MIL-STD-704F
12 MARCH 2004
SUPERSEDING
MIL-STD-704E
1 MAY 1991
DEPARTMENT OF DEFENSE
INTERFACE STANDARD
AIRCRAFT ELECTRIC POWER
CHARACTERISTICS
AMSC N/A AREA SESS
NOT MEASUREMENT
SENSITIVE
MIL-STD-704F
ii
FOREWORD
1. This standard is approved for use by all Departments and Agencies of the Department of
Defense.
2. The purpose of this interface standard is to ensure compatibility between the aircraft electric
system, external power, and airborne utilization equipment.
3. Comments, suggestions, or questions on this document should be addressed to Commander,
Naval Air Systems Command, Code 4.1.4, Highway 547, Lakehurst, NJ 08733-5100 or email to
thomas.omara@navy.mil. Since contact information can change, you may want to verify the
currency of this address information using the ASSIST Online database at www.dodssp.daps.mil.
MIL-STD-704F
iii
CONTENTS
PARAGRAPH PAGE
FORWARD ........................................................................................................................ii
1. SCOPE ......................................................................................................................... 1
1.1 Scope ...................................................................................................................... 1
2. APPLICABLE DOCUMENT ............................................................................................ 1
2.1 General ................................................................................................................... 1
2.2 Government documents ......................................................................................... 1
2.2.1 Specifications, standards and handbooks ............................................................... 1
2.3 Order of precedence ............................................................................................... 1
3. DEFINITIONS ................................................................................................................... 1
3.1 Acronyms used in this standard ............................................................................. 1
3.2 Abnormal operation ............................................................................................... 2
3.3 AC voltage ............................................................................................................. 2
3.4 Aircraft electric power systems ............................................................................. 2
3.5 Crest factor ............................................................................................................. 2
3.6 Current ................................................................................................................... 2
3.7 Current modulation ................................................................................................ 2
3.8 DC voltage ............................................................................................................. 2
3.9 Distortion ............................................................................................................... 3
3.10 Distortion factor ..................................................................................................... 3
3.11 Distortion spectrum ................................................................................................ 3
3.12 Electric starting operation ...................................................................................... 3
3.13 Emergency operation ............................................................................................. 3
3.14 External power source ............................................................................................ 3
3.15 Frequency ............................................................................................................... 3
3.16 Frequency modulation ........................................................................................... 3
3.17 Load unbalance ...................................................................................................... 3
3.18 Normal operation ................................................................................................... 3
3.19 Overfrequency and underfrequency ....................................................................... 4
3.20 Overvoltage and undervoltage ............................................................................... 4
3.21 Point of regulation .................................................................................................. 4
3.22 Power factor ........................................................................................................... 4
3.23 Pulsed load ............................................................................................................. 4
3.24 Rate of change of frequency .................................................................................. 4
3.25 Ripple ..................................................................................................................... 4
3.26 Steady state ............................................................................................................ 4
3.27 Transfer operation .................................................................................................. 4
3.28 Transient ................................................................................................................ 5
3.29 Utilization equipment ............................................................................................. 5
3.30 Utilization equipment terminals ............................................................................. 5
3.31 Voltage modulation ................................................................................................ 5
3.32 Voltage phase difference ........................................................................................ 5
3.33 Voltage unbalance .................................................................................................. 5
MIL-STD-704F
iv
CONTENTS
PARAGRAPH PAGE
4. GENERAL REQUIREMENTS ......................................................................................... 5
4.1 Aircraft electric power system requirements ......................................................... 5
4.1.1 Aircraft electric power system performance .......................................................... 5
4.1.2 Electric power source characteristics ..................................................................... 5
4.1.3 Protective devices .................................................................................................. 6
4.2 Aircraft utilization equipment requirements .......................................................... 6
4.2.1 Power compatibility ............................................................................................... 6
4.2.2 Operation ................................................................................................................ 6
4.2.2.1 Normal operation ................................................................................................... 6
4.2.2.2 Abnormal operation ............................................................................................... 6
4.2.2.3 Transfer operation .................................................................................................. 6
4.2.2.4 Emergency operation ............................................................................................. 6
4.2.2.5 Starting operation ................................................................................................... 6
4.2.3 Power failure .......................................................................................................... 7
4.2.4 AC power utilization .............................................................................................. 7
4.3 External power source requirement ....................................................................... 7
4.4 Test requirements ................................................................................................... 7
5. DETAILED REQUIREMENTS ........................................................................................ 7
5.1 Transfer operation characteristics .......................................................................... 7
5.2 AC power characteristics ....................................................................................... 7
5.2.1 Type system ........................................................................................................... 7
5.2.2 Phase sequence ....................................................................................................... 8
5.2.3 Normal operation ................................................................................................... 8
5.2.4 Abnormal operation ............................................................................................... 8
5.2.5 Emergency operation ............................................................................................. 8
5.3 DC power characteristics ....................................................................................... 8
5.3.1 Type system ........................................................................................................... 8
5.3.2 28 volts DC system ................................................................................................ 8
5.3.2.1 Normal operation ................................................................................................... 8
5.3.2.2 Abnormal operation ............................................................................................... 8
5.3.2.3 Emergency operation ............................................................................................. 9
5.3.2.4 Electric starting ...................................................................................................... 9
5.3.3 270 volts DC system .............................................................................................. 9
5.3.3.1 Normal operation ................................................................................................... 9
5.3.3.2 Abnormal operation ............................................................................................... 9
5.3.3.3 Emergency operation ............................................................................................. 9
5.4 Load characteristics ............................................................................................... 9
5.4.1 Grounding .............................................................................................................. 9
5.4.2 Load unbalance ...................................................................................................... 9
5.4.3 Power factor ........................................................................................................... 9
5.4.4 Polarity or phase reversal ....................................................................................... 9
5.4.5 Multiple input terminals ......................................................................................... 9
MIL-STD-704F
v
CONTENTS
PARAGRAPH PAGE
6. NOTES ....................................................................................................................... 10
6.1 Intended use ......................................................................................................... 10
6.2 Considerations ...................................................................................................... 10
6.3 Supersession data ................................................................................................. 10
6.4 International standardization implementation ...................................................... 10
6.5 Changes from previous issue ............................................................................... 10
6.6 Application of this standard in utilization equipment specifications ................... 10
6.7 Pulsed load design issues ..................................................................................... 11
6.8 Non-linear loads and effects ................................................................................ 11
6.9 Precedence ........................................................................................................... 11
6.10 Guidance and lessons learned .............................................................................. 11
6.10.1 Compatibility and testing ..................................................................................... 11
6.10.2 Compatibility and installation .............................................................................. 12
6.11 Subject term (keyword) listing ............................................................................. 12
TABLES
I AC normal operation characteristics - 400 Hertz (see 5.2.3) ............................... 13
II AC normal operation characteristics - variable frequency (see 5.2.3) ................. 13
III AC normal operation characteristics - 60 Hertz (see 5.2.3) ................................. 14
IV DC normal operation characteristics (see 5.3.2.1, 5.3.4.1) .................................. 14
FIGURES
1 Load unbalance limits for three phase utilization equipment .............................. 15
2 Phasor diagram showing required phase sequence relationship .......................... 16
3 Envelope of normal 400 Hz and variable frequency AC voltage transient ......... 17
4 Limits for 400 Hz and variable frequency AC overvoltage and undervoltage .... 18
5 Envelope of normal 400 Hz AC frequency transient ........................................... 19
6 Limits for 400 Hz AC overfrequency or underfrequency .................................... 20
7 Maximum distortion spectrum of 400 Hz and variable frequency AC voltage ... 21
8 Envelope of normal 60 Hz voltage transient ........................................................ 22
9 Limits for 60 Hz AC overvoltage and undervoltage ............................................ 23
10 Envelope of normal 60 Hz AC frequency transient ............................................. 24
11 Limits for 60 Hz AC overfrequency and underfrequency ................................... 25
12 Maximum distortion spectrum of 60 Hz AC voltage ........................................... 26
13 Envelope of normal voltage transients for 28 volts DC system ........................... 27
14 Limits for overvoltage and undervoltage for 28 volts DC system ....................... 28
15 Maximum distortion spectrum for 28 volts DC system ....................................... 29
16 Envelope of normal voltage transient for 270 volts DC system .......................... 30
17 Limits for DC overvoltage and undervoltage for 270 volts DC system .............. 31
18 Maximum distortion spectrum for 270 volts DC system. .................................... 32
CONCLUDING MATERIAL ......................................................................................... 33
MIL-STD-704F
1
1. SCOPE
1.1 Scope. This standard establishes the requirements and characteristics of aircraft
electric power provided at the input terminals of electric utilization equipment. MIL-HDBK-
704-1 through-8 defines test methods and procedures for determining airborne utilization
equipment compliance with the electric power characteristics requirements defined herein.
Electromagnetic interference and voltage spikes are not covered by this standard.
2. APPLICABLE DOCUMENTS
2.1 General. The document listed in this section is specified in sections 3, 4, and 5 of this
standard. This section does not include documents cited in other sections of this standard or
recommended for additional information or as examples. While every effort has been made to
ensure the completeness of this list, document users are cautioned that they must meet all
specified requirements documents cited in sections 3, 4, and 5 of this standard, whether or not
they are listed.
2.2 Government documents.
2.2.1 Specifications, standards and handbooks. The following specifications, standards,
and handbooks form a part of this document to the extent specified herein. Unless otherwise
specified, the issues of these documents are those cited in the solicitation or contract.
INTERNATIONAL STANDARDIZATION AGREEMENTS
STANAG 3456 Aircraft Electrical System Characteristics
(Copies of this document are available online at http://assist.daps.dla.mil/quicksearch/ or
www.dodssp.daps.mil or from the Standardization Document Order Desk, 700 Robbins Avenue,
Building 4D, Philadelphia, PA 19111-5094.)
2.3 Order of precedence. In the event of a conflict between the text of this document and
the references cited herein, the text of this standard takes precedence. Nothing in this document,
however, supersedes applicable laws and regulations unless a specific exemption has been
obtained.
3. DEFINITIONS
3.1 Acronyms used in this standard. The acronyms used in this standard are defined as
follows:
a. AC − Alternating Current
b. COTS − Commercial Off-The-Shelf
c. DC − Direct Current
d. DoD − Department of Defense
e. kVA − kilovolt-ampere
MIL-STD-704F
2
f. NATO − North Atlantic Treaty Organization
g. POR − Point of Regulation
h. RMS − Root Mean Square
i. STANAG − Standardization Agreement
j. VA − Volt-ampere
3.2 Abnormal operation. Abnormal operation occurs when a malfunction or failure in
the electric system has taken place and the protective devices of the system are operating to
remove the malfunction or failure from the remainder of the system before the limits for
abnormal operation are exceeded. The power source may operate in a degraded mode on a
continuous basis where the power characteristics supplied to the utilization equipment exceed
normal operation limits but remain within the limits for abnormal operation.
3.3 AC voltage. AC voltage is the root mean square (RMS) phase to neutral value for
each half cycle.
a. Steady state AC voltage is the time average of the RMS voltage over a period not to
exceed one second.
b. Peak AC voltage is the maximum absolute value of the instantaneous voltage.
c. The direct current (DC) component of the AC voltage is the average value of the
voltage.
3.4 Aircraft electric power systems. An aircraft electric power system consists of a main
power source, emergency power source, power conversion equipment, control and protection
devices, and an interconnection network (wires, cables, connectors, etc.). The main power is
derived from aircraft generators driven by the aircraft propulsion engines. Emergency power is
derived from batteries, engine bleed air, independent auxiliary power units, ram air driven
generators, or hydraulically driven generators.
3.5 Crest factor. The crest factor is the absolute value of the ratio of the peak to the
RMS value for each half cycle of the voltage waveform.
3.6 Current. Alternating Current (AC) current is the RMS value for one half cycle
