SlideShare a Scribd company logo
1 of 76
Download to read offline
IEEE SF / IAS Seminar
April 2011
Finn Schenck
Schneider Electric
Schneider Electric 2- Projects and Services – PEC – MV Transformers - 2010
Transformer Types
Liquid-Filled Padmount
Liquid-Filled Unit Substation
Schneider Electric 3- Projects and Services – PEC – MV Transformers - 2010
Transformer Types
VPI Dry Unit Substation
Cast Unit Substation
Schneider Electric 4- Projects and Services – PEC – MV Transformers - 2010
Dry Vs. Liquid Transformers
DRY
●No fluid to spill or burn
●Cost is higher than oil
●Resistant to moisture
●Minimum Maintenance
●UL Listed
Liquid
●Lowest Purchase Price
●Sealed Tank
●Lowest Losses per $
●UL Listing
●Loads of Options
●Pad Mounted (Tamper-
Resistant)
●Substation – Flexible
Schneider Electric 5- Projects and Services – PEC – MV Transformers - 2010
Definitions (Buzzwords)
● BIL (Basic Impulse Level)
The level of momentary over voltage that the transformers insulation can withstand
without damage/failure.
● IMPEDANCE
The percentage of rated voltage required to circulate rated current in one winding with
the other winding short circuited.
● EXAMPLE
●A transformer with a 5.75% impedance and a 480 volt low voltage winding would require
(0.0575 x 480 volt) or 27.6 volts to circulate rated current.
●IN SHORT Impedance is simply the opposition to the flow of current in the transformers
windings. (Impedance has a resistive and an inductive component.)
● REGULATION
The drop in secondary voltage that occurs as the load on the transformer is increased
and is expressed as a percentage of rated voltage.
● EFFICIENCY
The ratio of power absorbed by the transformer to the total power drawn from the supply
line.
Schneider Electric 6- Projects and Services – PEC – MV Transformers - 2010
“Rule of Thumb” Cost Comparison
●Mineral Oil 1.0
●Hi Fire Point Seed Oil 1.2
●VPI 1.25 – 1.75
●VPE (Epoxy) 1.35 – 1.85
●Cast Coil 1.55 – 2.0
●Lower Temerature Rise 15 % to 40 % Add
●Copper 35% - 35% Add
●5 DB Noise Reduction (Dry) 10%
●Hinged Doors on Dry and Cast Enclosures A bargain
●I.R. Viewing Windows on Dry and Cast Encl. An Even Better Bargain
●Insulated Bus on VPI and Cast Encl. $2K – 5K, but a good
idea just the same.
Schneider Electric 7- Projects and Services – PEC – MV Transformers - 2010
H.V. BIL Comparison
Dry Type Liquid/Cast
Voltage Class Std Opt Std Opt
2.4 KV 20 KV 30 KV 45 KV 60 KV
5 KV 30 KV 45 KV 60 KV 75 KV
8.3 KV 45 KV 60 KV 75 KV 95 KV
15 KV 60 KV 95 KV 95 KV 110 KV
25 KV 110 KV 125 KV 125 KV 150 KV
35 KV 150 KV ----- 150 KV 200 KV
46 KV ----- ------ 250 KV ------
Schneider Electric 8- Projects and Services – PEC – MV Transformers - 2010
Impedance
●IEEE Standard
● 5.75 Nominal for 750 kVA and Above
● Manufacturer’s standard within the IEEE Standard range for 500 kVA and
below
● Large units and higher voltages have different standards
●Note
● IEEE allows a +/- 7.5% Tolerance
● Example for 5.75% Impedance Range would be 5.32% to 6.18%
Schneider Electric 9- Projects and Services – PEC – MV Transformers - 2010
Insulation Classes
TRANSFORMER INSULATION WINDING MAXIMUM HOTSPOT HOT SPOT
TYPE CLASS RISE AMBIENT GRADIENT TEMPERATURE
POWER-DRY 220 DEG. C 150 DEG. C + 40 DEG. C + 30 DEG. C = 220 DEG. C
CAST COIL 185 DEG. C 115 DEG. C + 40 DEG. C + 30 DEG. C = 185 DEG. C
LIQUID-FILLED 120 DEG. C 65 DEG. C + 40 DEG. C + 15 DEG. C = 120 DEG. C
Schneider Electric 10- Projects and Services – PEC – MV Transformers - 2010
Temperature Rise
Dry 150 Degree C Standard
115 Degree C Optional
80 Degree C Optional
Cast 115 Degree C Standard
80 Degree C Option
Liquid Filled 65 Degree C Standard
55/65 Degree C Optional
Schneider Electric 11- Projects and Services – PEC – MV Transformers - 2010
Altitude
●STANDARD: Designed for operation at a maximum altitude of
3300 ft. (1000m) above sea level
●If a non standard condition exists (i.e.. Altitude above 3300 ft ASL
then:
● Transformer must be de-rated or
● Transformer must be specifically designed for the special altitude
consideration.
Schneider Electric 12- Projects and Services – PEC – MV Transformers - 2010
OVERLOAD EXAMPLE
3000 kVA Dry Type Xfmr.
AA + 33%
(5400)
Base kVA + 35%
(4050)
80/150
AA + 33%
(4600)
Base kVA + 15%,
(3450)
115/150
AA + 33%
(4000)
Base kVA
(3000)
150
Fan Cool Rating
(FA)
kVA Rating
(AA)
Temp. Rise
(Deg. C)
Schneider Electric 13- Projects and Services – PEC – MV Transformers - 2010
NEMA Standard Sound Levels
kVA LIQUID-FILLED VPI CAST
51-150 51 55 N/A
225-300 55 55 58
301-500 56 60 60
501-1000 58 64 64
1001-1500 60 65 65
1501-2000 61 66 66
2001-2500 62 68 68
2501-3000 63 68 68
3001-4000 64 70 70
4001-5000 66 71 71
7500 67 75 75
10,000 68 78 78
NOTE: ALL VALUES ARE IN DECIBELS (db) AND ARE FOR BASE kVA RATINGS (FAN PACKAGES WILL INCREASE
db LEVELS)
Schneider Electric 14- Projects and Services – PEC – MV Transformers - 2010
Energy Efficient (EE) MV Transformers
● The Department of Energy (DOE) has determined that energy conservation
standards for MV Distribution Transformers will result in significant conservation
of energy so they have passed DOE 10 CFR Part 431 Energy Conservation
program for Commercial Equipment.
● Starting January 1, 2010 all medium voltage distribution transformers with
ratings of 2500 kVA and below, 34.5 KV primary and below and 600V class
secondary voltages must meet minimum efficiency requirements.
● Liquid Filled Padmounts, Liquid Filled Substations, Dry Type VPI and Power
Cast products MANUFACTURED after January 1, 2010 are all included.
● EE Low Voltage transformers implemented in 2006, this law is extending
efficiencies to Medium Voltage.
Schneider Electric 15- Projects and Services – PEC – MV Transformers - 2010
DOE Energy Efficiency Applies to:
●Medium Voltage Liquid
● » 10-833 kVA 1 phase
● » 15-2500 kVA 3 phase
●2. Medium Voltage Dry
● » 15-833 kVA 1 phase
● » 15-2500 kVA 3 phase
Schneider Electric 16- Projects and Services – PEC – MV Transformers - 2010
Minimum Efficiency Tables
Liquid Filled
Note: All efficiency values are at 50 percent of nameplate-rated load, determined according to the
Appendix A, DOE Test procedure. 10 CFR Part 431, Subpart K
Table I.1
Table I.1 - Standard levels for Liquid Immersed Distribution Transformers,
tabular Form
10………………….. 15……………………
kVA
Three Phase
Efficiency %
98.62
Single Phase
Efficiency % kVA
15…………………..
25…………………..
37.5…………………
50……………………
75……………………
100………………….
167………………….
250………………….
333………………….
500………………….
667………………….
833………………….
98.76
98.97
99.01
99.08
99.17
99.23
99.25
99.32
99.36
99.42
99.46
99.49
30…………………..
45……………………
75…………………….
112.5……………….
150…………………..
225………………….
300…………………..
500…………………..
750…………………..
1000…………………
1500…………………
2000………………….
98.36
98.62
98.76
98.91
99.01
99.08
99.17
99.23
99.25
99.32
99.36
99.42
99.46
2500………………… 99.49
Schneider Electric 17- Projects and Services – PEC – MV Transformers - 2010
Applies to all Transformers Sold in:
●All 50 US States
●Unincorporated Territories (Possessions): American Samoa, Guam,
Marshall Islands, Puerto Rico, US Virgin Islands
●Freely-associated states: Federal States of Micronesia, Northern
Marianas, Palau
Schneider Electric 18- Projects and Services – PEC – MV Transformers - 2010
Does not Apply for Transformers
●Exported to a country outside the US
●Armed Forces bases located outside the US unless specified or to a US
territory
●US Embassies unless specified
Schneider Electric 19- Projects and Services – PEC – MV Transformers - 2010
Transformers Affected:
●Have an input voltage of 34.5 kilovolts or less;
●Have an output voltage of 600 volts or less; and
●Are rated for operation at a frequency of 60 Hertz
Schneider Electric 20- Projects and Services – PEC – MV Transformers - 2010
Excluded Transformers
●A transformer with multiple voltage taps, the highest of which
equals at least 20 percent more than the lowest;
●A transformer that is designed to be used in a special purpose
application and is unlikely to be used in general purpose
applications, or
●Any transformer not listed in this definition that is excluded by the
Secretary by rule
Schneider Electric 21- Projects and Services – PEC – MV Transformers - 2010
Excluded Transformers
● Autotransformers
● Drive (isolation) transformers
● Grounding transformers
● Machine-tool (control) transformers
● Nonventilated transformers
● Rectifier transformers
● Regulating transformers
● Sealed transformers
● Special-impedance transformers
● Testing transformers
● Transformer with tap range of 20 percent or more
● Uninterruptible power supply transformers
● Welding transformers
● Step up Transformers
Schneider Electric 22- Projects and Services – PEC – MV Transformers - 2010
Seismic
Schneider Electric 23- Projects and Services – PEC – MV Transformers - 2010
