SlideShare a Scribd company logo
1 of 8
Download to read offline
International Journal of Environmental & Agriculture Research (IJOEAR) ISSN:[2454-1850] [Vol-2, Issue-12, December- 2016]
Page | 137
Microbial analysis of Heating systems' surfaces
Olga Rubinová1
, Aleš Rubina2
, Jitka Mohelníková3
Department of building services, Brno University of Technology, Faculty of Civil Engineering, Czech Republic
Abstract— An analysis of experimental investigation focused on microbial pollution of heated was carried out for heating
systems installed in different types of buildings as residential houses and civil buildings. The results point on importance of
maintenance and cleaning the heating systems for quality of indoor air and occupants' comfort.
Keywords— building environment, indoor comfort, heating systems, microbial analysis.
I. INTRODUCTION
Good quality of indoor air is one of the most important requirements for indoor climate comfort. Especially dust
concentration of microorganism growth in indoor air are closely related with respiratory problems and in final consequences
with serious illnesses [1-3]. Hygienic quality of indoor air and for clearness of building surfaces as well as heating systems
are key issues for the indoor climate comfort [4-6]. It has been a subject of the world-wide research programmes [7-11].
Heating systems have to be cleared and repaired. Cleaning of internal surfaces in buildings as floors, furniture, windows,
indoor equipment is frequently completed their cleaning of radiators and heating surfaces is often neglected [12-17].
An analysis of experimental investigation focused on microbial pollution of heated surfaces is presented in the article. The
analysis was carried out for heating systems installed in different types of buildings as residential houses and civil buildings.
The results point on importance of maintenance and cleaning the heating systems for quality of indoor air and occupants'
comfort.
1.1 Requirements
Microbial climate in buildings is influenced by microorganism concentration in the indoor space [18-23]. The concentration
is defined for the Colony Forming Unit-CFU of bacteria or mould per m3 of indoor air. Requirements for the microorganism
concentration limits are specified for the controlled built-environment recommendations of hygienic demands for chemical
and physical limits for indoor climate comfort in occupied rooms:
 Non-acceptable visible mould growth on interior surfaces, it means visible mould growth and also laboratory
cultivated mould growth from sampling.
 Part from the spaces with extremely clear environment the bacteria concentration maximal concentration of 500
CFU/m3
bacteria and 500 CFU/m3 of mould in indoor air is required. Samplings are laboratory tested in
microscopic studies.
TABLE 1
CATEGORY OF THE INDOOR AIR POLLUTION IN ACCORDANCE WITH EUR 14988 [22] – CONCENTRATION OF
MIXED BACTERIAL POPULATION AND MOULDS IN OCCUPATIONAL AREAS AND IN RESIDENTIAL AREAS
Pollution category
Occupational areas Rooms in residential houses
Bacteria
CFU/m3
Mould
CFU/m3
Bacteria
CFU/m3
Mould
CFU/m3
Very low ˂50 ˂25 ˂100 ˂50
Low ˂100 ˂100 ˂500 ˂200
Middle ˂500 ˂500 ˂2500 ˂1000
High ˂2000 ˂2000 ˂10000 ˂10000
Very high ˃2000 ˃ 2000 ˃10000 ˃ 10000
Diagnostics of building state from the microbiological point of view is included into tasks of the environmental session of the
European Commission. The EU document 14988 published statistics of investigation in microbiological air pollution in
buildings in the EU countries. Results are summarized in Table 1, which gives an overview of the classification of mould and
International Journal of Environmental & Agriculture Research (IJOEAR) ISSN:[2454-1850] [Vol-2, Issue-12, December- 2016]
Page | 138
bacteria concentration in indoor air volume. Microorganisms are in common dusty air atmosphere. The dust gives growth to
the microorganisms. Mould concentration is from 1000 to 100 000 CFU per 1 g of dust.
Hygienic limits for many buildings are considered up to the middle pollution category of the concentration of bacteria and
moulds. But results of the investigations show that in residential buildings is microbiological pollution of indoor air is really
high than the hygienically permitted limits.
1.2 Microorganisms and their influence on people's health
Quality of indoor air in building is extremely important for occupants' health. Adults need about 12 000 litres of air per day.
Bacteria and microscopic moulds are allergens that because they produce toxins. They can growth and cumulate on interior
surfaces. Characteristic feature of microorganisms in buildings is ability to grow in a very small concentration and during
convenient hygro-thermal conditions they could significantly increase their growth. Circulated air moves the microorganisms
that could be inhaled by the room occupants. In case of high concentration of bacteria and mould microorganisms in indoor
air the occupants could be seriously endangered in their health. Tab. 2 gives information about negative influences of myco-
toxine microorganisms on living organisms.
TABLE 2
SOME MYCOTOXINS AND THEIR NEGATIVE EFFECTS
Toxin Producent toxinu Negative effects
Aflatoxins Aspergillus flavus Respiration problems and cancer
Ochratoxins spieces Apergillus and Penicillium Karcinogen
Patulin spieces Apergillus and Penicillium Affection of DNA molecules
Trichotecens spieces Stachybotrys and Trichoderma Karcinogen
It is not a purpose to create extremely disinfected climate in common buildings. Disinfection for liquidation of vegetative
form of microorganisms or sterilization of microorganisms and spores could shave also negative impact for occupants' health.
Their immune system is weaken and lose an ability of reaction on the external influences. Total liquidation of
microorganisms is important for special purposes for example for operation theatres in hospitals or in special productions as
pharmaceutic production etc. Microorganisms detected on surfaces are in many cases different than microorganisms in the air
which also must be taken into consideration.
II. EXPERIMENTAL TESTING OF RADIATOR SURFACES
2.1 Microorganisms on radiator surfaces in school building
Testing of microorganism concentrations on heating systems surfaces was completed within the frame of a research project.
The project was focused on the sampling of various systems for heating in buildings. Heating systems at a campus of the
Faculty of Civil Engineering, Brno University of Technology were tested in January 2014. Positions of the sampling are
shown in the scheme of Figure 1. The Dipslide Labm method was selected for the testing.
The contact sampling method is convenient because of easy and quick sampling and low risk of contamination. The sample
is sealed in the test tube before and after the test. The sample cultivation is inside of the tube. In this case the cultivation
process is not affected by influenced any external influences.
The samples of surface microorganisms (Figure 2) were selected for laboratory cultivation (Figure 3). Results determined
from the cultivation for the constant thermal conditions (bacteria 3 days, for 30 °C; moulds 5 days for 25 °C) were evaluated
for the CFU (Colony Forming Units) per m2 of the surface.
Tested heating systems:
 Radiator with lamellas – corridor E1 (about 13 years operation).
 Radiator without lamellas – corridor E2 (about 2 years operation).
 Cast iron articulated radiator – corridor to building D (more than 10 years operation).
 Floor convertor without ventilator with Al lamellas air – corridor to building D.
International Journal of Environmental & Agriculture Research (IJOEAR) ISSN:[2454-1850] [Vol-2, Issue-12, December- 2016]
Page | 139
FIG. 1: SCHEME OF THE FACULTY CAMPUS OF BRNO UNIVERSITY OF TECHNOLOGY POSITIONS 1 TO 4 ARE
THE TEST SAMPLING PLACES
FLOOR CONVECTOR IN THE CINEMA FLOOR CONVERTOR IN THE UNIVERSITY STUDY ROOM
FLOOR CONVERTOR IN RESIDENTIAL BUILDING A SLAB RADIATION IN RESIDENTIAL BUILDING A
FLOOR CONVERTOR IN RESIDENTIAL BUILDING B SLAB RADIATION IN RESIDENTIAL BUILDING B
FIG. 2: TESTED HEATERS, RADIATORS AND FLOOR HEAT CONVERTORS
4
3
2
1
International Journal of Environmental & Agriculture Research (IJOEAR) ISSN:[2454-1850] [Vol-2, Issue-12, December- 2016]
Page | 140
Samplings were selected on all heaters and were compared with samplings of interior surfaces. The sampling selection is
documented in Figure 3.
FIG. 3: POSITIONS OF SAMPLINGS ON THE TESTED HEATER
The example of a microbiological sample and its cultivation of bacteria (yellow) and mould (red) of sample 2 (new radiator
in school building corridor) is shown in Figure 4.
FIG. 3: THE SAMPLES LABORATORY CULTIVATION
Bacterial pollution of the heaters is adequate to other tested surfaces in interior. More intensive pollution is on the floor
convertor, where there were three types of moulds detected. Results of the laboratory tests of the samplings are shown in
Table 3 a Figure 4.
TABLE 3
RESULTS OF THE HEATER MICROBIOLOGICAL SAMPLES TESTING
Heating system
Bacteria
CFU/m2
Mould
CFU/m2 species
Desk radiator – building E1 10600 undetected
Desk radiator - building E2 18100 3125 Penicillium
Sectional heater - building D 4375 1800
Penicillium
Rhizopus
Floor convertor - corridor to building D 58750 11900
Aspergillus
