The 10-second start
NFPA 110 Type 10 starting requirements
for generator set applications
n White Paper
By Greg LaLiberte, Application Engineering Team Leader and Munir Kaderbhai, Application Engineer
The Type 10 start has been a point
of pride for quality generator set
manufacturers for several years.
Touting the ability to start a unit, bring
it up to acceptable frequency and
voltage, and connect it to a facility
suffering from an outage has made
engine-based generator sets the
standby power system of choice for
healthcare and critical power facilities.
However, there has been some
confusion in the industry regarding
what actually is included in those
critical 10 seconds and when the
clock technically starts and stops for
compliance.
Emergency Power Supplies was not
formed until 1976. The first standard that
comprehensively covered the safety aspects
surrounding the application and operation of
Emergency Power Systems was published
as a 1985 edition under the name of NFPA
110. Since this first release, this standard has
undergone numerous revisions, each with
contribution from industry technical experts
representing manufacturers, installers and
end-users.
NFPA 110 is currently on a three-year review
cycle, with the most current published revision
being released as the 2013 edition. It is
important to note that significant changes
occur year to year; as such, the particular
edition that local jurisdictions reference in
their own codes may not be the most current
revision. In these cases, the previous edition
should be reviewed for compliance to the
project in question. Copies of the NFPA
110 standard, as well as other offerings
from NFPA, are available directly from the
organization.
NFPA 110 and Generator Sets
NFPA 110 references Emergency Power
Supply Systems (EPSS) throughout the
standard and in many sections, does not
Power topic #5675 | Technical information from Cummins Power Generation
Our energy working for you.TM
History of NFPA 110
The National Fire Protection Agency (NFPA)
has served as a committee of technical and
nontechnical members that aims to bring fire
prevention and public safety to light through
its publication of various codes and standards.
While the NFPA was established in 1896, the
Technical Committee that advocates for
02PowerTopic#5675
discriminate between the requirements of the various
options that facility designers have to provide standby
power. One such section is the Classification of EPSS
found in Chapter 4 of the 2013 edition. Specifically,
this section addresses the terminology used to define
different applications.
NFPA 110 Standard for Emergency and
Standby Power Systems1
:
NFPA 70 National Electrical Code2
:
Table 4.1(a)
Table 4.1(b)
As stated in the excerpt, the Class defines the required
run time capability, while the Type dictates the allowable
time between a loss of utility power and the restoration
of acceptable power to the facilities’ loads. Because the
Class determination is self-explanatory, the remainder of
this paper will focus on the Type requirements and what
it means with respect to equipment manufacturers and
the applications where these products are installed.
Emergency Power Supply System Type
Designation
The NFPA 110 defines the types of Level I and Level
II EPSSs, but it leaves various other application codes
to define when a specific Type, Class and Level power
system needs to be designated for a certain application.
For example, the NFPA 70, otherwise known as the
National Electrical Code (NEC), dedicates the entirety
of article 700 to Emergency Systems. Two sections of
article 700 specifically address the types of loads and
the time required for power restoration.
700.2 Definitions
Emergency Systems: Those systems legally required
and classed as emergency by municipal, state,
federal, or other codes, or by any governmental
agency having jurisdiction. These systems are
intended to automatically supply illumination, power,
or both, to designated areas and equipment in the
event of failure of the normal supply or in the event
of accident to elements of a system intended to
supply, distribute, and control power and illumination
essential for safety to human life.
700.12 General Requirements
Current supply shall be such that, in the event of
a failure of the normal power supply, emergency
lighting, emergency power, or both shall be available
within the time required for the application, but not to
exceed 10 seconds.
4.1 General. The EPSS shall provide a source of
electrical power of required capacity, reliability, and
quality to loads for a length of time as specified in
Table 4.1(a) and within a specified time following
loss or failure of the normal power supply as
specified in Table 4.1(b).
As defined above, the NEC clearly states that power
and lighting loads which are essential for life safety
must be restored within 10 seconds; therefore, these
types of loads within a facility are Type 10.
As another example, the NFPA 99, the Healthcare
Facilities Code, repeats this requirement in its own
text under section 6.4 for Essential Electrical System
Requirements. The Healthcare Facilities Code classifies
its essential electrical system power sources as Type
10, Class X under NFPA 110.
Key Takeaway #1: Systems determined to
be essential for safety to human life are
assigned as Type 10 under NFPA 110.
“Ten” Second Start
Provide a source of electrical power of required
capacity, reliability, and quality to loads within 10
seconds following loss or failure of the normal power
supply. This is the breakdown of NFPA 110 section
4.1 as it applies to life safety loads. This alludes to the
distinction of two components in the standard: time
and load.
Let’s examine the time aspect first. In most applications
for standby power, the life safety loads that require
on-site power generation will have an engine-driven
generator set serving as its secondary source. Because
the engine requires time, fuel and stored energy to
start, nuisance starts—where the generator set is not
truly needed but is called to start due to a momentary
lapse in the utility’s power quality—should be avoided
as much as possible. With this in mind, NFPA 110
requires a delay for the starting signal of the unit.
03PowerTopic#5675
The one-second minimum must be accounted for when
generator set manufacturers evaluate the performance
of their products with NFPA 110 Type 10 compliance. In
effect, this leaves only nine seconds from the start signal
to the generator set to the life safety loads connected
to the load side of the transfer switch. This is inclusive
of the signal detection and ATS transfer time, which can
