Our range of World-class HV, MV and LV Cables includes Single & Multi Core Armoured and Un-armoured
Cables, Specialty, Control, Instrumentation and also LSF, FRLS, LSOH & Custom Cables to meet the
requirements of a broad spectrum of applications
Nuhas is the first and only cable producer in the Middle East to have been certified by DNV, Norway as capable of manufacturing power, control and instrumentation cables for shipboard, high speed/light craft and off-shore cables.
Nuhas is the first and only cable producer in the Middle East to have been certified by DNV, Norway as capable of manufacturing power, control and instrumentation cables for shipboard, high speed/light craft and off-shore cables.
Nuhas is the first and only cable producer in the Middle East to have been certified by DNV, Norway as capable of manufacturing power, control and instrumentation cables for shipboard, high speed/light craft and off-shore cables.
Nuhas is the first and only cable producer in the Middle East to have been certified by DNV, Norway as capable of manufacturing power, control and instrumentation cables for shipboard, high speed/light craft and off-shore cables.
CMP PX2K Cable Glands (Barrier Glands Exd Flameproof with ATEX Certification for Hazardous Areas)
Cable Gland Size 20S/16 (M20) 1/2" NPT Entry Thread Standard, 3/4" NPT Optional
Cable Gland Suits Cable Diameters 6.1mm-11.5mm
CMP PX2K barrier cable glands are ATEX certified and suitable for use with all forms of equipment protection permitted in Zone 1, Zone 2, Zone 21 and Zone 22. Flameproof compound filled barrier glands for cable terminations within ATEX areas are supplied with a "universal" reversible armour ring to suit all types of armoured cables - this includes steel wire armoured (SWA), steel tape armoured (STA) and wire braided cables for installation within hazardous areas. Barrier cable glands provide a compound barrier seal around the cable conductors and an environmental seal on the cable outer sheath. The CMP PX2K cable gland provides a mechanical cable retention and electrical continuity via the cable armour termination. A combined detachable armour cone and compound tube, together with AnyWay universal cable clamping ring arrangement allows the cable to be easily disconnected from the electrical equipment and easily re-connected. This cable gland feature facilitates remote make off procedures when the cable termination is to be conducted in confined spaces or in areas of restricted access.
Cable Glands are suitable for following cable types - Wire Braid Armour, Single Steel Wire Armour (SWA), Screened Flexible Wire Braid (eg CY or SY), Steel Tape Armour (STA), Pliable Wire Armour (PWA)
Cable Sealing Area - Inner Compound Barrier and Cable Outer Sheath
CMP PX2K cable glands with offshore and marine approvals including Lloyds, DNV and ABS are available - LSF cable gland shrouds available for low smoke and fume cable terminations.
Craig and Derricott Isolators
Isolation Equipment and Switch Disconnectors
Moulded Plastic Isolators & Switch Disconnectors IP65 20A-63A
Mild Steel Isolators & Switch Disconnectors IP65 20A-63A
Stainless Steel Isolators & Switch Disconnectors IP65 20A-63A
Die Cast Isolators & Switch Disconnectors IP65 20A-63A
Sheet Steel Isolators & Switch Disconnectors IP41 32A-630A
Sheet Steel Isolators & Switch Disconnectors IP65 32A-1000A
ATEX Zone 22 Isolators& Switch Disconnectors Cat 3D
Fire Rated Isolators & Switch Disconnectors 20A-125A
Isolation Equipment and Switch Disconnectors
Craig & Derricott Section 12 London Underground Isolators
Craig & Derricott Stainless Steel Water Utility Isolators
Lucy Lighting Street Lighting Trojan Isolators
Switch Disconnectors (Isolators) provide the means to safely disconnect or isolate an item of electrical equipment from the power supply - primarily designed to provide a means of local isolation when an elecrical item may need maintenance or repair. Switch Disconnectors also i) provide an effective clearance between the supply and the electrical load appropriate to the voltage applied, ii) provide a means of "locking off" (padlocking), iii) provide true indication of contact state, iv) provide a safe electrical disconnection from the power supply even under fault conditions.
LV-HV Cable Jointers Tools for 1000V, 11kV, 33kV Cable Preparation.
Low voltage cable jointing tools for cable stripping and cable preparation of DNO utility and industrial power cables including waveform, consac, XLPE and PILC. High voltage cable jointing tools enable the cable preparation, stripping, cutting and removal of insulation (XLPE, EPR), semi-conductive screens (bonded and peelable) and outer cable sheaths (PVC, PE, EPR) from single and multi-core 11-33kV cables, including Triplex cable. T&D also stock and distribute Cembre Cable Crimping & Cable Cutting Tools and SEB Cable Pulling and Laying Equipment including cable rollers, cable socks, drum jacks and conduit rods.
Straight and right angled bushing boots from stock suit switchgear and transformer bushings - bushing boots provide high voltage electrical insulation, preventing flashover caused by moisture ingress, industrial contamination, high humidity and rodents.
High Voltage 33kV Bushing Boots (RABK/STBK)
The high voltage bushing diameters on a 33kV switchgear or transformer system are normally in excess of 100mm in diameter so a standard boot is unsuitable. 33kV insulating boots are ex stock.
400 Series Interface C Compact Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface C bushings on switchgear and transformers.
Nexans Euromold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F.
Nexans Euromold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables.
EXD Hazardous Area Barrier Glands from Flexicon are manufactured from nickel plated brass with a nylon seal, to an IP rating of IP66, IP67, IP68 (5bar) and IP69K - ATEX certified barrier glands are suitable for use with Flexicon flexible conduit (liquid tight types) in Zone 1, Zone 2, Zone 21 and Zone 22.
EXD flameproof barrier glands are suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22 hazardous areas, when used with the Flexicon range of liquid-tight flexible conduits.
Hazardous Area Barrier Gland (ATEX) Certified
• High mechanical strength
• Suitable for threaded entries
• Operating temperature of -60oC to +85oC
• Two-part epoxy solid-setting putty, gloves and mixing instructions
ATEX barrier glands for indoor or outdoor use in Zone 1, Zone 2, Zone 21 and Zone 22 Hazardous Areas with all types of cables housed in Liquid Tight flexible conduit systems. ATEX barrier glands are suitable for knockouts or threaded entries. Nickel plated brass compression fitting comprising of body, nut, earthing ferrule, nylon compression seal and compound barrier. The compound barrier seals around the cable conductors for hazardous area cable glanding on conduit systems. The earthing ferrule is manufactured in machined nickel plated brass to facilitate easy assembly and re-use. Also ensures high mechanical strength and electrical continuity.
Flexicon flexible conduits with ATEX flameproof barrier glands (LTP-EXD flameproof barrier glands) are suitable for use with Flexicon LTP, LTPHC, LTPUL, LTPSS and LTPPU conduits.
High Voltage Cable Terminations (SWA) with CMP Zen Insulated Cable Glands & Cast Integral Earth Lug
CMP Zen Glands - Protect Against Short Circuit Earth Fault Currents
CMP CIEL Cast Integral Earth Lug - Aluminium HV Cable Glands
High voltage single core power cables (3.3kV, 6.6kV, 11kV, 33kV) can generate high fault current ratings via aluminium wire armours (AWA) where the actual fault current may exceed that of the standard CMP earth tag - it is vital for low and high voltage electrical safety to match the rated fault current of the cable gland earth tag to that of the cable armour. CMP unique Cast Integral Earth Lug (CIEL) cable gland designs overcome potential overheating and possible flash over problems - CMP BW CIEL, CMP CW CIEL, CMP E1W CIEL, CMP E1FW CIEL, CMP E2W CIEL and CMP E2FW CIEL cable gland ranges.
