SlideShare a Scribd company logo
1 of 6
Download to read offline
	 Some practical examples and experiences from
the use of VLF for AC breakdown and diagnostic
testing are summarized in chapter 4.
Theoretical background	
Permittivity and dielectric loss
At AC voltage, the resulting dielectric loss is usually
deduced by considering a parallel plate capacitor with
a complex permittivity . The resulting
dielectric loss factor tanδ is the sum of contributions
from both dielectric polarization and losses due to
conductivity σ :
tanδ = tanδ1
(1)
Figure 1 - Permittivity and dissipation factor versus frequency
and temperature
This means that electrical conduction may become
the dominant loss mechanism at very low frequencies.
The applied voltage magnitude and particularly
the temperature of the insulation may therefore
strongly affect the dielectric loss at VLF voltages.
On the other hand, the time constant of the dielectric
relaxation mechanisms will become lower at •••
Introduction
Very low frequency (VLF) AC voltage testing in the
frequency range from 0.01 to 1 Hz is increasingly
being used for both high voltage (Hi-Pot) acceptance
and condition assessment of installed large
capacitance power components [IEEE standards,
IEC standard, etc.].
The main advantage of such tests is the low amount
of reactive power needed compared to testing at
power frequency. Today, equipment for VLF after-
laying tests are becoming available at voltages up
to 400 kV. In addition, diagnostic parameters as
for example partial discharge activity and dielectric
losses, are regularly measured using VLF voltages.
Scope and outline of the work
The main purpose of WG D1.48 was to review the
present knowledge regarding the effects of VLF
voltage testing on electrical properties and ageing
mechanisms of high voltage insulation systems,
aiming at facilitating development of methods and
useful evaluation criteria for both acceptance and
maintenance VLF-tests.
The Technical Brochure consists of three main parts.
	 The theoretical part in chapter 2 gives an overview
of how permittivity, dielectric loss and electric field
distribution within insulation systems is expected
to vary with the frequency of the applied voltage
in the range from DC to AC power frequencies.
It presents the general principles of dielectric loss
and partial discharge measurements, as well as
mechanisms of ageing and initiation of electric
breakdown.
	 Chapter 3 describes the different ways of
generating VLF test voltages and the methods
available for both withstand and diagnostic testing.
Members
E. ILDSTAD, Convenor (NO), F. MAUSETH, Secretary (NO), M. BAUR (AT),
T. BLACKBURN (AU), J. BLENNOW (SE), J. CASTELLON (FR), A. CAVALLINI (IT),
J. HOLBØLL (DK), N. HOZUMI (JP), H. MAYER (AU), P. MOHAUPT (AT),
F. PETZOLD (DE), C. SUMEREDER (AT)
Electrical properties of insulating
materials under VLF voltage
751WG D1.48
technical brochure
No. 302 - February 2019 ELECTRA	 93
sufficiently low, causing local heating and melting of
the surrounding polymer.
The most important defects limiting the breakdown
strength of practical high voltage insulation systems
comprises cavities, particle inclusions, interface
irregularities, sharp edges at the electrode, etc.
The overall question addressed in this report is how
the physical and chemical erosion and degradation
process leading to tree initiation and subsequently
electrical breakdown is affected by VLF testing.
Electrical treeing
In case of electric tree formation, it is important to
consider the voltage or the electric field distribution
along the tree structure. As a first approximation, we
will here consider a simplified RC-model, presented
in Fig. 3. In this model, the tree channel is considered
a cylinder with radius r and a total channel resistance
of R, connected in series with the capacitance C of
the non-treed insulation section. In a real electric
tree, surface deposits of carbon determine the value
of this resistance, and its value is expected to reduce
as function of time due to partial discharge activity
and material degradation.
Figure 3 - Simplified RC-Model for a propagating electrical tree,
considered as a resistive tree channel in series with a capacitive
non-treed insulation between the tree tip and the ground electrode
Due to the thin tree channel it is a good approximation
to consider the capacitance C of the non-treed
insulation to be independent of the non-treed
insulation distance [2]. In the case of a channel with
a tip radius of 2 µm, the value of the capacitance
becomes C = 4.9∙10-4
pF. 	 •••
Figure 4 - Ratio of voltage across the tree channel, versus total tree
channel resistance R at 50, 10 and 0.1 Hz [3]
higher temperatures, shifting the maximum losses
towards a higher frequency, as illustrated in Fig. 1.
Partial discharge activity
At low frequencies, the electric field distribution within
an insulation system becomes more determined by
the conductivity of the materials, and the classic
capacitive abc-model needs to be modified. The first
approximate approach is to add insulation resistances
in parallel with the capacitances, as shown in Fig. 2.
Figure 2 - Extended abc-equivalent circuit for modelling
of partial discharges [1]
Due to the insulation conductivity σ, it is expected
that the number of PD pulses per voltage period will
be reduced at VLF-testing below a certain frequency.
As a rule of thumb, the applied voltage frequency
should be approximately higher than
(2)
where σ is the highest conductivity of the insulation
system.
In case of n equal partial discharges occurring per
half period, the power dissipated by the discharges
increase proportional with frequency
(3)
where qa is the apparent partial discharge magnitude,
Ui is the effective applied ac voltage at PD inception
and f is the voltage frequency. Thus, PD activity is
expected to result in a rate of degradation proportional
to the frequency of the applied voltage.
Ageing and electric breakdown of
polymers
In most cases, electric breakdown in polymers is
a progressive, cumulative process involving the
initiation and growth of tiny tubular channels forming
electrical trees during dry service conditions. In case
of ageing in wet environments, water trees grows
due to the combined effect of water condensation
and electric field. Electrical breakdown finally occurs
when the resistance of the tree structure becomes
751WG D1.48
technical brochure
No. 302 - February 2019 ELECTRA	 95
mechanical strength of the polymer will enhance
formation water filled tree shaped structures,
particularly following the amorphous regions of the
polymer. Due to the high electric conductivity of such
channels compared to the surrounding non-treed
insulation, high dielectric loss values is expected in
case of low frequency testing, particularly if water
trees bridge the insulation wall.
Short term VLF testing is of these reasons expected
not to enhance the formation of water trees.
Methods of generating VLF test
voltages
The report briefly gives an overview of the principle
of the four most common VLF test techniques
currently available, addressing limitations and future
possibilities.
Amplitude modulated VLF voltage
Here, a conventional high voltage transformer, fed
by a motor driven regulating transformer is used
to generate an amplitude modulated AC voltage.
The rectifiers connected to the high voltage side
are switched on at selected moments to create a
sinusoidal VLF voltage.
However, the motor-driven regulating transformer
limits the application to low power and low voltage.
Controlled DC charging and discharging
This principle is based upon combining high-voltage
transformers and two HVDC Greinacher cascades.
A sinusoidal VLF output voltage is obtained using a
complex control algorithm for the power module, DC
units and the discharge elements. The advantage of
this method is that there are no mechanically operated
parts. Choosing a sufficiently high frequency for the
power module, the dimensions and weight of the
transformers and cascades will be reduced. However,
due to the high complexity of the discharge elements
and the control algorithm, this concept cannot easily
be scaled to higher voltage levels.
Differential Resonance Technology (DRT)
This method exploits the property of both resonance
and superposition of two voltages at slightly different
high frequency adding to form a low frequency
voltage at the desired beat frequency. The beat
frequency oscillation consists of the carrier frequency
in the range of 1 kHz, whose amplitude is modulated
by the desired test frequency of, e.g., 0.1 Hz or
higher. Therein, a resonant circuit tuned to the carrier
frequency allows for the simple generation of the •••
The graph presented in Fig. 4 shows that the effect
of reducing the frequency, is that more of the applied
voltage will be across the non-treed insulation and
less stress along the tree structure. Thus, at lower
frequencies, the degree of branching will be reduced
compared to that at higher frequencies. Result
from laboratory experiments, presented in Fig. 5,
verify this expected frequency dependent shape of
electrical trees.
	
	 a) Bush shaped electrical	 b) Branch / filament type of	
	 tree at 50 Hz,10kV	 tree at 0.1 Hz,14kV
Figure 5 - Typical electrical trees formed from needle tips in XLPE
at 50 and 0.1 Hz voltage[3]
At 50 Hz, rounded-off bush type-shaped trees were
formed, while more filament type of trees were
formed at 0.1 Hz.
Water treeing
Water trees are caused by the synergic effect of
humidity and electric stress. They typically grow very
slowly in the direction of the electric field and in wet
service conditions it may take 10-15 years to bridge
the insulation of a 12 kV XLPE. Examples of typical
water trees are shown in Fig. 6.
	 a) Vented- and 	 b) bow-tie trees 	
Figure 6 - Typical Water trees formed in XLPE cables
during service stress at 50 Hz
Water trees are not associated with partial discharges
or emission of light during its initiation and growth.
At 50 Hz AC voltage water trees have, however,
been found to grow in all known polymeric insulation
at electric field stresses down to about 1 kV/mm.
While it has not been possible to detect water trees
formation in case of DC voltage application.
From a theoretical point of view, it is common to
explain formation of water trees by the combined and
slow action of condensation of water and Maxwell
forces acting on enclosed water droplets within the
insulation. Any chemical reactions reducing the
751WG D1.48
technical brochure
No. 302 - February 2019 ELECTRA	 97
insulation, space charge measurements showed
that the exponential space charge accumulation at
the interfaces followed a time constant of about 2.5
days. This is in good agreement with Eq. (2) using
the average conductivity for the layered insulation.
This strongly indicates that no major electric field
distortions is expected within XLPE cable insulation
during VLF 0.1 Hz testing.
In case of testing cable systems with accessories,
it is important to consider the conductivity of field
grading materials, particularly in case of dielectric
loss and PD measurements.
Dielectric losses
Resultsfrommeasurementsoflowfrequencydielectric
loss of XLPE cable samples have demonstrated that
conduction becomes the dominant loss mechanisms
at temperatures above approximately 50 °C [5].
In case of aged cable samples, the dissipation factor
at 0.1 Hz was, as illustrated in Figure 8, found to
increase significantly with the applied test voltage
[6]. A non-linearity strongly indicating water tree
degradation.
Some condition assessment criteria for service aged
XLPE cables are summarized in [7].
Partial discharges
PD diagnostic at VLF tests is still a challenging task
due to noise interference from the switching devices
within the VLF test sets, particularly at the highest
system voltages requiring higher sensitivity.
As an example, Figure 9 shows typical results from
laboratory PD measurements using test voltage in
the frequency range of 0.01 – 100 Hz and samples
of polycarbonate containing cavities [8]. The results
reveal a reduced number of partial discharges per
period when reducing the frequency. An effect •••
necessary high voltages. By changing the modulation
frequency, VLF voltages at several hundred kV can
be generated in the frequency range from 0.1 Hz up
to 10 Hz.
Cosine-rectangular VLF technology
This type of generator is based upon power electronic
switching or bipolar charging, using built-in positive
and negative HVDC sources, resulting in a square
shaped VLF output voltage.
The significant and most important property of the
cosine-rectangular VLF technology is, however, the
shape of the power recovery during polarity reversal. It
is common to aim at a slope close to that at a frequency
of 50 Hz. Thus, the field stress during polarity reversal
is comparable that at operating frequency.
Selected results from VLF testing
The brochure reviews some practical experience
from VLF testing, mainly from applications on XLPE
cable systems and electrical machines.
Interface charging and electric field
distribution
At low frequencies, the electric field distribution is
expected to be affected by the conductivity of the
insulation, according to Eq. (2). Results summarized
in Fig. 7 indicate that space charge accumulation
in XLPE cable insulations increases at frequencies
below 0.02 Hz [4].
In addition to frequency and duration of voltage
application, different combinations of electrode
materials (e.g. semi-conductor) are important
factors determining the space charge injection and
distribution under AC electric stress.
In case of applying DC voltage to layered XLPE
Figure 7 - Relationship between frequency of the applied electrical
stress and space charge build-up in the bulk of XLPE at room
temperature [4]
Figure 8 - Measured dissipation factors at 0.1 Hz versus test voltage
in kV applied to different type of service aged XLPE cables [6]
751WG D1.48
technical brochure
No. 302 - February 2019 ELECTRA	 99
It is important to relate the expected endurance at
0.1 Hz voltage testing to that at 50-60 Hz service
stress, considering similar type of defects. A
comprehensive comparison of such breakdown
values are summarized in Fig. 11 [10]. The results
show that in most cases breakdown at VLF (0.1
Hz) testing occur at voltage levels 1-4 times higher
than that at 50 Hz AC voltage. Voids are particularly
difficult to detect.
As shown in Fig. 12, there is a strong correlation
between breakdown at power frequency AC and VLF
voltages [11]. On average, the 0.1 Hz VLF breakdown
values of water treed cables are found to be about
two times higher than breakdown values at 50 Hz AC.
Figure 12 - AC 50 Hz (lower red) and VLF 0.1 Hz
(upper blue) breakdown voltages of water tree
degraded cable samples as a function of non-treed
insulation thickness. Filled and unfilled symbols
represents results from service and laboratory aged
cables, respectively [11].	 •••
which was explained using the model of Fig. 2
including charge decay after a discharge.
In most cases, small differences are found between
PD inception voltage, PD magnitudes and the phase-
resolved PD patterns measured at 0.1 Hz and 50 Hz.
In case of testing 12 kV service-aged XLPE cable
samples with cold-shrink joints, a clear frequency
dependence was , however, observed [9]. The results
presented in Fig. 10 show that at frequencies below
0.2 Hz both the PD inception and extinction voltages
were found to be below the service stress at 50 Hz.
This indicates a frequency dependent electric field
distribution within the joints, making it challenging
to correlate PD results obtained at VLF to that at
operating frequency.
Electric breakdown under VLF testing
By electric withstand testing, it is in general possible
to only locate the weakest sites. It can however give
an indication to whether the test object is in good or
bad condition.
Figure 9 - Total number of PDs per voltage cycle and right; average
PD magnitude for insulated cavities [8]
Figure 10 - PD inception (PDIV) and extinction (PDEV) voltage
for a cold-shrink 12 kV cable joint as a function of frequency [9].
Closed Void
Conductive
Protrusion
Insulating
Contaminant
XLPE
Insulation
Conductive
Contaminant
Conductive
Contaminant
Conductive
Contaminant
Insulating
Contaminant
Cut in Cable
Insulation Insufficient
Compression of I/F
Water
droplet
Rubber-
XLPE
Interface
DC
VLF
OSW
Rubber-
XLPE
Interface
Figure 11 - Ratio of breakdown value obtained at different type of
test voltage relative to AC voltage for several types of defects in
cables and accessories [10]
Figure 12 - AC 50 Hz (lower red) and VLF 0.1 Hz (upper blue)
breakdown voltages of water tree degraded cable samples as
a function of non-treed insulation thickness. Filled and unfilled
symbols represents results from service and laboratory aged cables,
respectively [11]
751WG D1.48
technical brochure
No. 302 - February 2019 ELECTRA	 101
shows that electric breakdown of XLPE cables
occur at voltage levels 1-4 times higher than that
at 50 Hz AC voltage. Voids are particularly difficult
to detect by VLF withstand voltage testing. In case
of water tree-degraded cables, the breakdown
at VLF voltage varies from 50 to 200% of that at
power frequency.
References
[1]	 P. K. Olsen, F. Mauseth, and E. Ildstad, “The effect of DC
superimposed AC voltage on partial discharges in dielectric
bounded cavities”, presented at the 2014 International
Conference on High Voltage Engineering and Application
(ICHVE), 2014
[2]	J. Lekner, “Capacitance coefficients of two spheres”,
Electrostat., vol. 69, pp. 11-14, 2011.
[3]	 E.Ildstad, K. Fauskanger and J. Holto, “Electrical Treeing
from Needle Implants in XLPE during Very Low Frequency
(VLF) Voltage Testing” IEEE ICSD, Bologna, Italy, June
2013.
[4]	 X. Wang, N. Yoshimura, Y. Tanaka, K. Murata, and T. Takada,
“Space charge characteristics in cross-linking polyethylene
under electrical stress from DC to power frequency”, J. Phys.
D: Appl. Phys. , vol. 31, pp. 2057-2064, 1998.
[5]	 C. Dang and S. Pelissou, “Some technical consideration
on very low frequency cable diagnostic”, presented at the
Transmission and Distribution Conference and Exposition,
2003.
[6]	J. C. Hernández-Mejía, R. Harley, N. Hampton, and R.
Hartlein, “Characterization of Ageing for MV Power Cables
Using Low Frequency Tan d Diagnostic Measurements”,
IEEE Trans. Diel. and El. Insul., pp. 862-870, 2009.
[7]	IEEE Guide for Field Testing of Shielded Power Cable
Systems Using Very Low Frequency (less than 1 Hz), 2013.
[8]	C. Forssén and H. Edin, “Partial discharges in a cavity
at variable applied frequency part 2: measurements and
modeling”, IEEE Trans. Diel. and El. Insul., vol. 15, no. 6, pp.
1610-1616, 2008.
[9]	 F. Mauseth, H. Tollefsen, and S. Hvidsten, “Effect of Test
Voltage Frequency on PD Inception on Service Aged Cable
Joint”, presented at the IEEE Int. Conf. on High Voltage Eng.,
Poznan, Poland, 2014.
[10]	K. Uchida, H. Tanaka, and K. Hirotsu, “Study on Detection
for the Defects of XLPE Cable Lines”, IEEE Trans. on Power
Delivery, vol. 11, no. 2, pp. 663-668, 1996.
[11]	K. Uchida, M. Nakade, D. Inoue, H. Sakakibara, and M. Yagi,
“Life Estimation of Water Tree Deteriorated XLPE Cables
by VLF(Very Low Frequency) Voltage Withstand Test”,
presented at the PES T&D 2002, 2002.	 
Conclusions
The data collected by the literature survey is
discussed with respect to known practical experience
and theoretical considerations. The main purpose of
addressing the physical mechanisms of space charge
formation and degradation has been to provide a
base for evaluation of possibilities and limitations
regarding application of VLF tests, both as high
voltage acceptance/after laying tests and diagnostic
tools. It is concluded that:
	 In case of VLF (0,1 Hz) testing of high voltage
insulation systems, the risk of space charge
accumulation is very low, and the electric
field distribution becomes similar to that at
power frequency, provided the conductivity of
the insulating materials is lower than about:
σ < 1·10-16
Ω-1
m-1
.
	 During VLF testing of installed cable systems it is
important to address the electric field distribution
within the accessories, as it may become
frequency-dependent, due to higher and non-linear
conductivity of field grading materials compared to
that of the insulation.
	At VLF voltages, the rate of electrical treeing
and gradual degradation is reduced compared to
that at power frequency. Mainly due to the lower
number of Partial discharges per time unit and
reduced voltage drop across voids and electrical
tree channels. More knowledge is, however,
needed to improve comparison and interpretation
of results from partial discharge measurements at
VLF test voltages with that at service stresses.
	 For condition assessment of insulation systems,
low frequency measurements of permittivity and
dielectric loss factors is a useful diagnostic tool -
revealing critical changes in conductivity and other
material parameters. For example, VLF testing
of severely water tree degraded XLPE cables is
indicated by high and increased value of dielectric
loss with increasing test voltage.
	 Experience from VLF (0.1 Hz) breakdown testing
BROCHURE N° 751
(en anglais seulement)
(in English only)
Disponible sur / Available on:
www.e-cigre.org
Prix non-Membres / Non-Member Price:
90 €
Purchase (non-members)
Free download (members)
751WG D1.48
technical brochure
No. 302 - February 2019 ELECTRA	 103

More Related Content

What's hot

Tertiary interbus transformer and alternative protection
Tertiary interbus transformer and alternative protectionTertiary interbus transformer and alternative protection
Tertiary interbus transformer and alternative protectionSouvik Dutta
 
Deicing of transmisson line by dielectrc losses
Deicing of transmisson line by dielectrc lossesDeicing of transmisson line by dielectrc losses
Deicing of transmisson line by dielectrc lossesbindasbhabani
 
Bundle conductors in transmission line
Bundle conductors in transmission line Bundle conductors in transmission line
Bundle conductors in transmission line chandan kumar
 
Chep 02 Power Frequency Disturbance
Chep 02 Power Frequency DisturbanceChep 02 Power Frequency Disturbance
Chep 02 Power Frequency DisturbancePiyush Tandel
 
Conductor material and ferranti effect
Conductor material and ferranti effectConductor material and ferranti effect
Conductor material and ferranti effectAbhishekLalkiya
 
high voltage engineering module1(EE369)-KTU
high voltage engineering module1(EE369)-KTUhigh voltage engineering module1(EE369)-KTU
high voltage engineering module1(EE369)-KTUAsha Anu Kurian
 
Effect of earth on transmission line, bundle conductor &amp; method of gmd
Effect of earth on transmission line, bundle conductor &amp; method of gmdEffect of earth on transmission line, bundle conductor &amp; method of gmd
Effect of earth on transmission line, bundle conductor &amp; method of gmdvishalgohel12195
 
Skin effect, proximity effect, ferranti effect, corona discharge
Skin effect, proximity effect, ferranti effect, corona dischargeSkin effect, proximity effect, ferranti effect, corona discharge
Skin effect, proximity effect, ferranti effect, corona dischargeRoungpaSukhe
 
Types of transmission lines
Types of transmission linesTypes of transmission lines
Types of transmission linesSelf-employed
 
Bioimpedance overview
Bioimpedance overviewBioimpedance overview
Bioimpedance overviewdishant garg
 
Darkawi_et_al_CEIDP_2012_VF_IEEE
Darkawi_et_al_CEIDP_2012_VF_IEEEDarkawi_et_al_CEIDP_2012_VF_IEEE
Darkawi_et_al_CEIDP_2012_VF_IEEEAbdallah Darkawi
 
EE8402 Transmission and Distribution
EE8402 Transmission and DistributionEE8402 Transmission and Distribution
EE8402 Transmission and Distributionrmkceteee
 

What's hot (20)

Mod5part1
Mod5part1Mod5part1
Mod5part1
 
Tertiary interbus transformer and alternative protection
Tertiary interbus transformer and alternative protectionTertiary interbus transformer and alternative protection
Tertiary interbus transformer and alternative protection
 
Deicing of transmisson line by dielectrc losses
Deicing of transmisson line by dielectrc lossesDeicing of transmisson line by dielectrc losses
Deicing of transmisson line by dielectrc losses
 
Bundle conductors in transmission line
Bundle conductors in transmission line Bundle conductors in transmission line
Bundle conductors in transmission line
 
Chep 02 Power Frequency Disturbance
Chep 02 Power Frequency DisturbanceChep 02 Power Frequency Disturbance
Chep 02 Power Frequency Disturbance
 
Proximity effect
Proximity effectProximity effect
Proximity effect
 
Conductor material and ferranti effect
Conductor material and ferranti effectConductor material and ferranti effect
Conductor material and ferranti effect
 
Short channel modified
Short channel modifiedShort channel modified
Short channel modified
 
high voltage engineering module1(EE369)-KTU
high voltage engineering module1(EE369)-KTUhigh voltage engineering module1(EE369)-KTU
high voltage engineering module1(EE369)-KTU
 
Effect of earth on transmission line, bundle conductor &amp; method of gmd
Effect of earth on transmission line, bundle conductor &amp; method of gmdEffect of earth on transmission line, bundle conductor &amp; method of gmd
Effect of earth on transmission line, bundle conductor &amp; method of gmd
 
Transmission lines
Transmission linesTransmission lines
Transmission lines
 
Module 6part1
Module 6part1Module 6part1
Module 6part1
 
Skin effect, proximity effect, ferranti effect, corona discharge
Skin effect, proximity effect, ferranti effect, corona dischargeSkin effect, proximity effect, ferranti effect, corona discharge
Skin effect, proximity effect, ferranti effect, corona discharge
 
Corona1
Corona1Corona1
Corona1
 
Types of transmission lines
Types of transmission linesTypes of transmission lines
Types of transmission lines
 
Bioimpedance overview
Bioimpedance overviewBioimpedance overview
Bioimpedance overview
 
Darkawi_et_al_CEIDP_2012_VF_IEEE
Darkawi_et_al_CEIDP_2012_VF_IEEEDarkawi_et_al_CEIDP_2012_VF_IEEE
Darkawi_et_al_CEIDP_2012_VF_IEEE
 
Measurement of DC resistivity
Measurement of DC resistivityMeasurement of DC resistivity
Measurement of DC resistivity
 
EE8402 Transmission and Distribution
EE8402 Transmission and DistributionEE8402 Transmission and Distribution
EE8402 Transmission and Distribution
 
AC TRANSMISSION by Dr. Kundur
AC TRANSMISSION by Dr. Kundur AC TRANSMISSION by Dr. Kundur
AC TRANSMISSION by Dr. Kundur
 

Similar to Electrical properties of insulating materials under VLF voltage

Dielectric Spectroscopy in Time and Frequency Domain
Dielectric Spectroscopy in Time and Frequency DomainDielectric Spectroscopy in Time and Frequency Domain
Dielectric Spectroscopy in Time and Frequency DomainGirish Gupta
 
Electric field detector
Electric field detectorElectric field detector
Electric field detectorJawad Ali
 
Resonance of a distribution feeder with a saturable core fault current limiter
Resonance of a distribution feeder with a saturable core fault current limiterResonance of a distribution feeder with a saturable core fault current limiter
Resonance of a distribution feeder with a saturable core fault current limiterFranco Moriconi
 
Parasitic Boost Circuit for Transform Less Active Voltage Quality Regulator
Parasitic Boost Circuit for Transform Less Active Voltage Quality RegulatorParasitic Boost Circuit for Transform Less Active Voltage Quality Regulator
Parasitic Boost Circuit for Transform Less Active Voltage Quality RegulatorIJMTST Journal
 
Paper Electron Tube Afs Epri R5
Paper   Electron Tube   Afs Epri R5Paper   Electron Tube   Afs Epri R5
Paper Electron Tube Afs Epri R5John Kappenman
 
Insulation-Coordination-Fundamentals.pptx
Insulation-Coordination-Fundamentals.pptxInsulation-Coordination-Fundamentals.pptx
Insulation-Coordination-Fundamentals.pptxSatriaThechildofgree
 
Short circuit test in brief
Short circuit test in briefShort circuit test in brief
Short circuit test in briefMuthar Hussain
 
22 9151 transformer exchangingwithvacuum edit septian
22 9151 transformer exchangingwithvacuum edit septian22 9151 transformer exchangingwithvacuum edit septian
22 9151 transformer exchangingwithvacuum edit septianIAESIJEECS
 
THD ANALYSIS OF LFAC TRANSMISSION SYSTEM
THD ANALYSIS OF LFAC TRANSMISSION SYSTEMTHD ANALYSIS OF LFAC TRANSMISSION SYSTEM
THD ANALYSIS OF LFAC TRANSMISSION SYSTEMijiert bestjournal
 
Reduced Dielectric Losses for Underground Cable Distribution Systems
Reduced Dielectric Losses for Underground Cable Distribution SystemsReduced Dielectric Losses for Underground Cable Distribution Systems
Reduced Dielectric Losses for Underground Cable Distribution SystemsIJAPEJOURNAL
 
Introduction to Power Quality
Introduction to Power Quality Introduction to Power Quality
Introduction to Power Quality Piyush Tandel
 
Protection of 20industrial electronic.pdf
Protection of 20industrial electronic.pdfProtection of 20industrial electronic.pdf
Protection of 20industrial electronic.pdfwhmonkey
 
03 partial discharge theory cutler-hammer
03 partial discharge theory cutler-hammer03 partial discharge theory cutler-hammer
03 partial discharge theory cutler-hammerprasadkappala
 
Short-Circuit calculation -Ppt-Slides - Copy.ppt
Short-Circuit calculation -Ppt-Slides - Copy.pptShort-Circuit calculation -Ppt-Slides - Copy.ppt
Short-Circuit calculation -Ppt-Slides - Copy.pptJatmylHarnero1
 
Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...IOSR Journals
 
Transient Recovery Voltage Test Results of a 25 MVA Saturable-Core Fault Curr...
Transient Recovery Voltage Test Results of a 25 MVA Saturable-Core Fault Curr...Transient Recovery Voltage Test Results of a 25 MVA Saturable-Core Fault Curr...
Transient Recovery Voltage Test Results of a 25 MVA Saturable-Core Fault Curr...Franco Moriconi
 
Improved Blocked Impedance Model for Loudspeakers
Improved Blocked Impedance Model for LoudspeakersImproved Blocked Impedance Model for Loudspeakers
Improved Blocked Impedance Model for LoudspeakersAndy Unruh
 

Similar to Electrical properties of insulating materials under VLF voltage (20)

Circuit Breakers
Circuit BreakersCircuit Breakers
Circuit Breakers
 
Dielectric Spectroscopy in Time and Frequency Domain
Dielectric Spectroscopy in Time and Frequency DomainDielectric Spectroscopy in Time and Frequency Domain
Dielectric Spectroscopy in Time and Frequency Domain
 
Electric field detector
Electric field detectorElectric field detector
Electric field detector
 
Sub station training
Sub station trainingSub station training
Sub station training
 
Resonance of a distribution feeder with a saturable core fault current limiter
Resonance of a distribution feeder with a saturable core fault current limiterResonance of a distribution feeder with a saturable core fault current limiter
Resonance of a distribution feeder with a saturable core fault current limiter
 
Parasitic Boost Circuit for Transform Less Active Voltage Quality Regulator
Parasitic Boost Circuit for Transform Less Active Voltage Quality RegulatorParasitic Boost Circuit for Transform Less Active Voltage Quality Regulator
Parasitic Boost Circuit for Transform Less Active Voltage Quality Regulator
 
Paper Electron Tube Afs Epri R5
Paper   Electron Tube   Afs Epri R5Paper   Electron Tube   Afs Epri R5
Paper Electron Tube Afs Epri R5
 
Insulation-Coordination-Fundamentals.pptx
Insulation-Coordination-Fundamentals.pptxInsulation-Coordination-Fundamentals.pptx
Insulation-Coordination-Fundamentals.pptx
 
Short circuit test in brief
Short circuit test in briefShort circuit test in brief
Short circuit test in brief
 
22 9151 transformer exchangingwithvacuum edit septian
22 9151 transformer exchangingwithvacuum edit septian22 9151 transformer exchangingwithvacuum edit septian
22 9151 transformer exchangingwithvacuum edit septian
 
THD ANALYSIS OF LFAC TRANSMISSION SYSTEM
THD ANALYSIS OF LFAC TRANSMISSION SYSTEMTHD ANALYSIS OF LFAC TRANSMISSION SYSTEM
THD ANALYSIS OF LFAC TRANSMISSION SYSTEM
 
Reduced Dielectric Losses for Underground Cable Distribution Systems
Reduced Dielectric Losses for Underground Cable Distribution SystemsReduced Dielectric Losses for Underground Cable Distribution Systems
Reduced Dielectric Losses for Underground Cable Distribution Systems
 
Introduction to Power Quality
Introduction to Power Quality Introduction to Power Quality
Introduction to Power Quality
 
R01043105113
R01043105113R01043105113
R01043105113
 
Protection of 20industrial electronic.pdf
Protection of 20industrial electronic.pdfProtection of 20industrial electronic.pdf
Protection of 20industrial electronic.pdf
 
03 partial discharge theory cutler-hammer
03 partial discharge theory cutler-hammer03 partial discharge theory cutler-hammer
03 partial discharge theory cutler-hammer
 
Short-Circuit calculation -Ppt-Slides - Copy.ppt
Short-Circuit calculation -Ppt-Slides - Copy.pptShort-Circuit calculation -Ppt-Slides - Copy.ppt
Short-Circuit calculation -Ppt-Slides - Copy.ppt
 
Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...Concept and Viability of High Temperature Superconductor Fault Current Limite...
Concept and Viability of High Temperature Superconductor Fault Current Limite...
 
Transient Recovery Voltage Test Results of a 25 MVA Saturable-Core Fault Curr...
Transient Recovery Voltage Test Results of a 25 MVA Saturable-Core Fault Curr...Transient Recovery Voltage Test Results of a 25 MVA Saturable-Core Fault Curr...
Transient Recovery Voltage Test Results of a 25 MVA Saturable-Core Fault Curr...
 
Improved Blocked Impedance Model for Loudspeakers
Improved Blocked Impedance Model for LoudspeakersImproved Blocked Impedance Model for Loudspeakers
Improved Blocked Impedance Model for Loudspeakers
 

More from Power System Operation

Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panelsPower System Operation
 
Big Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsBig Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsPower System Operation
 
SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action SchemePower System Operation
 
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...Power System Operation
 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePower System Operation
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)Power System Operation
 
Electrical Transmission Tower Types - Design & Parts
Electrical Transmission Tower  Types - Design & PartsElectrical Transmission Tower  Types - Design & Parts
Electrical Transmission Tower Types - Design & PartsPower System Operation
 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools Power System Operation
 
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
Power Quality  Trends in the Transition to  Carbon-Free Electrical Energy SystemPower Quality  Trends in the Transition to  Carbon-Free Electrical Energy System
Power Quality Trends in the Transition to Carbon-Free Electrical Energy SystemPower System Operation
 

More from Power System Operation (20)

ENERGY TRANSITION OUTLOOK 2021
ENERGY TRANSITION OUTLOOK  2021ENERGY TRANSITION OUTLOOK  2021
ENERGY TRANSITION OUTLOOK 2021
 
Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panels
 
What does peak shaving mean
What does peak shaving meanWhat does peak shaving mean
What does peak shaving mean
 
What's short circuit level
What's short circuit levelWhat's short circuit level
What's short circuit level
 
Power System Restoration Guide
Power System Restoration Guide  Power System Restoration Guide
Power System Restoration Guide
 
Big Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsBig Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid Operations
 
SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action Scheme
 
Substation Neutral Earthing
Substation Neutral EarthingSubstation Neutral Earthing
Substation Neutral Earthing
 
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground Resistance
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
 
Electrical Transmission Tower Types - Design & Parts
Electrical Transmission Tower  Types - Design & PartsElectrical Transmission Tower  Types - Design & Parts
Electrical Transmission Tower Types - Design & Parts
 
What is load management
What is load managementWhat is load management
What is load management
 
What does merit order mean
What does merit order meanWhat does merit order mean
What does merit order mean
 
What are Balancing Services ?
What are  Balancing Services ?What are  Balancing Services ?
What are Balancing Services ?
 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
 
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
Power Quality  Trends in the Transition to  Carbon-Free Electrical Energy SystemPower Quality  Trends in the Transition to  Carbon-Free Electrical Energy System
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
 
Power Purchase Agreement PPA
Power Purchase Agreement PPA Power Purchase Agreement PPA
Power Purchase Agreement PPA
 
Harmonic study and analysis
Harmonic study and analysisHarmonic study and analysis
Harmonic study and analysis
 
What is leakage current testing
What is leakage current testingWhat is leakage current testing
What is leakage current testing
 

Recently uploaded

(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...RajaP95
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 

Recently uploaded (20)

(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 

Electrical properties of insulating materials under VLF voltage

  • 1.  Some practical examples and experiences from the use of VLF for AC breakdown and diagnostic testing are summarized in chapter 4. Theoretical background Permittivity and dielectric loss At AC voltage, the resulting dielectric loss is usually deduced by considering a parallel plate capacitor with a complex permittivity . The resulting dielectric loss factor tanδ is the sum of contributions from both dielectric polarization and losses due to conductivity σ : tanδ = tanδ1 (1) Figure 1 - Permittivity and dissipation factor versus frequency and temperature This means that electrical conduction may become the dominant loss mechanism at very low frequencies. The applied voltage magnitude and particularly the temperature of the insulation may therefore strongly affect the dielectric loss at VLF voltages. On the other hand, the time constant of the dielectric relaxation mechanisms will become lower at ••• Introduction Very low frequency (VLF) AC voltage testing in the frequency range from 0.01 to 1 Hz is increasingly being used for both high voltage (Hi-Pot) acceptance and condition assessment of installed large capacitance power components [IEEE standards, IEC standard, etc.]. The main advantage of such tests is the low amount of reactive power needed compared to testing at power frequency. Today, equipment for VLF after- laying tests are becoming available at voltages up to 400 kV. In addition, diagnostic parameters as for example partial discharge activity and dielectric losses, are regularly measured using VLF voltages. Scope and outline of the work The main purpose of WG D1.48 was to review the present knowledge regarding the effects of VLF voltage testing on electrical properties and ageing mechanisms of high voltage insulation systems, aiming at facilitating development of methods and useful evaluation criteria for both acceptance and maintenance VLF-tests. The Technical Brochure consists of three main parts.  The theoretical part in chapter 2 gives an overview of how permittivity, dielectric loss and electric field distribution within insulation systems is expected to vary with the frequency of the applied voltage in the range from DC to AC power frequencies. It presents the general principles of dielectric loss and partial discharge measurements, as well as mechanisms of ageing and initiation of electric breakdown.  Chapter 3 describes the different ways of generating VLF test voltages and the methods available for both withstand and diagnostic testing. Members E. ILDSTAD, Convenor (NO), F. MAUSETH, Secretary (NO), M. BAUR (AT), T. BLACKBURN (AU), J. BLENNOW (SE), J. CASTELLON (FR), A. CAVALLINI (IT), J. HOLBØLL (DK), N. HOZUMI (JP), H. MAYER (AU), P. MOHAUPT (AT), F. PETZOLD (DE), C. SUMEREDER (AT) Electrical properties of insulating materials under VLF voltage 751WG D1.48 technical brochure No. 302 - February 2019 ELECTRA 93
  • 2. sufficiently low, causing local heating and melting of the surrounding polymer. The most important defects limiting the breakdown strength of practical high voltage insulation systems comprises cavities, particle inclusions, interface irregularities, sharp edges at the electrode, etc. The overall question addressed in this report is how the physical and chemical erosion and degradation process leading to tree initiation and subsequently electrical breakdown is affected by VLF testing. Electrical treeing In case of electric tree formation, it is important to consider the voltage or the electric field distribution along the tree structure. As a first approximation, we will here consider a simplified RC-model, presented in Fig. 3. In this model, the tree channel is considered a cylinder with radius r and a total channel resistance of R, connected in series with the capacitance C of the non-treed insulation section. In a real electric tree, surface deposits of carbon determine the value of this resistance, and its value is expected to reduce as function of time due to partial discharge activity and material degradation. Figure 3 - Simplified RC-Model for a propagating electrical tree, considered as a resistive tree channel in series with a capacitive non-treed insulation between the tree tip and the ground electrode Due to the thin tree channel it is a good approximation to consider the capacitance C of the non-treed insulation to be independent of the non-treed insulation distance [2]. In the case of a channel with a tip radius of 2 µm, the value of the capacitance becomes C = 4.9∙10-4 pF. ••• Figure 4 - Ratio of voltage across the tree channel, versus total tree channel resistance R at 50, 10 and 0.1 Hz [3] higher temperatures, shifting the maximum losses towards a higher frequency, as illustrated in Fig. 1. Partial discharge activity At low frequencies, the electric field distribution within an insulation system becomes more determined by the conductivity of the materials, and the classic capacitive abc-model needs to be modified. The first approximate approach is to add insulation resistances in parallel with the capacitances, as shown in Fig. 2. Figure 2 - Extended abc-equivalent circuit for modelling of partial discharges [1] Due to the insulation conductivity σ, it is expected that the number of PD pulses per voltage period will be reduced at VLF-testing below a certain frequency. As a rule of thumb, the applied voltage frequency should be approximately higher than (2) where σ is the highest conductivity of the insulation system. In case of n equal partial discharges occurring per half period, the power dissipated by the discharges increase proportional with frequency (3) where qa is the apparent partial discharge magnitude, Ui is the effective applied ac voltage at PD inception and f is the voltage frequency. Thus, PD activity is expected to result in a rate of degradation proportional to the frequency of the applied voltage. Ageing and electric breakdown of polymers In most cases, electric breakdown in polymers is a progressive, cumulative process involving the initiation and growth of tiny tubular channels forming electrical trees during dry service conditions. In case of ageing in wet environments, water trees grows due to the combined effect of water condensation and electric field. Electrical breakdown finally occurs when the resistance of the tree structure becomes 751WG D1.48 technical brochure No. 302 - February 2019 ELECTRA 95
  • 3. mechanical strength of the polymer will enhance formation water filled tree shaped structures, particularly following the amorphous regions of the polymer. Due to the high electric conductivity of such channels compared to the surrounding non-treed insulation, high dielectric loss values is expected in case of low frequency testing, particularly if water trees bridge the insulation wall. Short term VLF testing is of these reasons expected not to enhance the formation of water trees. Methods of generating VLF test voltages The report briefly gives an overview of the principle of the four most common VLF test techniques currently available, addressing limitations and future possibilities. Amplitude modulated VLF voltage Here, a conventional high voltage transformer, fed by a motor driven regulating transformer is used to generate an amplitude modulated AC voltage. The rectifiers connected to the high voltage side are switched on at selected moments to create a sinusoidal VLF voltage. However, the motor-driven regulating transformer limits the application to low power and low voltage. Controlled DC charging and discharging This principle is based upon combining high-voltage transformers and two HVDC Greinacher cascades. A sinusoidal VLF output voltage is obtained using a complex control algorithm for the power module, DC units and the discharge elements. The advantage of this method is that there are no mechanically operated parts. Choosing a sufficiently high frequency for the power module, the dimensions and weight of the transformers and cascades will be reduced. However, due to the high complexity of the discharge elements and the control algorithm, this concept cannot easily be scaled to higher voltage levels. Differential Resonance Technology (DRT) This method exploits the property of both resonance and superposition of two voltages at slightly different high frequency adding to form a low frequency voltage at the desired beat frequency. The beat frequency oscillation consists of the carrier frequency in the range of 1 kHz, whose amplitude is modulated by the desired test frequency of, e.g., 0.1 Hz or higher. Therein, a resonant circuit tuned to the carrier frequency allows for the simple generation of the ••• The graph presented in Fig. 4 shows that the effect of reducing the frequency, is that more of the applied voltage will be across the non-treed insulation and less stress along the tree structure. Thus, at lower frequencies, the degree of branching will be reduced compared to that at higher frequencies. Result from laboratory experiments, presented in Fig. 5, verify this expected frequency dependent shape of electrical trees. a) Bush shaped electrical b) Branch / filament type of tree at 50 Hz,10kV tree at 0.1 Hz,14kV Figure 5 - Typical electrical trees formed from needle tips in XLPE at 50 and 0.1 Hz voltage[3] At 50 Hz, rounded-off bush type-shaped trees were formed, while more filament type of trees were formed at 0.1 Hz. Water treeing Water trees are caused by the synergic effect of humidity and electric stress. They typically grow very slowly in the direction of the electric field and in wet service conditions it may take 10-15 years to bridge the insulation of a 12 kV XLPE. Examples of typical water trees are shown in Fig. 6. a) Vented- and b) bow-tie trees Figure 6 - Typical Water trees formed in XLPE cables during service stress at 50 Hz Water trees are not associated with partial discharges or emission of light during its initiation and growth. At 50 Hz AC voltage water trees have, however, been found to grow in all known polymeric insulation at electric field stresses down to about 1 kV/mm. While it has not been possible to detect water trees formation in case of DC voltage application. From a theoretical point of view, it is common to explain formation of water trees by the combined and slow action of condensation of water and Maxwell forces acting on enclosed water droplets within the insulation. Any chemical reactions reducing the 751WG D1.48 technical brochure No. 302 - February 2019 ELECTRA 97
  • 4. insulation, space charge measurements showed that the exponential space charge accumulation at the interfaces followed a time constant of about 2.5 days. This is in good agreement with Eq. (2) using the average conductivity for the layered insulation. This strongly indicates that no major electric field distortions is expected within XLPE cable insulation during VLF 0.1 Hz testing. In case of testing cable systems with accessories, it is important to consider the conductivity of field grading materials, particularly in case of dielectric loss and PD measurements. Dielectric losses Resultsfrommeasurementsoflowfrequencydielectric loss of XLPE cable samples have demonstrated that conduction becomes the dominant loss mechanisms at temperatures above approximately 50 °C [5]. In case of aged cable samples, the dissipation factor at 0.1 Hz was, as illustrated in Figure 8, found to increase significantly with the applied test voltage [6]. A non-linearity strongly indicating water tree degradation. Some condition assessment criteria for service aged XLPE cables are summarized in [7]. Partial discharges PD diagnostic at VLF tests is still a challenging task due to noise interference from the switching devices within the VLF test sets, particularly at the highest system voltages requiring higher sensitivity. As an example, Figure 9 shows typical results from laboratory PD measurements using test voltage in the frequency range of 0.01 – 100 Hz and samples of polycarbonate containing cavities [8]. The results reveal a reduced number of partial discharges per period when reducing the frequency. An effect ••• necessary high voltages. By changing the modulation frequency, VLF voltages at several hundred kV can be generated in the frequency range from 0.1 Hz up to 10 Hz. Cosine-rectangular VLF technology This type of generator is based upon power electronic switching or bipolar charging, using built-in positive and negative HVDC sources, resulting in a square shaped VLF output voltage. The significant and most important property of the cosine-rectangular VLF technology is, however, the shape of the power recovery during polarity reversal. It is common to aim at a slope close to that at a frequency of 50 Hz. Thus, the field stress during polarity reversal is comparable that at operating frequency. Selected results from VLF testing The brochure reviews some practical experience from VLF testing, mainly from applications on XLPE cable systems and electrical machines. Interface charging and electric field distribution At low frequencies, the electric field distribution is expected to be affected by the conductivity of the insulation, according to Eq. (2). Results summarized in Fig. 7 indicate that space charge accumulation in XLPE cable insulations increases at frequencies below 0.02 Hz [4]. In addition to frequency and duration of voltage application, different combinations of electrode materials (e.g. semi-conductor) are important factors determining the space charge injection and distribution under AC electric stress. In case of applying DC voltage to layered XLPE Figure 7 - Relationship between frequency of the applied electrical stress and space charge build-up in the bulk of XLPE at room temperature [4] Figure 8 - Measured dissipation factors at 0.1 Hz versus test voltage in kV applied to different type of service aged XLPE cables [6] 751WG D1.48 technical brochure No. 302 - February 2019 ELECTRA 99
  • 5. It is important to relate the expected endurance at 0.1 Hz voltage testing to that at 50-60 Hz service stress, considering similar type of defects. A comprehensive comparison of such breakdown values are summarized in Fig. 11 [10]. The results show that in most cases breakdown at VLF (0.1 Hz) testing occur at voltage levels 1-4 times higher than that at 50 Hz AC voltage. Voids are particularly difficult to detect. As shown in Fig. 12, there is a strong correlation between breakdown at power frequency AC and VLF voltages [11]. On average, the 0.1 Hz VLF breakdown values of water treed cables are found to be about two times higher than breakdown values at 50 Hz AC. Figure 12 - AC 50 Hz (lower red) and VLF 0.1 Hz (upper blue) breakdown voltages of water tree degraded cable samples as a function of non-treed insulation thickness. Filled and unfilled symbols represents results from service and laboratory aged cables, respectively [11]. ••• which was explained using the model of Fig. 2 including charge decay after a discharge. In most cases, small differences are found between PD inception voltage, PD magnitudes and the phase- resolved PD patterns measured at 0.1 Hz and 50 Hz. In case of testing 12 kV service-aged XLPE cable samples with cold-shrink joints, a clear frequency dependence was , however, observed [9]. The results presented in Fig. 10 show that at frequencies below 0.2 Hz both the PD inception and extinction voltages were found to be below the service stress at 50 Hz. This indicates a frequency dependent electric field distribution within the joints, making it challenging to correlate PD results obtained at VLF to that at operating frequency. Electric breakdown under VLF testing By electric withstand testing, it is in general possible to only locate the weakest sites. It can however give an indication to whether the test object is in good or bad condition. Figure 9 - Total number of PDs per voltage cycle and right; average PD magnitude for insulated cavities [8] Figure 10 - PD inception (PDIV) and extinction (PDEV) voltage for a cold-shrink 12 kV cable joint as a function of frequency [9]. Closed Void Conductive Protrusion Insulating Contaminant XLPE Insulation Conductive Contaminant Conductive Contaminant Conductive Contaminant Insulating Contaminant Cut in Cable Insulation Insufficient Compression of I/F Water droplet Rubber- XLPE Interface DC VLF OSW Rubber- XLPE Interface Figure 11 - Ratio of breakdown value obtained at different type of test voltage relative to AC voltage for several types of defects in cables and accessories [10] Figure 12 - AC 50 Hz (lower red) and VLF 0.1 Hz (upper blue) breakdown voltages of water tree degraded cable samples as a function of non-treed insulation thickness. Filled and unfilled symbols represents results from service and laboratory aged cables, respectively [11] 751WG D1.48 technical brochure No. 302 - February 2019 ELECTRA 101
  • 6. shows that electric breakdown of XLPE cables occur at voltage levels 1-4 times higher than that at 50 Hz AC voltage. Voids are particularly difficult to detect by VLF withstand voltage testing. In case of water tree-degraded cables, the breakdown at VLF voltage varies from 50 to 200% of that at power frequency. References [1] P. K. Olsen, F. Mauseth, and E. Ildstad, “The effect of DC superimposed AC voltage on partial discharges in dielectric bounded cavities”, presented at the 2014 International Conference on High Voltage Engineering and Application (ICHVE), 2014 [2] J. Lekner, “Capacitance coefficients of two spheres”, Electrostat., vol. 69, pp. 11-14, 2011. [3] E.Ildstad, K. Fauskanger and J. Holto, “Electrical Treeing from Needle Implants in XLPE during Very Low Frequency (VLF) Voltage Testing” IEEE ICSD, Bologna, Italy, June 2013. [4] X. Wang, N. Yoshimura, Y. Tanaka, K. Murata, and T. Takada, “Space charge characteristics in cross-linking polyethylene under electrical stress from DC to power frequency”, J. Phys. D: Appl. Phys. , vol. 31, pp. 2057-2064, 1998. [5] C. Dang and S. Pelissou, “Some technical consideration on very low frequency cable diagnostic”, presented at the Transmission and Distribution Conference and Exposition, 2003. [6] J. C. Hernández-Mejía, R. Harley, N. Hampton, and R. Hartlein, “Characterization of Ageing for MV Power Cables Using Low Frequency Tan d Diagnostic Measurements”, IEEE Trans. Diel. and El. Insul., pp. 862-870, 2009. [7] IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (less than 1 Hz), 2013. [8] C. Forssén and H. Edin, “Partial discharges in a cavity at variable applied frequency part 2: measurements and modeling”, IEEE Trans. Diel. and El. Insul., vol. 15, no. 6, pp. 1610-1616, 2008. [9] F. Mauseth, H. Tollefsen, and S. Hvidsten, “Effect of Test Voltage Frequency on PD Inception on Service Aged Cable Joint”, presented at the IEEE Int. Conf. on High Voltage Eng., Poznan, Poland, 2014. [10] K. Uchida, H. Tanaka, and K. Hirotsu, “Study on Detection for the Defects of XLPE Cable Lines”, IEEE Trans. on Power Delivery, vol. 11, no. 2, pp. 663-668, 1996. [11] K. Uchida, M. Nakade, D. Inoue, H. Sakakibara, and M. Yagi, “Life Estimation of Water Tree Deteriorated XLPE Cables by VLF(Very Low Frequency) Voltage Withstand Test”, presented at the PES T&D 2002, 2002.  Conclusions The data collected by the literature survey is discussed with respect to known practical experience and theoretical considerations. The main purpose of addressing the physical mechanisms of space charge formation and degradation has been to provide a base for evaluation of possibilities and limitations regarding application of VLF tests, both as high voltage acceptance/after laying tests and diagnostic tools. It is concluded that:  In case of VLF (0,1 Hz) testing of high voltage insulation systems, the risk of space charge accumulation is very low, and the electric field distribution becomes similar to that at power frequency, provided the conductivity of the insulating materials is lower than about: σ < 1·10-16 Ω-1 m-1 .  During VLF testing of installed cable systems it is important to address the electric field distribution within the accessories, as it may become frequency-dependent, due to higher and non-linear conductivity of field grading materials compared to that of the insulation.  At VLF voltages, the rate of electrical treeing and gradual degradation is reduced compared to that at power frequency. Mainly due to the lower number of Partial discharges per time unit and reduced voltage drop across voids and electrical tree channels. More knowledge is, however, needed to improve comparison and interpretation of results from partial discharge measurements at VLF test voltages with that at service stresses.  For condition assessment of insulation systems, low frequency measurements of permittivity and dielectric loss factors is a useful diagnostic tool - revealing critical changes in conductivity and other material parameters. For example, VLF testing of severely water tree degraded XLPE cables is indicated by high and increased value of dielectric loss with increasing test voltage.  Experience from VLF (0.1 Hz) breakdown testing BROCHURE N° 751 (en anglais seulement) (in English only) Disponible sur / Available on: www.e-cigre.org Prix non-Membres / Non-Member Price: 90 € Purchase (non-members) Free download (members) 751WG D1.48 technical brochure No. 302 - February 2019 ELECTRA 103