SlideShare a Scribd company logo
1 of 45
1
Power Factor Improvement
BY
Dr. Munthear Alqaderi
munthear@gmail.com
GENERAL EQUATION
FIG. 19.1 Defining the power delivered to a load.
RESISTIVE CIRCUIT
For a purely resistive circuit (such as that in
Fig. 19.2), v and i are in phase, and θ = 0°,
as appearing in Fig. 19.3.
FIG. 19.2 Determining the power delivered to a purely
resistive load.
RESISTIVE CIRCUIT
FIG. 19.3 Power versus time for a purely resistive load.
RESISTIVE CIRCUIT
FIG. 19.4 Example 19.1.
RESISTIVE CIRCUIT
FIG. 19.5 Power curve for Example 19.1.
APPARENT POWER
FIG. 19.6 Defining the apparent power to a load.
 Most plant loads are Inductive and require a magnetic field to
operate:
 Motors
 Transformers
 Florescent lighting
 The magnetic field is necessary, but produces no useful work
 The utility must supply the power to produce the magnetic field and
the power to produce the useful work: You pay for all of it!
 These two types of current are the ACTIVE and REACTIVE
components
ACTIVE & REACTIVE POWERS
Advantages of Phasor Analysis
0
2 2
Resistor ( ) ( )
( )
Inductor ( )
1 1
Capacitor ( ) (0)
C
Z = Impedance
R = Resistance
X = Reactance
X
Z = =arctan( )
t
v t Ri t V RI
di t
v t L V j LI
dt
i t dt v V I
j C
R jX Z
R X
R




 
 
 
   


Device Time Analysis Phasor
(Note: Z is a
complex number but
not a phasor)
INDUCTIVE CIRCUIT AND REACTIVE
POWER
FIG. 19.8 Defining the power level for a purely inductive
load.
INDUCTIVE CIRCUIT AND REACTIVE POWER
FIG. 19.9 The power curve for a purely inductive load.

Q
S
VARind
P
CAPACITIVE CIRCUIT
For a purely capacitive circuit (such as that
in Fig. 19.12), i leads v by 90°, as shown in
Fig. 19.13.
FIG. 19.12 Defining the power level for a purely capacitive
load.
CAPACITIVE CIRCUIT
FIG. 19.13 The power curve for a purely capacitive load.
S
Q

P
VARcap
Power Factor Fundamental
Definitions:
 Working /Active Power: Normally measured in
kilowatts (kW). It does the "work" for the system--
providing the motion, torque, heat, or whatever else
is required.
 Reactive Power: Normally measured in kilovolt-
amperes-reactive (kVAR), doesn't do useful "work."
It simply sustains the electromagnetic field.
 Apparent Power: Normally measured in kilovolt-
amperes (kVA). Working Power and Reactive
Power together make up apparent power.
Complex Power
 
*
cos( ) sin( )
P = Real Power (W, kW, MW)
Q = Reactive Power (var, kvar, Mvar)
S = Complex power (VA, kVA, MVA)
Power Factor (pf) = cos
If current leads voltage then pf is leading
If current
V I V I
V I
S V I j
P jQ
   

  




lags voltage then pf is lagging
(Note: S is a complex number but not a phasor)
Power Factor
P
I
V
(a) Purely Resistive Load (b) Resistive and Reactive Load
Pav = VavIav cos()
Power Factor:The Beer Analogy
Mug Capacity = Apparent Power (KVA)
Foam = Reactive Power (KVAR)
Beer = Real Power (kW)
Power Factor =
Beer (kW)
Mug Capacity (KVA)
Capacitors provide the Foam (KVAR),
freeing up Mug Capacity so you don’t have
to buy a bigger mug and/or so you can pay
less for your beer !
kVAR
Reactive
Power
kW
Active
Power
kVA
Apparent
Power
18
WHAT IS POWER FACTOR?
Power Factor is the ratio of ACTIVE
POWER to the TOTAL POWER (apparent
power):
= Active Power = P
Total Power S
S = Total power of Generator (or used)
P = Power consumed in the load (active power)
Q = Reactive power stored in magnetic field. Or
wasted power
Power Factor
19
WHAT IS POWER FACTOR?
Vectorial Representation:
S P.Q Φ
P
S
Q
j=90o
Generator
Load
Total power = S = VI = (units = KVA)
Active power = P = VI CosΦ = (units = KW)
Reactive power= Q = VI SinΦ = (units = KVAR)
Φ
V
I
V = Voltage : Volts
I = Current : Ampere
Φ = Physical displacement of V&I
Power Factor = CosΦ
20
HOW TO IMPROVE THE
POWER FACTOR ?
The power factor can be improved by
supplying KVAR to the loads (inductive type)
“Capacitor is source of KVARs”
Therefore the power factor of connected load
can be improved by installing power factor
improvement capacitors/capacitor banks
59.7 kV
17.6 MW
28.8 MVR
40.0 kV
16.0 MW
16.0 MVR
17.6 MW 16.0 MW
-16.0 MVR28.8 MVR
Power System Notation
Power system components are usually shown as
“one-line diagrams.” Previous circuit redrawn
Arrows are
used to
show loads
Generators are
shown as circles
Transmission lines
are shown as a
single line
Reactive Compensation
44.94 kV
16.8 MW
6.4 MVR
40.0 kV
16.0 MW
16.0 MVR
16.8 MW 16.0 MW
0.0 MVR6.4 MVR
16.0 MVR
Key idea of reactive compensation is to supply reactive
power locally. In the previous example this can
be done by adding a 16 Mvar capacitor at the load
Compensated circuit is identical to first example with
just real power load
Reactive Compensation, cont’d
 Reactive compensation decreased the line
flow from 564 Amps to 400 Amps. This has
advantages
 Lines losses, which are equal to I2 R decrease
 Lower current allows utility to use small wires, or alternatively, supply
more load over the same wires
 Voltage drop on the line is less
 Reactive compensation is used extensively by
utilities
 Capacitors can be used to “correct” a load’s
power factor to an arbitrary value.
24
HOW TO IMPROVE THE
POWER FACTOR ?
LOAD
LOW POWER FACTOR
LOAD
IMPROVED POWER FACTOR
CAPACITOR
Fig.I
Calculation
If the original inductive load has apparent
power S1, then
P = S1 cos 1 and Q1 = S1 sin 1 =
P tan 1
If we desired to increased the power
factor from cos1 to cos2 without
altering the real power, then the new
reactive power is
Q2 = P tan 2
The reduction in the reactive power is caused by the shunt
capacitor is given by
QC = Q1 – Q2 = P (tan 1 - tan 2)
26
Calculation
rms
2
21
rms
2
C
ωV
)tanθP(tanθ
ωV
Q
C


