IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 
_______________________________________________________________________________________ 
Volume: 03 Issue: 01 | Jan-2014, Available @ http://www.ijret.org 472 
EFFECTS OF NOCTURNAL VENTILATION AND RADIANT COOLING/ HEATING FLOORS ON INDOOR AIR TEMPERATURES IN AN OFFICE BUILDING IN HOT ARID REGION G. Alvarez1, M.J. Jiménez2, M.R. Heras2, M.A. Chagolla3, J. Arce2& J.P. Xamån2 
1ME Department, Centro Nacional de InvestigaciĂłn y Desarrollo TecnolĂłgico-TMN-SEP. Morelos. MĂ©xico. Email: gaby@cenidet.edu.mx. 
2 Energy Efficiency in Buildings Unit. Centro de Investigaciones EnergĂ©ticas, Medioambientales y TecnolĂłgicas. Spain. Email: mjose.jimenez@psa.es 3Instituto TecnolĂłgico de Zacatepec-TNM-SEP. Morelos, Mexico. Abstract The effects of nocturnal ventilation and radiant cooling/heating floors on indoor air temperatures in an office building in hot arid region are evaluated. Climatic and indoor temperatures are measured and compared against predicted ones using TRNSYSÂź, obtaining a 7% difference. A parametric study was conducted that varied floor temperatures to simulate radiant floor heating on the coolest day and nocturnal ventilation or/and radiant floor cooling on the hottest day in 2009. Results indicated that, during the winter, radiant floor heating increased the indoor air temperatures from 13.5ÂșC to 19.6ÂșC. During the summer, the indoor air temperature decreased from 32.1ÂșC to 27.4ÂșC at midnight, with a nocturnal ventilation of 5 ACH. Combining ventilation and radiant floor cooling decreased the indoor air temperatures to 26.9ÂșC (0.5ÂșC lower). As a result, the effect of nighttime ventilation was significant on indoor temperatures in the building; however, the effect of radiant floor cooling was almost negligible. Key Words: Office building, Radiant floor, Nocturnal ventilation, Conservation of energy. 
--------------------------------------------------------------------***---------------------------------------------------------------------- 1. INTRODUCTION Energy use in buildings accounts for 40% of total energy consumption. Developing countries are concerned over the augmented use of air conditioning systems [1]. Along with the increase in energy consumption, there are debates over whether air conditioned buildings should be recommended or prohibited due to discomfort (drafts, noise and impure air) [2]. In desert regions, energy consumption for thermal comfort conditions is very high. Some authors recommend using or managing passive or active techniques such as ventilation, radiant floor cooling or heating in order to decrease energy consumption and improve the indoor thermal environment in buildings during both summer and winter months [3]. Infiltration of air in buildings has been studied by McDowell et al. [4] to determine its impact on the thermal loads; they found that infiltration has a much higher negative impact on heating loads than on cooling loads. Also, management of passive cooling have a significant impact on the thermal summer comfort in a building [5]. Predictive control strategies improved the energy efficiency of intermittently heated radiant floor heating systems finding energy savings between 10% and 12% during cold winter months [6]. In 2006. Tian and Love [7] studied multi-floor radiant slab cooling through simulation and field measurements, reporting that even though radiant floor cooling has the potential to improve energy efficiency; it must be coordinated with air handling systems to avoid conflicts. However, radiant floor cooling systems are not recommended in humid climates because of condensation [8]. 
Very few authors have considered the combination of passive/active techniques such as nocturnal ventilation and radiant floor cooling. In 2000, Hayter and Torcellini [9] described a technique for designing and constructing low- energy buildings in which the HVAC design included radiant slab heating and natural ventilation cooling through an automatic window control, with a transpired solar collector (TSC) to preheat ventilation air for warehouses. However, Olesen et al. [10] found that the primary problem with combining radiant floor heating and displacement ventilation was inadvertently producing the opposite effects of the two systems; that is, if the floor temperature was too high, the supply air rose, reducing the ventilation effectiveness of the system and producing a mixing flow pattern in the room. If, however, the overheated floor is combined with displacement ventilation, the air could be supplied at a lower temperature for the ventilation system (depending on the external climate), with a resulting
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 
_______________________________________________________________________________________ 
Volume: 03 Issue: 01 | Jan-2014, Available @ http://www.ijret.org 473 
reduction in the energy consumption [11]. Thus, the 
combination of active/passive techniques is not sufficiently 
studied. 
The aim of this study is to study the effects of nocturnal 
ventilation and/or radiant floor cooling in summer and 
radiant floor heating in winter on the indoor air temperatures 
of a high thermal mass office building (heavyweight 
construction) located in an arid region. 
2. CASE OF STUDY 
The office building is a rectangular-shaped building of 
1,114.96 m2, shown in Fig. 1, with its façade facing south. It 
is located in the city of Tabernas in Spain, at 37Âș 05’ 27.8‖N 
latitude and 2Âș 21’ 19‖ W longitude. It lies at 555 m above 
sea level in a subtropical desert with scarce and irregular 
rain (200 mm per year), a high rate of irradiance (almost 
3000 hours of sunlight per year) and large ambient 
temperature swings (12oC). During 2009, the minimum 
monitored temperature was during January (-1.4ÂșC), and the 
maximum temperature was during July (41.7ÂșC). 
Fig. 1. View of the office building and location of the 
monitored office. 
2.1 Climate Conditions 
A meteorological station installed on the roof of the building 
monitored the environmental climate conditions. Figures 
2(a) and 2(b) show the average monthly solar radiation on 
the roof and south façade, the average monthly ambient 
temperature, the average monthly relative humidity and the 
average monthly wind velocity of 2009. Figure 2(a) shows 
that the monthly solar radiation was highest in June (7.66 
kW-h/m2) and July (7.63 kW-h/m2); the average monthly 
solar radiation falling on the south façade was lower in 
summer and higher in winter as expected at this latitude. 
Average amount of sunshine was 14 hours during summer 
and 9 hours in winter. Figure 2(b) shows the average 
monthly ambient temperatures, humidity and wind 
velocities. Maximum average monthly temperature was in 
July (27.6oC) and the minimum was in December (8.5oC); 
lowest average monthly relative humidity was in June 
(40.1%) and highest was in October (71.2%). Average 
monthly wind velocity oscillated in the range of 2.3-3.1 m/s. 
(a) (b) 
Fig. 2. (a) Monthly global horizontal and southern solar 
radiation and (b) Monthly average wind velocity, ambient 
temperature and relative humidity for 2009. 
2.2 Building Characteristics 
The envelope of the building is constructed of thick 
multilayer composite walls to guarantee insulation, and the 
double-glazed aluminum framed windows are shaded to 
reduce the amplitude of the indoor temperature changes and 
prevent direct solar gains in summer. The south façade is 
protected by a 2 m projection (porch roof) to avoid direct 
beam radiation during the summer. More detailed features of 
the building were previously reported in [12]. 
Table 1 shows the construction materials of the walls and 
roof and their thermophysical properties. The composite 
wall is 44 cm thick, with an air gap at the center and 
polyurethane insulation material between the air gap and the 
hollow bricks. A Planitherm 4S window (from Climalit 
Products), 4.63 m2 in size with a U-value of 3.21 W/m2K 
and a g-value of 0.722 is installed at the south wall. A 1 m 
wide overhang lies 1.5 m above the window to avoid direct 
sunshine on the window during summer. 
Table 1. Building envelope components, dimensions and 
thermophysical properties 
Material L 
(m) 
k 
(W/m K) 
ρ 
(kg/m)3 
Cp, 
(kJ/kg K) 
Walls 
Gypsum 0.02 1.08 900 1.00 
Hollow brick 0.11 1.764 1200 0.90 
Air 0.14 
Polyurethane 0.04 0.144 12 1.80 
Hollow brick 0.11 1.764 1200 0.90 
Mortar 0.02 5.04 2000 1.10 
Roof 
Concrete 0.24 3.744 1500 1.00 
Mortar 0.14 5.04 2000 1.10 
Bitumen 0.005 0.828 1100 1.00 
Polystyrene 0.04 0.144 25 1.50 
Polypropylene 0.003 0.792 910 1.80 
Gravel 0.06 2.916 1700 0.90 
Floor 
Ceramic plate 0.25 3.78 1200 2.00 
Mortar 0.04 5.04 2000 1.10 
Sand 0.035 7.20 2000 1.00 
Concrete 0.15 8.28 2300 1.00 
Gravel 0.20 2.916 1700 0.90 
6.89 m 2.91 m 
3.4 m 7.5 m 
Zone B Zone A 
Zone B Zone A 
W 
E 
S N 
Temperature 
sensor 
Temperature 
sensor 
Monitored 
office 
0.0 
1.0 
2.0 
3.0 
4.0 
5.0 
6.0 
7.0 
8.0 
JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC 
Solar Radiation, kW-hr/m2 
Month 
MONTHLY AVERAGE DAILY GLOBAL SOLAR RADIATION 
HORIZONTAL SOUTH 
2.5 3.0 2.8 2.3 2.8 2.5 2.4 2.8 2.6 3.1 2.4 2.3 0 
10 
20 
30 
40 
50 
60 
70 
80 
90 
100 
0 
5 
10 
15 
20 
25 
30 
JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC 
Air temperature [ÂșC] Wind velocity [m/s] Relative humidity [%]
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 
_______________________________________________________________________________________ 
Volume: 03 Issue: 01 | Jan-2014, Available @ http://www.ijret.org 474 
The monitored office was chosen due to its location; it is 
located in the corner of the west end of the building as 
shown in Fig. 3(a). It is irradiated on the west and south 
walls, as well as the roof. The vertical and horizontal 
sketches of the cross section are shown in Figures 3(a) and 
3(b). The north wall of the office is next to a long hall, and 
the east wall is adjacent to the subsequent office. 
Fig. 3(a). West façade of the office 
(b) 
Fig. 3(b). Vertical cross-section of the office, 
(c) 
Fig. 3(c). West façade of the office. 
3. THERMAL SIMULATION OF THE OFFICE 
TRNSYSÂź program was used to simulate the thermal 
performance of the office. The following methodology was 
applied: 1) Two weekend days; one of extreme cold and 
another one of extreme hot temperatures of 2009 were 
chosen as the input data for TRNSYSÂź. 2) The building 
location, weather conditions, orientation, envelope 
components and dimensions were input into the TRNSYSÂź 
program, the indoor air temperatures of the office under a 
free-floating condition (no HVAC systems) were calculated 
and compared against those measured in order to calibrate 
the simulation. 3) A parametric study changing the 
ventilation rates and floor temperatures were carried out to 
predict the indoor air temperatures of the office. 4) Effects 
of every heating and cooling technique on the indoor air 
temperature were determined. 
3.1 Days for the Simulation 
Following the previous methodology, January 17th (the 
coolest day in winter) and Saturday, July 25th (the hottest 
day in summer) were the days for the simulation. Figures 
5(a)-(d) show the horizontal and vertical solar radiation, 
ambient temperature, relative humidity and wind velocity, 
corresponding to January 17th and July 25th. It can be seen 
