Motor Bearing Current Phenomenon and
3-Level Inverter Technology
Applicable Product: G7
Rev: 05-06
G7 three-level output
waveform
Conventional two-level output
waveform
Subject: Application Note Product: G7 Doc#: AN.G7.02
Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology
Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 2/13
INTRODUCTION
Since the introduction of PWM inverters, it has been recognized that PWM inverters introduce motor shaft
voltages and bearing currents. The bearing damage in inverter-driven motors is mainly caused by the shaft
voltage and bearing currents created by the common-mode voltage and its sharp edges [1]. All inverters generate
common-mode voltages relative to the power source ground that cause coupling currents through the parasitic
capacitances inside the motor. The main source of bearing currents is the capacitance-coupling currents that
return via the motor bearings back to the ground.
This paper describes the common-mode voltage in inverter-driven AC machines and compares them in 2-level
and 3-level inverters. The relationship among common-mode voltage, motor shaft voltage, and bearing currents
are discussed using parasitic capacitances and its mathematical representation inside the motor. Test results of
shaft voltage and bearing currents are presented to prove that 3-level technology adopted in the Yaskawa G7 has
significant advantages over the 2-level inverter with regards to shaft voltage and bearing currents, which result in
reduced bearing damage.
COMMON-MODE VOLTAGE IN INVERTER-DRIVEN AC MACHINES
Common-mode Voltage
In a three-phase AC system, the common-mode voltage can be defined as the voltage difference between the
power source ground and the neutral point of a three-phase load. If the load is an AC motor, the neutral point of
the load means the stator neutral of the motor. It is important to define the common-mode voltage in mathematical
terms in order to compare its characteristics among different types of source and load combinations.
In a three-phase AC system, the phase to ground voltage can be written as the sum of the voltage from phase to
the neutral point of the load and the neutral point of the load to system ground. As per the definition, the common
mode voltage is the voltage across the neutral point of the load and the system ground. Since in a balanced
system, the sum of all three phase-to-neutral voltages is zero, the voltage from neutral to ground (common-mode
voltage) can be defined in terms of phase to ground voltage as shown below.
0
)
1
(
3
,
,
,
,
,
,
=
+
+
=
∴
+
=
∑ −
−
−
−
−
−
−
−
N
c
b
a
G
c
G
b
G
a
G
N
G
N
N
c
b
a
G
c
b
a
V
V
V
V
V
V
V
V
Q
Subject: Application Note Product: G7 Doc#: AN.G7.02
Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology
Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 3/13
In equation (1), it is assumed that the load is balanced so that the sum of all three phase-to-neutral voltages is
zero (∑Va,b,c-N = 0). If the source is also assumed to be balanced and ideal, then the sum of all three phase-to-
ground voltages is zero (∑Va,b,c-G = 0). Under such an ideal case, for a balanced AC motor driven by a balanced
three-phase AC source, from equation (1), the common mode voltage VN-G, will be zero. However, in the case of
an inverter-driven AC machine, there exists a common-mode voltage because the voltage source inverter does
not constitute an ideal balanced source. Figure 1 shows a typical 2-level voltage source inverter-fed AC machine.
G
Input
impedance
Diode rectifier
DC link choke
DC
capacitor
N
Ground
Neutral
point
Frame
Ground
Three-phase
Input source
IGBT switch
R
S
T
U
V
W
+
-
E
E/2
E/2
M
DC bus
mid point
G
Qu1
Qu2
Qv1
Qv2
Qw1
Qw2
icom
VN-G
VN-M
VM-G ( VN-G =Vcom)
≈
Figure 1. 2-level inverter-driven AC machine
In an inverter-driven system, the common mode voltage (Vcom or VN-G) can also be defined as the voltage across
the stator neutral (N) and the DC bus mid-point (M) because from a high-frequency viewpoint, the DC bus mid-
point (M) is same as the electrical ground (G) of the system. Using this definition, the common-mode voltage can
be redefined as done in equation (2). This definition would then be valid for 3-level inverters as well.
)
2
(
3
M
W
M
V
M
U
M
N
G
N
com
V
V
V
V
V
V −
−
−
−
−
+
+
=
≈
=
In equation (2), it should be noted that the source voltage nomenclature has been changed from Va,b,c-G to Vu,v,w-M
to reflect the fact that the source now is the voltage source inverter.
Subject: Application Note Product: G7 Doc#: AN.G7.02
Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology
Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 4/13
The common mode current (icom) is defined as the instantaneous sum-total of all the currents flowing through the
output conductors. Stray capacitances of the motor cable and inside the motor are the paths of this current, and a
source of EMI noise problems.
2-level Inverter
In 2-level voltage source inverters, there are eight different switching states for the six inverter-switches, and the
voltages across the output terminals and the DC bus mid-point (VU-M, VV-M, and VW-M) can be either +E/2 or -E/2
according to the inverter switching states. The three output legs could 1) be all connected to the positive or
negative rail of the DC bus; 2) two legs can be connected to the positive rail and one leg to the negative rail or
vice-versa. Given these constraints and from equation (2), the inverter output neutral with respect to the DC bus
mid-point will have a voltage of ±E/2 for condition 1) and a voltage of ±E/6 for condition 2). Figure 2 shows an
example of the switching states and the common-mode voltage waveform. During a PWM cycle, the change in
voltage from -E/2 to -E/6 constitutes a change of E/3. When the level changes from -E/6 to +E/6 the change in
voltage is again E/3. Since this change in voltage is proportional to the DC bus voltage and has a frequency equal
to the inverter carrier frequency, the change in the common-mode voltage level is steep and typically occurs in
hundreds of nanoseconds.
2-level Inverter Output Voltage
(Between inverter terminals and DC bus mid-point)
Common-mode
Voltage
VU-M VV-M VW-M Vcom
E/2 E/2 E/2 E/2
E/2 E/2 -E/2 E/6
E/2 -E/2 -E/2 -E/6
-E/2 -E/2 -E/2 -E/2
T/2
T/12
T/4 3T/4 T
E/2
E/6
-E/6
-E/2
time
Common-mode
voltage
Figure 2. 2-level inverter switching states and the corresponding common-mode voltage
Since the motor windings are fed from PWM pulses having fast rising and falling common mode voltage edges,
there exists a leakage current from each phase to ground due to the existence of various parasitic capacitances
that include cable capacitance formed between the power leads and ground and other capacitances between the
stator winding to the grounded frame. This leakage current flows only during the step change in the common
mode voltage and is called common mode current.
Subject: Application Note Product: G7 Doc#: AN.G7.02
Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology
Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 5/13
MOTOR SHAFT VOLTAGE AND COMMON-MODE VOLTAGE
Parasitic Capacitances Inside the Motor
Figure 3 shows the various parasitic capacitances in an AC motor that become relevant when the motor is driven
by a PWM voltage source inverter. The high dv/dt of the common mode voltage applied across the stator and
grounded frame of the motor causes pulsed currents to flow through the parasitic capacitances shown in Figure 3.
The parasitic capacitances shown are:
a. Stator to Frame capacitance or CSF: This is the primary capacitance that is formed between the stator
winding and the grounded frame. It is perhaps the largest single parasitic capacitance in the motor. Most
of the common mode current due to the high dv/dt of the common mode voltage flows through this path.
b. Stator to Rotor capacitance or CSR: This capacitance is formed in between the stator winding and the
rotor frame. The value of this capacitance is rather small but is the principal path that charges the rotor
body to which the motor shaft is physically connected. Hence, the value of this capacitance is very
important in evaluating the magnitude of the shaft voltage.
c. Rotor to Frame capacitance or CRF: The rotor to frame capacitance completes the charging path that
started from the stator winding to the rotor surface. The value of this capacitance is typically about ten