The value of the required shunt capacitance is
determined by the formula
Notice that the real power, P dissipated by the
load is not affected by the power factor correction
because the average power due to the capacitor
is zero
27
Example 11.15
When connected to a 120V (rms), 60Hz power line, a
load absorbs 4 kW at a lagging power factor of 0.8.
Find the value of capacitance necessary to raise the
pf to 0.95.
28
Solution
VA5000
8.0
4000
cos 1
1 

P
S
If the pf = 0.8 then,
cos1 = 0.8  1 = 36.87o
where 1 is the phase difference between the voltage and current.
We obtained the apparent power from the real power and the pf
as shown below.
The reactive power is
VAR300087.36sin5000sin 111  SQ
29
Solution
VA5.4210
95.0
4000
cos 2
2 

P
S
When the pf raised to 0.95,
cos2 = 0.95  2 = 18.19o
The real power P has not changed. But the apparent power has
changed. The new value is
The new reactive power is
VAR4.1314sin 222  SQ
30
Solution
VAR6.16854.1314300021  QQQC
The difference between the new and the old reactive power is
due to the parallel addition of the capacitor to the load.
The reactive power due to the capacitor is
The value of capacitance
added is
μF5.310
)120)(60(2
6.1685
22

 rms
C
V
Q
C
 In this example, demand
was reduced to 8250 kVA
from 10000 kVA.
 1750KVA Transformer
Capacity Release.
 The power factor was
improved from 80% to
97%
Before After
Why do we install Capacitors?
32
DISADVATAGES OF LOW
POWER FACTOR
1. For a given power to be supplied, the current
is increased.
2. The current thus increased in-return causes
increase in copper losses (PL=I2R) and
decrease in the efficiency of both apparatus
and the supply system, which results in
overloading and hence burning of the
associated equipment.
33
DISADVATAGES OF LOW
POWER FACTOR
3. Copper losses in transformers also increases.
4. Generators, transformers, switches, transmission
lines and other associated switchgear becomes
over-loaded.
5. Voltage regulation of generators, transformers
and transmission lines increases.
6. Hence, cost of generation, transmission and
distribution increases.
34
NATURAL POWER FACTORS
o CEILING FAN 0.5 TO 0.7
o CABIN FAN 0.5 TO 0.6
o EXAUST FAN 0.6 TO 0.7
o SEWING MACHINE 0.6 TO 0.7
o WASHING MACHINE 0.6 TO 0.7
o RADIO 0.9
o VACUUM CLEANER 0.6 TO 0.7
o TUBE LIGHT 0.5 TO 0.9
o CLOCK 0.9
o ELECTRONIC EQUIPMENT 0.4 TO 0.95
35
NATURAL POWER FACTORS
o NEON SIGN 0.5 TO 0.55
o WINDOW TYPE AIR CONDITIONER 0.62 TO 0.85
o HAIR DRYERS 0.7 TO 0.8
o LIQUIDISER 0.8
o MIXER 0.8
o COFFEE GRINDER 0.75
o REFRIGERATOR 0.65
o FREEZER 0.7
o SHAVER 0.6
o TABLE FAN 0.5 TO 0.6
36
NATURAL POWER FACTORS
o MERCURY VAPOUR LAMP O.4 TO 0.6
o INDUSTRIAL INDUCTION MOTOR:
◘ NO LOAD O.18
◘ 25% FULL LOAD 0.56
◘ 75% FULL LOAD 0.81
◘ 100% FULL LOAD 0.85
◘ 125% FULL LOAD 0.86
o COLD STORAGE O.76 TO 0.80
o CINEMAS 0.78 TO 0.80
o METAL PRESSING O.57 TO 0.72
MOTOR LOAD CHARACTERISTICS
38
NATURAL POWER FACTORS
o OIL MILLS O.51 TO 0.59
o WOOLEN MILLS O.70
o POTTERIES 0.61
o CIGARETTE MANUFACTURING 0.80
o FOUNDRIES 0.59
o STRUCTURAL ENGINEERING 0.53 TO 0.68
o CHEMICALS 0.72 TO 0.87
o MUNICIPAL PUMPING STATIONS 0.65 TO 0.75
o OIL TERMINALS 0.64 TO 0.83
o ROLLING MILLS 0.60 TO 0.72
39
NATURAL POWER FACTORS
o PLASTIC MOLDING 0.57 TO 0.73
o FILM STUDIOS O.65 TO 0.74
o HEAVY ENGINEERING WORK 0.48 TO 0.75
o RUBBER EXTRUSION AND MOLDING 0.48
o PHARMACEUTICALS 0.75 TO 0.86
o OIL AND PAINT MANUFACTURING 0.51 TO 0.69
o BISCUIT FACTORY 0.60
o LAUNDRIES 0.92
o FLOUR MILLS 0.61
o GLASS WORKS 0.87
40
NATURAL POWER FACTORS
o IRRIGATIONS PUMPS O.62 TO 0.80
o REPAIR SHOP, AUTOMATIC LATHE, 0.6
WORKSHOP, SPINNING MILLS,
WEAVING MILL
o WELDING SHOP 0.5 TO 0.6
o HEAT TREATMENT SHOP, STEEL 0.65 TO 0.8
WORKS, ROLLING MILLS
o TEXTILE 0.65 TO 0.75
o CEMENT 0.8 TO 0.85
o OFFICE BUILDING O.8 TO 0.85
Three Options for Applying Power Factor
Capacitors:
A) Fixed capacitors @ individual motors or @ MCC
B) Automatic Banks at Main Switch Board
C) De-tuned Automatic Capacitor Bank at Main Switch Board
M M M M M
A B C A
Harmonic
Source
e.g. Variable
Speed Drive
Capacitor Locations
42
ADVANTAGES OF POWER
FACTOR IMPROVEMENT
i. Adding capacitor, releases circuit capacity for
more load or relieves the overloaded circuit. The
capacitor KVAR per KVA of load increase is of
particular interest as this establishes the average
cost of supplying each additional KVA of load.
This cost can be compared with the cost per KVA
of increasing the transformer or supply circuit
rating and would justify the application of
capacitors.
PFI Capacitor’s addition, thus can be viewed in two lights.
43
ADVANTAGES OF POWER
FACTOR IMPROVEMENT
ii. Capacitors applied to given load reduce the I2R
losses in the supply circuit. For a 70 percent power
factor load with 40-KVAR of capacitors added for
each 100 KVA of circuit capacity, the I2R loss will
be 59% of its former value. The losses are not only
reduced in the circuit in which the capacitors are
applied but in all the circuit back to and including
the source generator.
44
ADVANTAGES OF POWER
FACTOR IMPROVEMENT
Automatic Power Factor improvement capacitors or
capacitor banks applied on the load end of circuit,
with lagging power factor (more than 95% loads),
have particular effects, one or more of which may be
the reason for the application.
1. Improves the power factor at the source.
2. Reduces system losses as current in
conductors decreases.
45
ADVANTAGES OF POWER
FACTOR IMPROVEMENT
3. Improves voltage level at the load.
4. Decreases KVA loading on the source.
5. Reduces investment in system facilities per
KW of load supplied.

