ArresterWorks
1/23/2013 r1 9/16
Jonathan Woodworth
ArresterFacts 032
The Sheath Voltage Limiter
Copyright 2013 ArresterWorks ArresterFacts 032 January 2013 2
(SVL), as discussed herein, is to protect the outer
jacket of the cable from electrical stresses caused
during transient events.
High voltage cable comes in many forms; however,
for sake of keeping it simple, we will discuss single
core HV cable with a metallic sheath and a
polymeric sheath jacket, as shown in Figure 1.
HV Cable System Overview
There are many positive factors fueling the
installation of underground cable, but there is a
negative environmental effect that needs special
attention when installing this type of system,
namely losses. Because cable is often installed
with metallic sheaths, current is induced onto the
sheath from the primary conductor. This induced
sheath current flows directly to earth and is a
100% loss. In the process of flowing to earth, it
also can raise the temperature of the cable, which
becomes a limiting factor in the overload capability
of the system. A common means of reducing the
losses in a cable system is to segment the cable
sheath as shown in Figure 2. When segmentation
is used to interrupt the flow of induced sheath
current, accommodations need to be made to limit
the induced voltage on the sheath during transient
Figure 1: Simple HV cable showing polymeric jacket that is in
some cases requires surge protection.
Introduction
High voltage cable for underground transmission
has been in use for many years; however, in the
past decade the demand for longer lines and
higher current capacity have increased which in
turn has required new methods of loss prevention.
Reliability of these lines is more important now
than ever, as the customers become more
intolerant of outages. This means that surge
protection of the underground cables is
increasingly more important. All of these factors
lead to the growing use of surge arresters on cable
systems. The surge protection scheme for a high
voltage cable sheath is unique in the surge
protection world, as you will see from this article.
The main purpose of the sheath voltage limiter
Figure 2: Common loss reduction method in cable systems using segmentation and Sheath Voltage Limiters
The Sheath Voltage Limiter
Copyright 2013 ArresterWorks ArresterFacts 032 January 2013 3
events. If the sheath voltage is not limited, the
Figure 3 Typical configuration of SVL on Riser Pole
voltage difference between the sheath and earth
can exceed the withstand voltage of the cable
jacket. If the cable jacket is punctured due to
excessive voltage across it, it can become a source
of moisture ingress into the cable, which can only
lead to longer term dielectric and failure issues.
There are numerous configurations used in cable
systems to reduce losses such as cross bonding of
the sheaths and transpositioning of phase
conductors. However, segmentation is considered
the most effective but requires surge protection of
the cable jacket when it is implemented. The link
box is a universally used junction box that
accommodates surge protectors and a point to
crossbond sheaths. This box is usually sealed and
found in manholes or cabinets. Figure 4 shows a
common link box setup that provides a location for
the sheath voltage limiters as well as cross bonding
of the sheath. The phase conductors do not enter
link boxes; only the sheath or sheath extension.
Figure 4: Link box with 3 SVL’s and cross bonded sheaths
The SVL
A sheath voltage limiter (SVL) is a surge arrester
with a different name. It functions as an arrester
and in most cases; it is in fact a re-labeled
distribution arrester. Two examples of sheath
voltage limiters are shown in Figures 5 and 6. In
Figure 5, it can be seen that the arrester has no
sheds. This is because this particular design can
only be used in the dry environment of a link box.
The SVL shown in Figure 6 has sheds similar to an
arrester because this model is designed for
outdoor use.
Figure 5: Sheath Voltage Limiter with typical ratings .8-4.8kV
Uc (MCOV) used inside link boxes. (Courtesy of Tridelta)
The Sheath Voltage Limiter
Copyright 2013 ArresterWorks ArresterFacts 032 January 2013 4
Figure 6: Sheath Voltage Limiter with typical ratings 4-14kV
Uc (MCOV) for use in outdoor environment. (Courtesy of
Tridelta)
Selecting an SVL
As stated in the introduction to this article, the
purpose of a sheath voltage limiter is to clamp or
limit the voltage stress across the cable jacket. If
the cable sheath is grounded at both ends, the
voltage stress across the jacket is quite low during
steady state and relatively low during transients;
however, if the cable is segmented to reduce
losses or there are link boxes along the cable at
transposition/cross bonding locations, it is
important to install the SVL at these locations to
eliminate any possibility of insulation breakdown
of the cable jacket or link box insulation. There is
no standard method prescribed by IEC or IEEEE for
selecting the optimum rating for cable
sheath/jacket protection. The following method is
one used by this author after discussion with cable
suppliers, arrester suppliers, and with the aid of
transient modeling of the systems to actually
determine the effects of a surge during transients.
Figure 7: Steps that can be used to determine the rating of an
SVL
This analysis assumes sheath segmentation with is
a single point bond (earthed at one end of the
sheath) and an open point at the other end of the
sheath.
Sheath Voltage from Power Frequency Sources
Because the sheath of a cable is in such close
proximity to the conductor, the voltage appearing
on an open sheath can be substantial. This
induced voltage is directly related to the current
flowing through the phase conductor. This
relationship applies during steady state and during
faults. Figure 8 displays an example where a 17kA
fault results in 3800V rms on the sheath. The most
common rationale in selecting an arrester for
protecting the sheath is to select an SVL with a
turn-on level above the worst case induced power
frequency voltage. This means the SVL does not
need to dissipate any energy during a temporary
overvoltage (TOV) caused by faults. For overhead
arresters, this is generally not the rule and in those
cases, the arresters are sized to conduct current
during the TOV but not enough to cause it to fail.
The overhead sizing rationale utilizing an arrester’s
TOV capability is not used for SVL selection unless
it is necessary to achieve a better margin of
protection.
Steps to Select the Optimum Sheath Voltage Limiter
Step 1: Determine the voltages that will appear on the
sheath during transient events
Step 2: Select AC Rating and TOV Rating
Step 3: Check Margin of Protection of the Selected Rating
Step 4: Check that the Energy Rating of the SVL is adequate
Step 5: Check mounting and failure mode for fit and
function
The Sheath Voltage Limiter
Copyright 2013 ArresterWorks ArresterFacts 032 January 2013 5
Sheath Voltage Calculations
The steady state voltage gradient is the voltage
that will appear along a 1km length of a sheath
with 1000 amps flowing continuously. This voltage
is a function of the configuration of the cable in the
trench and the cable dimensions. There are two
basic trench configurations: trefoil and flat. The
trefoil configuration is comprised of three cables
that are positions equal distance apart such that
the cross section forms a equilateral triangle. If
the flat configuration is used, all cables are laid
such that they are in the same plane and the same
distant apart. If the voltage gradient is not
supplied by the cable manufacturer for the
configuration to be used, it can be calculated as
follows. These equations and method are derived
from charts found in IEEE 575 “Guide for Bonding
Sheaths and Shields of Single-Conductor Power
Cables Rated 5 – 500 kV”:
Once the voltage gradient is known for 1 km at
1000 amps, the voltage that will appear at the
open end of a segment during a fault event can be
easily calculated. It is important to know this
voltage level because the SVL voltage rating (Uc)
needs to be set just above this level so that the
arrester does not conduct during a fault event. If
the arrester conducted during a fault event, it
would need a much higher energy handling
capability than generally available for distribution
type arresters. If it is later found in the sizing
