FIRE DAMPER INSTALLATION
Mohammed Mukaram Jah,
Mechanical Engineer
mukarram169@rediffmail.com
+91 9701 99 3862
1
CONTENTS
 FIRE DAMPER AND ITS SIGNIFICANCE
 FIRE RESISTANCE RATING
 WHERE FIRE DAMPERS ARE REQUIRED
 APPROVED INSTALLATION
 IMPROPER INSTALLATION
2
Fire Damper and its Significance
Fire Damper is a device installed in an air distribution system, designed to close automatically upon
detection of heat to interrupt migratory airflow and to restrict the passage of flame(NFPA 90A).
This is accomplished only when these dampers are installed in accordance with SMACNA Fire, Smoke
and Radiation Dampers Installation Guide.
Fire Resistance
The time in minutes and Hours, that materials or assemblies have withstood a fire exposure as
established in accordance with the test procedures of NFPA 251, Standards Methods of tests of fire
Endurance of building construction and Materials(NFPA 90A).
Where Fire Dampers are Required ??
• Fire Dampers are required wherever fire resistance integrity of the wall is to be maintained.
• Required wherever there is duct penetration either through fire rated wall or fire rated roof.
3
APPROVED INSTALLATION:
Fire and Smoke dampers shall be manufactured and installed as per the latest issue of
SMACNA “ Fire, Smoke and Radiation dampers installation guide.”
As per SMACNA below are the important items to be considered for installation.
A. Retaining Angle
B. Expansion Space
C. Damper Sleeve
D. Fire Damper
E. Retaining Angle fastened to sleeve
F. Damper attachment to sleeve
G. Connection to Duct
Below is the picture depicting above items in the installation of fire damper.
4
5
6
A. Retaining Angle :
• Retaining Angles shall be secured to sleeve on 8” centers and shall not be fixed to walls.
• Retaining angles shall overlap the structure opening 1” minimum and cover corner opening.
• Retaining angle shall be minimum of 1½” x 1½” x 16 gauge(40 x 40 x 1.6mm). However some
manufacturers may allow lower gauge for small size and may require heavier gauge for larger ducts.
B. Expansion Space :
• The annular space/clearance between fire damper sleeve and wall/roof opening is termed as
expansion space.
• This clearance shall be minimum 1/8” per linear foot(10mm per liner meter) of width and height
unless otherwise stated in the listing of the assembly.
• Sleeve may rest on the bottom of the opening and need not be centered(SMACNA)
7
C. Damper Sleeve : By UL 555, ducts are to be terminated at fire damper sleeves or damper frames.
Sleeve thickness depends on the type of connection as per below table.
.
Sleeves may be omitted on certain alternative damper arrangements that are in compliance with UL
555, Standard for Fire Dampers. The damper manufacturers Installations and Operating Instructions
shall state whether sleeves may be omitted
8
D. Fire Damper :
Fire dampers shall bear a label from a recognized testing laboratory (such as UL) or be tested in
accordance with the requirements of Uniform Building Code, UBC STD 43-7.
Note: Whether Fire Damper or Combination Fire/Smoke Damper is UL listed or not can be determined
from UL web page. Please visit UL site at WWW.UL.COM. You need to check and make sure that the
supplied model is listed. Also check for size, position, System type and rating of the supplied
dampers.
E. Retaining Angle Fastened to Sleeve
Secure retaining angles to sleeve ONLY on 8” centers (203mm) with
a. ½ “(12mm) long weld
b. ¼”(6mm) nut and bolts
c. No. 10 sheet metal screws
d. Minimum 3/16”(5mm) steel rivets
Note : The size and spacing requirements may differ by damper manufacturer. Consult manufacturer
installations for specifications.
9
F. Damper attachment to sleeve
Secure damper to sleeve on 8” centers with
a. ½” (12mm) long weld
b. ¼”(6mm) nut and bolts
c. No. 10 sheet metal screws
d. Minimum 3/16”(5mm) steel rivets
G. Connection to Duct
Fire dampers shall be securely mounted in rated fire separation wall, ceiling or floor, such that
ducts can break away without lessening fire separation rating. So type of duct connection to
Fire Damper sleeve shall be breakaway connection.
1. Above figure shows the Duct Sleeve connection listed in UL 555
2. Additional Duct –Sleeve connections were tested by SMACNA and witnessed by UL.. They
are
a). TDC AND TDF Roll Formed 4-Bolt flanged connections assembled as per the
manufacturer instructions using Gaskets, metal cleats and four 3/8” metal nuts and
bolts.
10
b). Manufactured slip on 4-Bolt flanged connections assembled as per manufacturer
instructions using Gaskets and Plastic Cleats.
H. Access Door :
Install access door shall be installed as shown in figure.
Access doors shall be maximum of 24”x24” and a minimum of 6”x 6”(SMACNA).
Access doors (points) shall be identified by a label with letters not less than ½” (13 mm) in
height reading FIRE DAMPER (UMC Para 605.5).
11
IMPROPER INSTALLATION
Figure below shows two main improper installations encountered as per SMACNA.
12
Item 1:
Sealing of the fire damper retaining angles is not a requirement of an approved damper installation
If the local authority having jurisdiction mandates that the angles be sealed, contractors should
issue a Request For Information (RFI) to design professionals such that the proper approved sealants
be used. In no case should the retaining angles be sealed with any product not approved by the
damper manufacturer including Through Penetration Fire stop products. Using unapproved
products could be a violation of the damper manufacturer’s conditions of test and listing, could
void the UL listing of the damper and could render the damper inoperable
Item 2:
Introduction of any materials including mineral wool, ceramic fiber or sealants of any kind into the
required expansion space between the damper sleeve and fire partition has not been tested, has
not been approved, and is not permitted by damper manufacturers. Doing so could be a violation
of the manufacturer’s conditions of test and listing, could void the UL listing of the damper and
could render the damper inoperable. Indiscriminate and unnecessary deviations from standard fire
damper installations should be avoided. Unless a deviation is specifically approved by the damper
manufacturer, it could compromise the function for which the damper was ultimately installed.
13
Below is the pictures showing improper installation in one project.
14
VERTICAL FIRE DAMPER INSTALLATION
15
HORIZONTAL FIRE DAMPER INSTALLATION
16
THANK YOU