More Related Content

What's hot

Series & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs DevicesSeries & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs Deviceskhemraj298
 
Economic operation of Power systems by Unit commitment
Economic operation of Power systems by Unit commitment Economic operation of Power systems by Unit commitment
Economic operation of Power systems by Unit commitment Pritesh Priyadarshi
 
DFIG BASED WIND TURBINE
DFIG BASED WIND TURBINEDFIG BASED WIND TURBINE
DFIG BASED WIND TURBINELogu Mani
 
Grid integration of the Wind Turbine Generator
Grid integration of the Wind Turbine GeneratorGrid integration of the Wind Turbine Generator
Grid integration of the Wind Turbine GeneratorPhani Kumar
 
power flow and optimal power flow
power flow and optimal power flowpower flow and optimal power flow
power flow and optimal power flowAhmed M. Elkholy
 
Principles of Power Systems V.K Mehta Complete Book - Chapter 4
Principles of Power Systems V.K Mehta Complete Book - Chapter 4Principles of Power Systems V.K Mehta Complete Book - Chapter 4
Principles of Power Systems V.K Mehta Complete Book - Chapter 4Power System Operation
 
Power System Planning
Power System PlanningPower System Planning
Power System Planninglinsstalex
 
Introduction to reactive power control in electrical power
Introduction to reactive power control in electrical powerIntroduction to reactive power control in electrical power
Introduction to reactive power control in electrical powerDr.Raja R
 
POWER SYSTEM PLANNING
POWER SYSTEM PLANNINGPOWER SYSTEM PLANNING
POWER SYSTEM PLANNINGNishaDangi99
 
Transient in Power system
Transient in Power systemTransient in Power system
Transient in Power systemPreet_patel
 
Grid Interconnection of Renewable Energy Sources at the Distribution Level Wi...
Grid Interconnection of Renewable Energy Sources at the Distribution Level Wi...Grid Interconnection of Renewable Energy Sources at the Distribution Level Wi...
Grid Interconnection of Renewable Energy Sources at the Distribution Level Wi...Pradeep Avanigadda
 

What's hot (20)

Introduction
IntroductionIntroduction
Introduction
 
Series & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs DevicesSeries & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs Devices
 
Facts devices power electronics
Facts devices power electronicsFacts devices power electronics
Facts devices power electronics
 
Economic operation of Power systems by Unit commitment
Economic operation of Power systems by Unit commitment Economic operation of Power systems by Unit commitment
Economic operation of Power systems by Unit commitment
 
DFIG BASED WIND TURBINE
DFIG BASED WIND TURBINEDFIG BASED WIND TURBINE
DFIG BASED WIND TURBINE
 
Grid integration of the Wind Turbine Generator
Grid integration of the Wind Turbine GeneratorGrid integration of the Wind Turbine Generator
Grid integration of the Wind Turbine Generator
 
power flow and optimal power flow
power flow and optimal power flowpower flow and optimal power flow
power flow and optimal power flow
 
Streamer theory
Streamer theoryStreamer theory
Streamer theory
 
Principles of Power Systems V.K Mehta Complete Book - Chapter 4
Principles of Power Systems V.K Mehta Complete Book - Chapter 4Principles of Power Systems V.K Mehta Complete Book - Chapter 4
Principles of Power Systems V.K Mehta Complete Book - Chapter 4
 
Power factor
Power factorPower factor
Power factor
 
Four Quadrant Metering
Four Quadrant MeteringFour Quadrant Metering
Four Quadrant Metering
 
Facts lectures-2014
Facts lectures-2014Facts lectures-2014
Facts lectures-2014
 
Power System Planning
Power System PlanningPower System Planning
Power System Planning
 
Introduction to reactive power control in electrical power
Introduction to reactive power control in electrical powerIntroduction to reactive power control in electrical power
Introduction to reactive power control in electrical power
 
Solar shading and its effects
Solar shading and its effectsSolar shading and its effects
Solar shading and its effects
 
Solar PV System
Solar PV SystemSolar PV System
Solar PV System
 
CHAPTER- 4.ppt
CHAPTER- 4.pptCHAPTER- 4.ppt
CHAPTER- 4.ppt
 
POWER SYSTEM PLANNING
POWER SYSTEM PLANNINGPOWER SYSTEM PLANNING
POWER SYSTEM PLANNING
 
Transient in Power system
Transient in Power systemTransient in Power system
Transient in Power system
 
Grid Interconnection of Renewable Energy Sources at the Distribution Level Wi...
Grid Interconnection of Renewable Energy Sources at the Distribution Level Wi...Grid Interconnection of Renewable Energy Sources at the Distribution Level Wi...
Grid Interconnection of Renewable Energy Sources at the Distribution Level Wi...
 

