SlideShare a Scribd company logo
1 of 9
Download to read offline
฀ ฀ ฀ ฀ ฀ ฀ ฀
118
Abstract
With an increasing number of photovoltaic (PV)
inverters in the distribution system, their impact is no
longer negligible, especially in the aspect of dynamic
interaction. Accordingly, a comparison is done among
PV inverters of different reactive power control modes,
to determine their impact on the system voltage profile,
power loss and small-signal stability. Generalized
Nyquist Criteria (GNC) based on impedances in DQ
frames is used for stability assessment, which is validated
by time domain simulation results and also system
eigenvalues calculation results from MATLAB. From
these, guidelines are formulated to manage PV inverter
reactive power control strategies. Reactive power
control mode of volt-var Q=f(V) is preferred to other
reactive power modes to avoid voltage profile problem
and reduce power loss, but will induce small-signal
instability and cause PV terminal voltage oscillations.
There’s tradeoff between static influence and dynamic
impact in choosing the local reactive power control
strategies.
1. Introduction
DUE to environment problems caused by fossil fuels,
installation of photovoltaic (PV) systems is increasing
rapidly worldwide. The impact on voltage profile is the
most commonly recognized problem caused by high PV
inverter penetration in distribution systems. The impact
on voltage profile is bigger as the PV capacity increases,
which has a limit in the amount of PV power to be
installed with respect to the overvoltage problem [1-7].
However, this scenario has been improved as according
to the revised IEEE 1547 standard, distribution resources
can actively participate in the voltage regulation [8].
Different local reactive power control strategies have
been designed and compared for PV generators to
regulate system voltage [9,10]. The comparison of
different Q control modes should not only consider the
regulation of voltage profile, but also take in effect of
the system power loss. Contrary to PV impact on voltage
profile, system power loss forms a U shape trajectory as
PV generator capacity increases [11]. The static analysis
in this paper demonstrates that system power loss is also
a U shape trajectory as reactive power injected by PV
varies.
IEEE 1547 newest version requires PV inverters to have
reactive power control, thus increasing inverter control
complexity. As negative incremental resistance caused
by constant power behavior of power converters may
bring stability problem, and stability of PV integration
to distributed system attracts more and more attention
[12-17]. Different from real-time simulation or
character root method, which require full models of
all components in distributed system, the Generalized
Nyquist stability Criterion (GNC) for stability analysis
of three-phase AC power system only uses measured
D-Q Frame impedances [18]. Compared to the positive
sequence impedance method used in [19], D-Q frame
impedance matrix method is more accurate for stability
assessment of system with PV inverter that has non-
symmetrical control in DQ frame including DC voltage
loop and phase locked loop (PLL) [20]. As there is
neither frequency control nor generator inertia dynamics
in the distribution system studied, the stability discussed
in this paper is mainly voltage stability. And only small-
signal stability can be investigated by GNC method
which is based on a certain steady state operation point
instead of stability during the transients including short-
term voltage stability or long-term voltage stability.
The goal of this paper is to analyze the small-signal
stability impact of utility scale PV farm composed by
multiple PV inverters under different reactive power
control modes to medium voltage distributed system.The
small-signal assessment approach is GNC based on grid
Small-signal tability mpact of tility PV
with eactive ower ontrol on the edium
oltage istributed stems
Y TANG*, R BURGOS
Center for Power Electronics Systems (CPES), Virginia Tech
KEYWORDS
Distribution system, photovoltaic (PV), power loss, reactive power control, small-signal stability, voltage profile.
*yetang@vt.edu
฀ ฀ ฀ ฀ ฀ ฀ ฀
119
as 5 MW. The circuit diagram of the distribution system
is shown by Fig.1, and impedance and load parameters
for the system are given in [21].
Fig. 1. Diagram of case systems. 56 bus system.
The commonly used photovoltaic generator local
reactive power control modes include mode 1 unity
power factor, mode 2 fixed reactive power, mode 3
fixed power factor, mode 4 reactive power as a function
of active power (Watt-var mode) and mode 5 reactive
power as a function of bus voltage (Volt-var mode) [8].
Mode 4 and mode 5 are illustrated by Fig.2.
Fig. 2. (a) Watt-var mode curve (b) Volt-var Q= f(V) mode droop curve
All five modes are applied on the PV farm connected to
bus 45. Fig.3 is the voltage profile of PV farm terminal
bus 45 when the PV active power increases from 0 to full
power in correspond to irradiance variation. In mode 2,
reactive power reference is set to be 1.5 MVar inductive
to compensate the voltage boost caused by active power
injection shown by mode 1 curve, but this setting has
the problem of under-voltage when irradiance is low,
showing that this mode is lack of flexibility for voltage
regulation as a local control strategy. In mode 3, power
factor is set to be 0.91 lagging. In mode 4, P1
= 3.5MW
and the slope is -1 in the curve in Fig.2(a). In mode 5,
and PV terminal D-Q frame impedances. Of all reactive
power local control modes in IEEE 1547, the volt-var
mode is the most preferred mode considering the static
impact on the system voltage profile and grid power loss.
Then a comparison is done among PV inverter terminal
D-Q frame impedances when PV is under different
reactive power control modes, which shows that volt-
var mode control have a significant impact on PV
terminal D-Q frame impedances and cause unstable PV
integration case in weak grids. When instability occurs,
PV terminal sees oscillation voltage magnitude. The
instability phenomena discovered by GNC application
is proved by both the time domain simulation of the grid
with the PV farm and the eigenvalue acquisition from the
state-space model of the PV connection. Finally, several
alternate solutions are provided to mitigate instability
issues of volt-var control schemes.
The paper is organized as follows: Section II introduces
the test-bed system of a radial 56 bus system with high
PV penetration. Different reactive power control modes
are listed and compared in the aspect of impact on
system voltage and power loss. Section III describes the
dynamic model of utility PV farm including switching
model and the average model of PV generator and
its controller, based on which PV generator terminal
impedance is derived in DQ frame. Section IV shows the
GNC application result using the DQ frame impedances
of the grid and the PV generators under different Q
control modes. Section V validates small-signal stability
assessment result of GNC by time domain waveform of
PV output currents and the eigenvalues of state space
model as well. Section VI is the conclusion about the
comparison of different Q control modes and impact of
PV penetration on distribution system voltage and small-
signal stability, and guidelines about PV allocation and
control for utility to avoid voltage profile problem and
ensure system stability.
2. Static Comparison of
Different Q Control
The test-bed distribution system in this paper is one of
Southern California Edison (SCE)’s distribution feeders
with very high penetration of Photovoltaics. It is a 12 kV
and very lightly loaded rural distribution feeder, with a
radial topology and a PV integration that can be as high
฀ ฀ ฀ ฀ ฀ ฀ ฀
120
bus 45 in 56 bus system. System power loss is plotted
in Fig.4, Fig.4 reveals that for the typical load condition
of 56 bus system, system power loss forms a U shape
curve both for active power injection and reactive power
injection. The typical loading condition for the testbed
is that all the loads are 40% constant power and 60%
constant impedance load with a lagging power factor.And
as the voltage magnitudes of the buses change very little
in percentage, so the active currents and reactive currents
can be estimated to be proportional to the active power and
reactive power flowing through the lines. In addition, the
power loss of the lines are quadratic functions in terms of
the active currents and reactive currents, so system power
loss forms a U shape curve both for active power injection
and reactive power injection. The dip of the U shape is the
point that active currents and reactive currents on the lines
caused by load are starting to change flowing direction
because of PV injection. The fact that certain amount
of active power and reactive power should be injected
to achieve minimum power loss helps to understand the
comparison of impact on system power loss of different
reactive power control modes in Fig.5. Power loss under
unity power factor is set as base value of 100% in each
set of bar curves. Mode 2 and 3 cause higher power loss
than other options because PV inverter in mode 2 and 3
is consuming reactive power all the way. In contrast, PV
under mode 4 and mode 5 is only inductive when needed
(the active power injected exceeds P1
or PV terminal
voltage is over the threshold of V3
). In addition, when
irradiance is zero, mode 5 injects reactive power because
voltage bus 45 is below V2
=1.00p.u., which reduces
system power loss compared to other modes.
Fig. 4. System loss in terms of P and Q injected to PV connection bus
Fig. 3. Voltage of under PV injection bus
