Four Types of
Heat Exchanger Failures
. . . mechanical, chemically induced corrosion, combination
of mechanical and chemically induced corrosion, and scale,
mud, and algae fouling
By MARVIN P. SCHWARTZ, Chief Product Engineer, ITT Bell & Gossett
a unit of Fluid Handling Div., International Telephone & Telegraph Corp , Skokie IL
Hcat exchangers usually provide a long service life with
little or no maintenance because they do not contain any
moving parts. However, there are four types of heat
exchanger failures that can occur, and can usually be
prevented: mechanical, chemically induced corrosion,
combination of mechanical and chemically induced
corrosion, and scale, mud. and algae fouling.
This article provides the plant engineer with a detailed
look at the problems that can develop and describes the
corrective actions that should be taken to prevent them.
Mechanical-These failures can take seven different
forms: metal erosion, steam or water hammer, vibration,
thermal fatigue, freeze-up, thermal expansion. and loss of
cooling water.
Metal Erosion-Excessive fluid velocity on either the
shell or tube side of the heat exchanger can cause
damaging erosion as metal wears from the tubing. Any
corrosion already present is accelerated as erosion
removes the tube's protective films, exposing fresh metal
to further attack.
Most metal erosion problems occur inside the tubes.
The U- bend of U-type heat exchangers and the tube
entrances are the areas most prone to erosion. Figure 1
shows the metal loss in a U- bend caused by high
temperature water flashing to steam.
Tube entrance areas experience severe metal loss when
high-velocity fluid from a nozzle is divided into much
smaller streams upon entering the heat exchanger. Stream
dividing results in excessive turbulence with very high
localized velocities. High velocity and turbulence produce
a horseshoe erosion pattern at the tube entrance. Fig. 2.
Fig. 1. Metal erosion in U bend.
Maximum recommended velocity in the tubes and
entrance nozzle is a function of many variables, including
tube material, fluid handled, and temperature. Materials
such as steel, stainless steel, and copper-nickel withstand
higher tube velocities than copper. Copper is normally
limited to 7.5 fps; the other materials can handle 10 or 11
fps. If water is flowing through copper tubing, the velocity
should be less than 7.5 fps when it contains suspended
solids or is softened.
Erosion problems on the outside of tubes usually result
from impingement of wet, high-velocity gases, such as
steam. Wet gas impingement is controlled by oversizing
inlet nozzles, or by placing impingement baffles in the
inlet nozzle.
Steam or Water, Hammer -- Pressure surges or shock
waves caused by the sudden and rapid acceleration or
deceleration of a liquid can cause steam or water hammer.
The resulting pressure surges have been measured at levels
up to 20,000 psi, which is high enough to rupture or
collapse the tubing in a heat exchanger. For example, 3/4
in. x 20 BWG light drawn copper tubing has a burst
pressure of 2100 psi and a collapse pressure of 600 psi.
Damaging pressure surges can result from a cooling
water flow interruption. The stagnant cooling water is
heated enough to generate steam, and the resumption of
the flow causes a sudden condensing of the steam and
produces a damaging pressure surge, or water hammer.
Cooling water flow should always be started before heat is
applied to the exchanger.
Fluid flow control valves that open or close suddenly
also produce water hammer. Modulating control valves
are preferable to on-off types.
Fig. 2. Metal erosion at tube entrance.
Vacuum breaker vents must be provided if
condensables are handled in either the shell or tubes: they
prevent steam hammer damage resulting from condensate
accumulation. Figure 3 shows typical tube damage caused
by steam hammer. In this case, condensate accumulated in
the shell and rapidly accelerated. producing a
high-pressure shock wave that collapsed the tube and
caused the tear holes.
Properly sized steam traps with return lines pitched to a
condensate receiver or condensate return pump should be
installed to prevent this type of damage.
Vibration-Fxecssive vibration from equipment such as
air compressors or refrigeration machines can cause tube
failures in the form of a fatigue stress crack or erosion of
tubing at the point of contact with baffles. Heat
exchangers should be isolated from this type of vibration.
Shell-side fluid velocities in excess of 4 fps can induce
damaging vibrations in the tubes. causing a cutting action
at support points with baffles. Fig. 4. Velocity-induced
vibrations can also cause fatigue failures by work
hardening the tubing at baffle contact points or in U-bend
areas until a fatigue crack appears.
Thermal Fatigue --Tubing, particularly in the U- bend
area, can fail because of fatigue resulting from
accumulated stresses associated with repeated thermal
cycling. This problem is greatly aggravated as the
temperature difference across the length of the U-bend
tube increases.
Figure 5 shows an example of thermal fatigue. The
temperature difference causes tube flexing, which
produces a stress that acts additively until the tensile
strength of the material is exceeded and it cracks. The
crack usually runs radially around the tube, and many
times results in a total break. In other cases, the crack
occurs only halfway through the tube and then runs
longitudinally along it.
Freeze-Up -- These failures are most common in
evaporators or condensers; however, they can occur in
any heat exchanger in which temperatures drop below the
freezing point of either fluid in the unit. Freeze-up results
from failure to provide thermal protection, a malfunction
of the thermal protection control system or protective
heating device, improper drainage of the unit for winter
shutdown, or inadequate concentration of antifreeze
solutions.
For example, assume a chiller has improper settings or
malfunctioning controls that cool the water to a point
below its freezing point. lce forms and exerts tremendous
pressure in the tubing, which causes it to rupture or
collapse. Collapse in an evaporator, Fig. 6, usually occurs
near the tube sheet where the tube is not protected by an
inner splint.
Freeze-up failure in a condenser tube is shown in Fig.
7. In this case, cooling water was circulating inside the
tube, refrigerant was condensed on the externally finned
surface, and the unit was not properly drained for winter
shutdown. The tube distortion indicates that it was
exposed to excessive pressure caused by the freezing
water.
This type of failure is also caused by the sudden release
of refrigerant pressure from the condenser. The sudden
release caused by a line break or relief valve discharge
suddenly drops the pressure below the boiling.
point of the refrigerant. Boiling extracts heat from water in
the tubes and the liquid freezes.
Thermal Expansion-These failures are must common in
steam heated exchangers; however, they can occur in any
type in which fluid being heated is valved off without
provisions to absorb thermal expansion.
In steam-heated systems, cooling down or condensing
residual steam in the shell after the steam control valve
closes continues to heat water or other fluids on the tube
side. Continued heating causes thermal expansion, which
creates pressures far in excess of the strength of tube
sheets, cast heads, and other heat exchanger components.
Cast iron parts usually fracture because of lack of
ductility: steel tube sheets become bowed or permanently
distorted because the material's yield point is exceeded.
Figure 8 shows thermal expansion failure of a cast iron
heat exchanger head.
Fig. 3. Tube damage from steam
Fig. 4. Velocity-induced vibration cut of tube.
Fig. 5. Thermal fatigue failure in U bend.
Relief valves are installed in the heated fluid system to
prevent this kind of failure. It is also advisable to provide
some means to absorb fluid expansion For example,
installing a tank in the heated fluid system prevents
periodic discharge of relief valves, which results in loss of
system fluid and places an undue burden on the valve.
These devices are installed between the heat exchanger
and any shutoff or control valves.
Loss of Cooling Water-Compressed air aftercoolers and
gas coolers should always have a supply of cooling fluid
before a flow of hot gas is started. High gas temperatures
melt or warp the tubing if there is not an adequate supply
of cooling fluid.
Figure 9 shows the tube warping that results without
enough cooling fluid. Temperature actuated modulating
control valves should be used to regulate cooling liquid
flow.
Chemically Induced Corrosion -- These failures result
from the complex chemical interaction between the
materials of the heat exchanger and the fluids circulated
through it. There are seven types of chemically induced
corrosion failures: general corrosion, pitting corrosion,
stress corrosion, dezincification, galvanic corrosion,
crevice corrosion, and condensate grooving.
General Corrosion -- This type of corrosion is
characterized by a relatively uniform attack over the tube,
tube sheet, or shell, and there may be no evidence that
corrosion is taking place. Figure 10 shows a tube that
became so thin it actually tore down the middle.
Fairly stable aggressive conditions generate this type of
attack. Low pH (less than 7) combined with carbon dioxide
or oxygen produces the attack on copper. The blue or
bluish-green color on the tubes in Fig. 11 shows the results
of carbon dioxide attack on the inside of a copper tube.
Various chemicals, such as acids. also produce this type of
metal loss.
Selecting a material with adequate corrosion resistance
for its environment, along with using proper treatment
chemicals, maximizes heat exchanger life.
Pitting Corrosion -- Localized pitting is frequently
encountered in ferrous and nonferrous metals. It results
from the electrochemical potential set up by differences in
oxygen concentration within and outside the pit, and is
frequently referred to as a concentration cell. The
oxygen-starved pit acts as an anode and the unattacked
metal surface as a cathode. A small number of pits may be
present; however, any one can cause a heat exchanger
failure.
Pitting corrosion is most likely to occur during
shutdown periods a when there is no flow and the
