This document provides specifications for single core and multicore flexible cables produced by Finolex for overseas markets. It includes tables listing the technical specifications of various cable types, sizes, and standards they conform to. The cables can be used for applications like UPS cabling, submersible pump wiring, and power distribution. Finolex offers a wide range of cable options that meet various international standards.
Industrial & Hazardous Area (ATEX) Plugs
Marechal Distribution Boxes
Marechal Electric - Plugs, Sockets & Decontactors
The Marechal distribution boxes cover a wide range of electrical installations: connecting power outlets and boxes. The Marechal boxes are particularly suited to power supply in tunnels.
Marechal Distribution Box Benefits
Equipment for tunnels
Boxes for distribution, tap-offs, liquefied gas transfer, service and terminals
Marechal Distribution Box Range:
Marechal Express Boxes - Distribution Boxes For Standard Lighting
Marechal Express Fire Boxes - Distribution Boxes For Emergency Lighting
Marechal F400 - Wall Mounting Socket-Outlet For Jet Fans
Marechal BF - Fire Department Boxes
Marechal CD - Distribution Boxes & Socket-Outlets With Protection
Marechal BM - Modular Distribution Boxes
Marechal BG - Box For Liquefied Gas Transfer
Marechal BRP - Portable Service Box
Industrial & Hazardous Area (ATEX) Plugs
Marechal Distribution Boxes
Marechal Electric - Plugs, Sockets & Decontactors
The Marechal distribution boxes cover a wide range of electrical installations: connecting power outlets and boxes. The Marechal boxes are particularly suited to power supply in tunnels.
Marechal Distribution Box Benefits
Equipment for tunnels
Boxes for distribution, tap-offs, liquefied gas transfer, service and terminals
Marechal Distribution Box Range:
Marechal Express Boxes - Distribution Boxes For Standard Lighting
Marechal Express Fire Boxes - Distribution Boxes For Emergency Lighting
Marechal F400 - Wall Mounting Socket-Outlet For Jet Fans
Marechal BF - Fire Department Boxes
Marechal CD - Distribution Boxes & Socket-Outlets With Protection
Marechal BM - Modular Distribution Boxes
Marechal BG - Box For Liquefied Gas Transfer
Marechal BRP - Portable Service Box
Commercial Grade Polyolefin Heat Shrink Tubing
SPN heat shrink is suitable for high volume commercial and industrial applications where flame retarded properties are not required.
SPN Heat Shrink Tubing - Specification
105°C Commercial Grade Non Flame Retarded Heat Shrinkable Tubing
Shrink Ratio: 2:1
Operating Temperature: -55°C to 105°C
Shrink Temperature : 90°C
Heat shrink colours - shiny black and clear
Thorne & Derrick are the largest UK distributor of heat shrink tubings and sleevings including 3M, Panduit, Hellermann Tyton, DSG Canusa, Shrinktek and Thomas & Betts.
Stock lines include thin, medium and thick wall adhesive lined heat shrink sleeves and moulded shapes (heat shrink cable caps, cable breakouts and cable boots) - insulate, seal, protect with heat shrinkable tubing.
RAXTON EExe Adaptors, EExd Right Angle Adaptors,EExd Male to Male and
Female to Female Adaptors,EExe Reducers,EExe Stopping Plugs,EExe Breather - Drain Plugs,EExd Compound Stopper Box/Adaptor,Raxton Part Number System,Accessories
Send enquires to mail@akbartrading.com
Nuhas is the first and only cable producer in the Middle East to have been certified by DNV, Norway as capable of manufacturing power, control and instrumentation cables for shipboard, high speed/light craft and off-shore cables.
High Voltage Cable Terminations (SWA) with CMP Zen Insulated Cable Glands & Cast Integral Earth Lug
CMP Zen Glands - Protect Against Short Circuit Earth Fault Currents
CMP CIEL Cast Integral Earth Lug - Aluminium HV Cable Glands
High voltage single core power cables (3.3kV, 6.6kV, 11kV, 33kV) can generate high fault current ratings via aluminium wire armours (AWA) where the actual fault current may exceed that of the standard CMP earth tag - it is vital for low and high voltage electrical safety to match the rated fault current of the cable gland earth tag to that of the cable armour. CMP unique Cast Integral Earth Lug (CIEL) cable gland designs overcome potential overheating and possible flash over problems - CMP BW CIEL, CMP CW CIEL, CMP E1W CIEL, CMP E1FW CIEL, CMP E2W CIEL and CMP E2FW CIEL cable gland ranges.
CMP CIEL 20S to 40mm - 26.0kA for 1 second short circuit fault rating
CMP CIEL 50s to 90mm - 43.0kA for 1 second short circuit fault rating
CMP Cast Integral Earth Lug (CIEL) Aluminium Cable Glands IP66 for SWA Cable Termination at High Voltage - Specification
CMP CW CIEL type aluminium cable gland for use with all types of low voltage and high voltage Single Wire Armour (SWA) cable providing an environmental seal on the cable outer sheath, mechanical retention and electrical continuity via armour wire termination. All CMP cable glands are EMC Tested. CMP CW CIEL range of industrial aluminium cable glands is designed and tested to BS 6121:Part 1:1989, meets or surpasses the requirements of EN 50262 :1999, and is produced from aluminium. The CW CIEL aluminium cable gland provides a high fault current rated cable termination complete with a CMP unique Cast Integral Earth Lug concept - especially suitable for medium and high voltage electrical cables and systems where a high level of protection against short circuit earth fault currents is required.
Craig and Derricott Isolators
Isolation Equipment and Switch Disconnectors
Moulded Plastic Isolators & Switch Disconnectors IP65 20A-63A
Mild Steel Isolators & Switch Disconnectors IP65 20A-63A
Stainless Steel Isolators & Switch Disconnectors IP65 20A-63A
Die Cast Isolators & Switch Disconnectors IP65 20A-63A
Sheet Steel Isolators & Switch Disconnectors IP41 32A-630A
Sheet Steel Isolators & Switch Disconnectors IP65 32A-1000A
ATEX Zone 22 Isolators& Switch Disconnectors Cat 3D
Fire Rated Isolators & Switch Disconnectors 20A-125A
Isolation Equipment and Switch Disconnectors
Craig & Derricott Section 12 London Underground Isolators
Craig & Derricott Stainless Steel Water Utility Isolators
Lucy Lighting Street Lighting Trojan Isolators
Switch Disconnectors (Isolators) provide the means to safely disconnect or isolate an item of electrical equipment from the power supply - primarily designed to provide a means of local isolation when an elecrical item may need maintenance or repair. Switch Disconnectors also i) provide an effective clearance between the supply and the electrical load appropriate to the voltage applied, ii) provide a means of "locking off" (padlocking), iii) provide true indication of contact state, iv) provide a safe electrical disconnection from the power supply even under fault conditions.