Viewers also liked

1590053 634881478003587500
1590053 6348814780035875001590053 634881478003587500
1590053 634881478003587500Navyasri Jiguru
 
Power factor improvement of an induction motor
Power factor improvement of an induction motorPower factor improvement of an induction motor
Power factor improvement of an induction motorIIT Roorkee
 
Power Factor
Power FactorPower Factor
Power FactorTim Cohen
 
Power Factor: what it is, how to measure it and how to improve it to reduce u...
Power Factor: what it is, how to measure it and how to improve it to reduce u...Power Factor: what it is, how to measure it and how to improve it to reduce u...
Power Factor: what it is, how to measure it and how to improve it to reduce u...Pulse Energy
 
Analysis of Power Factor Improvement Techniques in case of Non Linear System ...
Analysis of Power Factor Improvement Techniques in case of Non Linear System ...Analysis of Power Factor Improvement Techniques in case of Non Linear System ...
Analysis of Power Factor Improvement Techniques in case of Non Linear System ...Kaustubh Nande
 
Power Factor Basics
Power Factor BasicsPower Factor Basics
Power Factor Basicsno suhaila
 
Capacitor bank and improvement of power factor
Capacitor bank and improvement of power factorCapacitor bank and improvement of power factor
Capacitor bank and improvement of power factorAhshan Kabir
 
Automatic power factor controller by microcontroller
Automatic power factor controller by microcontrollerAutomatic power factor controller by microcontroller
Automatic power factor controller by microcontrollerSanket Shitole
 
automatic power factor controller
automatic power factor controllerautomatic power factor controller
automatic power factor controllersingh1515
 
Project report soofi
Project report soofiProject report soofi
Project report soofialmsoofi
 
Power factor & Power factor correction
Power factor & Power factor correctionPower factor & Power factor correction
Power factor & Power factor correctionLong Thang Pham
 
Economics of power generation
Economics of power generationEconomics of power generation
Economics of power generationAFAQAHMED JAMADAR
 
Micro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportMicro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportTheory to Practical
 
power factor correction using smart relay
power factor correction using smart relaypower factor correction using smart relay
power factor correction using smart relayHatem Seoudy
 
Product: Power Factor & Harmonics: StacoSine: Harmonics
Product: Power Factor & Harmonics: StacoSine: HarmonicsProduct: Power Factor & Harmonics: StacoSine: Harmonics
Product: Power Factor & Harmonics: StacoSine: HarmonicsStaco Energy
 
Power factor presentation
Power factor presentationPower factor presentation
Power factor presentationAzhar Abbas
 
Tarrif and load curves
Tarrif and load curvesTarrif and load curves
Tarrif and load curvesGPERI
 

Viewers also liked (20)

Power factor improvement
Power factor improvementPower factor improvement
Power factor improvement
 
1590053 634881478003587500
1590053 6348814780035875001590053 634881478003587500
1590053 634881478003587500
 
Power factor correction
Power factor correctionPower factor correction
Power factor correction
 
Power factor improvement of an induction motor
Power factor improvement of an induction motorPower factor improvement of an induction motor
Power factor improvement of an induction motor
 
Power Factor
Power FactorPower Factor
Power Factor
 
Power Factor: what it is, how to measure it and how to improve it to reduce u...
Power Factor: what it is, how to measure it and how to improve it to reduce u...Power Factor: what it is, how to measure it and how to improve it to reduce u...
Power Factor: what it is, how to measure it and how to improve it to reduce u...
 
Analysis of Power Factor Improvement Techniques in case of Non Linear System ...
Analysis of Power Factor Improvement Techniques in case of Non Linear System ...Analysis of Power Factor Improvement Techniques in case of Non Linear System ...
Analysis of Power Factor Improvement Techniques in case of Non Linear System ...
 
Power Factor Basics
Power Factor BasicsPower Factor Basics
Power Factor Basics
 
Capacitor bank and improvement of power factor
Capacitor bank and improvement of power factorCapacitor bank and improvement of power factor
Capacitor bank and improvement of power factor
 
Automatic power factor controller by microcontroller
Automatic power factor controller by microcontrollerAutomatic power factor controller by microcontroller
Automatic power factor controller by microcontroller
 
automatic power factor controller
automatic power factor controllerautomatic power factor controller
automatic power factor controller
 
Project report soofi
Project report soofiProject report soofi
Project report soofi
 
Power factor & Power factor correction
Power factor & Power factor correctionPower factor & Power factor correction
Power factor & Power factor correction
 
Economics of power generation
Economics of power generationEconomics of power generation
Economics of power generation
 
Micro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportMicro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System Report
 
power factor correction using smart relay
power factor correction using smart relaypower factor correction using smart relay
power factor correction using smart relay
 
Product: Power Factor & Harmonics: StacoSine: Harmonics
Product: Power Factor & Harmonics: StacoSine: HarmonicsProduct: Power Factor & Harmonics: StacoSine: Harmonics
Product: Power Factor & Harmonics: StacoSine: Harmonics
 
Power factor presentation
Power factor presentationPower factor presentation
Power factor presentation
 
Tarrif and load curves
Tarrif and load curvesTarrif and load curves
Tarrif and load curves
 
