SlideShare a Scribd company logo
Alternating Current Power Factor Monitoring and Correction:
Final Project Report
Bryan Underwood
Advisor: Prof. Gutschlag
May 9, 2012
Abstract:
Power factor is the value of a system that reflects how much power is being borrowed from the
power company for the system. Quantitatively, power factor ranges from zero to one and is the cosine
of the difference in the angle between the current and voltage. Many power companies regulate
residential and industrial power factors to make sure that they do not fall below a certain level and
charge the customer more on their utility bills if the power factor falls below a certain level.
Power factor correction serves to correct low power factors by reducing the phase difference between
the current and voltage at the distribution point for a company or residence. The most common way to
correct the power factor is to switch capacitor banks at the source to generate “negative” reactive
power. This project’s goal is to make a system that will switch capacitor banks in and out of the circuit
when the power factor drops below a certain point to avoid power company charges.
Table of Contents:
Introduction…………………………………………………………………………………………........4
System Description……………………………………………………………………………………....5
Equipment List….....……………………………………………………………………………………..5
• Hampden Motor………………………………………………………………………………….6
• SATEC Programmable Logic Controller………………………………………………………...7
• Relays…………………………………………………………………………………………….9
• Capacitor Banks……………………………………………………………………………….....9
• Damping Resistors……………………………………………………………………………...10
Software………………………………………………………………………………………………...11
Results………………………………………………………………………..…………………………12
SATEC Programmable Logic Controller Tutorial……………………………………………………...15
Introduction:
Power factor is the value of a system that reflects how much power is being borrowed from the power
company for the system. Quantitatively, power factor ranges from zero to one and is the cosine of the
difference in the angle between the current and voltage. Poor power factors are due to inductive loads
such as the induction motors found in air conditioners and refrigerators.
According to Pacific Gas & Electric Company, about 60% of all loads in the United States are electric
motors. This fact in combination with the United States Energy Information Administration (EIA)
statistic of only about 25,000 out of 200,000 manufacturing companies participating in power factor
correction, illustrates a need for companies to implement power factor correction devices to improve
efficiency and reduce energy waste.
One incentive for companies to install power factor correction devices is the charges that many utility
companies impose for falling below a certain power factor. For example, Ameren Illinois requires
customers to install power factor correction devices on their system if the power factor falls below
0.85. If the customer does not install any devices then Ameren can actually come out to the customer’s
property and install devices themselves and charge the customer a hefty rate for doing so.
Pacific Gas & Electric (PG&E) charges 0.6% for each percentage point of power factor below 0.85 on
a utility bill. So if a customer’s utility bill is $10,000 and has an average power factor of 0.83 for the
month, the customer would be charge 1.2% of the total bill more because of that low power factor.
PG&E also provides an incentive to maintain a power factor above 0.85 as well. If a customer has a
power factor above 0.85 the customer receives a credit equal to the process described above instead of
a charge.
There are also a couple of reasons for power companies to be concerned with low power factor. One of
the most important reasons they are concerned is the power losses that occur through their transmission
lines or the “I squared R losses.” This is power that the customer never uses and is not charged for.
This is a problem both for generating and distribution companies as a distribution company might be
charged for running at a low power factor in their system by a generating company. These charges
incurred are also important for keeping power companies’ rates low to remain competitive.
With several power companies offering incentives and most power companies charging some type of
fee for falling below their specified power factor, some may wonder why companies do not actively
pursue to improve their power factor. This can be due to several factors. One is that the companies’
administrators do not think the company will be able to recover costs from installing power factor
correction devices. Another is that some companies might not have enough inductive loads to be
concerned about power factor at all.
Power factor correction acts to improve poor power factors by keeping a customer’s power factor
above the level specified by the power company. The most common method of controlling power is by
the use of switching capacitor banks and was the method implemented in this project. Capacitor banks
generate “negative” reactive power or absorb the reactive power produced by inductive loads.
However, it is possible to add too much capacitance to the system and still incur power company
charges. This occurs when the amount of capacitance added is so much greater than the inductance of
the system that the power factor goes below 0.85 leading. The goal of this project was to obtain a
power factor as close to one as possible or to control the system power factor within a range that will
avoid any power company charges possible.
System Description:
Figure 4-1, System Diagram
A 120 [VAC] source was used to power an inductive load as seen in Figure 4-1 above, since the
load power factor can be easily changed by adjusting the inductance of the load. The load used in this
project was a three phase Hampden 1.4[A] 1/3 [HP] motor with attached pony brake to easily vary the
power factor of the motor. Capacitor banks were used in parallel with the motor to improve the power
factor due to the inductive load. The SATEC programmable power meter shown in Figure 2-1 was
used to measure the power factor, current, voltage, and the active, reactive, and apparent power. The
meter was also used to energize the relays that switched the capacitors in and out of the system. The
software program, Power Analysis Software, used with the power meter allowed to specify a set point
that when set to true, switched on a relay when the power factor dropped below a certain point.
Equipment List:
Hampden Type WRM-100 Three Phase Motor
Figure 6-1, Hampden Motor with Attached Load
Motor is rated at 1.4 [A] 220 [VAC] 1725 RPM 1/3 [HP]. Shown in Figure 6-1, attached is a pony
brake load that allows varying the power factor of the motor. The top of the pony brake is cut off, but
the load is varied by a knob that is twisted. A force meter is also attached so that efficiency can be
measured by calculating the torque of the motor at various loads. A tachometer was also used to
measure the RPM output of the motor. The torque was then multiplied by the output speed in radians
per second gave the output power of the motor. This output power was divided by input power, which
was obtained from meter readings, and multiplied by one hundred to obtain efficiency. A graph of
these results was prepared and compared against power factor and is shown on the next page.
Motor Power Factor and Efficiency:
Figure 7-1, Motor Power Factor vs Efficiency
As can be seen from Figure 7-1 the motor’s power factor is variable from about 0.3 to about 0.8
lagging. This provides a wide range in which to test different values of capacitance to switch in and
out of the system. The power factor also generally increases with motor efficiciency until an output
power of about 150 W. At this point the efficiency of the motor begins to level off at about fifty five
percent while the power factor continues to rise to its maximum value of about 0.8 lagging.
SATEC PM172E-N Three Phase Programmable Logic Controller
Figure 7-2, SATEC Programmable Logic Controller
The SATEC programmable logic controller was used as the meter for this project along with the energy
source used to energize the relays used for switching. The data values taken from the meter for this
project are the line to nuetral voltages, active power, power factor, apparent power, reactive power, line
currents, and the individual line powers and power factors. The controller is programmed either by the
buttons provided on the front of the meter or through SATEC’s free software program, Power Analysis
Software (PAS). This software allows the user to program set points that perform a certain action
when one or multiple conditions are set. One such action that can be taken is to energize or release
realys based on what the power factor of the system is. The software also provides several charts and
graphs that either stored data or real time data from the controller. A tutorial of the main functions of
the controller is provided at the end of this report.
Alternative Controllers:
It should be noted that there are other programmable logic controllers available and a lot of them have
more than two relay inputs and outputs. These alternative controllers also may have more
programming options, such as the ability to set an action when the power factor goes above a certain
point instead of only below as is the case for the controller used for this project. Two of the main
companies that make these other controllers are Schweitzer Engineering Laboratories and General
Electric Company. For this project, this controller was graciously loaned from Ameren Corporation so
it was the controller that was used.
The two controllers shown in Figure 8-1 and Figure 8-2 are two examples of alternative controllers that
can be used. The controller shown in Figure 8-1 is a Schweitzer Engineering Laboratory 734B Logic
Controller. The controller shown in Figure 8-2 is a General Electric PM35 Logic Controller.
Figure 8-1, SEL PLC Figure 8-2, GE PLC
Potter & Brumfield KRPA-11AG-120 Power Relays
Figure 9-1 shows the relays that were used to switch the capacitor banks in and out of the circuit.
These relays were controlled by the SATEC PLC and were also generously donated by Ameren
Corporation. Figure 9-2 is a side view of the relays.
Figure 9-1, Top View of Relay Figure 9-2, Side View of Relay
Capacitor Banks
These were the capacitor banks used in this project. There are two values of steps that could be used
with the range of capacitance per step that was able to be switched into the system was 1.6uF to 50uF.
Figure 9-3 shows a maximum value of 50uF capacitor bank with switches that enable different values
of capacitance to be configured. Figure 9-4 switches in the same way, but contains only a maximum
capacitance of 40uF.
Figure 9-3, 50uF Capacitor Bank Figure 9-4, 40uF Capacitor Bank
Damping Resistors:
Damping resistors are placed in series with the capacitors that are being switched into the system to
limit the inrush current that occurs. Figure 10-1 shows a resistor valued at 25 ohms. This inrush
current occurs because when a capacitor is switched on initially it looks like a short circuit and draws
very large currents for a short amount of time. Normally in a power factor correction system these
resistors are only placed in series with the capacitors for a very short amount of time to limit these
inrush currents and avoid excessive power losses due to the resistors. After this short amount of time,
the resistors are switched out of the circuit and the capacitors remain in parallel with the load. Due to
the limited about of relay outputs available on the controller used for this project, the damping resistors
were kept in series with the capacitors and losses were calculated.
Current through 10uF Capacitor
Power Losses
Current through 20uF Capacitor
Power Losses
Current through 30uF Capacitor
Power Losses
Figure 10-1, Damping Resistor 25 ohms
][6159.84450395.0
6159.84433.266
0120
AI °∠=
°−∠
°∠
=
][07139.525*)450395.0( 22
WRIP ===
][3252.79889119.0
3252.79965.134
0120
AI °∠=
°−∠
°∠
=
][7633.19 WP =
][2121.7430597.1
2121.748857.91
0120
AI °∠=
°−∠
°∠
=
][639.42 WP =
Software:
The software used in this project is the Power Analysis Software available directly from SATEC’s
website. There is no code involved with programming the meter so there is no specific programming
