Case Study - How your Motor Protection should designed when running in
parallel with Capacitor Bank
Hello Friends / Sirs,
Protection is a vast field and it’s designing, and implementation is a subject of involved
Technicality and Engineering Experience to larger extent. For Switchgears, Protective Relays are
designed to provide protection for electrical equipment and hence Engineering toward
Designing of Protection Scheme and Protection Relaying must be done keeping all the aspects in
mind.
During all these years in Engineering Services, we have mastered the art of Design and Selection
of Protection Scheme. We have also helped many of our valued customers to Rectify the issues
related to wrongly Designed and Implemented Protection Schemes and Philosophies.
Presenting you one of such case which we, System Protection have Identified and Rectified for
wrong Design of Protection Scheme which in turn reduces Selectivity and increases down time
or remain Inoperative in case of some genuine fault conditions.
In one of the Process Plant where switchboard was designed by some consultant who showed
ignorance owing to lesser experience and knowledge in Design & Engineering of Protection
Schemes. This has costs frequent failure of 6.6 kV HT Motors without any warnings and
abnormality reflected.
Till date we, System Protection were contacted and called upon to identify and rectify the root
cause, 3 Motors have been burnt due to Overheating / Overloading in just 9 -10 months.
Usually, we never suspect the Engineering of Protection Schemes, hence started analyzing the
data viz. Motor Ratings, CT Sizing, Transformer Ratings, Relay Settings, Load patterns, connected
loads etc.
Examining further when no check points left, we finally checked the Protection Scheme and SLD
that lead us to an instant conclusion that it was wrong Protection Scheme for Motors causing
frequent failure and loss of revenue with significant repairing cost and down time.
Page | 2
Authorised Channel Partners
Below is the SLD Representation of existing / old scheme and corrected Protection Scheme for
HT Motors with Capacitor Bank.
It was common CT and Relays for Both Motors and Capacitor banks which was causing the
frequent failure of motors. Here under are the reasons why Common Protection should not be
used for HT Motor with Capacitor Banks.
1. Protective relay will not sense the fault properly:
 In a common installed Protection Scheme for Parallel connected Motors and Capacitors,
current sensed by CT will be less than what is being consumed by Motor.
 Suppose 3600 kW, 6.6 kV, 384 Amp FLC (0.82 P.F) Slip Ring Induction Motor is running at
full load without capacitor bank than Motor will be taking 384 Amp normally.
 But when connected in parallel with capacitor bank of 1350 KVAR, loading remains the
same i.e. 3600 kW but as power factor is improved to 0.95, net current reduces to 335-
340 Ampere.
 Normally Motor Protection Relay settings shall be done as per 384 Amp as FLC +
permissive overload for a time being. Whereas in existing protection scheme Relay will
take 340 Amp only. So, to reach Threshold of 384 Amp, motor has to run at approx 4250
kW which is in actual 115% of rated capacity. Now if motor keep running at 115%
normally, it will be overheated and shall surely results into breakdown.
Page | 3
Authorised Channel Partners
2. Also, whenever Relay trips due to fault, it takes longer time for Engineers to identify the
fault / location since common protection for Motor and Capacitor Bank has been used, and
hence increases the down time of breakdown as Engineers have to check Motors,
Associated rotor equipments (If any) in the field and Capacitor Bank in the Substations.
System Protection provided them compete Engineering support with Selection of CT, Relay,
Design, Supply and Installation of new CT and Relays, Complete scheme Implementation and
testing.
Due to above described factors, we advise the Plant authorities to modify protection scheme,
by implementing separate protection for motors and capacitor bank. We also advise to
manipulate the Motor Protection Relay settings by reducing it to 88% approximately till the
modification in protection scheme is made.
Stitch in Time, Saves Nine!
Don’t let your Plant suffer the same as in described case study, do check your Protection
Scheme and if you have the same then feel free to Call / Write to us.
Page | 4
Authorised Channel Partners
If you are looking for a dedicated agency that understands the direct link between your assets
and your revenue, call/write to us, we will be happy to assist you.
SYSTEM PROTECTION
E-Mail : bdm@systemprotection.in
Web : www.systemprotection.in
Tele : +91-265-2225137
(Servicing & Testing of Circuit Breaker,
Relay, CT, PT, Transformer, Other
Switchyard Equipment’s, Relay Co-
ordination Studies, Cable, etc.)