V1
=0.975p.u., V2
=1.00p.u., V3
=1.025p.u., V4
=1.05p.u. and
Qmax
=2.5MVar. Mode 3 to mode 5 are all able to regulate
the PV bus voltage within the limit ofASIC standard [22].
The difference of different Q control modes in voltage
profile of Fig.3 can be interpreted more by employing
the sensitivity analysis results in [23] that active power
injection increases bus voltage by a ratio of resistor sum
on the line and reactive power consumption reduces bus
voltagebyaratioofreactancesumontheline.Unitypower
factor curve is a rising straight line, and constant Q is also
a straight line with the same ratio but parallelly lowered
because of a constant voltage reduction by a constant Q
consumption. The watt-var mode align with unity power
factor mode before the active power injected reaches the
inflection point of P1
in the watt-var curve and after that
point the reactive power consumption starts to compensate
the voltage rising caused by active power, so that the bus
voltage can be controlled within upper limit. As for the
fixed PF mode, with a lagging PF, the increasing ratio
of voltage over active power is lower compared to unity
power factor as a combination of rising ratio of active
power and falling ratio of reactive power consumption.
And different from all these Q modes, volt-var mode
regulates the AC terminal voltages directly so that the
PV produces reactive power if AC voltage magnitude is
lower than V2
=1.00p.u. and consumes reactive power if
AC voltage magnitude is higher than V3
=1.025p.u. and
the voltage profile can be controlled within lower limit
and upper limit.
To analyze the impact on system power loss, different
amount of active power and reactive power is injected to
฀ ฀ ฀ ฀ ฀ ฀ ฀
121
Fig.6 Topology of utility PV
With switching ripple ignored, average model of the PV
generator in DQ axis is formed in Fig.7. The average
model of DC side is on the left side and average model
of AC side is on the right side, which is based on primary
side voltage of step up transformer.
Fig.7 Average model of PV generator
For PV controller in Fig.6, AC current regulator is a PI
controller with parameter of kpi
= 0.0012 and kii
=0.36,
making the current control bandwidth to be 220 Hz . DC
voltage regulator is also a PI controller with parameter
of kpv
=-3, kiv
=-30, making the DC voltage control loop
bandwidth to be 22.2 Hz. Vdc_ref
is the DC voltage reference
given by maximum power point tracking (MPPT) block.
The most widely used MPPT principle is perturb and
observe (P&O), which perturbs PV array voltage to find
the right direction of adjusting DC voltage to increase
PV array output power . For utility scale single stage PV
inverter, the frequency of MPPT block to change Vdc_ref
is
smallerthan DC voltage loop bandwidth.The time interval
to perturb PV array voltage is long as environmental
condition changes not very fast in PV farms. So in this
paper, Vdc_ref
is considered to be constant. Phase Lock
Loop (PLL) track grid voltage phases to do transformation
between dq axis and abc axis. PLL bandwidth is set to be
6 Hz with PI block parameter to be kp_pll
=0.1, ki_pll
=1
Fig. 5. System power loss Comparison of different Q modes
In sum, mode 5 volt-var mode is the best option
considering voltage regulation and system power loss.
Mode 1 unity power factor and mode 2 constant Q are
not able to regulate the voltage within range. Mode 3
costs more system power loss than mode 4 and mode 5.
While mode 5 is only inductive when needed and is able
to deal with both overvoltage and under voltage.
3. Dynamic Model of PV
The circuit configuration of a utility PV generator is
shown in Fig.6. The switching model is built in Simulink
with switching frequency set to be 3 kHz. The rated
capacity is 250 kW. The topology contains PV arrays,
a DC capacitor, a single stage DC/AC inverter, a three
phase LCL filter and a step up transformer. The PV
arrays have 29 PV panels in series in each string and
40 strings in parallel. The rated DC voltage is 870 V,
which is also the MPPT point of PV arrays under
standard weather condition (1000 W/m2 and 25°C).
The DC capacitor is chosen to be 8.2 mF to keep DV
voltage ripple under ±5%. Parameters of LCL filter with
resistor in series with cap are L1
= 0.32 mH, L2
=0.32 mH,
C=70.3 µF, Rc
are set to make sure that PV inverter output voltage and
current harmonics are within standard limit. For three
phase step up transformer, the rms values of line to line
voltages of primary and secondary side are 330 V and
12 kV separately. Dual loop control strategy is applied
in which inner current loops regulate output current in
DQ axis separately and outer DC voltage loop regulates
DC voltage. Reactive power can be regulated based on
reactive current loop. The controller may have an outer
reactive power loop according to different reactive
power control strategies.
฀ ฀ ฀ ฀ ฀ ฀ ฀
122
arrows. In conclusion, Fig.8 includes dynamics of power
stage, PLL and controllers. The loop in Fig.8 is solved to
get PV impedance so that
The four DQ frame impedances in Fig.9 are single PV
inverter impedances under mode (1)-mode (4). In mode
(2-4), PV inverter is inductive in steady state. PV farm
is composed of 12 inverter modules. For each module,
P = 250 kW, Q = –75 kVar (Generator convention,
Output as positive direction). In mode 4, P1
= 175 kW,
ratio of slope is –1 in Fig.2 (a). In all four curves, PV
impedances in DQ frame are diagonal dominant, which
means Zdd
and Zqq
are much bigger than Zdq
and Zqd
in
magnitude. And all four curves are almost the same at
high frequencies over 200 Hz. At lower frequency, blue
curve of unity power factor is different from other curves,
Zdq
and Zqd
are zero in magnitude as Q is zero, while the
other three curves are almost the same. So mode (2-4)
can be represented by mode 2 in dynamics. It can be
observed from Fig.9 that the PV terminal impedances are
diagonal dominant under mode 1 to mode 4, or in other
words the decoupling terms of non-diagonal elements of
Zdq
and Zqq
is much smaller than diagonal elements of Zdd
and Zqq
, so the original system stability can be decoupled
into D axis stability and Q axis stability separately. As
the frequency goes from 10 kHz to 1hz, the bode plots
of Zdd
and Zqq
both reveals the dynamics of LCL filter
above 1kHz and have a rising trend below current
Fig.8 Small signal model of PV inverter controller
Linearization of average model with the controllers
around the steady state yields the small signal model
shown in Fig.8, in which is grid voltage
perturbation in grid DQ axis, T
qd
s
ddd ]
~
,
~
[=
~
is duty ratio
change, is DC voltage change, T
qd
s
iii ]
~
,
~
[=
~
is PV output
current response in grid DQ axis. Power stage dynamics
are shown by red arrows and blocks in Fig.8. c
v~ and
c
i
~
are grid voltage perturbation and PV output current
response in converter controller DQ axis separately. Grid
DQ axis and controller DQ axis don’t align with each
other because of PLL effect, which is reflected by blue
arrows and the corresponding blocks. And inner current,
outer DC voltage, outer reactive power controller and
digital control delay are reflected by black boxes and
Fig.9 PV impedances under mode 1 - mode 4
฀ ฀ ฀ ฀ ฀ ฀ ฀
123
becomes non-diagonal dominant, the interconnection
stability can not be observed directly from the bode
plots of the impedance matrices but need the application
of GNC and obtain of the two eigenvalues of the return
ratio matrix which is the combination of the impedances
of the grid and the PV farm.
4. GNC Application
The Nyquist Criterion can be used to assess DC system
stability by the number of encirclement of Nyquist
diagram of source impedance over load impedance
around (-1,0). GNC is an extended version of Nyquist
Criterion for multivariable systems [18]. Once the grid
impedance Zgrid
and PV impedance ZPV
are obtained, the
return ratio matrix can be calculated as
(1)
The generalized Nyquist stability criterion can be
formulated as [24] : “Let the multivariable system have
no open-loop unobservable or uncontrollable modes
whose corresponding characteristic frequencies lie in
the right-half plane. Then the system will be closed-
loop stable if and only if the net sum of anticlockwise
encirclements of the critical point (–1+j0) by the set of
bandwidth of 220Hz matching the dynamics of ideal
current source and are damped down below DC voltage
bandwidth around 20Hz. And the negative phase in Zqq
of frequency below 6Hz is caused by synchronization
function of PLL [18]. So the biggest stability concern for
mode 1 to mode 4 are high resistive on the lines from PV
farm to the grid, which is not observed in this paper as
the lines impedances are not high enough to trigger this
kind instability.
Fig.10 is the impedance of PV inverter under mode 1,
mode 2 (as it can represent mode 2, mode 3, and mode 4)
and mode 5. In mode 5, the steady state operation point
is the same as other modes, P = 250 kW, Q = –75 kVar
(Generator convention, Output as positive direction).
V1
= 0.0975 p.u., V2
= 1.0 p.u., V3
= 1.025 p.u., V4
=1.05
p.u., Qmax
= 112.5 kVar in Fig.2(b). Compared to mode 1
andmode2,oneobviousdifferenceofmode5isthatsigns
of Zdd
and Zqq
in zero frequency are inverted in mode 5.
The magnitude of Zdd
is decreased, while the magnitude
of Zqd
is increased obviously. This will cause unstable
PV integration case, which can be proved in section IV.
The volt-var control mode builds a huge link between d
axis and q axis by generating iq from vd, that’s why the
decoupling term Zqd becomes much higher compared
to other modes. As the PV terminal impedance matrix
Fig.10 PV impedances under mode 1, mode2 and mode 5
฀ ฀ ฀ ฀ ฀ ฀ ฀
124
stability problem under the control mode of volt-war
