Electrical Sub-Station
Transformer Oil
INTRODUCTION
•Insulating oil in an electrical power transformer is commonly k/a transformer
oil.
•It is normally obtained by fractional distillation and subsequent treatment of
crude petroleum.
Transformer oil serves the following purposes
 It is the liquid insulation in electrical power transformer
 It dissipates heat of the transformer i.e. acts as coolant.
 It helps to preserve the core and winding as these are fully immersed
inside oil
 It prevents direct contact of atmospheric oxygen with cellulose made
paper insulation of windings, which is susceptible to oxidation
TRANSFORMER OIL
DIELECTRIC STRENGTH
• The voltage at which the oil breaks down when subjected to an ac electric
field with a continuously increasing voltage contained in specified
apparatus.
• Break down voltage is measured by observing at what voltage, sparking
starts between two electrodes immerged in the oil, separated by specific
gap.
• Low value of BDV indicates presence of moisture content and conducting
substances in the oil.
•Drums used for transport and storage should
be kept under cover.
•Drums should be clearly marked to indicate
whether they are for clean or for dirty oil and
should be reserved for the type indicated.
•When oil is stored in drums, these should be
placed in such a position that there is a head of
oil on the stopper or plug to prevent the entry
of water during storage.
•When oil is stored in drums which have been
bent or otherwise damaged in transit or
storage, and the transfer of oil from such
containers to electrical equipment should
normally be through a suitable treatment plant.
HANDLING AND STORAGE OF OIL
BDV Kit
BDV TEST
• BDV is important and popular test of transformer oil, as it is primary
indication of health of oil and it can be easily carried out at site.
• Dry and clean oil gives BDV results, better than the oil with moisture
content and other conducting impurities.
• Minimum breakdown voltage of transformer oil or dielectric strength
of transformer oil at
• which this oil can safely be used in transformer, is considered as 30 KV.
•In s/s with fixed oil-handling equipment
the pipe work from the clean oil tanks to
the electrical apparatus should be kept
clean and free from moisture.
•Where portable oil handling equipment is
used, flexible pipe work and hand pumps
should be carefully inspected to ensure
that they are free from dirt and water, and
should be flushed with clean oil before
use.
•Hoses used for clean oil and dirty oil
should be clearly marked and provided
with plugs for sealing the ends when not
in use.
OIL TOP-UP
Chemical parameter
1. Acidity
2. Sludge content.
3. Water content
Physical Parameters
1. Inter Facial Tension
2. Flash point
3. Pour Point
4. Viscosity
THANK YOU

More Related Content

What's hot

Testing of Transformers.
Testing of Transformers.Testing of Transformers.
Testing of Transformers.Geetesh Verma
 
Operation and maintenance of transformer
Operation and maintenance of transformerOperation and maintenance of transformer
Operation and maintenance of transformerKapil Singh
 
Testing,maintenance&protection
Testing,maintenance&protectionTesting,maintenance&protection
Testing,maintenance&protectionRakesh Joshi
 
Notes transformer oil
 Notes transformer oil Notes transformer oil
Notes transformer oilM Hussam Adeni
 
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGHHIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGHShankar Singh
 
Power transformer testing and commissioning guidelines r
Power transformer testing and commissioning guidelines rPower transformer testing and commissioning guidelines r
Power transformer testing and commissioning guidelines rAshish Patel
 
Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...
Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...
Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...Thorne & Derrick International
 
Testing and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsTesting and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsSumeet Ratnawat
 
High voltage testing of electrical transformer
High voltage testing of electrical transformerHigh voltage testing of electrical transformer
High voltage testing of electrical transformerPraveenKumar5880
 
Electrical Power substation
Electrical Power substationElectrical Power substation
Electrical Power substationEmran Ali
 
switching substation, plcc and scada
switching substation, plcc and scadaswitching substation, plcc and scada
switching substation, plcc and scadaHemendra Kumar Rajput
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentationNadir Baloch
 
GENERATING OF HIGH ALTERNATING VOLTAGE
GENERATING OF HIGH ALTERNATING VOLTAGEGENERATING OF HIGH ALTERNATING VOLTAGE
GENERATING OF HIGH ALTERNATING VOLTAGEJamil Abdullah
 
Transformer differential protection
Transformer differential protection Transformer differential protection
Transformer differential protection michaeljmack
 
Manufaturing transformer
Manufaturing transformerManufaturing transformer
Manufaturing transformersuman
 
Switchgear Equipment in a Substation
Switchgear Equipment in a SubstationSwitchgear Equipment in a Substation
Switchgear Equipment in a SubstationMd. Atiqur Rahman
 

What's hot (20)

Testing of Transformers.
Testing of Transformers.Testing of Transformers.
Testing of Transformers.
 