More Related Content

What's hot

Continuity of Supply means Continuity of Production
Continuity of Supply means Continuity of ProductionContinuity of Supply means Continuity of Production
Continuity of Supply means Continuity of ProductionRusty Roar Enterprises
 
Online inverter fault diagnosis of buck converter bldc motor combinations
Online inverter fault diagnosis of buck converter bldc motor combinationsOnline inverter fault diagnosis of buck converter bldc motor combinations
Online inverter fault diagnosis of buck converter bldc motor combinationsLeMeniz Infotech
 
Agilent E3611A
Agilent  E3611AAgilent  E3611A
Agilent E3611Asavomir
 
A high gain input parallel output-series dcdc converter with dual coupled ind...
A high gain input parallel output-series dcdc converter with dual coupled ind...A high gain input parallel output-series dcdc converter with dual coupled ind...
A high gain input parallel output-series dcdc converter with dual coupled ind...LeMeniz Infotech
 
my pagemanager C.V
my pagemanager  C.Vmy pagemanager  C.V
my pagemanager C.VOsama ahmed
 
A high gain input parallel output-series dc dc converter with dual coupled in...
A high gain input parallel output-series dc dc converter with dual coupled in...A high gain input parallel output-series dc dc converter with dual coupled in...
A high gain input parallel output-series dc dc converter with dual coupled in...I3E Technologies
 
Michael Wood - Loader electric shocks, a case study
Michael Wood - Loader electric shocks, a case studyMichael Wood - Loader electric shocks, a case study
Michael Wood - Loader electric shocks, a case studyNSW Environment and Planning
 
Intro to Switchgear and its working
Intro to Switchgear and its workingIntro to Switchgear and its working
Intro to Switchgear and its workingGhafoorEngineering
 
Why the Alternator of your Car is not Charging
Why the Alternator of your Car is not ChargingWhy the Alternator of your Car is not Charging
Why the Alternator of your Car is not ChargingStar Motors
 

What's hot (19)

Continuity of Supply means Continuity of Production
Continuity of Supply means Continuity of ProductionContinuity of Supply means Continuity of Production
Continuity of Supply means Continuity of Production
 
Online inverter fault diagnosis of buck converter bldc motor combinations
Online inverter fault diagnosis of buck converter bldc motor combinationsOnline inverter fault diagnosis of buck converter bldc motor combinations
Online inverter fault diagnosis of buck converter bldc motor combinations
 
Agilent E3611A
Agilent  E3611AAgilent  E3611A
Agilent E3611A
 
A high gain input parallel output-series dcdc converter with dual coupled ind...
A high gain input parallel output-series dcdc converter with dual coupled ind...A high gain input parallel output-series dcdc converter with dual coupled ind...
A high gain input parallel output-series dcdc converter with dual coupled ind...
 
my pagemanager C.V
my pagemanager  C.Vmy pagemanager  C.V
my pagemanager C.V
 
High voltage design
High voltage designHigh voltage design
High voltage design
 
Substation stripout
Substation stripoutSubstation stripout
Substation stripout
 
A high gain input parallel output-series dc dc converter with dual coupled in...
A high gain input parallel output-series dc dc converter with dual coupled in...A high gain input parallel output-series dc dc converter with dual coupled in...
A high gain input parallel output-series dc dc converter with dual coupled in...
 
Rotatingelectrics
RotatingelectricsRotatingelectrics
Rotatingelectrics
 
MY CV
MY CVMY CV
MY CV
 
PPS 1
PPS 1PPS 1
PPS 1
 
CV_Parulkar
CV_ParulkarCV_Parulkar
CV_Parulkar
 
Michael Wood - Loader electric shocks, a case study
Michael Wood - Loader electric shocks, a case studyMichael Wood - Loader electric shocks, a case study
Michael Wood - Loader electric shocks, a case study
 
SENTHIL.k RESUME
SENTHIL.k RESUMESENTHIL.k RESUME
SENTHIL.k RESUME
 
ansary-cv
ansary-cvansary-cv
ansary-cv
 
Intro to Switchgear and its working
Intro to Switchgear and its workingIntro to Switchgear and its working
Intro to Switchgear and its working
 
LCOE_2015_2_pager_US
LCOE_2015_2_pager_USLCOE_2015_2_pager_US
LCOE_2015_2_pager_US
 
Why the Alternator of your Car is not Charging
Why the Alternator of your Car is not ChargingWhy the Alternator of your Car is not Charging
Why the Alternator of your Car is not Charging
 
Panel
PanelPanel
Panel
 

Similar to Case Study | How your Motor Protection should designed when running in parallel with Capacitor Bank

Understanding type 2 coordinated protection in motor branch circuit
Understanding type 2 coordinated protection in motor branch circuitUnderstanding type 2 coordinated protection in motor branch circuit
Understanding type 2 coordinated protection in motor branch circuitBassam Gomaa
 
Servo Motors Adjust
Servo Motors Adjust Servo Motors Adjust
Servo Motors Adjust Marc Vendrell
 
Servo Motors Adjust-English
Servo Motors Adjust-EnglishServo Motors Adjust-English
Servo Motors Adjust-EnglishMarc Vendrell
 
Guidelines for powersports electrical design success
Guidelines for powersports electrical design successGuidelines for powersports electrical design success
Guidelines for powersports electrical design successGary Gustafson
 
