d) For interruption of the full rated
capacity.
:
:
:
:
:
14. Arcing time ( milliseconds) :
15a
b.
c.
Making time (milliseconds)
Rated closing time (milliseconds)
Rated opening time (milliseconds)
:
:
:
16. Minimum reclosing time at rated
interrupting capacity from the in fault of
the trip coil energisation (Millisecond)
:
GETCO/E/06TS – CB/R3 May12
Page 20 of 26
SN PARTICULARS
17. A) Minimum dead time
a) 3 phase reclosing (Milliseconds).
b) Limit of adjustment of dead time
for 3-phase reclosing.
B) Whether restrike free and trip free. (IS
/ IEC applicable may be stated).
:
:
:
18. Date on restriking voltage for 100%, 50%
& 30% rated capacity
a) Amplitude factor (max)
b) Phase factor (max)
c) Natural Frequency (Hz)
d) Rate of rise of restriking voltage
(V/Micro-Sec) (max)
:
:
:
:
19. Maximum interrupting capacity under
phase opposition condition (MVA).
:
20. Maximum line charging current breaking
capacity without over voltage exceeding
2.5phase neutral voltage (Amps.)
:
21. Maximum line charging current breaking
capacity corresponding over-voltage
recorded
a) On supply side.
b) On line side.
:
:
22. Maximum cable charging current
breaking capacity & corresponding over-
voltage recorded in test.
a) On supply side.
b) On line side.
:
:
:
23. Maximum shunt capacitor Bank switching
capacity (MVA)
:
GETCO/E/06TS – CB/R3 May12
Page 21 of 26
SN PARTICULARS
24. Maximum breaking capacity on kilometric
fault (MVA)
:
25. Maximum over-voltage on switching
transformers on no load & the charging
current.
:
26. Dry 1 Minute power frequency test
withstand voltage, for complete circuit
breaker
a) Between line & Grounded parts (kV
rms)
b) Between line with breaker contacts
open (kV rms)
:
:
27. Wet 1-minute power frequency withstand
voltage for complete circuit breaker
a) Between line terminal & grounded
parts (kV rms)
b) Between terminals with breaker
contacts open (kV rms)
:
:
:
28. 1.2/50 Micro-second wave lightning
impulse withstand test voltage for
complete circuit breaker, as per type test
report submitted.
a) Between line terminal and ground
(kV peak)
b) Between terminal with circuit breaker
contacts open (kV peak).
:
:
:
SUPPORTING INSULATORS :
29. Make & Type :
30. Insulation Class :
31. Visible Corona discharge voltage :
32. Wet 1-minute power frequency flashover
voltage (kV rms).
:
GETCO/E/06TS – CB/R3 May12
Page 22 of 26
SN PARTICULARS
33. Dry 1-minute power frequency flashover
voltage (kV rms)
:
34. 1.2/50 micro-second impulse flashover
voltage (kV peak)
:
35. Total creepage distance for heavily
polluted atmosphere
:
36. Minimum clearance in air
a) Between phases (mm)
b) Live parts & earth (mm)
c) Live parts to Plinth level (mm).
:
:
:
:
36.a
36.b
Permissible safe cantilever loading on
installed porcelain (kg.m)
Permissible safe compressive strength of
installed porcelain
37. No. of poles per circuit
breaker
:
38. Breaks per pole (Nos). :
39. Total length of breaks per
phase (mm).
:
40 Type of main contacts :
41. Material of main contacts :
42. Whether main contacts silver
plates (Yes/No)
:
43. Thickness of silver coating on
main contacts (mm).
:
44. Contact pressure on main
contacts (Kg/M2).
:
45. Type of arcing contacts :
46. Contact pressure on arcing
contact (Kg/M2).
:
47. Type of auxiliary switches :
GETCO/E/06TS – CB/R3 May12
Page 23 of 26
SN PARTICULARS
48. Material of switch contacts :
49. Whether contacts silver plates
(Yes/No.)
:
50. No. of auxiliary switch
contacts operating with all
three poles of breaker
a) Which are closed when
breaker is closed.
b) Which are open when
breaker is closed
:
:
51A No. of spare auxiliary switch
contacts operating
a) Which are closed when
breaker is closed.
b) Which are open when
breaker is closed.
:
B Details of SF6 Gas pressure
switch and its setting for low
pressure alarm and low
pressure cut-out.
:
52. No. of operations possible
without maintenance
a) At full rated interrupting
capacity.
b) At 50% of rated
interrupted capacity
c) At 100% of rated current
d) At 50% of rated current
:
:
:
:
:
53. Details of foundation :
GETCO/E/06TS – CB/R3 May12
Page 24 of 26
SN PARTICULARS
54. Type of operating mechanism
(motor operated spring
charged).
a) Opening
b) Closing
c) Control voltage aux.
:
:
:
:
54a Details of spring charging motor
i) Type
ii) Rated supply voltage
iii) Wattage
iv) Max time for charging
spring
:
55. Tripping & closing circuit
voltage (V). (110 V/220 V.)
As per requirement.
:
56. Power required for trip coil (in
watts).
:
57. Power required for closing coil
(in watts).
:
58. Weight of 3-φ breaker
complete with operating
mechanism, supporting,
insulators, frame work etc.
:
59. Impact loading for foundation
design to include dead load
plug impact value on opening
it maximum interrupting rating
in terms of equivalent static
load.
:
60. Weight of heaviest package
(Kgs) space requirements
(Length, Width, Height).
:
GETCO/E/06TS – CB/R3 May12
Page 25 of 26
SN PARTICULARS
61. A) Details of Gas pressure
switch and its setting for
low pressure alarm and
low pressure cut-out.
:
:
62 SF6 GAS DETAILS:
a) Rated SF6 Gas
pressure (temperature
200
C) (Kg/cm2
)
b) IS / Equivalent standard
applicable for SF6 Gas.
c) Quantity in each pole
d) Total quantity
e) Spare gas quantity (%)
:
:
:
63 Terminal connector
(Bimetallic compression type)
:
64 Seismic level (g) :
__________________ _________________________
SEAL OF THE FIRM SIGNATURE OF TENDERER
GETCO/E/06TS – CB/R3 May12
Page 26 of 26
SECTION – V
List of documents attached with technical bid:
Bidder shall invariably attach the following documents and clearly marked
and duly flagged in technical bid. In absence of these documents offer will
be evaluated as a non submission.
Sr.
No.
Particulars of document Whether
attached the with
technical bid
1 Drawings in AutoCAD format
2 Drawings hard copies as indicated in
specification
3 Manual in PDF format
4 QAP for manufacturing process in SOFT
format
5 QAP for manufacturing process in Hard format
6 FQP in SOFT format
7 FQP in Hard copy
8 Type test Reports in hard copies
a for breaker
b for clamps & connectors
9 Confirmation regarding type tests as per
clause no. 1.10(a) page no. 10 –
“IMPORTANT NOTE”
10 Guaranteed Technical Particulars, completely
filled in
11 Any other essential documents
SIGNATURE OF BIDDER COMPANY’S ROUND SEAL
DATE:
PLACE:

More Related Content

What's hot

02- Manual Motor Starter - Fuji Electric
02- Manual Motor Starter - Fuji Electric02- Manual Motor Starter - Fuji Electric
02- Manual Motor Starter - Fuji ElectricCTY TNHH HẠO PHƯƠNG
 
Catalog Mitsubishi Inverter FR D700 Global-Beeteco.com
Catalog Mitsubishi Inverter FR D700 Global-Beeteco.comCatalog Mitsubishi Inverter FR D700 Global-Beeteco.com
Catalog Mitsubishi Inverter FR D700 Global-Beeteco.comBeeteco
 
Metal clad switchgear 33k v
Metal clad switchgear 33k v Metal clad switchgear 33k v
Metal clad switchgear 33k v JoeChueng
 
Far series outdoor auto circuit recloser
Far series outdoor auto circuit recloserFar series outdoor auto circuit recloser
Far series outdoor auto circuit recloserAUTO RECLOSER
 
Advanced motion controls 20a20
Advanced motion controls 20a20Advanced motion controls 20a20
Advanced motion controls 20a20Electromate
 
Advanced motion controls s30a40ac
Advanced motion controls s30a40acAdvanced motion controls s30a40ac
Advanced motion controls s30a40acElectromate
 
Mini-Contactors and Thermal Overload Relays - SK Series
Mini-Contactors and Thermal Overload Relays - SK SeriesMini-Contactors and Thermal Overload Relays - SK Series
Mini-Contactors and Thermal Overload Relays - SK SeriesCTY TNHH HẠO PHƯƠNG
 
01. superswitch switch disconnector fuse and din bs fuses
01. superswitch switch disconnector fuse and din bs fuses01. superswitch switch disconnector fuse and din bs fuses
01. superswitch switch disconnector fuse and din bs fusesangelochintu
 
ABB Medium Voltage MV Surge Arresters - AC & DC Surge Arresters & Protection...
ABB Medium Voltage MV Surge Arresters -  AC & DC Surge Arresters & Protection...ABB Medium Voltage MV Surge Arresters -  AC & DC Surge Arresters & Protection...
ABB Medium Voltage MV Surge Arresters - AC & DC Surge Arresters & Protection...Thorne & Derrick International
 
Catalog inverter family Mitsubishi Electric-Beeteco.com
Catalog inverter family Mitsubishi Electric-Beeteco.comCatalog inverter family Mitsubishi Electric-Beeteco.com
Catalog inverter family Mitsubishi Electric-Beeteco.comBeeteco
 

What's hot (20)

02- Manual Motor Starter - Fuji Electric
02- Manual Motor Starter - Fuji Electric02- Manual Motor Starter - Fuji Electric
02- Manual Motor Starter - Fuji Electric
 
Catalog Mitsubishi Inverter FR D700 Global-Beeteco.com
Catalog Mitsubishi Inverter FR D700 Global-Beeteco.comCatalog Mitsubishi Inverter FR D700 Global-Beeteco.com
Catalog Mitsubishi Inverter FR D700 Global-Beeteco.com
 
Metal clad switchgear 33k v
Metal clad switchgear 33k v Metal clad switchgear 33k v
Metal clad switchgear 33k v
 
Acb mitsu
Acb mitsuAcb mitsu
Acb mitsu
 
Cptg011 en (web)
Cptg011 en (web)Cptg011 en (web)
Cptg011 en (web)
 
Far series outdoor auto circuit recloser
Far series outdoor auto circuit recloserFar series outdoor auto circuit recloser
Far series outdoor auto circuit recloser
 
Advanced motion controls 20a20
Advanced motion controls 20a20Advanced motion controls 20a20
Advanced motion controls 20a20
 
Sicop datasheet
Sicop datasheetSicop datasheet
Sicop datasheet
 
Advanced motion controls s30a40ac
Advanced motion controls s30a40acAdvanced motion controls s30a40ac
Advanced motion controls s30a40ac
 
Mini-Contactors and Thermal Overload Relays - SK Series
Mini-Contactors and Thermal Overload Relays - SK SeriesMini-Contactors and Thermal Overload Relays - SK Series
Mini-Contactors and Thermal Overload Relays - SK Series
 
MIL-STD-461G - CS
MIL-STD-461G - CSMIL-STD-461G - CS
MIL-STD-461G - CS
 
4000 001
4000 0014000 001
4000 001
 
01. superswitch switch disconnector fuse and din bs fuses
01. superswitch switch disconnector fuse and din bs fuses01. superswitch switch disconnector fuse and din bs fuses
01. superswitch switch disconnector fuse and din bs fuses
 
Electromagnetic flowmeter battery power
Electromagnetic flowmeter battery powerElectromagnetic flowmeter battery power
Electromagnetic flowmeter battery power
 
3000 001
3000 0013000 001
3000 001
 
ABB Medium Voltage MV Surge Arresters - AC & DC Surge Arresters & Protection...
ABB Medium Voltage MV Surge Arresters -  AC & DC Surge Arresters & Protection...ABB Medium Voltage MV Surge Arresters -  AC & DC Surge Arresters & Protection...
ABB Medium Voltage MV Surge Arresters - AC & DC Surge Arresters & Protection...
 
MIL-STD-461G - CE
MIL-STD-461G - CEMIL-STD-461G - CE
MIL-STD-461G - CE
 
Catalog inverter family Mitsubishi Electric-Beeteco.com
Catalog inverter family Mitsubishi Electric-Beeteco.comCatalog inverter family Mitsubishi Electric-Beeteco.com
Catalog inverter family Mitsubishi Electric-Beeteco.com
 
Thông số kĩ thuật siemens monitoring devices
Thông số kĩ thuật siemens monitoring devicesThông số kĩ thuật siemens monitoring devices
Thông số kĩ thuật siemens monitoring devices
 
Thông số kĩ thuật siemens miniature circuit breakers
Thông số kĩ thuật siemens miniature circuit breakersThông số kĩ thuật siemens miniature circuit breakers
Thông số kĩ thuật siemens miniature circuit breakers
 

Similar to 66 k v_sf6_bkr_r3_may12

Acsr moose conductor
Acsr moose conductorAcsr moose conductor
Acsr moose conductorDineshsenthil
 