measured between consecutive zero crossings of the fundamental frequency component. Direct
Current (DC) current is the instantaneous value.
3.7 Current modulation. Current modulation is the difference between maximum
current and minimum current. Percent current modulation is the ratio of the current modulation
to the average (mean for DC, RMS of the fundamental for AC) current multiplied by 100 over a
one second period.
3.8 DC voltage. Steady state DC voltage is the time average of the instantaneous DC
voltage over a period not to exceed one second.
MIL-STD-704F
3
3.9 Distortion. AC distortion is the RMS value of the AC waveform exclusive of the
fundamental. In a DC system, DC distortion is the RMS value of the alternating voltage
component on the DC voltage.
3.10 Distortion factor. The AC distortion factor is the ratio of the AC distortion to the
RMS value of the fundamental component. The DC distortion factor is the ratio of the DC
distortion to the DC steady state voltage.
3.11 Distortion spectrum. The distortion spectrum quantifies AC or DC distortion in
terms of the amplitude of each frequency component. The distortion spectrum includes the
components resulting from amplitude and frequency modulation as well as harmonic and non-
harmonic components of the waveform.
3.12 Electric starting operation. Electric starting operation is a specialized case of
normal electric system operating conditions where the normal voltage limits may be exceeded
due to the high electric demand. The voltage limits for normal operation may be exceeded
during the following starting conditions:
a. An electric start of the propulsion engine. (Battery power, aircraft DC power or
external power applied on the aircraft bus.)
b. A battery start of an auxiliary power unit.
3.13 Emergency operation. Emergency operation occurs following the loss of the main
generating equipment when a limited electric source, independent of the main system, is used to
power a reduced complement of distribution and utilization equipment selected to maintain flight
and personnel safety.
3.14 External power source. The external power source refers to the ground or
shipboard power source used to provide power to the aircraft's electrical distribution system.
3.15 Frequency. Frequency is the reciprocal of the period of the AC voltage waveform.
The unit of frequency is Hertz (Hz). Steady state frequency is the time average of the frequency
over a period not to exceed one second.
3.16 Frequency modulation. Frequency modulation is the difference between the
maximum and minimum frequency values that occur in a one-minute period during steady state
operating conditions. Frequency modulation is a measure of the stability of the power system's
frequency regulation.
3.17 Load unbalance. Load unbalance for a three-phase load is the difference between
the highest and lowest phase loads.
3.18 Normal operation. Normal operation occurs when the system is operating as
intended in the absence of any fault or malfunction that degrades performance beyond
established requirements. It includes all system functions required for aircraft operation except
MIL-STD-704F
4
during the electric starting of propulsion engines and the battery start of an auxiliary power unit.
Normal operation includes switching of utilization equipment, prime mover speed changes,
synchronizing and paralleling of power sources, and operation from external power sources.
Transfer operation, as defined herein, is a normal function. It is treated separately in this standard
because of the power interruption that it may produce.
Conducted switching spikes, which are excursions of the instantaneous voltage not exceeding 50
microseconds, are normal operation characteristics.
3.19 Overfrequency and underfrequency. Overfrequency and underfrequency are those
frequencies that exceed the limits for normal operation and are limited by the action of protective
devices.
3.20 Overvoltage and undervoltage. Overvoltage and undervoltage are those voltages
that exceed the limits for normal operation and are limited by the action of protective devices.
3.21 Point of regulation. The POR is that point at which a power generation source
senses and regulates the system voltage. The POR should be at the input terminals of the line
contactor connecting the power source to the load bus.
3.22 Power factor. The ratio of real power (measured in watts) to apparent power
(measured in volt-amperes).
3.23 Pulsed load. Pulsed loads are loads whose power requirement varies under steady
state conditions because of underlying physical phenomena or the inherent operating mode of
equipment.
3.24 Rate of change of frequency. The rate of change of frequency is defined as the
ratio of the absolute difference in frequency over a designated period of time to the designated
period of time. The unit of rate of change of frequency is designated Hertz per second (Hz/s).
3.25 Ripple. Ripple is the variation of voltage about the steady state DC voltage during
steady state electric system operation. Sources of ripple may include, but are not limited to,
voltage regulation instability of the DC power source, commutation/rectification within the DC
power source, and load variations within utilization equipment.
Ripple amplitude is the maximum absolute value of the difference between the steady state and
the instantaneous DC voltage.
3.26 Steady state. Steady state is that condition in which the characteristics remain
within the limits for normal operation steady state characteristics throughout an arbitrarily long
period of time. Steady state conditions may include lesser transients.
3.27 Transfer operation. Transfer operation occurs when the electric system transfers
between power sources, including transfers from or to external power sources.
MIL-STD-704F
5
3.28 Transient. A transient is a changing value of a characteristic that usually occurs as
a result of normal disturbances such as electric load change and engine speed change. A
transient may also occur as a result of a momentary power interruption or an abnormal
disturbance such as fault clearing.
a. Transients that do not exceed the steady state limits are defined as lesser transients.
b. Transients that exceed the steady state limits but remain within the specified normal
transients limits are defined as normal transients.
c. Transients that exceed normal transients limits as a result of an abnormal disturbance
and eventually return to steady state limits are defined as abnormal transients.
3.29 Utilization equipment. Utilization equipment is that equipment which receives
power from the electric power system.
3.30 Utilization equipment terminals. Utilization equipment terminals provide the
interface with the electric power system. Power interconnections, within the utilization
equipment or equipment system, are excluded.
3.31 Voltage modulation. Voltage modulation is the variation of AC voltage during
steady state AC electric system operation. Sources of voltage modulation may include, but are
not limited to, voltage regulation stability of the AC power source, generator speed variations,
and load variations within utilization equipment. Voltage modulation amplitude is the difference
between the maximum and minimum AC voltage values that occur in a one second period during
steady state operating conditions.
3.32 Voltage phase difference. The voltage phase difference is the difference in
electrical degrees between the fundamental components of any two-phase voltages taken at
consecutive zero crossings traced in the negative to positive direction.
3.33 Voltage unbalance. Voltage unbalance is defined as the maximum difference
between RMS phase voltage amplitudes at the utilization equipment terminals.
4. GENERAL REQUIREMENTS
4.1 Aircraft electric power system requirements.
4.1.1 Aircraft electric power system performance. The aircraft electric power system
shall provide electric power having the characteristics specified in this standard at the utilization
equipment terminals during all operations of the power system.
4.1.2 Electrical power source characteristics. The characteristics of the electrical power
measured at the output terminals of an unregulated power source or the POR of a regulated
power source shall be within the limits specified in the applicable detail specification of the
MIL-STD-704F
6
power source. It is the responsibility of the airframe manufacturer or modifier to provide the
distribution and protection network to the terminals of the utilization equipment while
maintaining the power characteristics specified in this standard.
4.1.3 Protective devices. Protective devices shall function independently of control and
regulation equipment.
4.2 Aircraft utilization equipment requirements.
4.2.1 Power compatibility. Utilization equipment shall be compatible with the power
characteristics specified herein. Utilization equipment shall not require electric power of better
quality than specified herein. Utilization equipment shall be compatible with the applicable
aircraft specification requirements for control of electromagnetic interference and voltage spikes
induced by lightning, electromagnetic pulses, and power switching. Electromagnetic
interference and voltage spikes are not covered by this standard.
4.2.2 Operation. When supplied electric power having characteristics specified herein,
aircraft utilization equipment shall provide the level of performance required by its detail
specification for each operating condition. Operation of utilization equipment shall not cause the
power characteristics at its terminals to exceed the limits specified herein. Utilization equipment
operation under any electric system operating condition shall not have an adverse effect on or
cause malfunction of the electric system.
4.2.2.1 Normal operation. Utilization equipment shall provide the level of performance
specified in its detail specification.
4.2.2.2 Abnormal operation. Utilization equipment shall be permitted a degradation or
loss of function unless otherwise specified in its detail specification. Utilization equipment shall
not suffer damage or cause an unsafe condition. Utilization equipment shall automatically
resume full performance when normal operation of the electrical system is restored.
4.2.2.3 Transfer operation. Utilization equipment may not be required to operate under
the transfer condition unless a level of performance is specified by its detail specification.
Utilization equipment shall automatically resume specified performance when normal operating
characteristics are resumed.
4.2.2.4 Emergency operation. Utilization equipment shall provide the level of
performance specified in its detail specification when such performance is essential for flight or
safety.
4.2.2.5 Starting operation. Utilization equipment shall provide the level of
performance specified in its detail specification when performance is essential during the starting
operation.
MIL-STD-704F
7
4.2.3 Power failure. The loss of power (AC or DC) or the loss of one or more phases
of AC power to any utilization equipment terminal shall not result in an unsafe condition or
damage to utilization equipment.
4.2.4 AC power utilization. Utilization equipment that requires more than 0.5 kVA of
AC power shall be configured to utilize three-phase steady state balanced power. Load
unbalance of individual utilization equipment shall be within the limits of figure 1. The load
unbalance of utilization equipment whose total load is greater than 30 kVA shall be no greater
than 3.33 percent of its total three-phase load. Single-phase AC power shall be used only on a
line-to-neutral basis. AC power shall not be half-wave rectified.
4.3 External power source requirement. External electric power sources shall supply
power having the characteristics specified in this standard at the power input terminals of the
aircraft electric utilization equipment. In order to allow for steady state voltage drop between the
aircraft external power receptacle and the aircraft utilization equipment terminals, the voltage at
the external power receptacle shall be as follows:
a. AC system 113 to 118 volts (AC voltage drop of 0 to 5 volts)
b. 28 VDC system 24 to 29 volts (DC voltage drop of 0 to 2 volts)
c. 270 VDC system 260 to 280 volts (DC voltage drop of 0 to 10 volts)
4.4 Test requirements. Equipment testing is required to demonstrate utilization
equipment compatibility with the electric power characteristics of this standard. Utilization
equipment test requirements shall be in accordance with the equipment detail specification. The
applicable test methods of MIL-HDBK-704 shall be used to determine that the utilization
equipment complies with this standard. Aircraft shall be tested to demonstrate that the aircraft
electric system power characteristics are within the limits of this standard throughout all
operating conditions of the aircraft and its utilization equipment. Aircraft test requirements shall
be in accordance with the aircraft detail specification.
5. DETAILED REQUIREMENTS
5.1 Transfer operation characteristics. Under conditions of bus or power source
transfers, voltage and frequency shall not vary between zero and normal operating limits for
longer than 50 milliseconds. A normal transient may occur upon completion of a transfer.
5.2 AC power characteristics.
5.2.1 Type system. AC systems shall provide electrical power using single-phase or
three-phase wire-connected grounded neutral systems. The voltage waveform shall be a sine
wave with a nominal voltage of 115/200 volts and a nominal frequency of 400 Hz. Variable
frequency and double-voltage systems may be used as alternative electrical power systems.
Variable frequency systems have frequencies varying from 360 to 800 Hz with a nominal voltage
of 115/200 volts. Double-voltage systems have nominal voltages of 230/400 volts and a nominal
frequency of 400 Hz. A third alternative for secondary electric power systems is single-phase 60
MIL-STD-704F
8
Hz systems. These systems have a nominal voltage of 115 volts with a nominal frequency of 60
Hz and are used in support of COTS equipment only.
All power types may not be available on all aircraft platforms. The selection of the input power
type for utilization equipment shall take into consideration the aircraft power types available on
the intended platform and the capacity of the electrical system of that aircraft platform.
5.2.2 Phase sequence. The phase sequence shall be A-B-C and aircraft wiring and
equipment terminals shall be marked accordingly. Generator terminals shall be marked T1-T2-
T3 corresponding to A-B-C, respectively. The phase sequence shall be counterclockwise
(positive) as shown on figure 2.
5.2.3 Normal operation. Normal operation characteristics shall be in accordance with
figures 3, 5, and 7, table I for 400 Hz systems and table II for variable frequency systems; and
figures 8, 10 and 12, and table III for 60 Hz systems.
For variable frequency systems the rate of change of frequency from onset of a normal frequency
transient measured for over a period of time of greater than 25 milliseconds shall not exceed 250
Hz per second.
5.2.4 Abnormal operation. The overvoltage and undervoltage values shall be within
the limits of figure 4 for 400 Hz and variable frequency systems and figure 9 for 60 Hz systems.
The overfrequency and underfrequency values shall be within the limits of figure 6 for 400 Hz
systems, and figure 11 for 60 Hz systems. The overfrequency and underfrequency for variable
frequency systems shall not exceed the 360 - 800 Hz steady state values.
For variable frequency systems the rate of change of frequency from onset of an abnormal
frequency transient measured for over a period of time of greater than 25 milliseconds shall not
exceed 500 Hz per second.
5.2.5 Emergency operation. All power characteristics in emergency operation shall be
the same as normal operation.
5.3 DC power characteristics.
5.3.1 Type system. DC systems shall provide power using direct current, two-wire or
negative ground return system having a nominal voltage of 28 Volts or 270 Volts. These
systems shall conform to figures 13, 14, 15, 16, 17, 18 and table IV.
5.3.2 28 volts DC system.
5.3.2.1 Normal operation. Normal operation characteristics shall be in accordance with
figures 13, 15 and table IV.
5.3.2.2 Abnormal operation. Overvoltage and undervoltage values shall be within the
limits of figure 14.
MIL-STD-704F
9
5.3.2.3 Emergency operation. The DC steady state voltage in emergency operation
shall be between 16 and 29 volts.
5.3.2.4 Electric starting. The DC voltage in electric starting operation shall be between
12 and 29 volts. Electric starting of an auxiliary power unit (other than battery starts) is a normal
operating function and is not included under this condition.
5.3.3 270 volts DC system.
5.3.3.1 Normal operation. Normal operation characteristics shall be in accordance with
figures 16 and 18 and table IV.
5.3.3.2 Abnormal operation. Overvoltage and undervoltage values shall be within the
limits of figure 17.
5.3.3.3 Emergency operation. All power characteristics in emergency operation shall
be the same as normal operation.
5.4 Load characteristics.
5.4.1 Grounding. All electrical power input terminals, including AC neutral and DC
negative terminals, shall be electrically isolated from case ground. Equipment chassis shall not
be used for power returns.
5.4.2 Load unbalance. Load unbalance of three-phase AC equipment shall be in
accordance with figure 1. Load unbalance of equipment exceeding 30 kVA shall not exceed
3.33 percent of the total three-phase load.
5.4.3 Power factor. Power factor of AC equipment greater than 500 VA shall be
between 0.85 lagging and unity when operating at 50 percent or more of its rated load current in
steady state condition. AC equipment shall not have leading power factor when operating at
more than 100 VA.
5.4.4 Polarity or phase reversal. Three-phase AC equipment shall not be damaged by
reversal of input phase sequence. Single-phase AC equipment shall not be damaged by reversal
of line and neutral connections. DC equipment shall not be damaged by reversal of positive and
negative connections. Employing a positive physical means to prevent phase or polarity reversal
shall also fulfill this requirement.
5.4.5 Multiple input terminals. Equipment having multiple input terminals for
connection to more than one power source shall isolate the inputs from each other so that one
power source cannot supply power to another. AC inputs shall not be paralleled. DC inputs
shall be protected with blocking diodes if they are paralleled.
MIL-STD-704F
10
6. NOTES
(This section contains information of a general or explanatory nature that may be helpful, but is
not mandatory.)
6.1 Intended use. The intent of this document is to define the electric power quality
requirements for DoD aircraft, however it may also be used with commercial aircraft or other
types of vehicles. Other industry documents such as SAE-AS1212 and ISO 1540 also define
aircraft electric power quality requirements. These documents are generally not appropriate for