LFUS_AEB_Battery_Protection_Disconnect_Spotlight.pdf
LFUS_AEB_Battery_Protection_Disconnect_Spotlight.pdfLFUS_AEB_Battery_Protection_Disconnect_Spotlight.pdf
LFUS_AEB_Battery_Protection_Disconnect_Spotlight.pdfhruthvik1si19me053
 
WyoTech Course Description
WyoTech Course DescriptionWyoTech Course Description
WyoTech Course DescriptionDavid Chambers
 
Energy Storage - Hatch Innovative approach to cost reduction
Energy Storage - Hatch Innovative approach to cost reductionEnergy Storage - Hatch Innovative approach to cost reduction
Energy Storage - Hatch Innovative approach to cost reductionMichel Carreau
 
ULTRASOUND TO ASSESS USED BATTERIES TO ENHANCE PERFORMANCE/SAFETY OF SECOND LIFE
ULTRASOUND TO ASSESS USED BATTERIES TO ENHANCE PERFORMANCE/SAFETY OF SECOND LIFEULTRASOUND TO ASSESS USED BATTERIES TO ENHANCE PERFORMANCE/SAFETY OF SECOND LIFE
ULTRASOUND TO ASSESS USED BATTERIES TO ENHANCE PERFORMANCE/SAFETY OF SECOND LIFEDesignTeam8
 
Introduction relay
Introduction relayIntroduction relay
Introduction relayK R Vaghela
 
Littelfuse Solutions for xEV Powertrain Systems
Littelfuse Solutions for xEV Powertrain SystemsLittelfuse Solutions for xEV Powertrain Systems
Littelfuse Solutions for xEV Powertrain SystemsLittelfuse
 
Tahir Mahmood Butt
Tahir Mahmood ButtTahir Mahmood Butt
Tahir Mahmood ButtTahir Butt
 
Siemens Innovation Tools2010
Siemens Innovation Tools2010Siemens Innovation Tools2010
Siemens Innovation Tools2010Kirkdx
 
Power factor solution,presentation
Power factor solution,presentationPower factor solution,presentation
Power factor solution,presentationAmol Chande
 
Forum_Enviro_Brch_VPO
Forum_Enviro_Brch_VPOForum_Enviro_Brch_VPO
Forum_Enviro_Brch_VPOChris Forrest
 
DESIGN & IMPLEMENT OF PERFORMANCE OF MONITORING OF E- BATTERY USING NODEMCU E...
DESIGN & IMPLEMENT OF PERFORMANCE OF MONITORING OF E- BATTERY USING NODEMCU E...DESIGN & IMPLEMENT OF PERFORMANCE OF MONITORING OF E- BATTERY USING NODEMCU E...
DESIGN & IMPLEMENT OF PERFORMANCE OF MONITORING OF E- BATTERY USING NODEMCU E...IRJET Journal
 
Experience feedback steam turbine
Experience feedback steam turbineExperience feedback steam turbine
Experience feedback steam turbineSouvik Dutta
 
Electric motor asset management
Electric motor asset managementElectric motor asset management
Electric motor asset managementLeonardo ENERGY
 

Similar to Case Study | How your Motor Protection should designed when running in parallel with Capacitor Bank (20)

Understanding type 2 coordinated protection in motor branch circuit
Understanding type 2 coordinated protection in motor branch circuitUnderstanding type 2 coordinated protection in motor branch circuit
Understanding type 2 coordinated protection in motor branch circuit
 
Servo Motors Adjust
Servo Motors Adjust Servo Motors Adjust
Servo Motors Adjust
 
Servo Motors Adjust-English
Servo Motors Adjust-EnglishServo Motors Adjust-English
Servo Motors Adjust-English
 
Guidelines for powersports electrical design success
Guidelines for powersports electrical design successGuidelines for powersports electrical design success
Guidelines for powersports electrical design success
 
Structural Compliance of Electric Vehicle Battery Pack
Structural Compliance of Electric Vehicle Battery Pack Structural Compliance of Electric Vehicle Battery Pack
Structural Compliance of Electric Vehicle Battery Pack
 
LFUS_AEB_Battery_Protection_Disconnect_Spotlight.pdf
LFUS_AEB_Battery_Protection_Disconnect_Spotlight.pdfLFUS_AEB_Battery_Protection_Disconnect_Spotlight.pdf
LFUS_AEB_Battery_Protection_Disconnect_Spotlight.pdf
 
WyoTech Course Description
WyoTech Course DescriptionWyoTech Course Description
WyoTech Course Description
 
Energy Storage - Hatch Innovative approach to cost reduction
Energy Storage - Hatch Innovative approach to cost reductionEnergy Storage - Hatch Innovative approach to cost reduction
Energy Storage - Hatch Innovative approach to cost reduction
 
