UDC 621.315.21 : 620.193.5 IS 10810 (Part 82) : 1993
Indian Standard
METHQD OF TESTS FOR CABLES
PART 62 FLAME RETARDANCE TEST FOR BUNCHED CABLES
I Scope
I.1 This standard covers the method for testing of a bunch of cabks mounted vertically to determine their
elative ability to resist flame propagation.
I.2 This standard recommends three test categories, these being assessed by the amount of combustible
non-metallic) material contained in one meter of bunched cables being tested.
! Significance
2.1 The propagation of flame along a bunch of cables depends on a number of features, such as:
a) the volume of non-metallic material exposed to the fire and to any flame which may be produced
by the combustion of the cables;
b) the geometrical configuration of the cables and their relationship to any enclosure:
c) the temperature at which it is possible to ignite gases emitted from the cables;
d) the quality of combustible gas released from the cables for a given temperature rise;
e) the volume of air passing through the cable installation; and
9 the construction of the cable, for example, armoured or unarmoured.
2.2 AH of the foregoing assume that the cables are able to be ignited ihen involved in an external fire.
2.3 The fire test should demonstrate that the bunched cables do not propagate fire even if its outer covering
and insulation have been destroyed in the area of flame impingement.
2.4 The objective of the fire test should be to approximately simulate the installation condition and provide
consistent results.
3 Terminology
3.1 Flame Retardance Bunched Cables
The flame retardance bunched cables are those cables which do not propagate flame to the top of the cables
after the flame source is removed and are self extitiguishing to prove their relative ability to resist fire
propagation.
4 Test Apparatus
4.1 The test apparatus (see Fig. 1A) should comprise of vertical test chamber having a width of 1 000 * 100 mm,
a depth of 2 000 9 100 mm and~lieight of 4 000 2100 mm and the floor of the chamber should be raised
150*10 mm above the ground level. The test chamber should be nominally airtight along its sides, air being
admitted, without any substantial obstruction, at the base of the test chamber through an aperture of 8002
20 mm x 400 f 10 mm situated 150 +: 10 mm from the front wall of the test chamber.
July 1993 6 BIS 1993
I
Price Group 6
BUREAU OF INDIAN STANDARDS
-MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG
NEW DELHI 110002
1
( Reaffirmed 1998 )
IS 10810 (Part 82) : 1993
Smoke out&et
(300 f 30) x (1 000 * 100)
I
Rig raised gbove groubd level
All dimensions in millimetres.
FIG. 1A FLAME TEST APPARATUS (RIG)
4.2 An outlet 300 2 5 mm x 1 000 f 10 mm should be made at the rear edge of the top of the test chamber.
The back and sides of the test chamber should be thermally insulated to give a coefficient of heat transfer
of approximately 0.7 W/ (M’K). For example, a steel plate 1.5 mm thick covered with 65 mm of mineral wool
with a suitable external cladding is satisfactory (see Fig. 1B). The cables to be tested should be fixedma
suitable steel ladder (see Fig. 2A or 28) mounted~within the test chamber such that the distance between
the ladder and the rear wall of the chamber is 150 + 10 mm.
2
IS 10810 (Part 62) : 1993
0 33.7 f 0.5
Diameter
I--
of upright
I
I
r=I
I
i o)
II
!
I 1
I
II
‘I
All dimensions in millimetres.
FIG. 2A STANDARD TUBULAR
LADDER FOR CABLE TEST
li-
0 33.7 f 0.5
Diameter
of upright
Width
800 f 10
All dimensions in millimetres.
FIG. 28 WIDE TUBULAR LAPDER
FOR CABLE TEST
4
IS 10810 (Part 62) : 1993
4.3 Smoke cleaning attachment, if used, should be such as to collect the smoke leaving the chamber but
not cause a change in the air flow rate through the test chamber.
5 Ignition Source
5.1 The ignition source should be one or two ribbon type LPG burners whose flame producing surface consists
of a flat metal plate 341 mm long and 30 mm wide through which 242 holes of 1.32 mm in diameter are
drilled on 3.2 mm centres in three staggered rows of 81, 80 and 81 holes each to form an array having the
nominal dimensions 257 mm x 4.5 mm as shown in Fig. 3Aand 36. As the burner plate may be drilled without
the use of a drilling jig the spacing of the holes may vary slightly. Additionally, a row of small holes may be
milled on each side of the burner plate to serve as pilot holes with the function ,of keeping the flame burning.
341
t-Y-l
Venturi air-gas
gas entry
Canpressed airentry
t---Ja 0
1
O O---O 2 z
:y3.2y_OO=f=7
All dimensions in millimetres.
FIG. 3A BURNER
IS 1081Cj (Part 62) : 1993
682 I
‘Wenturi air-gas mixer
Compressed airentry
All dimensions in millimetres
FIG. 39 BURNERS
5.2 The burner should be fitted with an accurate means of controlling the input of fuel and air to the burner
(see Fig. 4). For the purpose of this~test the air shall have a dew point not higher than O°C and the input
should be 76.7 2 4.7 litres per minute, the LPG flow rate should be 9.56 + 0.5 litres per minute (see Note 1)
at one atmosphere and ambient temperature to provide a nominal 70 000 r 1 600 BTU/hour.
NOTES
‘1 Gross calorific value of LPG is 122 BTU/litre, required heat for the test is 70 000 BTU/hour, therefore, required LPG flow rate is:
20 000
- - 573.6 litres/hour
122
or
573.6
- = 9.56 litres/minute
60
The flow rate of LPG of 9.56 litres/minute is equivalent to the flow rate of 13.3 litres/minute of propane gas, in order to achieve heat
of 70 000 BTU/hour.
2 The calibration of the LPG rotameter should be checked after installation with a mass flow meter to ensure that the pipe work
and the venturi have not affected the calibration. Corrections for variations in temperature and pressure from that specified on the
LPG rotameter should be applied when necessary.
6
IS 10810 (Part 82) : 1993
h
Q
For lines to the flowmeter and pilot flame. I/4 inch or 8 mm outer diameter is suitable.
For air and propane to the burner 15 mm outer diameter is suitable.
Ignition transformer and a safety switch for the solenoid valve will complete the ciruitry.
KEY
a Propane input
b Air input
c Reducing tee-piece
d On/off valve
e Pressure regulator
f Filter
g Pressure gauge
h Control valve
r Flowmeters (rotameter type)
v solenoid valve
p Pilot line (optional)
FIG. 4 TYPICAL EXAMPLE OF GAS ‘rLOW CONTROLS
7
IS 10610 (Part 62) : 1993
6 Test Specimen
6.1 The specimen should comprise a number (IV) of pieces bf cable each 3.5 m long. The guidance for
calculation of N.is given in Annex A.
6.2 The total number of 3.5 m lengths of cable in the test sample should be in accordance with one of the
three categories as follows:
Category A - The number of cable lengths required to give a total volume of non-metallic material of 7
litres per metre.
Category B - The number of cable lengths required to give a total volume of non-metallic material of 3.5
litres per metre.
Category C - The number of cable lengths required to give a total volume of non-metallic material of 1.5
litres per metre.
Note -When calculating the number of cable lengths in the test sample, the values should be rounded to the nearest whole number.
7 Conditioning
7.1 The cables mounted on the ladder shall be conditioned at room temperature for 3 hours before
commencing the test. The chamber should be dry.
6 Procedure
8.1 Guidance on Cable Selection
The limited capacity of the ladder necessitates consideration of the cable size selected for testing to ensure
that the volume of non-metallic materiai may be accommodated within_the prescribed method of mounting.
For this purpose, four categories of mounting procedures have been prescribed. Their nomenclature are:
AF/R, AF, BF, CF
8.1.1 The following seledon criteria shall be applicable for cable size larger than 35 mm*.
8.1 .1-l Category AF/R
The size of cable selected shall not require more than thecapacity of 300 mm on each side of the ladder