language. Rather, several graphical user interfaces (GUI) are provided to program the meter. One
example is shown in Figure 11-1 below.
Figure 7-1, Software Set Point
This is the menu provided to program set points to the meter. With set points, the user can specify
certain conditions that need to occur for one or several actions to occur. In the figure above, the set
point becomes true and relay one is operated when the current in line A is above 0.1 Amps and the
power factor of the system is below 0.85 lagging. In addition to the relay being operated, the controller
records this event in the event log contained within the controller that is viewable by the program. This
set point can be described by the flow chart in Figure 11-2 and also is the process at which the system
in this project operates.
Flow Chart:
Figure 7-2, Software Flow Chart
Beginning at the top of Figure 7-2 once the controller powers up, it checks to see whether a load is
present by checking whether there is any line current in the system and if no current is present, any
relays that are on are turned off and this check is repeated. If there is current then the meter checks to
see if the system is running at a power factor below 0.85 lagging and if it is the relays are energized and
the capacitor banks are switched into the system. The check for line current and a lagging power factor
continue until the meter is powered down.
Results:
To determine what value of capacitance needed to be switched into the system, a theoretical model of
the motor was made. The magnitude of impedance of the motor was found by dividing the voltage by
the current of a single line of the motor. The phase angle of the impedance was found by taking the
inverse cosign of the power factor of the motor. The impedance of the motor was recorded at four
different power factors, 0.3, 0.45, 0.6, and 0.78 lagging. Five different values of capacitances were
each added with each of the different power factors. Once the model of the motor was developed, the
damping resistor and capacitor bank were added in parallel and the equivalent impedance was found.
This allowed a calculation of the phase angle of the total impedance and the cosign of this angle was
taken to obtain a source power factor. A table, Figure 12-1, and a graph, Figure 12-2, are shown below.
Any value above one should be subtracted from two and taken as a leading power factor.
0.3 0.45 0.6 0.78
10uF 0.609445 0.74704 0.855108 0.933201
15uF 0.873233 0.928109 0.964573 0.983411
20uF 0.999937 0.999926 1.00002 0.999972
30uF 1.13754 1.09493 1.06663 1.03199
40uF 1.21777 1.17129 1.13211 1.07689
Figure 12-1, Theoretical Values
Figure 12-2, Theoretical Graph
As can be seen from Figure 12-2, it is desired to use 20uF of capacitance per phase to increase power
factor to near unity and avoid any power company charges. Data was taken at the different values of
capacitance from the controller to confirm that 20uF was the ideal capacitane for this project. A
comparison of experimental and theoretical results is shown below. Again, any value over one
represents a leading power factor and should be subtracted from two to find the value of that power
factor.
Figure 13-1, Theoretical and Experimental Values
Figure 13-2, Theoretical and Experimental Values
0.3 0.45 0.6 0.78
10uF Meter 0.5815 0.704 0.85 0.93
15uF Meter 0.845 0.906 0.944 0.972
20uF Meter 0.992 0.997 0.999 0.999
30uF Meter 1.097 1.076 1.049 1.02
40uF Meter 1.196 1.154 1.1 1.074
10uF 0.609445 0.74704 0.855108 0.933201
15uF 0.873233 0.928109 0.964573 0.983411
20uF 0.999937 0.999926 1.00002 0.999972
30uF 1.13754 1.09493 1.06663 1.03199
40uF 1.21777 1.17129 1.13211 1.07689
A final picture of the system is shown in Figure 14-1. The motor seen on the right has the attached
pony brake and is currently running. This is shown by the controller in between the two capacitor
banks. The controller is currently measuring the apparent power, power factor, and active power.
Behind the controller is the fused power source, with several neutral points being used and a ground.
The damping resistors are right in front of the capacitor banks, but connected in series with them.
Finally, Power Analysis Software can be seen on the computer displaying real time values of the
system including individual active powers, line voltages, and individual line power factors.
Figure 14-1, Picture of Current System
Satec PM172-N Programmable Logic Controller and Power Analysis Software Tutorial:
Powering Controller and Communicating with Computer:
To power up the meter, a 120 [VAC] source is needed along with a ground and neutral connection.
These are connected to ports 10, 12 and ground as demonstrated in Figure 9-1 below.
Figure 9-1, Terminal Connections
When connecting the controller to line voltage and current there are several different wiring modes
available and depending on which are available the controller will need to be told which ones to use.
These settings can be set in the meter or the software program. One such configuration and the one
used in this project can be seen in Figure 10-1.
Figure 10-1, 4LL3 or 4Ln3 Wiring Configuration
Note in the above diagram that current transformers are used. The controller can be told what ratio of
potential and current transformers are used if not directly connecting the controller to line power.
The controller is able to be programmed from the front to do and see anything that would be set or seen
in the software program. As there are easily over two hundred settings and measurements that can be
viewed, this tutorial will only cover the settings used in this project and will only cover which method
was used to configure these settings. The rest can be found in the manual downloaded from the
SATEC website.
The most common way to connect the controller to a computer to view data or configure settings is
through a serial port connection, although an adapter can be bought to communicate over ethernet or
dial up. This serial port connection also needs to use a null modem cord and not a straight modem
cord, otherwise the controller will not respond to computer commands.
When using the Power Analysis Software, the user can create multiple databases corresponding to each
controller connected. For this project since only one controller was used, there was no need to create
multiple databases and remained with the default database.
To set up communications with the controller press Configuration from the Tools menu at the top and
select the site database to be used along with the model number of the controller, which for this project
was PM172-N.
The Device Address, Device ID, and Sampling Rate settings in the software need to match the settings
contained in the controller. To check the settings in the controller, press select and three options should
appear as Sta, Ops, and Chg as seen in Figure 11-1.
To move through these menus on the controller use the select button, while
pressing enter will enter that menu. To check the status of a setting the Sta
menu will be used, while changing a setting will require the Chg menu. Now
scroll through the menu that should appear like Figure 11-2.
Figure 11-1, Select Menu
Press the UP or DOWN button to scroll through these options with the top menu
highlighted until Prt.1 is blinking and press enter. Then use the up and down arrows
to scroll the different settings available for communications and make sure these
correspond to the settings in the software. This process is shown in Figure 11-3.
Figure 11-2, Status Menus
Figure 11-3, Diagram Showing Route to Communication Settings
Once all of the communication settings for the controller have been set, communications can be tested
by powering up the controller and setting the software to go “on-line.” This is a state in which the
software can communicate with the controller to read or send settings and read data. The button that
takes the controller on-line is to the right of the drop down menu where the database being used in
located. When pressed, communications are tested by trying to communicate with the controller in
anyway. The most common method used is selected the plus sign next to the database name in the tree
located in the right panel of the program.
Configuring Basic Device Setup:
The basic device settings need to be setup for the controller in order for data to be correctly read.
These settings can be accessed in two ways; the first is to select General Setup under the MeterSetup
menu at the top next to the Logs menu. The other way is to select the plus sign next to your database
name in the right panel and then the plus sign next to General Setup and finally double click Basic
Setup. This will bring up a window that contains the basic configuration settings on the meter starting
with wiring mode. For this project, the only setting that needed to be confirmed was the wiring mode,
PT ratio and multiplier, and the nominal frequency. Notice, that all the tabs at the top of this window
correspond to the options under General Setup, therefore all options can be accessed by clicking the
tabs at the top of the window. In the panel at the right the Memory/Log, Energy/TOU Setup,
Communication Setup, and Protocol Setup were not used in this project.
Viewing Data:
When the controller is initially power on, the line to neutral voltages are displayed which is shown by
the L present in the bottom left corner. To scroll through the measurements, the up and downs arrows
are used and if the down arrow is pressed the line to line voltages are displayed which is shown by a P.
The next set of measurements will be the line currents and the next measurements are the apparent
power, power factor, and real power respectively. The last set of menus displays the neutral line
current, frequency, and the reactive power.
These values can also be viewed in the software along with many other data. To view real time values
in chart or graph form, go to the monitor menu at the top and scroll over RT data monitor. This will list
all the available chart or graph types that can be read. The ones used in the project are the Data Set 1
Real Time Measurements and Data Set 2 Average Measurements. Initially, the chart form of data is
shown, but graph form can be displayed by pressing the first top left button that is called data trend
when hovered over. When in chart form, the data displayed can be changed for any data set by
pressing the fifth button from the left that when hovered over is called data set. For changing data
values displayed in the graph, the fifth button from the left is pressed.
An event log that displays user defined events, when set points are set, and when the controller is
powered up or down. This event log can be found by selecting the event log under the logs menu at the
top. This event log is very useful for viewing when a set point has been activated or released and when
the set points were sent to the controller.
Programming Set Points:
The set point menus can be accessed from the same window that was used to access the Basic Setup
Menu. Click the Control/Alarm Setpoints tab and there should be a drop down menu where the set
point number is chosen, a triggers box where logic operators, trigger parameters, and operate and
release limits are set, an actions box where actions to take when the set point becomes true, and a box
for operate and release delays.
For this project the three important trigger parameters that were used are the LO PF LAG AVR, LO PF
LEAD AVR, and HI I1 AVR. The operate parameter for a lagging power factor was set at 0.85 while
the release limit was at 1.0. This was anded with the current parameter to ensure the relays only switch
when line current is present. The set point became true when the power factor at the source fell below
0.85 lagging and line current is present. The actions taken were OPERATE RELAY #1 and EVENT
LOG. The operate relay action sent a signal out of the relay output #1 from the controller and the event
log action logged that the set point was evaluated to be true.
To send the current configuration to the controller there is a send button in the bottom left of the
window. Configurations can be saved and loaded into the databases mention earlier by pressing the
save as button and selecting the database pertinent to the controller being programmed.