without reducing the number of PV inverters in parallel.
The solutions include reducing current loop bandwidth
(reducing current controller PI parameters), reducing
reactive power loop bandwidth (reducing current
controller PI parameters) and reducing controller delay
by increasing switching frequency from 3kHz to 6kHz.
Fig. 12 shows the Nyquist diagrams of eigenvalues if
one of the solutions is applied. Compared to the blue
curves of original volt-var droop control, 1
(s) doesn’t
encircles (-1,0) in red, yellow and purple curves, which
shows that the system is stable after the modifications.
Fig.12 GNC application after alternative solutions
5. Time Domain Waveform and
Eigenvalues to Validate GNC
Results
The results from GNC can be validated by time domain
simulation results in Fig.13, which is output current of 3
MW PV farm (12 modules) under volt-var mode in DQ
frame. The oscillation frequency is 256 Hz. Oscillation
magnitude is limited by Q magnitude – Qmax
in droop
mode curve in Fig.2(b) before 0.5 s, which is removed
at 0.5s and the oscillation of current starts to increase,
proving system instability.
The most widely used tool of eigenvalues for small-
signal stability assessment is also applied on the system
with PV generator under volt-var mode. Fig.14 is the
plot of five eigenvalues which are closest to the right
half plan or in the right half plane on the complex plane.
The system has two eigenvalues in the right half plane,
which is a confirmation of the instability discovery from
GNC application from last section.
characteristic loci of L(s) is equal to the total number
of right-half plane poles of Zgrid
and YPV
”.The two
eigenvalues of L are 1
(s) and 2
(s). In all the cases of
this paper, Zgrid
and YPV
don’t have RHP pole, so if the
Nyquist diagrams of 1
(s) and 2
(s) don’t encircle (-1,0),
then the connection of PV inverters to the system is
stable. On the other hand, system is not stable if any of
the eigenvalue loci encircles (-1,0).
PV terminal impedances or admittances are derived in
last section. The grid is the 12 kV distribution grid in
Fig.1, in which PV is connected to bus 45. The PV farm
capacity is 3 MW, which means that 12 PV inverters
are operated in parallel. As this system is very lightly
loaded, grid impedance is determined by the cumulative
resistance R =3.35 W and inductance L=11.7mH of the
direct path from substation bus 1 to bus 45.
(2)
The results of GNC application are shown in Fig.11,
whichincludesNyquistdiagramsofeigenvaluesofreturn
ratio matrix L when PV is at different Q control modes
of mode 1, mode 2 and mode 5. In mode 2 and mode
5, PV generator operation point is P = 3 MW, Q = - 0.9
Mvar. Dynamics of mode 3-4 are represented by mode
2. It can be observed that if the multiple inverters are all
operating at mode 1 or mode 2, either of the eigenvalues
encircles (-1,0), meaning that the connection is stable.
But if PV is under mode 5, 1
(s) encircles (-1,0), and the
connection of PV to the grid becomes unstable.
Fig.11 Chatacteristid loci of PV connection to the grid
Some alternative solutions of modification on the
PV inverter controllers have been found to solve the
฀ ฀ ฀ ฀ ฀ ฀ ฀
125
modes, based on which GNC is used to assess the grid-
PV connection stability. The volt-var control mode
changes PV terminal impedance signs and magnitudes
significantly and may cause unstable connection to the
grid. The stability assessment is proved by time domain
simulationandalsoeigenvaluesacquisitionfromthestate
space model of the whole system with PV generators.
6. References
[1] W. Jewell, R. Rama kumar and S. Hill, “A Study of Dispersed PV
Generation on the PSO System,” IEEE Transactions on Energy
Conversion, vol. 3, no. 3, p. 473-478, Sep. 1988.
[2] A. Povlsen (2002, Feb.), Impacts of Power Penetration from
Photovoltaic Power Systems in Distribution Networks,
International Energy Agency report lEA PVPS T5-10:2002.
Fredericia, Denmark. [Online].Available: http://www.hme.ca/
gridconnect/IEA_PVPS_Task _5-10_Impacts_of_PV_Power_
Penetration.pdf.
[3] General Electric Corporate R&D (2003, Aug.), DG Power Quality,
Protection and Reliability Case Studies Report, NREL report
NRELlSR-560-34635. Niskayuna, New York, USA. [Online].
Available: http://www.nrel.gov/docs/fy03osti/34635.pdf
[4] H. Kobayashi and M. Takasaki, «Demonstration Study of
Autonomous Demand Area Power System,» in Proc. IEEE
Power Eng. Soc. Transm. Distrib. Conf. Expo., Aug. 2006, pp.
548–555.
[5] M. Thomson and D. G. Infield, “Network power-flow analysis
for a high penetration of distributed generation,” IEEE Trans.
Power Syst., vol. 22, no. 3, pp. 1157–1162, Aug. 2007.
[6] R. Tonkoski, D. Turcotte, and T. H. M. EL-Fouly, “Impact of high
PV penetration on voltage profiles in residential neighborhoods,”
IEEE Trans.Sustain. Energy, vol. 3, no. 3, pp. 518–527, Jul. 2012.
[7] A. Hoke, R. Butler, J. Hambrick, and B. Kroposki, “Steady-state
analysis of maximum photovoltaic penetra-tion levels on typical
distribution feeders,” IEEE Trans. Sustain. Energy, vol. 4, no. 2,
pp. 350–357, Apr. 2013.
[8] IEEE Standard for Interconnection and Interoperability of
Distributed Energy Resources with Associated Electric Power
Systems Interfaces, IEEE Std 1547-2018 (Revision of IEEE Std
1547-2003), 2018.
[9] E. Demirok et al., “Local reactive power control methods for
overvoltage prevention of distributed solar inverters in low-
voltage grids,” IEEE J. Photovolt., vol. 1, no. 2, pp. 174–182, Oct.
2011.
[10] I. Kim, R. Harley, R. Regassa and Y. Del Valle, «The effect of
the volt/var control of photovoltaic systems on the time-series
steady-state analysis of a distribution network,» in Proc. IEEE
Power Systems Conference, Clemson, SC, USA, 2015.
[11] V. H. M. Quezada, J. R. Abbad, and T. G. S. Roman, “Assessment
of energy distribution losses for increasing penetration of
distributed generation,” IEEE Trans. Power Syst., vol. 21, no. 2,
pp. 533–540, May 2006.
[12] W. Du, H. Wang, and L. Xiao, “Power system small-signal
stability as affected by grid-connected photovoltaic generation,”
Eur. Trans. Elect. Power, vol. 22, pp. 688–703, Jul. 2012.
Fig.13 Time domain simulation of PV under volt-var mode
Fig.14 System eigenvalues in complex plane
5. Conclusion
A known broad statement is that active power injected
by PV inverters increases the system voltage. In what
regards the reactive power compensation capability of
PV inverters, this paper showed that the reactive power
control mode Volt-var droop mode of Q = f (V) is
preferred over other reactive power control modes after
the static analysis of voltage regulation effect and the
impact on grid power loss.
The terminal impedances in DQ frame are derived of
utility-scale PV farm based on small signal model of PV
inverters. A comparison is done among impedances of
PV inverters under 5 different reactive power control
฀ ฀ ฀ ฀ ฀ ฀ ฀
126
system,” IEEE Trans.Power Electron., vol. 29, no. 12, pp. 6421–
6432, Dec. 2014.
[20] A. Rygg, M. Molinas, C. Zhang and X. Cai, “A Modified
sequence domain impedance definition and its equivalence to
the dq-domain impedance definition for the stability analysis of
AC power electronic systems,” IEEE J. Emerg. Sel. Topics Power
Electron., vol. 4, no. 4, pp. 1383–1396, Dec. 2016
[21] M. Farivar, R. Neal, C. Clarke, and S. Low, “Optimal inverter
VAR control in distribution systems with high PV penetration”,
in Proc. IEEE Power and Energy Society General Meeting, San
Diego, CA, 2012.
[22] American National Standard For Electric Power Systems and
Equipment—Voltage Ratings (60 Hertz), ANSI C84.1-2011,
2011.
[23] Y. Tang, R. Burgos, C. Li and D. Boroyevich, «Impact of PV
inverter penetration on voltage profile and power loss in medium
voltage distribution systems,» 2016 IEEE 17th Workshop on
Control and Modeling for Power Electronics (COMPEL),
Trondheim, 2016, pp. 1-8.
[24] A. G. J. MacFarlane and I. Postlethwaite, “The generalized
Nyquist stability criterion and multivariable root loci,” Int. J. of
Control, vol. 25, no. 1, pp. 81–127, 1977.
7. Acknowledgement
The authors wish to gratefully acknowledge the support
from Dominion Energy, USA.
[13] M. Duckheim, J. Reinschke, P. Gudivada and W. Dunford.
“Voltage and power flow oscillations induced by PV inverters
connected to a weak power distribution grid”, in Proc. 2013
IEEE Power and Energy Society General Meeting (PES), 21-25
July 2013.
[14] S. Liu, P. X. Liu and X. Wang. “Stability Analysis of Grid-
Interfacing Inverter Control in Distribution Systems With
Multiple Photovoltaic-Based Distributed Generators”, in IEEE
Transactions on Industrial Electronics, vol. 63, no. 12, pp 7339
– 7348 , 2016.
[15] N. Pogaku, M. Prodanovic, T. C. Green, W. L. Kling, and L.
Van Der Sluis, “Modeling, analysis and testing of autonomous
operation of an inverter-based microgrid,” IEEE Trans. Power
Electron., vol. 22, no. 2, pp. 613–625, Mar. 2007.
[16] B. Tamimi, C. Canizares, and K. Bhattacharya, “System
stability impact of large-scale and distributed solar photovoltaic
generation: The case of Ontario Canada,” IEEE Trans. Sustain.
Energy, vol. 4, no. 3, pp. 680–688, Jul. 2013.
[17] Z. Moradi-Shahrbabak and A. Tabesh, “Effects of Front-End
Converter and DC-Link of a Utility-Scale PV Energy System on
Dynamic Stability of a Power System”, IEEE Trans. on Industrial
Electronics, vol. 65, no. 1, pp. 403-411 Jan. 2018
[18] B. Wen, D. Boroyevich, R. Burgos, P. Mattavelli, and Z. Shen,
“Analysis of d-q small-signal impedance of grid-tied inverters,”
in IEEE Trans. Power Electron., vol. 31, no. 1, pp. 675–687, Jan.
2016..
[19] X. Wang, F. Blaabjerg, and W. Wu, “Modeling and analysis of
harmonic stability in an AC power-electronics-based power