use with military aircraft because they do not address all of the areas of concern with military
aircraft electric power quality and often require wider limits compared to this document due to
the differences in the types and sizes of aircraft covered. In addition, they do not always take
into account legacy DoD aircraft electrical power systems or legacy DoD utilization equipment.
The power characteristics requirements of this document also apply to commercial and non-
developmental utilization equipment purchased in accordance with the policy described in the
SD-2, “Buying Commercial & Nondevelopmental Items: A Handbook”. If such equipment does
not fully comply with the power characteristics requirement of this document, the effect of the
equipment noncompliance on the electrical power quality and on the equipment capability to
perform its intended function in the aircraft should be evaluated.
6.2 Considerations. Each element of the aircraft electrical power system is qualified
and purchased to its own specification requirements document. The requirements of this
document are less severe than the output power requirements of the typical electrical power
source, taking into account the degradation of electrical power quality that can occur between a
power source and the input electrical power terminals of utilization equipment. The effects of
the electrical power distribution, control, and protection system, and the interactions between
electrical power sources and utilization equipment may cause the degradation of electrical power
quality.
6.3 Supersession data. This edition of MIL-STD-704 supersedes all previous editions.
Previous editions of MIL-STD-704, which are cited in contracts for legacy aircraft electrical
systems remain in effect for procurement of utilization equipment. Therefore, copies of previous
editions should be retained, as they are no longer stocked by the Government.
6.4 International standardization implementation. This standard implements STANAG
3456, “Aircraft Electrical System Characteristics”. When changes to, revision, or cancellation of
this standard are proposed, the preparing activity must coordinate the action with the U.S.
National Point of Contact for the international standardization agreement, as identified in the
ASSIST database at www.dodssp.daps.mil.
6.5 Changes from previous issue. Marginal notations are not used in this revision to
identify changes with respect to the previous issue due to the extent of the changes.
6.6 Application of this standard in utilization equipment specifications. Utilization
equipment specifications should include a statement that "This equipment shall utilize electric
power in accordance with MIL-STD-704 and shall be in accordance with the utilization
MIL-STD-704F
11
equipment requirements of MIL-STD-704." The equipment specification should also specify the
type of electric power to be utilized and the detailed performance required during normal,
abnormal, emergency, starting, transfer and power failure operation of the electric system. The
electric power characteristics specified herein are minimum requirements for utilization
equipment. Therefore, specifications for utilization equipment that require greater operating
margins should include specific electric power characteristic operating ranges that exceed those
stated herein. Utilization equipment specifications should never specify operating ranges that are
narrower than those specified herein nor waive compatibility with the electric power
characteristics specified herein, since that could result in failure of the equipment to perform as
required. Utilization equipment specifications should also include requirements that reduce the
likelihood of the equipment having an adverse effect on the electric power characteristics
provided by the electric system. High inrush current, low lagging power factor, high peak power
to average power ratio, high current ripple amplitude, and current distortion are some
characteristics of utilization equipment that can adversely affect the electric system by degrading
electric power characteristics or increasing capacity requirements. Minimizing these undesirable
utilization equipment characteristics involves tradeoffs with weight, cost and reliability that are
specific to each type of equipment and should be addressed in the utilization equipment
specification.
6.7 Pulsed load design issues. Pulsed loads are a potential cause of unacceptable
voltage modulation. Hence large pulsed loads may require excess power source capacity or
dedicated power sources to protect other aircraft equipment. The utilization equipment designer
should strive to minimize the current modulation produced by pulsed loads.
6.8 Non-linear loads and effects. Attention must be given to non-linear loads and their
effect on the AC power bus. All loads should not introduce excessive current distortion such that
other equipment is affected.
6.9 Precedence. Tables and equations included in the figures take precedence over the
graphical representation of the figure itself. Continuous reproduction of the figures may result in
the distortion of the curves.
6.10 Guidance and lessons learned.
6.10.1 Compatibility and testing. Historically users of MIL-STD-704 interpret or view
the electrical power quality characteristics limits in this document as they would those of a
typical power source/generator. This interpretation is incorrect. An aircraft electrical system is
composed of a variety of power components (generation, conversion, inversion, control, power
distribution, power management devices, etc.) that provide power to aircraft buses and utilization
equipment terminals. Each component and subsystem is designed and tested to its individual
equipment specification, which often requires tighter performance than does MIL-STD-704 to
compensate for the effects of loads as well as the associated feeder/line voltage drops therein.
Therefore, the limits specified herein are minimum requirements for specifying that utilization
equipment is compatible with aircraft electrical power. To ensure utilization equipment is
compatible with the aircraft power, system testing as outlined in MIL-HDBK-704-1 through -8
MIL-STD-704F
12
should be performed. For information and access to the MIL-STD-704 compatibility test
laboratory and test methods of MIL-HDBK-704-1 through -8, please contact:
Naval Air Systems Command
Attn: MIL-STD-704 Laboratory
Electrical Power Systems Division (AIR-4.4.4)
48298 Shaw Road, Bldg. 1461
Patuxent River, MD 20670
Website: http://ppe.navair.navy.mil/
6.10.2 Compatibility and installation. Users of MIL-STD-704 power should consider
selection and installation processes when planning to integrate and install utilization equipment
or components in aircraft. System designers should be aware of the related interface standards,
MIL-STD-7080, MIL-STD-464 and SAE-AS50881, which address installation, electromagnetic
compatibility and wiring, respectively. Use of these standards is recommended, especially when
incorporating COTS equipment into military aircraft. The 60 Hz power requirements were
included to accommodate COTS and non-developmental items procured using procedures of SD-
2. Equipment designed for use on military aircraft should not use 60 Hz power, since it requires
more weight and prime mover capacity per unit of power consumed by the utilization equipment.
6.11 Subject term (keyword) listing.
AC power utilization
DC voltage
Electric starting operation
Equipment, utilization
Power compatibility
System, electrical
Voltage
MIL-STD-704F
13
TABLE I. AC normal operation characteristics - 400 Hertz (see 5.2.3).
Steady state characteristics Limits
Steady state voltage
Voltage unbalance
Voltage modulation
Voltage phase difference
Distortion factor
Distortion spectrum
Crest factor
DC component
Steady state frequency
Frequency modulation
108.0 to 118.0 Volts, RMS
3.0 Volts, RMS maximum
2.5 Volts, RMS maximum
116° to 124°
0.05 maximum
Figure 7
1.31 to 1.51
+ 0.10 to - 0.10 Volts
393 to 407 Hz
4 Hz
Transient characteristics Limits
Peak voltage
Voltage transient
Frequency transient
±271.8 Volts
Figure 3
Figure 5
TABLE II. AC normal operation characteristics - variable frequency (see 5.2.3).
Steady state characteristics Limits
Steady state voltage
Voltage unbalance
Voltage modulation
Voltage phase difference
Distortion factor
Distortion spectrum
Crest factor
DC component
Steady state frequency
Frequency modulation
108.0 to 118.0 Volts, RMS
3.0 Volts, RMS maximum
2.5 Volts, RMS maximum
116° to 124°
0.05 maximum
Figure 7
1.31 to 1.51
+0.10 to – 0.10 Volts
360 to 800 Hz
4 Hz
Transient characteristics Limits
Peak voltage
Voltage transient
Frequency transient
Maximum rate of change of frequency
±271.8 Volts
Figure 3
Not to exceed steady state values of 360 to 800 Hz
250 Hz/sec
MIL-STD-704F
14
TABLE III. AC normal operation characteristics - 60 Hertz (see 5.2.3).
Steady state characteristics Limits
Steady state voltage
Voltage unbalance
Voltage modulation
Voltage phase difference
Distortion factor
Distortion spectrum
Crest factor
DC component
Steady state frequency
Frequency modulation
105.0 to 125.0 Volts, RMS
3.0 Volts, RMS maximum
2.5 Volts, RMS maximum
116° to 124°
0.05 maximum
Figure 12
1.31 to 1.51
+0.10 to – 0.10 Volts
59.5 to 60.5 Hz
0.5 Hz
Transient characteristics Limits
Peak voltage
Voltage transient
Frequency transient
±271.8 Volts
Figure 8
Figure 10
TABLE IV. DC normal operation characteristics (see 5.3.2.1, 5.3.4.1).
Limits
Steady state characteristics 28 Volt DC system 270 Volt DC system
Steady state voltage
Distortion factor
Distortion spectrum
Ripple amplitude
22.0 to 29.0 Volts
0.035 maximum
Figure 15
1.5 Volts maximum
250.0 to 280.0 Volts
0.015 maximum
Figure 18
6.0 Volts maximum
Limits
Transient characteristics 28 Volts
DC system
270 Volts
DC system
Voltage transient Figure 13 Figure 16
MIL-STD-704F
15
FIGURE 1. Load unbalance limits for three-phase utilization equipment.
0
100
200
300
400
500
600
700
800
900
1000
0 5 10 15 20 25 30
Total Three Phase Load (kVA)
Maximum
Load
Unbalance
(VA)
Three Phase
Load (kVA)
0.5
1.0
4.0
7.0
12.0
20.0
24.0
27.0
30.0
Unbalance
(VA)
100
200
390
500
650
825
900
950
1000
See paragraph 4.2.4 for
total load over 30.0 kVA.
MIL-STD-704F
16
FIGURE 2. Phasor diagram showing required phase sequence relationship.
Fundamental Component
of Phase Voltage
120°
Phase Rotation
(Positive)
A
B
C
N
120°
Voltage
Phase Difference
MIL-STD-704F
17
Envelope of Normal AC Voltage Transient
40
60
80
100
120
140
160
180
200
0 0.025 0.05 0.075 0.1 0.125 0.15 0.175
Time from Onset of Transient (seconds)
Volts
(RMS)
180 V; 0.010 sec
118 V; 0.0875 sec
80 V; 0.010 sec
108 V; 0.080 sec
Note: Steady state limits do
not include disturbances
allowed in Table I
118
108
85
113
AC Power at External
Power Receptacle
See paragraph 4.3
FIGURE 3. Envelope of normal 400 Hz and variable frequency AC voltage transient.
18
FIGURE 4. Limits for 400 Hz and variable frequency AC overvoltage or undervoltage.
Limits for 400 Hz and Variable Frequency AC Overvoltage and
18
MIL-STD-704F
Limits for 400 Hz and Variable Frequency AC Overvoltage and Undervoltage
0
20
40
60
80
100
120
140
160
180
200
0.01 0.1 1 10 100
Time from Onset of Overvoltage or Undervoltage (seconds)
Volts
(RMS)
V = 180 for t < 0.05
V = 124.6 + 2.77/t for 0.05 ≤ t ≤ 6.925
V = 125 for t > 6.925
100
125
7
MIL-STD-704F
19
FIGURE 5. Envelope of normal 400 Hz AC frequency transient.
370
380
390
400
410
420
430
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14
Time from Onset of Transient (seconds)
Frequency,
Hz
407
393
Maximum Limit
425
375
Minimum Limit
Note:
1. Steady state limits do not include
the distrubances allowed in Table I.
MIL-STD-704F
20
0
50
100
150
200
250
300
350
400
450
500
0 1 2 3 4 5 6 7 8 9 10 11
Time from Onset of Overfrequency or Underfrequency, Seconds
Frequency,
Hz
480
420
380
Overfrequency Limit
Underfrequency Limit
FIGURE 6. Limits for 400 Hz AC overfrequency or underfrequency.
21
FIGURE 7. Maximum distortion spectrum of 400 Hz and variable frequency AC voltage.
Maximum Distortion Spectrum of 400 Hz and Variable Frequency AC Voltage
-35
-30
-25
-20
-15
-10
-5
0
5
10
15
20
10 100 1,000 10,000 100,000 1,000,000
Frequency, Hertz
Distortion
Amplitude,
dB
from
1.0
VRMS
+
2
0
d
B
/
d
e
c
a
d
e
-20dB/decade
Distortion
Amplitude,
Volts
RMS
0.0316
0.1000
0.3160
1.0000
3.1600
Upper Limit
400 Hz
Upper Limit
Variable Frequency
400 Hz VF
10 -10.00 -10.00
100 -10.00 -10.00
1,000 10.00 10.00
3,000 10.00 10.00
6,000 4.00 10.00
500,000 -34.44 -24.44
1,000,000 --- -34.44
Distortion Amplitude, dBV
Frequency
Maximum Distortion Spectrum of 400 Hz and Variable Frequency AC Voltage
-35
-30
-25
-20
-15
-10
-5
0
5
10
15
20
10 100 1,000 10,000 100,000 1,000,000
Frequency, Hertz
Distortion
Amplitude,
dB
from
1.0
VRMS
+
2
0
d
B
/
d
e
c
a
d
e
-20dB/decade
Distortion
Amplitude,
Volts
RMS
0.0316
0.1000
0.3160
1.0000
3.1600
Upper Limit
400 Hz
Upper Limit
Variable Frequency
400 Hz VF
10 -10.00 -10.00
100 -10.00 -10.00
1,000 10.00 10.00
3,000 10.00 10.00
6,000 4.00 10.00
500,000 -34.44 -24.44
1,000,000 --- -34.44
Distortion Amplitude, dBV
Frequency
Maximum Distortion Spectrum of 400 Hz and Variable Frequency AC Voltage
-35
-30
-25
-20
-15
-10
-5
0
5
10
15
20
10 100 1,000 10,000 100,000 1,000,000
Frequency, Hertz
Distortion
Amplitude,
dB
from
1.0
VRMS
+
2
0
d
B
/
d
e
c
a
d
e
-20dB/decade
Distortion
Amplitude,
Volts
RMS
0.0316
0.1000
0.3160
1.0000
3.1600
Upper Limit
400 Hz
Upper Limit
Variable Frequency
400 Hz VF
10
Maximum Distortion Spectrum of 400 Hz and Variable Frequency AC Voltage
-35
-30
-25
-20
-15
-10
-5
0
5
10
15
20
10 100 1,000 10,000 100,000 1,000,000
Frequency, Hertz
Distortion
Amplitude,
dB
from
1.0
VRMS
+
2
0
d
B
/
d
e
c
a
d
e
-20dB/decade
Distortion
Amplitude,
Volts
RMS
0.0316
0.1000
0.3160
1.0000
3.1600
Upper Limit
400 Hz
Upper Limit
Variable Frequency
400 Hz VF
10 -10.00 -10.00
100 -10.00 -10.00
1,000 10.00 10.00
3,000 10.00 10.00
6,000 4.00 10.00
500,000 -34.44 -24.44
1,000,000 --- -34.44
Distortion Amplitude, dBV
Frequency
21
MIL-STD-704F
MIL-STD-704F
22
Envelope of Normal 60 Hz Voltage Transient
0
20
40
60
80
100
120
140
160
0.000 0.025 0.050 0.075 0.100 0.125 0.150 0.175
Time from Onset of Transient (seconds)
Volts
(RMS)
125
105
115
152.0 V; 0.0083 sec
130.0 V; 0.0167 sec
70.0 V; 0.0167 sec
125.0 V; 0.1000 sec
105.0 V; 0.1000 sec
31.0 V; 0.0083 sec
Notes:
1. Voltage may go to zero potential during bus transfers
2. Steady state limits do not include the disturbances
allowed in Table III.
1 cycle @ 60 Hz
½ cycle @ 60 Hz
FIGURE 8. Envelope of normal 60 Hz voltage transient.
MIL-STD-704F
23
FIGURE 9. Limits for 60 Hz AC overvoltage and undervoltage.
MIL-STD-704F
23
2
0
20
40
60
80
100
120
140
160
180
200
0.00
1
0.0
1
0.1 1 1
0
Time from Onset of Overvoltage or Undervoltage
(seconds)
0.067
4 cycles @ 60 HZ
128
100
V = 180
V = 125.15 + 3.71/t
V = 128
t < 0.067
0.67 < t < 1.300
t > 1.300
for
for
for
Volts
(RMS)
MIL-STD-704F
24
FIGURE 10. Envelope of normal 60 Hz AC frequency transient.
58.5
59.0
59.5
60.0
60.5
61.0
61.5
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
Time from Onset of Transient, seconds
Frequency,
Hz
Upper Boundary
Lower Boundary
Note: Steady state limits do not include
disturbances allowed in Table III.
MIL-STD-704F
25
FIGURE 11. Limits for 60 Hz AC overfrequency and underfrequency.
61
59
58
57
56
10
5
0 15
59.5
Frequency,
HZ
Time from Onset of Overfrequency or Underfrequency, Seconds
60.5
0
7
60
26
FIGURE 12. Maximum distortion spectrum of 60 Hz AC voltage.
-35
-30
-25
-20
-15
-10
-5
0
5
10
15
20
1 10 100 1,000 10,000 100,000
Frequency, Hz
Distortion
Amplitude,
dB
from
1.0
V
RMS
Frequency, Hz
1
15
150
450
75,000
Distortion Amplitude
-10
-10
10
10
-34.44
-35
-30
-25
-20
-15
-10
-5
0
5
10
15
20
1 10 100 1,000 10,000 100,000
Frequency, Hz
Distortion
Amplitude,
dB
from
1.0
V
RMS
Frequency, Hz
1
15
150
450
75,000
Distortion Amplitude
-10
-10
10
10
-34.44
26
MIL-STD-704F
MIL-STD-704F
27
10
20
30
40
50
0.000 0.025 0.050 0.075 0.100 0.125 0.150 0.175
Time from Onset of Transient (seconds)
Volts,
DC
50 V, 0.0125 sec
29 V, 0.0825 sec
22 V, 0.1000 sec
18 V, 0.0150 sec
29
22
Note: Steady state limits do
not include the disturbances
allowed in Table IV
FIGURE 13. Envelope of normal voltage transients for 28 volts DC system.
28
0
10
20
30
40
50
60
0.01 0.1 1 10 100
Time from Onset of Overvoltage or Undervoltage (seconds)
Volts,
DC
V = 50 for t < 0.05
V = 31.38 + 0.931/t for 0.05 ≤ t ≤ 7.758
V = 31.5 for t > 7.758
31.5
20.0
7
FIGURE 14. Limits for overvoltage and undervoltage for 28 volts DC system.
28
MIL-STD-704F
29
FIGURE 15. Maximum distortion spectrum for 28 volts DC system.
-60.0
-50.0
-40.0
-30.0
-20.0
-10.0
0.0
10.0
10 100 1,000 10,000 100,000 1,000,000
Frequency, Hz
Distortion
Amplitude,
dB
from
1.0
VRMS
Frequency, Hz
10
1,000
5,000
50,000
500,000
Amplitude, dBV
-20.0
0.0
0.0
-20.0
-60.0
-
4
0
d
B
/
d
e
c
a
d
e
-20dB/decade
+10 dB/decade
-60.0
-50.0
-40.0
-30.0
-20.0
-10.0
0.0
10.0
10 100 1,000 10,000 100,000 1,000,000
Frequency, Hz
Distortion
Amplitude,
dB
from
1.0
VRMS
Frequency, Hz
10
1,000
5,000
50,000
500,000
Amplitude, dBV
-20.0
0.0
0.0
-20.0
-60.0
-
4
0
d
B
/
d
e
c
a
d
e
-20dB/decade
+10 dB/decade
29
MIL-STD-704F
MIL-STD-704F
30
FIGURE 16. Envelope of normal voltage transient for 270 volts DC system.
150
160
170
180
190
200
210
220
230
240
250
260
270
280
290
300
310
320
330
340
350
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
Time from Onset of Transient, Seconds
Volts,
DC
Note:
1. Steady state limits do not include the
disturbances allowed in Table IV.
280
250
330 V, 0.020 sec
280 V, 0.040 sec
250 V, 0.040 sec
200 V, 0.010 sec
31
FIGURE 17. Limits for DC overvoltage and undervoltage for 270 volts DC system.
31
MIL-STD-704F
0
50
100
150
200
250
300
350
400
450
0.01 0.1 1 10 100
Time from Onset of Overvoltage or Undervoltage, Seconds
Volts,
DC
V = 350 for t < 0.05
V = 289.6 + 3.02/t for 0.05 ≤ t ≤ 7.55
V = 290.0 for 7.55 < t
290
240
7
32
FIGURE 18. Maximum distortion spectrum for 270 volts DC system.
-50.0
-40.0
-30.0
-20.0
-10.0
0.0
10.0
20.0
10 100 1,000 10,000 100,000 1,000,000
Frequency, HZ
Distortion
Amplitude,
dB
from
1.0
V
RMS
+10 dB/decade
-20dB/decade
-
4
0
d
B
/
d
e
c
a
d
e
Frequency, HZ
10
1,000
5,000
50,000
500,000
Amplitude, dBV
-10.0
10.0
10.0
-10.0
-50.0
-50.0
-40.0
-30.0
-20.0
-10.0
0.0
10.0
20.0
10 100 1,000 10,000 100,000 1,000,000
Frequency, HZ
Distortion
Amplitude,
dB
from
1.0
V
RMS
+10 dB/decade
-20dB/decade
-
4
0
d
B
/
d
e
c
a
d
e
Frequency, HZ
10
1,000
5,000
50,000
500,000
Amplitude, dBV
-10.0
10.0
10.0
-10.0
-50.0
32
MIL-STD-704F
MIL-STD-704F
33
CONCLUDING MATERIAL
Custodians: Preparing Activity:
Army – AV Navy - AS
Navy – AS (Project No. SESS – 0046)
Air Force - 11
Review Activities:
Army – CR, MI, TE
Navy - EC, MC, SH, YD
NOTE: The activities listed above were interested in this document as of the date of this
document. Since organizations and responsibilities can change, you should verify the currency of
the information above using the ASSIST Online database at http://www.dodssp.daps.mil/.