High Voltage Cable Terminations (SWA) with CMP Zen Insulated Cable Glands & Cast Integral Earth Lug
CMP Zen Glands - Protect Against Short Circuit Earth Fault Currents
CMP Zen A324 Insulated Aluminium Cable Glands with Cast Integral Earth Lug (Supply)
CMP A324 Zen insulated aluminium cable glands are suitable for the cable termination of all low voltage and high voltage aluminium wire armoured (AWA) cables, indoor and outdoor with IP66 seal - CMP A324 Zen insulated aluminium cable glands feature CMP Cast Integral Earth Lug (CIEL) allowing the zoning of earth connections for earthed neutral systems.
CMP Zen Insulated Cable Glands - High Voltage Cable Termination with Brass or Aluminium Cable Glands
In the power generation industry unless special measures are taken to both segregate LV-HV cables in accordance with wiring regulations, and also isolate the metallic cable armour from running in continuous contact throughout the whole of the earthing system, interference or electrical noise would spread throughout the plant. CMP Zen Insulated cable gland system allows cables to be earthed at one end only - single point earthing - and insulated at the field end. Insulated Zen cable glands are available to ensure that no contact is made between the earth circuit carried through the cable armour and the low-high voltage electrical enclosure which the cable enters. CMP Zen Insulated cable glands permit electrical design engineers to implement safe earthing systems to deal with :
*Cross Talk Noise Reduction
*Electrical Separation of Main Earths
*Earth Fault Segregation
*Fault Current Reduction with Series Cable Resistance
*Electrical Noise Reduction in Instrument Cables
*Circulating Current Production in Single or 3 Core High Voltage Cables
CMP Zen Insulated Cable Glands - CMP A324 & A348
CMP Zen Insulated cable glands are suitable for use with all aluminium wire armoured (AWA) cables providing an IP66 environmental seal on the cable outer sheath. CMP A324 Zen glands feature Cast Integral Earth Lug (CIEL) suitable for high voltage power cable systems where a high level of protection against fault currents is required - CMP's unique cable glanding concept effectively insulates the gland and cable armour from the electrical equipment eliminating circulating currents. CMP Zen A324 cable gland is usually installed at the supply end of the cable and Zen A348 cable gland at the load end - suitable for 3.3kV, 6.6kV, 11kV and 33kV single core AWA high voltage power cable glanding.
Nuhas is the first and only cable producer in the Middle East to have been certified by DNV, Norway as capable of manufacturing power, control and instrumentation cables for shipboard, high speed/light craft and off-shore cables.
Batra Henlay Cables provides superior quality copper flexible wires, control instrumentation, telecommunication cables moreover high defined coaxial cables in various forms of insulation to the power, telecommunication, and energy industries.
Our range of World-class HV, MV and LV Cables includes Single & Multi Core Armoured and Un-armoured
Cables, Specialty, Control, Instrumentation and also LSF, FRLS, LSOH & Custom Cables to meet the
requirements of a broad spectrum of applications
Nuhas is the first and only cable producer in the Middle East to have been certified by DNV, Norway as capable of manufacturing power, control and instrumentation cables for shipboard, high speed/light craft and off-shore cables.
Commercial Grade Polyolefin Heat Shrink Tubing
SPN heat shrink is suitable for high volume commercial and industrial applications where flame retarded properties are not required.
SPN Heat Shrink Tubing - Specification
105°C Commercial Grade Non Flame Retarded Heat Shrinkable Tubing
Shrink Ratio: 2:1
Operating Temperature: -55°C to 105°C
Shrink Temperature : 90°C
Heat shrink colours - shiny black and clear
Thorne & Derrick are the largest UK distributor of heat shrink tubings and sleevings including 3M, Panduit, Hellermann Tyton, DSG Canusa, Shrinktek and Thomas & Betts.
Stock lines include thin, medium and thick wall adhesive lined heat shrink sleeves and moulded shapes (heat shrink cable caps, cable breakouts and cable boots) - insulate, seal, protect with heat shrinkable tubing.
RAXTON EExe Adaptors, EExd Right Angle Adaptors,EExd Male to Male and
Female to Female Adaptors,EExe Reducers,EExe Stopping Plugs,EExe Breather - Drain Plugs,EExd Compound Stopper Box/Adaptor,Raxton Part Number System,Accessories
Send enquires to mail@akbartrading.com
Nuhas is the first and only cable producer in the Middle East to have been certified by DNV, Norway as capable of manufacturing power, control and instrumentation cables for shipboard, high speed/light craft and off-shore cables.
High Voltage Cable Terminations (SWA) with CMP Zen Insulated Cable Glands & Cast Integral Earth Lug
CMP Zen Glands - Protect Against Short Circuit Earth Fault Currents
CMP CIEL Cast Integral Earth Lug - Aluminium HV Cable Glands
High voltage single core power cables (3.3kV, 6.6kV, 11kV, 33kV) can generate high fault current ratings via aluminium wire armours (AWA) where the actual fault current may exceed that of the standard CMP earth tag - it is vital for low and high voltage electrical safety to match the rated fault current of the cable gland earth tag to that of the cable armour. CMP unique Cast Integral Earth Lug (CIEL) cable gland designs overcome potential overheating and possible flash over problems - CMP BW CIEL, CMP CW CIEL, CMP E1W CIEL, CMP E1FW CIEL, CMP E2W CIEL and CMP E2FW CIEL cable gland ranges.
CMP CIEL 20S to 40mm - 26.0kA for 1 second short circuit fault rating
CMP CIEL 50s to 90mm - 43.0kA for 1 second short circuit fault rating
CMP Cast Integral Earth Lug (CIEL) Aluminium Cable Glands IP66 for SWA Cable Termination at High Voltage - Specification
CMP CW CIEL type aluminium cable gland for use with all types of low voltage and high voltage Single Wire Armour (SWA) cable providing an environmental seal on the cable outer sheath, mechanical retention and electrical continuity via armour wire termination. All CMP cable glands are EMC Tested. CMP CW CIEL range of industrial aluminium cable glands is designed and tested to BS 6121:Part 1:1989, meets or surpasses the requirements of EN 50262 :1999, and is produced from aluminium. The CW CIEL aluminium cable gland provides a high fault current rated cable termination complete with a CMP unique Cast Integral Earth Lug concept - especially suitable for medium and high voltage electrical cables and systems where a high level of protection against short circuit earth fault currents is required.