times that of the stator winding to rotor surface capacitance (CSR). Since the voltage across a capacitor is
inversely proportional to its capacitance value, the most of the applied common mode voltage appears
across CSR and only a small voltage is developed across CRF or the rotor to frame structure. This voltage
is called the “shaft voltage”. Thus the rotor to frame capacitance is vital in establishing the shaft voltage.
d. Shaft to Frame capacitance or Bearing capacitance, CB: When the motor is rotated at or above a certain
speed, the balls in a ball-bearing or rollers in a roller-bearing of the motor float up and occupy the space
in between the inner and outer race of the bearing. An insulating film is formed by the lubricant medium in
which the ball or roller is floating. The value of this capacitance depends on the shaft speed, type of
lubricant used, the surface area of the ball or roller in the bearing, the temperature of the lubricant, and
the mechanical load on the shaft. This parasitic capacitance is transient and is formed only when the
motor rotates and hence it is shown to be variable in Figure 3. The value of this capacitance is important
because its characteristics determine bearing current and dictates the life of the bearing.
All of the above parasitic capacitances are depicted in an electrical model shown in Figure 3(a) and its
physical presence shown in Figure 3(b).
Subject: Application Note Product: G7 Doc#: AN.G7.02
Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology
Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 6/13
V
C
SR
RF
Common
Mode
Voltage
CB
Bearing
Stator Winding
C V
SH
SF
C
Shaft
Frame
Rotor
Stator
Vcom
(a) Electrical representation of parasitic capacitances in a motor
(b) Physical position of parasitic capacitances in a motor
Inner Race
Outer Race
VSH
CSR
CSF
CRF CB
Vcom
Figure 3. Electrical and physical models of parasitic capacitances in a motor
Relationship Between Motor Shaft Voltage and Common-mode Voltage
Figure 4 shows typical common-mode voltage and shaft voltage in a two-level inverter. As show in Figure 4, the
shaft voltage (VSH) has the same shape as the stator common-mode voltage (Vcom) because as mentioned earlier,
the shaft voltage is formed as a result of the common mode voltage and the capacitive voltage divider circuit
shown in Figure 3. VSH can be obtained from the expression shown below.
)
3
(
V
C
C
C
C
V com
B
RF
SR
SR
SH ⋅
+
+
=
Subject: Application Note Product: G7 Doc#: AN.G7.02
Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology
Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 7/13
As mentioned earlier, the ratio VSH / Vcom is typically 1:10 because the value of CRF is much larger than that of CSR.
The exact ratio depends on the size of the motor. From (3), it is also interesting to note that at standstill and low
speeds, the inner race and outer race of the bearing are in physical contact via the balls or rollers in the bearing
that results in a value of infinity for CB, resulting in zero shaft voltage.
Common-mode voltage (250V/div)
Motor shaft voltage (10V/div)
Time (200µs/div) Time (200µs/div)
Motor shaft voltage (10V/div)
Common-mode voltage (250V/div)
Common-mode voltage (250V/div)
Time (20µs/div)
Figure 4. Common-mode voltage and shaft voltage in an inverter-driven AC machine
BEARING CURRENTS AND ITS GENERATION MECHANISMS
The common-mode voltage and its associated dv/dt, generate bearing currents. Due to the various physical paths
that exist as shown in Figure 3, different mechanisms can be assigned to the generation of different types of
bearing currents. As shown in Figure 5, bearing currents can be summarized into four different currents according
to their generation mechanism.
1) Capacitive bearing currents (i1)
High common-mode voltage dv/dt in the stator windings causes pulse currents to flow to the rotor through
the stray capacitance between the stator winding and the rotor surface (CSR). These currents get
distributed to two different paths. The first path is the return path formed by the capacitance between the
rotor and the frame CRF and the second path is that formed by the capacitance in between the inner race
of the bearing and the outer race of the bearing, CB. Since CSR is much smaller than the parallel
combination of CRF and CB, the amplitude of i1 is small compared to the total common-mode current (iSF).
However, the consistent flow of this current through the bearing capacitance causes heat in the lubricating
medium and its exact influence on bearing failure is still being investigated by researchers in this field. It
should be pointed out that the portion of the current that flows through the bearing is dependent on the
speed and mechanical load on the shaft. At low speeds, the bearing could be represented by a short
Subject: Application Note Product: G7 Doc#: AN.G7.02
Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology
Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 8/13
circuit resulting in relatively higher value of i1 to flow through it. Since this current flows through the
metallic parts in the bearing, its influence on the insulating film is thought to be negligible.
2) Electric Discharge Machining (EDM) bearing currents (i2)
Due to the common-mode voltage, an electric charge is stored in the capacitance (CRF) that is formed
across the rotor body and the grounded stator frame. The voltage across CRF is practically the voltage
across the shaft as seen from Figures 3(a) and (b). The voltage across this capacitor can keep building up
and eventually reach such a level so as to cause the insulation of the lubricating film to breakdown. This
dielectric breakdown results in the charge stored across CRF to discharge through the insulating film of the
bearing thereby creating what is known as EDM bearing current. Since the capacitance of CRF is relatively
higher than CSR, the energy stored in CRF can be sufficiently large to cause bearing damage. EDM
currents are not generated if the motor shaft is grounded or the rotating speed is low enough for the ball
bearing assembly to contact the stator frame. EDM current does not flow at every edge of the common
mode voltage. The instant at which it flows depends on when the insulation film undergoes a dielectric
breakdown and this could be arbitrary.
V
CRF
SR
CB
Bearing
Stator Winding
C V
SH
SF
C
Shaft
Frame
Rotor
Vcom
i2
i3
i1
Stator
Common
Mode
Voltage
i4
iSF
Figure 5. Bearing current paths in an inverter-driven AC machine
3) Common mode current flow through shaft due to poor grounding (i3)
If the motor frame is poorly grounded and the motor shaft is connected to a mechanical load that has
much lower ground impedance, the common mode current that flows at every edge of the common mode
voltage through the capacitor CSR and charges up the rotor structure now finds a way to flow through the
Subject: Application Note Product: G7 Doc#: AN.G7.02
Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology
Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 9/13
shaft into an external ground that has a lower impedance. This is exactly what happens when an external
grounding brush kit is used to ground the rotating shaft. The current bypasses the bearing and makes its
way safely into a lower impedance ground through the shaft or the load structure connected to the shaft.
4) Circulating bearing currents (i4)
The shaft voltage is due to asymmetry in the magnetic field from one end of the rotor to the other end of
the rotor and is prevalent in long axial machines. This asymmetry induces a shaft voltage across the
length of the rotor and is basically an electromagnetic induction phenomenon opposed to the capacitive
coupled phenomenon discussed thus far. This phenomenon is observed only in long axial machines that
are used for large horsepower applications typically greater than 110-kW [2]. Yet another distinction that
should be pointed out here is that the induced voltage is of very low frequency and depends on the
fundamental excitation of the motor. The circulating current flows along the axis of the rotor, through the
bearings and circulates through the stator frame and returns back from the other bearing end. This current
is generally not significant in small power AC machines less than 110kW [3].
BEARING CURRENT REDUCTION