More Related Content

What's hot

INTELLIGENT AUTOMATIC POWER FACTOR CORRECTION
INTELLIGENT AUTOMATIC POWER FACTOR CORRECTIONINTELLIGENT AUTOMATIC POWER FACTOR CORRECTION
INTELLIGENT AUTOMATIC POWER FACTOR CORRECTION
ijiert bestjournal
 
Automatic Power Factor Improvement by Using PLC & SCADA
Automatic Power Factor Improvement by Using PLC & SCADAAutomatic Power Factor Improvement by Using PLC & SCADA
Automatic Power Factor Improvement by Using PLC & SCADA
ferozpatowary
 
IRJET- PV System Connected High Step-Up Boost DC-DC Converter based Voltag...
IRJET- 	  PV System Connected High Step-Up Boost DC-DC Converter based Voltag...IRJET- 	  PV System Connected High Step-Up Boost DC-DC Converter based Voltag...
IRJET- PV System Connected High Step-Up Boost DC-DC Converter based Voltag...
IRJET Journal
 
Compensation of harmonic currents utilizing AHC by kingsprime
Compensation of harmonic currents utilizing AHC by kingsprimeCompensation of harmonic currents utilizing AHC by kingsprime
Compensation of harmonic currents utilizing AHC by kingsprime
Kalu Kingsley Ekperebuike
 
Dc dc sepic converter topologies
Dc dc sepic converter topologiesDc dc sepic converter topologies
Dc dc sepic converter topologies
eSAT Journals
 
IRJET- Automated Energy Monitering System and Power Factor Improvement
IRJET-  	  Automated Energy Monitering System and Power Factor ImprovementIRJET-  	  Automated Energy Monitering System and Power Factor Improvement
IRJET- Automated Energy Monitering System and Power Factor Improvement
IRJET Journal
 
IRJET- Interleaved DC-DC Boost Converter with High Voltage Gain and Effic...
IRJET-  	  Interleaved DC-DC Boost Converter with High Voltage Gain and Effic...IRJET-  	  Interleaved DC-DC Boost Converter with High Voltage Gain and Effic...
IRJET- Interleaved DC-DC Boost Converter with High Voltage Gain and Effic...
IRJET Journal
 
950313411009
950313411009950313411009
950313411009
nagarajaan
 
Simulation of DVR for power Quality Improvement by using Ultra Capacitor
Simulation of DVR for power Quality Improvement by using Ultra CapacitorSimulation of DVR for power Quality Improvement by using Ultra Capacitor
Simulation of DVR for power Quality Improvement by using Ultra Capacitor
IRJET Journal
 
IRJET- Design and Implementaion of DC-DC Boost Converter using Output Voltage...
IRJET- Design and Implementaion of DC-DC Boost Converter using Output Voltage...IRJET- Design and Implementaion of DC-DC Boost Converter using Output Voltage...
IRJET- Design and Implementaion of DC-DC Boost Converter using Output Voltage...
IRJET Journal
 
Minimizing Penalty in Industrial Power Consumption by Engaging APFC Unit : A ...
Minimizing Penalty in Industrial Power Consumption by Engaging APFC Unit : A ...Minimizing Penalty in Industrial Power Consumption by Engaging APFC Unit : A ...
Minimizing Penalty in Industrial Power Consumption by Engaging APFC Unit : A ...
IRJET Journal
 
IRJET- Design and Performance Analysis of Three-Phase Solar PV Integrated UPQC
IRJET- Design and Performance Analysis of Three-Phase Solar PV Integrated UPQCIRJET- Design and Performance Analysis of Three-Phase Solar PV Integrated UPQC
IRJET- Design and Performance Analysis of Three-Phase Solar PV Integrated UPQC
IRJET Journal
 
Voltage Sag Mitigation in Utility Connected System Using Current Source Conve...
Voltage Sag Mitigation in Utility Connected System Using Current Source Conve...Voltage Sag Mitigation in Utility Connected System Using Current Source Conve...
Voltage Sag Mitigation in Utility Connected System Using Current Source Conve...
IDES Editor
 
IRJET- Improved Power Quality Switched Inductor Cuk Converter for Battery Cha...
IRJET- Improved Power Quality Switched Inductor Cuk Converter for Battery Cha...IRJET- Improved Power Quality Switched Inductor Cuk Converter for Battery Cha...
IRJET- Improved Power Quality Switched Inductor Cuk Converter for Battery Cha...
IRJET Journal
 
Enhancement of power quality in distribution system by using D-STATCOM
Enhancement of power quality in distribution system by using D-STATCOMEnhancement of power quality in distribution system by using D-STATCOM
Enhancement of power quality in distribution system by using D-STATCOM
Eng Ahmed Salad Osman
 