reasonably be assumed to be about 0.5 seconds.
It should be noted that there is a controlled minimum
ambient condition of 40 degrees Fahrenheit for Level 1
installations utilizing rotating equipment. This temperature
allows generator set manufacturers to accurately plan for
the required amount of engine block heating that will be
needed to allow large engines to come up to speed in the
required time. The minimum allowable temperature also
limits the exposure of starting batteries to cold cycling,
which may impact the life expectancy and performance.
Key Takeaway #2: The generator set starting
sequence includes a one-second minimum
time delay upon starting, followed by up to
nine seconds of generator set start-up time to
acceptable power and switch transfer time to
have the load connected within 10 seconds.
Acceptable Power
NFPA 110 references that the power must be of
acceptable quality within the time limitation. The transfer
device itself has the control capability to recognize an
acceptable power source and connect loads to it, hence
the name automatic transfer switch. The voltage and
frequency pick-up settings in most industrial transfer
switches can be adjusted to best suit each installation
(typically 90% voltage and 90% frequency). While the
pick-up settings can be adjusted for each application, the
published NFPA 110 Type 10 compliance is based around
using the typical pick-up settings (above) for voltage and
frequency as acceptable power. While manufacturers
can test their equipment to start and energize within the
NFPA 110 Standard for Emergency and
Standby Power Systems1
:
6.2.5 Time Delay on Starting of EPS. A time-delay
device shall be provided to delay starting of the EPS.
The timer shall prevent nuisance starting of the EPS
and possible subsequent load transfer in the event of
harmless momentary power dips and interruptions of
the primary source.
8.4.5. Time delays shall be set as follows:
(1) Time delay on start:
	(a) 1 second minimum
	 (b) 0.5 second minimum for gas turbine units
(2) Time delay on transfer to emergency: no minimum
required
(3) Time delay on restoration to normal: 5 minutes
minimum
(4) Time delay on shutdown: 5 minutes minimum
required time, the subsequent voltage and frequency dip
will depend on the application. However, it is important to
understand that the generator set and load recovery time
is not included in the 10-second start requirement.
Another point to consider relevant to the transient
performance of the system is the time in which the
Emergency Power Supply (EPS) will require to recover
from the voltage and frequency excursions due to the
connecting of the emergency loads by the transfer
switch. This will depend on the connected loads and
the EPS capacity to support those loads. Selection
of the proper EPS is required to ensure that load-
protective devices will not disconnect the loads.
Key Takeaway #3: Power is deemed as
“acceptable” so long as it falls within the
acceptable load pick-up parameters of the
transfer device and it does not cause the
load’s protective functions to disconnect it
from the EPS.
What to Look For
With clarification brought to the two key components
for developing a Type 10 compliant system—time and
power quality—how does one go about specifying an
EPS that needs to meet the NFPA 110 requirement?
There is a critical evaluation criterion for each of the
requirements. In order to qualify that the generator
set will indeed meet the 10-second start requirement,
it is important to verify that generator set is capable
of meeting the requirements as stated by NFPA
110. Such a statement can typically be found on the
manufacturer’s specification sheet, referenced under a
common section with other industry code-compliance
and certification information.
Summary
The Type 10 requirement encompasses three
key aspects that relate to the applicability of the
requirement, what is actually required to occur during
those 10 seconds and what qualifies as acceptable
power from the perspective of the load. At the end of
the day, both manufacturers and system owners are
reaching toward a common goal: restoring power as
quickly as possible to facilities that need it the most.
However, due to the differences in every application,
compliance with the requirements laid out by NFPA 110
to start and transfer an emergency power system to
the load bus serves as a common ground that allows
manufacturers to test and certify their equipment while
providing peace of mind to facility owners.
04PowerTopic#5675
About the authors
Greg LaLiberte is a graduate of the
University of Minnesota with a bachelor’s
degree in electrical engineering. He has been
with Cummins Power Generation since 2011
and leads the Sales Application Engineering
group for North America with previous
experience in high-horsepower generator
set design. Greg’s primary focus is assisting clients and
distributors with technical guidance on application-
specific issues, and he is actively engaged in the Power
Seminar customer training program. He also provided
technical training content to support distribution teams
in the United States, Canada and Caribbean.
power.cummins.com
©2014 Cummins Power Generation Inc. All
right reserved. Cummins Power Generation and
Cummins are registered trademarks of Cummins
Inc. “Our energy working for you.” is a trademark
of Cummins Power Generation.
NAPT-5675-EN (9/14)
Munir Kaderbhai is a graduate of North
Dakota State University with a master’s
degree in electrical engineering. He has
been with Cummins Power Generation
since 2010 as an application engineer.
Munir’s primary focus is assisting clients
and distributors with technical guidance
on application-specific issues concerning
standard commercial products and unique
projects. In addition, he also supports the design and
analysis of hybrid power generation systems integrated
for telecom and microgrid applications (energy
storage and renewable energy integration). Munir is
actively engaged in the Power Seminar program as
an instructor in technical seminars and webinars, and
he also provides technical training content to support
distribution teams in the North American market.
1 Copyright 2012 National Fire Protection Agency,
“NFPA 110: Standard for Emergency and Standby
Power Systems, 2013 Edition”
2 Copyright 2010, National Fire Protection Agency,
“NFPA 70: National Electrical Code, 2011 Edition”
Disclaimer: With regard to the quoted material from
NFPA 70 and NFPA 110: This reprinted material is not
the complete and official position of the NFPA on the
referenced subject, which is represented solely by the
standard in its entirety.