from Figures 5(b) and 5(d) that the ambient temperatures 
dropped during the night and increased during the day; 
temperature; swings, day and night, were close to 10oC on 
both days. In winter day, Figure 5(a) shows that the solar 
radiation on the horizontal surface is lower than the 
radiation on the south surfaces–as expected. Sunrise was at 
8:00 hr; the solar radiation increased until 12:00 noon, then 
slowly decayed until 15:00 hr, when it abruptly dropped due 
to an obstruction on the roof relative to the position of the 
sun. 
(a) 
3.40 
4.94 
2.30 
1.50 
1.50 
Tf 
Tg 
Tw 
Tw 
Ta 
1.10 
1.00 
4.94 
6.00 
1.50 
1.10 
1.30 
Tf 
TR 
Ta Tg 
1.50 
0 
100 
200 
300 
400 
500 
600 
700 
800 
900 
1000 
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 
W/m2 
Hours 
Solar Radiation 
Horizontal South 
Winter day 
0 
10 
20 
30 
40 
50 
60 
70 
80 
90 
100 
0 
2 
4 
6 
8 
10 
12 
14 
16 
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 
Hours 
Ambient Temperature [C] Relative Humidity [%] Wind Velocity [m/s] 
Winter day
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 
_______________________________________________________________________________________ 
Volume: 03 Issue: 01 | Jan-2014, Available @ http://www.ijret.org 475 
(b) 
(c) 
(d) 
Fig. 5. (a) Incident solar radiation, (b) ambient temperature 
and relative humidity (January 17th); (c) solar radiation (d) 
ambient temperature and relative humidity (July 25th). 
The ambient temperature was 2.5 oC after 7:00 hr during the 
night and early morning; increasing to 13.2oC after 13:00 hr 
and then decreasing. The relative humidity was always 
higher at night (80-90%), decreasing during the day to 49% 
after 13:00 hr. Prior to 10:00 hr, as can be seen in Figure 
5(b), the wind velocity was in the low range (<2.5 m/s) but 
then fluctuated, reaching a maximum of 6.9 m/s after 11:00 
hr and decreasing (<3 m/s) after 17:00 hr. 
In the summer day, Figure 5(c) shows the solar radiation on 
the horizontal and south surfaces. The solar radiation on the 
horizontal surface was higher than the radiation on the south 
surface; sunrise was at 5:00 hr, and the solar radiation 
steadily increased after 12:00 hr. It then abruptly fell during 
the afternoon, and the humidity increased, indicating 
cloudiness see Figure 5(d). The ambient temperature was 
low at night, ranging between 26-28 oC and then rising to 33 
oC after 9:00hr; it then decreased after midnight to 21.8 oC, 
as expected due to cloudiness. The relative humidity was in 
the low range of 20-30 % at early morning and increased to 
90 % at midnight; the wind velocity fluctuation was in the 
low range at night (<3.5 m/s) and early morning, increasing 
after 7:00 hr to a maximum of 10.8 m/s after 12:00 hr and 
remaining high until the oscillations decreased after 23:00 
hr. 
For the TRNSYSÂź simulation, the office was divided into 
two zones: Zone A (hallway) and Zone B (office), as shown 
in Figure 3(b). The east wall of Zone B was considered to be 
adiabatic (adjacent office), as well as the eastside of the 
Zone A; the measured solar radiation was input to Type 16 
(Solar Radiation Processor). Envelope components of the 
office were input to Type 56 (Multi-Zone Building). 
TRNBuilt module was used to calculate the U-values for the 
wall. The U-values of the walls were 0.532 W/mÂČ K for heat 
transfer coefficients of 7.7 W/m2 K indoors and 25 W/m2 K 
outdoors. The roof U-value was 0.621 W/mÂČ K for 5.7 + 
3.8V outdoors and 9.26 W/mÂČ K indoors [15]. Absorptances 
of ceiling and walls were 0.3. Thermal capacitance of the 
office was 1000kJ/K (furniture + air), with lighting of 5 
W/m2. An ACH ventilation of 0.25 was considered, as 
suggested by ANSI/ASHRAE-62 [16]. Simulations were 
performed every minute for 24 hrs and results were plotted 
every hour. 
3.2 Measurement instruments of the office 
Six temperature sensors were installed in the office; the 
sensor measuring the air temperature was located 1.5 m 
above the floor and 0.10 m away from the north wall; the 
other five were attached at the middle of the floor, on the 
glazing, on the east and west walls and in the middle of the 
roof, as shown in Figure 3(b) [13]. The measurement 
instruments and their descriptions are presented in Table 2. 
Table 2. Instrumentation used for monitoring the office. 
Sensor Measured 
Variable 
Description 
2 Pyranometer, 
model CM11. 
Kipp and Zonen 
Horizontal 
and vertical 
global 
Solar 
Irradiance 
Spectral range from 285 
to 2800 nm; Sensitivity 
of 7 to 14 ÎŒV/W/mÂČ. 
1 Pygeometer, 
model CGR-4. 
Kipp and Zonen 
Long wave 
radiation 
from the 
surface of 
the test 
component 
Spectral range of 4500 to 
42000 nm, 5 to 15 
ÎŒV/W/mÂČ; Response time 
of18 s; Temperature 
dependence of sensitivity 
(-20 ÂșC to +50 ÂșC) < 1%. 
1 Sensor model 
WindSonic. 
Gill Instruments, 
LTD. 
Wind 
velocity 
Ultrasonic Output Rate of 
0.25, 0.5, 1, 2, and 4 Hz; 
Wind Speed of 0-60 m/s; 
1 Sensor model 
HMP45A/D. 
Vaisala. 
Outdoor 
relative 
humidity 
Range from 0.8 to 
100%RH; Accuracy at 
+20 °C. Response time 
(90% at +20 °C) 10 s. 
Platinum 
thermo-resistance, 
PT100 
Air 
temperature 
Accuracy: 1/10 DIN of 
Class B with a tolerance 
of ±0.3°C at 0°C. 
Platinum 
thermo- 
Surface 
temperature 
Accuracy: 1/10 DIN of 
Class B with a tolerance 
0 
100 
200 
300 
400 
500 
600 
700 
800 
900 
1000 
1100 
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 
W/m2 
Hours 
Solar Radiation 
Horizontal South 
Summer day 
0 
10 
20 
30 
40 
50 
60 
70 
80 
90 
100 
20 
22 
24 
26 
28 
30 
32 
34 
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 
Hours 
Ambient Temperature [C] Relative Humidity [%] Wind Velocity [m/s] 
Summer day
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 
_______________________________________________________________________________________ 
Volume: 03 Issue: 01 | Jan-2014, Available @ http://www.ijret.org 476 
resistance, 
PT100 
of ±0.3°C at 0°C. 
A data acquisition system of 16-bit A/D resolution was 
used. The uncertainty, u(Ti), corresponding to the 
measurement of indoor air temperature, Ti, was calculated 
according to ISO 5725 [14]. The calculated air temperature 
uncertainty was 0.4C with a 95% level of confidence, using 
a coverage factor of k*=2. 
3.3 Comparison between measured and predicted 
indoor temperatures 
Figures 6(a) and 6(b) show the mean ambient air 
temperature and the measured and predicted indoor air 
temperatures in both the winter and summer days, 
respectively. 
(a) 
(b) 
Fig 6. Ambient temperatures and monitored and predicted 
temperatures for (a) winter (Jan 17th) and (b) summer (July 
25th). 
Both Figures show that the predicted indoor air temperature 
of the office follows the same pattern of the measured one; 
the amplitude of the fluctuation compared to the ambient 
temperature was small due to the high thermal inertia of the 
envelope. As seen in Figure 6(a), the mean minimum 
outdoor ambient temperature was 3.1ÂșC at 7:00 hrs, and the 
maximum was 12.8ÂșC at 15:00 hrs a difference of 9.7ÂșC; the 
minimum and maximum mean measured temperatures were 
12.2ÂșC at 8:00 hrs and 13.5ÂșC a difference of 1.3ÂșC; the 
minimum and maximum mean predicted temperatures were 
11.6ÂșC at 8:00 hrs and 13.1ÂșC at 15:00 hrs a difference of 
1.5ÂșC. A comparison between the measured and predicted 
indoor air temperatures indicates that their maximum 
difference was 0.9ÂșC (7.2%) at night and the minimum was 
0.3ÂșC (2.5%), with a correlation coefficient of r2=0.92. 
During the night, the indoor air temperatures were not as 
low as the outside ambient temperatures, demonstrating that 
the thermal inertia of the building plays an important role. 
On the summer day, Figure 6(b) show that the maximum 
mean ambient temperature was 32.4ÂșC at 10:00 hrs, and the 
minimum was 22.0 ÂșC at 24:00hrs a difference of 10.4ÂșC. 
The maximum and minimum mean measured temperatures 
were 32.2ÂșC at 18:00 and 31.5ÂșC at 7:00 hrs—a difference 
of 0.7ÂșC; the maximum and minimum mean predicted 
temperatures were 31.5ÂșC at 15:00 hrs and 31.1ÂșC at 
24:00—a difference of 0.4ÂșC. As previously noted, the 
indoor air temperature fluctuation is nearly negligible, so it 
is clear that heat accumulated inside the building. A 
comparison between the measured and predicted indoor air 
temperatures shows that their maximum difference was 
1.0ÂșC (7.2%) at night, and their minimum difference was 
0.2ÂșC (2.5%), with a correlation coefficient of r2=0.92. The 
predicted and measured indoor air temperatures show very 
close agreement, thus calibrating the TRNSYSÂź program. 
These results show that it is necessary to remove the 
accumulated heat in the office during the summer. 
Therefore, nocturnal cooling is desirable for preventing 
overheating by taking advantage of the minimum outdoor 
air temperature. 
4. PARAMETRIC STUDY 
The parametric study considers three techniques: radiant 
floor heating and cooling and nocturnal ventilation. Radiant 
heating/cooling systems refer controlled surface floor 
temperature. To simulate the radiant floor heating or 
cooling, the measured floor temperature were taken as floor 
base temperature and increased for heating or decreased for 
cooling in the simulation. Nocturnal ventilation refers to 
cooler air driven into the building during the night, reducing 
temperatures in the building. Normally, ventilation rates are 
measured by AHC (Air Changes per Hour) [16]. 
4.1. Effect radiant floor heating 
For the winter day, two cases were considered: 1) the 
measured floor temperature, Tfloor-M, were increased by 5oC, 
10ÂșC and 15ÂșC during 9:00 to 18:00 hrs, and 2) the same but 
for 24 hrs. Figures 7(a) and 7(b) show the ambient 
temperatures (Tamb), floor base temperature (Tfloor-M), indoor 
measured air temperatures (TzoneB-M) and the predicted one 
(TzoneB) for cases 1) and 2), respectively. As can be seen in 
Figure 7(a), increasing Tfloor –M, by 5oC, 10ÂșC and 15ÂșC 
during 9 hours resulted in increments of indoor air 
temperatures (TzoneB) of 0.3oC, 1.2ÂșC and 2.2oC on average, 
respectively. 
0 
1 
2 
3 
4 
5 
6 
7 
8 
9 
10 
11 
12 
13 
14 
0 
2 
4 
6 
8 
10 
12 
14 
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 
Diff.(TzoneB-M, TzoneB-P),oC 
Air temperature, oC 
Tambient TzoneB-M TzoneB-P Diff. 
Time, hr 
Winter day 
0 
1 
2 
3 
4 
5 
6 
7 
8 
9 
10 
11 
12 
13 
14 
20 
22 
24 
26 
28 
30 
32 
34 
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 
Diff.(TzoneB-M,TzoneB-P),oC 
Air temperature, oC 
Tambient TzoneB-M TzoneB-P Diff. 
Time, hr 
Summer day
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 
_______________________________________________________________________________________ 
Volume: 03 Issue: 01 | Jan-2014, Available @ http://www.ijret.org 477 
Figure 7(a) shows that an increment of 15ÂșC of the floor 
base temperature increased the indoor air temperature to a 
maximum of 15.8oC at 15:00 hr, against the outdoor ambient 
temperature of 12.8oC. Similar results are presented by 
Figure 7(b), but for 24 hours of floor heating. The 
augmentation of the floor base temperatures of the office by 
increments of 5oC, 10oC and 15oC caused the increase in the 
indoor air temperatures in increments of 1.5oC, 3.7oC and 
5.8oC on average, respectively. For increments of 15ÂșC for 
24 hours, the minimum indoor air temperature reached was 
18.1oC and the maximum was 19.6oC at 15:00 hrs. The 
