SlideShare a Scribd company logo
1 of 168
Capacitors
Dominik Pieniazek, P.E. – VI Engineering, LLC
Nicholas A. Losito Jr. – Castle Power Solutions, LLC
Outline
Day 1Day 1
• Basic Power Calculations
• Capacitor Fundamentals
• Capacitor Ratings
• Capacitor Application
• Capacitor Protectionp
Day 2
• Harmonics
• Capacitor Bank Design Considerations• Capacitor Bank Design Considerations
Shunt Capacitors
• Medium Voltage
• Substation Applicationspp
• Power Factor Correction
Basic Power Calculations
Basic Power Calculations
C Q tiCommon Questions:
What are VARs?
Wh d b t VAR ?Why do we care about VARs?
Basic Power Calculations
Most plant loads (motors, transformers, etc) are INDUCTIVE
and require a magnetic field to operate. The magnetic field is
necessary, but produces NO USEFUL WORK. The utility
must supply the power to produce the magnetic field and themust supply the power to produce the magnetic field and the
power to produce USEFUL work.
The ACTIVE component produces the USEFUL work, the
REACTIVE component produces the magnetic field.
Basic Power Calculations
An analogy that
VAR
gy
most can understand.
Mug
i f i
VA
Capacity of equipment
(i.e. xfmr, cable, swgr, etc)
Beer
W
ee
Stuff that you want
Foam (Head)
St ff hi h tStuff which prevents
you from maximizing the
amount of beer that you get
Basic Power Calculations
f lV: Reference voltage
IR: Resistive load
IL: Inductive load
I : Capacitive loadIC: Capacitive load
Basic Power Calculations
Vref
Ires
Power = Re(V I*)
Basic Power Calculations
Vref
Ilag
Note that due to phase shift (30 degrees) only 86.66% of current is applied to calculate work.
Power = Re(V I*)
Basic Power Calculations
Vref
Ilead
Regardless whether leading or lagging, power calculation yields similar results
Power = Re(V I*)
Basic Power Calculations
Vref
I90
In the case where current leads or lags the voltage by 90 degrees, P = 0
Power = Re(V I*)
Basic Power Calculations
Power Factor [ PF ] = Cos = P / S
S (kVA)
Q (kVAR)
P (W)
Power Triangle
The relationship between S, P, and Q. This figure represents a lagging power
factor. If Q is negative, leading power factor.
g
Basic Power Calculations
So how do we know if our
current is lagging or leadingcurrent is lagging or leading
the voltage, and what can we
do to correct it?do to correct it?
Consider this exampleConsider this example,
Basic Power Calculations
Incoming service is at
5500 kW
3400 kVAR
g
99.5% capacity
6466 kVA
2000 kW 1000 kW 2500 kW
1000 kVAR 800 kVAR 1600 kVAR
Basic Power Calculations
Power Factor [ PF ] = Cos = P / S0.85 lag
S (kVA)
g
Q (kVAR)3400 kVAR
31.8 deg
P (W)
Power Triangle
5500 kW
g
Even though our facility require only 5500 kW to perform Real Work, our
incoming service must be sized for 6466 kVA.
Basic Power Calculations
We have a 6500 kVA mug
that is holding 5500 kW
and 3400 kVAR.
VAR
VA
W
With the existing configuration
the facility cannot add any loadsy y
without upgrading the incoming
service.
Basic Power Calculations
Incoming service is at
5500 kW
0 kVAR
g
85% capacity
5500 kVA
3400 kVAR
2000 kW 1000 kW 2500 kW
1000 kVAR 800 kVAR 1600 kVAR
Basic Power Calculations
Power Factor [ PF ] = Cos = P / S1.0 unity
S (kVA)
y
Q (kVAR)0 kVAR
0 deg
P (W)
Power Triangle
5500 kW
g
The cap bank is providing 3400 kVAR, so our service is now providing only
5500 kVA (reduction from 6466 kVA.
Basic Power Calculations
1,500 kVA
COS [ ] = 0.67
COS [ ] = 0.95
Q2 = Q1 + Qc Q1 = 1,118 kVAR
1 000 kW
1,053 kVA
Q2 = 330 kVAR 1,000 kWQ
Qc = 788 kVAR
Required Apparent Power
Before and After
Adding a Power Capacitor Bank
An example of how to calculate the size of a cap bank based on a target power factor
Basic Power Calculations
But wait, there’s more….
Basic Power Calculations
Odds are that the utility is
5500 kW
3400 kVAR
y
charging you for penalties
for a low power factor.
6466 kVA
5500
6466
= 0.85
Typically, penalties are
applied for power factor lessapplied for power factor less
than 0.95%.
2000 kW 1000 kW 2500 kW
1000 kVAR 800 kVAR 1600 kVAR
Basic Power Calculations
There are also voltage
5500 kW
3400 kVAR
g
considerations.
Assuming typical values:
6466 kVA
Assuming typical values:
Source impedance =
9% at 6500 kVAVolt Drop = 5.8%
The expected voltage drop at
the main bus will be close to
6%!
2000 kW 1000 kW 2500 kW
1000 kVAR 800 kVAR 1600 kVAR
Basic Power Calculations
Capacitor bank reduces the
voltage drop at main bus
5500 kW
0 kVAR
voltage drop at main bus
by 5%!
5500 kVA
Volt Drop = 1.0%
3400 kVAR
2000 kW 1000 kW 2500 kW
1000 kVAR 800 kVAR 1600 kVAR
Basic Power Calculations
Note that the capacitor bank
can also raise the bus voltage
5500 kW
-1600 kVAR
g
above the nominal value.
5728 kVA
Volt Drop = -1.5%
5000 kVAR
2000 kW 1000 kW 2500 kW
1000 kVAR 800 kVAR 1600 kVAR
Basic Power Calculations
The voltage continues to rise
if the capacitor bank remains
3000 kW
-3200 kVAR
p
connected and the load is
reduced.
4386 kVA
Volt Drop = -3.6%
5000 kVAR
Out of service
2000 kW 1000 kW 0 kW
1000 kVAR 800 kVAR 0 kVAR
Capacitor Fundamentals
Capacitor Fundamentals
C = eo A / d for a parallel plate capacitor,
where eo is the permittivity of the insulating material (dielectric)o
between plates.
Capacitor Fundamentals
We recall that we can add series capacitances to
1 / C = 1 / C1 + 1 / C2
We recall that we can add series capacitances to
obtain an equivalent capacitance.
1 / Ceq 1 / C1 + 1 / C2
Capacitor Fundamentals
Similarly, we can add parallel capacitances to
obtain an equivalent capacitance.
Ceq = C1 + C2
Capacitor Fundamentals
…but we typically do not have much use for capacitance values.
So we convert capacitance to impedance:So we convert capacitance to impedance:
fCC
XC
2
11

fCC
C
 2
Capacitor Fundamentals
cjXRZ 
cjXRZ 
CXZ 
V
Z
2

X
V
S
2

S CX
Capacitor Fundamentals
1000*
][
][
2

kVV
kVARS 000
][
][
Z
kVS
Example:Example:
The capacitance of a capacitor is 6.22 F and the
nameplate voltage is 8000 V. Calculate the power rating.
][7.426
)1022.6)(60)(14.3(2
1
6
 
x
XC
][150000,1
7.426
)8( 2
kVARS 
Capacitor Fundamentals
Capacitor Fundamentals
Capacitor Fundamentals
Capacitor Fundamentals
Capacitor Fundamentals
Capacitor Fundamentals
Note that IEEE Std 18
requires the discharge
Discharge resistor
requires the discharge
resistor to reduce the
terminal voltage to 50 V in
th ti f ifi dthe time frame as specified
in the table below.
Capacitor Ratings
Capacitor Ratings
Medium voltage capacitors are available in many different stylesMedium-voltage capacitors are available in many different styles.
The main points of differentiation are listed below:
• Voltage rating
• kVAR rating
• Single bushing or dual bushingg g g
• Internally fused, externally fused, or fuseless
Capacitor Ratings
IEEE 81 defines the ratings for capacitorsIEEE 81 defines the ratings for capacitors
• Voltage, rms (terminal to terminal)
• Terminal-to-case (or ground) insulation class
• Reactive power
• Number of phasesp
• Frequency
Capacitor Ratings
IEEE 18 provides capacitor tolerancesIEEE 18 provides capacitor tolerances
• The capacitance shall not vary more than -0% to +10% of
nominal value based on rated kVAR, voltage, and frequency
measured at 25 deg C.
This means that a new 150 kVAR unit can range anywhere fromg y
150 kVAR to 165 kVAR.
Capacitor Ratings
IEEE 18 states the capacitor is intended to operate at or belowIEEE 18 states the capacitor is intended to operate at or below
rated voltage. Capacitors shall be capable of continuous
operation given that none of the following limitations are
exceeded:
• 110% of rated rms voltage (temporary overvoltage parameters
will be discussed later))
• 120% of peak voltage, including harmonics but excluding
transients
• 135% of nominal rms current based on rated kVAR and rated• 135% of nominal rms current based on rated kVAR and rated
voltage
• 135% of rated kVAR
Capacitor Ratings
* Impulse tests shall be applied between terminals and case, with the terminals connected together. For capacitors
having bushings with two different BIL ratings, this test shall be based on the bushing with the lower
BIL. The nameplate shall show both BIL ratings, e.g. 150/95 kV BIL.
** Not applicable to indoor ratings
Capacitor Application
Capacitor Application
Power factor correction capacitor banks are typically installed inPower factor correction capacitor banks are typically installed in
the following ways :
• Pole top
• Metal-Enclosed / Pad-Mount
• Open rackOpe ac
• Terminal end at equipment
Capacitor Application
P l T I t ll tiPole Top Installation
Capacitor Application
Transient inrush reactors
P l T I t ll tiPole Top Installation
Capacitor Application
Pad Mounted InstallationPad-Mounted Installation
Capacitor Application
Metal-Enclosed Substation InstallationMetal Enclosed Substation Installation
Capacitor Application
Three-phase iron core
harmonic filter reactor
Metal-Enclosed Substation Installation
harmonic filter reactor
Metal Enclosed Substation Installation
Capacitor Application
Open Rack, Medium-Voltage Substation Installation
Capacitor Application
Open Rack, High-Voltage Substation Installation
Capacitor Application
Installation in Equipment
Capacitor Application
Power factor correction capacitor banks can be configured in thePower factor correction capacitor banks can be configured in the
following ways :
• Delta
• Wye - Solidly Grounded
• Wye - Ungroundedy g
A common misconception is that the capacitor bank should be
connected Delta since it is being applied to a delta or highconnected Delta since it is being applied to a delta or high-
impedance grounded system. This is NOT true.
Capacitor Application
The driving factor which determine the configuration for the
given application is COST.
Voltage considerationsVoltage considerations
IEEE 1036 suggests that only banks rated 2400 V and below
should be Delta connected This is mainly because standardshould be Delta connected. This is mainly because standard
voltage ratings for wye connected banks may not be available.
Cost of phase-to-phase vs phase-to-neutral rated capacitors at
higher voltages tends to point installations towards wye
connected banks for larger bank installations.connected banks for larger bank installations.
Capacitor Application
Delta
Lower voltages (<= 2400 V)
• Standard capacitors are typically not available at 1380 V
Distribution systems (pole top)
• Units are configured with a single series group of capacitors
with capacitors rated phase to phase Therefore unbalancewith capacitors rated phase-to-phase. Therefore, unbalance
detection is not required.
Capacitor Application
Wye – Solidly Grounded
• Initial cost of the bank may be lower since the neutral does not
have to be insulated from groundhave to be insulated from ground.
• Capacitor switch recovery voltages are reduced
• High inrush currents may occur in the station ground system
Th d d id l i d f l• The grounded-wye arrangement provides a low-impedance fault
path which may require revision to the existing system ground
protection scheme. Typically not applied to ungrounded systems.p yp y pp g y
• When applied to resistance-grounded systems, difficulty in
coordination between capacitor fuses and upstream ground
protection relays (consider coordination of 40 A fuse with a 400 Aprotection relays (consider coordination of 40 A fuse with a 400 A
grounded system).
• Typical for smaller installations (since auxiliary equipment is not
i d)required)
Capacitor Application
The most common capacitor bank configurations for
larger substation applications are Wye-Ungrounded
Three of the most common unbalance protection schemes are shown.
Discussion of the protection schemes will be presented later.
Capacitor Protection
Fusing
• Fuseless
I t ll F d• Internally Fused
• Externally Fused
Capacitor Protection
B k P t ti SBank Protection Summary
Capacitor Protection
Fuseless Capacitors
Constr cted of small capacitor elements hich are arranged inConstructed of small capacitor elements which are arranged in
series and parallel. The elements are constructed of aluminum
foil with a dielectric of electrical grade polypropylene. This
design provides a safe failure mode. In the event that the
dielectric fails, the energy in the resulting small arc punctures
many layers of the thin film and foil within the element. Themany layers of the thin film and foil within the element. The
arc causes the film layer to receded allowing many layers of the
aluminum foil electrodes to touch and weld together forming an
electrically stable electrical joint This results in an entireelectrically stable electrical joint. This results in an entire
series section being shorted.
Capacitor Protection
Example of Fuseless Installation
Capacitor Protection
Internally Fused Capacitors
Constr cted s ch that each elementConstructed such that each element
is protected with a series
connected current limiting fuse.
The design is such that isolated
fusing prevents potential damage
to the adjacent elements andto the adjacent elements and
fuses. The current limiting mode
chops the fault current to prevent
the energy stored in the parallelthe energy stored in the parallel
connected elements from being
discharged into the faulted
element.
Capacitor Protection
Group Fusing
Individual Fusingd v du us g
Capacitor Protection
Group Fusing– Considerations for Selecting Fuse
(typical for distribution pole mounted racks)
• Continuous Current• Continuous Current
• Transient Current
• Fault Current
k C C di i• Tank Rupture Curve Coordination
• Voltage on Good Capacitors
Capacitor Protection
Continuous Current
• For wye-solidly grounded systems: Fuse > = 135% of rated
capacitor current (includes overvoltage, capacitor tolerances,
and harmonics).
• For wye-ungrounded systems: Fuse > = 125% of ratedy g y
capacitor current (includes overvoltage, capacitor tolerances,
and harmonics).
Care should be taken when using NEMA Type T and K tin links which are rated
150%. In this case, the divide the fuse rating by 1.50.g y
Capacitor Protection
Transient Current
• Capacitor switching (specifically back-to-back switching)
• Lightning surges
Back-to-back is typically not a factor for pole mounted capacitorsyp y p p
banks.
High frequency lightning surges:High frequency lightning surges:
Use NEMA T tin links for ampere ratings up to 25 A.
Use NEMA K tin links for ampere ratings above 25 A.
Capacitor Protection
Fault Current
Ensure that the fuse can interrupt the available fault current
Tank Rupture Coordination
Ensure that the fuse maximum clearing TCC curve for the fuseg
link is plotted below the capacitor tank rupture curve. In cases of
high fault currents, the tank rupture curve should be compensated
for asymmetryfor asymmetry.
Voltage on Good Capacitors
d d f l h l iFor an ungrounded system, a fault on one phase results in a 1.73
times overvoltage on the un-faulted phases. Ensure that the fault
is cleared before the second capacitor failure.p
Capacitor Protection
Problems with Fusing of Small Ungrounded Banks
Consider a 12.47 kV, 1500 kVAR cap bank made of three (3)
500 kVAR i l h i500 kVAR single-phase units.
FuseAAA
kV
kVAR
][100][1045.144.69][44.69
][47.123
][1500