More Related Content

What's hot

Mitigation of Voltage Imbalance in A Two Feeder Distribution System Using Iupqc
Mitigation of Voltage Imbalance in A Two Feeder Distribution System Using IupqcMitigation of Voltage Imbalance in A Two Feeder Distribution System Using Iupqc
Mitigation of Voltage Imbalance in A Two Feeder Distribution System Using IupqcIJMERJOURNAL
 
Enhancement of Reactive Power Compensation in PV Grid System To Increase The ...
Enhancement of Reactive Power Compensation in PV Grid System To Increase The ...Enhancement of Reactive Power Compensation in PV Grid System To Increase The ...
Enhancement of Reactive Power Compensation in PV Grid System To Increase The ...IJSRD
 
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...IJSRD
 
A New Control Method for Grid-Connected PV System Based on Quasi-Z-Source Cas...
A New Control Method for Grid-Connected PV System Based on Quasi-Z-Source Cas...A New Control Method for Grid-Connected PV System Based on Quasi-Z-Source Cas...
A New Control Method for Grid-Connected PV System Based on Quasi-Z-Source Cas...IAES-IJPEDS
 
Optimal Placement of FACTS Controller
Optimal Placement of FACTS ControllerOptimal Placement of FACTS Controller
Optimal Placement of FACTS ControllerDivyang soni
 
MITIGATION OF UNBALANCED FAULTS IN DISTRIBUTION SYSTEM USING FD-STATCOM WITH ...
MITIGATION OF UNBALANCED FAULTS IN DISTRIBUTION SYSTEM USING FD-STATCOM WITH ...MITIGATION OF UNBALANCED FAULTS IN DISTRIBUTION SYSTEM USING FD-STATCOM WITH ...
MITIGATION OF UNBALANCED FAULTS IN DISTRIBUTION SYSTEM USING FD-STATCOM WITH ...Suganthi Thangaraj
 
Mitigation of Fault in the Distribution System by using Flexible Distributed ...
Mitigation of Fault in the Distribution System by using Flexible Distributed ...Mitigation of Fault in the Distribution System by using Flexible Distributed ...
Mitigation of Fault in the Distribution System by using Flexible Distributed ...IJMER
 
K021201077084
K021201077084K021201077084
K021201077084theijes
 
A Review of Matrix Converter and Novel Control Method of DC-AC Matrix Converter
A Review of Matrix Converter and Novel Control Method of DC-AC Matrix ConverterA Review of Matrix Converter and Novel Control Method of DC-AC Matrix Converter
A Review of Matrix Converter and Novel Control Method of DC-AC Matrix Converteridescitation
 
Hybrid T-I-D and Fuzzy Logic Based SVC Controller for Transient Stability Enh...
Hybrid T-I-D and Fuzzy Logic Based SVC Controller for Transient Stability Enh...Hybrid T-I-D and Fuzzy Logic Based SVC Controller for Transient Stability Enh...
Hybrid T-I-D and Fuzzy Logic Based SVC Controller for Transient Stability Enh...IJERA Editor
 
IRJET- Simulation of Unified Series Shunt Compensator for Power Quality Compe...
IRJET- Simulation of Unified Series Shunt Compensator for Power Quality Compe...IRJET- Simulation of Unified Series Shunt Compensator for Power Quality Compe...
IRJET- Simulation of Unified Series Shunt Compensator for Power Quality Compe...IRJET Journal
 
Ee423 fault analysis_notes
Ee423  fault analysis_notesEe423  fault analysis_notes
Ee423 fault analysis_notesAcot Benard
 
Mitigation of Voltage Fluctuations in Power System Using STATCOM
Mitigation of Voltage Fluctuations in Power System Using STATCOMMitigation of Voltage Fluctuations in Power System Using STATCOM
Mitigation of Voltage Fluctuations in Power System Using STATCOMIJERA Editor
 
Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...
Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...
Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...IJMTST Journal
 
IRJET - Power Quality Improvement in Distribution Power System using STATCOM
IRJET - Power Quality Improvement in Distribution Power System using STATCOMIRJET - Power Quality Improvement in Distribution Power System using STATCOM
IRJET - Power Quality Improvement in Distribution Power System using STATCOMIRJET Journal
 

What's hot (20)

Mitigation of Voltage Imbalance in A Two Feeder Distribution System Using Iupqc
Mitigation of Voltage Imbalance in A Two Feeder Distribution System Using IupqcMitigation of Voltage Imbalance in A Two Feeder Distribution System Using Iupqc
Mitigation of Voltage Imbalance in A Two Feeder Distribution System Using Iupqc
 
Power Quality Enhancement in Power System Network using DSTACOM
Power Quality Enhancement in Power System Network using DSTACOMPower Quality Enhancement in Power System Network using DSTACOM
Power Quality Enhancement in Power System Network using DSTACOM
 
Enhancement of Reactive Power Compensation in PV Grid System To Increase The ...
Enhancement of Reactive Power Compensation in PV Grid System To Increase The ...Enhancement of Reactive Power Compensation in PV Grid System To Increase The ...
Enhancement of Reactive Power Compensation in PV Grid System To Increase The ...
 
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
Comparison of Shunt Facts Devices for the Improvement of Transient Stability ...
 
A New Control Method for Grid-Connected PV System Based on Quasi-Z-Source Cas...
A New Control Method for Grid-Connected PV System Based on Quasi-Z-Source Cas...A New Control Method for Grid-Connected PV System Based on Quasi-Z-Source Cas...
A New Control Method for Grid-Connected PV System Based on Quasi-Z-Source Cas...
 
D010312127
D010312127D010312127
D010312127
 
Optimal Placement of FACTS Controller
Optimal Placement of FACTS ControllerOptimal Placement of FACTS Controller
Optimal Placement of FACTS Controller
 
MITIGATION OF UNBALANCED FAULTS IN DISTRIBUTION SYSTEM USING FD-STATCOM WITH ...
MITIGATION OF UNBALANCED FAULTS IN DISTRIBUTION SYSTEM USING FD-STATCOM WITH ...MITIGATION OF UNBALANCED FAULTS IN DISTRIBUTION SYSTEM USING FD-STATCOM WITH ...
MITIGATION OF UNBALANCED FAULTS IN DISTRIBUTION SYSTEM USING FD-STATCOM WITH ...
 
Mitigation of Fault in the Distribution System by using Flexible Distributed ...
Mitigation of Fault in the Distribution System by using Flexible Distributed ...Mitigation of Fault in the Distribution System by using Flexible Distributed ...
Mitigation of Fault in the Distribution System by using Flexible Distributed ...
 
K021201077084
K021201077084K021201077084
K021201077084
 
A Review of Matrix Converter and Novel Control Method of DC-AC Matrix Converter
A Review of Matrix Converter and Novel Control Method of DC-AC Matrix ConverterA Review of Matrix Converter and Novel Control Method of DC-AC Matrix Converter
A Review of Matrix Converter and Novel Control Method of DC-AC Matrix Converter
 
Hybrid T-I-D and Fuzzy Logic Based SVC Controller for Transient Stability Enh...
Hybrid T-I-D and Fuzzy Logic Based SVC Controller for Transient Stability Enh...Hybrid T-I-D and Fuzzy Logic Based SVC Controller for Transient Stability Enh...
Hybrid T-I-D and Fuzzy Logic Based SVC Controller for Transient Stability Enh...
 
IRJET- Simulation of Unified Series Shunt Compensator for Power Quality Compe...
IRJET- Simulation of Unified Series Shunt Compensator for Power Quality Compe...IRJET- Simulation of Unified Series Shunt Compensator for Power Quality Compe...
IRJET- Simulation of Unified Series Shunt Compensator for Power Quality Compe...
 
Ee423 fault analysis_notes
Ee423  fault analysis_notesEe423  fault analysis_notes
Ee423 fault analysis_notes
 
Enhanced decoupled current control with voltage compensation for modular mult...
Enhanced decoupled current control with voltage compensation for modular mult...Enhanced decoupled current control with voltage compensation for modular mult...
Enhanced decoupled current control with voltage compensation for modular mult...
 
26 k. subramanian
26 k. subramanian26 k. subramanian
26 k. subramanian
 
Mitigation of Voltage Fluctuations in Power System Using STATCOM
Mitigation of Voltage Fluctuations in Power System Using STATCOMMitigation of Voltage Fluctuations in Power System Using STATCOM
Mitigation of Voltage Fluctuations in Power System Using STATCOM
 
Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...
Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...
Voltage Regulation with Hybrid RES based Distributed Generation in the for Ac...
 