indoor air temperatures were in the low range (18oC-20oC) 
of acceptable temperatures [17]. 
(a) 
(b) 
Fig. 7. Ambient temperature, measured floor and indoor 
temperatures and predicted indoor temperatures for different 
radiant heating floor temperatures from (a) 9-18 hrs and (b) 
0-24 hrs. 
4.2. Effect of radiant floor cooling 
For the summer day, three cases were considered for the 
simulation: 1) floor base temperature of the office decreased 
by 1oC, 2oC, 3oC, 4oC and 5oC, during 9:00 to 18:00 hrs, 2) 
nocturnal ventilation rates of 1, 2, 3, 4 and 5 ACH from 
20:00 to 6:00 hrs and 3) a combination of these two 
techniques. Figures 8(a) and 8(b) show the ambient 
temperature, the floor base temperature and indoor 
temperature against the predicted one for cases 1) and 2). 
Both figures show that the oscillation of the indoor 
measured air temperature of the office (31.5oC-32.2oC) was 
lower than the oscillation of the ambient temperatures (22.0 
oC-32.4 oC). The indoor air temperatures were always higher 
than outdoor air temperatures, indicating that heat was 
accumulating inside the office and therefore throughout the 
building. 
(a) 
(b) 
Fig. 8. (a) Ambient temperature, floor base temperature and 
indoor measured air temperatures and predicted ones for 
different radiant cooling floor temperatures from 20-6 hrs 
and (b) for different infiltration rates from 20-6 hrs. 
For case 1), Figure 8(a), shows that floor base temperature 
decrements of 1oC, 2oC, 3oC, 4oC and 5oC from 9:00-18:00 
hrs causes decrements of the indoor air temperatures of 
0.7oC, 0.9oC, 1.1oC, 1.3oC and 1.5oC respectively. In this 
case, the predicted minimum indoor air temperature was 
30.2oC at midnight, which represented a very small decrease 
in 1.9oC. For case 2, Figure 8(b), shows the effect of 
nocturnal ventilation rates on indoor air temperatures. As 
seen in this figure, the predicted indoor air temperatures at 
the office rapidly decreased at night. For nocturnal ACH 
ventilation rates of 1, 2, 3, 4 and 5 (from 20:00 to 6:00 hrs), 
the decrement of the indoor air temperatures was 1.1oC, 
1.6oC, 2.0oC, 2.3oC, 2.5oC respectively. During the night, for 
an ACH rate of 5, the lowest predicted indoor air 
temperature was 27.4oC, which represented a decrease of 
4.7oC; during daylight. Thus, nocturnal ventilation 
techniques are very important in hot arid climates during the 
summer. 
0 
5 
10 
15 
20 
25 
30 
35 
40 
10 
11 
12 
13 
14 
15 
16 
17 
18 
19 
20 
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 
Tambient oC 
Temperature, oC 
Time, hr 
Tfloor-M. TzoneB-M. TzoneB(Tfloor-M+5ÂșC) 
TzoneB (Tfloor-M+10 ÂșC) TzoneB(Tfloor-M+15ÂșC) Tambient. 
Winter day 
0 
4 
8 
12 
16 
20 
24 
28 
32 
36 
40 
10 
11 
12 
13 
14 
15 
16 
17 
18 
19 
20 
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 
Tambient , oC 
Temperature, oC 
Time, hr 
Tfloor-M TzoneB-M TzoneB(Tfloor-M+ 5 ÂșC) 
TzoneB(Tfloor-M+10ÂșC) TzoneB(Tfloor-M+15 ÂșC) Tambient 
Winter day 
20 
30 
40 
50 
60 
70 
80 
27 
28 
29 
30 
31 
32 
33 
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 
Tambient, oC 
Temperature, oC 
Time, hr 
Tfloor-M TzoneB-M TzoneB(Tfloor-M-1ÂșC) 
TzoneB(Tfloor-M-2ÂșC) TzoneB(Tfloor-M- 3ÂșC) TzoneB(Tfloor-M-4ÂșC) 
TzoneB(Tfloor-M-5ÂșC) Tambient 
Summer day 
20 
30 
40 
50 
60 
70 
80 
27 
28 
29 
30 
31 
32 
33 
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 
Tambient, oC 
Temperature, oC 
Time, hr 
Tfloor-M TzoneB-M TzoneB(ACH=1) TzoneB(ACH=2) 
TzoneB(ACH=3) TzoneB(ACH=4) TzoneB(ACH=5) Tambient 
Summer day
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 
_______________________________________________________________________________________ 
Volume: 03 Issue: 01 | Jan-2014, Available @ http://www.ijret.org 478 
4.3. Effects of night ventilation and radiant floor cooling Figure 9 presents the ambient temperatures, the base floor and indoor air temperatures against the predicted ones for case 3). The notation is as follows: TzoneB (1, -1) indicates temperatures at an ACH value of 1, the -1 indicates the floor base temperature minus 1oC; the same notation is used for the other four cases. The simulation results in Figure 9 showed that for cases (1,-1), (2,-2), (3,-3), (4,-4) and (5,-5), the decrements of the floor base temperatures were 1.2oC, 1.9oC, 2.4oC, 2.8oC and 3.1oC respectively. It is noted that for case (5,-5), the office air temperature decreased from 32.1oC to 26.9oC, indicating a maximum temperature drop of 5.2oC. 
Fig. 9. Ambient temperature, monitored floor and room air temperatures and simulated room air temperatures for the combination of infiltration and radiant cooling floor from 20:00-6:00 hrs. Comparing this result against the ones of Figure 8(b) (considering only ventilation), it shows a slight decrease of indoor air temperature of only 0.5oC. Therefore, the effect of radiant floor cooling on the indoor air temperature was negligible compared to nocturnal ventilation. 4. CONCLUSIONS The effects of the combination of night ventilation and radiant floor cooling/heating on indoor air temperatures of a high thermal mass office building located in a hot arid region were evaluated. Simulated results indicated that the predicted indoor temperatures against measured ones showed closed agreement, between 7.2% for winter and 3.1% for summer. In the winter day, considering radiant floor heating showed a maximum increment of 5.8oC in the indoor air temperature (maximum indoor air temperature reached was 19.6oC). 
In the summer day, considering radiant floor cooling showed a maximum increment of 1.5oC on average, indicating that radiant floor cooling had no significant effect on diminishing the indoor air temperatures. Considering nocturnal ventilation for an ACH rate of 5, the air temperature of the office decreased at midnight to 27.4oC, a maximum temperature drop of 4.7oC. Combining both techniques, the lowest indoor air temperature was 26.9oC during the night, a temperature drop of 5.2oC. 
Thus, nocturnal ventilation is imperative in hot arid regions to reduce (or even avoid) the use of HVAC systems. On the other hand, radiant floor heating is highly recommended in the winter. ACKNOWLEDGEMENT The authors are grateful to the AECID (Agencia Española para la Cooperación Internacional y el Desarrollo) for the financial support provided to projects PCI-A/019437/08 and PCI-A/025/63/09. REFERENCES [1] IEA, 2006. International En ergy Agency (IEA). Key World Energy Statistics. [2] Nezhad, H.G. 2009. World Energy Scenarios for the year 2010. Journal of Strategic Planning for Energy and Environment, 9 (4), 26-44. 
[3] Al-Rabghia, O. M. and Hittle, D. C., 2001. Energy simulation in buildings: overview and BLAST example. Energy Conversion and Management.42, 1623–1635. [4] McDowell, T., Thornton, J., Emmerich, S. and Walton, G., 2003. Integration of Airflow and Energy Simulation using CONTAM and TRNSYS. National Institute of Standards and Technology, Gaithersburg, MD. Thermal Energy System Specialists, Madison, Wisc.ASHRAE Transactions 109, KC-03-10-2. 
[5] Breesch, H., Bossaer, A and Janssens, A., 2005. Passive cooling in a low-energy office building.Solar Energy 79, 682-696. 
[6] Cho, S. H. and Zaheer-uddin, M., 2003. Predictive control of intermittently operated radiant floor heating systems. Energy Conversion and Management. 44, 1333– 1342. [7] Tian, Z. and Love, , J.A., Aug. 2006. Radiant slab cooling: a case study of building energy performance. 2nd. National IBPSA-USA Conference, Cambridge, MA, USA, 2-4. 
[8] Song, D., Kimb, T., Song, S., Hwang, S. and Leighd, S. B., 2008. Performance evaluation of a radiant floor cooling system integrated with dehumidified ventilation. Applied Thermal Engineering 28, 1299-1311. [9] Hayter, S. J. and Torcellini, P.A., Aug 2000. A Case Study of the Energy Design Process Used for A Retail Application. NREL/CP-550-28129. Conference American Solar Energy Society. (ASES) Madison, Wisconsin. 
203040506070802627282930313233123456789101112131415161718192021222324 Tambient, oCTemperature, oC Time, hrTfloor-MTzoneB-MTzoneB(1,-1)TzoneB(2,-2) TzoneB(3, -3)TzoneB(4,-4)TzoneB(5,-5)TambientSummer day
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 
_______________________________________________________________________________________ 
Volume: 03 Issue: 01 | Jan-2014, Available @ http://www.ijret.org 479 
[10] Olesen, B. W., Sommer, K., DĂŒchting B., 2002. Control of Slab Heating and Cooling Systems Studied by Dynamic Computer Simulations.ASHRAE Transactions, 108, Pt. 2. [11] Causone, F., Baldin, F., Olesen, B. W. and Corgnati, S.P., 2010. Floor heating and cooling combined with displacement ventilation: Possibilities and limitations. Energy and Buildings 42, 2338–2352. [12] Palero, S., San Juan, C., EnrĂ­quez, R.Ferrer, J. A, Soutullo, S., MartĂ­, J., Bosqued, A., GuzmĂĄn, J. D., JimĂ©nez, M.J, Bosqued, R., Porcar, B. and Heras, M.R., 2006.Thorough Study of a Proposal to Improve the Thermal Behaviour of a Bioclimatic Building. Presented at 23rd. International Conference on Passive and Low Energy Architecture. Switzerland. 6-8 September. [13] JimĂ©nez, M.J., EnrĂ­quez, R., Olmedo, N., SĂĄnchez, N. andHeras, M.R., 2010. Monitorizacionenergetica de los C- DdIs del PSE-ARFRISOL.Diseño experimental. In Spanish. Presented at congress ―1st. Congress on Bioclimatic Architecture and Solar Cooling. 23-26. [14] ISO Standard 5725, 1995. ISO Guide to the expression of uncertainty in measurement. Ginebra. ISBN 92-67- 10188-9. [15] TRNSYS 16 Manual, 2006.Solar Energy Laboratory, Univ. of Wisconsin-Madison. http://sel.me.wisc.edu/trnsys [16] ANSI/ASHRAE, standard 62, 2001.Ventilation for Acceptable Indoor Air Quality. [17] ASHRAE 55, 2004. Thermal and environmental conditions for human occupancy. 
BIOGRAPHIES 
Gabriela del S. Álvarez García. Dr. in Engineering. Professor at ME Dept., Cenidet-ITM. Mexico. She has several publications in reputed international journals. Research and teaching of heat transfer, conjugate heat and mass transfer, experimental methods applied to passive/active systems for conservation of energy. 
Maria José Jimenez Taboada. Dr. in Physical Sciences. Researcher in Ciemat, Spain. She has several publications in reputed international journals. She does research in energy efficiency in buildings, integration of solar systems in buildings, experimental methods and analysis, thermal monitoring of buildings. 
MarĂ­a del Rosario Heras CelemĂ­n. Dr. in Physical Sciences. She is a researcher in Ciemat, Spain. She has several publications in reputed international journals. Research in Applied Physics, energy efficiency in buildings. Solar energy applied to buildings. 
Miguel Angel Chagolla Gaona. Dr. in Mechanical Engineering. Professor of Zacatepec Tecnology Institute-TNM. Research in solar energy in buildings, measurement of climatic conditions and building simulation. 
Jesus Arce Landa. Dr. in Engineering. Professor at ME Dept., CENIDET Mexico. He has publications in reputed international journals. Research in thermal and thermodynamical systems, solar energy, conservation of energy, passive ventilation using solar chimneys. 
Jesus P. Xaman Villaseñor. Dr. in Mechanical Engineering. Professor at ME Dept., CENIDET Mexico. He has publications in reputed international journals. Research in conjugate heat transfer problems, CFD, turbulence, passive and active systems, ventilation.