 kV ][47.123
If a capacitor fails, we will expect approximately 3x line current.
It will take a 100 A fuse approximately 500 seconds to clear thispp y
fault (3 x 69.44 A = 208.32 A). The capacitor case will rupture
long before the fuse clears the fault.
The solution is using smaller units (explanation to follow).
Capacitor Protection
Individual Fusing– Considerations for Selecting Fuse
(typical for substation capacitor banks)
• Continuous Current• Continuous Current
• Transient Current
• Fault Current
• Tank Rupture Curve Coordination
• Voltage on Good Capacitors
• Energy Discharge into Faulted UnitEnergy Discharge into Faulted Unit
• Outrush Current
• Coordination with Unbalance Detection System
Capacitor Protection
Continuous Current
• Fuse > = 135% of rated capacitor current (includes overvoltage,
capacitor tolerances, and harmonics)
Care should be taken when using NEMA Type T and K tin links which are rated
150% In this case the divide the fuse rating by 1 50150%. In this case, the divide the fuse rating by 1.50.
Capacitor Protection
Transient Current
• Lightning surges
• Capacitor switching (specifically back-to-back switching)
High magnitude, high frequency lightning surges are typically notg g , g q y g g g yp y
a concern for substation installations.
Back to back switching is typically controlled with pre insertionBack-to-back switching is typically controlled with pre-insertion
closing resistors or current limiting reactors.
h f i ll i h ll l f ill h hBy the nature of installation, the parallel fuses will share the
transient current and will not be a factor.
Capacitor Protection
Fault Current
Ensure that the fuse can interrupt the available fault current.
In substation banks with multiple series groups, fault current will
not flow through a failed capacitor unit unless other unitsg p
experience a simultaneous failure. For this reason expulsion
fuses are commonly used rather than current limiting fuses
Tank Rupture Coordination
Ensure that the fuse maximum clearing TCC curve for the fuse
li k i l d b l h i k flink is plotted below the capacitor tank rupture curve. In cases of
high fault currents, the tank rupture curve should be compensated
for asymmetry.y y
Capacitor Protection
Example of a DefiniteExample of a Definite
Tank Rupture Curve.
Th i b hThe time between the
rupture curve and the
fuse maximum clear
curve is the
coordination margin.
Capacitor Protection
Example of a 10% and 50%
Rupture Curve for a 100 kVARRupture Curve for a 100 kVAR
Capacitor.
Probability based tank rupturey p
curves are developed when there
is too much variance in rupture
test data.
Based on the 10% and 50%
curves, one can extrapolate the
f b bilicurves for any probability.
Capacitor Protection
Voltage on Good Capacitors
When a short-circuit on one unit occurs, an overvoltage results on
the un-faulted phases. Ensure that the fault is cleared before the
second capacitor failure. A table summarizes this voltage rise on
the un-faulted units
Per Unit Voltage on Un-failed Capacitors
Capacitor Protection
Energy Discharge Into a Failed Unit
When a capacitor failure occurs, the stored energy in the parallel
connected capacitors can discharge thro gh the failed capacitorconnected capacitors can discharge through the failed capacitor
and its fuse. The total calculated parallel stored energy should
not exceed the energy capability (Joule rating) of the capacitor
and fuse. If the energy capabilities are exceeded, a failure of the
fuse and/or rupture of the capacitor tank can result.
Typical rating of film capacitors is 15,000 Joules (4650 kVAR in
parallel) and 10,000 Joules (3100 kVAR in parallel) for paper-
film capacitors Expulsion fuses are typically rated 30 000film capacitors. Expulsion fuses are typically rated 30,000
Joules. Current limiting fuses are required if ratings are exceeded.
(1 Joule = 1 W x sec use 0 2 cycle clearing time for calculation)(1 Joule = 1 W x sec, use 0.2 cycle clearing time for calculation)
Capacitor Protection
Outrush Current
When a capacitor failure occurs, the parallel connected capacitors
can discharge high frequency current into the failed capacitor.
The fuses of the un-failed capacitors should be able to withstand
the high frequency discharge currents. These calculations andg q y g
measurements are complex and are determined by the
manufacturer.
Coordination with Unbalance Detection Scheme
The individual fuse must clear the fault before the unbalance
i h i h i i b kprotection scheme trips the entire capacitor bank.
Capacitor Protection
Fusing Recommendations by McGraw Edison
Capacitor Protection
Recall Problem with Fusing of Small Ungrounded Banks
12.47 kV, 1500 kVAR cap bank made of three (3) 500 kVAR units
FuseAAA
kV
kVAR
][100][1045.144.69][44.69
][47.123
][1500


It will take a 100 A fuse approximately 500 seconds to clear thisIt will take a 100 A fuse approximately 500 seconds to clear this
fault (3 x 69.44 A = 208.32 A). The capacitor case will rupture
long before the fuse clears the fault.
The solution is using smaller units with individual fusing.
Consider five (5) 100 kVAR capacitors per phase, each with a( ) p p p ,
25 A fuse. The clear time for a 25 A fuse @ 208.32 A is below
the published capacitor rupture curve.
Capacitor Protection
Why is the Current 3 x Nominal Line Current for a Phase-to-
Neutral Fault on a Wye-Ungrounded Capacitor Bank?
A
B
A
B
V
A
C
N
A
N
VNG C C
I 3 0
Since V = I*Z, where Z is
t t ( i f 60 h ) IA = 3.0 p.u.constant (assuming f = 60 hz)
If voltage across capacitor is
increased by 1.732, the current
also increases by factor of 1.732y
Capacitor Protection
Minimum Conductor Size
It was noted that capacitors are rated 135% of rating. This
requires the conductor to be sized 135% of the nominal capacitor
ratingrating.
Capacitor Protection
Unbalance Protection
As single-phase units in a multiple unit/phase installation fail and
are removed from service the remaining units are experience anare removed from service, the remaining units are experience an
overvoltage condition. IEEE Standard 1036 provides
overvoltage limitations.
Duration
Max Voltage
(x rated RMS)
6 cycles 2.20
15 c cles 2 0015 cycles 2.00
1 s 1.70
15 sec 1.40
1 min 1.301 min 1.30
An unbalance protection scheme must by implemented to prevent
the failure of the overvoltaged units.g
Capacitor Protection
Capacitor Protection
Neutral Voltage Unbalance with Unbalance Compensation
Capacitor Protection
VA
V
V
VN
VG
VNG
Normal Conditions
VN = VG
VAN = VBN = VCN
VC VB
VAN VBN VCN
Capacitor Protection
Ungrounded or Impedance
Grounded System
VA
V
V
VN
VG
VNG
Normal Conditions
VN = VG
VAN = VBN = VCN = 1.0 p.u.
VC VB
VAN VBN VCN .0 p.u.
Capacitor Protection
VVNG
Phase to Neutral FaultPhase to Neutral Fault
VNG = VLN
VAN = VBN = VLL = 1.732 p.u.
Capacitor Protection
VA
V
VNVG
VNG
One Can Removed
VNG = 0.2 p.u.
V = 1 2 p u
VC VB
VCN = 1.2 p.u.
Capacitor Protection
Ungrounded or Impedance
Grounded System
VA
V
V
VN
VG
VNG
Normal Conditions
VN = VG
VAN = VBN = VCN = 1.0 p.u.
VC VB
VAN VBN VCN .0 p.u.
Capacitor Protection
Ungrounded or Impedance
Grounded System
VA
V
Gnd
VN
VNG
VC
VB
Ground Fault
VNG = VLN
V = V = V = 1 732 p u
VC =VG
Ground Fault at Cap Bank or
A h h SVAG = VBG = VLL = 1.732 p.u. Anywhere on the System
Capacitor Protection
Wye-Ungrounded:
Voltage Between
Capacitor Bank Neutral
and Ground vs. Percentage
of Capacitor Units
Removed from Series
Group
Capacitor Protection
Wye-Ungrounded:
Voltage on Remaining
Capacitor Units in Series
Group vs. Percentage of
Capacitor Units Removed
from Series Group
Capacitor Protection
Wye-Grounded:
Neutral Current vs
Percentage of
Capacitor Units
Removed from Series
Group
Capacitor Protection
Wye-Grounded or Delta:
Voltage on Remaining
Units in Series Group vs.
Percentage of Capacitor
Units Removed from
Series Group
Capacitor Protection
Double Wye-Ungrounded,
Neutrals Tied Together:
Neutral Current vs.
Percentage of Capacitor
Units Removed from
Series Group
Capacitor Protection
Double Wye-Ungrounded,
Neutrals Tied Together:
Voltage on Remaining
Capacitor Units in Series
vs. Percentage of
Capacitor Units Removed
from Series Group
Capacitor Protection
A phase B phase C phase
P: Number of
units in groupunits in group
(P=6)
S: Number ofS: Number of
series groups
(S=4)
Reference Figure for Calculations to Follow
Capacitor Protection
# of Series Groups Grounded Y or Delta Ungrounded Y
Split Ungrounded Y
(equal sections)
1 - 4 21 4 2
2 6 8 7
3 8 9 8
4 9 10 9
5 9 10 10
6 10 10 10
7 10 10 10
8 10 11 10
9 10 11 10
10 10 11 11
11 10 11 11
12 and over 11 11 11
Minimum recommended number of units in parallel per series
Group to limit voltage on remaining units to 110% with one unit out
Capacitor Protection
Many more configurations and
calculations shown in IEEE C37.99
Day 2Day 2
Capacitor Fundamentals
Further discussion on capacitor voltage ratings:
On a ungrounded or impedance grounded system, a ground fault
on one phase will cause the other two phases will be elevated by
1 7321.732.
Does this mean that capacitors must be rated phase-to-phase?
Certainly nothing wrong with this, but cost will be significantly
higher.g
Capacitor Fundamentals
Recall:
X
V
S
2