INCIDENCE MATRIX
INCIDENCE MATRIXINCIDENCE MATRIX
INCIDENCE MATRIX
 
IRJET - Power Quality Improvement in Distribution Power System using STATCOM
IRJET - Power Quality Improvement in Distribution Power System using STATCOMIRJET - Power Quality Improvement in Distribution Power System using STATCOM
IRJET - Power Quality Improvement in Distribution Power System using STATCOM
 

Similar to Small signal stability impact of utility PV with reactive power control on the medium voltage distributed systems

Integration of Unified Power Quality Controller with DG
Integration of Unified Power Quality Controller with DGIntegration of Unified Power Quality Controller with DG
Integration of Unified Power Quality Controller with DGIJRST Journal
 
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...IAES-IJPEDS
 
IRJET- Power Quality Improvement in Solar by using Fuzzy Logic Controller
IRJET-  	  Power Quality Improvement in Solar by using Fuzzy Logic ControllerIRJET-  	  Power Quality Improvement in Solar by using Fuzzy Logic Controller
IRJET- Power Quality Improvement in Solar by using Fuzzy Logic ControllerIRJET Journal
 
Improving Stability of Utility-Tied Wind Generators using Dynamic Voltage Res...
Improving Stability of Utility-Tied Wind Generators using Dynamic Voltage Res...Improving Stability of Utility-Tied Wind Generators using Dynamic Voltage Res...
Improving Stability of Utility-Tied Wind Generators using Dynamic Voltage Res...IJMTST Journal
 
Seamless Transitions between Grid-Connected and Stand-Alone Operations of Dis...
Seamless Transitions between Grid-Connected and Stand-Alone Operations of Dis...Seamless Transitions between Grid-Connected and Stand-Alone Operations of Dis...
Seamless Transitions between Grid-Connected and Stand-Alone Operations of Dis...IJERD Editor
 
P-Q Theory Based UPQC for Reactive Power Compensation with UCAP
P-Q Theory Based UPQC for Reactive Power Compensation with UCAPP-Q Theory Based UPQC for Reactive Power Compensation with UCAP
P-Q Theory Based UPQC for Reactive Power Compensation with UCAPIRJET Journal
 
Power quality optimization using a novel backstepping control of a three-phas...
Power quality optimization using a novel backstepping control of a three-phas...Power quality optimization using a novel backstepping control of a three-phas...
Power quality optimization using a novel backstepping control of a three-phas...IJECEIAES
 
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faultsComparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faultselelijjournal
 
Battery Based Quasi Z-Source Inverter for PV power Generation Connected to Grid
Battery Based Quasi Z-Source Inverter for PV power Generation Connected to GridBattery Based Quasi Z-Source Inverter for PV power Generation Connected to Grid
Battery Based Quasi Z-Source Inverter for PV power Generation Connected to GridIJERA Editor
 
IRJET- Voltage Drop Compensation in Distribution System using Cascaded H-Brid...
IRJET- Voltage Drop Compensation in Distribution System using Cascaded H-Brid...IRJET- Voltage Drop Compensation in Distribution System using Cascaded H-Brid...
IRJET- Voltage Drop Compensation in Distribution System using Cascaded H-Brid...IRJET Journal
 
Grid fault Control Scheme for Peak Current Reduction in Photovoltaic Inverte...
Grid fault Control Scheme for Peak Current Reduction in  Photovoltaic Inverte...Grid fault Control Scheme for Peak Current Reduction in  Photovoltaic Inverte...
Grid fault Control Scheme for Peak Current Reduction in Photovoltaic Inverte...IJMER
 
Enhanced dynamic performance of grid feeding distributed generation under va...
Enhanced dynamic performance of grid feeding distributed  generation under va...Enhanced dynamic performance of grid feeding distributed  generation under va...
Enhanced dynamic performance of grid feeding distributed generation under va...IJECEIAES
 
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...IJMTST Journal
 
1.compensation of reactive power using d statcom in grid interfaced pv system
1.compensation of reactive power using d statcom in grid interfaced pv system1.compensation of reactive power using d statcom in grid interfaced pv system
1.compensation of reactive power using d statcom in grid interfaced pv systemEditorJST
 
IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...
IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...
IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...Wireilla
 
Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...
Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...
Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...ijfls
 
IRJET- Analysis of LVRT Capability of Grid Connected Solar Photovoltaic System
IRJET- Analysis of LVRT Capability of Grid Connected Solar Photovoltaic SystemIRJET- Analysis of LVRT Capability of Grid Connected Solar Photovoltaic System
IRJET- Analysis of LVRT Capability of Grid Connected Solar Photovoltaic SystemIRJET Journal
 

Similar to Small signal stability impact of utility PV with reactive power control on the medium voltage distributed systems (20)

Integration of Unified Power Quality Controller with DG
Integration of Unified Power Quality Controller with DGIntegration of Unified Power Quality Controller with DG
Integration of Unified Power Quality Controller with DG
 
High_reactive_power_DOC.docx
High_reactive_power_DOC.docxHigh_reactive_power_DOC.docx
High_reactive_power_DOC.docx
 
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
Improvement of Power Quality using Fuzzy Logic Controller in Grid Connected P...
 
A performance comparison of transformer-less grid tied PV system using diode ...
A performance comparison of transformer-less grid tied PV system using diode ...A performance comparison of transformer-less grid tied PV system using diode ...
A performance comparison of transformer-less grid tied PV system using diode ...
 
IRJET- Power Quality Improvement in Solar by using Fuzzy Logic Controller
IRJET-  	  Power Quality Improvement in Solar by using Fuzzy Logic ControllerIRJET-  	  Power Quality Improvement in Solar by using Fuzzy Logic Controller
IRJET- Power Quality Improvement in Solar by using Fuzzy Logic Controller
 
Improving Stability of Utility-Tied Wind Generators using Dynamic Voltage Res...
Improving Stability of Utility-Tied Wind Generators using Dynamic Voltage Res...Improving Stability of Utility-Tied Wind Generators using Dynamic Voltage Res...
Improving Stability of Utility-Tied Wind Generators using Dynamic Voltage Res...
 
Seamless Transitions between Grid-Connected and Stand-Alone Operations of Dis...
Seamless Transitions between Grid-Connected and Stand-Alone Operations of Dis...Seamless Transitions between Grid-Connected and Stand-Alone Operations of Dis...
Seamless Transitions between Grid-Connected and Stand-Alone Operations of Dis...
 
Kp2417961805
Kp2417961805Kp2417961805
Kp2417961805
 
P-Q Theory Based UPQC for Reactive Power Compensation with UCAP
P-Q Theory Based UPQC for Reactive Power Compensation with UCAPP-Q Theory Based UPQC for Reactive Power Compensation with UCAP
P-Q Theory Based UPQC for Reactive Power Compensation with UCAP
 
Power quality optimization using a novel backstepping control of a three-phas...
Power quality optimization using a novel backstepping control of a three-phas...Power quality optimization using a novel backstepping control of a three-phas...
Power quality optimization using a novel backstepping control of a three-phas...
 
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faultsComparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
 
Battery Based Quasi Z-Source Inverter for PV power Generation Connected to Grid
Battery Based Quasi Z-Source Inverter for PV power Generation Connected to GridBattery Based Quasi Z-Source Inverter for PV power Generation Connected to Grid
Battery Based Quasi Z-Source Inverter for PV power Generation Connected to Grid
 
IRJET- Voltage Drop Compensation in Distribution System using Cascaded H-Brid...
IRJET- Voltage Drop Compensation in Distribution System using Cascaded H-Brid...IRJET- Voltage Drop Compensation in Distribution System using Cascaded H-Brid...
IRJET- Voltage Drop Compensation in Distribution System using Cascaded H-Brid...
 
Grid fault Control Scheme for Peak Current Reduction in Photovoltaic Inverte...
Grid fault Control Scheme for Peak Current Reduction in  Photovoltaic Inverte...Grid fault Control Scheme for Peak Current Reduction in  Photovoltaic Inverte...
Grid fault Control Scheme for Peak Current Reduction in Photovoltaic Inverte...
 
Enhanced dynamic performance of grid feeding distributed generation under va...
Enhanced dynamic performance of grid feeding distributed  generation under va...Enhanced dynamic performance of grid feeding distributed  generation under va...
Enhanced dynamic performance of grid feeding distributed generation under va...
 
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
 
1.compensation of reactive power using d statcom in grid interfaced pv system
1.compensation of reactive power using d statcom in grid interfaced pv system1.compensation of reactive power using d statcom in grid interfaced pv system
1.compensation of reactive power using d statcom in grid interfaced pv system
 
IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...
IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...
IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...
 
Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...
Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...
Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...
 