Power factor(r)
Power factor(r)Power factor(r)
Power factor(r)
 

Similar to Power Factor

BEF 23803 - Lecture 8 - Conservation of Complex Power.ppt
BEF 23803 - Lecture 8 - Conservation of Complex Power.pptBEF 23803 - Lecture 8 - Conservation of Complex Power.ppt
BEF 23803 - Lecture 8 - Conservation of Complex Power.pptLiewChiaPing
 
Chapter1 Questions
Chapter1 QuestionsChapter1 Questions
Chapter1 Questionsguest4ca222
 
PowerFactorImprovement.pptx
PowerFactorImprovement.pptxPowerFactorImprovement.pptx
PowerFactorImprovement.pptxRishab Saini
 
Power relationship (Electrical Engineering)
Power relationship (Electrical Engineering)Power relationship (Electrical Engineering)
Power relationship (Electrical Engineering)MOHAMMADSHOAIBBABAR
 
5 a new technique of pwm boost inverter for solar home application
5 a new technique of pwm boost inverter for solar home application5 a new technique of pwm boost inverter for solar home application
5 a new technique of pwm boost inverter for solar home applicationAbdo Brahmi
 
Transformer Efficiency
Transformer EfficiencyTransformer Efficiency
Transformer EfficiencyRidwanul Hoque
 
Emec 1 bank nee 301
Emec 1 bank nee 301Emec 1 bank nee 301
Emec 1 bank nee 301Ravi Anand
 
UNIT-III complex reactive three phase.ppt
UNIT-III complex reactive three phase.pptUNIT-III complex reactive three phase.ppt
UNIT-III complex reactive three phase.pptAbinaya Saraswathy T
 
Improvement of Load Power Factor by Using Capacitor
Improvement of Load Power Factor by Using CapacitorImprovement of Load Power Factor by Using Capacitor
Improvement of Load Power Factor by Using CapacitorIOSRJEEE
 
REACTIVE POWER
REACTIVE POWERREACTIVE POWER
REACTIVE POWERJeetDatta3
 
Reactive Power : Problems and Solutions
Reactive Power : Problems and SolutionsReactive Power : Problems and Solutions
Reactive Power : Problems and SolutionsAbhinav Dubey
 
Design and Development of Power Electronic Controller for Grid-connected PV A...
Design and Development of Power Electronic Controller for Grid-connected PV A...Design and Development of Power Electronic Controller for Grid-connected PV A...
Design and Development of Power Electronic Controller for Grid-connected PV A...IJAPEJOURNAL
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 

Similar to Power Factor (20)

Power factor
Power factorPower factor
Power factor
 
BEF 23803 - Lecture 8 - Conservation of Complex Power.ppt
BEF 23803 - Lecture 8 - Conservation of Complex Power.pptBEF 23803 - Lecture 8 - Conservation of Complex Power.ppt
BEF 23803 - Lecture 8 - Conservation of Complex Power.ppt
 
Practice questions
Practice questionsPractice questions
Practice questions
 
Chapter1 Questions
Chapter1 QuestionsChapter1 Questions
Chapter1 Questions
 
PowerFactorImprovement.pptx
PowerFactorImprovement.pptxPowerFactorImprovement.pptx
PowerFactorImprovement.pptx
 
capacitors
capacitorscapacitors
capacitors
 
2011 ced capacitors
2011 ced capacitors2011 ced capacitors
2011 ced capacitors
 
Power relationship (Electrical Engineering)
Power relationship (Electrical Engineering)Power relationship (Electrical Engineering)
Power relationship (Electrical Engineering)
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
8925273.ppt
8925273.ppt8925273.ppt
8925273.ppt
 
5 a new technique of pwm boost inverter for solar home application
5 a new technique of pwm boost inverter for solar home application5 a new technique of pwm boost inverter for solar home application
5 a new technique of pwm boost inverter for solar home application
 
Transformer Efficiency
Transformer EfficiencyTransformer Efficiency
Transformer Efficiency
 
Emec 1 bank nee 301
Emec 1 bank nee 301Emec 1 bank nee 301
Emec 1 bank nee 301
 
UNIT-III complex reactive three phase.ppt
UNIT-III complex reactive three phase.pptUNIT-III complex reactive three phase.ppt
UNIT-III complex reactive three phase.ppt
 
Improvement of Load Power Factor by Using Capacitor
Improvement of Load Power Factor by Using CapacitorImprovement of Load Power Factor by Using Capacitor
Improvement of Load Power Factor by Using Capacitor
 
REACTIVE POWER
REACTIVE POWERREACTIVE POWER
REACTIVE POWER
 
Reactive Power : Problems and Solutions
Reactive Power : Problems and SolutionsReactive Power : Problems and Solutions
Reactive Power : Problems and Solutions
 
Design and Development of Power Electronic Controller for Grid-connected PV A...
Design and Development of Power Electronic Controller for Grid-connected PV A...Design and Development of Power Electronic Controller for Grid-connected PV A...
Design and Development of Power Electronic Controller for Grid-connected PV A...
 