CX
This means that a 150 kVAR 12470 V unit applied at 7200 VThis means that a 150 kVAR, 12470 V unit applied at 7200 V
will provide only 50 kVAR.
][50
][150
][12470
][7200
2
2
kVARS
kVAR
V
V
SNEW 
][50 kVARSNEW 
Capacitor Fundamentals
Using 12470 V capacitors on a 12470 V Ungrounded or
Resistance-Grounded System will require 3x more cans.y q
It should be noted that the 12470 V cans will also be larger than
the 7200 V cansthe 7200 V cans.
Results in a much larger and more costly installation.
This solution would be required if a ground fault could be
maintained for extended periods of time.p
Capacitor Fundamentals
Perhaps a 150 kVAR or 200 kVAR, 7620 V or 7960 V units
applied at 7200 V would be a better solution.
][150
][7620
][7200
2
2
kVAR
V
V
SNEW  ][200
][7620
][7200
2
2
kVAR
V
V
SNEW 
][134
OR
kVARSNEW  ][178
2
OR
kVARSNEW 
][123
][150
][7960
][7200
2
2
kVARS
kVAR
V
V
SNEW 
][163
][
][7960
][7200
2
2
kVARS
kVAR
V
V
SNEW


][123 kVARSNEW 
Note that the 7620 V unit provides an additional 6%
The 7960 V unit provides an additional 11%
][163 kVARSNEW 
The 7960 V unit provides an additional 11%
Capacitor Fundamentals
Explusion Fuses:
Provides a means of disconnecting a failed capacitor from the circuit by melting a
tin-lead low current link. The shorted capacitor unit causes a large increase in the
current through the fuse. The current is limited only by the power system
reactance and the other capacitor units in series with the failed capacitor unit. Thereactance and the other capacitor units in series with the failed capacitor unit. The
pressure is generated by the hot arc making contact with the fiber lining of the
fuse tube. The link is cooled and stretched as it is forced out the tube. The fuse
continues to conduct until a natural current zero occurs. The current zero is
d b th t f lt t i If th itcaused by the power system fault current crossing zero. If other capacitors are
connected in parallel with the failed unit, all the stored energy in these capacitors
will be absorbed in either the fuse operation or the failed capacitor unit. Most of
the energy is absorbed in the failed capacitor.gy p
Capacitor Fundamentals
Current Limiting Fuses:
Uses a long uniform cross section element. This configuration makes the fuse a
current chopping fuse. The fuse develops a back voltage per inch of element
across the entire length of the element. When this voltage exceeds the available
voltage across the fuse, the fuse forces the arc to extinguish. The result is that avoltage across the fuse, the fuse forces the arc to extinguish. The result is that a
trapped voltage may and probably will remain on the other capacitors in the
series group. The fuse by its design avoids absorbing all of the available energy
on the series group. This fuse is used for capacitor banks with a large number of
ll l it It b d li ti ith ti ll i fi it ll lparallel capacitors. It can be used on applications with essentially infinite parallel
stored energy, as long as sufficient back voltage can be developed to force the
current to extinguish. This is the fuse we apply to series, large shunt, and DC
banks.
Because of the high back voltage that is developed, this fuse must be used with
several capacitors in parallel to limit the voltage build up or a flashover may
occur elsewhere in the capacitor rackoccur elsewhere in the capacitor rack.
Capacitor Fundamentals
Current Limiting Fuses vs Expulsion Fuses:
C Li i i FExpulsion Fuse Current Limiting Fuse
Capacitor Fundamentals
Current Limiting Fuses vs Expulsion Fuses:
Expulsion Fuses
Operate mechanically and provide a visual indication
Require additional space for operationRequire additional space for operation
Typically applied for outdoor application due to ionized gas release.
C bi ti l i ith t li iti h t i ti f b d iCombination expulsion with current limiting characteristic fuses can be used in
indoor metal-enclosed equipment.
Less expensivep
Capacitor Fundamentals
Capacitor Fundamentals
Current Limiting Fuses
Do not emit ionized gases during operation Ionized gases are undesirableDo not emit ionized gases during operation. Ionized gases are undesirable
because they can cause bushing and insulator flashovers that result in additional
damage. Do not require ventilation.
Fast current-limiting operation
High interrupting capacity, noiseless operation
Can be specified for indoor and outdoor applications .
No pressure build-up, therefore, no vents or special reinforced compartments are
i drequired.
More expensive
Capacitor Fundamentals
Note no pigtail and blown fuse indication
Capacitor Fundamentals
Current Limiting with Expulsion
Capacitor Fundamentals
What about arresters? How and where should they be
applied?applied?
Depending on application, environment, exposure to
switching etc arresters may be necessaryswitching, etc, arresters may be necessary.
We recall that when a travelling wave meets a high
impedance, the wave can double in size. For this reason,
arresters (if used) should be installed as close to the capacitor
bank as possible. Installation of arresters at the breakerp
feeding the capacitor bank will not do much for protection of
the capacitor bank.
Capacitor Protection
A basic three (3) arrester method is shown below. This is
typical for solidly grounded systems and wye-groundedtypical for solidly grounded systems and wye grounded
capacitor banks.
Capacitor Protection
Depending on type of installation, system parameters and
level of protection required, a six(6) arrestor method may belevel of protection required, a six(6) arrestor method may be
applied.
Capacitor Protection
For an ungrounded system or a high-impedance grounded
system, a four (4) arrestor grounding method might besystem, a four (4) arrestor grounding method might be
considered an wye ungrounded bank.
Phase to Neutral Fault
VNG = VLNNG LN
VAN = VBN = VLL = 1.732 p.u.
Ground Fault
VNG = VLN
VLL
VLL
ArrNG LN
VAG = VBG = VLL = 1.732 p.u.
If faults can be maintained,
ArrN
V
ArrPH
ArrPH must be rated VLL
ArrN must be rated VLN
The effective arrester MCOV
N
is VLL + VLN
Capacitor Protection
Note that if a basic three (3) arrester method is applied to an ungrounded bank, the arresters
must be rated high enough to sustain a temporary overvoltage condition during a phase-to-
ground fault on the system. This may not provide an adequate level of protection for the
capacitors.
Phase to Neutral Fault
VNG = VLN
V V V 1 732VAN = VBN = VLL = 1.732 p.u.
Ground Fault
VNG = VLN
V V V 1 732
VLL
VLL
VAG = VBG = VLL = 1.732 p.u.
If faults can be maintained, Arresters
must be rated VLL
V
Arresters do not provide protection
across the capacitor bushings. Note
that the BIL applies to bushing-to-
i l ticase insulation.
Capacitor Protection
Good Presentations on Capacitor – Arrester Applications
“G id li f S l ti f S A t f Sh t“Guidelines for Selection of Surge Arresters for Shunt
Capacitor Banks” – ABB Technical Information
“Surge Arrester Application of MV-Capacitor Banks to
Mitigate Problems of Switching Restrike” – CIRED 19th
International Conference on Electricity Distribution ViennaInternational Conference on Electricity Distribution, Vienna,
21-24 May 2007.
B th f th l dd h t h tBoth of these papers also address phase-to-phase arrester
connections.
Harmonics
Harmonics
Recall that the impedance of a capacitor is inversely
proportional to the system frequencyproportional to the system frequency.
fCC
XC
 2
11