Operation and maintenance of transformer
Operation and maintenance of transformerOperation and maintenance of transformer
Operation and maintenance of transformer
 
Testing,maintenance&protection
Testing,maintenance&protectionTesting,maintenance&protection
Testing,maintenance&protection
 
Notes transformer oil
 Notes transformer oil Notes transformer oil
Notes transformer oil
 
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGHHIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
 
Transformer
TransformerTransformer
Transformer
 
Power transformer testing and commissioning guidelines r
Power transformer testing and commissioning guidelines rPower transformer testing and commissioning guidelines r
Power transformer testing and commissioning guidelines r
 
Transformer ppt.
Transformer ppt.Transformer ppt.
Transformer ppt.
 
Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...
Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...
Sheath Fault Location On Power Cables - Sheath Testing, Sheath Fault Location...
 
Testing and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsTesting and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation Equipments
 
High voltage testing of electrical transformer
High voltage testing of electrical transformerHigh voltage testing of electrical transformer
High voltage testing of electrical transformer
 
Electrical Power substation
Electrical Power substationElectrical Power substation
Electrical Power substation
 
switching substation, plcc and scada
switching substation, plcc and scadaswitching substation, plcc and scada
switching substation, plcc and scada
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
GENERATING OF HIGH ALTERNATING VOLTAGE
GENERATING OF HIGH ALTERNATING VOLTAGEGENERATING OF HIGH ALTERNATING VOLTAGE
GENERATING OF HIGH ALTERNATING VOLTAGE
 
Breaker Operation & Maintenance
Breaker Operation & MaintenanceBreaker Operation & Maintenance
Breaker Operation & Maintenance
 
Transformer differential protection
Transformer differential protection Transformer differential protection
Transformer differential protection
 
Manufaturing transformer
Manufaturing transformerManufaturing transformer
Manufaturing transformer
 
Switchgear Equipment in a Substation
Switchgear Equipment in a SubstationSwitchgear Equipment in a Substation
Switchgear Equipment in a Substation
 
Transformer basic
Transformer basicTransformer basic
Transformer basic
 

Similar to Transformer Oil Testing.pptx

high-Vacuum Transformer Oil Filtration And Dehydration Plants In India-AR ENGG.
high-Vacuum Transformer Oil Filtration And Dehydration Plants In India-AR ENGG.high-Vacuum Transformer Oil Filtration And Dehydration Plants In India-AR ENGG.
high-Vacuum Transformer Oil Filtration And Dehydration Plants In India-AR ENGG.vitika12345
 
high-Vacuum Transformer Oil Filtration And Dehydration Plants In India-AR ENGG.
high-Vacuum Transformer Oil Filtration And Dehydration Plants In India-AR ENGG.high-Vacuum Transformer Oil Filtration And Dehydration Plants In India-AR ENGG.
high-Vacuum Transformer Oil Filtration And Dehydration Plants In India-AR ENGG.vitika12345
 
Installation of power transformers
Installation of power transformersInstallation of power transformers
Installation of power transformersParul Patel
 
IRJET- Systematic Steps in Overhauling of a Transformer
IRJET- Systematic Steps in Overhauling of a TransformerIRJET- Systematic Steps in Overhauling of a Transformer
IRJET- Systematic Steps in Overhauling of a TransformerIRJET Journal
 
Day 04 Lubrication System
Day 04 Lubrication SystemDay 04 Lubrication System
Day 04 Lubrication SystemSuyog Khose
 
Oil circuit breaker
Oil circuit breakerOil circuit breaker
Oil circuit breakerRevathyyadav
 
Transformer Accessories for Testing and Protection
Transformer Accessories for Testing and ProtectionTransformer Accessories for Testing and Protection
Transformer Accessories for Testing and ProtectionSAGAR D
 
Bulk oil and min oil circuit breaker
Bulk oil and min oil circuit breakerBulk oil and min oil circuit breaker
Bulk oil and min oil circuit breakerSAURAV DAYAL SING
 