IRJET- Analysis of LVRT Capability of Grid Connected Solar Photovoltaic System
IRJET- Analysis of LVRT Capability of Grid Connected Solar Photovoltaic SystemIRJET- Analysis of LVRT Capability of Grid Connected Solar Photovoltaic System
IRJET- Analysis of LVRT Capability of Grid Connected Solar Photovoltaic System
 

More from Power System Operation

Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panelsPower System Operation
 
Big Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsBig Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsPower System Operation
 
SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action SchemePower System Operation
 
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...Power System Operation
 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePower System Operation
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)Power System Operation
 
Electrical Transmission Tower Types - Design & Parts
Electrical Transmission Tower  Types - Design & PartsElectrical Transmission Tower  Types - Design & Parts
Electrical Transmission Tower Types - Design & PartsPower System Operation
 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools Power System Operation
 
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
Power Quality  Trends in the Transition to  Carbon-Free Electrical Energy SystemPower Quality  Trends in the Transition to  Carbon-Free Electrical Energy System
Power Quality Trends in the Transition to Carbon-Free Electrical Energy SystemPower System Operation
 

More from Power System Operation (20)

ENERGY TRANSITION OUTLOOK 2021
ENERGY TRANSITION OUTLOOK  2021ENERGY TRANSITION OUTLOOK  2021
ENERGY TRANSITION OUTLOOK 2021
 
Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panels
 
What does peak shaving mean
What does peak shaving meanWhat does peak shaving mean
What does peak shaving mean
 
What's short circuit level
What's short circuit levelWhat's short circuit level
What's short circuit level
 
Power System Restoration Guide
Power System Restoration Guide  Power System Restoration Guide
Power System Restoration Guide
 
Big Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsBig Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid Operations
 
SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action Scheme
 
Substation Neutral Earthing
Substation Neutral EarthingSubstation Neutral Earthing
Substation Neutral Earthing
 
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground Resistance
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
 
Electrical Transmission Tower Types - Design & Parts
Electrical Transmission Tower  Types - Design & PartsElectrical Transmission Tower  Types - Design & Parts
Electrical Transmission Tower Types - Design & Parts
 
What is load management
What is load managementWhat is load management
What is load management
 
What does merit order mean
What does merit order meanWhat does merit order mean
What does merit order mean
 
What are Balancing Services ?
What are  Balancing Services ?What are  Balancing Services ?
What are Balancing Services ?
 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
 
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
Power Quality  Trends in the Transition to  Carbon-Free Electrical Energy SystemPower Quality  Trends in the Transition to  Carbon-Free Electrical Energy System
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
 
Power Purchase Agreement PPA
Power Purchase Agreement PPA Power Purchase Agreement PPA
Power Purchase Agreement PPA
 
Harmonic study and analysis
Harmonic study and analysisHarmonic study and analysis
Harmonic study and analysis
 
What is leakage current testing
What is leakage current testingWhat is leakage current testing
What is leakage current testing
 

Recently uploaded

result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 

Recently uploaded (20)

Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 

Small signal stability impact of utility PV with reactive power control on the medium voltage distributed systems