Simulation Analysis of Ac/Dc Adapter Under Zero No-Load Power Consumption usi...
Simulation Analysis of Ac/Dc Adapter Under Zero No-Load Power Consumption usi...Simulation Analysis of Ac/Dc Adapter Under Zero No-Load Power Consumption usi...
Simulation Analysis of Ac/Dc Adapter Under Zero No-Load Power Consumption usi...
IJPEDS-IAES
 
Enhancement of power quality in a
Enhancement of power quality in a Enhancement of power quality in a
Enhancement of power quality in a
eSAT Journals
 
IRJET - Voltage Stability Improvement by using STATCOM
IRJET - Voltage Stability Improvement by using STATCOMIRJET - Voltage Stability Improvement by using STATCOM
IRJET - Voltage Stability Improvement by using STATCOM
IRJET Journal
 
Automatic Phase Changer
Automatic Phase ChangerAutomatic Phase Changer
Automatic Phase Changer
Bhanu Bhawesh
 
Highly efficient Active Front End enables trouble free operation of low harmo...
Highly efficient Active Front End enables trouble free operation of low harmo...Highly efficient Active Front End enables trouble free operation of low harmo...
Highly efficient Active Front End enables trouble free operation of low harmo...
Schneider Electric
 

What's hot (20)

INTELLIGENT AUTOMATIC POWER FACTOR CORRECTION
INTELLIGENT AUTOMATIC POWER FACTOR CORRECTIONINTELLIGENT AUTOMATIC POWER FACTOR CORRECTION
INTELLIGENT AUTOMATIC POWER FACTOR CORRECTION
 
Automatic Power Factor Improvement by Using PLC & SCADA
Automatic Power Factor Improvement by Using PLC & SCADAAutomatic Power Factor Improvement by Using PLC & SCADA
Automatic Power Factor Improvement by Using PLC & SCADA
 
IRJET- PV System Connected High Step-Up Boost DC-DC Converter based Voltag...
IRJET- 	  PV System Connected High Step-Up Boost DC-DC Converter based Voltag...IRJET- 	  PV System Connected High Step-Up Boost DC-DC Converter based Voltag...
IRJET- PV System Connected High Step-Up Boost DC-DC Converter based Voltag...
 
Compensation of harmonic currents utilizing AHC by kingsprime
Compensation of harmonic currents utilizing AHC by kingsprimeCompensation of harmonic currents utilizing AHC by kingsprime
Compensation of harmonic currents utilizing AHC by kingsprime
 
Dc dc sepic converter topologies
Dc dc sepic converter topologiesDc dc sepic converter topologies
Dc dc sepic converter topologies
 
IRJET- Automated Energy Monitering System and Power Factor Improvement
IRJET-  	  Automated Energy Monitering System and Power Factor ImprovementIRJET-  	  Automated Energy Monitering System and Power Factor Improvement
IRJET- Automated Energy Monitering System and Power Factor Improvement
 
IRJET- Interleaved DC-DC Boost Converter with High Voltage Gain and Effic...
IRJET-  	  Interleaved DC-DC Boost Converter with High Voltage Gain and Effic...IRJET-  	  Interleaved DC-DC Boost Converter with High Voltage Gain and Effic...
IRJET- Interleaved DC-DC Boost Converter with High Voltage Gain and Effic...
 
950313411009
950313411009950313411009
950313411009
 
Simulation of DVR for power Quality Improvement by using Ultra Capacitor
Simulation of DVR for power Quality Improvement by using Ultra CapacitorSimulation of DVR for power Quality Improvement by using Ultra Capacitor
Simulation of DVR for power Quality Improvement by using Ultra Capacitor
 
IRJET- Design and Implementaion of DC-DC Boost Converter using Output Voltage...
IRJET- Design and Implementaion of DC-DC Boost Converter using Output Voltage...IRJET- Design and Implementaion of DC-DC Boost Converter using Output Voltage...
IRJET- Design and Implementaion of DC-DC Boost Converter using Output Voltage...
 
Minimizing Penalty in Industrial Power Consumption by Engaging APFC Unit : A ...
Minimizing Penalty in Industrial Power Consumption by Engaging APFC Unit : A ...Minimizing Penalty in Industrial Power Consumption by Engaging APFC Unit : A ...
Minimizing Penalty in Industrial Power Consumption by Engaging APFC Unit : A ...
 
IRJET- Design and Performance Analysis of Three-Phase Solar PV Integrated UPQC
IRJET- Design and Performance Analysis of Three-Phase Solar PV Integrated UPQCIRJET- Design and Performance Analysis of Three-Phase Solar PV Integrated UPQC
IRJET- Design and Performance Analysis of Three-Phase Solar PV Integrated UPQC
 
Voltage Sag Mitigation in Utility Connected System Using Current Source Conve...
Voltage Sag Mitigation in Utility Connected System Using Current Source Conve...Voltage Sag Mitigation in Utility Connected System Using Current Source Conve...
Voltage Sag Mitigation in Utility Connected System Using Current Source Conve...
 
IRJET- Improved Power Quality Switched Inductor Cuk Converter for Battery Cha...
IRJET- Improved Power Quality Switched Inductor Cuk Converter for Battery Cha...IRJET- Improved Power Quality Switched Inductor Cuk Converter for Battery Cha...
IRJET- Improved Power Quality Switched Inductor Cuk Converter for Battery Cha...
 
Enhancement of power quality in distribution system by using D-STATCOM
Enhancement of power quality in distribution system by using D-STATCOMEnhancement of power quality in distribution system by using D-STATCOM
Enhancement of power quality in distribution system by using D-STATCOM
 
Simulation Analysis of Ac/Dc Adapter Under Zero No-Load Power Consumption usi...
Simulation Analysis of Ac/Dc Adapter Under Zero No-Load Power Consumption usi...Simulation Analysis of Ac/Dc Adapter Under Zero No-Load Power Consumption usi...
Simulation Analysis of Ac/Dc Adapter Under Zero No-Load Power Consumption usi...
 
Enhancement of power quality in a
Enhancement of power quality in a Enhancement of power quality in a
Enhancement of power quality in a
 
IRJET - Voltage Stability Improvement by using STATCOM
IRJET - Voltage Stability Improvement by using STATCOMIRJET - Voltage Stability Improvement by using STATCOM
IRJET - Voltage Stability Improvement by using STATCOM
 
Automatic Phase Changer
Automatic Phase ChangerAutomatic Phase Changer
Automatic Phase Changer
 
Highly efficient Active Front End enables trouble free operation of low harmo...
Highly efficient Active Front End enables trouble free operation of low harmo...Highly efficient Active Front End enables trouble free operation of low harmo...
Highly efficient Active Front End enables trouble free operation of low harmo...
 

Viewers also liked

Micro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportMicro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System Report
Theory to Practical
 
Jinpat Precise Sip Ring , Fiber Optical Rotary Joint
Jinpat Precise Sip Ring , Fiber Optical Rotary Joint Jinpat Precise Sip Ring , Fiber Optical Rotary Joint
Jinpat Precise Sip Ring , Fiber Optical Rotary Joint
Sarah Wu
 
Vaisala Capital Markets Day 2014 - Energy
Vaisala Capital Markets Day 2014 - EnergyVaisala Capital Markets Day 2014 - Energy
Vaisala Capital Markets Day 2014 - EnergyVaisala Group
 
Vaisala Capital Markets Day 2014 - Weather
Vaisala Capital Markets Day 2014 - WeatherVaisala Capital Markets Day 2014 - Weather
Vaisala Capital Markets Day 2014 - WeatherVaisala Group
 
Global Validation of the REST2 Solar Model From Vaisala
Global Validation of the REST2 Solar Model From VaisalaGlobal Validation of the REST2 Solar Model From Vaisala
Global Validation of the REST2 Solar Model From Vaisala
Gwendalyn Bender
 
FMI Open Data Interface and Data Models
FMI Open Data Interface and Data ModelsFMI Open Data Interface and Data Models
FMI Open Data Interface and Data Models
Roope Tervo
 