Penicillium
Rhizopus
International Journal of Environmental & Agriculture Research (IJOEAR) ISSN:[2454-1850] [Vol-2, Issue-12, December- 2016]
Page | 141
Type Rhizopus is thermophile – it means moulds of this type could grow even for temperature of 50 °C. The mould types do
not produce mycotoxines, but spores have highly allergenic potential. Type Aspergillus grows under conditions of
temperatures 10 to 45 °C, type Penicillium grows from 4 °C. Type Aspergillus produces aflatoxins with carcinogenic effects.
FIG. 4: RESULTS OF MICROOGRANISM CULTIVATION ON VARIOUS SURFACES
2.2 Microorganisms in floor convertors
The above mentioned results show that the microbial pollution is the most problematic for the floor convertor. It is certainly
because of its shape and uneven surface that are and difficult to clean. Especially in dwellings and places with pets as cats or
dogs the convertors are very often “dust and hair accumulators”, Figure 5. Dust with organic compounds is a convenient base
for the mould growth. For this reason the next research has been focused on the floor convertors.
FIG. 5: FLOOR LAMELLAE CONVERTOR OF ROOM OF A FLAT WITH A CAT (TWICE A YEAR CLEARED);
DISTANCE OF THE CONVERTOR LAMELLAS IS 3 mm
International Journal of Environmental & Agriculture Research (IJOEAR) ISSN:[2454-1850] [Vol-2, Issue-12, December- 2016]
Page | 142
On the basis of the above mentioned experiment samples of floor heating convertors were tested. The testing was carried out
for the following floor heaters:
1. Floor convertor without ventilator located in circulation area in a cinema building in the city centre (new building –
only two years in operation).
2. Floor convertor in a study room of a university library (four years’ operation).
3. Floor convertor in a residential building A (ten years’ operation).
4. Slab radiator in a residential building A.
5. Floor convertor in a residential building B (two years’ operation).
6. Slab radiator in a residential building B.
Both of the residential buildings are occupied by four-member families there are no pets in the families. Low-temperature
heating systems are in service in those buildings. Results of the tests are presented in Table 4 and Figure 6.
TABLE 4
RESULTS OF THE MICROORGANISM CULTIVATION OF THE FLOOR CONVERTORS SAMPLINGS
Heating system
Bacteria
CFU/m2
Mould
CFU/m2 spieces
Floor convector in the cinema 78750 39400
Penicillium
Rhizopus
Floor convertor in the university study room 55700 2500 Penicillium
Floor convertor in residential building A 18500 5100
Aspergillus
Slab radiation in residential building A 7800 1500
Aspergillus
Floor convertor in residential building B 13750 undetected -
Slab radiation in residential building B 4400 1900 Rhizopus
FIG. 6: RESULTS OF THE MICROORGANISM CULTIVATION OF SAMPLES OF FLOOR CONVERTORS
International Journal of Environmental & Agriculture Research (IJOEAR) ISSN:[2454-1850] [Vol-2, Issue-12, December- 2016]
Page | 143
Microorganism growth was detected for many floor convertors in public buildings. The convertor itself is not source of
microorganisms but its construction and surface area and possibility to clean it influences microorganism concentration.
Low-temperature heating systems are weak to microorganism growth. Location of these systems is problematical because of
floor or very low positioning in the room places with increased concentration of microorganism. Microorganisms are moved
by the air circulation inside of the internal spaces in buildings. It can be expected that in public buildings the concentration of
microorganisms could be very high because of neglected regular service and cleaning of the heating systems. Moulds and
fungy Rhizopus are very rare in buildings but in case that they have convenient conditions they spread and increase their
allergenic potential.
2.3 Growth of microorganisms on surfaces of heating systems
The next experiment was aimed at the testing of heating surfaces that are commonly cleaned without disinfection detergents.
The slab radiator was cleaned and sampled (after 14, 21, 28 and 35 days). Samplings were selected due to surface sponges
(3M).
Samples were cultivated in laboratory. Two cultivation substances were used - PCA agar for bacteria cultivation and agar
with antibiotics for mould cultivation. Samples for the bacteria cultivation were tested for three days at temperature of 30 °C
and samples for moulds cultivation for 5 days at 25 °C.
The radiator bacterial pollution in forty days in presented in graph of Figure 7. It is clear that the bacteria contamination is
exponentially increased in time.
FIG. 7: BACTERIAL CONTAMINATION OF THE RADIATOR (COLOUR POINTS – DIFFERENT PLACES OF THE
DUST SAMPLING ON THE RADIATOR)
III. CONCLUSION
Heating radiators a shape that gives possibility to dust settlement on them create opportunity to microorganism growth. It can
be problematic in rooms with very low indoor temperature. Low-temperature heating systems with the service water
temperature below 50 o
C could be affected by microorganisms. It is very important to provide frequent revisions and
cleaning of the heating systems in public and residential buildings.
Heaters with complicated shape and uneven surface could accumulate dust and for this reason they support the mould growth
a microbial concentration. Low-temperature water heater systems (below 50 °C) give growth of mesophile types of organic
pollution. For the low-temperature heating systems regular thermic disinfection is recommended for the heaters maintenance.
The heaters construction and easy-to-clean surfaces as well as convenient positioning in the building are key factor for
elimination of dust concentration and organic pollution. Heaters with lamellas located in floors are directly exposed to the
pollution and microbial contamination. Another problem could be uncontrolled amount of dust in places where people do not
International Journal of Environmental & Agriculture Research (IJOEAR) ISSN:[2454-1850] [Vol-2, Issue-12, December- 2016]
Page | 144
change their shoes. In public buildings with high occupancy the dust contamination was proven much more serious
compared to dwelling where people wear clear home shoes. High occupancy has also negative influence on microbial
pollution.
It seems that frequent and thorough cleaning maintenance of heaters at public buildings is really necessary. Floor convertor
heaters are not recommended for spaces with high hygienic demands as hospitals and care homes. Plain surface radiators
positioned in easy-to –clean installations would be or convenient in these cases.
ACKNOWLEDGEMENTS
This article has been worked out under the project No. LO1408 "AdMaS UP - Advanced Materials, Structures and
Technologies", supported by Ministry of Education, Youth and Sports under the National Sustainability Programme I" of the
Czech Republic.
The research is supported by the Specific research at Brno University of Technology, Faculty of Civil Engineering, reg.
number FAST-S-15-2620.
REFERENCES
[1] Wanner H. U. a col. Biological Particles in Indoor Environment, EUR 14988 EN, v ed. Indoor air quality & its impact on man, Report
No.12. 1993.
[2] Górka-Kostrubiec B., Jeleńska1 M., Król E. Magnetic signature of indoor air pollution: Household dust study. Acta Geophysica.
Volume 62, Issue 6, Pages 1478–1503, ISSN (Online) 1895-7455, DOI: 10.2478/s11600-014-0238-1, September 2014.
[3] Górka-Kostrubiec B.; The magnetic properties of indoor dust fractions as markers of air pollution inside buildings, Building and
Environment, Volume 90, August 2015, Pages 186-195, ISSN 0360-1323.
[4] The results of the analysis of metal dust. Protocol EMPLA, Hradec Kralove 2011 (in Czech). http://orgo-
net.blogspot.cz/2011/03/vysledky-rozboru-kovoveho-prachu.html.
[5] Holopainen, R. et al. (2002), The effect of cleanliness control during installation work on the amount of accumulated dust in ducts of
new HVAC installations. Indoor Air, 12: 191–197. doi: 10.1034/j.1600-0668.2002.01119.x
[6] Oxkten Suzan, Asan Ahmet; Airborne fungi and bacteria in indoor and outdoor environment of the Pediatric Unit of Edirne; Environ
Monit Assess (2012) 184:1739–1751; Springer Science+Business Media B.V. 2011.
[7] Yassin, M. F.; Almouqatea, S., (2010). Assessment of airborne bacteria and fungi in an indoor and outdoor environment. Int. J.
Environ. Sci. Tech., 7 (3), 535-544.
[8] Górny RL, Reponen T, Willeke K, et al. Fungal Fragments as Indoor Air Biocontaminants. Applied and Environmental Microbiology.
2002;68(7):3522-3531 doi:10.1128/AEM.68.7.3522-3531.2002.
[9] D. Haas, J. Habib, J. Luxner, H. Galler, G. Zarfel, R. Schlacher, H. Friedl, F.F. Reinthaler: Comparison of background levels of
culturable fungal spore concentrations in indoor and outdoor air in southeastern Austria; Atmospheric Environment 98 (2014)
640e647.
[10] Linlin Liang, GuenterEngling, YuanCheng, FengkuiDuan, ZhenyuDu, KebinHe; Rapid detection and quantification of fungal spores
in the urban atmosphere by flow cytometry; Journal ofAerosolScience, 66(2013)179–186.
[11] Taekhee Lee, Sergey A. Grinshpun, Dainius Martuzevicius, Atin Adhikari, Carlos M. Crawford, Tiina Reponen; Culturability and
concentration of indoor and outdoor airborne fungi in six single-family homes; Atmospheric Environment 40 (2006) 2902–2910.