There are some approaches that prevent bearing current damage of AC machines. They are as follows:
• External passive / active common-mode filters
Common-mode noise filters are a good solution to cancel common-mode noise of the system, but typical
common-mode noise filters consist of magnetically coupled three-phase inductor and capacitor
components. These filters are bulky and expensive; in addition, filters reduce efficiency, and can cause
voltage oscillation if parameters of the passive components are not tuned properly.
• Motor shaft ground brushes or insulated bearings
The grounding of the motor shaft by connecting a brush between the motor shaft and the motor frame is
an effective way to shunt the current path that normally would flow through the motor bearing. However,
regular maintenance is required due to limited lifetime of the brush. Insulated bearings such as ceramic
bearings can also prevent bearing current problems but required the replacement of the existing bearings
in the motor.
• Multi-level inverter technologies
Reducing the amplitude and voltage transition step of the common-mode voltage can reduce bearing
currents. One way of achieving this is to use a multi-level inverter topology. Progress in inverter
Subject: Application Note Product: G7 Doc#: AN.G7.02
Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology
Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 10/13
technology has made it possible to introduce a 3-level inverter (i.e. the G7 Drive) to the general purpose-
inverter market [1]. The advantages of a 3-level inverter are discussed in the next section.
FEATURES AND ADVANTAGES OF THE G7 3-LEVEL INVERTER
General Features of the 3-Level Inverter
Figure 6 shows a typical neutral-point clamped 3-level inverter. In order to determine the common-mode voltage
in a three-level inverter, it is important to understand the various switching combinations in a 3-level inverter. In
contrast to a 2-level inverter, a 3-level inverter has four switches (IGBTs) per phase, totaling twelve switches
(IGBTs) for all three phases. According to the switching signals, each output phase voltage with respect to the DC
bus mid-point can have three distinct levels, i.e. E/2, 0, and -E/2. Consequently, this arrangement is called a 3-
level inverter.
+
-
U
V
W
E
2
E
+
-
E
2
VU-M
M
U V
W
-
+
N
DC link choke
DC
capacitor
R
S
T
G
Figure 6. A typical neutral-point clamped 3-level inverter
Figure 7 shows various switching states and common-mode voltage waveforms among 27 different switching
states of the 3-level inverter. By comparing the common-mode voltage of a 3-level inverter to that of a 2-level
inverter as shown in figure 2, it is clear that in a 2-level inverter the difference in voltage level from one state to the
other is always ±E/3. In the case of a 3-level inverter, the voltage level is generally ±E/6. This means that the
transition level of the common-mode voltage in a 3-level inverter is typically one-half of that in the 2-level inverter.
In a 3-level inverter, the amplitude of the common-mode voltage can be lower than a 2-level inverter in the high
voltage region. In fact, the maximum and minimum values of the common-mode voltage in a 3-level inverter at
higher voltage (i.e. at higher speed) reaches only ±E/3 as shown in Figure 7(b), while the common-mode voltage
Subject: Application Note Product: G7 Doc#: AN.G7.02
Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology
Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 11/13
reaches ±E/2 in the case of a traditional 2-level inverter as shown in Figure 2. The lower transition level of the 3-
level inverter also results in a lower common-mode current compared to the 2-level inverter. This is an important
advantage of the 3-level inverter over the traditional 2-level inverter.
3-level Inverter Output
Voltage
(Between inverter terminal and DC bus
mid-point)
Common-mode
Voltage
VU-M VV-M VW-M Vcom
E/2 E/2 E/2 E/2
E/2 E/2 0 E/3
E/2 0 0 E/6
0 0 0 0
0 0 -E/2 -E/6
0 -E/2 -E/2 -E/3
-E/2 -E/2 -E/2 -E/2
T/2
T/12 T/4 3T/4 T
E/2
E/6
-E/6
-E/2
time
Common-mode
Voltage
-E/3
E/3
T/2
T/8
T
E/2
E/6
-E/6
-E/2
time
-E/3
E/3
7T/8
3T/8
(a) Low output voltage operation
(b) High output voltage operation
Common-mode
Voltage
Figure 7. Various 3-level inverter switching-states and the corresponding common-mode voltage
Reduced Bearing Current and Increased Bearing Life with the G7 3-Level Inverter
The steep voltage transient in the shaft voltage causes current to flow through the bearing insulation. This leads
to the breakdown of the bearing grease insulation and discharge of the shaft voltage. Since the change of the
common-mode voltage is smaller in the 3-level inverter, this provides a significant advantage over the 2-level
inverter with regards to shaft voltage and bearing currents. Figure 8 shows the comparative test results of the
shaft voltage and bearing current for the 2-level and 3-level inverters. In these tests, insulation material was
inserted in between the bearing and the housing so that the current through the bearing could be observed.
Figure 8 shows that the bearing current of the 3-level inverter in Figure 8(b) is significantly smaller than a 2-level
inverter in Figure 8(a).
Actual longevity tests were conducted to verify the superiority of the 3-level inverter. The tests simulated extreme
conditions including temperature, types of grease, and motor speed. The results of the bearing life test are shown
in Figure 9. A key point to note during normal operation is that the normal bearing life would be longer than that
Subject: Application Note Product: G7 Doc#: AN.G7.02
Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology
Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 12/13
shown here. Figure 9 clearly proves that the use of a G7 Drive with a 3-level inverter topology can result in a
significantly longer bearing life.
S
10V
20mA 1ms
Bearing current
Shaft voltage
B
1ms
Shaft voltage
20mA
10V
Bearing current
(a) 2-level inverter (b) 3-level inverter
Figure 8. Shaft voltage and bearing current of the 2-level and 3-level inverters
0
2
4
6
8
10
12
14
16
18
20
0 1000 2000 3000 4000 5000 6000
Hours of operation (hour)
Vibration
at
load-side
bracket
(G)
3-level inverter
2-level inverter
Figure 9. Bearing life test results (1HP, 2100rpm)
Subject: Application Note Product: G7 Doc#: AN.G7.02
Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology
Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 13/13
CONCLUSION
In an inverter-driven AC machine, the common-mode voltage and dv/dt may cause premature motor bearing
failure. This paper compared the common-mode voltage of the 2-level and 3-level inverter. The common-mode
voltage and shaft voltage relationships were also described along with the bearing current mechanisms due to
common-mode voltages. Features and benefits of the G7 Drive 3-level inverter topology that reduce the shaft
voltage and bearing current generation have been presented. Analytical and experimental results show that the
G7 Drive has lower common-mode mode voltage that results in lower bearing currents. Long-term operation tests
also prove that the 3-level technology is effective to prevent bearing damage of motors.
REFERENCES
1. H.-P.Krug,T. Kume, M. Swamy,” Neutral-point clamped three-level general purpose inverter - features, benefits
and applications,” IEEE Power Electronics Specialists Conference, pp.323 - 328, 2004.
2. J. Erdman, R. Kerkman, D. Schlegel, and G. Skibinski, “Effect of PWM inverters in AC Motor Bearing Currents
and Shaft Voltages”, IEEE APEC Conference, Dallas, TX, 1995, CD-ROM
3. A. Muetze, A. Binder,” Experimental evaluation of mitigation techniques for bearing currents in inverter-supplied
drive-systems - investigations on induction motors up to 500 kW,” IEEE International Electric Machines and
Drives Conference, pp.1859 – 1865, vol.3, 2003.
USE OF TECHNICAL INFORMATION!
Technical content and illustrations are provided as technical advice to augment the information in manual, not supercede it. The information
described in this document is subject to change without notice. Yaskawa assumes no responsibility for errors or omissions or damages
resulting from the use of the information contained in any technical document. All warnings, cautions and product instruction for product use
must be followed. Qualified personnel should carry out installation, operation and maintenance.