More Related Content

What's hot

NFPA 96: A Guide for Commercial Kitchen Safety
NFPA 96: A Guide for Commercial Kitchen SafetyNFPA 96: A Guide for Commercial Kitchen Safety
NFPA 96: A Guide for Commercial Kitchen SafetyPerformance Industrial
 
Fire fighting system in buildings
Fire fighting system  in buildingsFire fighting system  in buildings
Fire fighting system in buildingsHetvi Trada
 
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPTFIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPTMEP ENGINEER'S SERVICES
 
Fire sprinkler systems read thoroughly
Fire sprinkler systems read thoroughlyFire sprinkler systems read thoroughly
Fire sprinkler systems read thoroughlyMuhammad Muhyuddin
 
HVAC Systems- A Complete Guide
HVAC Systems- A Complete GuideHVAC Systems- A Complete Guide
HVAC Systems- A Complete GuideFordly
 
Basic training water based fire protection
Basic training  water based fire protectionBasic training  water based fire protection
Basic training water based fire protectionSabrul Jamil
 
Smoke extraction in buildings
Smoke extraction in buildingsSmoke extraction in buildings
Smoke extraction in buildingsvysakhmanohar
 
Active and passive fire protection system
Active and passive fire protection systemActive and passive fire protection system
Active and passive fire protection systemKamran Hassan
 
Fire fighting system
Fire fighting systemFire fighting system
Fire fighting systemAmit Kumar
 
Fire protection system
Fire protection systemFire protection system
Fire protection systemDeepak Thapa
 
Quality HVAC Installation Made Easy
Quality HVAC Installation Made EasyQuality HVAC Installation Made Easy
Quality HVAC Installation Made EasyERH West
 
How to Maintain Fire Protection System
How to Maintain Fire Protection SystemHow to Maintain Fire Protection System
How to Maintain Fire Protection Systemzesslindia
 
Fully calculated firefighting systems with EN 12845 standard
Fully calculated firefighting systems with EN 12845 standardFully calculated firefighting systems with EN 12845 standard
Fully calculated firefighting systems with EN 12845 standardIsidoros Siderakis
 
Smoke Control in Buildings
Smoke Control in BuildingsSmoke Control in Buildings
Smoke Control in BuildingsIllinois ASHRAE
 