More Related Content

What's hot

Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systemsmichaeljmack
 
Selective Coordination
Selective CoordinationSelective Coordination
Selective Coordinationmichaeljmack
 
Artificial lift forum ul 1741 presentation - final
Artificial lift forum   ul 1741 presentation - finalArtificial lift forum   ul 1741 presentation - final
Artificial lift forum ul 1741 presentation - finalRon Henderson
 
Upgrading gen protect and grounding
Upgrading gen protect and groundingUpgrading gen protect and grounding
Upgrading gen protect and groundingmichaeljmack
 
Selection of Reference Node and Angular Baselining using Synchrophasors Meas...
Selection of Reference Node and Angular  Baselining using Synchrophasors Meas...Selection of Reference Node and Angular  Baselining using Synchrophasors Meas...
Selection of Reference Node and Angular Baselining using Synchrophasors Meas...Chandan Kumar
 
Remediation of Old Substations for Arc Flash hazard
Remediation of Old Substations for Arc Flash hazardRemediation of Old Substations for Arc Flash hazard
Remediation of Old Substations for Arc Flash hazardIJAPEJOURNAL
 
Critical Power: NFPA 110: Standard for Emergency and Standby Power
Critical Power: NFPA 110: Standard for Emergency and Standby Power Critical Power: NFPA 110: Standard for Emergency and Standby Power
Critical Power: NFPA 110: Standard for Emergency and Standby Power ConsultingSpecifyingEngineer
 
Evaluation of standby power system architectures
Evaluation of standby power system architecturesEvaluation of standby power system architectures
Evaluation of standby power system architecturesmichaeljmack
 
2005 16 autumn_wiring_matters__complete_no_adverts
2005 16 autumn_wiring_matters__complete_no_adverts2005 16 autumn_wiring_matters__complete_no_adverts
2005 16 autumn_wiring_matters__complete_no_advertsKhalid Sithari
 
Grid Event Analysis In Indian Power System
Grid Event Analysis In Indian Power SystemGrid Event Analysis In Indian Power System
Grid Event Analysis In Indian Power SystemChandan Kumar
 
ATS, Grounding Issues & Installation Considerations
ATS, Grounding Issues & Installation ConsiderationsATS, Grounding Issues & Installation Considerations
ATS, Grounding Issues & Installation Considerationsmichaeljmack
 