environment is most suitable for the buildup of
concentration cells. The susceptibility to pitting corrosion
is further enhanced by scratches, dirt or scale deposits,
surface defects, breaks in protective scale layers. breaks in
metal surface films, and grain boundarv conditions.
Figure 12 shows an oxygen pining attack on a copper
tube, and Fig. 13 illustrates a carbon dioxide pitting attack
on a copper tube.
Stress Corrosion -- This form of corrosion attacks the
grain boundaries in stressed areas. Heat exchanger tubes
usually have both avoidable and unavoidable residual
stresses. These stresses are the result of drawing or
forming the tube during manufacture, forming U bends, or
expanding the tubes into tubesheets.
Failures from this corrosion take the form of fine cracks,
which follow lines of stress and material grain boundaries.
Figure 14 shows stress corrosion failure in admiralty
tubing.
The corrodent that causes stress corrosion on stainless
steel tubes is the chloride ion, which is potentially present
in any compound formulated with chlorine. All naturally
occurring waters contain the chloride ion in varying
degrees. The chloride stress corrosion phenomenon is not
well understood, but it is known that the frequency of
occurrence rises with an increase in temperature and
chloride ion concentration. Keeping tube wall temperatures
below 115 F (calculated with maximum, not average. fluid
temperatures) prevents stress corrosion cracking problems
with chloride ion concentration up to 50 ppm. Figure 15
shows stress corrosion cracking in a type 304 stainless
steel U bend.
Fig. 6. Collapse of evaporator tube because of freeze-up.
Fig. 7. Rupture of condenser tube because of freeze up.
Fig 8. Thermal expansion failure of cast iron head.
The corrodent that causes stress corrosion cracking on
copper or copper alloy tubes is ammonia. Very small
concentrations (1 ppm or less) can create a problem.
The vacuum breaker used on steam-heated exchangers
draws in ammonia from any leak in the ammonia
refrigeration machine. The ammonia causes stress cracking
problems, particularly in the inner U bends of the heat
exchanger tubes. Copper-nickel alloys have good
resistance to stress corrosion cracking and should be used
in applications where low concentrations of ammonia are
expected.
Dezincification -- This problem occurs in copper-zinc
alloys containing less than 85 percent copper when they
are in contact with water having a high oxygen and carbon
dioxide content, or in stagnant solutions. The effect tends
to accelerate as temperature increases or pH decreases
below 7.
Dezincification creates a porous surface in which the
zinc is chemically removed from the alloy. The remaining
copper has a sponge-like appearance. Dezincification is
prevented by using a brass with lower zinc content or a
brass containing tin or arsenic to inhibit the chemical
action, or by controlling the environment causing the
problem.
Galvanic Corrosion -- This type of corrosion occurs
when dissimilar metals are joined in the presence of an
electrolyte, such as acidic water. Galvanic corrosion
usually produces a higher rate of reaction on the less noble
metal. For example, if a simple galvanic cell composed of
copper and steel is immersed in a solution of sulfuric acid,
the less noble steel corrodes quickly and the more noble
copper is virtually unattacked.
The galvanic chart shows the relative potential of
materials to support this type of corrosion. Metals grouped
together have relatively little tendency to produce galvanic
corrosion: when two metals from substantially different
groups are coupled together in an electrolyte, substantial
corrosion of the less noble metal results.
Figure 16 shows an example of galvanic corrosion on a
steel baffle. In this case, the less noble steel baffle was
sacrificed at its point of contact with the copper tubing
Crevice Corrosion -- This type of corrosion originates in
and around hidden and secluded areas, such as between
baffles and tubes, Fig 17, or under loose scale or dirt. A
localized call develops and the resulting corrosion appears
as a metal loss with local pits, often giving the impression
that erosion is taking place. This condition is in contrast to
a vibration failure in which the metal is sharply cut and
there are no pits. Relatively stagnant conditions must exist
for crevice corrosion to occur.
The attack can often be controlled by making sure that
velocities are adequate to prevent stagnation or the
accumulation of solids.
Condensate Grooving -- This problem occurs on the
outside of steam-to-water heat exchanger tubes.
particularly in the U-bend area. It is recognized by an
irregular groove, or channel. cut in the tube as the
condensate drains from the tubing in the form of rivulets.
A corrosion cell usually develops in the wetted area
because of the electrical potential difference between the
dry and wet areas.
Fig. 9. Tube Warping because of insufficient cooling water Fig. 10. Thinning of tube because of general corrosion.
Fig, 11 General corrosion inside copper tube because of C02. Fig. 12. Oxygen pitting attack on copper tube.
mechanical and corrosion failures; erosion-corrosion and
corrosion-fatigue.
Erosion-Corrosion -- Any corrosion is greatly
accelerated if the protective films are worn away by
excessive velocity, suspended solids, or mechanical
vibration. Erosion-corrosion is usually found in the
entrance area of tubes, below the shell inlet nozzle, at the
point of contact with baffles and tubes, and inside the
U-bend area of tubes, particularly the tighter bends,
Figure 19 shows an erosion-corrosion attack. The bright
copper surface at the tube entrance is erosion; the
yellowish deposit inside the tube is corrosion.
Corrosion-Fatigue -- In this dual failure mode, stresses
associated with fatigue are the result of externally applied
mechanical loads- such as vibrations from machinery,
expansion or contraction because of temperature cycles, or
light water hammer. In most environments where only
Figure 18 shows condensate grooving and the pitting
attack. The condensate, which must be aggressive for this
grooving to occur, wears away the protective oxide film
as it drains from the tubing.
Controlling condensate pH and dissolved gases and
cleaning the tube bundle outside surface to remove oils
that prevent uniform wetting of the tube usually reduce the
problem potential.
Combination Mechanical Failure and Chemically
Induced Corrosion -- In many instances heat exchanger
failure is not from a single cause, but a combination of
more than one condition. For example, a pitting attack,
galvanic attack, and crevice corrosion attack could occur
simultaneously at one or more locations. Quite often, a
mechanical problem combining with a corrosion problem
produces a quicker failure than either of them alone. There
are two common types of combination
Fig 13. Carbon dioxide pitting attack on copper tube. Fig. 14. Stress corrosion failure in admiralty tube.
Fig 15 Stress corrosion cracking m stainless steel U bend. Fig. 16. Galvanic corrosion on steal baffle.
Fig, 17. Crevice corrosion at contact between tube and baffle. Fig.18. Condensate grooving and pitting attack on tube.
corrosion occurs, corrosion products and films block or
retard further attack. However, in corrosion-fatigue, Fig.
20, cyclic stresses rupture the protected areas and make
them permeable; this action subjects open areas to
accelerated corrosion.
Improperly supported tube bundles in domestic hot
water storage tanks often suffer from this kind of failure.
Vibrations may not be very severe: however, resulting
stresses act additively to the existing internal tensile
stresses. The stress level is raised beyond the strength of
the material and cracking or a fracture results.
Scale, Mud, and Algae Funding- Various marine
growths deposit a film or coating on the surfaces of heat
transfer tubes. The film acts as an insulator, restricting
heat flow and protecting corrodents. As a result of this
insulating effect, tube wall temperatures go up and
corrosion increases.
Scale is the result of dissolved minerals precipitating out
of heat transfer fluids. The solubility of these minerals is
altered by forces within the heat exchanger, such as
changes in temperature or chemical reactions. For
example, when calcium bicarbonate, a common constituent
of many waters, is heated, carbon dioxide is released and
the material is reduced to calcium carbonate, a relatively
insoluble compound that precipitates and coats heat
transfer surfaces. Experience shows that the rate of
precipitation is reduced with increasing find velocity. Fluid
velocity must be matched to the tube material's ability to
withstand the erosive effects of velocity.
Suspended solids are usually found in the form of sand.
iron, silt, or other visible particles in one or both of the
heat transfer fluids, If velocities are not high enough to
keep them in suspension, particles settle out, causing the
same kinds of problems associated with scale from
dissolved solids. In addition, suspended solids are very
abrasive to tubing and other heat exchanger parts. If
abrasive suspended solids are handled in the heat
exchanger, fluid velocity must be kept low enough to
prevent erosion.
Algae and other marine growths are a serious problem if
they get in the heat exchanger. In many cases, the
environment in the heat exchanger is conducive to rapid
proliferation of the algae or other marine growths. which
restrict flow and impede heat transfer. Chemical algicides,
such as chlorine. are effective in controlling algae and
other marine growths; high fluid velocities also discourage
their attachment and expansion.
GALVANIC CHART
Anodic (active) corroded end
Magnesium
Zinc
Galvanized sleet
Cadmium
Aluminum
Mild steel
Wrought iron
Cast iron
18-8 stainless steel type 304 (alive)
18-8-3 stainless steel type 316 (active)
Lead
Tin
Muntz metal
Naval bras
Nickel (active)
Yellow and red brasses
Admiralty and aluminum brasses
Copper
Silicon bronze
70-30 copper, nickel
90-10 copper, nickel
Silver solder Nickel (passive)
Monel
Titanium
18-8 stainless steel, type 304 (passive)
18-8-3 stainless steal, type 318 (passive)
Silver
Graphite
Gold
Platinum
Cathodic (noble) protected end
Fig. 20. Corrosion-fatigue attack on tube.Fig. 19. Erosion-corrosion attack on tube.