More Related Content

What's hot

Evaluation of Cadmium tolerant Fungi in the dying Staff and their removal Pot...
Evaluation of Cadmium tolerant Fungi in the dying Staff and their removal Pot...Evaluation of Cadmium tolerant Fungi in the dying Staff and their removal Pot...
Evaluation of Cadmium tolerant Fungi in the dying Staff and their removal Pot...AI Publications
 
Antimicrobial silver fabric By Dr Anjum Hashmi MPH
Antimicrobial silver fabric By Dr Anjum Hashmi MPHAntimicrobial silver fabric By Dr Anjum Hashmi MPH
Antimicrobial silver fabric By Dr Anjum Hashmi MPHAnjum Hashmi MPH
 
Lect.6 (chapter 5 microbial control)
Lect.6 (chapter 5 microbial control)Lect.6 (chapter 5 microbial control)
Lect.6 (chapter 5 microbial control)Osama Rifat
 
Control of Microbial Growth
Control of Microbial Growth Control of Microbial Growth
Control of Microbial Growth rmasterson
 
Fundamentals of Control of Microorganisms
Fundamentals of Control of MicroorganismsFundamentals of Control of Microorganisms
Fundamentals of Control of MicroorganismsPharmacy Universe
 
Physical and chemical method to Control microbial growth
Physical and chemical method to Control microbial growthPhysical and chemical method to Control microbial growth
Physical and chemical method to Control microbial growthRajasekaranElangovan3
 
Industrial biotechnology in Nepal
Industrial biotechnology in Nepal Industrial biotechnology in Nepal
Industrial biotechnology in Nepal Suman Bhattarai
 
7 control of microbial growth
7 control of microbial growth7 control of microbial growth
7 control of microbial growthUiTM Jasin
 
Performance of integrated process using fungal strain corialus versicalor mtc
Performance of integrated process using fungal strain corialus versicalor mtcPerformance of integrated process using fungal strain corialus versicalor mtc
Performance of integrated process using fungal strain corialus versicalor mtcIAEME Publication
 
Control of microorganisms in food
Control of microorganisms in foodControl of microorganisms in food
Control of microorganisms in foodDr. Samira Fattah
 
Ch 07_lecture_presentation
 Ch 07_lecture_presentation Ch 07_lecture_presentation
Ch 07_lecture_presentationJane Xu
 
Application of Sensitized Silver Nanoparticles on Pretreated Polyester and Si...
Application of Sensitized Silver Nanoparticles on Pretreated Polyester and Si...Application of Sensitized Silver Nanoparticles on Pretreated Polyester and Si...
Application of Sensitized Silver Nanoparticles on Pretreated Polyester and Si...Associate Professor in VSB Coimbatore
 
control of microbial growth
control of microbial growthcontrol of microbial growth
control of microbial growthAshish Jawarkar
 
Microbial control lecture reference
Microbial control lecture referenceMicrobial control lecture reference
Microbial control lecture referenceMarilen Parungao
 

What's hot (20)

Pharma micro myths (sandle)
Pharma micro myths (sandle)Pharma micro myths (sandle)
Pharma micro myths (sandle)
 
Evaluation of Cadmium tolerant Fungi in the dying Staff and their removal Pot...
Evaluation of Cadmium tolerant Fungi in the dying Staff and their removal Pot...Evaluation of Cadmium tolerant Fungi in the dying Staff and their removal Pot...
Evaluation of Cadmium tolerant Fungi in the dying Staff and their removal Pot...
 
Antimicrobial silver fabric By Dr Anjum Hashmi MPH
Antimicrobial silver fabric By Dr Anjum Hashmi MPHAntimicrobial silver fabric By Dr Anjum Hashmi MPH
Antimicrobial silver fabric By Dr Anjum Hashmi MPH
 
Tho control of microbial growth
Tho control of microbial growthTho control of microbial growth
Tho control of microbial growth
 
A review on synthesis and their antibacterial activity of silver and selenium...
A review on synthesis and their antibacterial activity of silver and selenium...A review on synthesis and their antibacterial activity of silver and selenium...
A review on synthesis and their antibacterial activity of silver and selenium...
 