ULTRASOUND TO ASSESS USED BATTERIES TO ENHANCE PERFORMANCE/SAFETY OF SECOND LIFE
ULTRASOUND TO ASSESS USED BATTERIES TO ENHANCE PERFORMANCE/SAFETY OF SECOND LIFEULTRASOUND TO ASSESS USED BATTERIES TO ENHANCE PERFORMANCE/SAFETY OF SECOND LIFE
ULTRASOUND TO ASSESS USED BATTERIES TO ENHANCE PERFORMANCE/SAFETY OF SECOND LIFE
 
Introduction relay
Introduction relayIntroduction relay
Introduction relay
 
Littelfuse Solutions for xEV Powertrain Systems
Littelfuse Solutions for xEV Powertrain SystemsLittelfuse Solutions for xEV Powertrain Systems
Littelfuse Solutions for xEV Powertrain Systems
 
Tahir Mahmood Butt
Tahir Mahmood ButtTahir Mahmood Butt
Tahir Mahmood Butt
 
Siemens Innovation Tools2010
Siemens Innovation Tools2010Siemens Innovation Tools2010
Siemens Innovation Tools2010
 
Power factor solution,presentation
Power factor solution,presentationPower factor solution,presentation
Power factor solution,presentation
 
What does peak shaving mean
What does peak shaving meanWhat does peak shaving mean
What does peak shaving mean
 
Forum_Enviro_Brch_VPO
Forum_Enviro_Brch_VPOForum_Enviro_Brch_VPO
Forum_Enviro_Brch_VPO
 
DESIGN & IMPLEMENT OF PERFORMANCE OF MONITORING OF E- BATTERY USING NODEMCU E...
DESIGN & IMPLEMENT OF PERFORMANCE OF MONITORING OF E- BATTERY USING NODEMCU E...DESIGN & IMPLEMENT OF PERFORMANCE OF MONITORING OF E- BATTERY USING NODEMCU E...
DESIGN & IMPLEMENT OF PERFORMANCE OF MONITORING OF E- BATTERY USING NODEMCU E...
 
Experience feedback steam turbine
Experience feedback steam turbineExperience feedback steam turbine
Experience feedback steam turbine
 
Maintenance Network
Maintenance NetworkMaintenance Network
Maintenance Network
 
Electric motor asset management
Electric motor asset managementElectric motor asset management
Electric motor asset management
 

More from System Protection

Transformer differential protection – SIEMENS Reyrolle 7SR54
Transformer differential protection – SIEMENS Reyrolle 7SR54Transformer differential protection – SIEMENS Reyrolle 7SR54
Transformer differential protection – SIEMENS Reyrolle 7SR54System Protection
 
Mastering Motor Protection with SIEMENS Reyrolle 7SR17: Safeguarding Your Assets
Mastering Motor Protection with SIEMENS Reyrolle 7SR17: Safeguarding Your AssetsMastering Motor Protection with SIEMENS Reyrolle 7SR17: Safeguarding Your Assets
Mastering Motor Protection with SIEMENS Reyrolle 7SR17: Safeguarding Your AssetsSystem Protection
 
AC Digital Clamp Meter KEW 2204R Overview | System Protection
AC Digital Clamp Meter KEW 2204R Overview | System ProtectionAC Digital Clamp Meter KEW 2204R Overview | System Protection
AC Digital Clamp Meter KEW 2204R Overview | System ProtectionSystem Protection
 
Digital Multimeter with AC/DC Clamp Sensor KEWMATE 2012RA | System Protection
Digital Multimeter with AC/DC Clamp Sensor KEWMATE 2012RA | System ProtectionDigital Multimeter with AC/DC Clamp Sensor KEWMATE 2012RA | System Protection
Digital Multimeter with AC/DC Clamp Sensor KEWMATE 2012RA | System ProtectionSystem Protection
 
DIGITAL MULTIMETERS KEW 1052 | System Protection
DIGITAL MULTIMETERS KEW 1052 | System ProtectionDIGITAL MULTIMETERS KEW 1052 | System Protection
DIGITAL MULTIMETERS KEW 1052 | System ProtectionSystem Protection
 
Kyoritsu Voltage Detector KEW 5711
Kyoritsu Voltage Detector KEW 5711Kyoritsu Voltage Detector KEW 5711
Kyoritsu Voltage Detector KEW 5711System Protection
 
Earth Clamp Testing with the KEW 4202 | Ultimate Tool for Earth Clamp Testing
Earth Clamp Testing with the KEW 4202 | Ultimate Tool for Earth Clamp TestingEarth Clamp Testing with the KEW 4202 | Ultimate Tool for Earth Clamp Testing
Earth Clamp Testing with the KEW 4202 | Ultimate Tool for Earth Clamp TestingSystem Protection
 