Hydraulics-fundamentals of hydraulics.ppt
Hydraulics-fundamentals of hydraulics.pptHydraulics-fundamentals of hydraulics.ppt
Hydraulics-fundamentals of hydraulics.pptArbrHalilaj
 
40266484-Fundamentals-of-Hydraulics.pdf
40266484-Fundamentals-of-Hydraulics.pdf40266484-Fundamentals-of-Hydraulics.pdf
40266484-Fundamentals-of-Hydraulics.pdfVijaySharma983125
 
POWER TRANSFORMER INSULATION REVITALIZATION
POWER TRANSFORMER INSULATION REVITALIZATIONPOWER TRANSFORMER INSULATION REVITALIZATION
POWER TRANSFORMER INSULATION REVITALIZATIONDejan Pantić
 
Palm Oil As An Alternative Dielectric Transformer Coolant
Palm Oil As An Alternative Dielectric Transformer CoolantPalm Oil As An Alternative Dielectric Transformer Coolant
Palm Oil As An Alternative Dielectric Transformer CoolantIJRES Journal
 
Bulk oil & Minimum oil Circuit Breakers
Bulk oil & Minimum oil Circuit BreakersBulk oil & Minimum oil Circuit Breakers
Bulk oil & Minimum oil Circuit BreakersShailendra Shakya
 
Transformer oil dehydration importance & process
Transformer oil dehydration importance & processTransformer oil dehydration importance & process
Transformer oil dehydration importance & processTransfo Tech. Engineering
 
Transformer oil dehydration importance & process
Transformer oil dehydration importance & processTransformer oil dehydration importance & process
Transformer oil dehydration importance & processTransfo Tech. Engineering
 
LUBRICATION_SYSTEM.ppt
LUBRICATION_SYSTEM.pptLUBRICATION_SYSTEM.ppt
LUBRICATION_SYSTEM.pptJemilsultan1
 
Sentinel ICU Oilregen
Sentinel ICU OilregenSentinel ICU Oilregen
Sentinel ICU OilregenOil Regen Ltd
 
Hydro Power Plant Auxaleries
Hydro Power Plant AuxaleriesHydro Power Plant Auxaleries
Hydro Power Plant AuxaleriesMahajan Saurabh
 

Similar to Transformer Oil Testing.pptx (20)

high-Vacuum Transformer Oil Filtration And Dehydration Plants In India-AR ENGG.
high-Vacuum Transformer Oil Filtration And Dehydration Plants In India-AR ENGG.high-Vacuum Transformer Oil Filtration And Dehydration Plants In India-AR ENGG.
high-Vacuum Transformer Oil Filtration And Dehydration Plants In India-AR ENGG.
 
high-Vacuum Transformer Oil Filtration And Dehydration Plants In India-AR ENGG.
high-Vacuum Transformer Oil Filtration And Dehydration Plants In India-AR ENGG.high-Vacuum Transformer Oil Filtration And Dehydration Plants In India-AR ENGG.
high-Vacuum Transformer Oil Filtration And Dehydration Plants In India-AR ENGG.
 
Installation of power transformers
Installation of power transformersInstallation of power transformers
Installation of power transformers
 
IRJET- Systematic Steps in Overhauling of a Transformer
IRJET- Systematic Steps in Overhauling of a TransformerIRJET- Systematic Steps in Overhauling of a Transformer
IRJET- Systematic Steps in Overhauling of a Transformer
 
Day 04 Lubrication System
Day 04 Lubrication SystemDay 04 Lubrication System
Day 04 Lubrication System
 
Oil circuit breaker
Oil circuit breakerOil circuit breaker
Oil circuit breaker
 
TR OverHauling PPT
TR OverHauling PPTTR OverHauling PPT
TR OverHauling PPT
 
Transformer Accessories for Testing and Protection
Transformer Accessories for Testing and ProtectionTransformer Accessories for Testing and Protection
Transformer Accessories for Testing and Protection
 
Bulk oil and min oil circuit breaker
Bulk oil and min oil circuit breakerBulk oil and min oil circuit breaker
Bulk oil and min oil circuit breaker
 
Hydraulics-fundamentals of hydraulics.ppt
Hydraulics-fundamentals of hydraulics.pptHydraulics-fundamentals of hydraulics.ppt
Hydraulics-fundamentals of hydraulics.ppt
 
40266484-Fundamentals-of-Hydraulics.pdf
40266484-Fundamentals-of-Hydraulics.pdf40266484-Fundamentals-of-Hydraulics.pdf
40266484-Fundamentals-of-Hydraulics.pdf
 