Lect.6 (chapter 5 microbial control)
Lect.6 (chapter 5 microbial control)Lect.6 (chapter 5 microbial control)
Lect.6 (chapter 5 microbial control)
 
Control of Microbial Growth
Control of Microbial Growth Control of Microbial Growth
Control of Microbial Growth
 
Fundamentals of Control of Microorganisms
Fundamentals of Control of MicroorganismsFundamentals of Control of Microorganisms
Fundamentals of Control of Microorganisms
 
Physical and chemical method to Control microbial growth
Physical and chemical method to Control microbial growthPhysical and chemical method to Control microbial growth
Physical and chemical method to Control microbial growth
 
Industrial biotechnology in Nepal
Industrial biotechnology in Nepal Industrial biotechnology in Nepal
Industrial biotechnology in Nepal
 
7 control of microbial growth
7 control of microbial growth7 control of microbial growth
7 control of microbial growth
 
Performance of integrated process using fungal strain corialus versicalor mtc
Performance of integrated process using fungal strain corialus versicalor mtcPerformance of integrated process using fungal strain corialus versicalor mtc
Performance of integrated process using fungal strain corialus versicalor mtc
 
Control of microorganisms in food
Control of microorganisms in foodControl of microorganisms in food
Control of microorganisms in food
 
Ch 07_lecture_presentation
 Ch 07_lecture_presentation Ch 07_lecture_presentation
Ch 07_lecture_presentation
 
Control of microorganisms in foods
Control of microorganisms in foodsControl of microorganisms in foods
Control of microorganisms in foods
 
Nanopesticide
Nanopesticide Nanopesticide
Nanopesticide
 
Application of Sensitized Silver Nanoparticles on Pretreated Polyester and Si...
Application of Sensitized Silver Nanoparticles on Pretreated Polyester and Si...Application of Sensitized Silver Nanoparticles on Pretreated Polyester and Si...
Application of Sensitized Silver Nanoparticles on Pretreated Polyester and Si...
 
control of microbial growth
control of microbial growthcontrol of microbial growth
control of microbial growth
 
Microbial control lecture reference
Microbial control lecture referenceMicrobial control lecture reference
Microbial control lecture reference
 
Antibacterial paper
Antibacterial paperAntibacterial paper
Antibacterial paper
 

Similar to Microbial analysis of Heating systems' surfaces

Indoor and outdoor air quality in hospital environment
Indoor and outdoor air quality in hospital environmentIndoor and outdoor air quality in hospital environment
Indoor and outdoor air quality in hospital environmentAlexander Decker
 
China Kang Heating Room Fresh Air into the Indoor Research Facilities
China Kang Heating Room Fresh Air into the Indoor Research FacilitiesChina Kang Heating Room Fresh Air into the Indoor Research Facilities
China Kang Heating Room Fresh Air into the Indoor Research FacilitiesCSCJournals
 
Bv32891897
Bv32891897Bv32891897
Bv32891897IJMER
 
IRJET- Biofilter System for Air Pollution Control: A Review
IRJET- Biofilter System for Air Pollution Control: A ReviewIRJET- Biofilter System for Air Pollution Control: A Review
IRJET- Biofilter System for Air Pollution Control: A ReviewIRJET Journal
 
Evaluation of the indoor air quality of beato angelico building of the univer...
Evaluation of the indoor air quality of beato angelico building of the univer...Evaluation of the indoor air quality of beato angelico building of the univer...
Evaluation of the indoor air quality of beato angelico building of the univer...University of Santo Tomas
 
The indoor environment & air quality uv air & surface disinfection
The indoor environment & air quality   uv air & surface disinfectionThe indoor environment & air quality   uv air & surface disinfection
The indoor environment & air quality uv air & surface disinfectionTNenergy
 
Anti-Adhesion and Anti-Biofilm Effectiveness of Disinfectants Used In Hemodia...
Anti-Adhesion and Anti-Biofilm Effectiveness of Disinfectants Used In Hemodia...Anti-Adhesion and Anti-Biofilm Effectiveness of Disinfectants Used In Hemodia...
Anti-Adhesion and Anti-Biofilm Effectiveness of Disinfectants Used In Hemodia...IJERA Editor
 
Evaluation of biological and physicochemical risk of hospital liquid waste in...
Evaluation of biological and physicochemical risk of hospital liquid waste in...Evaluation of biological and physicochemical risk of hospital liquid waste in...
Evaluation of biological and physicochemical risk of hospital liquid waste in...Agriculture Journal IJOEAR
 
Wastewater, Liquid effluent, physicochemical pollution, bacteriological, trac...
Wastewater, Liquid effluent, physicochemical pollution, bacteriological, trac...Wastewater, Liquid effluent, physicochemical pollution, bacteriological, trac...
Wastewater, Liquid effluent, physicochemical pollution, bacteriological, trac...Agriculture Journal IJOEAR
 
DESIGN AND FABRICATION OF CATCH AND KILL AIR FILTER
DESIGN AND FABRICATION OF CATCH AND KILL AIR  FILTERDESIGN AND FABRICATION OF CATCH AND KILL AIR  FILTER
DESIGN AND FABRICATION OF CATCH AND KILL AIR FILTERvivatechijri
 
Biofilters for control of air pollution
Biofilters for control of air pollutionBiofilters for control of air pollution
Biofilters for control of air pollutionAshish kumar Yadav
 
Performance studies of microbial fuel cell
Performance studies of microbial fuel cellPerformance studies of microbial fuel cell
Performance studies of microbial fuel celleSAT Journals
 
Performance studies of microbial fuel cell
Performance studies of microbial fuel cellPerformance studies of microbial fuel cell
Performance studies of microbial fuel celleSAT Publishing House
 
Design, Installation and Commissioning Of Clean Room and Hvac Facility for St...
Design, Installation and Commissioning Of Clean Room and Hvac Facility for St...Design, Installation and Commissioning Of Clean Room and Hvac Facility for St...
Design, Installation and Commissioning Of Clean Room and Hvac Facility for St...IOSR Journals
 
Revised guideline for research in transgenic plants (
Revised guideline for research in transgenic plants (Revised guideline for research in transgenic plants (
Revised guideline for research in transgenic plants (Vipin Shukla
 
Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)IJERD Editor
 
Biochemical Engineering and its scope.pptx
Biochemical Engineering and its scope.pptxBiochemical Engineering and its scope.pptx
Biochemical Engineering and its scope.pptxAnitaLaghulkar1
 

Similar to Microbial analysis of Heating systems' surfaces (20)

Indoor and outdoor air quality in hospital environment
Indoor and outdoor air quality in hospital environmentIndoor and outdoor air quality in hospital environment
Indoor and outdoor air quality in hospital environment
 
China Kang Heating Room Fresh Air into the Indoor Research Facilities
China Kang Heating Room Fresh Air into the Indoor Research FacilitiesChina Kang Heating Room Fresh Air into the Indoor Research Facilities
China Kang Heating Room Fresh Air into the Indoor Research Facilities
 
Bv32891897
Bv32891897Bv32891897
Bv32891897
 
IRJET- Biofilter System for Air Pollution Control: A Review
IRJET- Biofilter System for Air Pollution Control: A ReviewIRJET- Biofilter System for Air Pollution Control: A Review
IRJET- Biofilter System for Air Pollution Control: A Review
 
Interior Landscape Plants for Indoor Air Pollution Abatement
Interior Landscape Plants for Indoor Air Pollution AbatementInterior Landscape Plants for Indoor Air Pollution Abatement
Interior Landscape Plants for Indoor Air Pollution Abatement
 
Evaluation of the indoor air quality of beato angelico building of the univer...
Evaluation of the indoor air quality of beato angelico building of the univer...Evaluation of the indoor air quality of beato angelico building of the univer...
Evaluation of the indoor air quality of beato angelico building of the univer...
 
The indoor environment & air quality uv air & surface disinfection
The indoor environment & air quality   uv air & surface disinfectionThe indoor environment & air quality   uv air & surface disinfection
The indoor environment & air quality uv air & surface disinfection
 
Anti-Adhesion and Anti-Biofilm Effectiveness of Disinfectants Used In Hemodia...
Anti-Adhesion and Anti-Biofilm Effectiveness of Disinfectants Used In Hemodia...Anti-Adhesion and Anti-Biofilm Effectiveness of Disinfectants Used In Hemodia...
Anti-Adhesion and Anti-Biofilm Effectiveness of Disinfectants Used In Hemodia...
 