CMP CIEL 20S to 40mm - 26.0kA for 1 second short circuit fault rating
CMP CIEL 50s to 90mm - 43.0kA for 1 second short circuit fault rating
CMP Cast Integral Earth Lug (CIEL) Aluminium Cable Glands IP66 for SWA Cable Termination at High Voltage - Specification
CMP CW CIEL type aluminium cable gland for use with all types of low voltage and high voltage Single Wire Armour (SWA) cable providing an environmental seal on the cable outer sheath, mechanical retention and electrical continuity via armour wire termination. All CMP cable glands are EMC Tested. CMP CW CIEL range of industrial aluminium cable glands is designed and tested to BS 6121:Part 1:1989, meets or surpasses the requirements of EN 50262 :1999, and is produced from aluminium. The CW CIEL aluminium cable gland provides a high fault current rated cable termination complete with a CMP unique Cast Integral Earth Lug concept - especially suitable for medium and high voltage electrical cables and systems where a high level of protection against short circuit earth fault currents is required.
Nuhas is the first and only cable producer in the Middle East to have been certified by DNV, Norway as capable of manufacturing power, control and instrumentation cables for shipboard, high speed/light craft and off-shore cables.
CMP PX2K Cable Glands (Barrier Glands Exd Flameproof with ATEX Certification for Hazardous Areas)
Cable Gland Size 20S/16 (M20) 1/2" NPT Entry Thread Standard, 3/4" NPT Optional
Cable Gland Suits Cable Diameters 6.1mm-11.5mm
CMP PX2K barrier cable glands are ATEX certified and suitable for use with all forms of equipment protection permitted in Zone 1, Zone 2, Zone 21 and Zone 22. Flameproof compound filled barrier glands for cable terminations within ATEX areas are supplied with a "universal" reversible armour ring to suit all types of armoured cables - this includes steel wire armoured (SWA), steel tape armoured (STA) and wire braided cables for installation within hazardous areas. Barrier cable glands provide a compound barrier seal around the cable conductors and an environmental seal on the cable outer sheath. The CMP PX2K cable gland provides a mechanical cable retention and electrical continuity via the cable armour termination. A combined detachable armour cone and compound tube, together with AnyWay universal cable clamping ring arrangement allows the cable to be easily disconnected from the electrical equipment and easily re-connected. This cable gland feature facilitates remote make off procedures when the cable termination is to be conducted in confined spaces or in areas of restricted access.
Cable Glands are suitable for following cable types - Wire Braid Armour, Single Steel Wire Armour (SWA), Screened Flexible Wire Braid (eg CY or SY), Steel Tape Armour (STA), Pliable Wire Armour (PWA)
Cable Sealing Area - Inner Compound Barrier and Cable Outer Sheath
CMP PX2K cable glands with offshore and marine approvals including Lloyds, DNV and ABS are available - LSF cable gland shrouds available for low smoke and fume cable terminations.
Craig and Derricott Isolators
Isolation Equipment and Switch Disconnectors
Moulded Plastic Isolators & Switch Disconnectors IP65 20A-63A
Mild Steel Isolators & Switch Disconnectors IP65 20A-63A
Stainless Steel Isolators & Switch Disconnectors IP65 20A-63A
Die Cast Isolators & Switch Disconnectors IP65 20A-63A
Sheet Steel Isolators & Switch Disconnectors IP41 32A-630A
Sheet Steel Isolators & Switch Disconnectors IP65 32A-1000A
ATEX Zone 22 Isolators& Switch Disconnectors Cat 3D
Fire Rated Isolators & Switch Disconnectors 20A-125A
Isolation Equipment and Switch Disconnectors
Craig & Derricott Section 12 London Underground Isolators
Craig & Derricott Stainless Steel Water Utility Isolators
Lucy Lighting Street Lighting Trojan Isolators
Switch Disconnectors (Isolators) provide the means to safely disconnect or isolate an item of electrical equipment from the power supply - primarily designed to provide a means of local isolation when an elecrical item may need maintenance or repair. Switch Disconnectors also i) provide an effective clearance between the supply and the electrical load appropriate to the voltage applied, ii) provide a means of "locking off" (padlocking), iii) provide true indication of contact state, iv) provide a safe electrical disconnection from the power supply even under fault conditions.
LV-HV Cable Jointers Tools for 1000V, 11kV, 33kV Cable Preparation.
Low voltage cable jointing tools for cable stripping and cable preparation of DNO utility and industrial power cables including waveform, consac, XLPE and PILC. High voltage cable jointing tools enable the cable preparation, stripping, cutting and removal of insulation (XLPE, EPR), semi-conductive screens (bonded and peelable) and outer cable sheaths (PVC, PE, EPR) from single and multi-core 11-33kV cables, including Triplex cable. T&D also stock and distribute Cembre Cable Crimping & Cable Cutting Tools and SEB Cable Pulling and Laying Equipment including cable rollers, cable socks, drum jacks and conduit rods.
Straight and right angled bushing boots from stock suit switchgear and transformer bushings - bushing boots provide high voltage electrical insulation, preventing flashover caused by moisture ingress, industrial contamination, high humidity and rodents.
High Voltage 33kV Bushing Boots (RABK/STBK)
The high voltage bushing diameters on a 33kV switchgear or transformer system are normally in excess of 100mm in diameter so a standard boot is unsuitable. 33kV insulating boots are ex stock.
400 Series Interface C Compact Nexans Euromold Cable Connectors and Bushings connect and terminate HV cables to Interface C bushings on switchgear and transformers.
Nexans Euromold provide high voltage cable accessories to suit the 7 main bushing interfaces : A, B, C (Compact), C (Symmetrical), D, E and F.
Nexans Euromold cable joints, cable terminations, epoxy bushings, angled (elbow) and straight plug-in or bolted separable connectors for connecting, jointing and terminating high voltage cables.
EXD Hazardous Area Barrier Glands from Flexicon are manufactured from nickel plated brass with a nylon seal, to an IP rating of IP66, IP67, IP68 (5bar) and IP69K - ATEX certified barrier glands are suitable for use with Flexicon flexible conduit (liquid tight types) in Zone 1, Zone 2, Zone 21 and Zone 22.
EXD flameproof barrier glands are suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22 hazardous areas, when used with the Flexicon range of liquid-tight flexible conduits.
Hazardous Area Barrier Gland (ATEX) Certified
• High mechanical strength
• Suitable for threaded entries
• Operating temperature of -60oC to +85oC
• Two-part epoxy solid-setting putty, gloves and mixing instructions
ATEX barrier glands for indoor or outdoor use in Zone 1, Zone 2, Zone 21 and Zone 22 Hazardous Areas with all types of cables housed in Liquid Tight flexible conduit systems. ATEX barrier glands are suitable for knockouts or threaded entries. Nickel plated brass compression fitting comprising of body, nut, earthing ferrule, nylon compression seal and compound barrier. The compound barrier seals around the cable conductors for hazardous area cable glanding on conduit systems. The earthing ferrule is manufactured in machined nickel plated brass to facilitate easy assembly and re-use. Also ensures high mechanical strength and electrical continuity.
