DESIGN OF HEAT EXCHANGER
SHELL & TUBE HEAT EXCHANGER
PROBLEM
Benzene is to be cooled from 60 to 35oC at a rate of 50,000 kg/hr. Cooling
water is available at 20oC and the maximum exit temperature must be
limited to 32oC. Design a suitable heat exchanger.
DATA GIVEN
Benzene is to be cooled from 60 to 35oC at a rate of 50,000 kg/hr. Cooling
water is available at 20oC and the maximum exit temperature must be
limited to 32oC.
Design a suitable heat exchanger.
 ask for a suitable heat exchanger, always – shell & tube
Hot fluid Cold fluid
benzene Water
T1 : 60oC t1 : 20oC
T2 : 35OC t2 : 32OC
W : 50,000 kg/hr
STEP 1 : ROOTING OF FLUIDS
 Tube side fluid
 Cooling water
 The more fouling, erosive or corrosive fluid
 Less viscous fluid
 The fluid under higher pressure
 The hotter fluid
 The smaller volumetric flow rate
 Condensing steam
 Shell side fluid
 Condensing vapours
 If fluid temperature change is > 150°C (300°F)
 Very small volumetric flow rates
 High viscosity streams
Here,
Tube side fluid – Water
Shell side fluid - Benzene
STEP 2 : HEAT BALANCE TO DETERMINE UNKNOWN QUANTITY
Mean temperature –
= 47.5 oC = 320.5 K
= 26 oC = 299 K
Shell side fluid
(hot fluid)
Tube side fluid
(cold fluid)
W, Cp,shell , T1, T2,
Benzene
T1 = 60oC T2 = 35oC
50,000 kg/hr
w, Cp,tube , t1 , t2
Water
t1 = 20oC t2 = 32oC
To determine Cp – refer page no: 2-165, table 2-153 – 8e
refer page no: 2-170, table 2-196 -7e
Write down the values of C1, C2, C3, C4 and C5 for both benzene and water
For Benzene, T = Tmean and for water T = tmean
After substituting
Cp, benzene = 141658.45 J/kmol.K
= 1813.53 J/kg.K
Cp, water = 75370.74 J/kmol.K
= 4183.78 J/kg.K
J / (Kmol K)
J / (Kg K)
÷ mol. wt
(kg/kmol)
W Cp, benzene (T1 – T2) = w Cp, water (t1 – t2)
Substitute all values and calculate unknown w
w = 45,152.79 kg/hr
W = 50,000 kg/hr
W = 13.89 kg/s
w = 12.54 kg/s
Kg/ hr
Kg/ s
÷ 3600
STEP 3 : DETERMINATION OF LMTD
Here,
Countercurrent heat exchanger is used
LMTD = 20.83OC
T1
t2
T2
t1
ΔT2 = T1-t2
ΔT1 = T2-t1
STEP 4 : MINIMUM FLOW AREA PER TUBE PASS
1. Allowable velocity
If tube side fluid is liquid  1 m/s
If tube side fluid is gas  20 m/s
here, tube side fluid is liquid, so v = 1 m/s
2. Mass flow rate, w
tube side fluid is considered
w = 45152.79 kg/hr
= 12.54 kg/s
3. Density – page no. 2-98, table – 2-32 7e & 8e
Here, tube side fluid is water and temp = 299 K,
ρ = 55.219 kmol/m3
= 994.77 Kg/ m3
Minimum flow area per tube pass = 0.0126 m2
Kmol / m3
Kg / m3
x Mol. Wt
(kg/kmol)
STEP 5 : MINIMUM NUMBER OF TUBES IN EACH PASS
Page no: 11-42, table 11-12  8e PCH
Assume, Out side dia of tube = ¾”
From table corresponding to ¾” OD, 14 BWG metal, 8ft length, we get
Inside dia = 0.584” = 0.584 x 0.0254 = 0.0148 m
Outside dia = ¾” = 0.75” = 0.01905 m
1 inch = 0.0254 m
Inside area of tube = 1.719 x 10-4 m2
Min. flow area = 0.0126 m2
No. of tubes/ pass = 73
STEP 6 : TOTAL NO. OF TUBES
Total no. of tubes = (no. of tubes/ pass) x no. of pass
Always opt for a 1-2 exchanger (1 shell pass and 2 tube pass)
So, No. of tube pass = 2
Check for no. of pass : page no. 11-6, fig 11-4 (a)
R = (T1 – T2) /(t2 – t1) S = (t2 – t1) / (T1 – t1)
Using chart to find FT
• Find the S (0.3) on X axis
and draw a normal line to
the R curve (R= 2.08).
• Then extend the line from
the point of intersection
with Y axis.
• The Y axis will give the FT
• From that can calculate FT
R = 2.08
S = 0.3
FT = 0.88
Check for no. of pass
If FT > 0.8, assumption is correct
So, No. of pass = 2
Total no. of tubes = 2 x 73 = 146
STEP 7: INSIDE DIAMETER OF SHELL
SHELL – contains shell fluid & the tube bundle
• Shell diameter should be selected to give a close fit of the tube bundle.
• The clearance between the tube bundle and inner shell wall depends
on the type of exchanger.
SHELL DIAMETER = BUNDLE DIAMETER + (2 X CLEARANCE)
• Industrially accepted clearance = 7/8 “
• The tubes are arranged in Triangular, Square and Rotated square
pattern
• Generally select triangular pitch
Page no- 11-43
For triangular pitch, PT = 1.25 OD = 0.0238m
By trial and error method, we can find C, C = -21.5
Substitute in eqn, C = 0.75 (D/d) – 36  D = 14.5” = 368 mm
Shell ID = 14.5 + 2x 7/8 = 16.25” = 412 mm
Compare it with Std shell thickness in 6th edition PCH
Shell ID = 438 mm
No. of tubes = 228
STEP 8: REYNOLDS NUMBER – TUBE SIDE FLUID
di = 0.0148 m
ρ = 994.77 kg/m3
v = ?
μ = ?
To determine ‘v’
w- Flow rate of tube side fluid
a – inside area of tube
Cumulative velocity = 73.35 m/s w = 45152.79kg/hr = 12.54 kg/s
a = 1.719 x 10-4 m2
ρ =994.77 kg/ m3
v = 0.64 m/s
Re = 10469.4
