1. SINGLE LINE DIAGRAM
LEGEND:
CIRCUIT CONNECTION
SWITCH CONNECTION
FROM POWER SOURCE
M
M
2-600 MCM AWG
METER
CONVENIENCE OUTLET
SPECIAL PURPOSE OUTLET
S#
450 AT
SWITCH
COMPACT FLUORESCENT LAMP
2-80 MM2
TW - COPPER WIRE
2-80 MM2
TW - COPPER WIRE
#
2-80 MM2
TW - COPPER WIRE
CIRCUIT BREAKER
SERVICE ENTRANCE
M
KILOWATT HOUR METER
M
KILOWATT HOUR METER
M
KILOWATT HOUR METER
MAIN DISTRIBUTION PANEL
GENERAL NOTES:
SCHEDULE OF LOADS
TYPE OF SERVICE ; 230 V , 2-WIRE , 60 HZ , S INGLE PHASE
CKT.
NO.
1
30AT
175 AT
30AT
2
1
30AT
30AT
2
22
LOAD DESCRIPTION
QTY.
WATTS
AMP.
CKT.
BRANCH PROTECTION
SIZE OF COPPER WIRE
CONVENIENCE OUTLET
10
3600
15.65
30A CIRCUIT BREAKER
2 - 3.50 MM2 TW WIRE
13 MM
ELECTRIC CONDUIT
CONVENIENCE OUTLET
6
3240
14.09
30A CIRCUIT BREAKER
2 - 3.50 MM2 TW WIRE
13 MM
ELECTRIC CONDUIT
3
70 AT
1
2
175 AT
CONVENIENCE OUTLET
7
2520
10.96
30A CIRCUIT BREAKER
2 - 3.50 MM2 TW WIRE
13 MM
ELECTRIC CONDUIT
SIZE OF CONDUIT
30AT
30AT
4
3
30AT
30AT
4
4
CONVENIENCE OUTLET
10
3600
15.65
30A CIRCUIT BREAKER
2 - 3.50 MM2 TW WIRE
13 MM
ELECTRIC CONDUIT
5
CONVENIENCE OUTLET
10
3600
15.65
30A CIRCUIT BREAKER
2 - 3.50 MM2 TW WIRE
13 MM
ELECTRIC CONDUIT
6
3
LAUNDRY UNIT
1
1500
5.22
30A CIRCUIT BREAKER
2 - 3.50 MM2 TW WIRE
13 MM
30AT
6
5
30AT
30AT
6
ELECTRIC CONDUIT
7
60AT
60AT
8
7
60AT
60AT
8
9
70AT
70AT
10
9
70AT
70AT
10
7
AIRCON UNIT
1
1865
8.11
60A CIRCUIT BREAKER
20 MM
ELECTRIC CONDUIT
AIRCON UNIT
1
1865
8.11
60A CIRCUIT BREAKER
2 - 5.50 MM2 TW WIRE
20 MM
ELECTRIC CONDUIT
9
AIRCON UNIT
1
2238
9.73
70A CIRCUIT BREAKER
2 - 8.00 MM2 TW WIRE
30 MM
ELECTRIC CONDUIT
10
30AT
2 - 5.50 MM2 TW WIRE
8
5
AIRCON UNIT
1
2238
9.73
70A CIRCUIT BREAKER
2 - 8.00 MM2 TW WIRE
30 MM
ELECTRIC CONDUIT
11
AIRCON UNIT
1
2238
9.73
70A CIRCUIT BREAKER
2 - 8.00 MM2 TW WIRE
30 MM
ELECTRIC CONDUIT
AIRCON UNIT
1
70A CIRCUIT BREAKER
2 - 8.00 MM2 TW WIRE
12
15
15AT
15AT
17
15AT
15AT
19
15AT
15AT
14
11
13
70AT
70AT
15AT
30AT
16
15
15AT
15AT
18
17
15AT
15AT
20
19
15AT
15AT
12
14
16
18
20
2238
9.73
1
5100
17.74
30A CIRCUIT BREAKER
2 - 5.50 MM2 TW WIRE
20 MM
1100
4.78
15A CIRCUIT BREAKER
2 - 2.00 MM2 TW WIRE
13 MM
15
LIGHTING OUTLET
8
800
3.48
15A CIRCUIT BREAKER
2 - 2.00 MM2 TW WIRE
13 MM
ELECTRIC CONDUIT
LIGHTING OUTLET
8
800
3.48
15A CIRCUIT BREAKER