More Related Content

What's hot

Damage mechanism in boiler (thermal power plant)
Damage mechanism in boiler (thermal power plant)Damage mechanism in boiler (thermal power plant)
Damage mechanism in boiler (thermal power plant)SHIVAJI CHOUDHURY
 
10 synthesis of reaction separation system lec 10 homogenous separation
10 synthesis of reaction separation system lec 10 homogenous separation10 synthesis of reaction separation system lec 10 homogenous separation
10 synthesis of reaction separation system lec 10 homogenous separationayimsevenfold
 
HANDBOOK ON POWER PLANT CHEMISTRY.pdf
HANDBOOK ON POWER PLANT CHEMISTRY.pdfHANDBOOK ON POWER PLANT CHEMISTRY.pdf
HANDBOOK ON POWER PLANT CHEMISTRY.pdfMohamedHusseinHamed
 
selective leaching type corrosion
selective leaching type corrosionselective leaching type corrosion
selective leaching type corrosionJAYESH PAREKH
 
Residence Time Distribution Data
Residence Time Distribution DataResidence Time Distribution Data
Residence Time Distribution DataGerard B. Hawkins
 
Corrosion control by inhibitor
Corrosion control by inhibitorCorrosion control by inhibitor
Corrosion control by inhibitorAhmed_Salih
 
the standers of the drinking waters
the standers of the drinking watersthe standers of the drinking waters
the standers of the drinking watersAshishBhadani4
 