Liquid Filled Transformers
Padmount
Unit Substation
Schneider Electric 24- Projects and Services – PEC – MV Transformers - 2010
Liquid Filled Padmount
●Product Scope:
●75-5000kVA
● 55, 65, 55/65 Temp. Rise
● 2.4 - 34.5kV Class Primary 150kV BIL Max
● 600V - 5kV Class Secondary 75kV BIL Max.
● Self-Cooled Overload Only (12% with 55/65)
● ONAN only - NO ONAN/ONAF (no fans)
●No Fans means, NO FANS!
●Weather Resistant high and low voltage compartments
●Tamper-Resistant Design
(Available up to 20,000 kVA via special quotation)
Schneider Electric 25- Projects and Services – PEC – MV Transformers - 2010
Fluid Offerings
MINERAL OIL
Type II (Inhibited) Ergon Hyvolt II
Mainly Outdoor (Fire Point = 165 Deg. C)
Least Expensive of all Fluids
BIOTEMP (ABB)
Renewable Natural Agricultural Product
Certified by UL® as “Less-Flammable Fluid”
Fire Point = 360 Deg. C
Factory Mutual Approved
Biodegrades 97% in 21 days
No fusing restrictions
LESS FLAMMABLE SEED OIL
FR3 FLUID ™ (Cooper Industries)
Certified by UL® as “Less-Flammable Fluid”
Fire Point = 360 Deg. C
Factory Mutual Approved
Biodegrades 99% in 21 days
No fusing restrictions
Extends insulation life
LESS FLAMMABLE SEED OIL
Schneider Electric 26- Projects and Services – PEC – MV Transformers - 2010
Liquid Filled Padmount
HV Bushings
Drain
Valve
Bay-o-net
Fuses
Tap Changer
Pressure
vacuum
Gauge
Upper Fill Plug
Temperature
Gauge
Liquid Level
GaugePressure Relief
valve
Name PlateLV Bushing
HV
Compartment LV Compartment
Schneider Electric 27- Projects and Services – PEC – MV Transformers - 2010
Radial Feed vs Loop Feed
A. Radial Feed
3 HV Bushings
B. Loop Feed
6 HV Bushings
A transformer with loop feed construction can be used on 2 types of systems:
1. Dual Source Radial Feed
2. Loop Feed System
Schneider Electric 28- Projects and Services – PEC – MV Transformers - 2010
Live Front Construction
●Contains “exposed current carrying parts” in HV
compartment (IEEE C57.12.34)
●Components: Porcelain Bushings
●Live Front bushings arranged in horizontal pattern,
Radial and Loop Feed
Schneider Electric 29- Projects and Services – PEC – MV Transformers - 2010
Liquid Filled Padmount
Live Front Transformer
Note: 5/8” eyebolt terminal-optional 2 or 4 hole pad is available by special quote
Schneider Electric 30- Projects and Services – PEC – MV Transformers - 2010
Dead Front Construction
“No exposed current carrying parts HV compartment” (IEEE
C57.12.34)
Components: Wells, Inserts, One Piece Bushings, Feed-thru inserts
Available In: 15, 25,35kV Classes
Available In: 200 Amp - Loadbreak
600 Amp - Non-Loadbreak
Note: Can not interchange different classes of components.
Radial Feed: Bushings in horizontal pattern.
Loop Feed: “V” Type Configuration
Schneider Electric 31- Projects and Services – PEC – MV Transformers - 2010
Liquid Filled Padmount
Dead Front-Radial Feed Dead Front-Loop Feed
Schneider Electric 32- Projects and Services – PEC – MV Transformers - 2010
Liquid Filled Padmount
Dead Front Bushing Well
Schneider Electric 33- Projects and Services – PEC – MV Transformers - 2010
Liquid Filled Padmount
Bushing Insert
Schneider Electric 34- Projects and Services – PEC – MV Transformers - 2010
Liquid Filled Padmount
No Load Tap Changer
Schneider Electric 35- Projects and Services – PEC – MV Transformers - 2010
Liquid Filled Padmount
Schneider Electric 36- Projects and Services – PEC – MV Transformers - 2010
Switching
All transformers (radial and loop feed construction) are not equipped with
HV switches. Switching can be accomplished remotely.
Padmount can be equipped with:
1. Two Position (ON-OFF) Switch
(Can be used on radial and loop units.)
2. Three Position Switch
Line A Only, Line B Only, Off
(Dual source application.)
3. Four Position Switch - Permits Sectionalizing
(Loop feed transformers only.)
Schneider Electric 37- Projects and Services – PEC – MV Transformers - 2010
Arresters
●Arresters
● Silicone carbide or MOV (Metal-Oxide Varistor) most common.
●Operation
● MOV is a granular ceramic (semi-conductor)
● Conducts during a “High Amplitude Transient” and diverts excess voltage to
ground
● Provides a transient path to a common point earth ground.
Schneider Electric 38- Projects and Services – PEC – MV Transformers - 2010
Liquid Filled Padmount
Bayonet Type Fuse
Schneider Electric 39- Projects and Services – PEC – MV Transformers - 2010
Liquid Filled Padmount
Schneider Electric 40- Projects and Services – PEC – MV Transformers - 2010
Liquid Filled Padmount
Schneider Electric 41- Projects and Services – PEC – MV Transformers - 2010
Liquid Filled Padmount
Schneider Electric 42- Projects and Services – PEC – MV Transformers - 2010
Liquid Filled Padmount
Schneider Electric 43- Projects and Services – PEC – MV Transformers - 2010
Liquid Filled Unit Substation
Schneider Electric 44- Projects and Services – PEC – MV Transformers - 2010
Liquid Filled Unit Substation
●225-10,000kVA
● 55, 65, 55/65 Temp. Rise
● 2.4 - 34.5kV Class Primary - 250 kV BIL Max.
● 600V - 8.7kV Class Secondary - 75kV BIL Max.
● ONAN/ONAF also known as AA/FA
●Available up to 20,000 kVA - 69 kV primary, 5 kV up to 34.5 kV
secondary via special quotation with Square D Name Plate.
●Now available up to 60 MVA base rating, 161 KV primary, 34.5
Secondary with ABB Name Plate
Schneider Electric 45- Projects and Services – PEC – MV Transformers - 2010
Liquid Filled Unit Substation
●Standard efficiency (Energy Efficient per DOE2010)
● K-Rated units
● UL Listing
● Factory Mutual
● Evaluated loss designs
● Oil, Silicone, and Less Flammable Seed Oil
Schneider Electric 46- Projects and Services – PEC – MV Transformers - 2010
Fluid Offerings
MINERAL OIL Type II (Inhibited) Ergon Hyvolt II
• Mainly Outdoor (Fire Point = 165 Deg. C)
• Least Expensive of all Fluids
SILICONE (Dow Corning 561)
• “Less Flammable Liquid” (Fire Point = 343 Deg. C)
• Indoor Use
• Expensive Fluid
BIOTEMP (ABB)
Renewable Natural Agricultural Product
• Certified by UL® as “Less-Flammable Fluid”
• Fire Point = 360 Deg. C
• Factory Mutual Approved
• Biodegrades 97% in 21 days
• No fusing restrictions
• LESS FLAMMABLE SEED OIL
FR3 FLUID ™ (Cooper Industries)
• Certified by UL® as “Less-Flammable Fluid”
• Fire Point = 360 Deg. C
• Factory Mutual Approved
• Biodegrades 99% in 21 days
• No fusing restrictions
• LESS FLAMMABLE SEED OIL
Schneider Electric 47- Projects and Services – PEC – MV Transformers - 2010
Unit Substation Transformers
●Close coupled to HV or LV switchgear
● Includes throats, flanges, etc.
● Coordination through Unit Substation Coordination Group
●Stand alone with full or partial height ATC’s
●Connection to HV Non-Seg Busway or LV I-Line Busway
● Includes standard 12” Throat
● Busway Plant will provide connection box to throat
● Coordination through MV Transformer Group
●Special retro-fit connections/dimensions available
Schneider Electric 48- Projects and Services – PEC – MV Transformers - 2010
Liquid Filled Unit Substation
Cooling Options
●(ONAN) Self-Cooled (Oil Natural Air Natural)
(55/65 Deg. C Self-Cooled = 12% Overload)
●(ONAN / FONFA) * Self-Cooled With Provisions For Future
Addition Of Fans
●(ONAN / ONFA) * Self-Cooled With Fans To Provide Additional
Capacity
● *NOTE: Controlled By: Top Of Oil or Winding Temperature Indicator
(Winding Temp Ind. is expensive option)
Schneider Electric 49- Projects and Services – PEC – MV Transformers - 2010
Liquid Filled Transformers
Fans Increase Capacity As Follows:
< 2000 kVA
Increase 15%
2500 Through 10000 kVA
Increase 25%
Schneider Electric 50- Projects and Services – PEC – MV Transformers - 2010
Arrester Classes
1. Distribution Class Heavy Duty Type
2. Intermediate Class Higher Energy Handling Capability
3. Station Class Provide Greatest Degree Of Protection,
Highest Level Of Energy Handling, Max
Capability = 80kA
Note: Intermediate or Station Class Arresters require larger ATC’s
Schneider Electric 51- Projects and Services – PEC – MV Transformers - 2010
Liquid Filled Unit Substation
Schneider Electric 52- Projects and Services – PEC – MV Transformers - 2010
Unit Substation Transformers
Schneider Electric 53- Projects and Services – PEC – MV Transformers - 2010
End of Section
Schneider Electric 54- Projects and Services – PEC – MV Transformers - 2010
Dry Transformers
Schneider Electric 55- Projects and Services – PEC – MV Transformers - 2010
Dry Transformers
Advantages
●Excellent for Indoor Use
● Schools, Hospitals, Office Buildings
● Locations where a liquid spill can not be tolerated
● No containment pit required, providing for lower installation and
maintenance costs
●Non-Flammable
● 220C Insulation Class
● Will not support combustion
●Approximately the same Price of a Seed Oil Unit