width including half one cable diameter but not exceeding 20 mm space.
8.1 .I .2 Category AF
The size of cables selected shall not require more than the capacity of 600 mm of ladder width including half
one cable diameter but not exceeding 20 mm space.
8.1 -1.3 Category BF
The size of the cable selected shall not require more than the capacity of 300 mm of ladder with including
half one cable diameter but not exceeding 20 mm space.
8.1 .I .4 Category CF
The size of cable selected shall require at least 2 cables to be mounted.
8.1.2 For cable sizes equal to or smaller than 35 mm2 and also for telephone cables, there is no restriction
on conductor size selected for all the three categories of non-metallic material.
8.2 Method of Mounting the Test Sample
The method of mounting of test sample of all categories shall be as follows.
Volume Cable Size Category
7 Litre Up to 35 sq mm AF
Cab/e Arrangement
Volurne Cable Size Category
Above 35 sq mm AI=
3.5 litre Up to 35 sq mm
1.5 litre
Above 35 sq mm
Up to 35 sq mm
Above 35 sq mm
AF/R
BF
BF
CF
CF
IS 10810 (Part 62) : 1993
Cable Arrangement
- 4 1-112 d
Notes
1 All dimensions are in millimetres.
2 For samples of sizes up to 35 sq mm touching formation has been specified. While for cables of sizes above 35 sq mm, formation
with specifiedgap of l/2 of the diameter (CI)of single cable, not exceeding 20 mm is specified.
3 For arrangement of test samples on the ladder, see Fig. 5.
9
IS 10810 (Part 62) : 1993
Round steel
NngS 
Metal wire
ties --
Ce&e line
of ~bumer
*wP .roximate
t
,
I-
I-
,_
,
c,
-
All dimensions in mlllimetres.
FIG. 5. ARRANGEMENT OF TEST SAMPLE ON LADDER
8.2.1 Method of attachment
For cable having a conductor cross section exceeding 35 mm2, each cable is attached individually to each
10
IS 10810 (Part 82) : 1993
rung of the ladder by means of a metal wire between 0.5 and 1 .O mm diameter.
In all other cases, the same method is used whenever possible, for example, cables mounted in a single
layer, but in this case, the wires are placed obliquely across the layer.
If several layers are required to make up a bunch, the cables are attached in discrete bunches of a width
equal to 5 cables using the specified metal wire, each separate bunch being attached to that adjacent by the
outer cable pieces.
For consistency, especially for small diameter cables, for example, c 35 mm*, it is recommended that discrete
bunches touching are secured together at every rung.
8.2.2 Positioning of test specimen
For cables having a conductor cross-section not equal to or less than 35 mm*, the cables are placed touching
on the front of the ladder so as not to exceed 300 mm in width, there being~a minimum distance of 50 mm
between the edges of the bunched cables and the ladder uprights.
Cables, having conductor cross section greater than 35 mm*, are attached to the front of the ladder in a
single layer with a space between each cable of 0.5 x cable diameter by this space may not exceed 20 mm.
The gaps etween the ladder upright and the edge of the cable for different categories shall be as follows:
For categories AF and AF/R the gap between the ladder upright and the edge of the cable should
be atleast 100 mm. For category AF/R where the number of cable N, is such that the bunch width
exceeds 300 mm, the remaining cables are to be mounted on the rear of the ladder starting from
the centre.
For categories BF and CF the gap between the ladder upright and the edge of the cable is 50 mm.
8.3 Positioning of Ignition Source
The burner should be arranged horizontally at a distance of 75 * 5 mm from the front surface of the cable
sample and 600 f 5 mm above the floor of the test chamber. The poitit of application of the burner flame
should lie in the centre between two cross-bars on the tadder and at least 500 mm above the lower end of
the sample. When two burners are used in tandem, they shall be positioned as shown in Fig. 38.
8.4 Test Conditions
8.4.1 The test should not be carried~out if the external wind speed measured by an anemometer fitted on the
top of the test chamber is greater than 8 m/s, and if the temperature of the walls of the chamber is below 5°C
or above 40°C measured at a point 1 500 mm above floor level, 50 mm from a side wall and 100 mm from
the door. The cabin door shall be closed throughout the test.
8.4.2 The air flow to the chamber through the 800 z 20 mm x 400 + 10 mm aperture at the base, shall be
regulated at a constant rate of 5 + 0.5 m3/min at a constant controlled temperature of 20 t 10% These
measurements shall be monitored throughout the test and the air flow measurements close to the device
taken on the inlet side.
8.5 Time of Applicable of Flame
In the case of cable sample~in category A and category B, the test flame shall be applied for 40 minutes. The
cable samples in category C should have the test flame applied for 20 minutes.
8.6 After burning has ceased or after a maximum time of 1 h from the completion of the test flame period,
the flame shall be extinguished and the cable wiped clean.
All soot is to be.ignored if, when wiped off, the original surface is undamaged. Softening or any deformation
of the non-metallic material is also to be ignored. The extent of the damage is measured from the bottom
edge of the burner to the onset of char, which is defined as follows:
Press against the cable surface with a sharp object, where the surface changes from a resilient to a
brittle (crumbling) surface, indicates the onset of char.
9 Retest Procedure
9.1 Jn the case of doubt, two further tests shatt be undertaken as detailed in 8. The test shall be deemed to
be satisfactory, if both tests meet the requirements.
11
IS 10810 (Part 62) : 1993
10 Tabulation of Observation
Category of No. of Cab/e
Cable Length
Period of Application
of Flame
(Min)
Length of Affected
Portion
(4
11 Calculation
11.I No calculation is involved.
12 Report
Designation of Material Length of Affected Portion
(M)
12.1 Conclusion
Specimen meets/does not meet the requirements of the specification.
ANNEX A
(Clause 6.1)
NUMERICAL DETERMINATION OF TEST PIECES
A-l In order to calculate the number of test pieces, it is necessary to determine the volume per metre of
non-metallic material.
A-2 Acable sample, the length of which shall not be less than 0.3 m, is carefully cut to ensure that the surfaces
are at right angles to the cable axis, thus enabling precise measurements of the length L of the test piece.
A-3 Each non-metallic material Ci constituting more than 5 percent by weight of all non-metallic materials
shall be extracted from the test piece and weighed.
A-4 Where semi-conducting screen cannot be removed from the insulating material, the components may
be considered as one for the purposes of measuring their weight and density. In the case of non-metallic
tape the volume may be calculated from the geometrical dimensions in preference to weight and density.
A-5 The density of each non-metallic component shall be measured using relevant standard method. Fibrous
components (tapes or textiles) shall be assumed to have an effective density of unity.
A-6 The volume Vr ( litres per metre of cables ) of each non-metallic material Ci is calculated as follows:
Yy,----
PiX L
Mi being the mass of the component Ci (kg) and Pi being the density of the component Ci (kg/dm3).
A-7 The total volume V, of the non-metallic materials contained in one metre of cable is equal to the sum of
the individual volumes.
A-8 The number of test pieces to be mounted isobtained by dividing the volume per metre of the test category
specified in 6, by the total volume of non-metallic material per metre of cable.
EXPLANATORY NOTE
In preparing this standard, assistance has been derived from IEC Pub 332-2(1982) and its draft revision, IEC
Dot : 20(Sectt) 242.
Printed at New India Printing-Press, Khurja, India
12