Electrical Lessons learned
Electrical Lessons learnedElectrical Lessons learned
Electrical Lessons learnedmichaeljmack
 
Proposed Changes & Revisions to the 2017 National Electrical Code©
Proposed Changes & Revisions to the 2017 National Electrical Code©Proposed Changes & Revisions to the 2017 National Electrical Code©
Proposed Changes & Revisions to the 2017 National Electrical Code©Nicole Kearney
 
RELAY CO-ORDINATION WITH FAULT CALCULATION
RELAY CO-ORDINATION WITH FAULT CALCULATIONRELAY CO-ORDINATION WITH FAULT CALCULATION
RELAY CO-ORDINATION WITH FAULT CALCULATIONMd Sarowar Alam
 
17th Edition Part 4 4
17th  Edition  Part 4 417th  Edition  Part 4 4
17th Edition Part 4 4Paul Holden
 

What's hot (20)

Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systems
 
Selective Coordination
Selective CoordinationSelective Coordination
Selective Coordination
 
Artificial lift forum ul 1741 presentation - final
Artificial lift forum   ul 1741 presentation - finalArtificial lift forum   ul 1741 presentation - final
Artificial lift forum ul 1741 presentation - final
 
IEEE Blue Book
IEEE Blue BookIEEE Blue Book
IEEE Blue Book
 
Surge Protection
Surge ProtectionSurge Protection
Surge Protection
 
2. genset ratings (3)
2. genset ratings (3)2. genset ratings (3)
2. genset ratings (3)
 
Upgrading gen protect and grounding
Upgrading gen protect and groundingUpgrading gen protect and grounding
Upgrading gen protect and grounding
 
Selection of Reference Node and Angular Baselining using Synchrophasors Meas...
Selection of Reference Node and Angular  Baselining using Synchrophasors Meas...Selection of Reference Node and Angular  Baselining using Synchrophasors Meas...
Selection of Reference Node and Angular Baselining using Synchrophasors Meas...
 
Remediation of Old Substations for Arc Flash hazard
Remediation of Old Substations for Arc Flash hazardRemediation of Old Substations for Arc Flash hazard
Remediation of Old Substations for Arc Flash hazard
 
Critical Power: NFPA 110: Standard for Emergency and Standby Power
Critical Power: NFPA 110: Standard for Emergency and Standby Power Critical Power: NFPA 110: Standard for Emergency and Standby Power
Critical Power: NFPA 110: Standard for Emergency and Standby Power
 
Evaluation of standby power system architectures
Evaluation of standby power system architecturesEvaluation of standby power system architectures
Evaluation of standby power system architectures
 
2005 16 autumn_wiring_matters__complete_no_adverts
2005 16 autumn_wiring_matters__complete_no_adverts2005 16 autumn_wiring_matters__complete_no_adverts
2005 16 autumn_wiring_matters__complete_no_adverts
 
Grid Event Analysis In Indian Power System
Grid Event Analysis In Indian Power SystemGrid Event Analysis In Indian Power System
Grid Event Analysis In Indian Power System
 
ATS, Grounding Issues & Installation Considerations
ATS, Grounding Issues & Installation ConsiderationsATS, Grounding Issues & Installation Considerations
ATS, Grounding Issues & Installation Considerations
 
Electrical Lessons learned
Electrical Lessons learnedElectrical Lessons learned
Electrical Lessons learned
 
Code questions
Code questionsCode questions
Code questions
 
Ieee pes psrc
Ieee pes psrcIeee pes psrc
Ieee pes psrc
 
Proposed Changes & Revisions to the 2017 National Electrical Code©
Proposed Changes & Revisions to the 2017 National Electrical Code©Proposed Changes & Revisions to the 2017 National Electrical Code©
Proposed Changes & Revisions to the 2017 National Electrical Code©
 
RELAY CO-ORDINATION WITH FAULT CALCULATION
RELAY CO-ORDINATION WITH FAULT CALCULATIONRELAY CO-ORDINATION WITH FAULT CALCULATION
RELAY CO-ORDINATION WITH FAULT CALCULATION
 
17th Edition Part 4 4
17th  Edition  Part 4 417th  Edition  Part 4 4
17th Edition Part 4 4
 

Similar to NAPT-5675-EN

Access control basics-4
Access control basics-4Access control basics-4
Access control basics-4grantlerc
 