● Most economical when compared to UniCast II or PowerCast II
Schneider Electric 56- Projects and Services – PEC – MV Transformers - 2010
Dry Transformers
Disadvantages
● Lower BIL Levels than Liquid Filled
● Standard for 15kV Class is 60kV BIL, Liquid Filled is 95kV BIL
● Standard for 600V Class is 10kV BIL, Liquid Filled is 30kV BIL
● Moisture Absorption
● Must pre-dry unit before energizing to eliminate moisture from coils
● More Susceptible to Airborne Contaminants
● Ventilated enclosure, contaminants may accumulate on coils
Schneider Electric 57- Projects and Services – PEC – MV Transformers - 2010
Picture of VPI Process
Schneider Electric 58- Projects and Services – PEC – MV Transformers - 2010
Dry Transformer
COOLING OPTIONS
●(AA) Self Cooled
●(AA/FFA)* Self Cooled with provisions for future forced air
●(AA/FA)* Self cooled with forced air
* Capacity will be increased by 33 1/3% with the addition of fans
For example:
● 1000kVA @ 150C = 1000/1333kVA
● 1000kVA @ 115/150C = 1000/1150/1533kVA
● 1000kVA @ 80/150C = 1000/1300/1733kVA
Schneider Electric 59- Projects and Services – PEC – MV Transformers - 2010
Unit Substation Transformers
Selectable Product Scope
225 - 5000 kVA
150, 115, and 80 Degree C Rise
2.4 - 34.5 kV Class Primary
150kV Primary BIL
600V - 5kV Class Secondary
(Available up to 13,000 kVA via special quotation)
Schneider Electric 60- Projects and Services – PEC – MV Transformers - 2010
Cast Coil Transformers
Power Cast II and UniCast II
Schneider Electric 61- Projects and Services – PEC – MV Transformers - 2010
Cast Resin Transformers
(The Need)
●Replacement for Askarel
(Non-Flammable)
●Environmentally Safe
(By Products of Combustion)
●BIL Equivalent to Liquid Filled
●Primary Voltages Higher than Dry Type
●Mechanical Short Circuit Strength
(Superior)
Schneider Electric 62- Projects and Services – PEC – MV Transformers - 2010
Cast Coil Transformers
(The Coil)
HV/LV Coil
Schneider Electric 63- Projects and Services – PEC – MV Transformers - 2010
Cast Coil Transformers
LV Coil w/Cooling Ducts
Schneider Electric 64- Projects and Services – PEC – MV Transformers - 2010
Cast Coil Transformers
Core/Coil Assembly
Schneider Electric 65- Projects and Services – PEC – MV Transformers - 2010
Benefits
Cast Coil vs. Liquid
●No Fluids to Leak, Contaminate, or Burn
●Far Less Maintenance, No Yearly Fluid Testing
●No Decommissioning Costs
●Higher Short Circuit Strength
●Non - Flammable
●Longer Design Life when compared to Mineral Oil
●Greater Fan Overload Capability
●Lower Installation Costs
Schneider Electric 66- Projects and Services – PEC – MV Transformers - 2010
Benefits of Cast Coil vs.
Conventional “VPI”
●Resistant to Moisture and Contaminants
●Higher Standard BIL Levels
●Lower Operating Costs
Lower Standard Temperature Rise - 80 vs 150
More Efficient
Less Maintenance
●Longer Design Life
●More Reliable
●Greater Design Flexibility
Higher kVA Ratings
Higher Primary and Secondary Voltages
Schneider Electric 67- Projects and Services – PEC – MV Transformers - 2010
IMPEDANCE
● DEFINITION
The percentage of rated voltage required to circulate rated current in one
winding with the other winding short circuited.
● EXAMPLE
A transformer with a 5.75% impedance and a 480 volt low voltage winding
would require (0.0575 x 480 volt) or 27.6 volts to circulate rated current.
● IN SHORT
Impedance is simply the opposition to the flow of current in the transformers
windings.
(Impedance has a resistive and an inductive component.)
Schneider Electric 68- Projects and Services – PEC – MV Transformers - 2010
IMPEDANCE
● High or Low Impedance does not necessarily mean Low or High Efficiency.
● Impedance consists of two components:
1) A Resistive Component
2) A Reactive Component
%IZ = ( % IR ) 2 + ( % IX ) 2
Schneider Electric 69- Projects and Services – PEC – MV Transformers - 2010
Efficiency
Definition:
The ratio of power absorbed by the transformer to the total power drawn from the supply
line.
Efficiency can be calculated using the following formula:
EFF = [1 - (Y + (L)2 (X))/(100L + Y + (L)2 x)] 100
Where X = % IR @ 100% Load
Cosine 0
Cosine 0 = Power Factor Cosine 0 = Power Factor
% IR = Load Loss (KW) x 100 % FE = No Load Loss (KW) x 100
Rated kVA Rated kVA
Y = % FE @ 100% Load L = Load Factor = % Load
Cosine 0 (Per Unit Load) 100
Schneider Electric 70- Projects and Services – PEC – MV Transformers - 2010
Example:
What is the efficiency at 100% load and 1.0 power factor of the 75kVA
transformer with:
No-Load Loss: 341 Watts
Load Loss: 1478 Watts
Impedance: 3.45 %
% IR = (1.478/75) x 100 = 1.97
PF = 1.0
X = % IR = 1.97 = 1.97
PF 1
% FE = .0341 x 100 = 0.454
75kVA
Y = % FE = 0.454 = 0.454
PF 1
L = % Load = 100 = 1
100 100
Schneider Electric 71- Projects and Services – PEC – MV Transformers - 2010
Heat Dissipation
Some consultants think that a transformer with a lower
temperature rise is better for vault and indoor applications. This
is not correct.
Transformers have losses.
Each watt of total loss = 3.413 BTU/Hr
Multiply the total loss by this value to determine the heat which
must be dissipated by air conditioning, ventilation, etc.
Schneider Electric 72- Projects and Services – PEC – MV Transformers - 2010
Tests
● WINDING RESISTANCE
● PURPOSE: The fundamental purpose of this test is to supply resistance data which
will be used to calculate I2R conductor losses and winding temperatures. It also
enables a check of coil continuity and hence, is often used in the field as an indicator
of possible damage to any internal coil connections.
● RATIO, POLARITY, AND PHASE RELATION
● PURPOSE: To verify that the transformer has the correct number of turns in each
winding (ratio and that the polarity and phase relationship of the windings are correct.
● INSULATION POWER FACTOR
● PURPOSE: To verify that the transformer has been properly dried and that its
moisture content is not excessive. Insulation power factor is defined as the ratio of
power dissipated in the transformer insulation (in watts) to the product of the effective
voltage and current (in volt-amperes) while being tested with a sine-wave voltage.
Schneider Electric 73- Projects and Services – PEC – MV Transformers - 2010
Tests
●EXCITATION LOSS
● PURPOSE: To verify that excitation losses, which consist primarily of winding losses
due to exciting current and losses in the transformer’s core, meet guaranteed values
promised to the customer.
●EXCITATION CURRENT
● PURPOSE: To verify core construction quality
●LOAD LOSS
● PURPOSE: To verify that the load losses meet the guarantees given to a customer.
●IMPEDANCE
● PURPOSE: To verify guarantees given to the customer.
Schneider Electric 74- Projects and Services – PEC – MV Transformers - 2010
Dielectric Tests
● APPLIED POTENTIAL TEST
● PURPOSE: To verify that the dielectric strength of the insulation from
winding to ground and winding to winding is adequate.
● PROCEDURE: A voltage level defined by IEEE is applied to the winding
under test for a period of 60 seconds. (34KV for 15 KV, 95KV BIL Units)
● INDUCED POTENTIAL TEST
● PURPOSE: To verify the insulation between turns and layers of the same
winding, and phase to phase clearance is sufficient.
● PROCEDURE: A special high frequency generator is used to prevent the
core from saturating due to the high voltage that is induced in the winding.
(120, 180, 240 or 400 Hz are commonly used). A voltage up to two times
the rating of the winding is applied for a period of 7200 cycles.
Schneider Electric 75- Projects and Services – PEC – MV Transformers - 2010
Impulse Test
● PURPOSE
● To verify that the transformer
insulation (BIL) can withstand the
transient over voltages.
● TYPES OF IMPULSE TESTS
● Half Wave
● Full Wave
● Chopped Wave: A more severe
test as it simulates a transient that is
chopped to ground by an arrester
QC impulse is done on all of our
products. This impulse test includes
full and half wave. The Chopped
Wave is included when ANSI
Impulse Test is included in the
specification.
Schneider Electric 76- Projects and Services – PEC – MV Transformers - 2010
Design Tests
●TEMPERATURE RISE TEST
● PURPOSE: To verify that the top oil and winding temperature rise does not
exceed the guaranteed levels under full load operation.
●SOUND LEVEL TEST
● PURPOSE: To verify that the sound level produced by the transformer is
within guaranteed values. The principle noise associated with transformers,
aside from that produced by any cooling fans, is an audible hum due to a
phenomenon called Magnetostriction. When core steel is excited by a
magnetic field it contracts slightly. This dimensional change which occurs
120 times per second for a 60 cycle system (once every half cycle) is
defined as Magnetostriction.