More Related Content

What's hot

George hoetricks, evapco
George hoetricks, evapcoGeorge hoetricks, evapco
George hoetricks, evapcoSarah El Akkad
 
Ankersmid regulated heated line datasheet 0
Ankersmid regulated heated line datasheet 0Ankersmid regulated heated line datasheet 0
Ankersmid regulated heated line datasheet 0a1-cbiss
 
Sizing & Wiring a lab
Sizing & Wiring a labSizing & Wiring a lab
Sizing & Wiring a labguy mongeon
 
IRJET- Experimental Analysis of Circular Perforated Fin Arrays by Forced Conv...
IRJET- Experimental Analysis of Circular Perforated Fin Arrays by Forced Conv...IRJET- Experimental Analysis of Circular Perforated Fin Arrays by Forced Conv...
IRJET- Experimental Analysis of Circular Perforated Fin Arrays by Forced Conv...IRJET Journal
 
Industrial chimneys
Industrial chimneysIndustrial chimneys
Industrial chimneysManjunath Sn
 
Design Optimization and Development in Air Pollution Control Device
Design Optimization and Development in Air Pollution Control DeviceDesign Optimization and Development in Air Pollution Control Device
Design Optimization and Development in Air Pollution Control DeviceIJERA Editor
 
Flameproof High Range Pressure Switches without Scale FC series
Flameproof High Range Pressure Switches without Scale FC seriesFlameproof High Range Pressure Switches without Scale FC series
Flameproof High Range Pressure Switches without Scale FC seriesNK Instruments Pvt. Ltd.
 