Kyoritsu Multi-Function Testers | KEW 6016
Kyoritsu Multi-Function Testers | KEW 6016Kyoritsu Multi-Function Testers | KEW 6016
Kyoritsu Multi-Function Testers | KEW 6016System Protection
 
Honeywell | Overcoat | Fabric Composition (Patented)
Honeywell | Overcoat | Fabric Composition (Patented)Honeywell | Overcoat | Fabric Composition (Patented)
Honeywell | Overcoat | Fabric Composition (Patented)System Protection
 
Case Study – How an Unchecked Capacitor can cause loss of revenue
Case Study – How an Unchecked Capacitor can cause loss of revenueCase Study – How an Unchecked Capacitor can cause loss of revenue
Case Study – How an Unchecked Capacitor can cause loss of revenueSystem Protection
 
HONEYWELL - Electrical Safety Mat | HONEYWELL Insulating Rubber Mat
HONEYWELL - Electrical Safety Mat | HONEYWELL Insulating Rubber MatHONEYWELL - Electrical Safety Mat | HONEYWELL Insulating Rubber Mat
HONEYWELL - Electrical Safety Mat | HONEYWELL Insulating Rubber MatSystem Protection
 
Salisbury By Honeywell | 51511 Di – Electric Over Shoes
Salisbury By Honeywell | 51511 Di – Electric Over ShoesSalisbury By Honeywell | 51511 Di – Electric Over Shoes
Salisbury By Honeywell | 51511 Di – Electric Over ShoesSystem Protection
 
Salisbury By Honeywell | 4556 Voltage Detector 240V to 230kV
Salisbury By Honeywell | 4556 Voltage Detector 240V to 230kVSalisbury By Honeywell | 4556 Voltage Detector 240V to 230kV
Salisbury By Honeywell | 4556 Voltage Detector 240V to 230kVSystem Protection
 
LOGGER KEW 5020 | KYORITSU | System Protection
LOGGER KEW 5020 | KYORITSU | System ProtectionLOGGER KEW 5020 | KYORITSU | System Protection
LOGGER KEW 5020 | KYORITSU | System ProtectionSystem Protection
 
PORTABLE APPLIANCE TESTER KEW 6205 | KYORITSU | System Protection
PORTABLE APPLIANCE TESTER KEW 6205 | KYORITSU | System ProtectionPORTABLE APPLIANCE TESTER KEW 6205 | KYORITSU | System Protection
PORTABLE APPLIANCE TESTER KEW 6205 | KYORITSU | System ProtectionSystem Protection
 
RCD TESTER KEW 5410| KYORITSU | System Protection
RCD TESTER KEW 5410| KYORITSU | System ProtectionRCD TESTER KEW 5410| KYORITSU | System Protection
RCD TESTER KEW 5410| KYORITSU | System ProtectionSystem Protection
 
Case Study | How we saved a Generator (in fact two), again!
Case Study | How we saved a Generator (in fact two), again!Case Study | How we saved a Generator (in fact two), again!
Case Study | How we saved a Generator (in fact two), again!System Protection
 
AC/DC Digital Clamp Meters | KEW 2010 | Kyoritsu
AC/DC Digital Clamp Meters | KEW 2010 | KyoritsuAC/DC Digital Clamp Meters | KEW 2010 | Kyoritsu
AC/DC Digital Clamp Meters | KEW 2010 | KyoritsuSystem Protection
 
Digital Multimeters | KEW 1051 | Kyoritsu
Digital Multimeters | KEW 1051 | KyoritsuDigital Multimeters | KEW 1051 | Kyoritsu
Digital Multimeters | KEW 1051 | KyoritsuSystem Protection
 
Digital Multimeters | KEW 1020R | Kyoritsu
Digital Multimeters | KEW 1020R | KyoritsuDigital Multimeters | KEW 1020R | Kyoritsu
Digital Multimeters | KEW 1020R | KyoritsuSystem Protection
 

More from System Protection (20)

Transformer differential protection – SIEMENS Reyrolle 7SR54
Transformer differential protection – SIEMENS Reyrolle 7SR54Transformer differential protection – SIEMENS Reyrolle 7SR54
Transformer differential protection – SIEMENS Reyrolle 7SR54
 
Mastering Motor Protection with SIEMENS Reyrolle 7SR17: Safeguarding Your Assets
Mastering Motor Protection with SIEMENS Reyrolle 7SR17: Safeguarding Your AssetsMastering Motor Protection with SIEMENS Reyrolle 7SR17: Safeguarding Your Assets
Mastering Motor Protection with SIEMENS Reyrolle 7SR17: Safeguarding Your Assets
 
AC Digital Clamp Meter KEW 2204R Overview | System Protection
AC Digital Clamp Meter KEW 2204R Overview | System ProtectionAC Digital Clamp Meter KEW 2204R Overview | System Protection
AC Digital Clamp Meter KEW 2204R Overview | System Protection
 