Evaluation of biological and physicochemical risk of hospital liquid waste in...
Evaluation of biological and physicochemical risk of hospital liquid waste in...Evaluation of biological and physicochemical risk of hospital liquid waste in...
Evaluation of biological and physicochemical risk of hospital liquid waste in...
 
Wastewater, Liquid effluent, physicochemical pollution, bacteriological, trac...
Wastewater, Liquid effluent, physicochemical pollution, bacteriological, trac...Wastewater, Liquid effluent, physicochemical pollution, bacteriological, trac...
Wastewater, Liquid effluent, physicochemical pollution, bacteriological, trac...
 
DESIGN AND FABRICATION OF CATCH AND KILL AIR FILTER
DESIGN AND FABRICATION OF CATCH AND KILL AIR  FILTERDESIGN AND FABRICATION OF CATCH AND KILL AIR  FILTER
DESIGN AND FABRICATION OF CATCH AND KILL AIR FILTER
 
E045072630
E045072630E045072630
E045072630
 
negative ion generator
negative ion generator   negative ion generator
negative ion generator
 
Biofilters for control of air pollution
Biofilters for control of air pollutionBiofilters for control of air pollution
Biofilters for control of air pollution
 
Performance studies of microbial fuel cell
Performance studies of microbial fuel cellPerformance studies of microbial fuel cell
Performance studies of microbial fuel cell
 
Performance studies of microbial fuel cell
Performance studies of microbial fuel cellPerformance studies of microbial fuel cell
Performance studies of microbial fuel cell
 
Design, Installation and Commissioning Of Clean Room and Hvac Facility for St...
Design, Installation and Commissioning Of Clean Room and Hvac Facility for St...Design, Installation and Commissioning Of Clean Room and Hvac Facility for St...
Design, Installation and Commissioning Of Clean Room and Hvac Facility for St...
 
Revised guideline for research in transgenic plants (
Revised guideline for research in transgenic plants (Revised guideline for research in transgenic plants (
Revised guideline for research in transgenic plants (
 
Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)
 
Biochemical Engineering and its scope.pptx
Biochemical Engineering and its scope.pptxBiochemical Engineering and its scope.pptx
Biochemical Engineering and its scope.pptx
 

Recently uploaded

Call Girls Budhwar Peth Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Budhwar Peth Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Budhwar Peth Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Budhwar Peth Call Me 7737669865 Budget Friendly No Advance Bookingroncy bisnoi
 
Call Girls Magarpatta Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Magarpatta Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Magarpatta Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Magarpatta Call Me 7737669865 Budget Friendly No Advance Bookingroncy bisnoi
 
VIP Call Girls Valsad 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Valsad 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Valsad 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Valsad 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
DENR EPR Law Compliance Updates April 2024
DENR EPR Law Compliance Updates April 2024DENR EPR Law Compliance Updates April 2024
DENR EPR Law Compliance Updates April 2024itadmin50
 
Booking open Available Pune Call Girls Parvati Darshan 6297143586 Call Hot I...
Booking open Available Pune Call Girls Parvati Darshan  6297143586 Call Hot I...Booking open Available Pune Call Girls Parvati Darshan  6297143586 Call Hot I...
Booking open Available Pune Call Girls Parvati Darshan 6297143586 Call Hot I...Call Girls in Nagpur High Profile
 
Verified Trusted Kalyani Nagar Call Girls 8005736733 𝐈𝐍𝐃𝐄𝐏𝐄𝐍𝐃𝐄𝐍𝐓 Call 𝐆𝐈𝐑𝐋 𝐕...
Verified Trusted Kalyani Nagar Call Girls  8005736733 𝐈𝐍𝐃𝐄𝐏𝐄𝐍𝐃𝐄𝐍𝐓 Call 𝐆𝐈𝐑𝐋 𝐕...Verified Trusted Kalyani Nagar Call Girls  8005736733 𝐈𝐍𝐃𝐄𝐏𝐄𝐍𝐃𝐄𝐍𝐓 Call 𝐆𝐈𝐑𝐋 𝐕...
Verified Trusted Kalyani Nagar Call Girls 8005736733 𝐈𝐍𝐃𝐄𝐏𝐄𝐍𝐃𝐄𝐍𝐓 Call 𝐆𝐈𝐑𝐋 𝐕...tanu pandey
 
Cyclone Case Study Odisha 1999 Super Cyclone in India.
Cyclone Case Study Odisha 1999 Super Cyclone in India.Cyclone Case Study Odisha 1999 Super Cyclone in India.
Cyclone Case Study Odisha 1999 Super Cyclone in India.cojitesh
 
Proposed Amendments to Chapter 15, Article X: Wetland Conservation Areas
Proposed Amendments to Chapter 15, Article X: Wetland Conservation AreasProposed Amendments to Chapter 15, Article X: Wetland Conservation Areas
Proposed Amendments to Chapter 15, Article X: Wetland Conservation Areas💥Victoria K. Colangelo
 
VVIP Pune Call Girls Vishal Nagar WhatSapp Number 8005736733 With Elite Staff...
VVIP Pune Call Girls Vishal Nagar WhatSapp Number 8005736733 With Elite Staff...VVIP Pune Call Girls Vishal Nagar WhatSapp Number 8005736733 With Elite Staff...
VVIP Pune Call Girls Vishal Nagar WhatSapp Number 8005736733 With Elite Staff...SUHANI PANDEY
 
Enhancing forest data transparency for climate action
Enhancing forest data transparency for climate actionEnhancing forest data transparency for climate action
Enhancing forest data transparency for climate actionRocioDanicaCondorGol1
 
Presentation: Farmer-led climate adaptation - Project launch and overview by ...
Presentation: Farmer-led climate adaptation - Project launch and overview by ...Presentation: Farmer-led climate adaptation - Project launch and overview by ...
Presentation: Farmer-led climate adaptation - Project launch and overview by ...AICCRA
 
VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...
VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...
VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...SUHANI PANDEY
 
Call Girls Jejuri Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Jejuri Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Jejuri Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Jejuri Call Me 7737669865 Budget Friendly No Advance Bookingroncy bisnoi
 
Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...
Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...
Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...MOHANI PANDEY
 
GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756
GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756
GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756dollysharma2066
 
Call Now ☎ Russian Call Girls Connaught Place @ 9899900591 # Russian Escorts ...
Call Now ☎ Russian Call Girls Connaught Place @ 9899900591 # Russian Escorts ...Call Now ☎ Russian Call Girls Connaught Place @ 9899900591 # Russian Escorts ...
Call Now ☎ Russian Call Girls Connaught Place @ 9899900591 # Russian Escorts ...kauryashika82
 
RATING SYSTEMS- IGBC, GRIHA, LEED--.pptx
RATING  SYSTEMS- IGBC, GRIHA, LEED--.pptxRATING  SYSTEMS- IGBC, GRIHA, LEED--.pptx
RATING SYSTEMS- IGBC, GRIHA, LEED--.pptxJIT KUMAR GUPTA
 
Kondhwa ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Kondhwa ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Kondhwa ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Kondhwa ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...tanu pandey
 

Recently uploaded (20)

Call Girls Budhwar Peth Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Budhwar Peth Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Budhwar Peth Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Budhwar Peth Call Me 7737669865 Budget Friendly No Advance Booking
 