Craig and Derricott Isolators
Isolation Equipment and Switch Disconnectors
Moulded Plastic Isolators & Switch Disconnectors IP65 20A-63A
Mild Steel Isolators & Switch Disconnectors IP65 20A-63A
Stainless Steel Isolators & Switch Disconnectors IP65 20A-63A
Die Cast Isolators & Switch Disconnectors IP65 20A-63A
Sheet Steel Isolators & Switch Disconnectors IP41 32A-630A
Sheet Steel Isolators & Switch Disconnectors IP65 32A-1000A
ATEX Zone 22 Isolators& Switch Disconnectors Cat 3D
Fire Rated Isolators & Switch Disconnectors 20A-125A
Isolation Equipment and Switch Disconnectors
Craig & Derricott Section 12 London Underground Isolators
Craig & Derricott Stainless Steel Water Utility Isolators
Lucy Lighting Street Lighting Trojan Isolators
Switch Disconnectors (Isolators) provide the means to safely disconnect or isolate an item of electrical equipment from the power supply - primarily designed to provide a means of local isolation when an elecrical item may need maintenance or repair. Switch Disconnectors also i) provide an effective clearance between the supply and the electrical load appropriate to the voltage applied, ii) provide a means of "locking off" (padlocking), iii) provide true indication of contact state, iv) provide a safe electrical disconnection from the power supply even under fault conditions.
High Voltage Cable Terminations (SWA) with CMP Zen Insulated Cable Glands & Cast Integral Earth Lug
CMP Zen Glands - Protect Against Short Circuit Earth Fault Currents
CMP Zen A324 Insulated Aluminium Cable Glands with Cast Integral Earth Lug (Supply)
CMP A324 Zen insulated aluminium cable glands are suitable for the cable termination of all low voltage and high voltage aluminium wire armoured (AWA) cables, indoor and outdoor with IP66 seal - CMP A324 Zen insulated aluminium cable glands feature CMP Cast Integral Earth Lug (CIEL) allowing the zoning of earth connections for earthed neutral systems.
CMP Zen Insulated Cable Glands - High Voltage Cable Termination with Brass or Aluminium Cable Glands
In the power generation industry unless special measures are taken to both segregate LV-HV cables in accordance with wiring regulations, and also isolate the metallic cable armour from running in continuous contact throughout the whole of the earthing system, interference or electrical noise would spread throughout the plant. CMP Zen Insulated cable gland system allows cables to be earthed at one end only - single point earthing - and insulated at the field end. Insulated Zen cable glands are available to ensure that no contact is made between the earth circuit carried through the cable armour and the low-high voltage electrical enclosure which the cable enters. CMP Zen Insulated cable glands permit electrical design engineers to implement safe earthing systems to deal with :
*Cross Talk Noise Reduction
*Electrical Separation of Main Earths
*Earth Fault Segregation
*Fault Current Reduction with Series Cable Resistance
*Electrical Noise Reduction in Instrument Cables
*Circulating Current Production in Single or 3 Core High Voltage Cables
CMP Zen Insulated Cable Glands - CMP A324 & A348
CMP Zen Insulated cable glands are suitable for use with all aluminium wire armoured (AWA) cables providing an IP66 environmental seal on the cable outer sheath. CMP A324 Zen glands feature Cast Integral Earth Lug (CIEL) suitable for high voltage power cable systems where a high level of protection against fault currents is required - CMP's unique cable glanding concept effectively insulates the gland and cable armour from the electrical equipment eliminating circulating currents. CMP Zen A324 cable gland is usually installed at the supply end of the cable and Zen A348 cable gland at the load end - suitable for 3.3kV, 6.6kV, 11kV and 33kV single core AWA high voltage power cable glanding.
Nuhas is the first and only cable producer in the Middle East to have been certified by DNV, Norway as capable of manufacturing power, control and instrumentation cables for shipboard, high speed/light craft and off-shore cables.
Batra Henlay Cables provides superior quality copper flexible wires, control instrumentation, telecommunication cables moreover high defined coaxial cables in various forms of insulation to the power, telecommunication, and energy industries.
Our range of World-class HV, MV and LV Cables includes Single & Multi Core Armoured and Un-armoured
Cables, Specialty, Control, Instrumentation and also LSF, FRLS, LSOH & Custom Cables to meet the
requirements of a broad spectrum of applications
Nuhas is the first and only cable producer in the Middle East to have been certified by DNV, Norway as capable of manufacturing power, control and instrumentation cables for shipboard, high speed/light craft and off-shore cables.
Yamuna Infra & Technology Pvt. Ltd. is an India based leading manufacturer and exporter of high-quality heat shrinkable power cable jointing kits, heat shrinkable power cable termination kits and power cable accessories upto 36kV. Established in 1996, we have been supplying many of the leading power and telecom industries all over the world. We manufacture and market our products under 'US-SEAL' brand/trademark, which itself speak about million acknowledgements for their performance. We are one of the leading companies focused on manufacturing high-quality heat shrinkable moulded components such as cable breakout boots, cable end sealing caps and other electric cable accessories.
For more information visit www.yamunainfra.com
Máy biến áp do tập đoàn LS sản xuất cũng thuộc nhóm sản phẩm cao cấp của thế giới, hiện đang được bán đại trà cho Mỹ, Nhật, Canada, Trung đông, Asia. Các tập đoàn công nghệ hàng đầu như Mitsubishi, Hitachi, Fuji, Siemens,….cũng đang là khách hàng của sản phẩm này trên phạm vi toàn cầu. Hiện LS cũng là một trong những nhà cung cấp Biến thế khô chính của Việt nam với các công trình tiêu biểu như :Royal City, Time City, Nam Á Bank, Air Cargo, Việt Thuận Thành Tower, Lim Tower, Thảo Điền Pearl, Petrovietnam Power Landmark, Petroland Quận 2, Diamond Island, The Era, Royal City, Cresent Mall, Petroland Tower tại Phú Mỹ Hưng, Dragon Hill Residence, Belleza, Khách sạn Continential, Khách sạn Rex, Khách sạn 5 sao Le Meriden, Phú Quốc Airport, Saigon Airport Plaza, Times City, Star City...