More Related Content

What's hot

Passive House Principles for Hot Humid Climates
Passive House Principles for Hot Humid ClimatesPassive House Principles for Hot Humid Climates
Passive House Principles for Hot Humid Climates
aiahouston
 
Final building service (assignment)
Final   building service (assignment)Final   building service (assignment)
Final building service (assignment)
Chee Lee
 
Climate responsive architecture and PEDA literature study
Climate responsive architecture and PEDA literature study Climate responsive architecture and PEDA literature study
Climate responsive architecture and PEDA literature study
Ubaid Khan
 
Thermal Storage Wall or Thrombe Wall (prototype model)
Thermal Storage Wall or Thrombe Wall (prototype model)Thermal Storage Wall or Thrombe Wall (prototype model)
Thermal Storage Wall or Thrombe Wall (prototype model)
Prachurya Sarma
 
GreenStudio - Chapter 4 4 2 Stack Ventilation
GreenStudio - Chapter 4 4 2 Stack VentilationGreenStudio - Chapter 4 4 2 Stack Ventilation
GreenStudio - Chapter 4 4 2 Stack Ventilation
Galala University
 
Climate and the built environment
Climate and the built environmentClimate and the built environment
Climate and the built environment
Israel Marcus
 

What's hot (20)

Passive House Principles for Hot Humid Climates
Passive House Principles for Hot Humid ClimatesPassive House Principles for Hot Humid Climates
Passive House Principles for Hot Humid Climates
 
Need of climate responsive measures for buildings
Need of climate responsive measures for buildingsNeed of climate responsive measures for buildings
Need of climate responsive measures for buildings
 
Optimization of energy use intensity in a design build framework
Optimization of energy use intensity in a design build frameworkOptimization of energy use intensity in a design build framework
Optimization of energy use intensity in a design build framework
 
Natural ventilation
Natural ventilationNatural ventilation
Natural ventilation
 
Composite climate
Composite climateComposite climate
Composite climate
 
Final building service (assignment)
Final   building service (assignment)Final   building service (assignment)
Final building service (assignment)
 
1001 063
1001 0631001 063
1001 063
 
Lecture 8 heating ventilation &amp; air-conditioning
Lecture 8   heating ventilation &amp; air-conditioningLecture 8   heating ventilation &amp; air-conditioning
Lecture 8 heating ventilation &amp; air-conditioning
 
Manual of tropical housing-koenigsberger
Manual of tropical housing-koenigsbergerManual of tropical housing-koenigsberger
Manual of tropical housing-koenigsberger
 
Natural ventilation
Natural ventilationNatural ventilation
Natural ventilation
 
Climate responsive architecture and PEDA literature study
Climate responsive architecture and PEDA literature study Climate responsive architecture and PEDA literature study
Climate responsive architecture and PEDA literature study
 
Climatic architectural
Climatic architecturalClimatic architectural
Climatic architectural
 
Lecture 7 passive ventilation system
Lecture 7 passive ventilation systemLecture 7 passive ventilation system
Lecture 7 passive ventilation system
 
Thermal Storage Wall or Thrombe Wall (prototype model)
Thermal Storage Wall or Thrombe Wall (prototype model)Thermal Storage Wall or Thrombe Wall (prototype model)
Thermal Storage Wall or Thrombe Wall (prototype model)
 
Passive Cooling (tropical architecture)
Passive Cooling (tropical architecture)Passive Cooling (tropical architecture)
Passive Cooling (tropical architecture)
 
GreenStudio - Chapter 4 4 2 Stack Ventilation
GreenStudio - Chapter 4 4 2 Stack VentilationGreenStudio - Chapter 4 4 2 Stack Ventilation
GreenStudio - Chapter 4 4 2 Stack Ventilation
 
Case Study of Tropical Design of an Architect
Case Study of Tropical Design of an ArchitectCase Study of Tropical Design of an Architect
Case Study of Tropical Design of an Architect
 
earth air tunnel latest ppt
earth air tunnel latest pptearth air tunnel latest ppt
earth air tunnel latest ppt
 
Climate and the built environment
Climate and the built environmentClimate and the built environment
Climate and the built environment
 
Passive cooling
Passive coolingPassive cooling
Passive cooling
 

Viewers also liked

Viewers also liked (20)

Green Buildings-passive cooling techniques
Green Buildings-passive cooling techniquesGreen Buildings-passive cooling techniques
Green Buildings-passive cooling techniques
 
Growth and characterization of cd s doped kdp single
Growth and characterization of cd s doped kdp singleGrowth and characterization of cd s doped kdp single
Growth and characterization of cd s doped kdp single
 
A novel active charge equalisation method for series connected batteries
A novel active charge equalisation method for series connected batteriesA novel active charge equalisation method for series connected batteries
A novel active charge equalisation method for series connected batteries
 
Simulation of pedestrian at intersection in urban congested area
Simulation of pedestrian at intersection in urban congested areaSimulation of pedestrian at intersection in urban congested area
Simulation of pedestrian at intersection in urban congested area
 
Designing multi agent based linked state machine
Designing multi agent based linked state machineDesigning multi agent based linked state machine
Designing multi agent based linked state machine
 
Nonlinear fe modelling of anchorage bond in
Nonlinear fe modelling of anchorage bond inNonlinear fe modelling of anchorage bond in
Nonlinear fe modelling of anchorage bond in
 
Unravelling the molecular linkage of co morbid
Unravelling the molecular linkage of co morbidUnravelling the molecular linkage of co morbid
Unravelling the molecular linkage of co morbid
 
Stability and surface free energy analysis of a liquid drop on a horizontal c...
Stability and surface free energy analysis of a liquid drop on a horizontal c...Stability and surface free energy analysis of a liquid drop on a horizontal c...
Stability and surface free energy analysis of a liquid drop on a horizontal c...
 
Impact of inadvertent interchange pricing in
Impact of inadvertent interchange pricing inImpact of inadvertent interchange pricing in
Impact of inadvertent interchange pricing in
 
Adaptive neurofuzzy system for asthama
Adaptive neurofuzzy system for asthamaAdaptive neurofuzzy system for asthama
Adaptive neurofuzzy system for asthama
 
Computational study of a trailblazer multi reactor
Computational study of a trailblazer multi reactorComputational study of a trailblazer multi reactor
Computational study of a trailblazer multi reactor
 
Fault detection and diagnosis ingears using wavelet
Fault detection and diagnosis ingears using waveletFault detection and diagnosis ingears using wavelet
Fault detection and diagnosis ingears using wavelet
 
Computational model to design circular runner
Computational model to design circular runnerComputational model to design circular runner
Computational model to design circular runner
 
Beam steering in smart antennas by using low complex
Beam steering in smart antennas by using low complexBeam steering in smart antennas by using low complex
Beam steering in smart antennas by using low complex
 
An improved ip traceback mechanism for network
An improved ip traceback mechanism for networkAn improved ip traceback mechanism for network
An improved ip traceback mechanism for network
 
Selection of intra prediction modes for intra frame
Selection of intra prediction modes for intra frameSelection of intra prediction modes for intra frame
Selection of intra prediction modes for intra frame
 
Performance analysis of linkage learning techniques
Performance analysis of linkage learning techniquesPerformance analysis of linkage learning techniques
Performance analysis of linkage learning techniques
 
Risk assessment of a hydroelectric dam with parallel
Risk assessment of a hydroelectric dam with parallelRisk assessment of a hydroelectric dam with parallel
Risk assessment of a hydroelectric dam with parallel
 
Study of bad block management and wear leveling in
Study of bad block management and wear leveling inStudy of bad block management and wear leveling in
Study of bad block management and wear leveling in
 
Novel technique in charactarizing a pv module using
Novel technique in charactarizing a pv module usingNovel technique in charactarizing a pv module using
Novel technique in charactarizing a pv module using
 

Similar to Effects of nocturnal ventilation and radiant cooling heating floors on indoor air temperatures in an office building in hot arid region

Building Fabric 2014 2015_K.Koletsos
Building Fabric 2014 2015_K.KoletsosBuilding Fabric 2014 2015_K.Koletsos
Building Fabric 2014 2015_K.Koletsos
Konstantinos Koletsos
 
Statement of the problem
Statement of the problemStatement of the problem
Statement of the problem
felix chuswe
 

Similar to Effects of nocturnal ventilation and radiant cooling heating floors on indoor air temperatures in an office building in hot arid region (20)

Design of AC system for a Multiplex
Design of AC system for a MultiplexDesign of AC system for a Multiplex
Design of AC system for a Multiplex
 
Building Fabric 2014 2015_K.Koletsos
Building Fabric 2014 2015_K.KoletsosBuilding Fabric 2014 2015_K.Koletsos
Building Fabric 2014 2015_K.Koletsos
 
Karpagam Academy of Higher Education.pdf
Karpagam Academy of Higher Education.pdfKarpagam Academy of Higher Education.pdf
Karpagam Academy of Higher Education.pdf
 
A Pitched Roof with Forced Ventilation to Limit Solar Gains_Crimson Publishers
A Pitched Roof with Forced Ventilation to Limit Solar Gains_Crimson PublishersA Pitched Roof with Forced Ventilation to Limit Solar Gains_Crimson Publishers
A Pitched Roof with Forced Ventilation to Limit Solar Gains_Crimson Publishers
 
Modeling and performance evaluation of energy efficient buildings envelope us...
Modeling and performance evaluation of energy efficient buildings envelope us...Modeling and performance evaluation of energy efficient buildings envelope us...
Modeling and performance evaluation of energy efficient buildings envelope us...
 