To determine ‘μ’ - page no 2-449, fig 2- 32
To calculate μ using chart
• From table 2-318, identify the X & Y
coordinates of liquid (water: 10.2,13)
• Mark that point on fig 2-32
• On LHS Y-axis mark corresponding
temp in degree Celsius (26 C)
• Join both points and extend to RHS Y-
axis. The point on RHS Y-axis give
viscosity in cP.
μ = 0.9cP = 0.9x10-3P=0.9x10-3
μ = 9 x 10-4
Poise
kg/ms
STEP 9 : jH FACTOR
Page no : 5 -16, eqn 5-50c 7e PCH
jH = 3.6119 x 10-3
STEP 10: HEAT TRANSFER COEFFICIENT
To determine hi , eqn 5-50c is used
Nst = Stanton number
Npr = Prandtl number
Thermal conductivity, k is to be calculated to calculate Npr
Here we are using water as coolant , page no. 2-451, table 2-322 give Npr
of liquid refrigerants
From table we get, Npr of water at 300K = 5.69
Heat transfer coefficient
Heat transfer coefficient, hi = 3018.59 W/m2K
Npr
STEP 11: CALCULATION OF hio
hio= 2345.16 W/m2K
Reynolds number, Re = 26806.37
I. = 0.0138 m
II. Gs = v . ρ = mass flow rate (W) / area (as)
= 0.013 m C = PT – OD of tube = 4.75 x 10-3
Gs = v. ρ = 1068.37 kg/m2s B = 150 mm (assumption)
III. μ from page no. 2-449 (as shown earlier, here check for benzene)
μ = 0.55 cP = 5.5 x 10-4 kg/ms
STEP 12: REYNOLDS NUMBER – SHELL SIDE FLUID
STEP 13 : jH FACTOR
Page no : 5 -16, eqn 5-50c 7e PCH
jH = 2.9928 x 10-3
STEP 14: HEAT TRANSFER COEFFICIENT
To determine hi , eqn 5-50c is used
Nst = Stanton number
Npr = Prandtl number
To determine hi , eqn 5-50c is used
Nst = Stanton number
Npr = Prandtl number
Heat transfer coefficient,
ho = 7199.88 W/m2K
• Thermal conductivity,
k is to be calculated
to calculate Npr
• Page no. 2-450
• Fig 2-33
1. Note temp of shell
side fluid on LHS y-
axis (47.5 C)
2. Identify the
compound number
and mark that in the
fig (Benzene-13)
3. Join these two
points (Temp and
compound number)
and extend to RHS
Y-axis (k)
4. k= 138 mW/mK
= 0.138 W/mK
STEP 15 : CALCULATE tw
• Tmean = mean temperature of benzene = 320.5 K
• tmean = mean temperature of water = 299 K
tw = 304.28 K = 31.28oC
STEP 16: CALCULATION OF (μw/μb)0.14
• μb = bulk viscosity at mean temp
• μw = viscosity at tw
From page no. 2 -449 calculate μb,benzene, μw, benzene, μb, water, μw, water
(μb)benzene = 5.5 x 10-4 (μb)water = 9x10-4
(μw)benzene = 5.6 x10-4 (μw)water = 8.3 x10-4
hi, corrected = hi/(μw/μb)0.14
water = 3053.09 W/m2K
ho, corrected = ho /(μw/μb)0.14
benzene = 7181.74 W/m2K
= 0.002125 m
= 0.0168 m
kw  page no. 2-461, table 2-328- 8e
page no. 2-335, table 2-375- 7e
kw = 9.4 Btu/h.ft2.(oF/ft) = 18.91 W/mK
1/Ui = 5.347 x 10-4 m2K/W
Ui = 1870.17 W/m2K
STEP 17: OVERALL HEAT TRANSFER COEFFICIENT, Ui
Btu/h.ft2.(oF/ft)
Kcal/hr.m.oC
W/mK
X 1.73
X 1.163
Q = Ui. Ai. FT. ΔTLMTD
• Q = W Cp (T1 – T2) = w Cp (t2 – t1) = 6.29 x105 J/s
• FT = 0.88
• ΔTLMTD = 293.83 K
• Ui = 1870.17 W/m2K
Ai = 1.3 m2
STEP 18: HEAT TRANSFER AREA, Ai
Calculated Dirt factor,
Ui = Uc = 1870.17 W/m2K
n = 228
di = 0.0148 m
L = 8ft = 2.45 m
UDa = 74.55 W/m2K
Rdc = 0.0129 m2K/W
STEP 19: CALCULATION OF DIRT FACTOR, Rdc
Page no. 11-25, table 11-3 – 8e
Dirt factor, Rd = 0.03 (oF . Ft2 . H)/ Btu
= 5.283 x 10-4 m2Ks/J
Rdc > Rd : so our assumptions are
correct
(oF . Ft2 . H)/ Btu
M2.K. s/ J
X 0.1761
STEP 20: PRESSURE DROP – TUBE SIDE / TUBE PASS
Pressure drop through tube side fluid (ΔP)T = (ΔP)t + (ΔP)r
1. Pressure drop (ΔP)t for std length of tube is given by Fanning eqn:
= 1187.13 N/m2
2. Pressure drop through expansion & contraction, (ΔP)r
= 1629.83 N/m2
(ΔP)T = 2816.96 N/m2
For 1 tube pass- 2 expansion
& 2 contraction losses. At
entrance and exit there is
contraction and expansion.
( 2x0.5)+(2x1)+(2x0.5)=4
So, 4 velocity heads per pass
nT = 2
V = 0.64 m/s
ρ = 994.77 kg/m3
L = 2.45m
d = 0.0148 m
f  page no. 6-10, figure 6-9
From table 6-1, surface roughness, ε, for particular material, here assume
commercial steel or wrought iron = 0.0457
X axis = NRe = 1.04 x 104
Y axis (RHS) = f = 0.0088
Yaxis (LHS)= ε/di = 0.00309
Use chart to calculate ‘f’
• Find the NRe (1.04x104) on X axis and draw a normal line to the ε/di
(0.00309) curve.
• Then extend the line from the point of intersection with Y axis.
• The Y axis will give the f (0.0088)
= 0.0203
• ρ of benzene is measured from page no. 2-98, table – 2-32 7e & 8e
STEP 20: PRESSURE DROP – SHELL SIDE
(ΔP)shell = 56388.20 N/m2
Assume allowable pressure drop inside tube = 10psi
= 10 x 6894.757 N/m2
= 68947.57 N/m2
(ΔP) allowable > (ΔP) shell > (ΔP) tube
68947.57 N/m2 > 56388.20 N/m2 > 2816.96 N/m2
So, check for shell side and tube side fluid is correct
Our design is correct.