Types of Distillation & column internals
Types of Distillation & column internalsTypes of Distillation & column internals
Types of Distillation & column internalsBharat Kumar
 
Flow Accelerated Corrosion
Flow Accelerated Corrosion Flow Accelerated Corrosion
Flow Accelerated Corrosion Sruthi R
 
Cooling water Treatment presentation
Cooling water Treatment presentationCooling water Treatment presentation
Cooling water Treatment presentationkamran ul hassan
 
Cooling water problems and solutions
Cooling water problems and solutionsCooling water problems and solutions
Cooling water problems and solutionsmunawar hussain
 
Corrosion and prevention basic principles-write-up
Corrosion and prevention basic principles-write-upCorrosion and prevention basic principles-write-up
Corrosion and prevention basic principles-write-upProf. T. K. G. Namboodhiri
 
Hydrogenation Reactor Design Considerations
Hydrogenation Reactor Design ConsiderationsHydrogenation Reactor Design Considerations
Hydrogenation Reactor Design ConsiderationsGerard B. Hawkins
 
Thickner and clarifiers
Thickner and clarifiersThickner and clarifiers
Thickner and clarifiersSarwan Ursani
 
Corrosion inspection in oil and gas pipeline
Corrosion inspection in oil and gas pipelineCorrosion inspection in oil and gas pipeline
Corrosion inspection in oil and gas pipelinedia_dean
 
Magnetite layer
Magnetite layerMagnetite layer
Magnetite layerImran Khan
 
How to Use the GBHE Mixing Guides
How to Use the GBHE Mixing GuidesHow to Use the GBHE Mixing Guides
How to Use the GBHE Mixing GuidesGerard B. Hawkins
 

What's hot (20)

Damage mechanism in boiler (thermal power plant)
Damage mechanism in boiler (thermal power plant)Damage mechanism in boiler (thermal power plant)
Damage mechanism in boiler (thermal power plant)
 
10 synthesis of reaction separation system lec 10 homogenous separation
10 synthesis of reaction separation system lec 10 homogenous separation10 synthesis of reaction separation system lec 10 homogenous separation
10 synthesis of reaction separation system lec 10 homogenous separation
 
HANDBOOK ON POWER PLANT CHEMISTRY.pdf
HANDBOOK ON POWER PLANT CHEMISTRY.pdfHANDBOOK ON POWER PLANT CHEMISTRY.pdf
HANDBOOK ON POWER PLANT CHEMISTRY.pdf
 
selective leaching type corrosion
selective leaching type corrosionselective leaching type corrosion
selective leaching type corrosion
 
Three Phase Separators
Three Phase SeparatorsThree Phase Separators
Three Phase Separators
 
Residence Time Distribution Data
Residence Time Distribution DataResidence Time Distribution Data
Residence Time Distribution Data
 
Corrosion control by inhibitor
Corrosion control by inhibitorCorrosion control by inhibitor
Corrosion control by inhibitor
 
the standers of the drinking waters
the standers of the drinking watersthe standers of the drinking waters
the standers of the drinking waters
 
Zone melting
Zone meltingZone melting
Zone melting
 
Types of Distillation & column internals
Types of Distillation & column internalsTypes of Distillation & column internals
Types of Distillation & column internals
 
Flow Accelerated Corrosion
Flow Accelerated Corrosion Flow Accelerated Corrosion
Flow Accelerated Corrosion
 
Boiler water quality requirements abma
Boiler water quality requirements abmaBoiler water quality requirements abma
Boiler water quality requirements abma
 
Cooling water Treatment presentation
Cooling water Treatment presentationCooling water Treatment presentation
Cooling water Treatment presentation
 
Cooling water problems and solutions
Cooling water problems and solutionsCooling water problems and solutions
Cooling water problems and solutions
 
Corrosion and prevention basic principles-write-up
Corrosion and prevention basic principles-write-upCorrosion and prevention basic principles-write-up
Corrosion and prevention basic principles-write-up
 
Hydrogenation Reactor Design Considerations
Hydrogenation Reactor Design ConsiderationsHydrogenation Reactor Design Considerations
Hydrogenation Reactor Design Considerations
 
Thickner and clarifiers
Thickner and clarifiersThickner and clarifiers
Thickner and clarifiers
 
Corrosion inspection in oil and gas pipeline
Corrosion inspection in oil and gas pipelineCorrosion inspection in oil and gas pipeline
Corrosion inspection in oil and gas pipeline
 
Magnetite layer
Magnetite layerMagnetite layer
Magnetite layer
 
How to Use the GBHE Mixing Guides
How to Use the GBHE Mixing GuidesHow to Use the GBHE Mixing Guides
How to Use the GBHE Mixing Guides
 

Similar to 4 types-of-heat-exchanger-failures-article

Water treatment,Water Treatment & Basic Steam Distribution
Water treatment,Water Treatment&Basic Steam DistributionWater treatment,Water Treatment&Basic Steam Distribution
Water treatment,Water Treatment & Basic Steam DistributionBSMRSTU
 
BTL Steag Presentation for improving the reliability
BTL Steag Presentation for improving the reliabilityBTL Steag Presentation for improving the reliability
BTL Steag Presentation for improving the reliabilityabhilashg51
 
Is your hot water leaking
Is your hot water leakingIs your hot water leaking
Is your hot water leakinghotwaterrepairs
 
Steam distribution system by Varun Pratap Singh
Steam distribution system by Varun Pratap SinghSteam distribution system by Varun Pratap Singh
Steam distribution system by Varun Pratap SinghVarun Pratap Singh
 
Construction of babcock and wilcox boiler
Construction of babcock and wilcox boilerConstruction of babcock and wilcox boiler
Construction of babcock and wilcox boilerAQIB_HAIDER
 
Steam Condenser types,function, tube test, condenser vacuum
Steam Condenser types,function, tube test, condenser vacuumSteam Condenser types,function, tube test, condenser vacuum
Steam Condenser types,function, tube test, condenser vacuumwaqarahmed445
 
Three Mile Island Nuclear Plant steam generator safety is suspect
Three Mile Island Nuclear Plant steam generator safety is suspectThree Mile Island Nuclear Plant steam generator safety is suspect
Three Mile Island Nuclear Plant steam generator safety is suspectScott Portzline
 
Heat Exchanger (Shell and tubes) by sujan kharel..
Heat Exchanger (Shell and tubes) by sujan kharel..Heat Exchanger (Shell and tubes) by sujan kharel..
Heat Exchanger (Shell and tubes) by sujan kharel..ansaluniversity3
 