Flameproof High Range Pressure Switches with Scale FC series
Flameproof High Range Pressure Switches with Scale FC seriesFlameproof High Range Pressure Switches with Scale FC series
Flameproof High Range Pressure Switches with Scale FC seriesNK Instruments Pvt. Ltd.
 
Chimney present
Chimney presentChimney present
Chimney presentmathusaran
 

What's hot (16)

A002
A002A002
A002
 
Chimney design
Chimney designChimney design
Chimney design
 
George hoetricks, evapco
George hoetricks, evapcoGeorge hoetricks, evapco
George hoetricks, evapco
 
Resistance temp sensors
Resistance temp sensorsResistance temp sensors
Resistance temp sensors
 
Ankersmid regulated heated line datasheet 0
Ankersmid regulated heated line datasheet 0Ankersmid regulated heated line datasheet 0
Ankersmid regulated heated line datasheet 0
 
COMPOSITE
COMPOSITECOMPOSITE
COMPOSITE
 
Sizing & Wiring a lab
Sizing & Wiring a labSizing & Wiring a lab
Sizing & Wiring a lab
 
IRJET- Experimental Analysis of Circular Perforated Fin Arrays by Forced Conv...
IRJET- Experimental Analysis of Circular Perforated Fin Arrays by Forced Conv...IRJET- Experimental Analysis of Circular Perforated Fin Arrays by Forced Conv...
IRJET- Experimental Analysis of Circular Perforated Fin Arrays by Forced Conv...
 
30120140505015 2
30120140505015 230120140505015 2
30120140505015 2
 
Industrial chimneys
Industrial chimneysIndustrial chimneys
Industrial chimneys
 
Design Optimization and Development in Air Pollution Control Device
Design Optimization and Development in Air Pollution Control DeviceDesign Optimization and Development in Air Pollution Control Device
Design Optimization and Development in Air Pollution Control Device
 
Flameproof High Range Pressure Switches without Scale FC series
Flameproof High Range Pressure Switches without Scale FC seriesFlameproof High Range Pressure Switches without Scale FC series
Flameproof High Range Pressure Switches without Scale FC series
 
Flameproof High Range Pressure Switches with Scale FC series
Flameproof High Range Pressure Switches with Scale FC seriesFlameproof High Range Pressure Switches with Scale FC series
Flameproof High Range Pressure Switches with Scale FC series
 
XL18 Series - L117-L217 Indicators
XL18 Series - L117-L217 IndicatorsXL18 Series - L117-L217 Indicators
XL18 Series - L117-L217 Indicators
 
Chimney present
Chimney presentChimney present
Chimney present
 
Insulation Resistance Test
Insulation Resistance TestInsulation Resistance Test
Insulation Resistance Test
 

Viewers also liked

Future Earth 8 June 2016
Future Earth 8 June 2016Future Earth 8 June 2016
Future Earth 8 June 2016Future Earth
 
Iter certification Estimator 2016_1
Iter certification Estimator 2016_1Iter certification Estimator 2016_1
Iter certification Estimator 2016_1pierdavide pitto
 
report kapile_fx7378
report kapile_fx7378report kapile_fx7378
report kapile_fx7378Parag Kapile
 
GSS capabilities
GSS capabilitiesGSS capabilities
GSS capabilitiesLisa A. F
 
KyleBates - Letter of Recommendation
KyleBates - Letter of RecommendationKyleBates - Letter of Recommendation
KyleBates - Letter of RecommendationKyle Bates
 
Vivir plenamente
Vivir plenamenteVivir plenamente
Vivir plenamenteAlain Ruiz
 
Les capteurs de l'Internet des Objets, par Jean-Samuel Chenard
Les capteurs de l'Internet des Objets, par Jean-Samuel ChenardLes capteurs de l'Internet des Objets, par Jean-Samuel Chenard
Les capteurs de l'Internet des Objets, par Jean-Samuel ChenardCleverToday
 
Apostila processamento de cereais
Apostila processamento de cereaisApostila processamento de cereais
Apostila processamento de cereaisEli Lima
 

Viewers also liked (19)

Edição serrano 141
Edição serrano 141Edição serrano 141
Edição serrano 141
 
Android
AndroidAndroid
Android
 
ESPN FC
ESPN FCESPN FC
ESPN FC
 
Future Earth 8 June 2016
Future Earth 8 June 2016Future Earth 8 June 2016
Future Earth 8 June 2016
 
2 is 5831
2 is 58312 is 5831
2 is 5831
 
Iter certification Estimator 2016_1
Iter certification Estimator 2016_1Iter certification Estimator 2016_1
Iter certification Estimator 2016_1
 
report kapile_fx7378
report kapile_fx7378report kapile_fx7378
report kapile_fx7378
 