More Related Content

What's hot

Cooling tower full report
Cooling tower full reportCooling tower full report
Cooling tower full reportAzlan Skool
 
Mass transfer dr auroba
Mass transfer dr aurobaMass transfer dr auroba
Mass transfer dr aurobacbhattr
 
Measurement of density S.G and API gravity
 Measurement of density S.G and API gravity  Measurement of density S.G and API gravity
Measurement of density S.G and API gravity Zanyar qaradaxe
 
Heat loss in bare and lagged pipes
Heat loss in bare and lagged pipesHeat loss in bare and lagged pipes
Heat loss in bare and lagged pipesNicely Jane Eleccion
 
Shell and Tube Heat Exchanger in heat Transfer
Shell and Tube Heat Exchanger in heat TransferShell and Tube Heat Exchanger in heat Transfer
Shell and Tube Heat Exchanger in heat TransferUsman Shah
 
Chemical Process Calculations – Short Tutorial
Chemical Process Calculations – Short TutorialChemical Process Calculations – Short Tutorial
Chemical Process Calculations – Short TutorialVijay Sarathy
 
Some dimensionless numbers in heat transfer
Some dimensionless numbers in heat transferSome dimensionless numbers in heat transfer
Some dimensionless numbers in heat transferSarmad Rasheed
 
Fouling effects on boiler
Fouling effects on boilerFouling effects on boiler
Fouling effects on boilerMaharshi Soni
 
Heat Exchanger
Heat ExchangerHeat Exchanger
Heat ExchangerNathan
 
Parts of shell and tube heat exchanger
Parts of shell and tube heat exchangerParts of shell and tube heat exchanger
Parts of shell and tube heat exchangerKarnav Rana
 
Types and design of the towers trays
Types and design of the towers traysTypes and design of the towers trays
Types and design of the towers traysFertiglobe
 

What's hot (20)

Heat exchangers
Heat exchangersHeat exchangers
Heat exchangers
 
Cooling tower full report
Cooling tower full reportCooling tower full report
Cooling tower full report
 
Mass transfer dr auroba
Mass transfer dr aurobaMass transfer dr auroba
Mass transfer dr auroba
 
Lab I final presentation
Lab I final presentationLab I final presentation
Lab I final presentation
 
Measurement of density S.G and API gravity
 Measurement of density S.G and API gravity  Measurement of density S.G and API gravity
Measurement of density S.G and API gravity
 
Condenser design
Condenser designCondenser design
Condenser design
 
Heat loss in bare and lagged pipes
Heat loss in bare and lagged pipesHeat loss in bare and lagged pipes
Heat loss in bare and lagged pipes
 
95396211 heat-transfer-lab-manual
95396211 heat-transfer-lab-manual95396211 heat-transfer-lab-manual
95396211 heat-transfer-lab-manual
 
Shell and Tube Heat Exchanger in heat Transfer
Shell and Tube Heat Exchanger in heat TransferShell and Tube Heat Exchanger in heat Transfer
Shell and Tube Heat Exchanger in heat Transfer
 
Chemical Process Calculations – Short Tutorial
Chemical Process Calculations – Short TutorialChemical Process Calculations – Short Tutorial
Chemical Process Calculations – Short Tutorial
 
Some dimensionless numbers in heat transfer
Some dimensionless numbers in heat transferSome dimensionless numbers in heat transfer
Some dimensionless numbers in heat transfer
 
Fouling effects on boiler
Fouling effects on boilerFouling effects on boiler
Fouling effects on boiler
 
Process calculation condensation
Process calculation  condensationProcess calculation  condensation
Process calculation condensation
 
conversion and reactor sizing
conversion and reactor sizingconversion and reactor sizing
conversion and reactor sizing
 
Heat Exchanger
Heat ExchangerHeat Exchanger
Heat Exchanger
 
Pour point
Pour pointPour point
Pour point
 
Parts of shell and tube heat exchanger
Parts of shell and tube heat exchangerParts of shell and tube heat exchanger
Parts of shell and tube heat exchanger
 
Types and design of the towers trays
Types and design of the towers traysTypes and design of the towers trays
Types and design of the towers trays
 
Notches and weir
Notches and weirNotches and weir
Notches and weir
 
Exp 10 flow_rate
Exp 10 flow_rateExp 10 flow_rate
Exp 10 flow_rate
 

Similar to Design of Shell & tube Heat Exchanger.pptx

مبدل های حرارتی
مبدل های حرارتیمبدل های حرارتی
مبدل های حرارتیObeid Aghaei
 
Designofcondenser 130801223803-phpapp02
Designofcondenser 130801223803-phpapp02Designofcondenser 130801223803-phpapp02
Designofcondenser 130801223803-phpapp02ThamizhmaniT
 
Designofcondenser 130801223803-phpapp02
Designofcondenser 130801223803-phpapp02Designofcondenser 130801223803-phpapp02
Designofcondenser 130801223803-phpapp02ThamizhmaniT
 
friction loss along a pipe
friction loss along a pipefriction loss along a pipe
friction loss along a pipeSaif al-din ali
 