Electric aplience
Electric aplienceElectric aplience
Electric aplienceAhamed Ha
 
S3 End Of Chapter - Loss of a Trap Seal
S3 End Of Chapter - Loss of a Trap SealS3 End Of Chapter - Loss of a Trap Seal
S3 End Of Chapter - Loss of a Trap Sealno suhaila
 
2nd Revised FYP Reporting
2nd Revised FYP Reporting2nd Revised FYP Reporting
2nd Revised FYP ReportingBurhan Ahmed
 
Condenser in thermal power plants
Condenser in thermal power plantsCondenser in thermal power plants
Condenser in thermal power plantsSHIVAJI CHOUDHURY
 
Chilled water piping basics
Chilled water piping basicsChilled water piping basics
Chilled water piping basicsAp Naseem
 
electric arc furnace
electric arc furnaceelectric arc furnace
electric arc furnaceSanjitDhar
 
How to prevent water heater leaks
How to prevent water heater leaksHow to prevent water heater leaks
How to prevent water heater leaks21 Handshake
 

Similar to 4 types-of-heat-exchanger-failures-article (20)

Troubleshooting the Boiler Problems
Troubleshooting the Boiler ProblemsTroubleshooting the Boiler Problems
Troubleshooting the Boiler Problems
 
Water treatment,Water Treatment & Basic Steam Distribution
Water treatment,Water Treatment&Basic Steam DistributionWater treatment,Water Treatment&Basic Steam Distribution
Water treatment,Water Treatment & Basic Steam Distribution
 
Sugar Industrial Boiler tube failure.pdf
Sugar Industrial Boiler tube failure.pdfSugar Industrial Boiler tube failure.pdf
Sugar Industrial Boiler tube failure.pdf
 
BTL Steag Presentation for improving the reliability
BTL Steag Presentation for improving the reliabilityBTL Steag Presentation for improving the reliability
BTL Steag Presentation for improving the reliability
 
Is your hot water leaking
Is your hot water leakingIs your hot water leaking
Is your hot water leaking
 
Steam distribution system by Varun Pratap Singh
Steam distribution system by Varun Pratap SinghSteam distribution system by Varun Pratap Singh
Steam distribution system by Varun Pratap Singh
 
Heat pipe Best PPT
Heat pipe Best PPTHeat pipe Best PPT
Heat pipe Best PPT
 
Construction of babcock and wilcox boiler
Construction of babcock and wilcox boilerConstruction of babcock and wilcox boiler
Construction of babcock and wilcox boiler
 
Steam Condenser types,function, tube test, condenser vacuum
Steam Condenser types,function, tube test, condenser vacuumSteam Condenser types,function, tube test, condenser vacuum
Steam Condenser types,function, tube test, condenser vacuum
 
Thermal fatigue failure in a FBC boiler
Thermal fatigue failure in a FBC boilerThermal fatigue failure in a FBC boiler
Thermal fatigue failure in a FBC boiler
 
Three Mile Island Nuclear Plant steam generator safety is suspect
Three Mile Island Nuclear Plant steam generator safety is suspectThree Mile Island Nuclear Plant steam generator safety is suspect
Three Mile Island Nuclear Plant steam generator safety is suspect
 
Heat Exchanger (Shell and tubes) by sujan kharel..
Heat Exchanger (Shell and tubes) by sujan kharel..Heat Exchanger (Shell and tubes) by sujan kharel..
Heat Exchanger (Shell and tubes) by sujan kharel..
 
Electric aplience
Electric aplienceElectric aplience
Electric aplience
 
S3 End Of Chapter - Loss of a Trap Seal
S3 End Of Chapter - Loss of a Trap SealS3 End Of Chapter - Loss of a Trap Seal
S3 End Of Chapter - Loss of a Trap Seal
 
2nd Revised FYP Reporting
2nd Revised FYP Reporting2nd Revised FYP Reporting
2nd Revised FYP Reporting
 
Condenser in thermal power plants
Condenser in thermal power plantsCondenser in thermal power plants
Condenser in thermal power plants
 
Chilled water piping basics
Chilled water piping basicsChilled water piping basics
Chilled water piping basics
 
electric arc furnace
electric arc furnaceelectric arc furnace
electric arc furnace
 
How to prevent water heater leaks
How to prevent water heater leaksHow to prevent water heater leaks
How to prevent water heater leaks
 
Sealed system components
Sealed system componentsSealed system components
Sealed system components
 

Recently uploaded

Web & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdfWeb & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdfJayanti Pande
 
Separation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and ActinidesSeparation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and ActinidesFatimaKhan178732
 
Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)eniolaolutunde
 
Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111Sapana Sha
 
1029 - Danh muc Sach Giao Khoa 10 . pdf
1029 -  Danh muc Sach Giao Khoa 10 . pdf1029 -  Danh muc Sach Giao Khoa 10 . pdf
1029 - Danh muc Sach Giao Khoa 10 . pdfQucHHunhnh
 
Activity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdfActivity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdfciinovamais
 
Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104misteraugie
 
Introduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The BasicsIntroduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The BasicsTechSoup
 
A Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy ReformA Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy ReformChameera Dedduwage
 
The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13Steve Thomason
 
Russian Call Girls in Andheri Airport Mumbai WhatsApp 9167673311 💞 Full Nigh...
Russian Call Girls in Andheri Airport Mumbai WhatsApp  9167673311 💞 Full Nigh...Russian Call Girls in Andheri Airport Mumbai WhatsApp  9167673311 💞 Full Nigh...
Russian Call Girls in Andheri Airport Mumbai WhatsApp 9167673311 💞 Full Nigh...Pooja Nehwal
 
POINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptx
POINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptxPOINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptx
POINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptxSayali Powar
 
Ecosystem Interactions Class Discussion Presentation in Blue Green Lined Styl...
Ecosystem Interactions Class Discussion Presentation in Blue Green Lined Styl...Ecosystem Interactions Class Discussion Presentation in Blue Green Lined Styl...
Ecosystem Interactions Class Discussion Presentation in Blue Green Lined Styl...fonyou31
 
Accessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactAccessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactdawncurless
 
Measures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and ModeMeasures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and ModeThiyagu K
 
microwave assisted reaction. General introduction
microwave assisted reaction. General introductionmicrowave assisted reaction. General introduction
microwave assisted reaction. General introductionMaksud Ahmed
 
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptxSOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptxiammrhaywood
 

Recently uploaded (20)

Mattingly "AI & Prompt Design: Structured Data, Assistants, & RAG"
Mattingly "AI & Prompt Design: Structured Data, Assistants, & RAG"Mattingly "AI & Prompt Design: Structured Data, Assistants, & RAG"
Mattingly "AI & Prompt Design: Structured Data, Assistants, & RAG"
 