CRITERIA FOR OVERHEAD TRANSMISSION LINE AMPACITY RATINGS
CRITERIA FOR OVERHEAD TRANSMISSION LINE AMPACITY RATINGSCRITERIA FOR OVERHEAD TRANSMISSION LINE AMPACITY RATINGS
CRITERIA FOR OVERHEAD TRANSMISSION LINE AMPACITY RATINGSArchili Kokhtashvili
 
PowerHour_NFPA110.pdf
PowerHour_NFPA110.pdfPowerHour_NFPA110.pdf
PowerHour_NFPA110.pdfManuel676208
 
So Tay Bao Duong Dong Co Dien
So Tay Bao Duong Dong Co DienSo Tay Bao Duong Dong Co Dien
So Tay Bao Duong Dong Co DienMan_Ebook
 
Power system stability issues and Defence Mechanism in Indian Grid
Power system stability issues and Defence Mechanism in Indian GridPower system stability issues and Defence Mechanism in Indian Grid
Power system stability issues and Defence Mechanism in Indian GridChandan Kumar
 
Selecting proper dg set
Selecting proper dg setSelecting proper dg set
Selecting proper dg setMKJain1511
 
Factors to Consider When Perfroming Maint - IEEE Transactions
Factors to Consider When Perfroming Maint - IEEE TransactionsFactors to Consider When Perfroming Maint - IEEE Transactions
Factors to Consider When Perfroming Maint - IEEE TransactionsJim White
 
Fault Ride-Through of DFIG Wind Turbine by DVR Using Synchronous Reference Fr...
Fault Ride-Through of DFIG Wind Turbine by DVR Using Synchronous Reference Fr...Fault Ride-Through of DFIG Wind Turbine by DVR Using Synchronous Reference Fr...
Fault Ride-Through of DFIG Wind Turbine by DVR Using Synchronous Reference Fr...theijes
 
Arc Flash Calculations What Does It All Mean
Arc Flash Calculations What Does It All MeanArc Flash Calculations What Does It All Mean
Arc Flash Calculations What Does It All MeanB Bhargav Reddy
 
Battery Maintenance Solutions for Critical Facilities: Meeting Regulatory Req...
Battery Maintenance Solutions for Critical Facilities: Meeting Regulatory Req...Battery Maintenance Solutions for Critical Facilities: Meeting Regulatory Req...
Battery Maintenance Solutions for Critical Facilities: Meeting Regulatory Req...Electrical Reliability Services
 
Electricty wiring code 2016
Electricty wiring code 2016Electricty wiring code 2016
Electricty wiring code 2016Manikandan Mani
 
General principles of motor control
General principles of motor controlGeneral principles of motor control
General principles of motor controlmegashane
 
Transformer factory acceptance tests
Transformer factory acceptance testsTransformer factory acceptance tests
Transformer factory acceptance testsengrsurif
 
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMSLOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMSEditor IJMTER
 
Electrical Safety In The Workplace by Crawford Engineering Services
Electrical Safety In The Workplace by Crawford Engineering ServicesElectrical Safety In The Workplace by Crawford Engineering Services
Electrical Safety In The Workplace by Crawford Engineering ServicesAtlantic Training, LLC.
 
11925351_05.pdf
11925351_05.pdf11925351_05.pdf
11925351_05.pdfViVoy
 
Enhancement of reactive power capability of doubly fed induction generator 2-3
Enhancement of reactive power capability of doubly fed induction generator 2-3Enhancement of reactive power capability of doubly fed induction generator 2-3
Enhancement of reactive power capability of doubly fed induction generator 2-3IAEME Publication
 
Powering-Up the Industrial Network
Powering-Up the Industrial NetworkPowering-Up the Industrial Network
Powering-Up the Industrial NetworkPanduit
 

Similar to NAPT-5675-EN (20)

Access control basics-4
Access control basics-4Access control basics-4
Access control basics-4
 
CRITERIA FOR OVERHEAD TRANSMISSION LINE AMPACITY RATINGS
CRITERIA FOR OVERHEAD TRANSMISSION LINE AMPACITY RATINGSCRITERIA FOR OVERHEAD TRANSMISSION LINE AMPACITY RATINGS
CRITERIA FOR OVERHEAD TRANSMISSION LINE AMPACITY RATINGS
 
PowerHour_NFPA110.pdf
PowerHour_NFPA110.pdfPowerHour_NFPA110.pdf
PowerHour_NFPA110.pdf
 
So Tay Bao Duong Dong Co Dien
So Tay Bao Duong Dong Co DienSo Tay Bao Duong Dong Co Dien
So Tay Bao Duong Dong Co Dien
 