Manufacture of nitrobenzene
Manufacture of nitrobenzeneManufacture of nitrobenzene
Manufacture of nitrobenzeneparthdhurvey
 
DESIGN OF AIR PRE HEATER AND ECONOMIZER
DESIGN OF AIR PRE HEATER AND ECONOMIZERDESIGN OF AIR PRE HEATER AND ECONOMIZER
DESIGN OF AIR PRE HEATER AND ECONOMIZERGopi Chand
 
Shell and tube heat Exchanger Design.pptx
Shell and tube heat Exchanger Design.pptxShell and tube heat Exchanger Design.pptx
Shell and tube heat Exchanger Design.pptxsandeepsharma432939
 
Counter flow
Counter flowCounter flow
Counter flowqusay7
 
Process equipment numericals problems
Process equipment numericals problemsProcess equipment numericals problems
Process equipment numericals problemsAnand Upadhyay
 
Convective Heat Transfer - Part 3.pdf
Convective Heat Transfer - Part 3.pdfConvective Heat Transfer - Part 3.pdf
Convective Heat Transfer - Part 3.pdfXuanNguyen277499
 
Coiled tubing calculations.pdf
Coiled tubing calculations.pdfCoiled tubing calculations.pdf
Coiled tubing calculations.pdfJesusCubillas1
 
Jamuna Oil Comany Ltd recruitment question & ans (5th july 2018)
Jamuna Oil Comany Ltd recruitment question & ans (5th july 2018)Jamuna Oil Comany Ltd recruitment question & ans (5th july 2018)
Jamuna Oil Comany Ltd recruitment question & ans (5th july 2018)Alamin Md
 
pressure drop calculation in sieve plate distillation column
pressure drop calculation in sieve plate distillation columnpressure drop calculation in sieve plate distillation column
pressure drop calculation in sieve plate distillation columnAli Shaan Ghumman
 
Ρευστά σε Κίνηση Γ΄ Λυκείου - Προβλήματα
Ρευστά σε Κίνηση Γ΄ Λυκείου - ΠροβλήματαΡευστά σε Κίνηση Γ΄ Λυκείου - Προβλήματα
Ρευστά σε Κίνηση Γ΄ Λυκείου - ΠροβλήματαΒατάτζης .
 
2A- Hydraulics, Water Distribution and WW Collection_AC_W2022 (1).pdf
2A- Hydraulics, Water Distribution and WW Collection_AC_W2022 (1).pdf2A- Hydraulics, Water Distribution and WW Collection_AC_W2022 (1).pdf
2A- Hydraulics, Water Distribution and WW Collection_AC_W2022 (1).pdfBhargãv Pâtel
 
Section 7 multistage separation processes
Section 7   multistage separation processesSection 7   multistage separation processes
Section 7 multistage separation processesAmal Magdy
 

Similar to Design of Shell & tube Heat Exchanger.pptx (20)

مبدل های حرارتی
مبدل های حرارتیمبدل های حرارتی
مبدل های حرارتی
 
Designofcondenser 130801223803-phpapp02
Designofcondenser 130801223803-phpapp02Designofcondenser 130801223803-phpapp02
Designofcondenser 130801223803-phpapp02
 
Designofcondenser 130801223803-phpapp02
Designofcondenser 130801223803-phpapp02Designofcondenser 130801223803-phpapp02
Designofcondenser 130801223803-phpapp02
 
تصمم.pptx
تصمم.pptxتصمم.pptx
تصمم.pptx
 
friction loss along a pipe
friction loss along a pipefriction loss along a pipe
friction loss along a pipe
 
Manufacture of nitrobenzene
Manufacture of nitrobenzeneManufacture of nitrobenzene
Manufacture of nitrobenzene
 
DESIGN OF AIR PRE HEATER AND ECONOMIZER
DESIGN OF AIR PRE HEATER AND ECONOMIZERDESIGN OF AIR PRE HEATER AND ECONOMIZER
DESIGN OF AIR PRE HEATER AND ECONOMIZER
 
project ppt
project pptproject ppt
project ppt
 
Shell and tube heat Exchanger Design.pptx
Shell and tube heat Exchanger Design.pptxShell and tube heat Exchanger Design.pptx
Shell and tube heat Exchanger Design.pptx
 
Counter flow
Counter flowCounter flow
Counter flow
 
Process equipment numericals problems
Process equipment numericals problemsProcess equipment numericals problems
Process equipment numericals problems
 
Convective Heat Transfer - Part 3.pdf
Convective Heat Transfer - Part 3.pdfConvective Heat Transfer - Part 3.pdf
Convective Heat Transfer - Part 3.pdf
 
Coiled tubing calculations.pdf
Coiled tubing calculations.pdfCoiled tubing calculations.pdf
Coiled tubing calculations.pdf
 
Jamuna Oil Comany Ltd recruitment question & ans (5th july 2018)
Jamuna Oil Comany Ltd recruitment question & ans (5th july 2018)Jamuna Oil Comany Ltd recruitment question & ans (5th july 2018)
Jamuna Oil Comany Ltd recruitment question & ans (5th july 2018)
 
Mc conkey 10-pb
Mc conkey 10-pbMc conkey 10-pb
Mc conkey 10-pb
 
pressure drop calculation in sieve plate distillation column
pressure drop calculation in sieve plate distillation columnpressure drop calculation in sieve plate distillation column
pressure drop calculation in sieve plate distillation column
 
Ρευστά σε Κίνηση Γ΄ Λυκείου - Προβλήματα
Ρευστά σε Κίνηση Γ΄ Λυκείου - ΠροβλήματαΡευστά σε Κίνηση Γ΄ Λυκείου - Προβλήματα
Ρευστά σε Κίνηση Γ΄ Λυκείου - Προβλήματα
 
Hvac formulas
Hvac formulasHvac formulas
Hvac formulas
 
2A- Hydraulics, Water Distribution and WW Collection_AC_W2022 (1).pdf
2A- Hydraulics, Water Distribution and WW Collection_AC_W2022 (1).pdf2A- Hydraulics, Water Distribution and WW Collection_AC_W2022 (1).pdf
2A- Hydraulics, Water Distribution and WW Collection_AC_W2022 (1).pdf
 