Open Weather Data as Part of Big Data
Open Weather Data as Part of Big DataOpen Weather Data as Part of Big Data
Open Weather Data as Part of Big Data
Roope Tervo
 
Trolley Wheel Assembly
Trolley Wheel AssemblyTrolley Wheel Assembly
Trolley Wheel Assembly
Shaun Cappelluti
 
Probing the atmosphere - new radar & lidar technologies for remote sensing of...
Probing the atmosphere - new radar & lidar technologies for remote sensing of...Probing the atmosphere - new radar & lidar technologies for remote sensing of...
Probing the atmosphere - new radar & lidar technologies for remote sensing of...
CLIC Innovation Ltd
 
PIC based automatic fire fighting robot
PIC based automatic fire fighting robotPIC based automatic fire fighting robot
PIC based automatic fire fighting robot
kitta1010
 
Advances in polarimetric X-band weather radar
Advances in polarimetric X-band weather radarAdvances in polarimetric X-band weather radar
Advances in polarimetric X-band weather radar
tobiasotto
 
Fire fighting robot remotely operated by android applications
Fire fighting robot remotely operated by android applicationsFire fighting robot remotely operated by android applications
Fire fighting robot remotely operated by android applications
Edgefxkits & Solutions
 
Rf controlled fire fighting robot
Rf controlled fire fighting robotRf controlled fire fighting robot
Rf controlled fire fighting robotPRADEEP Cheekatla
 
mechanical eng anna university final year Project thesis of bio plastics
mechanical eng anna university final year Project thesis of bio plastics mechanical eng anna university final year Project thesis of bio plastics
mechanical eng anna university final year Project thesis of bio plastics
Pichaimuthu MPM
 
Fire fighting robot ppt
Fire fighting robot pptFire fighting robot ppt
Fire fighting robot ppt
athmeg
 
Automatic power factor correction
Automatic power factor correction Automatic power factor correction
Automatic power factor correction
VIKAS KUMAR MANJHI
 
Principle of FMCW radar
Principle of FMCW radarPrinciple of FMCW radar
Principle of FMCW radar
tobiasotto
 

Viewers also liked (20)

Micro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportMicro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System Report
 
Jinpat Precise Sip Ring , Fiber Optical Rotary Joint
Jinpat Precise Sip Ring , Fiber Optical Rotary Joint Jinpat Precise Sip Ring , Fiber Optical Rotary Joint
Jinpat Precise Sip Ring , Fiber Optical Rotary Joint
 
Vaisala Capital Markets Day 2014 - Energy
Vaisala Capital Markets Day 2014 - EnergyVaisala Capital Markets Day 2014 - Energy
Vaisala Capital Markets Day 2014 - Energy
 
Vaisala Capital Markets Day 2014 - Weather
Vaisala Capital Markets Day 2014 - WeatherVaisala Capital Markets Day 2014 - Weather
Vaisala Capital Markets Day 2014 - Weather
 
Global Validation of the REST2 Solar Model From Vaisala
Global Validation of the REST2 Solar Model From VaisalaGlobal Validation of the REST2 Solar Model From Vaisala
Global Validation of the REST2 Solar Model From Vaisala
 
FMI Open Data Interface and Data Models
FMI Open Data Interface and Data ModelsFMI Open Data Interface and Data Models
FMI Open Data Interface and Data Models
 
Open Weather Data as Part of Big Data
Open Weather Data as Part of Big DataOpen Weather Data as Part of Big Data
Open Weather Data as Part of Big Data
 
Trolley Wheel Assembly
Trolley Wheel AssemblyTrolley Wheel Assembly
Trolley Wheel Assembly
 
Firebot
FirebotFirebot
Firebot
 
Probing the atmosphere - new radar & lidar technologies for remote sensing of...
Probing the atmosphere - new radar & lidar technologies for remote sensing of...Probing the atmosphere - new radar & lidar technologies for remote sensing of...
Probing the atmosphere - new radar & lidar technologies for remote sensing of...
 
PIC based automatic fire fighting robot
PIC based automatic fire fighting robotPIC based automatic fire fighting robot
PIC based automatic fire fighting robot
 
final bs project
final bs projectfinal bs project
final bs project
 
Advances in polarimetric X-band weather radar
Advances in polarimetric X-band weather radarAdvances in polarimetric X-band weather radar
Advances in polarimetric X-band weather radar
 
Fire fighting robot remotely operated by android applications
Fire fighting robot remotely operated by android applicationsFire fighting robot remotely operated by android applications
Fire fighting robot remotely operated by android applications
 
Rf controlled fire fighting robot
Rf controlled fire fighting robotRf controlled fire fighting robot
Rf controlled fire fighting robot
 
mechanical eng anna university final year Project thesis of bio plastics
mechanical eng anna university final year Project thesis of bio plastics mechanical eng anna university final year Project thesis of bio plastics
mechanical eng anna university final year Project thesis of bio plastics
 
Fire fighting robot ppt
Fire fighting robot pptFire fighting robot ppt
Fire fighting robot ppt
 
Automatic power factor correction
Automatic power factor correction Automatic power factor correction
Automatic power factor correction
 
Floods
FloodsFloods
Floods
 
Principle of FMCW radar
Principle of FMCW radarPrinciple of FMCW radar
Principle of FMCW radar
 

Similar to Final project report

Bg4201393395
Bg4201393395Bg4201393395
Bg4201393395
IJERA Editor
 
IRJET- Automatic Power Factor Correction
IRJET- Automatic Power Factor CorrectionIRJET- Automatic Power Factor Correction
IRJET- Automatic Power Factor Correction
IRJET Journal
 
Apfc project 2016 17
Apfc project 2016 17Apfc project 2016 17
Apfc project 2016 17
Tejas Gramopadhye
 
Power Factor & Utility Rates
Power Factor & Utility RatesPower Factor & Utility Rates
Power Factor & Utility Rates
John Wolfram
 
Notes of Load Shifting, Motor Drive, Lighting System, Selection of UPS.
Notes of Load Shifting, Motor Drive, Lighting System, Selection of UPS.Notes of Load Shifting, Motor Drive, Lighting System, Selection of UPS.
Notes of Load Shifting, Motor Drive, Lighting System, Selection of UPS.
Amar Preet Singh
 
Organization Profile
Organization ProfileOrganization Profile
Organization ProfileAmol Chande
 
MINOR PROJECT gb 08 (3).pdf
MINOR PROJECT gb 08 (3).pdfMINOR PROJECT gb 08 (3).pdf
MINOR PROJECT gb 08 (3).pdf
DrSabhyataSoni
 
Variable Frequency Drives and Energy Savings: It‘s More Than Just Fan and Pum...
Variable Frequency Drives and Energy Savings: It‘s More Than Just Fan and Pum...Variable Frequency Drives and Energy Savings: It‘s More Than Just Fan and Pum...
Variable Frequency Drives and Energy Savings: It‘s More Than Just Fan and Pum...
Instrument Specialties, Inc.
 
power quality improvement in distrution system using D statcom
power quality improvement in distrution system using D statcompower quality improvement in distrution system using D statcom
power quality improvement in distrution system using D statcom
7867867869
 
Power Quality Enhancement in Power System Network using DSTACOM
Power Quality Enhancement in Power System Network using DSTACOMPower Quality Enhancement in Power System Network using DSTACOM
Power Quality Enhancement in Power System Network using DSTACOM
International Journal of Engineering Inventions www.ijeijournal.com
 
FYP presentation-1.pptxgsushwwhwhwhwhwhwhwhwhwhe
FYP presentation-1.pptxgsushwwhwhwhwhwhwhwhwhwheFYP presentation-1.pptxgsushwwhwhwhwhwhwhwhwhwhe
FYP presentation-1.pptxgsushwwhwhwhwhwhwhwhwhwhe
BilalAhmed65290
 
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET Journal
 
Automatic power factor correction by fine tuning of graded capacitors
Automatic power factor correction by fine tuning of graded capacitorsAutomatic power factor correction by fine tuning of graded capacitors
Automatic power factor correction by fine tuning of graded capacitors
IJARIIT
 