Call Girls Magarpatta Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Magarpatta Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Magarpatta Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Magarpatta Call Me 7737669865 Budget Friendly No Advance Booking
 
(INDIRA) Call Girl Katra Call Now 8617697112 Katra Escorts 24x7
(INDIRA) Call Girl Katra Call Now 8617697112 Katra Escorts 24x7(INDIRA) Call Girl Katra Call Now 8617697112 Katra Escorts 24x7
(INDIRA) Call Girl Katra Call Now 8617697112 Katra Escorts 24x7
 
VIP Call Girls Valsad 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Valsad 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Valsad 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Valsad 7001035870 Whatsapp Number, 24/07 Booking
 
DENR EPR Law Compliance Updates April 2024
DENR EPR Law Compliance Updates April 2024DENR EPR Law Compliance Updates April 2024
DENR EPR Law Compliance Updates April 2024
 
Booking open Available Pune Call Girls Parvati Darshan 6297143586 Call Hot I...
Booking open Available Pune Call Girls Parvati Darshan  6297143586 Call Hot I...Booking open Available Pune Call Girls Parvati Darshan  6297143586 Call Hot I...
Booking open Available Pune Call Girls Parvati Darshan 6297143586 Call Hot I...
 
Verified Trusted Kalyani Nagar Call Girls 8005736733 𝐈𝐍𝐃𝐄𝐏𝐄𝐍𝐃𝐄𝐍𝐓 Call 𝐆𝐈𝐑𝐋 𝐕...
Verified Trusted Kalyani Nagar Call Girls  8005736733 𝐈𝐍𝐃𝐄𝐏𝐄𝐍𝐃𝐄𝐍𝐓 Call 𝐆𝐈𝐑𝐋 𝐕...Verified Trusted Kalyani Nagar Call Girls  8005736733 𝐈𝐍𝐃𝐄𝐏𝐄𝐍𝐃𝐄𝐍𝐓 Call 𝐆𝐈𝐑𝐋 𝐕...
Verified Trusted Kalyani Nagar Call Girls 8005736733 𝐈𝐍𝐃𝐄𝐏𝐄𝐍𝐃𝐄𝐍𝐓 Call 𝐆𝐈𝐑𝐋 𝐕...
 
Cyclone Case Study Odisha 1999 Super Cyclone in India.
Cyclone Case Study Odisha 1999 Super Cyclone in India.Cyclone Case Study Odisha 1999 Super Cyclone in India.
Cyclone Case Study Odisha 1999 Super Cyclone in India.
 
Proposed Amendments to Chapter 15, Article X: Wetland Conservation Areas
Proposed Amendments to Chapter 15, Article X: Wetland Conservation AreasProposed Amendments to Chapter 15, Article X: Wetland Conservation Areas
Proposed Amendments to Chapter 15, Article X: Wetland Conservation Areas
 
VVIP Pune Call Girls Vishal Nagar WhatSapp Number 8005736733 With Elite Staff...
VVIP Pune Call Girls Vishal Nagar WhatSapp Number 8005736733 With Elite Staff...VVIP Pune Call Girls Vishal Nagar WhatSapp Number 8005736733 With Elite Staff...
VVIP Pune Call Girls Vishal Nagar WhatSapp Number 8005736733 With Elite Staff...
 
Enhancing forest data transparency for climate action
Enhancing forest data transparency for climate actionEnhancing forest data transparency for climate action
Enhancing forest data transparency for climate action
 
(Anamika) VIP Call Girls Jammu Call Now 8617697112 Jammu Escorts 24x7
(Anamika) VIP Call Girls Jammu Call Now 8617697112 Jammu Escorts 24x7(Anamika) VIP Call Girls Jammu Call Now 8617697112 Jammu Escorts 24x7
(Anamika) VIP Call Girls Jammu Call Now 8617697112 Jammu Escorts 24x7
 
Presentation: Farmer-led climate adaptation - Project launch and overview by ...
Presentation: Farmer-led climate adaptation - Project launch and overview by ...Presentation: Farmer-led climate adaptation - Project launch and overview by ...
Presentation: Farmer-led climate adaptation - Project launch and overview by ...
 
VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...
VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...
VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...
 
Call Girls Jejuri Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Jejuri Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Jejuri Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Jejuri Call Me 7737669865 Budget Friendly No Advance Booking
 
Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...
Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...
Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...
 
GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756
GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756
GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756
 
Call Now ☎ Russian Call Girls Connaught Place @ 9899900591 # Russian Escorts ...
Call Now ☎ Russian Call Girls Connaught Place @ 9899900591 # Russian Escorts ...Call Now ☎ Russian Call Girls Connaught Place @ 9899900591 # Russian Escorts ...
Call Now ☎ Russian Call Girls Connaught Place @ 9899900591 # Russian Escorts ...
 
RATING SYSTEMS- IGBC, GRIHA, LEED--.pptx
RATING  SYSTEMS- IGBC, GRIHA, LEED--.pptxRATING  SYSTEMS- IGBC, GRIHA, LEED--.pptx
RATING SYSTEMS- IGBC, GRIHA, LEED--.pptx
 
Kondhwa ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Kondhwa ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Kondhwa ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Kondhwa ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
 