RAYCHEM SAUDI ARABIA LTD. (TYCO ELECTRONICS) |AKBAR TRADING EST. SAUDI ARABIA...AKBAR TRADING
te connectivity saudi arabia
TYCO TERMINATION KIT IN ALL VOLTAGE
Raychem terminations for polymeric and MIND
paper insulated cables from 7.2 kV up to 36 kV
System Designer
케이블 종단-거-瑞侃工具包电缆终端-阿克巴交易
ชุด การเลิกจ้าง
RAYCHEM SAUDI ARABIA LTD. (TYCO ELECTRONICS)
11kV-33kV Medium Voltage Heat Shrink Cable Joints & Cable Terminations
11kV and 33kV heat shrink cable joints and cable terminations for medium voltage power cables - SPS heat shrink cable joints and cable terminations are suitable for installation at indoors and outdoors in the Middle East countries, this includes salt laden and dusty atmospheres associated with the Middle East oil, gas and petrochemical industries. Cable terminations and cable joints are suitable for XLPE and paper insulated single core and three 3 core cables of 11kV and 33kV voltages, 3 phase, 50HZ type electrical systems with highest system voltages of 12kV and 36kV. Cable joints are suitable for connecting two XLPE insulated cables of same size or dissimilar sizes and for transition between XLPE and paper insulated lead covered (PILC) medium voltage cables.
Forklift Classes Overview by Intella PartsIntella Parts
Discover the different forklift classes and their specific applications. Learn how to choose the right forklift for your needs to ensure safety, efficiency, and compliance in your operations.
For more technical information, visit our website https://intellaparts.com
Final project report on grocery store management system..pdfKamal Acharya
In today’s fast-changing business environment, it’s extremely important to be able to respond to client needs in the most effective and timely manner. If your customers wish to see your business online and have instant access to your products or services.
Online Grocery Store is an e-commerce website, which retails various grocery products. This project allows viewing various products available enables registered users to purchase desired products instantly using Paytm, UPI payment processor (Instant Pay) and also can place order by using Cash on Delivery (Pay Later) option. This project provides an easy access to Administrators and Managers to view orders placed using Pay Later and Instant Pay options.
In order to develop an e-commerce website, a number of Technologies must be studied and understood. These include multi-tiered architecture, server and client-side scripting techniques, implementation technologies, programming language (such as PHP, HTML, CSS, JavaScript) and MySQL relational databases. This is a project with the objective to develop a basic website where a consumer is provided with a shopping cart website and also to know about the technologies used to develop such a website.
This document will discuss each of the underlying technologies to create and implement an e- commerce website.
Student information management system project report ii.pdfKamal Acharya
Our project explains about the student management. This project mainly explains the various actions related to student details. This project shows some ease in adding, editing and deleting the student details. It also provides a less time consuming process for viewing, adding, editing and deleting the marks of the students.
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptxR&R Consult
CFD analysis is incredibly effective at solving mysteries and improving the performance of complex systems!
Here's a great example: At a large natural gas-fired power plant, where they use waste heat to generate steam and energy, they were puzzled that their boiler wasn't producing as much steam as expected.
R&R and Tetra Engineering Group Inc. were asked to solve the issue with reduced steam production.
An inspection had shown that a significant amount of hot flue gas was bypassing the boiler tubes, where the heat was supposed to be transferred.
R&R Consult conducted a CFD analysis, which revealed that 6.3% of the flue gas was bypassing the boiler tubes without transferring heat. The analysis also showed that the flue gas was instead being directed along the sides of the boiler and between the modules that were supposed to capture the heat. This was the cause of the reduced performance.
Based on our results, Tetra Engineering installed covering plates to reduce the bypass flow. This improved the boiler's performance and increased electricity production.
It is always satisfying when we can help solve complex challenges like this. Do your systems also need a check-up or optimization? Give us a call!
Work done in cooperation with James Malloy and David Moelling from Tetra Engineering.
More examples of our work https://www.r-r-consult.dk/en/cases-en/
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)MdTanvirMahtab2
This presentation is about the working procedure of Shahjalal Fertilizer Company Limited (SFCL). A Govt. owned Company of Bangladesh Chemical Industries Corporation under Ministry of Industries.
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Dr.Costas Sachpazis
Terzaghi's soil bearing capacity theory, developed by Karl Terzaghi, is a fundamental principle in geotechnical engineering used to determine the bearing capacity of shallow foundations. This theory provides a method to calculate the ultimate bearing capacity of soil, which is the maximum load per unit area that the soil can support without undergoing shear failure. The Calculation HTML Code included.
COLLEGE BUS MANAGEMENT SYSTEM PROJECT REPORT.pdfKamal Acharya
The College Bus Management system is completely developed by Visual Basic .NET Version. The application is connect with most secured database language MS SQL Server. The application is develop by using best combination of front-end and back-end languages. The application is totally design like flat user interface. This flat user interface is more attractive user interface in 2017. The application is gives more important to the system functionality. The application is to manage the student’s details, driver’s details, bus details, bus route details, bus fees details and more. The application has only one unit for admin. The admin can manage the entire application. The admin can login into the application by using username and password of the admin. The application is develop for big and small colleges. It is more user friendly for non-computer person. Even they can easily learn how to manage the application within hours. The application is more secure by the admin. The system will give an effective output for the VB.Net and SQL Server given as input to the system. The compiled java program given as input to the system, after scanning the program will generate different reports. The application generates the report for users. The admin can view and download the report of the data. The application deliver the excel format reports. Because, excel formatted reports is very easy to understand the income and expense of the college bus. This application is mainly develop for windows operating system users. In 2017, 73% of people enterprises are using windows operating system. So the application will easily install for all the windows operating system users. The application-developed size is very low. The application consumes very low space in disk. Therefore, the user can allocate very minimum local disk space for this application.
1. An IS / ISO 9001 Company
Finolex
SingleandMulticoreFlexibleCables
CABLES FOR OVERSEAS MARKETS
Finolex cables have been used in many countries for over two decades. Cables can be offered to British or equivalent
standards. Specifications for a representative single core range are given below :
TABLE 6 : SINGLE CORE UNSHEATHED CABLES AS PER BS 6004
Nominal Radial
Cross- Thickness Conductor Overall Conductor Overall
Sectional of Resistance Diameter Resistance Diameter
Area of Insulation Cable Conductor (Max.) (Max.) Cable Conductor (Max.) (Max.)