Section 7 multistage separation processes
Section 7   multistage separation processesSection 7   multistage separation processes
Section 7 multistage separation processes
 

Recently uploaded

WAEC Carpentry and Joinery Past Questions
WAEC Carpentry and Joinery Past QuestionsWAEC Carpentry and Joinery Past Questions
WAEC Carpentry and Joinery Past QuestionsCharles Obaleagbon
 
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service 🧵
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service  🧵CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service  🧵
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service 🧵anilsa9823
 
Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...
Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...
Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...home
 
VIP Russian Call Girls in Gorakhpur Deepika 8250192130 Independent Escort Ser...
VIP Russian Call Girls in Gorakhpur Deepika 8250192130 Independent Escort Ser...VIP Russian Call Girls in Gorakhpur Deepika 8250192130 Independent Escort Ser...
VIP Russian Call Girls in Gorakhpur Deepika 8250192130 Independent Escort Ser...Suhani Kapoor
 
CALL ON ➥8923113531 🔝Call Girls Aminabad Lucknow best Night Fun service
CALL ON ➥8923113531 🔝Call Girls Aminabad Lucknow best Night Fun serviceCALL ON ➥8923113531 🔝Call Girls Aminabad Lucknow best Night Fun service
CALL ON ➥8923113531 🔝Call Girls Aminabad Lucknow best Night Fun serviceanilsa9823
 
3D Printing And Designing Final Report.pdf
3D Printing And Designing Final Report.pdf3D Printing And Designing Final Report.pdf
3D Printing And Designing Final Report.pdfSwaraliBorhade
 
MASONRY -Building Technology and Construction
MASONRY -Building Technology and ConstructionMASONRY -Building Technology and Construction
MASONRY -Building Technology and Constructionmbermudez3
 
PODSCAPE - Brochure 2023_ prefab homes in Bangalore India
PODSCAPE - Brochure 2023_ prefab homes in Bangalore IndiaPODSCAPE - Brochure 2023_ prefab homes in Bangalore India
PODSCAPE - Brochure 2023_ prefab homes in Bangalore IndiaYathish29
 
Cheap Rate ➥8448380779 ▻Call Girls In Iffco Chowk Gurgaon
Cheap Rate ➥8448380779 ▻Call Girls In Iffco Chowk GurgaonCheap Rate ➥8448380779 ▻Call Girls In Iffco Chowk Gurgaon
Cheap Rate ➥8448380779 ▻Call Girls In Iffco Chowk GurgaonDelhi Call girls
 
VIP Call Girls Bhiwandi Ananya 8250192130 Independent Escort Service Bhiwandi
VIP Call Girls Bhiwandi Ananya 8250192130 Independent Escort Service BhiwandiVIP Call Girls Bhiwandi Ananya 8250192130 Independent Escort Service Bhiwandi
VIP Call Girls Bhiwandi Ananya 8250192130 Independent Escort Service BhiwandiSuhani Kapoor
 
Design Portfolio - 2024 - William Vickery
Design Portfolio - 2024 - William VickeryDesign Portfolio - 2024 - William Vickery
Design Portfolio - 2024 - William VickeryWilliamVickery6
 
SD_The MATATAG Curriculum Training Design.pptx
SD_The MATATAG Curriculum Training Design.pptxSD_The MATATAG Curriculum Training Design.pptx
SD_The MATATAG Curriculum Training Design.pptxjanettecruzeiro1
 
The_Canvas_of_Creative_Mastery_Newsletter_April_2024_Version.pdf
The_Canvas_of_Creative_Mastery_Newsletter_April_2024_Version.pdfThe_Canvas_of_Creative_Mastery_Newsletter_April_2024_Version.pdf
The_Canvas_of_Creative_Mastery_Newsletter_April_2024_Version.pdfAmirYakdi
 
Raj Nagar Extension Call Girls 9711199012 WhatsApp No, Delhi Escorts in Raj N...
Raj Nagar Extension Call Girls 9711199012 WhatsApp No, Delhi Escorts in Raj N...Raj Nagar Extension Call Girls 9711199012 WhatsApp No, Delhi Escorts in Raj N...
Raj Nagar Extension Call Girls 9711199012 WhatsApp No, Delhi Escorts in Raj N...ankitnayak356677
 
Cheap Rate Call girls Kalkaji 9205541914 shot 1500 night
Cheap Rate Call girls Kalkaji 9205541914 shot 1500 nightCheap Rate Call girls Kalkaji 9205541914 shot 1500 night
Cheap Rate Call girls Kalkaji 9205541914 shot 1500 nightDelhi Call girls
 
Best VIP Call Girls Noida Sector 47 Call Me: 8448380779
Best VIP Call Girls Noida Sector 47 Call Me: 8448380779Best VIP Call Girls Noida Sector 47 Call Me: 8448380779
Best VIP Call Girls Noida Sector 47 Call Me: 8448380779Delhi Call girls
 
VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130
VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130
VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130Suhani Kapoor
 
VIP College Call Girls Gorakhpur Bhavna 8250192130 Independent Escort Service...
VIP College Call Girls Gorakhpur Bhavna 8250192130 Independent Escort Service...VIP College Call Girls Gorakhpur Bhavna 8250192130 Independent Escort Service...
VIP College Call Girls Gorakhpur Bhavna 8250192130 Independent Escort Service...Suhani Kapoor
 

Recently uploaded (20)

WAEC Carpentry and Joinery Past Questions
WAEC Carpentry and Joinery Past QuestionsWAEC Carpentry and Joinery Past Questions
WAEC Carpentry and Joinery Past Questions
 
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service 🧵
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service  🧵CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service  🧵
CALL ON ➥8923113531 🔝Call Girls Kalyanpur Lucknow best Female service 🧵
 
Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...
Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...
Recommendable # 971589162217 # philippine Young Call Girls in Dubai By Marina...
 