3D_Distribution transformer_Specification.pdf
3D_Distribution transformer_Specification.pdf3D_Distribution transformer_Specification.pdf
3D_Distribution transformer_Specification.pdfShahrukhKhan424745
 
2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revised2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revisedBasudev patra
 
Technical specification for 3.ph 4 wire stw 12 02-11
Technical specification for 3.ph 4 wire stw 12 02-11Technical specification for 3.ph 4 wire stw 12 02-11
Technical specification for 3.ph 4 wire stw 12 02-11laxman prasad
 
110KV Substation spec with AnnexuresR.pdf
110KV Substation spec with AnnexuresR.pdf110KV Substation spec with AnnexuresR.pdf
110KV Substation spec with AnnexuresR.pdfKSLDESIGN
 
A study on IEC 60947- 2 amendments
A study on IEC 60947- 2 amendmentsA study on IEC 60947- 2 amendments
A study on IEC 60947- 2 amendmentsricha diptisikha
 
Technical information for high voltage disconnector & earthing switch in enqu...
Technical information for high voltage disconnector & earthing switch in enqu...Technical information for high voltage disconnector & earthing switch in enqu...
Technical information for high voltage disconnector & earthing switch in enqu...Ali Sepehri
 
Tes p-122.01-r0 (2)
Tes p-122.01-r0 (2)Tes p-122.01-r0 (2)
Tes p-122.01-r0 (2)Ibrahim Ali
 
ENATS 12-24 Technical Specification For Plastic Ducts For Buried Electric Cables
ENATS 12-24 Technical Specification For Plastic Ducts For Buried Electric CablesENATS 12-24 Technical Specification For Plastic Ducts For Buried Electric Cables
ENATS 12-24 Technical Specification For Plastic Ducts For Buried Electric CablesThorne & Derrick International
 
Specifications of Solar Power system (Issue-II).pdf
Specifications of Solar Power system (Issue-II).pdfSpecifications of Solar Power system (Issue-II).pdf
Specifications of Solar Power system (Issue-II).pdfAmjiShah
 
ABB WBT Indoor Fuses IEC Standard 1.9kV-4kV - ABB Medium Voltage Indoor Railw...
ABB WBT Indoor Fuses IEC Standard 1.9kV-4kV - ABB Medium Voltage Indoor Railw...ABB WBT Indoor Fuses IEC Standard 1.9kV-4kV - ABB Medium Voltage Indoor Railw...
ABB WBT Indoor Fuses IEC Standard 1.9kV-4kV - ABB Medium Voltage Indoor Railw...Thorne & Derrick International
 
Tender Document for Solar Power Plant in Gujarat Part 2
Tender Document for Solar Power Plant in Gujarat Part 2Tender Document for Solar Power Plant in Gujarat Part 2
Tender Document for Solar Power Plant in Gujarat Part 2Headway Solar
 

Similar to 66 k v_sf6_bkr_r3_may12 (20)

Acsr moose conductor
Acsr moose conductorAcsr moose conductor
Acsr moose conductor
 
3D_Distribution transformer_Specification.pdf
3D_Distribution transformer_Specification.pdf3D_Distribution transformer_Specification.pdf
3D_Distribution transformer_Specification.pdf
 
2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revised2011 12-33kv tech.spec for v c b type- m2-c1-revised
2011 12-33kv tech.spec for v c b type- m2-c1-revised
 
Technical specification for 3.ph 4 wire stw 12 02-11
Technical specification for 3.ph 4 wire stw 12 02-11Technical specification for 3.ph 4 wire stw 12 02-11
Technical specification for 3.ph 4 wire stw 12 02-11
 
BOQ _UN.pptx
BOQ _UN.pptxBOQ _UN.pptx
BOQ _UN.pptx
 
14 mq11 02-te-0000-ee0012-0
14 mq11 02-te-0000-ee0012-014 mq11 02-te-0000-ee0012-0
14 mq11 02-te-0000-ee0012-0
 
03c-eil-mr-3002-dd1059.pdf
03c-eil-mr-3002-dd1059.pdf03c-eil-mr-3002-dd1059.pdf
03c-eil-mr-3002-dd1059.pdf
 
110KV Substation spec with AnnexuresR.pdf
110KV Substation spec with AnnexuresR.pdf110KV Substation spec with AnnexuresR.pdf
110KV Substation spec with AnnexuresR.pdf
 
A study on IEC 60947- 2 amendments
A study on IEC 60947- 2 amendmentsA study on IEC 60947- 2 amendments
A study on IEC 60947- 2 amendments
 
Technical information for high voltage disconnector & earthing switch in enqu...
Technical information for high voltage disconnector & earthing switch in enqu...Technical information for high voltage disconnector & earthing switch in enqu...
Technical information for high voltage disconnector & earthing switch in enqu...
 
Tes p-122.01-r0 (2)
Tes p-122.01-r0 (2)Tes p-122.01-r0 (2)
Tes p-122.01-r0 (2)
 
Sas guj
Sas gujSas guj
Sas guj
 
11.docx
11.docx11.docx
11.docx
 
Telescopic poles nea
Telescopic poles  neaTelescopic poles  nea
Telescopic poles nea
 
ENATS 12-24 Technical Specification For Plastic Ducts For Buried Electric Cables
ENATS 12-24 Technical Specification For Plastic Ducts For Buried Electric CablesENATS 12-24 Technical Specification For Plastic Ducts For Buried Electric Cables
ENATS 12-24 Technical Specification For Plastic Ducts For Buried Electric Cables
 
Specifications of Solar Power system (Issue-II).pdf
Specifications of Solar Power system (Issue-II).pdfSpecifications of Solar Power system (Issue-II).pdf
Specifications of Solar Power system (Issue-II).pdf
 
ABB WBT Indoor Fuses IEC Standard 1.9kV-4kV - ABB Medium Voltage Indoor Railw...
ABB WBT Indoor Fuses IEC Standard 1.9kV-4kV - ABB Medium Voltage Indoor Railw...ABB WBT Indoor Fuses IEC Standard 1.9kV-4kV - ABB Medium Voltage Indoor Railw...
ABB WBT Indoor Fuses IEC Standard 1.9kV-4kV - ABB Medium Voltage Indoor Railw...
 