Conductor (Nom.) Code Construction at 20 0
C Code Construction at 20 0
C
mm² mm (No./mm) ohm/km mm (No./mm) ohm/km mm
0.50 0.6 H05V-U 1/0.80 36.0 2.3 H05V-K 16/0.2 39.0 2.6
0.75 0.6 H05V-U 1/0.97 24.5 2.5 H05V-K 24/0.2 26.0 2.8
1.0 0.6 H05V-U 1/1.13 18.1 2.7 H05V-K 32/0.2 19.5 3.0
1.5 0.7 H07V-R 7/0.53 12.1 3.3 H07V-K 30/0.25 13.3 3.4
2.5 0.8 H07V-R 7/0.67 7.41 4.0 H07V-K 50/0.25 7.98 4.1
4 0.8 H07V-R 7/0.85 4.61 4.6 H07V-K 56/0.3 4.95 4.8
6 0.8 H07V-R 7/1.04 3.08 5.2 H07V-K 84/0.3 3.30 5.3
10 1.0 H07V-R 7/1.35 1.83 6.7 H07V-K 80/0.4 1.91 6.8
16 1.0 H07V-R 7/1.70 1.15 7.8 H07V-K 126/0.4 1.21 8.1
25 1.2 H07V-R 7/2.14 0.727 9.7 H07V-K 196/0.4 0.780 10.2
35 1.2 H07V-R 7/2.52 0.524 10.9 H07V-K 276/0.4 0.554 11.7
50 1.4 H07V-R 19/1.78 0.387 12.8 H07V-K 396/0.4 0.386 13.9
70 1.4 H07V-R 19/2.14 0.268 14.6 H07V-K 360/0.5 0.272 16.0
95 1.6 H07V-R 19/2.52 0.193 17.1 H07V-K 475/0.5 0.206 18.2
120 1.6 H07V-R 37/2.03 0.153 18.8 H07V-K 608/0.5 0.161 20.2
150 1.8 H07V-R 37/2.25 0.124 20.9 H07V-K 750/0.5 0.129 22.5
185 2.0 H07V-R 37/2.52 0.0991 23.3 H07V-K 925/0.5 0.106 24.9
240 2.2 H07V-R 61/2.25 0.0754 26.6 H07V-K 1221/0.5 0.0801 28.4
Note : The conductor construction given above is indicative only, and will be such that all requirements of BS 6360 are met.
l Harmonized code designations are described below :
Cable Code Type of Conductor Voltage Grade
H05V-U Solid 300 / 500 V
H05V-K Flexible 300 / 500 V
H07V-R Stranded 450 / 750 V
H07V-K Flexible 450 / 750 V
l Solid Conductors are as per Class 1, Stranded Conductors are as per Class 2 and Flexible Conductors are as per Class 5
according to BS 6360.
l Cables up to and including 10 mm² can be offered with Solid Conductor also (harmonized code H07V-U).
Other types of cables offered to overseas markets include :
l Multicore sheathed cables as per BS 6004 or BS 6500, with stranded (Class 2) or Flexible (Class 5) conductors.
l HR PVC Insulated winding wires for submersible pump motors
l PVC Insulated and sheathed three core flat cables and three core round double sheathed cables for submersible pumps
l HR PVC Insulated single core flexible cables as per BS 6231 Type CK
l PVC Insulated auto and battery cables as per DIN 72551, JIS C 3406, JASO D 611, ISO 6722 and IS 2465.
l PVC Insulated and sheathed power and control cables as per BS 6346 and IEC 60502
l XLPE Insulated and sheathed power cables as per BS 5467 and IEC 60502
Cables with Rigid (Solid / Stranded) Copper Conductor Cables with Flexible Copper Conductor
All information given herein is in good faith. Finolex shall not be liable for any damages arising out of incorrect use or interpretation.
The Company reserves the right to change any of the above specifications without any prior notice.
2. SINGLE CORE FLEXIBLE CABLES FOR UPS CABLING
SPECIAL!
For UPS
Cabling
TABLE 3 : FLEXIBLE MULTICORE CABLES (6 CORES TO 19 CORES) GENERALLY CONFORMING TO
IS 694 : 1990, VOLTAGE GRADE UPTO 1100 VOLTS
CORES AREA sq.mm 0.5 0.75 1.0 1.5 2.5 4.0
6 SHEATH THICKNESS (Nom.) mm 0.9 1.0 1.0 1.0 1.1 1.2
OVERALL DIAMETER (Approx.) mm 8.1 9.4 9.8 10.7 12.9 16.0
7 SHEATH THICKNESS (Nom.) mm 0.9 1.0 1.0 1.0 1.1 1.2
OVERALL DIAMETER (Approx.) mm 8.1 9.4 9.8 10.7 12.9 16.0
8 SHEATH THICKNESS (Nom.) mm 1.0 1.0 1.0 1.1 1.2 1.3
OVERALL DIAMETER (Approx.) mm 9.4 10.4 10.9 12.2 14.6 17.0
10 SHEATH THICKNESS (Nom.) mm 1.0 1.1 1.1 1.1 1.3 1.4
OVERALL DIAMETER (Approx.) mm 10.5 11.9 12.5 13.7 16.7 19.5
12 SHEATH THICKNESS (Nom.) mm 1.0 1.1 1.1 1.1 1.3 1.4
OVERALL DIAMETER (Approx.) mm 10.8 12.3 12.9 14.1 17.3 20.5
14 SHEATH THICKNESS (Nom.) mm 1.1 1.1 1.1 1.2 1.3 1.4
OVERALL DIAMETER (Approx.) mm 11.5 12.8 13.5 15.0 18.1 22.5
16 SHEATH THICKNESS (Nom.) mm 1.1 1.2 1.2 1.2 1.4 1.5
OVERALL DIAMETER (Approx.) mm 12.1 13.7 14.4 15.8 19.3 24.0
19 SHEATH THICKNESS (Nom.) mm 1.1 1.2 1.3 1.3 1.4 1.5
OVERALL DIAMETER (Approx.) mm 12.7 14.4 15.1 16.8 20.3 25.5
TABLE 2 : SINGLE CORE FLEXIBLE CABLES GENERALLY CONFORMING TO IS 694 : 1990
VOLTAGE GRADE UPTO 1100 VOLTS
AREA sq.mm. 70.0 95.0 120.0 150.0 185.0 240.0
NO. & SIZE OF WIRE No./mm 360/.5 475/.5 608/.5 750/.5 925/.5 1221/.5
CONDUCTOR MAX RES. @200
C Ohms/km 0.272 0.206 0.161 0.129 0.106 0.0801
CURRENT DC/AC Amps 214 260 305 355 415 500
INSULATION THICKNESS (Nom.) mm 1.4 1.6 1.6 1.8 2.0 2.2
O.D. (Approx.) mm 13.9 15.9 17.8 19.8 22.0 26.0
TABLE 4 : THREE & FOUR CORE FLEXIBLE CABLES FOR VOLTAGE GRADE UPTO 1100 VOLTS
AREA sq.mm. 6.0 10.0 16.0 25.0 35.0 50.0 70.0 95.0 120.0
NO. & SIZE No./mm 84/.3 140/.3 226/.3 354/.3 495/.3 703/.3 360/.5 475/.5 608/.5
OF WIRE OR OR OR OR OR
80/.4 126/.4 196/.4 276/.4 396/.4
CONDUCTOR MAX. RES @200
C Ohms/Km 3.30 1.91 1.21 0.78 0.554 0.386 0.272 0.206 0.161
CURRENT Amps 31 42 57 72 91 120 165 200 225
INSULATION THICKNESS mm 0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6
SHEATH THICKNESS mm 1.3 1.4 1.4 1.5 1.6 2.0 2.2 2.4 2.5
3-CORE (Nom.)