More Related Content

What's hot

Power transformer protection
Power transformer protectionPower transformer protection
Power transformer protectionmichaeljmack
 
Electrical Design calculations
Electrical Design calculationsElectrical Design calculations
Electrical Design calculationsPankaj Chavan
 
MV MetalClad Switchgear
MV MetalClad SwitchgearMV MetalClad Switchgear
MV MetalClad Switchgearmichaeljmack
 
Transformer testing
Transformer testingTransformer testing
Transformer testingajayknows
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protectionashwin fcc
 
Transformer overcurrent
Transformer overcurrentTransformer overcurrent
Transformer overcurrentmichaeljmack
 
Switchgear and protection 1
Switchgear and protection 1Switchgear and protection 1
Switchgear and protection 1Md Irshad Ahmad
 
Testing of transformer
Testing of transformerTesting of transformer
Testing of transformervikasgupta1965
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersSARAVANAN A
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settingsmichaeljmack
 
Principles of Cable Sizing
Principles of Cable SizingPrinciples of Cable Sizing
Principles of Cable SizingLeonardo ENERGY
 
Operation and maintenance of transformer
Operation and maintenance of transformerOperation and maintenance of transformer
Operation and maintenance of transformerKapil Singh
 
A2.34+transformer+maintenance+tutorial
A2.34+transformer+maintenance+tutorialA2.34+transformer+maintenance+tutorial
A2.34+transformer+maintenance+tutorialJack Duff
 
Ieee std-1313-2-1999
Ieee std-1313-2-1999Ieee std-1313-2-1999
Ieee std-1313-2-1999Noel Ramos
 
ETAP - Short circuit analysis iec standard
ETAP - Short circuit analysis iec standardETAP - Short circuit analysis iec standard
ETAP - Short circuit analysis iec standardHimmelstern
 
ETAP - Ugs Underground Raceway Systems
ETAP - Ugs Underground Raceway SystemsETAP - Ugs Underground Raceway Systems
ETAP - Ugs Underground Raceway SystemsHimmelstern
 

What's hot (20)

IEEE substation design
IEEE substation designIEEE substation design
IEEE substation design
 
Power transformer protection
Power transformer protectionPower transformer protection
Power transformer protection
 
Flashover Tests
Flashover TestsFlashover Tests
Flashover Tests
 
Electrical Design calculations
Electrical Design calculationsElectrical Design calculations
Electrical Design calculations
 
Cable sizing.pptx
Cable sizing.pptxCable sizing.pptx
Cable sizing.pptx
 
MV MetalClad Switchgear
MV MetalClad SwitchgearMV MetalClad Switchgear
MV MetalClad Switchgear
 
Transformer testing
Transformer testingTransformer testing
Transformer testing
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protection
 
Transformer overcurrent
Transformer overcurrentTransformer overcurrent
Transformer overcurrent
 
Switchgear and protection 1
Switchgear and protection 1Switchgear and protection 1
Switchgear and protection 1
 
Testing of transformer
Testing of transformerTesting of transformer
Testing of transformer
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineers
 
Transformer basic
Transformer basicTransformer basic
Transformer basic
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settings
 
Principles of Cable Sizing
Principles of Cable SizingPrinciples of Cable Sizing
Principles of Cable Sizing
 
Operation and maintenance of transformer
Operation and maintenance of transformerOperation and maintenance of transformer
Operation and maintenance of transformer
 
A2.34+transformer+maintenance+tutorial
A2.34+transformer+maintenance+tutorialA2.34+transformer+maintenance+tutorial
A2.34+transformer+maintenance+tutorial
 
Ieee std-1313-2-1999
Ieee std-1313-2-1999Ieee std-1313-2-1999
Ieee std-1313-2-1999
 
ETAP - Short circuit analysis iec standard
ETAP - Short circuit analysis iec standardETAP - Short circuit analysis iec standard
ETAP - Short circuit analysis iec standard
 
ETAP - Ugs Underground Raceway Systems
ETAP - Ugs Underground Raceway SystemsETAP - Ugs Underground Raceway Systems
ETAP - Ugs Underground Raceway Systems
 

Similar to Transformers

Powering Every House, Powering Every Industry
Powering Every House, Powering Every IndustryPowering Every House, Powering Every Industry
Powering Every House, Powering Every IndustryAkil Siddiqui
 
An introduction to Zeversolar inverters
An introduction to Zeversolar invertersAn introduction to Zeversolar inverters
An introduction to Zeversolar invertersAlternergy
 
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC GridsNeil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC GridsEnergyTech2015
 
Power transformers rating
Power transformers ratingPower transformers rating
Power transformers ratingLeonardo ENERGY
 
Challenges in Transformer Technology -by Mr. Krishnaiah (Kryfs)
Challenges in Transformer Technology -by Mr. Krishnaiah (Kryfs)Challenges in Transformer Technology -by Mr. Krishnaiah (Kryfs)
Challenges in Transformer Technology -by Mr. Krishnaiah (Kryfs)ProSIM R & D Pvt. Ltd.
 