More Related Content

Similar to MIL-STD-704F.pdf

Jcb vibromax w1500 trench roller service repair manual
Jcb vibromax w1500 trench roller service repair manualJcb vibromax w1500 trench roller service repair manual
Jcb vibromax w1500 trench roller service repair manualfujsekfkksemm
 
350209_NGU-2000 BB (799020).pdf
350209_NGU-2000 BB (799020).pdf350209_NGU-2000 BB (799020).pdf
350209_NGU-2000 BB (799020).pdfGerson37561
 
Asme b30 2-2011 ok
Asme b30 2-2011 okAsme b30 2-2011 ok
Asme b30 2-2011 okSIGPROMAP
 
US Army Cyber Warfare Field Manual FM 3-38 CEMS
US Army Cyber Warfare Field Manual  FM 3-38  CEMSUS Army Cyber Warfare Field Manual  FM 3-38  CEMS
US Army Cyber Warfare Field Manual FM 3-38 CEMSDavid Sweigert
 
NX Air also Any other MV Training Index
NX Air also Any other MV Training IndexNX Air also Any other MV Training Index
NX Air also Any other MV Training IndexNiels Inderbiethen
 
Guia de instalacao at 8000 s
Guia de instalacao at 8000 sGuia de instalacao at 8000 s
Guia de instalacao at 8000 sNetPlus
 
INTERCONNECTION GRID CODE FOR THE PAN ARAB ELECTRICITY MARKET
INTERCONNECTION GRID CODE FOR THE PAN ARAB ELECTRICITY MARKETINTERCONNECTION GRID CODE FOR THE PAN ARAB ELECTRICITY MARKET
INTERCONNECTION GRID CODE FOR THE PAN ARAB ELECTRICITY MARKETPower System Operation
 
Power Supply Equipment Market for Water Electrolysis.pdf
Power Supply Equipment Market for Water Electrolysis.pdfPower Supply Equipment Market for Water Electrolysis.pdf
Power Supply Equipment Market for Water Electrolysis.pdfMohit BISResearch
 
Search and Rescue Challenge Mission, rules and .docx
Search and Rescue Challenge  Mission, rules and .docxSearch and Rescue Challenge  Mission, rules and .docx
Search and Rescue Challenge Mission, rules and .docxbagotjesusa
 
Catalog hitachi 50 hitachi-tr-series_dienhathe.org
Catalog hitachi 50 hitachi-tr-series_dienhathe.orgCatalog hitachi 50 hitachi-tr-series_dienhathe.org
Catalog hitachi 50 hitachi-tr-series_dienhathe.orgDien Ha The
 
Nasa std-4003
Nasa std-4003Nasa std-4003
Nasa std-4003qingx.cui
 
LED Driver "BCR420U / BCR421U" | Infineon Technologies
LED Driver "BCR420U / BCR421U" | Infineon TechnologiesLED Driver "BCR420U / BCR421U" | Infineon Technologies
LED Driver "BCR420U / BCR421U" | Infineon TechnologiesInfineon Technologies AG
 
Motorola solutions ap 6521 access point installation guide - wi ng 5.5 versio...
Motorola solutions ap 6521 access point installation guide - wi ng 5.5 versio...Motorola solutions ap 6521 access point installation guide - wi ng 5.5 versio...
Motorola solutions ap 6521 access point installation guide - wi ng 5.5 versio...Advantec Distribution
 

Similar to MIL-STD-704F.pdf (20)

Jcb vibromax w1500 trench roller service repair manual
Jcb vibromax w1500 trench roller service repair manualJcb vibromax w1500 trench roller service repair manual
Jcb vibromax w1500 trench roller service repair manual
 
350209_NGU-2000 BB (799020).pdf
350209_NGU-2000 BB (799020).pdf350209_NGU-2000 BB (799020).pdf
350209_NGU-2000 BB (799020).pdf
 
Asme b30 2-2011 ok
Asme b30 2-2011 okAsme b30 2-2011 ok
Asme b30 2-2011 ok
 
US Army Cyber Warfare Field Manual FM 3-38 CEMS
US Army Cyber Warfare Field Manual  FM 3-38  CEMSUS Army Cyber Warfare Field Manual  FM 3-38  CEMS
US Army Cyber Warfare Field Manual FM 3-38 CEMS
 
Aermap userguide under-revision
Aermap userguide under-revisionAermap userguide under-revision
Aermap userguide under-revision
 
NX Air also Any other MV Training Index
NX Air also Any other MV Training IndexNX Air also Any other MV Training Index
NX Air also Any other MV Training Index
 
Guia de instalacao at 8000 s
Guia de instalacao at 8000 sGuia de instalacao at 8000 s
Guia de instalacao at 8000 s
 
INTERCONNECTION GRID CODE FOR THE PAN ARAB ELECTRICITY MARKET
INTERCONNECTION GRID CODE FOR THE PAN ARAB ELECTRICITY MARKETINTERCONNECTION GRID CODE FOR THE PAN ARAB ELECTRICITY MARKET
INTERCONNECTION GRID CODE FOR THE PAN ARAB ELECTRICITY MARKET
 
717plus (1)
717plus (1)717plus (1)
717plus (1)
 
Power Supply Equipment Market for Water Electrolysis.pdf
Power Supply Equipment Market for Water Electrolysis.pdfPower Supply Equipment Market for Water Electrolysis.pdf
Power Supply Equipment Market for Water Electrolysis.pdf
 
Service Manual.pdf
Service Manual.pdfService Manual.pdf
Service Manual.pdf
 
Search and Rescue Challenge Mission, rules and .docx
Search and Rescue Challenge  Mission, rules and .docxSearch and Rescue Challenge  Mission, rules and .docx
Search and Rescue Challenge Mission, rules and .docx
 
Catalog hitachi 50 hitachi-tr-series_dienhathe.org
Catalog hitachi 50 hitachi-tr-series_dienhathe.orgCatalog hitachi 50 hitachi-tr-series_dienhathe.org
Catalog hitachi 50 hitachi-tr-series_dienhathe.org
 
Nasa std-4003
Nasa std-4003Nasa std-4003
Nasa std-4003
 
Arm7
Arm7Arm7
Arm7
 
Oxymat 61 o2 analyzer
Oxymat 61  o2 analyzerOxymat 61  o2 analyzer
Oxymat 61 o2 analyzer
 
LED Driver "BCR420U / BCR421U" | Infineon Technologies
LED Driver "BCR420U / BCR421U" | Infineon TechnologiesLED Driver "BCR420U / BCR421U" | Infineon Technologies
LED Driver "BCR420U / BCR421U" | Infineon Technologies
 
Manual de PLC Micrologix 1200
Manual de PLC Micrologix 1200Manual de PLC Micrologix 1200
Manual de PLC Micrologix 1200
 
Nes 362
Nes 362Nes 362
Nes 362
 
Motorola solutions ap 6521 access point installation guide - wi ng 5.5 versio...
Motorola solutions ap 6521 access point installation guide - wi ng 5.5 versio...Motorola solutions ap 6521 access point installation guide - wi ng 5.5 versio...
Motorola solutions ap 6521 access point installation guide - wi ng 5.5 versio...
 