More Related Content

Similar to AN.G7.02.pdf

Power Quality Improvement Using Cascaded H-Bridge Multilevel Inverter Based D...
Power Quality Improvement Using Cascaded H-Bridge Multilevel Inverter Based D...Power Quality Improvement Using Cascaded H-Bridge Multilevel Inverter Based D...
Power Quality Improvement Using Cascaded H-Bridge Multilevel Inverter Based D...
IJERA Editor
 
Simulation of 3-phase matrix converter using space vector modulation
Simulation of 3-phase matrix converter using space vector modulationSimulation of 3-phase matrix converter using space vector modulation
Simulation of 3-phase matrix converter using space vector modulation
IJECEIAES
 
DC-link voltage balancing and control of qZ-source inverter fed induction mo...
DC-link voltage balancing and control of qZ-source inverter fed  induction mo...DC-link voltage balancing and control of qZ-source inverter fed  induction mo...
DC-link voltage balancing and control of qZ-source inverter fed induction mo...
IJECEIAES
 
I41045662
I41045662I41045662
I41045662
IJERA Editor
 
Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...
Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...
Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...
IAES-IJPEDS
 
Application of SVM Technique for Three Phase Three Leg Ac/Ac Converter Topology
Application of SVM Technique for Three Phase Three Leg Ac/Ac Converter TopologyApplication of SVM Technique for Three Phase Three Leg Ac/Ac Converter Topology
Application of SVM Technique for Three Phase Three Leg Ac/Ac Converter Topology
IOSR Journals
 
Proposed Method for Shoot-Through in Three Phase ZSI and Comparison of Differ...
Proposed Method for Shoot-Through in Three Phase ZSI and Comparison of Differ...Proposed Method for Shoot-Through in Three Phase ZSI and Comparison of Differ...
Proposed Method for Shoot-Through in Three Phase ZSI and Comparison of Differ...
IAES-IJPEDS
 
Analysis Approach for Five Phase Two-Level Voltage Source Inverter with PWM T...
Analysis Approach for Five Phase Two-Level Voltage Source Inverter with PWM T...Analysis Approach for Five Phase Two-Level Voltage Source Inverter with PWM T...
Analysis Approach for Five Phase Two-Level Voltage Source Inverter with PWM T...
ijsrd.com
 
Simulation of D-STATCOM to study Voltage Stability in Distribution system
Simulation of D-STATCOM to study Voltage Stability in Distribution systemSimulation of D-STATCOM to study Voltage Stability in Distribution system
Simulation of D-STATCOM to study Voltage Stability in Distribution system
ijsrd.com
 
Inductorless DC-AC Cascaded H-bridge Multilevel Boost Inverter for Electric/...
Inductorless DC-AC Cascaded H-bridge MultilevelBoost Inverter for Electric/...Inductorless DC-AC Cascaded H-bridge MultilevelBoost Inverter for Electric/...
Inductorless DC-AC Cascaded H-bridge Multilevel Boost Inverter for Electric/...mkanth
 
Dc motor
Dc motorDc motor
Dc motor
ashok singh
 
A Novel Space Vector Modulation (SVM) Controlled Inverter For Adjustable Spee...
A Novel Space Vector Modulation (SVM) Controlled Inverter For Adjustable Spee...A Novel Space Vector Modulation (SVM) Controlled Inverter For Adjustable Spee...
A Novel Space Vector Modulation (SVM) Controlled Inverter For Adjustable Spee...
International Journal of Engineering Inventions www.ijeijournal.com
 
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...
IRJET Journal
 
Power Circuits and Transforers-Unit 6 Labvolt Student Manual
Power Circuits and Transforers-Unit 6 Labvolt Student ManualPower Circuits and Transforers-Unit 6 Labvolt Student Manual
Power Circuits and Transforers-Unit 6 Labvolt Student Manual
phase3-120A
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
IJERD Editor
 
POWER SYSTEM ANALYSIS-3
POWER SYSTEM ANALYSIS-3POWER SYSTEM ANALYSIS-3
POWER SYSTEM ANALYSIS-3
M Ugur Kebir
 
EMEC-II, unit 1
EMEC-II, unit 1EMEC-II, unit 1
EMEC-II, unit 1
Mohammad Imran
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
IJERD Editor
 
Simulation and Analysis of a D-STATCOM for Load Compensation and Power Facto...
Simulation and Analysis of a D-STATCOM for Load  Compensation and Power Facto...Simulation and Analysis of a D-STATCOM for Load  Compensation and Power Facto...
Simulation and Analysis of a D-STATCOM for Load Compensation and Power Facto...
IJMER
 
Analysis and hardware implementation of five level cascaded H Bridge inverter
Analysis and hardware implementation of five level cascaded H Bridge inverterAnalysis and hardware implementation of five level cascaded H Bridge inverter
Analysis and hardware implementation of five level cascaded H Bridge inverter
IJERA Editor
 

Similar to AN.G7.02.pdf (20)

Power Quality Improvement Using Cascaded H-Bridge Multilevel Inverter Based D...
Power Quality Improvement Using Cascaded H-Bridge Multilevel Inverter Based D...Power Quality Improvement Using Cascaded H-Bridge Multilevel Inverter Based D...
Power Quality Improvement Using Cascaded H-Bridge Multilevel Inverter Based D...
 
Simulation of 3-phase matrix converter using space vector modulation
Simulation of 3-phase matrix converter using space vector modulationSimulation of 3-phase matrix converter using space vector modulation
Simulation of 3-phase matrix converter using space vector modulation
 
DC-link voltage balancing and control of qZ-source inverter fed induction mo...
DC-link voltage balancing and control of qZ-source inverter fed  induction mo...DC-link voltage balancing and control of qZ-source inverter fed  induction mo...
DC-link voltage balancing and control of qZ-source inverter fed induction mo...
 
I41045662
I41045662I41045662
I41045662
 
Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...
Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...
Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...
 
Application of SVM Technique for Three Phase Three Leg Ac/Ac Converter Topology
Application of SVM Technique for Three Phase Three Leg Ac/Ac Converter TopologyApplication of SVM Technique for Three Phase Three Leg Ac/Ac Converter Topology
Application of SVM Technique for Three Phase Three Leg Ac/Ac Converter Topology
 
Proposed Method for Shoot-Through in Three Phase ZSI and Comparison of Differ...
Proposed Method for Shoot-Through in Three Phase ZSI and Comparison of Differ...Proposed Method for Shoot-Through in Three Phase ZSI and Comparison of Differ...
Proposed Method for Shoot-Through in Three Phase ZSI and Comparison of Differ...
 
Analysis Approach for Five Phase Two-Level Voltage Source Inverter with PWM T...
Analysis Approach for Five Phase Two-Level Voltage Source Inverter with PWM T...Analysis Approach for Five Phase Two-Level Voltage Source Inverter with PWM T...
Analysis Approach for Five Phase Two-Level Voltage Source Inverter with PWM T...
 