FIRE FIGHTING PRESENTATION
FIRE FIGHTING PRESENTATIONFIRE FIGHTING PRESENTATION
FIRE FIGHTING PRESENTATIONASGHAR KHALIL
 

What's hot (20)

NFPA 96: A Guide for Commercial Kitchen Safety
NFPA 96: A Guide for Commercial Kitchen SafetyNFPA 96: A Guide for Commercial Kitchen Safety
NFPA 96: A Guide for Commercial Kitchen Safety
 
Fire fighting system in buildings
Fire fighting system  in buildingsFire fighting system  in buildings
Fire fighting system in buildings
 
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPTFIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
 
Fire sprinkler systems read thoroughly
Fire sprinkler systems read thoroughlyFire sprinkler systems read thoroughly
Fire sprinkler systems read thoroughly
 
HVAC Systems- A Complete Guide
HVAC Systems- A Complete GuideHVAC Systems- A Complete Guide
HVAC Systems- A Complete Guide
 
Presentation mechanical car parking ventilation system
Presentation mechanical car parking ventilation systemPresentation mechanical car parking ventilation system
Presentation mechanical car parking ventilation system
 
ASHRAE62.1-2019.pdf
ASHRAE62.1-2019.pdfASHRAE62.1-2019.pdf
ASHRAE62.1-2019.pdf
 
Basic training water based fire protection
Basic training  water based fire protectionBasic training  water based fire protection
Basic training water based fire protection
 
MEP & Construction Package
MEP & Construction PackageMEP & Construction Package
MEP & Construction Package
 
Smoke extraction in buildings
Smoke extraction in buildingsSmoke extraction in buildings
Smoke extraction in buildings
 
Active and passive fire protection system
Active and passive fire protection systemActive and passive fire protection system
Active and passive fire protection system
 
Fire fighting system
Fire fighting systemFire fighting system
Fire fighting system
 
Fire protection system
Fire protection systemFire protection system
Fire protection system
 
Quality HVAC Installation Made Easy
Quality HVAC Installation Made EasyQuality HVAC Installation Made Easy
Quality HVAC Installation Made Easy
 
How to Maintain Fire Protection System
How to Maintain Fire Protection SystemHow to Maintain Fire Protection System
How to Maintain Fire Protection System
 
Fire fighting system
Fire fighting systemFire fighting system
Fire fighting system
 
Fully calculated firefighting systems with EN 12845 standard
Fully calculated firefighting systems with EN 12845 standardFully calculated firefighting systems with EN 12845 standard
Fully calculated firefighting systems with EN 12845 standard
 
fire hydrant system .pptx
fire hydrant system .pptxfire hydrant system .pptx
fire hydrant system .pptx
 
Smoke Control in Buildings
Smoke Control in BuildingsSmoke Control in Buildings
Smoke Control in Buildings
 
FIRE FIGHTING PRESENTATION
FIRE FIGHTING PRESENTATIONFIRE FIGHTING PRESENTATION
FIRE FIGHTING PRESENTATION
 

Similar to Fire dampers installation

Prima Smooth flue system installation instructions
Prima Smooth flue system installation instructionsPrima Smooth flue system installation instructions
Prima Smooth flue system installation instructionsSchiedel UK
 
2.-Deflagration-Flame-Arrester-In-Line.pdf
2.-Deflagration-Flame-Arrester-In-Line.pdf2.-Deflagration-Flame-Arrester-In-Line.pdf
2.-Deflagration-Flame-Arrester-In-Line.pdfssuser9ddbb1
 
Prima Plus flue system installation instructions
Prima Plus flue system installation instructionsPrima Plus flue system installation instructions
Prima Plus flue system installation instructionsSchiedel UK
 
Defender smokehalt - V automatic overhead coiling fabric smoke curtain
Defender smokehalt - V automatic overhead coiling fabric smoke curtainDefender smokehalt - V automatic overhead coiling fabric smoke curtain
Defender smokehalt - V automatic overhead coiling fabric smoke curtainlyndaflintof
 
Flexible Liners installation instructions
Flexible Liners installation instructionsFlexible Liners installation instructions
Flexible Liners installation instructionsSchiedel UK
 