Recently uploaded

engineering chemistry power point presentation
engineering chemistry  power point presentationengineering chemistry  power point presentation
engineering chemistry power point presentationsj9399037128
 
Involute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdf
Involute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdfInvolute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdf
Involute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdfJNTUA
 
The Entity-Relationship Model(ER Diagram).pptx
The Entity-Relationship Model(ER Diagram).pptxThe Entity-Relationship Model(ER Diagram).pptx
The Entity-Relationship Model(ER Diagram).pptxMANASINANDKISHORDEOR
 
History of Indian Railways - the story of Growth & Modernization
History of Indian Railways - the story of Growth & ModernizationHistory of Indian Railways - the story of Growth & Modernization
History of Indian Railways - the story of Growth & ModernizationEmaan Sharma
 
Circuit Breakers for Engineering Students
Circuit Breakers for Engineering StudentsCircuit Breakers for Engineering Students
Circuit Breakers for Engineering Studentskannan348865
 
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...drjose256
 
Instruct Nirmaana 24-Smart and Lean Construction Through Technology.pdf
Instruct Nirmaana 24-Smart and Lean Construction Through Technology.pdfInstruct Nirmaana 24-Smart and Lean Construction Through Technology.pdf
Instruct Nirmaana 24-Smart and Lean Construction Through Technology.pdfEr.Sonali Nasikkar
 
Augmented Reality (AR) with Augin Software.pptx
Augmented Reality (AR) with Augin Software.pptxAugmented Reality (AR) with Augin Software.pptx
Augmented Reality (AR) with Augin Software.pptxMustafa Ahmed
 
Final DBMS Manual (2).pdf final lab manual
Final DBMS Manual (2).pdf final lab manualFinal DBMS Manual (2).pdf final lab manual
Final DBMS Manual (2).pdf final lab manualBalamuruganV28
 
Basics of Relay for Engineering Students
Basics of Relay for Engineering StudentsBasics of Relay for Engineering Students
Basics of Relay for Engineering Studentskannan348865
 
Raashid final report on Embedded Systems
Raashid final report on Embedded SystemsRaashid final report on Embedded Systems
Raashid final report on Embedded SystemsRaashidFaiyazSheikh
 
Maher Othman Interior Design Portfolio..
Maher Othman Interior Design Portfolio..Maher Othman Interior Design Portfolio..
Maher Othman Interior Design Portfolio..MaherOthman7
 
UNIT 4 PTRP final Convergence in probability.pptx
UNIT 4 PTRP final Convergence in probability.pptxUNIT 4 PTRP final Convergence in probability.pptx
UNIT 4 PTRP final Convergence in probability.pptxkalpana413121
 
Filters for Electromagnetic Compatibility Applications
Filters for Electromagnetic Compatibility ApplicationsFilters for Electromagnetic Compatibility Applications
Filters for Electromagnetic Compatibility ApplicationsMathias Magdowski
 
Autodesk Construction Cloud (Autodesk Build).pptx
Autodesk Construction Cloud (Autodesk Build).pptxAutodesk Construction Cloud (Autodesk Build).pptx
Autodesk Construction Cloud (Autodesk Build).pptxMustafa Ahmed
 
Passive Air Cooling System and Solar Water Heater.ppt
Passive Air Cooling System and Solar Water Heater.pptPassive Air Cooling System and Solar Water Heater.ppt
Passive Air Cooling System and Solar Water Heater.pptamrabdallah9
 
Independent Solar-Powered Electric Vehicle Charging Station
Independent Solar-Powered Electric Vehicle Charging StationIndependent Solar-Powered Electric Vehicle Charging Station
Independent Solar-Powered Electric Vehicle Charging Stationsiddharthteach18
 
Interfacing Analog to Digital Data Converters ee3404.pdf
Interfacing Analog to Digital Data Converters ee3404.pdfInterfacing Analog to Digital Data Converters ee3404.pdf
Interfacing Analog to Digital Data Converters ee3404.pdfragupathi90
 
Seismic Hazard Assessment Software in Python by Prof. Dr. Costas Sachpazis
Seismic Hazard Assessment Software in Python by Prof. Dr. Costas SachpazisSeismic Hazard Assessment Software in Python by Prof. Dr. Costas Sachpazis
Seismic Hazard Assessment Software in Python by Prof. Dr. Costas SachpazisDr.Costas Sachpazis
 
Intro to Design (for Engineers) at Sydney Uni
Intro to Design (for Engineers) at Sydney UniIntro to Design (for Engineers) at Sydney Uni
Intro to Design (for Engineers) at Sydney UniR. Sosa
 

Recently uploaded (20)

engineering chemistry power point presentation
engineering chemistry  power point presentationengineering chemistry  power point presentation
engineering chemistry power point presentation
 
Involute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdf
Involute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdfInvolute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdf
Involute of a circle,Square, pentagon,HexagonInvolute_Engineering Drawing.pdf
 
The Entity-Relationship Model(ER Diagram).pptx
The Entity-Relationship Model(ER Diagram).pptxThe Entity-Relationship Model(ER Diagram).pptx
The Entity-Relationship Model(ER Diagram).pptx
 
History of Indian Railways - the story of Growth & Modernization
History of Indian Railways - the story of Growth & ModernizationHistory of Indian Railways - the story of Growth & Modernization
History of Indian Railways - the story of Growth & Modernization
 
Circuit Breakers for Engineering Students
Circuit Breakers for Engineering StudentsCircuit Breakers for Engineering Students
Circuit Breakers for Engineering Students
 
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...
 
Instruct Nirmaana 24-Smart and Lean Construction Through Technology.pdf
Instruct Nirmaana 24-Smart and Lean Construction Through Technology.pdfInstruct Nirmaana 24-Smart and Lean Construction Through Technology.pdf
Instruct Nirmaana 24-Smart and Lean Construction Through Technology.pdf
 
Augmented Reality (AR) with Augin Software.pptx
Augmented Reality (AR) with Augin Software.pptxAugmented Reality (AR) with Augin Software.pptx
Augmented Reality (AR) with Augin Software.pptx
 
Final DBMS Manual (2).pdf final lab manual
Final DBMS Manual (2).pdf final lab manualFinal DBMS Manual (2).pdf final lab manual
Final DBMS Manual (2).pdf final lab manual
 
Basics of Relay for Engineering Students
Basics of Relay for Engineering StudentsBasics of Relay for Engineering Students
Basics of Relay for Engineering Students
 
Raashid final report on Embedded Systems
Raashid final report on Embedded SystemsRaashid final report on Embedded Systems
Raashid final report on Embedded Systems
 
Maher Othman Interior Design Portfolio..
Maher Othman Interior Design Portfolio..Maher Othman Interior Design Portfolio..
Maher Othman Interior Design Portfolio..
 
UNIT 4 PTRP final Convergence in probability.pptx
UNIT 4 PTRP final Convergence in probability.pptxUNIT 4 PTRP final Convergence in probability.pptx
UNIT 4 PTRP final Convergence in probability.pptx
 
Filters for Electromagnetic Compatibility Applications
Filters for Electromagnetic Compatibility ApplicationsFilters for Electromagnetic Compatibility Applications
Filters for Electromagnetic Compatibility Applications
 
Autodesk Construction Cloud (Autodesk Build).pptx
Autodesk Construction Cloud (Autodesk Build).pptxAutodesk Construction Cloud (Autodesk Build).pptx
Autodesk Construction Cloud (Autodesk Build).pptx
 
Passive Air Cooling System and Solar Water Heater.ppt
Passive Air Cooling System and Solar Water Heater.pptPassive Air Cooling System and Solar Water Heater.ppt
Passive Air Cooling System and Solar Water Heater.ppt
 
Independent Solar-Powered Electric Vehicle Charging Station
Independent Solar-Powered Electric Vehicle Charging StationIndependent Solar-Powered Electric Vehicle Charging Station
Independent Solar-Powered Electric Vehicle Charging Station
 
Interfacing Analog to Digital Data Converters ee3404.pdf
Interfacing Analog to Digital Data Converters ee3404.pdfInterfacing Analog to Digital Data Converters ee3404.pdf
Interfacing Analog to Digital Data Converters ee3404.pdf
 
Seismic Hazard Assessment Software in Python by Prof. Dr. Costas Sachpazis
Seismic Hazard Assessment Software in Python by Prof. Dr. Costas SachpazisSeismic Hazard Assessment Software in Python by Prof. Dr. Costas Sachpazis
Seismic Hazard Assessment Software in Python by Prof. Dr. Costas Sachpazis
 
Intro to Design (for Engineers) at Sydney Uni
Intro to Design (for Engineers) at Sydney UniIntro to Design (for Engineers) at Sydney Uni
Intro to Design (for Engineers) at Sydney Uni
 