Flexicon flexible conduits with ATEX flameproof barrier glands (LTP-EXD flameproof barrier glands) are suitable for use with Flexicon LTP, LTPHC, LTPUL, LTPSS and LTPPU conduits.
High Voltage Cable Terminations (SWA) with CMP Zen Insulated Cable Glands & Cast Integral Earth Lug
CMP Zen Glands - Protect Against Short Circuit Earth Fault Currents
CMP CIEL Cast Integral Earth Lug - Aluminium HV Cable Glands
High voltage single core power cables (3.3kV, 6.6kV, 11kV, 33kV) can generate high fault current ratings via aluminium wire armours (AWA) where the actual fault current may exceed that of the standard CMP earth tag - it is vital for low and high voltage electrical safety to match the rated fault current of the cable gland earth tag to that of the cable armour. CMP unique Cast Integral Earth Lug (CIEL) cable gland designs overcome potential overheating and possible flash over problems - CMP BW CIEL, CMP CW CIEL, CMP E1W CIEL, CMP E1FW CIEL, CMP E2W CIEL and CMP E2FW CIEL cable gland ranges.
CMP CIEL 20S to 40mm - 26.0kA for 1 second short circuit fault rating
CMP CIEL 50s to 90mm - 43.0kA for 1 second short circuit fault rating
CMP Cast Integral Earth Lug (CIEL) Aluminium Cable Glands IP66 for SWA Cable Termination at High Voltage - Specification
CMP CW CIEL type aluminium cable gland for use with all types of low voltage and high voltage Single Wire Armour (SWA) cable providing an environmental seal on the cable outer sheath, mechanical retention and electrical continuity via armour wire termination. All CMP cable glands are EMC Tested. CMP CW CIEL range of industrial aluminium cable glands is designed and tested to BS 6121:Part 1:1989, meets or surpasses the requirements of EN 50262 :1999, and is produced from aluminium. The CW CIEL aluminium cable gland provides a high fault current rated cable termination complete with a CMP unique Cast Integral Earth Lug concept - especially suitable for medium and high voltage electrical cables and systems where a high level of protection against short circuit earth fault currents is required.
Nuhas is the first and only cable producer in the Middle East to have been certified by DNV, Norway as capable of manufacturing power, control and instrumentation cables for shipboard, high speed/light craft and off-shore cables.
Batra Henlay Cables provides superior quality copper flexible wires, control instrumentation, telecommunication cables moreover high defined coaxial cables in various forms of insulation to the power, telecommunication, and energy industries.
Everest Cables And Connectors Private Limited, Delhi, India
Started to create milestones, we Everest Cables And Connectors Private Limited marked our presence in the year 1965 and operates in the manufacturing/servicing of Everest LAN Cables, Radio Coaxial Cables, Data Cables, Alarm Cables, Wire Harness Assemblies since 47 years. Our quality services/products have always won us many appreciations from our clients. Our spontaneous performance and confident approach in offering the excellent range of Everest LAN Cables, Radio Coaxial Cables, Data Cables, Alarm Cables, Wire Harness Assemblies, LAN Cables that has made us to deepen our roots in the market.
Get more details visit us : http://www.everestcables.co.in
Prysmian offers a comprehensive range of flexible cable solutions with Class 5 conductors for fixed installations. With Flexible XLPE and Fire Performance cables, Prysmian has a full suite of cables for the entire Construction market.
As a successful international cable manufacturer nobody knows more about cable than Draka. Through a continual programme of research and development, Draka lead the way with a world beating range of premium quality cables that meet and often exceed British Standards and are fully BASEC approved.
Draka is a major supplier to the construction industry, with a complete range of housewiring and low voltage supply cables, for use in domestic premises, commercial office developments and public buildings, such as retail business parks, hospitals and sports complexes. In addition to this general range of energy cables, the company is a market leader in the production of fire retardant cables and addresses the needs of a host of specific, individual markets and applications.
Sensortronics Load Cells from Vishay are some of the highest quality load cells in the market place. Sensortronics is a top manufacturer of sensors used in force-based measurement. The heart of any weighing system is the Sensortronics load cell. While they are not exciting to watch, load cells are highly accurate transducers which provides the user with information not generally obtainable by other technology due to commercial factors. Sensortronics load cells are designed to sense force or weight under a wide range of adverse conditions; they are not only the most essential part of an electronic weighing system, but also the most vulnerable.
In addition, it is imperative that the user selects the correct load cell for the application and provide the necessary care for the load cell during its lifetime. Understanding these important issues and properly maintaining the Sensortronics load cells will ensure trouble free weighing for a long period of time. Load cells may be damaged because of (shock) overloading, lightning strikes or heavy surges in current, chemical or moisture ingress, mishandling (dropping, lifting on cable, etc.), vibration, seismic events or internal component malfunctioning. Also available, great selection of load cells for mixing tanks in a wide variety of styles and capacities.
For control circuits unenclosed, enclosed in conduit, buried direct or in underground ducts for commercial, industrial, mining and electricity authority systems where mechanical damage may occur. The 90°C cable is used where improved aging properties to those of 75°C PVC insulated cable are required because of higher ambient temperatures.
Don't Wait Until It's Too Late! 5-Signs Your Garage Door Needs ReplacingCR Garage Doors
This infographic unveils the 5 telltale signs your garage door needs a replacement. Avoid costly repairs and upgrade to a modern, secure, and silent entryway. Visit our website for more information about garage door replacement.
Website-> https://cr-garagedoors.com/
Are Gutters Necessary? Explore the details now!AmeliaLauren3
Gutters are typically installed at a slight downward slope to allow water to flow freely towards downspouts or drains – the downspout being the vertical pipe attached to the gutters. The water is subsequently transported by the downspout to either the ground or an underground drainage system. Maintaining a gutter system that is free of blockages and functional requires regular maintenance.
But, many wonder in what situations gutters are required and not required. In this ppt we will discuss in detail the matter, ‘Are Gutters Necessary?’
Are Seamless Gutters Worth It? Explore nowacadiaborton
Seamless gutters live up to their name: they are uncomplicated gutters that flow freely without needless joins or seams. They do have seams, but they are limited to the downspouts and corners. Painted metal is used to make seamless gutters. If you're wondering why seamless gutters could be preferable to traditional ones, keep reading this ppt for the advantages.
Business Solutions with .NET Development in Quantum Computing.pdfQServices Inc.
Unlock the power of quantum computing with QServices. Our .NET experts deliver cutting-edge solutions to drive your business forward. Experience the future of computing and gain a competitive edge today.
Unlocking Insights: AI-powered Enhanced Due Diligence Strategies for Increase...RNayak3
Explore how a risk-based approach to Enhanced Due Diligence can deliver effective Anti-Money Laundering (AML) compliance and monitoring in banking and financial services.
A Bulgarian work permit is valid for up to one year, after which it can be renewed as long as the conditions of employment have not changed. After obtaining a work permit, the employee will need to apply for a Type D visa at the Bulgarian embassy or consulate in their country. Urgent requirement for Bulgaria 🇧🇬🇧🇬work D Category National Permit Visa ( Indian /Nepali Nationality only) Visa Validity - 3 to 6 months on renewables basis. Job category - General worker/ Helper Salary - 800 Euro @ 8 hrs.+ Over time extra Age- 20- 40 years Total processing time -4-5 Months
Get your dream bridal look with top North Indian makeup artist - Pallavi KadalePallavi Makeup Artist
Achieve your dream wedding day look with renowned North Indian bridal makeup artist, Pallavi Kadale. With years of experience, her expert techniques and skills will leave you looking flawless and radiant. Book today for your perfect bridal makeover.