GSS capabilities
GSS capabilitiesGSS capabilities
GSS capabilities
 
Is 694 amed 5
Is 694 amed 5Is 694 amed 5
Is 694 amed 5
 
KyleBates - Letter of Recommendation
KyleBates - Letter of RecommendationKyleBates - Letter of Recommendation
KyleBates - Letter of Recommendation
 
Vivir plenamente
Vivir plenamenteVivir plenamente
Vivir plenamente
 
Les capteurs de l'Internet des Objets, par Jean-Samuel Chenard
Les capteurs de l'Internet des Objets, par Jean-Samuel ChenardLes capteurs de l'Internet des Objets, par Jean-Samuel Chenard
Les capteurs de l'Internet des Objets, par Jean-Samuel Chenard
 
MWEB
MWEB MWEB
MWEB
 
The solar system
The solar systemThe solar system
The solar system
 
5 Slide Challange
5 Slide Challange5 Slide Challange
5 Slide Challange
 
ROBOTS
ROBOTSROBOTS
ROBOTS
 
Solar system
Solar systemSolar system
Solar system
 
Apostila processamento de cereais
Apostila processamento de cereaisApostila processamento de cereais
Apostila processamento de cereais
 
Preparo da Cana-de-açúcar
Preparo da Cana-de-açúcarPreparo da Cana-de-açúcar
Preparo da Cana-de-açúcar
 

Similar to 10810 62 (20)

Technical specification EEE
Technical specification EEETechnical specification EEE
Technical specification EEE
 
API 570 open book.pdf
API 570 open book.pdfAPI 570 open book.pdf
API 570 open book.pdf
 
AMAN PPT 4985 Assignment-1.pptx
AMAN PPT 4985 Assignment-1.pptxAMAN PPT 4985 Assignment-1.pptx
AMAN PPT 4985 Assignment-1.pptx
 
Bs 1881 122(1) 1983
Bs 1881 122(1) 1983Bs 1881 122(1) 1983
Bs 1881 122(1) 1983
 
3 is 694 pvc cables
3 is 694 pvc cables3 is 694 pvc cables
3 is 694 pvc cables
 
Design of pulse jet engine for UAV - 2
Design of pulse jet engine for UAV - 2Design of pulse jet engine for UAV - 2
Design of pulse jet engine for UAV - 2
 
API 570 B31.3 qustion.pdf
API 570 B31.3 qustion.pdfAPI 570 B31.3 qustion.pdf
API 570 B31.3 qustion.pdf
 
A study on IEC 60947- 2 amendments
A study on IEC 60947- 2 amendmentsA study on IEC 60947- 2 amendments
A study on IEC 60947- 2 amendments
 
torsion testing machine
 torsion testing machine torsion testing machine
torsion testing machine
 
Shyam cable catalogue
Shyam cable catalogueShyam cable catalogue
Shyam cable catalogue
 
IRJET-Enhancing the Performance of Hybrid Microgrid using non Isolated Single...
IRJET-Enhancing the Performance of Hybrid Microgrid using non Isolated Single...IRJET-Enhancing the Performance of Hybrid Microgrid using non Isolated Single...
IRJET-Enhancing the Performance of Hybrid Microgrid using non Isolated Single...
 
SERVICE MAINS.pdf
SERVICE MAINS.pdfSERVICE MAINS.pdf
SERVICE MAINS.pdf
 
Bs 1881 209 1990
Bs 1881 209 1990Bs 1881 209 1990
Bs 1881 209 1990
 
10334
1033410334
10334
 
3808
38083808
3808
 
A31
A31A31
A31
 
ASTM A789
ASTM A789ASTM A789
ASTM A789
 
Flex Brochure
Flex BrochureFlex Brochure
Flex Brochure
 
160512 160804-electrical machine design
160512 160804-electrical machine design160512 160804-electrical machine design
160512 160804-electrical machine design
 
-electrical machine design
-electrical machine design-electrical machine design
-electrical machine design
 

More from Samsher Singh

Is 3961 p 2 current rating for heavy duty pvc cable
Is 3961 p 2 current rating for heavy duty pvc cableIs 3961 p 2 current rating for heavy duty pvc cable
Is 3961 p 2 current rating for heavy duty pvc cableSamsher Singh
 
5 is 1554_2_pvc cables hd
5 is 1554_2_pvc cables hd5 is 1554_2_pvc cables hd
5 is 1554_2_pvc cables hdSamsher Singh
 
3 is_694_2010 newwwww
3  is_694_2010 newwwww3  is_694_2010 newwwww
3 is_694_2010 newwwwwSamsher Singh
 
10810 64 (temp index)
10810 64 (temp index)10810 64 (temp index)
10810 64 (temp index)Samsher Singh
 
10810 60 thermal stability
10810 60 thermal stability10810 60 thermal stability
10810 60 thermal stabilitySamsher Singh
 
Rdso vendor registration guideline
Rdso vendor registration guidelineRdso vendor registration guideline
Rdso vendor registration guidelineSamsher Singh
 

More from Samsher Singh (10)

Msds & ppe
Msds & ppeMsds & ppe
Msds & ppe
 
Is 3961 p 2 current rating for heavy duty pvc cable
Is 3961 p 2 current rating for heavy duty pvc cableIs 3961 p 2 current rating for heavy duty pvc cable
Is 3961 p 2 current rating for heavy duty pvc cable
 
5 is 1554_2_pvc cables hd
5 is 1554_2_pvc cables hd5 is 1554_2_pvc cables hd
5 is 1554_2_pvc cables hd
 