O.D. (Approx.) mm 13.3 16.9 19.1 23.0 26.3 31.7 38.5 45.0 49.0
SHEATH THICKNESS mm 1.4 1.4 1.4 1.6 1.7 2.0 2.2 2.4 2.5
(Nom.)
4-CORE O.D. (Approx.) mm 14.7 18.6 21.0 25.5 29.2 33.4 40.0 46.5 51.0
TABLE 5 : COLOUR CODING
COLOURS
Type Core Sheath
Single Core Unsheathed Red; Yellow; Blue; Black; White & Grey
Single Core Sheathed Black Black
Twin Twisted Red & Black
Twin Flat Sheathed Red & Black Black
2 Core Round Sheathed Red & Black Black
3 Core Round Sheathed Red; Black & Yellow/Green for earth Black
4 Core Round Sheathed Red; Yellow; Blue & Yellow/Green for earth Black
5 Core Round Sheathed Red; Yellow; Blue; Black & Grey Black
Note : Any required colour can be provided on specific request.
TABLE 1 : SINGLE CORE / MULTICORE FLEXIBLE CABLES AS PER IS 694 : 1990
VOLTAGE GRADE UPTO 1100 VOLTS
AREA Sq.mm. 0.5 0.75 1.0 1.5 2.5 4.0 6.0 10.0 16.0 25.0 35.0 50.0
NO. & SIZE 16/.2 24/.2 32/.2 30/.25 50/.25 56/.3 84/0.3 80/.4 126/.4 196/.4 276/.4 396/.4
OF WIRE (Nom.) No./mm OR OR OR
48/.2 80/.2 140/.3
CONDUCTOR RESISTANCE (MAX.) @ 200
C Ohms/km 39.0 26.0 19.5 13.3 7.98 4.95 3.30 1.91 1.21 0.780 0.554 0.386
CURRENT RATING
DC or AC Amps
4 7 12 15 20 27 35 46 62 80 102 138
INSULATION THICKNESS (Nom.) mm 0.6 0.6 0.6 0.6 0.7 0.8 0.8 1.0 1.0 1.2 1.2 1.4
SINGLE CORE OVERALL DIAMETER mm
2.00 2.30 2.45 2.75 3.50 4.10 4.75 6.30 7.25 8.80 10.35 12.25
UNSHEATHED (Approx.)
SINGLE CORE SHEATH THICKNESS (Nom.) mm 0.9 0.9 0.9 0.9 1.0 1.0
SHEATHED OVERALL DIAMETER (Approx.) mm 4.00 4.25 4.50 4.80 5.45 6.30
TWIN FLAT OVERALL WIDTH (Approx.) mm 6.2 6.7 – – – –
SHEATHED OVERALL HEIGHT (Approx.) mm 4.0 4.25 – – – –
SHEATH THICKNESS (Nom.) mm 0.9 0.9 0.9 0.9 1.0 1.0
2 CORE
OVERALL DIAMETER (Approx.) mm 6.1 6.7 7.0 7.6 9.1 10.5
SHEATH THICKNESS (Nom.) mm 0.9 0.9 0.9 0.9 1.0 1.0
3 CORE
OVERALL DIAMETER (Approx.) mm 6.4 7.1 7.4 8.0 9.6 11.4
SHEATH THICKNESS (Nom.) mm 0.9 0.9 0.9 1.0 1.0 1.0
4 CORE
OVERALL DIAMETER (Approx.) mm 6.9 7.7 8.1 9.2 10.7 12.4
SHEATH THICKNESS (Nom.) mm 0.9 0.9 1.0 1.0 1.0 1.1
5 CORE
OVERALL DIAMETER (Approx.) mm 7.5 8.3 9.1 9.9 11.7 13.8
Note : The conductor construction given above is indicative only and will be such that all requirements of strand
diameter and conductor resistance as per IS 694 and IS 8130 are met.
IS : 694
Finolex PVC insulated single core flexible cables in grey and white colour are ideal for use in
cabling for UPS in establishments that have large computer networks. These unique colours
can help identify the cabling for UPS wiring in the circuit and are available in sizes 0.5 sq. mm
to 6.0 sq.mm. These cables conforming to IS 694 : 1990, carry the prestigious ISI mark and are
duly approved by FIA/TAC. These cables can also be made available with FR or FRLS
insulating compound on request. Technical details as per Table 1.
PVC compound insulated single core and multi core flexible cables have a wide range of application in machine tools,
appliances, control panels, machinery and industries of every nature.
The conductors, drawn from 99.97% bright electrolytic grade copper with more than 100% conductivity, are annealed
and bunched together. The conductors are insulated with a PVC compound with high insulation resistance and dielectric
strength, formulated and manufactured in-house.
In case of multicore cables, the insulated cores are laid up to form the core assembly. The inner cores are coded for
ease of identification as per National/International coding practices. The sheathing is provided with a specially formulated
PVC compound to facilitate not only ease in stripping but also to withstand mechanical abrasion while in use. These
PVC compounds used for insulation and sheathing have a high oxygen and temperature index. These properties help in
restricting the spread of fire even at very high temperatures.
The single core and multicore sheathed cables are manufactured as per IS 694 : 1990, in sizes from 0.5 sq. mm. to 50
sq. mm. in single core, and in sizes 0.5 sq.mm. to 4.0 sq. mm. upto 5 cores. These sizes carry the prestigious ISI mark
and are duly approved by FIA/TAC. The rest of the sizes generally conform to IS 694 : 1990.
Cables as per BS 6004 and BS 6500 are also available for the export market. Special purpose cables in screened
construction can also be made available.
3. SINGLE CORE FLEXIBLE CABLES FOR UPS CABLING
SPECIAL!