IRJET- Sanctioned Load Monitoring & Controlling by using PLC
IRJET- Sanctioned Load Monitoring & Controlling by using PLCIRJET- Sanctioned Load Monitoring & Controlling by using PLC
IRJET- Sanctioned Load Monitoring & Controlling by using PLC
IRJET Journal
 
Development of a power factor model for power sysytem loads
Development of a power factor model for power sysytem loadsDevelopment of a power factor model for power sysytem loads
Development of a power factor model for power sysytem loads
theijes
 
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
IRJET Journal
 
2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf
2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf
2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf
asprilla mangombe
 
Simulation and Analysis of a D-STATCOM for Load Compensation and Power Facto...
Simulation and Analysis of a D-STATCOM for Load  Compensation and Power Facto...Simulation and Analysis of a D-STATCOM for Load  Compensation and Power Facto...
Simulation and Analysis of a D-STATCOM for Load Compensation and Power Facto...
IJMER
 
IRJET - Power Quality Improvement in Distribution Power System using STATCOM
IRJET - Power Quality Improvement in Distribution Power System using STATCOMIRJET - Power Quality Improvement in Distribution Power System using STATCOM
IRJET - Power Quality Improvement in Distribution Power System using STATCOM
IRJET Journal
 

Similar to Final project report (20)

Bg4201393395
Bg4201393395Bg4201393395
Bg4201393395
 
IRJET- Automatic Power Factor Correction
IRJET- Automatic Power Factor CorrectionIRJET- Automatic Power Factor Correction
IRJET- Automatic Power Factor Correction
 
Applied automation apr2014
Applied automation apr2014Applied automation apr2014
Applied automation apr2014
 
Apfc project 2016 17
Apfc project 2016 17Apfc project 2016 17
Apfc project 2016 17
 
Power Factor & Utility Rates
Power Factor & Utility RatesPower Factor & Utility Rates
Power Factor & Utility Rates
 
Notes of Load Shifting, Motor Drive, Lighting System, Selection of UPS.
Notes of Load Shifting, Motor Drive, Lighting System, Selection of UPS.Notes of Load Shifting, Motor Drive, Lighting System, Selection of UPS.
Notes of Load Shifting, Motor Drive, Lighting System, Selection of UPS.
 
Organization Profile
Organization ProfileOrganization Profile
Organization Profile
 
MINOR PROJECT gb 08 (3).pdf
MINOR PROJECT gb 08 (3).pdfMINOR PROJECT gb 08 (3).pdf
MINOR PROJECT gb 08 (3).pdf
 
Variable Frequency Drives and Energy Savings: It‘s More Than Just Fan and Pum...
Variable Frequency Drives and Energy Savings: It‘s More Than Just Fan and Pum...Variable Frequency Drives and Energy Savings: It‘s More Than Just Fan and Pum...
Variable Frequency Drives and Energy Savings: It‘s More Than Just Fan and Pum...
 
power quality improvement in distrution system using D statcom
power quality improvement in distrution system using D statcompower quality improvement in distrution system using D statcom
power quality improvement in distrution system using D statcom
 
Power Quality Enhancement in Power System Network using DSTACOM
Power Quality Enhancement in Power System Network using DSTACOMPower Quality Enhancement in Power System Network using DSTACOM
Power Quality Enhancement in Power System Network using DSTACOM
 
FYP presentation-1.pptxgsushwwhwhwhwhwhwhwhwhwhe
FYP presentation-1.pptxgsushwwhwhwhwhwhwhwhwhwheFYP presentation-1.pptxgsushwwhwhwhwhwhwhwhwhwhe
FYP presentation-1.pptxgsushwwhwhwhwhwhwhwhwhwhe
 
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
IRJET- Power Saver for Industrial and Commercial Establishments by Power Fact...
 
Automatic power factor correction by fine tuning of graded capacitors
Automatic power factor correction by fine tuning of graded capacitorsAutomatic power factor correction by fine tuning of graded capacitors
Automatic power factor correction by fine tuning of graded capacitors
 
IRJET- Sanctioned Load Monitoring & Controlling by using PLC
IRJET- Sanctioned Load Monitoring & Controlling by using PLCIRJET- Sanctioned Load Monitoring & Controlling by using PLC
IRJET- Sanctioned Load Monitoring & Controlling by using PLC
 
Development of a power factor model for power sysytem loads
Development of a power factor model for power sysytem loadsDevelopment of a power factor model for power sysytem loads
Development of a power factor model for power sysytem loads
 
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
 
2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf
2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf
2006_18_spring_wiring_matters_power_factor_correction_pfc.pdf
 
Simulation and Analysis of a D-STATCOM for Load Compensation and Power Facto...
Simulation and Analysis of a D-STATCOM for Load  Compensation and Power Facto...Simulation and Analysis of a D-STATCOM for Load  Compensation and Power Facto...
Simulation and Analysis of a D-STATCOM for Load Compensation and Power Facto...
 
IRJET - Power Quality Improvement in Distribution Power System using STATCOM
IRJET - Power Quality Improvement in Distribution Power System using STATCOMIRJET - Power Quality Improvement in Distribution Power System using STATCOM
IRJET - Power Quality Improvement in Distribution Power System using STATCOM
 