VIP Russian Call Girls in Gorakhpur Deepika 8250192130 Independent Escort Ser...
VIP Russian Call Girls in Gorakhpur Deepika 8250192130 Independent Escort Ser...VIP Russian Call Girls in Gorakhpur Deepika 8250192130 Independent Escort Ser...
VIP Russian Call Girls in Gorakhpur Deepika 8250192130 Independent Escort Ser...
 
CALL ON ➥8923113531 🔝Call Girls Aminabad Lucknow best Night Fun service
CALL ON ➥8923113531 🔝Call Girls Aminabad Lucknow best Night Fun serviceCALL ON ➥8923113531 🔝Call Girls Aminabad Lucknow best Night Fun service
CALL ON ➥8923113531 🔝Call Girls Aminabad Lucknow best Night Fun service
 
3D Printing And Designing Final Report.pdf
3D Printing And Designing Final Report.pdf3D Printing And Designing Final Report.pdf
3D Printing And Designing Final Report.pdf
 
MASONRY -Building Technology and Construction
MASONRY -Building Technology and ConstructionMASONRY -Building Technology and Construction
MASONRY -Building Technology and Construction
 
PODSCAPE - Brochure 2023_ prefab homes in Bangalore India
PODSCAPE - Brochure 2023_ prefab homes in Bangalore IndiaPODSCAPE - Brochure 2023_ prefab homes in Bangalore India
PODSCAPE - Brochure 2023_ prefab homes in Bangalore India
 
Cheap Rate ➥8448380779 ▻Call Girls In Iffco Chowk Gurgaon
Cheap Rate ➥8448380779 ▻Call Girls In Iffco Chowk GurgaonCheap Rate ➥8448380779 ▻Call Girls In Iffco Chowk Gurgaon
Cheap Rate ➥8448380779 ▻Call Girls In Iffco Chowk Gurgaon
 
VIP Call Girls Bhiwandi Ananya 8250192130 Independent Escort Service Bhiwandi
VIP Call Girls Bhiwandi Ananya 8250192130 Independent Escort Service BhiwandiVIP Call Girls Bhiwandi Ananya 8250192130 Independent Escort Service Bhiwandi
VIP Call Girls Bhiwandi Ananya 8250192130 Independent Escort Service Bhiwandi
 
Design Portfolio - 2024 - William Vickery
Design Portfolio - 2024 - William VickeryDesign Portfolio - 2024 - William Vickery
Design Portfolio - 2024 - William Vickery
 
SD_The MATATAG Curriculum Training Design.pptx
SD_The MATATAG Curriculum Training Design.pptxSD_The MATATAG Curriculum Training Design.pptx
SD_The MATATAG Curriculum Training Design.pptx
 
The_Canvas_of_Creative_Mastery_Newsletter_April_2024_Version.pdf
The_Canvas_of_Creative_Mastery_Newsletter_April_2024_Version.pdfThe_Canvas_of_Creative_Mastery_Newsletter_April_2024_Version.pdf
The_Canvas_of_Creative_Mastery_Newsletter_April_2024_Version.pdf
 
Raj Nagar Extension Call Girls 9711199012 WhatsApp No, Delhi Escorts in Raj N...
Raj Nagar Extension Call Girls 9711199012 WhatsApp No, Delhi Escorts in Raj N...Raj Nagar Extension Call Girls 9711199012 WhatsApp No, Delhi Escorts in Raj N...
Raj Nagar Extension Call Girls 9711199012 WhatsApp No, Delhi Escorts in Raj N...
 
Cheap Rate Call girls Kalkaji 9205541914 shot 1500 night
Cheap Rate Call girls Kalkaji 9205541914 shot 1500 nightCheap Rate Call girls Kalkaji 9205541914 shot 1500 night
Cheap Rate Call girls Kalkaji 9205541914 shot 1500 night
 
escort service sasti (*~Call Girls in Prasad Nagar Metro❤️9953056974
escort service sasti (*~Call Girls in Prasad Nagar Metro❤️9953056974escort service sasti (*~Call Girls in Prasad Nagar Metro❤️9953056974
escort service sasti (*~Call Girls in Prasad Nagar Metro❤️9953056974
 
Best VIP Call Girls Noida Sector 47 Call Me: 8448380779
Best VIP Call Girls Noida Sector 47 Call Me: 8448380779Best VIP Call Girls Noida Sector 47 Call Me: 8448380779
Best VIP Call Girls Noida Sector 47 Call Me: 8448380779
 
VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130
VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130
VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130
 
young call girls in Vivek Vihar🔝 9953056974 🔝 Delhi escort Service
young call girls in Vivek Vihar🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Vivek Vihar🔝 9953056974 🔝 Delhi escort Service
young call girls in Vivek Vihar🔝 9953056974 🔝 Delhi escort Service
 
VIP College Call Girls Gorakhpur Bhavna 8250192130 Independent Escort Service...
VIP College Call Girls Gorakhpur Bhavna 8250192130 Independent Escort Service...VIP College Call Girls Gorakhpur Bhavna 8250192130 Independent Escort Service...
VIP College Call Girls Gorakhpur Bhavna 8250192130 Independent Escort Service...
 