Ricardo DC-DC Converter Presentation for NMI
Ricardo DC-DC Converter Presentation for NMIRicardo DC-DC Converter Presentation for NMI
Ricardo DC-DC Converter Presentation for NMIFrank Warnes
 
Padmounted transformer
Padmounted transformerPadmounted transformer
Padmounted transformerJoeChueng
 
Electric Transformers and Energy Efficiency
Electric Transformers and Energy EfficiencyElectric Transformers and Energy Efficiency
Electric Transformers and Energy EfficiencyANIE Energia
 
Dry type autotransformer
Dry type autotransformerDry type autotransformer
Dry type autotransformerJoeChueng
 
CG (Crompton Greaves) Alternators
CG (Crompton Greaves) AlternatorsCG (Crompton Greaves) Alternators
CG (Crompton Greaves) AlternatorsRichard Schembri
 
European Regulation N 548/14 on power transformers
European Regulation N 548/14 on power transformersEuropean Regulation N 548/14 on power transformers
European Regulation N 548/14 on power transformersLeonardo ENERGY
 
Fcs capacitor switch
Fcs capacitor switchFcs capacitor switch
Fcs capacitor switchJoeChueng
 
Single phase pole mounted transformer
Single phase pole mounted transformerSingle phase pole mounted transformer
Single phase pole mounted transformerJoeChueng
 
abb_switchgear_pricelist.pdf
abb_switchgear_pricelist.pdfabb_switchgear_pricelist.pdf
abb_switchgear_pricelist.pdfDinesh Kalola
 

Similar to Transformers (20)

Powering Every House, Powering Every Industry
Powering Every House, Powering Every IndustryPowering Every House, Powering Every Industry
Powering Every House, Powering Every Industry
 
ABB Price List of Capacitors 008
ABB Price List of Capacitors 008ABB Price List of Capacitors 008
ABB Price List of Capacitors 008
 
An introduction to Zeversolar inverters
An introduction to Zeversolar invertersAn introduction to Zeversolar inverters
An introduction to Zeversolar inverters
 
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC GridsNeil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids
Neil Kirby: VSC HVDC Transmission and Emerging Technologies in DC Grids
 
Power transformers rating
Power transformers ratingPower transformers rating
Power transformers rating
 
Challenges in Transformer Technology -by Mr. Krishnaiah (Kryfs)
Challenges in Transformer Technology -by Mr. Krishnaiah (Kryfs)Challenges in Transformer Technology -by Mr. Krishnaiah (Kryfs)
Challenges in Transformer Technology -by Mr. Krishnaiah (Kryfs)
 
Pragati pt cataloge
Pragati pt catalogePragati pt cataloge
Pragati pt cataloge
 
Ricardo DC-DC Converter Presentation for NMI
Ricardo DC-DC Converter Presentation for NMIRicardo DC-DC Converter Presentation for NMI
Ricardo DC-DC Converter Presentation for NMI
 
ATS-Catalogue-Latest
ATS-Catalogue-LatestATS-Catalogue-Latest
ATS-Catalogue-Latest
 
Catalogue-Oil Cooled-Resin Cast CTs-PTs-ATS
Catalogue-Oil Cooled-Resin Cast CTs-PTs-ATSCatalogue-Oil Cooled-Resin Cast CTs-PTs-ATS
Catalogue-Oil Cooled-Resin Cast CTs-PTs-ATS
 
Padmounted transformer
Padmounted transformerPadmounted transformer
Padmounted transformer
 
Electric Transformers and Energy Efficiency
Electric Transformers and Energy EfficiencyElectric Transformers and Energy Efficiency
Electric Transformers and Energy Efficiency
 
Dry type autotransformer
Dry type autotransformerDry type autotransformer
Dry type autotransformer
 
CG (Crompton Greaves) Alternators
CG (Crompton Greaves) AlternatorsCG (Crompton Greaves) Alternators
CG (Crompton Greaves) Alternators
 
European Regulation N 548/14 on power transformers
European Regulation N 548/14 on power transformersEuropean Regulation N 548/14 on power transformers
European Regulation N 548/14 on power transformers
 
Fcs capacitor switch
Fcs capacitor switchFcs capacitor switch
Fcs capacitor switch
 
Single phase pole mounted transformer
Single phase pole mounted transformerSingle phase pole mounted transformer
Single phase pole mounted transformer
 
electrician
electricianelectrician
electrician
 
Two Quadrant chopper
Two Quadrant chopperTwo Quadrant chopper
Two Quadrant chopper
 
abb_switchgear_pricelist.pdf
abb_switchgear_pricelist.pdfabb_switchgear_pricelist.pdf
abb_switchgear_pricelist.pdf
 

More from michaeljmack

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993michaeljmack
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbookmichaeljmack
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbookmichaeljmack
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systemsmichaeljmack
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flashmichaeljmack
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgearmichaeljmack
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrushmichaeljmack
 
Building information modeling
Building information modelingBuilding information modeling
Building information modelingmichaeljmack
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protectionmichaeljmack
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systemsmichaeljmack
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spacesmichaeljmack
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708michaeljmack
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distributionmichaeljmack
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performancemichaeljmack
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulatormichaeljmack
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plantsmichaeljmack
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Storiesmichaeljmack
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Sheddingmichaeljmack
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentalsmichaeljmack
 

More from michaeljmack (20)

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbook
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbook
 
Surge Protection
Surge ProtectionSurge Protection
Surge Protection
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systems
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flash
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgear
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
 
Building information modeling
Building information modelingBuilding information modeling
Building information modeling
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protection
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systems
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spaces
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distribution
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performance
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulator
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plants
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Stories
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Shedding
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentals
 

Recently uploaded

22-prompt engineering noted slide shown.pdf
22-prompt engineering noted slide shown.pdf22-prompt engineering noted slide shown.pdf
22-prompt engineering noted slide shown.pdf203318pmpc
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Standamitlee9823
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projectssmsksolar
 
Employee leave management system project.
Employee leave management system project.Employee leave management system project.
Employee leave management system project.Kamal Acharya
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapRishantSharmaFr
 
Unit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfUnit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfRagavanV2
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdfKamal Acharya
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringmulugeta48
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Bookingroncy bisnoi
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfJiananWang21
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptNANDHAKUMARA10
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationBhangaleSonal
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptMsecMca
 

Recently uploaded (20)

22-prompt engineering noted slide shown.pdf
22-prompt engineering noted slide shown.pdf22-prompt engineering noted slide shown.pdf
22-prompt engineering noted slide shown.pdf
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 
2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects
 
Employee leave management system project.
Employee leave management system project.Employee leave management system project.
Employee leave management system project.
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
Unit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfUnit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdf
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 