MIL-STD-704F.pdf

  • 1. MIL-STD-704F 12 MARCH 2004 SUPERSEDING MIL-STD-704E 1 MAY 1991 DEPARTMENT OF DEFENSE INTERFACE STANDARD AIRCRAFT ELECTRIC POWER CHARACTERISTICS AMSC N/A AREA SESS NOT MEASUREMENT SENSITIVE
  • 2. MIL-STD-704F ii FOREWORD 1. This standard is approved for use by all Departments and Agencies of the Department of Defense. 2. The purpose of this interface standard is to ensure compatibility between the aircraft electric system, external power, and airborne utilization equipment. 3. Comments, suggestions, or questions on this document should be addressed to Commander, Naval Air Systems Command, Code 4.1.4, Highway 547, Lakehurst, NJ 08733-5100 or email to thomas.omara@navy.mil. Since contact information can change, you may want to verify the currency of this address information using the ASSIST Online database at www.dodssp.daps.mil.
  • 3. MIL-STD-704F iii CONTENTS PARAGRAPH PAGE FORWARD ........................................................................................................................ii 1. SCOPE ......................................................................................................................... 1 1.1 Scope ...................................................................................................................... 1 2. APPLICABLE DOCUMENT ............................................................................................ 1 2.1 General ................................................................................................................... 1 2.2 Government documents ......................................................................................... 1 2.2.1 Specifications, standards and handbooks ............................................................... 1 2.3 Order of precedence ............................................................................................... 1 3. DEFINITIONS ................................................................................................................... 1 3.1 Acronyms used in this standard ............................................................................. 1 3.2 Abnormal operation ............................................................................................... 2 3.3 AC voltage ............................................................................................................. 2 3.4 Aircraft electric power systems ............................................................................. 2 3.5 Crest factor ............................................................................................................. 2 3.6 Current ................................................................................................................... 2 3.7 Current modulation ................................................................................................ 2 3.8 DC voltage ............................................................................................................. 2 3.9 Distortion ............................................................................................................... 3 3.10 Distortion factor ..................................................................................................... 3 3.11 Distortion spectrum ................................................................................................ 3 3.12 Electric starting operation ...................................................................................... 3 3.13 Emergency operation ............................................................................................. 3 3.14 External power source ............................................................................................ 3 3.15 Frequency ............................................................................................................... 3 3.16 Frequency modulation ........................................................................................... 3 3.17 Load unbalance ...................................................................................................... 3 3.18 Normal operation ................................................................................................... 3 3.19 Overfrequency and underfrequency ....................................................................... 4 3.20 Overvoltage and undervoltage ............................................................................... 4 3.21 Point of regulation .................................................................................................. 4 3.22 Power factor ........................................................................................................... 4 3.23 Pulsed load ............................................................................................................. 4 3.24 Rate of change of frequency .................................................................................. 4 3.25 Ripple ..................................................................................................................... 4 3.26 Steady state ............................................................................................................ 4 3.27 Transfer operation .................................................................................................. 4 3.28 Transient ................................................................................................................ 5 3.29 Utilization equipment ............................................................................................. 5 3.30 Utilization equipment terminals ............................................................................. 5 3.31 Voltage modulation ................................................................................................ 5 3.32 Voltage phase difference ........................................................................................ 5 3.33 Voltage unbalance .................................................................................................. 5
  • 4. MIL-STD-704F iv CONTENTS PARAGRAPH PAGE 4. GENERAL REQUIREMENTS ......................................................................................... 5 4.1 Aircraft electric power system requirements ......................................................... 5 4.1.1 Aircraft electric power system performance .......................................................... 5 4.1.2 Electric power source characteristics ..................................................................... 5 4.1.3 Protective devices .................................................................................................. 6 4.2 Aircraft utilization equipment requirements .......................................................... 6 4.2.1 Power compatibility ............................................................................................... 6 4.2.2 Operation ................................................................................................................ 6 4.2.2.1 Normal operation ................................................................................................... 6 4.2.2.2 Abnormal operation ............................................................................................... 6 4.2.2.3 Transfer operation .................................................................................................. 6 4.2.2.4 Emergency operation ............................................................................................. 6 4.2.2.5 Starting operation ................................................................................................... 6 4.2.3 Power failure .......................................................................................................... 7 4.2.4 AC power utilization .............................................................................................. 7 4.3 External power source requirement ....................................................................... 7 4.4 Test requirements ................................................................................................... 7 5. DETAILED REQUIREMENTS ........................................................................................ 7 5.1 Transfer operation characteristics .......................................................................... 7 5.2 AC power characteristics ....................................................................................... 7 5.2.1 Type system ........................................................................................................... 7 5.2.2 Phase sequence ....................................................................................................... 8 5.2.3 Normal operation ................................................................................................... 8 5.2.4 Abnormal operation ............................................................................................... 8 5.2.5 Emergency operation ............................................................................................. 8 5.3 DC power characteristics ....................................................................................... 8 5.3.1 Type system ........................................................................................................... 8 5.3.2 28 volts DC system ................................................................................................ 8 5.3.2.1 Normal operation ................................................................................................... 8 5.3.2.2 Abnormal operation ............................................................................................... 8 5.3.2.3 Emergency operation ............................................................................................. 9 5.3.2.4 Electric starting ...................................................................................................... 9 5.3.3 270 volts DC system .............................................................................................. 9 5.3.3.1 Normal operation ................................................................................................... 9 5.3.3.2 Abnormal operation ............................................................................................... 9 5.3.3.3 Emergency operation ............................................................................................. 9 5.4 Load characteristics ............................................................................................... 9 5.4.1 Grounding .............................................................................................................. 9 5.4.2 Load unbalance ...................................................................................................... 9 5.4.3 Power factor ........................................................................................................... 9 5.4.4 Polarity or phase reversal ....................................................................................... 9 5.4.5 Multiple input terminals ......................................................................................... 9
  • 5. MIL-STD-704F v CONTENTS PARAGRAPH PAGE 6. NOTES ....................................................................................................................... 10 6.1 Intended use ......................................................................................................... 10 6.2 Considerations ...................................................................................................... 10 6.3 Supersession data ................................................................................................. 10 6.4 International standardization implementation ...................................................... 10 6.5 Changes from previous issue ............................................................................... 10 6.6 Application of this standard in utilization equipment specifications ................... 10 6.7 Pulsed load design issues ..................................................................................... 11 6.8 Non-linear loads and effects ................................................................................ 11 6.9 Precedence ........................................................................................................... 11 6.10 Guidance and lessons learned .............................................................................. 11 6.10.1 Compatibility and testing ..................................................................................... 11 6.10.2 Compatibility and installation .............................................................................. 12 6.11 Subject term (keyword) listing ............................................................................. 12 TABLES I AC normal operation characteristics - 400 Hertz (see 5.2.3) ............................... 13 II AC normal operation characteristics - variable frequency (see 5.2.3) ................. 13 III AC normal operation characteristics - 60 Hertz (see 5.2.3) ................................. 14 IV DC normal operation characteristics (see 5.3.2.1, 5.3.4.1) .................................. 14 FIGURES 1 Load unbalance limits for three phase utilization equipment .............................. 15 2 Phasor diagram showing required phase sequence relationship .......................... 16 3 Envelope of normal 400 Hz and variable frequency AC voltage transient ......... 17 4 Limits for 400 Hz and variable frequency AC overvoltage and undervoltage .... 18 5 Envelope of normal 400 Hz AC frequency transient ........................................... 19 6 Limits for 400 Hz AC overfrequency or underfrequency .................................... 20 7 Maximum distortion spectrum of 400 Hz and variable frequency AC voltage ... 21 8 Envelope of normal 60 Hz voltage transient ........................................................ 22 9 Limits for 60 Hz AC overvoltage and undervoltage ............................................ 23 10 Envelope of normal 60 Hz AC frequency transient ............................................. 24 11 Limits for 60 Hz AC overfrequency and underfrequency ................................... 25 12 Maximum distortion spectrum of 60 Hz AC voltage ........................................... 26 13 Envelope of normal voltage transients for 28 volts DC system ........................... 27 14 Limits for overvoltage and undervoltage for 28 volts DC system ....................... 28 15 Maximum distortion spectrum for 28 volts DC system ....................................... 29 16 Envelope of normal voltage transient for 270 volts DC system .......................... 30 17 Limits for DC overvoltage and undervoltage for 270 volts DC system .............. 31 18 Maximum distortion spectrum for 270 volts DC system. .................................... 32 CONCLUDING MATERIAL ......................................................................................... 33
  • 6. MIL-STD-704F 1 1. SCOPE 1.1 Scope. This standard establishes the requirements and characteristics of aircraft electric power provided at the input terminals of electric utilization equipment. MIL-HDBK- 704-1 through-8 defines test methods and procedures for determining airborne utilization equipment compliance with the electric power characteristics requirements defined herein. Electromagnetic interference and voltage spikes are not covered by this standard. 2. APPLICABLE DOCUMENTS 2.1 General. The document listed in this section is specified in sections 3, 4, and 5 of this standard. This section does not include documents cited in other sections of this standard or recommended for additional information or as examples. While every effort has been made to ensure the completeness of this list, document users are cautioned that they must meet all specified requirements documents cited in sections 3, 4, and 5 of this standard, whether or not they are listed. 2.2 Government documents. 2.2.1 Specifications, standards and handbooks. The following specifications, standards, and handbooks form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those cited in the solicitation or contract. INTERNATIONAL STANDARDIZATION AGREEMENTS STANAG 3456 Aircraft Electrical System Characteristics (Copies of this document are available online at http://assist.daps.dla.mil/quicksearch/ or www.dodssp.daps.mil or from the Standardization Document Order Desk, 700 Robbins Avenue, Building 4D, Philadelphia, PA 19111-5094.) 2.3 Order of precedence. In the event of a conflict between the text of this document and the references cited herein, the text of this standard takes precedence. Nothing in this document, however, supersedes applicable laws and regulations unless a specific exemption has been obtained. 3. DEFINITIONS 3.1 Acronyms used in this standard. The acronyms used in this standard are defined as follows: a. AC − Alternating Current b. COTS − Commercial Off-The-Shelf c. DC − Direct Current d. DoD − Department of Defense e. kVA − kilovolt-ampere
  • 7. MIL-STD-704F 2 f. NATO − North Atlantic Treaty Organization g. POR − Point of Regulation h. RMS − Root Mean Square i. STANAG − Standardization Agreement j. VA − Volt-ampere 3.2 Abnormal operation. Abnormal operation occurs when a malfunction or failure in the electric system has taken place and the protective devices of the system are operating to remove the malfunction or failure from the remainder of the system before the limits for abnormal operation are exceeded. The power source may operate in a degraded mode on a continuous basis where the power characteristics supplied to the utilization equipment exceed normal operation limits but remain within the limits for abnormal operation. 3.3 AC voltage. AC voltage is the root mean square (RMS) phase to neutral value for each half cycle. a. Steady state AC voltage is the time average of the RMS voltage over a period not to exceed one second. b. Peak AC voltage is the maximum absolute value of the instantaneous voltage. c. The direct current (DC) component of the AC voltage is the average value of the voltage. 3.4 Aircraft electric power systems. An aircraft electric power system consists of a main power source, emergency power source, power conversion equipment, control and protection devices, and an interconnection network (wires, cables, connectors, etc.). The main power is derived from aircraft generators driven by the aircraft propulsion engines. Emergency power is derived from batteries, engine bleed air, independent auxiliary power units, ram air driven generators, or hydraulically driven generators. 3.5 Crest factor. The crest factor is the absolute value of the ratio of the peak to the RMS value for each half cycle of the voltage waveform. 3.6 Current. Alternating Current (AC) current is the RMS value for one half cycle measured between consecutive zero crossings of the fundamental frequency component. Direct Current (DC) current is the instantaneous value. 3.7 Current modulation. Current modulation is the difference between maximum current and minimum current. Percent current modulation is the ratio of the current modulation to the average (mean for DC, RMS of the fundamental for AC) current multiplied by 100 over a one second period. 3.8 DC voltage. Steady state DC voltage is the time average of the instantaneous DC voltage over a period not to exceed one second.