Digital Multimeter with AC/DC Clamp Sensor KEWMATE 2012RA | System Protection
Digital Multimeter with AC/DC Clamp Sensor KEWMATE 2012RA | System ProtectionDigital Multimeter with AC/DC Clamp Sensor KEWMATE 2012RA | System Protection
Digital Multimeter with AC/DC Clamp Sensor KEWMATE 2012RA | System Protection
 
DIGITAL MULTIMETERS KEW 1052 | System Protection
DIGITAL MULTIMETERS KEW 1052 | System ProtectionDIGITAL MULTIMETERS KEW 1052 | System Protection
DIGITAL MULTIMETERS KEW 1052 | System Protection
 
Kyoritsu Voltage Detector KEW 5711
Kyoritsu Voltage Detector KEW 5711Kyoritsu Voltage Detector KEW 5711
Kyoritsu Voltage Detector KEW 5711
 
Earth Clamp Testing with the KEW 4202 | Ultimate Tool for Earth Clamp Testing
Earth Clamp Testing with the KEW 4202 | Ultimate Tool for Earth Clamp TestingEarth Clamp Testing with the KEW 4202 | Ultimate Tool for Earth Clamp Testing
Earth Clamp Testing with the KEW 4202 | Ultimate Tool for Earth Clamp Testing
 
Kyoritsu Multi-Function Testers | KEW 6016
Kyoritsu Multi-Function Testers | KEW 6016Kyoritsu Multi-Function Testers | KEW 6016
Kyoritsu Multi-Function Testers | KEW 6016
 
Honeywell | Overcoat | Fabric Composition (Patented)
Honeywell | Overcoat | Fabric Composition (Patented)Honeywell | Overcoat | Fabric Composition (Patented)
Honeywell | Overcoat | Fabric Composition (Patented)
 
Case Study – How an Unchecked Capacitor can cause loss of revenue
Case Study – How an Unchecked Capacitor can cause loss of revenueCase Study – How an Unchecked Capacitor can cause loss of revenue
Case Study – How an Unchecked Capacitor can cause loss of revenue
 
HONEYWELL - Electrical Safety Mat | HONEYWELL Insulating Rubber Mat
HONEYWELL - Electrical Safety Mat | HONEYWELL Insulating Rubber MatHONEYWELL - Electrical Safety Mat | HONEYWELL Insulating Rubber Mat
HONEYWELL - Electrical Safety Mat | HONEYWELL Insulating Rubber Mat
 
Salisbury By Honeywell | 51511 Di – Electric Over Shoes
Salisbury By Honeywell | 51511 Di – Electric Over ShoesSalisbury By Honeywell | 51511 Di – Electric Over Shoes
Salisbury By Honeywell | 51511 Di – Electric Over Shoes
 
Salisbury By Honeywell | 4556 Voltage Detector 240V to 230kV
Salisbury By Honeywell | 4556 Voltage Detector 240V to 230kVSalisbury By Honeywell | 4556 Voltage Detector 240V to 230kV
Salisbury By Honeywell | 4556 Voltage Detector 240V to 230kV
 
LOGGER KEW 5020 | KYORITSU | System Protection
LOGGER KEW 5020 | KYORITSU | System ProtectionLOGGER KEW 5020 | KYORITSU | System Protection
LOGGER KEW 5020 | KYORITSU | System Protection
 
PORTABLE APPLIANCE TESTER KEW 6205 | KYORITSU | System Protection
PORTABLE APPLIANCE TESTER KEW 6205 | KYORITSU | System ProtectionPORTABLE APPLIANCE TESTER KEW 6205 | KYORITSU | System Protection
PORTABLE APPLIANCE TESTER KEW 6205 | KYORITSU | System Protection
 
RCD TESTER KEW 5410| KYORITSU | System Protection
RCD TESTER KEW 5410| KYORITSU | System ProtectionRCD TESTER KEW 5410| KYORITSU | System Protection
RCD TESTER KEW 5410| KYORITSU | System Protection
 
Case Study | How we saved a Generator (in fact two), again!
Case Study | How we saved a Generator (in fact two), again!Case Study | How we saved a Generator (in fact two), again!
Case Study | How we saved a Generator (in fact two), again!
 