Dialectirc tests
Dialectirc testsDialectirc tests
Dialectirc tests
 
Tender Document for Solar Power Plant in Gujarat Part 2
Tender Document for Solar Power Plant in Gujarat Part 2Tender Document for Solar Power Plant in Gujarat Part 2
Tender Document for Solar Power Plant in Gujarat Part 2
 
20150209111021 tech spn dtd 29.jan 2015
20150209111021 tech spn dtd 29.jan 201520150209111021 tech spn dtd 29.jan 2015
20150209111021 tech spn dtd 29.jan 2015
 

Recently uploaded

Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...RajaP95
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 

Recently uploaded (20)

Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 

66 k v_sf6_bkr_r3_may12

  • 1. GETCO/E/06TS – CB/R3 May12 Page 1 of 26 GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA – 390 007. TECHNICAL SPECIFICATION FOR 66 kV SF6 CIRCUIT BREAKER (SPRING OPERATED) GETCO/E/06TS – CB/R3 May12
  • 2. GETCO/E/06TS – CB/R3 May12 Page 2 of 26 SPECIAL INSTRUCTIONS TO BIDDER Please read following instructions carefully before submitting your bid. 1. All the drawings, i.e. elevation, side view, plan, cross sectional view etc., in AutoCAD format and manuals in PDF format, for offered item shall be submitted. Also the hard copies as per specification shall be submitted. 2. The bidder shall submit Quality Assurance Plan with the technical bid. 3. The bidder shall have to submit all the required type test reports for the offered item. In absence of this, the evaluation shall be carried out accordingly as non-submission of type test reports. 4. The bidder must fill up all the points of GTP for offered item/s. Instead of indicating “refer drawing, or as per IS/IEC”, the exact value/s must be filled in. 5. All the points other than GTP, which are asked to confirm in technical specifications must be submitted separately with the bid. 6. The bidder is required to impart training in view of manufacture, assembly, erection, operation and maintenance for offered item, at his works, to the person/s identified by GETCO, in the event of an order, free of cost. The cost of logistics will be bear by GETCO. 7. Please note that the evaluation will be carried out on the strength of content of bid only. No further correspondence will be made. 8. The bidder shall bring out all the technical deviation/s only at the specified annexure.
  • 3. GETCO/E/06TS – CB/R3 May12 Page 3 of 26 QUALIFYING REQUIREMENT DATA (For Supply) Bidder to satisfy all the following requirements. 1) The bidder shall be Original Equipment Manufacturer (OEM). The offered equipment have to be designed, manufactured and tested as per relevant IS/IEC with latest amendments. 2) The minimum requirement of manufacturing capacity of offered type, size and rating of equipment shall be FIVE times tender/ bid quantity. The bidder should indicate manufacturing capacity by submitting latest updated certificate of a Chartered Engineer (CE). 3) Equipment proposed shall be of similar or higher rating and in service for a minimum period of THREE (3) years and satisfactory performance certificate in respect of this is to be available and submitted. 4) The bidder should clearly indicate the quantity and Single Value Contract executed during last FIVE (5) years, for the offered equipment. Bidder should have executed one single contract during last five years for the quantity equivalent to tender / bid. The details are to be submitted in following format, Sr. No ITEMS SUPPL IED TO ORDER REFEREN CE No. & DATE ITEMS QUANTITY ORDER FULLY EXECUTED. YES/NO STATUS, IF ORDER UNDER EXECUTION REMARK e) Equipment offered shall have Type Test Certificates from accredited laboratory (accredited based on ISO/IEC Guide 25 / 17025 or EN 45001 by the National accredition body of the country where laboratory is located), as per IEC / IS / technical specification. The type test reports shall not be older than FIVE years and shall be valid up to expiry of validity of offer.
  • 4. GETCO/E/06TS – CB/R3 May12 Page 4 of 26 TECHNICAL SPECIFICATION FOR 66 kV SF6 GAS CIRCUIT BREAKER SECTION – I GENERAL TECHNICAL REQUIREMENTS 1.1 SCOPE : 1.1.1 This section covers the design, manufacture, testing, inspection, supply and delivery of 66 kV SF6 gas Circuit Breakers SPRING operated, along with associated accessories and complete in all respects specified in the schedule of requirements. 1.2 APPLICABLE STANDARDS: 1.2.1 The equipment to be supplied under this specification shall conform to the latest issue of standards, rules and codes some of which are mentioned below. 1. IEC-62271/ IS 13118 Specification for alternating current Circuit breaker 2. IEC-60376 Specification and acceptance of new Supply of sulfur Hexafluoride. 3. IS: 2147 Degree of protection provided for Enclosures for low voltage switchgear and control gear. 4. IS: 375 Marking and arrangement for switchgear bus- bar, main connections and auxiliary wiring. 5. IS: 325 Specification for 3ph induction motor. 6. IS: 2516 Specification for circuit breaker. 7. IS: 2099 High voltage porcelain bushing. 9. IS: 2629 Recommended practice for hot dip galvanizing of iron and steel. The components & accessories to be used in the manufacture of circuit breaker shall conform to relevant Indian Standards/the standard specified under respective clause in this specification. However, in the event the offered breakers confirming to any other standard, salient points of differences between the standard adopted and the specified standards shall be clearly indicated in the offer.
  • 5. GETCO/E/06TS – CB/R3 May12 Page 5 of 26 1.3 DRAWINGS/DOCUMENTS: 1.3.1 The bidder shall furnish the drawings in triplicate incorporating the following particulars. a) Drawing showing the general outlines dimensions of circuit breakers, with clear identification of parts / items. b) Drawing showing control cabinets and circuit diagrams for operating mechanism of circuit breakers. c) Drawing showing the complete operation cycle of the circuit breaker with description. d) Compression type terminal connectors for the breakers. e) All the documents required shall be submitted over and above as indicated in Section - V of the specification. 1.3.1.1 The Bidder shall submit the following drawings within 15 days from the date of receipt of clear order: - a) Outline dimensional drawings showing all parts / items, transport weight etc. of circuit breaker & its support structure. b) Detailed drawings of operating mechanism of circuit breakers. c) Wiring and control diagram. d) Drawings of foundation details, mounting structures, spacing of bolts etc. e) Compression type terminal connectors, with STC rating, bill of materials, etc., complete with all dimensions. f) MQP, FQP, erection, operation & maintenance manuals. 1.3.1.2 The bidder may also, submit any other drawings found necessary in addition to the drawings stated above. 1.4.1 GENERAL DESIGN FEATURES OF CIRCUIT BREAKERS: 1.4.1.1 The circuit breakers shall be capable of rapid and smooth interruption of currents under all conditions completely suppressing all undesirable phenomena even under the most severe and persistent short circuit conditions or when interrupting small currents or leading or lagging reactive currents. The circuit breakers shall be ‘Restrike-Free’ under all operating conditions. The details of any device incorporated to limit or control the rate of rise of restriking voltage across, the circuit breaker contacts shall be stated. The over voltages caused by circuit breaker while switching inductive or capacitive loads shall not exceed 2.5 times the highest phase to neutral voltage. The actual make and break times for the circuit breakers throughout the ranges of their operating duties shall be stated in the offer and guaranteed. 1.4.1.2 The arc quenching chambers shall have devices to ensure almost uniform distribution of voltage across the interrupters.