Simulation of D-STATCOM to study Voltage Stability in Distribution system
Simulation of D-STATCOM to study Voltage Stability in Distribution systemSimulation of D-STATCOM to study Voltage Stability in Distribution system
Simulation of D-STATCOM to study Voltage Stability in Distribution system
 
Inductorless DC-AC Cascaded H-bridge Multilevel Boost Inverter for Electric/...
Inductorless DC-AC Cascaded H-bridge MultilevelBoost Inverter for Electric/...Inductorless DC-AC Cascaded H-bridge MultilevelBoost Inverter for Electric/...
Inductorless DC-AC Cascaded H-bridge Multilevel Boost Inverter for Electric/...
 
Dc motor
Dc motorDc motor
Dc motor
 
A Novel Space Vector Modulation (SVM) Controlled Inverter For Adjustable Spee...
A Novel Space Vector Modulation (SVM) Controlled Inverter For Adjustable Spee...A Novel Space Vector Modulation (SVM) Controlled Inverter For Adjustable Spee...
A Novel Space Vector Modulation (SVM) Controlled Inverter For Adjustable Spee...
 
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...
 
Power Circuits and Transforers-Unit 6 Labvolt Student Manual
Power Circuits and Transforers-Unit 6 Labvolt Student ManualPower Circuits and Transforers-Unit 6 Labvolt Student Manual
Power Circuits and Transforers-Unit 6 Labvolt Student Manual
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
POWER SYSTEM ANALYSIS-3
POWER SYSTEM ANALYSIS-3POWER SYSTEM ANALYSIS-3
POWER SYSTEM ANALYSIS-3
 
EMEC-II, unit 1
EMEC-II, unit 1EMEC-II, unit 1
EMEC-II, unit 1
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Simulation and Analysis of a D-STATCOM for Load Compensation and Power Facto...
Simulation and Analysis of a D-STATCOM for Load  Compensation and Power Facto...Simulation and Analysis of a D-STATCOM for Load  Compensation and Power Facto...
Simulation and Analysis of a D-STATCOM for Load Compensation and Power Facto...
 
Analysis and hardware implementation of five level cascaded H Bridge inverter
Analysis and hardware implementation of five level cascaded H Bridge inverterAnalysis and hardware implementation of five level cascaded H Bridge inverter
Analysis and hardware implementation of five level cascaded H Bridge inverter
 

Recently uploaded

Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&BDesign and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Sreedhar Chowdam
 
Democratizing Fuzzing at Scale by Abhishek Arya
Democratizing Fuzzing at Scale by Abhishek AryaDemocratizing Fuzzing at Scale by Abhishek Arya
Democratizing Fuzzing at Scale by Abhishek Arya
abh.arya
 
Planning Of Procurement o different goods and services
Planning Of Procurement o different goods and servicesPlanning Of Procurement o different goods and services
Planning Of Procurement o different goods and services
JoytuBarua2
 
road safety engineering r s e unit 3.pdf
road safety engineering  r s e unit 3.pdfroad safety engineering  r s e unit 3.pdf
road safety engineering r s e unit 3.pdf
VENKATESHvenky89705
 
Halogenation process of chemical process industries
Halogenation process of chemical process industriesHalogenation process of chemical process industries
Halogenation process of chemical process industries
MuhammadTufail242431
 
Automobile Management System Project Report.pdf
Automobile Management System Project Report.pdfAutomobile Management System Project Report.pdf
Automobile Management System Project Report.pdf
Kamal Acharya
 
The role of big data in decision making.
The role of big data in decision making.The role of big data in decision making.
The role of big data in decision making.
ankuprajapati0525
 
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
obonagu
 
Railway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdfRailway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdf
TeeVichai
 
CME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional ElectiveCME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional Elective
karthi keyan
 
Architectural Portfolio Sean Lockwood
Architectural Portfolio Sean LockwoodArchitectural Portfolio Sean Lockwood
Architectural Portfolio Sean Lockwood
seandesed
 
Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
Kamal Acharya
 
Quality defects in TMT Bars, Possible causes and Potential Solutions.
Quality defects in TMT Bars, Possible causes and Potential Solutions.Quality defects in TMT Bars, Possible causes and Potential Solutions.
Quality defects in TMT Bars, Possible causes and Potential Solutions.
PrashantGoswami42
 
weather web application report.pdf
weather web application report.pdfweather web application report.pdf
weather web application report.pdf
Pratik Pawar
 
ASME IX(9) 2007 Full Version .pdf
ASME IX(9)  2007 Full Version       .pdfASME IX(9)  2007 Full Version       .pdf
ASME IX(9) 2007 Full Version .pdf
AhmedHussein950959
 
Forklift Classes Overview by Intella Parts
Forklift Classes Overview by Intella PartsForklift Classes Overview by Intella Parts
Forklift Classes Overview by Intella Parts
Intella Parts
 
Cosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdfCosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdf
Kamal Acharya
 
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdfTop 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Teleport Manpower Consultant
 
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdfAKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
SamSarthak3
 
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Dr.Costas Sachpazis
 

Recently uploaded (20)

Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&BDesign and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
Design and Analysis of Algorithms-DP,Backtracking,Graphs,B&B
 
Democratizing Fuzzing at Scale by Abhishek Arya
Democratizing Fuzzing at Scale by Abhishek AryaDemocratizing Fuzzing at Scale by Abhishek Arya
Democratizing Fuzzing at Scale by Abhishek Arya
 
Planning Of Procurement o different goods and services
Planning Of Procurement o different goods and servicesPlanning Of Procurement o different goods and services
Planning Of Procurement o different goods and services
 
road safety engineering r s e unit 3.pdf
road safety engineering  r s e unit 3.pdfroad safety engineering  r s e unit 3.pdf
road safety engineering r s e unit 3.pdf
 
Halogenation process of chemical process industries
Halogenation process of chemical process industriesHalogenation process of chemical process industries
Halogenation process of chemical process industries
 
Automobile Management System Project Report.pdf
Automobile Management System Project Report.pdfAutomobile Management System Project Report.pdf
Automobile Management System Project Report.pdf
 
The role of big data in decision making.
The role of big data in decision making.The role of big data in decision making.
The role of big data in decision making.
 
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
 
Railway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdfRailway Signalling Principles Edition 3.pdf
Railway Signalling Principles Edition 3.pdf
 
CME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional ElectiveCME397 Surface Engineering- Professional Elective
CME397 Surface Engineering- Professional Elective
 
Architectural Portfolio Sean Lockwood
Architectural Portfolio Sean LockwoodArchitectural Portfolio Sean Lockwood
Architectural Portfolio Sean Lockwood
 
Final project report on grocery store management system..pdf
Final project report on grocery store management system..pdfFinal project report on grocery store management system..pdf
Final project report on grocery store management system..pdf
 
Quality defects in TMT Bars, Possible causes and Potential Solutions.
Quality defects in TMT Bars, Possible causes and Potential Solutions.Quality defects in TMT Bars, Possible causes and Potential Solutions.
Quality defects in TMT Bars, Possible causes and Potential Solutions.
 
weather web application report.pdf
weather web application report.pdfweather web application report.pdf
weather web application report.pdf
 
ASME IX(9) 2007 Full Version .pdf
ASME IX(9)  2007 Full Version       .pdfASME IX(9)  2007 Full Version       .pdf
ASME IX(9) 2007 Full Version .pdf
 