3 a 3975 - 1999
3 a 3975 - 19993 a 3975 - 1999
3 a 3975 - 1999
 
3 is_694_2010 newwwww
3  is_694_2010 newwwww3  is_694_2010 newwwww
3 is_694_2010 newwwww
 
1 is 8130
1 is 81301 is 8130
1 is 8130
 
10810 64 (temp index)
10810 64 (temp index)10810 64 (temp index)
10810 64 (temp index)
 
10810 60 thermal stability
10810 60 thermal stability10810 60 thermal stability
10810 60 thermal stability
 
10810 56
10810 5610810 56
10810 56
 
Rdso vendor registration guideline
Rdso vendor registration guidelineRdso vendor registration guideline
Rdso vendor registration guideline
 

Recently uploaded

Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01KreezheaRecto
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756dollysharma2066
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...SUHANI PANDEY
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesPrabhanshu Chaturvedi
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Bookingroncy bisnoi
 
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLPVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLManishPatel169454
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VDineshKumar4165
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 

Recently uploaded (20)

Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
NFPA 5000 2024 standard .
NFPA 5000 2024 standard                                  .NFPA 5000 2024 standard                                  .
NFPA 5000 2024 standard .
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and Properties
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
 
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLPVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 

10810 62

  • 1. UDC 621.315.21 : 620.193.5 IS 10810 (Part 82) : 1993 Indian Standard METHQD OF TESTS FOR CABLES PART 62 FLAME RETARDANCE TEST FOR BUNCHED CABLES I Scope I.1 This standard covers the method for testing of a bunch of cabks mounted vertically to determine their elative ability to resist flame propagation. I.2 This standard recommends three test categories, these being assessed by the amount of combustible non-metallic) material contained in one meter of bunched cables being tested. ! Significance 2.1 The propagation of flame along a bunch of cables depends on a number of features, such as: a) the volume of non-metallic material exposed to the fire and to any flame which may be produced by the combustion of the cables; b) the geometrical configuration of the cables and their relationship to any enclosure: c) the temperature at which it is possible to ignite gases emitted from the cables; d) the quality of combustible gas released from the cables for a given temperature rise; e) the volume of air passing through the cable installation; and 9 the construction of the cable, for example, armoured or unarmoured. 2.2 AH of the foregoing assume that the cables are able to be ignited ihen involved in an external fire. 2.3 The fire test should demonstrate that the bunched cables do not propagate fire even if its outer covering and insulation have been destroyed in the area of flame impingement. 2.4 The objective of the fire test should be to approximately simulate the installation condition and provide consistent results. 3 Terminology 3.1 Flame Retardance Bunched Cables The flame retardance bunched cables are those cables which do not propagate flame to the top of the cables after the flame source is removed and are self extitiguishing to prove their relative ability to resist fire propagation. 4 Test Apparatus 4.1 The test apparatus (see Fig. 1A) should comprise of vertical test chamber having a width of 1 000 * 100 mm, a depth of 2 000 9 100 mm and~lieight of 4 000 2100 mm and the floor of the chamber should be raised 150*10 mm above the ground level. The test chamber should be nominally airtight along its sides, air being admitted, without any substantial obstruction, at the base of the test chamber through an aperture of 8002 20 mm x 400 f 10 mm situated 150 +: 10 mm from the front wall of the test chamber. July 1993 6 BIS 1993 I Price Group 6 BUREAU OF INDIAN STANDARDS -MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG NEW DELHI 110002 1 ( Reaffirmed 1998 )
  • 2. IS 10810 (Part 82) : 1993 Smoke out&et (300 f 30) x (1 000 * 100) I Rig raised gbove groubd level All dimensions in millimetres. FIG. 1A FLAME TEST APPARATUS (RIG) 4.2 An outlet 300 2 5 mm x 1 000 f 10 mm should be made at the rear edge of the top of the test chamber. The back and sides of the test chamber should be thermally insulated to give a coefficient of heat transfer of approximately 0.7 W/ (M’K). For example, a steel plate 1.5 mm thick covered with 65 mm of mineral wool with a suitable external cladding is satisfactory (see Fig. 1B). The cables to be tested should be fixedma suitable steel ladder (see Fig. 2A or 28) mounted~within the test chamber such that the distance between the ladder and the rear wall of the chamber is 150 + 10 mm. 2
  • 3.
  • 4. IS 10810 (Part 62) : 1993 0 33.7 f 0.5 Diameter I-- of upright I I r=I I i o) II ! I 1 I II ‘I All dimensions in millimetres. FIG. 2A STANDARD TUBULAR LADDER FOR CABLE TEST li- 0 33.7 f 0.5 Diameter of upright Width 800 f 10 All dimensions in millimetres. FIG. 28 WIDE TUBULAR LAPDER FOR CABLE TEST 4
  • 5. IS 10810 (Part 62) : 1993 4.3 Smoke cleaning attachment, if used, should be such as to collect the smoke leaving the chamber but not cause a change in the air flow rate through the test chamber. 5 Ignition Source 5.1 The ignition source should be one or two ribbon type LPG burners whose flame producing surface consists of a flat metal plate 341 mm long and 30 mm wide through which 242 holes of 1.32 mm in diameter are drilled on 3.2 mm centres in three staggered rows of 81, 80 and 81 holes each to form an array having the nominal dimensions 257 mm x 4.5 mm as shown in Fig. 3Aand 36. As the burner plate may be drilled without the use of a drilling jig the spacing of the holes may vary slightly. Additionally, a row of small holes may be milled on each side of the burner plate to serve as pilot holes with the function ,of keeping the flame burning. 341 t-Y-l Venturi air-gas gas entry Canpressed airentry t---Ja 0 1 O O---O 2 z :y3.2y_OO=f=7 All dimensions in millimetres. FIG. 3A BURNER