Design of air preheater for solar dryer for drying cereals
Design of air preheater for solar dryer for drying cerealsDesign of air preheater for solar dryer for drying cereals
Design of air preheater for solar dryer for drying cereals
 
Design of Air Preheater for Solar Dryer for Drying Cereals
Design of Air Preheater for Solar Dryer for Drying CerealsDesign of Air Preheater for Solar Dryer for Drying Cereals
Design of Air Preheater for Solar Dryer for Drying Cereals
 
Design and Experimental Analysis of Solar air Conditioner
Design and Experimental Analysis of Solar air ConditionerDesign and Experimental Analysis of Solar air Conditioner
Design and Experimental Analysis of Solar air Conditioner
 
IRJET- Design and Fabrication of Solar Air Heater to Increase Heat Transfer R...
IRJET- Design and Fabrication of Solar Air Heater to Increase Heat Transfer R...IRJET- Design and Fabrication of Solar Air Heater to Increase Heat Transfer R...
IRJET- Design and Fabrication of Solar Air Heater to Increase Heat Transfer R...
 
Statement of the problem
Statement of the problemStatement of the problem
Statement of the problem
 
Characterization of reflectors and absorber coatings
Characterization of reflectors and absorber coatingsCharacterization of reflectors and absorber coatings
Characterization of reflectors and absorber coatings
 
Comparison of Intelligent Façade’s Energy Efficiency in Hot and Humid Climate...
Comparison of Intelligent Façade’s Energy Efficiency in Hot and Humid Climate...Comparison of Intelligent Façade’s Energy Efficiency in Hot and Humid Climate...
Comparison of Intelligent Façade’s Energy Efficiency in Hot and Humid Climate...
 
Efficiency Analysis For an Experimentally Set-up Double-Pass V-Corrugated Sol...
Efficiency Analysis For an Experimentally Set-up Double-Pass V-Corrugated Sol...Efficiency Analysis For an Experimentally Set-up Double-Pass V-Corrugated Sol...
Efficiency Analysis For an Experimentally Set-up Double-Pass V-Corrugated Sol...
 
Fq3310001010
Fq3310001010Fq3310001010
Fq3310001010
 
Computational fluid dynamic analysis of solar chimney design
Computational fluid dynamic analysis of solar chimney designComputational fluid dynamic analysis of solar chimney design
Computational fluid dynamic analysis of solar chimney design
 
Performance investigation of a flat plate collector incorporated with differe...
Performance investigation of a flat plate collector incorporated with differe...Performance investigation of a flat plate collector incorporated with differe...
Performance investigation of a flat plate collector incorporated with differe...
 
Performance investigation of a flat plate collector
Performance investigation of a flat plate collectorPerformance investigation of a flat plate collector
Performance investigation of a flat plate collector
 
Low Energy Office Proposal
Low Energy Office Proposal Low Energy Office Proposal
Low Energy Office Proposal
 
B04120610
B04120610B04120610
B04120610
 
Design of a modified natural Egyptian solar house
Design of a modified natural Egyptian solar house  Design of a modified natural Egyptian solar house
Design of a modified natural Egyptian solar house
 

More from eSAT Publishing House

Likely impacts of hudhud on the environment of visakhapatnam
Likely impacts of hudhud on the environment of visakhapatnamLikely impacts of hudhud on the environment of visakhapatnam
Likely impacts of hudhud on the environment of visakhapatnam
eSAT Publishing House
 
Impact of flood disaster in a drought prone area – case study of alampur vill...
Impact of flood disaster in a drought prone area – case study of alampur vill...Impact of flood disaster in a drought prone area – case study of alampur vill...
Impact of flood disaster in a drought prone area – case study of alampur vill...
eSAT Publishing House
 
Hudhud cyclone – a severe disaster in visakhapatnam
Hudhud cyclone – a severe disaster in visakhapatnamHudhud cyclone – a severe disaster in visakhapatnam
Hudhud cyclone – a severe disaster in visakhapatnam
eSAT Publishing House
 
Groundwater investigation using geophysical methods a case study of pydibhim...
Groundwater investigation using geophysical methods  a case study of pydibhim...Groundwater investigation using geophysical methods  a case study of pydibhim...
Groundwater investigation using geophysical methods a case study of pydibhim...
eSAT Publishing House
 
Flood related disasters concerned to urban flooding in bangalore, india
Flood related disasters concerned to urban flooding in bangalore, indiaFlood related disasters concerned to urban flooding in bangalore, india
Flood related disasters concerned to urban flooding in bangalore, india
eSAT Publishing House
 
Enhancing post disaster recovery by optimal infrastructure capacity building
Enhancing post disaster recovery by optimal infrastructure capacity buildingEnhancing post disaster recovery by optimal infrastructure capacity building
Enhancing post disaster recovery by optimal infrastructure capacity building
eSAT Publishing House
 
Effect of lintel and lintel band on the global performance of reinforced conc...
Effect of lintel and lintel band on the global performance of reinforced conc...Effect of lintel and lintel band on the global performance of reinforced conc...
Effect of lintel and lintel band on the global performance of reinforced conc...
eSAT Publishing House
 
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
eSAT Publishing House
 
Wind damage to buildings, infrastrucuture and landscape elements along the be...
Wind damage to buildings, infrastrucuture and landscape elements along the be...Wind damage to buildings, infrastrucuture and landscape elements along the be...
Wind damage to buildings, infrastrucuture and landscape elements along the be...
eSAT Publishing House
 
Shear strength of rc deep beam panels – a review
Shear strength of rc deep beam panels – a reviewShear strength of rc deep beam panels – a review
Shear strength of rc deep beam panels – a review
eSAT Publishing House
 
Role of voluntary teams of professional engineers in dissater management – ex...
Role of voluntary teams of professional engineers in dissater management – ex...Role of voluntary teams of professional engineers in dissater management – ex...
Role of voluntary teams of professional engineers in dissater management – ex...
eSAT Publishing House
 
Risk analysis and environmental hazard management
Risk analysis and environmental hazard managementRisk analysis and environmental hazard management
Risk analysis and environmental hazard management
eSAT Publishing House
 
Review study on performance of seismically tested repaired shear walls
Review study on performance of seismically tested repaired shear wallsReview study on performance of seismically tested repaired shear walls
Review study on performance of seismically tested repaired shear walls
eSAT Publishing House
 
Monitoring and assessment of air quality with reference to dust particles (pm...
Monitoring and assessment of air quality with reference to dust particles (pm...Monitoring and assessment of air quality with reference to dust particles (pm...
Monitoring and assessment of air quality with reference to dust particles (pm...
eSAT Publishing House
 
Low cost wireless sensor networks and smartphone applications for disaster ma...
Low cost wireless sensor networks and smartphone applications for disaster ma...Low cost wireless sensor networks and smartphone applications for disaster ma...
Low cost wireless sensor networks and smartphone applications for disaster ma...
eSAT Publishing House
 
Coastal zones – seismic vulnerability an analysis from east coast of india
Coastal zones – seismic vulnerability an analysis from east coast of indiaCoastal zones – seismic vulnerability an analysis from east coast of india
Coastal zones – seismic vulnerability an analysis from east coast of india
eSAT Publishing House
 
Can fracture mechanics predict damage due disaster of structures
Can fracture mechanics predict damage due disaster of structuresCan fracture mechanics predict damage due disaster of structures
Can fracture mechanics predict damage due disaster of structures
eSAT Publishing House
 
Assessment of seismic susceptibility of rc buildings
Assessment of seismic susceptibility of rc buildingsAssessment of seismic susceptibility of rc buildings
Assessment of seismic susceptibility of rc buildings
eSAT Publishing House
 
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
eSAT Publishing House
 
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
eSAT Publishing House
 

More from eSAT Publishing House (20)

Likely impacts of hudhud on the environment of visakhapatnam
Likely impacts of hudhud on the environment of visakhapatnamLikely impacts of hudhud on the environment of visakhapatnam
Likely impacts of hudhud on the environment of visakhapatnam
 
Impact of flood disaster in a drought prone area – case study of alampur vill...
Impact of flood disaster in a drought prone area – case study of alampur vill...Impact of flood disaster in a drought prone area – case study of alampur vill...
Impact of flood disaster in a drought prone area – case study of alampur vill...
 
Hudhud cyclone – a severe disaster in visakhapatnam
Hudhud cyclone – a severe disaster in visakhapatnamHudhud cyclone – a severe disaster in visakhapatnam
Hudhud cyclone – a severe disaster in visakhapatnam
 
Groundwater investigation using geophysical methods a case study of pydibhim...
Groundwater investigation using geophysical methods  a case study of pydibhim...Groundwater investigation using geophysical methods  a case study of pydibhim...
Groundwater investigation using geophysical methods a case study of pydibhim...
 
Flood related disasters concerned to urban flooding in bangalore, india
Flood related disasters concerned to urban flooding in bangalore, indiaFlood related disasters concerned to urban flooding in bangalore, india
Flood related disasters concerned to urban flooding in bangalore, india
 
Enhancing post disaster recovery by optimal infrastructure capacity building
Enhancing post disaster recovery by optimal infrastructure capacity buildingEnhancing post disaster recovery by optimal infrastructure capacity building
Enhancing post disaster recovery by optimal infrastructure capacity building
 
Effect of lintel and lintel band on the global performance of reinforced conc...
Effect of lintel and lintel band on the global performance of reinforced conc...Effect of lintel and lintel band on the global performance of reinforced conc...
Effect of lintel and lintel band on the global performance of reinforced conc...
 
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
 
Wind damage to buildings, infrastrucuture and landscape elements along the be...
Wind damage to buildings, infrastrucuture and landscape elements along the be...Wind damage to buildings, infrastrucuture and landscape elements along the be...
Wind damage to buildings, infrastrucuture and landscape elements along the be...
 
Shear strength of rc deep beam panels – a review
Shear strength of rc deep beam panels – a reviewShear strength of rc deep beam panels – a review
Shear strength of rc deep beam panels – a review
 
Role of voluntary teams of professional engineers in dissater management – ex...
Role of voluntary teams of professional engineers in dissater management – ex...Role of voluntary teams of professional engineers in dissater management – ex...
Role of voluntary teams of professional engineers in dissater management – ex...
 
Risk analysis and environmental hazard management
Risk analysis and environmental hazard managementRisk analysis and environmental hazard management
Risk analysis and environmental hazard management
 
Review study on performance of seismically tested repaired shear walls
Review study on performance of seismically tested repaired shear wallsReview study on performance of seismically tested repaired shear walls
Review study on performance of seismically tested repaired shear walls
 
Monitoring and assessment of air quality with reference to dust particles (pm...
Monitoring and assessment of air quality with reference to dust particles (pm...Monitoring and assessment of air quality with reference to dust particles (pm...
Monitoring and assessment of air quality with reference to dust particles (pm...
 
Low cost wireless sensor networks and smartphone applications for disaster ma...
Low cost wireless sensor networks and smartphone applications for disaster ma...Low cost wireless sensor networks and smartphone applications for disaster ma...
Low cost wireless sensor networks and smartphone applications for disaster ma...
 