AC/DC Digital Clamp Meters | KEW 2010 | Kyoritsu
AC/DC Digital Clamp Meters | KEW 2010 | KyoritsuAC/DC Digital Clamp Meters | KEW 2010 | Kyoritsu
AC/DC Digital Clamp Meters | KEW 2010 | Kyoritsu
 
Digital Multimeters | KEW 1051 | Kyoritsu
Digital Multimeters | KEW 1051 | KyoritsuDigital Multimeters | KEW 1051 | Kyoritsu
Digital Multimeters | KEW 1051 | Kyoritsu
 
Digital Multimeters | KEW 1020R | Kyoritsu
Digital Multimeters | KEW 1020R | KyoritsuDigital Multimeters | KEW 1020R | Kyoritsu
Digital Multimeters | KEW 1020R | Kyoritsu
 

Recently uploaded

VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒anilsa9823
 
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRLMONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRLSeo
 
Progress Report - Oracle Database Analyst Summit
Progress  Report - Oracle Database Analyst SummitProgress  Report - Oracle Database Analyst Summit
Progress Report - Oracle Database Analyst SummitHolger Mueller
 
A DAY IN THE LIFE OF A SALESMAN / WOMAN
A DAY IN THE LIFE OF A  SALESMAN / WOMANA DAY IN THE LIFE OF A  SALESMAN / WOMAN
A DAY IN THE LIFE OF A SALESMAN / WOMANIlamathiKannappan
 
Monte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSMMonte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSMRavindra Nath Shukla
 
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 DelhiCall Girls in Delhi
 
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...Any kyc Account
 
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Dave Litwiller
 
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdfRenandantas16
 
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779Delhi Call girls
 
Pharma Works Profile of Karan Communications
Pharma Works Profile of Karan CommunicationsPharma Works Profile of Karan Communications
Pharma Works Profile of Karan Communicationskarancommunications
 
BEST ✨ Call Girls In Indirapuram Ghaziabad ✔️ 9871031762 ✔️ Escorts Service...
BEST ✨ Call Girls In  Indirapuram Ghaziabad  ✔️ 9871031762 ✔️ Escorts Service...BEST ✨ Call Girls In  Indirapuram Ghaziabad  ✔️ 9871031762 ✔️ Escorts Service...
BEST ✨ Call Girls In Indirapuram Ghaziabad ✔️ 9871031762 ✔️ Escorts Service...noida100girls
 
VIP Kolkata Call Girl Howrah 👉 8250192130 Available With Room
VIP Kolkata Call Girl Howrah 👉 8250192130  Available With RoomVIP Kolkata Call Girl Howrah 👉 8250192130  Available With Room
VIP Kolkata Call Girl Howrah 👉 8250192130 Available With Roomdivyansh0kumar0
 
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature SetCreating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature SetDenis Gagné
 
Mondelez State of Snacking and Future Trends 2023
Mondelez State of Snacking and Future Trends 2023Mondelez State of Snacking and Future Trends 2023
Mondelez State of Snacking and Future Trends 2023Neil Kimberley
 
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesMysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesDipal Arora
 
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...anilsa9823
 
HONOR Veterans Event Keynote by Michael Hawkins
HONOR Veterans Event Keynote by Michael HawkinsHONOR Veterans Event Keynote by Michael Hawkins
HONOR Veterans Event Keynote by Michael HawkinsMichael W. Hawkins
 

Recently uploaded (20)

VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
 
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRLMONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
 
Progress Report - Oracle Database Analyst Summit
Progress  Report - Oracle Database Analyst SummitProgress  Report - Oracle Database Analyst Summit
Progress Report - Oracle Database Analyst Summit
 
A DAY IN THE LIFE OF A SALESMAN / WOMAN
A DAY IN THE LIFE OF A  SALESMAN / WOMANA DAY IN THE LIFE OF A  SALESMAN / WOMAN
A DAY IN THE LIFE OF A SALESMAN / WOMAN
 
Monte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSMMonte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSM
 
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
 
Forklift Operations: Safety through Cartoons
Forklift Operations: Safety through CartoonsForklift Operations: Safety through Cartoons
Forklift Operations: Safety through Cartoons
 
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
 
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
 
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
 
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
 
Pharma Works Profile of Karan Communications
Pharma Works Profile of Karan CommunicationsPharma Works Profile of Karan Communications
Pharma Works Profile of Karan Communications
 
BEST ✨ Call Girls In Indirapuram Ghaziabad ✔️ 9871031762 ✔️ Escorts Service...
BEST ✨ Call Girls In  Indirapuram Ghaziabad  ✔️ 9871031762 ✔️ Escorts Service...BEST ✨ Call Girls In  Indirapuram Ghaziabad  ✔️ 9871031762 ✔️ Escorts Service...
BEST ✨ Call Girls In Indirapuram Ghaziabad ✔️ 9871031762 ✔️ Escorts Service...
 
VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...
VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...
VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...
 