Top Best Astrologer +91-9463629203 LoVe Problem SolUtion specialist In InDia ...gitapress3
Top Best Astrologer +91-9463629203 LoVe Problem SolUtion specialist In InDia Love ProBlem asTroloGer +91-9463629203 love problem solution astrologer
best love problem solution astrologer
online love problem solution astrologer
love problem solution astrologer in india
love problem solution astrologer in kolkata
love problem solution astrologer near me
love problem solution astrologer in ludhiana
love problem solution astrologer acharya ji
love problem solution astrologer in delhi
love problem solution astrologer amritsar
astrologer love problem solution
astrologer for love problem
astrology love problem solution
love solution astrologer
love problem solution specialist astrologer
love problem solution by astrologer
astrology love problem solution baba ji
love problem solve astrologer
love problem solution usa
love problem solution expert astrologer
astrologer for love marriage problem solution
love problem solution astrologer in mumbai
love problem solution muslim astrologer
love marriage specialist astrologer problem solution
famous love astrologer
love problem solution astrologer specialist
love problem solution astrologer baba ji
Delightful Finds: Unveiling the Power of Gifts Under 100JoyTree Global
Stretch your budget and spread joy! This guide explores the world of gifts under 100, proving thoughtful gestures don't require a hefty price tag. Discover unique and practical options for birthdays, holidays, or simply showing someone you care. Find inspiration for every occasion within your budget!
Comprehensive Water Damage Restoration Serviceskleenupdisaster
Find out how Disaster Kleenup's professional water damage restoration services can quickly and efficiently restore your property. Find more about our advanced techniques and quick action plans. Visit here: https://iddk.com/disaster-cleanup-services/flood-damage/
Elevate Your Brand with Digital Marketing for Fashion IndustryMatebiz Pvt. Ltd
Matebiz Pvt. Ltd. specializes in providing cutting-edge digital marketing for Fashion Industry. Our comprehensive strategies ensure that your brand stands out in the competitive fashion landscape. From targeted social media campaigns to search engine optimization tailored for fashion keywords, we cover it all. With a deep understanding of industry trends and consumer behavior, we craft compelling content and engaging visuals to enhance your online presence. Trust Matebiz Pvt. Ltd. to elevate your fashion brand through strategic digital marketing initiatives.
Unlock the potential of Ruby on Rails for your next project. Hire RoR Developers from Semiosis for scalable and efficient web solutions. With expertise in RoR development, our team crafts robust applications to meet your business goals. Dial +1 9177322215 to collaborate with us and elevate your online presence.
SMS2ORBIT | launched in 2022 in Mumbai's Andheri area, aims to be the most reliable Bulk SMS Service Provider in Mumbai.
If More Information About The SMS Service Provided By SMS2ORBIT Is Desired, Please Don’t Hesitate To Contact The Business Team. They Can Be Reached At
business@sms2orbit.com Or By Calling 97248 55877.
Earth moving equipment refers to heavy-duty machines used in construction, mining, agriculture, and other industries to move large amounts of earth, soil, and other materials. These machines include excavators, bulldozers, loaders, and backhoes, which are essential for tasks such as digging, grading, and leveling land.
Earthmovers is a leading brand in the industry, known for providing reliable and high-performance earth moving equipment. Their machines are designed to handle the toughest jobs with efficiency and precision, ensuring optimal productivity on any project.
All Trophies at Trophy-World Malaysia | Custom Trophies & Plaques Supplier. Come to our Trophy Shop today and check out all our variety of Trophies available. We have the widest range of Trophies in Malaysia. Our team is always ready to greet your needs and discuss with you on your custom Trophy for your event. Rest assured, you will be with the best Trophy Supplier in Malaysia. The official Trophy Malaysia. Thank you for your support.
Islamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxamilabibi1
Islamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docxIslamabad No 1 Amil Baba In Pakistan amil baba kala ilm.docx
Looking for the Reliable Logistics Solutions in India? Discover unparalleled efficiency and reliability with our top-rated logistics services. We specialize in streamlining supply chains, ensuring timely deliveries, and providing cutting-edge tracking solutions. Our platform caters to businesses of all sizes, offering customizable logistics solutions to meet your unique needs. With a focus on innovation and customer satisfaction, we are your trusted partner in navigating the complexities of logistics in India. Choose us for seamless, cost-effective, and scalable logistics solutions. Experience the best in Indian logistics with our expert team by your side.
Office Business Furnishings | Office EquipmentOFWD
OFWD is Edmonton’s Newest and most cost-effective source for Office Furnishings. Conveniently located on 170 street and 114 Avenue in Edmonton’s West End. We take pride in servicing a client base of over 500 corporations throughout the Edmonton and Alberta area. OFWD is in the business of satisfying the home or corporate office environment needs of our clients, from individual pieces of furniture for the home user to the implementation of complete turn-key projects on much larger scales. We supply only quality products from reputable manufacturers. It is our intention to continue to earn the trust of our clients by dealing with honesty and integrity and by providing service and after sales follow-up second to none.
Experience the breathtaking beauty of a Waikiki sunset aboard the MAITAI Catamaran. Sail along the stunning coastline as the sun dips below the horizon, casting vibrant hues across the sky. Enjoy the gentle ocean breeze, refreshing drinks, and a relaxed atmosphere. This unforgettable voyage offers panoramic views of Diamond Head and the Waikiki skyline, making it the perfect way to end your day in paradise. Join us for a memorable sunset cruise you won't forget. Please visit our website: https://www.maitaicatamaran.net/ and call us at 808-922-5665 for additional information.
2. 1
NUHAS OMAN – QUALITY & RELIABILITY.
INTRODUCTION
INTRODUCTION
����������������������������������������
�����������������������������������
�������������������������������������
�������������������������������������������
����������������������������������������
����������������������������
����������������������������������������
������������������������������
�������������������������������
�������������������������������
Nuhas Oman LLC, an integral part of The Al Bahja Group of Companies, is a Quality producer of:
• HV, MV and LV Cables
• Enamelled Copper Wires
• Oxygen Free Continuous Cast Copper Wire Rods
• Drawn Copper Conductors
Our state-of-the-art manufacturing facilities with cutting edge technology ensure that our products meet with
highest quality standards. All our products utilize only OXYGEN FREE HIGH CONDUCTIVITY
ELECTRONIC GRADE Copper produced through the Outokompu UPCAST technology, producing minimum
99.99% pure copper with oxygen content less than 5 ppm. The usage of �������������������������������������
��������������������������������������������
Our range of World-class HV, MV and LV Cables includes Single & Multi Core Armoured and Un-armoured
Cables, Specialty, Control, Instrumentation and also LSF, FRLS, LSOH & Custom Cables to meet the
requirements of a broad spectrum of applications ranging from �����������������������������������������������������
�������������������������������������������������������������������������������������
The Cables are produced in compliance to the requirements of BS, IEC, VDE, ASTM, ICEA & UL
specifications. The �������������������������������� by acclaimed independent international certifying agencies
confirming compliance to respective standards.
Nuhas ���������������������������������������� that conform to relevant International standards and ��������
�����������������������������������������������������������������
����������������������������������������������������������������������������������������������
�
Our quality cycle encompasses raw material and consumable sourcing, in-process production controls and
certification of finished goods prior to delivery. A well-equipped in-house quality assurance facility, manned by
qualified professionals from the industry, ensures that all products delivered meet stringent quality controls
and parameters. Our state-of-the-art laboratory is equipped to test as per relevant international standards as
also to individual customer specifications.