For UPS
Cabling
TABLE 3 : FLEXIBLE MULTICORE CABLES (6 CORES TO 19 CORES) GENERALLY CONFORMING TO
IS 694 : 1990, VOLTAGE GRADE UPTO 1100 VOLTS
CORES AREA sq.mm 0.5 0.75 1.0 1.5 2.5 4.0
6 SHEATH THICKNESS (Nom.) mm 0.9 1.0 1.0 1.0 1.1 1.2
OVERALL DIAMETER (Approx.) mm 8.1 9.4 9.8 10.7 12.9 16.0
7 SHEATH THICKNESS (Nom.) mm 0.9 1.0 1.0 1.0 1.1 1.2
OVERALL DIAMETER (Approx.) mm 8.1 9.4 9.8 10.7 12.9 16.0
8 SHEATH THICKNESS (Nom.) mm 1.0 1.0 1.0 1.1 1.2 1.3
OVERALL DIAMETER (Approx.) mm 9.4 10.4 10.9 12.2 14.6 17.0
10 SHEATH THICKNESS (Nom.) mm 1.0 1.1 1.1 1.1 1.3 1.4
OVERALL DIAMETER (Approx.) mm 10.5 11.9 12.5 13.7 16.7 19.5
12 SHEATH THICKNESS (Nom.) mm 1.0 1.1 1.1 1.1 1.3 1.4
OVERALL DIAMETER (Approx.) mm 10.8 12.3 12.9 14.1 17.3 20.5
14 SHEATH THICKNESS (Nom.) mm 1.1 1.1 1.1 1.2 1.3 1.4
OVERALL DIAMETER (Approx.) mm 11.5 12.8 13.5 15.0 18.1 22.5
16 SHEATH THICKNESS (Nom.) mm 1.1 1.2 1.2 1.2 1.4 1.5
OVERALL DIAMETER (Approx.) mm 12.1 13.7 14.4 15.8 19.3 24.0
19 SHEATH THICKNESS (Nom.) mm 1.1 1.2 1.3 1.3 1.4 1.5
OVERALL DIAMETER (Approx.) mm 12.7 14.4 15.1 16.8 20.3 25.5
TABLE 2 : SINGLE CORE FLEXIBLE CABLES GENERALLY CONFORMING TO IS 694 : 1990
VOLTAGE GRADE UPTO 1100 VOLTS
AREA sq.mm. 70.0 95.0 120.0 150.0 185.0 240.0
NO. & SIZE OF WIRE No./mm 360/.5 475/.5 608/.5 750/.5 925/.5 1221/.5
CONDUCTOR MAX RES. @200
C Ohms/km 0.272 0.206 0.161 0.129 0.106 0.0801
CURRENT DC/AC Amps 214 260 305 355 415 500
INSULATION THICKNESS (Nom.) mm 1.4 1.6 1.6 1.8 2.0 2.2
O.D. (Approx.) mm 13.9 15.9 17.8 19.8 22.0 26.0
TABLE 4 : THREE & FOUR CORE FLEXIBLE CABLES FOR VOLTAGE GRADE UPTO 1100 VOLTS
AREA sq.mm. 6.0 10.0 16.0 25.0 35.0 50.0 70.0 95.0 120.0
NO. & SIZE No./mm 84/.3 140/.3 226/.3 354/.3 495/.3 703/.3 360/.5 475/.5 608/.5
OF WIRE OR OR OR OR OR
80/.4 126/.4 196/.4 276/.4 396/.4
CONDUCTOR MAX. RES @200
C Ohms/Km 3.30 1.91 1.21 0.78 0.554 0.386 0.272 0.206 0.161
CURRENT Amps 31 42 57 72 91 120 165 200 225
INSULATION THICKNESS mm 0.8 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6
SHEATH THICKNESS mm 1.3 1.4 1.4 1.5 1.6 2.0 2.2 2.4 2.5
3-CORE (Nom.)
O.D. (Approx.) mm 13.3 16.9 19.1 23.0 26.3 31.7 38.5 45.0 49.0
SHEATH THICKNESS mm 1.4 1.4 1.4 1.6 1.7 2.0 2.2 2.4 2.5
(Nom.)
4-CORE O.D. (Approx.) mm 14.7 18.6 21.0 25.5 29.2 33.4 40.0 46.5 51.0
TABLE 5 : COLOUR CODING
COLOURS
Type Core Sheath
Single Core Unsheathed Red; Yellow; Blue; Black; White & Grey
Single Core Sheathed Black Black
Twin Twisted Red & Black
Twin Flat Sheathed Red & Black Black
2 Core Round Sheathed Red & Black Black
3 Core Round Sheathed Red; Black & Yellow/Green for earth Black
4 Core Round Sheathed Red; Yellow; Blue & Yellow/Green for earth Black
5 Core Round Sheathed Red; Yellow; Blue; Black & Grey Black
Note : Any required colour can be provided on specific request.
TABLE 1 : SINGLE CORE / MULTICORE FLEXIBLE CABLES AS PER IS 694 : 1990
VOLTAGE GRADE UPTO 1100 VOLTS
AREA Sq.mm. 0.5 0.75 1.0 1.5 2.5 4.0 6.0 10.0 16.0 25.0 35.0 50.0
NO. & SIZE 16/.2 24/.2 32/.2 30/.25 50/.25 56/.3 84/0.3 80/.4 126/.4 196/.4 276/.4 396/.4
OF WIRE (Nom.) No./mm OR OR OR
48/.2 80/.2 140/.3
CONDUCTOR RESISTANCE (MAX.) @ 200
C Ohms/km 39.0 26.0 19.5 13.3 7.98 4.95 3.30 1.91 1.21 0.780 0.554 0.386
CURRENT RATING
DC or AC Amps
4 7 12 15 20 27 35 46 62 80 102 138
INSULATION THICKNESS (Nom.) mm 0.6 0.6 0.6 0.6 0.7 0.8 0.8 1.0 1.0 1.2 1.2 1.4
SINGLE CORE OVERALL DIAMETER mm
2.00 2.30 2.45 2.75 3.50 4.10 4.75 6.30 7.25 8.80 10.35 12.25
UNSHEATHED (Approx.)
SINGLE CORE SHEATH THICKNESS (Nom.) mm 0.9 0.9 0.9 0.9 1.0 1.0
SHEATHED OVERALL DIAMETER (Approx.) mm 4.00 4.25 4.50 4.80 5.45 6.30
TWIN FLAT OVERALL WIDTH (Approx.) mm 6.2 6.7 – – – –
SHEATHED OVERALL HEIGHT (Approx.) mm 4.0 4.25 – – – –
SHEATH THICKNESS (Nom.) mm 0.9 0.9 0.9 0.9 1.0 1.0
2 CORE
OVERALL DIAMETER (Approx.) mm 6.1 6.7 7.0 7.6 9.1 10.5
SHEATH THICKNESS (Nom.) mm 0.9 0.9 0.9 0.9 1.0 1.0
3 CORE
OVERALL DIAMETER (Approx.) mm 6.4 7.1 7.4 8.0 9.6 11.4
SHEATH THICKNESS (Nom.) mm 0.9 0.9 0.9 1.0 1.0 1.0
4 CORE
OVERALL DIAMETER (Approx.) mm 6.9 7.7 8.1 9.2 10.7 12.4
SHEATH THICKNESS (Nom.) mm 0.9 0.9 1.0 1.0 1.0 1.1
5 CORE
OVERALL DIAMETER (Approx.) mm 7.5 8.3 9.1 9.9 11.7 13.8
Note : The conductor construction given above is indicative only and will be such that all requirements of strand
diameter and conductor resistance as per IS 694 and IS 8130 are met.