  • 8. MIL-STD-704F 3 3.9 Distortion. AC distortion is the RMS value of the AC waveform exclusive of the fundamental. In a DC system, DC distortion is the RMS value of the alternating voltage component on the DC voltage. 3.10 Distortion factor. The AC distortion factor is the ratio of the AC distortion to the RMS value of the fundamental component. The DC distortion factor is the ratio of the DC distortion to the DC steady state voltage. 3.11 Distortion spectrum. The distortion spectrum quantifies AC or DC distortion in terms of the amplitude of each frequency component. The distortion spectrum includes the components resulting from amplitude and frequency modulation as well as harmonic and non- harmonic components of the waveform. 3.12 Electric starting operation. Electric starting operation is a specialized case of normal electric system operating conditions where the normal voltage limits may be exceeded due to the high electric demand. The voltage limits for normal operation may be exceeded during the following starting conditions: a. An electric start of the propulsion engine. (Battery power, aircraft DC power or external power applied on the aircraft bus.) b. A battery start of an auxiliary power unit. 3.13 Emergency operation. Emergency operation occurs following the loss of the main generating equipment when a limited electric source, independent of the main system, is used to power a reduced complement of distribution and utilization equipment selected to maintain flight and personnel safety. 3.14 External power source. The external power source refers to the ground or shipboard power source used to provide power to the aircraft's electrical distribution system. 3.15 Frequency. Frequency is the reciprocal of the period of the AC voltage waveform. The unit of frequency is Hertz (Hz). Steady state frequency is the time average of the frequency over a period not to exceed one second. 3.16 Frequency modulation. Frequency modulation is the difference between the maximum and minimum frequency values that occur in a one-minute period during steady state operating conditions. Frequency modulation is a measure of the stability of the power system's frequency regulation. 3.17 Load unbalance. Load unbalance for a three-phase load is the difference between the highest and lowest phase loads. 3.18 Normal operation. Normal operation occurs when the system is operating as intended in the absence of any fault or malfunction that degrades performance beyond established requirements. It includes all system functions required for aircraft operation except
  • 9. MIL-STD-704F 4 during the electric starting of propulsion engines and the battery start of an auxiliary power unit. Normal operation includes switching of utilization equipment, prime mover speed changes, synchronizing and paralleling of power sources, and operation from external power sources. Transfer operation, as defined herein, is a normal function. It is treated separately in this standard because of the power interruption that it may produce. Conducted switching spikes, which are excursions of the instantaneous voltage not exceeding 50 microseconds, are normal operation characteristics. 3.19 Overfrequency and underfrequency. Overfrequency and underfrequency are those frequencies that exceed the limits for normal operation and are limited by the action of protective devices. 3.20 Overvoltage and undervoltage. Overvoltage and undervoltage are those voltages that exceed the limits for normal operation and are limited by the action of protective devices. 3.21 Point of regulation. The POR is that point at which a power generation source senses and regulates the system voltage. The POR should be at the input terminals of the line contactor connecting the power source to the load bus. 3.22 Power factor. The ratio of real power (measured in watts) to apparent power (measured in volt-amperes). 3.23 Pulsed load. Pulsed loads are loads whose power requirement varies under steady state conditions because of underlying physical phenomena or the inherent operating mode of equipment. 3.24 Rate of change of frequency. The rate of change of frequency is defined as the ratio of the absolute difference in frequency over a designated period of time to the designated period of time. The unit of rate of change of frequency is designated Hertz per second (Hz/s). 3.25 Ripple. Ripple is the variation of voltage about the steady state DC voltage during steady state electric system operation. Sources of ripple may include, but are not limited to, voltage regulation instability of the DC power source, commutation/rectification within the DC power source, and load variations within utilization equipment. Ripple amplitude is the maximum absolute value of the difference between the steady state and the instantaneous DC voltage. 3.26 Steady state. Steady state is that condition in which the characteristics remain within the limits for normal operation steady state characteristics throughout an arbitrarily long period of time. Steady state conditions may include lesser transients. 3.27 Transfer operation. Transfer operation occurs when the electric system transfers between power sources, including transfers from or to external power sources.
  • 10. MIL-STD-704F 5 3.28 Transient. A transient is a changing value of a characteristic that usually occurs as a result of normal disturbances such as electric load change and engine speed change. A transient may also occur as a result of a momentary power interruption or an abnormal disturbance such as fault clearing. a. Transients that do not exceed the steady state limits are defined as lesser transients. b. Transients that exceed the steady state limits but remain within the specified normal transients limits are defined as normal transients. c. Transients that exceed normal transients limits as a result of an abnormal disturbance and eventually return to steady state limits are defined as abnormal transients. 3.29 Utilization equipment. Utilization equipment is that equipment which receives power from the electric power system. 3.30 Utilization equipment terminals. Utilization equipment terminals provide the interface with the electric power system. Power interconnections, within the utilization equipment or equipment system, are excluded. 3.31 Voltage modulation. Voltage modulation is the variation of AC voltage during steady state AC electric system operation. Sources of voltage modulation may include, but are not limited to, voltage regulation stability of the AC power source, generator speed variations, and load variations within utilization equipment. Voltage modulation amplitude is the difference between the maximum and minimum AC voltage values that occur in a one second period during steady state operating conditions. 3.32 Voltage phase difference. The voltage phase difference is the difference in electrical degrees between the fundamental components of any two-phase voltages taken at consecutive zero crossings traced in the negative to positive direction. 3.33 Voltage unbalance. Voltage unbalance is defined as the maximum difference between RMS phase voltage amplitudes at the utilization equipment terminals. 4. GENERAL REQUIREMENTS 4.1 Aircraft electric power system requirements. 4.1.1 Aircraft electric power system performance. The aircraft electric power system shall provide electric power having the characteristics specified in this standard at the utilization equipment terminals during all operations of the power system. 4.1.2 Electrical power source characteristics. The characteristics of the electrical power measured at the output terminals of an unregulated power source or the POR of a regulated power source shall be within the limits specified in the applicable detail specification of the
  • 11. MIL-STD-704F 6 power source. It is the responsibility of the airframe manufacturer or modifier to provide the distribution and protection network to the terminals of the utilization equipment while maintaining the power characteristics specified in this standard. 4.1.3 Protective devices. Protective devices shall function independently of control and regulation equipment. 4.2 Aircraft utilization equipment requirements. 4.2.1 Power compatibility. Utilization equipment shall be compatible with the power characteristics specified herein. Utilization equipment shall not require electric power of better quality than specified herein. Utilization equipment shall be compatible with the applicable aircraft specification requirements for control of electromagnetic interference and voltage spikes induced by lightning, electromagnetic pulses, and power switching. Electromagnetic interference and voltage spikes are not covered by this standard. 4.2.2 Operation. When supplied electric power having characteristics specified herein, aircraft utilization equipment shall provide the level of performance required by its detail specification for each operating condition. Operation of utilization equipment shall not cause the power characteristics at its terminals to exceed the limits specified herein. Utilization equipment operation under any electric system operating condition shall not have an adverse effect on or cause malfunction of the electric system. 4.2.2.1 Normal operation. Utilization equipment shall provide the level of performance specified in its detail specification. 4.2.2.2 Abnormal operation. Utilization equipment shall be permitted a degradation or loss of function unless otherwise specified in its detail specification. Utilization equipment shall not suffer damage or cause an unsafe condition. Utilization equipment shall automatically resume full performance when normal operation of the electrical system is restored. 4.2.2.3 Transfer operation. Utilization equipment may not be required to operate under the transfer condition unless a level of performance is specified by its detail specification. Utilization equipment shall automatically resume specified performance when normal operating characteristics are resumed. 4.2.2.4 Emergency operation. Utilization equipment shall provide the level of performance specified in its detail specification when such performance is essential for flight or safety. 4.2.2.5 Starting operation. Utilization equipment shall provide the level of performance specified in its detail specification when performance is essential during the starting operation.
  • 12. MIL-STD-704F 7 4.2.3 Power failure. The loss of power (AC or DC) or the loss of one or more phases of AC power to any utilization equipment terminal shall not result in an unsafe condition or damage to utilization equipment. 4.2.4 AC power utilization. Utilization equipment that requires more than 0.5 kVA of AC power shall be configured to utilize three-phase steady state balanced power. Load unbalance of individual utilization equipment shall be within the limits of figure 1. The load unbalance of utilization equipment whose total load is greater than 30 kVA shall be no greater than 3.33 percent of its total three-phase load. Single-phase AC power shall be used only on a line-to-neutral basis. AC power shall not be half-wave rectified. 4.3 External power source requirement. External electric power sources shall supply power having the characteristics specified in this standard at the power input terminals of the aircraft electric utilization equipment. In order to allow for steady state voltage drop between the aircraft external power receptacle and the aircraft utilization equipment terminals, the voltage at the external power receptacle shall be as follows: a. AC system 113 to 118 volts (AC voltage drop of 0 to 5 volts) b. 28 VDC system 24 to 29 volts (DC voltage drop of 0 to 2 volts) c. 270 VDC system 260 to 280 volts (DC voltage drop of 0 to 10 volts) 4.4 Test requirements. Equipment testing is required to demonstrate utilization equipment compatibility with the electric power characteristics of this standard. Utilization equipment test requirements shall be in accordance with the equipment detail specification. The applicable test methods of MIL-HDBK-704 shall be used to determine that the utilization equipment complies with this standard. Aircraft shall be tested to demonstrate that the aircraft electric system power characteristics are within the limits of this standard throughout all operating conditions of the aircraft and its utilization equipment. Aircraft test requirements shall be in accordance with the aircraft detail specification. 5. DETAILED REQUIREMENTS 5.1 Transfer operation characteristics. Under conditions of bus or power source transfers, voltage and frequency shall not vary between zero and normal operating limits for longer than 50 milliseconds. A normal transient may occur upon completion of a transfer. 5.2 AC power characteristics. 5.2.1 Type system. AC systems shall provide electrical power using single-phase or three-phase wire-connected grounded neutral systems. The voltage waveform shall be a sine wave with a nominal voltage of 115/200 volts and a nominal frequency of 400 Hz. Variable frequency and double-voltage systems may be used as alternative electrical power systems. Variable frequency systems have frequencies varying from 360 to 800 Hz with a nominal voltage of 115/200 volts. Double-voltage systems have nominal voltages of 230/400 volts and a nominal frequency of 400 Hz. A third alternative for secondary electric power systems is single-phase 60
  • 13. MIL-STD-704F 8 Hz systems. These systems have a nominal voltage of 115 volts with a nominal frequency of 60 Hz and are used in support of COTS equipment only. All power types may not be available on all aircraft platforms. The selection of the input power type for utilization equipment shall take into consideration the aircraft power types available on the intended platform and the capacity of the electrical system of that aircraft platform. 5.2.2 Phase sequence. The phase sequence shall be A-B-C and aircraft wiring and equipment terminals shall be marked accordingly. Generator terminals shall be marked T1-T2- T3 corresponding to A-B-C, respectively. The phase sequence shall be counterclockwise (positive) as shown on figure 2. 5.2.3 Normal operation. Normal operation characteristics shall be in accordance with figures 3, 5, and 7, table I for 400 Hz systems and table II for variable frequency systems; and figures 8, 10 and 12, and table III for 60 Hz systems. For variable frequency systems the rate of change of frequency from onset of a normal frequency transient measured for over a period of time of greater than 25 milliseconds shall not exceed 250 Hz per second. 5.2.4 Abnormal operation. The overvoltage and undervoltage values shall be within the limits of figure 4 for 400 Hz and variable frequency systems and figure 9 for 60 Hz systems. The overfrequency and underfrequency values shall be within the limits of figure 6 for 400 Hz systems, and figure 11 for 60 Hz systems. The overfrequency and underfrequency for variable frequency systems shall not exceed the 360 - 800 Hz steady state values. For variable frequency systems the rate of change of frequency from onset of an abnormal frequency transient measured for over a period of time of greater than 25 milliseconds shall not exceed 500 Hz per second. 5.2.5 Emergency operation. All power characteristics in emergency operation shall be the same as normal operation. 5.3 DC power characteristics. 5.3.1 Type system. DC systems shall provide power using direct current, two-wire or negative ground return system having a nominal voltage of 28 Volts or 270 Volts. These systems shall conform to figures 13, 14, 15, 16, 17, 18 and table IV. 5.3.2 28 volts DC system. 5.3.2.1 Normal operation. Normal operation characteristics shall be in accordance with figures 13, 15 and table IV. 5.3.2.2 Abnormal operation. Overvoltage and undervoltage values shall be within the limits of figure 14.
  • 14. MIL-STD-704F 9 5.3.2.3 Emergency operation. The DC steady state voltage in emergency operation shall be between 16 and 29 volts. 5.3.2.4 Electric starting. The DC voltage in electric starting operation shall be between 12 and 29 volts. Electric starting of an auxiliary power unit (other than battery starts) is a normal operating function and is not included under this condition. 5.3.3 270 volts DC system. 5.3.3.1 Normal operation. Normal operation characteristics shall be in accordance with figures 16 and 18 and table IV. 5.3.3.2 Abnormal operation. Overvoltage and undervoltage values shall be within the limits of figure 17. 5.3.3.3 Emergency operation. All power characteristics in emergency operation shall be the same as normal operation. 5.4 Load characteristics. 5.4.1 Grounding. All electrical power input terminals, including AC neutral and DC negative terminals, shall be electrically isolated from case ground. Equipment chassis shall not be used for power returns. 5.4.2 Load unbalance. Load unbalance of three-phase AC equipment shall be in accordance with figure 1. Load unbalance of equipment exceeding 30 kVA shall not exceed 3.33 percent of the total three-phase load. 5.4.3 Power factor. Power factor of AC equipment greater than 500 VA shall be between 0.85 lagging and unity when operating at 50 percent or more of its rated load current in steady state condition. AC equipment shall not have leading power factor when operating at more than 100 VA. 5.4.4 Polarity or phase reversal. Three-phase AC equipment shall not be damaged by reversal of input phase sequence. Single-phase AC equipment shall not be damaged by reversal of line and neutral connections. DC equipment shall not be damaged by reversal of positive and negative connections. Employing a positive physical means to prevent phase or polarity reversal shall also fulfill this requirement. 5.4.5 Multiple input terminals. Equipment having multiple input terminals for connection to more than one power source shall isolate the inputs from each other so that one power source cannot supply power to another. AC inputs shall not be paralleled. DC inputs shall be protected with blocking diodes if they are paralleled.