Microbial analysis of Heating systems' surfaces

  • 1. International Journal of Environmental & Agriculture Research (IJOEAR) ISSN:[2454-1850] [Vol-2, Issue-12, December- 2016] Page | 137 Microbial analysis of Heating systems' surfaces Olga Rubinová1 , Aleš Rubina2 , Jitka Mohelníková3 Department of building services, Brno University of Technology, Faculty of Civil Engineering, Czech Republic Abstract— An analysis of experimental investigation focused on microbial pollution of heated was carried out for heating systems installed in different types of buildings as residential houses and civil buildings. The results point on importance of maintenance and cleaning the heating systems for quality of indoor air and occupants' comfort. Keywords— building environment, indoor comfort, heating systems, microbial analysis. I. INTRODUCTION Good quality of indoor air is one of the most important requirements for indoor climate comfort. Especially dust concentration of microorganism growth in indoor air are closely related with respiratory problems and in final consequences with serious illnesses [1-3]. Hygienic quality of indoor air and for clearness of building surfaces as well as heating systems are key issues for the indoor climate comfort [4-6]. It has been a subject of the world-wide research programmes [7-11]. Heating systems have to be cleared and repaired. Cleaning of internal surfaces in buildings as floors, furniture, windows, indoor equipment is frequently completed their cleaning of radiators and heating surfaces is often neglected [12-17]. An analysis of experimental investigation focused on microbial pollution of heated surfaces is presented in the article. The analysis was carried out for heating systems installed in different types of buildings as residential houses and civil buildings. The results point on importance of maintenance and cleaning the heating systems for quality of indoor air and occupants' comfort. 1.1 Requirements Microbial climate in buildings is influenced by microorganism concentration in the indoor space [18-23]. The concentration is defined for the Colony Forming Unit-CFU of bacteria or mould per m3 of indoor air. Requirements for the microorganism concentration limits are specified for the controlled built-environment recommendations of hygienic demands for chemical and physical limits for indoor climate comfort in occupied rooms:  Non-acceptable visible mould growth on interior surfaces, it means visible mould growth and also laboratory cultivated mould growth from sampling.  Part from the spaces with extremely clear environment the bacteria concentration maximal concentration of 500 CFU/m3 bacteria and 500 CFU/m3 of mould in indoor air is required. Samplings are laboratory tested in microscopic studies. TABLE 1 CATEGORY OF THE INDOOR AIR POLLUTION IN ACCORDANCE WITH EUR 14988 [22] – CONCENTRATION OF MIXED BACTERIAL POPULATION AND MOULDS IN OCCUPATIONAL AREAS AND IN RESIDENTIAL AREAS Pollution category Occupational areas Rooms in residential houses Bacteria CFU/m3 Mould CFU/m3 Bacteria CFU/m3 Mould CFU/m3 Very low ˂50 ˂25 ˂100 ˂50 Low ˂100 ˂100 ˂500 ˂200 Middle ˂500 ˂500 ˂2500 ˂1000 High ˂2000 ˂2000 ˂10000 ˂10000 Very high ˃2000 ˃ 2000 ˃10000 ˃ 10000 Diagnostics of building state from the microbiological point of view is included into tasks of the environmental session of the European Commission. The EU document 14988 published statistics of investigation in microbiological air pollution in buildings in the EU countries. Results are summarized in Table 1, which gives an overview of the classification of mould and
  • 2. International Journal of Environmental & Agriculture Research (IJOEAR) ISSN:[2454-1850] [Vol-2, Issue-12, December- 2016] Page | 138 bacteria concentration in indoor air volume. Microorganisms are in common dusty air atmosphere. The dust gives growth to the microorganisms. Mould concentration is from 1000 to 100 000 CFU per 1 g of dust. Hygienic limits for many buildings are considered up to the middle pollution category of the concentration of bacteria and moulds. But results of the investigations show that in residential buildings is microbiological pollution of indoor air is really high than the hygienically permitted limits. 1.2 Microorganisms and their influence on people's health Quality of indoor air in building is extremely important for occupants' health. Adults need about 12 000 litres of air per day. Bacteria and microscopic moulds are allergens that because they produce toxins. They can growth and cumulate on interior surfaces. Characteristic feature of microorganisms in buildings is ability to grow in a very small concentration and during convenient hygro-thermal conditions they could significantly increase their growth. Circulated air moves the microorganisms that could be inhaled by the room occupants. In case of high concentration of bacteria and mould microorganisms in indoor air the occupants could be seriously endangered in their health. Tab. 2 gives information about negative influences of myco- toxine microorganisms on living organisms. TABLE 2 SOME MYCOTOXINS AND THEIR NEGATIVE EFFECTS Toxin Producent toxinu Negative effects Aflatoxins Aspergillus flavus Respiration problems and cancer Ochratoxins spieces Apergillus and Penicillium Karcinogen Patulin spieces Apergillus and Penicillium Affection of DNA molecules Trichotecens spieces Stachybotrys and Trichoderma Karcinogen It is not a purpose to create extremely disinfected climate in common buildings. Disinfection for liquidation of vegetative form of microorganisms or sterilization of microorganisms and spores could shave also negative impact for occupants' health. Their immune system is weaken and lose an ability of reaction on the external influences. Total liquidation of microorganisms is important for special purposes for example for operation theatres in hospitals or in special productions as pharmaceutic production etc. Microorganisms detected on surfaces are in many cases different than microorganisms in the air which also must be taken into consideration. II. EXPERIMENTAL TESTING OF RADIATOR SURFACES 2.1 Microorganisms on radiator surfaces in school building Testing of microorganism concentrations on heating systems surfaces was completed within the frame of a research project. The project was focused on the sampling of various systems for heating in buildings. Heating systems at a campus of the Faculty of Civil Engineering, Brno University of Technology were tested in January 2014. Positions of the sampling are shown in the scheme of Figure 1. The Dipslide Labm method was selected for the testing. The contact sampling method is convenient because of easy and quick sampling and low risk of contamination. The sample is sealed in the test tube before and after the test. The sample cultivation is inside of the tube. In this case the cultivation process is not affected by influenced any external influences. The samples of surface microorganisms (Figure 2) were selected for laboratory cultivation (Figure 3). Results determined from the cultivation for the constant thermal conditions (bacteria 3 days, for 30 °C; moulds 5 days for 25 °C) were evaluated for the CFU (Colony Forming Units) per m2 of the surface. Tested heating systems:  Radiator with lamellas – corridor E1 (about 13 years operation).  Radiator without lamellas – corridor E2 (about 2 years operation).  Cast iron articulated radiator – corridor to building D (more than 10 years operation).  Floor convertor without ventilator with Al lamellas air – corridor to building D.
  • 3. International Journal of Environmental & Agriculture Research (IJOEAR) ISSN:[2454-1850] [Vol-2, Issue-12, December- 2016] Page | 139 FIG. 1: SCHEME OF THE FACULTY CAMPUS OF BRNO UNIVERSITY OF TECHNOLOGY POSITIONS 1 TO 4 ARE THE TEST SAMPLING PLACES FLOOR CONVECTOR IN THE CINEMA FLOOR CONVERTOR IN THE UNIVERSITY STUDY ROOM FLOOR CONVERTOR IN RESIDENTIAL BUILDING A SLAB RADIATION IN RESIDENTIAL BUILDING A FLOOR CONVERTOR IN RESIDENTIAL BUILDING B SLAB RADIATION IN RESIDENTIAL BUILDING B FIG. 2: TESTED HEATERS, RADIATORS AND FLOOR HEAT CONVERTORS 4 3 2 1
  • 4. International Journal of Environmental & Agriculture Research (IJOEAR) ISSN:[2454-1850] [Vol-2, Issue-12, December- 2016] Page | 140 Samplings were selected on all heaters and were compared with samplings of interior surfaces. The sampling selection is documented in Figure 3. FIG. 3: POSITIONS OF SAMPLINGS ON THE TESTED HEATER The example of a microbiological sample and its cultivation of bacteria (yellow) and mould (red) of sample 2 (new radiator in school building corridor) is shown in Figure 4. FIG. 3: THE SAMPLES LABORATORY CULTIVATION Bacterial pollution of the heaters is adequate to other tested surfaces in interior. More intensive pollution is on the floor convertor, where there were three types of moulds detected. Results of the laboratory tests of the samplings are shown in Table 3 a Figure 4. TABLE 3 RESULTS OF THE HEATER MICROBIOLOGICAL SAMPLES TESTING Heating system Bacteria CFU/m2 Mould CFU/m2 species Desk radiator – building E1 10600 undetected Desk radiator - building E2 18100 3125 Penicillium Sectional heater - building D 4375 1800 Penicillium Rhizopus Floor convertor - corridor to building D 58750 11900 Aspergillus Penicillium Rhizopus
