This document outlines requirements for marking means of egress in buildings. It states that all required exits must be signposted, except for main exterior doors that are clearly identifiable as exits. Exit signs must be installed at stair doors, horizontal exits, and other required exits from each story. Exception is made for small occupant loads. Tactical signage reading "EXIT" is required on exit stair doors. Placement of exit signs cannot be more than 100 feet from any point in an exit access corridor. Floor proximity exit signs must be no less than 6 inches or more than 8 inches above the floor. A listed floor proximity egress path marking system is required within 8 inches of the floor to delineate the exit path.