Final project report

  • 1. Alternating Current Power Factor Monitoring and Correction: Final Project Report Bryan Underwood Advisor: Prof. Gutschlag May 9, 2012
  • 2. Abstract: Power factor is the value of a system that reflects how much power is being borrowed from the power company for the system. Quantitatively, power factor ranges from zero to one and is the cosine of the difference in the angle between the current and voltage. Many power companies regulate residential and industrial power factors to make sure that they do not fall below a certain level and charge the customer more on their utility bills if the power factor falls below a certain level. Power factor correction serves to correct low power factors by reducing the phase difference between the current and voltage at the distribution point for a company or residence. The most common way to correct the power factor is to switch capacitor banks at the source to generate “negative” reactive power. This project’s goal is to make a system that will switch capacitor banks in and out of the circuit when the power factor drops below a certain point to avoid power company charges.
  • 3. Table of Contents: Introduction…………………………………………………………………………………………........4 System Description……………………………………………………………………………………....5 Equipment List….....……………………………………………………………………………………..5 • Hampden Motor………………………………………………………………………………….6 • SATEC Programmable Logic Controller………………………………………………………...7 • Relays…………………………………………………………………………………………….9 • Capacitor Banks……………………………………………………………………………….....9 • Damping Resistors……………………………………………………………………………...10 Software………………………………………………………………………………………………...11 Results………………………………………………………………………..…………………………12 SATEC Programmable Logic Controller Tutorial……………………………………………………...15
  • 4. Introduction: Power factor is the value of a system that reflects how much power is being borrowed from the power company for the system. Quantitatively, power factor ranges from zero to one and is the cosine of the difference in the angle between the current and voltage. Poor power factors are due to inductive loads such as the induction motors found in air conditioners and refrigerators. According to Pacific Gas & Electric Company, about 60% of all loads in the United States are electric motors. This fact in combination with the United States Energy Information Administration (EIA) statistic of only about 25,000 out of 200,000 manufacturing companies participating in power factor correction, illustrates a need for companies to implement power factor correction devices to improve efficiency and reduce energy waste. One incentive for companies to install power factor correction devices is the charges that many utility companies impose for falling below a certain power factor. For example, Ameren Illinois requires customers to install power factor correction devices on their system if the power factor falls below 0.85. If the customer does not install any devices then Ameren can actually come out to the customer’s property and install devices themselves and charge the customer a hefty rate for doing so. Pacific Gas & Electric (PG&E) charges 0.6% for each percentage point of power factor below 0.85 on a utility bill. So if a customer’s utility bill is $10,000 and has an average power factor of 0.83 for the month, the customer would be charge 1.2% of the total bill more because of that low power factor. PG&E also provides an incentive to maintain a power factor above 0.85 as well. If a customer has a power factor above 0.85 the customer receives a credit equal to the process described above instead of a charge. There are also a couple of reasons for power companies to be concerned with low power factor. One of the most important reasons they are concerned is the power losses that occur through their transmission lines or the “I squared R losses.” This is power that the customer never uses and is not charged for. This is a problem both for generating and distribution companies as a distribution company might be charged for running at a low power factor in their system by a generating company. These charges incurred are also important for keeping power companies’ rates low to remain competitive. With several power companies offering incentives and most power companies charging some type of fee for falling below their specified power factor, some may wonder why companies do not actively pursue to improve their power factor. This can be due to several factors. One is that the companies’ administrators do not think the company will be able to recover costs from installing power factor correction devices. Another is that some companies might not have enough inductive loads to be concerned about power factor at all. Power factor correction acts to improve poor power factors by keeping a customer’s power factor above the level specified by the power company. The most common method of controlling power is by the use of switching capacitor banks and was the method implemented in this project. Capacitor banks generate “negative” reactive power or absorb the reactive power produced by inductive loads. However, it is possible to add too much capacitance to the system and still incur power company charges. This occurs when the amount of capacitance added is so much greater than the inductance of the system that the power factor goes below 0.85 leading. The goal of this project was to obtain a power factor as close to one as possible or to control the system power factor within a range that will avoid any power company charges possible.
  • 5. System Description: Figure 4-1, System Diagram A 120 [VAC] source was used to power an inductive load as seen in Figure 4-1 above, since the load power factor can be easily changed by adjusting the inductance of the load. The load used in this project was a three phase Hampden 1.4[A] 1/3 [HP] motor with attached pony brake to easily vary the power factor of the motor. Capacitor banks were used in parallel with the motor to improve the power factor due to the inductive load. The SATEC programmable power meter shown in Figure 2-1 was used to measure the power factor, current, voltage, and the active, reactive, and apparent power. The meter was also used to energize the relays that switched the capacitors in and out of the system. The software program, Power Analysis Software, used with the power meter allowed to specify a set point that when set to true, switched on a relay when the power factor dropped below a certain point.
  • 6. Equipment List: Hampden Type WRM-100 Three Phase Motor Figure 6-1, Hampden Motor with Attached Load Motor is rated at 1.4 [A] 220 [VAC] 1725 RPM 1/3 [HP]. Shown in Figure 6-1, attached is a pony brake load that allows varying the power factor of the motor. The top of the pony brake is cut off, but the load is varied by a knob that is twisted. A force meter is also attached so that efficiency can be measured by calculating the torque of the motor at various loads. A tachometer was also used to measure the RPM output of the motor. The torque was then multiplied by the output speed in radians per second gave the output power of the motor. This output power was divided by input power, which was obtained from meter readings, and multiplied by one hundred to obtain efficiency. A graph of these results was prepared and compared against power factor and is shown on the next page.
  • 7. Motor Power Factor and Efficiency: Figure 7-1, Motor Power Factor vs Efficiency As can be seen from Figure 7-1 the motor’s power factor is variable from about 0.3 to about 0.8 lagging. This provides a wide range in which to test different values of capacitance to switch in and out of the system. The power factor also generally increases with motor efficiciency until an output power of about 150 W. At this point the efficiency of the motor begins to level off at about fifty five percent while the power factor continues to rise to its maximum value of about 0.8 lagging. SATEC PM172E-N Three Phase Programmable Logic Controller Figure 7-2, SATEC Programmable Logic Controller
  • 8. The SATEC programmable logic controller was used as the meter for this project along with the energy source used to energize the relays used for switching. The data values taken from the meter for this project are the line to nuetral voltages, active power, power factor, apparent power, reactive power, line currents, and the individual line powers and power factors. The controller is programmed either by the buttons provided on the front of the meter or through SATEC’s free software program, Power Analysis Software (PAS). This software allows the user to program set points that perform a certain action when one or multiple conditions are set. One such action that can be taken is to energize or release realys based on what the power factor of the system is. The software also provides several charts and graphs that either stored data or real time data from the controller. A tutorial of the main functions of the controller is provided at the end of this report. Alternative Controllers: It should be noted that there are other programmable logic controllers available and a lot of them have more than two relay inputs and outputs. These alternative controllers also may have more programming options, such as the ability to set an action when the power factor goes above a certain point instead of only below as is the case for the controller used for this project. Two of the main companies that make these other controllers are Schweitzer Engineering Laboratories and General Electric Company. For this project, this controller was graciously loaned from Ameren Corporation so it was the controller that was used. The two controllers shown in Figure 8-1 and Figure 8-2 are two examples of alternative controllers that can be used. The controller shown in Figure 8-1 is a Schweitzer Engineering Laboratory 734B Logic Controller. The controller shown in Figure 8-2 is a General Electric PM35 Logic Controller. Figure 8-1, SEL PLC Figure 8-2, GE PLC
  • 9. Potter & Brumfield KRPA-11AG-120 Power Relays Figure 9-1 shows the relays that were used to switch the capacitor banks in and out of the circuit. These relays were controlled by the SATEC PLC and were also generously donated by Ameren Corporation. Figure 9-2 is a side view of the relays. Figure 9-1, Top View of Relay Figure 9-2, Side View of Relay Capacitor Banks These were the capacitor banks used in this project. There are two values of steps that could be used with the range of capacitance per step that was able to be switched into the system was 1.6uF to 50uF. Figure 9-3 shows a maximum value of 50uF capacitor bank with switches that enable different values of capacitance to be configured. Figure 9-4 switches in the same way, but contains only a maximum capacitance of 40uF. Figure 9-3, 50uF Capacitor Bank Figure 9-4, 40uF Capacitor Bank
  • 10. Damping Resistors: Damping resistors are placed in series with the capacitors that are being switched into the system to limit the inrush current that occurs. Figure 10-1 shows a resistor valued at 25 ohms. This inrush current occurs because when a capacitor is switched on initially it looks like a short circuit and draws very large currents for a short amount of time. Normally in a power factor correction system these resistors are only placed in series with the capacitors for a very short amount of time to limit these inrush currents and avoid excessive power losses due to the resistors. After this short amount of time, the resistors are switched out of the circuit and the capacitors remain in parallel with the load. Due to the limited about of relay outputs available on the controller used for this project, the damping resistors were kept in series with the capacitors and losses were calculated. Current through 10uF Capacitor Power Losses Current through 20uF Capacitor Power Losses Current through 30uF Capacitor Power Losses Figure 10-1, Damping Resistor 25 ohms ][6159.84450395.0 6159.84433.266 0120 AI °∠= °−∠ °∠ = ][07139.525*)450395.0( 22 WRIP === ][3252.79889119.0 3252.79965.134 0120 AI °∠= °−∠ °∠ = ][7633.19 WP = ][2121.7430597.1 2121.748857.91 0120 AI °∠= °−∠ °∠ = ][639.42 WP =