Transformers

  • 1. IEEE SF / IAS Seminar April 2011 Finn Schenck Schneider Electric
  • 2. Schneider Electric 2- Projects and Services – PEC – MV Transformers - 2010 Transformer Types Liquid-Filled Padmount Liquid-Filled Unit Substation
  • 3. Schneider Electric 3- Projects and Services – PEC – MV Transformers - 2010 Transformer Types VPI Dry Unit Substation Cast Unit Substation
  • 4. Schneider Electric 4- Projects and Services – PEC – MV Transformers - 2010 Dry Vs. Liquid Transformers DRY ●No fluid to spill or burn ●Cost is higher than oil ●Resistant to moisture ●Minimum Maintenance ●UL Listed Liquid ●Lowest Purchase Price ●Sealed Tank ●Lowest Losses per $ ●UL Listing ●Loads of Options ●Pad Mounted (Tamper- Resistant) ●Substation – Flexible
  • 5. Schneider Electric 5- Projects and Services – PEC – MV Transformers - 2010 Definitions (Buzzwords) ● BIL (Basic Impulse Level) The level of momentary over voltage that the transformers insulation can withstand without damage/failure. ● IMPEDANCE The percentage of rated voltage required to circulate rated current in one winding with the other winding short circuited. ● EXAMPLE ●A transformer with a 5.75% impedance and a 480 volt low voltage winding would require (0.0575 x 480 volt) or 27.6 volts to circulate rated current. ●IN SHORT Impedance is simply the opposition to the flow of current in the transformers windings. (Impedance has a resistive and an inductive component.) ● REGULATION The drop in secondary voltage that occurs as the load on the transformer is increased and is expressed as a percentage of rated voltage. ● EFFICIENCY The ratio of power absorbed by the transformer to the total power drawn from the supply line.
  • 6. Schneider Electric 6- Projects and Services – PEC – MV Transformers - 2010 “Rule of Thumb” Cost Comparison ●Mineral Oil 1.0 ●Hi Fire Point Seed Oil 1.2 ●VPI 1.25 – 1.75 ●VPE (Epoxy) 1.35 – 1.85 ●Cast Coil 1.55 – 2.0 ●Lower Temerature Rise 15 % to 40 % Add ●Copper 35% - 35% Add ●5 DB Noise Reduction (Dry) 10% ●Hinged Doors on Dry and Cast Enclosures A bargain ●I.R. Viewing Windows on Dry and Cast Encl. An Even Better Bargain ●Insulated Bus on VPI and Cast Encl. $2K – 5K, but a good idea just the same.
  • 7. Schneider Electric 7- Projects and Services – PEC – MV Transformers - 2010 H.V. BIL Comparison Dry Type Liquid/Cast Voltage Class Std Opt Std Opt 2.4 KV 20 KV 30 KV 45 KV 60 KV 5 KV 30 KV 45 KV 60 KV 75 KV 8.3 KV 45 KV 60 KV 75 KV 95 KV 15 KV 60 KV 95 KV 95 KV 110 KV 25 KV 110 KV 125 KV 125 KV 150 KV 35 KV 150 KV ----- 150 KV 200 KV 46 KV ----- ------ 250 KV ------
  • 8. Schneider Electric 8- Projects and Services – PEC – MV Transformers - 2010 Impedance ●IEEE Standard ● 5.75 Nominal for 750 kVA and Above ● Manufacturer’s standard within the IEEE Standard range for 500 kVA and below ● Large units and higher voltages have different standards ●Note ● IEEE allows a +/- 7.5% Tolerance ● Example for 5.75% Impedance Range would be 5.32% to 6.18%
  • 9. Schneider Electric 9- Projects and Services – PEC – MV Transformers - 2010 Insulation Classes TRANSFORMER INSULATION WINDING MAXIMUM HOTSPOT HOT SPOT TYPE CLASS RISE AMBIENT GRADIENT TEMPERATURE POWER-DRY 220 DEG. C 150 DEG. C + 40 DEG. C + 30 DEG. C = 220 DEG. C CAST COIL 185 DEG. C 115 DEG. C + 40 DEG. C + 30 DEG. C = 185 DEG. C LIQUID-FILLED 120 DEG. C 65 DEG. C + 40 DEG. C + 15 DEG. C = 120 DEG. C
  • 10. Schneider Electric 10- Projects and Services – PEC – MV Transformers - 2010 Temperature Rise Dry 150 Degree C Standard 115 Degree C Optional 80 Degree C Optional Cast 115 Degree C Standard 80 Degree C Option Liquid Filled 65 Degree C Standard 55/65 Degree C Optional
  • 11. Schneider Electric 11- Projects and Services – PEC – MV Transformers - 2010 Altitude ●STANDARD: Designed for operation at a maximum altitude of 3300 ft. (1000m) above sea level ●If a non standard condition exists (i.e.. Altitude above 3300 ft ASL then: ● Transformer must be de-rated or ● Transformer must be specifically designed for the special altitude consideration.
  • 12. Schneider Electric 12- Projects and Services – PEC – MV Transformers - 2010 OVERLOAD EXAMPLE 3000 kVA Dry Type Xfmr. AA + 33% (5400) Base kVA + 35% (4050) 80/150 AA + 33% (4600) Base kVA + 15%, (3450) 115/150 AA + 33% (4000) Base kVA (3000) 150 Fan Cool Rating (FA) kVA Rating (AA) Temp. Rise (Deg. C)
  • 13. Schneider Electric 13- Projects and Services – PEC – MV Transformers - 2010 NEMA Standard Sound Levels kVA LIQUID-FILLED VPI CAST 51-150 51 55 N/A 225-300 55 55 58 301-500 56 60 60 501-1000 58 64 64 1001-1500 60 65 65 1501-2000 61 66 66 2001-2500 62 68 68 2501-3000 63 68 68 3001-4000 64 70 70 4001-5000 66 71 71 7500 67 75 75 10,000 68 78 78 NOTE: ALL VALUES ARE IN DECIBELS (db) AND ARE FOR BASE kVA RATINGS (FAN PACKAGES WILL INCREASE db LEVELS)
  • 14. Schneider Electric 14- Projects and Services – PEC – MV Transformers - 2010 Energy Efficient (EE) MV Transformers ● The Department of Energy (DOE) has determined that energy conservation standards for MV Distribution Transformers will result in significant conservation of energy so they have passed DOE 10 CFR Part 431 Energy Conservation program for Commercial Equipment. ● Starting January 1, 2010 all medium voltage distribution transformers with ratings of 2500 kVA and below, 34.5 KV primary and below and 600V class secondary voltages must meet minimum efficiency requirements. ● Liquid Filled Padmounts, Liquid Filled Substations, Dry Type VPI and Power Cast products MANUFACTURED after January 1, 2010 are all included. ● EE Low Voltage transformers implemented in 2006, this law is extending efficiencies to Medium Voltage.
  • 15. Schneider Electric 15- Projects and Services – PEC – MV Transformers - 2010 DOE Energy Efficiency Applies to: ●Medium Voltage Liquid ● » 10-833 kVA 1 phase ● » 15-2500 kVA 3 phase ●2. Medium Voltage Dry ● » 15-833 kVA 1 phase ● » 15-2500 kVA 3 phase
  • 16. Schneider Electric 16- Projects and Services – PEC – MV Transformers - 2010 Minimum Efficiency Tables Liquid Filled Note: All efficiency values are at 50 percent of nameplate-rated load, determined according to the Appendix A, DOE Test procedure. 10 CFR Part 431, Subpart K Table I.1 Table I.1 - Standard levels for Liquid Immersed Distribution Transformers, tabular Form 10………………….. 15…………………… kVA Three Phase Efficiency % 98.62 Single Phase Efficiency % kVA 15………………….. 25………………….. 37.5………………… 50…………………… 75…………………… 100…………………. 167…………………. 250…………………. 333…………………. 500…………………. 667…………………. 833…………………. 98.76 98.97 99.01 99.08 99.17 99.23 99.25 99.32 99.36 99.42 99.46 99.49 30………………….. 45…………………… 75……………………. 112.5………………. 150………………….. 225…………………. 300………………….. 500………………….. 750………………….. 1000………………… 1500………………… 2000…………………. 98.36 98.62 98.76 98.91 99.01 99.08 99.17 99.23 99.25 99.32 99.36 99.42 99.46 2500………………… 99.49
  • 17. Schneider Electric 17- Projects and Services – PEC – MV Transformers - 2010 Applies to all Transformers Sold in: ●All 50 US States ●Unincorporated Territories (Possessions): American Samoa, Guam, Marshall Islands, Puerto Rico, US Virgin Islands ●Freely-associated states: Federal States of Micronesia, Northern Marianas, Palau
  • 18. Schneider Electric 18- Projects and Services – PEC – MV Transformers - 2010 Does not Apply for Transformers ●Exported to a country outside the US ●Armed Forces bases located outside the US unless specified or to a US territory ●US Embassies unless specified
  • 19. Schneider Electric 19- Projects and Services – PEC – MV Transformers - 2010 Transformers Affected: ●Have an input voltage of 34.5 kilovolts or less; ●Have an output voltage of 600 volts or less; and ●Are rated for operation at a frequency of 60 Hertz
  • 20. Schneider Electric 20- Projects and Services – PEC – MV Transformers - 2010 Excluded Transformers ●A transformer with multiple voltage taps, the highest of which equals at least 20 percent more than the lowest; ●A transformer that is designed to be used in a special purpose application and is unlikely to be used in general purpose applications, or ●Any transformer not listed in this definition that is excluded by the Secretary by rule
  • 21. Schneider Electric 21- Projects and Services – PEC – MV Transformers - 2010 Excluded Transformers ● Autotransformers ● Drive (isolation) transformers ● Grounding transformers ● Machine-tool (control) transformers ● Nonventilated transformers ● Rectifier transformers ● Regulating transformers ● Sealed transformers ● Special-impedance transformers ● Testing transformers ● Transformer with tap range of 20 percent or more ● Uninterruptible power supply transformers ● Welding transformers ● Step up Transformers
  • 22. Schneider Electric 22- Projects and Services – PEC – MV Transformers - 2010 Seismic
  • 23. Schneider Electric 23- Projects and Services – PEC – MV Transformers - 2010 Liquid Filled Transformers Padmount Unit Substation