Web & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdfWeb & Social Media Analytics Previous Year Question Paper.pdf
Web & Social Media Analytics Previous Year Question Paper.pdf
 
Separation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and ActinidesSeparation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and Actinides
 
Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)
 
Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111
 
1029 - Danh muc Sach Giao Khoa 10 . pdf
1029 -  Danh muc Sach Giao Khoa 10 . pdf1029 -  Danh muc Sach Giao Khoa 10 . pdf
1029 - Danh muc Sach Giao Khoa 10 . pdf
 
Activity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdfActivity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdf
 
Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104
 
Introduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The BasicsIntroduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The Basics
 
A Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy ReformA Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy Reform
 
The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13
 
Russian Call Girls in Andheri Airport Mumbai WhatsApp 9167673311 💞 Full Nigh...
Russian Call Girls in Andheri Airport Mumbai WhatsApp  9167673311 💞 Full Nigh...Russian Call Girls in Andheri Airport Mumbai WhatsApp  9167673311 💞 Full Nigh...
Russian Call Girls in Andheri Airport Mumbai WhatsApp 9167673311 💞 Full Nigh...
 
POINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptx
POINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptxPOINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptx
POINT- BIOCHEMISTRY SEM 2 ENZYMES UNIT 5.pptx
 
Código Creativo y Arte de Software | Unidad 1
Código Creativo y Arte de Software | Unidad 1Código Creativo y Arte de Software | Unidad 1
Código Creativo y Arte de Software | Unidad 1
 
Ecosystem Interactions Class Discussion Presentation in Blue Green Lined Styl...
Ecosystem Interactions Class Discussion Presentation in Blue Green Lined Styl...Ecosystem Interactions Class Discussion Presentation in Blue Green Lined Styl...
Ecosystem Interactions Class Discussion Presentation in Blue Green Lined Styl...
 
Accessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactAccessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impact
 
Measures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and ModeMeasures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and Mode
 
microwave assisted reaction. General introduction
microwave assisted reaction. General introductionmicrowave assisted reaction. General introduction
microwave assisted reaction. General introduction
 
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptxSOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
 
Mattingly "AI & Prompt Design: The Basics of Prompt Design"
Mattingly "AI & Prompt Design: The Basics of Prompt Design"Mattingly "AI & Prompt Design: The Basics of Prompt Design"
Mattingly "AI & Prompt Design: The Basics of Prompt Design"
 