  • 6. GETCO/E/06TS – CB/R3 May12 Page 6 of 26 1.4.1.3 Breaking Capacity: The interrupting capacity of the breaker for kilometric faults (short line faults) shall be equal to its interrupting capacity as per IS: 13118 / IEC 62271 and shall be stated in the tender. The details of tests conducted for confirming the capability of the breakers under kilometric fault conditions shall be furnished in the offer. 1.4.1.4 The circuit breakers shall be designed for interrupting line charging currents without undue rise in the voltage on supply side and without any restrike and without showing signs of undue strain. The guaranteed over voltage which shall not be exceeded while interrupting the line charging currents as specified under the Clause 2.4.10 of Section-II of this specification shall be stated in the offer. 1.4.1.5 The circuit breakers shall be capable of interrupting small inductive currents (occurring while switching off unloaded transformer) without giving rise to undue over voltage and without restrikes. The maximum over voltage value which will not be exceeded under such conditions shall be stated in the offer, and in conformity to this, test reports along with oscillograph shall be furnished in the offer. 1.4.1.6 Restriking Voltage: The circuit breakers shall be capable of interrupting the rated power when the restriking voltage has a frequency of not less than 400 Hz and with a restriking voltage having frequency of 2000 Hz. The circuit breakers shall be capable of interrupting at least 50% of nominal breaking capacity. 1.4.1.7 The measures adopted for ensuring proper operation at high rate of rise of restriking voltage and for limiting the actual voltage values across the breaks shall be described in the tender. The type characteristics and rating of the resistor used, if any, to shunt the breaker contacts and of the auxiliary switching devices used for interrupting the resistor current shall be clearly stated. 1.4.1.8 Recovery voltage and power Factor: The circuit breaker shall be capable of interrupting the rated power with recovery voltage equal to the rated maximum line to line service voltage at rated frequency and at a power factor not exceeding 0.15. 1.4.1.9 The circuit breakers shall also be capable of satisfactory operation even under conditions of phase opposition that may arise due to faulty synchronizing. The maximum power which the breaker can satisfactorily interrupt under phase opposition shall be stated in the offer.
  • 7. GETCO/E/06TS – CB/R3 May12 Page 7 of 26 1.4.1.10 The operating duty of the circuit breaker shall be as specified under Clause - 2.4.12 of specific technical requirement for breakers. 1.4.2 Temperature Rise: 1.4.2.1 The temperature rise and the maximum temperature on any part of the breaker when in service under continuous full load conditions and exposed continuously to the direct sun-rays shall not exceed the permissible limits as per relevant ISS. When the standard specifies the limits of temperature rise, this shall not be exceeded when corrected for the difference between ambient temperature at site and the ambient temperature specified in the relevant specification. The correction proposed shall be stated in offer and shall be subject to the approval of the purchaser. 1.4.3 General Features of Circuit Breakers: 1.4.3.1 The circuit breakers shall be suitable for outdoor operation under the climatic conditions specified in section-II of this specification. 1.4.3.1(a) The circuit breakers operating mechanism shall have two nos. of tripping coils and one no. of closing coil for both 66 kV SF6 Gas CB for better reliability. There shall be separate contactor for each coil. 1.4.3.2 Exposed live parts shall be placed high enough above ground to meet the requirements of local safety codes. 1.4.3.3 All similar parts, particularly removable one and shall be interchangeable with one another. 1.4.4 Insulation of the Circuit Breaker: The insulation to ground, the insulation between open contacts and the insulation between phases of the completely assembled circuit breaker shall capable of withstanding satisfactorily die-electric test voltages corresponding to BIL specified in Clause – 2.4.2 of this specification. 1.4.5(a) The minimum clearances in open air shall be as under in case of SF-6 Breakers: Minimum clearance between phase : As per relevant IS. Minimum clearance between live parts : As per relevant IS. and grounded objects. 1.4.5(b) Adequate clearance in air shall be provided between phase and from phase to ground. The clearance shall be such that the breaker shall withstand the BIL specified in the specification. The minimum clearance from live parts to ground level shall not be less than 4000 mm – including plinth height as 300 mm.
  • 8. GETCO/E/06TS – CB/R3 May12 Page 8 of 26 1.4.6 Contacts of Circuit Breaker: 1.4.6.1 The main contacts shall have adequate area and contact pressure for carrying the rated currents and the short time rated breaking currents of the breaker without excessive temperature rise. Contacts shall be easily replaceable and shall have a minimum of movable parts and adjustments. The main contacts shall be first to open and last to close so that burning of the contact may be negligible. 1.4.7 Operating Mechanism of Circuit Breakers: 1.4.7.1 Circuit breakers shall be power operated by a motor compressed spring charging mechanism; the mechanism will be trip-free electrically and mechanically. The mechanism shall be strong, quick in action and shall be removable without disturbing other parts of the circuit breakers. All the working parts in the mechanism shall be of corrosion resistant materials and all bearings which require greasing, shall be equipped with pressure grease fittings. The mechanism and breaker shall be such that the failure of any spring will not prevent tripping and will not cause tripping or closing. 1.4.7.2 The circuit breakers shall be designed for remote control from the control room and there shall be provision for manual operation of circuit breakers during maintenance and for local tripping and closing by normal means. 1.4.7.3 The circuit breaker shall have a mechanical ‘ON-OFF’ indicator in addition to facilities for remote electrical indicator. 1.4.7.4 The operating mechanism along with its accessories shall be suitable for electrical operation and shall be mounted in a weather proof cabinet with hinged doors located near the breakers. The cabinet shall be suitable for IP 55 degree of protection. The operation shall be possible from ground or necessary HDG stand/platform of suitable height maintaining all safety clearance with live parts shall be supplied as a part of breaker. The local control switch and the breaker position indicator shall be provided in this cabinet, which shall be free standing and supported by suitable arrangement. The control circuit shall be designed to operate on D.C. as specified in section-II of this specification. The closing and opening coils shall be designed to operate satisfactorily at any control voltage from 85% to 110% & 70% to 110% of the normal voltage, respectively. A heater of adequate capacity with thermostat shall be provided in the cabinet to avoid moisture condensation. 1.4.7.4(a) The terminal block shall of 1.1 KV voltage grade & shall be with stud type connections instead of with screw types connections.