fCC  2
Harmonics flow to the point of lowest impedance. The higher
the harmonic the lower the impedance of the capacitorthe harmonic, the lower the impedance of the capacitor.
As capacitors absorb harmonics, the capacitor heats up and
th lif t i d d Th lt h i tthe life expectancy is reduced. The voltage harmonics stress
the capacitor dielectric and reduce the life expectancy of the
capacitor.
Harmonics
Harmonics
Where do harmonics come from?
• Power Electronics (drives, rectifiers, computer power
supplies, etc)
• Arcing Devices (welders, arc furnaces, florescent lights, etc)g ( , , g , )
• Iron Saturating Devices (transformers)
• Rotating Machines (Generators)
• Parallel Resonance (between cap bank and power• Parallel Resonance (between cap bank and power
equipment)
IEEE Std 519 provides recommended limits of harmonic
distortion at the point-of-common-coupling (PCC) with the
utility.y
Harmonics
Harmonics
Harmonics
Resonance
When a number of harmonic current sources are injecting currents
into the supply and the frequency of one of the harmonics coincides
with the resonant frequency of the supply transformer andwith the resonant frequency of the supply transformer and
Power Factor Correction capacitor combination, the system
resonates and a large circulating harmonic current is excited
between these components The result of this is that a largebetween these components. The result of this is that a large
current at this harmonic flows in the supply transformer, this
resulting in a large harmonic voltage distortion being imposed upon
the load voltage.
Harmonics
A study should be performed to determine levels of harmonics on ay p
system to determine if any filters are necessary when installing a
capacitor bank.
Care should be taken to determine if the filtered capacitor bank will
introduce any resonance problems. If resonance problems exist, the
fil d i b dj dfilter design must be adjusted.
Harmonics
An example of a 13 8 kV harmonic filterAn example of a 13.8 kV harmonic filter
Capacitor Bank Design Considerations
Design Considerations
So how do we size a capacitor bank?
D t i i lDetermine your primary goal
• Voltage support
• Lower utility bill (avoid penalties)
• Increase capacity of system
It can be all three, or any combination of the above.It can be all three, or any combination of the above.
Note that correcting to unity power factor at maximum load is
tl d t bcostly and may not be necessary.
Design Considerations
For a 20 MVA load at 0 88 power factor (17 6 MW 9 5 MVAR)For a 20 MVA load at 0.88 power factor (17.6 MW, 9.5 MVAR)
To achieve 95% power factor, a 3.72 MVAR bank is required
To achieve 98% power factor, a 5.93 MVAR bank is required
To achieve unity power factor, a 9.50 MVAR bank is required
Design Considerations
Determine if current limiting reactors or tuning reactors areDetermine if current limiting reactors or tuning reactors are
required.
Harmonics and resonance may dictate tuning reactors
Back-to-back switching may require current limiting reactorsBack to back switching may require current limiting reactors
(unless another method is used to mitigate the switching surges,
i.e. pre-insertion closing resistors/reactors, zero-crossing
breakers etc)breakers, etc)
Design Considerations
Determine the proper voltage.
Capacitors are very susceptible to voltage transients and
harmonics. Increasing the rated voltage increases the protective
margin on the insulation.margin on the insulation.
The voltage at the capacitor terminals will be higher than bus
lt if t tili d It i i t t t t f thivoltage if reactors are utilized. It is important to account for this
voltage difference.
Determine the voltage swing of the system. Will the capacitors
remain on-line while the facility is lightly loaded.
Design Considerations
We listed some reasons for specifying higher than bus nominalWe listed some reasons for specifying higher than bus nominal
rating of capacitors. However, care must be taken to ensure that
the kVAR rating is properly adjusted as a result.
Three (6) 150 kVAR, 7960 V wye-connected capacitors provide a
nominal 901 kVAR when connected to a 13.8 kV bus.
Three (6) 150 kVAR, 8320 V wye-connected capacitors provide a
nominal 825 kVAR when connected to a 13 8 kV busnominal 825 kVAR when connected to a 13.8 kV bus
Design Considerations
Determine optimal size and number of stages.
D di i i l t l d i l b k i d f f llDepending on swing in plant load, a single bank sized for full
plant capacity may not be the answer.
IEEE 1036 recommends limiting the voltage change to 2-3%. The
delta voltage can be estimated by:
MVAR
Switch of a capacitor applies high stresses to the insulation
%100
SCMVA
MVAR
V
Switch of a capacitor applies high stresses to the insulation.
Limiting the number of stages and limiting the frequency of
switching will increase the life. Ideally, a capacitor is switched
on and left on.
Design Considerations
Determine best location for the installation The most effectiveDetermine best location for the installation. The most effective
placement for power factor correction capacitor banks is at the
load. However, this is not always practical or cost effective.
Typically, a capacitor bank is installed on each bus of a main-tie-
main switchgear.main switchgear.
If capacitors are installed at the motor pecker head (running
capacitors) ensure that the capacitor VAR rating does not exceedcapacitors), ensure that the capacitor VAR rating does not exceed
90% of the motor no-load VAR. Otherwise, it is possible to
damage the motor by overexcitation.
Design Considerations
Use caution when sizing motor running capacitors.
Logic would suggest that installation of a power factor
correction capacitor at the motor terminals sized to provide
unity power factor makes sense.y p
THIS IS NOT THE CASE. Do not exceed 90% of the
motor no load kVAR demand Exceeding this value canmotor no-load kVAR demand. Exceeding this value can
result in damage to the motor insulation as a result of
overexcitation.
Design Considerations
As an example for a 4000 V, 4000 hp motor:
100% load current = 495 A @ 89.7% pf
100% load kVAR = 1516 kVAR
No load current = 117 A @ 6.3 % pf
No load kVAR = 809 kVAR
Max size of running capacitor is 0 90 x 809 kVAR = 728 kVARMax size of running capacitor is 0.90 x 809 kVAR = 728 kVAR
Design Considerations
M: Motor Magnetizing CurveM: Motor Magnetizing Curve
C1: Capacitor size at 100% motor mag current
C2: Capacitor sized > 100% motor mag current
C4: Capacitor sized < 100% motor mag current
If the capacitive reactance of the capacitor is less less than that of the motor reactance (this occurs
when to large of a capacitor is chosen). This combination of reactance will result in a resonant
frequency below 60 hertz Therefore as the motor slows in speed the frequency of the motorfrequency below 60 hertz. Therefore, as the motor slows in speed, the frequency of the motor
terminal voltage will decrease from a value of near 60 hertz toward zero. When the motor's terminal
voltage frequency passes through the resonant frequency setup between the capacitor reactance and
the motor reactance, the terminal voltage will become very high, only limited by the properties of the
iron Depending on the inertia of the motor this resonance (or high voltage) may be present for airon. Depending on the inertia of the motor, this resonance (or high voltage) may be present for a
considerable period of time.
Design Considerations
Determine the most optimal type of installationDetermine the most optimal type of installation.
Will the capacitor bank be installed within a fenced substation?
Metal-enclosed, pad mount, or open rack may be good choices
Will the capacitor bank be installed in a process area?Will the capacitor bank be installed in a process area?
Metal-enclosed or pad mount may be good choices
Will the capacitor bank be pole mounted on a distribution line?Will the capacitor bank be pole mounted on a distribution line?
Bank Failures
Design Considerations
Consider the impact to personnel safety adjacent equipment when
deciding between a metal-enclosed and open-rack system.
Porcelain can resemble shrapnel when a capacitor bushing fails.
Design Considerations
Determine the most optimal configuration.
Higher reliability costs more.
2400 kVAR, 13800 V, wye-grounded (1) 800 kVAR per phase, , y g ( ) p p
bank will be a smaller footprint and cost less than
2400 kVAR 13800 V wye ungrounded (8) 100 kVAR per2400 kVAR, 13800 V, wye-ungrounded (8) 100 kVAR per
phase bank.
H h li bili f h d d b k iHowever, the reliability of the wye-ungrounded bank is
significantly higher
Design Considerations
Determine the switching equipment
When breakers are used for switching capacitors (single bank
or back-to-back switching), the breakers must be rated for
capacitor switching.p g
IEEE C37.99 provides the equations for calculating the inrush
current and frequencycurrent and frequency.
Design Considerations
Design Considerations
Consider a single 4800 kVAR wye-ungrounded bank switched
(with nominal inductance from equipment):
3253A pk @ 600 Hz, the product is 0.20 x 107
Switching a second similar bank on the same bus without
current limiting reactor:
24,058 A pk @ 7.66 kHz, the product is 18.4 x 107
B ddi 100 H li i i h i h iBy adding a 100 mH current limiting reactor, the inrush is:
7254 A pk @ 2.31 kHz, the product is 1.7 x 107p @ , p
Design Considerations
Design Considerations
Design Considerations
Energization of a single capacitor bank.
Design Considerations
B k b k i hi f h iBack-to-back switching of the same unit.
Design Considerations
E l f b k i h i i iExample of breaker with pre-insertion resistor.
Design Considerations
Another application.Another application.
Design Considerations
A Pre-Insertion Manufacture’s Perspective.p
Design Considerations
Another concern is voltage amplification as a result of switching a
second capacitor bank.
Design Considerations
Design Considerations
Consider other accessories:
• Disconnect switch
• Grounding switch
• Kirk-key interlocky
• Ventilation requirements
• Control power
Design Considerations
Design Considerations
Design Considerations
Be aware that larger medium voltage motors may include
surge packs.g p
The surge pack will decrease the crest voltage and rate of
rise of the impending surge High rates of rise damage endrise of the impending surge. High rates of rise damage end
turns while high crest voltage damage winding to core
insulation.
Typically the capacitance of the is small enough that it can
be neglected, but this should be verified.g
Design Considerations
Typical Surge Pack Application
Design Considerations
Do not confuse Harmonic Filter Banks with Power Factor
Correction BanksCorrection Banks.
The voltage ratings of harmonic filter banks are substantially
higher because they are connected on the back end of a tuning
reactor where the voltage is substantially higher. As a result of
the higher voltage, the installed kVAR can be anywhere frome g e vo ge, e s ed V c be yw e e o
25% to 40% higher than nominal design.
The capacitor cans must be capable of this outputThe capacitor cans must be capable of this output.
Grounding of Wye Banks
If multiple wye-grounded banks are in close proximity, use
peninsula grounding or single-point grounding.p g g g p g g
Single-Point Grounding
The neutrals of all banks of a given voltage are connectedThe neutrals of all banks of a given voltage are connected
together with insulated cable/bus and tied to the ground
grid only at one point. This prevents high-frequency
(d b k b k i hi ) f fl i icurrents (due to back-to-back switching) from flowing into
the ground grid.
Grounding of Wye Banks
Peninsula Grounding
One or more isolated ground grid conductors are carriedg g
underneath the capacitor rack of each phase and tied to the
station ground grid at one point at the edge of the capacitor
area All capacitor bank neutral connections are made toarea. All capacitor bank neutral connections are made to
this isolated peninsula ground grid conductor.
Grounding of Wye Banks
Grounding of Wye Banks
References
• IEEE Std. 18
• IEEE C37.99
• NEMA CP-1
• IEEE Std 1036
•IEEE Std 399 (Brown Book)IEEE Std 399 (Brown Book)

More Related Content

What's hot

Understanding transformer vector group
Understanding transformer vector groupUnderstanding transformer vector group
Understanding transformer vector groupShyamkant Vasekar
 
Instrument Transformer Presentation
Instrument Transformer PresentationInstrument Transformer Presentation
Instrument Transformer PresentationRishi Raj
 
Difference of CT & PT
Difference of CT & PT Difference of CT & PT
Difference of CT & PT Jay Ranvir
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & MaintenanceHimansu Pradhan
 
Electric substation
Electric substation Electric substation
Electric substation ANNU KUMAR
 
unit-iii- Sphere Gap.ppt
unit-iii- Sphere Gap.pptunit-iii- Sphere Gap.ppt
unit-iii- Sphere Gap.pptVijayHiremath26
 
Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)RP6997
 
Per unit representation
Per unit representationPer unit representation
Per unit representationMd. Rimon Mia
 
Measurement of high_voltage_and_high_currentunit_iv_full_version
Measurement of high_voltage_and_high_currentunit_iv_full_versionMeasurement of high_voltage_and_high_currentunit_iv_full_version
Measurement of high_voltage_and_high_currentunit_iv_full_versionAman Ansari
 
ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...
ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...
ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...Jobin Abraham
 
Three phase-circuits
Three phase-circuitsThree phase-circuits
Three phase-circuitsrsamurti
 
Power BJT and Power MOSFET
Power BJT and Power MOSFETPower BJT and Power MOSFET
Power BJT and Power MOSFETPeriyanayagiS
 
Extra High voltage(BOOK)
Extra High voltage(BOOK) Extra High voltage(BOOK)
Extra High voltage(BOOK) khemraj298
 
Star & Delta Connection
Star & Delta ConnectionStar & Delta Connection
Star & Delta Connectionmansour048
 
Testing of circuit breakers
Testing of circuit breakersTesting of circuit breakers
Testing of circuit breakersKabilesh K
 
DETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINE
DETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINEDETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINE
DETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINEvishalgohel12195
 

What's hot (20)

Understanding transformer vector group
Understanding transformer vector groupUnderstanding transformer vector group
Understanding transformer vector group
 
Introduction to mv switchgear
Introduction to mv switchgearIntroduction to mv switchgear
Introduction to mv switchgear
 
Instrument Transformer Presentation
Instrument Transformer PresentationInstrument Transformer Presentation
Instrument Transformer Presentation
 
Difference of CT & PT
Difference of CT & PT Difference of CT & PT
Difference of CT & PT
 
Gss herapura report
Gss herapura reportGss herapura report
Gss herapura report
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
 
Electric substation
Electric substation Electric substation
Electric substation
 
unit-iii- Sphere Gap.ppt
unit-iii- Sphere Gap.pptunit-iii- Sphere Gap.ppt
unit-iii- Sphere Gap.ppt
 
Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)Generation of High D.C. Voltage (HVDC generation)
Generation of High D.C. Voltage (HVDC generation)
 
THE POWER FACTOR
THE POWER FACTOR THE POWER FACTOR
THE POWER FACTOR
 
Per unit representation
Per unit representationPer unit representation
Per unit representation
 
Measurement of high_voltage_and_high_currentunit_iv_full_version
Measurement of high_voltage_and_high_currentunit_iv_full_versionMeasurement of high_voltage_and_high_currentunit_iv_full_version
Measurement of high_voltage_and_high_currentunit_iv_full_version
 
ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...
ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...
ELECTRICAL POWER SYSTEM - II. symmetrical three phase faults. PREPARED BY : J...
 
Three phase-circuits
Three phase-circuitsThree phase-circuits
Three phase-circuits
 
Power BJT and Power MOSFET
Power BJT and Power MOSFETPower BJT and Power MOSFET
Power BJT and Power MOSFET
 
Extra High voltage(BOOK)
Extra High voltage(BOOK) Extra High voltage(BOOK)
Extra High voltage(BOOK)
 
Star & Delta Connection
Star & Delta ConnectionStar & Delta Connection
Star & Delta Connection
 
Testing of circuit breakers
Testing of circuit breakersTesting of circuit breakers
Testing of circuit breakers
 
DETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINE
DETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINEDETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINE
DETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINE
 
Vacuum circuit breaker
Vacuum circuit breakerVacuum circuit breaker
Vacuum circuit breaker
 

Similar to capacitors

Power Factor : Basics and Benefits of Improvement
Power Factor : Basics and  Benefits of ImprovementPower Factor : Basics and  Benefits of Improvement
Power Factor : Basics and Benefits of ImprovementBijadhar Pandey
 
Day 3: Power Supply Quality in Buildings
Day 3: Power Supply Quality in Buildings Day 3: Power Supply Quality in Buildings
Day 3: Power Supply Quality in Buildings RCREEE
 
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...Staco Energy
 
Installation testing and_commissioning_o (1)
Installation testing and_commissioning_o (1)Installation testing and_commissioning_o (1)
Installation testing and_commissioning_o (1)FunExplode
 
Power factor correction
Power factor correctionPower factor correction
Power factor correctionAbdur rehman
 
Webinar: Desmistificando projetos de fontes chaveadas
Webinar: Desmistificando projetos de fontes chaveadasWebinar: Desmistificando projetos de fontes chaveadas
Webinar: Desmistificando projetos de fontes chaveadasEmbarcados
 
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUESpower factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUESEMERSON EDUARDO RODRIGUES
 
power factor correction soham+niraj
power factor correction soham+nirajpower factor correction soham+niraj
power factor correction soham+nirajsoham patel
 
Principles of Power Systems V.K Mehta Complete Book - Chapter 6
Principles of Power Systems V.K Mehta Complete Book - Chapter 6Principles of Power Systems V.K Mehta Complete Book - Chapter 6
Principles of Power Systems V.K Mehta Complete Book - Chapter 6Power System Operation
 
LOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOM
LOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOMLOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOM
LOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOMASWATHYSANAND1
 

Similar to capacitors (20)

Power Factor : Basics and Benefits of Improvement
Power Factor : Basics and  Benefits of ImprovementPower Factor : Basics and  Benefits of Improvement
Power Factor : Basics and Benefits of Improvement
 
Day 3: Power Supply Quality in Buildings
Day 3: Power Supply Quality in Buildings Day 3: Power Supply Quality in Buildings
Day 3: Power Supply Quality in Buildings
 
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...
Product: Power Factor & Harmonics: StacoVAR: Let's Discuss Power Factor Corre...
 