4 types-of-heat-exchanger-failures-article

  • 1. Four Types of Heat Exchanger Failures . . . mechanical, chemically induced corrosion, combination of mechanical and chemically induced corrosion, and scale, mud, and algae fouling By MARVIN P. SCHWARTZ, Chief Product Engineer, ITT Bell & Gossett a unit of Fluid Handling Div., International Telephone & Telegraph Corp , Skokie IL Hcat exchangers usually provide a long service life with little or no maintenance because they do not contain any moving parts. However, there are four types of heat exchanger failures that can occur, and can usually be prevented: mechanical, chemically induced corrosion, combination of mechanical and chemically induced corrosion, and scale, mud. and algae fouling. This article provides the plant engineer with a detailed look at the problems that can develop and describes the corrective actions that should be taken to prevent them. Mechanical-These failures can take seven different forms: metal erosion, steam or water hammer, vibration, thermal fatigue, freeze-up, thermal expansion. and loss of cooling water. Metal Erosion-Excessive fluid velocity on either the shell or tube side of the heat exchanger can cause damaging erosion as metal wears from the tubing. Any corrosion already present is accelerated as erosion removes the tube's protective films, exposing fresh metal to further attack. Most metal erosion problems occur inside the tubes. The U- bend of U-type heat exchangers and the tube entrances are the areas most prone to erosion. Figure 1 shows the metal loss in a U- bend caused by high temperature water flashing to steam. Tube entrance areas experience severe metal loss when high-velocity fluid from a nozzle is divided into much smaller streams upon entering the heat exchanger. Stream dividing results in excessive turbulence with very high localized velocities. High velocity and turbulence produce a horseshoe erosion pattern at the tube entrance. Fig. 2. Fig. 1. Metal erosion in U bend. Maximum recommended velocity in the tubes and entrance nozzle is a function of many variables, including tube material, fluid handled, and temperature. Materials such as steel, stainless steel, and copper-nickel withstand higher tube velocities than copper. Copper is normally limited to 7.5 fps; the other materials can handle 10 or 11 fps. If water is flowing through copper tubing, the velocity should be less than 7.5 fps when it contains suspended solids or is softened. Erosion problems on the outside of tubes usually result from impingement of wet, high-velocity gases, such as steam. Wet gas impingement is controlled by oversizing inlet nozzles, or by placing impingement baffles in the inlet nozzle. Steam or Water, Hammer -- Pressure surges or shock waves caused by the sudden and rapid acceleration or deceleration of a liquid can cause steam or water hammer. The resulting pressure surges have been measured at levels up to 20,000 psi, which is high enough to rupture or collapse the tubing in a heat exchanger. For example, 3/4 in. x 20 BWG light drawn copper tubing has a burst pressure of 2100 psi and a collapse pressure of 600 psi. Damaging pressure surges can result from a cooling water flow interruption. The stagnant cooling water is heated enough to generate steam, and the resumption of the flow causes a sudden condensing of the steam and produces a damaging pressure surge, or water hammer. Cooling water flow should always be started before heat is applied to the exchanger. Fluid flow control valves that open or close suddenly also produce water hammer. Modulating control valves are preferable to on-off types. Fig. 2. Metal erosion at tube entrance.
  • 2. Vacuum breaker vents must be provided if condensables are handled in either the shell or tubes: they prevent steam hammer damage resulting from condensate accumulation. Figure 3 shows typical tube damage caused by steam hammer. In this case, condensate accumulated in the shell and rapidly accelerated. producing a high-pressure shock wave that collapsed the tube and caused the tear holes. Properly sized steam traps with return lines pitched to a condensate receiver or condensate return pump should be installed to prevent this type of damage. Vibration-Fxecssive vibration from equipment such as air compressors or refrigeration machines can cause tube failures in the form of a fatigue stress crack or erosion of tubing at the point of contact with baffles. Heat exchangers should be isolated from this type of vibration. Shell-side fluid velocities in excess of 4 fps can induce damaging vibrations in the tubes. causing a cutting action at support points with baffles. Fig. 4. Velocity-induced vibrations can also cause fatigue failures by work hardening the tubing at baffle contact points or in U-bend areas until a fatigue crack appears. Thermal Fatigue --Tubing, particularly in the U- bend area, can fail because of fatigue resulting from accumulated stresses associated with repeated thermal cycling. This problem is greatly aggravated as the temperature difference across the length of the U-bend tube increases. Figure 5 shows an example of thermal fatigue. The temperature difference causes tube flexing, which produces a stress that acts additively until the tensile strength of the material is exceeded and it cracks. The crack usually runs radially around the tube, and many times results in a total break. In other cases, the crack occurs only halfway through the tube and then runs longitudinally along it. Freeze-Up -- These failures are most common in evaporators or condensers; however, they can occur in any heat exchanger in which temperatures drop below the freezing point of either fluid in the unit. Freeze-up results from failure to provide thermal protection, a malfunction of the thermal protection control system or protective heating device, improper drainage of the unit for winter shutdown, or inadequate concentration of antifreeze solutions. For example, assume a chiller has improper settings or malfunctioning controls that cool the water to a point below its freezing point. lce forms and exerts tremendous pressure in the tubing, which causes it to rupture or collapse. Collapse in an evaporator, Fig. 6, usually occurs near the tube sheet where the tube is not protected by an inner splint. Freeze-up failure in a condenser tube is shown in Fig. 7. In this case, cooling water was circulating inside the tube, refrigerant was condensed on the externally finned surface, and the unit was not properly drained for winter shutdown. The tube distortion indicates that it was exposed to excessive pressure caused by the freezing water. This type of failure is also caused by the sudden release of refrigerant pressure from the condenser. The sudden release caused by a line break or relief valve discharge suddenly drops the pressure below the boiling. point of the refrigerant. Boiling extracts heat from water in the tubes and the liquid freezes. Thermal Expansion-These failures are must common in steam heated exchangers; however, they can occur in any type in which fluid being heated is valved off without provisions to absorb thermal expansion. In steam-heated systems, cooling down or condensing residual steam in the shell after the steam control valve closes continues to heat water or other fluids on the tube side. Continued heating causes thermal expansion, which creates pressures far in excess of the strength of tube sheets, cast heads, and other heat exchanger components. Cast iron parts usually fracture because of lack of ductility: steel tube sheets become bowed or permanently distorted because the material's yield point is exceeded. Figure 8 shows thermal expansion failure of a cast iron heat exchanger head. Fig. 3. Tube damage from steam Fig. 4. Velocity-induced vibration cut of tube. Fig. 5. Thermal fatigue failure in U bend.
  • 3. Relief valves are installed in the heated fluid system to prevent this kind of failure. It is also advisable to provide some means to absorb fluid expansion For example, installing a tank in the heated fluid system prevents periodic discharge of relief valves, which results in loss of system fluid and places an undue burden on the valve. These devices are installed between the heat exchanger and any shutoff or control valves. Loss of Cooling Water-Compressed air aftercoolers and gas coolers should always have a supply of cooling fluid before a flow of hot gas is started. High gas temperatures melt or warp the tubing if there is not an adequate supply of cooling fluid. Figure 9 shows the tube warping that results without enough cooling fluid. Temperature actuated modulating control valves should be used to regulate cooling liquid flow. Chemically Induced Corrosion -- These failures result from the complex chemical interaction between the materials of the heat exchanger and the fluids circulated through it. There are seven types of chemically induced corrosion failures: general corrosion, pitting corrosion, stress corrosion, dezincification, galvanic corrosion, crevice corrosion, and condensate grooving. General Corrosion -- This type of corrosion is characterized by a relatively uniform attack over the tube, tube sheet, or shell, and there may be no evidence that corrosion is taking place. Figure 10 shows a tube that became so thin it actually tore down the middle. Fairly stable aggressive conditions generate this type of attack. Low pH (less than 7) combined with carbon dioxide or oxygen produces the attack on copper. The blue or bluish-green color on the tubes in Fig. 11 shows the results of carbon dioxide attack on the inside of a copper tube. Various chemicals, such as acids. also produce this type of metal loss. Selecting a material with adequate corrosion resistance for its environment, along with using proper treatment chemicals, maximizes heat exchanger life. Pitting Corrosion -- Localized pitting is frequently encountered in ferrous and nonferrous metals. It results from the electrochemical potential set up by differences in oxygen concentration within and outside the pit, and is frequently referred to as a concentration cell. The oxygen-starved pit acts as an anode and the unattacked metal surface as a cathode. A small number of pits may be present; however, any one can cause a heat exchanger failure. Pitting corrosion is most likely to occur during shutdown