process that a lower level Uc is needed, a transient
analysis will likely be needed to determine the Uc
and energy rating of the SVL.
Figure 8: Example of sheath voltage during a 27kA fault on a trefoil configured cable
Figure 8 17kA fault resulting in 3800 Volts on Sheath
The Sheath Voltage Limiter
Copyright 2013 ArresterWorks ArresterFacts 032 January 2013 6
Assuming that the margin of protection will be
adequate, then the Uc (MCOV) rating of the SVL
will be greater than or equal to the voltage at the
open point (Eopen).
Uc ≥ Eopen = Voltage Gradient x segment length
x max expected fault current
Where: Voltage gradient is V/km/1000A
Length is in km
Fault current is in kA
Using the above method, if a voltage gradient on a
particular system is 200v/km/kA and a line is 2 km
long with a potential of 17.5kA, then the minimum
acceptable Uc rating for the SVL would be 7000
volts.
Note that if the line was only 1 km long, the
minimum Uc for the SVL would be half that of the
2 km long line and could be 3500V minimum.
Figure 9 shows the current flow through an
appropriately rated SVL on a 1 km line with the
previously mentioned voltage gradient and fault
current. It can be seen that only micro-amps flow
through the SVL, which is exactly what is desired;
Figure 9: Current conduction through properly sized SVL
Figure 10: Current through improperly sized SVL with peak levels in the 600amp range per half cycle
Figure 11: Temperature rise of an improperly sized SVL showing eminent failure if the breaker does not interrupt the fault
immediately
The Sheath Voltage Limiter
Copyright 2013 ArresterWorks ArresterFacts 032 January 2013 7
however if the same SVL is applied to a similar line
but is 2 km long, the current through the SVL is
significant, as shown in Figure 10, and the
immediate temperature rise to failure is shown in
Figure 11. Therefore, when sizing SVL Uc ratings,
one cannot choose one rating for all link boxes
unless the lengths of all the segments are the
same. If the SVL is chosen correctly in this manner,
it will not be required to absorb any significant
level of energy during a fault on the system.
Protecting the Jacket from Switching Surge
The jacket and the sheath interrupts are the
weakest insulation in a HV Power Cable system.
Figure 12 shows the withstand levels of the jacket
and sheath interrupt per IEEE 575.
Typical BIL withstand of Sheath
Interrupt and Jacket
kV peak (1.2x50 us wave)
System
kV
Across
Halves
Each Half
to Ground
Jacket
69-138 60 30 30
161-240 80 40 40
345-500 120 60 60
Figure 12: Lightning Impulse withstand of sheath interrupts
and cable jacket.
The switching surge impulse withstand of the
sheath interrupt and the jacket are assumed to be
similar to other insulator types and are 83% of the
lightning impulse withstand rating (BIL).
When there is a switching surge event on the
phase conductor of a cable, the current through
the phase conductor induces a voltage on the
sheath in the same way it does at steady state and
fault events, even though the wave shape is
significantly different. Since the voltage and
current on the phase conductor during a switching
surge is not sinusoidal or even a simple impulse
(see Figure 13), it is not possible to accurately
predict the resulting voltage and current on the
sheath.
The only way to accurately determine the actual
voltage and current on the sheath is though
transient simulations of real life tests. Since real
world tests are not practical, transient simulations
are the only real option. After running many of
these simulations, a few rules of thumb have
surfaced:
1. If the SVL is selected to ride through a fault
event with minimal to no serious
conduction, then the switching surge
energy withstand capability of a 10kA
rated distribution type arrester is
adequate. If the SVL is not dimensioned to
Figure 13: Switching Surge on Phase Conductor of a 345kV cable with (green) and without (red) arrester protection on the phase
The Sheath Voltage Limiter
Copyright 2013 ArresterWorks ArresterFacts 032 January 2013 8
ride through the fault, then station type
arresters may need to be used.
2. If the 1000 amp switching surge residual
voltage is not available, then the 1.5kA
8/20 lightning impulse residual voltage can
be used for the margin of protection
calculation.
In the case study used to create Figure 14, the
switching surge voltage on the sheath without SVL
protection would rise to greater than 100kV. Per
Figure 12, this is more than 40kV above what the
jacket or interrupt insulation can withstand,
representing certain failure of the cable jacket. In
this case, with a 9.6kV Uc SVL, the voltage on the
sheath is limited to 33kV maximum.
To calculate the margin of protection during a
switching surge, it is recommended that the 1000A
switching surge residual voltage be used. Since
switching surge residual voltage is not a mandated
test for distribution type arresters, the 1000A
residual voltage may not be available. If it is not
available, a reasonable substitute for the switching
surge voltage is the 8x20 residual voltage at 1.5kA.
For the 9.6kV SVL used in the above study, the
V1000 = 1000A 30/75us residual voltage is 28.4kV.
From Figure 12, we can see that the BIL withstand
level of the jacket for a 345kV line is 60kV. This
means the switching surge margin of protection
(MP2) for this case is: MP2 = ( [( BIL x .83 ) / V1000
]-1) x 100 = 75%
Protecting the Jacket from Lightning Surge
When lightning strikes the overhead line before
the transition pole, the surge is clamped by the
arrester that is universally mounted at that
location. Most of the surge current is diverted to
earth at this pole; however, a surge voltage of
significant magnitude can travel into the cable with
a moderate level of current also entering the
cable. Figure 15 shows the voltage and current
entering a 345kV cable with a 100kA strike a few
spans away.
Calculating margin of protection (MP1) for
lightning is very similar to what is done for
switching surges. In this case, 10kA is used for the
coordinating current and the full BIL is used for the
withstand of the jacket and interrupt insulation.
Using the same SVL as above for the switching
surge calculation, the residual voltage at 10kA is
35kV and cable BIL is 60kV, therefore: MP1 = ( [
BIL / V1000 ]-1) x 100 = 71% Again, a 9.6kV Uc
SVL provides adequate insulation protection for
the cable jacket.
Figure 14: Switching surge voltage
inducted on to Sheath of a 345kV
Cable with and without SVL
protection.
 3pu switching surge on phase
conductor.
 Green w/o SVL and Red with SVL.
Figure 15: Shows the voltage and current on the phase conductor of a 345kV cable with a 100kA surge to the phase a few
spans away from the transition pole
The Sheath Voltage Limiter
Copyright 2013 ArresterWorks ArresterFacts 032 January 2013 9
ArresterFacts are a compilation of facts about arresters to assist all stakeholders in the application and
understanding of arresters. All ArresterFacts assume a base knowledge of surge protection of power systems;
however, we always welcome the opportunity to assist a student in obtaining their goal, so please call if you
have any questions. Visit our library of ArresterFacts for more reading on topics of interest to those involved
in the protection of power system at: http://www.arresterworks.com/arresterfacts/arresterfacts.php
About the author:
Jonathan started his career after receiving his Bachelor's degree in Electronic Engineering from The Ohio Institute of
Technology, at Fermi National Accelerator Laboratory in Batavia, IL. As an Engineering Physicist at Fermi Lab, he was an
integral member of the high energy particle physics team in search of the elusive quark. Wishing to
return to his home state, he joined the design engineering team at McGraw Edison (later Cooper
Power Systems) in Olean, New York. During his tenure at Cooper, he was involved in the design,
development, and manufacturing of arresters. He served as Engineering Manager as well as Arrester
Marketing Manager during that time. Jonathan has been active for the last 30 years in the IEEE and
IEC standard associations. Jonathan is inventor/co-inventor on five US patents. Jonathan received his
MBA from St. Bonaventure University.
www.arresterworks.com
jonathan.woodworth@arresterworks.com
+1.716.307.2431
Jonathan Woodworth
ArresterWorks
Principle Engineer

More Related Content

What's hot

Abb+ +presentacion+descagadores+de+sobre+tension+-+bolivia+-+mayo+2013
Abb+ +presentacion+descagadores+de+sobre+tension+-+bolivia+-+mayo+2013Abb+ +presentacion+descagadores+de+sobre+tension+-+bolivia+-+mayo+2013
Abb+ +presentacion+descagadores+de+sobre+tension+-+bolivia+-+mayo+2013Manuel Pochet
 
Sesion 2 - Curso de FORMACION en Cables de Energia para Media y Alta Tension
Sesion 2 - Curso de FORMACION en Cables de Energia para Media y Alta TensionSesion 2 - Curso de FORMACION en Cables de Energia para Media y Alta Tension
Sesion 2 - Curso de FORMACION en Cables de Energia para Media y Alta Tensionfernando nuño
 
IMPLEMENTATION OF LONG AC HV AND EHV CABLE SYSTEMS
IMPLEMENTATION OF LONG AC HV AND EHV CABLE SYSTEMSIMPLEMENTATION OF LONG AC HV AND EHV CABLE SYSTEMS
IMPLEMENTATION OF LONG AC HV AND EHV CABLE SYSTEMSPower System Operation
 
Circuit breaker, Types of circuit breaker & different CB related questions
Circuit breaker, Types of circuit breaker & different CB related questionsCircuit breaker, Types of circuit breaker & different CB related questions
Circuit breaker, Types of circuit breaker & different CB related questionsUrooj Abid
 
17th Edition Part 5 1
17th  Edition  Part 5 117th  Edition  Part 5 1
17th Edition Part 5 1Paul Holden
 
Installation & maintenance of power cable
Installation & maintenance of power cableInstallation & maintenance of power cable
Installation & maintenance of power cableAmbuj Mishra
 
3. protecciones eléctricas y criterios de ajuste ETAP
3. protecciones eléctricas y criterios de ajuste ETAP3. protecciones eléctricas y criterios de ajuste ETAP
3. protecciones eléctricas y criterios de ajuste ETAPHimmelstern
 
Surge arrester ppt
Surge arrester pptSurge arrester ppt
Surge arrester pptIrinElsa
 
11kV 33kV Heat Shrink Terminations - Outdoor Armour Earthing Kits XLPE AWA Si...
11kV 33kV Heat Shrink Terminations - Outdoor Armour Earthing Kits XLPE AWA Si...11kV 33kV Heat Shrink Terminations - Outdoor Armour Earthing Kits XLPE AWA Si...
11kV 33kV Heat Shrink Terminations - Outdoor Armour Earthing Kits XLPE AWA Si...Thorne & Derrick International
 
Guide for the operation of self contained fluid filled cable systems
Guide for the operation of self contained fluid filled cable systemsGuide for the operation of self contained fluid filled cable systems
Guide for the operation of self contained fluid filled cable systemsPower System Operation
 

What's hot (20)

Circuit breakers
Circuit breakers Circuit breakers
Circuit breakers
 
Abb+ +presentacion+descagadores+de+sobre+tension+-+bolivia+-+mayo+2013
Abb+ +presentacion+descagadores+de+sobre+tension+-+bolivia+-+mayo+2013Abb+ +presentacion+descagadores+de+sobre+tension+-+bolivia+-+mayo+2013
Abb+ +presentacion+descagadores+de+sobre+tension+-+bolivia+-+mayo+2013
 
Sesion 2 - Curso de FORMACION en Cables de Energia para Media y Alta Tension
Sesion 2 - Curso de FORMACION en Cables de Energia para Media y Alta TensionSesion 2 - Curso de FORMACION en Cables de Energia para Media y Alta Tension
Sesion 2 - Curso de FORMACION en Cables de Energia para Media y Alta Tension
 
IMPLEMENTATION OF LONG AC HV AND EHV CABLE SYSTEMS
IMPLEMENTATION OF LONG AC HV AND EHV CABLE SYSTEMSIMPLEMENTATION OF LONG AC HV AND EHV CABLE SYSTEMS
IMPLEMENTATION OF LONG AC HV AND EHV CABLE SYSTEMS
 
Power cables
Power cablesPower cables
Power cables
 
Copper for Busbars
Copper for BusbarsCopper for Busbars
Copper for Busbars
 
Circuit breaker, Types of circuit breaker & different CB related questions
Circuit breaker, Types of circuit breaker & different CB related questionsCircuit breaker, Types of circuit breaker & different CB related questions
Circuit breaker, Types of circuit breaker & different CB related questions
 
Mcb Breaker
Mcb Breaker Mcb Breaker
Mcb Breaker
 
17th Edition Part 5 1
17th  Edition  Part 5 117th  Edition  Part 5 1
17th Edition Part 5 1
 
Dog Conductor
Dog ConductorDog Conductor
Dog Conductor
 
Conexiones cross bonding
Conexiones cross bondingConexiones cross bonding
Conexiones cross bonding
 
HV Substation Earthing Guide - Central Networks
HV Substation Earthing Guide - Central NetworksHV Substation Earthing Guide - Central Networks
HV Substation Earthing Guide - Central Networks
 
Installation & maintenance of power cable
Installation & maintenance of power cableInstallation & maintenance of power cable
Installation & maintenance of power cable
 
Empalmes Electricos
Empalmes ElectricosEmpalmes Electricos
Empalmes Electricos
 
3. protecciones eléctricas y criterios de ajuste ETAP
3. protecciones eléctricas y criterios de ajuste ETAP3. protecciones eléctricas y criterios de ajuste ETAP
3. protecciones eléctricas y criterios de ajuste ETAP
 
Surge arrester ppt
Surge arrester pptSurge arrester ppt
Surge arrester ppt
 
11kV 33kV Heat Shrink Terminations - Outdoor Armour Earthing Kits XLPE AWA Si...
11kV 33kV Heat Shrink Terminations - Outdoor Armour Earthing Kits XLPE AWA Si...11kV 33kV Heat Shrink Terminations - Outdoor Armour Earthing Kits XLPE AWA Si...
11kV 33kV Heat Shrink Terminations - Outdoor Armour Earthing Kits XLPE AWA Si...
 
Lightning arrester
Lightning arresterLightning arrester
Lightning arrester
 
Cable and laying
Cable and layingCable and laying
Cable and laying
 
Guide for the operation of self contained fluid filled cable systems
Guide for the operation of self contained fluid filled cable systemsGuide for the operation of self contained fluid filled cable systems
Guide for the operation of self contained fluid filled cable systems
 

Viewers also liked

Modeling and analysis of power transformers under ferroresonance phenomenon
Modeling and analysis of power transformers under ferroresonance phenomenonModeling and analysis of power transformers under ferroresonance phenomenon
Modeling and analysis of power transformers under ferroresonance phenomenonGilberto Mejía
 
00 programa de la asignatura
00 programa de la asignatura00 programa de la asignatura
00 programa de la asignaturaGilberto Mejía
 
Modelacion de redes aereas
Modelacion de redes aereasModelacion de redes aereas
Modelacion de redes aereasGilberto Mejía
 
Seminario de investigación
Seminario de investigaciónSeminario de investigación
Seminario de investigaciónleonardo cardona
 
Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...
Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...
Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...Gilberto Mejía
 
Tutorial de instalacion del programa atp draw pdf
Tutorial de instalacion del programa atp draw pdfTutorial de instalacion del programa atp draw pdf
Tutorial de instalacion del programa atp draw pdfGilberto Mejía
 
3 4-energizacion-de-condensadores
3 4-energizacion-de-condensadores3 4-energizacion-de-condensadores
3 4-energizacion-de-condensadoresGilberto Mejía
 
Estudio de seleccion de ruta de la linea
Estudio de seleccion de ruta de la lineaEstudio de seleccion de ruta de la linea
Estudio de seleccion de ruta de la lineaGilberto Mejía
 
Cyme equipment reference manual
Cyme equipment reference manualCyme equipment reference manual
Cyme equipment reference manualGilberto Mejía
 
Bentley substation administrator v8i trn016050 1-0001 ge-energy_05-jun-2012
Bentley substation administrator v8i trn016050 1-0001 ge-energy_05-jun-2012Bentley substation administrator v8i trn016050 1-0001 ge-energy_05-jun-2012
Bentley substation administrator v8i trn016050 1-0001 ge-energy_05-jun-2012Gilberto Mejía
 
Transitorios electromagneticos por maniobras
Transitorios electromagneticos por maniobrasTransitorios electromagneticos por maniobras
Transitorios electromagneticos por maniobrasGilberto Mejía
 
Atp AtpDraw Guia Basica de uso
Atp AtpDraw Guia Basica de usoAtp AtpDraw Guia Basica de uso
Atp AtpDraw Guia Basica de usoGilberto Mejía
 
Bentley substation civil instruction manual-v2.3
Bentley substation civil instruction manual-v2.3Bentley substation civil instruction manual-v2.3
Bentley substation civil instruction manual-v2.3Gilberto Mejía
 
Transformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching TransientsTransformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching Transientsmichaeljmack
 
Atp, ATPDraw libro, alternative transientrs program
Atp, ATPDraw libro, alternative transientrs programAtp, ATPDraw libro, alternative transientrs program
Atp, ATPDraw libro, alternative transientrs programGilberto Mejía
 
Conductor size considerations_for_station_class_arresters
Conductor size considerations_for_station_class_arrestersConductor size considerations_for_station_class_arresters
Conductor size considerations_for_station_class_arrestersGilberto Mejía
 
Transients in-power-systems-wiley
Transients in-power-systems-wileyTransients in-power-systems-wiley
Transients in-power-systems-wileyGilberto Mejía
 

Viewers also liked (20)

Modeling and analysis of power transformers under ferroresonance phenomenon
Modeling and analysis of power transformers under ferroresonance phenomenonModeling and analysis of power transformers under ferroresonance phenomenon
Modeling and analysis of power transformers under ferroresonance phenomenon
 
00 programa de la asignatura
00 programa de la asignatura00 programa de la asignatura
00 programa de la asignatura
 
Modelacion de redes aereas
Modelacion de redes aereasModelacion de redes aereas
Modelacion de redes aereas
 
Seminario de investigación
Seminario de investigaciónSeminario de investigación
Seminario de investigación
 
5220 l11
5220 l115220 l11
5220 l11
 
Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...
Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...
Swartley b santinia_maled_jaccinob-destructive-arcong-of-insulated-joints-in-...
 
Capitulo 6.1
Capitulo 6.1Capitulo 6.1
Capitulo 6.1
 
7839 10179-1-pb
7839 10179-1-pb7839 10179-1-pb
7839 10179-1-pb
 
Tutorial de instalacion del programa atp draw pdf
Tutorial de instalacion del programa atp draw pdfTutorial de instalacion del programa atp draw pdf
Tutorial de instalacion del programa atp draw pdf
 
3 4-energizacion-de-condensadores
3 4-energizacion-de-condensadores3 4-energizacion-de-condensadores
3 4-energizacion-de-condensadores
 
Estudio de seleccion de ruta de la linea
Estudio de seleccion de ruta de la lineaEstudio de seleccion de ruta de la linea
Estudio de seleccion de ruta de la linea
 
Cyme equipment reference manual
Cyme equipment reference manualCyme equipment reference manual
Cyme equipment reference manual
 
Bentley substation administrator v8i trn016050 1-0001 ge-energy_05-jun-2012
Bentley substation administrator v8i trn016050 1-0001 ge-energy_05-jun-2012Bentley substation administrator v8i trn016050 1-0001 ge-energy_05-jun-2012
Bentley substation administrator v8i trn016050 1-0001 ge-energy_05-jun-2012
 
Transitorios electromagneticos por maniobras
Transitorios electromagneticos por maniobrasTransitorios electromagneticos por maniobras
Transitorios electromagneticos por maniobras
 
Atp AtpDraw Guia Basica de uso
Atp AtpDraw Guia Basica de usoAtp AtpDraw Guia Basica de uso
Atp AtpDraw Guia Basica de uso
 
Bentley substation civil instruction manual-v2.3
Bentley substation civil instruction manual-v2.3Bentley substation civil instruction manual-v2.3
Bentley substation civil instruction manual-v2.3
 
Transformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching TransientsTransformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching Transients
 
Atp, ATPDraw libro, alternative transientrs program
Atp, ATPDraw libro, alternative transientrs programAtp, ATPDraw libro, alternative transientrs program
Atp, ATPDraw libro, alternative transientrs program
 
Conductor size considerations_for_station_class_arresters
Conductor size considerations_for_station_class_arrestersConductor size considerations_for_station_class_arresters
Conductor size considerations_for_station_class_arresters
 
Transients in-power-systems-wiley
Transients in-power-systems-wileyTransients in-power-systems-wiley
Transients in-power-systems-wiley
 

Similar to The sheath voltage_limiter

Application data explusion links
Application data explusion linksApplication data explusion links
Application data explusion linksing_eliali4748
 
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINECOMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINEIRJET Journal
 
Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...
Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...
Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...IJERA Editor
 
Electrostatic stress analysis of high voltage cables
Electrostatic stress analysis of high voltage cablesElectrostatic stress analysis of high voltage cables
Electrostatic stress analysis of high voltage cableseSAT Publishing House
 
IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...
IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...
IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...IRJET Journal
 
Short-Circuit calculation -Ppt-Slides - Copy.ppt
Short-Circuit calculation -Ppt-Slides - Copy.pptShort-Circuit calculation -Ppt-Slides - Copy.ppt
Short-Circuit calculation -Ppt-Slides - Copy.pptJatmylHarnero1
 
Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...IOSR Journals
 
Capacitance and Cable Testing
Capacitance and Cable TestingCapacitance and Cable Testing
Capacitance and Cable TestingHussein Kassem
 
Review of Reduction of Leakage Current in Cascaded Multilevel Inverter
Review of Reduction of Leakage Current in Cascaded Multilevel InverterReview of Reduction of Leakage Current in Cascaded Multilevel Inverter
Review of Reduction of Leakage Current in Cascaded Multilevel InverterIJRST Journal
 
Analsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substationsAnalsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substationseSAT Journals
 
Analsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substationsAnalsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substationseSAT Publishing House
 
A vocational summer training at Jindal Steel and Power Limited
A vocational summer training at Jindal Steel and Power LimitedA vocational summer training at Jindal Steel and Power Limited
A vocational summer training at Jindal Steel and Power LimitedKishan Gabel
 
Experiments manual
Experiments manual Experiments manual
Experiments manual Ramesh Meti
 
Schneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersSchneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersThorne & Derrick International
 
Electrical properties of insulating materials under VLF voltage
Electrical properties of insulating materials under VLF voltageElectrical properties of insulating materials under VLF voltage
Electrical properties of insulating materials under VLF voltagePower System Operation
 

Similar to The sheath voltage_limiter (20)

2009 fusing-tutorial-rev1
2009 fusing-tutorial-rev12009 fusing-tutorial-rev1
2009 fusing-tutorial-rev1
 
Gss report
Gss reportGss report
Gss report
 
Application data explusion links
Application data explusion linksApplication data explusion links
Application data explusion links
 
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINECOMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
 
Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...
Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...
Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...
 
Electrostatic stress analysis of high voltage cables
Electrostatic stress analysis of high voltage cablesElectrostatic stress analysis of high voltage cables
Electrostatic stress analysis of high voltage cables
 
IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...
IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...
IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...
 
B011120723
B011120723B011120723
B011120723
 
Cable sizing.pptx
Cable sizing.pptxCable sizing.pptx
Cable sizing.pptx
 
Short-Circuit calculation -Ppt-Slides - Copy.ppt
Short-Circuit calculation -Ppt-Slides - Copy.pptShort-Circuit calculation -Ppt-Slides - Copy.ppt
Short-Circuit calculation -Ppt-Slides - Copy.ppt
 
Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...
 
Capacitance and Cable Testing
Capacitance and Cable TestingCapacitance and Cable Testing
Capacitance and Cable Testing
 
Review of Reduction of Leakage Current in Cascaded Multilevel Inverter
Review of Reduction of Leakage Current in Cascaded Multilevel InverterReview of Reduction of Leakage Current in Cascaded Multilevel Inverter
Review of Reduction of Leakage Current in Cascaded Multilevel Inverter
 
Analsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substationsAnalsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substations
 
Analsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substationsAnalsis of very fast transient over voltages in gas insulated substations
Analsis of very fast transient over voltages in gas insulated substations
 
Ce31533536
Ce31533536Ce31533536
Ce31533536
 
A vocational summer training at Jindal Steel and Power Limited
A vocational summer training at Jindal Steel and Power LimitedA vocational summer training at Jindal Steel and Power Limited
A vocational summer training at Jindal Steel and Power Limited
 
Experiments manual
Experiments manual Experiments manual
Experiments manual
 
Schneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersSchneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment Designers
 
Electrical properties of insulating materials under VLF voltage
Electrical properties of insulating materials under VLF voltageElectrical properties of insulating materials under VLF voltage
Electrical properties of insulating materials under VLF voltage
 

More from Gilberto Mejía

Analisis de-falla-sistema-de-transmision-26-enero-2011
Analisis de-falla-sistema-de-transmision-26-enero-2011Analisis de-falla-sistema-de-transmision-26-enero-2011
Analisis de-falla-sistema-de-transmision-26-enero-2011Gilberto Mejía
 
Guía de prácticas fenómenos transitorios electromagnéticos
Guía de prácticas fenómenos transitorios electromagnéticosGuía de prácticas fenómenos transitorios electromagnéticos
Guía de prácticas fenómenos transitorios electromagnéticosGilberto Mejía
 
2. operacion de sistemas de transmision de 500k v rep
2. operacion de sistemas de transmision de 500k v rep2. operacion de sistemas de transmision de 500k v rep
2. operacion de sistemas de transmision de 500k v repGilberto Mejía
 
Transients in-power-systems
Transients in-power-systemsTransients in-power-systems
Transients in-power-systemsGilberto Mejía
 
Taller evaluacion descargas_ atmosfericas
Taller evaluacion descargas_ atmosfericasTaller evaluacion descargas_ atmosfericas
Taller evaluacion descargas_ atmosfericasGilberto Mejía
 
Resumen de teoria de atp
Resumen de teoria de atpResumen de teoria de atp
Resumen de teoria de atpGilberto Mejía
 
Aislamiento lineas transmision_energia
Aislamiento lineas transmision_energiaAislamiento lineas transmision_energia
Aislamiento lineas transmision_energiaGilberto Mejía
 
Mitsubishi - substation insulation coordination studies-sparacino
Mitsubishi - substation insulation coordination studies-sparacinoMitsubishi - substation insulation coordination studies-sparacino
Mitsubishi - substation insulation coordination studies-sparacinoGilberto Mejía
 
Libro coordinación aislamiento unal
Libro coordinación aislamiento unalLibro coordinación aislamiento unal
Libro coordinación aislamiento unalGilberto Mejía
 
Taller entregable calculo_parametros_2013_01
Taller entregable calculo_parametros_2013_01Taller entregable calculo_parametros_2013_01
Taller entregable calculo_parametros_2013_01Gilberto Mejía
 
Lightning protection for overhead distribution lines
Lightning protection for overhead distribution linesLightning protection for overhead distribution lines
Lightning protection for overhead distribution linesGilberto Mejía
 
Le.h insulation coordination - Digsilent
Le.h insulation coordination - DigsilentLe.h insulation coordination - Digsilent
Le.h insulation coordination - DigsilentGilberto Mejía
 
Guia trabajo seleccion de ruta
Guia trabajo seleccion de rutaGuia trabajo seleccion de ruta
Guia trabajo seleccion de rutaGilberto Mejía
 

More from Gilberto Mejía (14)

Analisis de-falla-sistema-de-transmision-26-enero-2011
Analisis de-falla-sistema-de-transmision-26-enero-2011Analisis de-falla-sistema-de-transmision-26-enero-2011
Analisis de-falla-sistema-de-transmision-26-enero-2011
 
Guía de prácticas fenómenos transitorios electromagnéticos
Guía de prácticas fenómenos transitorios electromagnéticosGuía de prácticas fenómenos transitorios electromagnéticos
Guía de prácticas fenómenos transitorios electromagnéticos
 
2. operacion de sistemas de transmision de 500k v rep
2. operacion de sistemas de transmision de 500k v rep2. operacion de sistemas de transmision de 500k v rep
2. operacion de sistemas de transmision de 500k v rep
 
Atp draw-tutorial
Atp draw-tutorialAtp draw-tutorial
Atp draw-tutorial
 
Transients in-power-systems
Transients in-power-systemsTransients in-power-systems
Transients in-power-systems
 
Taller evaluacion descargas_ atmosfericas
Taller evaluacion descargas_ atmosfericasTaller evaluacion descargas_ atmosfericas
Taller evaluacion descargas_ atmosfericas
 
Resumen de teoria de atp
Resumen de teoria de atpResumen de teoria de atp
Resumen de teoria de atp
 
Aislamiento lineas transmision_energia
Aislamiento lineas transmision_energiaAislamiento lineas transmision_energia
Aislamiento lineas transmision_energia
 
Mitsubishi - substation insulation coordination studies-sparacino
Mitsubishi - substation insulation coordination studies-sparacinoMitsubishi - substation insulation coordination studies-sparacino
Mitsubishi - substation insulation coordination studies-sparacino
 
Libro coordinación aislamiento unal
Libro coordinación aislamiento unalLibro coordinación aislamiento unal
Libro coordinación aislamiento unal
 
Taller entregable calculo_parametros_2013_01
Taller entregable calculo_parametros_2013_01Taller entregable calculo_parametros_2013_01
Taller entregable calculo_parametros_2013_01
 
Lightning protection for overhead distribution lines
Lightning protection for overhead distribution linesLightning protection for overhead distribution lines
Lightning protection for overhead distribution lines
 
Le.h insulation coordination - Digsilent
Le.h insulation coordination - DigsilentLe.h insulation coordination - Digsilent
Le.h insulation coordination - Digsilent
 
Guia trabajo seleccion de ruta
Guia trabajo seleccion de rutaGuia trabajo seleccion de ruta
Guia trabajo seleccion de ruta
 

Recently uploaded

GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girlsssuser7cb4ff
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
microprocessor 8085 and its interfacing
microprocessor 8085  and its interfacingmicroprocessor 8085  and its interfacing
microprocessor 8085 and its interfacingjaychoudhary37
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxvipinkmenon1
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 

Recently uploaded (20)

young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girls
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
microprocessor 8085 and its interfacing
microprocessor 8085  and its interfacingmicroprocessor 8085  and its interfacing
microprocessor 8085 and its interfacing
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptx
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 

The sheath voltage_limiter

  • 1. ArresterWorks 1/23/2013 r1 9/16 Jonathan Woodworth ArresterFacts 032
  • 2. The Sheath Voltage Limiter Copyright 2013 ArresterWorks ArresterFacts 032 January 2013 2 (SVL), as discussed herein, is to protect the outer jacket of the cable from electrical stresses caused during transient events. High voltage cable comes in many forms; however, for sake of keeping it simple, we will discuss single core HV cable with a metallic sheath and a polymeric sheath jacket, as shown in Figure 1. HV Cable System Overview There are many positive factors fueling the installation of underground cable, but there is a negative environmental effect that needs special attention when installing this type of system, namely losses. Because cable is often installed with metallic sheaths, current is induced onto the sheath from the primary conductor. This induced sheath current flows directly to earth and is a 100% loss. In the process of flowing to earth, it also can raise the temperature of the cable, which becomes a limiting factor in the overload capability of the system. A common means of reducing the losses in a cable system is to segment the cable sheath as shown in Figure 2. When segmentation is used to interrupt the flow of induced sheath current, accommodations need to be made to limit the induced voltage on the sheath during transient Figure 1: Simple HV cable showing polymeric jacket that is in some cases requires surge protection. Introduction High voltage cable for underground transmission has been in use for many years; however, in the past decade the demand for longer lines and higher current capacity have increased which in turn has required new methods of loss prevention. Reliability of these lines is more important now than ever, as the customers become more intolerant of outages. This means that surge protection of the underground cables is increasingly more important. All of these factors lead to the growing use of surge arresters on cable systems. The surge protection scheme for a high voltage cable sheath is unique in the surge protection world, as you will see from this article. The main purpose of the sheath voltage limiter Figure 2: Common loss reduction method in cable systems using segmentation and Sheath Voltage Limiters
  • 3. The Sheath Voltage Limiter Copyright 2013 ArresterWorks ArresterFacts 032 January 2013 3 events. If the sheath voltage is not limited, the Figure 3 Typical configuration of SVL on Riser Pole voltage difference between the sheath and earth can exceed the withstand voltage of the cable jacket. If the cable jacket is punctured due to excessive voltage across it, it can become a source of moisture ingress into the cable, which can only lead to longer term dielectric and failure issues. There are numerous configurations used in cable systems to reduce losses such as cross bonding of the sheaths and transpositioning of phase conductors. However, segmentation is considered the most effective but requires surge protection of the cable jacket when it is implemented. The link box is a universally used junction box that accommodates surge protectors and a point to crossbond sheaths. This box is usually sealed and found in manholes or cabinets. Figure 4 shows a common link box setup that provides a location for the sheath voltage limiters as well as cross bonding of the sheath. The phase conductors do not enter link boxes; only the sheath or sheath extension. Figure 4: Link box with 3 SVL’s and cross bonded sheaths The SVL A sheath voltage limiter (SVL) is a surge arrester with a different name. It functions as an arrester and in most cases; it is in fact a re-labeled distribution arrester. Two examples of sheath voltage limiters are shown in Figures 5 and 6. In Figure 5, it can be seen that the arrester has no sheds. This is because this particular design can only be used in the dry environment of a link box. The SVL shown in Figure 6 has sheds similar to an arrester because this model is designed for outdoor use. Figure 5: Sheath Voltage Limiter with typical ratings .8-4.8kV Uc (MCOV) used inside link boxes. (Courtesy of Tridelta)
  • 4. The Sheath Voltage Limiter Copyright 2013 ArresterWorks ArresterFacts 032 January 2013 4 Figure 6: Sheath Voltage Limiter with typical ratings 4-14kV Uc (MCOV) for use in outdoor environment. (Courtesy of Tridelta) Selecting an SVL As stated in the introduction to this article, the purpose of a sheath voltage limiter is to clamp or limit the voltage stress across the cable jacket. If the cable sheath is grounded at both ends, the voltage stress across the jacket is quite low during steady state and relatively low during transients; however, if the cable is segmented to reduce losses or there are link boxes along the cable at transposition/cross bonding locations, it is important to install the SVL at these locations to eliminate any possibility of insulation breakdown of the cable jacket or link box insulation. There is no standard method prescribed by IEC or IEEEE for selecting the optimum rating for cable sheath/jacket protection. The following method is one used by this author after discussion with cable suppliers, arrester suppliers, and with the aid of transient modeling of the systems to actually determine the effects of a surge during transients. Figure 7: Steps that can be used to determine the rating of an SVL This analysis assumes sheath segmentation with is a single point bond (earthed at one end of the sheath) and an open point at the other end of the sheath. Sheath Voltage from Power Frequency Sources Because the sheath of a cable is in such close proximity to the conductor, the voltage appearing on an open sheath can be substantial. This induced voltage is directly related to the current flowing through the phase conductor. This relationship applies during steady state and during faults. Figure 8 displays an example where a 17kA fault results in 3800V rms on the sheath. The most common rationale in selecting an arrester for protecting the sheath is to select an SVL with a turn-on level above the worst case induced power frequency voltage. This means the SVL does not need to dissipate any energy during a temporary overvoltage (TOV) caused by faults. For overhead arresters, this is generally not the rule and in those cases, the arresters are sized to conduct current during the TOV but not enough to cause it to fail. The overhead sizing rationale utilizing an arrester’s TOV capability is not used for SVL selection unless it is necessary to achieve a better margin of protection. Steps to Select the Optimum Sheath Voltage Limiter Step 1: Determine the voltages that will appear on the sheath during transient events Step 2: Select AC Rating and TOV Rating Step 3: Check Margin of Protection of the Selected Rating Step 4: Check that the Energy Rating of the SVL is adequate Step 5: Check mounting and failure mode for fit and function
  • 5. The Sheath Voltage Limiter Copyright 2013 ArresterWorks ArresterFacts 032 January 2013 5 Sheath Voltage Calculations The steady state voltage gradient is the voltage that will appear along a 1km length of a sheath with 1000 amps flowing continuously. This voltage is a function of the configuration of the cable in the trench and the cable dimensions. There are two basic trench configurations: trefoil and flat. The trefoil configuration is comprised of three cables that are positions equal distance apart such that the cross section forms a equilateral triangle. If the flat configuration is used, all cables are laid such that they are in the same plane and the same distant apart. If the voltage gradient is not supplied by the cable manufacturer for the configuration to be used, it can be calculated as follows. These equations and method are derived from charts found in IEEE 575 “Guide for Bonding Sheaths and Shields of Single-Conductor Power Cables Rated 5 – 500 kV”: Once the voltage gradient is known for 1 km at 1000 amps, the voltage that will appear at the open end of a segment during a fault event can be easily calculated. It is important to know this voltage level because the SVL voltage rating (Uc) needs to be set just above this level so that the arrester does not conduct during a fault event. If the arrester conducted during a fault event, it would need a much higher energy handling capability than generally available for distribution type arresters. If it is later found in the sizing process that a lower level Uc is needed, a transient analysis will likely be needed to determine the Uc and energy rating of the SVL. Figure 8: Example of sheath voltage during a 27kA fault on a trefoil configured cable Figure 8 17kA fault resulting in 3800 Volts on Sheath
  • 6. The Sheath Voltage Limiter Copyright 2013 ArresterWorks ArresterFacts 032 January 2013 6 Assuming that the margin of protection will be adequate, then the Uc (MCOV) rating of the SVL will be greater than or equal to the voltage at the open point (Eopen). Uc ≥ Eopen = Voltage Gradient x segment length x max expected fault current Where: Voltage gradient is V/km/1000A Length is in km Fault current is in kA Using the above method, if a voltage gradient on a particular system is 200v/km/kA and a line is 2 km long with a potential of 17.5kA, then the minimum acceptable Uc rating for the SVL would be 7000 volts. Note that if the line was only 1 km long, the minimum Uc for the SVL would be half that of the 2 km long line and could be 3500V minimum. Figure 9 shows the current flow through an appropriately rated SVL on a 1 km line with the previously mentioned voltage gradient and fault current. It can be seen that only micro-amps flow through the SVL, which is exactly what is desired; Figure 9: Current conduction through properly sized SVL Figure 10: Current through improperly sized SVL with peak levels in the 600amp range per half cycle Figure 11: Temperature rise of an improperly sized SVL showing eminent failure if the breaker does not interrupt the fault immediately
  • 7. The Sheath Voltage Limiter Copyright 2013 ArresterWorks ArresterFacts 032 January 2013 7 however if the same SVL is applied to a similar line but is 2 km long, the current through the SVL is significant, as shown in Figure 10, and the immediate temperature rise to failure is shown in Figure 11. Therefore, when sizing SVL Uc ratings, one cannot choose one rating for all link boxes unless the lengths of all the segments are the same. If the SVL is chosen correctly in this manner, it will not be required to absorb any significant level of energy during a fault on the system. Protecting the Jacket from Switching Surge The jacket and the sheath interrupts are the weakest insulation in a HV Power Cable system. Figure 12 shows the withstand levels of the jacket and sheath interrupt per IEEE 575. Typical BIL withstand of Sheath Interrupt and Jacket kV peak (1.2x50 us wave) System kV Across Halves Each Half to Ground Jacket 69-138 60 30 30 161-240 80 40 40 345-500 120 60 60 Figure 12: Lightning Impulse withstand of sheath interrupts and cable jacket. The switching surge impulse withstand of the sheath interrupt and the jacket are assumed to be similar to other insulator types and are 83% of the lightning impulse withstand rating (BIL). When there is a switching surge event on the phase conductor of a cable, the current through the phase conductor induces a voltage on the sheath in the same way it does at steady state and fault events, even though the wave shape is significantly different. Since the voltage and current on the phase conductor during a switching surge is not sinusoidal or even a simple impulse (see Figure 13), it is not possible to accurately predict the resulting voltage and current on the sheath. The only way to accurately determine the actual voltage and current on the sheath is though transient simulations of real life tests. Since real world tests are not practical, transient simulations are the only real option. After running many of these simulations, a few rules of thumb have surfaced: 1. If the SVL is selected to ride through a fault event with minimal to no serious conduction, then the switching surge energy withstand capability of a 10kA rated distribution type arrester is adequate. If the SVL is not dimensioned to Figure 13: Switching Surge on Phase Conductor of a 345kV cable with (green) and without (red) arrester protection on the phase
  • 8. The Sheath Voltage Limiter Copyright 2013 ArresterWorks ArresterFacts 032 January 2013 8 ride through the fault, then station type arresters may need to be used. 2. If the 1000 amp switching surge residual voltage is not available, then the 1.5kA 8/20 lightning impulse residual voltage can be used for the margin of protection calculation. In the case study used to create Figure 14, the switching surge voltage on the sheath without SVL protection would rise to greater than 100kV. Per Figure 12, this is more than 40kV above what the jacket or interrupt insulation can withstand, representing certain failure of the cable jacket. In this case, with a 9.6kV Uc SVL, the voltage on the sheath is limited to 33kV maximum. To calculate the margin of protection during a switching surge, it is recommended that the 1000A switching surge residual voltage be used. Since switching surge residual voltage is not a mandated test for distribution type arresters, the 1000A residual voltage may not be available. If it is not available, a reasonable substitute for the switching surge voltage is the 8x20 residual voltage at 1.5kA. For the 9.6kV SVL used in the above study, the V1000 = 1000A 30/75us residual voltage is 28.4kV. From Figure 12, we can see that the BIL withstand level of the jacket for a 345kV line is 60kV. This means the switching surge margin of protection (MP2) for this case is: MP2 = ( [( BIL x .83 ) / V1000 ]-1) x 100 = 75% Protecting the Jacket from Lightning Surge When lightning strikes the overhead line before the transition pole, the surge is clamped by the arrester that is universally mounted at that location. Most of the surge current is diverted to earth at this pole; however, a surge voltage of significant magnitude can travel into the cable with a moderate level of current also entering the cable. Figure 15 shows the voltage and current entering a 345kV cable with a 100kA strike a few spans away. Calculating margin of protection (MP1) for lightning is very similar to what is done for switching surges. In this case, 10kA is used for the coordinating current and the full BIL is used for the withstand of the jacket and interrupt insulation. Using the same SVL as above for the switching surge calculation, the residual voltage at 10kA is 35kV and cable BIL is 60kV, therefore: MP1 = ( [ BIL / V1000 ]-1) x 100 = 71% Again, a 9.6kV Uc SVL provides adequate insulation protection for the cable jacket. Figure 14: Switching surge voltage inducted on to Sheath of a 345kV Cable with and without SVL protection.  3pu switching surge on phase conductor.  Green w/o SVL and Red with SVL. Figure 15: Shows the voltage and current on the phase conductor of a 345kV cable with a 100kA surge to the phase a few spans away from the transition pole
  • 9. The Sheath Voltage Limiter Copyright 2013 ArresterWorks ArresterFacts 032 January 2013 9 ArresterFacts are a compilation of facts about arresters to assist all stakeholders in the application and understanding of arresters. All ArresterFacts assume a base knowledge of surge protection of power systems; however, we always welcome the opportunity to assist a student in obtaining their goal, so please call if you have any questions. Visit our library of ArresterFacts for more reading on topics of interest to those involved in the protection of power system at: http://www.arresterworks.com/arresterfacts/arresterfacts.php About the author: Jonathan started his career after receiving his Bachelor's degree in Electronic Engineering from The Ohio Institute of Technology, at Fermi National Accelerator Laboratory in Batavia, IL. As an Engineering Physicist at Fermi Lab, he was an integral member of the high energy particle physics team in search of the elusive quark. Wishing to return to his home state, he joined the design engineering team at McGraw Edison (later Cooper Power Systems) in Olean, New York. During his tenure at Cooper, he was involved in the design, development, and manufacturing of arresters. He served as Engineering Manager as well as Arrester Marketing Manager during that time. Jonathan has been active for the last 30 years in the IEEE and IEC standard associations. Jonathan is inventor/co-inventor on five US patents. Jonathan received his MBA from St. Bonaventure University. www.arresterworks.com jonathan.woodworth@arresterworks.com +1.716.307.2431 Jonathan Woodworth ArresterWorks Principle Engineer