  • 24. Schneider Electric 24- Projects and Services – PEC – MV Transformers - 2010 Liquid Filled Padmount ●Product Scope: ●75-5000kVA ● 55, 65, 55/65 Temp. Rise ● 2.4 - 34.5kV Class Primary 150kV BIL Max ● 600V - 5kV Class Secondary 75kV BIL Max. ● Self-Cooled Overload Only (12% with 55/65) ● ONAN only - NO ONAN/ONAF (no fans) ●No Fans means, NO FANS! ●Weather Resistant high and low voltage compartments ●Tamper-Resistant Design (Available up to 20,000 kVA via special quotation)
  • 25. Schneider Electric 25- Projects and Services – PEC – MV Transformers - 2010 Fluid Offerings MINERAL OIL Type II (Inhibited) Ergon Hyvolt II Mainly Outdoor (Fire Point = 165 Deg. C) Least Expensive of all Fluids BIOTEMP (ABB) Renewable Natural Agricultural Product Certified by UL® as “Less-Flammable Fluid” Fire Point = 360 Deg. C Factory Mutual Approved Biodegrades 97% in 21 days No fusing restrictions LESS FLAMMABLE SEED OIL FR3 FLUID ™ (Cooper Industries) Certified by UL® as “Less-Flammable Fluid” Fire Point = 360 Deg. C Factory Mutual Approved Biodegrades 99% in 21 days No fusing restrictions Extends insulation life LESS FLAMMABLE SEED OIL
  • 26. Schneider Electric 26- Projects and Services – PEC – MV Transformers - 2010 Liquid Filled Padmount HV Bushings Drain Valve Bay-o-net Fuses Tap Changer Pressure vacuum Gauge Upper Fill Plug Temperature Gauge Liquid Level GaugePressure Relief valve Name PlateLV Bushing HV Compartment LV Compartment
  • 27. Schneider Electric 27- Projects and Services – PEC – MV Transformers - 2010 Radial Feed vs Loop Feed A. Radial Feed 3 HV Bushings B. Loop Feed 6 HV Bushings A transformer with loop feed construction can be used on 2 types of systems: 1. Dual Source Radial Feed 2. Loop Feed System
  • 28. Schneider Electric 28- Projects and Services – PEC – MV Transformers - 2010 Live Front Construction ●Contains “exposed current carrying parts” in HV compartment (IEEE C57.12.34) ●Components: Porcelain Bushings ●Live Front bushings arranged in horizontal pattern, Radial and Loop Feed
  • 29. Schneider Electric 29- Projects and Services – PEC – MV Transformers - 2010 Liquid Filled Padmount Live Front Transformer Note: 5/8” eyebolt terminal-optional 2 or 4 hole pad is available by special quote
  • 30. Schneider Electric 30- Projects and Services – PEC – MV Transformers - 2010 Dead Front Construction “No exposed current carrying parts HV compartment” (IEEE C57.12.34) Components: Wells, Inserts, One Piece Bushings, Feed-thru inserts Available In: 15, 25,35kV Classes Available In: 200 Amp - Loadbreak 600 Amp - Non-Loadbreak Note: Can not interchange different classes of components. Radial Feed: Bushings in horizontal pattern. Loop Feed: “V” Type Configuration
  • 31. Schneider Electric 31- Projects and Services – PEC – MV Transformers - 2010 Liquid Filled Padmount Dead Front-Radial Feed Dead Front-Loop Feed
  • 32. Schneider Electric 32- Projects and Services – PEC – MV Transformers - 2010 Liquid Filled Padmount Dead Front Bushing Well
  • 33. Schneider Electric 33- Projects and Services – PEC – MV Transformers - 2010 Liquid Filled Padmount Bushing Insert
  • 34. Schneider Electric 34- Projects and Services – PEC – MV Transformers - 2010 Liquid Filled Padmount No Load Tap Changer
  • 35. Schneider Electric 35- Projects and Services – PEC – MV Transformers - 2010 Liquid Filled Padmount
  • 36. Schneider Electric 36- Projects and Services – PEC – MV Transformers - 2010 Switching All transformers (radial and loop feed construction) are not equipped with HV switches. Switching can be accomplished remotely. Padmount can be equipped with: 1. Two Position (ON-OFF) Switch (Can be used on radial and loop units.) 2. Three Position Switch Line A Only, Line B Only, Off (Dual source application.) 3. Four Position Switch - Permits Sectionalizing (Loop feed transformers only.)
  • 37. Schneider Electric 37- Projects and Services – PEC – MV Transformers - 2010 Arresters ●Arresters ● Silicone carbide or MOV (Metal-Oxide Varistor) most common. ●Operation ● MOV is a granular ceramic (semi-conductor) ● Conducts during a “High Amplitude Transient” and diverts excess voltage to ground ● Provides a transient path to a common point earth ground.
  • 38. Schneider Electric 38- Projects and Services – PEC – MV Transformers - 2010 Liquid Filled Padmount Bayonet Type Fuse
  • 39. Schneider Electric 39- Projects and Services – PEC – MV Transformers - 2010 Liquid Filled Padmount
  • 40. Schneider Electric 40- Projects and Services – PEC – MV Transformers - 2010 Liquid Filled Padmount
  • 41. Schneider Electric 41- Projects and Services – PEC – MV Transformers - 2010 Liquid Filled Padmount
  • 42. Schneider Electric 42- Projects and Services – PEC – MV Transformers - 2010 Liquid Filled Padmount
  • 43. Schneider Electric 43- Projects and Services – PEC – MV Transformers - 2010 Liquid Filled Unit Substation
  • 44. Schneider Electric 44- Projects and Services – PEC – MV Transformers - 2010 Liquid Filled Unit Substation ●225-10,000kVA ● 55, 65, 55/65 Temp. Rise ● 2.4 - 34.5kV Class Primary - 250 kV BIL Max. ● 600V - 8.7kV Class Secondary - 75kV BIL Max. ● ONAN/ONAF also known as AA/FA ●Available up to 20,000 kVA - 69 kV primary, 5 kV up to 34.5 kV secondary via special quotation with Square D Name Plate. ●Now available up to 60 MVA base rating, 161 KV primary, 34.5 Secondary with ABB Name Plate
  • 45. Schneider Electric 45- Projects and Services – PEC – MV Transformers - 2010 Liquid Filled Unit Substation ●Standard efficiency (Energy Efficient per DOE2010) ● K-Rated units ● UL Listing ● Factory Mutual ● Evaluated loss designs ● Oil, Silicone, and Less Flammable Seed Oil
  • 46. Schneider Electric 46- Projects and Services – PEC – MV Transformers - 2010 Fluid Offerings MINERAL OIL Type II (Inhibited) Ergon Hyvolt II • Mainly Outdoor (Fire Point = 165 Deg. C) • Least Expensive of all Fluids SILICONE (Dow Corning 561) • “Less Flammable Liquid” (Fire Point = 343 Deg. C) • Indoor Use • Expensive Fluid BIOTEMP (ABB) Renewable Natural Agricultural Product • Certified by UL® as “Less-Flammable Fluid” • Fire Point = 360 Deg. C • Factory Mutual Approved • Biodegrades 97% in 21 days • No fusing restrictions • LESS FLAMMABLE SEED OIL FR3 FLUID ™ (Cooper Industries) • Certified by UL® as “Less-Flammable Fluid” • Fire Point = 360 Deg. C • Factory Mutual Approved • Biodegrades 99% in 21 days • No fusing restrictions • LESS FLAMMABLE SEED OIL
  • 47. Schneider Electric 47- Projects and Services – PEC – MV Transformers - 2010 Unit Substation Transformers ●Close coupled to HV or LV switchgear ● Includes throats, flanges, etc. ● Coordination through Unit Substation Coordination Group ●Stand alone with full or partial height ATC’s ●Connection to HV Non-Seg Busway or LV I-Line Busway ● Includes standard 12” Throat ● Busway Plant will provide connection box to throat ● Coordination through MV Transformer Group ●Special retro-fit connections/dimensions available
  • 48. Schneider Electric 48- Projects and Services – PEC – MV Transformers - 2010 Liquid Filled Unit Substation Cooling Options ●(ONAN) Self-Cooled (Oil Natural Air Natural) (55/65 Deg. C Self-Cooled = 12% Overload) ●(ONAN / FONFA) * Self-Cooled With Provisions For Future Addition Of Fans ●(ONAN / ONFA) * Self-Cooled With Fans To Provide Additional Capacity ● *NOTE: Controlled By: Top Of Oil or Winding Temperature Indicator (Winding Temp Ind. is expensive option)
  • 49. Schneider Electric 49- Projects and Services – PEC – MV Transformers - 2010 Liquid Filled Transformers Fans Increase Capacity As Follows: < 2000 kVA Increase 15% 2500 Through 10000 kVA Increase 25%
  • 50. Schneider Electric 50- Projects and Services – PEC – MV Transformers - 2010 Arrester Classes 1. Distribution Class Heavy Duty Type 2. Intermediate Class Higher Energy Handling Capability 3. Station Class Provide Greatest Degree Of Protection, Highest Level Of Energy Handling, Max Capability = 80kA Note: Intermediate or Station Class Arresters require larger ATC’s
  • 51. Schneider Electric 51- Projects and Services – PEC – MV Transformers - 2010 Liquid Filled Unit Substation
  • 52. Schneider Electric 52- Projects and Services – PEC – MV Transformers - 2010 Unit Substation Transformers
  • 53. Schneider Electric 53- Projects and Services – PEC – MV Transformers - 2010 End of Section
  • 54. Schneider Electric 54- Projects and Services – PEC – MV Transformers - 2010 Dry Transformers
  • 55. Schneider Electric 55- Projects and Services – PEC – MV Transformers - 2010 Dry Transformers Advantages ●Excellent for Indoor Use ● Schools, Hospitals, Office Buildings ● Locations where a liquid spill can not be tolerated ● No containment pit required, providing for lower installation and maintenance costs ●Non-Flammable ● 220C Insulation Class ● Will not support combustion ●Approximately the same Price of a Seed Oil Unit ● Most economical when compared to UniCast II or PowerCast II