Mohsin rana
Mohsin ranaMohsin rana
Mohsin rana
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 

More from Dr. Munthear Alqaderi

مشروع أتمتة صوامع الحبوب
مشروع أتمتة  صوامع الحبوبمشروع أتمتة  صوامع الحبوب
مشروع أتمتة صوامع الحبوبDr. Munthear Alqaderi
 
نظام الاستشعار الحراري لمراقبة الحبوب
نظام الاستشعار الحراري لمراقبة الحبوبنظام الاستشعار الحراري لمراقبة الحبوب
نظام الاستشعار الحراري لمراقبة الحبوبDr. Munthear Alqaderi
 
نظام الاستشعار الحراري لمراقبة الحبوب
نظام الاستشعار الحراري لمراقبة الحبوبنظام الاستشعار الحراري لمراقبة الحبوب
نظام الاستشعار الحراري لمراقبة الحبوبDr. Munthear Alqaderi
 
ترشيد الاستهلاك الكهربائي المنزلي
ترشيد الاستهلاك الكهربائي المنزليترشيد الاستهلاك الكهربائي المنزلي
ترشيد الاستهلاك الكهربائي المنزليDr. Munthear Alqaderi
 
التحكم العصبوني العائم Neuro fuzzy systems
التحكم العصبوني العائم  Neuro  fuzzy systemsالتحكم العصبوني العائم  Neuro  fuzzy systems
التحكم العصبوني العائم Neuro fuzzy systemsDr. Munthear Alqaderi
 
إدارة المرافق وصيانتها
إدارة  المرافق وصيانتهاإدارة  المرافق وصيانتها
إدارة المرافق وصيانتهاDr. Munthear Alqaderi
 
دورة كتابة التقرير الفنية
دورة كتابة التقرير الفنيةدورة كتابة التقرير الفنية
دورة كتابة التقرير الفنيةDr. Munthear Alqaderi
 
دورة إدارة الجودة الشاملة
دورة إدارة الجودة الشاملة دورة إدارة الجودة الشاملة
دورة إدارة الجودة الشاملة Dr. Munthear Alqaderi
 
دراسة الجدوى الاقتصادية لمشروع
دراسة الجدوى الاقتصادية لمشروعدراسة الجدوى الاقتصادية لمشروع
دراسة الجدوى الاقتصادية لمشروعDr. Munthear Alqaderi
 

More from Dr. Munthear Alqaderi (20)

Short courses
Short coursesShort courses
Short courses
 
مشروع أتمتة صوامع الحبوب
مشروع أتمتة  صوامع الحبوبمشروع أتمتة  صوامع الحبوب
مشروع أتمتة صوامع الحبوب
 
نظام الاستشعار الحراري لمراقبة الحبوب
نظام الاستشعار الحراري لمراقبة الحبوبنظام الاستشعار الحراري لمراقبة الحبوب
نظام الاستشعار الحراري لمراقبة الحبوب
 
حاضنة البيض
حاضنة البيضحاضنة البيض
حاضنة البيض
 
نظام الاستشعار الحراري لمراقبة الحبوب
نظام الاستشعار الحراري لمراقبة الحبوبنظام الاستشعار الحراري لمراقبة الحبوب
نظام الاستشعار الحراري لمراقبة الحبوب
 
ترشيد الاستهلاك الكهربائي المنزلي
ترشيد الاستهلاك الكهربائي المنزليترشيد الاستهلاك الكهربائي المنزلي
ترشيد الاستهلاك الكهربائي المنزلي
 
التحكم العصبوني العائم Neuro fuzzy systems
التحكم العصبوني العائم  Neuro  fuzzy systemsالتحكم العصبوني العائم  Neuro  fuzzy systems
التحكم العصبوني العائم Neuro fuzzy systems
 
إدارة المرافق وصيانتها
إدارة  المرافق وصيانتهاإدارة  المرافق وصيانتها
إدارة المرافق وصيانتها
 
ادارة المرافق
ادارة المرافقادارة المرافق
ادارة المرافق
 
دورة كتابة التقرير الفنية
دورة كتابة التقرير الفنيةدورة كتابة التقرير الفنية
دورة كتابة التقرير الفنية
 
دورة إدارة الجودة الشاملة
دورة إدارة الجودة الشاملة دورة إدارة الجودة الشاملة
دورة إدارة الجودة الشاملة
 
دراسة الجدوى الاقتصادية لمشروع
دراسة الجدوى الاقتصادية لمشروعدراسة الجدوى الاقتصادية لمشروع
دراسة الجدوى الاقتصادية لمشروع
 
Scada course
Scada courseScada course
Scada course
 
Power management system course
Power management system coursePower management system course
Power management system course
 
Plc course level 1
Plc course level 1Plc course level 1
Plc course level 1
 
Industrial networks
Industrial networksIndustrial networks
Industrial networks
 
Fire alarm system
Fire alarm systemFire alarm system
Fire alarm system
 
Decision support system
Decision support systemDecision support system
Decision support system
 
Bms
BmsBms
Bms
 
Advanced maintenance planning
Advanced maintenance planningAdvanced maintenance planning
Advanced maintenance planning
 