Power system stability issues and Defence Mechanism in Indian Grid
Power system stability issues and Defence Mechanism in Indian GridPower system stability issues and Defence Mechanism in Indian Grid
Power system stability issues and Defence Mechanism in Indian Grid
 
Selecting proper dg set
Selecting proper dg setSelecting proper dg set
Selecting proper dg set
 
Factors to Consider When Perfroming Maint - IEEE Transactions
Factors to Consider When Perfroming Maint - IEEE TransactionsFactors to Consider When Perfroming Maint - IEEE Transactions
Factors to Consider When Perfroming Maint - IEEE Transactions
 
Fault Ride-Through of DFIG Wind Turbine by DVR Using Synchronous Reference Fr...
Fault Ride-Through of DFIG Wind Turbine by DVR Using Synchronous Reference Fr...Fault Ride-Through of DFIG Wind Turbine by DVR Using Synchronous Reference Fr...
Fault Ride-Through of DFIG Wind Turbine by DVR Using Synchronous Reference Fr...
 
Arc Flash Calculations What Does It All Mean
Arc Flash Calculations What Does It All MeanArc Flash Calculations What Does It All Mean
Arc Flash Calculations What Does It All Mean
 
Battery Maintenance Solutions for Critical Facilities: Meeting Regulatory Req...
Battery Maintenance Solutions for Critical Facilities: Meeting Regulatory Req...Battery Maintenance Solutions for Critical Facilities: Meeting Regulatory Req...
Battery Maintenance Solutions for Critical Facilities: Meeting Regulatory Req...
 
Electricty wiring code 2016
Electricty wiring code 2016Electricty wiring code 2016
Electricty wiring code 2016
 
Advanced Power Reactor 1400 MWe
Advanced Power Reactor 1400 MWe  Advanced Power Reactor 1400 MWe
Advanced Power Reactor 1400 MWe
 
General principles of motor control
General principles of motor controlGeneral principles of motor control
General principles of motor control
 
Transformer factory acceptance tests
Transformer factory acceptance testsTransformer factory acceptance tests
Transformer factory acceptance tests
 
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMSLOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
 
2015 03-16 nfpa-70_e_changes
2015 03-16 nfpa-70_e_changes2015 03-16 nfpa-70_e_changes
2015 03-16 nfpa-70_e_changes
 
Electrical Safety In The Workplace by Crawford Engineering Services
Electrical Safety In The Workplace by Crawford Engineering ServicesElectrical Safety In The Workplace by Crawford Engineering Services
Electrical Safety In The Workplace by Crawford Engineering Services
 
11925351_05.pdf
11925351_05.pdf11925351_05.pdf
11925351_05.pdf
 
Enhancement of reactive power capability of doubly fed induction generator 2-3
Enhancement of reactive power capability of doubly fed induction generator 2-3Enhancement of reactive power capability of doubly fed induction generator 2-3
Enhancement of reactive power capability of doubly fed induction generator 2-3
 
Powering-Up the Industrial Network
Powering-Up the Industrial NetworkPowering-Up the Industrial Network
Powering-Up the Industrial Network
 