Installation testing and_commissioning_o (1)
Installation testing and_commissioning_o (1)Installation testing and_commissioning_o (1)
Installation testing and_commissioning_o (1)
 
Power factor
Power factorPower factor
Power factor
 
APFC AMTL 30.01.2015
APFC  AMTL  30.01.2015APFC  AMTL  30.01.2015
APFC AMTL 30.01.2015
 
Power factor improvement
Power factor improvementPower factor improvement
Power factor improvement
 
09 rasool opportunities and challenges in using advanced inverter functionality
09 rasool opportunities and challenges in using advanced inverter functionality09 rasool opportunities and challenges in using advanced inverter functionality
09 rasool opportunities and challenges in using advanced inverter functionality
 
En528032
En528032En528032
En528032
 
Power factor correction
Power factor correctionPower factor correction
Power factor correction
 
EDS Unit 5.pptx
EDS Unit 5.pptxEDS Unit 5.pptx
EDS Unit 5.pptx
 
Power factor improvement
Power factor improvementPower factor improvement
Power factor improvement
 
Power Factor
Power FactorPower Factor
Power Factor
 
Webinar: Desmistificando projetos de fontes chaveadas
Webinar: Desmistificando projetos de fontes chaveadasWebinar: Desmistificando projetos de fontes chaveadas
Webinar: Desmistificando projetos de fontes chaveadas
 
General Power Quality
General Power QualityGeneral Power Quality
General Power Quality
 
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUESpower factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
power factor and power factor correction schneider EMERSON EDUARDO RODRIGUES
 
power factor correction soham+niraj
power factor correction soham+nirajpower factor correction soham+niraj
power factor correction soham+niraj
 
Principles of Power Systems V.K Mehta Complete Book - Chapter 6
Principles of Power Systems V.K Mehta Complete Book - Chapter 6Principles of Power Systems V.K Mehta Complete Book - Chapter 6
Principles of Power Systems V.K Mehta Complete Book - Chapter 6
 
LOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOM
LOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOMLOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOM
LOW CAPACITANCE CASCADED H BRIDGE MULTILEVEL BASED STATCOM
 
8925273.ppt
8925273.ppt8925273.ppt
8925273.ppt
 

More from Vincent Wedelich, PE MBA

Part 3 motor application considerations understanding power concepts rev 5 vi...
Part 3 motor application considerations understanding power concepts rev 5 vi...Part 3 motor application considerations understanding power concepts rev 5 vi...
Part 3 motor application considerations understanding power concepts rev 5 vi...Vincent Wedelich, PE MBA
 
Electrical master plan for chemical engineers and managers
Electrical master plan for chemical engineers and managersElectrical master plan for chemical engineers and managers
Electrical master plan for chemical engineers and managersVincent Wedelich, PE MBA
 
Affordable automobile for low income families
Affordable automobile for low income families Affordable automobile for low income families
Affordable automobile for low income families Vincent Wedelich, PE MBA
 
PERCEPTIONS OF GENDER EQUALITY IN CORPORATE AMERICA
PERCEPTIONS OF GENDER EQUALITY IN CORPORATE AMERICAPERCEPTIONS OF GENDER EQUALITY IN CORPORATE AMERICA
PERCEPTIONS OF GENDER EQUALITY IN CORPORATE AMERICAVincent Wedelich, PE MBA
 
Tracking firm presentation (vincent wedelich) mmm
Tracking firm presentation (vincent wedelich) mmmTracking firm presentation (vincent wedelich) mmm
Tracking firm presentation (vincent wedelich) mmmVincent Wedelich, PE MBA
 
Tracking firm presentation (vincent wedelich) mmm 3M
Tracking firm presentation (vincent wedelich) mmm 3MTracking firm presentation (vincent wedelich) mmm 3M
Tracking firm presentation (vincent wedelich) mmm 3MVincent Wedelich, PE MBA
 

More from Vincent Wedelich, PE MBA (20)

Part 3 motor application considerations understanding power concepts rev 5 vi...
Part 3 motor application considerations understanding power concepts rev 5 vi...Part 3 motor application considerations understanding power concepts rev 5 vi...
Part 3 motor application considerations understanding power concepts rev 5 vi...
 
Electrical master plan for chemical engineers and managers
Electrical master plan for chemical engineers and managersElectrical master plan for chemical engineers and managers
Electrical master plan for chemical engineers and managers
 
Solar skin
Solar skinSolar skin
Solar skin
 
Executive compensation main ppt
Executive compensation main pptExecutive compensation main ppt
Executive compensation main ppt
 
Affordable automobile for low income families
Affordable automobile for low income families Affordable automobile for low income families
Affordable automobile for low income families
 
Amerada hess final presentation
Amerada hess final presentationAmerada hess final presentation
Amerada hess final presentation
 
American barrick vww
American barrick vwwAmerican barrick vww
American barrick vww
 
Balanced scorecard presentation rev 0
Balanced scorecard presentation rev 0Balanced scorecard presentation rev 0
Balanced scorecard presentation rev 0
 
THE PROFIT CHAIN
THE PROFIT CHAINTHE PROFIT CHAIN
THE PROFIT CHAIN
 
MANAGEMENT ACCOUNTING STUDY PPT
MANAGEMENT ACCOUNTING STUDY PPTMANAGEMENT ACCOUNTING STUDY PPT
MANAGEMENT ACCOUNTING STUDY PPT
 
MANAGEMENT ACCOUNTING STUDY PPT
MANAGEMENT ACCOUNTING STUDY PPTMANAGEMENT ACCOUNTING STUDY PPT
MANAGEMENT ACCOUNTING STUDY PPT
 
FUTURES TRADING
FUTURES TRADINGFUTURES TRADING
FUTURES TRADING
 
Frontier corporation
Frontier corporationFrontier corporation
Frontier corporation
 
Good to great ppt (vww)
Good to great ppt (vww)Good to great ppt (vww)
Good to great ppt (vww)
 
PERCEPTIONS OF GENDER EQUALITY IN CORPORATE AMERICA
PERCEPTIONS OF GENDER EQUALITY IN CORPORATE AMERICAPERCEPTIONS OF GENDER EQUALITY IN CORPORATE AMERICA
PERCEPTIONS OF GENDER EQUALITY IN CORPORATE AMERICA
 
Financial Derivatives and Options
Financial Derivatives and OptionsFinancial Derivatives and Options
Financial Derivatives and Options
 
Tracking firm presentation (vincent wedelich) mmm
Tracking firm presentation (vincent wedelich) mmmTracking firm presentation (vincent wedelich) mmm
Tracking firm presentation (vincent wedelich) mmm
 
Iceland krona vincent wedelich
Iceland krona vincent wedelichIceland krona vincent wedelich
Iceland krona vincent wedelich
 
Tracking firm presentation (vincent wedelich) mmm 3M
Tracking firm presentation (vincent wedelich) mmm 3MTracking firm presentation (vincent wedelich) mmm 3M
Tracking firm presentation (vincent wedelich) mmm 3M
 
Electrical Condition monitoring part 1
Electrical Condition monitoring part 1Electrical Condition monitoring part 1
Electrical Condition monitoring part 1
 

Recently uploaded

Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 

Recently uploaded (20)

Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 

capacitors

  • 1. Capacitors Dominik Pieniazek, P.E. – VI Engineering, LLC Nicholas A. Losito Jr. – Castle Power Solutions, LLC
  • 2. Outline Day 1Day 1 • Basic Power Calculations • Capacitor Fundamentals • Capacitor Ratings • Capacitor Application • Capacitor Protectionp Day 2 • Harmonics • Capacitor Bank Design Considerations• Capacitor Bank Design Considerations
  • 3. Shunt Capacitors • Medium Voltage • Substation Applicationspp • Power Factor Correction
  • 5. Basic Power Calculations C Q tiCommon Questions: What are VARs? Wh d b t VAR ?Why do we care about VARs?
  • 6. Basic Power Calculations Most plant loads (motors, transformers, etc) are INDUCTIVE and require a magnetic field to operate. The magnetic field is necessary, but produces NO USEFUL WORK. The utility must supply the power to produce the magnetic field and themust supply the power to produce the magnetic field and the power to produce USEFUL work. The ACTIVE component produces the USEFUL work, the REACTIVE component produces the magnetic field.
  • 7. Basic Power Calculations An analogy that VAR gy most can understand. Mug i f i VA Capacity of equipment (i.e. xfmr, cable, swgr, etc) Beer W ee Stuff that you want Foam (Head) St ff hi h tStuff which prevents you from maximizing the amount of beer that you get
  • 8. Basic Power Calculations f lV: Reference voltage IR: Resistive load IL: Inductive load I : Capacitive loadIC: Capacitive load
  • 10. Basic Power Calculations Vref Ilag Note that due to phase shift (30 degrees) only 86.66% of current is applied to calculate work. Power = Re(V I*)
  • 11. Basic Power Calculations Vref Ilead Regardless whether leading or lagging, power calculation yields similar results Power = Re(V I*)
  • 12. Basic Power Calculations Vref I90 In the case where current leads or lags the voltage by 90 degrees, P = 0 Power = Re(V I*)
  • 13. Basic Power Calculations Power Factor [ PF ] = Cos = P / S S (kVA) Q (kVAR) P (W) Power Triangle The relationship between S, P, and Q. This figure represents a lagging power factor. If Q is negative, leading power factor. g
  • 14. Basic Power Calculations So how do we know if our current is lagging or leadingcurrent is lagging or leading the voltage, and what can we do to correct it?do to correct it? Consider this exampleConsider this example,
  • 15. Basic Power Calculations Incoming service is at 5500 kW 3400 kVAR g 99.5% capacity 6466 kVA 2000 kW 1000 kW 2500 kW 1000 kVAR 800 kVAR 1600 kVAR
  • 16. Basic Power Calculations Power Factor [ PF ] = Cos = P / S0.85 lag S (kVA) g Q (kVAR)3400 kVAR 31.8 deg P (W) Power Triangle 5500 kW g Even though our facility require only 5500 kW to perform Real Work, our incoming service must be sized for 6466 kVA.
  • 17. Basic Power Calculations We have a 6500 kVA mug that is holding 5500 kW and 3400 kVAR. VAR VA W With the existing configuration the facility cannot add any loadsy y without upgrading the incoming service.
  • 18. Basic Power Calculations Incoming service is at 5500 kW 0 kVAR g 85% capacity 5500 kVA 3400 kVAR 2000 kW 1000 kW 2500 kW 1000 kVAR 800 kVAR 1600 kVAR
  • 19. Basic Power Calculations Power Factor [ PF ] = Cos = P / S1.0 unity S (kVA) y Q (kVAR)0 kVAR 0 deg P (W) Power Triangle 5500 kW g The cap bank is providing 3400 kVAR, so our service is now providing only 5500 kVA (reduction from 6466 kVA.
  • 20. Basic Power Calculations 1,500 kVA COS [ ] = 0.67 COS [ ] = 0.95 Q2 = Q1 + Qc Q1 = 1,118 kVAR 1 000 kW 1,053 kVA Q2 = 330 kVAR 1,000 kWQ Qc = 788 kVAR Required Apparent Power Before and After Adding a Power Capacitor Bank An example of how to calculate the size of a cap bank based on a target power factor
  • 21. Basic Power Calculations But wait, there’s more….
  • 22. Basic Power Calculations Odds are that the utility is 5500 kW 3400 kVAR y charging you for penalties for a low power factor. 6466 kVA 5500 6466 = 0.85 Typically, penalties are applied for power factor lessapplied for power factor less than 0.95%. 2000 kW 1000 kW 2500 kW 1000 kVAR 800 kVAR 1600 kVAR
  • 23. Basic Power Calculations There are also voltage 5500 kW 3400 kVAR g considerations. Assuming typical values: 6466 kVA Assuming typical values: Source impedance = 9% at 6500 kVAVolt Drop = 5.8% The expected voltage drop at the main bus will be close to 6%! 2000 kW 1000 kW 2500 kW 1000 kVAR 800 kVAR 1600 kVAR
  • 24. Basic Power Calculations Capacitor bank reduces the voltage drop at main bus 5500 kW 0 kVAR voltage drop at main bus by 5%! 5500 kVA Volt Drop = 1.0% 3400 kVAR 2000 kW 1000 kW 2500 kW 1000 kVAR 800 kVAR 1600 kVAR
  • 25. Basic Power Calculations Note that the capacitor bank can also raise the bus voltage 5500 kW -1600 kVAR g above the nominal value. 5728 kVA Volt Drop = -1.5% 5000 kVAR 2000 kW 1000 kW 2500 kW 1000 kVAR 800 kVAR 1600 kVAR
  • 26. Basic Power Calculations The voltage continues to rise if the capacitor bank remains 3000 kW -3200 kVAR p connected and the load is reduced. 4386 kVA Volt Drop = -3.6% 5000 kVAR Out of service 2000 kW 1000 kW 0 kW 1000 kVAR 800 kVAR 0 kVAR
  • 28. Capacitor Fundamentals C = eo A / d for a parallel plate capacitor, where eo is the permittivity of the insulating material (dielectric)o between plates.
  • 29. Capacitor Fundamentals We recall that we can add series capacitances to 1 / C = 1 / C1 + 1 / C2 We recall that we can add series capacitances to obtain an equivalent capacitance. 1 / Ceq 1 / C1 + 1 / C2
  • 30. Capacitor Fundamentals Similarly, we can add parallel capacitances to obtain an equivalent capacitance. Ceq = C1 + C2
  • 31. Capacitor Fundamentals …but we typically do not have much use for capacitance values. So we convert capacitance to impedance:So we convert capacitance to impedance: fCC XC 2 11  fCC C  2
  • 32. Capacitor Fundamentals cjXRZ  cjXRZ  CXZ  V Z 2  X V S 2  S CX
  • 33. Capacitor Fundamentals 1000* ][ ][ 2  kVV kVARS 000 ][ ][ Z kVS Example:Example: The capacitance of a capacitor is 6.22 F and the nameplate voltage is 8000 V. Calculate the power rating. ][7.426 )1022.6)(60)(14.3(2 1 6   x XC ][150000,1 7.426 )8( 2 kVARS 
  • 39. Capacitor Fundamentals Note that IEEE Std 18 requires the discharge Discharge resistor requires the discharge resistor to reduce the terminal voltage to 50 V in th ti f ifi dthe time frame as specified in the table below.
  • 41. Capacitor Ratings Medium voltage capacitors are available in many different stylesMedium-voltage capacitors are available in many different styles. The main points of differentiation are listed below: • Voltage rating • kVAR rating • Single bushing or dual bushingg g g • Internally fused, externally fused, or fuseless
  • 42. Capacitor Ratings IEEE 81 defines the ratings for capacitorsIEEE 81 defines the ratings for capacitors • Voltage, rms (terminal to terminal) • Terminal-to-case (or ground) insulation class • Reactive power • Number of phasesp • Frequency
  • 43. Capacitor Ratings IEEE 18 provides capacitor tolerancesIEEE 18 provides capacitor tolerances • The capacitance shall not vary more than -0% to +10% of nominal value based on rated kVAR, voltage, and frequency measured at 25 deg C. This means that a new 150 kVAR unit can range anywhere fromg y 150 kVAR to 165 kVAR.
  • 44. Capacitor Ratings IEEE 18 states the capacitor is intended to operate at or belowIEEE 18 states the capacitor is intended to operate at or below rated voltage. Capacitors shall be capable of continuous operation given that none of the following limitations are exceeded: • 110% of rated rms voltage (temporary overvoltage parameters will be discussed later)) • 120% of peak voltage, including harmonics but excluding transients • 135% of nominal rms current based on rated kVAR and rated• 135% of nominal rms current based on rated kVAR and rated voltage • 135% of rated kVAR
  • 45. Capacitor Ratings * Impulse tests shall be applied between terminals and case, with the terminals connected together. For capacitors having bushings with two different BIL ratings, this test shall be based on the bushing with the lower BIL. The nameplate shall show both BIL ratings, e.g. 150/95 kV BIL. ** Not applicable to indoor ratings
  • 47. Capacitor Application Power factor correction capacitor banks are typically installed inPower factor correction capacitor banks are typically installed in the following ways : • Pole top • Metal-Enclosed / Pad-Mount • Open rackOpe ac • Terminal end at equipment
  • 48. Capacitor Application P l T I t ll tiPole Top Installation
  • 49. Capacitor Application Transient inrush reactors P l T I t ll tiPole Top Installation
  • 50. Capacitor Application Pad Mounted InstallationPad-Mounted Installation
  • 51. Capacitor Application Metal-Enclosed Substation InstallationMetal Enclosed Substation Installation
  • 52. Capacitor Application Three-phase iron core harmonic filter reactor Metal-Enclosed Substation Installation harmonic filter reactor Metal Enclosed Substation Installation
  • 53. Capacitor Application Open Rack, Medium-Voltage Substation Installation
  • 54. Capacitor Application Open Rack, High-Voltage Substation Installation
  • 56. Capacitor Application Power factor correction capacitor banks can be configured in thePower factor correction capacitor banks can be configured in the following ways : • Delta • Wye - Solidly Grounded • Wye - Ungroundedy g A common misconception is that the capacitor bank should be connected Delta since it is being applied to a delta or highconnected Delta since it is being applied to a delta or high- impedance grounded system. This is NOT true.
  • 57. Capacitor Application The driving factor which determine the configuration for the given application is COST. Voltage considerationsVoltage considerations IEEE 1036 suggests that only banks rated 2400 V and below should be Delta connected This is mainly because standardshould be Delta connected. This is mainly because standard voltage ratings for wye connected banks may not be available. Cost of phase-to-phase vs phase-to-neutral rated capacitors at higher voltages tends to point installations towards wye connected banks for larger bank installations.connected banks for larger bank installations.
  • 58. Capacitor Application Delta Lower voltages (<= 2400 V) • Standard capacitors are typically not available at 1380 V Distribution systems (pole top) • Units are configured with a single series group of capacitors with capacitors rated phase to phase Therefore unbalancewith capacitors rated phase-to-phase. Therefore, unbalance detection is not required.
  • 59. Capacitor Application Wye – Solidly Grounded • Initial cost of the bank may be lower since the neutral does not have to be insulated from groundhave to be insulated from ground. • Capacitor switch recovery voltages are reduced • High inrush currents may occur in the station ground system Th d d id l i d f l• The grounded-wye arrangement provides a low-impedance fault path which may require revision to the existing system ground protection scheme. Typically not applied to ungrounded systems.p yp y pp g y • When applied to resistance-grounded systems, difficulty in coordination between capacitor fuses and upstream ground protection relays (consider coordination of 40 A fuse with a 400 Aprotection relays (consider coordination of 40 A fuse with a 400 A grounded system). • Typical for smaller installations (since auxiliary equipment is not i d)required)
  • 60. Capacitor Application The most common capacitor bank configurations for larger substation applications are Wye-Ungrounded Three of the most common unbalance protection schemes are shown. Discussion of the protection schemes will be presented later.
  • 61. Capacitor Protection Fusing • Fuseless I t ll F d• Internally Fused • Externally Fused
  • 62. Capacitor Protection B k P t ti SBank Protection Summary
  • 63. Capacitor Protection Fuseless Capacitors Constr cted of small capacitor elements hich are arranged inConstructed of small capacitor elements which are arranged in series and parallel. The elements are constructed of aluminum foil with a dielectric of electrical grade polypropylene. This design provides a safe failure mode. In the event that the dielectric fails, the energy in the resulting small arc punctures many layers of the thin film and foil within the element. Themany layers of the thin film and foil within the element. The arc causes the film layer to receded allowing many layers of the aluminum foil electrodes to touch and weld together forming an electrically stable electrical joint This results in an entireelectrically stable electrical joint. This results in an entire series section being shorted.
  • 64. Capacitor Protection Example of Fuseless Installation
  • 65. Capacitor Protection Internally Fused Capacitors Constr cted s ch that each elementConstructed such that each element is protected with a series connected current limiting fuse. The design is such that isolated fusing prevents potential damage to the adjacent elements andto the adjacent elements and fuses. The current limiting mode chops the fault current to prevent the energy stored in the parallelthe energy stored in the parallel connected elements from being discharged into the faulted element.
  • 67. Capacitor Protection Group Fusing– Considerations for Selecting Fuse (typical for distribution pole mounted racks) • Continuous Current• Continuous Current • Transient Current • Fault Current k C C di i• Tank Rupture Curve Coordination • Voltage on Good Capacitors
  • 68. Capacitor Protection Continuous Current • For wye-solidly grounded systems: Fuse > = 135% of rated capacitor current (includes overvoltage, capacitor tolerances, and harmonics). • For wye-ungrounded systems: Fuse > = 125% of ratedy g y capacitor current (includes overvoltage, capacitor tolerances, and harmonics). Care should be taken when using NEMA Type T and K tin links which are rated 150%. In this case, the divide the fuse rating by 1.50.g y
  • 69. Capacitor Protection Transient Current • Capacitor switching (specifically back-to-back switching) • Lightning surges Back-to-back is typically not a factor for pole mounted capacitorsyp y p p banks. High frequency lightning surges:High frequency lightning surges: Use NEMA T tin links for ampere ratings up to 25 A. Use NEMA K tin links for ampere ratings above 25 A.
  • 70. Capacitor Protection Fault Current Ensure that the fuse can interrupt the available fault current Tank Rupture Coordination Ensure that the fuse maximum clearing TCC curve for the fuseg link is plotted below the capacitor tank rupture curve. In cases of high fault currents, the tank rupture curve should be compensated for asymmetryfor asymmetry. Voltage on Good Capacitors d d f l h l iFor an ungrounded system, a fault on one phase results in a 1.73 times overvoltage on the un-faulted phases. Ensure that the fault is cleared before the second capacitor failure.p