Forklift Classes Overview by Intella Parts
Forklift Classes Overview by Intella PartsForklift Classes Overview by Intella Parts
Forklift Classes Overview by Intella Parts
 
Cosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdfCosmetic shop management system project report.pdf
Cosmetic shop management system project report.pdf
 
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdfTop 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
 
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdfAKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
AKS UNIVERSITY Satna Final Year Project By OM Hardaha.pdf
 
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
 

AN.G7.02.pdf

  • 1. Application Note Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 1/13 Product Application Note Motor Bearing Current Phenomenon and 3-Level Inverter Technology Applicable Product: G7 Rev: 05-06 G7 three-level output waveform Conventional two-level output waveform
  • 2. Subject: Application Note Product: G7 Doc#: AN.G7.02 Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 2/13 INTRODUCTION Since the introduction of PWM inverters, it has been recognized that PWM inverters introduce motor shaft voltages and bearing currents. The bearing damage in inverter-driven motors is mainly caused by the shaft voltage and bearing currents created by the common-mode voltage and its sharp edges [1]. All inverters generate common-mode voltages relative to the power source ground that cause coupling currents through the parasitic capacitances inside the motor. The main source of bearing currents is the capacitance-coupling currents that return via the motor bearings back to the ground. This paper describes the common-mode voltage in inverter-driven AC machines and compares them in 2-level and 3-level inverters. The relationship among common-mode voltage, motor shaft voltage, and bearing currents are discussed using parasitic capacitances and its mathematical representation inside the motor. Test results of shaft voltage and bearing currents are presented to prove that 3-level technology adopted in the Yaskawa G7 has significant advantages over the 2-level inverter with regards to shaft voltage and bearing currents, which result in reduced bearing damage. COMMON-MODE VOLTAGE IN INVERTER-DRIVEN AC MACHINES Common-mode Voltage In a three-phase AC system, the common-mode voltage can be defined as the voltage difference between the power source ground and the neutral point of a three-phase load. If the load is an AC motor, the neutral point of the load means the stator neutral of the motor. It is important to define the common-mode voltage in mathematical terms in order to compare its characteristics among different types of source and load combinations. In a three-phase AC system, the phase to ground voltage can be written as the sum of the voltage from phase to the neutral point of the load and the neutral point of the load to system ground. As per the definition, the common mode voltage is the voltage across the neutral point of the load and the system ground. Since in a balanced system, the sum of all three phase-to-neutral voltages is zero, the voltage from neutral to ground (common-mode voltage) can be defined in terms of phase to ground voltage as shown below. 0 ) 1 ( 3 , , , , , , = + + = ∴ + = ∑ − − − − − − − − N c b a G c G b G a G N G N N c b a G c b a V V V V V V V V Q
  • 3. Subject: Application Note Product: G7 Doc#: AN.G7.02 Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 3/13 In equation (1), it is assumed that the load is balanced so that the sum of all three phase-to-neutral voltages is zero (∑Va,b,c-N = 0). If the source is also assumed to be balanced and ideal, then the sum of all three phase-to- ground voltages is zero (∑Va,b,c-G = 0). Under such an ideal case, for a balanced AC motor driven by a balanced three-phase AC source, from equation (1), the common mode voltage VN-G, will be zero. However, in the case of an inverter-driven AC machine, there exists a common-mode voltage because the voltage source inverter does not constitute an ideal balanced source. Figure 1 shows a typical 2-level voltage source inverter-fed AC machine. G Input impedance Diode rectifier DC link choke DC capacitor N Ground Neutral point Frame Ground Three-phase Input source IGBT switch R S T U V W + - E E/2 E/2 M DC bus mid point G Qu1 Qu2 Qv1 Qv2 Qw1 Qw2 icom VN-G VN-M VM-G ( VN-G =Vcom) ≈ Figure 1. 2-level inverter-driven AC machine In an inverter-driven system, the common mode voltage (Vcom or VN-G) can also be defined as the voltage across the stator neutral (N) and the DC bus mid-point (M) because from a high-frequency viewpoint, the DC bus mid- point (M) is same as the electrical ground (G) of the system. Using this definition, the common-mode voltage can be redefined as done in equation (2). This definition would then be valid for 3-level inverters as well. ) 2 ( 3 M W M V M U M N G N com V V V V V V − − − − − + + = ≈ = In equation (2), it should be noted that the source voltage nomenclature has been changed from Va,b,c-G to Vu,v,w-M to reflect the fact that the source now is the voltage source inverter.
  • 4. Subject: Application Note Product: G7 Doc#: AN.G7.02 Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 4/13 The common mode current (icom) is defined as the instantaneous sum-total of all the currents flowing through the output conductors. Stray capacitances of the motor cable and inside the motor are the paths of this current, and a source of EMI noise problems. 2-level Inverter In 2-level voltage source inverters, there are eight different switching states for the six inverter-switches, and the voltages across the output terminals and the DC bus mid-point (VU-M, VV-M, and VW-M) can be either +E/2 or -E/2 according to the inverter switching states. The three output legs could 1) be all connected to the positive or negative rail of the DC bus; 2) two legs can be connected to the positive rail and one leg to the negative rail or vice-versa. Given these constraints and from equation (2), the inverter output neutral with respect to the DC bus mid-point will have a voltage of ±E/2 for condition 1) and a voltage of ±E/6 for condition 2). Figure 2 shows an example of the switching states and the common-mode voltage waveform. During a PWM cycle, the change in voltage from -E/2 to -E/6 constitutes a change of E/3. When the level changes from -E/6 to +E/6 the change in voltage is again E/3. Since this change in voltage is proportional to the DC bus voltage and has a frequency equal to the inverter carrier frequency, the change in the common-mode voltage level is steep and typically occurs in hundreds of nanoseconds. 2-level Inverter Output Voltage (Between inverter terminals and DC bus mid-point) Common-mode Voltage VU-M VV-M VW-M Vcom E/2 E/2 E/2 E/2 E/2 E/2 -E/2 E/6 E/2 -E/2 -E/2 -E/6 -E/2 -E/2 -E/2 -E/2 T/2 T/12 T/4 3T/4 T E/2 E/6 -E/6 -E/2 time Common-mode voltage Figure 2. 2-level inverter switching states and the corresponding common-mode voltage Since the motor windings are fed from PWM pulses having fast rising and falling common mode voltage edges, there exists a leakage current from each phase to ground due to the existence of various parasitic capacitances that include cable capacitance formed between the power leads and ground and other capacitances between the stator winding to the grounded frame. This leakage current flows only during the step change in the common mode voltage and is called common mode current.