  • 5. International Journal of Environmental & Agriculture Research (IJOEAR) ISSN:[2454-1850] [Vol-2, Issue-12, December- 2016] Page | 141 Type Rhizopus is thermophile – it means moulds of this type could grow even for temperature of 50 °C. The mould types do not produce mycotoxines, but spores have highly allergenic potential. Type Aspergillus grows under conditions of temperatures 10 to 45 °C, type Penicillium grows from 4 °C. Type Aspergillus produces aflatoxins with carcinogenic effects. FIG. 4: RESULTS OF MICROOGRANISM CULTIVATION ON VARIOUS SURFACES 2.2 Microorganisms in floor convertors The above mentioned results show that the microbial pollution is the most problematic for the floor convertor. It is certainly because of its shape and uneven surface that are and difficult to clean. Especially in dwellings and places with pets as cats or dogs the convertors are very often “dust and hair accumulators”, Figure 5. Dust with organic compounds is a convenient base for the mould growth. For this reason the next research has been focused on the floor convertors. FIG. 5: FLOOR LAMELLAE CONVERTOR OF ROOM OF A FLAT WITH A CAT (TWICE A YEAR CLEARED); DISTANCE OF THE CONVERTOR LAMELLAS IS 3 mm
  • 6. International Journal of Environmental & Agriculture Research (IJOEAR) ISSN:[2454-1850] [Vol-2, Issue-12, December- 2016] Page | 142 On the basis of the above mentioned experiment samples of floor heating convertors were tested. The testing was carried out for the following floor heaters: 1. Floor convertor without ventilator located in circulation area in a cinema building in the city centre (new building – only two years in operation). 2. Floor convertor in a study room of a university library (four years’ operation). 3. Floor convertor in a residential building A (ten years’ operation). 4. Slab radiator in a residential building A. 5. Floor convertor in a residential building B (two years’ operation). 6. Slab radiator in a residential building B. Both of the residential buildings are occupied by four-member families there are no pets in the families. Low-temperature heating systems are in service in those buildings. Results of the tests are presented in Table 4 and Figure 6. TABLE 4 RESULTS OF THE MICROORGANISM CULTIVATION OF THE FLOOR CONVERTORS SAMPLINGS Heating system Bacteria CFU/m2 Mould CFU/m2 spieces Floor convector in the cinema 78750 39400 Penicillium Rhizopus Floor convertor in the university study room 55700 2500 Penicillium Floor convertor in residential building A 18500 5100 Aspergillus Slab radiation in residential building A 7800 1500 Aspergillus Floor convertor in residential building B 13750 undetected - Slab radiation in residential building B 4400 1900 Rhizopus FIG. 6: RESULTS OF THE MICROORGANISM CULTIVATION OF SAMPLES OF FLOOR CONVERTORS
  • 7. International Journal of Environmental & Agriculture Research (IJOEAR) ISSN:[2454-1850] [Vol-2, Issue-12, December- 2016] Page | 143 Microorganism growth was detected for many floor convertors in public buildings. The convertor itself is not source of microorganisms but its construction and surface area and possibility to clean it influences microorganism concentration. Low-temperature heating systems are weak to microorganism growth. Location of these systems is problematical because of floor or very low positioning in the room places with increased concentration of microorganism. Microorganisms are moved by the air circulation inside of the internal spaces in buildings. It can be expected that in public buildings the concentration of microorganisms could be very high because of neglected regular service and cleaning of the heating systems. Moulds and fungy Rhizopus are very rare in buildings but in case that they have convenient conditions they spread and increase their allergenic potential. 2.3 Growth of microorganisms on surfaces of heating systems The next experiment was aimed at the testing of heating surfaces that are commonly cleaned without disinfection detergents. The slab radiator was cleaned and sampled (after 14, 21, 28 and 35 days). Samplings were selected due to surface sponges (3M). Samples were cultivated in laboratory. Two cultivation substances were used - PCA agar for bacteria cultivation and agar with antibiotics for mould cultivation. Samples for the bacteria cultivation were tested for three days at temperature of 30 °C and samples for moulds cultivation for 5 days at 25 °C. The radiator bacterial pollution in forty days in presented in graph of Figure 7. It is clear that the bacteria contamination is exponentially increased in time. FIG. 7: BACTERIAL CONTAMINATION OF THE RADIATOR (COLOUR POINTS – DIFFERENT PLACES OF THE DUST SAMPLING ON THE RADIATOR) III. CONCLUSION Heating radiators a shape that gives possibility to dust settlement on them create opportunity to microorganism growth. It can be problematic in rooms with very low indoor temperature. Low-temperature heating systems with the service water temperature below 50 o C could be affected by microorganisms. It is very important to provide frequent revisions and cleaning of the heating systems in public and residential buildings. Heaters with complicated shape and uneven surface could accumulate dust and for this reason they support the mould growth a microbial concentration. Low-temperature water heater systems (below 50 °C) give growth of mesophile types of organic pollution. For the low-temperature heating systems regular thermic disinfection is recommended for the heaters maintenance. The heaters construction and easy-to-clean surfaces as well as convenient positioning in the building are key factor for elimination of dust concentration and organic pollution. Heaters with lamellas located in floors are directly exposed to the pollution and microbial contamination. Another problem could be uncontrolled amount of dust in places where people do not
  • 8. International Journal of Environmental & Agriculture Research (IJOEAR) ISSN:[2454-1850] [Vol-2, Issue-12, December- 2016] Page | 144 change their shoes. In public buildings with high occupancy the dust contamination was proven much more serious compared to dwelling where people wear clear home shoes. High occupancy has also negative influence on microbial pollution. It seems that frequent and thorough cleaning maintenance of heaters at public buildings is really necessary. Floor convertor heaters are not recommended for spaces with high hygienic demands as hospitals and care homes. Plain surface radiators positioned in easy-to –clean installations would be or convenient in these cases. ACKNOWLEDGEMENTS This article has been worked out under the project No. LO1408 "AdMaS UP - Advanced Materials, Structures and Technologies", supported by Ministry of Education, Youth and Sports under the National Sustainability Programme I" of the Czech Republic. The research is supported by the Specific research at Brno University of Technology, Faculty of Civil Engineering, reg. number FAST-S-15-2620. REFERENCES [1] Wanner H. U. a col. Biological Particles in Indoor Environment, EUR 14988 EN, v ed. Indoor air quality & its impact on man, Report No.12. 1993. [2] Górka-Kostrubiec B., Jeleńska1 M., Król E. Magnetic signature of indoor air pollution: Household dust study. Acta Geophysica. Volume 62, Issue 6, Pages 1478–1503, ISSN (Online) 1895-7455, DOI: 10.2478/s11600-014-0238-1, September 2014. [3] Górka-Kostrubiec B.; The magnetic properties of indoor dust fractions as markers of air pollution inside buildings, Building and Environment, Volume 90, August 2015, Pages 186-195, ISSN 0360-1323. [4] The results of the analysis of metal dust. Protocol EMPLA, Hradec Kralove 2011 (in Czech). http://orgo- net.blogspot.cz/2011/03/vysledky-rozboru-kovoveho-prachu.html. [5] Holopainen, R. et al. (2002), The effect of cleanliness control during installation work on the amount of accumulated dust in ducts of new HVAC installations. Indoor Air, 12: 191–197. doi: 10.1034/j.1600-0668.2002.01119.x [6] Oxkten Suzan, Asan Ahmet; Airborne fungi and bacteria in indoor and outdoor environment of the Pediatric Unit of Edirne; Environ Monit Assess (2012) 184:1739–1751; Springer Science+Business Media B.V. 2011. [7] Yassin, M. F.; Almouqatea, S., (2010). Assessment of airborne bacteria and fungi in an indoor and outdoor environment. Int. J. Environ. Sci. Tech., 7 (3), 535-544. [8] Górny RL, Reponen T, Willeke K, et al. Fungal Fragments as Indoor Air Biocontaminants. Applied and Environmental Microbiology. 2002;68(7):3522-3531 doi:10.1128/AEM.68.7.3522-3531.2002. [9] D. Haas, J. Habib, J. Luxner, H. Galler, G. Zarfel, R. Schlacher, H. Friedl, F.F. Reinthaler: Comparison of background levels of culturable fungal spore concentrations in indoor and outdoor air in southeastern Austria; Atmospheric Environment 98 (2014) 640e647. [10] Linlin Liang, GuenterEngling, YuanCheng, FengkuiDuan, ZhenyuDu, KebinHe; Rapid detection and quantification of fungal spores in the urban atmosphere by flow cytometry; Journal ofAerosolScience, 66(2013)179–186. [11] Taekhee Lee, Sergey A. Grinshpun, Dainius Martuzevicius, Atin Adhikari, Carlos M. Crawford, Tiina Reponen; Culturability and concentration of indoor and outdoor airborne fungi in six single-family homes; Atmospheric Environment 40 (2006) 2902–2910.