NAPT-5675-EN

  • 1. The 10-second start NFPA 110 Type 10 starting requirements for generator set applications n White Paper By Greg LaLiberte, Application Engineering Team Leader and Munir Kaderbhai, Application Engineer The Type 10 start has been a point of pride for quality generator set manufacturers for several years. Touting the ability to start a unit, bring it up to acceptable frequency and voltage, and connect it to a facility suffering from an outage has made engine-based generator sets the standby power system of choice for healthcare and critical power facilities. However, there has been some confusion in the industry regarding what actually is included in those critical 10 seconds and when the clock technically starts and stops for compliance. Emergency Power Supplies was not formed until 1976. The first standard that comprehensively covered the safety aspects surrounding the application and operation of Emergency Power Systems was published as a 1985 edition under the name of NFPA 110. Since this first release, this standard has undergone numerous revisions, each with contribution from industry technical experts representing manufacturers, installers and end-users. NFPA 110 is currently on a three-year review cycle, with the most current published revision being released as the 2013 edition. It is important to note that significant changes occur year to year; as such, the particular edition that local jurisdictions reference in their own codes may not be the most current revision. In these cases, the previous edition should be reviewed for compliance to the project in question. Copies of the NFPA 110 standard, as well as other offerings from NFPA, are available directly from the organization. NFPA 110 and Generator Sets NFPA 110 references Emergency Power Supply Systems (EPSS) throughout the standard and in many sections, does not Power topic #5675 | Technical information from Cummins Power Generation Our energy working for you.TM History of NFPA 110 The National Fire Protection Agency (NFPA) has served as a committee of technical and nontechnical members that aims to bring fire prevention and public safety to light through its publication of various codes and standards. While the NFPA was established in 1896, the Technical Committee that advocates for
  • 2. 02PowerTopic#5675 discriminate between the requirements of the various options that facility designers have to provide standby power. One such section is the Classification of EPSS found in Chapter 4 of the 2013 edition. Specifically, this section addresses the terminology used to define different applications. NFPA 110 Standard for Emergency and Standby Power Systems1 : NFPA 70 National Electrical Code2 : Table 4.1(a) Table 4.1(b) As stated in the excerpt, the Class defines the required run time capability, while the Type dictates the allowable time between a loss of utility power and the restoration of acceptable power to the facilities’ loads. Because the Class determination is self-explanatory, the remainder of this paper will focus on the Type requirements and what it means with respect to equipment manufacturers and the applications where these products are installed. Emergency Power Supply System Type Designation The NFPA 110 defines the types of Level I and Level II EPSSs, but it leaves various other application codes to define when a specific Type, Class and Level power system needs to be designated for a certain application. For example, the NFPA 70, otherwise known as the National Electrical Code (NEC), dedicates the entirety of article 700 to Emergency Systems. Two sections of article 700 specifically address the types of loads and the time required for power restoration. 700.2 Definitions Emergency Systems: Those systems legally required and classed as emergency by municipal, state, federal, or other codes, or by any governmental agency having jurisdiction. These systems are intended to automatically supply illumination, power, or both, to designated areas and equipment in the event of failure of the normal supply or in the event of accident to elements of a system intended to supply, distribute, and control power and illumination essential for safety to human life. 700.12 General Requirements Current supply shall be such that, in the event of a failure of the normal power supply, emergency lighting, emergency power, or both shall be available within the time required for the application, but not to exceed 10 seconds. 4.1 General. The EPSS shall provide a source of electrical power of required capacity, reliability, and quality to loads for a length of time as specified in Table 4.1(a) and within a specified time following loss or failure of the normal power supply as specified in Table 4.1(b). As defined above, the NEC clearly states that power and lighting loads which are essential for life safety must be restored within 10 seconds; therefore, these types of loads within a facility are Type 10. As another example, the NFPA 99, the Healthcare Facilities Code, repeats this requirement in its own text under section 6.4 for Essential Electrical System Requirements. The Healthcare Facilities Code classifies its essential electrical system power sources as Type 10, Class X under NFPA 110. Key Takeaway #1: Systems determined to be essential for safety to human life are assigned as Type 10 under NFPA 110. “Ten” Second Start Provide a source of electrical power of required capacity, reliability, and quality to loads within 10 seconds following loss or failure of the normal power supply. This is the breakdown of NFPA 110 section 4.1 as it applies to life safety loads. This alludes to the distinction of two components in the standard: time and load. Let’s examine the time aspect first. In most applications for standby power, the life safety loads that require on-site power generation will have an engine-driven generator set serving as its secondary source. Because the engine requires time, fuel and stored energy to start, nuisance starts—where the generator set is not truly needed but is called to start due to a momentary lapse in the utility’s power quality—should be avoided as much as possible. With this in mind, NFPA 110 requires a delay for the starting signal of the unit.