Design of Shell & tube Heat Exchanger.pptx

  • 1. DESIGN OF HEAT EXCHANGER SHELL & TUBE HEAT EXCHANGER
  • 2. PROBLEM Benzene is to be cooled from 60 to 35oC at a rate of 50,000 kg/hr. Cooling water is available at 20oC and the maximum exit temperature must be limited to 32oC. Design a suitable heat exchanger.
  • 3. DATA GIVEN Benzene is to be cooled from 60 to 35oC at a rate of 50,000 kg/hr. Cooling water is available at 20oC and the maximum exit temperature must be limited to 32oC. Design a suitable heat exchanger.  ask for a suitable heat exchanger, always – shell & tube Hot fluid Cold fluid benzene Water T1 : 60oC t1 : 20oC T2 : 35OC t2 : 32OC W : 50,000 kg/hr
  • 4. STEP 1 : ROOTING OF FLUIDS  Tube side fluid  Cooling water  The more fouling, erosive or corrosive fluid  Less viscous fluid  The fluid under higher pressure  The hotter fluid  The smaller volumetric flow rate  Condensing steam  Shell side fluid  Condensing vapours  If fluid temperature change is > 150°C (300°F)  Very small volumetric flow rates  High viscosity streams Here, Tube side fluid – Water Shell side fluid - Benzene
  • 5. STEP 2 : HEAT BALANCE TO DETERMINE UNKNOWN QUANTITY Mean temperature – = 47.5 oC = 320.5 K = 26 oC = 299 K Shell side fluid (hot fluid) Tube side fluid (cold fluid) W, Cp,shell , T1, T2, Benzene T1 = 60oC T2 = 35oC 50,000 kg/hr w, Cp,tube , t1 , t2 Water t1 = 20oC t2 = 32oC
  • 6. To determine Cp – refer page no: 2-165, table 2-153 – 8e refer page no: 2-170, table 2-196 -7e Write down the values of C1, C2, C3, C4 and C5 for both benzene and water For Benzene, T = Tmean and for water T = tmean After substituting Cp, benzene = 141658.45 J/kmol.K = 1813.53 J/kg.K Cp, water = 75370.74 J/kmol.K = 4183.78 J/kg.K J / (Kmol K) J / (Kg K) ÷ mol. wt (kg/kmol)
  • 7. W Cp, benzene (T1 – T2) = w Cp, water (t1 – t2) Substitute all values and calculate unknown w w = 45,152.79 kg/hr W = 50,000 kg/hr W = 13.89 kg/s w = 12.54 kg/s Kg/ hr Kg/ s ÷ 3600
  • 8. STEP 3 : DETERMINATION OF LMTD
  • 9. Here, Countercurrent heat exchanger is used LMTD = 20.83OC T1 t2 T2 t1 ΔT2 = T1-t2 ΔT1 = T2-t1
  • 10. STEP 4 : MINIMUM FLOW AREA PER TUBE PASS 1. Allowable velocity If tube side fluid is liquid  1 m/s If tube side fluid is gas  20 m/s here, tube side fluid is liquid, so v = 1 m/s 2. Mass flow rate, w tube side fluid is considered w = 45152.79 kg/hr = 12.54 kg/s
  • 11. 3. Density – page no. 2-98, table – 2-32 7e & 8e Here, tube side fluid is water and temp = 299 K, ρ = 55.219 kmol/m3 = 994.77 Kg/ m3 Minimum flow area per tube pass = 0.0126 m2 Kmol / m3 Kg / m3 x Mol. Wt (kg/kmol)
  • 12. STEP 5 : MINIMUM NUMBER OF TUBES IN EACH PASS Page no: 11-42, table 11-12  8e PCH Assume, Out side dia of tube = ¾” From table corresponding to ¾” OD, 14 BWG metal, 8ft length, we get Inside dia = 0.584” = 0.584 x 0.0254 = 0.0148 m Outside dia = ¾” = 0.75” = 0.01905 m 1 inch = 0.0254 m
  • 13. Inside area of tube = 1.719 x 10-4 m2 Min. flow area = 0.0126 m2 No. of tubes/ pass = 73
  • 14. STEP 6 : TOTAL NO. OF TUBES Total no. of tubes = (no. of tubes/ pass) x no. of pass Always opt for a 1-2 exchanger (1 shell pass and 2 tube pass) So, No. of tube pass = 2 Check for no. of pass : page no. 11-6, fig 11-4 (a) R = (T1 – T2) /(t2 – t1) S = (t2 – t1) / (T1 – t1)
  • 15. Using chart to find FT • Find the S (0.3) on X axis and draw a normal line to the R curve (R= 2.08). • Then extend the line from the point of intersection with Y axis. • The Y axis will give the FT • From that can calculate FT R = 2.08 S = 0.3 FT = 0.88 Check for no. of pass If FT > 0.8, assumption is correct So, No. of pass = 2 Total no. of tubes = 2 x 73 = 146
  • 16. STEP 7: INSIDE DIAMETER OF SHELL SHELL – contains shell fluid & the tube bundle • Shell diameter should be selected to give a close fit of the tube bundle. • The clearance between the tube bundle and inner shell wall depends on the type of exchanger. SHELL DIAMETER = BUNDLE DIAMETER + (2 X CLEARANCE) • Industrially accepted clearance = 7/8 “ • The tubes are arranged in Triangular, Square and Rotated square pattern • Generally select triangular pitch
  • 17. Page no- 11-43 For triangular pitch, PT = 1.25 OD = 0.0238m By trial and error method, we can find C, C = -21.5 Substitute in eqn, C = 0.75 (D/d) – 36  D = 14.5” = 368 mm Shell ID = 14.5 + 2x 7/8 = 16.25” = 412 mm Compare it with Std shell thickness in 6th edition PCH Shell ID = 438 mm No. of tubes = 228
  • 18. STEP 8: REYNOLDS NUMBER – TUBE SIDE FLUID di = 0.0148 m ρ = 994.77 kg/m3 v = ? μ = ? To determine ‘v’ w- Flow rate of tube side fluid a – inside area of tube Cumulative velocity = 73.35 m/s w = 45152.79kg/hr = 12.54 kg/s a = 1.719 x 10-4 m2 ρ =994.77 kg/ m3 v = 0.64 m/s Re = 10469.4