  • 1. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 118 Abstract With an increasing number of photovoltaic (PV) inverters in the distribution system, their impact is no longer negligible, especially in the aspect of dynamic interaction. Accordingly, a comparison is done among PV inverters of different reactive power control modes, to determine their impact on the system voltage profile, power loss and small-signal stability. Generalized Nyquist Criteria (GNC) based on impedances in DQ frames is used for stability assessment, which is validated by time domain simulation results and also system eigenvalues calculation results from MATLAB. From these, guidelines are formulated to manage PV inverter reactive power control strategies. Reactive power control mode of volt-var Q=f(V) is preferred to other reactive power modes to avoid voltage profile problem and reduce power loss, but will induce small-signal instability and cause PV terminal voltage oscillations. There’s tradeoff between static influence and dynamic impact in choosing the local reactive power control strategies. 1. Introduction DUE to environment problems caused by fossil fuels, installation of photovoltaic (PV) systems is increasing rapidly worldwide. The impact on voltage profile is the most commonly recognized problem caused by high PV inverter penetration in distribution systems. The impact on voltage profile is bigger as the PV capacity increases, which has a limit in the amount of PV power to be installed with respect to the overvoltage problem [1-7]. However, this scenario has been improved as according to the revised IEEE 1547 standard, distribution resources can actively participate in the voltage regulation [8]. Different local reactive power control strategies have been designed and compared for PV generators to regulate system voltage [9,10]. The comparison of different Q control modes should not only consider the regulation of voltage profile, but also take in effect of the system power loss. Contrary to PV impact on voltage profile, system power loss forms a U shape trajectory as PV generator capacity increases [11]. The static analysis in this paper demonstrates that system power loss is also a U shape trajectory as reactive power injected by PV varies. IEEE 1547 newest version requires PV inverters to have reactive power control, thus increasing inverter control complexity. As negative incremental resistance caused by constant power behavior of power converters may bring stability problem, and stability of PV integration to distributed system attracts more and more attention [12-17]. Different from real-time simulation or character root method, which require full models of all components in distributed system, the Generalized Nyquist stability Criterion (GNC) for stability analysis of three-phase AC power system only uses measured D-Q Frame impedances [18]. Compared to the positive sequence impedance method used in [19], D-Q frame impedance matrix method is more accurate for stability assessment of system with PV inverter that has non- symmetrical control in DQ frame including DC voltage loop and phase locked loop (PLL) [20]. As there is neither frequency control nor generator inertia dynamics in the distribution system studied, the stability discussed in this paper is mainly voltage stability. And only small- signal stability can be investigated by GNC method which is based on a certain steady state operation point instead of stability during the transients including short- term voltage stability or long-term voltage stability. The goal of this paper is to analyze the small-signal stability impact of utility scale PV farm composed by multiple PV inverters under different reactive power control modes to medium voltage distributed system.The small-signal assessment approach is GNC based on grid Small-signal tability mpact of tility PV with eactive ower ontrol on the edium oltage istributed stems Y TANG*, R BURGOS Center for Power Electronics Systems (CPES), Virginia Tech KEYWORDS Distribution system, photovoltaic (PV), power loss, reactive power control, small-signal stability, voltage profile. *yetang@vt.edu
  • 2. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 119 as 5 MW. The circuit diagram of the distribution system is shown by Fig.1, and impedance and load parameters for the system are given in [21]. Fig. 1. Diagram of case systems. 56 bus system. The commonly used photovoltaic generator local reactive power control modes include mode 1 unity power factor, mode 2 fixed reactive power, mode 3 fixed power factor, mode 4 reactive power as a function of active power (Watt-var mode) and mode 5 reactive power as a function of bus voltage (Volt-var mode) [8]. Mode 4 and mode 5 are illustrated by Fig.2. Fig. 2. (a) Watt-var mode curve (b) Volt-var Q= f(V) mode droop curve All five modes are applied on the PV farm connected to bus 45. Fig.3 is the voltage profile of PV farm terminal bus 45 when the PV active power increases from 0 to full power in correspond to irradiance variation. In mode 2, reactive power reference is set to be 1.5 MVar inductive to compensate the voltage boost caused by active power injection shown by mode 1 curve, but this setting has the problem of under-voltage when irradiance is low, showing that this mode is lack of flexibility for voltage regulation as a local control strategy. In mode 3, power factor is set to be 0.91 lagging. In mode 4, P1 = 3.5MW and the slope is -1 in the curve in Fig.2(a). In mode 5, and PV terminal D-Q frame impedances. Of all reactive power local control modes in IEEE 1547, the volt-var mode is the most preferred mode considering the static impact on the system voltage profile and grid power loss. Then a comparison is done among PV inverter terminal D-Q frame impedances when PV is under different reactive power control modes, which shows that volt- var mode control have a significant impact on PV terminal D-Q frame impedances and cause unstable PV integration case in weak grids. When instability occurs, PV terminal sees oscillation voltage magnitude. The instability phenomena discovered by GNC application is proved by both the time domain simulation of the grid with the PV farm and the eigenvalue acquisition from the state-space model of the PV connection. Finally, several alternate solutions are provided to mitigate instability issues of volt-var control schemes. The paper is organized as follows: Section II introduces the test-bed system of a radial 56 bus system with high PV penetration. Different reactive power control modes are listed and compared in the aspect of impact on system voltage and power loss. Section III describes the dynamic model of utility PV farm including switching model and the average model of PV generator and its controller, based on which PV generator terminal impedance is derived in DQ frame. Section IV shows the GNC application result using the DQ frame impedances of the grid and the PV generators under different Q control modes. Section V validates small-signal stability assessment result of GNC by time domain waveform of PV output currents and the eigenvalues of state space model as well. Section VI is the conclusion about the comparison of different Q control modes and impact of PV penetration on distribution system voltage and small- signal stability, and guidelines about PV allocation and control for utility to avoid voltage profile problem and ensure system stability. 2. Static Comparison of Different Q Control The test-bed distribution system in this paper is one of Southern California Edison (SCE)’s distribution feeders with very high penetration of Photovoltaics. It is a 12 kV and very lightly loaded rural distribution feeder, with a radial topology and a PV integration that can be as high
  • 3. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 120 bus 45 in 56 bus system. System power loss is plotted in Fig.4, Fig.4 reveals that for the typical load condition of 56 bus system, system power loss forms a U shape curve both for active power injection and reactive power injection. The typical loading condition for the testbed is that all the loads are 40% constant power and 60% constant impedance load with a lagging power factor.And as the voltage magnitudes of the buses change very little in percentage, so the active currents and reactive currents can be estimated to be proportional to the active power and reactive power flowing through the lines. In addition, the power loss of the lines are quadratic functions in terms of the active currents and reactive currents, so system power loss forms a U shape curve both for active power injection and reactive power injection. The dip of the U shape is the point that active currents and reactive currents on the lines caused by load are starting to change flowing direction because of PV injection. The fact that certain amount of active power and reactive power should be injected to achieve minimum power loss helps to understand the comparison of impact on system power loss of different reactive power control modes in Fig.5. Power loss under unity power factor is set as base value of 100% in each set of bar curves. Mode 2 and 3 cause higher power loss than other options because PV inverter in mode 2 and 3 is consuming reactive power all the way. In contrast, PV under mode 4 and mode 5 is only inductive when needed (the active power injected exceeds P1 or PV terminal voltage is over the threshold of V3 ). In addition, when irradiance is zero, mode 5 injects reactive power because voltage bus 45 is below V2 =1.00p.u., which reduces system power loss compared to other modes. Fig. 4. System loss in terms of P and Q injected to PV connection bus Fig. 3. Voltage of under PV injection bus V1 =0.975p.u., V2 =1.00p.u., V3 =1.025p.u., V4 =1.05p.u. and Qmax =2.5MVar. Mode 3 to mode 5 are all able to regulate the PV bus voltage within the limit ofASIC standard [22]. The difference of different Q control modes in voltage profile of Fig.3 can be interpreted more by employing the sensitivity analysis results in [23] that active power injection increases bus voltage by a ratio of resistor sum on the line and reactive power consumption reduces bus voltagebyaratioofreactancesumontheline.Unitypower factor curve is a rising straight line, and constant Q is also a straight line with the same ratio but parallelly lowered because of a constant voltage reduction by a constant Q consumption. The watt-var mode align with unity power factor mode before the active power injected reaches the inflection point of P1 in the watt-var curve and after that point the reactive power consumption starts to compensate the voltage rising caused by active power, so that the bus voltage can be controlled within upper limit. As for the fixed PF mode, with a lagging PF, the increasing ratio of voltage over active power is lower compared to unity power factor as a combination of rising ratio of active power and falling ratio of reactive power consumption. And different from all these Q modes, volt-var mode regulates the AC terminal voltages directly so that the PV produces reactive power if AC voltage magnitude is lower than V2 =1.00p.u. and consumes reactive power if AC voltage magnitude is higher than V3 =1.025p.u. and the voltage profile can be controlled within lower limit and upper limit. To analyze the impact on system power loss, different amount of active power and reactive power is injected to
  • 4. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 121 Fig.6 Topology of utility PV With switching ripple ignored, average model of the PV generator in DQ axis is formed in Fig.7. The average model of DC side is on the left side and average model of AC side is on the right side, which is based on primary side voltage of step up transformer. Fig.7 Average model of PV generator For PV controller in Fig.6, AC current regulator is a PI controller with parameter of kpi = 0.0012 and kii =0.36, making the current control bandwidth to be 220 Hz . DC voltage regulator is also a PI controller with parameter of kpv =-3, kiv =-30, making the DC voltage control loop bandwidth to be 22.2 Hz. Vdc_ref is the DC voltage reference given by maximum power point tracking (MPPT) block. The most widely used MPPT principle is perturb and observe (P&O), which perturbs PV array voltage to find the right direction of adjusting DC voltage to increase PV array output power . For utility scale single stage PV inverter, the frequency of MPPT block to change Vdc_ref is smallerthan DC voltage loop bandwidth.The time interval to perturb PV array voltage is long as environmental condition changes not very fast in PV farms. So in this paper, Vdc_ref is considered to be constant. Phase Lock Loop (PLL) track grid voltage phases to do transformation between dq axis and abc axis. PLL bandwidth is set to be 6 Hz with PI block parameter to be kp_pll =0.1, ki_pll =1 Fig. 5. System power loss Comparison of different Q modes In sum, mode 5 volt-var mode is the best option considering voltage regulation and system power loss. Mode 1 unity power factor and mode 2 constant Q are not able to regulate the voltage within range. Mode 3 costs more system power loss than mode 4 and mode 5. While mode 5 is only inductive when needed and is able to deal with both overvoltage and under voltage. 3. Dynamic Model of PV The circuit configuration of a utility PV generator is shown in Fig.6. The switching model is built in Simulink with switching frequency set to be 3 kHz. The rated capacity is 250 kW. The topology contains PV arrays, a DC capacitor, a single stage DC/AC inverter, a three phase LCL filter and a step up transformer. The PV arrays have 29 PV panels in series in each string and 40 strings in parallel. The rated DC voltage is 870 V, which is also the MPPT point of PV arrays under standard weather condition (1000 W/m2 and 25°C). The DC capacitor is chosen to be 8.2 mF to keep DV voltage ripple under ±5%. Parameters of LCL filter with resistor in series with cap are L1 = 0.32 mH, L2 =0.32 mH, C=70.3 µF, Rc are set to make sure that PV inverter output voltage and current harmonics are within standard limit. For three phase step up transformer, the rms values of line to line voltages of primary and secondary side are 330 V and 12 kV separately. Dual loop control strategy is applied in which inner current loops regulate output current in DQ axis separately and outer DC voltage loop regulates DC voltage. Reactive power can be regulated based on reactive current loop. The controller may have an outer reactive power loop according to different reactive power control strategies.