Coastal zones – seismic vulnerability an analysis from east coast of india
Coastal zones – seismic vulnerability an analysis from east coast of indiaCoastal zones – seismic vulnerability an analysis from east coast of india
Coastal zones – seismic vulnerability an analysis from east coast of india
 
Can fracture mechanics predict damage due disaster of structures
Can fracture mechanics predict damage due disaster of structuresCan fracture mechanics predict damage due disaster of structures
Can fracture mechanics predict damage due disaster of structures
 
Assessment of seismic susceptibility of rc buildings
Assessment of seismic susceptibility of rc buildingsAssessment of seismic susceptibility of rc buildings
Assessment of seismic susceptibility of rc buildings
 
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
 
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
 

Recently uploaded

VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
SUHANI PANDEY
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
sivaprakash250
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
Epec Engineered Technologies
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
Call Now ≜ 9953056974 â‰ŒđŸ” Call Girls In New Ashok Nagar â‰ŒđŸ” Delhi door step de...
Call Now ≜ 9953056974 â‰ŒđŸ” Call Girls In New Ashok Nagar  â‰ŒđŸ” Delhi door step de...Call Now ≜ 9953056974 â‰ŒđŸ” Call Girls In New Ashok Nagar  â‰ŒđŸ” Delhi door step de...
Call Now ≜ 9953056974 â‰ŒđŸ” Call Girls In New Ashok Nagar â‰ŒđŸ” Delhi door step de...
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 

Recently uploaded (20)

A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 
2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
 
Call Now ≜ 9953056974 â‰ŒđŸ” Call Girls In New Ashok Nagar â‰ŒđŸ” Delhi door step de...
Call Now ≜ 9953056974 â‰ŒđŸ” Call Girls In New Ashok Nagar  â‰ŒđŸ” Delhi door step de...Call Now ≜ 9953056974 â‰ŒđŸ” Call Girls In New Ashok Nagar  â‰ŒđŸ” Delhi door step de...
Call Now ≜ 9953056974 â‰ŒđŸ” Call Girls In New Ashok Nagar â‰ŒđŸ” Delhi door step de...
 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
Employee leave management system project.
Employee leave management system project.Employee leave management system project.
Employee leave management system project.
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 

Effects of nocturnal ventilation and radiant cooling heating floors on indoor air temperatures in an office building in hot arid region