Power Factor

  • 1. 1 Power Factor Improvement BY Dr. Munthear Alqaderi munthear@gmail.com
  • 2. GENERAL EQUATION FIG. 19.1 Defining the power delivered to a load.
  • 3. RESISTIVE CIRCUIT For a purely resistive circuit (such as that in Fig. 19.2), v and i are in phase, and θ = 0°, as appearing in Fig. 19.3. FIG. 19.2 Determining the power delivered to a purely resistive load.
  • 4. RESISTIVE CIRCUIT FIG. 19.3 Power versus time for a purely resistive load.
  • 6. RESISTIVE CIRCUIT FIG. 19.5 Power curve for Example 19.1.
  • 7. APPARENT POWER FIG. 19.6 Defining the apparent power to a load.
  • 8.  Most plant loads are Inductive and require a magnetic field to operate:  Motors  Transformers  Florescent lighting  The magnetic field is necessary, but produces no useful work  The utility must supply the power to produce the magnetic field and the power to produce the useful work: You pay for all of it!  These two types of current are the ACTIVE and REACTIVE components ACTIVE & REACTIVE POWERS
  • 9. Advantages of Phasor Analysis 0 2 2 Resistor ( ) ( ) ( ) Inductor ( ) 1 1 Capacitor ( ) (0) C Z = Impedance R = Resistance X = Reactance X Z = =arctan( ) t v t Ri t V RI di t v t L V j LI dt i t dt v V I j C R jX Z R X R                 Device Time Analysis Phasor (Note: Z is a complex number but not a phasor)
  • 10. INDUCTIVE CIRCUIT AND REACTIVE POWER FIG. 19.8 Defining the power level for a purely inductive load.
  • 11. INDUCTIVE CIRCUIT AND REACTIVE POWER FIG. 19.9 The power curve for a purely inductive load.  Q S VARind P
  • 12. CAPACITIVE CIRCUIT For a purely capacitive circuit (such as that in Fig. 19.12), i leads v by 90°, as shown in Fig. 19.13. FIG. 19.12 Defining the power level for a purely capacitive load.
  • 13. CAPACITIVE CIRCUIT FIG. 19.13 The power curve for a purely capacitive load. S Q  P VARcap
  • 14. Power Factor Fundamental Definitions:  Working /Active Power: Normally measured in kilowatts (kW). It does the "work" for the system-- providing the motion, torque, heat, or whatever else is required.  Reactive Power: Normally measured in kilovolt- amperes-reactive (kVAR), doesn't do useful "work." It simply sustains the electromagnetic field.  Apparent Power: Normally measured in kilovolt- amperes (kVA). Working Power and Reactive Power together make up apparent power.
  • 15. Complex Power   * cos( ) sin( ) P = Real Power (W, kW, MW) Q = Reactive Power (var, kvar, Mvar) S = Complex power (VA, kVA, MVA) Power Factor (pf) = cos If current leads voltage then pf is leading If current V I V I V I S V I j P jQ             lags voltage then pf is lagging (Note: S is a complex number but not a phasor)
  • 16. Power Factor P I V (a) Purely Resistive Load (b) Resistive and Reactive Load Pav = VavIav cos()
  • 17. Power Factor:The Beer Analogy Mug Capacity = Apparent Power (KVA) Foam = Reactive Power (KVAR) Beer = Real Power (kW) Power Factor = Beer (kW) Mug Capacity (KVA) Capacitors provide the Foam (KVAR), freeing up Mug Capacity so you don’t have to buy a bigger mug and/or so you can pay less for your beer ! kVAR Reactive Power kW Active Power kVA Apparent Power
  • 18. 18 WHAT IS POWER FACTOR? Power Factor is the ratio of ACTIVE POWER to the TOTAL POWER (apparent power): = Active Power = P Total Power S S = Total power of Generator (or used) P = Power consumed in the load (active power) Q = Reactive power stored in magnetic field. Or wasted power Power Factor
  • 19. 19 WHAT IS POWER FACTOR? Vectorial Representation: S P.Q Φ P S Q j=90o Generator Load Total power = S = VI = (units = KVA) Active power = P = VI CosΦ = (units = KW) Reactive power= Q = VI SinΦ = (units = KVAR) Φ V I V = Voltage : Volts I = Current : Ampere Φ = Physical displacement of V&I Power Factor = CosΦ
  • 20. 20 HOW TO IMPROVE THE POWER FACTOR ? The power factor can be improved by supplying KVAR to the loads (inductive type) “Capacitor is source of KVARs” Therefore the power factor of connected load can be improved by installing power factor improvement capacitors/capacitor banks
  • 21. 59.7 kV 17.6 MW 28.8 MVR 40.0 kV 16.0 MW 16.0 MVR 17.6 MW 16.0 MW -16.0 MVR28.8 MVR Power System Notation Power system components are usually shown as “one-line diagrams.” Previous circuit redrawn Arrows are used to show loads Generators are shown as circles Transmission lines are shown as a single line
  • 22. Reactive Compensation 44.94 kV 16.8 MW 6.4 MVR 40.0 kV 16.0 MW 16.0 MVR 16.8 MW 16.0 MW 0.0 MVR6.4 MVR 16.0 MVR Key idea of reactive compensation is to supply reactive power locally. In the previous example this can be done by adding a 16 Mvar capacitor at the load Compensated circuit is identical to first example with just real power load
  • 23. Reactive Compensation, cont’d  Reactive compensation decreased the line flow from 564 Amps to 400 Amps. This has advantages  Lines losses, which are equal to I2 R decrease  Lower current allows utility to use small wires, or alternatively, supply more load over the same wires  Voltage drop on the line is less  Reactive compensation is used extensively by utilities  Capacitors can be used to “correct” a load’s power factor to an arbitrary value.
  • 24. 24 HOW TO IMPROVE THE POWER FACTOR ? LOAD LOW POWER FACTOR LOAD IMPROVED POWER FACTOR CAPACITOR Fig.I
  • 25. Calculation If the original inductive load has apparent power S1, then P = S1 cos 1 and Q1 = S1 sin 1 = P tan 1 If we desired to increased the power factor from cos1 to cos2 without altering the real power, then the new reactive power is Q2 = P tan 2 The reduction in the reactive power is caused by the shunt capacitor is given by QC = Q1 – Q2 = P (tan 1 - tan 2)