  • 6. IS 1081Cj (Part 62) : 1993 682 I ‘Wenturi air-gas mixer Compressed airentry All dimensions in millimetres FIG. 39 BURNERS 5.2 The burner should be fitted with an accurate means of controlling the input of fuel and air to the burner (see Fig. 4). For the purpose of this~test the air shall have a dew point not higher than O°C and the input should be 76.7 2 4.7 litres per minute, the LPG flow rate should be 9.56 + 0.5 litres per minute (see Note 1) at one atmosphere and ambient temperature to provide a nominal 70 000 r 1 600 BTU/hour. NOTES ‘1 Gross calorific value of LPG is 122 BTU/litre, required heat for the test is 70 000 BTU/hour, therefore, required LPG flow rate is: 20 000 - - 573.6 litres/hour 122 or 573.6 - = 9.56 litres/minute 60 The flow rate of LPG of 9.56 litres/minute is equivalent to the flow rate of 13.3 litres/minute of propane gas, in order to achieve heat of 70 000 BTU/hour. 2 The calibration of the LPG rotameter should be checked after installation with a mass flow meter to ensure that the pipe work and the venturi have not affected the calibration. Corrections for variations in temperature and pressure from that specified on the LPG rotameter should be applied when necessary. 6
  • 7. IS 10810 (Part 82) : 1993 h Q For lines to the flowmeter and pilot flame. I/4 inch or 8 mm outer diameter is suitable. For air and propane to the burner 15 mm outer diameter is suitable. Ignition transformer and a safety switch for the solenoid valve will complete the ciruitry. KEY a Propane input b Air input c Reducing tee-piece d On/off valve e Pressure regulator f Filter g Pressure gauge h Control valve r Flowmeters (rotameter type) v solenoid valve p Pilot line (optional) FIG. 4 TYPICAL EXAMPLE OF GAS ‘rLOW CONTROLS 7
  • 8. IS 10610 (Part 62) : 1993 6 Test Specimen 6.1 The specimen should comprise a number (IV) of pieces bf cable each 3.5 m long. The guidance for calculation of N.is given in Annex A. 6.2 The total number of 3.5 m lengths of cable in the test sample should be in accordance with one of the three categories as follows: Category A - The number of cable lengths required to give a total volume of non-metallic material of 7 litres per metre. Category B - The number of cable lengths required to give a total volume of non-metallic material of 3.5 litres per metre. Category C - The number of cable lengths required to give a total volume of non-metallic material of 1.5 litres per metre. Note -When calculating the number of cable lengths in the test sample, the values should be rounded to the nearest whole number. 7 Conditioning 7.1 The cables mounted on the ladder shall be conditioned at room temperature for 3 hours before commencing the test. The chamber should be dry. 6 Procedure 8.1 Guidance on Cable Selection The limited capacity of the ladder necessitates consideration of the cable size selected for testing to ensure that the volume of non-metallic materiai may be accommodated within_the prescribed method of mounting. For this purpose, four categories of mounting procedures have been prescribed. Their nomenclature are: AF/R, AF, BF, CF 8.1.1 The following seledon criteria shall be applicable for cable size larger than 35 mm*. 8.1 .1-l Category AF/R The size of cable selected shall not require more than thecapacity of 300 mm on each side of the ladder width including half one cable diameter but not exceeding 20 mm space. 8.1 .I .2 Category AF The size of cables selected shall not require more than the capacity of 600 mm of ladder width including half one cable diameter but not exceeding 20 mm space. 8.1 -1.3 Category BF The size of the cable selected shall not require more than the capacity of 300 mm of ladder with including half one cable diameter but not exceeding 20 mm space. 8.1 .I .4 Category CF The size of cable selected shall require at least 2 cables to be mounted. 8.1.2 For cable sizes equal to or smaller than 35 mm2 and also for telephone cables, there is no restriction on conductor size selected for all the three categories of non-metallic material. 8.2 Method of Mounting the Test Sample The method of mounting of test sample of all categories shall be as follows. Volume Cable Size Category 7 Litre Up to 35 sq mm AF Cab/e Arrangement
  • 9. Volurne Cable Size Category Above 35 sq mm AI= 3.5 litre Up to 35 sq mm 1.5 litre Above 35 sq mm Up to 35 sq mm Above 35 sq mm AF/R BF BF CF CF IS 10810 (Part 62) : 1993 Cable Arrangement - 4 1-112 d Notes 1 All dimensions are in millimetres. 2 For samples of sizes up to 35 sq mm touching formation has been specified. While for cables of sizes above 35 sq mm, formation with specifiedgap of l/2 of the diameter (CI)of single cable, not exceeding 20 mm is specified. 3 For arrangement of test samples on the ladder, see Fig. 5. 9
  • 10. IS 10810 (Part 62) : 1993 Round steel NngS Metal wire ties -- Ce&e line of ~bumer *wP .roximate t , I- I- ,_ , c, - All dimensions in mlllimetres. FIG. 5. ARRANGEMENT OF TEST SAMPLE ON LADDER 8.2.1 Method of attachment For cable having a conductor cross section exceeding 35 mm2, each cable is attached individually to each 10