periods a when there is no flow and the environment is most suitable for the buildup of concentration cells. The susceptibility to pitting corrosion is further enhanced by scratches, dirt or scale deposits, surface defects, breaks in protective scale layers. breaks in metal surface films, and grain boundarv conditions. Figure 12 shows an oxygen pining attack on a copper tube, and Fig. 13 illustrates a carbon dioxide pitting attack on a copper tube. Stress Corrosion -- This form of corrosion attacks the grain boundaries in stressed areas. Heat exchanger tubes usually have both avoidable and unavoidable residual stresses. These stresses are the result of drawing or forming the tube during manufacture, forming U bends, or expanding the tubes into tubesheets. Failures from this corrosion take the form of fine cracks, which follow lines of stress and material grain boundaries. Figure 14 shows stress corrosion failure in admiralty tubing. The corrodent that causes stress corrosion on stainless steel tubes is the chloride ion, which is potentially present in any compound formulated with chlorine. All naturally occurring waters contain the chloride ion in varying degrees. The chloride stress corrosion phenomenon is not well understood, but it is known that the frequency of occurrence rises with an increase in temperature and chloride ion concentration. Keeping tube wall temperatures below 115 F (calculated with maximum, not average. fluid temperatures) prevents stress corrosion cracking problems with chloride ion concentration up to 50 ppm. Figure 15 shows stress corrosion cracking in a type 304 stainless steel U bend. Fig. 6. Collapse of evaporator tube because of freeze-up. Fig. 7. Rupture of condenser tube because of freeze up. Fig 8. Thermal expansion failure of cast iron head.
  • 4. The corrodent that causes stress corrosion cracking on copper or copper alloy tubes is ammonia. Very small concentrations (1 ppm or less) can create a problem. The vacuum breaker used on steam-heated exchangers draws in ammonia from any leak in the ammonia refrigeration machine. The ammonia causes stress cracking problems, particularly in the inner U bends of the heat exchanger tubes. Copper-nickel alloys have good resistance to stress corrosion cracking and should be used in applications where low concentrations of ammonia are expected. Dezincification -- This problem occurs in copper-zinc alloys containing less than 85 percent copper when they are in contact with water having a high oxygen and carbon dioxide content, or in stagnant solutions. The effect tends to accelerate as temperature increases or pH decreases below 7. Dezincification creates a porous surface in which the zinc is chemically removed from the alloy. The remaining copper has a sponge-like appearance. Dezincification is prevented by using a brass with lower zinc content or a brass containing tin or arsenic to inhibit the chemical action, or by controlling the environment causing the problem. Galvanic Corrosion -- This type of corrosion occurs when dissimilar metals are joined in the presence of an electrolyte, such as acidic water. Galvanic corrosion usually produces a higher rate of reaction on the less noble metal. For example, if a simple galvanic cell composed of copper and steel is immersed in a solution of sulfuric acid, the less noble steel corrodes quickly and the more noble copper is virtually unattacked. The galvanic chart shows the relative potential of materials to support this type of corrosion. Metals grouped together have relatively little tendency to produce galvanic corrosion: when two metals from substantially different groups are coupled together in an electrolyte, substantial corrosion of the less noble metal results. Figure 16 shows an example of galvanic corrosion on a steel baffle. In this case, the less noble steel baffle was sacrificed at its point of contact with the copper tubing Crevice Corrosion -- This type of corrosion originates in and around hidden and secluded areas, such as between baffles and tubes, Fig 17, or under loose scale or dirt. A localized call develops and the resulting corrosion appears as a metal loss with local pits, often giving the impression that erosion is taking place. This condition is in contrast to a vibration failure in which the metal is sharply cut and there are no pits. Relatively stagnant conditions must exist for crevice corrosion to occur. The attack can often be controlled by making sure that velocities are adequate to prevent stagnation or the accumulation of solids. Condensate Grooving -- This problem occurs on the outside of steam-to-water heat exchanger tubes. particularly in the U-bend area. It is recognized by an irregular groove, or channel. cut in the tube as the condensate drains from the tubing in the form of rivulets. A corrosion cell usually develops in the wetted area because of the electrical potential difference between the dry and wet areas. Fig. 9. Tube Warping because of insufficient cooling water Fig. 10. Thinning of tube because of general corrosion. Fig, 11 General corrosion inside copper tube because of C02. Fig. 12. Oxygen pitting attack on copper tube.
  • 5. mechanical and corrosion failures; erosion-corrosion and corrosion-fatigue. Erosion-Corrosion -- Any corrosion is greatly accelerated if the protective films are worn away by excessive velocity, suspended solids, or mechanical vibration. Erosion-corrosion is usually found in the entrance area of tubes, below the shell inlet nozzle, at the point of contact with baffles and tubes, and inside the U-bend area of tubes, particularly the tighter bends, Figure 19 shows an erosion-corrosion attack. The bright copper surface at the tube entrance is erosion; the yellowish deposit inside the tube is corrosion. Corrosion-Fatigue -- In this dual failure mode, stresses associated with fatigue are the result of externally applied mechanical loads- such as vibrations from machinery, expansion or contraction because of temperature cycles, or light water hammer. In most environments where only Figure 18 shows condensate grooving and the pitting attack. The condensate, which must be aggressive for this grooving to occur, wears away the protective oxide film as it drains from the tubing. Controlling condensate pH and dissolved gases and cleaning the tube bundle outside surface to remove oils that prevent uniform wetting of the tube usually reduce the problem potential. Combination Mechanical Failure and Chemically Induced Corrosion -- In many instances heat exchanger failure is not from a single cause, but a combination of more than one condition. For example, a pitting attack, galvanic attack, and crevice corrosion attack could occur simultaneously at one or more locations. Quite often, a mechanical problem combining with a corrosion problem produces a quicker failure than either of them alone. There are two common types of combination Fig 13. Carbon dioxide pitting attack on copper tube. Fig. 14. Stress corrosion failure in admiralty tube. Fig 15 Stress corrosion cracking m stainless steel U bend. Fig. 16. Galvanic corrosion on steal baffle. Fig, 17. Crevice corrosion at contact between tube and baffle. Fig.18. Condensate grooving and pitting attack on tube.
  • 6. corrosion occurs, corrosion products and films block or retard further attack. However, in corrosion-fatigue, Fig. 20, cyclic stresses rupture the protected areas and make them permeable; this action subjects open areas to accelerated corrosion. Improperly supported tube bundles in domestic hot water storage tanks often suffer from this kind of failure. Vibrations may not be very severe: however, resulting stresses act additively to the existing internal tensile stresses. The stress level is raised beyond the strength of the material and cracking or a fracture results. Scale, Mud, and Algae Funding- Various marine growths deposit a film or coating on the surfaces of heat transfer tubes. The film acts as an insulator, restricting heat flow and protecting corrodents. As a result of this insulating effect, tube wall temperatures go up and corrosion increases. Scale is the result of dissolved minerals precipitating out of heat transfer fluids. The solubility of these minerals is altered by forces within the heat exchanger, such as changes in temperature or chemical reactions. For example, when calcium bicarbonate, a common constituent of many waters, is heated, carbon dioxide is released and the material is reduced to calcium carbonate, a relatively insoluble compound that precipitates and coats heat transfer surfaces. Experience shows that the rate of precipitation is reduced with increasing find velocity. Fluid velocity must be matched to the tube material's ability to withstand the erosive effects of velocity. Suspended solids are usually found in the form of sand. iron, silt, or other visible particles in one or both of the heat transfer fluids, If velocities are not high enough to keep them in suspension, particles settle out, causing the same kinds of problems associated with scale from dissolved solids. In addition, suspended solids are very abrasive to tubing and other heat exchanger parts. If abrasive suspended solids are handled in the heat exchanger, fluid velocity must be kept low enough to prevent erosion. Algae and other marine growths are a serious problem if they get in the heat exchanger. In many cases, the environment in the heat exchanger is conducive to rapid proliferation of the algae or other marine growths. which restrict flow and impede heat transfer. Chemical algicides, such as chlorine. are effective in controlling algae and other marine growths; high fluid velocities also discourage their attachment and expansion. GALVANIC CHART Anodic (active) corroded end Magnesium Zinc Galvanized sleet Cadmium Aluminum Mild steel Wrought iron Cast iron 18-8 stainless steel type 304 (alive) 18-8-3 stainless steel type 316 (active) Lead Tin Muntz metal Naval bras Nickel (active) Yellow and red brasses Admiralty and aluminum brasses Copper Silicon bronze 70-30 copper, nickel 90-10 copper, nickel Silver solder Nickel (passive) Monel Titanium 18-8 stainless steel, type 304 (passive) 18-8-3 stainless steal, type 318 (passive) Silver Graphite Gold Platinum Cathodic (noble) protected end Fig. 20. Corrosion-fatigue attack on tube.Fig. 19. Erosion-corrosion attack on tube.