Sargas Stove System Brochure
Sargas Stove System Brochure Sargas Stove System Brochure
Sargas Stove System Brochure Schiedel UK
 
ICS flue system installation instructions
ICS flue system installation instructionsICS flue system installation instructions
ICS flue system installation instructionsSchiedel UK
 
Wylex nmfs intumescent
Wylex nmfs intumescentWylex nmfs intumescent
Wylex nmfs intumescentDarren Garbett
 
Isokern Celsius stove system installation instructions
Isokern Celsius stove system installation instructionsIsokern Celsius stove system installation instructions
Isokern Celsius stove system installation instructionsSchiedel UK
 
Blazemaster Fire Protection System Residential Brochure
Blazemaster Fire Protection System Residential BrochureBlazemaster Fire Protection System Residential Brochure
Blazemaster Fire Protection System Residential BrochurePoojaShetty87
 
8.0 Installation of Ceiling Batts.pdf
8.0 Installation of Ceiling Batts.pdf8.0 Installation of Ceiling Batts.pdf
8.0 Installation of Ceiling Batts.pdfInsulation2
 
Gas Installation Guidelines for Designers and Builders - Domestic Sites
Gas Installation Guidelines for Designers and Builders - Domestic SitesGas Installation Guidelines for Designers and Builders - Domestic Sites
Gas Installation Guidelines for Designers and Builders - Domestic SitesGas Networks Ireland
 
9.0 Installation of Wall Batts.pdf
9.0 Installation of Wall Batts.pdf9.0 Installation of Wall Batts.pdf
9.0 Installation of Wall Batts.pdfInsulation2
 
ICS 5000 commercial flue system instructions
ICS 5000 commercial flue system instructionsICS 5000 commercial flue system instructions
ICS 5000 commercial flue system instructionsSchiedel UK
 
CMP Cable Glands - Triton T3CDS Deluge Proof Glands (ATEX)
CMP Cable Glands - Triton T3CDS Deluge Proof Glands (ATEX)CMP Cable Glands - Triton T3CDS Deluge Proof Glands (ATEX)
CMP Cable Glands - Triton T3CDS Deluge Proof Glands (ATEX)Thorne & Derrick International
 
Protection of Curtained Limited Finishing Workstations using Ul 1254 Listed P...
Protection of Curtained Limited Finishing Workstations using Ul 1254 Listed P...Protection of Curtained Limited Finishing Workstations using Ul 1254 Listed P...
Protection of Curtained Limited Finishing Workstations using Ul 1254 Listed P...Fire Equipment Manufacturers' Association
 

Similar to Fire dampers installation (20)

Prima Smooth flue system installation instructions
Prima Smooth flue system installation instructionsPrima Smooth flue system installation instructions
Prima Smooth flue system installation instructions
 
2.-Deflagration-Flame-Arrester-In-Line.pdf
2.-Deflagration-Flame-Arrester-In-Line.pdf2.-Deflagration-Flame-Arrester-In-Line.pdf
2.-Deflagration-Flame-Arrester-In-Line.pdf
 
Prima Plus flue system installation instructions
Prima Plus flue system installation instructionsPrima Plus flue system installation instructions
Prima Plus flue system installation instructions
 
Defender smokehalt - V automatic overhead coiling fabric smoke curtain
Defender smokehalt - V automatic overhead coiling fabric smoke curtainDefender smokehalt - V automatic overhead coiling fabric smoke curtain
Defender smokehalt - V automatic overhead coiling fabric smoke curtain
 
Flexible Liners installation instructions
Flexible Liners installation instructionsFlexible Liners installation instructions
Flexible Liners installation instructions
 
Sargas Stove System Brochure
Sargas Stove System Brochure Sargas Stove System Brochure
Sargas Stove System Brochure
 
3M Interam Endothermic Mat E-5A-4
3M Interam Endothermic Mat E-5A-43M Interam Endothermic Mat E-5A-4
3M Interam Endothermic Mat E-5A-4
 
Fire smokedampers
Fire smokedampersFire smokedampers
Fire smokedampers
 
Flex Brochure
Flex BrochureFlex Brochure
Flex Brochure
 
ICS flue system installation instructions
ICS flue system installation instructionsICS flue system installation instructions
ICS flue system installation instructions
 
