SlideShare a Scribd company logo
1 of 7
Download to read offline
1 INTRODUCTION
Today’s regulatory air quality standards for
healthcare facilities effectively maintain heating,
cooling, and ventilation requirements within acute
patient room by fulfilling overall air change rates.
American Society of Heating, Refrigeration, and Air
conditioning Engineers or ASHRAE require that air
changes occur to keep fresh air continuously enter-
ing spaces, however this guideline does not suggest
how to effectively remove contaminated air that may
be caught in dead zones effected by room design.
The standard does not consider that the air being
mixed in the ventilated spaces is allowing clean air
to be mixed with contaminated air.
These airflow patterns created by the ventilation
contribute to air-temperature, distribution, thermal
comfort, air quality, and the possibility of airborne
pathogen transmission within a space or spaces. Air-
flow patterns of existing rooms need to be studied in
order to understand pre-existing relationships be-
tween location and type of supply diffusers, supply
airflow rates, supply temperature, air return location
and size, infiltration, furniture arrangement, heat
sources and location of the patient and others in the
room.
An example used to look at risk of infection due
to room design is Influenza. Influenza was chosen in
part because of its seasonal and continued yearly ef-
fects on populations as well as its lower quantum
level. The quantum level explained more fully in the
risk assessment method portion, is a measure of the
infectious material present and the pathogenicity of
that material (Wagner et al. 2009). Other airborne
threats such as Tuberculosis, and SARS would yield
a larger quanta production rate.
Studies have been done proving influenza as an
airborne threat within hospitals at close range like
that in patient rooms (Blachere et al. 2009,
Brankston et al. 2007). However, there have only
been a few significant studies showing how airflow
patterns can be affected by supply and return vents
as well as room configuration. A review article lead
by Dr. Yuguo Li in 2007 found only 40 studies fo-
cusing on ventilations impact on airborne transmis-
sion in the built environment databased between
1960 and 2005. Of these forty studies only ten were
deemed conclusive by a team of multidisciplinary
reviewers. These conclusive studies had met the
teams determined evidentiary threshold, and provide
strong evidence on ventilation effects of airborne
transmission of diseases including Tuberculosis,
SARS, Influenza and chickenpox(Li et al. 2007).
Most recently a study using computational fluid
dynamic modeling was completed by Khankari. Two
mechanical placements were tested in one patient
room to show resultant airflow patterns (Khankari
2015). The information gathered from this study can
be significantly furthered by looking at two common
The impact of patient room design on airborne Hospital-Acquired
Infections
A. Copeland & A. Sharag-Eldin
Kent State University, Kent, Ohio, United States
ABSTRACT: Transmission of airborne diseases in healthcare facilities is an increasingly important concern.
This, in part, is due to the reduction in funding from insurance companies for hospital-acquired infections
(HAI) and the consequent economic impact of an influenza outbreak in a hospital. With increasing cases of
HAI in the USA, it became necessary to examine the current ventilation standards for healthcare facilities.
While design guidelines have focused on recommending appropriate ventilation rates, it ignored the delivery
of conditioned air to occupied spaces and the impact of room layout relative to the placement of air supply and
return. The paper will also estimate the probability of infection based on air change effectiveness, and the rela-
tive spatial relationship between HVAC air delivery system and room design. The resulting outcome is a
guideline intended to support health facility designers.
patient room designs and computational fluid dy-
namic models to test a plethora of supply and return
air locations in relation to patient, caregiver and
door.
The following study using a calibrated model veri-
fied by field measurements of air distribution pat-
terns in patient rooms. In addition to airflow pat-
terns, the CFD algorithm is used to determine the
age of the air to measure the effectiveness of the
recommended air changes in the standards delineat-
ing through graphical and numerical means the po-
tential location for concentrated airborne contamina-
tion. It is also intended to encourage the
development of design codes and standards that take
into account airborne pathogen transmission in plac-
es where the patient is most vulnerable to infection
from visitors or staff.
2 RESEARCH METHOD
2.1 Room Criteria and Selection
The geometries selected and tested in this paper cor-
respond with the general trends in the healthcare de-
sign field. While shapes and sizes of rooms can dif-
fer drastically, three average room sizes were
selected to correspond with small, medium and large
patient room sizes.
The room sizes are as following 21.4 m2
(230 ft2),
27.87 m2
(300 ft2
) and 34.84 m2
(375 ft2
) all inclu-
sive. The sizes address the possibility of the imple-
mentation of universal or acuity adaptable rooms in
all sizes and critical care patients in the larger room
size (Brown & Gallant, 2006).
The patient rooms used for the simulation follow the
FGI Guidelines for Hospitals and Outpatient Facili-
ties 2014, thus having private bathrooms, and glaz-
ing that is no less than 8% of the floor area of the
room served (2014 FGI Guidelines for Hospitals and
Outpatient Facilities 2014).
Each room tested is rectangular in shape and pro-
pose either an inboard bathroom located at the en-
trance of the patient room or outboard bathroom, lo-
cated along the exterior wall of the room and
building. The bathrooms are placed on the headwall,
or where the patients head is located near the wall in
bed with supply air being placed above the patient
bed and return located near the door to the patient
room. The supply diffuser is a 4 way diffuser supply
air at 360 degrees at 6 air changes per hour calculat-
ed by room’s volume from finish floor to 6ft above.
2.2 Computational Fluid Dynamic Modeling
Computational Fluid Dynamic Simulation focuses
on the numerical and algorithm modelling of fluid
flow and heat transfer processes. Given boundary
conditions including climate, internal energy
sources, and HVAC systems CFD simulates a build-
ing’s likely internal or external airflow.
The numerical solution of the airflow simulation
uses differential equations to find values of flow
quantities at certain points of a system. These values
are then converted to a system of algebraic equation
that represent the interdependency of the flow at
each point (Sayma 2009). The points correspond to a
grid or mesh used by the modelling system.
2.3 CFD Modeling
IES VE has been tested and fully validated under
ASHRAE Standard 140. The IES VE program al-
lows for dynamic thermal simulation, including de-
sign load calculations, and simplified computational
fluid dynamic modelling. IES VE primarily focuses
on integrated graphics-driven results, however does
allow for simple numerical analysis based on points
located within the graphic model.
IES VE uses the k-epsilon turbulence model to
find the turbulent viscosity of a 3D space. The
standard k-epsilon model is widely accepted due to
its applicability to wide ranging flow situations pri-
marily looking at internal flows with weak stream-
line curvature models. The equation solves for the
kinetic energy turbulence and the dissipation of the
kinetic energy (Awbi 2003).
While the standard k-epsilon turbulence model is
accepted it has limitations when more complex
flows are being studied and the length scale for the
determination of turbulence can only be speculated.
The RNG k-ε or renormalization group model and
low Reynolds number k-ε model are more accurate
when looking at forced convection or mixed convec-
tion turbulence models while the Large Eddy-
Simulation (LES) model is a more accurate predictor
of flows with strong streamline curvatures (Awbi
2003).
IES VE’s MicroFlo 3D Computational Fluid Dy-
namic modeling application was used to simulate
different conditions. Boundary conditions such as
America’s northeast climate were applied to the
model through the apache application that uses
weather data to provide an environment for the eval-
uation of a building and system design. Thermal
comfort conditions were regulated by specifying
HVAC system and placement based on ASHRAE
170, 2013 healthcare patient room standards includ-
ing required air changes per hour (ACH) and humid-
ity.
MicroFlo produces visual representation of an in-
ternal space’s airflow based on velocity, concentra-
tion of CO2
and local mean age of air. Local mean
age of air (LMA) is the amount of time a parcel of
air has been in certain areas of the simulation space.
Higher values indicated areas with poor ventilation.
2.4 Calibration
In order to calibrate IES VE an educational nursing
simulation room was tested with field measurements
to prove that results gathered from IES VE would be
correct. The nursing simulation room was located in
Northeast Ohio and had an overall area of 34.19 m2
(368 ft2
). The field measurements were taken on
two days November 2nd and November 23rd, 2015.
Figure 1. (Left) Simulation room layout, (Right) simulation
room ceiling plan
2.4.1 Field Measurements
Field measurements were performed in the nursing
simulation room, 5.43 m (17.83 ft.) (L) x 6.4 m
(21.0 ft.) (W) x 3.05 m (10 ft.) (H), with the bed lo-
cated on the same wall as the bathroom shown in
figure 1. The air is supplied and returned through
linear slot diffusers located at the ceiling. The room
is illuminated by six 2’x4’ fluorescent lights, one lo-
cated within the bathroom. Measurements were tak-
en at 3’ grid intervals at .15 m (6in.), 1.1 m (3.5 ft.),
1.8 m (6ft.) above the floor using TSI indoor air
quality meters model 8386A and 8760 to gather
temperature, humidity, carbon dioxide and air veloc-
ity at nine specific points.
The boundary conditions that would be completed
by IES VE were also collected like wall surface
temperature, outside temperature and weather.
IES VE run of simulation room. The simulation
room’s CFD run had boundary conditions collected
from the field measurements, including outside tem-
perature as well as surface temperatures. The supply
air was delivered through slot diffusers that was
equivalent to 360 cfm, approximately 6 ACH. The
simulation room also used perimeter radiators locat-
ed on the exterior walls, causing higher surface tem-
peratures on the respective walls.
2.5 CFD Runs of Patient Rooms
The selected six room designs for patient rooms
were tested through IES VE, similar to the simula-
tion room specific data was collected through the
micro flow runs at three specific heights .15 m
(6in.), 1.1 m (3.5 ft.), 1.8 m (6ft.). Each room was
supplied with 6 ACH, the required ACH per
ASHRAE 170. This required 252 cfm for the small,
315 cfm for the medium, and 400 cfm for the large
patient room’s in order to satisfy the required 6
ACH.
The results all pertain the same climatic influence,
boundary conditions that coincide with February 8th.
Each result is reflecting sixty minutes of time, the
length of time for the required amount of air changes
to take place.
Table 1: Boundary Conditions for Patient Rooms
Flowrate Temperature
CFM* °F °C
Small Room 252 70 21.1
Medium Room 315 70 21.1
Large Room 400 70 21.1
*CFM based on required 6 air changes/ hour per ASHRAE 170
2.6 Data Analysis
2.6.1 Risk Assessment: Wells-Riley Equation vs.
Gammaitoni-Nucci Equation
Local mean age of air and Velocity of air vectors in
the different patient rooms are analyzed to see if any
significant differences were seen in different room
size or layouts.
The risk of transmission is evaluated using the
steady state Wells-Riley equation and non-steady
state Gammaitoni-Nucci equation. Exposure times
can vary in patient rooms from days for a patient, to
as little as a few minutes for a staff member, thus the
risk of transmission is influenced by chance events
(Beggs et al. 2010).
The Gammaitoni-Nucci equation is a modified
version of the Wells-Riley equation that reflects the
exponential increase in number of new cases of in-
fections in a room. The Gammaitoni-Nucci equation
takes into consideration the transient behavior of
transmission over shorter periods of time, and that
not every newly infected person may infect another
due to their short time in a particular space
(NOAKES et al. 2006). The equation considers
room volume, which varies per room size, ventila-
tion rate, and the quanta production rate. The quanta
production rate is best explained as the infections
dose required to infect 63.2% of the people in the af-
filiated enclosed space.
The mean quanta production rate for influenza
that is used for the Gammaitoni-Nucci equation is
100.0 quanta/h, a value for a highly contagious case
(Rudnick & Milton 2003). However, there is still
dispute over an official range of quanta production
rate for Influenza, as found by Rudnick and Milton it
can vary from 15-128 q/h depending on which
steady or non-steady state Wells-Riley equation used
to determine the quanta production rate.
The equation assumes ventilation as a large factor
in particle removal, while it is a significant source,
many other sources also factor in pathogen settle-
ment (Rudnick & Milton, 2003). For Influenza A, a
large factor in pathogen removal is inactivation
through settling, thus removed from the air but not
the space entirely. The equations do not take into
consideration that outside factors such as tempera-
ture, humidity and settling can have an impact on a
person’s risk of airborne infection.
Table 2: Simulation Room CFD Simulation compared to field
measurements
3 RESULTS
Each CFD run resulted in velocity quantities and lo-
cal mean age of air approximations that differed
based on room size and layout, inboard vs. outboard.
The LMA or local mean age of air and known vol-
ume of the rooms were then used for a risk analysis
of Influenza A in those respective rooms using the
Wells-Riley and Gammaitoni-Nucci equations.
3.1 Simulation Room CFD Run
The simulation room’s CFD model ran closely to the
documented field notes. The boundary conditions
were controlled by the data taken from the field
measurement like, surface temperature and input air
temperature. Table 2 shows the averages for each
differing height level for the simulation room CFD
model compared to that of the field measurements.
3.2 Room Comparison
3.2.1 Size
The selected rooms varied in three sizes considered
small, medium and large. Figure 2 shows the differ-
ences of air age in the different patient rooms. Over-
all the size did not have a large impact on velocity
and air age, rather design had an impact on the mean
air age at different areas within the room.
3.2.2 Layout
3.2.2.1 Inboard Patient Room
The inboard CFD model show that the air is circu-
lated relatively consistently among all room sizes
and the local mean age of air is similar throughout
the rooms, ranging from 10.9 minutes to 12.7
minutes. Local mean age of air is older or higher in
the bathroom if the door remains open, resulting in
Height
Average Velocity -
Simulation
Average Velocity -
Field Measurements
ft.-in. ft. /mins. ft. /mins.
0'-6" 4.74 5.625
3'-6" 8.15 10.375
6'-0" 12.11 12.5
Figure 2. Small outboard room (left: 0’-6” AFF, middle:
3’-6” AFF, right: 6’-0” AFF) LMA in minutes
air age of 14.5 minutes. This on average would ap-
proximately result in 6 ACH per hour, each air
change taking on average 10 minutes.
3.2.2.2 Outboard Patient Room
The outboard patient room is relatively different
when it comes to local mean age of air throughout
the space. The CFD model shows that the back zone
in all the outboard rooms have older air parcels as
shown in figure 2. This area has an air that is an av-
erage of 15 minutes old, which would be the equiva-
lent of 4 ACH, while the area around the patient bed
has an average air age of 10.5 minutes which would
result in the required 6ACH.
This air change discrepancy is significant the risk
of transmission will significantly increase in the are-
as of poor circulation. The following mathematical
risk assessments show the increased risk associated
with the poor circulation.
3.3 Risk Assessment
The Wells-Riley steady rate and Gammaitoni-Nucci
non-steady rate are mathematical models that predict
the rate of airborne transmission. The Gammaitoni-
Nucci model is better suited for short term exposure
models, however both will be used and compared to
understand the risk of transmission. Each room is
analyzed using the average ACH, thus the outboard
will be broken into zones and analyzed according to
the different LMA associated with the different
zones of the room. The differing LMA would result
in a different ventilation rate for that space, so in-
stead of the required 6 ACH there may be less in
poorly ventilated areas.
3.4 Local Mean Age of Air
The mathematical risk models predict the transmis-
sion of airborne disease and are based off of flow
rate or the ACH. However, a dimensionless equation
that shows how efficiently different room airflow
structures remove contaminants regardless of the
flow rate can also be utilized (Bartak et al. 2001).
The following table 3 shows the efficiency of the air-
flows in the six rooms. The outboard rooms were
broken into different volumes based on average local
air age to understand the changing efficiency rates
with relation to the local mean age of air at points
within the room.
3.5 Comparison between Mathematical Risk
Assessment Models
It is important to understand the above table
shows three drastically different equations, and in
turn drastically different results. The Wells-Riley re-
sults show the potential for new cases in exponential
increase or decreasing form. If the results are less
than 1 (a < 1) the pathogen would be removed or
settled before infecting any of the susceptible targets,
while the results that are greater than 1 (a > 1) would
result in increasing pathogen transmission. There-
fore, the zones that were identified as poorly venti-
lated in the outboard design have an increasing
chance of infection, while the inboard room and bet-
ter ventilated areas in the outboard would not.
The Gammaitoni-Nucci results are based on per-
centages, thus the results that are shown as decimals,
could also be shown as the equivalent percentage
(i.e. large inboard: 0.0611= 6.11%). Again, like the
Wells-Riley model the inboard rooms have well
mixed air resulting in a low percentage of people
that will contract Influenza through the airborne
Table 3: Mathematical Risk Assessment Models and Efficiency of Airflow in Patient Rooms
Room Design and Zone Wells-Riley *
Wells-Riley
with required
6 ACH
Gammaitoni-
Nucci
Gammaitoni-
Nucci with re-
quired 6 ACH
Airflow Efficiency
(Bartak et al.,
2001)**
Small Outboard 0.1061
43.89 m3
@ 10.5 LMA 0.9451 0.1560 2.0170
27.47 m3
@ 15 LMA 1.7696 0.5303 0.3544 10.61% 4.6040
Small Inboard 0.6045 0.0991 1.3588
Medium Outboard 0.0858
69.38 m3
@ 11.5 LMA 0.6206 0.1017 1.1147
19.82 m3
@ 13 LMA 2.0399 0.4289 0.3376 8.58% 4.4109
Medium Inboard 0.4898 0.0801 0.8670
Large Outboard 0.0682
91.17 m3
@ 10.9 LMA 0.4564 0.0754 0.6332
22.1 m3
@ 14.5 LMA 2.0411 0.3410 0.4087 6.82% 3.4752
Large Inboard 0.3708 0.0611 0.5097
*
Solves for P, a dimensionless exponential increase of new cases
**
The lower the number the higher the efficiency of airflow
route. Contrastingly, the particular outboard room
zones that have nominal ventilation result in a prob-
ability of infection of 35-40%. It is important to note
that this model looked at the probability of an indi-
vidual who has been in the room with the infected
for an hour.
Furthermore, if 15 minutes was used as the expo-
sure time rather than an hour the probability of a
susceptible person being infected would decrease
(i.e. Small outboard patient room, the poorly venti-
lated area decrease by 86% from a 35% probability
of infection to a 5% probability). The required 6
ACH in a well-mixed and ventilated room would
drastically decrease the probability of a person be-
coming infected, however depending on room design
certain areas are not getting properly ventilated and
the air age is increasing.
Lastly, the equation used by Bartak and others
takes the relationship between air age in the room of
certain volumes to find the efficiency of the airflow,
while not considering the ventilation rate. Similar to
the Gammaitoni-Nucci model, if 6 ACH were
achieved everywhere in the room regardless of the
design, the airflow efficiency in the rooms would be
improved.
4 DISCUSSION AND CONCLUSION
4.1 Significance
The main regulatory source for healthcare facilities’
ventilation systems is ASHRAE 170, it is also in-
cluded as part of the FGI Guidelines for Hospitals
and Outpatient Facilities 2014. According to
ASHRAE, non-critical patient rooms should receive
6 ACH, with a minimum of 2 outdoor ACH. Many
studies have been completed that have been the basis
of ASHRAEs regulations that dictate 6 ACH. How-
ever, from this study not all patient rooms can be
considered suitable with 6 ACH. The design has to
be taken into consideration when writing and con-
sidering minimum ventilation standards.
While the airflow in the inboard patient rooms
were effective shown by the local mean age of air,
the outboard patient room airflow was less then ef-
fective for circulating fresh air. The rooms tested
were linear in design and less suitable room designs
may be found if tested.
The outboard design’s least effective space is
what is used for family and visitor zones. The regu-
lations primarily have supply outlets located over the
patient beds to protect the patient from airborne in-
fection. However, this leaves visitors and staff more
susceptible to airborne infection like Influenza A as
well as other more transmissible diseases.
The airflow effectiveness is important to prevent
airborne disease within the room. As seen using the
mathematical risk assessment models the air age has
a large impact on Influenza A infection probability.
Thus, ventilation with room design in considera-
tion can effectively be a primary measure against
airborne infections like Influenza A or other airborne
disease. However ventilation regulation needs to fo-
cus on how design impacts spaces and its result on
the ventilation needs.
4.2 Limitations and considerations
This study primarily focused on two designs of pa-
tient rooms which leaves a lot of geometry’s untest-
ed, thus it would be suggested that room designs are
tested to understand ventilation properties for better
efficiency and prevention measures
The supply and return air were also only tested at
one location with the supply air above the patient
bed and the return near the exit. Other placement
could have shown more effective ventilation strate-
gies, and should be considered to maximize effective
airflow. While other ventilation strategies should be
explored, 6 ACH have been found to be adequate as
long as the room is receiving the adequate airflow
that allows for the required ACH, thus possible add-
ed supply to evenly distribute air may also be an ide-
al strategy.
Limitations for the CFD modeling include the
software used IES VE is a simplified CFD program
that is based more on visual representation, thus
LMA numbers are based on produced contours and
not actual data points. Furthermore, a more complex
system could produce more data per cell to better
understand small air vector characteristics like ed-
dies instead of the general room level airflow analy-
sis. The Standard k-epsilon turbulence models also
is found to over-predicts the gas turbulence kinetic
energy which results to a high turbulence viscosity,
and an estimated over mixing. Thus the result could
be showing slightly better conditions then what actu-
ally exists in the rooms (Tian et al. 2007).
The mathematical equations assumed an hour of
exposure, while many times visitors or staff are in
the areas for shorter periods of time. The quanta
used for Influenza, q = 100, is suggested as a highly
infectious strand. There is controversy over the actu-
al quantum of a disease due to large variance a quan-
ta can have. The quanta itself measures the infec-
tious material present and the pathogenicity of that
material, however the consideration for droplet
evaporation and settlement is still disputed(Wagner
et al. 2009).
The equations are also based on an assumption
that the room air is well mixed and has a proportion-
al distribution of quanta or infectious material
throughout (NOAKES et al. 2006). Due to this as-
sumption the equations were used on the different
zones that have visibly different airflow efficiency as
shown by the CFD models.
Lastly, other airborne diseases could have a sig-
nificantly higher or lower risk of infection based on
their quantum level. A study by Qian estimated that
the SARS quantum level ranged from 2460-4680
contingent on filter efficiency. These quanta levels
are drastically higher than the tested Influenza quan-
ta level and would lead to a faster and more devas-
tating transmission rate (Qian et al. 2009).
5 REFERENCES
Awbi, H., 2003. Ventilation of buildings, Available at:
http://books.google.com/books?hl=en&lr=&id=Nq5XYF
QRFD4C&oi=fnd&pg=PR9&dq=Ventilation+of+buildin
gs&ots=gdXMoJwoz3&sig=NXCPgyMvFiTiXYDBzDl8
Wm-dFBE.
Bartak, M. et al., 2001. Experimental and Numerical Study of
Local Mean Age of Air Numerical Computation of the.
7th International Building Performance Simulation
Association Conference (IBPSA), pp.773–780.
Beggs, C.B., Shepherd, S.J. & Kerr, K.G., 2010. Potential for
airborne transmission of infection in the waiting areas of
healthcare premises: stochastic analysis using a Monte
Carlo model. BMC infectious diseases, 10, p.247.
Brankston, G. et al., 2007. Transmission of influenza A in
human beings. Lancet Infectious Diseases, 7(4), pp.257–
265.
Khankari, K., 2015. Health-Care Patient-Room HVAC Airflow
Patterns. HPAC Engineering.
Li, Y. et al., 2007. Role of ventilation in airborne transmission
of infectious agents in the built environment - A
multidisciplinary systematic review. Indoor Air, 17(1),
pp.2–18.
NOAKES, C.J. et al., 2006. Modelling the transmission of
airborne infections in enclosed spaces. Epidemiology and
Infection, 134(05), p.1082. Available at:
http://www.journals.cambridge.org/abstract_S095026880
6005875.
Qian, H. et al., 2009. Spatial distribution of infection risk of
SARS transmission in a hospital ward. Building and
Environment, 44(8), pp.1651–1658. Available at:
http://dx.doi.org/10.1016/j.buildenv.2008.11.002.
Rudnick, S.N. & Milton, D.K., 2003. Risk of indoor airborne
infection transmission estimated from carbon dioxide
concentration. Indoor air, 13, pp.237–245.
Sayma, A., 2009. Computational Fluid Dynamics, Ventus
Publishing ApS.
Tian, Z.F., Tu, J.Y. & Yeoh, G.H., 2007. CFD Studies of
Indoor Airflow and Contaminant Particle Transportation.
Particulate Science and Technology, 25(6), pp.555–570.
Wagner, B.G., Coburn, B.J. & Blower, S., 2009. Calculating
the potential for within-flight transmission of influenza A
(H1N1). BMC medicine, 7, p.81. Available at:
http://www.pubmedcentral.nih.gov/articlerender.fcgi?arti
d=2813231&tool=pmcentrez&rendertype=abstract.

More Related Content

What's hot

CFD Simulation of Air Conditioning System of the Classroom
CFD Simulation of Air Conditioning System of the ClassroomCFD Simulation of Air Conditioning System of the Classroom
CFD Simulation of Air Conditioning System of the Classroomijtsrd
 
A Computational Investigation of Flow Structure Within a Sinuous Duct
A Computational Investigation of Flow Structure Within a Sinuous DuctA Computational Investigation of Flow Structure Within a Sinuous Duct
A Computational Investigation of Flow Structure Within a Sinuous DuctIJERA Editor
 
Developing Flow Pressure Drop and Friction Factor of Water in Copper Microcha...
Developing Flow Pressure Drop and Friction Factor of Water in Copper Microcha...Developing Flow Pressure Drop and Friction Factor of Water in Copper Microcha...
Developing Flow Pressure Drop and Friction Factor of Water in Copper Microcha...Mirmanto
 
Control of Suddenly Expanded Flow at Low Supersonic Mach Numbers
Control of Suddenly Expanded Flow at Low Supersonic Mach NumbersControl of Suddenly Expanded Flow at Low Supersonic Mach Numbers
Control of Suddenly Expanded Flow at Low Supersonic Mach NumbersIJERA Editor
 
Effect of controlling parameters on heat transfer during spray impingement co...
Effect of controlling parameters on heat transfer during spray impingement co...Effect of controlling parameters on heat transfer during spray impingement co...
Effect of controlling parameters on heat transfer during spray impingement co...BIBHUTI BHUSAN SAMANTARAY
 
Experimental investigation of flow condensation heat transfer in rectangular ...
Experimental investigation of flow condensation heat transfer in rectangular ...Experimental investigation of flow condensation heat transfer in rectangular ...
Experimental investigation of flow condensation heat transfer in rectangular ...IAEME Publication
 
IRJET- Study of Heat Transfer Characteristics for the Flow of Air over a Heat...
IRJET- Study of Heat Transfer Characteristics for the Flow of Air over a Heat...IRJET- Study of Heat Transfer Characteristics for the Flow of Air over a Heat...
IRJET- Study of Heat Transfer Characteristics for the Flow of Air over a Heat...IRJET Journal
 
petro94-00380103
petro94-00380103petro94-00380103
petro94-00380103Reza Naeli
 
Experimental investigation of flow condensation in 'v' shaped minichannel
Experimental investigation of flow condensation in 'v' shaped minichannelExperimental investigation of flow condensation in 'v' shaped minichannel
Experimental investigation of flow condensation in 'v' shaped minichanneleSAT Publishing House
 
New Microsoft Office PowerPoint Presentation
New Microsoft Office PowerPoint PresentationNew Microsoft Office PowerPoint Presentation
New Microsoft Office PowerPoint PresentationSudhir Shinde
 
IRJET- Study of Jet Impingement Heat Transfer
IRJET-  	  Study of Jet Impingement Heat TransferIRJET-  	  Study of Jet Impingement Heat Transfer
IRJET- Study of Jet Impingement Heat TransferIRJET Journal
 
CFD Simulation of Cooling Pipes Distance in The Growing Medium for Hydroponic...
CFD Simulation of Cooling Pipes Distance in The Growing Medium for Hydroponic...CFD Simulation of Cooling Pipes Distance in The Growing Medium for Hydroponic...
CFD Simulation of Cooling Pipes Distance in The Growing Medium for Hydroponic...IJERDJOURNAL
 
Numerical Predictions of Enhanced Impingement Jet Cooling with Ribs and Pins ...
Numerical Predictions of Enhanced Impingement Jet Cooling with Ribs and Pins ...Numerical Predictions of Enhanced Impingement Jet Cooling with Ribs and Pins ...
Numerical Predictions of Enhanced Impingement Jet Cooling with Ribs and Pins ...AZOJETE UNIMAID
 
Effects of Wind Direction on VOC Concentrations in Southeast Kansas
Effects of Wind Direction on VOC  Concentrations in Southeast KansasEffects of Wind Direction on VOC  Concentrations in Southeast Kansas
Effects of Wind Direction on VOC Concentrations in Southeast KansasSergio A. Guerra
 
Numerical investigation of flow characteristics in a
Numerical investigation of flow characteristics in aNumerical investigation of flow characteristics in a
Numerical investigation of flow characteristics in aIAEME Publication
 

What's hot (17)

CFD Simulation of Air Conditioning System of the Classroom
CFD Simulation of Air Conditioning System of the ClassroomCFD Simulation of Air Conditioning System of the Classroom
CFD Simulation of Air Conditioning System of the Classroom
 
A Computational Investigation of Flow Structure Within a Sinuous Duct
A Computational Investigation of Flow Structure Within a Sinuous DuctA Computational Investigation of Flow Structure Within a Sinuous Duct
A Computational Investigation of Flow Structure Within a Sinuous Duct
 
Developing Flow Pressure Drop and Friction Factor of Water in Copper Microcha...
Developing Flow Pressure Drop and Friction Factor of Water in Copper Microcha...Developing Flow Pressure Drop and Friction Factor of Water in Copper Microcha...
Developing Flow Pressure Drop and Friction Factor of Water in Copper Microcha...
 
Control of Suddenly Expanded Flow at Low Supersonic Mach Numbers
Control of Suddenly Expanded Flow at Low Supersonic Mach NumbersControl of Suddenly Expanded Flow at Low Supersonic Mach Numbers
Control of Suddenly Expanded Flow at Low Supersonic Mach Numbers
 
Effect of controlling parameters on heat transfer during spray impingement co...
Effect of controlling parameters on heat transfer during spray impingement co...Effect of controlling parameters on heat transfer during spray impingement co...
Effect of controlling parameters on heat transfer during spray impingement co...
 
At4301239243
At4301239243At4301239243
At4301239243
 
Experimental investigation of flow condensation heat transfer in rectangular ...
Experimental investigation of flow condensation heat transfer in rectangular ...Experimental investigation of flow condensation heat transfer in rectangular ...
Experimental investigation of flow condensation heat transfer in rectangular ...
 
IRJET- Study of Heat Transfer Characteristics for the Flow of Air over a Heat...
IRJET- Study of Heat Transfer Characteristics for the Flow of Air over a Heat...IRJET- Study of Heat Transfer Characteristics for the Flow of Air over a Heat...
IRJET- Study of Heat Transfer Characteristics for the Flow of Air over a Heat...
 
petro94-00380103
petro94-00380103petro94-00380103
petro94-00380103
 
Experimental investigation of flow condensation in 'v' shaped minichannel
Experimental investigation of flow condensation in 'v' shaped minichannelExperimental investigation of flow condensation in 'v' shaped minichannel
Experimental investigation of flow condensation in 'v' shaped minichannel
 
New Microsoft Office PowerPoint Presentation
New Microsoft Office PowerPoint PresentationNew Microsoft Office PowerPoint Presentation
New Microsoft Office PowerPoint Presentation
 
IRJET- Study of Jet Impingement Heat Transfer
IRJET-  	  Study of Jet Impingement Heat TransferIRJET-  	  Study of Jet Impingement Heat Transfer
IRJET- Study of Jet Impingement Heat Transfer
 
CFD Simulation of Cooling Pipes Distance in The Growing Medium for Hydroponic...
CFD Simulation of Cooling Pipes Distance in The Growing Medium for Hydroponic...CFD Simulation of Cooling Pipes Distance in The Growing Medium for Hydroponic...
CFD Simulation of Cooling Pipes Distance in The Growing Medium for Hydroponic...
 
Numerical Predictions of Enhanced Impingement Jet Cooling with Ribs and Pins ...
Numerical Predictions of Enhanced Impingement Jet Cooling with Ribs and Pins ...Numerical Predictions of Enhanced Impingement Jet Cooling with Ribs and Pins ...
Numerical Predictions of Enhanced Impingement Jet Cooling with Ribs and Pins ...
 
DIFFUSER ANGLE CONTROL TO AVOID FLOW SEPARATION
DIFFUSER ANGLE CONTROL TO AVOID FLOW SEPARATIONDIFFUSER ANGLE CONTROL TO AVOID FLOW SEPARATION
DIFFUSER ANGLE CONTROL TO AVOID FLOW SEPARATION
 
Effects of Wind Direction on VOC Concentrations in Southeast Kansas
Effects of Wind Direction on VOC  Concentrations in Southeast KansasEffects of Wind Direction on VOC  Concentrations in Southeast Kansas
Effects of Wind Direction on VOC Concentrations in Southeast Kansas
 
Numerical investigation of flow characteristics in a
Numerical investigation of flow characteristics in aNumerical investigation of flow characteristics in a
Numerical investigation of flow characteristics in a
 

Viewers also liked

Effects of nocturnal ventilation and radiant cooling heating floors on indoor...
Effects of nocturnal ventilation and radiant cooling heating floors on indoor...Effects of nocturnal ventilation and radiant cooling heating floors on indoor...
Effects of nocturnal ventilation and radiant cooling heating floors on indoor...eSAT Publishing House
 
Hvac basics lunch & learn
Hvac basics lunch & learnHvac basics lunch & learn
Hvac basics lunch & learnQaimuddin SODHO
 
HVAC FOR ENERGY EFFICIENT BUILDING
HVAC FOR ENERGY EFFICIENT BUILDINGHVAC FOR ENERGY EFFICIENT BUILDING
HVAC FOR ENERGY EFFICIENT BUILDINGHarsha Singh
 
Service environment
Service environmentService environment
Service environmentPrithvi Ghag
 
Air Conditioning & Hvac Systems
Air Conditioning & Hvac SystemsAir Conditioning & Hvac Systems
Air Conditioning & Hvac SystemsGAURAV. H .TANDON
 
Complete hvac ppt by kk 354647.pptx 1234
Complete hvac ppt by kk 354647.pptx 1234Complete hvac ppt by kk 354647.pptx 1234
Complete hvac ppt by kk 354647.pptx 1234KRISHAN KUMAR
 

Viewers also liked (8)

Effects of nocturnal ventilation and radiant cooling heating floors on indoor...
Effects of nocturnal ventilation and radiant cooling heating floors on indoor...Effects of nocturnal ventilation and radiant cooling heating floors on indoor...
Effects of nocturnal ventilation and radiant cooling heating floors on indoor...
 
Hvac Basics
Hvac Basics Hvac Basics
Hvac Basics
 
Hvac basics lunch & learn
Hvac basics lunch & learnHvac basics lunch & learn
Hvac basics lunch & learn
 
HVAC FOR ENERGY EFFICIENT BUILDING
HVAC FOR ENERGY EFFICIENT BUILDINGHVAC FOR ENERGY EFFICIENT BUILDING
HVAC FOR ENERGY EFFICIENT BUILDING
 
Service environment
Service environmentService environment
Service environment
 
Air Conditioning & Hvac Systems
Air Conditioning & Hvac SystemsAir Conditioning & Hvac Systems
Air Conditioning & Hvac Systems
 
Complete hvac ppt by kk 354647.pptx 1234
Complete hvac ppt by kk 354647.pptx 1234Complete hvac ppt by kk 354647.pptx 1234
Complete hvac ppt by kk 354647.pptx 1234
 
United kingdom
United kingdomUnited kingdom
United kingdom
 

Similar to Copeland_ EAAE ARCC CONFERENCE 2016

MuhammadNadzmibinMohammadNazari_SKMM_Article
MuhammadNadzmibinMohammadNazari_SKMM_ArticleMuhammadNadzmibinMohammadNazari_SKMM_Article
MuhammadNadzmibinMohammadNazari_SKMM_ArticleNadzmi Nazari
 
Indoor air changes and potential implications for SARS-CoV-2 transmission.pdf
Indoor air changes and potential implications for SARS-CoV-2 transmission.pdfIndoor air changes and potential implications for SARS-CoV-2 transmission.pdf
Indoor air changes and potential implications for SARS-CoV-2 transmission.pdfREVIEGAS
 
Modeling of heat and moisture transfer in building using rlf method
Modeling of heat and moisture transfer in building using rlf methodModeling of heat and moisture transfer in building using rlf method
Modeling of heat and moisture transfer in building using rlf methodBasrah University for Oil and Gas
 
Ashrae rp 1301 quantification of ventilation effectiveness
Ashrae rp 1301 quantification of ventilation effectivenessAshrae rp 1301 quantification of ventilation effectiveness
Ashrae rp 1301 quantification of ventilation effectivenessCliff Cooper, MS, CIH
 
Experimental Investigation of Ventilation Effectiveness in an Airliner Cabin ...
Experimental Investigation of Ventilation Effectiveness in an Airliner Cabin ...Experimental Investigation of Ventilation Effectiveness in an Airliner Cabin ...
Experimental Investigation of Ventilation Effectiveness in an Airliner Cabin ...JIGNESH PATEL
 
Proposal Procedure toDesign AnOptimum Ventilation System For Chemical Laboratory
Proposal Procedure toDesign AnOptimum Ventilation System For Chemical LaboratoryProposal Procedure toDesign AnOptimum Ventilation System For Chemical Laboratory
Proposal Procedure toDesign AnOptimum Ventilation System For Chemical LaboratoryIJRESJOURNAL
 
Chapter 9 room ventilation systems (1)
Chapter 9 room ventilation systems (1)Chapter 9 room ventilation systems (1)
Chapter 9 room ventilation systems (1)Imran Sultan
 
Life Cycle Analysis of Multi Split VRF System
Life Cycle Analysis of Multi Split VRF SystemLife Cycle Analysis of Multi Split VRF System
Life Cycle Analysis of Multi Split VRF SystemSYED KHURSHID ALAM ARZOO
 
Modeling and optimization of nebulizers' performance in non-invasive ventilat...
Modeling and optimization of nebulizers' performance in non-invasive ventilat...Modeling and optimization of nebulizers' performance in non-invasive ventilat...
Modeling and optimization of nebulizers' performance in non-invasive ventilat...Ahmed Elberry
 
Cfd analaysis of flow through a conical exhaust
Cfd analaysis of flow through a conical exhaustCfd analaysis of flow through a conical exhaust
Cfd analaysis of flow through a conical exhausteSAT Publishing House
 
MEP Design Project
MEP Design ProjectMEP Design Project
MEP Design ProjectAhmed Medhat
 
PTP 3111 - Hospital Air Distribution Systems (PDF).pdf
PTP 3111 - Hospital Air Distribution Systems (PDF).pdfPTP 3111 - Hospital Air Distribution Systems (PDF).pdf
PTP 3111 - Hospital Air Distribution Systems (PDF).pdfJorgeMarroquin31
 
Energy saving by integrated control of natural ventilation and hvac
Energy saving by integrated control of natural ventilation and hvacEnergy saving by integrated control of natural ventilation and hvac
Energy saving by integrated control of natural ventilation and hvacBasrah University for Oil and Gas
 

Similar to Copeland_ EAAE ARCC CONFERENCE 2016 (20)

Effective Airflow Design
Effective Airflow DesignEffective Airflow Design
Effective Airflow Design
 
MuhammadNadzmibinMohammadNazari_SKMM_Article
MuhammadNadzmibinMohammadNazari_SKMM_ArticleMuhammadNadzmibinMohammadNazari_SKMM_Article
MuhammadNadzmibinMohammadNazari_SKMM_Article
 
Indoor air changes and potential implications for SARS-CoV-2 transmission.pdf
Indoor air changes and potential implications for SARS-CoV-2 transmission.pdfIndoor air changes and potential implications for SARS-CoV-2 transmission.pdf
Indoor air changes and potential implications for SARS-CoV-2 transmission.pdf
 
Modeling of heat and moisture transfer in building using rlf method
Modeling of heat and moisture transfer in building using rlf methodModeling of heat and moisture transfer in building using rlf method
Modeling of heat and moisture transfer in building using rlf method
 
Ashrae rp 1301 quantification of ventilation effectiveness
Ashrae rp 1301 quantification of ventilation effectivenessAshrae rp 1301 quantification of ventilation effectiveness
Ashrae rp 1301 quantification of ventilation effectiveness
 
Experimental Investigation of Ventilation Effectiveness in an Airliner Cabin ...
Experimental Investigation of Ventilation Effectiveness in an Airliner Cabin ...Experimental Investigation of Ventilation Effectiveness in an Airliner Cabin ...
Experimental Investigation of Ventilation Effectiveness in an Airliner Cabin ...
 
Proposal Procedure toDesign AnOptimum Ventilation System For Chemical Laboratory
Proposal Procedure toDesign AnOptimum Ventilation System For Chemical LaboratoryProposal Procedure toDesign AnOptimum Ventilation System For Chemical Laboratory
Proposal Procedure toDesign AnOptimum Ventilation System For Chemical Laboratory
 
Chapter 9 room ventilation systems (1)
Chapter 9 room ventilation systems (1)Chapter 9 room ventilation systems (1)
Chapter 9 room ventilation systems (1)
 
Life Cycle Analysis of Multi Split VRF System
Life Cycle Analysis of Multi Split VRF SystemLife Cycle Analysis of Multi Split VRF System
Life Cycle Analysis of Multi Split VRF System
 
Modeling and optimization of nebulizers' performance in non-invasive ventilat...
Modeling and optimization of nebulizers' performance in non-invasive ventilat...Modeling and optimization of nebulizers' performance in non-invasive ventilat...
Modeling and optimization of nebulizers' performance in non-invasive ventilat...
 
s41742-020-00286-x.pdf
s41742-020-00286-x.pdfs41742-020-00286-x.pdf
s41742-020-00286-x.pdf
 
Cadd semi 2
Cadd semi 2Cadd semi 2
Cadd semi 2
 
Cfd analaysis of flow through a conical exhaust
Cfd analaysis of flow through a conical exhaustCfd analaysis of flow through a conical exhaust
Cfd analaysis of flow through a conical exhaust
 
Project report1
Project report1Project report1
Project report1
 
MEP Design Project
MEP Design ProjectMEP Design Project
MEP Design Project
 
VPOD
VPODVPOD
VPOD
 
Air impingement technologyfor food processing
Air impingement technologyfor food processingAir impingement technologyfor food processing
Air impingement technologyfor food processing
 
30120130405023
3012013040502330120130405023
30120130405023
 
PTP 3111 - Hospital Air Distribution Systems (PDF).pdf
PTP 3111 - Hospital Air Distribution Systems (PDF).pdfPTP 3111 - Hospital Air Distribution Systems (PDF).pdf
PTP 3111 - Hospital Air Distribution Systems (PDF).pdf
 
Energy saving by integrated control of natural ventilation and hvac
Energy saving by integrated control of natural ventilation and hvacEnergy saving by integrated control of natural ventilation and hvac
Energy saving by integrated control of natural ventilation and hvac
 

Copeland_ EAAE ARCC CONFERENCE 2016

  • 1. 1 INTRODUCTION Today’s regulatory air quality standards for healthcare facilities effectively maintain heating, cooling, and ventilation requirements within acute patient room by fulfilling overall air change rates. American Society of Heating, Refrigeration, and Air conditioning Engineers or ASHRAE require that air changes occur to keep fresh air continuously enter- ing spaces, however this guideline does not suggest how to effectively remove contaminated air that may be caught in dead zones effected by room design. The standard does not consider that the air being mixed in the ventilated spaces is allowing clean air to be mixed with contaminated air. These airflow patterns created by the ventilation contribute to air-temperature, distribution, thermal comfort, air quality, and the possibility of airborne pathogen transmission within a space or spaces. Air- flow patterns of existing rooms need to be studied in order to understand pre-existing relationships be- tween location and type of supply diffusers, supply airflow rates, supply temperature, air return location and size, infiltration, furniture arrangement, heat sources and location of the patient and others in the room. An example used to look at risk of infection due to room design is Influenza. Influenza was chosen in part because of its seasonal and continued yearly ef- fects on populations as well as its lower quantum level. The quantum level explained more fully in the risk assessment method portion, is a measure of the infectious material present and the pathogenicity of that material (Wagner et al. 2009). Other airborne threats such as Tuberculosis, and SARS would yield a larger quanta production rate. Studies have been done proving influenza as an airborne threat within hospitals at close range like that in patient rooms (Blachere et al. 2009, Brankston et al. 2007). However, there have only been a few significant studies showing how airflow patterns can be affected by supply and return vents as well as room configuration. A review article lead by Dr. Yuguo Li in 2007 found only 40 studies fo- cusing on ventilations impact on airborne transmis- sion in the built environment databased between 1960 and 2005. Of these forty studies only ten were deemed conclusive by a team of multidisciplinary reviewers. These conclusive studies had met the teams determined evidentiary threshold, and provide strong evidence on ventilation effects of airborne transmission of diseases including Tuberculosis, SARS, Influenza and chickenpox(Li et al. 2007). Most recently a study using computational fluid dynamic modeling was completed by Khankari. Two mechanical placements were tested in one patient room to show resultant airflow patterns (Khankari 2015). The information gathered from this study can be significantly furthered by looking at two common The impact of patient room design on airborne Hospital-Acquired Infections A. Copeland & A. Sharag-Eldin Kent State University, Kent, Ohio, United States ABSTRACT: Transmission of airborne diseases in healthcare facilities is an increasingly important concern. This, in part, is due to the reduction in funding from insurance companies for hospital-acquired infections (HAI) and the consequent economic impact of an influenza outbreak in a hospital. With increasing cases of HAI in the USA, it became necessary to examine the current ventilation standards for healthcare facilities. While design guidelines have focused on recommending appropriate ventilation rates, it ignored the delivery of conditioned air to occupied spaces and the impact of room layout relative to the placement of air supply and return. The paper will also estimate the probability of infection based on air change effectiveness, and the rela- tive spatial relationship between HVAC air delivery system and room design. The resulting outcome is a guideline intended to support health facility designers.
  • 2. patient room designs and computational fluid dy- namic models to test a plethora of supply and return air locations in relation to patient, caregiver and door. The following study using a calibrated model veri- fied by field measurements of air distribution pat- terns in patient rooms. In addition to airflow pat- terns, the CFD algorithm is used to determine the age of the air to measure the effectiveness of the recommended air changes in the standards delineat- ing through graphical and numerical means the po- tential location for concentrated airborne contamina- tion. It is also intended to encourage the development of design codes and standards that take into account airborne pathogen transmission in plac- es where the patient is most vulnerable to infection from visitors or staff. 2 RESEARCH METHOD 2.1 Room Criteria and Selection The geometries selected and tested in this paper cor- respond with the general trends in the healthcare de- sign field. While shapes and sizes of rooms can dif- fer drastically, three average room sizes were selected to correspond with small, medium and large patient room sizes. The room sizes are as following 21.4 m2 (230 ft2), 27.87 m2 (300 ft2 ) and 34.84 m2 (375 ft2 ) all inclu- sive. The sizes address the possibility of the imple- mentation of universal or acuity adaptable rooms in all sizes and critical care patients in the larger room size (Brown & Gallant, 2006). The patient rooms used for the simulation follow the FGI Guidelines for Hospitals and Outpatient Facili- ties 2014, thus having private bathrooms, and glaz- ing that is no less than 8% of the floor area of the room served (2014 FGI Guidelines for Hospitals and Outpatient Facilities 2014). Each room tested is rectangular in shape and pro- pose either an inboard bathroom located at the en- trance of the patient room or outboard bathroom, lo- cated along the exterior wall of the room and building. The bathrooms are placed on the headwall, or where the patients head is located near the wall in bed with supply air being placed above the patient bed and return located near the door to the patient room. The supply diffuser is a 4 way diffuser supply air at 360 degrees at 6 air changes per hour calculat- ed by room’s volume from finish floor to 6ft above. 2.2 Computational Fluid Dynamic Modeling Computational Fluid Dynamic Simulation focuses on the numerical and algorithm modelling of fluid flow and heat transfer processes. Given boundary conditions including climate, internal energy sources, and HVAC systems CFD simulates a build- ing’s likely internal or external airflow. The numerical solution of the airflow simulation uses differential equations to find values of flow quantities at certain points of a system. These values are then converted to a system of algebraic equation that represent the interdependency of the flow at each point (Sayma 2009). The points correspond to a grid or mesh used by the modelling system. 2.3 CFD Modeling IES VE has been tested and fully validated under ASHRAE Standard 140. The IES VE program al- lows for dynamic thermal simulation, including de- sign load calculations, and simplified computational fluid dynamic modelling. IES VE primarily focuses on integrated graphics-driven results, however does allow for simple numerical analysis based on points located within the graphic model. IES VE uses the k-epsilon turbulence model to find the turbulent viscosity of a 3D space. The standard k-epsilon model is widely accepted due to its applicability to wide ranging flow situations pri- marily looking at internal flows with weak stream- line curvature models. The equation solves for the kinetic energy turbulence and the dissipation of the kinetic energy (Awbi 2003). While the standard k-epsilon turbulence model is accepted it has limitations when more complex flows are being studied and the length scale for the determination of turbulence can only be speculated. The RNG k-ε or renormalization group model and low Reynolds number k-ε model are more accurate when looking at forced convection or mixed convec- tion turbulence models while the Large Eddy- Simulation (LES) model is a more accurate predictor of flows with strong streamline curvatures (Awbi 2003). IES VE’s MicroFlo 3D Computational Fluid Dy- namic modeling application was used to simulate different conditions. Boundary conditions such as America’s northeast climate were applied to the model through the apache application that uses weather data to provide an environment for the eval- uation of a building and system design. Thermal comfort conditions were regulated by specifying HVAC system and placement based on ASHRAE
  • 3. 170, 2013 healthcare patient room standards includ- ing required air changes per hour (ACH) and humid- ity. MicroFlo produces visual representation of an in- ternal space’s airflow based on velocity, concentra- tion of CO2 and local mean age of air. Local mean age of air (LMA) is the amount of time a parcel of air has been in certain areas of the simulation space. Higher values indicated areas with poor ventilation. 2.4 Calibration In order to calibrate IES VE an educational nursing simulation room was tested with field measurements to prove that results gathered from IES VE would be correct. The nursing simulation room was located in Northeast Ohio and had an overall area of 34.19 m2 (368 ft2 ). The field measurements were taken on two days November 2nd and November 23rd, 2015. Figure 1. (Left) Simulation room layout, (Right) simulation room ceiling plan 2.4.1 Field Measurements Field measurements were performed in the nursing simulation room, 5.43 m (17.83 ft.) (L) x 6.4 m (21.0 ft.) (W) x 3.05 m (10 ft.) (H), with the bed lo- cated on the same wall as the bathroom shown in figure 1. The air is supplied and returned through linear slot diffusers located at the ceiling. The room is illuminated by six 2’x4’ fluorescent lights, one lo- cated within the bathroom. Measurements were tak- en at 3’ grid intervals at .15 m (6in.), 1.1 m (3.5 ft.), 1.8 m (6ft.) above the floor using TSI indoor air quality meters model 8386A and 8760 to gather temperature, humidity, carbon dioxide and air veloc- ity at nine specific points. The boundary conditions that would be completed by IES VE were also collected like wall surface temperature, outside temperature and weather. IES VE run of simulation room. The simulation room’s CFD run had boundary conditions collected from the field measurements, including outside tem- perature as well as surface temperatures. The supply air was delivered through slot diffusers that was equivalent to 360 cfm, approximately 6 ACH. The simulation room also used perimeter radiators locat- ed on the exterior walls, causing higher surface tem- peratures on the respective walls. 2.5 CFD Runs of Patient Rooms The selected six room designs for patient rooms were tested through IES VE, similar to the simula- tion room specific data was collected through the micro flow runs at three specific heights .15 m (6in.), 1.1 m (3.5 ft.), 1.8 m (6ft.). Each room was supplied with 6 ACH, the required ACH per ASHRAE 170. This required 252 cfm for the small, 315 cfm for the medium, and 400 cfm for the large patient room’s in order to satisfy the required 6 ACH. The results all pertain the same climatic influence, boundary conditions that coincide with February 8th. Each result is reflecting sixty minutes of time, the length of time for the required amount of air changes to take place. Table 1: Boundary Conditions for Patient Rooms Flowrate Temperature CFM* °F °C Small Room 252 70 21.1 Medium Room 315 70 21.1 Large Room 400 70 21.1 *CFM based on required 6 air changes/ hour per ASHRAE 170 2.6 Data Analysis 2.6.1 Risk Assessment: Wells-Riley Equation vs. Gammaitoni-Nucci Equation Local mean age of air and Velocity of air vectors in the different patient rooms are analyzed to see if any significant differences were seen in different room size or layouts. The risk of transmission is evaluated using the steady state Wells-Riley equation and non-steady state Gammaitoni-Nucci equation. Exposure times can vary in patient rooms from days for a patient, to as little as a few minutes for a staff member, thus the risk of transmission is influenced by chance events (Beggs et al. 2010). The Gammaitoni-Nucci equation is a modified version of the Wells-Riley equation that reflects the exponential increase in number of new cases of in- fections in a room. The Gammaitoni-Nucci equation takes into consideration the transient behavior of transmission over shorter periods of time, and that
  • 4. not every newly infected person may infect another due to their short time in a particular space (NOAKES et al. 2006). The equation considers room volume, which varies per room size, ventila- tion rate, and the quanta production rate. The quanta production rate is best explained as the infections dose required to infect 63.2% of the people in the af- filiated enclosed space. The mean quanta production rate for influenza that is used for the Gammaitoni-Nucci equation is 100.0 quanta/h, a value for a highly contagious case (Rudnick & Milton 2003). However, there is still dispute over an official range of quanta production rate for Influenza, as found by Rudnick and Milton it can vary from 15-128 q/h depending on which steady or non-steady state Wells-Riley equation used to determine the quanta production rate. The equation assumes ventilation as a large factor in particle removal, while it is a significant source, many other sources also factor in pathogen settle- ment (Rudnick & Milton, 2003). For Influenza A, a large factor in pathogen removal is inactivation through settling, thus removed from the air but not the space entirely. The equations do not take into consideration that outside factors such as tempera- ture, humidity and settling can have an impact on a person’s risk of airborne infection. Table 2: Simulation Room CFD Simulation compared to field measurements 3 RESULTS Each CFD run resulted in velocity quantities and lo- cal mean age of air approximations that differed based on room size and layout, inboard vs. outboard. The LMA or local mean age of air and known vol- ume of the rooms were then used for a risk analysis of Influenza A in those respective rooms using the Wells-Riley and Gammaitoni-Nucci equations. 3.1 Simulation Room CFD Run The simulation room’s CFD model ran closely to the documented field notes. The boundary conditions were controlled by the data taken from the field measurement like, surface temperature and input air temperature. Table 2 shows the averages for each differing height level for the simulation room CFD model compared to that of the field measurements. 3.2 Room Comparison 3.2.1 Size The selected rooms varied in three sizes considered small, medium and large. Figure 2 shows the differ- ences of air age in the different patient rooms. Over- all the size did not have a large impact on velocity and air age, rather design had an impact on the mean air age at different areas within the room. 3.2.2 Layout 3.2.2.1 Inboard Patient Room The inboard CFD model show that the air is circu- lated relatively consistently among all room sizes and the local mean age of air is similar throughout the rooms, ranging from 10.9 minutes to 12.7 minutes. Local mean age of air is older or higher in the bathroom if the door remains open, resulting in Height Average Velocity - Simulation Average Velocity - Field Measurements ft.-in. ft. /mins. ft. /mins. 0'-6" 4.74 5.625 3'-6" 8.15 10.375 6'-0" 12.11 12.5 Figure 2. Small outboard room (left: 0’-6” AFF, middle: 3’-6” AFF, right: 6’-0” AFF) LMA in minutes
  • 5. air age of 14.5 minutes. This on average would ap- proximately result in 6 ACH per hour, each air change taking on average 10 minutes. 3.2.2.2 Outboard Patient Room The outboard patient room is relatively different when it comes to local mean age of air throughout the space. The CFD model shows that the back zone in all the outboard rooms have older air parcels as shown in figure 2. This area has an air that is an av- erage of 15 minutes old, which would be the equiva- lent of 4 ACH, while the area around the patient bed has an average air age of 10.5 minutes which would result in the required 6ACH. This air change discrepancy is significant the risk of transmission will significantly increase in the are- as of poor circulation. The following mathematical risk assessments show the increased risk associated with the poor circulation. 3.3 Risk Assessment The Wells-Riley steady rate and Gammaitoni-Nucci non-steady rate are mathematical models that predict the rate of airborne transmission. The Gammaitoni- Nucci model is better suited for short term exposure models, however both will be used and compared to understand the risk of transmission. Each room is analyzed using the average ACH, thus the outboard will be broken into zones and analyzed according to the different LMA associated with the different zones of the room. The differing LMA would result in a different ventilation rate for that space, so in- stead of the required 6 ACH there may be less in poorly ventilated areas. 3.4 Local Mean Age of Air The mathematical risk models predict the transmis- sion of airborne disease and are based off of flow rate or the ACH. However, a dimensionless equation that shows how efficiently different room airflow structures remove contaminants regardless of the flow rate can also be utilized (Bartak et al. 2001). The following table 3 shows the efficiency of the air- flows in the six rooms. The outboard rooms were broken into different volumes based on average local air age to understand the changing efficiency rates with relation to the local mean age of air at points within the room. 3.5 Comparison between Mathematical Risk Assessment Models It is important to understand the above table shows three drastically different equations, and in turn drastically different results. The Wells-Riley re- sults show the potential for new cases in exponential increase or decreasing form. If the results are less than 1 (a < 1) the pathogen would be removed or settled before infecting any of the susceptible targets, while the results that are greater than 1 (a > 1) would result in increasing pathogen transmission. There- fore, the zones that were identified as poorly venti- lated in the outboard design have an increasing chance of infection, while the inboard room and bet- ter ventilated areas in the outboard would not. The Gammaitoni-Nucci results are based on per- centages, thus the results that are shown as decimals, could also be shown as the equivalent percentage (i.e. large inboard: 0.0611= 6.11%). Again, like the Wells-Riley model the inboard rooms have well mixed air resulting in a low percentage of people that will contract Influenza through the airborne Table 3: Mathematical Risk Assessment Models and Efficiency of Airflow in Patient Rooms Room Design and Zone Wells-Riley * Wells-Riley with required 6 ACH Gammaitoni- Nucci Gammaitoni- Nucci with re- quired 6 ACH Airflow Efficiency (Bartak et al., 2001)** Small Outboard 0.1061 43.89 m3 @ 10.5 LMA 0.9451 0.1560 2.0170 27.47 m3 @ 15 LMA 1.7696 0.5303 0.3544 10.61% 4.6040 Small Inboard 0.6045 0.0991 1.3588 Medium Outboard 0.0858 69.38 m3 @ 11.5 LMA 0.6206 0.1017 1.1147 19.82 m3 @ 13 LMA 2.0399 0.4289 0.3376 8.58% 4.4109 Medium Inboard 0.4898 0.0801 0.8670 Large Outboard 0.0682 91.17 m3 @ 10.9 LMA 0.4564 0.0754 0.6332 22.1 m3 @ 14.5 LMA 2.0411 0.3410 0.4087 6.82% 3.4752 Large Inboard 0.3708 0.0611 0.5097 * Solves for P, a dimensionless exponential increase of new cases ** The lower the number the higher the efficiency of airflow
  • 6. route. Contrastingly, the particular outboard room zones that have nominal ventilation result in a prob- ability of infection of 35-40%. It is important to note that this model looked at the probability of an indi- vidual who has been in the room with the infected for an hour. Furthermore, if 15 minutes was used as the expo- sure time rather than an hour the probability of a susceptible person being infected would decrease (i.e. Small outboard patient room, the poorly venti- lated area decrease by 86% from a 35% probability of infection to a 5% probability). The required 6 ACH in a well-mixed and ventilated room would drastically decrease the probability of a person be- coming infected, however depending on room design certain areas are not getting properly ventilated and the air age is increasing. Lastly, the equation used by Bartak and others takes the relationship between air age in the room of certain volumes to find the efficiency of the airflow, while not considering the ventilation rate. Similar to the Gammaitoni-Nucci model, if 6 ACH were achieved everywhere in the room regardless of the design, the airflow efficiency in the rooms would be improved. 4 DISCUSSION AND CONCLUSION 4.1 Significance The main regulatory source for healthcare facilities’ ventilation systems is ASHRAE 170, it is also in- cluded as part of the FGI Guidelines for Hospitals and Outpatient Facilities 2014. According to ASHRAE, non-critical patient rooms should receive 6 ACH, with a minimum of 2 outdoor ACH. Many studies have been completed that have been the basis of ASHRAEs regulations that dictate 6 ACH. How- ever, from this study not all patient rooms can be considered suitable with 6 ACH. The design has to be taken into consideration when writing and con- sidering minimum ventilation standards. While the airflow in the inboard patient rooms were effective shown by the local mean age of air, the outboard patient room airflow was less then ef- fective for circulating fresh air. The rooms tested were linear in design and less suitable room designs may be found if tested. The outboard design’s least effective space is what is used for family and visitor zones. The regu- lations primarily have supply outlets located over the patient beds to protect the patient from airborne in- fection. However, this leaves visitors and staff more susceptible to airborne infection like Influenza A as well as other more transmissible diseases. The airflow effectiveness is important to prevent airborne disease within the room. As seen using the mathematical risk assessment models the air age has a large impact on Influenza A infection probability. Thus, ventilation with room design in considera- tion can effectively be a primary measure against airborne infections like Influenza A or other airborne disease. However ventilation regulation needs to fo- cus on how design impacts spaces and its result on the ventilation needs. 4.2 Limitations and considerations This study primarily focused on two designs of pa- tient rooms which leaves a lot of geometry’s untest- ed, thus it would be suggested that room designs are tested to understand ventilation properties for better efficiency and prevention measures The supply and return air were also only tested at one location with the supply air above the patient bed and the return near the exit. Other placement could have shown more effective ventilation strate- gies, and should be considered to maximize effective airflow. While other ventilation strategies should be explored, 6 ACH have been found to be adequate as long as the room is receiving the adequate airflow that allows for the required ACH, thus possible add- ed supply to evenly distribute air may also be an ide- al strategy. Limitations for the CFD modeling include the software used IES VE is a simplified CFD program that is based more on visual representation, thus LMA numbers are based on produced contours and not actual data points. Furthermore, a more complex system could produce more data per cell to better understand small air vector characteristics like ed- dies instead of the general room level airflow analy- sis. The Standard k-epsilon turbulence models also is found to over-predicts the gas turbulence kinetic energy which results to a high turbulence viscosity, and an estimated over mixing. Thus the result could be showing slightly better conditions then what actu- ally exists in the rooms (Tian et al. 2007). The mathematical equations assumed an hour of exposure, while many times visitors or staff are in the areas for shorter periods of time. The quanta used for Influenza, q = 100, is suggested as a highly infectious strand. There is controversy over the actu- al quantum of a disease due to large variance a quan- ta can have. The quanta itself measures the infec- tious material present and the pathogenicity of that material, however the consideration for droplet evaporation and settlement is still disputed(Wagner et al. 2009). The equations are also based on an assumption that the room air is well mixed and has a proportion- al distribution of quanta or infectious material throughout (NOAKES et al. 2006). Due to this as- sumption the equations were used on the different zones that have visibly different airflow efficiency as shown by the CFD models. Lastly, other airborne diseases could have a sig- nificantly higher or lower risk of infection based on
  • 7. their quantum level. A study by Qian estimated that the SARS quantum level ranged from 2460-4680 contingent on filter efficiency. These quanta levels are drastically higher than the tested Influenza quan- ta level and would lead to a faster and more devas- tating transmission rate (Qian et al. 2009). 5 REFERENCES Awbi, H., 2003. Ventilation of buildings, Available at: http://books.google.com/books?hl=en&lr=&id=Nq5XYF QRFD4C&oi=fnd&pg=PR9&dq=Ventilation+of+buildin gs&ots=gdXMoJwoz3&sig=NXCPgyMvFiTiXYDBzDl8 Wm-dFBE. Bartak, M. et al., 2001. Experimental and Numerical Study of Local Mean Age of Air Numerical Computation of the. 7th International Building Performance Simulation Association Conference (IBPSA), pp.773–780. Beggs, C.B., Shepherd, S.J. & Kerr, K.G., 2010. Potential for airborne transmission of infection in the waiting areas of healthcare premises: stochastic analysis using a Monte Carlo model. BMC infectious diseases, 10, p.247. Brankston, G. et al., 2007. Transmission of influenza A in human beings. Lancet Infectious Diseases, 7(4), pp.257– 265. Khankari, K., 2015. Health-Care Patient-Room HVAC Airflow Patterns. HPAC Engineering. Li, Y. et al., 2007. Role of ventilation in airborne transmission of infectious agents in the built environment - A multidisciplinary systematic review. Indoor Air, 17(1), pp.2–18. NOAKES, C.J. et al., 2006. Modelling the transmission of airborne infections in enclosed spaces. Epidemiology and Infection, 134(05), p.1082. Available at: http://www.journals.cambridge.org/abstract_S095026880 6005875. Qian, H. et al., 2009. Spatial distribution of infection risk of SARS transmission in a hospital ward. Building and Environment, 44(8), pp.1651–1658. Available at: http://dx.doi.org/10.1016/j.buildenv.2008.11.002. Rudnick, S.N. & Milton, D.K., 2003. Risk of indoor airborne infection transmission estimated from carbon dioxide concentration. Indoor air, 13, pp.237–245. Sayma, A., 2009. Computational Fluid Dynamics, Ventus Publishing ApS. Tian, Z.F., Tu, J.Y. & Yeoh, G.H., 2007. CFD Studies of Indoor Airflow and Contaminant Particle Transportation. Particulate Science and Technology, 25(6), pp.555–570. Wagner, B.G., Coburn, B.J. & Blower, S., 2009. Calculating the potential for within-flight transmission of influenza A (H1N1). BMC medicine, 7, p.81. Available at: http://www.pubmedcentral.nih.gov/articlerender.fcgi?arti d=2813231&tool=pmcentrez&rendertype=abstract.