POWER TRANSFORMER INSULATION REVITALIZATION
POWER TRANSFORMER INSULATION REVITALIZATIONPOWER TRANSFORMER INSULATION REVITALIZATION
POWER TRANSFORMER INSULATION REVITALIZATION
 
Palm Oil As An Alternative Dielectric Transformer Coolant
Palm Oil As An Alternative Dielectric Transformer CoolantPalm Oil As An Alternative Dielectric Transformer Coolant
Palm Oil As An Alternative Dielectric Transformer Coolant
 
Bulk oil & Minimum oil Circuit Breakers
Bulk oil & Minimum oil Circuit BreakersBulk oil & Minimum oil Circuit Breakers
Bulk oil & Minimum oil Circuit Breakers
 
Transformer oil dehydration importance & process
Transformer oil dehydration importance & processTransformer oil dehydration importance & process
Transformer oil dehydration importance & process
 
Transformer oil dehydration importance & process
Transformer oil dehydration importance & processTransformer oil dehydration importance & process
Transformer oil dehydration importance & process
 
Transformer
TransformerTransformer
Transformer
 
LUBRICATION_SYSTEM.ppt
LUBRICATION_SYSTEM.pptLUBRICATION_SYSTEM.ppt
LUBRICATION_SYSTEM.ppt
 
Sentinel ICU Oilregen
Sentinel ICU OilregenSentinel ICU Oilregen
Sentinel ICU Oilregen
 
Hydro Power Plant Auxaleries
Hydro Power Plant AuxaleriesHydro Power Plant Auxaleries
Hydro Power Plant Auxaleries
 

Recently uploaded

Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxvipinkmenon1
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girlsssuser7cb4ff
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxKartikeyaDwivedi3
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .Satyam Kumar
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.eptoze12
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 

Recently uploaded (20)

Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
Design and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdfDesign and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdf
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptx
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girls
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptx
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.
 
young call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Serviceyoung call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Service
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 

Transformer Oil Testing.pptx

  • 2. INTRODUCTION •Insulating oil in an electrical power transformer is commonly k/a transformer oil. •It is normally obtained by fractional distillation and subsequent treatment of crude petroleum. Transformer oil serves the following purposes  It is the liquid insulation in electrical power transformer  It dissipates heat of the transformer i.e. acts as coolant.  It helps to preserve the core and winding as these are fully immersed inside oil  It prevents direct contact of atmospheric oxygen with cellulose made paper insulation of windings, which is susceptible to oxidation
  • 4. DIELECTRIC STRENGTH • The voltage at which the oil breaks down when subjected to an ac electric field with a continuously increasing voltage contained in specified apparatus. • Break down voltage is measured by observing at what voltage, sparking starts between two electrodes immerged in the oil, separated by specific gap. • Low value of BDV indicates presence of moisture content and conducting substances in the oil.
  • 5. •Drums used for transport and storage should be kept under cover. •Drums should be clearly marked to indicate whether they are for clean or for dirty oil and should be reserved for the type indicated. •When oil is stored in drums, these should be placed in such a position that there is a head of oil on the stopper or plug to prevent the entry of water during storage. •When oil is stored in drums which have been bent or otherwise damaged in transit or storage, and the transfer of oil from such containers to electrical equipment should normally be through a suitable treatment plant. HANDLING AND STORAGE OF OIL
  • 7. BDV TEST • BDV is important and popular test of transformer oil, as it is primary indication of health of oil and it can be easily carried out at site. • Dry and clean oil gives BDV results, better than the oil with moisture content and other conducting impurities. • Minimum breakdown voltage of transformer oil or dielectric strength of transformer oil at • which this oil can safely be used in transformer, is considered as 30 KV.
  • 8. •In s/s with fixed oil-handling equipment the pipe work from the clean oil tanks to the electrical apparatus should be kept clean and free from moisture. •Where portable oil handling equipment is used, flexible pipe work and hand pumps should be carefully inspected to ensure that they are free from dirt and water, and should be flushed with clean oil before use. •Hoses used for clean oil and dirty oil should be clearly marked and provided with plugs for sealing the ends when not in use. OIL TOP-UP
  • 9. Chemical parameter 1. Acidity 2. Sludge content. 3. Water content Physical Parameters 1. Inter Facial Tension 2. Flash point 3. Pour Point 4. Viscosity