  • 1. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Issue: 01 | Jan-2014, Available @ http://www.ijret.org 472 EFFECTS OF NOCTURNAL VENTILATION AND RADIANT COOLING/ HEATING FLOORS ON INDOOR AIR TEMPERATURES IN AN OFFICE BUILDING IN HOT ARID REGION G. Alvarez1, M.J. JimĂ©nez2, M.R. Heras2, M.A. Chagolla3, J. Arce2& J.P. XamĂĄn2 1ME Department, Centro Nacional de InvestigaciĂłn y Desarrollo TecnolĂłgico-TMN-SEP. Morelos. MĂ©xico. Email: gaby@cenidet.edu.mx. 2 Energy Efficiency in Buildings Unit. Centro de Investigaciones EnergĂ©ticas, Medioambientales y TecnolĂłgicas. Spain. Email: mjose.jimenez@psa.es 3Instituto TecnolĂłgico de Zacatepec-TNM-SEP. Morelos, Mexico. Abstract The effects of nocturnal ventilation and radiant cooling/heating floors on indoor air temperatures in an office building in hot arid region are evaluated. Climatic and indoor temperatures are measured and compared against predicted ones using TRNSYSÂź, obtaining a 7% difference. A parametric study was conducted that varied floor temperatures to simulate radiant floor heating on the coolest day and nocturnal ventilation or/and radiant floor cooling on the hottest day in 2009. Results indicated that, during the winter, radiant floor heating increased the indoor air temperatures from 13.5ÂșC to 19.6ÂșC. During the summer, the indoor air temperature decreased from 32.1ÂșC to 27.4ÂșC at midnight, with a nocturnal ventilation of 5 ACH. Combining ventilation and radiant floor cooling decreased the indoor air temperatures to 26.9ÂșC (0.5ÂșC lower). As a result, the effect of nighttime ventilation was significant on indoor temperatures in the building; however, the effect of radiant floor cooling was almost negligible. Key Words: Office building, Radiant floor, Nocturnal ventilation, Conservation of energy. --------------------------------------------------------------------***---------------------------------------------------------------------- 1. INTRODUCTION Energy use in buildings accounts for 40% of total energy consumption. Developing countries are concerned over the augmented use of air conditioning systems [1]. Along with the increase in energy consumption, there are debates over whether air conditioned buildings should be recommended or prohibited due to discomfort (drafts, noise and impure air) [2]. In desert regions, energy consumption for thermal comfort conditions is very high. Some authors recommend using or managing passive or active techniques such as ventilation, radiant floor cooling or heating in order to decrease energy consumption and improve the indoor thermal environment in buildings during both summer and winter months [3]. Infiltration of air in buildings has been studied by McDowell et al. [4] to determine its impact on the thermal loads; they found that infiltration has a much higher negative impact on heating loads than on cooling loads. Also, management of passive cooling have a significant impact on the thermal summer comfort in a building [5]. Predictive control strategies improved the energy efficiency of intermittently heated radiant floor heating systems finding energy savings between 10% and 12% during cold winter months [6]. In 2006. Tian and Love [7] studied multi-floor radiant slab cooling through simulation and field measurements, reporting that even though radiant floor cooling has the potential to improve energy efficiency; it must be coordinated with air handling systems to avoid conflicts. However, radiant floor cooling systems are not recommended in humid climates because of condensation [8]. Very few authors have considered the combination of passive/active techniques such as nocturnal ventilation and radiant floor cooling. In 2000, Hayter and Torcellini [9] described a technique for designing and constructing low- energy buildings in which the HVAC design included radiant slab heating and natural ventilation cooling through an automatic window control, with a transpired solar collector (TSC) to preheat ventilation air for warehouses. However, Olesen et al. [10] found that the primary problem with combining radiant floor heating and displacement ventilation was inadvertently producing the opposite effects of the two systems; that is, if the floor temperature was too high, the supply air rose, reducing the ventilation effectiveness of the system and producing a mixing flow pattern in the room. If, however, the overheated floor is combined with displacement ventilation, the air could be supplied at a lower temperature for the ventilation system (depending on the external climate), with a resulting
  • 2. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Issue: 01 | Jan-2014, Available @ http://www.ijret.org 473 reduction in the energy consumption [11]. Thus, the combination of active/passive techniques is not sufficiently studied. The aim of this study is to study the effects of nocturnal ventilation and/or radiant floor cooling in summer and radiant floor heating in winter on the indoor air temperatures of a high thermal mass office building (heavyweight construction) located in an arid region. 2. CASE OF STUDY The office building is a rectangular-shaped building of 1,114.96 m2, shown in Fig. 1, with its façade facing south. It is located in the city of Tabernas in Spain, at 37Âș 05’ 27.8‖N latitude and 2Âș 21’ 19‖ W longitude. It lies at 555 m above sea level in a subtropical desert with scarce and irregular rain (200 mm per year), a high rate of irradiance (almost 3000 hours of sunlight per year) and large ambient temperature swings (12oC). During 2009, the minimum monitored temperature was during January (-1.4ÂșC), and the maximum temperature was during July (41.7ÂșC). Fig. 1. View of the office building and location of the monitored office. 2.1 Climate Conditions A meteorological station installed on the roof of the building monitored the environmental climate conditions. Figures 2(a) and 2(b) show the average monthly solar radiation on the roof and south façade, the average monthly ambient temperature, the average monthly relative humidity and the average monthly wind velocity of 2009. Figure 2(a) shows that the monthly solar radiation was highest in June (7.66 kW-h/m2) and July (7.63 kW-h/m2); the average monthly solar radiation falling on the south façade was lower in summer and higher in winter as expected at this latitude. Average amount of sunshine was 14 hours during summer and 9 hours in winter. Figure 2(b) shows the average monthly ambient temperatures, humidity and wind velocities. Maximum average monthly temperature was in July (27.6oC) and the minimum was in December (8.5oC); lowest average monthly relative humidity was in June (40.1%) and highest was in October (71.2%). Average monthly wind velocity oscillated in the range of 2.3-3.1 m/s. (a) (b) Fig. 2. (a) Monthly global horizontal and southern solar radiation and (b) Monthly average wind velocity, ambient temperature and relative humidity for 2009. 2.2 Building Characteristics The envelope of the building is constructed of thick multilayer composite walls to guarantee insulation, and the double-glazed aluminum framed windows are shaded to reduce the amplitude of the indoor temperature changes and prevent direct solar gains in summer. The south façade is protected by a 2 m projection (porch roof) to avoid direct beam radiation during the summer. More detailed features of the building were previously reported in [12]. Table 1 shows the construction materials of the walls and roof and their thermophysical properties. The composite wall is 44 cm thick, with an air gap at the center and polyurethane insulation material between the air gap and the hollow bricks. A Planitherm 4S window (from Climalit Products), 4.63 m2 in size with a U-value of 3.21 W/m2K and a g-value of 0.722 is installed at the south wall. A 1 m wide overhang lies 1.5 m above the window to avoid direct sunshine on the window during summer. Table 1. Building envelope components, dimensions and thermophysical properties Material L (m) k (W/m K) ρ (kg/m)3 Cp, (kJ/kg K) Walls Gypsum 0.02 1.08 900 1.00 Hollow brick 0.11 1.764 1200 0.90 Air 0.14 Polyurethane 0.04 0.144 12 1.80 Hollow brick 0.11 1.764 1200 0.90 Mortar 0.02 5.04 2000 1.10 Roof Concrete 0.24 3.744 1500 1.00 Mortar 0.14 5.04 2000 1.10 Bitumen 0.005 0.828 1100 1.00 Polystyrene 0.04 0.144 25 1.50 Polypropylene 0.003 0.792 910 1.80 Gravel 0.06 2.916 1700 0.90 Floor Ceramic plate 0.25 3.78 1200 2.00 Mortar 0.04 5.04 2000 1.10 Sand 0.035 7.20 2000 1.00 Concrete 0.15 8.28 2300 1.00 Gravel 0.20 2.916 1700 0.90 6.89 m 2.91 m 3.4 m 7.5 m Zone B Zone A Zone B Zone A W E S N Temperature sensor Temperature sensor Monitored office 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC Solar Radiation, kW-hr/m2 Month MONTHLY AVERAGE DAILY GLOBAL SOLAR RADIATION HORIZONTAL SOUTH 2.5 3.0 2.8 2.3 2.8 2.5 2.4 2.8 2.6 3.1 2.4 2.3 0 10 20 30 40 50 60 70 80 90 100 0 5 10 15 20 25 30 JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC Air temperature [ÂșC] Wind velocity [m/s] Relative humidity [%]
  • 3. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Issue: 01 | Jan-2014, Available @ http://www.ijret.org 474 The monitored office was chosen due to its location; it is located in the corner of the west end of the building as shown in Fig. 3(a). It is irradiated on the west and south walls, as well as the roof. The vertical and horizontal sketches of the cross section are shown in Figures 3(a) and 3(b). The north wall of the office is next to a long hall, and the east wall is adjacent to the subsequent office. Fig. 3(a). West façade of the office (b) Fig. 3(b). Vertical cross-section of the office, (c) Fig. 3(c). West façade of the office. 3. THERMAL SIMULATION OF THE OFFICE TRNSYSÂź program was used to simulate the thermal performance of the office. The following methodology was applied: 1) Two weekend days; one of extreme cold and another one of extreme hot temperatures of 2009 were chosen as the input data for TRNSYSÂź. 2) The building location, weather conditions, orientation, envelope components and dimensions were input into the TRNSYSÂź program, the indoor air temperatures of the office under a free-floating condition (no HVAC systems) were calculated and compared against those measured in order to calibrate the simulation. 3) A parametric study changing the ventilation rates and floor temperatures were carried out to predict the indoor air temperatures of the office. 4) Effects of every heating and cooling technique on the indoor air temperature were determined. 3.1 Days for the Simulation Following the previous methodology, January 17th (the coolest day in winter) and Saturday, July 25th (the hottest day in summer) were the days for the simulation. Figures 5(a)-(d) show the horizontal and vertical solar radiation, ambient temperature, relative humidity and wind velocity, corresponding to January 17th and July 25th. It can be seen from Figures 5(b) and 5(d) that the ambient temperatures dropped during the night and increased during the day; temperature; swings, day and night, were close to 10oC on both days. In winter day, Figure 5(a) shows that the solar radiation on the horizontal surface is lower than the radiation on the south surfaces–as expected. Sunrise was at 8:00 hr; the solar radiation increased until 12:00 noon, then slowly decayed until 15:00 hr, when it abruptly dropped due to an obstruction on the roof relative to the position of the sun. (a) 3.40 4.94 2.30 1.50 1.50 Tf Tg Tw Tw Ta 1.10 1.00 4.94 6.00 1.50 1.10 1.30 Tf TR Ta Tg 1.50 0 100 200 300 400 500 600 700 800 900 1000 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 W/m2 Hours Solar Radiation Horizontal South Winter day 0 10 20 30 40 50 60 70 80 90 100 0 2 4 6 8 10 12 14 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Hours Ambient Temperature [C] Relative Humidity [%] Wind Velocity [m/s] Winter day
  • 4. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Issue: 01 | Jan-2014, Available @ http://www.ijret.org 475 (b) (c) (d) Fig. 5. (a) Incident solar radiation, (b) ambient temperature and relative humidity (January 17th); (c) solar radiation (d) ambient temperature and relative humidity (July 25th). The ambient temperature was 2.5 oC after 7:00 hr during the night and early morning; increasing to 13.2oC after 13:00 hr and then decreasing. The relative humidity was always higher at night (80-90%), decreasing during the day to 49% after 13:00 hr. Prior to 10:00 hr, as can be seen in Figure 5(b), the wind velocity was in the low range (<2.5 m/s) but then fluctuated, reaching a maximum of 6.9 m/s after 11:00 hr and decreasing (<3 m/s) after 17:00 hr. In the summer day, Figure 5(c) shows the solar radiation on the horizontal and south surfaces. The solar radiation on the horizontal surface was higher than the radiation on the south surface; sunrise was at 5:00 hr, and the solar radiation steadily increased after 12:00 hr. It then abruptly fell during the afternoon, and the humidity increased, indicating cloudiness see Figure 5(d). The ambient temperature was low at night, ranging between 26-28 oC and then rising to 33 oC after 9:00hr; it then decreased after midnight to 21.8 oC, as expected due to cloudiness. The relative humidity was in the low range of 20-30 % at early morning and increased to 90 % at midnight; the wind velocity fluctuation was in the low range at night (<3.5 m/s) and early morning, increasing after 7:00 hr to a maximum of 10.8 m/s after 12:00 hr and remaining high until the oscillations decreased after 23:00 hr. For the TRNSYSÂź simulation, the office was divided into two zones: Zone A (hallway) and Zone B (office), as shown in Figure 3(b). The east wall of Zone B was considered to be adiabatic (adjacent office), as well as the eastside of the Zone A; the measured solar radiation was input to Type 16 (Solar Radiation Processor). Envelope components of the office were input to Type 56 (Multi-Zone Building). TRNBuilt module was used to calculate the U-values for the wall. The U-values of the walls were 0.532 W/mÂČ K for heat transfer coefficients of 7.7 W/m2 K indoors and 25 W/m2 K outdoors. The roof U-value was 0.621 W/mÂČ K for 5.7 + 3.8V outdoors and 9.26 W/mÂČ K indoors [15]. Absorptances of ceiling and walls were 0.3. Thermal capacitance of the office was 1000kJ/K (furniture + air), with lighting of 5 W/m2. An ACH ventilation of 0.25 was considered, as suggested by ANSI/ASHRAE-62 [16]. Simulations were performed every minute for 24 hrs and results were plotted every hour. 3.2 Measurement instruments of the office Six temperature sensors were installed in the office; the sensor measuring the air temperature was located 1.5 m above the floor and 0.10 m away from the north wall; the other five were attached at the middle of the floor, on the glazing, on the east and west walls and in the middle of the roof, as shown in Figure 3(b) [13]. The measurement instruments and their descriptions are presented in Table 2. Table 2. Instrumentation used for monitoring the office. Sensor Measured Variable Description 2 Pyranometer, model CM11. Kipp and Zonen Horizontal and vertical global Solar Irradiance Spectral range from 285 to 2800 nm; Sensitivity of 7 to 14 ÎŒV/W/mÂČ. 1 Pygeometer, model CGR-4. Kipp and Zonen Long wave radiation from the surface of the test component Spectral range of 4500 to 42000 nm, 5 to 15 ÎŒV/W/mÂČ; Response time of18 s; Temperature dependence of sensitivity (-20 ÂșC to +50 ÂșC) < 1%. 1 Sensor model WindSonic. Gill Instruments, LTD. Wind velocity Ultrasonic Output Rate of 0.25, 0.5, 1, 2, and 4 Hz; Wind Speed of 0-60 m/s; 1 Sensor model HMP45A/D. Vaisala. Outdoor relative humidity Range from 0.8 to 100%RH; Accuracy at +20 °C. Response time (90% at +20 °C) 10 s. Platinum thermo-resistance, PT100 Air temperature Accuracy: 1/10 DIN of Class B with a tolerance of ±0.3°C at 0°C. Platinum thermo- Surface temperature Accuracy: 1/10 DIN of Class B with a tolerance 0 100 200 300 400 500 600 700 800 900 1000 1100 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 W/m2 Hours Solar Radiation Horizontal South Summer day 0 10 20 30 40 50 60 70 80 90 100 20 22 24 26 28 30 32 34 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Hours Ambient Temperature [C] Relative Humidity [%] Wind Velocity [m/s] Summer day