Duct opening protectives 2017
Duct opening protectives 2017Duct opening protectives 2017
Duct opening protectives 2017
 
Wylex nmfs intumescent
Wylex nmfs intumescentWylex nmfs intumescent
Wylex nmfs intumescent
 
Isokern Celsius stove system installation instructions
Isokern Celsius stove system installation instructionsIsokern Celsius stove system installation instructions
Isokern Celsius stove system installation instructions
 
Blazemaster Fire Protection System Residential Brochure
Blazemaster Fire Protection System Residential BrochureBlazemaster Fire Protection System Residential Brochure
Blazemaster Fire Protection System Residential Brochure
 
8.0 Installation of Ceiling Batts.pdf
8.0 Installation of Ceiling Batts.pdf8.0 Installation of Ceiling Batts.pdf
8.0 Installation of Ceiling Batts.pdf
 
Gas Installation Guidelines for Designers and Builders - Domestic Sites
Gas Installation Guidelines for Designers and Builders - Domestic SitesGas Installation Guidelines for Designers and Builders - Domestic Sites
Gas Installation Guidelines for Designers and Builders - Domestic Sites
 
9.0 Installation of Wall Batts.pdf
9.0 Installation of Wall Batts.pdf9.0 Installation of Wall Batts.pdf
9.0 Installation of Wall Batts.pdf
 
ICS 5000 commercial flue system instructions
ICS 5000 commercial flue system instructionsICS 5000 commercial flue system instructions
ICS 5000 commercial flue system instructions
 
CMP Cable Glands - Triton T3CDS Deluge Proof Glands (ATEX)
CMP Cable Glands - Triton T3CDS Deluge Proof Glands (ATEX)CMP Cable Glands - Triton T3CDS Deluge Proof Glands (ATEX)
CMP Cable Glands - Triton T3CDS Deluge Proof Glands (ATEX)
 
Protection of Curtained Limited Finishing Workstations using Ul 1254 Listed P...
Protection of Curtained Limited Finishing Workstations using Ul 1254 Listed P...Protection of Curtained Limited Finishing Workstations using Ul 1254 Listed P...
Protection of Curtained Limited Finishing Workstations using Ul 1254 Listed P...
 

Recently uploaded

High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and usesDevarapalliHaritha
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 

Recently uploaded (20)

High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and uses
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 