  • 71. Capacitor Protection Problems with Fusing of Small Ungrounded Banks Consider a 12.47 kV, 1500 kVAR cap bank made of three (3) 500 kVAR i l h i500 kVAR single-phase units. FuseAAA kV kVAR ][100][1045.144.69][44.69 ][47.123 ][1500   kV ][47.123 If a capacitor fails, we will expect approximately 3x line current. It will take a 100 A fuse approximately 500 seconds to clear thispp y fault (3 x 69.44 A = 208.32 A). The capacitor case will rupture long before the fuse clears the fault. The solution is using smaller units (explanation to follow).
  • 72. Capacitor Protection Individual Fusing– Considerations for Selecting Fuse (typical for substation capacitor banks) • Continuous Current• Continuous Current • Transient Current • Fault Current • Tank Rupture Curve Coordination • Voltage on Good Capacitors • Energy Discharge into Faulted UnitEnergy Discharge into Faulted Unit • Outrush Current • Coordination with Unbalance Detection System
  • 73. Capacitor Protection Continuous Current • Fuse > = 135% of rated capacitor current (includes overvoltage, capacitor tolerances, and harmonics) Care should be taken when using NEMA Type T and K tin links which are rated 150% In this case the divide the fuse rating by 1 50150%. In this case, the divide the fuse rating by 1.50.
  • 74. Capacitor Protection Transient Current • Lightning surges • Capacitor switching (specifically back-to-back switching) High magnitude, high frequency lightning surges are typically notg g , g q y g g g yp y a concern for substation installations. Back to back switching is typically controlled with pre insertionBack-to-back switching is typically controlled with pre-insertion closing resistors or current limiting reactors. h f i ll i h ll l f ill h hBy the nature of installation, the parallel fuses will share the transient current and will not be a factor.
  • 75. Capacitor Protection Fault Current Ensure that the fuse can interrupt the available fault current. In substation banks with multiple series groups, fault current will not flow through a failed capacitor unit unless other unitsg p experience a simultaneous failure. For this reason expulsion fuses are commonly used rather than current limiting fuses Tank Rupture Coordination Ensure that the fuse maximum clearing TCC curve for the fuse li k i l d b l h i k flink is plotted below the capacitor tank rupture curve. In cases of high fault currents, the tank rupture curve should be compensated for asymmetry.y y
  • 76. Capacitor Protection Example of a DefiniteExample of a Definite Tank Rupture Curve. Th i b hThe time between the rupture curve and the fuse maximum clear curve is the coordination margin.
  • 77. Capacitor Protection Example of a 10% and 50% Rupture Curve for a 100 kVARRupture Curve for a 100 kVAR Capacitor. Probability based tank rupturey p curves are developed when there is too much variance in rupture test data. Based on the 10% and 50% curves, one can extrapolate the f b bilicurves for any probability.
  • 78. Capacitor Protection Voltage on Good Capacitors When a short-circuit on one unit occurs, an overvoltage results on the un-faulted phases. Ensure that the fault is cleared before the second capacitor failure. A table summarizes this voltage rise on the un-faulted units Per Unit Voltage on Un-failed Capacitors
  • 79. Capacitor Protection Energy Discharge Into a Failed Unit When a capacitor failure occurs, the stored energy in the parallel connected capacitors can discharge thro gh the failed capacitorconnected capacitors can discharge through the failed capacitor and its fuse. The total calculated parallel stored energy should not exceed the energy capability (Joule rating) of the capacitor and fuse. If the energy capabilities are exceeded, a failure of the fuse and/or rupture of the capacitor tank can result. Typical rating of film capacitors is 15,000 Joules (4650 kVAR in parallel) and 10,000 Joules (3100 kVAR in parallel) for paper- film capacitors Expulsion fuses are typically rated 30 000film capacitors. Expulsion fuses are typically rated 30,000 Joules. Current limiting fuses are required if ratings are exceeded. (1 Joule = 1 W x sec use 0 2 cycle clearing time for calculation)(1 Joule = 1 W x sec, use 0.2 cycle clearing time for calculation)
  • 80. Capacitor Protection Outrush Current When a capacitor failure occurs, the parallel connected capacitors can discharge high frequency current into the failed capacitor. The fuses of the un-failed capacitors should be able to withstand the high frequency discharge currents. These calculations andg q y g measurements are complex and are determined by the manufacturer. Coordination with Unbalance Detection Scheme The individual fuse must clear the fault before the unbalance i h i h i i b kprotection scheme trips the entire capacitor bank.
  • 82. Capacitor Protection Recall Problem with Fusing of Small Ungrounded Banks 12.47 kV, 1500 kVAR cap bank made of three (3) 500 kVAR units FuseAAA kV kVAR ][100][1045.144.69][44.69 ][47.123 ][1500   It will take a 100 A fuse approximately 500 seconds to clear thisIt will take a 100 A fuse approximately 500 seconds to clear this fault (3 x 69.44 A = 208.32 A). The capacitor case will rupture long before the fuse clears the fault. The solution is using smaller units with individual fusing. Consider five (5) 100 kVAR capacitors per phase, each with a( ) p p p , 25 A fuse. The clear time for a 25 A fuse @ 208.32 A is below the published capacitor rupture curve.
  • 83. Capacitor Protection Why is the Current 3 x Nominal Line Current for a Phase-to- Neutral Fault on a Wye-Ungrounded Capacitor Bank? A B A B V A C N A N VNG C C I 3 0 Since V = I*Z, where Z is t t ( i f 60 h ) IA = 3.0 p.u.constant (assuming f = 60 hz) If voltage across capacitor is increased by 1.732, the current also increases by factor of 1.732y
  • 84. Capacitor Protection Minimum Conductor Size It was noted that capacitors are rated 135% of rating. This requires the conductor to be sized 135% of the nominal capacitor ratingrating.
  • 85. Capacitor Protection Unbalance Protection As single-phase units in a multiple unit/phase installation fail and are removed from service the remaining units are experience anare removed from service, the remaining units are experience an overvoltage condition. IEEE Standard 1036 provides overvoltage limitations. Duration Max Voltage (x rated RMS) 6 cycles 2.20 15 c cles 2 0015 cycles 2.00 1 s 1.70 15 sec 1.40 1 min 1.301 min 1.30 An unbalance protection scheme must by implemented to prevent the failure of the overvoltaged units.g
  • 87. Capacitor Protection Neutral Voltage Unbalance with Unbalance Compensation
  • 88. Capacitor Protection VA V V VN VG VNG Normal Conditions VN = VG VAN = VBN = VCN VC VB VAN VBN VCN
  • 89. Capacitor Protection Ungrounded or Impedance Grounded System VA V V VN VG VNG Normal Conditions VN = VG VAN = VBN = VCN = 1.0 p.u. VC VB VAN VBN VCN .0 p.u.
  • 90. Capacitor Protection VVNG Phase to Neutral FaultPhase to Neutral Fault VNG = VLN VAN = VBN = VLL = 1.732 p.u.
  • 91. Capacitor Protection VA V VNVG VNG One Can Removed VNG = 0.2 p.u. V = 1 2 p u VC VB VCN = 1.2 p.u.
  • 92. Capacitor Protection Ungrounded or Impedance Grounded System VA V V VN VG VNG Normal Conditions VN = VG VAN = VBN = VCN = 1.0 p.u. VC VB VAN VBN VCN .0 p.u.
  • 93. Capacitor Protection Ungrounded or Impedance Grounded System VA V Gnd VN VNG VC VB Ground Fault VNG = VLN V = V = V = 1 732 p u VC =VG Ground Fault at Cap Bank or A h h SVAG = VBG = VLL = 1.732 p.u. Anywhere on the System
  • 94. Capacitor Protection Wye-Ungrounded: Voltage Between Capacitor Bank Neutral and Ground vs. Percentage of Capacitor Units Removed from Series Group
  • 95. Capacitor Protection Wye-Ungrounded: Voltage on Remaining Capacitor Units in Series Group vs. Percentage of Capacitor Units Removed from Series Group
  • 96. Capacitor Protection Wye-Grounded: Neutral Current vs Percentage of Capacitor Units Removed from Series Group
  • 97. Capacitor Protection Wye-Grounded or Delta: Voltage on Remaining Units in Series Group vs. Percentage of Capacitor Units Removed from Series Group
  • 98. Capacitor Protection Double Wye-Ungrounded, Neutrals Tied Together: Neutral Current vs. Percentage of Capacitor Units Removed from Series Group
  • 99. Capacitor Protection Double Wye-Ungrounded, Neutrals Tied Together: Voltage on Remaining Capacitor Units in Series vs. Percentage of Capacitor Units Removed from Series Group
  • 100. Capacitor Protection A phase B phase C phase P: Number of units in groupunits in group (P=6) S: Number ofS: Number of series groups (S=4) Reference Figure for Calculations to Follow
  • 101. Capacitor Protection # of Series Groups Grounded Y or Delta Ungrounded Y Split Ungrounded Y (equal sections) 1 - 4 21 4 2 2 6 8 7 3 8 9 8 4 9 10 9 5 9 10 10 6 10 10 10 7 10 10 10 8 10 11 10 9 10 11 10 10 10 11 11 11 10 11 11 12 and over 11 11 11 Minimum recommended number of units in parallel per series Group to limit voltage on remaining units to 110% with one unit out
  • 102. Capacitor Protection Many more configurations and calculations shown in IEEE C37.99
  • 104. Capacitor Fundamentals Further discussion on capacitor voltage ratings: On a ungrounded or impedance grounded system, a ground fault on one phase will cause the other two phases will be elevated by 1 7321.732. Does this mean that capacitors must be rated phase-to-phase? Certainly nothing wrong with this, but cost will be significantly higher.g
  • 105. Capacitor Fundamentals Recall: X V S 2  CX This means that a 150 kVAR 12470 V unit applied at 7200 VThis means that a 150 kVAR, 12470 V unit applied at 7200 V will provide only 50 kVAR. ][50 ][150 ][12470 ][7200 2 2 kVARS kVAR V V SNEW  ][50 kVARSNEW 
  • 106. Capacitor Fundamentals Using 12470 V capacitors on a 12470 V Ungrounded or Resistance-Grounded System will require 3x more cans.y q It should be noted that the 12470 V cans will also be larger than the 7200 V cansthe 7200 V cans. Results in a much larger and more costly installation. This solution would be required if a ground fault could be maintained for extended periods of time.p
  • 107. Capacitor Fundamentals Perhaps a 150 kVAR or 200 kVAR, 7620 V or 7960 V units applied at 7200 V would be a better solution. ][150 ][7620 ][7200 2 2 kVAR V V SNEW  ][200 ][7620 ][7200 2 2 kVAR V V SNEW  ][134 OR kVARSNEW  ][178 2 OR kVARSNEW  ][123 ][150 ][7960 ][7200 2 2 kVARS kVAR V V SNEW  ][163 ][ ][7960 ][7200 2 2 kVARS kVAR V V SNEW   ][123 kVARSNEW  Note that the 7620 V unit provides an additional 6% The 7960 V unit provides an additional 11% ][163 kVARSNEW  The 7960 V unit provides an additional 11%
  • 108. Capacitor Fundamentals Explusion Fuses: Provides a means of disconnecting a failed capacitor from the circuit by melting a tin-lead low current link. The shorted capacitor unit causes a large increase in the current through the fuse. The current is limited only by the power system reactance and the other capacitor units in series with the failed capacitor unit. Thereactance and the other capacitor units in series with the failed capacitor unit. The pressure is generated by the hot arc making contact with the fiber lining of the fuse tube. The link is cooled and stretched as it is forced out the tube. The fuse continues to conduct until a natural current zero occurs. The current zero is d b th t f lt t i If th itcaused by the power system fault current crossing zero. If other capacitors are connected in parallel with the failed unit, all the stored energy in these capacitors will be absorbed in either the fuse operation or the failed capacitor unit. Most of the energy is absorbed in the failed capacitor.gy p
  • 109. Capacitor Fundamentals Current Limiting Fuses: Uses a long uniform cross section element. This configuration makes the fuse a current chopping fuse. The fuse develops a back voltage per inch of element across the entire length of the element. When this voltage exceeds the available voltage across the fuse, the fuse forces the arc to extinguish. The result is that avoltage across the fuse, the fuse forces the arc to extinguish. The result is that a trapped voltage may and probably will remain on the other capacitors in the series group. The fuse by its design avoids absorbing all of the available energy on the series group. This fuse is used for capacitor banks with a large number of ll l it It b d li ti ith ti ll i fi it ll lparallel capacitors. It can be used on applications with essentially infinite parallel stored energy, as long as sufficient back voltage can be developed to force the current to extinguish. This is the fuse we apply to series, large shunt, and DC banks. Because of the high back voltage that is developed, this fuse must be used with several capacitors in parallel to limit the voltage build up or a flashover may occur elsewhere in the capacitor rackoccur elsewhere in the capacitor rack.
  • 110. Capacitor Fundamentals Current Limiting Fuses vs Expulsion Fuses: C Li i i FExpulsion Fuse Current Limiting Fuse
  • 111. Capacitor Fundamentals Current Limiting Fuses vs Expulsion Fuses: Expulsion Fuses Operate mechanically and provide a visual indication Require additional space for operationRequire additional space for operation Typically applied for outdoor application due to ionized gas release. C bi ti l i ith t li iti h t i ti f b d iCombination expulsion with current limiting characteristic fuses can be used in indoor metal-enclosed equipment. Less expensivep
  • 113. Capacitor Fundamentals Current Limiting Fuses Do not emit ionized gases during operation Ionized gases are undesirableDo not emit ionized gases during operation. Ionized gases are undesirable because they can cause bushing and insulator flashovers that result in additional damage. Do not require ventilation. Fast current-limiting operation High interrupting capacity, noiseless operation Can be specified for indoor and outdoor applications . No pressure build-up, therefore, no vents or special reinforced compartments are i drequired. More expensive
  • 114. Capacitor Fundamentals Note no pigtail and blown fuse indication