The company endeavours to cater to the domestic, regional and global markets while maintaining the sanctity
of our pristine environment.
����������������������� is a continuing process at Nuhas Oman LLC and we at Nuhas Oman ceaselessly
strive to achieve product excellence through TOTAL QUALITY MANAGEMENT to provide the best value to
our customers.
3. 2 3
SINGLE CORE PVC INSULATED CABLES
Type H05V-U, H07V-U, H07V-R Applications
Standards BS EN 50525-2-31 : 2011
Construction 1) Oxygen Free
Electronic
Copper Conductor
2) PVC Insulation
Packing In rolls of 100 yards, spools,
drums or as per customer
requirements
Technical
Data
Max. Operating Temperature: 70º
C
Rated Voltage: 300/500 V (H05V-U)
450/750 V(H07V-U, H07V-R)
NOMINAL CROSS
SECTION
CLASS OF
COPPER
CON-
DUCTOR
INSULATION
THICKNESS
NOM. OVERALL
DIAMETER
APPROX. NET
WEIGHT
STANDARD
LENGTH
(mm2
) (mm Nominal) (mm) (kg/km)
H05V-U 300/500 V Yards
0.50 1 0.6 2.3 9 100
0.75 1 0.6 2.5 11 100
1.0 1 0.6 2.7 14 100
H07V-U 450/750 V
1.5 1 0.7 3.2 21 100
2.5 1 0.8 3.9 32 100
4 1 0.8 4.4 47 100
6 1 0.8 5.0 66 100
H07V-R 450/750 V
1.5 2 0.7 3.3 21 100
2.5 2 0.8 4.0 32 100
4 2 0.8 4.6 47 100
6 2 0.8 5.2 66 100
Meters
10 2 1.0 6.7 115 300
16 2 1.0 7.8 175 300
25 2 1.2 9.3 260 1000
35 2 1.2 10.5 350 1000
50 2 1.4 11.9 480 1000
70 2 1.4 13.6 670 1000
95 2 1.6 15.7 925 1000
120 2 1.6 17.2 1150 1000
150 2 1.8 19.0 1415 1000
185 2 2.0 21.1 1775 1000
240 2 2.2 23.8 2320 1000
300 2 2.4 26.5 2895 1000
400 2 2.6 29.6 3695 1000
500 2 2.8 33.0 4720 1000
630 2 2.8 36.7 6030 500
In dry rooms, in apparatus, switch and
distribution boards, for laying in conduit
on and under plaster and on insulating
supports above plaster
SINGLE CORE PVC INSULATED FLEXIBLE CABLES
Type H05V-K, H07V-K
Applications Flexible wire, for protected installation in
equipment and lighting fitting conduit or
under plaster
Standards BS EN 50525-2-31 : 2011
Construction 1) Fine stranded Oxygen
Free Electronic copper
wire
2) PVC Insulation
Packing In rolls of 100 yards, spools,
drums or as per customer
requirements
Technical
Data
Max. Operating Temperature: 700
C
Rated Voltage: 300/500 V H05V-K
450/750 V H07V-K
NOMINAL CROSS
SECTION
CLASS OF
COPPER
CON-
DUCTOR
INSULATION
THICKNESS
NOM. OVERALL
DIAMETER
APPROX. NET
WEIGHT
STANDARD
LENGTH
(mm2
) (mm Nominal) (mm) (kg/km)
H05V-K 300/500 V Yards
0.5 5 0.6 2.5 9 100
0.75 5 0.6 2.7 11 100
1.0 5 0.6 2.8 14 100
H07V-K 450/750 V
1.5 5 0.7 3.4 21 100
2.5 5 0.8 4.1 32 100
4 5 0.8 4.8 47 100
6 5 0.8 5.3 66 100
Meters
10 5 1.0 6.8 110 300
16 5 1.0 8.1 170 300
25 5 1.2 10.2 266 1000
35 5 1.2 11.7 360 1000
50 5 1.4 13.9 494 1000
70 5 1.4 16.0 696 1000
95 5 1.6 18.2 965 1000
120 5 1.6 20.2 1203 1000
150 5 1.8 22.5 1483 1000
185 5 2.0 24.9 1852 1000
240 5 2.2 28.4 2424 1000
4. 4 5
HEAT RESISTANT SINGLE CORE PVC INSULATED CABLES
Type H07V2-R
H07V2-U
Applications In dry rooms, in apparatus, switch and
distribution boards, for laying in conduit
on and under plaster and on insulating
supports above plaster
Standards BS EN 50525-2-31 : 2011
Construction 1) Oxygen Free Electronic
Copper Conductor
2) HR PVC Insulation
Packing In rolls of 100 yards, spools,
drums or as per customer
requirements
Technical
Data
Max. Operating Temperature: 90˚C
Rated Voltage: 450/750 V
NOMINAL CROSS
SECTION
CLASS OF
COPPER
CON-
DUCTOR
INSULATION
THICKNESS
NOM. OVERALL
DIAMETER
APPROX. NET
WEIGHT
STANDARD
LENGTH
(mm2
) (mm Nominal) (mm) (kg/km)
H07V2-U 450/750 V Yards
1.5 1 0.7 3.2 21 100
2.5 1 0.8 3.9 32 100
4 1 0.8 4.4 47 100
6 1 0.8 5.0 66 100
H07V2-R 450/750 V
1.5 2 0.7 3.3 21 100
2.5 2 0.8 4.0 32 100
4 2 0.8 4.6 47 100
6 2 0.8 5.2 66 100
Meters
10 2 1.0 6.7 110 300
16 2 1.0 7.8 170 300
25 2 1.2 9.3 255 1000
35 2 1.2 10.5 345 1000
50 2 1.4 11.9 470 1000
70 2 1.4 13.6 665 1000
95 2 1.6 15.7 920 1000
120 2 1.6 17.2 1145 1000
150 2 1.8 19.0 1410 1000
185 2 2.0 21.1 1765 1000
240 2 2.2 23.8 2310 1000
300 2 2.4 26.5 2885 1000
400 2 2.6 29.6 3685 1000
500 2 2.8 33.0 4710 1000
630 2 2.8 36.7 6030 500
HEAT RESISTANT SINGLE CORE PVC INSULATED FLEXIBLE CABLES
Type H07V2-K
Applications Flexible wire, for protected installation
in equipment and lighting fitting
conduit or under plaster
Standards BS EN 50525-2-31 : 2011
Construction 1) Fine stranded Oxygen Free
Electronic copper wire
2) HR PVC Insulation
Packing In rolls of 100 yards, spools,
drums or as per customer
requirements
Technical
Data
Max. Operating Temperature: 90˚C
Rated Voltage: 450/750 V
NOMINAL CROSS
SECTION
CLASS OF
COPPER
CON-
DUCTOR
INSULATION
THICKNESS
NOM. OVERALL
DIAMETER
APPROX. NET
WEIGHT
STANDARD
LENGTH
(mm2
) (mm Nominal) (mm) (kg/km)
H07V2-K 450/750 V Yards
1.5 5 0.7 3.4 21 100
2.5 5 0.8 4.1 32 100
4 5 0.8 4.8 47 100
6 5 0.8 5.3 66 100
Meters
10 5 1.0 6.8 110 300
16 5 1.0 8.1 170 300
25 5 1.2 10.2 266 1000
35 5 1.2 11.7 360 1000
50 5 1.4 13.9 494 1000
70 5 1.4 16.0 696 1000
95 5 1.6 18.2 965 1000
120 5 1.6 20.2 1203 1000
150 5 1.8 22.5 1483 1000
185 5 2.0 24.9 1852 1000
240 5 2.2 28.4 2424 1000
5. 6 7
FLEXIBLE CIRCULAR, 3, 4 & 5 CORE CABLES
Reference
Standards
BS EN 50525-2-11 : 2011
Applications For household appliances under
mediummechanicalstresses,also
in damp and wet conditions
Construction 1) Oxygen Free Electronic
Copper Conductor – Class 5
2) PVC Insulation Type TI 2
3) PVC Sheath – Type TM 2
Packing In coils/drums or as per customer
requirements
Technical
Data
Rated Voltage: 300/500 V
Temperature: 70°C
No. of cores
Nominal Cross
Section
Nominal
Insulation
thickness
Nominal cable dia.