  • 19. To determine ‘μ’ - page no 2-449, fig 2- 32 To calculate μ using chart • From table 2-318, identify the X & Y coordinates of liquid (water: 10.2,13) • Mark that point on fig 2-32 • On LHS Y-axis mark corresponding temp in degree Celsius (26 C) • Join both points and extend to RHS Y- axis. The point on RHS Y-axis give viscosity in cP. μ = 0.9cP = 0.9x10-3P=0.9x10-3 μ = 9 x 10-4 Poise kg/ms
  • 20. STEP 9 : jH FACTOR Page no : 5 -16, eqn 5-50c 7e PCH jH = 3.6119 x 10-3
  • 21. STEP 10: HEAT TRANSFER COEFFICIENT To determine hi , eqn 5-50c is used Nst = Stanton number Npr = Prandtl number Thermal conductivity, k is to be calculated to calculate Npr Here we are using water as coolant , page no. 2-451, table 2-322 give Npr of liquid refrigerants From table we get, Npr of water at 300K = 5.69
  • 22. Heat transfer coefficient Heat transfer coefficient, hi = 3018.59 W/m2K Npr
  • 23. STEP 11: CALCULATION OF hio hio= 2345.16 W/m2K
  • 24. Reynolds number, Re = 26806.37 I. = 0.0138 m II. Gs = v . ρ = mass flow rate (W) / area (as) = 0.013 m C = PT – OD of tube = 4.75 x 10-3 Gs = v. ρ = 1068.37 kg/m2s B = 150 mm (assumption) III. μ from page no. 2-449 (as shown earlier, here check for benzene) μ = 0.55 cP = 5.5 x 10-4 kg/ms STEP 12: REYNOLDS NUMBER – SHELL SIDE FLUID
  • 25. STEP 13 : jH FACTOR Page no : 5 -16, eqn 5-50c 7e PCH jH = 2.9928 x 10-3
  • 26. STEP 14: HEAT TRANSFER COEFFICIENT To determine hi , eqn 5-50c is used Nst = Stanton number Npr = Prandtl number To determine hi , eqn 5-50c is used Nst = Stanton number Npr = Prandtl number Heat transfer coefficient, ho = 7199.88 W/m2K
  • 27. • Thermal conductivity, k is to be calculated to calculate Npr • Page no. 2-450 • Fig 2-33 1. Note temp of shell side fluid on LHS y- axis (47.5 C) 2. Identify the compound number and mark that in the fig (Benzene-13) 3. Join these two points (Temp and compound number) and extend to RHS Y-axis (k) 4. k= 138 mW/mK = 0.138 W/mK
  • 28. STEP 15 : CALCULATE tw • Tmean = mean temperature of benzene = 320.5 K • tmean = mean temperature of water = 299 K tw = 304.28 K = 31.28oC
  • 29. STEP 16: CALCULATION OF (μw/μb)0.14 • μb = bulk viscosity at mean temp • μw = viscosity at tw From page no. 2 -449 calculate μb,benzene, μw, benzene, μb, water, μw, water (μb)benzene = 5.5 x 10-4 (μb)water = 9x10-4 (μw)benzene = 5.6 x10-4 (μw)water = 8.3 x10-4 hi, corrected = hi/(μw/μb)0.14 water = 3053.09 W/m2K ho, corrected = ho /(μw/μb)0.14 benzene = 7181.74 W/m2K
  • 30. = 0.002125 m = 0.0168 m kw  page no. 2-461, table 2-328- 8e page no. 2-335, table 2-375- 7e kw = 9.4 Btu/h.ft2.(oF/ft) = 18.91 W/mK 1/Ui = 5.347 x 10-4 m2K/W Ui = 1870.17 W/m2K STEP 17: OVERALL HEAT TRANSFER COEFFICIENT, Ui Btu/h.ft2.(oF/ft) Kcal/hr.m.oC W/mK X 1.73 X 1.163
  • 31. Q = Ui. Ai. FT. ΔTLMTD • Q = W Cp (T1 – T2) = w Cp (t2 – t1) = 6.29 x105 J/s • FT = 0.88 • ΔTLMTD = 293.83 K • Ui = 1870.17 W/m2K Ai = 1.3 m2 STEP 18: HEAT TRANSFER AREA, Ai
  • 32. Calculated Dirt factor, Ui = Uc = 1870.17 W/m2K n = 228 di = 0.0148 m L = 8ft = 2.45 m UDa = 74.55 W/m2K Rdc = 0.0129 m2K/W STEP 19: CALCULATION OF DIRT FACTOR, Rdc
  • 33. Page no. 11-25, table 11-3 – 8e Dirt factor, Rd = 0.03 (oF . Ft2 . H)/ Btu = 5.283 x 10-4 m2Ks/J Rdc > Rd : so our assumptions are correct (oF . Ft2 . H)/ Btu M2.K. s/ J X 0.1761
  • 34. STEP 20: PRESSURE DROP – TUBE SIDE / TUBE PASS Pressure drop through tube side fluid (ΔP)T = (ΔP)t + (ΔP)r 1. Pressure drop (ΔP)t for std length of tube is given by Fanning eqn: = 1187.13 N/m2 2. Pressure drop through expansion & contraction, (ΔP)r = 1629.83 N/m2 (ΔP)T = 2816.96 N/m2 For 1 tube pass- 2 expansion & 2 contraction losses. At entrance and exit there is contraction and expansion. ( 2x0.5)+(2x1)+(2x0.5)=4 So, 4 velocity heads per pass
  • 35. nT = 2 V = 0.64 m/s ρ = 994.77 kg/m3 L = 2.45m d = 0.0148 m f  page no. 6-10, figure 6-9 From table 6-1, surface roughness, ε, for particular material, here assume commercial steel or wrought iron = 0.0457
  • 36.
  • 37. X axis = NRe = 1.04 x 104 Y axis (RHS) = f = 0.0088 Yaxis (LHS)= ε/di = 0.00309 Use chart to calculate ‘f’ • Find the NRe (1.04x104) on X axis and draw a normal line to the ε/di (0.00309) curve. • Then extend the line from the point of intersection with Y axis. • The Y axis will give the f (0.0088)
  • 38. = 0.0203 • ρ of benzene is measured from page no. 2-98, table – 2-32 7e & 8e STEP 20: PRESSURE DROP – SHELL SIDE (ΔP)shell = 56388.20 N/m2
  • 39. Assume allowable pressure drop inside tube = 10psi = 10 x 6894.757 N/m2 = 68947.57 N/m2 (ΔP) allowable > (ΔP) shell > (ΔP) tube 68947.57 N/m2 > 56388.20 N/m2 > 2816.96 N/m2 So, check for shell side and tube side fluid is correct Our design is correct.