IS : 694
Finolex PVC insulated single core flexible cables in grey and white colour are ideal for use in
cabling for UPS in establishments that have large computer networks. These unique colours
can help identify the cabling for UPS wiring in the circuit and are available in sizes 0.5 sq. mm
to 6.0 sq.mm. These cables conforming to IS 694 : 1990, carry the prestigious ISI mark and are
duly approved by FIA/TAC. These cables can also be made available with FR or FRLS
insulating compound on request. Technical details as per Table 1.
PVC compound insulated single core and multi core flexible cables have a wide range of application in machine tools,
appliances, control panels, machinery and industries of every nature.
The conductors, drawn from 99.97% bright electrolytic grade copper with more than 100% conductivity, are annealed
and bunched together. The conductors are insulated with a PVC compound with high insulation resistance and dielectric
strength, formulated and manufactured in-house.
In case of multicore cables, the insulated cores are laid up to form the core assembly. The inner cores are coded for
ease of identification as per National/International coding practices. The sheathing is provided with a specially formulated
PVC compound to facilitate not only ease in stripping but also to withstand mechanical abrasion while in use. These
PVC compounds used for insulation and sheathing have a high oxygen and temperature index. These properties help in
restricting the spread of fire even at very high temperatures.
The single core and multicore sheathed cables are manufactured as per IS 694 : 1990, in sizes from 0.5 sq. mm. to 50
sq. mm. in single core, and in sizes 0.5 sq.mm. to 4.0 sq. mm. upto 5 cores. These sizes carry the prestigious ISI mark
and are duly approved by FIA/TAC. The rest of the sizes generally conform to IS 694 : 1990.
Cables as per BS 6004 and BS 6500 are also available for the export market. Special purpose cables in screened
construction can also be made available.
4. An IS / ISO 9001 Company
Finolex
SingleandMulticoreFlexibleCables
CABLES FOR OVERSEAS MARKETS
Finolex cables have been used in many countries for over two decades. Cables can be offered to British or equivalent
standards. Specifications for a representative single core range are given below :
TABLE 6 : SINGLE CORE UNSHEATHED CABLES AS PER BS 6004
Nominal Radial
Cross- Thickness Conductor Overall Conductor Overall
Sectional of Resistance Diameter Resistance Diameter
Area of Insulation Cable Conductor (Max.) (Max.) Cable Conductor (Max.) (Max.)
Conductor (Nom.) Code Construction at 20 0
C Code Construction at 20 0
C
mm² mm (No./mm) ohm/km mm (No./mm) ohm/km mm
0.50 0.6 H05V-U 1/0.80 36.0 2.3 H05V-K 16/0.2 39.0 2.6
0.75 0.6 H05V-U 1/0.97 24.5 2.5 H05V-K 24/0.2 26.0 2.8
1.0 0.6 H05V-U 1/1.13 18.1 2.7 H05V-K 32/0.2 19.5 3.0
1.5 0.7 H07V-R 7/0.53 12.1 3.3 H07V-K 30/0.25 13.3 3.4
2.5 0.8 H07V-R 7/0.67 7.41 4.0 H07V-K 50/0.25 7.98 4.1
4 0.8 H07V-R 7/0.85 4.61 4.6 H07V-K 56/0.3 4.95 4.8
6 0.8 H07V-R 7/1.04 3.08 5.2 H07V-K 84/0.3 3.30 5.3
10 1.0 H07V-R 7/1.35 1.83 6.7 H07V-K 80/0.4 1.91 6.8
16 1.0 H07V-R 7/1.70 1.15 7.8 H07V-K 126/0.4 1.21 8.1
25 1.2 H07V-R 7/2.14 0.727 9.7 H07V-K 196/0.4 0.780 10.2
35 1.2 H07V-R 7/2.52 0.524 10.9 H07V-K 276/0.4 0.554 11.7
50 1.4 H07V-R 19/1.78 0.387 12.8 H07V-K 396/0.4 0.386 13.9
70 1.4 H07V-R 19/2.14 0.268 14.6 H07V-K 360/0.5 0.272 16.0
95 1.6 H07V-R 19/2.52 0.193 17.1 H07V-K 475/0.5 0.206 18.2
120 1.6 H07V-R 37/2.03 0.153 18.8 H07V-K 608/0.5 0.161 20.2
150 1.8 H07V-R 37/2.25 0.124 20.9 H07V-K 750/0.5 0.129 22.5
185 2.0 H07V-R 37/2.52 0.0991 23.3 H07V-K 925/0.5 0.106 24.9
240 2.2 H07V-R 61/2.25 0.0754 26.6 H07V-K 1221/0.5 0.0801 28.4
Note : The conductor construction given above is indicative only, and will be such that all requirements of BS 6360 are met.
l Harmonized code designations are described below :
Cable Code Type of Conductor Voltage Grade
H05V-U Solid 300 / 500 V
H05V-K Flexible 300 / 500 V
H07V-R Stranded 450 / 750 V
H07V-K Flexible 450 / 750 V
l Solid Conductors are as per Class 1, Stranded Conductors are as per Class 2 and Flexible Conductors are as per Class 5
according to BS 6360.
l Cables up to and including 10 mm² can be offered with Solid Conductor also (harmonized code H07V-U).
Other types of cables offered to overseas markets include :
l Multicore sheathed cables as per BS 6004 or BS 6500, with stranded (Class 2) or Flexible (Class 5) conductors.
l HR PVC Insulated winding wires for submersible pump motors
l PVC Insulated and sheathed three core flat cables and three core round double sheathed cables for submersible pumps
l HR PVC Insulated single core flexible cables as per BS 6231 Type CK
l PVC Insulated auto and battery cables as per DIN 72551, JIS C 3406, JASO D 611, ISO 6722 and IS 2465.
l PVC Insulated and sheathed power and control cables as per BS 6346 and IEC 60502
l XLPE Insulated and sheathed power cables as per BS 5467 and IEC 60502
Cables with Rigid (Solid / Stranded) Copper Conductor Cables with Flexible Copper Conductor
All information given herein is in good faith. Finolex shall not be liable for any damages arising out of incorrect use or interpretation.
The Company reserves the right to change any of the above specifications without any prior notice.