  • 5. Subject: Application Note Product: G7 Doc#: AN.G7.02 Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 5/13 MOTOR SHAFT VOLTAGE AND COMMON-MODE VOLTAGE Parasitic Capacitances Inside the Motor Figure 3 shows the various parasitic capacitances in an AC motor that become relevant when the motor is driven by a PWM voltage source inverter. The high dv/dt of the common mode voltage applied across the stator and grounded frame of the motor causes pulsed currents to flow through the parasitic capacitances shown in Figure 3. The parasitic capacitances shown are: a. Stator to Frame capacitance or CSF: This is the primary capacitance that is formed between the stator winding and the grounded frame. It is perhaps the largest single parasitic capacitance in the motor. Most of the common mode current due to the high dv/dt of the common mode voltage flows through this path. b. Stator to Rotor capacitance or CSR: This capacitance is formed in between the stator winding and the rotor frame. The value of this capacitance is rather small but is the principal path that charges the rotor body to which the motor shaft is physically connected. Hence, the value of this capacitance is very important in evaluating the magnitude of the shaft voltage. c. Rotor to Frame capacitance or CRF: The rotor to frame capacitance completes the charging path that started from the stator winding to the rotor surface. The value of this capacitance is typically about ten times that of the stator winding to rotor surface capacitance (CSR). Since the voltage across a capacitor is inversely proportional to its capacitance value, the most of the applied common mode voltage appears across CSR and only a small voltage is developed across CRF or the rotor to frame structure. This voltage is called the “shaft voltage”. Thus the rotor to frame capacitance is vital in establishing the shaft voltage. d. Shaft to Frame capacitance or Bearing capacitance, CB: When the motor is rotated at or above a certain speed, the balls in a ball-bearing or rollers in a roller-bearing of the motor float up and occupy the space in between the inner and outer race of the bearing. An insulating film is formed by the lubricant medium in which the ball or roller is floating. The value of this capacitance depends on the shaft speed, type of lubricant used, the surface area of the ball or roller in the bearing, the temperature of the lubricant, and the mechanical load on the shaft. This parasitic capacitance is transient and is formed only when the motor rotates and hence it is shown to be variable in Figure 3. The value of this capacitance is important because its characteristics determine bearing current and dictates the life of the bearing. All of the above parasitic capacitances are depicted in an electrical model shown in Figure 3(a) and its physical presence shown in Figure 3(b).
  • 6. Subject: Application Note Product: G7 Doc#: AN.G7.02 Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 6/13 V C SR RF Common Mode Voltage CB Bearing Stator Winding C V SH SF C Shaft Frame Rotor Stator Vcom (a) Electrical representation of parasitic capacitances in a motor (b) Physical position of parasitic capacitances in a motor Inner Race Outer Race VSH CSR CSF CRF CB Vcom Figure 3. Electrical and physical models of parasitic capacitances in a motor Relationship Between Motor Shaft Voltage and Common-mode Voltage Figure 4 shows typical common-mode voltage and shaft voltage in a two-level inverter. As show in Figure 4, the shaft voltage (VSH) has the same shape as the stator common-mode voltage (Vcom) because as mentioned earlier, the shaft voltage is formed as a result of the common mode voltage and the capacitive voltage divider circuit shown in Figure 3. VSH can be obtained from the expression shown below. ) 3 ( V C C C C V com B RF SR SR SH ⋅ + + =
  • 7. Subject: Application Note Product: G7 Doc#: AN.G7.02 Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 7/13 As mentioned earlier, the ratio VSH / Vcom is typically 1:10 because the value of CRF is much larger than that of CSR. The exact ratio depends on the size of the motor. From (3), it is also interesting to note that at standstill and low speeds, the inner race and outer race of the bearing are in physical contact via the balls or rollers in the bearing that results in a value of infinity for CB, resulting in zero shaft voltage. Common-mode voltage (250V/div) Motor shaft voltage (10V/div) Time (200µs/div) Time (200µs/div) Motor shaft voltage (10V/div) Common-mode voltage (250V/div) Common-mode voltage (250V/div) Time (20µs/div) Figure 4. Common-mode voltage and shaft voltage in an inverter-driven AC machine BEARING CURRENTS AND ITS GENERATION MECHANISMS The common-mode voltage and its associated dv/dt, generate bearing currents. Due to the various physical paths that exist as shown in Figure 3, different mechanisms can be assigned to the generation of different types of bearing currents. As shown in Figure 5, bearing currents can be summarized into four different currents according to their generation mechanism. 1) Capacitive bearing currents (i1) High common-mode voltage dv/dt in the stator windings causes pulse currents to flow to the rotor through the stray capacitance between the stator winding and the rotor surface (CSR). These currents get distributed to two different paths. The first path is the return path formed by the capacitance between the rotor and the frame CRF and the second path is that formed by the capacitance in between the inner race of the bearing and the outer race of the bearing, CB. Since CSR is much smaller than the parallel combination of CRF and CB, the amplitude of i1 is small compared to the total common-mode current (iSF). However, the consistent flow of this current through the bearing capacitance causes heat in the lubricating medium and its exact influence on bearing failure is still being investigated by researchers in this field. It should be pointed out that the portion of the current that flows through the bearing is dependent on the speed and mechanical load on the shaft. At low speeds, the bearing could be represented by a short
  • 8. Subject: Application Note Product: G7 Doc#: AN.G7.02 Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 8/13 circuit resulting in relatively higher value of i1 to flow through it. Since this current flows through the metallic parts in the bearing, its influence on the insulating film is thought to be negligible. 2) Electric Discharge Machining (EDM) bearing currents (i2) Due to the common-mode voltage, an electric charge is stored in the capacitance (CRF) that is formed across the rotor body and the grounded stator frame. The voltage across CRF is practically the voltage across the shaft as seen from Figures 3(a) and (b). The voltage across this capacitor can keep building up and eventually reach such a level so as to cause the insulation of the lubricating film to breakdown. This dielectric breakdown results in the charge stored across CRF to discharge through the insulating film of the bearing thereby creating what is known as EDM bearing current. Since the capacitance of CRF is relatively higher than CSR, the energy stored in CRF can be sufficiently large to cause bearing damage. EDM currents are not generated if the motor shaft is grounded or the rotating speed is low enough for the ball bearing assembly to contact the stator frame. EDM current does not flow at every edge of the common mode voltage. The instant at which it flows depends on when the insulation film undergoes a dielectric breakdown and this could be arbitrary. V CRF SR CB Bearing Stator Winding C V SH SF C Shaft Frame Rotor Vcom i2 i3 i1 Stator Common Mode Voltage i4 iSF Figure 5. Bearing current paths in an inverter-driven AC machine 3) Common mode current flow through shaft due to poor grounding (i3) If the motor frame is poorly grounded and the motor shaft is connected to a mechanical load that has much lower ground impedance, the common mode current that flows at every edge of the common mode voltage through the capacitor CSR and charges up the rotor structure now finds a way to flow through the