  • 9. GETCO/E/06TS – CB/R3 May12 Page 9 of 26 1.4.8 Auxiliary switches: 1.4.8.1 A minimum number of 6 NC + 6 NO Auxiliary switches contacts shall be provided on each circuit breaker for use in remote indication control scheme of the circular breakers and for safety interlocking. Special contacts for use with trip coils and auto reclosing operation shall also be provided. Provision shall be made for adding more auxiliary switches, if required. Auxiliary switches shall be placed in weatherproof galvanized casing and current rating of switches shall be mentioned in the offer. 1.5 BUSHING & INSULATORS: 1.5.1 The porcelain insulator used in manufacturing the bushings shall be homogeneous, free from laminations, cavities and other flaws or imperfection that might affect the mechanical or dielectric qualities. All bushings of identical ratings shall be interchangeable. The insulators shall conform to the latest edition of IS: 3447 or other equivalent standard. The puncture strengths of the bushings shall be greater than their flashover values. The bushings shall be entirely free from external and internal corona. The protected and total creepage distance of the bushings shall be suitable for heavily polluted atmosphere. The minimum creepage distance of the insulator shall be 1810 mm suitable for heaving polluted atmosphere. The compressive and cantilever strength shall conform to the relevant IS. 1.6 TERMINAL CONNECTORS AND EARTHING TERMINALS : 1.6.1 Compression joint type terminal connectors suitable for single or twin ACSR panther/zebra/Moose as indicated in Schedule – A of respective tender, shall be supplied and they shall be suitable for both vertical and horizontal connections of the Transmission line conductor or station bus bar. Suitable terminal earth connectors (two Nos.) for earthing connections shall also be supplied. The drawings for these connectors shall be submitted. SS bolt for connector shall be provided with two Nos. of SS nuts (including lock nut & one SS washer. 1.7 TROPICALISATION: 1.7.1 All control wiring, electric motors and accessories shall be protected against fungus growth and other harmful effects due to tropical environments. 1.8 GALVANIZING:
  • 10. GETCO/E/06TS – CB/R3 May12 Page 10 of 26 1.8.1 All ferrous parts of breakers and bolts, nuts etc. shall be hot-dip galvanized as per latest edition of IS: 2629. Support structure’s galvanizing shall be done as per IS 4843 (latest edition). Electro galvanized bolts nuts, & washers are also acceptable. 1.9 PAINTING: 1.9.1 Interior and exteriors of tanks, mechanisms, enclosures, cabinets and other metal parts shall be thoroughly cleaned to remove all rust scales, corrosion and other adhering foreign matter, steel surfaces in contacts with insulation oil, as far as possible shall be painting with not less than two coats of heat resistant, oil insoluble, insulating varnish light-grey paint shade 631 as per IS:5 shall be selected to withstand tropical heat and extremes of weather. 1.10 TEST AND TEST REPORTS: 1.10.1 Reports of following type tests carried out in NABL / Govt. approved laboratory within five years prior to expiry of validity of offer, as per IS: 13118 / IEC 62271-100 for A C circuit breakers shall be submitted along with the offer : (i) Lightning impulse withstand voltage test (ii) Power frequency voltage withstand voltage test. (Dry as well as Wet) (iii) Temperature rise test. (iv) Measurement of resistance of main circuit (v) Short time current withstand and peak current withstand Test (vi) Mechanical endurance test (vii) Duty cycle & Single phase short circuit test. (viii) Out of phase making and breaking current test. (ix) Capacitor current switching test for isolated neutral capacitor banks. (x) Line charging current switching test (xi) Cable charging current switching test (xii) Short line fault duty test (xiii) Degree of protection test on cubicles IMPORTANT NOTE: In case of non-submission of some of the type test reports, the bidder shall confirm the submission of same before commencement of supply, without affecting delivery schedule, from NABL accredited laboratory, free of cost. In absence of this confirmation, the offer will be evaluated as non submission of type test report. 1.10.2 Routine tests as per the latest edition of IS: 13118/IEC 62271 for circuit breakers shall be carried out on each circuit breaker. All the acceptance tests in presence of GETCO representative shall be carried out on circuit breakers selected from offered lot.
  • 11. GETCO/E/06TS – CB/R3 May12 Page 11 of 26 1.10.3 In addition to above, speed curves for each breaker shall be obtained with the help of a suitable operation analyzer to determine the breaker contact movement during opening, closing, auto-re-closing and trip free operations under normal as well as limiting operating conditions (of control voltage) The tests shall show the speed of contacts directly at various stages of operation, travel of contacts, opening time, closing time, shortest time between separation and meeting of contacts at make-break operation and dynamic contact resistance measurement (DCRM) etc. 1.10.4 The test reports for type tests and routine tests in respect of associated items such as spring charging motors, instruments, pressure switches, relays, terminal connectors, etc. as per the latest edition of the relevant IS shall be supplied by the bidder. All the routine test reports for all the breakers and for all the insulators utilized shall be submitted with inspection report. 1.10.5 All tests reports for acceptance / routine tests shall be submitted in spiral bound volume and got approved from the purchaser before dispatching the breaker. 1.11 SPARE PARTS: 1.11.1 Bidder shall submit list of spares recommended by him for satisfactory operation of the circuit breakers for first five years and rate for each spare shall also be quoted. The purchaser will decide the actual quantity of spare parts to be ordered on the basis of the prices of the spare parts, quoted by the bidder. 1.12 TECHNICAL & GUARANTEED PARTICULARS : The bidder shall furnish all guaranteed technical particulars as called for in section - IV of this specification. Particulars which are subject to guarantee shall be clearly stated offers not containing this information will not be considered. Deviation against any clause of this technical specification shall be clearly described separately. 1.13 INSTRUCTION MANUALS: 1.13.1 Three copies of operation, maintenance and erection manuals in English language shall be provided in each circuit breaker supplied. The manuals shall be bound volumes and shall contain all the drawings and instructions required for erection, operation and maintenance and in addition the following particulars:
  • 12. GETCO/E/06TS – CB/R3 May12 Page 12 of 26 a) Marked erection prints identifying the component parts of the circuit breakers and current transformers as dispatched with the assembly drawings. b) Details dimensions, assembly and description of all the components and catalogues for operation of the circuit breaker and accessories. c) List of recommended spare parts of circuit breaker.
  • 13. GETCO/E/06TS – CB/R3 May12 Page 13 of 26 TECHNICAL SPECIFICATION FOR 66 kV SF6 GAS CIRCUIT BREAKER SECTION – II TECHNICAL REQUIREMENTS 2.1 SCOPE: This section covers the specific technical requirements, climatic and Isoceraunic conditions and system particulars for which the circuit breakers shall be offered as per the General Technical Requirements given in Section-I of this specification and the schedule of requirements specified herein. 2.2 CLIMATIC & ISOKERAUNIC CONDITIONS: 2.2.1 The climatic conditions under which the breaker shall operate satisfactorily are as follows: a) Maximum ambient temperature of air in shade (0 C). : 500 C b) Minimum ambient temperature of air in shade (0 C). : 40 C c) Maximum daily average ambient temperature (0 C). : 400 C d) Maximum yearly average ambient temperature (0 C). : 300 C e) Maximum relative humidity (%). : 95 % f) Average number of thunderstorm days / annum. : 15 g) Average annual rainfall (Cm.) : 150 cm. h) Maximum wind pressure (Kg/m2) : 150 kg/M2 . i) Height above mean see level (m). : Not exceeding 1000 meters.
  • 14. GETCO/E/06TS – CB/R3 May12 Page 14 of 26 2.2.2 All breakers offered shall be suitable for continuous satisfactory operation at the full rated capacity under the above climatic conditions. 2.2.3 Since the sub-station may be near seashore or Industrial area, the breaker offered shall be suitable for heavily polluted atmosphere. 2.3 SYSTEM DETAILS: i) Nominal system voltage : 66 kV ii) Maximum rated voltage : 72.5 kV iii) Frequency : 50 Cycle / Second. iv) Number of phases : 3 v) Neutral Earthing : Solidly earthed. vi) Auxiliary power supply : 1) 240 Volts 1-φ & 415 Volts 3-φ, 50 Hz A.C., with the variation of frequency ± 5% and voltage + 10% & -15%. 2) 110 Volts or 220 Volts 2-wire D.C. supply subject to variations of ± 10%. 2.4 The circuit breakers shall be complete with following technical requirements. : 11) Number of Poles : 3 2) Basic Insulation level 1) 1.2/50 Microsecond impulse withstand voltage. 2) On Minute Power Frequency withstand voltage. : : 350 kVp 140 kV rms 3) Rated normal current : 1600 Amps. 3a) Rated symmetrical breaking capacity at highest system voltage. : 3000 MVA
  • 15. GETCO/E/06TS – CB/R3 May12 Page 15 of 26 4) Rated short circuit breaking capacity. : 31.5 kA rms 5) Rated duration of short circuit : 3 second. 6) Total break time for any current upto the rated breaking current. : 3 cycles 7) Closing time. : Not more than 10 cycles. 8) Rated characteristics for short line faults : As per IS: 13118 / IEC 62271. 9) Rated transient recovery voltage for terminal fault. : As per IS: 13118 / IEC 62271. 10) Rated line charging current breaking capacity. : 10 Amps. 11) Rated short circuit making current. : 78.75 kAp 12) Rated operating duty : O–0.3 S–CO–3 M–CO 13) Rated SF6 Gas pressure (AT 200 C). : 5 kg / Cm2 14) Total creepage distance for heavily polluted atmosphere. : 1810 mm min. 15) Live part to plinth level clearance in mm : 4000 mm 2.5 EARTH QUAKE & WIND DESIGN LOADS: Each circuit breaker including its supporting structure shall be designed to withstand required earthquake acceleration of 0.08 x 2 g and with wind loads of 150 Kg/m2 on the projected area (non- simultaneous) without damage to component parts and without impairment of operation.
  • 16. GETCO/E/06TS – CB/R3 May12 Page 16 of 26 TECHNICAL SPECIFICATION FOR 66 kV SF6 GAS CIRCUIT BREAKER SECTION – III GENERAL DESIGN OF 66 kV SF6 GAS CIRCUIT BREAKER 3.2 GENERAL DESIGN FEATURE OF SF6 BREAKER: 3.2.1 SF6 Gas Circuit breaker shall consist of three identical single phase units with common Spring operating mechanism suitable for specified duty. Separate SF6 Gas Cylinder along with suitable gas system, incorporating required gas stop valves, copper piping of suitable size shall be provided. Required pressure switches as stated in Cl. 1.4.8.2 shall be provided. Gas pressure gauge shall be fitted on the common feed pipe to monitor the pressure of SF6 gas in the interrupter. Absorbent shall also be provided in each interrupting unit to keep the SF6 gas dry & absorb the decomposed product of SF6 gas, formed during arcing. Bidder shall give complete constructional details for SF6 gas circuit breaker offered by them. The insulation level of porcelain of the circuit breaker shall be so coordinated with that of the breaker that flashover shall occur externally to the breaker. 3.2.2 In case of SF6 circuit breaker, it shall be possible to arrange for either automatic tripping of the circuit breaker or tripping of circuit breaker on fault and will be automatically locked when the pressure in the individual interrupter reaches below the limit value. Arrangements shall be made to prevent closing of the breaker due to leakage of gas passing through the closing valve without a positive impulse from the closing coil. 3.2.3 The SF6 gas used in the circuit Breaker shall comply in all respect with the provisions of the latest edition of relevant standard. 3.2.4 Inter Locks : 3.2.4(a) Pressure switches with the required pressure fitting must be incorporated to ensure safety of breaker operation when SF6 gas
  • 17. GETCO/E/06TS – CB/R3 May12 Page 17 of 26 pressure goes below the specified pressure range due to leakage, the trip coil circuit & closing coil circuit must be cut-off. The pressure switch shall generally be temperature compensated gas pressure switch having two micro-switches, operating at different pressures one for low pressure alarm and other for low pressure cutout. 3.2.4(b) Additional dedicated pressure switch with 4 poles for Normal, Low gas, Lockout, etc shall be provided for SCADA remote operations. L/R switch shall have spare contacts. 3.2.4(c) Limit switch for motors shall be provided with 4 NO and 4 NC contacts.
  • 18. GETCO/E/06TS – CB/R3 May12 Page 18 of 26 SECTION – IV SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR 66KV SF-6 GAS Spring operated CIRCUIT BREAKERS (TO BE FILLED IN & SIGNED BY THE BIDDER) SN PARTICULARS 1. Name of Manufacturer : 2. 2.a Type Designation of CB Type designation of Spring mechanism (as per Mech. Endu. test report) : : 3. Governing Standard : 4. Rated Voltage (KV) : 5. Maximum continuous rated service voltage (KV) : 6. Frequency (Hz) : 7. Whether outdoor breaker offered (Yes / No) : 8. Nominal current rating i) Under standard condition. (Amp) ii) Under site condition (Amp). iii) Type test reports submitted of (Amp) : : : 9. Short time current rating (kA) for 3 seconds : 10. Maximum temperature rise over ambient temp. due to rated current in main contacts measured after breaking test. (0 C) :