  • 3. 03PowerTopic#5675 The one-second minimum must be accounted for when generator set manufacturers evaluate the performance of their products with NFPA 110 Type 10 compliance. In effect, this leaves only nine seconds from the start signal to the generator set to the life safety loads connected to the load side of the transfer switch. This is inclusive of the signal detection and ATS transfer time, which can reasonably be assumed to be about 0.5 seconds. It should be noted that there is a controlled minimum ambient condition of 40 degrees Fahrenheit for Level 1 installations utilizing rotating equipment. This temperature allows generator set manufacturers to accurately plan for the required amount of engine block heating that will be needed to allow large engines to come up to speed in the required time. The minimum allowable temperature also limits the exposure of starting batteries to cold cycling, which may impact the life expectancy and performance. Key Takeaway #2: The generator set starting sequence includes a one-second minimum time delay upon starting, followed by up to nine seconds of generator set start-up time to acceptable power and switch transfer time to have the load connected within 10 seconds. Acceptable Power NFPA 110 references that the power must be of acceptable quality within the time limitation. The transfer device itself has the control capability to recognize an acceptable power source and connect loads to it, hence the name automatic transfer switch. The voltage and frequency pick-up settings in most industrial transfer switches can be adjusted to best suit each installation (typically 90% voltage and 90% frequency). While the pick-up settings can be adjusted for each application, the published NFPA 110 Type 10 compliance is based around using the typical pick-up settings (above) for voltage and frequency as acceptable power. While manufacturers can test their equipment to start and energize within the NFPA 110 Standard for Emergency and Standby Power Systems1 : 6.2.5 Time Delay on Starting of EPS. A time-delay device shall be provided to delay starting of the EPS. The timer shall prevent nuisance starting of the EPS and possible subsequent load transfer in the event of harmless momentary power dips and interruptions of the primary source. 8.4.5. Time delays shall be set as follows: (1) Time delay on start: (a) 1 second minimum (b) 0.5 second minimum for gas turbine units (2) Time delay on transfer to emergency: no minimum required (3) Time delay on restoration to normal: 5 minutes minimum (4) Time delay on shutdown: 5 minutes minimum required time, the subsequent voltage and frequency dip will depend on the application. However, it is important to understand that the generator set and load recovery time is not included in the 10-second start requirement. Another point to consider relevant to the transient performance of the system is the time in which the Emergency Power Supply (EPS) will require to recover from the voltage and frequency excursions due to the connecting of the emergency loads by the transfer switch. This will depend on the connected loads and the EPS capacity to support those loads. Selection of the proper EPS is required to ensure that load- protective devices will not disconnect the loads. Key Takeaway #3: Power is deemed as “acceptable” so long as it falls within the acceptable load pick-up parameters of the transfer device and it does not cause the load’s protective functions to disconnect it from the EPS. What to Look For With clarification brought to the two key components for developing a Type 10 compliant system—time and power quality—how does one go about specifying an EPS that needs to meet the NFPA 110 requirement? There is a critical evaluation criterion for each of the requirements. In order to qualify that the generator set will indeed meet the 10-second start requirement, it is important to verify that generator set is capable of meeting the requirements as stated by NFPA 110. Such a statement can typically be found on the manufacturer’s specification sheet, referenced under a common section with other industry code-compliance and certification information. Summary The Type 10 requirement encompasses three key aspects that relate to the applicability of the requirement, what is actually required to occur during those 10 seconds and what qualifies as acceptable power from the perspective of the load. At the end of the day, both manufacturers and system owners are reaching toward a common goal: restoring power as quickly as possible to facilities that need it the most. However, due to the differences in every application, compliance with the requirements laid out by NFPA 110 to start and transfer an emergency power system to the load bus serves as a common ground that allows manufacturers to test and certify their equipment while providing peace of mind to facility owners.
  • 4. 04PowerTopic#5675 About the authors Greg LaLiberte is a graduate of the University of Minnesota with a bachelor’s degree in electrical engineering. He has been with Cummins Power Generation since 2011 and leads the Sales Application Engineering group for North America with previous experience in high-horsepower generator set design. Greg’s primary focus is assisting clients and distributors with technical guidance on application- specific issues, and he is actively engaged in the Power Seminar customer training program. He also provided technical training content to support distribution teams in the United States, Canada and Caribbean. power.cummins.com ©2014 Cummins Power Generation Inc. All right reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. NAPT-5675-EN (9/14) Munir Kaderbhai is a graduate of North Dakota State University with a master’s degree in electrical engineering. He has been with Cummins Power Generation since 2010 as an application engineer. Munir’s primary focus is assisting clients and distributors with technical guidance on application-specific issues concerning standard commercial products and unique projects. In addition, he also supports the design and analysis of hybrid power generation systems integrated for telecom and microgrid applications (energy storage and renewable energy integration). Munir is actively engaged in the Power Seminar program as an instructor in technical seminars and webinars, and he also provides technical training content to support distribution teams in the North American market. 1 Copyright 2012 National Fire Protection Agency, “NFPA 110: Standard for Emergency and Standby Power Systems, 2013 Edition” 2 Copyright 2010, National Fire Protection Agency, “NFPA 70: National Electrical Code, 2011 Edition” Disclaimer: With regard to the quoted material from NFPA 70 and NFPA 110: This reprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented solely by the standard in its entirety.