  • 5. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Issue: 01 | Jan-2014, Available @ http://www.ijret.org 476 resistance, PT100 of ±0.3°C at 0°C. A data acquisition system of 16-bit A/D resolution was used. The uncertainty, u(Ti), corresponding to the measurement of indoor air temperature, Ti, was calculated according to ISO 5725 [14]. The calculated air temperature uncertainty was 0.4C with a 95% level of confidence, using a coverage factor of k*=2. 3.3 Comparison between measured and predicted indoor temperatures Figures 6(a) and 6(b) show the mean ambient air temperature and the measured and predicted indoor air temperatures in both the winter and summer days, respectively. (a) (b) Fig 6. Ambient temperatures and monitored and predicted temperatures for (a) winter (Jan 17th) and (b) summer (July 25th). Both Figures show that the predicted indoor air temperature of the office follows the same pattern of the measured one; the amplitude of the fluctuation compared to the ambient temperature was small due to the high thermal inertia of the envelope. As seen in Figure 6(a), the mean minimum outdoor ambient temperature was 3.1ÂșC at 7:00 hrs, and the maximum was 12.8ÂșC at 15:00 hrs a difference of 9.7ÂșC; the minimum and maximum mean measured temperatures were 12.2ÂșC at 8:00 hrs and 13.5ÂșC a difference of 1.3ÂșC; the minimum and maximum mean predicted temperatures were 11.6ÂșC at 8:00 hrs and 13.1ÂșC at 15:00 hrs a difference of 1.5ÂșC. A comparison between the measured and predicted indoor air temperatures indicates that their maximum difference was 0.9ÂșC (7.2%) at night and the minimum was 0.3ÂșC (2.5%), with a correlation coefficient of r2=0.92. During the night, the indoor air temperatures were not as low as the outside ambient temperatures, demonstrating that the thermal inertia of the building plays an important role. On the summer day, Figure 6(b) show that the maximum mean ambient temperature was 32.4ÂșC at 10:00 hrs, and the minimum was 22.0 ÂșC at 24:00hrs a difference of 10.4ÂșC. The maximum and minimum mean measured temperatures were 32.2ÂșC at 18:00 and 31.5ÂșC at 7:00 hrs—a difference of 0.7ÂșC; the maximum and minimum mean predicted temperatures were 31.5ÂșC at 15:00 hrs and 31.1ÂșC at 24:00—a difference of 0.4ÂșC. As previously noted, the indoor air temperature fluctuation is nearly negligible, so it is clear that heat accumulated inside the building. A comparison between the measured and predicted indoor air temperatures shows that their maximum difference was 1.0ÂșC (7.2%) at night, and their minimum difference was 0.2ÂșC (2.5%), with a correlation coefficient of r2=0.92. The predicted and measured indoor air temperatures show very close agreement, thus calibrating the TRNSYSÂź program. These results show that it is necessary to remove the accumulated heat in the office during the summer. Therefore, nocturnal cooling is desirable for preventing overheating by taking advantage of the minimum outdoor air temperature. 4. PARAMETRIC STUDY The parametric study considers three techniques: radiant floor heating and cooling and nocturnal ventilation. Radiant heating/cooling systems refer controlled surface floor temperature. To simulate the radiant floor heating or cooling, the measured floor temperature were taken as floor base temperature and increased for heating or decreased for cooling in the simulation. Nocturnal ventilation refers to cooler air driven into the building during the night, reducing temperatures in the building. Normally, ventilation rates are measured by AHC (Air Changes per Hour) [16]. 4.1. Effect radiant floor heating For the winter day, two cases were considered: 1) the measured floor temperature, Tfloor-M, were increased by 5oC, 10ÂșC and 15ÂșC during 9:00 to 18:00 hrs, and 2) the same but for 24 hrs. Figures 7(a) and 7(b) show the ambient temperatures (Tamb), floor base temperature (Tfloor-M), indoor measured air temperatures (TzoneB-M) and the predicted one (TzoneB) for cases 1) and 2), respectively. As can be seen in Figure 7(a), increasing Tfloor –M, by 5oC, 10ÂșC and 15ÂșC during 9 hours resulted in increments of indoor air temperatures (TzoneB) of 0.3oC, 1.2ÂșC and 2.2oC on average, respectively. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 0 2 4 6 8 10 12 14 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Diff.(TzoneB-M, TzoneB-P),oC Air temperature, oC Tambient TzoneB-M TzoneB-P Diff. Time, hr Winter day 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 20 22 24 26 28 30 32 34 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Diff.(TzoneB-M,TzoneB-P),oC Air temperature, oC Tambient TzoneB-M TzoneB-P Diff. Time, hr Summer day
  • 6. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Issue: 01 | Jan-2014, Available @ http://www.ijret.org 477 Figure 7(a) shows that an increment of 15ÂșC of the floor base temperature increased the indoor air temperature to a maximum of 15.8oC at 15:00 hr, against the outdoor ambient temperature of 12.8oC. Similar results are presented by Figure 7(b), but for 24 hours of floor heating. The augmentation of the floor base temperatures of the office by increments of 5oC, 10oC and 15oC caused the increase in the indoor air temperatures in increments of 1.5oC, 3.7oC and 5.8oC on average, respectively. For increments of 15ÂșC for 24 hours, the minimum indoor air temperature reached was 18.1oC and the maximum was 19.6oC at 15:00 hrs. The indoor air temperatures were in the low range (18oC-20oC) of acceptable temperatures [17]. (a) (b) Fig. 7. Ambient temperature, measured floor and indoor temperatures and predicted indoor temperatures for different radiant heating floor temperatures from (a) 9-18 hrs and (b) 0-24 hrs. 4.2. Effect of radiant floor cooling For the summer day, three cases were considered for the simulation: 1) floor base temperature of the office decreased by 1oC, 2oC, 3oC, 4oC and 5oC, during 9:00 to 18:00 hrs, 2) nocturnal ventilation rates of 1, 2, 3, 4 and 5 ACH from 20:00 to 6:00 hrs and 3) a combination of these two techniques. Figures 8(a) and 8(b) show the ambient temperature, the floor base temperature and indoor temperature against the predicted one for cases 1) and 2). Both figures show that the oscillation of the indoor measured air temperature of the office (31.5oC-32.2oC) was lower than the oscillation of the ambient temperatures (22.0 oC-32.4 oC). The indoor air temperatures were always higher than outdoor air temperatures, indicating that heat was accumulating inside the office and therefore throughout the building. (a) (b) Fig. 8. (a) Ambient temperature, floor base temperature and indoor measured air temperatures and predicted ones for different radiant cooling floor temperatures from 20-6 hrs and (b) for different infiltration rates from 20-6 hrs. For case 1), Figure 8(a), shows that floor base temperature decrements of 1oC, 2oC, 3oC, 4oC and 5oC from 9:00-18:00 hrs causes decrements of the indoor air temperatures of 0.7oC, 0.9oC, 1.1oC, 1.3oC and 1.5oC respectively. In this case, the predicted minimum indoor air temperature was 30.2oC at midnight, which represented a very small decrease in 1.9oC. For case 2, Figure 8(b), shows the effect of nocturnal ventilation rates on indoor air temperatures. As seen in this figure, the predicted indoor air temperatures at the office rapidly decreased at night. For nocturnal ACH ventilation rates of 1, 2, 3, 4 and 5 (from 20:00 to 6:00 hrs), the decrement of the indoor air temperatures was 1.1oC, 1.6oC, 2.0oC, 2.3oC, 2.5oC respectively. During the night, for an ACH rate of 5, the lowest predicted indoor air temperature was 27.4oC, which represented a decrease of 4.7oC; during daylight. Thus, nocturnal ventilation techniques are very important in hot arid climates during the summer. 0 5 10 15 20 25 30 35 40 10 11 12 13 14 15 16 17 18 19 20 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Tambient oC Temperature, oC Time, hr Tfloor-M. TzoneB-M. TzoneB(Tfloor-M+5ÂșC) TzoneB (Tfloor-M+10 ÂșC) TzoneB(Tfloor-M+15ÂșC) Tambient. Winter day 0 4 8 12 16 20 24 28 32 36 40 10 11 12 13 14 15 16 17 18 19 20 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Tambient , oC Temperature, oC Time, hr Tfloor-M TzoneB-M TzoneB(Tfloor-M+ 5 ÂșC) TzoneB(Tfloor-M+10ÂșC) TzoneB(Tfloor-M+15 ÂșC) Tambient Winter day 20 30 40 50 60 70 80 27 28 29 30 31 32 33 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Tambient, oC Temperature, oC Time, hr Tfloor-M TzoneB-M TzoneB(Tfloor-M-1ÂșC) TzoneB(Tfloor-M-2ÂșC) TzoneB(Tfloor-M- 3ÂșC) TzoneB(Tfloor-M-4ÂșC) TzoneB(Tfloor-M-5ÂșC) Tambient Summer day 20 30 40 50 60 70 80 27 28 29 30 31 32 33 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Tambient, oC Temperature, oC Time, hr Tfloor-M TzoneB-M TzoneB(ACH=1) TzoneB(ACH=2) TzoneB(ACH=3) TzoneB(ACH=4) TzoneB(ACH=5) Tambient Summer day
  • 7. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Issue: 01 | Jan-2014, Available @ http://www.ijret.org 478 4.3. Effects of night ventilation and radiant floor cooling Figure 9 presents the ambient temperatures, the base floor and indoor air temperatures against the predicted ones for case 3). The notation is as follows: TzoneB (1, -1) indicates temperatures at an ACH value of 1, the -1 indicates the floor base temperature minus 1oC; the same notation is used for the other four cases. The simulation results in Figure 9 showed that for cases (1,-1), (2,-2), (3,-3), (4,-4) and (5,-5), the decrements of the floor base temperatures were 1.2oC, 1.9oC, 2.4oC, 2.8oC and 3.1oC respectively. It is noted that for case (5,-5), the office air temperature decreased from 32.1oC to 26.9oC, indicating a maximum temperature drop of 5.2oC. Fig. 9. Ambient temperature, monitored floor and room air temperatures and simulated room air temperatures for the combination of infiltration and radiant cooling floor from 20:00-6:00 hrs. Comparing this result against the ones of Figure 8(b) (considering only ventilation), it shows a slight decrease of indoor air temperature of only 0.5oC. Therefore, the effect of radiant floor cooling on the indoor air temperature was negligible compared to nocturnal ventilation. 4. CONCLUSIONS The effects of the combination of night ventilation and radiant floor cooling/heating on indoor air temperatures of a high thermal mass office building located in a hot arid region were evaluated. Simulated results indicated that the predicted indoor temperatures against measured ones showed closed agreement, between 7.2% for winter and 3.1% for summer. In the winter day, considering radiant floor heating showed a maximum increment of 5.8oC in the indoor air temperature (maximum indoor air temperature reached was 19.6oC). In the summer day, considering radiant floor cooling showed a maximum increment of 1.5oC on average, indicating that radiant floor cooling had no significant effect on diminishing the indoor air temperatures. Considering nocturnal ventilation for an ACH rate of 5, the air temperature of the office decreased at midnight to 27.4oC, a maximum temperature drop of 4.7oC. Combining both techniques, the lowest indoor air temperature was 26.9oC during the night, a temperature drop of 5.2oC. Thus, nocturnal ventilation is imperative in hot arid regions to reduce (or even avoid) the use of HVAC systems. On the other hand, radiant floor heating is highly recommended in the winter. ACKNOWLEDGEMENT The authors are grateful to the AECID (Agencia Española para la CooperaciĂłn Internacional y el Desarrollo) for the financial support provided to projects PCI-A/019437/08 and PCI-A/025/63/09. REFERENCES [1] IEA, 2006. International En ergy Agency (IEA). Key World Energy Statistics. [2] Nezhad, H.G. 2009. World Energy Scenarios for the year 2010. Journal of Strategic Planning for Energy and Environment, 9 (4), 26-44. [3] Al-Rabghia, O. M. and Hittle, D. C., 2001. Energy simulation in buildings: overview and BLAST example. Energy Conversion and Management.42, 1623–1635. [4] McDowell, T., Thornton, J., Emmerich, S. and Walton, G., 2003. Integration of Airflow and Energy Simulation using CONTAM and TRNSYS. National Institute of Standards and Technology, Gaithersburg, MD. Thermal Energy System Specialists, Madison, Wisc.ASHRAE Transactions 109, KC-03-10-2. [5] Breesch, H., Bossaer, A and Janssens, A., 2005. Passive cooling in a low-energy office building.Solar Energy 79, 682-696. [6] Cho, S. H. and Zaheer-uddin, M., 2003. Predictive control of intermittently operated radiant floor heating systems. Energy Conversion and Management. 44, 1333– 1342. [7] Tian, Z. and Love, , J.A., Aug. 2006. Radiant slab cooling: a case study of building energy performance. 2nd. National IBPSA-USA Conference, Cambridge, MA, USA, 2-4. [8] Song, D., Kimb, T., Song, S., Hwang, S. and Leighd, S. B., 2008. Performance evaluation of a radiant floor cooling system integrated with dehumidified ventilation. Applied Thermal Engineering 28, 1299-1311. [9] Hayter, S. J. and Torcellini, P.A., Aug 2000. A Case Study of the Energy Design Process Used for A Retail Application. NREL/CP-550-28129. Conference American Solar Energy Society. (ASES) Madison, Wisconsin. 203040506070802627282930313233123456789101112131415161718192021222324 Tambient, oCTemperature, oC Time, hrTfloor-MTzoneB-MTzoneB(1,-1)TzoneB(2,-2) TzoneB(3, -3)TzoneB(4,-4)TzoneB(5,-5)TambientSummer day
  • 8. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 _______________________________________________________________________________________ Volume: 03 Issue: 01 | Jan-2014, Available @ http://www.ijret.org 479 [10] Olesen, B. W., Sommer, K., DĂŒchting B., 2002. Control of Slab Heating and Cooling Systems Studied by Dynamic Computer Simulations.ASHRAE Transactions, 108, Pt. 2. [11] Causone, F., Baldin, F., Olesen, B. W. and Corgnati, S.P., 2010. Floor heating and cooling combined with displacement ventilation: Possibilities and limitations. Energy and Buildings 42, 2338–2352. [12] Palero, S., San Juan, C., EnrĂ­quez, R.Ferrer, J. A, Soutullo, S., MartĂ­, J., Bosqued, A., GuzmĂĄn, J. D., JimĂ©nez, M.J, Bosqued, R., Porcar, B. and Heras, M.R., 2006.Thorough Study of a Proposal to Improve the Thermal Behaviour of a Bioclimatic Building. Presented at 23rd. International Conference on Passive and Low Energy Architecture. Switzerland. 6-8 September. [13] JimĂ©nez, M.J., EnrĂ­quez, R., Olmedo, N., SĂĄnchez, N. andHeras, M.R., 2010. Monitorizacionenergetica de los C- DdIs del PSE-ARFRISOL.Diseño experimental. In Spanish. Presented at congress ―1st. Congress on Bioclimatic Architecture and Solar Cooling. 23-26. [14] ISO Standard 5725, 1995. ISO Guide to the expression of uncertainty in measurement. Ginebra. ISBN 92-67- 10188-9. [15] TRNSYS 16 Manual, 2006.Solar Energy Laboratory, Univ. of Wisconsin-Madison. http://sel.me.wisc.edu/trnsys [16] ANSI/ASHRAE, standard 62, 2001.Ventilation for Acceptable Indoor Air Quality. [17] ASHRAE 55, 2004. Thermal and environmental conditions for human occupancy. BIOGRAPHIES Gabriela del S. Álvarez GarcĂ­a. Dr. in Engineering. Professor at ME Dept., Cenidet-ITM. Mexico. She has several publications in reputed international journals. Research and teaching of heat transfer, conjugate heat and mass transfer, experimental methods applied to passive/active systems for conservation of energy. Maria JosĂ© Jimenez Taboada. Dr. in Physical Sciences. Researcher in Ciemat, Spain. She has several publications in reputed international journals. She does research in energy efficiency in buildings, integration of solar systems in buildings, experimental methods and analysis, thermal monitoring of buildings. MarĂ­a del Rosario Heras CelemĂ­n. Dr. in Physical Sciences. She is a researcher in Ciemat, Spain. She has several publications in reputed international journals. Research in Applied Physics, energy efficiency in buildings. Solar energy applied to buildings. Miguel Angel Chagolla Gaona. Dr. in Mechanical Engineering. Professor of Zacatepec Tecnology Institute-TNM. Research in solar energy in buildings, measurement of climatic conditions and building simulation. Jesus Arce Landa. Dr. in Engineering. Professor at ME Dept., CENIDET Mexico. He has publications in reputed international journals. Research in thermal and thermodynamical systems, solar energy, conservation of energy, passive ventilation using solar chimneys. Jesus P. Xaman Villaseñor. Dr. in Mechanical Engineering. Professor at ME Dept., CENIDET Mexico. He has publications in reputed international journals. Research in conjugate heat transfer problems, CFD, turbulence, passive and active systems, ventilation.