  • 5. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 122 arrows. In conclusion, Fig.8 includes dynamics of power stage, PLL and controllers. The loop in Fig.8 is solved to get PV impedance so that The four DQ frame impedances in Fig.9 are single PV inverter impedances under mode (1)-mode (4). In mode (2-4), PV inverter is inductive in steady state. PV farm is composed of 12 inverter modules. For each module, P = 250 kW, Q = –75 kVar (Generator convention, Output as positive direction). In mode 4, P1 = 175 kW, ratio of slope is –1 in Fig.2 (a). In all four curves, PV impedances in DQ frame are diagonal dominant, which means Zdd and Zqq are much bigger than Zdq and Zqd in magnitude. And all four curves are almost the same at high frequencies over 200 Hz. At lower frequency, blue curve of unity power factor is different from other curves, Zdq and Zqd are zero in magnitude as Q is zero, while the other three curves are almost the same. So mode (2-4) can be represented by mode 2 in dynamics. It can be observed from Fig.9 that the PV terminal impedances are diagonal dominant under mode 1 to mode 4, or in other words the decoupling terms of non-diagonal elements of Zdq and Zqq is much smaller than diagonal elements of Zdd and Zqq , so the original system stability can be decoupled into D axis stability and Q axis stability separately. As the frequency goes from 10 kHz to 1hz, the bode plots of Zdd and Zqq both reveals the dynamics of LCL filter above 1kHz and have a rising trend below current Fig.8 Small signal model of PV inverter controller Linearization of average model with the controllers around the steady state yields the small signal model shown in Fig.8, in which is grid voltage perturbation in grid DQ axis, T qd s ddd ] ~ , ~ [= ~ is duty ratio change, is DC voltage change, T qd s iii ] ~ , ~ [= ~ is PV output current response in grid DQ axis. Power stage dynamics are shown by red arrows and blocks in Fig.8. c v~ and c i ~ are grid voltage perturbation and PV output current response in converter controller DQ axis separately. Grid DQ axis and controller DQ axis don’t align with each other because of PLL effect, which is reflected by blue arrows and the corresponding blocks. And inner current, outer DC voltage, outer reactive power controller and digital control delay are reflected by black boxes and Fig.9 PV impedances under mode 1 - mode 4
  • 6. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 123 becomes non-diagonal dominant, the interconnection stability can not be observed directly from the bode plots of the impedance matrices but need the application of GNC and obtain of the two eigenvalues of the return ratio matrix which is the combination of the impedances of the grid and the PV farm. 4. GNC Application The Nyquist Criterion can be used to assess DC system stability by the number of encirclement of Nyquist diagram of source impedance over load impedance around (-1,0). GNC is an extended version of Nyquist Criterion for multivariable systems [18]. Once the grid impedance Zgrid and PV impedance ZPV are obtained, the return ratio matrix can be calculated as (1) The generalized Nyquist stability criterion can be formulated as [24] : “Let the multivariable system have no open-loop unobservable or uncontrollable modes whose corresponding characteristic frequencies lie in the right-half plane. Then the system will be closed- loop stable if and only if the net sum of anticlockwise encirclements of the critical point (–1+j0) by the set of bandwidth of 220Hz matching the dynamics of ideal current source and are damped down below DC voltage bandwidth around 20Hz. And the negative phase in Zqq of frequency below 6Hz is caused by synchronization function of PLL [18]. So the biggest stability concern for mode 1 to mode 4 are high resistive on the lines from PV farm to the grid, which is not observed in this paper as the lines impedances are not high enough to trigger this kind instability. Fig.10 is the impedance of PV inverter under mode 1, mode 2 (as it can represent mode 2, mode 3, and mode 4) and mode 5. In mode 5, the steady state operation point is the same as other modes, P = 250 kW, Q = –75 kVar (Generator convention, Output as positive direction). V1 = 0.0975 p.u., V2 = 1.0 p.u., V3 = 1.025 p.u., V4 =1.05 p.u., Qmax = 112.5 kVar in Fig.2(b). Compared to mode 1 andmode2,oneobviousdifferenceofmode5isthatsigns of Zdd and Zqq in zero frequency are inverted in mode 5. The magnitude of Zdd is decreased, while the magnitude of Zqd is increased obviously. This will cause unstable PV integration case, which can be proved in section IV. The volt-var control mode builds a huge link between d axis and q axis by generating iq from vd, that’s why the decoupling term Zqd becomes much higher compared to other modes. As the PV terminal impedance matrix Fig.10 PV impedances under mode 1, mode2 and mode 5
  • 7. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 124 stability problem under the control mode of volt-war without reducing the number of PV inverters in parallel. The solutions include reducing current loop bandwidth (reducing current controller PI parameters), reducing reactive power loop bandwidth (reducing current controller PI parameters) and reducing controller delay by increasing switching frequency from 3kHz to 6kHz. Fig. 12 shows the Nyquist diagrams of eigenvalues if one of the solutions is applied. Compared to the blue curves of original volt-var droop control, 1 (s) doesn’t encircles (-1,0) in red, yellow and purple curves, which shows that the system is stable after the modifications. Fig.12 GNC application after alternative solutions 5. Time Domain Waveform and Eigenvalues to Validate GNC Results The results from GNC can be validated by time domain simulation results in Fig.13, which is output current of 3 MW PV farm (12 modules) under volt-var mode in DQ frame. The oscillation frequency is 256 Hz. Oscillation magnitude is limited by Q magnitude – Qmax in droop mode curve in Fig.2(b) before 0.5 s, which is removed at 0.5s and the oscillation of current starts to increase, proving system instability. The most widely used tool of eigenvalues for small- signal stability assessment is also applied on the system with PV generator under volt-var mode. Fig.14 is the plot of five eigenvalues which are closest to the right half plan or in the right half plane on the complex plane. The system has two eigenvalues in the right half plane, which is a confirmation of the instability discovery from GNC application from last section. characteristic loci of L(s) is equal to the total number of right-half plane poles of Zgrid and YPV ”.The two eigenvalues of L are 1 (s) and 2 (s). In all the cases of this paper, Zgrid and YPV don’t have RHP pole, so if the Nyquist diagrams of 1 (s) and 2 (s) don’t encircle (-1,0), then the connection of PV inverters to the system is stable. On the other hand, system is not stable if any of the eigenvalue loci encircles (-1,0). PV terminal impedances or admittances are derived in last section. The grid is the 12 kV distribution grid in Fig.1, in which PV is connected to bus 45. The PV farm capacity is 3 MW, which means that 12 PV inverters are operated in parallel. As this system is very lightly loaded, grid impedance is determined by the cumulative resistance R =3.35 W and inductance L=11.7mH of the direct path from substation bus 1 to bus 45. (2) The results of GNC application are shown in Fig.11, whichincludesNyquistdiagramsofeigenvaluesofreturn ratio matrix L when PV is at different Q control modes of mode 1, mode 2 and mode 5. In mode 2 and mode 5, PV generator operation point is P = 3 MW, Q = - 0.9 Mvar. Dynamics of mode 3-4 are represented by mode 2. It can be observed that if the multiple inverters are all operating at mode 1 or mode 2, either of the eigenvalues encircles (-1,0), meaning that the connection is stable. But if PV is under mode 5, 1 (s) encircles (-1,0), and the connection of PV to the grid becomes unstable. Fig.11 Chatacteristid loci of PV connection to the grid Some alternative solutions of modification on the PV inverter controllers have been found to solve the
  • 8. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 125 modes, based on which GNC is used to assess the grid- PV connection stability. The volt-var control mode changes PV terminal impedance signs and magnitudes significantly and may cause unstable connection to the grid. The stability assessment is proved by time domain simulationandalsoeigenvaluesacquisitionfromthestate space model of the whole system with PV generators. 6. References [1] W. Jewell, R. Rama kumar and S. Hill, “A Study of Dispersed PV Generation on the PSO System,” IEEE Transactions on Energy Conversion, vol. 3, no. 3, p. 473-478, Sep. 1988. [2] A. Povlsen (2002, Feb.), Impacts of Power Penetration from Photovoltaic Power Systems in Distribution Networks, International Energy Agency report lEA PVPS T5-10:2002. Fredericia, Denmark. [Online].Available: http://www.hme.ca/ gridconnect/IEA_PVPS_Task _5-10_Impacts_of_PV_Power_ Penetration.pdf. [3] General Electric Corporate R&D (2003, Aug.), DG Power Quality, Protection and Reliability Case Studies Report, NREL report NRELlSR-560-34635. Niskayuna, New York, USA. [Online]. Available: http://www.nrel.gov/docs/fy03osti/34635.pdf [4] H. Kobayashi and M. Takasaki, «Demonstration Study of Autonomous Demand Area Power System,» in Proc. IEEE Power Eng. Soc. Transm. Distrib. Conf. Expo., Aug. 2006, pp. 548–555. [5] M. Thomson and D. G. Infield, “Network power-flow analysis for a high penetration of distributed generation,” IEEE Trans. Power Syst., vol. 22, no. 3, pp. 1157–1162, Aug. 2007. [6] R. Tonkoski, D. Turcotte, and T. H. M. EL-Fouly, “Impact of high PV penetration on voltage profiles in residential neighborhoods,” IEEE Trans.Sustain. Energy, vol. 3, no. 3, pp. 518–527, Jul. 2012. [7] A. Hoke, R. Butler, J. Hambrick, and B. Kroposki, “Steady-state analysis of maximum photovoltaic penetra-tion levels on typical distribution feeders,” IEEE Trans. Sustain. Energy, vol. 4, no. 2, pp. 350–357, Apr. 2013. [8] IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces, IEEE Std 1547-2018 (Revision of IEEE Std 1547-2003), 2018. [9] E. Demirok et al., “Local reactive power control methods for overvoltage prevention of distributed solar inverters in low- voltage grids,” IEEE J. Photovolt., vol. 1, no. 2, pp. 174–182, Oct. 2011. [10] I. Kim, R. Harley, R. Regassa and Y. Del Valle, «The effect of the volt/var control of photovoltaic systems on the time-series steady-state analysis of a distribution network,» in Proc. IEEE Power Systems Conference, Clemson, SC, USA, 2015. [11] V. H. M. Quezada, J. R. Abbad, and T. G. S. Roman, “Assessment of energy distribution losses for increasing penetration of distributed generation,” IEEE Trans. Power Syst., vol. 21, no. 2, pp. 533–540, May 2006. [12] W. Du, H. Wang, and L. Xiao, “Power system small-signal stability as affected by grid-connected photovoltaic generation,” Eur. Trans. Elect. Power, vol. 22, pp. 688–703, Jul. 2012. Fig.13 Time domain simulation of PV under volt-var mode Fig.14 System eigenvalues in complex plane 5. Conclusion A known broad statement is that active power injected by PV inverters increases the system voltage. In what regards the reactive power compensation capability of PV inverters, this paper showed that the reactive power control mode Volt-var droop mode of Q = f (V) is preferred over other reactive power control modes after the static analysis of voltage regulation effect and the impact on grid power loss. The terminal impedances in DQ frame are derived of utility-scale PV farm based on small signal model of PV inverters. A comparison is done among impedances of PV inverters under 5 different reactive power control
  • 9. ฀ ฀ ฀ ฀ ฀ ฀ ฀ 126 system,” IEEE Trans.Power Electron., vol. 29, no. 12, pp. 6421– 6432, Dec. 2014. [20] A. Rygg, M. Molinas, C. Zhang and X. Cai, “A Modified sequence domain impedance definition and its equivalence to the dq-domain impedance definition for the stability analysis of AC power electronic systems,” IEEE J. Emerg. Sel. Topics Power Electron., vol. 4, no. 4, pp. 1383–1396, Dec. 2016 [21] M. Farivar, R. Neal, C. Clarke, and S. Low, “Optimal inverter VAR control in distribution systems with high PV penetration”, in Proc. IEEE Power and Energy Society General Meeting, San Diego, CA, 2012. [22] American National Standard For Electric Power Systems and Equipment—Voltage Ratings (60 Hertz), ANSI C84.1-2011, 2011. [23] Y. Tang, R. Burgos, C. Li and D. Boroyevich, «Impact of PV inverter penetration on voltage profile and power loss in medium voltage distribution systems,» 2016 IEEE 17th Workshop on Control and Modeling for Power Electronics (COMPEL), Trondheim, 2016, pp. 1-8. [24] A. G. J. MacFarlane and I. Postlethwaite, “The generalized Nyquist stability criterion and multivariable root loci,” Int. J. of Control, vol. 25, no. 1, pp. 81–127, 1977. 7. Acknowledgement The authors wish to gratefully acknowledge the support from Dominion Energy, USA. [13] M. Duckheim, J. Reinschke, P. Gudivada and W. Dunford. “Voltage and power flow oscillations induced by PV inverters connected to a weak power distribution grid”, in Proc. 2013 IEEE Power and Energy Society General Meeting (PES), 21-25 July 2013. [14] S. Liu, P. X. Liu and X. Wang. “Stability Analysis of Grid- Interfacing Inverter Control in Distribution Systems With Multiple Photovoltaic-Based Distributed Generators”, in IEEE Transactions on Industrial Electronics, vol. 63, no. 12, pp 7339 – 7348 , 2016. [15] N. Pogaku, M. Prodanovic, T. C. Green, W. L. Kling, and L. Van Der Sluis, “Modeling, analysis and testing of autonomous operation of an inverter-based microgrid,” IEEE Trans. Power Electron., vol. 22, no. 2, pp. 613–625, Mar. 2007. [16] B. Tamimi, C. Canizares, and K. Bhattacharya, “System stability impact of large-scale and distributed solar photovoltaic generation: The case of Ontario Canada,” IEEE Trans. Sustain. Energy, vol. 4, no. 3, pp. 680–688, Jul. 2013. [17] Z. Moradi-Shahrbabak and A. Tabesh, “Effects of Front-End Converter and DC-Link of a Utility-Scale PV Energy System on Dynamic Stability of a Power System”, IEEE Trans. on Industrial Electronics, vol. 65, no. 1, pp. 403-411 Jan. 2018 [18] B. Wen, D. Boroyevich, R. Burgos, P. Mattavelli, and Z. Shen, “Analysis of d-q small-signal impedance of grid-tied inverters,” in IEEE Trans. Power Electron., vol. 31, no. 1, pp. 675–687, Jan. 2016.. [19] X. Wang, F. Blaabjerg, and W. Wu, “Modeling and analysis of harmonic stability in an AC power-electronics-based power