3. • A scalar quantity that determines the direction of heat flow
between two bodies
• A statistical measurement
. Temperature measurement relies on the transfer of heat
energy from the process material to the measuring device
• Temperature is an important parameter in many control
systems
• These include non electrical as well as electrical methods
• A thermometer is the most common non electrical sensor
5. • Thermocouples operate under the
principle that the junction of two
dissimilar metals produces a
measurable voltage (emf-
electromotive force) when the
two ends of the thermocouple are
at different temperatures.
• Most thermocouple metals
produce a relationship between
the two temperatures and the
E.M.F. as follows: e = a(T1 – T2)
+b(T12 – T22)
• e is the e.m.f, a and b are
constants for the thermocouple, T1
and T2 are the temperatures. The
relationship is nearly linear over
the operating range
Display
Device
+
-
A
B
Reference
Junction
Measuring Junction
6. GOVERNING EFFECTS
The three main principles that
governs the operation of
thermocouple are
SEEBECK EFFECT
PELTIER EFFECT
THOMSON EFFECT
SEEBECK EFECT
The Seebeck effect states that when
two different or unlike metals are joined
together at two junctions, an
electromotive force (emf) is generated
at the two junctions.The amount of emf
generated is different for different
combinations of the metals.
7. PELTIER EFFECT
• As per the Peltier effect, when two
dissimilar metals are joined together to
form two junctions, emf is generated
within the circuit due to the different
temperatures of the two junctions of the
circuit
• THOMSON EFFECT
• As per theThomson effect, when two
unlike metals are joined together forming
two junctions, the potential exists within
the circuit due to temperature gradient
along the entire length of the conductors
within the circuit.
8. • Thermocouples are designated as classes such
as type E, K, J, N, orT based on the
composition of the two materials used to form
the junction. Each type has a different
temperature range/voltage response curve.
• Chromel-Alumel (K TYPE)
• The Chromel-Alumel thermocouple, with a
positive Chromel wire and a negative Alumel
wire, is recommended for use in clean oxidizing
atmospheres. The operating range for this alloy is
1260ºC for the largest wire sizes. Smaller wires
should operate in correspondingly lower
temperatures.
• Iron-Constantan (J TYPE)
• The Iron-Constantan thermocouple with a positive
iron wire and a negative Constantan wire is
recommended for reducing atmospheres. The
operating range for this alloy combination is
870ºC for the largest wire sizes. Smaller wire
sizes should operate in correspondingly lower
temperatures
9. • TYPE E (chromel – constantan)
• it is non-magnetic.
• Wide range is −50 °C to +740 °C and
Narrow range is −110 °C to +140 °C.
• This Thermocouple has the highest EMF
output per degree of all recognized
thermocouples.
• If the temperature is between 316 to
593°C, (600 to 1100°F) type J or N is
recommend because of aging which can
cause drift of 1 to 2°C, (2 to 4°F) in a few
hours time.
• TYPE M
• Type M (Ni/Mo 82%/18% – Ni/Co
99.2%/0.8%, by weight) are used in
vacuum furnaces.
• Upper temperature is limited to 1400 °C. It
is less commonly used than other types.
10. TYPE N
Type N (Nicrosil – Nisil) thermocouples are suitable for use
between −270 °C and +1300 °C owing to its stability and oxidation
resistance.
Sensitivity is about 39 µV/°C at 900 °C, slightly lower compared
to type K.
The Nicrosil and Nisil thermocouple alloys show greatly
enhanced thermoelectric stability relative to the other standard
base-metal thermocouple alloys because their compositions
substantially reduce the thermoelectric instabilities.
TYPE S
Type S thermocouples (Pt/Rh 90%/10% – Pt, by weight), similar
to type R, are used up to 1600 °C.
Before the introduction of the International Temperature
Scale of 1990 (ITS-90), precision type S thermocouples were
used as the practical standard thermometers for the range of
630 °C to 1064 °C, based on an interpolation between the
freezing points of antimony, silver, and gold.
Starting with ITS-90, platinum resistance thermometers have
taken over this range as standard thermometers
11.
12.
13.
14. • Ungrounded: Electrical
isolation is obtained at the cost
of response time.
• Grounded : Good heat transfer
to junction.
• Exposed : Best response time,
but is limited to noncorrosive
and non-pressurized
applications.
15. Grade is based on calibration accuracy of the wire.
• Precision grade - (± 0.5 % reading or 1°C) , greater of the two
• Standard grade -(± 0.75 % reading or 2°C), greater of the two
• Extension or Lead-wire grade - (± 1 % reading or 4 °C)
Wire diameter
• 0.001 inches and up is possible
• Standard diameters are: 0.01”, 0.02”, 0.032”, 0.040”, 1/16”, 1/8”,
3/16”, and 1/4”
• Smaller the better but fragility is an issue
16. • Thermopile-Thermocouples
connected in series between two
temperature zones.
• Good for determining small
temperature differences
• Amplification affect
• Averaging Circuit- Thermocouple
are connected in parallel between
two temperature zones.
17.
18. • If a thermocouple circuit
develops a net emf1-2 for
measuring junction temperatures
T1 and T2,
• and a net emf2-3 for temperatures
T2 and T3,
• then it will develop a net voltage
of
• emf1-3 = emf1-2 + emf2-3
• when the junctions are at
temperatures T1 and T3.
emf1-2+ emf2-3= emf1-3
T2
T3 T1
T3 T2
T1
20. • Failed = inaccuracy
- When wires are heated/cooled changes take place on
molecular level
Physically: molecular structure changes
Chemically: wires react with oxygen or other substances, changing
chemical composition
- Result: millivolt signal “drifts”
Time
EMF
(mV)
Tolerance Band
- Recalibration: adjust controller to compensate for errors
21. • 3 General constructions
Insulated Wire
Ceramic-beaded
Metal-sheathed
22. • Bare wires wrapped with insulation
• Insulations
• Fibrous, woven material made of fiber-
glass, mica, or ceramic fiber
• Plastics (Teflon)
• Polyimides (Kapton)
• Purpose
• Electrically isolate wires
• Protects wires from contamination
• Easier wire installation
23. • Junction and wires are assembled in small diameter
metal tubes
• Insulation
• Fiberglass
• MgO
• Purpose
• Protects against contamination
• Defends against chemical attack
• Provides mechanical stability
24. Simple, Rugged
High temperature
operation
Low cost
No resistance lead wire
problems
Point temperature
sensing
Fastest response to
temperature changes
Least stable, least
repeatable
Low sensitivity to small
temperature changes
Extension wire must be
of the same
thermocouple type
Wire may pick up
radiated electrical noise
if not shielded
Lowest accuracy
Advantages Disadvantages