  • 26. 26 Calculation rms 2 21 rms 2 C ωV )tanθP(tanθ ωV Q C   The value of the required shunt capacitance is determined by the formula Notice that the real power, P dissipated by the load is not affected by the power factor correction because the average power due to the capacitor is zero
  • 27. 27 Example 11.15 When connected to a 120V (rms), 60Hz power line, a load absorbs 4 kW at a lagging power factor of 0.8. Find the value of capacitance necessary to raise the pf to 0.95.
  • 28. 28 Solution VA5000 8.0 4000 cos 1 1   P S If the pf = 0.8 then, cos1 = 0.8  1 = 36.87o where 1 is the phase difference between the voltage and current. We obtained the apparent power from the real power and the pf as shown below. The reactive power is VAR300087.36sin5000sin 111  SQ
  • 29. 29 Solution VA5.4210 95.0 4000 cos 2 2   P S When the pf raised to 0.95, cos2 = 0.95  2 = 18.19o The real power P has not changed. But the apparent power has changed. The new value is The new reactive power is VAR4.1314sin 222  SQ
  • 30. 30 Solution VAR6.16854.1314300021  QQQC The difference between the new and the old reactive power is due to the parallel addition of the capacitor to the load. The reactive power due to the capacitor is The value of capacitance added is μF5.310 )120)(60(2 6.1685 22   rms C V Q C
  • 31.  In this example, demand was reduced to 8250 kVA from 10000 kVA.  1750KVA Transformer Capacity Release.  The power factor was improved from 80% to 97% Before After Why do we install Capacitors?
  • 32. 32 DISADVATAGES OF LOW POWER FACTOR 1. For a given power to be supplied, the current is increased. 2. The current thus increased in-return causes increase in copper losses (PL=I2R) and decrease in the efficiency of both apparatus and the supply system, which results in overloading and hence burning of the associated equipment.
  • 33. 33 DISADVATAGES OF LOW POWER FACTOR 3. Copper losses in transformers also increases. 4. Generators, transformers, switches, transmission lines and other associated switchgear becomes over-loaded. 5. Voltage regulation of generators, transformers and transmission lines increases. 6. Hence, cost of generation, transmission and distribution increases.
  • 34. 34 NATURAL POWER FACTORS o CEILING FAN 0.5 TO 0.7 o CABIN FAN 0.5 TO 0.6 o EXAUST FAN 0.6 TO 0.7 o SEWING MACHINE 0.6 TO 0.7 o WASHING MACHINE 0.6 TO 0.7 o RADIO 0.9 o VACUUM CLEANER 0.6 TO 0.7 o TUBE LIGHT 0.5 TO 0.9 o CLOCK 0.9 o ELECTRONIC EQUIPMENT 0.4 TO 0.95
  • 35. 35 NATURAL POWER FACTORS o NEON SIGN 0.5 TO 0.55 o WINDOW TYPE AIR CONDITIONER 0.62 TO 0.85 o HAIR DRYERS 0.7 TO 0.8 o LIQUIDISER 0.8 o MIXER 0.8 o COFFEE GRINDER 0.75 o REFRIGERATOR 0.65 o FREEZER 0.7 o SHAVER 0.6 o TABLE FAN 0.5 TO 0.6
  • 36. 36 NATURAL POWER FACTORS o MERCURY VAPOUR LAMP O.4 TO 0.6 o INDUSTRIAL INDUCTION MOTOR: ◘ NO LOAD O.18 ◘ 25% FULL LOAD 0.56 ◘ 75% FULL LOAD 0.81 ◘ 100% FULL LOAD 0.85 ◘ 125% FULL LOAD 0.86 o COLD STORAGE O.76 TO 0.80 o CINEMAS 0.78 TO 0.80 o METAL PRESSING O.57 TO 0.72
  • 38. 38 NATURAL POWER FACTORS o OIL MILLS O.51 TO 0.59 o WOOLEN MILLS O.70 o POTTERIES 0.61 o CIGARETTE MANUFACTURING 0.80 o FOUNDRIES 0.59 o STRUCTURAL ENGINEERING 0.53 TO 0.68 o CHEMICALS 0.72 TO 0.87 o MUNICIPAL PUMPING STATIONS 0.65 TO 0.75 o OIL TERMINALS 0.64 TO 0.83 o ROLLING MILLS 0.60 TO 0.72
  • 39. 39 NATURAL POWER FACTORS o PLASTIC MOLDING 0.57 TO 0.73 o FILM STUDIOS O.65 TO 0.74 o HEAVY ENGINEERING WORK 0.48 TO 0.75 o RUBBER EXTRUSION AND MOLDING 0.48 o PHARMACEUTICALS 0.75 TO 0.86 o OIL AND PAINT MANUFACTURING 0.51 TO 0.69 o BISCUIT FACTORY 0.60 o LAUNDRIES 0.92 o FLOUR MILLS 0.61 o GLASS WORKS 0.87
  • 40. 40 NATURAL POWER FACTORS o IRRIGATIONS PUMPS O.62 TO 0.80 o REPAIR SHOP, AUTOMATIC LATHE, 0.6 WORKSHOP, SPINNING MILLS, WEAVING MILL o WELDING SHOP 0.5 TO 0.6 o HEAT TREATMENT SHOP, STEEL 0.65 TO 0.8 WORKS, ROLLING MILLS o TEXTILE 0.65 TO 0.75 o CEMENT 0.8 TO 0.85 o OFFICE BUILDING O.8 TO 0.85
  • 41. Three Options for Applying Power Factor Capacitors: A) Fixed capacitors @ individual motors or @ MCC B) Automatic Banks at Main Switch Board C) De-tuned Automatic Capacitor Bank at Main Switch Board M M M M M A B C A Harmonic Source e.g. Variable Speed Drive Capacitor Locations
  • 42. 42 ADVANTAGES OF POWER FACTOR IMPROVEMENT i. Adding capacitor, releases circuit capacity for more load or relieves the overloaded circuit. The capacitor KVAR per KVA of load increase is of particular interest as this establishes the average cost of supplying each additional KVA of load. This cost can be compared with the cost per KVA of increasing the transformer or supply circuit rating and would justify the application of capacitors. PFI Capacitor’s addition, thus can be viewed in two lights.
  • 43. 43 ADVANTAGES OF POWER FACTOR IMPROVEMENT ii. Capacitors applied to given load reduce the I2R losses in the supply circuit. For a 70 percent power factor load with 40-KVAR of capacitors added for each 100 KVA of circuit capacity, the I2R loss will be 59% of its former value. The losses are not only reduced in the circuit in which the capacitors are applied but in all the circuit back to and including the source generator.
  • 44. 44 ADVANTAGES OF POWER FACTOR IMPROVEMENT Automatic Power Factor improvement capacitors or capacitor banks applied on the load end of circuit, with lagging power factor (more than 95% loads), have particular effects, one or more of which may be the reason for the application. 1. Improves the power factor at the source. 2. Reduces system losses as current in conductors decreases.
  • 45. 45 ADVANTAGES OF POWER FACTOR IMPROVEMENT 3. Improves voltage level at the load. 4. Decreases KVA loading on the source. 5. Reduces investment in system facilities per KW of load supplied.