2 - 2.00 MM2 TW WIRE
13 MM
ELECTRIC CONDUIT
17
LIGHTING OUTLET
9
900
3.91
15A CIRCUIT BREAKER
2 - 2.00 MM2 TW `
WIRE
13 MM
ELECTRIC CONDUIT
LIGHTING OUTLET
10
1000
4.35
15A CIRCUIT BREAKER
2 - 2.00 MM2 TW WIRE
13 MM
ELECTRIC CONDUIT
19
LIGHTING OUTLET
11
1100
4.78
15A CIRCUIT BREAKER
2 - 2.00 MM2 TW WIRE
13 MM
ELECTRIC CONDUIT
LIGHTING OUTLET
8
800
3.48
15A CIRCUIT BREAKER
2 - 2.00 MM2 TW WIRE
13 MM
ELECTRIC CONDUIT
21
LIGHTING OUTLET
11
1100
4.78
15A CIRCUIT BREAKER
2 - 2.00 MM2 TW WIRE
13 MM
ELECTRIC CONDUIT
SPARE
-
-
-
-
-
21
15AT
SPARE
21
15AT
3 HP MOTOR
1
2238
9.73
70A CIRCUIT BREAKER
2 - 8.00 MM2 TW WIRE
3. WIRING METHOD SHALL BE AS FOLLOWS:
A. FEEDERS AND RISERS - INTERMEDIATE
METALLIC CONDUIT
B. LIGHTING, POWER RECEPTACLE - POLYVINYL
CHLORIDE CONDUIT
ELECTRIC CONDUIT
-
30 MM
2. THE ELECTRICAL SERVICE POWER IS SINGLE PHASE,
2 - WIRE, 220 V AC, 60 HZ.
ELECTRIC CONDUIT
11
20
15AT
12
COOKING UNIT
18
30AT
70AT
LIGHTING OUTLET
16
13
70AT
13
14
11
1. ALL ELECTRICAL WORKS SHALL COMPLY IN
ACCORDANCE WITH THESE PLANS AND
SPECIFICATIONS.
THE APPLICABLE PROVISIONS OF THE LATEST EDITION
OF THE PHILIPPINE ELECTRICAL CODE ( PEC ).
THE RULES AND REGULATION OF THE LOCAL
ENFORCING AUTHORITY AND THE REQUIREMENTS OF
THE LOCAL POWER COMPANY. THE ELECTRICAL WORKS
SHALL BE DONE UNDER THE IMMEDIATE SUPERVISION
OF A DUTY REGISTERED ELECTRICAL ENGINEER.
ELECTRIC CONDUIT
4. ALL WIRES SHOULD BE COPPER AND
THERMOPLASTIC INSULATED TYPE " TW " UNLESS
OTHERWISE INDICATED ON THE PLAN THE MINIMUM
SIZE OF THE WIRE FOR LIGHTING CIRCUIT HOMERUN
SHALL BE 2.0 sq. mm AND FOR POWER CIRCUIT
HOMERUN SHALL BE 3.5 sq. mm INSULATED FOR 600
VOLTS.
SMALLEST RACEWAYS SHALL BE 13 mm DIAMETER
TRADE/NOMINAL SIZE.
5. ALL MATERIALS TO BE USED BE BRAND NEW AND
APPROVED TYPE FOR PARTICULAR LOCATION AND
PURPOSE OF USAGE.
-
SPARE
22
30 MM
ELECTRIC CONDUIT
6. GROUNDING SYSTEM SHALL BE PROVIDED TO ALL
LIGHTING AND POWER CIRCUIT AS PER PHILIPPINE
ELECTRICAL CODE REQUIREMENT.
7. MOUNTING HEIGHT OF WIRING DEVICES SHALL BE
AS FOLLOWS:
DRAFTED AND CADD BY:
PROJECT TITLE:
APPROVED BY:
SHEET CONTENT:
PROPOSED CONSTRUCTION OF
ANGELIE M. MOROSCALLO BSEE-V
MARK ANTHONY B. ENOY BSEE-V
TWO-STOREY TWO-DOOR APARTMENT BUILDING
ENGR. URSINO P. TABILIRAN
ELECTRICAL LAYOUT