Approx. weight per
km.
(No.) (mm2
) (mm) (mm) (kg.)
2 1.0 0.6 7.3 70
2 1.5 0.7 8.7 97
2 2.5 0.8 9.9 130
3 1.0 0.6 7.7 90
3 1.5 0.7 9.2 125
3 2.5 0.8 10.5 170
Temperature: 90°C
requirements
FIRE ALARM / SIGNAL CABLES
Reference
Standards
BS 7629-1,
BS 6387 Category CWZ
Applications In populated places where there
is risk of fire. Can be used in
wide variety of applications
including voice alarm, fire and
security circuits and networking
requirements due to excellent data/
signal transmission characteristics
Voltage: 300/500 V
Construction 1) Oxygen Free Electronic Copper
Conductor
2) Mica tape
3) FRLSOH Insulation
4) Overall Screen with Aluminium
Mylar tape and Tinned copper drain
wire
5) FRLSOH Sheath
Packing In coils/drums or as per customer
Technical
Data
2 0.75 0.6 0.8 5.7 7.2 65
2 1.0 0.6 0.8 5.9 7.5 70
2 1.5 0.7 0.8 6.8 8.6 100
2 2.5 0.8 1.0 8.4 10.6 150
2 4 0.8 1.1 9.7 12.1 195
3 0.75 0.6 0.8 6.0 7.6 75
3 1.0 0.6 0.8 6.3 8.0 90
3 1.5 0.7 0.9 7.4 9.4 120
3 2.5 0.8 1.1 9.2 11.4 185
3 4 0.8 1.2 10.5 13.1 240
4 0.75 0.6 0.8 6.6 8.3 90
4 1.0 0.6 0.9 7.1 9.0 110
4 1.5 0.7 1.0 8.4 10.5 160
4 2.5 0.8 1.1 10.1 12.5 230
4 4 0.8 1.2 11.5 14.3 300
5 0.75 0.6 0.9 7.4 9.3 110
5 1.0 0.6 0.9 7.8 9.8 130
5 1.5 0.7 1.1 9.3 11.6 190
5 2.5 0.8 1.2 11.2 13.9 275
5 4 0.8 1.4 13.0 16.1 370
Approx. Weight
per km
Mean Overall Diameter
Lower Limit
No. of
Cores
Nominal
Cross
Section
Nominal
Insulation
Thickness
Nominal
Sheath
Thickness Upper Limit
(mm²) (mm) (mm) (mm) (kg.)
6. 9
No. of cores
Nominal cross-sectional
area of conductors mm2
Radial thickness of
Insulation (mm)
Nom. overall dimension
(mm)
2 1.0 0.6 4.7 x 7.4
2 1.5 0.7 5.4 x 8.4
2 2.5 0.8 6.2 x 9.8
2 4.0 0.8 6.9 x 11.5
2 6.0 0.8 7.8 x 13.0
2 10.0 1.0 9.6 x 16.0
2 16.0 1.0 10.8 x 18.5
3 1.0 0.6 4.7 x 9.8
3 1.5 0.7 5.3 x 11.5
3 2.5 0.8 6.2 x 13.5
3 4.0 0.8 7.1 x 16.3
3 6.0 0.8 7.8 x 18.0
3 10.0 1.0 9.6 x 22.5
3 16.0 1.0 10.8 x 26.3
FLAT CABLES WITHOUT EARTH CONDUCTOR
Reference
Standards
BS 6004:2012
Applications Fixed installation in dry or damp
premises, electric power & lighting
devices, telecommunication appliances
Voltage: 300/500 V.
Temperature : 700
C
Construction 1) Oxygen Free Electronic
Copper Conductor
2) PVC Insulation
3) PVC Sheath
Packing In drums or as per customers
requirements
Technical
Data
FLAT CABLES WITH EARTH CONDUCTOR
Standards BS 6004:2012 Applications Fixed installation in dry or damp premises
Construction 1) Oxygen Free Electronic
Copper Conductor
2) PVC Insulation
3) PVC Sheath
4) Earth Conductor
Packing In drums or as per customer
requirements
Technical
Data
Voltage: 300/500 V.
Temperature: 70˚C
No. of cores
Copper
conductor mm2
Thickness of
Insulation (mm)
Nom. overall
dimension (mm)
Earth Conductor,
minimum nominal cross-
sectional area mm2
2 1.0 0.6 4.7 x 8.6 1
2 1.5 0.7 5.3 x 9.6 1
2 2.5 0.8 6.2 x 11.5 1.5
2 4.0 0.8 6.9 x 13.0 1.5
2 6.0 0.8 7.8 x 15.0 2.5
2 10.0 1.0 9.5 x 18.9 4
2 16.0 1.0 10.8 x 21.9 6
3 1.0 0.6 4.7 x 11.0 1
3 1.5 0.7 5.3 x 12.5 1
3 2.5 0.8 6.2 x 14.5 1.5
3 4.0 0.8 7.1 x 17.9 1.5
3 6.0 0.8 7.8 x 20.0 2.5
3 10.0 1.0 9.5 x 25.5 4
3 16.0 1.0 10.8 x 29.5 6
8
SINGLE CORE THERMOSETTING INSULATED LSF WIRING CABLES
Type H05Z-U , H07Z- U, HO7Z- R Applications These types of Cables are having
self-extinguishing behaviour
without halogenidric acids emission.
Furthermore toxic and corrosive gases
and smoke evolution is reduced to
very low level. These characteristics
make this ideal for usage where safety
behaviour is important at public places
in case of fire.