  • 56. Schneider Electric 56- Projects and Services – PEC – MV Transformers - 2010 Dry Transformers Disadvantages ● Lower BIL Levels than Liquid Filled ● Standard for 15kV Class is 60kV BIL, Liquid Filled is 95kV BIL ● Standard for 600V Class is 10kV BIL, Liquid Filled is 30kV BIL ● Moisture Absorption ● Must pre-dry unit before energizing to eliminate moisture from coils ● More Susceptible to Airborne Contaminants ● Ventilated enclosure, contaminants may accumulate on coils
  • 57. Schneider Electric 57- Projects and Services – PEC – MV Transformers - 2010 Picture of VPI Process
  • 58. Schneider Electric 58- Projects and Services – PEC – MV Transformers - 2010 Dry Transformer COOLING OPTIONS ●(AA) Self Cooled ●(AA/FFA)* Self Cooled with provisions for future forced air ●(AA/FA)* Self cooled with forced air * Capacity will be increased by 33 1/3% with the addition of fans For example: ● 1000kVA @ 150C = 1000/1333kVA ● 1000kVA @ 115/150C = 1000/1150/1533kVA ● 1000kVA @ 80/150C = 1000/1300/1733kVA
  • 59. Schneider Electric 59- Projects and Services – PEC – MV Transformers - 2010 Unit Substation Transformers Selectable Product Scope 225 - 5000 kVA 150, 115, and 80 Degree C Rise 2.4 - 34.5 kV Class Primary 150kV Primary BIL 600V - 5kV Class Secondary (Available up to 13,000 kVA via special quotation)
  • 60. Schneider Electric 60- Projects and Services – PEC – MV Transformers - 2010 Cast Coil Transformers Power Cast II and UniCast II
  • 61. Schneider Electric 61- Projects and Services – PEC – MV Transformers - 2010 Cast Resin Transformers (The Need) ●Replacement for Askarel (Non-Flammable) ●Environmentally Safe (By Products of Combustion) ●BIL Equivalent to Liquid Filled ●Primary Voltages Higher than Dry Type ●Mechanical Short Circuit Strength (Superior)
  • 62. Schneider Electric 62- Projects and Services – PEC – MV Transformers - 2010 Cast Coil Transformers (The Coil) HV/LV Coil
  • 63. Schneider Electric 63- Projects and Services – PEC – MV Transformers - 2010 Cast Coil Transformers LV Coil w/Cooling Ducts
  • 64. Schneider Electric 64- Projects and Services – PEC – MV Transformers - 2010 Cast Coil Transformers Core/Coil Assembly
  • 65. Schneider Electric 65- Projects and Services – PEC – MV Transformers - 2010 Benefits Cast Coil vs. Liquid ●No Fluids to Leak, Contaminate, or Burn ●Far Less Maintenance, No Yearly Fluid Testing ●No Decommissioning Costs ●Higher Short Circuit Strength ●Non - Flammable ●Longer Design Life when compared to Mineral Oil ●Greater Fan Overload Capability ●Lower Installation Costs
  • 66. Schneider Electric 66- Projects and Services – PEC – MV Transformers - 2010 Benefits of Cast Coil vs. Conventional “VPI” ●Resistant to Moisture and Contaminants ●Higher Standard BIL Levels ●Lower Operating Costs Lower Standard Temperature Rise - 80 vs 150 More Efficient Less Maintenance ●Longer Design Life ●More Reliable ●Greater Design Flexibility Higher kVA Ratings Higher Primary and Secondary Voltages
  • 67. Schneider Electric 67- Projects and Services – PEC – MV Transformers - 2010 IMPEDANCE ● DEFINITION The percentage of rated voltage required to circulate rated current in one winding with the other winding short circuited. ● EXAMPLE A transformer with a 5.75% impedance and a 480 volt low voltage winding would require (0.0575 x 480 volt) or 27.6 volts to circulate rated current. ● IN SHORT Impedance is simply the opposition to the flow of current in the transformers windings. (Impedance has a resistive and an inductive component.)
  • 68. Schneider Electric 68- Projects and Services – PEC – MV Transformers - 2010 IMPEDANCE ● High or Low Impedance does not necessarily mean Low or High Efficiency. ● Impedance consists of two components: 1) A Resistive Component 2) A Reactive Component %IZ = ( % IR ) 2 + ( % IX ) 2
  • 69. Schneider Electric 69- Projects and Services – PEC – MV Transformers - 2010 Efficiency Definition: The ratio of power absorbed by the transformer to the total power drawn from the supply line. Efficiency can be calculated using the following formula: EFF = [1 - (Y + (L)2 (X))/(100L + Y + (L)2 x)] 100 Where X = % IR @ 100% Load Cosine 0 Cosine 0 = Power Factor Cosine 0 = Power Factor % IR = Load Loss (KW) x 100 % FE = No Load Loss (KW) x 100 Rated kVA Rated kVA Y = % FE @ 100% Load L = Load Factor = % Load Cosine 0 (Per Unit Load) 100
  • 70. Schneider Electric 70- Projects and Services – PEC – MV Transformers - 2010 Example: What is the efficiency at 100% load and 1.0 power factor of the 75kVA transformer with: No-Load Loss: 341 Watts Load Loss: 1478 Watts Impedance: 3.45 % % IR = (1.478/75) x 100 = 1.97 PF = 1.0 X = % IR = 1.97 = 1.97 PF 1 % FE = .0341 x 100 = 0.454 75kVA Y = % FE = 0.454 = 0.454 PF 1 L = % Load = 100 = 1 100 100
  • 71. Schneider Electric 71- Projects and Services – PEC – MV Transformers - 2010 Heat Dissipation Some consultants think that a transformer with a lower temperature rise is better for vault and indoor applications. This is not correct. Transformers have losses. Each watt of total loss = 3.413 BTU/Hr Multiply the total loss by this value to determine the heat which must be dissipated by air conditioning, ventilation, etc.
  • 72. Schneider Electric 72- Projects and Services – PEC – MV Transformers - 2010 Tests ● WINDING RESISTANCE ● PURPOSE: The fundamental purpose of this test is to supply resistance data which will be used to calculate I2R conductor losses and winding temperatures. It also enables a check of coil continuity and hence, is often used in the field as an indicator of possible damage to any internal coil connections. ● RATIO, POLARITY, AND PHASE RELATION ● PURPOSE: To verify that the transformer has the correct number of turns in each winding (ratio and that the polarity and phase relationship of the windings are correct. ● INSULATION POWER FACTOR ● PURPOSE: To verify that the transformer has been properly dried and that its moisture content is not excessive. Insulation power factor is defined as the ratio of power dissipated in the transformer insulation (in watts) to the product of the effective voltage and current (in volt-amperes) while being tested with a sine-wave voltage.
  • 73. Schneider Electric 73- Projects and Services – PEC – MV Transformers - 2010 Tests ●EXCITATION LOSS ● PURPOSE: To verify that excitation losses, which consist primarily of winding losses due to exciting current and losses in the transformer’s core, meet guaranteed values promised to the customer. ●EXCITATION CURRENT ● PURPOSE: To verify core construction quality ●LOAD LOSS ● PURPOSE: To verify that the load losses meet the guarantees given to a customer. ●IMPEDANCE ● PURPOSE: To verify guarantees given to the customer.
  • 74. Schneider Electric 74- Projects and Services – PEC – MV Transformers - 2010 Dielectric Tests ● APPLIED POTENTIAL TEST ● PURPOSE: To verify that the dielectric strength of the insulation from winding to ground and winding to winding is adequate. ● PROCEDURE: A voltage level defined by IEEE is applied to the winding under test for a period of 60 seconds. (34KV for 15 KV, 95KV BIL Units) ● INDUCED POTENTIAL TEST ● PURPOSE: To verify the insulation between turns and layers of the same winding, and phase to phase clearance is sufficient. ● PROCEDURE: A special high frequency generator is used to prevent the core from saturating due to the high voltage that is induced in the winding. (120, 180, 240 or 400 Hz are commonly used). A voltage up to two times the rating of the winding is applied for a period of 7200 cycles.
  • 75. Schneider Electric 75- Projects and Services – PEC – MV Transformers - 2010 Impulse Test ● PURPOSE ● To verify that the transformer insulation (BIL) can withstand the transient over voltages. ● TYPES OF IMPULSE TESTS ● Half Wave ● Full Wave ● Chopped Wave: A more severe test as it simulates a transient that is chopped to ground by an arrester QC impulse is done on all of our products. This impulse test includes full and half wave. The Chopped Wave is included when ANSI Impulse Test is included in the specification.
  • 76. Schneider Electric 76- Projects and Services – PEC – MV Transformers - 2010 Design Tests ●TEMPERATURE RISE TEST ● PURPOSE: To verify that the top oil and winding temperature rise does not exceed the guaranteed levels under full load operation. ●SOUND LEVEL TEST ● PURPOSE: To verify that the sound level produced by the transformer is within guaranteed values. The principle noise associated with transformers, aside from that produced by any cooling fans, is an audible hum due to a phenomenon called Magnetostriction. When core steel is excited by a magnetic field it contracts slightly. This dimensional change which occurs 120 times per second for a 60 cycle system (once every half cycle) is defined as Magnetostriction.