  • 9. Subject: Application Note Product: G7 Doc#: AN.G7.02 Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 9/13 shaft into an external ground that has a lower impedance. This is exactly what happens when an external grounding brush kit is used to ground the rotating shaft. The current bypasses the bearing and makes its way safely into a lower impedance ground through the shaft or the load structure connected to the shaft. 4) Circulating bearing currents (i4) The shaft voltage is due to asymmetry in the magnetic field from one end of the rotor to the other end of the rotor and is prevalent in long axial machines. This asymmetry induces a shaft voltage across the length of the rotor and is basically an electromagnetic induction phenomenon opposed to the capacitive coupled phenomenon discussed thus far. This phenomenon is observed only in long axial machines that are used for large horsepower applications typically greater than 110-kW [2]. Yet another distinction that should be pointed out here is that the induced voltage is of very low frequency and depends on the fundamental excitation of the motor. The circulating current flows along the axis of the rotor, through the bearings and circulates through the stator frame and returns back from the other bearing end. This current is generally not significant in small power AC machines less than 110kW [3]. BEARING CURRENT REDUCTION There are some approaches that prevent bearing current damage of AC machines. They are as follows: • External passive / active common-mode filters Common-mode noise filters are a good solution to cancel common-mode noise of the system, but typical common-mode noise filters consist of magnetically coupled three-phase inductor and capacitor components. These filters are bulky and expensive; in addition, filters reduce efficiency, and can cause voltage oscillation if parameters of the passive components are not tuned properly. • Motor shaft ground brushes or insulated bearings The grounding of the motor shaft by connecting a brush between the motor shaft and the motor frame is an effective way to shunt the current path that normally would flow through the motor bearing. However, regular maintenance is required due to limited lifetime of the brush. Insulated bearings such as ceramic bearings can also prevent bearing current problems but required the replacement of the existing bearings in the motor. • Multi-level inverter technologies Reducing the amplitude and voltage transition step of the common-mode voltage can reduce bearing currents. One way of achieving this is to use a multi-level inverter topology. Progress in inverter
  • 10. Subject: Application Note Product: G7 Doc#: AN.G7.02 Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 10/13 technology has made it possible to introduce a 3-level inverter (i.e. the G7 Drive) to the general purpose- inverter market [1]. The advantages of a 3-level inverter are discussed in the next section. FEATURES AND ADVANTAGES OF THE G7 3-LEVEL INVERTER General Features of the 3-Level Inverter Figure 6 shows a typical neutral-point clamped 3-level inverter. In order to determine the common-mode voltage in a three-level inverter, it is important to understand the various switching combinations in a 3-level inverter. In contrast to a 2-level inverter, a 3-level inverter has four switches (IGBTs) per phase, totaling twelve switches (IGBTs) for all three phases. According to the switching signals, each output phase voltage with respect to the DC bus mid-point can have three distinct levels, i.e. E/2, 0, and -E/2. Consequently, this arrangement is called a 3- level inverter. + - U V W E 2 E + - E 2 VU-M M U V W - + N DC link choke DC capacitor R S T G Figure 6. A typical neutral-point clamped 3-level inverter Figure 7 shows various switching states and common-mode voltage waveforms among 27 different switching states of the 3-level inverter. By comparing the common-mode voltage of a 3-level inverter to that of a 2-level inverter as shown in figure 2, it is clear that in a 2-level inverter the difference in voltage level from one state to the other is always ±E/3. In the case of a 3-level inverter, the voltage level is generally ±E/6. This means that the transition level of the common-mode voltage in a 3-level inverter is typically one-half of that in the 2-level inverter. In a 3-level inverter, the amplitude of the common-mode voltage can be lower than a 2-level inverter in the high voltage region. In fact, the maximum and minimum values of the common-mode voltage in a 3-level inverter at higher voltage (i.e. at higher speed) reaches only ±E/3 as shown in Figure 7(b), while the common-mode voltage
  • 11. Subject: Application Note Product: G7 Doc#: AN.G7.02 Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 11/13 reaches ±E/2 in the case of a traditional 2-level inverter as shown in Figure 2. The lower transition level of the 3- level inverter also results in a lower common-mode current compared to the 2-level inverter. This is an important advantage of the 3-level inverter over the traditional 2-level inverter. 3-level Inverter Output Voltage (Between inverter terminal and DC bus mid-point) Common-mode Voltage VU-M VV-M VW-M Vcom E/2 E/2 E/2 E/2 E/2 E/2 0 E/3 E/2 0 0 E/6 0 0 0 0 0 0 -E/2 -E/6 0 -E/2 -E/2 -E/3 -E/2 -E/2 -E/2 -E/2 T/2 T/12 T/4 3T/4 T E/2 E/6 -E/6 -E/2 time Common-mode Voltage -E/3 E/3 T/2 T/8 T E/2 E/6 -E/6 -E/2 time -E/3 E/3 7T/8 3T/8 (a) Low output voltage operation (b) High output voltage operation Common-mode Voltage Figure 7. Various 3-level inverter switching-states and the corresponding common-mode voltage Reduced Bearing Current and Increased Bearing Life with the G7 3-Level Inverter The steep voltage transient in the shaft voltage causes current to flow through the bearing insulation. This leads to the breakdown of the bearing grease insulation and discharge of the shaft voltage. Since the change of the common-mode voltage is smaller in the 3-level inverter, this provides a significant advantage over the 2-level inverter with regards to shaft voltage and bearing currents. Figure 8 shows the comparative test results of the shaft voltage and bearing current for the 2-level and 3-level inverters. In these tests, insulation material was inserted in between the bearing and the housing so that the current through the bearing could be observed. Figure 8 shows that the bearing current of the 3-level inverter in Figure 8(b) is significantly smaller than a 2-level inverter in Figure 8(a). Actual longevity tests were conducted to verify the superiority of the 3-level inverter. The tests simulated extreme conditions including temperature, types of grease, and motor speed. The results of the bearing life test are shown in Figure 9. A key point to note during normal operation is that the normal bearing life would be longer than that
  • 12. Subject: Application Note Product: G7 Doc#: AN.G7.02 Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 12/13 shown here. Figure 9 clearly proves that the use of a G7 Drive with a 3-level inverter topology can result in a significantly longer bearing life. S 10V 20mA 1ms Bearing current Shaft voltage B 1ms Shaft voltage 20mA 10V Bearing current (a) 2-level inverter (b) 3-level inverter Figure 8. Shaft voltage and bearing current of the 2-level and 3-level inverters 0 2 4 6 8 10 12 14 16 18 20 0 1000 2000 3000 4000 5000 6000 Hours of operation (hour) Vibration at load-side bracket (G) 3-level inverter 2-level inverter Figure 9. Bearing life test results (1HP, 2100rpm)
  • 13. Subject: Application Note Product: G7 Doc#: AN.G7.02 Title: Motor Bearing Current Phenomenon and 3-Level Inverter Technology Doc#: AN.G7.02 Copyright Yaskawa Electric America, Inc.© 2005 www.yaskawa.com June 22, 2005 13/13 CONCLUSION In an inverter-driven AC machine, the common-mode voltage and dv/dt may cause premature motor bearing failure. This paper compared the common-mode voltage of the 2-level and 3-level inverter. The common-mode voltage and shaft voltage relationships were also described along with the bearing current mechanisms due to common-mode voltages. Features and benefits of the G7 Drive 3-level inverter topology that reduce the shaft voltage and bearing current generation have been presented. Analytical and experimental results show that the G7 Drive has lower common-mode mode voltage that results in lower bearing currents. Long-term operation tests also prove that the 3-level technology is effective to prevent bearing damage of motors. REFERENCES 1. H.-P.Krug,T. Kume, M. Swamy,” Neutral-point clamped three-level general purpose inverter - features, benefits and applications,” IEEE Power Electronics Specialists Conference, pp.323 - 328, 2004. 2. J. Erdman, R. Kerkman, D. Schlegel, and G. Skibinski, “Effect of PWM inverters in AC Motor Bearing Currents and Shaft Voltages”, IEEE APEC Conference, Dallas, TX, 1995, CD-ROM 3. A. Muetze, A. Binder,” Experimental evaluation of mitigation techniques for bearing currents in inverter-supplied drive-systems - investigations on induction motors up to 500 kW,” IEEE International Electric Machines and Drives Conference, pp.1859 – 1865, vol.3, 2003. USE OF TECHNICAL INFORMATION! Technical content and illustrations are provided as technical advice to augment the information in manual, not supercede it. The information described in this document is subject to change without notice. Yaskawa assumes no responsibility for errors or omissions or damages resulting from the use of the information contained in any technical document. All warnings, cautions and product instruction for product use must be followed. Qualified personnel should carry out installation, operation and maintenance.