  • 11. IS 10810 (Part 82) : 1993 rung of the ladder by means of a metal wire between 0.5 and 1 .O mm diameter. In all other cases, the same method is used whenever possible, for example, cables mounted in a single layer, but in this case, the wires are placed obliquely across the layer. If several layers are required to make up a bunch, the cables are attached in discrete bunches of a width equal to 5 cables using the specified metal wire, each separate bunch being attached to that adjacent by the outer cable pieces. For consistency, especially for small diameter cables, for example, c 35 mm*, it is recommended that discrete bunches touching are secured together at every rung. 8.2.2 Positioning of test specimen For cables having a conductor cross-section not equal to or less than 35 mm*, the cables are placed touching on the front of the ladder so as not to exceed 300 mm in width, there being~a minimum distance of 50 mm between the edges of the bunched cables and the ladder uprights. Cables, having conductor cross section greater than 35 mm*, are attached to the front of the ladder in a single layer with a space between each cable of 0.5 x cable diameter by this space may not exceed 20 mm. The gaps etween the ladder upright and the edge of the cable for different categories shall be as follows: For categories AF and AF/R the gap between the ladder upright and the edge of the cable should be atleast 100 mm. For category AF/R where the number of cable N, is such that the bunch width exceeds 300 mm, the remaining cables are to be mounted on the rear of the ladder starting from the centre. For categories BF and CF the gap between the ladder upright and the edge of the cable is 50 mm. 8.3 Positioning of Ignition Source The burner should be arranged horizontally at a distance of 75 * 5 mm from the front surface of the cable sample and 600 f 5 mm above the floor of the test chamber. The poitit of application of the burner flame should lie in the centre between two cross-bars on the tadder and at least 500 mm above the lower end of the sample. When two burners are used in tandem, they shall be positioned as shown in Fig. 38. 8.4 Test Conditions 8.4.1 The test should not be carried~out if the external wind speed measured by an anemometer fitted on the top of the test chamber is greater than 8 m/s, and if the temperature of the walls of the chamber is below 5°C or above 40°C measured at a point 1 500 mm above floor level, 50 mm from a side wall and 100 mm from the door. The cabin door shall be closed throughout the test. 8.4.2 The air flow to the chamber through the 800 z 20 mm x 400 + 10 mm aperture at the base, shall be regulated at a constant rate of 5 + 0.5 m3/min at a constant controlled temperature of 20 t 10% These measurements shall be monitored throughout the test and the air flow measurements close to the device taken on the inlet side. 8.5 Time of Applicable of Flame In the case of cable sample~in category A and category B, the test flame shall be applied for 40 minutes. The cable samples in category C should have the test flame applied for 20 minutes. 8.6 After burning has ceased or after a maximum time of 1 h from the completion of the test flame period, the flame shall be extinguished and the cable wiped clean. All soot is to be.ignored if, when wiped off, the original surface is undamaged. Softening or any deformation of the non-metallic material is also to be ignored. The extent of the damage is measured from the bottom edge of the burner to the onset of char, which is defined as follows: Press against the cable surface with a sharp object, where the surface changes from a resilient to a brittle (crumbling) surface, indicates the onset of char. 9 Retest Procedure 9.1 Jn the case of doubt, two further tests shatt be undertaken as detailed in 8. The test shall be deemed to be satisfactory, if both tests meet the requirements. 11
  • 12. IS 10810 (Part 62) : 1993 10 Tabulation of Observation Category of No. of Cab/e Cable Length Period of Application of Flame (Min) Length of Affected Portion (4 11 Calculation 11.I No calculation is involved. 12 Report Designation of Material Length of Affected Portion (M) 12.1 Conclusion Specimen meets/does not meet the requirements of the specification. ANNEX A (Clause 6.1) NUMERICAL DETERMINATION OF TEST PIECES A-l In order to calculate the number of test pieces, it is necessary to determine the volume per metre of non-metallic material. A-2 Acable sample, the length of which shall not be less than 0.3 m, is carefully cut to ensure that the surfaces are at right angles to the cable axis, thus enabling precise measurements of the length L of the test piece. A-3 Each non-metallic material Ci constituting more than 5 percent by weight of all non-metallic materials shall be extracted from the test piece and weighed. A-4 Where semi-conducting screen cannot be removed from the insulating material, the components may be considered as one for the purposes of measuring their weight and density. In the case of non-metallic tape the volume may be calculated from the geometrical dimensions in preference to weight and density. A-5 The density of each non-metallic component shall be measured using relevant standard method. Fibrous components (tapes or textiles) shall be assumed to have an effective density of unity. A-6 The volume Vr ( litres per metre of cables ) of each non-metallic material Ci is calculated as follows: Yy,---- PiX L Mi being the mass of the component Ci (kg) and Pi being the density of the component Ci (kg/dm3). A-7 The total volume V, of the non-metallic materials contained in one metre of cable is equal to the sum of the individual volumes. A-8 The number of test pieces to be mounted isobtained by dividing the volume per metre of the test category specified in 6, by the total volume of non-metallic material per metre of cable. EXPLANATORY NOTE In preparing this standard, assistance has been derived from IEC Pub 332-2(1982) and its draft revision, IEC Dot : 20(Sectt) 242. Printed at New India Printing-Press, Khurja, India 12