Fire dampers installation

  • 1. FIRE DAMPER INSTALLATION Mohammed Mukaram Jah, Mechanical Engineer mukarram169@rediffmail.com +91 9701 99 3862 1
  • 2. CONTENTS  FIRE DAMPER AND ITS SIGNIFICANCE  FIRE RESISTANCE RATING  WHERE FIRE DAMPERS ARE REQUIRED  APPROVED INSTALLATION  IMPROPER INSTALLATION 2
  • 3. Fire Damper and its Significance Fire Damper is a device installed in an air distribution system, designed to close automatically upon detection of heat to interrupt migratory airflow and to restrict the passage of flame(NFPA 90A). This is accomplished only when these dampers are installed in accordance with SMACNA Fire, Smoke and Radiation Dampers Installation Guide. Fire Resistance The time in minutes and Hours, that materials or assemblies have withstood a fire exposure as established in accordance with the test procedures of NFPA 251, Standards Methods of tests of fire Endurance of building construction and Materials(NFPA 90A). Where Fire Dampers are Required ?? • Fire Dampers are required wherever fire resistance integrity of the wall is to be maintained. • Required wherever there is duct penetration either through fire rated wall or fire rated roof. 3
  • 4. APPROVED INSTALLATION: Fire and Smoke dampers shall be manufactured and installed as per the latest issue of SMACNA “ Fire, Smoke and Radiation dampers installation guide.” As per SMACNA below are the important items to be considered for installation. A. Retaining Angle B. Expansion Space C. Damper Sleeve D. Fire Damper E. Retaining Angle fastened to sleeve F. Damper attachment to sleeve G. Connection to Duct Below is the picture depicting above items in the installation of fire damper. 4
  • 5. 5
  • 6. 6 A. Retaining Angle : • Retaining Angles shall be secured to sleeve on 8” centers and shall not be fixed to walls. • Retaining angles shall overlap the structure opening 1” minimum and cover corner opening. • Retaining angle shall be minimum of 1½” x 1½” x 16 gauge(40 x 40 x 1.6mm). However some manufacturers may allow lower gauge for small size and may require heavier gauge for larger ducts. B. Expansion Space : • The annular space/clearance between fire damper sleeve and wall/roof opening is termed as expansion space. • This clearance shall be minimum 1/8” per linear foot(10mm per liner meter) of width and height unless otherwise stated in the listing of the assembly. • Sleeve may rest on the bottom of the opening and need not be centered(SMACNA)
  • 7. 7 C. Damper Sleeve : By UL 555, ducts are to be terminated at fire damper sleeves or damper frames. Sleeve thickness depends on the type of connection as per below table. . Sleeves may be omitted on certain alternative damper arrangements that are in compliance with UL 555, Standard for Fire Dampers. The damper manufacturers Installations and Operating Instructions shall state whether sleeves may be omitted
  • 8. 8 D. Fire Damper : Fire dampers shall bear a label from a recognized testing laboratory (such as UL) or be tested in accordance with the requirements of Uniform Building Code, UBC STD 43-7. Note: Whether Fire Damper or Combination Fire/Smoke Damper is UL listed or not can be determined from UL web page. Please visit UL site at WWW.UL.COM. You need to check and make sure that the supplied model is listed. Also check for size, position, System type and rating of the supplied dampers. E. Retaining Angle Fastened to Sleeve Secure retaining angles to sleeve ONLY on 8” centers (203mm) with a. ½ “(12mm) long weld b. ¼”(6mm) nut and bolts c. No. 10 sheet metal screws d. Minimum 3/16”(5mm) steel rivets Note : The size and spacing requirements may differ by damper manufacturer. Consult manufacturer installations for specifications.
  • 9. 9 F. Damper attachment to sleeve Secure damper to sleeve on 8” centers with a. ½” (12mm) long weld b. ¼”(6mm) nut and bolts c. No. 10 sheet metal screws d. Minimum 3/16”(5mm) steel rivets G. Connection to Duct Fire dampers shall be securely mounted in rated fire separation wall, ceiling or floor, such that ducts can break away without lessening fire separation rating. So type of duct connection to Fire Damper sleeve shall be breakaway connection. 1. Above figure shows the Duct Sleeve connection listed in UL 555 2. Additional Duct –Sleeve connections were tested by SMACNA and witnessed by UL.. They are a). TDC AND TDF Roll Formed 4-Bolt flanged connections assembled as per the manufacturer instructions using Gaskets, metal cleats and four 3/8” metal nuts and bolts.
  • 10. 10 b). Manufactured slip on 4-Bolt flanged connections assembled as per manufacturer instructions using Gaskets and Plastic Cleats. H. Access Door : Install access door shall be installed as shown in figure. Access doors shall be maximum of 24”x24” and a minimum of 6”x 6”(SMACNA). Access doors (points) shall be identified by a label with letters not less than ½” (13 mm) in height reading FIRE DAMPER (UMC Para 605.5).
  • 11. 11 IMPROPER INSTALLATION Figure below shows two main improper installations encountered as per SMACNA.
  • 12. 12 Item 1: Sealing of the fire damper retaining angles is not a requirement of an approved damper installation If the local authority having jurisdiction mandates that the angles be sealed, contractors should issue a Request For Information (RFI) to design professionals such that the proper approved sealants be used. In no case should the retaining angles be sealed with any product not approved by the damper manufacturer including Through Penetration Fire stop products. Using unapproved products could be a violation of the damper manufacturer’s conditions of test and listing, could void the UL listing of the damper and could render the damper inoperable Item 2: Introduction of any materials including mineral wool, ceramic fiber or sealants of any kind into the required expansion space between the damper sleeve and fire partition has not been tested, has not been approved, and is not permitted by damper manufacturers. Doing so could be a violation of the manufacturer’s conditions of test and listing, could void the UL listing of the damper and could render the damper inoperable. Indiscriminate and unnecessary deviations from standard fire damper installations should be avoided. Unless a deviation is specifically approved by the damper manufacturer, it could compromise the function for which the damper was ultimately installed.
  • 13. 13 Below is the pictures showing improper installation in one project.
  • 14. 14 VERTICAL FIRE DAMPER INSTALLATION