  • 116. Capacitor Fundamentals What about arresters? How and where should they be applied?applied? Depending on application, environment, exposure to switching etc arresters may be necessaryswitching, etc, arresters may be necessary. We recall that when a travelling wave meets a high impedance, the wave can double in size. For this reason, arresters (if used) should be installed as close to the capacitor bank as possible. Installation of arresters at the breakerp feeding the capacitor bank will not do much for protection of the capacitor bank.
  • 117. Capacitor Protection A basic three (3) arrester method is shown below. This is typical for solidly grounded systems and wye-groundedtypical for solidly grounded systems and wye grounded capacitor banks.
  • 118. Capacitor Protection Depending on type of installation, system parameters and level of protection required, a six(6) arrestor method may belevel of protection required, a six(6) arrestor method may be applied.
  • 119. Capacitor Protection For an ungrounded system or a high-impedance grounded system, a four (4) arrestor grounding method might besystem, a four (4) arrestor grounding method might be considered an wye ungrounded bank. Phase to Neutral Fault VNG = VLNNG LN VAN = VBN = VLL = 1.732 p.u. Ground Fault VNG = VLN VLL VLL ArrNG LN VAG = VBG = VLL = 1.732 p.u. If faults can be maintained, ArrN V ArrPH ArrPH must be rated VLL ArrN must be rated VLN The effective arrester MCOV N is VLL + VLN
  • 120. Capacitor Protection Note that if a basic three (3) arrester method is applied to an ungrounded bank, the arresters must be rated high enough to sustain a temporary overvoltage condition during a phase-to- ground fault on the system. This may not provide an adequate level of protection for the capacitors. Phase to Neutral Fault VNG = VLN V V V 1 732VAN = VBN = VLL = 1.732 p.u. Ground Fault VNG = VLN V V V 1 732 VLL VLL VAG = VBG = VLL = 1.732 p.u. If faults can be maintained, Arresters must be rated VLL V Arresters do not provide protection across the capacitor bushings. Note that the BIL applies to bushing-to- i l ticase insulation.
  • 121. Capacitor Protection Good Presentations on Capacitor – Arrester Applications “G id li f S l ti f S A t f Sh t“Guidelines for Selection of Surge Arresters for Shunt Capacitor Banks” – ABB Technical Information “Surge Arrester Application of MV-Capacitor Banks to Mitigate Problems of Switching Restrike” – CIRED 19th International Conference on Electricity Distribution ViennaInternational Conference on Electricity Distribution, Vienna, 21-24 May 2007. B th f th l dd h t h tBoth of these papers also address phase-to-phase arrester connections.
  • 123. Harmonics Recall that the impedance of a capacitor is inversely proportional to the system frequencyproportional to the system frequency. fCC XC  2 11  fCC  2 Harmonics flow to the point of lowest impedance. The higher the harmonic the lower the impedance of the capacitorthe harmonic, the lower the impedance of the capacitor. As capacitors absorb harmonics, the capacitor heats up and th lif t i d d Th lt h i tthe life expectancy is reduced. The voltage harmonics stress the capacitor dielectric and reduce the life expectancy of the capacitor.
  • 125. Harmonics Where do harmonics come from? • Power Electronics (drives, rectifiers, computer power supplies, etc) • Arcing Devices (welders, arc furnaces, florescent lights, etc)g ( , , g , ) • Iron Saturating Devices (transformers) • Rotating Machines (Generators) • Parallel Resonance (between cap bank and power• Parallel Resonance (between cap bank and power equipment) IEEE Std 519 provides recommended limits of harmonic distortion at the point-of-common-coupling (PCC) with the utility.y
  • 128. Harmonics Resonance When a number of harmonic current sources are injecting currents into the supply and the frequency of one of the harmonics coincides with the resonant frequency of the supply transformer andwith the resonant frequency of the supply transformer and Power Factor Correction capacitor combination, the system resonates and a large circulating harmonic current is excited between these components The result of this is that a largebetween these components. The result of this is that a large current at this harmonic flows in the supply transformer, this resulting in a large harmonic voltage distortion being imposed upon the load voltage.
  • 129. Harmonics A study should be performed to determine levels of harmonics on ay p system to determine if any filters are necessary when installing a capacitor bank. Care should be taken to determine if the filtered capacitor bank will introduce any resonance problems. If resonance problems exist, the fil d i b dj dfilter design must be adjusted.
  • 130. Harmonics An example of a 13 8 kV harmonic filterAn example of a 13.8 kV harmonic filter
  • 131. Capacitor Bank Design Considerations
  • 132. Design Considerations So how do we size a capacitor bank? D t i i lDetermine your primary goal • Voltage support • Lower utility bill (avoid penalties) • Increase capacity of system It can be all three, or any combination of the above.It can be all three, or any combination of the above. Note that correcting to unity power factor at maximum load is tl d t bcostly and may not be necessary.
  • 133. Design Considerations For a 20 MVA load at 0 88 power factor (17 6 MW 9 5 MVAR)For a 20 MVA load at 0.88 power factor (17.6 MW, 9.5 MVAR) To achieve 95% power factor, a 3.72 MVAR bank is required To achieve 98% power factor, a 5.93 MVAR bank is required To achieve unity power factor, a 9.50 MVAR bank is required
  • 134. Design Considerations Determine if current limiting reactors or tuning reactors areDetermine if current limiting reactors or tuning reactors are required. Harmonics and resonance may dictate tuning reactors Back-to-back switching may require current limiting reactorsBack to back switching may require current limiting reactors (unless another method is used to mitigate the switching surges, i.e. pre-insertion closing resistors/reactors, zero-crossing breakers etc)breakers, etc)
  • 135. Design Considerations Determine the proper voltage. Capacitors are very susceptible to voltage transients and harmonics. Increasing the rated voltage increases the protective margin on the insulation.margin on the insulation. The voltage at the capacitor terminals will be higher than bus lt if t tili d It i i t t t t f thivoltage if reactors are utilized. It is important to account for this voltage difference. Determine the voltage swing of the system. Will the capacitors remain on-line while the facility is lightly loaded.
  • 136. Design Considerations We listed some reasons for specifying higher than bus nominalWe listed some reasons for specifying higher than bus nominal rating of capacitors. However, care must be taken to ensure that the kVAR rating is properly adjusted as a result. Three (6) 150 kVAR, 7960 V wye-connected capacitors provide a nominal 901 kVAR when connected to a 13.8 kV bus. Three (6) 150 kVAR, 8320 V wye-connected capacitors provide a nominal 825 kVAR when connected to a 13 8 kV busnominal 825 kVAR when connected to a 13.8 kV bus
  • 137. Design Considerations Determine optimal size and number of stages. D di i i l t l d i l b k i d f f llDepending on swing in plant load, a single bank sized for full plant capacity may not be the answer. IEEE 1036 recommends limiting the voltage change to 2-3%. The delta voltage can be estimated by: MVAR Switch of a capacitor applies high stresses to the insulation %100 SCMVA MVAR V Switch of a capacitor applies high stresses to the insulation. Limiting the number of stages and limiting the frequency of switching will increase the life. Ideally, a capacitor is switched on and left on.
  • 138. Design Considerations Determine best location for the installation The most effectiveDetermine best location for the installation. The most effective placement for power factor correction capacitor banks is at the load. However, this is not always practical or cost effective. Typically, a capacitor bank is installed on each bus of a main-tie- main switchgear.main switchgear. If capacitors are installed at the motor pecker head (running capacitors) ensure that the capacitor VAR rating does not exceedcapacitors), ensure that the capacitor VAR rating does not exceed 90% of the motor no-load VAR. Otherwise, it is possible to damage the motor by overexcitation.
  • 139. Design Considerations Use caution when sizing motor running capacitors. Logic would suggest that installation of a power factor correction capacitor at the motor terminals sized to provide unity power factor makes sense.y p THIS IS NOT THE CASE. Do not exceed 90% of the motor no load kVAR demand Exceeding this value canmotor no-load kVAR demand. Exceeding this value can result in damage to the motor insulation as a result of overexcitation.
  • 140. Design Considerations As an example for a 4000 V, 4000 hp motor: 100% load current = 495 A @ 89.7% pf 100% load kVAR = 1516 kVAR No load current = 117 A @ 6.3 % pf No load kVAR = 809 kVAR Max size of running capacitor is 0 90 x 809 kVAR = 728 kVARMax size of running capacitor is 0.90 x 809 kVAR = 728 kVAR
  • 141. Design Considerations M: Motor Magnetizing CurveM: Motor Magnetizing Curve C1: Capacitor size at 100% motor mag current C2: Capacitor sized > 100% motor mag current C4: Capacitor sized < 100% motor mag current If the capacitive reactance of the capacitor is less less than that of the motor reactance (this occurs when to large of a capacitor is chosen). This combination of reactance will result in a resonant frequency below 60 hertz Therefore as the motor slows in speed the frequency of the motorfrequency below 60 hertz. Therefore, as the motor slows in speed, the frequency of the motor terminal voltage will decrease from a value of near 60 hertz toward zero. When the motor's terminal voltage frequency passes through the resonant frequency setup between the capacitor reactance and the motor reactance, the terminal voltage will become very high, only limited by the properties of the iron Depending on the inertia of the motor this resonance (or high voltage) may be present for airon. Depending on the inertia of the motor, this resonance (or high voltage) may be present for a considerable period of time.
  • 142. Design Considerations Determine the most optimal type of installationDetermine the most optimal type of installation. Will the capacitor bank be installed within a fenced substation? Metal-enclosed, pad mount, or open rack may be good choices Will the capacitor bank be installed in a process area?Will the capacitor bank be installed in a process area? Metal-enclosed or pad mount may be good choices Will the capacitor bank be pole mounted on a distribution line?Will the capacitor bank be pole mounted on a distribution line?
  • 144. Design Considerations Consider the impact to personnel safety adjacent equipment when deciding between a metal-enclosed and open-rack system. Porcelain can resemble shrapnel when a capacitor bushing fails.
  • 145. Design Considerations Determine the most optimal configuration. Higher reliability costs more. 2400 kVAR, 13800 V, wye-grounded (1) 800 kVAR per phase, , y g ( ) p p bank will be a smaller footprint and cost less than 2400 kVAR 13800 V wye ungrounded (8) 100 kVAR per2400 kVAR, 13800 V, wye-ungrounded (8) 100 kVAR per phase bank. H h li bili f h d d b k iHowever, the reliability of the wye-ungrounded bank is significantly higher
  • 146. Design Considerations Determine the switching equipment When breakers are used for switching capacitors (single bank or back-to-back switching), the breakers must be rated for capacitor switching.p g IEEE C37.99 provides the equations for calculating the inrush current and frequencycurrent and frequency.
  • 148. Design Considerations Consider a single 4800 kVAR wye-ungrounded bank switched (with nominal inductance from equipment): 3253A pk @ 600 Hz, the product is 0.20 x 107 Switching a second similar bank on the same bus without current limiting reactor: 24,058 A pk @ 7.66 kHz, the product is 18.4 x 107 B ddi 100 H li i i h i h iBy adding a 100 mH current limiting reactor, the inrush is: 7254 A pk @ 2.31 kHz, the product is 1.7 x 107p @ , p
  • 151. Design Considerations Energization of a single capacitor bank.
  • 152. Design Considerations B k b k i hi f h iBack-to-back switching of the same unit.
  • 153. Design Considerations E l f b k i h i i iExample of breaker with pre-insertion resistor.
  • 155. Design Considerations A Pre-Insertion Manufacture’s Perspective.p
  • 156. Design Considerations Another concern is voltage amplification as a result of switching a second capacitor bank.
  • 158. Design Considerations Consider other accessories: • Disconnect switch • Grounding switch • Kirk-key interlocky • Ventilation requirements • Control power
  • 161. Design Considerations Be aware that larger medium voltage motors may include surge packs.g p The surge pack will decrease the crest voltage and rate of rise of the impending surge High rates of rise damage endrise of the impending surge. High rates of rise damage end turns while high crest voltage damage winding to core insulation. Typically the capacitance of the is small enough that it can be neglected, but this should be verified.g
  • 163. Design Considerations Do not confuse Harmonic Filter Banks with Power Factor Correction BanksCorrection Banks. The voltage ratings of harmonic filter banks are substantially higher because they are connected on the back end of a tuning reactor where the voltage is substantially higher. As a result of the higher voltage, the installed kVAR can be anywhere frome g e vo ge, e s ed V c be yw e e o 25% to 40% higher than nominal design. The capacitor cans must be capable of this outputThe capacitor cans must be capable of this output.
  • 164. Grounding of Wye Banks If multiple wye-grounded banks are in close proximity, use peninsula grounding or single-point grounding.p g g g p g g Single-Point Grounding The neutrals of all banks of a given voltage are connectedThe neutrals of all banks of a given voltage are connected together with insulated cable/bus and tied to the ground grid only at one point. This prevents high-frequency (d b k b k i hi ) f fl i icurrents (due to back-to-back switching) from flowing into the ground grid.
  • 165. Grounding of Wye Banks Peninsula Grounding One or more isolated ground grid conductors are carriedg g underneath the capacitor rack of each phase and tied to the station ground grid at one point at the edge of the capacitor area All capacitor bank neutral connections are made toarea. All capacitor bank neutral connections are made to this isolated peninsula ground grid conductor.
  • 168. References • IEEE Std. 18 • IEEE C37.99 • NEMA CP-1 • IEEE Std 1036 •IEEE Std 399 (Brown Book)IEEE Std 399 (Brown Book)