Reference
Standards
BS EN 50525-3-41: 2011
Construction 1) Oxygen Free Electronic
Copper Conductor
2) Thermosetting / LSF
Insulation
Technical
Data
Max. Operating Temperature: 90˚C
Rated Voltage: 300/500 V H05Z-U
450/750 V H07Z- U, HO7Z- R
Packing In rolls of 100 yards, spools,
drums or as per customer
requirements. Requirements
for LSF Cables
Oxygen index - Minimum 30
Smoke density - Maximum 60%
Acid gas - Maximum 0.5% by
weight
NOMINAL CROSS
SECTION
CLASS OF
COPPER
CON-
DUCTOR
INSULATION
THICKNESS
NOM. OVERALL
DIAMETER
APPROX. NET
WEIGHT
STANDARD
LENGTH
(mm2
) (mm) (mm) (kg/km)
H05Z-U 300/500 V Yards
0.50 1 0.6 2.3 9 100
0.75 1 0.6 2.5 11 100
1.00 1 0.6 2.7 14 100
H07Z-U 450/750 V
1.5 1 0.7 3.2 21 100
2.5 1 0.8 3.9 32 100
4.0 1 0.8 4.4 47 100
6.0 1 0.8 5.0 66 100
H07Z-R 450/750 V
1.5 2 0.7 3.3 21 100
2.5 2 0.8 4.0 32 100
4.0 2 0.8 4.6 47 100
6.0 2 0.8 5.2 66 100
Meters
10 2 1.0 6.7 110 300
16 2 1.0 7.8 170 300
25 2 1.2 8.2 255 1000
35 2 1.2 9.3 345 1000
50 2 1.4 10.9 470 1000
70 2 1.4 12.6 665 1000
95 2 1.6 14.7 920 1000
120 2 1.6 16.2 1150 1000
150 2 1.8 17.8 1415 1000
185 2 2.0 20.1 1765 1000
240 2 2.2 22.8 2310 1000
300 2 2.4 25.3 2890 1000
400 2 2.6 29.0 3685 1000
500 2 2.8 32.2 4700 1000
630 2 2.8 35.4 6000 500
7. 10 11
SINGLE CORE THERMOSETTING INSULATED SHEATHED LSF CABLES
Reference
Standards
BS 7211: 2012 Applications These types of Cables are having
self-extinguishing behaviour
without halogenidric acids emission.
Furthermore toxic and corrosive gases
and smoke evolution is reduced to
very low level. These characteristics
make this ideal for usage where safety
behaviour is important at public places
in case of fire
Max. Operating Temperature: 90˚C
Rated Voltage: 300/500 V
Construction 1) Oxygen Free Electronic
Copper Conductor
2) Thermosetting / LSF
Insulation
3) LSF Sheath
Packing In rolls of 100 yards, spools,
drums or as per customer
requirements.
Technical
Data
Requirements
for LSF Cables
Oxygen index - Minimum 30
Smoke density - Maximum 60%
Acid gas - Maximum 0.5% by
weight
NOMINAL
CROSS
SECTION
CLASS OF COPPER
CONDUCTOR
INSULATION
THICKNESS
SHEATH
THICKNESS
NOM. OVERALL
DIAMETER
APPROX.
NET WEIGHT
(mm2
) (mm) (mm) (mm) (kg/km)
1.0 1 0.7 0.8 4.8 28
1.0 2 0.7 0.8 4.9 28
1.5 1 0.7 0.8 5.0 36
1.5 2 0.7 0.8 5.2 36
2.5 1 0.7 0.8 5.5 50
2.5 2 0.7 0.8 5.6 51
4 1 0.7 0.9 6.3 72
4 2 0.7 0.9 6.4 75
6 1 0.7 0.9 6.8 95
6 2 0.7 0.9 7.1 98
10 2 0.7 0.9 8.1 150
16 2 0.7 0.9 9.2 220
25 2 0.9 1.0 11.4 300
35 2 0.9 1.1 12.8 400
FLEXIBLE CIRCULAR 2, 3, 4 & 5 CORE CABLES
Reference
Standards
BS 7211: 2012 Applications These types of Cables are having
self-extinguishing behaviour
without halogenidric acids emission.
Furthermore toxic and corrosive gases
and smoke evolution is reduced to
very low level. These characteristics
make this ideal for usage where safety
behaviour is important at public places
in case of fire
Max. Operating Temperature: 90˚C
Rated Voltage: 450/750 V
Construction 1) Oxygen Free Electronic
Copper Conductor
2) Thermosetting / LSF
Insulation
3) LSF Sheath
Packing In rolls of 100 yards, spools,
drums or as per customer
requirements
Technical
Data
Requirements
for LSF Cables
Oxygen index - Minimum 30
Smoke density - Maximum 60%
Acid gas - Maximum 0.5% by
weight
CONDUCTOR
SIZE
CLASS OF
COPPER
CONDUCTOR
INSULATION
THICKNESS
INNER
COVERING
THICKNESS
SHEATH
THICKNESS
NOM. OVERALL
DIAMETER
(mm2
) (mm) (mm) (mm) (mm)
2x1.0 1 0.7 0.4 1.2 9.5
2x1.0 2 0.7 0.4 1.2 9.7
2x1.5 1 0.7 0.4 1.2 10.1
2x1.5 2 0.7 0.4 1.2 10.3
2x2.5 1 0.7 0.4 1.2 11.0
2x2.5 2 0.7 0.4 1.2 11.3
2x4 1 0.7 0.4 1.2 12.1
2x4 2 0.7 0.4 1.2 12.4
2x6 1 0.7 0.4 1.2 13.2
2x6 2 0.7 0.4 1.2 13.7
2x10 1 0.7 0.4 1.4 16.0
2x10 2 0.7 0.6 1.4 16.7
2x16 2 0.7 0.6 1.4 18.8
2x25 2 0.9 0.8 1.4 23.2
2x35 2 0.9 0.8 1.6 26.0
8. 12 13
THREE CORE THERMOSETTING INSULATED SHEATHED LSF CABLES
Reference
Standards
BS 7211: 2012 Applications These types of Cables are having
self-extinguishing behaviour
without halogenidric acids emission.
Furthermore toxic and corrosive gases
and smoke evolution is reduced to
very low level. These characteristics
make this ideal for usage where safety
behaviour is important at public places
in case of fire
Max. Operating Temperature: 90˚C
Rated Voltage: 450/750 V
Construction 1) Oxygen Free Electronic
Copper Conductor
2) Thermosetting / LSF
Insulation
3) LSF Sheath
Packing In rolls of 100 yards, spools,
drums or as per customer
requirements
Technical
Data
Requirements
for LSF Cables
Oxygen index - Minimum 30
Smoke density - Maximum 60%
Acid gas - Maximum 0.5% by
weight
CONDUCTOR
SIZE
CLASS OF
COPPER
CONDUCTOR
INSULATION
THICKNESS
INNER
COVERING
THICKNESS
SHEATH
THICKNESS
NOM. OVERALL
DIAMETER
(mm2
) (mm) (mm) (mm) (mm)
3x1.0 1 0.7 0.4 1.2 10.0
3x1.0 2 0.7 0.4 1.2 10.2
3x1.5 1 0.7 0.4 1.2 10.6
3x1.5 2 0.7 0.4 1.2 10.9
3x2.5 1 0.7 0.4 1.2 11.6
3x2.5 2 0.7 0.4 1.2 11.9
3x4 1 0.7 0.4 1.2 12.7
3x4 2 0.7 0.4 1.2 13.1
3x6 1 0.7 0.4 1.2 14.4
3x6 2 0.7 0.4 1.4 15.0
3x10 1 0.7 0.6 1.4 16.9
3x10 2 0.7 0.6 1.4 17.7
3x16 2 0.7 0.6 1.4 19.9
3x25 2 0.9 0.8 1.4 24.6
3x35 2 0.9 0.8 1.6 27.6
FOUR CORE THERMOSETTING INSULATED SHEATHED LSF CABLES
BS 7211: 2012 Applications These types of Cables are having
self-extinguishing behaviour without
halogenidric acids emission. Furthermore
toxic and corrosive gases and smoke
evolution is reduced to very low level.