  • 19. GETCO/E/06TS – CB/R3 May12 Page 19 of 26 SN PARTICULARS 11. Rated short circuit breaking current a) Rated short circuit current (AC component) (KV rms). b) Percentage DC component c) Asymmetrical breaking current (including DC component (KA rms). d) Rated symmetrical breaking capacity in MVA FOR SF6 CB : : : 12. Making capacity (kA Peak) : 13. Total breaking time (Milli-seconds) : a) For interruption of 10% of the rated capacity. b) For interruption of 30% of the rated capacity. c) For interruption of 60% of rated capacity. d) For interruption of the full rated capacity. : : : : : 14. Arcing time ( milliseconds) : 15a b. c. Making time (milliseconds) Rated closing time (milliseconds) Rated opening time (milliseconds) : : : 16. Minimum reclosing time at rated interrupting capacity from the in fault of the trip coil energisation (Millisecond) :
  • 20. GETCO/E/06TS – CB/R3 May12 Page 20 of 26 SN PARTICULARS 17. A) Minimum dead time a) 3 phase reclosing (Milliseconds). b) Limit of adjustment of dead time for 3-phase reclosing. B) Whether restrike free and trip free. (IS / IEC applicable may be stated). : : : 18. Date on restriking voltage for 100%, 50% & 30% rated capacity a) Amplitude factor (max) b) Phase factor (max) c) Natural Frequency (Hz) d) Rate of rise of restriking voltage (V/Micro-Sec) (max) : : : : 19. Maximum interrupting capacity under phase opposition condition (MVA). : 20. Maximum line charging current breaking capacity without over voltage exceeding 2.5phase neutral voltage (Amps.) : 21. Maximum line charging current breaking capacity corresponding over-voltage recorded a) On supply side. b) On line side. : : 22. Maximum cable charging current breaking capacity & corresponding over- voltage recorded in test. a) On supply side. b) On line side. : : : 23. Maximum shunt capacitor Bank switching capacity (MVA) :
  • 21. GETCO/E/06TS – CB/R3 May12 Page 21 of 26 SN PARTICULARS 24. Maximum breaking capacity on kilometric fault (MVA) : 25. Maximum over-voltage on switching transformers on no load & the charging current. : 26. Dry 1 Minute power frequency test withstand voltage, for complete circuit breaker a) Between line & Grounded parts (kV rms) b) Between line with breaker contacts open (kV rms) : : 27. Wet 1-minute power frequency withstand voltage for complete circuit breaker a) Between line terminal & grounded parts (kV rms) b) Between terminals with breaker contacts open (kV rms) : : : 28. 1.2/50 Micro-second wave lightning impulse withstand test voltage for complete circuit breaker, as per type test report submitted. a) Between line terminal and ground (kV peak) b) Between terminal with circuit breaker contacts open (kV peak). : : : SUPPORTING INSULATORS : 29. Make & Type : 30. Insulation Class : 31. Visible Corona discharge voltage : 32. Wet 1-minute power frequency flashover voltage (kV rms). :
  • 22. GETCO/E/06TS – CB/R3 May12 Page 22 of 26 SN PARTICULARS 33. Dry 1-minute power frequency flashover voltage (kV rms) : 34. 1.2/50 micro-second impulse flashover voltage (kV peak) : 35. Total creepage distance for heavily polluted atmosphere : 36. Minimum clearance in air a) Between phases (mm) b) Live parts & earth (mm) c) Live parts to Plinth level (mm). : : : : 36.a 36.b Permissible safe cantilever loading on installed porcelain (kg.m) Permissible safe compressive strength of installed porcelain 37. No. of poles per circuit breaker : 38. Breaks per pole (Nos). : 39. Total length of breaks per phase (mm). : 40 Type of main contacts : 41. Material of main contacts : 42. Whether main contacts silver plates (Yes/No) : 43. Thickness of silver coating on main contacts (mm). : 44. Contact pressure on main contacts (Kg/M2). : 45. Type of arcing contacts : 46. Contact pressure on arcing contact (Kg/M2). : 47. Type of auxiliary switches :
  • 23. GETCO/E/06TS – CB/R3 May12 Page 23 of 26 SN PARTICULARS 48. Material of switch contacts : 49. Whether contacts silver plates (Yes/No.) : 50. No. of auxiliary switch contacts operating with all three poles of breaker a) Which are closed when breaker is closed. b) Which are open when breaker is closed : : 51A No. of spare auxiliary switch contacts operating a) Which are closed when breaker is closed. b) Which are open when breaker is closed. : B Details of SF6 Gas pressure switch and its setting for low pressure alarm and low pressure cut-out. : 52. No. of operations possible without maintenance a) At full rated interrupting capacity. b) At 50% of rated interrupted capacity c) At 100% of rated current d) At 50% of rated current : : : : : 53. Details of foundation :
  • 24. GETCO/E/06TS – CB/R3 May12 Page 24 of 26 SN PARTICULARS 54. Type of operating mechanism (motor operated spring charged). a) Opening b) Closing c) Control voltage aux. : : : : 54a Details of spring charging motor i) Type ii) Rated supply voltage iii) Wattage iv) Max time for charging spring : 55. Tripping & closing circuit voltage (V). (110 V/220 V.) As per requirement. : 56. Power required for trip coil (in watts). : 57. Power required for closing coil (in watts). : 58. Weight of 3-φ breaker complete with operating mechanism, supporting, insulators, frame work etc. : 59. Impact loading for foundation design to include dead load plug impact value on opening it maximum interrupting rating in terms of equivalent static load. : 60. Weight of heaviest package (Kgs) space requirements (Length, Width, Height). :
  • 25. GETCO/E/06TS – CB/R3 May12 Page 25 of 26 SN PARTICULARS 61. A) Details of Gas pressure switch and its setting for low pressure alarm and low pressure cut-out. : : 62 SF6 GAS DETAILS: a) Rated SF6 Gas pressure (temperature 200 C) (Kg/cm2 ) b) IS / Equivalent standard applicable for SF6 Gas. c) Quantity in each pole d) Total quantity e) Spare gas quantity (%) : : : 63 Terminal connector (Bimetallic compression type) : 64 Seismic level (g) : __________________ _________________________ SEAL OF THE FIRM SIGNATURE OF TENDERER
  • 26. GETCO/E/06TS – CB/R3 May12 Page 26 of 26 SECTION – V List of documents attached with technical bid: Bidder shall invariably attach the following documents and clearly marked and duly flagged in technical bid. In absence of these documents offer will be evaluated as a non submission. Sr. No. Particulars of document Whether attached the with technical bid 1 Drawings in AutoCAD format 2 Drawings hard copies as indicated in specification 3 Manual in PDF format 4 QAP for manufacturing process in SOFT format 5 QAP for manufacturing process in Hard format 6 FQP in SOFT format 7 FQP in Hard copy 8 Type test Reports in hard copies a for breaker b for clamps & connectors 9 Confirmation regarding type tests as per clause no. 1.10(a) page no. 10 – “IMPORTANT NOTE” 10 Guaranteed Technical Particulars, completely filled in 11 Any other essential documents SIGNATURE OF BIDDER COMPANY’S ROUND SEAL DATE: PLACE: