International Journal of Environmental Research (2020) 14:685–692
https://doi.org/10.1007/s41742-020-00286-x
RESEARCH PAPER
Impact of Filtration Conditions on Air Quality in an Operating Room
Marcelo Luiz Pereira1
· Rogério Vilain1
· Patricia Rocha Kawase1
· Arlindo Tribess2
· Lidia Morawska3
Received: 13 March 2020 / Revised: 10 September 2020 / Accepted: 3 October 2020 / Published online: 23 October 2020
© University of Tehran 2020
Abstract
The aim of this study was to assess the impact of ventilation and filtration conditions on particle concentrations in an ortho-
pedic operating room. Total particle, viable particle, and ­
CO2 concentration were measured under three different situations,
namely before air filter replacement, after air filter replacement, and in an operating room with a new air conditioning system.
Before air filter replacement, the mean values of airflow, total particle concentration, and viable particle concentration were
706 ­m3
/h, 15.0×106
±4.0×106
particles/m3
, and 57 CFU/m3
, respectively. After replacement, the airflow increased to 1954
­m3
/h, and total and viable particle concentrations decreased to 0.4×106
±0.2×106
particles/m3
and 24 CFU/m3
, respectively.
In the room with a new air conditioning system, the airflow was 2051 ­
m3
/h, and total and viable particle concentrations were
0.3×106.
±0.1×106
particles/m3
and 15 CFU/m3
, respectively. The ­
CO2 levels were 663 ppm (before), 659 ppm (after), and
574 ppm (new room). The results showed that inappropriate or no maintenance of filters in an air conditioning system had
significant negative effects on indoor air quality in operating rooms. Air conditioning systems operating with saturated filters
can be affected by pressure drop, which can lead to a reduction in airflow, thereby resulting in an increase in the average total
particle and viable particle concentrations and the risk of infection in operating rooms. However, the results showed that the
­CO2 concentration was not affected by the filter replacement.
Article Highlights
• Improper maintenance of the air filters poses negative effects in operating rooms.
• Particles remain inside the room with less air exchange caused by saturated filters.
• Change in filters produces a greater effect on air quality in operating rooms.
• CO2 concentration generated by the people may not be affected by the filter replacement.
Keywords Indoor particles · Total particle · Viable particle · CO2 concentration · Filtration system · Operating room
Introduction
Indoor air quality in operating rooms is a matter of great
concern for patients and medical personnel (Dascalaki et al.
2008), especially because of the presence of a vast array of
air contaminants, such as chemicals from medical gases used
for anesthesia, disinfection and sterilizing substances, and
particles of skin debris, lint, respiratory droplets, and aero-
sols (Gormley et al. 2017). Given this diversity of sources,
knowledge of the variation in indoor particle concentrations
in operating rooms as well as the factors that affect these var-
iations are important to control the incidence of surgical site
infections. According to Pereira et al. (2012), a decrease in
particle concentrations can result in a decrease in the number
of carriers of organic or microbiological agents in operating
rooms and can consequently decrease the risk of infection.
Microbiological contamination of operating room air,
which is commonly caused by contaminated skin scales
released by the surgical team, is generally considered to
be the main risk factor for surgical site infection in clean
* Marcelo Luiz Pereira
marcelo.pereira@ifsc.edu.br
1
Instituto Federal de Educacao Ciencia e Tecnologia de Santa
Catarina, São José, Santa Catarina, Brazil
2
Department of MechanicalEngineering, Polytechnic School
of the University of São Paulo, São Paulo, São Paulo, Brazil
3
International Laboratory for Air Quality and Health,
Queensland University of Technology, Brisbane, Queensland,
Australia
686 International Journal of Environmental Research (2020) 14:685–692
1 3
surgeries (Pereira et al. 2013; Landrin et al. 2005). For
example, bacteria such as Staphylococcus aureus are con-
tinuously released into the air by operating room personnel
and can subsequently precipitate onto the surgical site. These
organisms cause the majority of infections in prosthetic
implant surgeries, such as hip and knee replacements (Gos-
den et al. 1998). Additionally, according to their size, many
microorganisms that are present in an operating room can
be broadly classified, as follows: bacterial cells and spores
(0.3–10 μm in diameter), fungal spores (2.0–5.0 μm), and
viruses (0.02–0.30 μm) (Morawska, 2006; Fernstrom and
Goldblatt 2013).
Filtration and air exchange with the outdoor air plays a
key role in maintaining acceptable air quality in operating
rooms. Indoor particle concentrations can be decreased by
exhausting and diluting the return air with outdoor air (Sim-
mons et al. 1997; Cole and Cook 1998). By means of air
renewal, a significant decrease in the pollutants generated in
the room can be obtained to keep them below the threshold
levels. Dilution ventilation requires the system to condition
the outdoor air before it is introduced into the room. Out-
door air usually contains contaminants, such as bacteria,
pollen, insects, soot, ash, and dust. These contaminants can
penetrate buildings, thereby influencing indoor particle con-
centrations. Filtration systems constitute a very important
defense against outdoor air pollution, especially in environ-
ments that demand a large amount of external air, such as
operating rooms. The filtration systems must protect the sur-
gical wound, sterile equipment, and occupants against the
dangerous effects of outdoor and/or return particles (Pereira
et al. 2012). However, mechanical ventilation systems are
only effective if the filters are frequently replaced and if the
ventilation system is properly maintained. In other words,
most of the pollutants from outdoor and/or return air can
be effectively removed if the filtration system is properly
designed, installed, and well-maintained, which can further
aid in improving building cleanliness and air conditioning
system efficiency. Some studies suggest that the air condi-
tioning system and its components, such as the air filter and
air-handling system, are often poorly maintained and can
be an ideal environment for microbial growth (Pereira et al.
2017; Jamariska et al. 2000).
Despite the importance of environmental hygiene in hos-
pitals (Beggs 2003; Pereira et al. 2017), few studies have
focused on the impact of maintenance of air conditioning
filters on particle concentrations in operating rooms; the
existing information on this topic is limited. Consequently,
it is common to find many hospitals with insufficient main-
tenance or lack of filter substitution, which has serious con-
sequences, particularly for patients.
Air contamination caused by saturated filters is also a seri-
ous health hazard for operating room occupants, especially
during orthopedic surgeries that have high production of
smoke and aerosols due to the use of tools, such as electro-
surgical apparatus, bone saws, and drills. These aerosols are
spread over the operating room, thereby contaminating the
animate and inanimate environmental surfaces (Chow and
Yang 2004; Nogler et al. 2001). According to Stetzenbach
et al. (2004), airborne microorganisms are a health hazard
when present in high concentrations in indoor environments,
thereby resulting in health problems.
Another aspect that has been highlighted regarding the use
of saturated filters is that humidity and the presence of organic
matter on the filter surface can serve as a source of carbon and
energy, thereby enabling microbes to grow (Maus et al. 2001).
Simmons and Crow (1995) showed that molds can grow in
fibrous filter media provided the relative humidity of the air
is above 70–80% and/or atmospheric dust is present in the
filter media.
It is also important to note that saturated filters make air
conditioning systems operate beyond their foreseen capacity,
thereby increasing energy consumption and equipment main-
tenance costs (Hanley et al. 1994; Offermann et al. 1992; Fisk
et al. 2002; CDC 2003).
To prevent HVAC (heating, ventilation, and air condi-
tioning) performance degradation and malfunction that can
increase energy consumption, air filters need to be replaced
periodically. However, the criteria and the frequency of filter
replacement can vary due to the fluctuation in the debris-accu-
mulation rate in the air filters. Current manufacturers recom-
mend the replacement of air filters every 3 months (Alsaleem
et al. 2016). In the case of high-efficiency filters, this criterion
is not feasible due to the costs involved. Thus, many installa-
tions with high-efficiency filters use monitoring of the pressure
drop increase through the filters or the electric current increase
on the fans (Yang et al. 2007).
Normally, the level of ­
CO2 that is generated in rooms can
be considered as a good indicator of the efficiency of the air
conditioning system in the process of air renewal (Spagnoli
et al. 1996).CO2 is a metabolic gas that is expelled naturally as
a human respirational sub-product. Indoors, the recommended
limits should be below 1000 ppm (ASHRAE 2019). According
to Karthikeyan and Samuel (2008), ­CO2 concentration can also
be an indirect indicator of the occurrence of post-operative
wound infections.
Few published studies have examined the impact of filtra-
tion conditions on particle and ­
CO2 concentration levels in
operating rooms.
In this context, to identify the impact of the filtration system
on indoor contamination in an orthopedic operating room, we
measured the total particle, viable particle, and ­
CO2 concen-
tration in an old operating room before and after the air con-
ditioning filters were replaced as well as in a new operating
room that had a new filter and normal airflow.
687
International Journal of Environmental Research (2020) 14:685–692
1 3
Methodology
The study was conducted in an orthopedic hospital located
in São Paulo, Brazil, and was approved by the Ethics Com-
mittee of the Institute of Orthopedics and Traumatology
under protocol number 109506.
Study Design
This study was conducted in two operating rooms: one in
which the air filter of the HVAC system was poorly main-
tained. In this room, the filter of the HVAC system was
replaced every year. However, due to contract problems
with the maintenance company, the HVAC system had been
running for approximately four and a half months without
a filter replacement. The other operating room had a newly
installed HVAC system. Both rooms were placed in the same
surgery center.
The first round of measurements was performed 2 weeks
before the filters were replaced (Case 1), that is, approxi-
mately 4 months after the filter replacement period had
expired. The second set of measurements was carried out
1 week after filter replacement (Case 2). The results obtained
in Cases 1 and 2 were compared with the measurements in
another operating room with a new HVAC system (Case 3).
Both operating rooms had the same layout: the room area
was approximately 28 ­
m2
with a height of 2.7 m (Fig. 1);
they were designed according to the Brazilian standard
ABNT NBR 7256 (ABNT 2005) (Table 1).
The distribution system in both rooms was laminar
(unidirectional) and the a filter package with three filters
was used: first filter with an efficiency of 30%, second
filter with an efficiency of 90%, and a third filter, with
absolute filtration [high-efficiency particulate air (HEPA)].
The system operated at an air renewal rate of 30% of the
outdoor air.
Five major orthopedic surgeries were conducted for
each of these cases. In ­
thi
s study, all measurements were
performed under the same conditions for the three cases.
In other words, all measurements were performed dur-
ing similar surgeries, involving approximately the same
number of people inside the room. In addition, during the
measurements, all the doors of the operating room were
kept closed, eliminating the possibility of infiltration of
pollutants from adjacent areas.
Fig. 1  Operating room layout
Table 1  Brazilian standard ABNT NBR 7256 recommendation
688 International Journal of Environmental Research (2020) 14:685–692
1 3
Measurement of Total Particle Concentration
and Size
Measurements of particle concentrations were conducted
using real-time, size-resolved optical particle counters,
which were calibrated by the manufacturer (Met One,
Model HHPC-6). These portable (27 × 10 × 5 cm) particle
counters have a flow rate of 2.83 L/min, which is able to
measure the particle number concentration in the follow-
ing range: 0.3–0.5 µm, 0.5–1.0 µm, 1.0–3.0 µm, 3–5 µm,
5–10 µm and > 10 µm. Since the aim of the present study
was to analyze the impact of filtration conditions on air
quality, the results in terms of particles were reported as
the sum of the concentrations measured for all six channels
(0.3–10.0 µm), which represent the size range of typical
airborne infectious particles in operating rooms.
For each surgery, measurements were recorded every
5 min with a 1 min sampling time throughout the surgery.
The first measurement was recorded in the empty room
soon after the cleaning procedure and before the patient’s
arrival. The measurement equipment was placed on the
surgical lamp arm above the patient. In this position, the
convective currents due to the temperature of the surgi-
cal lamps did not affect the measurements. Furthermore,
with a vertical flow system, heat generated by the surgical
lamps created only minor air turbulence (Zoon et al. 2010).
Bacterial Collection and Identification
Airborne viable bacteria were collected using a single-
stage Andersen air sampler. The instrument was placed
1.5 m above the floor at a distance of 1 m from the surgical
area. Samples were collected every 30 min at an air sam-
pling rate of 28.3 L/min throughout the surgeries.
The samples were incubated in blood agar plates
(Newprov) for 48 h at 37 °C; the colony forming units
were counted by direct visual observation and expressed
in CFU/m3
(Pereira et al. 2012; Andersen 1958). To iden-
tify bacteria, colonies were stained for a Gram stain test
(Newprov), followed by the biochemical analyses for S.
aureus.
Air Velocity
The airflow ­
(m3
/h) was obtained in each case by measur-
ing the velocity of the air at several points of the laminar
diffuser and multiplying the average by the area of the
air passage. The equipment used to measure air velocity
was the Airflow TA-5, which has a measurement range of
0–20 m/s, resolution of 0.01 m/s, and measurement uncer-
tainty of ± 2%.
CO2 Concentration
The ­CO2 concentration in the operating rooms was recorded
at 5 min intervals using a fixed monitor at breathing height,
which was approximately 1.7 m above the floor. The moni-
tor was tested and calibrated in the laboratory before the
field measurements were conducted. For ­
CO2 concentration,
the measurement uncertainty of the instrument (Instrutemp)
was ± 30 ppm (± 5%) of the reading (0–10000 ppm). As
the main source of ­
CO2 emissions in the operating room is
anthropogenic, the number of personnel was also considered
in the study. Psychrometric parameters, such as temperature
and relative humidity, were also measured with the same
instrument, and the airflow was assessed with a hot wire
anemometer (Dantec 54T33).
Data Analyses
Data were analyzed using SPSS version 20.0 (SPSS 2015)
as well as descriptive and inferential statistics. Descriptive
statistics was used to check the maximum and minimum
values, and dispersion of data was reported using standard
deviation. Mann–Whitney U and Kruskal–Wallis tests were
used to compare mean particle (bacteria and total parti-
cle) concentrations. The significance level was defined as
p<0.05 for all tests.
In this study, the results are accompanied by the standard
error of the mean (ISO/IEC 2008).
Results
Table 2 summarizes the airflow rate and psychromet-
ric parameters measured in all three cases. The airflow
increased from 706 ± 14 ­
m3
/h (9.3 ± 0.2 ACH) before the
filters were replaced (Case 1) to 1954±40 ­
m3
/h (25.8±0.5
ACH) after the filters were replaced (Case 2). This value
was very close to the airflow in Case 3, which was 2051±41
­m3
/h (27.1±0.5 ACH) and close to the Brazilian standard
ABNT NBR 7256 (2005) (Table 1). For Case 1, the airflow
rate was 66.4% below the recommendation; for Case 2, it
was 7%; and for Case 3, it was near 2% of the Brazilian
standard.
Table 2  Psychrometric and airflow rate parameters
689
International Journal of Environmental Research (2020) 14:685–692
1 3
Figure 2 presents the impact of the filter on the total par-
ticle count, which was assessed before and after the air con-
ditioning filters were replaced (Cases 1 and 2, respectively)
and in the new room (Case 3). It can be seen from this figure
that the change in the filter significantly decreased the par-
ticle concentration inside the room. For Case 1, the average
particle concentration was 15.0×106
±4.0×106
particles/
m3
. For Case 2, the average decreased to 0.4×106
±0.2×106
particles/m3
, thereby indicating that the average total particle
concentration decreased by approximately 97%. Statistical
analysis showed that the difference between the average
particle concentrations for these two cases was significant
(p < 0.05). For Case 3, the particle concentration had an
average of 0.3×106
±0.1×106
particles/m3
. Comparing the
average particle concentration for Case 1 with that of Case
3, the latter was approximately 98% lower than the former
(p < 0.05). The average particle concentrations for Case 2
and Case 3 were close, which was already expected, as all
the parameters, according to Brazilian standard ABNTNBR
7256 (2005), for both rooms were almost the same.
Figure 3 shows the concentration of viable particles
measured before (Case 1) and after (Case 2) the air con-
ditioning filters were replaced in the old room and in the
new room (Case 3). The concentration of viable particles
measured in Case 1 was notably higher than that measured
in Case 2 and Case 3. The average viable particle concen-
trations were57 ± 8 CFU/m3
in Case 1, 24 ± 7 CFU/m3
in
Case 2, and 15 ± 3 CFU/m3
in Case 3. On comparing the
averages between Case 1 and Case 2, the viable particle con-
centration in Case 2 was lower, thereby indicating that the
average total particle concentration was almost half (53%).
Statistical analysis showed that the difference was significant
(p < 0.05). The average viable particle concentration was
72% higher before the filters were replaced (Case 1) than
in the new room (Case 3). This difference was statistically
significant (p≤0.05). However, the differences between the
average particle concentrations after the filters were replaced
(Case 2) and in the new room (Case 3) were not significant
(p>0.05).
Table 3 presents the gram-negative and gram-positive
bacterial percentages, the prevalence of coagulase-negative
Staphylococci, and the concentrations of ­
CO2 measured
during all the surgeries. The concentration of gram-positive
bacteria was greater than that of gram-negative bacteria. The
prevalence of gram-positive bacteria was not affected by fil-
ter replacement (p > 0.05); that is, it continued to remain
high at 91±4% for Case 1, 92±5% for Case 2, and 90±6%
for Case 3.
The samples were also tested for coagulase-negative
bacteria to differentiate S. aureus from coagulase-nega-
tive Staphylococci. The prevalence of coagulase-negative
Staphylococci remained high in all surgeries. For Case 1,
the average was 86±3%; for Case 2.67±16%; and for Case
3.76±9%. It is important to highlight that coagulase-nega-
tive Staphylococci are the most common cause of nosoco-
mial infections.
Table 3 shows that the ­
CO2 concentrations were practi-
cally not affected by the filter replacements. In the new room,
­CO2 concentration was kept constant. The average ­
CO2 con-
centrations were 663±21 ppm in Case 1, 659±28 ppm in
Case 2, and 575±4 ppm in Case 3.
Discussion
Before the filters were replaced, the system operated at
an airflow of 706 ­
m3
/h (9.3 ACH), and the average total
and viable particle concentrations inside the room were
15.0×106
±4.0×106
particles/m3
and 57.4 CFU/m3
, respec-
tively. After the replacement, the airflow increased to 1954
­m3
/h (25.8 ACH), and the respective averages of particle
1.0E+05
1.0E+06
1.0E+07
1.0E+08
Case 1 Case 2 Case 3
Par
cles/m
3
Fig. 2  Total particle (0.3–10 μm) count in Case 1 (before filter
replacement); Case 2 (after filter replacement); and Case 3 (new
room)
0
10
20
30
40
50
60
70
Case 1 Case 2 Case 3
CFU/m
3
Fig. 3  Colony forming units (CFU) measured before (Case 1) and
after (Case 2) the air conditioning filters replacement and in the new
room (Case 3)
690 International Journal of Environmental Research (2020) 14:685–692
1 3
concentrations decreased to 0.4×106
±0.2×106
particles/
m3
and 24.5 CFU/m3
, respectively. The Brazilian standard
ABNT (2005) recommends 2800 ­
m3
/h (28 ACH) in an oper-
ating room. These results showed that with filter replace-
ment, the airflow inside the room increased by almost three
times, and viable particle concentration and total particle
concentration decreased by 53% and 97%, respectively.
The differences between the average particle concentra-
tions after the filters were replaced and in the new room were
around 60%. However, it is important to highlight that this
difference was due to the fact that in the new room there was
no dust or debris accumulated from years of use within the
duct system. Thus, this is the reason for the large difference
in the particle concentration between the two rooms.
These results suggest that inadequate or ineffective venti-
lation, caused by dirty or saturated filters, results in elevated
contaminant levels. This is because the particles remain
inside the room with less air exchange. On the other hand,
proper ventilation with greater airflow causes them to follow
the airflow pattern, leading to their capture by filters. It is
also worth mentioning that changing filters and increasing
airflow produces a greater effect on the total particle con-
centration than on the viable particle concentration. This is
expected, because viable particles make up only a very small
portion of the total particle concentration.
These results are in agreement with those reported by
Memarzadeh and Manning (2002) and Vonci et al. (2019).
They concluded that increasing air change per hour results
in high removal of particles inside an operating room. Chow
and Yang (2004) reported that a higher dilution effect leads
to a lower concentration of airborne contaminants in operat-
ing rooms, including bacteria and anesthetic gas. Accord-
ing to Pereira et al. (2012), indoor particle concentration
decreases with increasing air change rate in operating rooms,
as indicated by the simulation results.
Although there is presently no common standard method
used to determine the microbiological threshold limits in
surgical room settings (Dharan and Pittet 2002), the average
microbiological particle concentration determined in this
study after filter replacement was similar to that previously
reported in other studies (Vonci et al., 2019). Landrin et al.
(2005) determined a microbiological count ranging from 0
to 38 CFU/m3
. Dallolio et al. (2017) monitored 10 operating
rooms found a microbiological contamination of air ranging
from 2 to 27 CFU/m3
.
The results also showed that after filter replacement, the
total count of particle concentration agreed with previous
studies (Pereira et al., 2012; Nimra et al., 2015). Mirhoseini
et al. (2015), using an optical particle counter (0.5–10 µm) to
assess the total particle concentration in an operating room
and found an average concentration of 0.4 × 106
particle/
m3
. Nimra et al. (2015) compared the total concentration of
particles in the air in public and private hospitals and found
an average concentration of 4.0×106
particles/m3
in pub-
lic hospitals and 0.1×106
particles/m3
in private hospitals.
Morawska et al. (1998) investigated the particle concentra-
tion levels and size distribution in a complex hospital system
using submicrometer and supermicrometer instrumentation.
The authors found a particle concentration (0.5–30 µm) of
0.7×106
particles/m3
in a small surgical room. Regarding
the species of microorganisms found inside the room, the
results showed a significant prevalence of gram-positive
bacteria during most of the surgeries. It was also found that
the prevalence of gram-positive bacteria was not affected
by filter replacement. This finding was in accordance with
Dolinger et al. (2010), who also found a high prevalence of
gram-positive bacteria during different orthopedic surgeries.
Furthermore, Gallo et al. (2003) suggested that the gram-
positive bacteria that are released from skin, hair, and nos-
trils may be deposited on surfaces. However, according to
Edmiston et al. (2005), skin and nasal shedding by members
Table 3  Gram-negative and gram-positive bacterial percentages, prevalence of coagulase-negative Staphylococci, and concentrations of ­
CO2
measured during all the surgeries
691
International Journal of Environmental Research (2020) 14:685–692
1 3
of the surgical team might be a risk factor for perioperative
contamination and subsequent infection.
Further observation regarding the species of microor-
ganisms revealed that after filter replacement, there was
a decrease of 23% in coagulase-negative Staphylococci,
which were found to be present during 76.75% of surger-
ies, while gram-negative bacteria were present in 9.0% of
the cases. Edmiston et al. (2005)found that Staphylococci
and gram-negative bacteria were present in 86% and 33% of
cases, respectively. Coagulase-negative Staphylococci are
among the most commonly identified microorganisms in
surgical site infections (Edmiston et al. 2005; Becker et al.
2014). According to Dolinger et al. (2010), most ortho-
pedic implant-related infections are due to gram-positive
aerobic bacteria, predominantly S. aureus and S. epider-
midis (44–50%). These microorganisms form biofilms on
the surfaces of prostheses and implants, thereby providing
resistance to antibiotics Roberts et al. (2006). Suggested that
skin flakes are relatively large particles (4–25 µm) that can
transport Staphylococci when released or re-suspended.
Therefore, despite the threats posed by these microorgan-
isms, few studies have comprehensively addressed the trans-
mission route of coagulase-negative Staphylococci in hospi-
tals (Milisavljevic et al. 2005; Monsen et al. 2005; Botelho
et al. 2012). According to studies, coagulase-negative Staph-
ylococci have emerged as high-risk pathogens in relation to
the development of post-surgical infections, particularly in
prostheses surgeries (Dolinger et al. 2010). According to
Sagi et al.( 2002), instruments that have an air exhaust may
be a source of airborne microorganisms, among which the
major microorganisms are coagulase-negative Staphylococci
and Micrococcus sp.
With respect to ­
CO2, it was found that the concentration
was not affected by filter replacement. The ­
CO2 concentra-
tions remained practically constant and below 1000 ppm for
all three cases. This is because even with saturated filters, the
amount of air supplied to the room is sufficient to dilute the
­CO2 generated by the people. However, it is not sufficient to
dilute the particles generated inside the room.
Finally, it was also found that temperature and humidity
were not affected by filter replacement. Both remained con-
stant for all three cases.
Conclusions
The total and viable particle and ­
CO2 concentration in an
old operating room before the air conditioning filters were
replaced, after the air conditioning filters were replaced, and
in a new operating room with a new filter and normal airflow
were studied. The results of this exploratory study showed
that systems operating with saturated filters can suffer from
pressure drop, which can lead to reduced air flow, resulting
in an increase in the average of total particle and viable par-
ticle concentrations. However, the replacement of the filters
does not affect the ­
CO2 concentration.
Few studies have undertaken a quantitative determination
of the impact of the filtration system on indoor contamina-
tion in an orthopedic operating room. Further studies are
needed in this field to ensure good indoor air quality and
to protect patients and healthcare workers against hospital-
acquired infections and occupational diseases. Therefore, the
practical data presented in this work could serve as a basis
for corrective action in controlling airborne contamination
in operating rooms and may contribute to the overall knowl-
edge of the importance of ventilation and filtration systems
in this field.
Finally, it is also important to highlight that the pressure
drop in filters is a factor that directly affects the extra electric
energy power in the fan operation and may adversely affect
the performance of the air conditioning system. Hence, in
future studies, it will be important to assess whether the fan
motor electric energy consumption savings would cover the
costs of replacing the filters.
Acknowledgements The authors would like to thank Eng. Tomaz
Pulga from the Orthopedics and Traumatology Institute of São Paulo
for his immense support. Marcelo Luiz Pereira would like to thank the
International Laboratory for Air Quality & Health (ILAQH), Queens-
land University of Technology (QUT), where he was a visiting fellow.
Compliance with Ethical Standards
Conflict of Interest On behalf of all authors, the corresponding author
states that there is no conflict of interest.
References
Nbr ABNT (2005) Air conditioning for health care facilities - Require-
ments for design and installation. Standard 7256:2005
Alsaleem F, Munroe M, Rafaie M (2016) Current based HVAC systems
air filter diagnostics and monitoring. In: 4th International High
Performance Buildings Conference at Purdue, July 11–14, 2016.
Andersen AA (1958) New sampler for the collection, sizing, and enu-
meration of viable airborne particles. J Bacteriol 76(5):471–484
ASHRAE (2019) Ventilation for acceptable indoor air. Atlanta: Ameri-
can Society of Heating, Refrigerating and Air-Conditioning Engi-
neers. Standard 62: 2019.
Becker K, Heilmann C, Peters G (2014) Coagulase-Negative Staphy-
lococci. Clin Microbiol Rev 27(4):870–926
Beggs CB (2003) The Airborne Transmission of Infection in Hospital
Buildings: fact or fiction? Indoor Built Environ 12:9–18
Botelho AM, Nunes ZD, Asensi MD, Gomes MZ, Fracalanzza SE,
Figueiredo AM (2012) Characterization of coagulase-negative
Staphylococci isolated from hospital indoor air and a comparative
analysis between airborne and inpatient isolates of Staphylococcus
epidermidis. J Med Microbiol 61:1136–1145
Centres for Disease Control and Prevention (CDC) (2003) Guide-
lines for environmental infection control in health-care facilities.
692 International Journal of Environmental Research (2020) 14:685–692
1 3
Atlanta, U.S. Department of Health and Human Services Centres
for Disease Control and Prevention.
Chow TT, Yang Y (2004) Ventilation performance in operating theatres
against airborne infection: review of research activities and practi-
cal guidance. J Hosp Infect 56(2):85–92
Cole EC, Cook CE (1998) Characterization of infectious aerosols in
health care facilities: an aid to effective engineering controls and
preventive strategies. Am J Infect Control 26:453–464
Dallolio L, Raggi A, Sanna T et al (2017) Surveillance of environmen-
tal and procedural measures of infection control in the operating
theatre setting. Int J Environ Res Public Health 15(1):46
Dascalaki EG, Lagoudi A, Balaras CA, Gaglia AG (2008) Air quality
in hospital operating rooms. Build Environ 43:1945–1952
Dharan S, Pittet D (2002) Environmental controls in operating theatres.
J Hosp Infect 51(2):79–84
Dolinger EJ, Brito DV, Souza GM, Melo GB, Gontijo Filho PP (2010)
Air contamination levels in operating rooms during surgery of
total hip and total knee arthroplasty, hemiarthroplasty and osteo-
synthesis in the surgical center of a Brazilian hospital. Rev Soc
Bras Med Trop 43(5):584–587 ((article in Portuguese))
Edmiston CE Jr, Seabrook GR, Cambria RA, Brown KR, Lewis BD,
Sommers JR (2005) Molecular epidemiology of microbial con-
tamination in the operating room environment: Is there a risk for
infection? Surgery 138:573–582
Fernstrom A, Goldblatt M (2013) Aerobiology and itsrole inthe trans-
mission of infectious diseases. J Pathog 2013:493960
Fisk WJ, Faulkner D, Palonen J, Seppanen O (2002) Performance
and costs of particle air filtration technologies. Indoor Air
12(4):223–234
Gallo J, Kolar M, Novotny R, Rihakova P, Ticha V (2003) Pathogen
Prosthes-Relat Infect Biomed Papers 147:27–35
Gormley T, Markel TA, Jones H, Greeley D, Ostojic J, Clarke JH,
Abkowitz M, Wagner J (2017) Cost-benefit analysis of different
air change rates in an operating room environment. Am J Infect
Control 45(12):1318–1323
Gosden PE, MacGowan AP, Bannister GC (1998) Importance of air
quality and related factors in the prevention of infection in ortho-
paedic implant surgery. J Hosp Infect 39:173–180
Hanley JT, Esnor DS, Smith DD, Sparks LE (1994) Fraction aerosol
filtration efficiency of in-duct ventilation air cleaners. Indoor Air
4:169–178
ISO/IEC – International Organization for Standardization/International
Electrotchnical Commission. GUM 98–3. Guide to the expression
of uncertainty in measurement. 2008.
Jamariska M, Morawska L, Clark BA (2000) Effect of ventilation and
filtration on submicrometer particles in an indoor environment.
Indoor Air 10(1):19–26
Karthikeyan CP, Samuel AA (2008) CO2-dispersion studies in an oper-
ation theatre under transient conditions. Energy Build 40:231–239
Landrin A, Bissery A, Kac G (2005) Monitoring air sampling in operat-
ing theatres: can particle counting replace microbiological sam-
pling? J Hosp Infect 61:27–29
Maus R, Goppelsroder A, Umhauer H (2001) Survival of bacterial
and mold spores in air filter media. Atmos Environ 35:105–113
Memarzadeh F, Manning AP (2002) Comparison of operating room
ventilation systems in the protection of the surgical site. ASHRAE
Trans 108(2):3–15
Milisavljevic V, Wu F, Cimmotti J, Haas J, Della-Latta P, Larson E et al
(2005) Genetic relatedness of Staphylococcus epidermidis from
infected infants and staff in the neonatal intensive care unit. Am J
Infect Control 33:341–347
Mirhoseini SH, Nikaeen M, Khanahmd H, Hatamzadeh M, Hassan-
zadeh A (2015) Monitoring of airborne bacteria and aerosols
in different wards of hospitals—particle counting usefulness
in investigation of airborne bacteria. Ann Agric Environ Med
22(4):670–673
Monsen T, Karlsson C, Wistro MJ (2005) Spread of clones of multid-
rug-resistant, coagulase-negative Staphylococci within a univer-
sity hospital. Infect Control Hosp Epidemiol 26(1):76–80
Morawska L, Jamriska M, Francis P (1998) Particulate matter in the
hospital environment. Indoor Air 8:285–294
Morawska L (2006) Droplet fate in indoor environments, or can we
prevent the spread of infection? Indoor Air 16:335–347
Nimra A, Ali Z, Khan MN, Gulshan T, Sidra S, Gardezi JR, Tarar MR,
Saleem M, Nasir ZA, Colbeck I (2015) Comparative ambient and
indoor particulate matter analysis of operation theatres of govern-
ment and private (trust) Hospitals of Lahore, Pakistan’. J Anim
Plant Sci 25(3):628–635
Nogler M, Krismer M, Haid C, Ogon M, Bach C, Wimmer C (2001)
Excessive heat generation during Cutting of cement in the Robo-
doc hip-revision procedure. Acta Orthop Scand 72(6):595–599
Offermann FJI, Loiselle SA, Sextro G (1992) Performance of air clean-
ers in a residential forced air system. ASHRAE J 34(7):51–57
Pereira ML, Vilain R, Leivas TP, Tribess A (2012) Measurement of the
concentration and size of aerosol particles and identification of the
sources in orthopedic surgeries. HVAC&R Res 18(4):588–601
Pereira ML, Vilain R, Galvão FHF, Tribess A, Morawska L (2013)
Experimental and numerical analysis of the relationship between
indoor and outdoor airborne particles in an operating room. Indoor
Built Environ 22(6):864–875
Pereira ML, Knibbs LD, He C, Grzybowski P, Johnson GR, Huffman
JA, Bell SC, Wainwright CE, Matte DL, Dominski FH, Andrade
A, Morawska L (2017) Sources and dynamics of fluorescent par-
ticles in hospitals. Indoor Air 27(5):988–1000
Roberts K, Hathway A, Fletcher LA, Beggs CB, Elliott MW, Sleigh
PA (2006) Bioaerosol production on a respiratory ward. Indoor
Built Environ 15(1):35–40
Sagi HC, DiPasquale T, Sanders R, Herscovici D (2002) Compressed-
air power tools in orthopaedic surgery: exhaust air is a potential
source of contamination. J Orthop Trauma 16(10):696–700
Simmons RB, Crow SA (1995) Fungal colonization of air filters for
use in heating, ventilating, and air conditioning (HVAC) systems.
J Ind Microbiol 14:41–45
Simmons RB, Price DL, Noble JA (1997) Fungal colonization of air
filters from hospitals. Am Ind Hyg Assoc J 58:900–904
SPSS (2015) SPSS for windows. Version 16.0. SPSS Inc., Chicago
Stetzenbach LD, Buttner MP, Cruz P (2004) Detection and enumera-
tion of airborne contaminants. Curr Opin Biotech 15(3):170–174
Vonci N, Marco MF, Grasso A, Spataro G, Cevenini G, Messina G
(2019) Association between air changes and airborne micro-
bial contamination in operating rooms. J Infect Public Health
12(60):827–830
Yang L, Braun JE, Groll EA (2007) The impact of evaporator fouling
and filtration on the performance of packaged air conditioners. Int
J Refrig 30(3):506–514
Zoon WAC, Van Der Heijden MGM, Loomans MGLC, Hensen JLM
(2010) On the applicability of the laminar flow index when select-
ing surgical lighting. Build Environ 45(9):1976–1983

More Related Content

Similar to s41742-020-00286-x.pdf

IRJET- Biofilter System for Air Pollution Control: A Review
IRJET- Biofilter System for Air Pollution Control: A ReviewIRJET- Biofilter System for Air Pollution Control: A Review
IRJET- Biofilter System for Air Pollution Control: A ReviewIRJET Journal
 
The indoor environment & air quality uv air & surface disinfection
The indoor environment & air quality   uv air & surface disinfectionThe indoor environment & air quality   uv air & surface disinfection
The indoor environment & air quality uv air & surface disinfectionTNenergy
 
The benefits of ventilation and filtration in schools
The benefits of ventilation and filtration in schoolsThe benefits of ventilation and filtration in schools
The benefits of ventilation and filtration in schoolsTake Care of Your Air
 
Ashrae rp 1301 quantification of ventilation effectiveness
Ashrae rp 1301 quantification of ventilation effectivenessAshrae rp 1301 quantification of ventilation effectiveness
Ashrae rp 1301 quantification of ventilation effectivenessCliff Cooper, MS, CIH
 
International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)inventionjournals
 
BE SARS-COV-2 17_mar_2020 Slides Presented
BE SARS-COV-2 17_mar_2020 Slides PresentedBE SARS-COV-2 17_mar_2020 Slides Presented
BE SARS-COV-2 17_mar_2020 Slides PresentedAndrew Hoisington
 
Indoor air quality
Indoor air qualityIndoor air quality
Indoor air qualityECRD IN
 
Indoor air quality
Indoor air qualityIndoor air quality
Indoor air qualityECRD2015
 
Indoor air quality
Indoor air qualityIndoor air quality
Indoor air qualityECRD2015
 
The Legal and Regulatory Consequences of New PM 2.5 Exposure Research
The Legal and Regulatory Consequences of New PM 2.5 Exposure ResearchThe Legal and Regulatory Consequences of New PM 2.5 Exposure Research
The Legal and Regulatory Consequences of New PM 2.5 Exposure ResearchGregory P Nichols, MPH, CPH
 
Chapter 9 room ventilation systems (1)
Chapter 9 room ventilation systems (1)Chapter 9 room ventilation systems (1)
Chapter 9 room ventilation systems (1)Imran Sultan
 
MEE 6501, Advanced Air Quality Control 1 Course Le.docx
MEE 6501, Advanced Air Quality Control 1 Course Le.docxMEE 6501, Advanced Air Quality Control 1 Course Le.docx
MEE 6501, Advanced Air Quality Control 1 Course Le.docxgertrudebellgrove
 
Electronic Cigarettes and Indoor Air Quality: A Simple Approach to Modeling P...
Electronic Cigarettes and Indoor Air Quality: A Simple Approach to Modeling P...Electronic Cigarettes and Indoor Air Quality: A Simple Approach to Modeling P...
Electronic Cigarettes and Indoor Air Quality: A Simple Approach to Modeling P...Fontem Ventures
 
Hospital hvac design salah ramadan
Hospital hvac design  salah ramadanHospital hvac design  salah ramadan
Hospital hvac design salah ramadanEng Salah Ramadan
 
Air Based Hazards, M.pharm, sem 2,Bhumi Suratiya,.pptx
Air Based Hazards, M.pharm, sem 2,Bhumi Suratiya,.pptxAir Based Hazards, M.pharm, sem 2,Bhumi Suratiya,.pptx
Air Based Hazards, M.pharm, sem 2,Bhumi Suratiya,.pptxBhumiSuratiya
 
International conference2017
International conference2017International conference2017
International conference2017vishwajeet potdar
 
Indoor Air Quality (IAQ) and Sick Building Syndrome (SBS) among Office Worker...
Indoor Air Quality (IAQ) and Sick Building Syndrome (SBS) among Office Worker...Indoor Air Quality (IAQ) and Sick Building Syndrome (SBS) among Office Worker...
Indoor Air Quality (IAQ) and Sick Building Syndrome (SBS) among Office Worker...BRF
 
FACTORS ASSOCIATED WITH LUNG FUNCTION DISTURBANCE TO TEXTILE INDUSTRY WORKER ...
FACTORS ASSOCIATED WITH LUNG FUNCTION DISTURBANCE TO TEXTILE INDUSTRY WORKER ...FACTORS ASSOCIATED WITH LUNG FUNCTION DISTURBANCE TO TEXTILE INDUSTRY WORKER ...
FACTORS ASSOCIATED WITH LUNG FUNCTION DISTURBANCE TO TEXTILE INDUSTRY WORKER ...irjes
 

Similar to s41742-020-00286-x.pdf (20)

IRJET- Biofilter System for Air Pollution Control: A Review
IRJET- Biofilter System for Air Pollution Control: A ReviewIRJET- Biofilter System for Air Pollution Control: A Review
IRJET- Biofilter System for Air Pollution Control: A Review
 
The indoor environment & air quality uv air & surface disinfection
The indoor environment & air quality   uv air & surface disinfectionThe indoor environment & air quality   uv air & surface disinfection
The indoor environment & air quality uv air & surface disinfection
 
Air changes
Air changesAir changes
Air changes
 
The benefits of ventilation and filtration in schools
The benefits of ventilation and filtration in schoolsThe benefits of ventilation and filtration in schools
The benefits of ventilation and filtration in schools
 
BE_SARS_16_mar_2020
BE_SARS_16_mar_2020BE_SARS_16_mar_2020
BE_SARS_16_mar_2020
 
Ashrae rp 1301 quantification of ventilation effectiveness
Ashrae rp 1301 quantification of ventilation effectivenessAshrae rp 1301 quantification of ventilation effectiveness
Ashrae rp 1301 quantification of ventilation effectiveness
 
International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)
 
BE SARS-COV-2 17_mar_2020 Slides Presented
BE SARS-COV-2 17_mar_2020 Slides PresentedBE SARS-COV-2 17_mar_2020 Slides Presented
BE SARS-COV-2 17_mar_2020 Slides Presented
 
Indoor air quality
Indoor air qualityIndoor air quality
Indoor air quality
 
Indoor air quality
Indoor air qualityIndoor air quality
Indoor air quality
 
Indoor air quality
Indoor air qualityIndoor air quality
Indoor air quality
 
The Legal and Regulatory Consequences of New PM 2.5 Exposure Research
The Legal and Regulatory Consequences of New PM 2.5 Exposure ResearchThe Legal and Regulatory Consequences of New PM 2.5 Exposure Research
The Legal and Regulatory Consequences of New PM 2.5 Exposure Research
 
Chapter 9 room ventilation systems (1)
Chapter 9 room ventilation systems (1)Chapter 9 room ventilation systems (1)
Chapter 9 room ventilation systems (1)
 
MEE 6501, Advanced Air Quality Control 1 Course Le.docx
MEE 6501, Advanced Air Quality Control 1 Course Le.docxMEE 6501, Advanced Air Quality Control 1 Course Le.docx
MEE 6501, Advanced Air Quality Control 1 Course Le.docx
 
Electronic Cigarettes and Indoor Air Quality: A Simple Approach to Modeling P...
Electronic Cigarettes and Indoor Air Quality: A Simple Approach to Modeling P...Electronic Cigarettes and Indoor Air Quality: A Simple Approach to Modeling P...
Electronic Cigarettes and Indoor Air Quality: A Simple Approach to Modeling P...
 
Hospital hvac design salah ramadan
Hospital hvac design  salah ramadanHospital hvac design  salah ramadan
Hospital hvac design salah ramadan
 
Air Based Hazards, M.pharm, sem 2,Bhumi Suratiya,.pptx
Air Based Hazards, M.pharm, sem 2,Bhumi Suratiya,.pptxAir Based Hazards, M.pharm, sem 2,Bhumi Suratiya,.pptx
Air Based Hazards, M.pharm, sem 2,Bhumi Suratiya,.pptx
 
International conference2017
International conference2017International conference2017
International conference2017
 
Indoor Air Quality (IAQ) and Sick Building Syndrome (SBS) among Office Worker...
Indoor Air Quality (IAQ) and Sick Building Syndrome (SBS) among Office Worker...Indoor Air Quality (IAQ) and Sick Building Syndrome (SBS) among Office Worker...
Indoor Air Quality (IAQ) and Sick Building Syndrome (SBS) among Office Worker...
 
FACTORS ASSOCIATED WITH LUNG FUNCTION DISTURBANCE TO TEXTILE INDUSTRY WORKER ...
FACTORS ASSOCIATED WITH LUNG FUNCTION DISTURBANCE TO TEXTILE INDUSTRY WORKER ...FACTORS ASSOCIATED WITH LUNG FUNCTION DISTURBANCE TO TEXTILE INDUSTRY WORKER ...
FACTORS ASSOCIATED WITH LUNG FUNCTION DISTURBANCE TO TEXTILE INDUSTRY WORKER ...
 

Recently uploaded

Forest laws, Indian forest laws, why they are important
Forest laws, Indian forest laws, why they are importantForest laws, Indian forest laws, why they are important
Forest laws, Indian forest laws, why they are importantadityabhardwaj282
 
Vision and reflection on Mining Software Repositories research in 2024
Vision and reflection on Mining Software Repositories research in 2024Vision and reflection on Mining Software Repositories research in 2024
Vision and reflection on Mining Software Repositories research in 2024AyushiRastogi48
 
The dark energy paradox leads to a new structure of spacetime.pptx
The dark energy paradox leads to a new structure of spacetime.pptxThe dark energy paradox leads to a new structure of spacetime.pptx
The dark energy paradox leads to a new structure of spacetime.pptxEran Akiva Sinbar
 
Pests of safflower_Binomics_Identification_Dr.UPR.pdf
Pests of safflower_Binomics_Identification_Dr.UPR.pdfPests of safflower_Binomics_Identification_Dr.UPR.pdf
Pests of safflower_Binomics_Identification_Dr.UPR.pdfPirithiRaju
 
Call Us ≽ 9953322196 ≼ Call Girls In Lajpat Nagar (Delhi) |
Call Us ≽ 9953322196 ≼ Call Girls In Lajpat Nagar (Delhi) |Call Us ≽ 9953322196 ≼ Call Girls In Lajpat Nagar (Delhi) |
Call Us ≽ 9953322196 ≼ Call Girls In Lajpat Nagar (Delhi) |aasikanpl
 
Bentham & Hooker's Classification. along with the merits and demerits of the ...
Bentham & Hooker's Classification. along with the merits and demerits of the ...Bentham & Hooker's Classification. along with the merits and demerits of the ...
Bentham & Hooker's Classification. along with the merits and demerits of the ...Nistarini College, Purulia (W.B) India
 
Speech, hearing, noise, intelligibility.pptx
Speech, hearing, noise, intelligibility.pptxSpeech, hearing, noise, intelligibility.pptx
Speech, hearing, noise, intelligibility.pptxpriyankatabhane
 
Scheme-of-Work-Science-Stage-4 cambridge science.docx
Scheme-of-Work-Science-Stage-4 cambridge science.docxScheme-of-Work-Science-Stage-4 cambridge science.docx
Scheme-of-Work-Science-Stage-4 cambridge science.docxyaramohamed343013
 
Transposable elements in prokaryotes.ppt
Transposable elements in prokaryotes.pptTransposable elements in prokaryotes.ppt
Transposable elements in prokaryotes.pptArshadWarsi13
 
(9818099198) Call Girls In Noida Sector 14 (NOIDA ESCORTS)
(9818099198) Call Girls In Noida Sector 14 (NOIDA ESCORTS)(9818099198) Call Girls In Noida Sector 14 (NOIDA ESCORTS)
(9818099198) Call Girls In Noida Sector 14 (NOIDA ESCORTS)riyaescorts54
 
TOPIC 8 Temperature and Heat.pdf physics
TOPIC 8 Temperature and Heat.pdf physicsTOPIC 8 Temperature and Heat.pdf physics
TOPIC 8 Temperature and Heat.pdf physicsssuserddc89b
 
Best Call Girls In Sector 29 Gurgaon❤️8860477959 EscorTs Service In 24/7 Delh...
Best Call Girls In Sector 29 Gurgaon❤️8860477959 EscorTs Service In 24/7 Delh...Best Call Girls In Sector 29 Gurgaon❤️8860477959 EscorTs Service In 24/7 Delh...
Best Call Girls In Sector 29 Gurgaon❤️8860477959 EscorTs Service In 24/7 Delh...lizamodels9
 
STOPPED FLOW METHOD & APPLICATION MURUGAVENI B.pptx
STOPPED FLOW METHOD & APPLICATION MURUGAVENI B.pptxSTOPPED FLOW METHOD & APPLICATION MURUGAVENI B.pptx
STOPPED FLOW METHOD & APPLICATION MURUGAVENI B.pptxMurugaveni B
 
Is RISC-V ready for HPC workload? Maybe?
Is RISC-V ready for HPC workload? Maybe?Is RISC-V ready for HPC workload? Maybe?
Is RISC-V ready for HPC workload? Maybe?Patrick Diehl
 
Pests of castor_Binomics_Identification_Dr.UPR.pdf
Pests of castor_Binomics_Identification_Dr.UPR.pdfPests of castor_Binomics_Identification_Dr.UPR.pdf
Pests of castor_Binomics_Identification_Dr.UPR.pdfPirithiRaju
 
BREEDING FOR RESISTANCE TO BIOTIC STRESS.pptx
BREEDING FOR RESISTANCE TO BIOTIC STRESS.pptxBREEDING FOR RESISTANCE TO BIOTIC STRESS.pptx
BREEDING FOR RESISTANCE TO BIOTIC STRESS.pptxPABOLU TEJASREE
 
Call Girls in Mayapuri Delhi 💯Call Us 🔝9953322196🔝 💯Escort.
Call Girls in Mayapuri Delhi 💯Call Us 🔝9953322196🔝 💯Escort.Call Girls in Mayapuri Delhi 💯Call Us 🔝9953322196🔝 💯Escort.
Call Girls in Mayapuri Delhi 💯Call Us 🔝9953322196🔝 💯Escort.aasikanpl
 
Environmental Biotechnology Topic:- Microbial Biosensor
Environmental Biotechnology Topic:- Microbial BiosensorEnvironmental Biotechnology Topic:- Microbial Biosensor
Environmental Biotechnology Topic:- Microbial Biosensorsonawaneprad
 

Recently uploaded (20)

Forest laws, Indian forest laws, why they are important
Forest laws, Indian forest laws, why they are importantForest laws, Indian forest laws, why they are important
Forest laws, Indian forest laws, why they are important
 
Vision and reflection on Mining Software Repositories research in 2024
Vision and reflection on Mining Software Repositories research in 2024Vision and reflection on Mining Software Repositories research in 2024
Vision and reflection on Mining Software Repositories research in 2024
 
The dark energy paradox leads to a new structure of spacetime.pptx
The dark energy paradox leads to a new structure of spacetime.pptxThe dark energy paradox leads to a new structure of spacetime.pptx
The dark energy paradox leads to a new structure of spacetime.pptx
 
Pests of safflower_Binomics_Identification_Dr.UPR.pdf
Pests of safflower_Binomics_Identification_Dr.UPR.pdfPests of safflower_Binomics_Identification_Dr.UPR.pdf
Pests of safflower_Binomics_Identification_Dr.UPR.pdf
 
Hot Sexy call girls in Moti Nagar,🔝 9953056974 🔝 escort Service
Hot Sexy call girls in  Moti Nagar,🔝 9953056974 🔝 escort ServiceHot Sexy call girls in  Moti Nagar,🔝 9953056974 🔝 escort Service
Hot Sexy call girls in Moti Nagar,🔝 9953056974 🔝 escort Service
 
Call Us ≽ 9953322196 ≼ Call Girls In Lajpat Nagar (Delhi) |
Call Us ≽ 9953322196 ≼ Call Girls In Lajpat Nagar (Delhi) |Call Us ≽ 9953322196 ≼ Call Girls In Lajpat Nagar (Delhi) |
Call Us ≽ 9953322196 ≼ Call Girls In Lajpat Nagar (Delhi) |
 
Bentham & Hooker's Classification. along with the merits and demerits of the ...
Bentham & Hooker's Classification. along with the merits and demerits of the ...Bentham & Hooker's Classification. along with the merits and demerits of the ...
Bentham & Hooker's Classification. along with the merits and demerits of the ...
 
Speech, hearing, noise, intelligibility.pptx
Speech, hearing, noise, intelligibility.pptxSpeech, hearing, noise, intelligibility.pptx
Speech, hearing, noise, intelligibility.pptx
 
Scheme-of-Work-Science-Stage-4 cambridge science.docx
Scheme-of-Work-Science-Stage-4 cambridge science.docxScheme-of-Work-Science-Stage-4 cambridge science.docx
Scheme-of-Work-Science-Stage-4 cambridge science.docx
 
Transposable elements in prokaryotes.ppt
Transposable elements in prokaryotes.pptTransposable elements in prokaryotes.ppt
Transposable elements in prokaryotes.ppt
 
(9818099198) Call Girls In Noida Sector 14 (NOIDA ESCORTS)
(9818099198) Call Girls In Noida Sector 14 (NOIDA ESCORTS)(9818099198) Call Girls In Noida Sector 14 (NOIDA ESCORTS)
(9818099198) Call Girls In Noida Sector 14 (NOIDA ESCORTS)
 
TOPIC 8 Temperature and Heat.pdf physics
TOPIC 8 Temperature and Heat.pdf physicsTOPIC 8 Temperature and Heat.pdf physics
TOPIC 8 Temperature and Heat.pdf physics
 
Best Call Girls In Sector 29 Gurgaon❤️8860477959 EscorTs Service In 24/7 Delh...
Best Call Girls In Sector 29 Gurgaon❤️8860477959 EscorTs Service In 24/7 Delh...Best Call Girls In Sector 29 Gurgaon❤️8860477959 EscorTs Service In 24/7 Delh...
Best Call Girls In Sector 29 Gurgaon❤️8860477959 EscorTs Service In 24/7 Delh...
 
STOPPED FLOW METHOD & APPLICATION MURUGAVENI B.pptx
STOPPED FLOW METHOD & APPLICATION MURUGAVENI B.pptxSTOPPED FLOW METHOD & APPLICATION MURUGAVENI B.pptx
STOPPED FLOW METHOD & APPLICATION MURUGAVENI B.pptx
 
Is RISC-V ready for HPC workload? Maybe?
Is RISC-V ready for HPC workload? Maybe?Is RISC-V ready for HPC workload? Maybe?
Is RISC-V ready for HPC workload? Maybe?
 
Pests of castor_Binomics_Identification_Dr.UPR.pdf
Pests of castor_Binomics_Identification_Dr.UPR.pdfPests of castor_Binomics_Identification_Dr.UPR.pdf
Pests of castor_Binomics_Identification_Dr.UPR.pdf
 
BREEDING FOR RESISTANCE TO BIOTIC STRESS.pptx
BREEDING FOR RESISTANCE TO BIOTIC STRESS.pptxBREEDING FOR RESISTANCE TO BIOTIC STRESS.pptx
BREEDING FOR RESISTANCE TO BIOTIC STRESS.pptx
 
Call Girls in Mayapuri Delhi 💯Call Us 🔝9953322196🔝 💯Escort.
Call Girls in Mayapuri Delhi 💯Call Us 🔝9953322196🔝 💯Escort.Call Girls in Mayapuri Delhi 💯Call Us 🔝9953322196🔝 💯Escort.
Call Girls in Mayapuri Delhi 💯Call Us 🔝9953322196🔝 💯Escort.
 
Volatile Oils Pharmacognosy And Phytochemistry -I
Volatile Oils Pharmacognosy And Phytochemistry -IVolatile Oils Pharmacognosy And Phytochemistry -I
Volatile Oils Pharmacognosy And Phytochemistry -I
 
Environmental Biotechnology Topic:- Microbial Biosensor
Environmental Biotechnology Topic:- Microbial BiosensorEnvironmental Biotechnology Topic:- Microbial Biosensor
Environmental Biotechnology Topic:- Microbial Biosensor
 

s41742-020-00286-x.pdf

  • 1. Vol.:(0123456789) 1 3 International Journal of Environmental Research (2020) 14:685–692 https://doi.org/10.1007/s41742-020-00286-x RESEARCH PAPER Impact of Filtration Conditions on Air Quality in an Operating Room Marcelo Luiz Pereira1 · Rogério Vilain1 · Patricia Rocha Kawase1 · Arlindo Tribess2 · Lidia Morawska3 Received: 13 March 2020 / Revised: 10 September 2020 / Accepted: 3 October 2020 / Published online: 23 October 2020 © University of Tehran 2020 Abstract The aim of this study was to assess the impact of ventilation and filtration conditions on particle concentrations in an ortho- pedic operating room. Total particle, viable particle, and ­ CO2 concentration were measured under three different situations, namely before air filter replacement, after air filter replacement, and in an operating room with a new air conditioning system. Before air filter replacement, the mean values of airflow, total particle concentration, and viable particle concentration were 706 ­m3 /h, 15.0×106 ±4.0×106 particles/m3 , and 57 CFU/m3 , respectively. After replacement, the airflow increased to 1954 ­m3 /h, and total and viable particle concentrations decreased to 0.4×106 ±0.2×106 particles/m3 and 24 CFU/m3 , respectively. In the room with a new air conditioning system, the airflow was 2051 ­ m3 /h, and total and viable particle concentrations were 0.3×106. ±0.1×106 particles/m3 and 15 CFU/m3 , respectively. The ­ CO2 levels were 663 ppm (before), 659 ppm (after), and 574 ppm (new room). The results showed that inappropriate or no maintenance of filters in an air conditioning system had significant negative effects on indoor air quality in operating rooms. Air conditioning systems operating with saturated filters can be affected by pressure drop, which can lead to a reduction in airflow, thereby resulting in an increase in the average total particle and viable particle concentrations and the risk of infection in operating rooms. However, the results showed that the ­CO2 concentration was not affected by the filter replacement. Article Highlights • Improper maintenance of the air filters poses negative effects in operating rooms. • Particles remain inside the room with less air exchange caused by saturated filters. • Change in filters produces a greater effect on air quality in operating rooms. • CO2 concentration generated by the people may not be affected by the filter replacement. Keywords Indoor particles · Total particle · Viable particle · CO2 concentration · Filtration system · Operating room Introduction Indoor air quality in operating rooms is a matter of great concern for patients and medical personnel (Dascalaki et al. 2008), especially because of the presence of a vast array of air contaminants, such as chemicals from medical gases used for anesthesia, disinfection and sterilizing substances, and particles of skin debris, lint, respiratory droplets, and aero- sols (Gormley et al. 2017). Given this diversity of sources, knowledge of the variation in indoor particle concentrations in operating rooms as well as the factors that affect these var- iations are important to control the incidence of surgical site infections. According to Pereira et al. (2012), a decrease in particle concentrations can result in a decrease in the number of carriers of organic or microbiological agents in operating rooms and can consequently decrease the risk of infection. Microbiological contamination of operating room air, which is commonly caused by contaminated skin scales released by the surgical team, is generally considered to be the main risk factor for surgical site infection in clean * Marcelo Luiz Pereira marcelo.pereira@ifsc.edu.br 1 Instituto Federal de Educacao Ciencia e Tecnologia de Santa Catarina, São José, Santa Catarina, Brazil 2 Department of MechanicalEngineering, Polytechnic School of the University of São Paulo, São Paulo, São Paulo, Brazil 3 International Laboratory for Air Quality and Health, Queensland University of Technology, Brisbane, Queensland, Australia
  • 2. 686 International Journal of Environmental Research (2020) 14:685–692 1 3 surgeries (Pereira et al. 2013; Landrin et al. 2005). For example, bacteria such as Staphylococcus aureus are con- tinuously released into the air by operating room personnel and can subsequently precipitate onto the surgical site. These organisms cause the majority of infections in prosthetic implant surgeries, such as hip and knee replacements (Gos- den et al. 1998). Additionally, according to their size, many microorganisms that are present in an operating room can be broadly classified, as follows: bacterial cells and spores (0.3–10 μm in diameter), fungal spores (2.0–5.0 μm), and viruses (0.02–0.30 μm) (Morawska, 2006; Fernstrom and Goldblatt 2013). Filtration and air exchange with the outdoor air plays a key role in maintaining acceptable air quality in operating rooms. Indoor particle concentrations can be decreased by exhausting and diluting the return air with outdoor air (Sim- mons et al. 1997; Cole and Cook 1998). By means of air renewal, a significant decrease in the pollutants generated in the room can be obtained to keep them below the threshold levels. Dilution ventilation requires the system to condition the outdoor air before it is introduced into the room. Out- door air usually contains contaminants, such as bacteria, pollen, insects, soot, ash, and dust. These contaminants can penetrate buildings, thereby influencing indoor particle con- centrations. Filtration systems constitute a very important defense against outdoor air pollution, especially in environ- ments that demand a large amount of external air, such as operating rooms. The filtration systems must protect the sur- gical wound, sterile equipment, and occupants against the dangerous effects of outdoor and/or return particles (Pereira et al. 2012). However, mechanical ventilation systems are only effective if the filters are frequently replaced and if the ventilation system is properly maintained. In other words, most of the pollutants from outdoor and/or return air can be effectively removed if the filtration system is properly designed, installed, and well-maintained, which can further aid in improving building cleanliness and air conditioning system efficiency. Some studies suggest that the air condi- tioning system and its components, such as the air filter and air-handling system, are often poorly maintained and can be an ideal environment for microbial growth (Pereira et al. 2017; Jamariska et al. 2000). Despite the importance of environmental hygiene in hos- pitals (Beggs 2003; Pereira et al. 2017), few studies have focused on the impact of maintenance of air conditioning filters on particle concentrations in operating rooms; the existing information on this topic is limited. Consequently, it is common to find many hospitals with insufficient main- tenance or lack of filter substitution, which has serious con- sequences, particularly for patients. Air contamination caused by saturated filters is also a seri- ous health hazard for operating room occupants, especially during orthopedic surgeries that have high production of smoke and aerosols due to the use of tools, such as electro- surgical apparatus, bone saws, and drills. These aerosols are spread over the operating room, thereby contaminating the animate and inanimate environmental surfaces (Chow and Yang 2004; Nogler et al. 2001). According to Stetzenbach et al. (2004), airborne microorganisms are a health hazard when present in high concentrations in indoor environments, thereby resulting in health problems. Another aspect that has been highlighted regarding the use of saturated filters is that humidity and the presence of organic matter on the filter surface can serve as a source of carbon and energy, thereby enabling microbes to grow (Maus et al. 2001). Simmons and Crow (1995) showed that molds can grow in fibrous filter media provided the relative humidity of the air is above 70–80% and/or atmospheric dust is present in the filter media. It is also important to note that saturated filters make air conditioning systems operate beyond their foreseen capacity, thereby increasing energy consumption and equipment main- tenance costs (Hanley et al. 1994; Offermann et al. 1992; Fisk et al. 2002; CDC 2003). To prevent HVAC (heating, ventilation, and air condi- tioning) performance degradation and malfunction that can increase energy consumption, air filters need to be replaced periodically. However, the criteria and the frequency of filter replacement can vary due to the fluctuation in the debris-accu- mulation rate in the air filters. Current manufacturers recom- mend the replacement of air filters every 3 months (Alsaleem et al. 2016). In the case of high-efficiency filters, this criterion is not feasible due to the costs involved. Thus, many installa- tions with high-efficiency filters use monitoring of the pressure drop increase through the filters or the electric current increase on the fans (Yang et al. 2007). Normally, the level of ­ CO2 that is generated in rooms can be considered as a good indicator of the efficiency of the air conditioning system in the process of air renewal (Spagnoli et al. 1996).CO2 is a metabolic gas that is expelled naturally as a human respirational sub-product. Indoors, the recommended limits should be below 1000 ppm (ASHRAE 2019). According to Karthikeyan and Samuel (2008), ­CO2 concentration can also be an indirect indicator of the occurrence of post-operative wound infections. Few published studies have examined the impact of filtra- tion conditions on particle and ­ CO2 concentration levels in operating rooms. In this context, to identify the impact of the filtration system on indoor contamination in an orthopedic operating room, we measured the total particle, viable particle, and ­ CO2 concen- tration in an old operating room before and after the air con- ditioning filters were replaced as well as in a new operating room that had a new filter and normal airflow.
  • 3. 687 International Journal of Environmental Research (2020) 14:685–692 1 3 Methodology The study was conducted in an orthopedic hospital located in São Paulo, Brazil, and was approved by the Ethics Com- mittee of the Institute of Orthopedics and Traumatology under protocol number 109506. Study Design This study was conducted in two operating rooms: one in which the air filter of the HVAC system was poorly main- tained. In this room, the filter of the HVAC system was replaced every year. However, due to contract problems with the maintenance company, the HVAC system had been running for approximately four and a half months without a filter replacement. The other operating room had a newly installed HVAC system. Both rooms were placed in the same surgery center. The first round of measurements was performed 2 weeks before the filters were replaced (Case 1), that is, approxi- mately 4 months after the filter replacement period had expired. The second set of measurements was carried out 1 week after filter replacement (Case 2). The results obtained in Cases 1 and 2 were compared with the measurements in another operating room with a new HVAC system (Case 3). Both operating rooms had the same layout: the room area was approximately 28 ­ m2 with a height of 2.7 m (Fig. 1); they were designed according to the Brazilian standard ABNT NBR 7256 (ABNT 2005) (Table 1). The distribution system in both rooms was laminar (unidirectional) and the a filter package with three filters was used: first filter with an efficiency of 30%, second filter with an efficiency of 90%, and a third filter, with absolute filtration [high-efficiency particulate air (HEPA)]. The system operated at an air renewal rate of 30% of the outdoor air. Five major orthopedic surgeries were conducted for each of these cases. In ­ thi s study, all measurements were performed under the same conditions for the three cases. In other words, all measurements were performed dur- ing similar surgeries, involving approximately the same number of people inside the room. In addition, during the measurements, all the doors of the operating room were kept closed, eliminating the possibility of infiltration of pollutants from adjacent areas. Fig. 1  Operating room layout Table 1  Brazilian standard ABNT NBR 7256 recommendation
  • 4. 688 International Journal of Environmental Research (2020) 14:685–692 1 3 Measurement of Total Particle Concentration and Size Measurements of particle concentrations were conducted using real-time, size-resolved optical particle counters, which were calibrated by the manufacturer (Met One, Model HHPC-6). These portable (27 × 10 × 5 cm) particle counters have a flow rate of 2.83 L/min, which is able to measure the particle number concentration in the follow- ing range: 0.3–0.5 µm, 0.5–1.0 µm, 1.0–3.0 µm, 3–5 µm, 5–10 µm and > 10 µm. Since the aim of the present study was to analyze the impact of filtration conditions on air quality, the results in terms of particles were reported as the sum of the concentrations measured for all six channels (0.3–10.0 µm), which represent the size range of typical airborne infectious particles in operating rooms. For each surgery, measurements were recorded every 5 min with a 1 min sampling time throughout the surgery. The first measurement was recorded in the empty room soon after the cleaning procedure and before the patient’s arrival. The measurement equipment was placed on the surgical lamp arm above the patient. In this position, the convective currents due to the temperature of the surgi- cal lamps did not affect the measurements. Furthermore, with a vertical flow system, heat generated by the surgical lamps created only minor air turbulence (Zoon et al. 2010). Bacterial Collection and Identification Airborne viable bacteria were collected using a single- stage Andersen air sampler. The instrument was placed 1.5 m above the floor at a distance of 1 m from the surgical area. Samples were collected every 30 min at an air sam- pling rate of 28.3 L/min throughout the surgeries. The samples were incubated in blood agar plates (Newprov) for 48 h at 37 °C; the colony forming units were counted by direct visual observation and expressed in CFU/m3 (Pereira et al. 2012; Andersen 1958). To iden- tify bacteria, colonies were stained for a Gram stain test (Newprov), followed by the biochemical analyses for S. aureus. Air Velocity The airflow ­ (m3 /h) was obtained in each case by measur- ing the velocity of the air at several points of the laminar diffuser and multiplying the average by the area of the air passage. The equipment used to measure air velocity was the Airflow TA-5, which has a measurement range of 0–20 m/s, resolution of 0.01 m/s, and measurement uncer- tainty of ± 2%. CO2 Concentration The ­CO2 concentration in the operating rooms was recorded at 5 min intervals using a fixed monitor at breathing height, which was approximately 1.7 m above the floor. The moni- tor was tested and calibrated in the laboratory before the field measurements were conducted. For ­ CO2 concentration, the measurement uncertainty of the instrument (Instrutemp) was ± 30 ppm (± 5%) of the reading (0–10000 ppm). As the main source of ­ CO2 emissions in the operating room is anthropogenic, the number of personnel was also considered in the study. Psychrometric parameters, such as temperature and relative humidity, were also measured with the same instrument, and the airflow was assessed with a hot wire anemometer (Dantec 54T33). Data Analyses Data were analyzed using SPSS version 20.0 (SPSS 2015) as well as descriptive and inferential statistics. Descriptive statistics was used to check the maximum and minimum values, and dispersion of data was reported using standard deviation. Mann–Whitney U and Kruskal–Wallis tests were used to compare mean particle (bacteria and total parti- cle) concentrations. The significance level was defined as p<0.05 for all tests. In this study, the results are accompanied by the standard error of the mean (ISO/IEC 2008). Results Table 2 summarizes the airflow rate and psychromet- ric parameters measured in all three cases. The airflow increased from 706 ± 14 ­ m3 /h (9.3 ± 0.2 ACH) before the filters were replaced (Case 1) to 1954±40 ­ m3 /h (25.8±0.5 ACH) after the filters were replaced (Case 2). This value was very close to the airflow in Case 3, which was 2051±41 ­m3 /h (27.1±0.5 ACH) and close to the Brazilian standard ABNT NBR 7256 (2005) (Table 1). For Case 1, the airflow rate was 66.4% below the recommendation; for Case 2, it was 7%; and for Case 3, it was near 2% of the Brazilian standard. Table 2  Psychrometric and airflow rate parameters
  • 5. 689 International Journal of Environmental Research (2020) 14:685–692 1 3 Figure 2 presents the impact of the filter on the total par- ticle count, which was assessed before and after the air con- ditioning filters were replaced (Cases 1 and 2, respectively) and in the new room (Case 3). It can be seen from this figure that the change in the filter significantly decreased the par- ticle concentration inside the room. For Case 1, the average particle concentration was 15.0×106 ±4.0×106 particles/ m3 . For Case 2, the average decreased to 0.4×106 ±0.2×106 particles/m3 , thereby indicating that the average total particle concentration decreased by approximately 97%. Statistical analysis showed that the difference between the average particle concentrations for these two cases was significant (p < 0.05). For Case 3, the particle concentration had an average of 0.3×106 ±0.1×106 particles/m3 . Comparing the average particle concentration for Case 1 with that of Case 3, the latter was approximately 98% lower than the former (p < 0.05). The average particle concentrations for Case 2 and Case 3 were close, which was already expected, as all the parameters, according to Brazilian standard ABNTNBR 7256 (2005), for both rooms were almost the same. Figure 3 shows the concentration of viable particles measured before (Case 1) and after (Case 2) the air con- ditioning filters were replaced in the old room and in the new room (Case 3). The concentration of viable particles measured in Case 1 was notably higher than that measured in Case 2 and Case 3. The average viable particle concen- trations were57 ± 8 CFU/m3 in Case 1, 24 ± 7 CFU/m3 in Case 2, and 15 ± 3 CFU/m3 in Case 3. On comparing the averages between Case 1 and Case 2, the viable particle con- centration in Case 2 was lower, thereby indicating that the average total particle concentration was almost half (53%). Statistical analysis showed that the difference was significant (p < 0.05). The average viable particle concentration was 72% higher before the filters were replaced (Case 1) than in the new room (Case 3). This difference was statistically significant (p≤0.05). However, the differences between the average particle concentrations after the filters were replaced (Case 2) and in the new room (Case 3) were not significant (p>0.05). Table 3 presents the gram-negative and gram-positive bacterial percentages, the prevalence of coagulase-negative Staphylococci, and the concentrations of ­ CO2 measured during all the surgeries. The concentration of gram-positive bacteria was greater than that of gram-negative bacteria. The prevalence of gram-positive bacteria was not affected by fil- ter replacement (p > 0.05); that is, it continued to remain high at 91±4% for Case 1, 92±5% for Case 2, and 90±6% for Case 3. The samples were also tested for coagulase-negative bacteria to differentiate S. aureus from coagulase-nega- tive Staphylococci. The prevalence of coagulase-negative Staphylococci remained high in all surgeries. For Case 1, the average was 86±3%; for Case 2.67±16%; and for Case 3.76±9%. It is important to highlight that coagulase-nega- tive Staphylococci are the most common cause of nosoco- mial infections. Table 3 shows that the ­ CO2 concentrations were practi- cally not affected by the filter replacements. In the new room, ­CO2 concentration was kept constant. The average ­ CO2 con- centrations were 663±21 ppm in Case 1, 659±28 ppm in Case 2, and 575±4 ppm in Case 3. Discussion Before the filters were replaced, the system operated at an airflow of 706 ­ m3 /h (9.3 ACH), and the average total and viable particle concentrations inside the room were 15.0×106 ±4.0×106 particles/m3 and 57.4 CFU/m3 , respec- tively. After the replacement, the airflow increased to 1954 ­m3 /h (25.8 ACH), and the respective averages of particle 1.0E+05 1.0E+06 1.0E+07 1.0E+08 Case 1 Case 2 Case 3 Par cles/m 3 Fig. 2  Total particle (0.3–10 μm) count in Case 1 (before filter replacement); Case 2 (after filter replacement); and Case 3 (new room) 0 10 20 30 40 50 60 70 Case 1 Case 2 Case 3 CFU/m 3 Fig. 3  Colony forming units (CFU) measured before (Case 1) and after (Case 2) the air conditioning filters replacement and in the new room (Case 3)
  • 6. 690 International Journal of Environmental Research (2020) 14:685–692 1 3 concentrations decreased to 0.4×106 ±0.2×106 particles/ m3 and 24.5 CFU/m3 , respectively. The Brazilian standard ABNT (2005) recommends 2800 ­ m3 /h (28 ACH) in an oper- ating room. These results showed that with filter replace- ment, the airflow inside the room increased by almost three times, and viable particle concentration and total particle concentration decreased by 53% and 97%, respectively. The differences between the average particle concentra- tions after the filters were replaced and in the new room were around 60%. However, it is important to highlight that this difference was due to the fact that in the new room there was no dust or debris accumulated from years of use within the duct system. Thus, this is the reason for the large difference in the particle concentration between the two rooms. These results suggest that inadequate or ineffective venti- lation, caused by dirty or saturated filters, results in elevated contaminant levels. This is because the particles remain inside the room with less air exchange. On the other hand, proper ventilation with greater airflow causes them to follow the airflow pattern, leading to their capture by filters. It is also worth mentioning that changing filters and increasing airflow produces a greater effect on the total particle con- centration than on the viable particle concentration. This is expected, because viable particles make up only a very small portion of the total particle concentration. These results are in agreement with those reported by Memarzadeh and Manning (2002) and Vonci et al. (2019). They concluded that increasing air change per hour results in high removal of particles inside an operating room. Chow and Yang (2004) reported that a higher dilution effect leads to a lower concentration of airborne contaminants in operat- ing rooms, including bacteria and anesthetic gas. Accord- ing to Pereira et al. (2012), indoor particle concentration decreases with increasing air change rate in operating rooms, as indicated by the simulation results. Although there is presently no common standard method used to determine the microbiological threshold limits in surgical room settings (Dharan and Pittet 2002), the average microbiological particle concentration determined in this study after filter replacement was similar to that previously reported in other studies (Vonci et al., 2019). Landrin et al. (2005) determined a microbiological count ranging from 0 to 38 CFU/m3 . Dallolio et al. (2017) monitored 10 operating rooms found a microbiological contamination of air ranging from 2 to 27 CFU/m3 . The results also showed that after filter replacement, the total count of particle concentration agreed with previous studies (Pereira et al., 2012; Nimra et al., 2015). Mirhoseini et al. (2015), using an optical particle counter (0.5–10 µm) to assess the total particle concentration in an operating room and found an average concentration of 0.4 × 106 particle/ m3 . Nimra et al. (2015) compared the total concentration of particles in the air in public and private hospitals and found an average concentration of 4.0×106 particles/m3 in pub- lic hospitals and 0.1×106 particles/m3 in private hospitals. Morawska et al. (1998) investigated the particle concentra- tion levels and size distribution in a complex hospital system using submicrometer and supermicrometer instrumentation. The authors found a particle concentration (0.5–30 µm) of 0.7×106 particles/m3 in a small surgical room. Regarding the species of microorganisms found inside the room, the results showed a significant prevalence of gram-positive bacteria during most of the surgeries. It was also found that the prevalence of gram-positive bacteria was not affected by filter replacement. This finding was in accordance with Dolinger et al. (2010), who also found a high prevalence of gram-positive bacteria during different orthopedic surgeries. Furthermore, Gallo et al. (2003) suggested that the gram- positive bacteria that are released from skin, hair, and nos- trils may be deposited on surfaces. However, according to Edmiston et al. (2005), skin and nasal shedding by members Table 3  Gram-negative and gram-positive bacterial percentages, prevalence of coagulase-negative Staphylococci, and concentrations of ­ CO2 measured during all the surgeries
  • 7. 691 International Journal of Environmental Research (2020) 14:685–692 1 3 of the surgical team might be a risk factor for perioperative contamination and subsequent infection. Further observation regarding the species of microor- ganisms revealed that after filter replacement, there was a decrease of 23% in coagulase-negative Staphylococci, which were found to be present during 76.75% of surger- ies, while gram-negative bacteria were present in 9.0% of the cases. Edmiston et al. (2005)found that Staphylococci and gram-negative bacteria were present in 86% and 33% of cases, respectively. Coagulase-negative Staphylococci are among the most commonly identified microorganisms in surgical site infections (Edmiston et al. 2005; Becker et al. 2014). According to Dolinger et al. (2010), most ortho- pedic implant-related infections are due to gram-positive aerobic bacteria, predominantly S. aureus and S. epider- midis (44–50%). These microorganisms form biofilms on the surfaces of prostheses and implants, thereby providing resistance to antibiotics Roberts et al. (2006). Suggested that skin flakes are relatively large particles (4–25 µm) that can transport Staphylococci when released or re-suspended. Therefore, despite the threats posed by these microorgan- isms, few studies have comprehensively addressed the trans- mission route of coagulase-negative Staphylococci in hospi- tals (Milisavljevic et al. 2005; Monsen et al. 2005; Botelho et al. 2012). According to studies, coagulase-negative Staph- ylococci have emerged as high-risk pathogens in relation to the development of post-surgical infections, particularly in prostheses surgeries (Dolinger et al. 2010). According to Sagi et al.( 2002), instruments that have an air exhaust may be a source of airborne microorganisms, among which the major microorganisms are coagulase-negative Staphylococci and Micrococcus sp. With respect to ­ CO2, it was found that the concentration was not affected by filter replacement. The ­ CO2 concentra- tions remained practically constant and below 1000 ppm for all three cases. This is because even with saturated filters, the amount of air supplied to the room is sufficient to dilute the ­CO2 generated by the people. However, it is not sufficient to dilute the particles generated inside the room. Finally, it was also found that temperature and humidity were not affected by filter replacement. Both remained con- stant for all three cases. Conclusions The total and viable particle and ­ CO2 concentration in an old operating room before the air conditioning filters were replaced, after the air conditioning filters were replaced, and in a new operating room with a new filter and normal airflow were studied. The results of this exploratory study showed that systems operating with saturated filters can suffer from pressure drop, which can lead to reduced air flow, resulting in an increase in the average of total particle and viable par- ticle concentrations. However, the replacement of the filters does not affect the ­ CO2 concentration. Few studies have undertaken a quantitative determination of the impact of the filtration system on indoor contamina- tion in an orthopedic operating room. Further studies are needed in this field to ensure good indoor air quality and to protect patients and healthcare workers against hospital- acquired infections and occupational diseases. Therefore, the practical data presented in this work could serve as a basis for corrective action in controlling airborne contamination in operating rooms and may contribute to the overall knowl- edge of the importance of ventilation and filtration systems in this field. Finally, it is also important to highlight that the pressure drop in filters is a factor that directly affects the extra electric energy power in the fan operation and may adversely affect the performance of the air conditioning system. Hence, in future studies, it will be important to assess whether the fan motor electric energy consumption savings would cover the costs of replacing the filters. Acknowledgements The authors would like to thank Eng. Tomaz Pulga from the Orthopedics and Traumatology Institute of São Paulo for his immense support. Marcelo Luiz Pereira would like to thank the International Laboratory for Air Quality & Health (ILAQH), Queens- land University of Technology (QUT), where he was a visiting fellow. Compliance with Ethical Standards Conflict of Interest On behalf of all authors, the corresponding author states that there is no conflict of interest. References Nbr ABNT (2005) Air conditioning for health care facilities - Require- ments for design and installation. Standard 7256:2005 Alsaleem F, Munroe M, Rafaie M (2016) Current based HVAC systems air filter diagnostics and monitoring. In: 4th International High Performance Buildings Conference at Purdue, July 11–14, 2016. Andersen AA (1958) New sampler for the collection, sizing, and enu- meration of viable airborne particles. J Bacteriol 76(5):471–484 ASHRAE (2019) Ventilation for acceptable indoor air. Atlanta: Ameri- can Society of Heating, Refrigerating and Air-Conditioning Engi- neers. Standard 62: 2019. Becker K, Heilmann C, Peters G (2014) Coagulase-Negative Staphy- lococci. Clin Microbiol Rev 27(4):870–926 Beggs CB (2003) The Airborne Transmission of Infection in Hospital Buildings: fact or fiction? Indoor Built Environ 12:9–18 Botelho AM, Nunes ZD, Asensi MD, Gomes MZ, Fracalanzza SE, Figueiredo AM (2012) Characterization of coagulase-negative Staphylococci isolated from hospital indoor air and a comparative analysis between airborne and inpatient isolates of Staphylococcus epidermidis. J Med Microbiol 61:1136–1145 Centres for Disease Control and Prevention (CDC) (2003) Guide- lines for environmental infection control in health-care facilities.
  • 8. 692 International Journal of Environmental Research (2020) 14:685–692 1 3 Atlanta, U.S. Department of Health and Human Services Centres for Disease Control and Prevention. Chow TT, Yang Y (2004) Ventilation performance in operating theatres against airborne infection: review of research activities and practi- cal guidance. J Hosp Infect 56(2):85–92 Cole EC, Cook CE (1998) Characterization of infectious aerosols in health care facilities: an aid to effective engineering controls and preventive strategies. Am J Infect Control 26:453–464 Dallolio L, Raggi A, Sanna T et al (2017) Surveillance of environmen- tal and procedural measures of infection control in the operating theatre setting. Int J Environ Res Public Health 15(1):46 Dascalaki EG, Lagoudi A, Balaras CA, Gaglia AG (2008) Air quality in hospital operating rooms. Build Environ 43:1945–1952 Dharan S, Pittet D (2002) Environmental controls in operating theatres. J Hosp Infect 51(2):79–84 Dolinger EJ, Brito DV, Souza GM, Melo GB, Gontijo Filho PP (2010) Air contamination levels in operating rooms during surgery of total hip and total knee arthroplasty, hemiarthroplasty and osteo- synthesis in the surgical center of a Brazilian hospital. Rev Soc Bras Med Trop 43(5):584–587 ((article in Portuguese)) Edmiston CE Jr, Seabrook GR, Cambria RA, Brown KR, Lewis BD, Sommers JR (2005) Molecular epidemiology of microbial con- tamination in the operating room environment: Is there a risk for infection? Surgery 138:573–582 Fernstrom A, Goldblatt M (2013) Aerobiology and itsrole inthe trans- mission of infectious diseases. J Pathog 2013:493960 Fisk WJ, Faulkner D, Palonen J, Seppanen O (2002) Performance and costs of particle air filtration technologies. Indoor Air 12(4):223–234 Gallo J, Kolar M, Novotny R, Rihakova P, Ticha V (2003) Pathogen Prosthes-Relat Infect Biomed Papers 147:27–35 Gormley T, Markel TA, Jones H, Greeley D, Ostojic J, Clarke JH, Abkowitz M, Wagner J (2017) Cost-benefit analysis of different air change rates in an operating room environment. Am J Infect Control 45(12):1318–1323 Gosden PE, MacGowan AP, Bannister GC (1998) Importance of air quality and related factors in the prevention of infection in ortho- paedic implant surgery. J Hosp Infect 39:173–180 Hanley JT, Esnor DS, Smith DD, Sparks LE (1994) Fraction aerosol filtration efficiency of in-duct ventilation air cleaners. Indoor Air 4:169–178 ISO/IEC – International Organization for Standardization/International Electrotchnical Commission. GUM 98–3. Guide to the expression of uncertainty in measurement. 2008. Jamariska M, Morawska L, Clark BA (2000) Effect of ventilation and filtration on submicrometer particles in an indoor environment. Indoor Air 10(1):19–26 Karthikeyan CP, Samuel AA (2008) CO2-dispersion studies in an oper- ation theatre under transient conditions. Energy Build 40:231–239 Landrin A, Bissery A, Kac G (2005) Monitoring air sampling in operat- ing theatres: can particle counting replace microbiological sam- pling? J Hosp Infect 61:27–29 Maus R, Goppelsroder A, Umhauer H (2001) Survival of bacterial and mold spores in air filter media. Atmos Environ 35:105–113 Memarzadeh F, Manning AP (2002) Comparison of operating room ventilation systems in the protection of the surgical site. ASHRAE Trans 108(2):3–15 Milisavljevic V, Wu F, Cimmotti J, Haas J, Della-Latta P, Larson E et al (2005) Genetic relatedness of Staphylococcus epidermidis from infected infants and staff in the neonatal intensive care unit. Am J Infect Control 33:341–347 Mirhoseini SH, Nikaeen M, Khanahmd H, Hatamzadeh M, Hassan- zadeh A (2015) Monitoring of airborne bacteria and aerosols in different wards of hospitals—particle counting usefulness in investigation of airborne bacteria. Ann Agric Environ Med 22(4):670–673 Monsen T, Karlsson C, Wistro MJ (2005) Spread of clones of multid- rug-resistant, coagulase-negative Staphylococci within a univer- sity hospital. Infect Control Hosp Epidemiol 26(1):76–80 Morawska L, Jamriska M, Francis P (1998) Particulate matter in the hospital environment. Indoor Air 8:285–294 Morawska L (2006) Droplet fate in indoor environments, or can we prevent the spread of infection? Indoor Air 16:335–347 Nimra A, Ali Z, Khan MN, Gulshan T, Sidra S, Gardezi JR, Tarar MR, Saleem M, Nasir ZA, Colbeck I (2015) Comparative ambient and indoor particulate matter analysis of operation theatres of govern- ment and private (trust) Hospitals of Lahore, Pakistan’. J Anim Plant Sci 25(3):628–635 Nogler M, Krismer M, Haid C, Ogon M, Bach C, Wimmer C (2001) Excessive heat generation during Cutting of cement in the Robo- doc hip-revision procedure. Acta Orthop Scand 72(6):595–599 Offermann FJI, Loiselle SA, Sextro G (1992) Performance of air clean- ers in a residential forced air system. ASHRAE J 34(7):51–57 Pereira ML, Vilain R, Leivas TP, Tribess A (2012) Measurement of the concentration and size of aerosol particles and identification of the sources in orthopedic surgeries. HVAC&R Res 18(4):588–601 Pereira ML, Vilain R, Galvão FHF, Tribess A, Morawska L (2013) Experimental and numerical analysis of the relationship between indoor and outdoor airborne particles in an operating room. Indoor Built Environ 22(6):864–875 Pereira ML, Knibbs LD, He C, Grzybowski P, Johnson GR, Huffman JA, Bell SC, Wainwright CE, Matte DL, Dominski FH, Andrade A, Morawska L (2017) Sources and dynamics of fluorescent par- ticles in hospitals. Indoor Air 27(5):988–1000 Roberts K, Hathway A, Fletcher LA, Beggs CB, Elliott MW, Sleigh PA (2006) Bioaerosol production on a respiratory ward. Indoor Built Environ 15(1):35–40 Sagi HC, DiPasquale T, Sanders R, Herscovici D (2002) Compressed- air power tools in orthopaedic surgery: exhaust air is a potential source of contamination. J Orthop Trauma 16(10):696–700 Simmons RB, Crow SA (1995) Fungal colonization of air filters for use in heating, ventilating, and air conditioning (HVAC) systems. J Ind Microbiol 14:41–45 Simmons RB, Price DL, Noble JA (1997) Fungal colonization of air filters from hospitals. Am Ind Hyg Assoc J 58:900–904 SPSS (2015) SPSS for windows. Version 16.0. SPSS Inc., Chicago Stetzenbach LD, Buttner MP, Cruz P (2004) Detection and enumera- tion of airborne contaminants. Curr Opin Biotech 15(3):170–174 Vonci N, Marco MF, Grasso A, Spataro G, Cevenini G, Messina G (2019) Association between air changes and airborne micro- bial contamination in operating rooms. J Infect Public Health 12(60):827–830 Yang L, Braun JE, Groll EA (2007) The impact of evaporator fouling and filtration on the performance of packaged air conditioners. Int J Refrig 30(3):506–514 Zoon WAC, Van Der Heijden MGM, Loomans MGLC, Hensen JLM (2010) On the applicability of the laminar flow index when select- ing surgical lighting. Build Environ 45(9):1976–1983