These characteristics make this ideal for
usage where safety behaviour is important
at public places in case of fire
Max. Operating Temperature: 90˚C
Rated Voltage: 450/750 V
Construction 1) Oxygen Free Electronic
Copper Conductor
2) Thermosetting / LSF
Insulation
3) LSF Sheath
Packing In rolls of 100 yards, spools,
drums or as per customer
requirements
Technical
Data
Requirements
for LSF Cables
Oxygen index - Minimum 30
Smoke density - Maximum 60%
Acid gas - Maximum 0.5%
by weight
CONDUCTOR
SIZE
CLASS OF
COPPER
CONDUCTOR
INSULATION
THICKNESS
INNER
COVERING
THICKNESS
SHEATH
THICKNESS
NOM. OVERALL
DIAMETER
(mm2
) (mm) (mm) (mm) (mm)
4x1.0 1 0.7 0.4 1.2 10.7
4x1.0 2 0.7 0.4 1.2 11.0
4x1.5 1 0.7 0.4 1.2 11.4
4x1.5 2 0.7 0.4 1.2 11.7
4x2.5 1 0.7 0.4 1.2 12.6
4x2.5 2 0.7 0.4 1.2 12.8
4x4 1 0.7 0.4 1.2 13.8
4x4 2 0.7 0.4 1.2 14.2
4x6 1 0.7 0.4 1.4 16.1
4x6 2 0.7 0.6 1.4 16.7
4x10 1 0.7 0.6 1.4 18.4
4x10 2 0.7 0.6 1.4 19.2
4x16 2 0.7 0.6 1.4 21.8
4x25 2 0.9 0.8 1.6 27.5
4x35 2 0.9 1.0 1.6 30.7
9. 14 15
FIVE CORE THERMOSETTING INSULATED SHEATHED LSF CABLES
Reference
Standards
BS 7211: 2012 Applications These types of Cables are having
self-extinguishing behaviour without
halogenidric acids emission. Furthermore
toxic and corrosive gases and smoke
evolution is reduced to very low level.
These characteristics make this ideal for
usage where safety behaviour is important
at public places in case of fire
Max. Operating Temperature: 90˚C
Rated Voltage: 450/750 V
Construction 1) Oxygen Free Electronic
Copper Conductor
2) Thermosetting / LSF
Insulation
3) LSF Sheath
Packing In rolls of 100 yards, spools,
drums or as per customer
requirements
Technical
Data
Requirements
for LSF Cables
Oxygen index - Minimum 30
Smoke density - Maximum 60%
Acid gas - Maximum 0.5%
by weight
CONDUCTOR
SIZE
CLASS OF
COPPER
CONDUCTOR
INSULATION
THICKNESS
INNER
COVERING
THICKNESS
SHEATH
THICKNESS
NOM. OVERALL
DIAMETER
(mm2
) (mm) (mm) (mm) (mm)
5x1.0 1 0.7 0.4 1.2 11.5
5x1.0 2 0.7 0.4 1.2 11.9
5x1.5 1 0.7 0.4 1.2 12.3
5x1.5 2 0.7 0.4 1.2 12.6
5x2.5 1 0.7 0.4 1.2 13.6
5x2.5 2 0.7 0.4 1.2 13.9
5x4 1 0.7 0.4 1.4 15.9
5x4 2 0.7 0.6 1.4 16.4
5x6 1 0.7 0.6 1.4 17.5
5x6 2 0.7 0.6 1.4 18.1
5x10 1 0.7 0.6 1.4 20.0
5x10 2 0.7 0.6 1.4 20.9
5x16 2 0.7 0.8 1.4 24.2
5x25 2 0.9 1.0 1.6 30.5
5x35 2 0.9 1.0 1.6 33.6
11. 17
Current carrying capacities at ambient temperature 30°C
Volt Drop Data
+ Volt drop for sizes 25mm2
and 35mm2
are based on total impedance 'z' only. For 'r' and 'x: data, lEE Wiring
Regulations 16th Edition should be referred to.
NOTE: Data in the above table is based on lEE Wiring Regulations 16th Edition. The current carrying capacities of
Heat Resistant PVC insulated cables are higher, please refer to Technical Department if data is required.
The tabulated current carrying capacities relate to continuous loading and are also known as the "full thermal ratings"
implying that the cables will operate at their maximum conductor continuous temperature of 70°C. The data is extracted
from lEE Wiring Regulations 16th Edition.
The tabulated current rating capacities also relate to installations where the overload protection is afforded by a fuse to
BS 88 or BS 1361 or a miniature circuit breaker to BS 3871. Where the conductor is protected by a semi-enclosed fuse
to BS 3036, the size of the conductor is to be such that its tabulated current carrying capacity is not less than the value
of the fuse rating adjusted by multiplier 1.38 in addition to the correction factors for ambient temperature, thermal
insulation and grouping. For details refer to clause 6.2 of Appendix 4 - lEE Wiring Regulations 16th Edition.
For a given cable run, to calculate the voltage drop (in mV), the tabulated value (mV/A/m) has to be multiplied by
the cable route length in metres and the design current. For three-phase circuits the tabulated mV/A/m values relate
to the line voltage.
For cables of 16mm2
or less cross sectional area, the inductance can be ignored and mV/A/m values are based on
resistance (r) only. For cables of cross sectional area greater than 16mm2
, mV/A/m values based on resistance (r)
and inductance (x) are significant. However for brevity, Table, for single core cables of sizes 25mm2
& 35mm2
, list
(mV/A/m) z values based on total impedance (z) only.
Where the power factor of the A.C. load is widely different from the cable power factor, use of (mV/A/m) z values for
calculating the volt drop may give a pessimistically high value. For detailed information, reference should be made to
Appendix 4 of the lEE Wiring Regulations 16th Edition.
Table 1
Single Core PVC Insulated Non-Sheathed Cables - Cables
in conduit on a wall or ceiling or in trunking (Reference Method 3)
2
Current
carrying
Capacities
(amperes)
Volt Drop
(mV/A/m)
Current
carrying
capacities
(amperes)
Volt Drop
(mV/A/m)
3 or 4
three
phase
ac
2 cables single
phase ac
r x z
3 or 4 cables
three phase ac
r x z
134 0.95 0.30 1.00 0.81 0.26 0.85
171 0.65 0.29 0.72 0.56 0.25 0.61
207 0.49 0.28 0.56 0.42 0.24 0.48
239 0.39 0.27 0.47 0.33 0.23 0.41
262 0.31 0.27 0.41 0.27 0.23 0.36
296 0.25 0.27 0.37 0.22 0.23 0.32
346 0.195 0.26 0.33 0.17 0.23 0.29
Conductor
Cross
Sectional
Area
mm
1
1.5
2.5
4
6
10
16
+25
+35
394 0.160 0.26 0.31 0.14 0.23 0.27
467 0.130 0.26 0.29 0.12 0.22 0.25
2 cables
single
phase ac
or dc
13.5
17.5
24
32
41
57
76
101
125
3 or 4
cables
three
phase
ac
12
15.5
21
28
36
50
68
89
110
2 cables
single
phase ac
44
29
18
11
7.3
4.4
2.8
1.8
1.3
3 or 4
cables
three
phase
ac
38
25
15
9.5
6.4
3.8
2.4
1.55
1.10 533 0.110 0.26 0.28 0.10 0.22 0.25
Conductor
Cross
Sectional
Area
mm 2
50
70
95
120
150
185
240
300
400
500
630
2 cables
single
phase ac
or dc
151
192
232
269
300
341
400
458
546
626
720 611 0.094 0.25 0.27 0.08 0.22 0.24