  • 15. MIL-STD-704F 10 6. NOTES (This section contains information of a general or explanatory nature that may be helpful, but is not mandatory.) 6.1 Intended use. The intent of this document is to define the electric power quality requirements for DoD aircraft, however it may also be used with commercial aircraft or other types of vehicles. Other industry documents such as SAE-AS1212 and ISO 1540 also define aircraft electric power quality requirements. These documents are generally not appropriate for use with military aircraft because they do not address all of the areas of concern with military aircraft electric power quality and often require wider limits compared to this document due to the differences in the types and sizes of aircraft covered. In addition, they do not always take into account legacy DoD aircraft electrical power systems or legacy DoD utilization equipment. The power characteristics requirements of this document also apply to commercial and non- developmental utilization equipment purchased in accordance with the policy described in the SD-2, “Buying Commercial & Nondevelopmental Items: A Handbook”. If such equipment does not fully comply with the power characteristics requirement of this document, the effect of the equipment noncompliance on the electrical power quality and on the equipment capability to perform its intended function in the aircraft should be evaluated. 6.2 Considerations. Each element of the aircraft electrical power system is qualified and purchased to its own specification requirements document. The requirements of this document are less severe than the output power requirements of the typical electrical power source, taking into account the degradation of electrical power quality that can occur between a power source and the input electrical power terminals of utilization equipment. The effects of the electrical power distribution, control, and protection system, and the interactions between electrical power sources and utilization equipment may cause the degradation of electrical power quality. 6.3 Supersession data. This edition of MIL-STD-704 supersedes all previous editions. Previous editions of MIL-STD-704, which are cited in contracts for legacy aircraft electrical systems remain in effect for procurement of utilization equipment. Therefore, copies of previous editions should be retained, as they are no longer stocked by the Government. 6.4 International standardization implementation. This standard implements STANAG 3456, “Aircraft Electrical System Characteristics”. When changes to, revision, or cancellation of this standard are proposed, the preparing activity must coordinate the action with the U.S. National Point of Contact for the international standardization agreement, as identified in the ASSIST database at www.dodssp.daps.mil. 6.5 Changes from previous issue. Marginal notations are not used in this revision to identify changes with respect to the previous issue due to the extent of the changes. 6.6 Application of this standard in utilization equipment specifications. Utilization equipment specifications should include a statement that "This equipment shall utilize electric power in accordance with MIL-STD-704 and shall be in accordance with the utilization
  • 16. MIL-STD-704F 11 equipment requirements of MIL-STD-704." The equipment specification should also specify the type of electric power to be utilized and the detailed performance required during normal, abnormal, emergency, starting, transfer and power failure operation of the electric system. The electric power characteristics specified herein are minimum requirements for utilization equipment. Therefore, specifications for utilization equipment that require greater operating margins should include specific electric power characteristic operating ranges that exceed those stated herein. Utilization equipment specifications should never specify operating ranges that are narrower than those specified herein nor waive compatibility with the electric power characteristics specified herein, since that could result in failure of the equipment to perform as required. Utilization equipment specifications should also include requirements that reduce the likelihood of the equipment having an adverse effect on the electric power characteristics provided by the electric system. High inrush current, low lagging power factor, high peak power to average power ratio, high current ripple amplitude, and current distortion are some characteristics of utilization equipment that can adversely affect the electric system by degrading electric power characteristics or increasing capacity requirements. Minimizing these undesirable utilization equipment characteristics involves tradeoffs with weight, cost and reliability that are specific to each type of equipment and should be addressed in the utilization equipment specification. 6.7 Pulsed load design issues. Pulsed loads are a potential cause of unacceptable voltage modulation. Hence large pulsed loads may require excess power source capacity or dedicated power sources to protect other aircraft equipment. The utilization equipment designer should strive to minimize the current modulation produced by pulsed loads. 6.8 Non-linear loads and effects. Attention must be given to non-linear loads and their effect on the AC power bus. All loads should not introduce excessive current distortion such that other equipment is affected. 6.9 Precedence. Tables and equations included in the figures take precedence over the graphical representation of the figure itself. Continuous reproduction of the figures may result in the distortion of the curves. 6.10 Guidance and lessons learned. 6.10.1 Compatibility and testing. Historically users of MIL-STD-704 interpret or view the electrical power quality characteristics limits in this document as they would those of a typical power source/generator. This interpretation is incorrect. An aircraft electrical system is composed of a variety of power components (generation, conversion, inversion, control, power distribution, power management devices, etc.) that provide power to aircraft buses and utilization equipment terminals. Each component and subsystem is designed and tested to its individual equipment specification, which often requires tighter performance than does MIL-STD-704 to compensate for the effects of loads as well as the associated feeder/line voltage drops therein. Therefore, the limits specified herein are minimum requirements for specifying that utilization equipment is compatible with aircraft electrical power. To ensure utilization equipment is compatible with the aircraft power, system testing as outlined in MIL-HDBK-704-1 through -8
  • 17. MIL-STD-704F 12 should be performed. For information and access to the MIL-STD-704 compatibility test laboratory and test methods of MIL-HDBK-704-1 through -8, please contact: Naval Air Systems Command Attn: MIL-STD-704 Laboratory Electrical Power Systems Division (AIR-4.4.4) 48298 Shaw Road, Bldg. 1461 Patuxent River, MD 20670 Website: http://ppe.navair.navy.mil/ 6.10.2 Compatibility and installation. Users of MIL-STD-704 power should consider selection and installation processes when planning to integrate and install utilization equipment or components in aircraft. System designers should be aware of the related interface standards, MIL-STD-7080, MIL-STD-464 and SAE-AS50881, which address installation, electromagnetic compatibility and wiring, respectively. Use of these standards is recommended, especially when incorporating COTS equipment into military aircraft. The 60 Hz power requirements were included to accommodate COTS and non-developmental items procured using procedures of SD- 2. Equipment designed for use on military aircraft should not use 60 Hz power, since it requires more weight and prime mover capacity per unit of power consumed by the utilization equipment. 6.11 Subject term (keyword) listing. AC power utilization DC voltage Electric starting operation Equipment, utilization Power compatibility System, electrical Voltage
  • 18. MIL-STD-704F 13 TABLE I. AC normal operation characteristics - 400 Hertz (see 5.2.3). Steady state characteristics Limits Steady state voltage Voltage unbalance Voltage modulation Voltage phase difference Distortion factor Distortion spectrum Crest factor DC component Steady state frequency Frequency modulation 108.0 to 118.0 Volts, RMS 3.0 Volts, RMS maximum 2.5 Volts, RMS maximum 116° to 124° 0.05 maximum Figure 7 1.31 to 1.51 + 0.10 to - 0.10 Volts 393 to 407 Hz 4 Hz Transient characteristics Limits Peak voltage Voltage transient Frequency transient ±271.8 Volts Figure 3 Figure 5 TABLE II. AC normal operation characteristics - variable frequency (see 5.2.3). Steady state characteristics Limits Steady state voltage Voltage unbalance Voltage modulation Voltage phase difference Distortion factor Distortion spectrum Crest factor DC component Steady state frequency Frequency modulation 108.0 to 118.0 Volts, RMS 3.0 Volts, RMS maximum 2.5 Volts, RMS maximum 116° to 124° 0.05 maximum Figure 7 1.31 to 1.51 +0.10 to – 0.10 Volts 360 to 800 Hz 4 Hz Transient characteristics Limits Peak voltage Voltage transient Frequency transient Maximum rate of change of frequency ±271.8 Volts Figure 3 Not to exceed steady state values of 360 to 800 Hz 250 Hz/sec
  • 19. MIL-STD-704F 14 TABLE III. AC normal operation characteristics - 60 Hertz (see 5.2.3). Steady state characteristics Limits Steady state voltage Voltage unbalance Voltage modulation Voltage phase difference Distortion factor Distortion spectrum Crest factor DC component Steady state frequency Frequency modulation 105.0 to 125.0 Volts, RMS 3.0 Volts, RMS maximum 2.5 Volts, RMS maximum 116° to 124° 0.05 maximum Figure 12 1.31 to 1.51 +0.10 to – 0.10 Volts 59.5 to 60.5 Hz 0.5 Hz Transient characteristics Limits Peak voltage Voltage transient Frequency transient ±271.8 Volts Figure 8 Figure 10 TABLE IV. DC normal operation characteristics (see 5.3.2.1, 5.3.4.1). Limits Steady state characteristics 28 Volt DC system 270 Volt DC system Steady state voltage Distortion factor Distortion spectrum Ripple amplitude 22.0 to 29.0 Volts 0.035 maximum Figure 15 1.5 Volts maximum 250.0 to 280.0 Volts 0.015 maximum Figure 18 6.0 Volts maximum Limits Transient characteristics 28 Volts DC system 270 Volts DC system Voltage transient Figure 13 Figure 16
  • 20. MIL-STD-704F 15 FIGURE 1. Load unbalance limits for three-phase utilization equipment. 0 100 200 300 400 500 600 700 800 900 1000 0 5 10 15 20 25 30 Total Three Phase Load (kVA) Maximum Load Unbalance (VA) Three Phase Load (kVA) 0.5 1.0 4.0 7.0 12.0 20.0 24.0 27.0 30.0 Unbalance (VA) 100 200 390 500 650 825 900 950 1000 See paragraph 4.2.4 for total load over 30.0 kVA.
  • 21. MIL-STD-704F 16 FIGURE 2. Phasor diagram showing required phase sequence relationship. Fundamental Component of Phase Voltage 120° Phase Rotation (Positive) A B C N 120° Voltage Phase Difference
  • 22. MIL-STD-704F 17 Envelope of Normal AC Voltage Transient 40 60 80 100 120 140 160 180 200 0 0.025 0.05 0.075 0.1 0.125 0.15 0.175 Time from Onset of Transient (seconds) Volts (RMS) 180 V; 0.010 sec 118 V; 0.0875 sec 80 V; 0.010 sec 108 V; 0.080 sec Note: Steady state limits do not include disturbances allowed in Table I 118 108 85 113 AC Power at External Power Receptacle See paragraph 4.3 FIGURE 3. Envelope of normal 400 Hz and variable frequency AC voltage transient.
  • 23. 18 FIGURE 4. Limits for 400 Hz and variable frequency AC overvoltage or undervoltage. Limits for 400 Hz and Variable Frequency AC Overvoltage and 18 MIL-STD-704F Limits for 400 Hz and Variable Frequency AC Overvoltage and Undervoltage 0 20 40 60 80 100 120 140 160 180 200 0.01 0.1 1 10 100 Time from Onset of Overvoltage or Undervoltage (seconds) Volts (RMS) V = 180 for t < 0.05 V = 124.6 + 2.77/t for 0.05 ≤ t ≤ 6.925 V = 125 for t > 6.925 100 125 7
  • 24. MIL-STD-704F 19 FIGURE 5. Envelope of normal 400 Hz AC frequency transient. 370 380 390 400 410 420 430 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Time from Onset of Transient (seconds) Frequency, Hz 407 393 Maximum Limit 425 375 Minimum Limit Note: 1. Steady state limits do not include the distrubances allowed in Table I.
  • 25. MIL-STD-704F 20 0 50 100 150 200 250 300 350 400 450 500 0 1 2 3 4 5 6 7 8 9 10 11 Time from Onset of Overfrequency or Underfrequency, Seconds Frequency, Hz 480 420 380 Overfrequency Limit Underfrequency Limit FIGURE 6. Limits for 400 Hz AC overfrequency or underfrequency.
  • 26. 21 FIGURE 7. Maximum distortion spectrum of 400 Hz and variable frequency AC voltage. Maximum Distortion Spectrum of 400 Hz and Variable Frequency AC Voltage -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 10 100 1,000 10,000 100,000 1,000,000 Frequency, Hertz Distortion Amplitude, dB from 1.0 VRMS + 2 0 d B / d e c a d e -20dB/decade Distortion Amplitude, Volts RMS 0.0316 0.1000 0.3160 1.0000 3.1600 Upper Limit 400 Hz Upper Limit Variable Frequency 400 Hz VF 10 -10.00 -10.00 100 -10.00 -10.00 1,000 10.00 10.00 3,000 10.00 10.00 6,000 4.00 10.00 500,000 -34.44 -24.44 1,000,000 --- -34.44 Distortion Amplitude, dBV Frequency Maximum Distortion Spectrum of 400 Hz and Variable Frequency AC Voltage -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 10 100 1,000 10,000 100,000 1,000,000 Frequency, Hertz Distortion Amplitude, dB from 1.0 VRMS + 2 0 d B / d e c a d e -20dB/decade Distortion Amplitude, Volts RMS 0.0316 0.1000 0.3160 1.0000 3.1600 Upper Limit 400 Hz Upper Limit Variable Frequency 400 Hz VF 10 -10.00 -10.00 100 -10.00 -10.00 1,000 10.00 10.00 3,000 10.00 10.00 6,000 4.00 10.00 500,000 -34.44 -24.44 1,000,000 --- -34.44 Distortion Amplitude, dBV Frequency Maximum Distortion Spectrum of 400 Hz and Variable Frequency AC Voltage -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 10 100 1,000 10,000 100,000 1,000,000 Frequency, Hertz Distortion Amplitude, dB from 1.0 VRMS + 2 0 d B / d e c a d e -20dB/decade Distortion Amplitude, Volts RMS 0.0316 0.1000 0.3160 1.0000 3.1600 Upper Limit 400 Hz Upper Limit Variable Frequency 400 Hz VF 10 Maximum Distortion Spectrum of 400 Hz and Variable Frequency AC Voltage -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 10 100 1,000 10,000 100,000 1,000,000 Frequency, Hertz Distortion Amplitude, dB from 1.0 VRMS + 2 0 d B / d e c a d e -20dB/decade Distortion Amplitude, Volts RMS 0.0316 0.1000 0.3160 1.0000 3.1600 Upper Limit 400 Hz Upper Limit Variable Frequency 400 Hz VF 10 -10.00 -10.00 100 -10.00 -10.00 1,000 10.00 10.00 3,000 10.00 10.00 6,000 4.00 10.00 500,000 -34.44 -24.44 1,000,000 --- -34.44 Distortion Amplitude, dBV Frequency 21 MIL-STD-704F
  • 27. MIL-STD-704F 22 Envelope of Normal 60 Hz Voltage Transient 0 20 40 60 80 100 120 140 160 0.000 0.025 0.050 0.075 0.100 0.125 0.150 0.175 Time from Onset of Transient (seconds) Volts (RMS) 125 105 115 152.0 V; 0.0083 sec 130.0 V; 0.0167 sec 70.0 V; 0.0167 sec 125.0 V; 0.1000 sec 105.0 V; 0.1000 sec 31.0 V; 0.0083 sec Notes: 1. Voltage may go to zero potential during bus transfers 2. Steady state limits do not include the disturbances allowed in Table III. 1 cycle @ 60 Hz ½ cycle @ 60 Hz FIGURE 8. Envelope of normal 60 Hz voltage transient.
  • 28. MIL-STD-704F 23 FIGURE 9. Limits for 60 Hz AC overvoltage and undervoltage. MIL-STD-704F 23 2 0 20 40 60 80 100 120 140 160 180 200 0.00 1 0.0 1 0.1 1 1 0 Time from Onset of Overvoltage or Undervoltage (seconds) 0.067 4 cycles @ 60 HZ 128 100 V = 180 V = 125.15 + 3.71/t V = 128 t < 0.067 0.67 < t < 1.300 t > 1.300 for for for Volts (RMS)
  • 29. MIL-STD-704F 24 FIGURE 10. Envelope of normal 60 Hz AC frequency transient. 58.5 59.0 59.5 60.0 60.5 61.0 61.5 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 Time from Onset of Transient, seconds Frequency, Hz Upper Boundary Lower Boundary Note: Steady state limits do not include disturbances allowed in Table III.
  • 30. MIL-STD-704F 25 FIGURE 11. Limits for 60 Hz AC overfrequency and underfrequency. 61 59 58 57 56 10 5 0 15 59.5 Frequency, HZ Time from Onset of Overfrequency or Underfrequency, Seconds 60.5 0 7 60
  • 31. 26 FIGURE 12. Maximum distortion spectrum of 60 Hz AC voltage. -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 1 10 100 1,000 10,000 100,000 Frequency, Hz Distortion Amplitude, dB from 1.0 V RMS Frequency, Hz 1 15 150 450 75,000 Distortion Amplitude -10 -10 10 10 -34.44 -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 1 10 100 1,000 10,000 100,000 Frequency, Hz Distortion Amplitude, dB from 1.0 V RMS Frequency, Hz 1 15 150 450 75,000 Distortion Amplitude -10 -10 10 10 -34.44 26 MIL-STD-704F
  • 32. MIL-STD-704F 27 10 20 30 40 50 0.000 0.025 0.050 0.075 0.100 0.125 0.150 0.175 Time from Onset of Transient (seconds) Volts, DC 50 V, 0.0125 sec 29 V, 0.0825 sec 22 V, 0.1000 sec 18 V, 0.0150 sec 29 22 Note: Steady state limits do not include the disturbances allowed in Table IV FIGURE 13. Envelope of normal voltage transients for 28 volts DC system.
  • 33. 28 0 10 20 30 40 50 60 0.01 0.1 1 10 100 Time from Onset of Overvoltage or Undervoltage (seconds) Volts, DC V = 50 for t < 0.05 V = 31.38 + 0.931/t for 0.05 ≤ t ≤ 7.758 V = 31.5 for t > 7.758 31.5 20.0 7 FIGURE 14. Limits for overvoltage and undervoltage for 28 volts DC system. 28 MIL-STD-704F
  • 34. 29 FIGURE 15. Maximum distortion spectrum for 28 volts DC system. -60.0 -50.0 -40.0 -30.0 -20.0 -10.0 0.0 10.0 10 100 1,000 10,000 100,000 1,000,000 Frequency, Hz Distortion Amplitude, dB from 1.0 VRMS Frequency, Hz 10 1,000 5,000 50,000 500,000 Amplitude, dBV -20.0 0.0 0.0 -20.0 -60.0 - 4 0 d B / d e c a d e -20dB/decade +10 dB/decade -60.0 -50.0 -40.0 -30.0 -20.0 -10.0 0.0 10.0 10 100 1,000 10,000 100,000 1,000,000 Frequency, Hz Distortion Amplitude, dB from 1.0 VRMS Frequency, Hz 10 1,000 5,000 50,000 500,000 Amplitude, dBV -20.0 0.0 0.0 -20.0 -60.0 - 4 0 d B / d e c a d e -20dB/decade +10 dB/decade 29 MIL-STD-704F
  • 35. MIL-STD-704F 30 FIGURE 16. Envelope of normal voltage transient for 270 volts DC system. 150 160 170 180 190 200 210 220 230 240 250 260 270 280 290 300 310 320 330 340 350 0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 Time from Onset of Transient, Seconds Volts, DC Note: 1. Steady state limits do not include the disturbances allowed in Table IV. 280 250 330 V, 0.020 sec 280 V, 0.040 sec 250 V, 0.040 sec 200 V, 0.010 sec
  • 36. 31 FIGURE 17. Limits for DC overvoltage and undervoltage for 270 volts DC system. 31 MIL-STD-704F 0 50 100 150 200 250 300 350 400 450 0.01 0.1 1 10 100 Time from Onset of Overvoltage or Undervoltage, Seconds Volts, DC V = 350 for t < 0.05 V = 289.6 + 3.02/t for 0.05 ≤ t ≤ 7.55 V = 290.0 for 7.55 < t 290 240 7
  • 37. 32 FIGURE 18. Maximum distortion spectrum for 270 volts DC system. -50.0 -40.0 -30.0 -20.0 -10.0 0.0 10.0 20.0 10 100 1,000 10,000 100,000 1,000,000 Frequency, HZ Distortion Amplitude, dB from 1.0 V RMS +10 dB/decade -20dB/decade - 4 0 d B / d e c a d e Frequency, HZ 10 1,000 5,000 50,000 500,000 Amplitude, dBV -10.0 10.0 10.0 -10.0 -50.0 -50.0 -40.0 -30.0 -20.0 -10.0 0.0 10.0 20.0 10 100 1,000 10,000 100,000 1,000,000 Frequency, HZ Distortion Amplitude, dB from 1.0 V RMS +10 dB/decade -20dB/decade - 4 0 d B / d e c a d e Frequency, HZ 10 1,000 5,000 50,000 500,000 Amplitude, dBV -10.0 10.0 10.0 -10.0 -50.0 32 MIL-STD-704F
  • 38. MIL-STD-704F 33 CONCLUDING MATERIAL Custodians: Preparing Activity: Army – AV Navy - AS Navy – AS (Project No. SESS – 0046) Air Force - 11 Review Activities: Army – CR, MI, TE Navy - EC, MC, SH, YD NOTE: The activities listed above were interested in this document as of the date of this document. Since organizations and responsibilities can change, you should verify the currency of the information above using the ASSIST Online database at http://www.dodssp.daps.mil/.