VIP Kolkata Call Girl Howrah 👉 8250192130 Available With Room
VIP Kolkata Call Girl Howrah 👉 8250192130  Available With RoomVIP Kolkata Call Girl Howrah 👉 8250192130  Available With Room
VIP Kolkata Call Girl Howrah 👉 8250192130 Available With Room
 
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature SetCreating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
 
Mondelez State of Snacking and Future Trends 2023
Mondelez State of Snacking and Future Trends 2023Mondelez State of Snacking and Future Trends 2023
Mondelez State of Snacking and Future Trends 2023
 
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesMysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
 
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
 
HONOR Veterans Event Keynote by Michael Hawkins
HONOR Veterans Event Keynote by Michael HawkinsHONOR Veterans Event Keynote by Michael Hawkins
HONOR Veterans Event Keynote by Michael Hawkins
 

Case Study | How your Motor Protection should designed when running in parallel with Capacitor Bank

  • 1. Page | 1 Authorised Channel Partners Case Study - How your Motor Protection should designed when running in parallel with Capacitor Bank Hello Friends / Sirs, Protection is a vast field and it’s designing, and implementation is a subject of involved Technicality and Engineering Experience to larger extent. For Switchgears, Protective Relays are designed to provide protection for electrical equipment and hence Engineering toward Designing of Protection Scheme and Protection Relaying must be done keeping all the aspects in mind. During all these years in Engineering Services, we have mastered the art of Design and Selection of Protection Scheme. We have also helped many of our valued customers to Rectify the issues related to wrongly Designed and Implemented Protection Schemes and Philosophies. Presenting you one of such case which we, System Protection have Identified and Rectified for wrong Design of Protection Scheme which in turn reduces Selectivity and increases down time or remain Inoperative in case of some genuine fault conditions. In one of the Process Plant where switchboard was designed by some consultant who showed ignorance owing to lesser experience and knowledge in Design & Engineering of Protection Schemes. This has costs frequent failure of 6.6 kV HT Motors without any warnings and abnormality reflected. Till date we, System Protection were contacted and called upon to identify and rectify the root cause, 3 Motors have been burnt due to Overheating / Overloading in just 9 -10 months. Usually, we never suspect the Engineering of Protection Schemes, hence started analyzing the data viz. Motor Ratings, CT Sizing, Transformer Ratings, Relay Settings, Load patterns, connected loads etc. Examining further when no check points left, we finally checked the Protection Scheme and SLD that lead us to an instant conclusion that it was wrong Protection Scheme for Motors causing frequent failure and loss of revenue with significant repairing cost and down time.
  • 2. Page | 2 Authorised Channel Partners Below is the SLD Representation of existing / old scheme and corrected Protection Scheme for HT Motors with Capacitor Bank. It was common CT and Relays for Both Motors and Capacitor banks which was causing the frequent failure of motors. Here under are the reasons why Common Protection should not be used for HT Motor with Capacitor Banks. 1. Protective relay will not sense the fault properly:  In a common installed Protection Scheme for Parallel connected Motors and Capacitors, current sensed by CT will be less than what is being consumed by Motor.  Suppose 3600 kW, 6.6 kV, 384 Amp FLC (0.82 P.F) Slip Ring Induction Motor is running at full load without capacitor bank than Motor will be taking 384 Amp normally.  But when connected in parallel with capacitor bank of 1350 KVAR, loading remains the same i.e. 3600 kW but as power factor is improved to 0.95, net current reduces to 335- 340 Ampere.  Normally Motor Protection Relay settings shall be done as per 384 Amp as FLC + permissive overload for a time being. Whereas in existing protection scheme Relay will take 340 Amp only. So, to reach Threshold of 384 Amp, motor has to run at approx 4250 kW which is in actual 115% of rated capacity. Now if motor keep running at 115% normally, it will be overheated and shall surely results into breakdown.
  • 3. Page | 3 Authorised Channel Partners 2. Also, whenever Relay trips due to fault, it takes longer time for Engineers to identify the fault / location since common protection for Motor and Capacitor Bank has been used, and hence increases the down time of breakdown as Engineers have to check Motors, Associated rotor equipments (If any) in the field and Capacitor Bank in the Substations. System Protection provided them compete Engineering support with Selection of CT, Relay, Design, Supply and Installation of new CT and Relays, Complete scheme Implementation and testing. Due to above described factors, we advise the Plant authorities to modify protection scheme, by implementing separate protection for motors and capacitor bank. We also advise to manipulate the Motor Protection Relay settings by reducing it to 88% approximately till the modification in protection scheme is made. Stitch in Time, Saves Nine! Don’t let your Plant suffer the same as in described case study, do check your Protection Scheme and if you have the same then feel free to Call / Write to us.
  • 4. Page | 4 Authorised Channel Partners If you are looking for a dedicated agency that understands the direct link between your assets and your revenue, call/write to us, we will be happy to assist you. SYSTEM PROTECTION E-Mail : bdm@systemprotection.in Web : www.systemprotection.in Tele : +91-265-2225137 (Servicing & Testing of Circuit Breaker, Relay, CT, PT, Transformer, Other Switchyard Equipment’s, Relay Co- ordination Studies, Cable, etc.)