  • 11. Software: The software used in this project is the Power Analysis Software available directly from SATEC’s website. There is no code involved with programming the meter so there is no specific programming language. Rather, several graphical user interfaces (GUI) are provided to program the meter. One example is shown in Figure 11-1 below. Figure 7-1, Software Set Point This is the menu provided to program set points to the meter. With set points, the user can specify certain conditions that need to occur for one or several actions to occur. In the figure above, the set point becomes true and relay one is operated when the current in line A is above 0.1 Amps and the power factor of the system is below 0.85 lagging. In addition to the relay being operated, the controller records this event in the event log contained within the controller that is viewable by the program. This set point can be described by the flow chart in Figure 11-2 and also is the process at which the system in this project operates. Flow Chart: Figure 7-2, Software Flow Chart
  • 12. Beginning at the top of Figure 7-2 once the controller powers up, it checks to see whether a load is present by checking whether there is any line current in the system and if no current is present, any relays that are on are turned off and this check is repeated. If there is current then the meter checks to see if the system is running at a power factor below 0.85 lagging and if it is the relays are energized and the capacitor banks are switched into the system. The check for line current and a lagging power factor continue until the meter is powered down. Results: To determine what value of capacitance needed to be switched into the system, a theoretical model of the motor was made. The magnitude of impedance of the motor was found by dividing the voltage by the current of a single line of the motor. The phase angle of the impedance was found by taking the inverse cosign of the power factor of the motor. The impedance of the motor was recorded at four different power factors, 0.3, 0.45, 0.6, and 0.78 lagging. Five different values of capacitances were each added with each of the different power factors. Once the model of the motor was developed, the damping resistor and capacitor bank were added in parallel and the equivalent impedance was found. This allowed a calculation of the phase angle of the total impedance and the cosign of this angle was taken to obtain a source power factor. A table, Figure 12-1, and a graph, Figure 12-2, are shown below. Any value above one should be subtracted from two and taken as a leading power factor. 0.3 0.45 0.6 0.78 10uF 0.609445 0.74704 0.855108 0.933201 15uF 0.873233 0.928109 0.964573 0.983411 20uF 0.999937 0.999926 1.00002 0.999972 30uF 1.13754 1.09493 1.06663 1.03199 40uF 1.21777 1.17129 1.13211 1.07689 Figure 12-1, Theoretical Values Figure 12-2, Theoretical Graph
  • 13. As can be seen from Figure 12-2, it is desired to use 20uF of capacitance per phase to increase power factor to near unity and avoid any power company charges. Data was taken at the different values of capacitance from the controller to confirm that 20uF was the ideal capacitane for this project. A comparison of experimental and theoretical results is shown below. Again, any value over one represents a leading power factor and should be subtracted from two to find the value of that power factor. Figure 13-1, Theoretical and Experimental Values Figure 13-2, Theoretical and Experimental Values 0.3 0.45 0.6 0.78 10uF Meter 0.5815 0.704 0.85 0.93 15uF Meter 0.845 0.906 0.944 0.972 20uF Meter 0.992 0.997 0.999 0.999 30uF Meter 1.097 1.076 1.049 1.02 40uF Meter 1.196 1.154 1.1 1.074 10uF 0.609445 0.74704 0.855108 0.933201 15uF 0.873233 0.928109 0.964573 0.983411 20uF 0.999937 0.999926 1.00002 0.999972 30uF 1.13754 1.09493 1.06663 1.03199 40uF 1.21777 1.17129 1.13211 1.07689
  • 14. A final picture of the system is shown in Figure 14-1. The motor seen on the right has the attached pony brake and is currently running. This is shown by the controller in between the two capacitor banks. The controller is currently measuring the apparent power, power factor, and active power. Behind the controller is the fused power source, with several neutral points being used and a ground. The damping resistors are right in front of the capacitor banks, but connected in series with them. Finally, Power Analysis Software can be seen on the computer displaying real time values of the system including individual active powers, line voltages, and individual line power factors. Figure 14-1, Picture of Current System
  • 15. Satec PM172-N Programmable Logic Controller and Power Analysis Software Tutorial: Powering Controller and Communicating with Computer: To power up the meter, a 120 [VAC] source is needed along with a ground and neutral connection. These are connected to ports 10, 12 and ground as demonstrated in Figure 9-1 below. Figure 9-1, Terminal Connections When connecting the controller to line voltage and current there are several different wiring modes available and depending on which are available the controller will need to be told which ones to use.
  • 16. These settings can be set in the meter or the software program. One such configuration and the one used in this project can be seen in Figure 10-1. Figure 10-1, 4LL3 or 4Ln3 Wiring Configuration Note in the above diagram that current transformers are used. The controller can be told what ratio of potential and current transformers are used if not directly connecting the controller to line power. The controller is able to be programmed from the front to do and see anything that would be set or seen in the software program. As there are easily over two hundred settings and measurements that can be viewed, this tutorial will only cover the settings used in this project and will only cover which method was used to configure these settings. The rest can be found in the manual downloaded from the SATEC website. The most common way to connect the controller to a computer to view data or configure settings is through a serial port connection, although an adapter can be bought to communicate over ethernet or dial up. This serial port connection also needs to use a null modem cord and not a straight modem cord, otherwise the controller will not respond to computer commands. When using the Power Analysis Software, the user can create multiple databases corresponding to each controller connected. For this project since only one controller was used, there was no need to create multiple databases and remained with the default database. To set up communications with the controller press Configuration from the Tools menu at the top and select the site database to be used along with the model number of the controller, which for this project was PM172-N.
  • 17. The Device Address, Device ID, and Sampling Rate settings in the software need to match the settings contained in the controller. To check the settings in the controller, press select and three options should appear as Sta, Ops, and Chg as seen in Figure 11-1. To move through these menus on the controller use the select button, while pressing enter will enter that menu. To check the status of a setting the Sta menu will be used, while changing a setting will require the Chg menu. Now scroll through the menu that should appear like Figure 11-2. Figure 11-1, Select Menu Press the UP or DOWN button to scroll through these options with the top menu highlighted until Prt.1 is blinking and press enter. Then use the up and down arrows to scroll the different settings available for communications and make sure these correspond to the settings in the software. This process is shown in Figure 11-3. Figure 11-2, Status Menus Figure 11-3, Diagram Showing Route to Communication Settings Once all of the communication settings for the controller have been set, communications can be tested by powering up the controller and setting the software to go “on-line.” This is a state in which the software can communicate with the controller to read or send settings and read data. The button that takes the controller on-line is to the right of the drop down menu where the database being used in located. When pressed, communications are tested by trying to communicate with the controller in anyway. The most common method used is selected the plus sign next to the database name in the tree located in the right panel of the program. Configuring Basic Device Setup: The basic device settings need to be setup for the controller in order for data to be correctly read. These settings can be accessed in two ways; the first is to select General Setup under the MeterSetup menu at the top next to the Logs menu. The other way is to select the plus sign next to your database name in the right panel and then the plus sign next to General Setup and finally double click Basic Setup. This will bring up a window that contains the basic configuration settings on the meter starting with wiring mode. For this project, the only setting that needed to be confirmed was the wiring mode, PT ratio and multiplier, and the nominal frequency. Notice, that all the tabs at the top of this window correspond to the options under General Setup, therefore all options can be accessed by clicking the tabs at the top of the window. In the panel at the right the Memory/Log, Energy/TOU Setup, Communication Setup, and Protocol Setup were not used in this project.
  • 18. Viewing Data: When the controller is initially power on, the line to neutral voltages are displayed which is shown by the L present in the bottom left corner. To scroll through the measurements, the up and downs arrows are used and if the down arrow is pressed the line to line voltages are displayed which is shown by a P. The next set of measurements will be the line currents and the next measurements are the apparent power, power factor, and real power respectively. The last set of menus displays the neutral line current, frequency, and the reactive power. These values can also be viewed in the software along with many other data. To view real time values in chart or graph form, go to the monitor menu at the top and scroll over RT data monitor. This will list all the available chart or graph types that can be read. The ones used in the project are the Data Set 1 Real Time Measurements and Data Set 2 Average Measurements. Initially, the chart form of data is shown, but graph form can be displayed by pressing the first top left button that is called data trend when hovered over. When in chart form, the data displayed can be changed for any data set by pressing the fifth button from the left that when hovered over is called data set. For changing data values displayed in the graph, the fifth button from the left is pressed. An event log that displays user defined events, when set points are set, and when the controller is powered up or down. This event log can be found by selecting the event log under the logs menu at the top. This event log is very useful for viewing when a set point has been activated or released and when the set points were sent to the controller. Programming Set Points: The set point menus can be accessed from the same window that was used to access the Basic Setup Menu. Click the Control/Alarm Setpoints tab and there should be a drop down menu where the set point number is chosen, a triggers box where logic operators, trigger parameters, and operate and release limits are set, an actions box where actions to take when the set point becomes true, and a box for operate and release delays. For this project the three important trigger parameters that were used are the LO PF LAG AVR, LO PF LEAD AVR, and HI I1 AVR. The operate parameter for a lagging power factor was set at 0.85 while the release limit was at 1.0. This was anded with the current parameter to ensure the relays only switch when line current is present. The set point became true when the power factor at the source fell below 0.85 lagging and line current is present. The actions taken were OPERATE RELAY #1 and EVENT LOG. The operate relay action sent a signal out of the relay output #1 from the controller and the event log action logged that the set point was evaluated to be true. To send the current configuration to the controller there is a send button in the bottom left of the window. Configurations can be saved and loaded into the databases mention earlier by pressing the save as button and selecting the database pertinent to the controller being programmed.